Omega DPF20 Series Owner Manual

Add to my manuals
40 Pages

advertisement

Omega DPF20 Series Owner Manual | Manualzz

TM

User’s Guide

Shop online at omega.com

e-mail: [email protected]

For latest product manuals: www.omegamanual.info

DPF20 Series

Panel Meter for

Frequency, Rate, Total or Period Counter

6-Digit,

1

8

DIN Panel Mount

U.S.A.

Headquarters: www.

omega.com [email protected]

Servicing North America:

Omega Engineering, Inc.

Toll-Free: 1-800-826-6342 (USA & Canada only)

Customer Service: 1-800-622-2378 (USA & Canada only)

Engineering Service: 1-800-872-9436 (USA & Canada only)

Tel: (203) 359-1660 e-mail: [email protected]

Fax: (203) 359-7700

For Other Locations Visit omega.com/worldwide

The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.

2

WARRANTY/DISCLAIMER

OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 61 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to the normal five (5) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.

If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service

Department will issue an Authorized Return (AR) number immediately upon phone or written request.

Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper s p e c i f i c a t i o n ; m i s a p p l i c a t i o n ; m i s u s e o r o t h e r o p e r a t i n g c o n d i t i o n s o u t s i d e o f

OMEGA’s control. Components in which wear is not warranted, include but are not limited to contact points, fuses, and triacs.

OMEGA is pleased to offer suggestions on the use of its various products. However,

O M E G A n e i t h e r a s s u m e s r e s p o n s i b i l i t y f o r a n y o m i s s i o n s o r e r r o r s n o r a s s u m e s l i a b i l i t y fo r a ny d a m a g e s t h a t re s u l t f ro m t h e use of its products i n a c c o r d a n c e w i t h i n f o r m a t i o n p r o v i d e d b y O M E G A , e i t h e r v e r b a l o r written. OMEGA warrants only that the par ts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR

REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT

THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY

DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.

CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a

“Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS/INQUIRIES

Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.

BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED

RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID

PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.

The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.

FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:

1. Purchase Order number under which the product was PURCHASED,

2. Model and serial number of the product under warranty, and

3. Repair instructions and/or specific problems

relative to the product.

FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:

1. Purchase Order number to cover the COST

of the repair,

2. Model and serial number of the product, and

3. Repair instructions and/or specific problems

relative to the product.

OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.

OMEGA is a registered trademark of OMEGA ENGINEERING, INC.

© Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the

prior written consent of OMEGA ENGINEERING, INC.

3

Instruction Manual DPF20 Frequency, rate, total or period counter

1. Panel meter DPF20

Counter, ratemeter and periodmeter, 96 x 48 mm (1/8 DIN)

Panel meter 96 x 48 mm (1/8 DIN) and 6 digits with 14 mm digit height, configurable with 5 impulse counter modes

(see section 1.2) , 2 rate

-

meter modes (see section 1.3) and a 1 periodmeter mode (see section

1.4)

.

Highly configurable, accepts all types of sensors (NPN, PNP, pushpull, Namur, inductive, pick-up, mechanical, TTL, CMOS, ...) including quadrature signals (single and bidirectional encoder signals).

Reading from 999999 to -199999 with decimal point, scalable read ing with configurable multiplier factor (1 to 999999) and configurable divider factor (1 to 999999). Includes internal pull-up and pull-down resistors, configurable trigger levels, detection by rising or falling edge, excitation voltage configurable from 5 Vdc to 18 Vdc.

Options for output and control with 1, 2 and 3 relays, transistor out puts, SSR drive controls, isolated analog outputs, communications in

Modbus RTU, RS-485 ASCII and RS-232. Special options with 4 and 6 relay outputs.

Independent alarms configurable as maximum or minimum, with 1 or

2 setpoints per alarm, hysteresis, independent activation and deacti vation delays and control for inverted relay.

Front protection IP65. Connections by plug-in screw terminals. For in dustrial applications.

• ‘ Fast access’ menu to selected functions, accessible with key UP ( 5 )

(see section 1.19.12)

• Function ‘On power up’ for system protection on first ‘cold’ start-up

or automatic reset (see section 1.19.15)

• Special ‘FAST’ mode for fast counting applications

(see section 1.16)

• Special ‘SLOW’ mode for slow ratemeter applications (low frequency

applications) (see section 1.15)

• Direct configuration for most usual sensor, at the ‘ SnSr / Auto ’ menu

(see section 1.19.10)

• Function ‘Trigger Sense’ helps to detect the correct trigger level (see section 1.13)

Multiple display filters, memory for maximum and minimum reading, password protection, 5 brightness levels.

Index

1. Panel meter DPF20 . . . . . . . . . . . . . . . . . . . . . . . 4

1.1 How to order . . . . . . . . . . . . . . . . . . . . . . . . 5

1.2 Impulse counter modes . . . . . . . . . . . . . . . . . . 5

1.3 Ratemeter modes . . . . . . . . . . . . . . . . . . . . . . 5

1.4 Periodmeter mode . . . . . . . . . . . . . . . . . . . . . 5

1.5 Functions included . . . . . . . . . . . . . . . . . . . . . 5

1.6 Front view . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.7 Power connections . . . . . . . . . . . . . . . . . . . . . 6

1.8 Sensor configuration and connections . . . . . . . . . . 6

1.9 Rear view . . . . . . . . . . . . . . . . . . . . . . . . . . 6

1.10 Signal connections . . . . . . . . . . . . . . . . . . . . 6

1.11 Technical specifications . . . . . . . . . . . . . . . . . . 7

1.12 Mechanical dimensions (mm) (in ) . . . . . . . . . . . . 7

1.13 Function ‘Trigger Sense’ . . . . . . . . . . . . . . . . . 8

1.14 Function ‘cycle counter’ . . . . . . . . . . . . . . . . . 8

1.15 ‘SLOW’ mode . . . . . . . . . . . . . . . . . . . . . . . 8

1.16 ‘FAST’ mode . . . . . . . . . . . . . . . . . . . . . . . . 8

1.17 How to operate the menus . . . . . . . . . . . . . . . . 9

1.18 Messages and errors . . . . . . . . . . . . . . . . . . . 9

1.19 Configuration menu . . . . . . . . . . . . . . . . . . . .

10

1.19.1 Initial set-up . . . . . . . . . . . . . . . . . . . . . .

10

1.19.2 Configuration for ‘cn.1’ . . . . . . . . . . . . . . . .

10

1.19.3 Configuration for ‘cnq.2’ . . . . . . . . . . . . . . .

11

1.19.4 Configuration for ‘cnI.3’ . . . . . . . . . . . . . . . .

11

1.19.5 Configuration for ‘cnc.4’ . . . . . . . . . . . . . . .

11

1.19.6 Configuration for ‘cnd.5’ . . . . . . . . . . . . . . .

12

1.19.7 Configuration for ‘rt.6’ . . . . . . . . . . . . . . . .

12

1.19.8 Configuration for ‘rtq.7’ . . . . . . . . . . . . . . . .

12

1.19.9 Configuration for ‘Prd.8’ . . . . . . . . . . . . . . .

13

1.19.10 Sensor configuration . . . . . . . . . . . . . . . . .

13

1.19.11 Alarms . . . . . . . . . . . . . . . . . . . . . . . .

15

1.19.12 Fast access . . . . . . . . . . . . . . . . . . . . . .

16

1.19.13 Super fast access . . . . . . . . . . . . . . . . . . .

16

1.19.15 Menu ‘On Power Up’ . . . . . . . . . . . . . . . .

16

1.19.14 Menu ‘Key LE’ . . . . . . . . . . . . . . . . . . . .

16

1.19.16 Menus ‘Overrange / underrange’ . . . . . . . . . .

17

1.19.17 Left zeros . . . . . . . . . . . . . . . . . . . . . . .

17

1.19.18 Vexc. control . . . . . . . . . . . . . . . . . . . . .

17

1.19.19 Function ‘Password’ . . . . . . . . . . . . . . . . .

17

1.19.20 Factory reset . . . . . . . . . . . . . . . . . . . . .

17

1.19.21 Firmware version . . . . . . . . . . . . . . . . . . .

17

1.19.22 Brightness . . . . . . . . . . . . . . . . . . . . . .

17

1.19.23 Access to optional modules . . . . . . . . . . . . .

17

1.20 Full configuration menu . . . . . . . . . . . . . . . . .

18

1.21 Factory configuration . . . . . . . . . . . . . . . . . . .

21

1.22 To access the instrument . . . . . . . . . . . . . . . . .22

1.23 Modular system . . . . . . . . . . . . . . . . . . . . . .22

1.24 Precautions on installation . . . . . . . . . . . . . . . .23

1.25 CE declaration of conformity . . . . . . . . . . . . . . .23

2. Output and control modules . . . . . . . . . . . . . . . . .24

2.1 Módules R1, T1 and SSR . . . . . . . . . . . . . . . . . .24

2.2 Module AO . . . . . . . . . . . . . . . . . . . . . . . . .

25

2.2.1 Configuration menu . . . . . . . . . . . . . . . . . .26

2.2.2 Error codes . . . . . . . . . . . . . . . . . . . . . . .26

2.2.3 Factory configuration . . . . . . . . . . . . . . . . . .26

2.3 Module RTU . . . . . . . . . . . . . . . . . . . . . . . . .

27

2.3.1 Accessible registers . . . . . . . . . . . . . . . . . . .

27

2.3.2 Configuration menu . . . . . . . . . . . . . . . . . .

28

2.3.3 Exception codes . . . . . . . . . . . . . . . . . . . . .

28

2.3.4 Description and example for Modbus RTU registers 29

2.4 Module S4 . . . . . . . . . . . . . . . . . . . . . . . . . .

30

2.4.1 Accessible registers . . . . . . . . . . . . . . . . . . .

30

2.4.2 Configuration menu . . . . . . . . . . . . . . . . . .

31

2.4.3 Factory configuration . . . . . . . . . . . . . . . . . .

31

2.4.4 Frame types . . . . . . . . . . . . . . . . . . . . . . .32

2.4.5 Frame structure . . . . . . . . . . . . . . . . . . . . .32

2.4.6 Error codes . . . . . . . . . . . . . . . . . . . . . . .32

2.4.7 Frame examples . . . . . . . . . . . . . . . . . . . . .33

2.4.8 CRC calculation . . . . . . . . . . . . . . . . . . . . .33

2.5 Module S2 . . . . . . . . . . . . . . . . . . . . . . . . . .34

2.6 Modules R2, R4 and R6 . . . . . . . . . . . . . . . . . . .34

2.6.1 Configuration menu . . . . . . . . . . . . . . . . . .

35

2.6.2 Factory configuration . . . . . . . . . . . . . . . . . .

35

3. How to open and close . . . . . . . . . . . . . . . . . . . . .36

3.1 How to open the housing . . . . . . . . . . . . . . . . .36

3.2 How to close the housing . . . . . . . . . . . . . . . . .

37

4

DPF20 Frequency, rate, total or period counter Instruction Manual

1.1 How to order

Model

DPF20 HV

Power

-HV (85-265   Vac/dc)

-LV (11/60   Vdc,

24   Vac, 48   Vac)

-R1 (1 relay)

-AO (analog output)

-RTU (Modbus RTU)

-S4 (RS-485)

-S2 (RS-232)

-T1 (1 transistor)

-SSR (1 SSR drive)

- (empty)

1.2 Impulse counter modes

The instrument allows for 5 selectable impulse counter modes :

• Counter (‘cn.1’)

(see section 1.19.2)

• Counter quadrature (‘cnq.2’) (see section 1.19.3)

• Counter with inhibition (‘ cnI.3

’)

(see section 1.19.4)

• Counter with control add / substract (‘ cnc.4

’) (see section 1.19.5)

• Counter differential (‘cnd.5’)

(see section 1.19.6)

Configurable up or down counting, ‘reset’ at rear terminals, front key and/or at alarm activation. Configurable ‘Preset’ value. Relay activa tion and deactivation delays.

Alarm functions with ‘return to preset’ or ‘reset to 0’ generate cycles of counting (instrument counts from ‘preset’ value to alarm value in never ending cycle). The instrument provides memory of cycles counter.

Scalable reading with configurable multiplier factor (1 to 999999) and configurable divider factor (1 to 999999). Memory retention in case or power loss. Retains configuration and last reading.

Counting frequency up to 250 KHz, in ‘FAST’ mode (see section 1.16)

.

1.3 Ratemeter modes

In ratemeter mode the reading is proportional to the measured fre quency. The instrument allows for 2 selectable ratemeter modes :

• Ratemeter (‘rt.6’) (see section 1.19.7)

• Ratemeter quadrature (‘rtq.7’)

(see section 1.19.8)

The ratemeter mode has a single input channel, with scalable read ing. The quadrature ratemeter mode has 2 inpur channels available for detection of sense of turn when working with quadrature signals.

Scalable reading with configurable multiplier factor (1 to 999999) and configurable divider factor (1 to 999999).

For low frequency applications, the ‘SLOW’ mode provides the best response time for each application

(see section 1.15) .

Maximum frequency up to 500 KHz and minimum frequency down to de 0.001 Hz (1 mHz) with ‘SLOW’ mode active.

1.4 Periodmeter mode

-

Option 1

-

Option 2

Reading is proportional to the signal period. Scalable reading with configurable multiplier factor (1 to 999999) and configurable divider factor (1 to 999999).

For applications with long periods (slow frequencies), the ‘SLOW ’ mode provides the best response time for each application

(see section 1.15) .

1.5

-

Option 3

-

Others

-NBT (no buttons)

-GN (green led)

Functions included

Functions included

‘Fast access’

‘SLOW’ mode

‘FAST’ mode

Display filters

Memory yes yes, for slow frequencies yes, for fast counting recursive

Section

1.19.12

1.15

1.16

Multiplier and divider

Reset configurable from 1 to 999999

1.19.2

yes (front, rear and linked to alarm activation)

1.19.14 and

1.10 and

1.19.11

yes

1.19.2

Preset

Trigger level configurable

‘Trigger Sense’ function helps to set the trigger

1.19.10

1.13

Sensor selection

Cycle counter

Retention memory

‘On Power Up’ by menu yes yes

, recovers with power

1.19.10

1.14

1.11

1.19.15

Excitation voltage configurable

1.19.10

1.19.7 and

1.19.8 and

1.19.9

1.19.12

Password

Alarms

Display brightness

Table 1 - Functions included max., min., cycles blocks access to configu ration menu double setpoints activation delays deactivation delays hysteresis inverted relays locked alarms

5 levels

1.19.19

1.19.11

1.19.22

5

DPF20 Frequency, rate, total or period counter

1.6 Front view

Alarms

Instruction Manual

1.9 Rear view

Option 3 Option 1 Option 2

Logo Units

Button ‘LE’

Front reset

(see section 1.19.14)

Button ‘UP’

‘Fast access‘

(see section 1.19.12)

Button ‘SQ’

‘Configuration menu’

(see section 1.19)

Signal Power

1.7 Power connections

Earth connection - Although a terminal is provided for earth connection, this connection is optional. The instrument does not need earth connection for correct operation nor for com pliance with the security regu lations.

8 9 0

~ +

~ -

Fuse - To comply with security regulation 61010-1, add to the power line a protection fuse acting as disconnection element, easily acces sible to the operator and identified as a protection device.

Power ‘H’ fuse 250 mA time lag

Power ‘L’ fuse 400 mA time lag

1.10

Detail of the plug-in screw terminals provided with the instrument. The instrument is provided with all terminals needed, both male and female.

Signal connections

1 2 3 4 5

Reset

Canal B

Canal A

Vexc.

0 V

1.8 Sensor configuration and connections

Selecting one of the sensors listed at the

SnSr’ menu entry, will configure the sen sor parameters to the values indicated in the table.

The table also indicates the typical con nections for each type of sensor. Param eters can be manually modified.

Connections are indicated for a single sen sor connected to the channel A. For two sensors (for inhibition control, quadrature signal, etc) apply the same connection cri teria also to channel B.

Note : indicated values are typical values.

Check the correct specifications with your sensor datasheet and adapt the required configuration and connections as needed.

Sensor Connections Pulls Vexc. Antirrebound filter

Mechanical contact 0 V channel A

Namur pull-up no channel A Vexc pull-down 9 Vdc

100 mSec.

no

NPN 2 wires 0 V channel A pull-up 18 Vdc no

NPN 3 wires

PNP 2 wires

PNP 3 wires

0 V channel A Vexc pull-up 18 Vdc

0 V channel A pull-down 18 Vdc

0 V channel A Vexc pull-down 18 Vdc

0 V channel A Vexc no 18 Vdc no no no no Push-pull

TTL

CMOS

Pick-up

AC<30   Vp

Inductive

0 V channel A

0 V channel A no no

5 Vdc no no no

Table 2 - Configuration and connections for different types of sensors.

Trigger

2,5 Vdc

0 Vdc

2,5 Vdc

3,0 Vdc

2,5 Vdc

2,5 Vdc

2,5 Vdc

2,5 Vdc

2,5 Vdc

6

DPF20 Frequency, rate, total or period counter Instruction Manual

1.11 Technical specifications

Digits number of digits led color digit height

6

7 segments led red or green

14 mm

Reading maximum reading minimum reading decimal point

999999

-199999 configurable X.X.X.X.X.X.

overrange / underrange configurable to flash, reset or preset

(see section 1.19.16)

display refresh 15 readings / second memory retention yes, retains reading value in case of pow er loss

Signals accepted

Max. Vdc at input

Input impedance

NPN, PNP, Namur, pick-up, TTL, induc tive, mechanical, quadrature, ...

±30 Vdc

2K4 with pull-up or pull-down resistor

470K without pull resistor

Accuracy of the quartz ±0.01 %

Thermal drift 20 ppm / ºC

Excitation voltage output voltage maximum current protection

Frequencies configurable

+18 Vdc, +15 Vdc, +9  Vdc, +5 Vdc

70 mA yes, current limited to 70 mA

counter modes (see Table 3) ratemeter modes (see Table 4)

periodmeter modes

(see Table 5)

Power power ‘H’ power ‘L’ isolation* consumption

Configuration

Front protection

85 to 265 Vac/dc

11 to 60 Vdc and 24/48 Vac

2500 Veff with power ‘H’

1500 Veff with power ‘L’

*tested for 60   sec.

<1.5 W only meter

<4.0 W meter with options

3 buttons front keypad

IP65

Output and control options relays, analog outputs, serial communi cations

(see section 2)

Mechanical mounting connections housing material weight front size panel cut-out depth from panel panel plug-in screw terminal

ABS, polycarbonate (V0)

<150 grams

96 x 48 mm (1/8 DIN)

92 x 44 mm

91 mm (including terminals)

Temperature operation storage warm-up time from 0 to +50 ºC from -20 to +70 ºC

15 minutes

Counter

Counter

Mode Frequency

‘FAST’ mode active max. 250 KHz normal mode max. 9 KHz

Counter + inhibition

Counter + control A/S

Counter differential mode x1

Counter quadrature mode x2 mode x4 max. 9 KHz max. 9 KHz max. 9 KHz max. 17 KHz max. 16 KHz max. 11 KHz

Table 3 - Maximum input frequency for counter modes

Ratemeter

Ratemeter

Ratemeter quadrature

Mode normal mode

‘SLOW’ mode ac tive mode x1 mode x2 mode x4

Frequency max. 500 KHz max. 200 Hz min. 1 mHz max. 17 KHz max. 16 KHz max. 11 KHz

Table 4 - Maximum and minimum input frequency for ratemeter modes

Section

1.19.7

1.19.7

1.19.8

1.19.8

1.19.8

Periodmeter Mode normal mode

Frequency max. 500 KHz

Section

1.19.9

Periodmeter

‘SLOW’ mode ac tive

max. 200 Hz min. 1 mHz

(1000 sec.)

Table 5 - Maximum and minimum input frequency for periodmeter modes

1.19.9

1.12 Mechanical dimensions (mm)

(in )

Panel cut-out

92

(3.63)

Section

1.19.2

1.19.2

1.19.4

1.19.5

1.19.6

1.19.3

1.19.3

1.19.3

7

DPF20 Frequency, rate, total or period counter

1.13 Function ‘Trigger Sense’

The trigger level is automatically configured when selecting a sensor from the ‘Sensor / Configuration’ (‘SnSr’ / ‘Auto’) menu list. The trig ger level can be also manually modified from the ‘SnSr’ / ‘ TrIG ’ menu entry. The selected value applies to channels ‘A’ and ‘B’ (the reset has a fixed trigger level at 2.5 Vdc).

At the ‘SnSr’ / ‘ TrIG ’ menu, the instrument shows the trigger level and two vertical leds to the left. These leds inform in real time about the status (‘0’ or ‘1’) of the input channels ‘A’ and ‘B’. When the led switches between up and down position, it indicates that impulses are being detected at the input. If the instrument does not detect impulses, the led positions remain fixed.

Increase the trigger level pressing key ‘UP’ ( 5 ) and decrease press ing key ‘LE’ ( 3 ).

channel ‘A’ channel ‘B’

Status ‘1’

Status ‘0’

Trigger level

Leds of the ‘Trigger

Sense’ function

‘1’

‘0’

Vdc

Trigger level

Instruction Manual

Time

Signal detected

1.14 Function ‘cycle counter’

The counter modes allow to activate a reset function (to ‘0’ or to

‘preset’ value) when an alarm setpoint is reached. With this configu ration, the instrument counts in cycles, counting from the instrument preset value up to the alarm setpoint. Each cycle is counted and ac cumulated into an internal memory, accessible through the ‘fast ac cess’ menu (key UP ( 5

) (see section 1.19.12))

.

To reset the memory of cycles, visualize the value at the ‘uP’ menu, then press the ( 5 ) key and the ‘rSt’ message appears. Press ( < ) to reset.

Reading Impulse counter, with ‘reset to preset’ when setpoint 1 is reached

Setpoint 1

Preset

Time

1.15 ‘SLOW’ mode

Special working mode for applications with low frequency signals.

Applies to ratemeter (‘rt.6’), ratemeter quadrature (‘rtq.7’) and peri odmeter (‘Prd.8’). The ‘SLOW’ mode allows to measure slow fre quencies down to 1 mHz (0,001 Hz) and is functional up to 200 Hz.

The ‘SLOW’ mode provides the fastest response time possible for a given application, calculating the frequency and the period based on the time between consecutive impulses.

The ‘SLOW’ mode needs to define the parameter ‘ maximum waiting time ’ to a value between 1 and 1000 seconds. If this time expires without a single impulse being received, the reading jumps to ‘0’

(both for ratemeter and periodmeter modes). The ‘GATE’ parameter is not used if ‘SLOW’ mode is active.

In ‘ratemeter quadrature’ (‘rtq.7’) mode, the activation of the

SLOW’ mode calculates the frequency based on the time between consecutive impulses received on channel A, and calculates the sense of turn (clockwise or counter-clockwise) by comparing each impulse with the state of channel B. The ‘edge’ parameter is fixed to a ‘ 1--1’. Typical application for quadrature frequency measure with two inductive sensors at low frequency.

Cycle counter

3

2

0

1

Time

1.16 ‘FAST’ mode

Special working mode for counter applications with high frequency signals, up to 250 KHz. Applies only to the counter mode (‘cn.1’).

The activation of the ‘FAST’ mode configures the signal detection by rising edge. The first edge detected, either rising or falling edge, after the instrument restart (power-up, or configuration change) is used for internal initialization and will not be counted as impulse.

8

DPF20 Frequency, rate, total or period counter Instruction Manual

1.17 How to operate the menus

The instrument has two menus accessible to the user :

‘ Configuration menu ’ (key SQ) ( < )

‘ Fast access ’ menu (key UP) ( 5 )

Configuration menu

The ‘ configuration menu ’ modifies the configuration parameters to adapt the instrument to the application needs. To access the ‘ con figuration menu ’ press for 1 second the SQ ( < ) key. This access can be blocked by activating the ‘Password’ (‘PASS’) function. While operating the ‘ configuration menu ’, the alarm status is ‘hold’ to the status they had before accessing the menu, and the output and con trol modules remain in ‘ error ’ state. When leaving the ‘ configuration menu ’, the instrument applies a system reset, followed by a brief disconnection of the alarms and the output and control modules.

Functionality is then recovered.

For a detailed explanation on the ‘ configuration menu ’ see section

1.19

, and for a full view of the ‘

configuration menu ’ structure see

section 1.20

.

‘ Fast access ’ menu

The ‘ fast access ’ menu is an operator configurable menu, providing fast and direct access to the most usual functions of the instrument with a single key pad stroke. Press key UP ( 5 ) to access this menu.

See section

1.19.12

for a list of functions eligible for ‘

fast access ’ in this instrument. The ‘Password’ (‘PASS’) function does not block ac cess to this menu. Accessing and modifying parameters in the ‘ fast access ’ menu does not interfere with the normal functionality of the instrument, and it does not generate any system reset when validat ing the changes.

Front key pad description

Key SQ ( < ) - press the SQ ( < ) key for 1 second to access the ‘ con figuration menu ’. Inside the menu, the SQ ( < ) key functions as a

‘ENTER’ key. It selects and accesses the menu option currently dis played. At menus with numerical value entries, it validates the num ber displayed.

Key UP ( 5 ) - the UP ( 5 ) key gives access to the ‘fast access’ menu.

Inside the menus, it moves vertically through the different menu op tions. At menus with numerical value entries, it modifies the digit selected by increasing its value to 0, 1, 2, 3, 4, 5, 6, 7, 8, 9.

Key LE ( 3 ) - inside the menus, the LE ( 3 ) key functions as the ‘ ES-

CAPE ’ key. It leaves the selected menu, and eventually, will leave the whole menu. When leaving the ‘ configuration menu ’ with the LE ( 3 ) key, the changed parameters are activated. At menus with numeri cal value entries, the LE ( 3 ) key allows to select the active digit. To modify the value of the selected digit use the UP ( 5 ) key.

Menu ‘rollback’

After 30 seconds without interaction from the operator, the instru ment will rollback and leave the ‘ configuration menu ’ or the ‘ fast access ’ menu. All changes will be discarded.

(1)

(6)

Function mode

(3)

(5)

(2)

(5)

(6)

(3)

(5)

(5)

(3)

(3)

(3)

(3)

(3)

(4)

(4)

(4)

(4)

Example of operation inside the

‘ configuration menu ’.

1. The SQ ( < ) key enters into the

‘configuration menu’.

2. The SQ ( < ) key enters into the

Func’ option menu.

3. The UP ( 5 ) key moves through the menu options.

4. The SQ ( < ) key selects the desired range and returns to the

Func’ menu.

5. The LE ( 3 ) key leaves the ac tual menu level and moves to the previous menu level.

6. The LE ( 3 ) key leaves the ‘con figuration menu’. Changes are ap plied and saved at this moment.

1.18 Messages and errors

The error messages are shown on display in flash mode.

Messages and errors

‘Err.1’ incorrect password.

‘Err.2’ at ‘ oPt.X’ menu entry. Installed module is not recognized.

‘Err.8’ excitation voltage overload.

‘999999’ + flashing mode. Reading is in overrange.

‘-199999’ + flashing mode. Reading is in underrange.

Table 6 - Messages and error codes

9

DPF20 Frequency, rate, total or period counter Instruction Manual

1.19 Configuration menu

Press ‘SQ’ ( < ) for 1 second to access the ‘ configuration menu ’.

For a description on how to operate inside the menus see section

1.17

. For a full vision of the ‘

configuration menu ’ structure see

section 1.20

.

Counter

Function mode Counter quadrature

Counter + inhibition

Counter + control add / substract

Decimal point

Counter differential

Ratemeter

Ratemeter quadrature

Periodmeter

The next menu accesses the configuration parameters for the ‘ function mode’ (‘Func ’) selected. Configuration parameters are slightly different for each ‘ function mode ’. In the next entries, all 7 possible configuration menus are explained, ‘ cnF.1

’ to ‘ cnF.7

’, one for each ‘ function mode ’.

1.19.1 Initial set-up

To configure the initial set up of the instrument, select the function mode, the decimal point position, scale the reading and configure the mode selected and the sensor.

Enter the ‘ Function mode ’ (‘Func’) menu and select the desired func tion, from the 5 counting modes, 2 ratemeter modes and the period meter mode available.

• ‘ Counter’ (‘cn. 1’) - normal counter mode. Impulses input at chan nel A. Channel B disabled.

• ‘ Counter quadrature’ (‘cnq.2’) - counter mode for quadrature sig nals. Impulses input at channel A and B, in quadrature.

• ‘ Counter + inhibition ’ (‘ cnI.3

’) - counter mode with inhibition con trol. Impulses input at channel A. Inhibition control on channel B.

• ‘ Counter + control add  /   substract ’ (‘ cnc.4

’) - counter mode with control for add / substract. Impulses input at channel A. Control for the add or substract function on channel B.

 • ‘ Counter differential ’ (‘cnd.5’) - counter mode with differential function. Impulses received at channel A add. Impulses received at channel B substract.

• ‘ Ratemeter’ (‘rt.6’) - ratemeter mode. Impulses input at channel

A. Channel B disabled.

• ‘ Ratemeter quadrature’ (‘rtq.7’) - ratemeter mode for quadrature signals. Impulses input at channel A and B, in quadrature.

• ‘ Periodmeter’ (‘Prd.8’) - periodmeter mode. Impulses input at channel A. Channel B disabled.

Access the ‘Decimal point’ (‘dP’) menu to select the decimal point position. Move the decimal point by pressing the ‘LE’ ( 3 ) key.

Configure the function mode selected (‘cnF.2 ’ to ‘ cnF.8’). See sec -

tions 1.19.2

to 1.19.9

.

Configure the sensor at the ‘SnSr’ menu. See section 1.19.10

.

Configuration counter

Multiplier

Divider

Preset

Mode

‘FAST’ mode

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-199999 to 999999

Up

Down

1.19.2 Configuration for ‘cn.1’

Configuration menu for mode ‘counter’ (‘cn.1’). Total impulses re ceived are multiplied by the value of the ‘multiplier’ (‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• assign the value for ‘Preset’ (‘PrSt’) from -199999 to 999999. Reset activation loads on display the preset value.

• select the counting mode (‘ModE’) to ‘uP’ for upwards counting

(impulses received add) or ‘doWn’ for downwards counting (impuls es received substract).

• to activate the ‘FAST’ mode (‘FASt’) select ‘on’. See section 1.16

for more information on the ‘FAST’ mode.

10

DPF20 Frequency, rate, total or period counter

Conf. counter

+ inhibition

Configuration counter + control add / substract

Multiplier

Divider

Preset

Mode

Inhibition

Multiplier

Divider

Preset

Control A/S

Instruction Manual

1.19 Configuration menu (cont.)

Conf. counter quadrature

Multiplier

Divider

Preset

Edges

Multiplier

1 to 999999

Divider

1 to 999999

Valor del preset

-199999 to 999999

1 imp. per cycle

2 imp. per cycle

4 imp. per cycle

1.19.3 Configuration for ‘cnq.2’

Configuration menu for mode ‘counter quadrature’ (‘cnq.2’). To tal impulses received are multiplied by the value of the ‘multiplier’

(‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• assign the value for ‘Preset’ (‘PrSt’) from -199999 to 999999. Reset activation loads on display the preset value.

• select the ‘ edges’ to count for each quadrature cycle (‘ q.124

’). Se lect ‘ 1--1’ for 1 impulse per quadrature cycle. Select ‘1--2’ for 2 im pulses per quadrature cycle. Select ‘ 1--4 ’ for 4 impulses per quadra ture cycle.

Multiplier

1 to 999999

Divider

1 to 999999

Valor del preset

-199999 to 999999

Up

Down

Inhibits if chan nel B is high

Inhibits if chan nel B is 0 Vdc

1.19.4 Configuration for ‘cnI.3’

Configuration menu for mode ‘ counter + inhibition control ’ (‘ cnI.3

’).

Total impulses received are multiplied by the value of the ‘multiplier’

(‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• assign the value for ‘Preset’ (‘PrSt’) from -199999 to 999999. Reset activation loads on display the preset value.

• select the counting mode (‘ModE’) to ‘uP’ for upwards counting

(impulses received add) or ‘doWn’ for downwards counting (impuls es received substract).

• select the activation mode for the ‘ inhibition ’ (‘ Inh ’) control. Select

on_h’ to inhibit the counting when channel B is at logical state ‘1’.

Select ‘on_0’ to inhibit the counting when channel B is at logical state

‘0’.

Multiplier

1 to 999999

Divider

1 to 999999

Valor del preset

-199999 to 999999

Adds if channel

B is high

Adds if channel

B is 0 Vdc

1.19.5 Configuration for ‘cnc.4’

Configuration menu for mode ‘ counter + control add / substract ’

(‘ cnc.4

’). Total impulses received are multiplied by the value of the

‘multiplier’ (‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) regis ter. Result is refreshed on the display.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• assign the value for ‘Preset’ (‘PrSt’) from -199999 to 999999. Reset activation loads on display the preset value.

• select the activation mode for the ‘ control add / substract ’ (‘Add’).

Select ‘on_h’ activates the addition of impulses received on chan nel A when channel B is at logical state ‘1’ (impulses on channel A substract if channel B is at logical state ‘0’). Select ‘on_0’ activates the addition of impulses received on channel A when channel B is at logical state ‘0’ (impulses on channel A substract if channel B is at logical state ‘1’).

11

DPF20 Frequency, rate, total or period counter Instruction Manual

1.19 Configuration menu (cont.)

Configuration counter differential

Conf. ratemeter

Conf. ratemeter quadrature

Multiplier

Divider

Preset

Multiplier

Divider

Time window

‘SLOW’ mode

Average filter

Multiplier

Divider

Time window

Edges

Filter strength

(0 = disabled)

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-199999 to 999999

Multiplier

1 to 999999

1.19.6 Configuration for ‘cnd.5’

Configuration menu for mode ‘ counter differential ’ (‘cnd.5’). To tal impulses received are multiplied by the value of the ‘multiplier’

(‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• assign the value for ‘Preset’ (‘PrSt’) from -199999 to 999999. Reset activation loads on display the preset value.

Impulses received on channel A add. Impulses received on channel

B substract.

Divider

1 to 999999

Seconds

Max. waiting time

Number of pulses

Multiplier

1 to 999999

Divider

1 to 999999

Seconds

1 imp. per cycle

2 imp. per cycle

4 imp. per cycle

1.19.7 Configuration for ‘rt.6’

Configuration menu for mode ‘ratemeter’ (‘rt.6’). Frequency mea sured is multiplied by the value of the ‘multiplier’ (‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display. Measure is updated at the rate defined on the ‘GATE’ regis ter.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• select the value for the ‘Time window’ (‘GAtE’). Available values are : 0.5, 1.0, 2.0, 4.0, 8.0 or 16.0 seconds. The time window defines the display refresh time. This parameter has no effect if the ‘SLOW ’ mode is active.

• for slow frequencies activate the ‘SLoW’ parameter configuring the

‘ tIME ’ parameter between 1 and 1000 seconds. Configure the ‘ nuMb ’ parameter between 1 and 32 impulses. See section

1.15

for more in

formation on the ‘ SLoW’ mode.

• in case of unstable signals, activate the ‘ average filter ’ (‘ AVr ’) func tion. It activates a recursive filter on the reading. the filter is stronger for higher values, from 0.0 to 99.9.

1.19.8 Configuration for ‘rtq.7’

Configuration menu for mode ‘ratemeter quadrature’ (‘rtq.7’).

Frequency measured is multiplied by the value of the ‘multiplier’

(‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display. Measure is updated at the rate defined on the ‘GATE’ register.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• select the value for the ‘Time window’ (‘GAtE’). Available values are : 0.5, 1.0, 2.0, 4.0, 8.0 or 16.0 seconds. The time window defines the display refresh time. This parameter has no effect if the ‘SLOW ’ mode is active.

• select the ‘ edges’ to count for each quadrature cycle (‘ q.124

’). Se lect ‘ 1--1’ for 1 impulse per quadrature cycle. Select ‘1--2’ for 2 im pulses per quadrature cycle. Select ‘ 1--4 ’ for 4 impulses per quadra ture cycle.

12

DPF20 Frequency, rate, total or period counter Instruction Manual

1.19 Configuration menu (cont.)

‘SLOW’ mode

Average filter

Filter strength

(0 = disabled)

Max. waiting time

Number of pulses

• for slow frequencies activate the ‘SLoW’ parameter configuring the

‘ tIME ’ parameter between 1 and 1000 seconds. Configure the ‘ nuMb ’ parameter between 1 and 32 impulses. See section

1.15

for more in

formation on the ‘ SLoW’ mode.

• in case of unstable signals, activate the ‘ average filter ’ (‘ AVr ’) func tion. It activates a recursive filter on the reading. the filter is stronger for higher values, from 0.0 to 99.9.

Conf.

Periodmeter

Sensor

Multiplier

Divider

Time window

‘SLOW’ mode

Average filter

Filter strength

(0 = disabled)

Multiplier

1 to 999999

Divider

1 to 999999

Seconds

Max. waiting time

Number of pulses

1.19.9 Configuration for ‘Prd.8’

Configuration menu for mode ‘periodmeter’ (‘Prd.8’). Period mea sured is multiplied by the value of the ‘multiplier’ (‘MuLt’) register and divided by the ‘divider’ (‘ dIV ’) register. Result is refreshed on the display. Measure is updated at the rate defined on the ‘GATE’ regis ter.

• assign the value for parameter ‘ Multiplier ’ (‘MuLt’) from 1 to

999999.

• assign the value for parameter ‘Divider’ (‘ dIV ’) from 1 to 999999.

• select the value for the ‘Time window’ (‘GAtE’). Available values are : 0.5, 1.0, 2.0, 4.0, 8.0 or 16.0 seconds. The time window defines the display refresh time. This parameter has no effect if the ‘SLOW ’ mode is active.

• for long periods activate the ‘SLoW’ parameter configuring the

‘ tIME ’ parameter between 1 and 1000 seconds. Configure the ‘ nuMb ’ parameter between 1 and 32 impulses. See section

1.15

for more in

formation on the ‘ SLoW’ mode.

• in case of unstable signals, activate the ‘ average filter ’ (‘ AVr ’) func tion. It activates a recursive filter on the reading. the filter is stronger for higher values, from 0.0 to 99.9.

Automatic conf.

Push pull

TTL

CMOS

Pick-up

Inductive

Vac <30 V

Mechanical contact

Namur

NPN 2 wire

NPN 3 wire

PNP 2 wire

PNP 3 wire

1.19.10 Sensor configuration

The sensor configuration menu (‘SnSr’) provides configuration for the input section of the instrument, the excitation voltage and the trigger level, for accurate detection of the impulses.

• ‘ Automatic configuration’ (‘Auto’) - if a standard sensor is used, select one of the sensors provided at the ‘Auto’ menu list. The instru -

ment will automatically configure the parameters according to Table

2 (see section 1.8)

. If this configuration does not detect impulses, manually modify the values for the parameters indicated below.

13

DPF20 Frequency, rate, total or period counter

1.19 Configuration menu (cont.)

Pulls on channel A

Pulls on channel B

Pulls on reset

Trigger level

Activation for channel A

Activation for reset

No pull resistor

Pull-up

Pull-down

No pull resistor

Pull-up

Pull-down

No pull resistor

Pull-up

Pull-down

Trigger level (from

0.0 Vdc a 3.9 Vdc).

See section 1.15 for ‘Trigger Sense’ utility by rising edge by falling edge by rising edge by falling edge

Instruction Manual

• ‘ Pulls on channel A’ (‘PuL.A’) - activates pull resistors at chan nel A. Select ‘P.uP’ to activate pull-up resistors (needed for NPN sensors). Select ‘P.dn’ to activate pull-down resistors (needed PNP sensors). Pull-up and pull-down selection configure the trigger level to 2,5 Vdc.

• ‘ Pulls on channel B’ (‘ PuL.b

’) - see previous menu entry ‘Pulls on channel A’.

• ‘ Pulls on reset’ (‘PuL.r’) - see previous menu entry ‘Pulls on channel

A’. Trigger level for reset channel is fixed to 2,5 Vdc.

• ‘ trigger level’ (‘ trIG ’) - input signal value in Vdc at which the in strument detects impulse. Selectable between 0,0 and 3,9 Vdc. Trig ger level is the same for channels A and B. Trigger level for reset channel is fixed at 2,5 Vdc. The two leds at the left of the trigger level are part of the ‘Trigger Sense’ utility for easy location of the

proper trigger level (see section 1.13) .

• ‘ Activation for channel A ’ (‘Act.A’) - configures the activation of channel A by rising edge (‘on_h’) or by falling edge (‘on_0’)

• ‘ Activation for reset channel ’ (‘Act.r’) - configures the activa tion of the reset channel by rising edge (‘on_h’) or by falling edge

(‘on_0’)

• ‘ Excitation voltage ’ (‘ V.EXc

’) - configures the value of the excita tion voltage at 5 Vdc, 9 Vdc, 15 Vdc and 18 Vdc. Select ‘no’ to disable the excitation voltage.

• ‘ Antirrebound filter ’ (‘ rbnd ’) - the antirrebound filter blocks ad ditional rebounds (typically from a mechanical contact sensor) from the same single impulse, preventing that a single impulse counts for more than 1. Value between 0 mSeconds and 1000 mSeconds.

When an impulse is received, impulse detection is disabled for the duration of the time configured in this parameter. After time has passed, impulse detection is enabled again. Recommended value for a mechanical contact : 100 mSeconds.

Excitation voltage

Antirrebound

Antirrebound filter

(0 to 1000 mSec.)

14

on off on off on off

DPF20 Frequency, rate, total or period counter

1.19 Configuration menu (cont.)

Alarms

Reading

Alarm 1 activation delay

Instruction Manual

Active

Alarm type

Setpoint

Hysteresis

Activation delay

Deactivation delay

Setpoint 2

Relay inverted

Locked alarm

On alarm hysteresis setpoint

Continue

To zero

To preset

Time

Alarm as maximum, no hysteresis, no delays

Time deactivation delay

Alarm as maximum, with hysteresis and delays

Time

Alarm as minimum, no hysteresis, no delays

Time

15

1.19.11 Alarms

The ‘Alarms’ (‘ALr’) menu configures the independent activation of up to 3 relay outputs (or transistor or SSR drive control), installed with the R1 optional modules (or T1 or SSR)

(see section 2.1) . For

outputs up to 4 and 6 relays, see special modules R2, R4 and R6 at section

2.6

. The alarm states are indicated in the front display with

leds marked as ‘1’, ‘2’ and ‘3’.

To configure an alarm, enter into the alarm menu (‘ALr1’, ‘ALr2 ’ or

‘ ALr3 ’) and configure the following parameters :

• select ‘ Active ’ (‘Act’) to ‘on

• at ‘ Alarm type’ (‘TypE’) select the alarm to act as a maximum type alarm (‘MAX’) or a minimum type alarm (‘ MIn ’). The maximum type alarm (or minimum type alarm) activates when the display value is higher (or lower) than the setpoint value.

• at ‘ Setpoint’ (‘SEt’) enter the value for the alarm activation point .

This parameter is eligible for configuration through the ‘ Fast access ’ menu

(see section 1.19.12).

• configure the hysteresis value at ‘Hysteresis’ (‘hySt’). The hyster esis applies to the deactivation process of the alarm. The alarm de activates when the reading has passed the setpoint value plus the hysteresis value. Hysteresis helps to avoid repetitive switching of the alarm relays, due to fluctuating input signals around the setpoint.

• at ‘ Activation delay ’ (‘dEL.0’) configure the delay to apply before alarm activation. The activation delay starts counting when the set point value is passed. Value from 0.0 to 99.9 seconds.

• at ‘ Deactivation delay ’ (‘dEL.1’) configure the delay to apply before alarm deactivation. The deactivation delay starts counting when the setpoint value plus the hysteresis value, is passed. Value from 0.0 to 99.9 seconds.

• to work with ‘windowed alarms’ (see graphical example below) activate ‘Setpoint2’ (‘SEt2’) to ‘on’ and then configure the desired second setpoint value. Second setpoint must always be higher in value than the first setpoint.

• the ‘Relay inverted’ (‘ r.Inv

’) parameter inverts the normal relay connections. When set to ‘on’ the relay will be active when alarm is inactive. For security applications where an inactive relay controls the shutdown of the system.

• the ‘Locked alarm’ (‘A.Lck’) parameter disables the automatic deactivation of the alarm. Alarm deactivation must be performed

manually, by pressing the ‘LE’ front button (see section 1.19.14)

• the ‘On alarm’ (‘on.AL’) parameter assigns a predefined behav iour when alarm is activated. Select ‘cont’ to continue counting.

Select ‘to_0’ to load ‘0’ on displays. Select ‘to_p’ to load preset value on display. Parameter ‘dEL.1’ is set to 1 second when ‘to_0 ’ or ‘ to_p’ are selected.

Reading

Setpoint 2

Setpoint 1 on off

Time

Alarm as minimum, with double setpoint, no hysteresis, no delays

Time

DPF20 Frequency, rate, total or period counter

1.19 Configuration menu (cont.)

Tools

Key UP

(‘fast access’)

Setpoint 1

Setpoint 2

Setpoint 3

Memory of maximum

Memory of minimum

Memory of cycles

Preset value

On power-up Delay

Reset

Seconds

Key LE No function

Front reset

Alarm unlock

Reset and alarm unlock

Instruction Manual

16

1.19.12 Fast access

The ‘UP’ ( 5 ) key at the front of the instrument gives access to a list of func -

tions configurable by the operator. See section 1.17

for an explanation on how to operate the ‘ fast access ’ menu.

The ‘ Key UP (Fast access) ’ (‘K.uP’) menu allows to select which functions will be accessible through the ‘fast access’ menu. Select ‘on’ to activate each func tion.

• the ‘Setpoint1’ (‘ALr1’) function allows to visualize and modify the alarm   1 setpoint through the ‘fast access’ menu.

• the ‘Setpoint2’ (‘ALr2’) function allows to visualize and modify the alarm   2 setpoint through the ‘fast access’ menu.

• the ‘Setpoint   3 ’ (‘ ALr3 ’) function allows to visualize and modify the alarm   3 setpoint through the ‘fast access’ menu.

• the ‘ Memory of maximum ’ (‘MAX’) or ‘ Memory of minimum ’ (‘ MIn ’) func tions allow to visualize the maximum or minimum reading value stored in memory. To reset this value, visualize the memory value at the ‘fast access’ menu with key UP ( 5 ) and when message ‘rSt’ is displayed, press ( < ) to re set.

• the ‘ Memory of cycles ’ (‘cYcL’) function allow to visualize and reset the memory of cycles. To reset this value, visualize the memory value at the ‘fast access’ menu with key UP ( 5 ) and when message ‘rSt’ is displayed, press ( < ) to reset. The memory of cycles countes ‘+1’ each time a reset alarm occurs

(‘on_AL’ / ‘to_0’ or ‘to_P’) or a reset by ‘overrange’ / ‘underrange’ occurs.

• the ‘Preset value’ (‘PrSt’) function allows to visualize and modify the preset value configured.

1.19.13 Super fast access

If only a single function is selected for the ‘fast access’ menu, press ing the the ‘UP’ ( 5 ) key will shortly display the function name and then automatically jump to the function value.

1.19.15 Menu ‘On Power Up’

The ‘On Power Up’ (‘on.Pu’) menu configures functions to apply at start-up. It applies only to instrument restart after power loss. It does not apply to instru ment restart due to change in configuration.

• parameter ‘Delay’ (‘dLAy’) assigns a waiting time in seconds. The instrument waits the configured time before starting normal function. During this waiting time, the display shows all decimal points on in flash mode, all alarms are in

‘oFF’ state, there is no signal acquisition and there is no communications or control being performed. After the configured time is over, the instrument starts in normal function. Delay value between 0 and 200 seconds.

• the ‘Reset’ (‘rSt’) parameter will execute a reset of the counter each time the instrument is restarted.

1.19.14 Menu ‘Key LE’

The ‘LE’ ( 3 ) key at the front of the instrument can be configured to activate a function.

• the ‘ No function ’ (‘nonE’) value assigns no function.

• the ‘Front reset’ (‘F.rSt’) value asigns the reset funtion.

• the ‘Alarm unlock’ (‘A.Lck’) value assigns the manual unlock of the alarms function, for instruments with the ‘Locked alarms’ (‘A.Lck’) function activated

(see section 1.19.11)

• the ‘Reset and alarm unlock’ (‘Fr.AL’) assigns the two previous functions to the same button.

DPF20 Frequency, rate, total or period counter

1.19 Configuration menu (cont.)

Counter overrange

Flash

To zero

To preset

Counter underrange

Left zeros

Vexc. control

Flash

To zero

To preset

With left zeros

Without left zeros with Vexc. error control without Vexc. error control

Password

Factory reset

Version

Brightness

Minimum

Standard

Maximum

Configuration menu for the module installed at Opt.1

Option   1

Option   2

Configuration menu for the module installed at Opt.2

Configuration menu for the module installed at Opt.3

Option   3

Instruction Manual

1.19.16 Menus ‘Overrange / underrange’

The ‘Counter overrange’ (‘c.orG’) and ‘Counter underrange’ (‘c.urG’) parameters configure the behavior of the instrument when reading is higher than ‘9999’ (overrange) or lower than ‘-1999’ (underrange).

Select ‘FLSH’ to enter reading into flash mode. Select ‘to_0’ to apply a reset to ‘0’. Select ‘to_P’ to apply a reset to preset value.

1.19.17 Left zeros

The ‘ Left zeros ’ (‘L.ZEr’) parameter controls the left zeros on or off.

1.19.18 Vexc. control

The ‘ Vexc control ’ (‘ V.ctr

’) parameters enables the ‘Err.8’ message, when consumption requested to the excitation voltage is higher than the current the instrument can provide.

1.19.19 Function ‘Password’

At the ‘Password’ (‘PASS’) menu select a 6 digit code to block access to the ‘ configuration menu ’. Instrument configuration will not be ac cessible to non authorized personnel. To activate the ‘Password’ se lect ‘ on’ and introduce the code.

The code will be requested when trying to access the ‘ configuration menu ’ (key ‘SQ’ ( < )). The ‘ fast access ’ menu is not password pro tected.

1.19.20 Factory reset

At the ‘Factory reset’ (‘FAct’) menu, select ‘yes’ to load the default factory configuration for the instrument

(see section 1.21).

1.19.21 Firmware version

The ‘ Version ’ (‘ VEr ’) menu informs of the current firmware version installed in the module.

1.19.22 Brightness

At the ‘Brightness’ (‘ LIGh ’) menu select the light intensity for the front leds. With this function it is possible to adapt the instrument to the environment light intensity.

1.19.23 Access to optional modules

Menus ‘OPt.1’, ‘OPt.2’ and ‘ OPt.3

’ give access to the ‘ configuration menus ’ of the output and control modules installed at slots Opt.1,

Opt.2 and Opt.3.

See section

2 for a list of output and control modules available for

each slot. The ‘ configuration menu ’ of each module is described at the User’s Manual of each module.

17

DPF20 Frequency, rate, total or period counter

1.20 Full configuration menu

Press ‘SQ’ ( < ) for 1 second to access the ‘Configuration menu’. See

section 1.19

for a description of each menu entry.

Function mode

Counter

Counter quadrature

Counter + inhibition

Counter + control add / substract

Counter differential

Ratemeter

Ratemeter quadrature

Periodmeter

Select with key LE

Decimal point

Configuration counter

Conf. counter quadrature

Multiplier

Divider

Preset

Mode

‘FAST’ mode

Multiplier

Divider

Preset

Edges

Conf. counter

+ inhibition

Multiplier

Divider

Preset

Mode

Inhibition

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-199999 to 999999

Up

Down

Configuration counter + control add / substract

Multiplier

Divider

Preset

Control A/S

Configuration counter differential

Multiplier

Divider

Preset

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-199999 to 999999

1 imp. per cycle

2 imp. per cycle

4 imp. per cycle

Conf. ratemeter

Multiplier

Divider

Time window

Instruction Manual

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-199999 to 999999

Up

Down

Inhibits if chan nel B is high

Inhibits if chan nel B is 0 Vdc

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-199999 to 999999

Adds if channel

B is high

Adds if channel

B is 0 Vdc

Multiplier

1 to 999999

Divider

1 to 999999

Preset value

-1999 to 999999

Multiplier

1 to 999999

Divider

1 to 999999

Seconds

18

DPF20 Frequency, rate, total or period counter

1.20 Full configuration menu (cont.)

‘SLOW’ mode

Max. waiting time

Number of pulses

Average filter

Filter strength

(0 = disabled)

Conf. ratemeter quadrature

Multiplier

Divider

Multiplier

1 to 999999

Divider

1 to 999999

Seconds

Time window

Sensor

Conf. ratemeter

Edges

‘SLOW’ mode

Average filter

Filter strength

(0 = disabled)

1 imp. per cycle

2 imp. per cycle

4 imp. per cycle

Max. waiting time

Number of pulses

Multiplier

Divider

Time window

Multiplier

1 to 999999

Divider

1 to 999999

Seconds

Instruction Manual

‘SLOW’ mode

Average filter

Filter strength

(0 = disabled)

Max. waiting time

Number of pulses

Automatic conf.

Push pull

TTL

CMOS

Pick-up

Inductive

Vac <30 V

Mechanical contact

Namur

NPN 2 wire

NPN 3 wire

PNP 2 wire

PNP 3 wire

Pulls on channel A

Pulls on channel B

Pulls on reset

Trigger level

No pull resistor

Pull-up

Pull-down

No pull resistor

Pull-up

Pull-down

No pull resistor

Pull-up

Pull-down

Trigger level (from

0.0 Vdc a 3.9 Vdc).

See section 1.15 for ‘Trigger Sense’ utility

19

DPF20 Frequency, rate, total or period counter

1.20 Full configuration menu (cont.)

rising edge

Channel A acti vation falling edge by rising edge

Activation for reset by falling edge

Excitation voltage

Antirrebound filter

(0 to 1000 mSec.)

Tools

Key UP

(‘fast access’)

Setpoint 1

Setpoint 2

Setpoint 3

Memory of maximum

Memory of minimum

Memory of cycles

Preset value

Antirrebound

Alarms

Alarm 1 Active

Alarm type

Setpoint

Hysteresis

Activation delay

Deactivation delay

Setpoint 2

Relay inverted

Locked alarm

On alarm

Continue

To zero

To preset

Instruction Manual

On power-up

Key LE

Delay

Reset

No function

Front reset

Alarm unlock

Reset and alarm unlock

Seconds

Counter overrange

Counter underrange

Flash

To zero

To preset

Flash

To zero

To preset

20

DPF20 Frequency, rate, total or period counter

1.20 Full configuration menu (cont.)

Left zeros

With left zeros

Without left zeros

Control Vexc.

with Vexc. error control without Vexc. error control

Password

Factory reset

Version

Brightness

Minimum

Standard

Maximum

Option   1

Configuration menu for the module installed at Opt.1

Configuration menu for the module installed at Opt.2

Option   2

Configuration menu for the module installed at Opt.3

Option   3

Instruction Manual

1.21 Factory configuration

Function

Decimal point

Counter configuration

Multiplier

Divider

Preset

Mode

‘FAST’

Sensor

Pulls on channel A

Pulls on channel B

Pulls on reset counter (‘cn.1’) no x1

/1

0 up off no pull resistor no pull resistor pull-up

2,5 Vdc Trigger

Activation for channel A on rising edge (‘on_h’)

Excitation voltage

Antirrebound filter

5 Vdc

0 mSeconds

Tools

Fast access (Key UP)

‘On Power Up’

Delay

Key ‘LE’ off

0 seconds reset function

Memory of maximum -199999

Memory of minimum 999999

Memory of cycles

Counter overrange

Counter underrange

Left zeros

Vexc. control

0 flash flash off off off

3

Password

Brightness

Alarms 1,2 and 3

Active

Type

Setpoint

Hysteresis

Activation delay

Deactivation delay

Setpoint 2

On Alarm

Inverted relay

Locked alarms off (disabled) maximum

1000

0 counts

0.0 seconds

0.0 seconds off continue off off

Factory configuration for Ratemeter (‘cnF.6) and periodmeter (‘cnF.8) modes.

Multiplier

Divider

Time windows

‘SLOW’ mode

tIME

nuMb

Recursive filter x1

/1

0.5

0 (off)

1

0 (off)

Factory configuration for output and control modules, see section

2.

21

DPF20 Frequency, rate, total or period counter

1.22 To access the instrument

To open the housing, use a flat screwdriver to free the fixation clips, if possible, in the following order : D, C, B and A. Remove the front cover. Let the inside of the instrument slide out of the housing.

To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module. Place all the set into the housing, assuring that the modules correctly fit into the internal guiding slides of the housing. Once introduced, place again the front cover in front of the housing, placing first corner ‘X’ and then insert ing clips ‘A’, ‘B’, ‘C’ and ‘D’ in this order.

See section

3

for a detailed description on how to open and close the housing.

Instruction Manual

B D

1.23 Modular system

DPF20 panel meters are designed to create a modular system. This modular system allows for addition, replacement or substitution of any of the internal modules conforming the instrument. Below is a graphic explanation for the position of each module.

Front Filter

Opt.3

Opt.1

Opt.2

Display Module

C

X

A

Risk of electric shock. Removing the front cover will grant access to the internal circuits. Disconnect the in put signal to prevent electric shock to the operator. Op eration must be performed by qualified personnel only.

Observe precautions for handling ESD (electrostatic dis charge) sensitive devices

Optional Control Modules

Power Supply Module

Input Signal Module

22

Housing

DPF20 Frequency, rate, total or period counter Instruction Manual

1.24 Precautions on installation

Risk of electrical shock. Instrument terminals can be connected to dangerous voltage.

Instrument protected with double isolation. No earth connection required.

Instrument conforms to CE rules and regulations.

This instrument has been designed and verified conforming to the 61010-1

CE Security Regulation, for industrial applications.

Installation of this instrument must be performed by qualified personnel only. This manual contains the appropriate information for the installation.

Using the instrument in ways not specified by the manufacturer may lead to a reduction of the specified protection level. Disconnect the instrument from power before starting any maintenance and / or installation action.

The instrument does not have a general switch and will start operation as soon as power is connected. The instrument does not have protection fuse, the fuse must be added during installation.

The instrument is designed to be panel mounted. An appropriate ventilation of the instrument must be assured. Do not expose the instrument to excess of humidity. Maintain clean by using a humid rag and do NOT use abrasive products such as alcohols, solvents, etc.

General recommendations for electrical installations apply, and for proper functionality we recommend : if possible, install the instrument far from electrical noise or magnetic field generators such as power relays, electrical motors, speed variators, ... If possible, do not install along the same conduits power cables (power, motor controllers, electrovalves, ...) together with sig nal and/or control cables.

Before proceeding to the power connection, verify that the voltage level available matches the power levels indicated in the label on the instrument.

In case of fire, disconnect the instrument from the power line, fire alarm according to local rules, disconnect the air conditioning, attack fire with car bonic snow, never with water.

1.25 CE declaration of conformity

Products DPF20

The manufacturer declares that the instruments indicated comply with the directives and rules indicated below.

Electromagnetic compatibility directive 2014/30/EU

Low voltage directive 2014/35/EU

Directive ROHS 2011/65/EU

Security rules EN-61010-1

Instrument Fixed

Permanently connected

Pollution degree 1 and 2 (without condensation)

Isolation Double

Electromagnetic compatibility rules EN-61326-1

EM environment Industrial

Immunity levels

EN-61000-4-2 By contact ±4 KV

By air ±8 KV

EN-61000-4-3

EN-61000-4-4 On AC power lines : ±2 KV

On DC power lines : ±2 KV

On signal lines : ±1 KV

EN-61000-4-5 Between AC power lines ±1 KV

Between AC power lines and earth ±2 KV

Between DC power lines ±1 KV

Between DC power lines and earth ±2 KV

Between signal lines and earth ±1 KV

EN-61000-4-6

EN-61000-4-8 30 A/m at 50/60 Hz

EN-61000-4-11 0 % 1 cycle

40 % 10 cycles

70 % 25 cycles

0 % 250 cycles

Emission levels

CISPR 11 Instrument Class A, Group 1 Criteria A

Criteria B

Criteria B

Criteria A

Criteria B

Criteria B

Criteria B

Criteria B

Criteria B

Criteria B

Criteria B

Criteria B

Criteria A

Criteria A

Criteria A

Criteria A

Criteria B

Criteria B

According to directive 2012/19/EU, electronic equip ment must be recycled in a selective and controlled way at the end of its useful life.

23

DPF20 Frequency, rate, total or period counter Instruction Manual

2. Output and control modules

2.1 Módules R1, T1 and SSR

The R1, T1 and SSR modules provides 1 relay output, 1 transistor out put or 1 SSR drive output, to install in DPF20 digital panel meters, up to a maximum of 3 modules in a single meter.

Note : for more than three relays per instrument or larger relay den sity per module, see special modules R2, R4 and R6 .

Configuration is performed from the frontal keypad of the meter, by setting the parameters at the alarms configuration menu (‘ALr.1’,

‘ALr.2’ or ‘ALr.3’ depending on the position the module is installed).

The menu allows to configure the setpoint, hysteresis, independent activation and deactivation delays, and a second setpoint to create alarm windows.

Modules R1, T1 and SSR are isolated against all other instrument cir cuits, and isolated between them.

Modules R1, T1 and SSR can be ordered pre-installed into a DPF20 digital panel meter, or standalone for delayed installation, as they do not require soldering or special configuration.

Option

Output type

Relay type

Maximum current

Maximum voltage

Isolation

Type of terminal

Installation allowed at

Option

Output type

Maximum voltage

Maximum current

Isolation

Type of terminal

Installation allowed at

Option

Output type

Output voltage

Maximum current

Isolation

Type of terminal

Installation allowed at

R1 relay

3 contact relay (NC, NO, common)

8 A (resistive load)

250 Vac continuous

3500 Veff plug-in screw terminal pitch 5.08 mm

‘Opt.1’, ‘Opt.2’, ‘ Opt.3’

T1 transistor

35 Vdc

50 mA

3500 Veff plug-in screw terminal pitch 5.08 mm

‘Opt.1’, ‘Opt.2’, ‘ Opt.3’

SSR to control a SSR relay

+15 Vdc

45 mA

1000 Vdc plug-in screw terminal pitch 5.08 mm

‘Opt.1’, ‘Opt.2’, ‘ Opt.3’

Module

Module R1 - Relay output

Module T1 - Transistor output

Output schematics and connections

‘com’ (‘A’)

‘NC’ (‘C’)

‘NO’ (‘B’)

Schematic for R1 output

‘B’

‘A’

Schematic for T1 output

+15 Vdc ‘C’

‘B’

Module SSR - SSR drive output

‘A’

Schematic for SSR drive output

Table 7 - Connections

SSR relay

Opt.1

A B C

Opt.2

A B C

Signal

Rear view DPF20

Power

24

DPF20 Frequency, rate, total or period counter Instruction Manual

2.2 Module AO

Module AO provides 1 analog output configurable as 4/20 mA or

0/10 Vdc, to install in DPF20 digital panel meters.

Configuration is performed from the frontal keypad of the meter, by setting the parameters at the options configuration menu (‘Opt.1’,

‘Opt.2’ or ‘Opt.3’ depending on the position the module is installed).

The output signal is proportional to the instrument reading, and it can be fully scaled with direct (positive) or inverted (negative) slopes.

The mA output can be configured as an active loop (the instrument provides the excitation for the loop ) or as a passive loop (the loop is externally powered).

Up to a maximum of 3 analog output modules can be installed in a single instrument, all outputs isolated between them and isolated from all other circuits.

Modules AO can be ordered pre-installed into a DPF20 digital panel meter, or standalone for delayed installation, as they do not require soldering or special configuration.

Option

Output type

Output signals

Max. signal output

Min. signal output

Scaling

Vexc (terminal A)

Load impedances

Accuracy (at 25   ºC)

Thermal stability

Step response

Isolation

Warm-up

Type of terminal

Installation allowed at

Opt.1

MV A B C

AO analog output

4/20   mA active

4/20   mA passive

0/10   Vdc

22   mA, 10.5

  Vdc

0   mA, -50   mVdc related to the instruments reading direct or inverse slope

+13.8

  Vdc ± 0.4

  Vdc (max. 25   mA) protected against short circuit

≤350   Ohms (in 4/20   mA active)

≤800   Ohms (in 4/20   mA passive) (with a

24 Vdc external Vexc) (maximum 27 Vdc between terminals ‘B’ and ‘C’)

≥10   KOhms (in 0/10   Vdc)

<0.1

  % FS

60   ppm/ºC in mA mode

50   ppm/ºC in Vdc mode

<75   mSeconds + meter step response

(0% to 99% signal)

1000 Vdc

15 minutes plug-in screw terminal pitch 5.08 mm

‘Opt.1’, ‘Opt.2’, ‘Opt.3’

Module

Module AO - Analog output

Table 8 - Connection terminals

Output 4/20   mA active

The current loop is pow ered from the ‘AO’ mod ule

Output 4/20   mA passive

The current loop is pow ered from an external equipment

Connections

Terminal A

Terminal B

Terminal C

Jumper M

Jumper V

Jumper ‘M’ closed

Vexc

Signal (mA or Vdc)

GND closed for ‘mA’ closed for ‘Vdc’

M V A B C

Jumper ‘M’ closed

M V A B C

Signal

Vexc.

Signal-

Signal+

Output 0/10 Vdc

Opt.2

MV A B C

M V A B C

Com.

Signal

Signal

Rear view DPF20

Power

25

Jumper ‘V’ closed

Table 9 - Connections for each output mode

DPF20 Frequency, rate, total or period counter

2.2.1 Configuration menu

Configure at menu ‘Mode’ (‘ModE’) the output signal range to

‘ 4/20   mA’ (‘mA’) or ‘ 0/10   Vdc ‘ (‘ Vdc ’). Position for jumpers ‘V’ and

‘M’ must be according to the range selected.

At menu ‘Scaling’ (‘ScAL’) configure the values that define the two points (‘high’ and ‘low’) of the ‘signal-reading’ slope:

• the lower slope point, defined by ‘Display low’ (‘d.Lo’) and ‘Out-

put low’ (‘Ao.Lo’)

• the higher slope point, defined by ‘Display high’ (‘ d.hI

’) and ‘Out-

put high’ (‘ Ao.hI

’)

Analog output values are shown with ‘XX.XX’ format, acceptable val ues are ‘0.00’ to ‘10.00’   Vdc for voltage, and ‘0.00’ to ‘20.00’   mA for current.

Reading

Example - analog output in 4/20   mA, associated to a reading of -50.0 to 100.0

100.0

‘d.hI’=‘100.0’

‘Ao.hI’=‘20.00’

4   mA

-50.0

‘d.Lo’=‘-50.0’

‘Ao.Lo’=‘4.00’

20   mA

Analog output

2.2.2

Error codes

‘Er.34’ output signal configured to value lower than 0   Vdc or 0   mA

‘Er.35’ output signal configured to a value higher than 10   Vdc or 20   mA

‘Er.36’ configured slope points are not acceptable, such as :

‘d.Hi’=’d.Lo’

‘Ao.Hi’=’Ao.Lo’

(‘Ao.Hi’-’Ao.Lo’)>(’d.Hi’-’d.Lo’)

2.2.3

Factory configuration

Mode

Scaling

Display Low

Output Low

Display High

Output High

On error

‘mA’

0

4.00 [mA]

9999

20.00 [mA] to high level(‘to_h’)’

Instruction Manual

Mode

Mode 4/20   mA

Mode 0/10   Vdc

Scaling Display low

Output low

Display high

Output high

‘On error’

Factory configuration

Version in case of error, ‘to_h’ to drive output to high level, ‘to_L’ to drive output to low level select ‘yES’ to reload the default factory configuration

26

DPF20 Frequency, rate, total or period counter Instruction Manual

2.3 Module RTU

Module RTU provides 1 Modbus RTU communications port, to install in DPF20 digital panel meters. Enables protocol function ‘4’ (‘ Read In put Registers ’) to access the instrument registers (reading value, alarm status, memory of maximum and minimum, setpoint values, ...).

Protocol configuration is performed from the frontal keypad of the meter, by setting the parameters at the options configuration menu

(‘Opt.1’, ‘Opt.2’ or ‘Opt.3’ depending on the position the module is installed).

Option

Output type

RTU

Modbus RTU communication port

Function implemented 4 (Read_Input_Registers)

Addresses

Exception codes

Registers

Bus speed

Data format bus terminator

Isolation

Configuration

Temperature

Factory configuration

Installation allowed at

01 to 247 see section see section

2.3.1

RS-485

57.6 Kbps to 600 bps

8n1 (standard), 8o1, 8n2, 8e1 not included

1000 Vdc

3 button front keypad operation from 0 to 50 ºC storage from -20 to +70 ºC

‘Address 1’

‘Speed 19.2 Kbps’

‘Format 8n1’

‘Decimal point Auto’

‘Opt.1’, ‘Opt.2’, ‘Opt.3’

Up to a maximum of 3 RTU modules can be installed in a single in strument, all modules isolated between them and isolated from all other circuits.

Modules RTU can be ordered pre-installed into a DPF20 digital panel meter, or standalone for delayed installation, as they do not require soldering or special configuration.

Module Connections

Module RTU - Modbus RTU

Table 11 - Connection terminals

Terminal B B signal from RS-485 bus

Terminal A A signal from RS-485 bus

Terminal G GND

Opt.1

B A G

Signal

Rear view DPF20

Opt.2

B A G

Power

2.3.1 Accessible registers

Register Name

0 DISPLAY1_L

1

9

10

7

8

11

12

13

4

5

2

3

6

DISPLAY1_H

DECIMALS1

MAXMEM_L

MAXMEM_H

MINMEM_L

MINMEM_H

SETPOINT1_L

SETPOINT1_H

SETPOINT2_L

SETPOINT2_H

SETPOINT3_L

SETPOINT3_H

STATUS

Description

Display value

Decimals on display

Memory of maximum

Memory of minimum

Setpoint 1 value

Setpoint 2 value

Setpoint 3 value

Size

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

16 bits

14 a 16 Reserved

Alarm status

Instrument status

Reserved 16 x 3 bits

Table 10 - Registers accessible via MODBUS-RTU.

All registers codified as binary numbers. Negative values are codified in two’s complement.

Refresh same as display every

30 seconds every

2 seconds same as display

Value : Series M

999999 to -199999

0 to 6

999999 to -199999

999999 to -199999

999999 to -199999

999999 to -199999

999999 to -199999

Value : Series K and S

9999 to -1999

0 to 4

9999 to -1999

9999 to -1999

9999 to -1999

9999 to -1999

9999 to -1999* bit 0...7 alarm status bit 8...16 instrument status

Not accessible Not accessible

27

DPF20 Frequency, rate, total or period counter

2.3.2

Configuration menu

Configuration Address

Speed

(kbps)

1 to 247

57.6

...

  Kbps

...

to 600   bps

Instruction Manual

Configure at menu ‘ Configuration ’ (‘rtu’), the address value between

‘1’ and ‘247’ at parameter ‘Address’ (‘Addr’), bus speed in kbps at parameter ‘Speed’ (‘ bAud ’) and data format at parameter ‘Format

(‘ bItS ’).

Special tools are grouped inside the ‘Tools’ (‘TooL’) menu.

• the ‘Decimal point’ (‘dP’) menu is provided for compatibility with ancient hardware that does not support decimal point retransmis sion. By default, select ‘ Automatic ’ (‘Auto’). If your instrument does nos transmit the decimal point position, select ‘Manual

(‘MAnL’) and fix the position of the decimal point manually.

• at the ‘Factory reset’ (‘FAct’) menu, select ‘yes’ to load the de fault factory configuration for the instrument.

the ‘ Version ’ (‘ VEr ’) menu informs of the current firmware version installed in the module.

Tools

Format

Decimal point

Factory configuration

Version

Automatic

Manual

8 bits, no parity, 1 stop

8 bits, even parity, 1 stop

8 bits, odd parity, 1 stop

8 bits, no parity, 2 stop

Move with LE

2.3.3

Exception codes

The Modbus RTU protocol defines the following scenarios when a

‘Master’ is sending a frame to a ‘Slave’:

• the ‘Slave’ device receives the frame correctly and replies with the requested data

• the ‘Slave’ devices detects a CRC error, parity error, or other. and discards the frame without generating a reply frame. The ‘Master’ will detect a ‘TIMEOUT’ condition due to the absence of reply.

• the ‘Slave’ device receives the frame correctly, but replies with an

‘EXCEPTION_CODE’ as it can not process the function or register re quested.

The ‘EXCEPTION_CODES’ configured in the RTU module are :

Description Exception code

Name

0 ILLEGAL_FUNCTION

1 ILLEGAL_DATA_ADDRESS

Table 12 - Exception codes

Requested function is not supported

Requested register is not supported

28

DPF20 Frequency, rate, total or period counter Instruction Manual

2.3.4

Description and example for Modbus RTU registers

Register R0 and R1 (DISPLAY1_L and DISPLAY1_H)

Contains the display value of the instrument, codified in two registers of 16 bits each. Possible values are from 999999 to -199999. Decimal point position is codified on register R2.

Example R0=FBF1 (hex) and R1=0009 (hex)

Register value = 0009 FBF1 (hex)

Reading value = 654321

Register R9 and R10 (SETPOINT2_L and SETPOINT2_H)

Contains the setpoint value of alarm 2, codified in two registers of 16 bits each. Possible values are from 999999 to -199999. Decimal point position is codified on register R2.

Example - same example as in R0 and R1 but accessing to R9 and

R10.

Register R2 (DECIMALS1)

Contains the number of decimals of the display, codified in a single register of 16 bits. Possible values are from 0 to 6.

Example R2=0002 (hex)

Number of decimals = 2 = 6543.21

Register R11 and R12 (SETPOINT3_L and SETPOINT3_H)

Contains the setpoint value of alarm 3, codified in two registers of 16 bits each. Possible values are from 999999 to -199999. Decimal point position is codified on register R2.

Example - same example as in R0 and R1 but accessing to R11 and

R12.

Register R3 and R4 (MAXMEM_L and MAXMEM_H)

Contains the memory of maximum reading of the instrument, codi fied in two registers of 16 bits each. Possible values are from 999999 to -199999. Decimal point position is codified on register R2.

Example - same example as in R0 and R1 but accessing to R3 and

R4.

Register R5 and R6 (MINMEM_L and MINMEM_H)

Contains the memory of minimum reading of the instrument, codi fied in two registers of 16 bits each. Possible values are from 999999 to -199999. Decimal point position is codified on register R2.

Example - same example as in R0 and R1 but accessing to R5 and

R6.

Register R13 (STATUS)

Information bit-by-bit, for the alarm status (on / off) and instrument status. See below for a description.

Bit 0

Bit 1

Alarm 1 status (0 = inactive, 1 = active)

Alarm 2 status (0 = inactive, 1 = active)

Bit 2 Alarm 3 status (0 = inactive, 1 = active)

Bit 3 a 7 Reserved

Bit 8

Bit 9

Display overrange

Display underrange

Bit 10 Lost communication with the main processor

Bit 11 to 15 Reserved

Registers R14, R15 and R16

Reserved

Register R7 and R8 (SETPOINT1_L and SETPOINT1_H)

Contains the setpoint value of alarm 1, codified in two registers of 16 bits each. Possible values are from 999999 to -199999. Decimal point position is codified on register R2.

Example - same example as in R0 and R1 but accessing to R7 and

R8.

29

DPF20 Frequency, rate, total or period counter Instruction Manual

2.4 Module S4

Module S4 provides 1 RS-485 ASCII communications port, to install in

DPF20 digital panel meters. ASCII protocol with ‘ master ’ - ‘ slave ’ architecture. Addressable up to 31 modules. Frames codified in rep resentable ASCII characters (codes 32 to 255), directly visible using

‘hyperterminal’ or similar programs.

Instrument registers are accessible through the RS-485 ASCII port

(reading value, alarm status, memory of maximum and minimum, setpoint values, ...).

Protocol configuration is performed from the frontal keypad of the meter, by setting the parameters at the options configuration menu

(‘Opt.1’, ‘Opt.2’ or ‘Opt.3’ depending on the position the module is installed).

Up to a maximum of 3 S4 modules can be installed in a single instru ment, all modules isolated between them and isolated from all other circuits.

Modules S4 can be ordered pre-installed into a DPF20 digital panel meter, or standalone for delayed installation, as they do not require soldering or special configuration.

Option

Output type

Bus

Speed

Data format

Protocol

Architecture

Addresses

‘Broadcast’ address

Registers

Isolation

Configuration

Temperature

Installation allowed at

S4

RS-485 ASCII communication port

RS-485

57.6 Kbps to 600 bps

8n1 (standard), 8o1, 8n2, 8e1

ASCII

‘master - slave’

01 to 31

128 see section

2.4.1

1000 Vdc

3 button front keypad operation from 0 to 50 ºC storage from -20 to +70 ºC

‘Opt.1’, ‘Opt.2’, ‘Opt.3’

Module Connections

Module S4 - RS-485 ASCII

Table 13 - Connection terminals

Terminal B B signal from RS-485 bus

Terminal A A signal from RS-485 bus

Terminal G GND

Opt.1

B A G

Opt.2

B A G

Signal

Rear view DPF20

Power

2.4.1 Accessible registers

Display values (DISPLAY1, MAXMEM, MINMEM, AL1, AL2, AL3) are codified with a minimum of 6 digits (left zeros are added if neces sary), polarity and decimal point.

Register

0

3

4

1

2

5

6

Name

DISPLAY1

MAXMEM

MINMEM

AL1

AL2

AL3

STATUS

Table 14 - Accessible registers for ASCII protocol.

Description

Display1 value

Memory of maximum

Memory of minimum

Setpoint 1 value

Setpoint 2 value

Setpoint 3 value

Alarm status

Register 0 - DISPLAY1

Contains the display value of the instrument, in ASCII code, including polarity (positive / negative) and decimal point.

Example 1 R0=’+’ ‘0’ ’6’ ‘5’ ‘4’ ‘3’ ‘.’ ‘2’

Display value = 6543.2

Example 2 R0=’-’ ‘0’ ‘0’ ‘0’ ‘4’ ‘.’ ‘5’ ‘2’

Display value = -4.52

Register 1 - MAXMEM

Contains the value for memory of maximum, in ASCII code, including polarity (positive / negative) and decimal point.

Register 2 - MINMEM

Contains the value for memory of minimum, in ASCII code, including polarity (positive / negative) and decimal point.

Register 3 - AL1

Contains the value for alarm 1 setpoint, in ASCII code, including po larity (positive / negative) and decimal point.

Register 4 - AL2

Contains the value for alarm 2 setpoint, in ASCII code, including po larity (positive / negative) and decimal point.

Register 5 - AL3

Contains the value for alarm 3 setpoint, in ASCII code, including po larity (positive / negative) and decimal point.

Register 6 - STATUS

Contains the alarm status (on/off).

Bit 0

Bit 1

Alarm 1 status (0 = inactive, 1 = active)

Alarm 2 status (0 = inactive, 1 = active)

Bit 2 Alarm 3 status (0 = inactive, 1 = active)

Bit 3 to 15 Reserved

30

DPF20 Frequency, rate, total or period counter Instruction Manual

2.4.2

Configuration menu

Configuration

ASCII

Configuration

‘Master’

Tools

Mode

Address

Speed

(kbps)

Format

Decimal point

1 to 31

Automatic

‘Slave’ mode

‘Master’ mode

8 bits, no parity, 1 stop

8 bits, even parity, 1 stop

8 bits, odd parity, 1 stop

8 bits, no parity, 2 stop

At menu ‘ Configuration ASCII ’ (‘ AScI ’), configure the instrument at parameter ‘Mode’ (‘ModE’) to work as ‘slave’ or ‘master’, at param eter ‘ Address’ (‘Addr’) set the address value from ‘1’ to ‘31’, set the bus speed in kbps at parameter ‘Speed’ (‘ bAud ’) and set the data format at parameter ‘Format’ (‘ bItS ’).

When working as ‘master’, the instrument continuously transmits the display value data frame. The local module address is ‘0’. Con figure at menu ‘ Configuration Master ’ (‘cnF.M’) the ‘ Destination ad -

dress’ (‘d.Add’) parameter from ‘1’ to ‘31’ or use value ‘128’ for a broadcast message. At parameter ‘Frequency’ (‘FrEq’) select the how often the frame with the reading value will be transmitted.

Special tools are grouped inside the ‘Tools’ (‘TooL’) menu.

• the ‘Decimal point’ (‘dP’) menu is provided for compatibility with ancient hardware that does not support decimal point retransmis sion. By default, select ‘ Automatic ’ (‘Auto’). If your instrument does nos transmit the decimal point position, select ‘Manual

(‘MAnL’) and fix the position of the decimal point manually.

•the ‘Legacy mode’ (‘ LEG’ ) parameter is provided to maintain compatibility with instruments with older communication proto cols. Select ‘on’ to activate this mode.

• the ‘Answer delay’ (‘ AnS.d’ ) parameter applies only to ‘Slave’ mode. The local module delays the answer frame. Configure for applications where the ‘Master’ needs additional time to switch between ‘transmit’ and ‘receive’ modes. Enter a numeric value be tween ‘0’ and ‘1000’ mSeconds.

• at the ‘Factory reset’ (‘FAct’) menu, select ‘yes’ to load the de fault factory configuration for the instrument.

the ‘ Version ’ (‘ VEr ’) menu informs of the current firmware version installed in the module.

Destination address

Frequency

1 to 31

128 for ‘broadcast’

0.1

  seconds

0.5

  seconds

1   seconds

5   seconds

15   seconds

60   seconds

2.4.3

Factory configuration

Configuration ASCII

Mode

Address

Speed (‘bAud’)

Format (‘bItS’)

Configuration ‘Master’

Destination address

Frequency

Tools

Decimal point

Legacy

Answer delay

Slave

1

19.2 Kbps

8n1

31

0.5 seconds

Auto

Off

0 mSeconds

Manual use key ‘LE’ to select

Legacy mode delay for answers, from 0 to 1000 mSec.

Answer delay

Factory configuration

Version

31

DPF20 Frequency, rate, total or period counter Instruction Manual

2.4.4

Frame types

The ASCII protocol defines the following frames:

• Frame ‘read’ (‘RD’). Id code 36. Request data frame. The requested register is indicated into the ‘REG’ byte (‘Header’ section).

• Frame ‘answer’ (‘ ANS ’). Id code 37. Response frame to a request data frame. The requested register is indicated into the ‘REG’ byte’

(‘Header’ section). Data of the requested register is indicated into data bytes ‘D0’ to ‘Dn’ (‘Data’ section).

2.4.5 Frame structure

• Frame ‘error’ (‘ERR’). Id code 38. Response frame to a request data frame. Indicates that an error has occurred. Error code is codified into the ‘REG’ byte (‘Header’ section).

• Frame ‘ping’ (‘ PING ’). Id code 32. Used to confirm the existence of the remote instrument.

• Frame ‘pong’ (‘ PONG ’). Id code 33. Response to a ‘ping’ frame. It confirms the existence of the remote instrument.

STX

2

0

ID x

1

Header

RSV FROM TO

32 x x

2 3 4

REG x

5

RSV LONG

32 n+1

6 7

D0

8

Data

D1

[data]

...

9 ...

Dn n+7

CRC x n+8

Trail

ETX

3 n+9

Protocol frames have a structure made of ‘Header’, ‘Data’ and ‘Trail’.

Section ‘Header’

Contains the start byte (‘STX’), the frame identifier (‘ID’), the origin address (‘FROM’) and the destination address (‘TO’), the register id

(‘REG’) and the length (‘LONG’) of the ‘Data’ section.

Section ‘Data’

Contains data for the requested register (‘REG’).

Section ‘Trail’

Contains the ‘CRC’ code and the end of frame byte (‘ETX’).

‘Real value’ and ‘Frame value’

To use representable ASCII values, the real values are codified before being sent into the frame. The following definitions apply :

• ‘real value’ is the value of the field without codification

• ‘frame value’ is the value of the field, codified

Field

STX

ID

RSV

FROM

TO

REG

RSV

Description

Start of frame

Frame type

Reserved

Origin address

Destination address

Register identification

Reserved

LONG Length of ‘Data’ section

D0 … Dn Data

CRC

ETX

CRC calculation

End of frame

Table 15 - Description of the bytes for the ASCII frame

Size

1 byte

1 byte

Position Real value

0 does not apply

1

(see section 2.4.4)

Frame value

2 real_value

1 byte

1 byte

1 byte

2

3

4

1 byte 5

1 byte 6 0

1 byte 7 n (between 0 and 32) n bytes 8 to n+7 number 0 to 9 decimal point polarity (+/-)

1 byte

1 byte n+8 n+9

0 32

0 (‘Master’) / 1 to 31 (‘Slave’) 32 + real_value

0 (‘Master’) / 1 to 31 (‘Slave’)

128 (‘broadcast’)

32 + real_value

(see section 2.4.1)

32 + real_value does not apply does not apply

32

32 + real_value

ASCII code of the number (48 to 57)

ASCII code of decimal point (46)

ASCII code of ‘+’ (43)

ASCII code of ‘-’ (45)

(see section 2.4.8)

3

2.4.6

Error codes

Frames ‘ERR’ contain within the ‘REG’ field, the error code. Available error codes are : error 1 error 2 unknown register display overrange error 3 display underrange error 4 error 5

CRC error internal error

32

DPF20 Frequency, rate, total or period counter Instruction Manual

2.4.7 Frame examples

Frames ‘RD’ (36) and ‘ANS’ (37)

Example - ‘Master’ (address ‘0’) requests the value of register ‘0’ (dis play value) to the ‘Slave’ at address ‘28’ (‘RD’ frame) and the ‘Slave’ replies to the ‘Master’ with a reply frame (‘ANS’ frame) containing the requested data (765.43).

*Instruments with 4 digits also send reading values formatted with 6 digits : value -321.5 is transmitted as -00321.5

Header

STX

2

ID

36

Start RD

Header

STX

2

ID

37

Start ANS

RSV

32

---

RSV

32

---

FROM TO

32 60

0 28

FROM TO

60 32

28 0

REG

32

0

REG

32

0

RSV

32

---

RSV

32

---

32

0

Trail

LONG CRC

58

CRC

ETX

3

Stop

Data Trail

LONG D0 D1 D2 D3 D4 D5 D6 D7 CRC

40

8

43 48 55 54 53

+0765.43

46 52 51 15

CRC

ETX

3

Stop

Frames ‘ERR’ (38)

Example - ‘Slave’ at address ‘11’ replies to the ‘Master’ (address ‘0’) with an error frame (‘ERR’ frame) indicating that the requested regis ter number is unknown (‘UNKNOWN_REGISTER’, error code ‘1’). The

Header

STX ID

2 38

Start ERR

RSV

32

---

FROM TO

43

11

32

0

REG

33

1

RSV

32

--error code is codified into the ‘REG’ byte. For a list of error code see

section 2.4.6.

Trail

LONG CRC

32

0

46

CRC

ETX

3

Stop

Frames ‘PING’ (32) and ‘PONG’ (33)

Example - ‘Master’ (address ‘0’) requests confirmation of existence to the ‘Slave’ at addrress ‘22’ (‘PING’ frame) and the ‘Slave’ replies to the ‘Master’ with a ‘PONG’ frame.

Header Trail

STX ID RSV FROM TO REG RSV LONG CRC ETX

2 32 32 32 54 32 32 32 52 3

Start Ping --0 22 0 --0 CRC Stop

Header Trail

STX ID RSV FROM TO REG RSV LONG CRC ETX

2 33 32 54 32 32 32 32 53 3

Start Pong --22 0 0 --0 CRC Stop

2.4.8 CRC calculation

The ‘frame value’ for the CRC byte is calculated applying a XOR func tion to the ‘frame value’

(see section 2.4.5) of all bytes in sections

‘Header’ and ‘Data’, from byte ‘0’ (‘STX’) to the last data byte (‘Dn’).

• if the calculated CRC value is lower than ‘32’, it is normalized by ap plying the ‘one’s complement’ function .

CRC0=STX ^ ID ^ RSV ^ FROM ^ TO ^ REG ^ RSV ^ LONG ^ D0 ^...^ Dn

• if (CRC0<32) -> CRC=!CRC0 (one’s complement function)

• if (CRC0>31) -> CRC=CRC0

//example of CRC calculation in C language

{ int8 Calculate_CRC(int8 CRC_Position)

int8 i,CRC=0;

for(i=0;c<CRC_Position;c++)

{

crc=crc ^ frame[i];

}

}

if(crc<32) CRC=~CRC;

return(CRC);

33

DPF20 Frequency, rate, total or period counter Instruction Manual

2.5 Module S2

Module S2 provides 1 RS-232 ASCII communications port, to install in

DPF20 digital panel meters. Protocol specifications are the same as with module S4

(see section 2.4) , with only difference that the physical bus is

RS-232 instead of RS-485.

S2 modules allow for point-to-point communication over RS-232 and also allow for multinode communication over RS-232 using a ‘Daisy-Chain’ type of connection.

Terminals RX1 and TX1 are for connection to the RS-232 bus. Terminals

RX2 and TX2 are for RS-232 multinode connection. Frames received on

RX1 with destination address different than the local instrument’s ad dress, will be retransmitted over the TX2 terminal. In a similar way, frames received from RX2 with destination address other than the local address, will be retransmitted over TX1 terminal.

Up to a maximum of 3 S4 modules can be installed in a single instrument, all modules isolated between them and isolated from all other circuits.

Modules S2 can be ordered pre-installed into a DPF20 digital panel meter, or standalone for delayed installation, as they do not require soldering or special configuration.

Option

Output type

Bus

Speed

Data format

Protocol

Architecture

Addresses

‘Broadcast’ address

Registers

Isolation

Configuration

Temperature

Installation allowed at

S2

RS-232 ASCII communication port

RS-232

57.6 Kbps to 600 bps

8n1 (standard), 8o1, 8n2, 8e1

ASCII

‘master - slave’

01 to 31

128 see section

2.4.1

1000 Vdc

3 button front keypad operation from 0 to 50 ºC storage from -20 to +70 ºC

‘Opt.1’, ‘Opt.2’, ‘Opt.3’

2.6 Modules R2, R4 and R6

Modules R2, R4 and R6 provide 2, 4 and 6 relay outputs, to install in

DPF20 digital panel meters.

Configuration is performed from the frontal keypad of the meter, by setting the parameters at the ‘Opt.1’ configuration menu (not from the alarm configuration menu (‘ALr.1’, ‘ALr.2’ o ‘ALr.3’) of the instru ment).

The menu allows to configure the setpoint, hysteresis, independent activation and deactivation delays, and a second setpoint to create alarm windows.

Only 1 modules R2, R4 or R6 can be installed in a single instrument, as the are not compatible with themselves (2 modules R2 are not ac cepted) and are not compatible with modules R1, T1 or SSR.

Modules R2, R4 and R6 are isolated against all other instrument cir cuits.

Modules R2, R4 and R6 can be ordered pre-installed into a DPF20 digital panel meter, or standalone for delayed installation, as they do not require soldering or special configuration.

Option R2, R4, R6

Output type

Relay type

Maximum current

Maximum voltage*

* terminals approved for 300   V (as per UL1059, groups B and D) and

160   V (as per VDE at CAT-III and pollution degree 3).

Isolation

Type of terminal

Installation allowed at relay (2, 4 and 6 relays)

3 contacts (NC, NO, common)

6 A per relay (resistive load)

250 Vac continuous

2500 Veff plug-in screw terminal pitch 5.08 mm

‘Opt.1’

Module R2

Module R4

Module R6 occupies Opt.1 (2 relays) occupies Opt.1 and Opt.2 (4 relays) occupies Opt.1, Opt.2 and Opt.3 (6 relays)

Module Connections

Module S2 - RS-232 ASCII

Table 16 - Connection terminals

Opt.1

Terminal A

Terminal B

Terminal C

Terminal D

Terminal E

A B C D E

Opt.2

A B C D E

Tx2

Rx2

Tx1

Rx1

GND

Signal

Rear view DPF20

Power

34

Relay relay 1 relay 2 relay 3 relay 4 relay 5 relay 6

Common

A

D

G

J

M

P

Table 17 - Connection terminals

Normally Open (NO) Normally Closed (NC)

B

E

H

K

N

Q

C

I

F

L

O

R

Opt.1

Opt.2

A B C D E F G H I J K L

Signal

Rear view DPF20

Power

DPF20 Frequency, rate, total or period counter

2.6.1 Configuration menu

Alarm   1 Active

Type of alarm

Setpoint

Hysteresis

Delay   0

Delay   1

Setpoint   2

Menu for Alarm 2, at modules R2, R4 and R6

Menu for Alarm 3, at modules R4 and R6

Menu for Alarm 4, at modules R4 and R6

Menu for Alarm 5, at modules R6

Menu for Alarm 6, at modules R6

Factory configuration

Version

Instruction Manual

To configure alarm 1, access the ‘Alarm1’ (‘ALr1’) menu and config ure the following parameters : To configure alarms 2, 3, etc, access the corresponding menu entries.

• select ‘ Active ’ (‘Act’) to ‘on

• at ‘ Alarm type’ (‘TypE’) select the maximum alarm (‘MAX’) or minimum alarm (‘ MIn ’). The maximum alarm (or type alarm) ac tivates when display value is higher (or lower) than the setpoint value.

• at ‘ Setpoint’ (‘SEt’) enter the alarm activation value.

• configure the hysteresis value at ‘Hysteresis’ (‘hySt’). The hyster esis applies to the deactivation process of the alarm. The alarm de activates when the reading has passed the setpoint value plus the hysteresis value.

• at ‘ Delay0’ (‘dEL.0’) assign the delay to be applied before alarm activation. The activation delay starts counting when the setpoint value is passed. Configurable from 0.0 to 99.9 seconds.

• at ‘ Delay1’ (‘dEL.1’) assign the delay to be applied before alarm deactivation. The deactivation delay starts counting when the set point value plus the hysteresis value, is passed. Configurable from

0.0 to 99.9 seconds.

• to activate the second setpoint, activate ‘Setpoint2’ (‘SEt2’) to

on’ and then configure the desired setpoint value. Second setpoint allows for windowed alarms. The first setpoint activates the alarm, and the second setpoint deactivates the alarm (configuration for

‘Alarm as maximum’ type of alarm). Second setpoint must always be higher in value than the first setpoint.

2.6.2

Factory configuration

Factory configuration for alarms 1, 2, 3, 4, 5 and 6

‘Active

‘Type

‘Setpoint 1

‘Setpoint 2

‘Setpoint 3

‘Setpoint 4

‘Setpoint 5

‘Setpoint 6

‘Hysteresis

‘Activation delay

‘Deactivation delay

‘Setpoint 2 on’ de maxima’

1000’

2000’

3000’

4000’

5000’

6000’

0 counts’

0.0 counts’

0.0 seconds’

Off’

35

DPF20 Frequency, rate, total or period counter

3.

How to open and close

3.1 How to open the housing

A. Locate the clips

Locate the 4 clips (A B C D). Clips are covered by the front filter.

Clips can be seen when looking from the rear of the instrument, just below the front filter.

A.1

B D A.2

A.3

D B

Instruction Manual

B

C

C A

A A

B. How to unclip one clip

Place a flat screw driver at the first clip. Insert firmly until the end of the clip space, and then turn gently the screwdriver clockwise approx.

45º (while still pushing against the clip). The front filter will ‘move up’ and unclip itself. Clip is unclipped when the front filter corner moves slightly to the front.

B.1

B.2

B.3

Screw driver placed

B

Screw driver turned

B

B B

Clipped Unclipped

A

C. Repeat with all clips

Repeat for remaining 3 clips. All 4 clips are now unclipped.

Front filter is slightly moved to the front on each corner. It can now be removed by hand.

C.1

C.2

D B

Unclipped

A

C.3

C A Unclipped

36

DPF20 Frequency, rate, total or period counter Instruction Manual

3.2 How to close the housing

A. Locate the clips

Locate the 4 clips (A B C D) at the housing (image A.1) and the 4 matting clips at the filter (image A.2). With the instrument inside the housing, face the front filter against the housing (do not clip yet). Do not press the rear terminals with your hand, as the instrument would force the filter outwards.

A.1

B D A.2

A.3

D B

A

C

C

Front filter

Internal View

A

B. Fit corner ‘X’ and clip ‘A’

Fully insert corner ‘X’ into the housing. See at image B.2 that the filter is not yet clipped : only corner ‘X’ is completely fitted. Corner ‘Y’ can be also fitted or not fitted (it is not important). With corner X fitted and firmly pressed (it must remain fitted), press clip ‘A’ and it will clip (you will hear a clear ‘snap’).

B.1

B.2

B.3

Corner ‘Y’ can be fitted or not fitted

Corner ‘X’ fitted

‘X’

Press ‘A’

Corner ‘X’ fitted

C. Clip remaining clips ‘B’, ‘C’ & ‘D’

Still press firmly corner ‘X’ until all four clips are clipped. You can release your finger from clip ‘A’ as clip ‘A’ will not unclip once it is clipped.

Press on clip ‘B’ until it clips (you will hear a clear ‘snap’). Then press on clips ‘C’ and ‘D’ (you will hear a clear ‘snap’ on each case).

C.1

C.2

C.3

2n

Press ‘D’

Press ‘B’

Corner ‘X’ fitted

1st

Press ‘C’

Corner ‘X’ fitted

37

DPF20 Frequency, rate, total or period counter Instruction Manual

38

DPF20 Frequency, rate, total or period counter Instruction Manual

39

Where Do I Find Everything I Need for

Process Measurement and Control?

OMEGA…Of Course!

Shop online at omega.com

TEMPERATURE

Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies

Wire: Thermocouple, RTD & Thermistor

Calibrators & Ice Point References

Recorders, Controllers & Process Monitors

Infrared Pyrometers

PRESSURE, STRAIN AND FORCE

Transducers & Strain Gages

Load Cells & Pressure Gages

Displacement Transducers

Instrumentation & Accessories

FLOW/LEVEL

Rotameters, Gas Mass Flowmeters & Flow Computers

Air Velocity Indicators

Turbine/Paddlewheel Systems

Totalizers & Batch Controllers pH/CONDUCTIVITY pH Electrodes, Testers & Accessories

Benchtop/Laboratory Meters

Controllers, Calibrators, Simulators & Pumps

Industrial pH & Conductivity Equipment

DATA ACQUISITION

Communications-Based Acquisition Systems

Data Logging Systems

Wireless Sensors, Transmitters, & Receivers

Signal Conditioners

Data Acquisition Software

HEATERS

Heating Cable

Cartridge & Strip Heaters

Immersion & Band Heaters

Flexible Heaters

Laboratory Heaters

ENVIRONMENTAL

MONITORING AND CONTROL

Metering & Control Instrumentation

Refractometers

Pumps & Tubing

Air, Soil & Water Monitors

Industrial Water & Wastewater Treatment pH, Conductivity & Dissolved Oxygen Instruments

M5675/0818

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement