Error Code
Atmospheric Vent Water Heaters - ICON
Definition Service Action Possible Parts Needed
No LED
One flash & three second pause
LED Strobe (two quick flashes)
& three second pause
LED on continuously
Two flashes & three second pause
Three flashes & three second pause
Four flashes & three second pause
Five flashes & three second pause
Six flashes & three second pause
No pilot light / Heater not in operation
Knob in pilot position or thermostat satisfied
Thermostat calling for heat
Control knob turned to the off position
Weak pilot signal detected
Gas valve has not seen temp rise in proper amount of time
High tank temperature
Thermostat sensor fault Check temp probe ohms
Check water temperature
Water leak detected by the accessory module Refer to troubleshooting for the
(if installed) accessory module
Seven flashes & three second pause Gas valve fault
Eight flashes & three second pause Pilot remains lit while the control knob is in off position
Follow lighting instructions on the water heater
None
None
Wait for LED to go off before relighting
Verify pilot is lit
Check thermopile voltage output
Check wire connections at gas valve
Check temp probe ohms
Verify water is not flowing
Check temp probe ohms
Check water temperature
Reset gas valve; if problem persists replace gas valve
Check gas pressure
Replace gas valve
1) None
1) None
1) None
1) None
1) Pilot assembly
2) Gas valve
1) Gas valve cover w/ temp probe
1) Gas valve cover w/ temp probe
1) Gas valve cover w/ temp probe
1) Refer to troubleshooting for the
accessory module
1) Gas valve
1) Gas valve
NOTE: Check all wire connections
Check gas inlet and manifold gas pressure
Check for grounding connections
Technical Support
800-334-3393 www.bradfordwhite.com