Bradford White BMFTCF-199 Brute FT Floor Standing Boilers (BMFTCF) Installation Manual

Add to My manuals
88 Pages

advertisement

Bradford White BMFTCF-199  Brute FT Floor Standing Boilers (BMFTCF) Installation Manual | Manualzz
Installation and Operation Instructions
Document 1320C
Installation and Operation
Instructions for
THE
FT SERIES
Floor-Standing, Modulating
Gas, Condensing, Combination Boiler
Model MFTCF
140,000 BTU/hr
199,000 BTU/hr
• Natural Gas (NG) - Factory Configuration
• Propane Gas (LP) - Field-Convertible
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation
could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or
death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
H2373000C
Installation and service must be performed
by a qualified installer, service agency, or gas
supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ou ni
d’autres vapeurs ou liquides inflammables dans
le à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE
GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir
des téléphones dans le bâtiment où vous vous
trovez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié
ou par le fournisseur de gaz.
SECTION 1
Product Accessories
TABLE OF CONTENTS
1.2 Included with the Appliance................................. 1-2
4.16 Disposal of Condensate.......................................43
4.17 Electrical Wiring Connections............................ 44
4.18 DIP Switches..................................................... 45
SECTION 2
Product Characteristics
4.19 Control Board, Electrical Diagram ..................... 47
4.20 Ladder Diagram................................................. 48
4.21 Electrical Connections....................................... 49
1.1 Introduction............................................................ 1
2.1
2.2
2.3
2.4
2.5
Model Nomenclature (model number).................... 3
Specifications......................................................... 4
Dimensions............................................................ 6
Names of Components.......................................... 8
Product Flow and Characteristics........................ 10
2.5.1 Central Heating Flow...................................10
2.5.2 Domestic Hot Water Flow........................... 11
SECTION 3
Safety Regulations
3.1 Safety Symbols.................................................... 12
3.2 Safety Precautions and Proper Use..................... 14
SECTION 5
Control Display and Operation
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
Control Dial and Buttons.......................................50
LCD Overview.......................................................51
Operating Mode.................................................. 52
Status Display Mode.......................................... 53
DHW Set Point Change Mode............................ 54
CH Set Point Change Mode............................... 55
Storage Mode..................................................... 55
Installer Mode..................................................... 56
Outside Temperature (option)............................. 58
External Set Point Temperature Control............. 58
SECTION 4
Installation
5.11 Error Mode......................................................... 59
4.1 Location and Clearances......................................16
4.2 Wall Mount Bracket...............................................17
4.2.1 Installation Height and Location..................17
4.2.2 Hang the Boiler...........................................17
4.3 Combustion Air......................................................18
4.3.1 Combustion Air from Room.........................18
4.3.2 Ducted Combustion Air...............................18
4.4 Venting (exhaust)..................................................20
4.5 General Location Guidelines.................................21
4.6 Locations for Vent Pipe Terminator.......................23
4.6.1 Direct Venting Clearances...........................23
4.6.2 Non-Direct Venting Clearances...................24
4.6.3 Venting Requirements in Massachusetts....25
4.7 Air Supply and Vent Connections at the Appliance..26
4.7.1 Vent / Air Pipe Lengths................................26
4.7.2 Direct Venting..............................................26
4.7.3 Indoor Combustion Air.................................27
4.8 Vent / Air Pipe Termination....................................27
4.9 Gas Supply and Piping..........................................29
4.10 Gas Supply Pressure...........................................32
4.11 Gas Set Up and Adjustment.................................32
4.12 High Altitude Installations. 2,000' to 10,000'.........33
4.13 Natural Gas to Propane Conversion....................34
4.14 Plumbing Guideline..............................................38
4.15 Pressure Relief Valves.........................................42
SECTION 6
Error Codes
6.1 Error Codes........................................................ 60
6.2 Fault Tree Analysis............................................. 63
SECTION 7
Trouble Shooting
7.1 Diagnostics......................................................... 65
7.2 Suggested Corrective Actions............................ 67
SECTION 8
Maintenance
8.1 Annual Startup and General Maintenance......... 68
8.2 Flushing or Draining........................................... 70
SECTION 9
Installation Check
9.1 Quick View......................................................... 71
9.2 Final Check Lists................................................ 72
SECTION 10
Repair Part Diagrams
10.1 Parts List and Illustrations............................. 74-85
Page 1
The FT Series Floor Standing, Combination Boiler
SECTION 1
Product Accessories
1.1 Introduction
2) CSA B149.1 “Natural Gas and Propane Installation Code” and
with the requirement of the local utility or other authorities having
jurisdiction. Such applicable requirements take precedence over
the general instructions contained herein.
This manual provides information necessary for the
installation, operation, and maintenance of the floorstanding
FT. All application and installation procedures must be
read and reviewed completely before proceeding with
the installation. Consult the factory, or your local factory
representative, with any problems or questions regarding
this equipment. Experience has shown that most operating
problems are caused by improper installation.
All electrical wiring is to be done in accordance with the local
codes, or in the absence of local codes, with: 1) The National
Electrical Code ANSI/NFPA No. 70-latest Edition, or 2) CSA
STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance
must be electrically grounded in accordance with these codes.
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest
Edition “National Fuel Gas Code” or
1.2 Included with the Appliance
Item
Description
Qty
Floor-Standing,
Combination Boiler
FTCF140 or FTCF199
1
FTCF140
Kit # R20771
Document 4290B
The FT Series, Floor-Standing, Gas Conversion Kit
H2373900B
Kit # R20771
Top Access Panel
Front Panel Knob
The FT Series, floor standing, condensing boiler is configured
for Natural Gas (NG) from the factory. A Natural Gas to Propane
Front Panel
Conversion Kit is included with every FT. The gas conversion kit will
show you how to convert your FT boiler to propane gas. If your FT
does not have the bag containing the conversion kit, a replacement kit can be
obtained. Contact the manufacturer and request a replacement conversion kit.
NOTICE
If your installation altitude is greater than 2000 ft, please check that the ‘High Altitude’
Installer Setting has been adjusted to suit your installation altitude. Refer to Section
4.12 of the Installation and Operation Instructions (Document 1320).
WARNING
2.
Turn OFF the GAS and WATER supply to the
FT (valves are located on the plumbing pipes.)
Natural Gas
(NG) Part #
Propane Gas
(LP) Part #
FTCF140
FT1722
FT1722P
FTCF199
FT1780
FT1802
Nozzle
_________________________________
This gas conversion kit shall be installed by a qualified service
agency in accordance with the manufacturer’s instructions and
all applicable codes and requirements of the authority having
jurisdiction. The information in these instructions must be
followed to minimize the risk of fire or explosion or to prevent
property damage, personal injury or death. The qualified service
agency is responsible for the proper installation of this kit. The
installation is not proper and complete until the operation of the
converted appliance is checked as specified in the manufacturer’s
instructions supplied with the kit.
Installation must conform to local codes and the latest edition
of the National Fuel Gas Code, ANSI Z223.1 and CAN-B149.1.
Failure to follow instructions could result in serious injury or
property damage.
The qualified agency performing this work assumes
responsibility for gas conversion.
This combination boiler has already been set to burn
natural gas, but can be converted to burn LP gas. Before
placing the combination boiler into operation, verify that
your fuel source is natural gas. Or verify that your fuel
source is propane if you are converting this combination
unit to propane.
2.
Turn OFF the FT.
The ON / OFF button is
located at the bottom left of the Control Display.
Turn OFF the GAS and WATER supply to the
FT (valves are located on the plumbing pipes.)
Natural Gas
(NG) Part #
Propane Gas
(LP) Part #
FTCF140
FT1722
FT1722P
FTCF199
FT1780
FT1802
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 1 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
This conversion shall be installed by a qualified service
agency in accordance with the manufacturer's instructions
and all applicable codes and requirements of the authority
having jurisdiction. If the information in these instructions
is not followed exactly, a fire, an explosion or production
of carbon monoxide may result causing property damage,
personal injury or loss of life. The qualified service agency is
responsible for the proper and complete installation of this kit.
The installation is not proper and complete until the operation
of the converted appliance is checked as specified in the
manufacturer's instruction supplied with the kit.
Nozzle
Orifice
Table A
WARNING
AVERTISSEMENT
Ce conversion doit être installé par un organisme de service
conformément aux instructions du fabricant et tous les
codes et les exigences de l’autorité compétente. Si les
informations contenues dans ces instructions n’est pas suivi
à la lettre, un incendie, une explosion ou de la production de
monoxyde de carbone mais résultat causant des dommages
matériels, des blessures ou des pertes de vie. Le service est
responsable pour la bonne et complète l’installation de ce kit.
L’installation n’est pas correcte et complète jusqu’à ce que
le fonctionnement de l’appareil converti est vérifiée comme
spécifié dans le manuel d’instruction fourni avec le kit.
AVERTISSEMENT
Ce conversion doit être installé par un organisme de service
conformément aux instructions du fabricant et tous les
codes et les exigences de l’autorité compétente. Si les
informations contenues dans ces instructions n’est pas suivi
à la lettre, un incendie, une explosion ou de la production de
monoxyde de carbone mais résultat causant des dommages
matériels, des blessures ou des pertes de vie. Le service est
responsable pour la bonne et complète l’installation de ce kit.
L’installation n’est pas correcte et complète jusqu’à ce que
le fonctionnement de l’appareil converti est vérifiée comme
spécifié dans le manuel d’instruction fourni avec le kit.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 1 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
THE
Figure A
ON / OFF
Steps 1 thru 26
To convert from Natural Gas to Propane Gas
1.
CAUTION
Orifice
Table A
WARNING
This conversion shall be installed by a qualified service
agency in accordance with the manufacturer's instructions
and all applicable codes and requirements of the authority
having jurisdiction. If the information in these instructions
is not followed exactly, a fire, an explosion or production
of carbon monoxide may result causing property damage,
personal injury or loss of life. The qualified service agency is
responsible for the proper and complete installation of this kit.
The installation is not proper and complete until the operation
of the converted appliance is checked as specified in the
manufacturer's instruction supplied with the kit.
This water heater applied to the ____ gas.
(Ce chauffe-eau appliquee au gaz ____.)
Gas conversion date : ____ / ____ / ____
(Date de conversion de gaz :)
Converted by the technicians :
(Converti par les techniciens:)
Turn OFF the FT.
The ON / OFF button is
located at the bottom left of the Control Display.
.18
This combination boiler has already been set to burn
natural gas, but can be converted to burn LP gas. Before
placing the combination boiler into operation, verify that
your fuel source is natural gas. Or verify that your fuel
source is propane if you are converting this combination
unit to propane.
Figure A
ON / OFF
Steps 1 thru 26
To convert from Natural Gas to Propane Gas
1.
CAUTION
H2373900B
1
WARNING
This gas conversion kit shall be installed by a qualified service
agency in accordance with the manufacturer’s instructions and
all applicable codes and requirements of the authority having
jurisdiction. The information in these instructions must be
followed to minimize the risk of fire or explosion or to prevent
property damage, personal injury or death. The qualified service
agency is responsible for the proper installation of this kit. The
installation is not proper and complete until the operation of the
converted appliance is checked as specified in the manufacturer’s
instructions supplied with the kit.
Installation must conform to local codes and the latest edition
of the National Fuel Gas Code, ANSI Z223.1 and CAN-B149.1.
Failure to follow instructions could result in serious injury or
property damage.
The qualified agency performing this work assumes
responsibility for gas conversion.
.18
This boiler was converted on ____/____/____/ to____ gas
with Kit No._________ by _________ ( name and address of
organization making this conversion, who accepts the
responsibility for the correctness of this coversion)."
« Cette chaudière a été convertie le (annéemoisjour) ____ pour
fonctionner au gaz ____ à l’aide de la trousse n° par (nom et
adresse de l’organisme qui a effectué la conversion), qui
a effectué la conversion), qui accepte l’entière
responsabilité de la qualité de la conversion. »
Document 4290B
Top Access Panel
Front Panel Knob
The FT Series, floor standing, condensing boiler is configured
for Natural Gas (NG) from the factory. A Natural Gas to Propane
Front Panel
Conversion Kit is included with every FT. The gas conversion kit will
show you how to convert your FT boiler to propane gas. If your FT
does not have the bag containing the conversion kit, a replacement kit can be
obtained. Contact the manufacturer and request a replacement conversion kit.
NOTICE
If your installation altitude is greater than 2000 ft, please check that the ‘High Altitude’
Installer Setting has been adjusted to suit your installation altitude. Refer to Section
4.12 of the Installation and Operation Instructions (Document 1320).
H2373900B
LP Conversion Kit.
This kit includes the new LP orifice and
the gas conversion instructions.
FTCF199
The FT Series, Floor-Standing, Gas Conversion Kit
H2373900B
www.Laars.com
FT
THE
FT
Installation Instructions and
User’s Manual
1 Each
Spare Parts Kit
(Gaskets and O-Rings)
1
Condensate Hose
1
Page 2
1.2 Included with the Appliance (continued)
Items
Mesh screen
(3" mesh)
Descriptions
Qty
2
Outdoor Sensor with
Screws and Anchors
1
Pressure Relief Valve
(CH LINE 3/4″ 30psi)
Model : CASH ACME F-82
1
Page 3
The FT Series Floor Standing, Combination Boiler
SECTION 2.
Product Characteristics
2.1
Model Nomenclature (model number)
The Model Nomenclature is shown on your Rating Plate and consists of a series of letters and numbers
( Nomenclature ) that further identifies the characteristics of your FT.
1
2
3
4
M
F
T
C
SERIES
FT
5
7
8
9
F
CONFIG
C - Combi
6
F - Floor Stnd
SIZE
MBTU/h
140
199
FUEL
N - Natural
10
11
12
13
A
1
X
N
ALTITUDE
A - 0 -10,000 Feet
REVISION
1 - First
OPTIONS
X - Standard
P - Propane
Figure 1. Model Nomenclature
MODEL NUMBER
Figure 2. Locating the model number
PUMP
N - with Pump
Page 4
2.2
18.
19.
combustion readings. At this point, just record the CO2 readings at MAX Fire. Do NOT attempt to adjust
CO2 at MAX Fire. ONLY in MIN Fire, so...
Per Table B for MIN Fire, change dip switch 6 to OFF and 7 to ON. The unit will cycle down to MIN Fire.
WAIT for your combustion analyser to stabilize. Then check the CO2 measurement at MIN fire. Refer to
Specifications
Table D for acceptable MIN fire combustion readings.
20.
21.
If CO2 readings in Max Fire and MIN fire are acceptable, then skip ahead to Step 23. If not, then open the
Model
Name
FTCF140
Gas
Valve
Adjustment Port by removing the cap screw with
a 4mm Allen wrench. See Figure E.
Then use the 4 mmMAX
Allen wrench to make a minor adjustment
turn) to either increase or decrease CO2.
140,000(1/8
Btu/h
Gas Input Rate
MIN
35°F Rise
Manifold
pressure
45°F Rise
MAX Fire
FTCF140
77°F Rise
MIN Fire
Installation
MAX Fire
FTCF199
Flue System
MIN Fire
Vent Run
Hot Water Capacity
Table C
Gas Supply Pressure
NG
3.5" WC to 10.5" WC
LP
8.0" WC to 13" WC
Gas Type
CO2 value
Vent size
Manifold Pressure
28,000 Btu/h
‘NG’ type combustibility
‘LP’ type combustibility
7.1 Gal
2" VENT
3" VENT
2" VENT
3" VENT
5.5 Gal
-0.15" WC
-0.216" WC
-0.15" WC
-0.216" WC
3.2 Gal
0” WC
0.002” WC
0.1” WC
0.079” WC
Indoor / Floor stand type
-0.134” WC
-0.173” WC
Sealed Combustion Direct / Single / Concentric Vent/ SideWall Vent
-0.015” WC
-0.015” WC
2"(50ft) , 3"(100ft) Schedule 40 CPVC, PP
FTCF140
FTCF140
‘NG’ typeLP
combustibility
VENT
2"2"
VENT
‘LP’ typeNG
combustibility
VENT
3"3"
VENT
VENT
2"2"VENT
VENT
3"3"VENT
MAXfire
Fire
Min
-0.15" WC8.5~10.5%
-0.216" WC
%
-0.15" WC9.5~11-0.216"
WC
MINfire
Fire
Low
0.1" WC 8~10%
0.079" WC
%
0" WC 9~10.50.002"
WC
MAX Fire
8.5~10.0% 120V 60Hz / 6A
9.5~11 %
Main Supply
FTCF199
800.900.9276
•
Fax
800.559.1583
(Customer
Service,
Power Supply
MIN Fire
8~10%
9~10.5
% Service Advisors)
Maximum Power
20 Industrial Way, Rochester, NH 03867 160W
• 603.335.6300 • Fax 603.335.3355 (Applications Engineering
Consumption
Table D
pg 3 o
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
Ignition System
Direct Electronic Ignition / Automatic Flame Sensing
www.Laars.com
Burner System
Single Orifice Premixed Fuel Modulation Ceramic Infrared
Gas Valve System
Combination modulating (Current proportional)
Minimum Flow Rate
0.5 GPM
Dimensions
W15.7" - H52.4" – D26.7"
Shipping Weight
230 lbs
( 104 kg )
Sub Heat Exchanger Water Capacity(DHW)
Under 15 Gallon
Main Controller / Control Panel
GTX-920CP / P-920C
Water Pressure
Min 15 ~ Max 150 PSI
Connection Sizes
Materials
Cold Water Inlet / Hot
Water Outlet
3/4" NPT
Space Heating
Supply / Return
1" NPT
Gas Inlet
3/4" NPT
Casing
Cold Rolled Carbon Steel
Heat Exchanger
Primary Heat Exchanger : Stainless Steel
Sub Heat Exchanger : Stainless Steel
Safety Devices
Flame Rod, Overheat Cut Off Device, Gas Valve Operation
Detector, Exhaust Temperature High Limit Switch, Water
Temperature High Limit Switch
2
combustion readings. At this point, just record the CO2 readings at MAX
Fire. Do NOT attempt to adju
Table
D
for
acceptable
MIN
fi
re
combustion
readings.
CO
at
MAX
Fire.
ONLY
in
MIN
Fire,
so...
2
If CO
in Max
and MIN
fire are6acceptable,
skip The
ahead
Step
23.down
If not,
, change
Per
Table
B for MIN
FireFire
dip switch
to OFF and then
7 to ON.
unittowill
cycle
tothen
MIN
Fire. the
Page
5 open
20.
The FT Series18.
Floor
Standing,
Combination
Boiler
2 readings
Gas Valve
Adjustment
Portanalyser
by removing
the capThen
screwcheck
with athe
4mm
wrench. See
E. Refer to
for your
combustion
to stabilize.
COAllen
at Figure
MIN fire.
19. WAIT
2 measurement
21.
20.
If CO2 readings in Max Fire and MIN fire are acceptable, then skip ahead to Step 23. If not, then open the
21.
Gas Valve Manifold
Adjustmentpressure
Port by removing the cap screw with a 4mm Allen wrench. See Figure E.
2" VENT
3" VENT
2"
VENT
VENT or decrease CO
MAX
199,000(1/8
Btu/h
Then use the 4 mm
Allen wrench to make
a minor adjustment
turn)
to either 3"
increase
Then use
4 mm Allen
wrench
to make a readings.
minor adjustment (1/8 turn) to either increase or decrease CO
Table
D forthe
acceptable
MIN
fire combustion
Model Name
Gas Input Rate
‘NG’ type combustibility
FTCF199‘LP’ type combustibility
MIN MAX Fire
FTCF140
MIN Fire
35°F Rise
Manifold
pressure
45°F RiseMAX Fire
MAX Fire
FTCF199
FTCF140
77°F RiseMIN Fire
MIN Fire
Installation
Table C
MAX Fire
Flue System
FTCF199
MIN Fire
Vent Run
Hot Water Capacity
Table C
Gas Supply Pressure
Manifold Pressure
CONG
2 value
LP
Gas Type MAX Fire
FTCF140
CO2 value
Vent size MIN Fire
-0.216
-0.216" WC
19,900
" WC Btu/h-0.15" WC
‘NG’ type combustibility
‘LP’ type combustibility
0” WC
0.002” 9.88
WC Gal 0.1” WC
0.079” WC
2" VENT
3" VENT
2" VENT
3" VENT
-0.134” WC
-0.173” WC
7.7 Gal
-0.15" WC
-0.216" WC
-0.15" WC
-0.216" WC
-0.015” WC
-0.015” WC
4.8 Gal
0” WC
0.002” WC
0.1” WC
0.079” WC
Indoor / Floor stand type
-0.134” WC
-0.173” WC
Sealed Combustion Direct / Single / Concentric Vent/ SideWall Vent
-0.015” WC
-0.015” WC
2"(50ft) , 3"(100ft) Schedule 40 CPVC, PP
-0.15" WC
‘NG’ type combustibility
‘LP’ type combustibility
3.5" WC to 10.5" WC
2" VENT
3"
VENT
2" VENT
3" VENT
8.0"
WC to 13" WC
8.5~10.5%
‘NG’ type
LPcombustibility
9.5~11
%
‘LP’ type
combustibility
NG
VENT8~10%
VENT
2" 2"
VENT
3" 3"
VENT
9~10.53"
%
VENT
3"VENT
VENT
2"2"
VENT
8.5~10.0%
9.5~11
%
%
-0.15" WC8.5~10.5%
-0.216" WC
-0.15" WC9.5~11
-0.216"
WC
800.900.9276
•
Fax
800.559.1583
(Customer
Service,
Service
MIN
%
Low
fireFire
0.1" WC 8~10%
0.079" WC
0" WC 9~10.50.002"
WC Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engine
Fire
8.5~10.0% 120V 60Hz / 6A
9.5~11 %
Table DMain SupplyMAX 1869
p
Sismet Road, Mississauga,
Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.01
FTCF199
800.900.9276
•
Fax
800.559.1583
(Customer
Service,
Service
Advisors)
Power Supply
MIN
Fire
8~10%
9~10.5
%
www.Laars.com
Maximum Power
• 603.335.6300 • Fax 603.335.3355 (Applications Engine
Consumption 20 Industrial Way, Rochester, NH 03867160W
Table D
p
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.01
Ignition System
Direct
Electronic
Ignition
/
Automatic
Flame
Sensing
www.Laars.com
FTCF199
FTCF140
FTCF140
MAX
Fire
MAX
Min
fireFire
Burner System
Single Orifice Premixed Fuel Modulation Ceramic Infrared
Gas Valve System
Combination modulating (Current proportional)
Minimum Flow Rate
0.5 GPM
Dimensions
W15.7” - H53.7” – D26.7”
Shipping Weight
242 lbs
( 110 kg )
Sub Heat Exchanger Water Capacity(DHW)
Under 15 Gallon
Main Controller / Control Panel
GTX-920CP / P-920C
Water Pressure
Min 15 ~ Max 150 PSI
Connection Sizes
Materials
Cold Water Inlet / Hot
Water Outlet
3/4" NPT
Space Heating
Supply / Return
1" NPT
Gas Inlet
3/4" NPT
Casing
Cold Rolled Carbon Steel
Heat Exchanger
Primary Heat Exchanger : Stainless Steel
Sub Heat Exchanger : Stainless Steel
Safety Devices
Flame Rod, Overheat Cut Off Device, Gas Valve Operation
Detector, Exhaust Temperature High Limit Switch, Water
Temperature High Limit Switch
Note; The greatest installation difference between the FTCF140 and FTCF199, other than general output capability
(BTU’s), is that the air inlet and exhaust vents are opposite. See Section 2.4
Page 6
2.3 Dimensions
3.0" 7.6 cm
FTCF140
3.3" 8 cm
15.7" 40 cm
9.2" 23 cm
TOP
3” O EXHAUST VENT
26.7"
3” O AIR INLET
20.5"
A
GAS CONNECTION
9.3"
39.3"
2.7"
4.3"
52.4" 133 cm
30"
C
HYDRONIC SUPPLY
HYDRONIC RETURN
B
D
E
4.3"
27.3"
5.8"
23"
18.7" 9.2"
12.9"
3.7"
FRONT
68 cm
F
DHW OUTLET
DHW INLET
CONDENSATE
G
DRAIN ADAPTER
19.7"
23.3"
Description
Diameter
A
Gas Connection
3/4" NPT
B
‘CH supply’ Connection
1" NPT
C
‘CH return’ Connection
1" NPT
D
‘DHW outlet’ Connection
3/4" NPT
E
‘DHW inlet’ Connection
3/4" NPT
F
Condensate
1/2" NPT
G
Drain
1/2" NPT
SIDE
Page 7
The FT Series Floor Standing, Combination Boiler
3.0" 7.6 cm
5.0" 13 cm
FTCF199
4.0" 10.4 cm
Note: The greatest installation difference between the
FTCF140 and FTCF199, other than general output
capability (BTU’s), is that the air inlet and exhaust vent
are opposite. See Section 2.4
6.6" 16.9 cm
15.7" 40 cm
TOP
3” O AIR INLET
68 cm
26.7"
3” O EXHAUST VENT
17.9"
GAS CONNECTION
A
18.9"
48.3"
2.6"
53.7" 137 cm
4.3"
29.4"
HYDRONIC SUPPLY
HYDRONIC RETURN
B
D
E
4.3"
26.8"
5.7"
22.5"
18.2" 8.8"
12.5"
3.7"
FRONT
C
F
DHW OUTLET
DHW INLET
CONDENSATE
G
DRAIN ADAPTER
19.7"
23.3"
SIDE
Description
Diameter
A
Gas Connection
3/4" NPT
B
‘CH supply’ Connection
1" NPT
C
‘CH return’ Connection
1" NPT
D
‘DHW outlet’ Connection
3/4" NPT
E
‘DHW inlet’ Connection
3/4" NPT
F
Condensate
1/2" NPT
G
Drain
1/2" NPT
Page 8
2.4 Names of Components
FTCF140
NO
Name of Component
NO
Name of Component
1
Exhaust Vent
17
Condensate Drain Hose
2
Air Pressure Sensor
18
DHW Inlet Adapter
3
Blower
19
Condensate Trap
4
PCB Bracket
20
DHW Outlet Adapter
5
Flame Detection Sensor
21
Condensate Heat Exchanger Hose
6
Sight Glass
22
CH Return Connection
7
Manual Switch
23
Air Pressure Switch
8
Display Control
24
CH Supply Connection
9
Exhaust Pipe
25
Heat Exchanger
10
Recirculation Pump (CH)
26
Gas Inlet Connection
11
Mixing Valve
27
Gas Valve
12
Recirculation Pump (DHW)
28
Air Vent (air eliminator)
13
DHW Tank Assembly
29
Ignition Transformer
14
Water Drain Valve
30
Igniter
15
Water Drain Adapter
31
Air Intake Pipe
16
Condensate Trap Adapter
32
Air Inlet
Page 9
The FT Series Floor Standing, Combination Boiler
FTCF199
Note: The greatest installation
difference between the
FTCF140 and FTCF199,
other than general output
capability (BTU’s), is that the
air inlet and exhaust vent are
opposite.
NO
Name of Component
NO
Name of Component
1
Air Inlet
17
Condensate Drain Hose
2
Air Pressure Sensor
18
DHW Inlet Adapter
3
Blower
19
Condensate Trap
4
PCB Bracket
20
DHW Outlet Adapter
5
Sight Glass
21
Condensate Heat Exchanger Hose
6
Flame Detection Window
22
CH Return Connection
7
Manual Switch
23
CH Supply Connection
8
Display Control
24
Air Pressure Switch
9
Air Intake Pipe
25
Heat Exchanger
10
Recirculation Pump (CH)
26
Igniter
11
Mixing Valve
27
Gas Valve
12
Recirculation Pump (DHW)
28
Ignition Transformer
13
DHW Tank Assembly
29
Gas Inlet Connection
14
Water Discharge Valve
30
Air Vent (air eliminator)
15
Water Discharge Adapter
31
Exhaust Pipe
16
Condensate Trap Adapter
32
Exhaust Vent
Page 10
2.5 Product Flow Paths and Characteristics
2.5.1 Central Heating flow. Combination Boiler Heating Mode.
Water in the heating pipe is used for space heating.
acteristics
Operating Mode
Space Heating
Water Supply
ng mode. (Central Heating = CH mode)
Space Heating
Water Return
d for space heating.
Combustion
Air Inlet
GasInlet
Inlet
Gas
Space Heating
WaterHeating
Supply
Space
Water Supply
Space
Heating
Space Heating
Water Return
Water
Return
Space Heating
Water Supply
Space Heating
Water Return
Note: The
condensate trap
has been hidden
to simplify the
view
The FT Series Floor Standing, Combination Boiler
Page 11
2.5 Product Flow Paths and Characteristics
uct Characteristics
2.5.2 Domestic Hot Water flow.
Operating Mode
Combination Boiler Domestic Hot Water Mode.
Cold water passes through the exchanger and is heated via a mini indirect tank.
The domestic hot water (DHW) is provided on demand.
r of Hot water mode. (Domestic Hot Water = DHW mode)
e ‘Sub heat exchanger’, then cold water transformed into hot water.
er (DHW) is controlled by the consumer. It can provide hot water on demand.
Combustion
Air Inlet
Gas Inlet
Gas Inlet
Domestic Hot
Water Outlet
Domestic Hot
WaterDomestic
Outlet
Hot
Water Outlet
Domestic Hot
Domestic
Hot Inlet
Water
Water Inlet
Domestic Hot
Water Inlet
Note: The
condensate trap
has been hidden
to simplify the
view
Page 12
SECTION 3.
Safety Regulations
3.1 Safety Symbols
WARNING
To avoid product damage, personal injury, or even
possible death, carefully read, understand, and
follow all the instructions in the Installation and
Operation manual before installation, operation
and service the Boiler.
The manufacturer cannot anticipate every
circumstance that might involve a potential
hazard. Therefore, all possible incidents are not
included in our warnings. Proper installation,
operation, and service are your responsibility.
You must make sure that the operation and
settings of the Boiler are safe for you and for
others.
This manual provides Safety Symbols. When the
user fails to adhere to the following requirement,
it may cause death, serious injury, and substantial
property damage.
For safety symbols, ‘DANGER’, ‘WARNING’,
CAUTION’ are indicated and the definitions for these
terms are as follow:
DANGER
Indicates an imminently hazardous situation
which, if not avoided, will result in death or
serious injury. This signal word is limited to the
most extreme situations.
WARNING
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
CAUTION
Indicates a potentially hazardous situation
which, if not avoided, may result in minor or
moderate injury. It is also used to alert against
unsafe practices and hazards involving only
property damage.
WARNING
FOR YOUR SAFETY READ BEFORE
OPERATING
If you do not follow these instructions exactly, a
fire or explosion could result causing property
damage, personal injury or loss of life.
A. This appliance does not have a pilot. It
is equipped with an ignition device which
automatically lights the burner. Do not try to
light the burner by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next
to the floor because some gas is heavier than
air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will
not push in or turn by hand, don’t try to repair
it, call a qualified service technician. Force
or attempted repair may result in a fire or
explosion.
D. Do not use this appliance if any part has
been under water. Immediately call a qualified
service technician to inspect the appliance and
to replace any part of the control system and
any gas control which has been under water.
This appliance must be installed in accordance with
local codes if any; if not, follow ANSI Z224.1/NFPA
54 or CAN/CSA B149.1, Natural Gas and Propane
Installation Code, as applicable.
This appliance is certified for use at altitudes up
to 4,500ft(1,370m) in accordance to the latest CSA/
CGA 2.17-M91 Gas-Fired Appliances for Use at
High Altitudes.
The FT Series Floor Standing, Combination Boiler
Page 13
damaging condition that might affect the operation
of the unit. Boiler must be checked by a qualified
technician before resuming operation.
DANGER
Vapors from flammable liquids can explode and
catch on fire, resulting in severe burns or death.
Do not use or store flammable products such
as gasoline, solvents or adhesives in the same
room or area near the appliance.
Keep flammable products
Far away from boiler
In approved containers
Tightly closed
Out of children’s reach
Vapors
Cannot be seen
Are heavier than air
Spread on the floor
Can spread from other rooms to the main burner
by air currents
Do not install the appliance where flammable
products will be stored.Read and follow boiler
warnings and instructions thoroughly. If owner’s
manual is missing, contact the retailer or
manufacturer.
This combination boiler must be installed by a
qualified plumber, a licensed gas fitter, and/or a
professional service technician.
Improper installation and/or operation will cause a
potentially hazardous situation, such as serious injury
or death. Also, it will void the warranty.
• The National Fuel Gas Code NFPA 54 / ANSI Z224.1
• National Electric Code ANSI/NEPA 70
• All applicable local, state, national and provincial
codes, regulations and laws.
Proper care is your responsibility. Carefully read and
understand the Operating Information in this manual
before operating the boiler.
Be aware of the location of the gas shut-off valve
and operation method. Close the gas shut-off valve
immediately if the appliance is subjected to fire,
overheating, flood, physical damage, or any other
DO NOT use this Boiler if any part has been under
water. Immediately call a qualified technician for
inspecting the Boiler and replacing any part of the
control system and gas control which have been
under water.
Do not power up the unit until the gas and water
supply valves are fully opened. Make sure that the
fresh air intake port and exhaust gas port are opened
and functional.
DO NOT attempt to install, repair, or service this
Boiler by yourself.
Do not change any part of the Boiler.
Contact a qualified technician if the Boiler needs
repair or maintenance.
Ask your gas supplier for a list of qualified service
providers.
DO NOT use spray paint, hair spray, or any other
flammable spray near Boiler or near the exterior fresh
air inlet port. DO NOT place any items in or around
the exterior exhaust gas outlet port and/or fresh air
inlet port. These could restrict or block the flow in or
out of the vent system.
“Caution: While repairing control, all wires are
labeled. You must connect the wires in accordance
with the instruction. Wiring errors can cause improper
and dangerous
operation.
“Verify proper operation after servicing operation”
This consists of the gas ignition system components
which are protected from water (dripping, spraying, rain,
etc.) during operation and service (circulator replacement,
condensate trap, control replacement, etc.).
After installing the heater, safety devices must be
tested.
This boiler is equipped with a blocked vent shutoff
system.
If the error code ‘41’ occurs, follow the instructions
below.
- First, turn off the manual gas valve.
- Make sure that there is no foreign object in the vent
passage or rodent screen.
- If you do not find any problem, do the following.
- Turn off the error state by pressing the power button
of control panel.
- If the error occurs repeatedly, call your service
technician or gas supplier.
Page 14
SECTION 3.
Safety Regulations
3.2 Safety Precautions and Proper Use
When in Operation
Before Operation
1. Check
the Gas Type (NG/LP)
When using or moving the unit for the first time, check
if gas type matches with the gas type of the Boiler.
Check whether the gas type which is supplied is NG
(Natural Gas) or LP (Propane) and also check the
Boiler gas type. The gas type is indicated on the rating
plate on side of the Boiler.
2. Check the Power (120V 60Hz)
Check that the appliance is connected properly.
3. Check the Cold Water
Inlet valve. Please keep the
appliance water inlet valve
open at all times. The appliance
will not ignite when insufficient
water or no water is in the
heating pipes. (valve: always
open position)
open
4. Check the Gas Valve
Check that the manual gas shut-off valve
that supplies the FT is opened.
5. Check the area around the appliance and remove
any combustible or flammable materials. Remove
laundry or any other items that are on or near the
boiler or vent pipe.
CAUTION
1. Caution for Gas leak
Frequently check for a gas leak at the gas connection
portion with soapy water.
Steps to take if you have a Gas leak.
1.Shut down the boiler as soon as gas fumes are
detected.
2. Close the intermediate gas valve.
3. Open windows for ventilation.
4. Call a qualified service technician for immediate
repair.
2. Caution for Ventilation
Make sure that there is sufficient inflow and outflow of air
ventilation while using the unit.
If the ventilation is improper, combustion quality may
deteriorate inside the appliance and cause shortened life
of the appliance.
3. Burn Warning
Be careful not to burn yourself on the flue or pipes. They
become extremely hot during operation.
Page 15
The FT Series Floor Standing, Combination Boiler
WARNING
Do not use the appliance for any other purpose
than for heating and hot water.
Do not store combustibles or flammable material
such as gasoline near the appliance.
Do not store other items on or near this boiler.
Do not store combustible (flammable) materials
such as papers.
Do not hang clothes on the vent pipe. This may
start a fire.
CAUTION
Scalding Risk: Manufacturer recommends
the use of a thermostatic mixing
valve at domestic hot water
outlet (boiler location) to
reduce potential for scalding.
Contact Manufacturer for
recommended models.
__________________________________________
fter repair of gas pipeline or gas regulator
A
replacement, call A qualified contractor for inspection
before starting it up.
Carbon monoxide poisoning
If vent pipe fumes enter the room, it could cause
poisoning by carbon monoxide gas. Check that the
vent pipes are properly connected. Open windows
for ventilation. Call a qualified service technician for
immediate repair.
Gas leakage test.
Gas supply line must be inspected regularly.
Do not shut off the Boiler.
When you leave home for a long time, do not
shut off Boiler. The Boiler has a freeze protection
function. The ceramic heater is installed inside of
the heater’s internal pipe to protect the heater from
freezing.
Do not wipe the appliance or control panel
with wet cloth. Electric shock may occur, or
internal parts may fail due to the exposure to
moisture.
Do not disassemble the Boiler.
If repair is required, call your local qualified
technician.
Page 16
SECTION 4. Installation
4.1 Location and Clearances
The appliance should be located to provide clearances
on all sides for maintenance and inspection. It should
not be located in an area where leakage of any
connections will result in damage to the area adjacent to
the appliance or to lower floors of the structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
FT Boilers must never be installed on carpeting. The
location for the appliance should be chosen with regard
to the vent pipe lengths and external plumbing and on
a level surface. The unit shall be installed such that
the gas ignition system components are protected
Minimum Clearance
15 in
38 cm
10 in
25 cm
5/
8
in
1.6 cm
from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement,
control replacement, etc.). When vented vertically,
the FT must be located as close as practical to the
vertical section of the vent. If the vent terminal and/
or combustion air terminal terminate through a wall,
and there is potential for snow accumulation in the
local area, both terminals should be installed at
an appropriate level above grade or the maximum
expected snow line.
Minimum Clearances
For installation
From Non-Combustibles
/combustibles
10 in
25 cm
3 in
8 cm
d
te
es
gg
Su
25 in
64 cm
rv
nc
ra
ea
Cl
e
Figure 3.
40 in
101 cm
Locating the Appliance.
Minimum clearances to Combustibles.
15 in (38 cm)
15 in (38 cm)
Back of
appliance
5/8 in (1.6 cm)
5/8 in (1.6 cm)
Front of
appliance
10 in (25 cm)
40 in (101 cm)
or more
Side of
appliance(right)
10 in (25 cm)
25 in (64 cm)
or more
Side of
appliance(left)
3 in (8 cm)
3 in (8 cm)
Bottom of
appliance
0in (0 cm)
0in (0 cm)
Minimum Clearances
to Combustibles and
Suggested Service Clearance.
ice
g
Sug
Top of appliance
Table 1.
Se
ce
ervi
dS
este
ce
aran
Cle
Suggested
Service
Clearance
The FT Series Floor Standing, Combination Boiler
WARNING
Installations must comply with
•All the local, state, provincial, and national codes,
laws, regulations and ordinances.
•National Fuel Gas Code, ANSI Z223.1 – The latest
version.
•National Electrical Code.
•A National Standard of Canada CAN/CSA-B149.1
Check before placing the Combination boiler
•Always check the connected components which are
near to the heater. The components are below.
Water piping position / Venting adapter / Gas supply
piping / Electrical power / Condensate drain hose.
•Inspect area around Combination boiler. Remove
any combustible materials, gasoline and other
flammable liquids. Failure to keep Combination
boiler area clear and free of combustible materials,
gasoline and other flammable liquids and vapors can
result in severe personal injury, death or substantial
property damage.
•The Combination boiler which has gas control
system components must be protected from any
possible danger during operation and service.
•If new Combination boiler replaces an existing
appliance, check and correct system problems, for
example:
-Do not install if: System leaks causing oxygen
corrosion or heat exchanger cracks from hard water
deposits.
Provide clearances
•If the heater was installed in a narrow space
or corner, please ensure that there is sufficient
space for service and maintenance access. For
regular maintenance, gas and water lines must be
accessible.
The boiler must be installed on a wall that can bear its weight.
WARNING
CLEARANCES FOR SERVICE ACCESS
•If you do not provide the minimum clearances
shown, it might not be possible to service the
boiler without removing it from the space.
•Space must be provided with combustion /
ventilation air openings correctly sized for
all other appliances located in the same
space as the boiler. The boiler cover must be
securely fastened to prevent it from drawing
air from the boiler room. This is particularly
important if the boiler is in a room with other
appliances. Failure to comply with the above
warnings could result in substantial property
damage, severe personal injury, or death.
Page 17
Page 18
SECTION 4. Installation
4.3 Combustion Air
FT boilers must have provisions for combustion
and ventilation air in accordance with the applicable
requirements for Combustion Air Supply and Ventilation
in the National Fuel Gas Code, ANSI Z223 1; or in
Canada, the Natural Gas and Propane Installation Code,
CSA B149.1. All applicable provisions of local building
codes must also be adhered to.
A FT unit can take combustion air from the space
in which it is installed, or the combustion air can be
ducted directly to the unit. Ventilation air must be
provided in either case.
4.3.1 Combustion Air from Room
In the United States, the most common requirements
specify that the space shall communicate with the
outdoors in accordance with method 1 or 2, which follow.
Where ducts are used, they shall be of the same crosssectional area as the free area of the openings to which
they connect.
Method 1: Two permanent openings, one commencing
within 12” (300mm) of the top and one commencing
within 12” (300mm) of the bottom, of the enclosure
shall be provided. The openings shall communicate
directly, or by ducts, with the outdoors or spaces
that freely communicate with the outdoors. When
directly communicating with the outdoors, or when
communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1
square inch per 4000 Btu/hr (550 square mm/kW) of
total input rating of all equipment in the enclosure. When
communicating to the outdoors through horizontal ducts,
each opening shall have a minimum free area of not
less than 1 square inch per 2000 Btu/hr (1100 square
mm/kW) of total input rating of all equipment in the
enclosure.
Method 2: One permanent opening, commencing
within 12” (300mm) of the top of the enclosure, shall
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform to
the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in
absence of such requirements, follow CAN/CGA B149.1
4.3.2 Ducted Combustion Air
The combustion air can be taken through the wall, or
through the roof. When taken from the wall, it must be
taken from out-of-doors by means of the horizontal wall
terminal. When taken from the roof, a field-supplied rain
cap or an elbow arrangement must be used to prevent
entry of rain water.
Use ABS, PVC, CPVC, polypropylene, or galvanized
pipe for the combustion air intake. Route the intake
to the boiler as directly as possible. Seal all joints.
Provide adequate hangers. The unit must not support
the weight of the combustion air intake pipe. Maximum
linear pipe length allowed is shown in Table 6. Subtract
5 allowable linear ft. (1.5m) for every elbow used.
The connection for the intake air pipe is at the top of
the unit.
In addition to air needed for combustion, air shall also
be supplied for ventilation, including air required for
comfort and proper working conditions for personnel.
COMBUSTION AIR INSTALLATION STANDARDS
MATERIAL
ABS
PVC, sch 40
CPVC, sch 40
Polypropylene
Single wall galv. steel
Table 2.
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces
that directly communicate with the outdoors and shall
have a minimum free area of 1 square inch per 3000
Btu/hr (734 square mm/kW) of the total input rating of
all equipment located in the enclosure. This opening
must not be less than the sum of the areas of all vent
connectors in the confined space.
UNITED STATES
ANSI/ASTM D1527
ANSI/ASTM D1785 or D2665
ANSI/ASTM F441
UL1738, ULC S636.
26 gauge
Required Combustion Air Pipe Material.
CANADA
Air pipe material must be chosen
CPVC, sch 40, ANSI/ASTM, Polypropylene
based upon the intended application of the boiler.
Page 19
The FT Series Floor Standing, Combination Boiler
NOTICE
The instructions for the installation of the venting
system shall specify that the horizontal portions of
the venting system shall be supported to prevent
sagging; the methods of and intervals for support
shall be specified. These instructions shall also
specify that the venting system:
Category I, II and IV boilers must be installed so
that horizontal sections have a slope of at least ¼
inch per foot (21 mm/m) to prevent accumulation of
condensate; and
For Category II and IV boilers, where necessary,
have means provided for drainage of condensate.
CAUTION
The FT is standard as a Natural Gas Boiler and
must be converted if propane is the desired gas, unless
specifically manufactured for propane.
Adequate drainage
•The appliance should be installed not to damage
the adjacent area. If such locations cannot be
avoided, it is recommended that a suitable drain
pan, adequately drained, be installed under the
appliance. The pan must not block combustion air
flow.
Connecting the Water Supply
•To conserve water and energy, insulate all water
piping—especially the hot and recirculation water
lines. Never cover the drain or pressure relief valve.
Having a backflow preventer in the cold water
supply line will prevent thermal expansion
backflow. Contact the water supplier or local
plumbing inspector for information about how to
control this situation.
Ifoverheating occurs or the gas supply fails to shut
off, turn off the manual gas valve.
This installation must conform with below section
•“Air for Combustion and Ventilation” of the
National Fuel Gas Code, ANSI Z224.1/NFPA 54,
or Sections 8.2, 8.3 or 8.4 of Natural Gas and
Propane Installation Code, CAN/CSA B149.1, or
applicable provisions of the local building codes.
AVIS
Les instructions d'installation du système
d'évacuation doivent préciser que les sections
horizontales doivent être supportées pour prévenir
le fléchissement. Les méthodes et les intervalles
de support doivent être spécifiés. Les instructions
doivent aussi indiquer les renseignements suivants:
les chaudières de catégories I, II et IV doivent
présenter des tronçons horizontaux dont la pente
montante est d'au moins ¼ po par pied (21 mm/m)
entre la chaudière et l'évent; les chaudières de
catégories II et IV doivent être installées de façon à
empêcher l'accumulation de condensat;
et si nécessaire, les chaudières de catégories II et IV
doivent être pourvues de dispositifs d'évacuation du
condensat.
Page 20
SECTION 4. Installation
4.4 Venting (Exhaust)
NOTICE
DO NOT COMMON VENT FT UNITS.FT units are
never permitted to share a vent with Category I
appliances.
The flue temperature of the FT changes dramatically
with changes in operating water temperature.
Therefore, it is necessary to assess the application
of the boiler to determine the required certified vent
class. If the FT is installed in an application where
the ambient temperature is elevated, and/or installed
in a closet/alcove, CPVC, polypropylene, or stainless
steel material is required. If the system temperatures
are unknown at the time of installation, stainless,
polypropylene or CPVC material is recommended.
The FT is a Category IV appliance and may be installed
with PVC, CPVC or polypropylene that complies with
ULC-S636, ANSI/ASTM D1785 F441 (see Table 3) or
a stainless steel venting system that complies with UL
1738 Standard and ULC S636.
WARNING
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenolsulfone) in venting
systems shall be prohibited.
WARNING
Failure to use the appropriate vent material, installation
techniques, glues/sealants could lead to vent failure
causing property damage, personal injury or death.
WARNING
All venting must be installed according to this manual
and any other applicable local codes, including but not
limited to, ANSI Z224.1/NFPA 54, CAN/CSA B149.1
and ULC-S636. Failure to follow this manual and
applicable codes may lead to property damage, severe
injury, or death.
AVIS
NE PAS ÉVENT COMMUNE FT UNITÉS. FT unités
ne sont jamais autorisés à partager un évent
Catégorie I avec les appareils.
WARNING
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenolsulfone) in non-metallic
venting systems is prohibited and that covering nonmetallic vent pipe and fittings with thermal insulation is
prohibited.
__________________________________________
INSTALLATIONS IN CANADA require the use of
venting material certified to ULCS636. All Gas
vents connected to the FT, plastic, stainless
steel or otherwise must be certified to this ULC
standard. Appropriate selection of vent material is
very important for proper performance and safe
operation of the FT.
The flue temperature of the FT changes
dramatically with changes in operating water
temperature. Therefore, it is necessary to assess
the application of the boiler to determine the
required certified vent class. If the FT is installed in
an application where the outlet water temperature
exceeds 145°F, and/or installed in a closet, class
IIB or higher vent material is required. If the
system temperatures are unknown at the time of
installation, class IIB or higher venting material is
recommended.
IN CANADA all venting used must meet the
following requirements:
1.
ULC-S636 certified and marked
2.
The first 3 feet of venting must be accessible
for visual inspection.
3.
All components used in the vent system must
be from a certified manufacturer.
4 . Vent system components must not be mixed
with alternate manufacturers certified
___________________________________________
VENTING INSTALLATION STANDARDS
MATERIAL
Stainless Steel
PVC, sch 40
CPVC, sch 40
Polypropylene
Table 3.
UNITED STATES
UL 1738
ANSI/ASTM D1785
ANSI/ASTM F441
UL1738 or ULC-S636
Required Exhaust Vent Material.
CANADA
Venting must be ULC-S636 certified for use as
venting material. The venting material must be chosen
based upon the intended application of the boiler.
Page 21
The FT Series Floor Standing, Combination Boiler
components and/or unlisted components.
5 . The venting must be installed according
to the vent manufacturers installation
instructions.
The unit’s vent can terminate through the roof, or
through an outside wall.
Vent pipe must pitch upward, toward the vent
terminal, not less than 1/4” per foot, so that
condensate will run back to the FT to drain. Route
vent pipe to the heater as directly as possible.
Seal all joints and provide adequate hangers as
required in the venting system manufacturer’s
Installation Instructions. Horizontal portions of
the venting system must be supported to prevent
sagging and may not have any low sections that
could trap condensate. The unit must not support
the weight of the vent pipe.
WARNING
Failure to vent this Boiler in accordance with
these instructions could cause a fire, resulting
in severe property damage, personal injury or
death.
Do not interchange vent systems or materials
unless it is specified.
The use of thermal insulation covering pipe and
fittings is prohibited.
Do not apply an electric damper, draft hood or
vent damper with this Boiler.
Do not locate vent termination where exposed
to prevailing winds. Moisture and ice may fall
on surface around vent termination. To prevent
deterioration, surface must be in good repair
(sealed, painted, etc.).
4.5 General Location Guideline
1.Vent system installation must be in accordance
with Local codes or, in the absence of local codes,
the National Fuel Gas Code, ANSI Z224.1 /NFPA
54 and/or CSA B149.1, Natural Gas and Propane
Installation Code.
2.The Boiler is designed to be installed as a Direct
Vent (sealed combustion) type. The air for
combustion must be supplied directly from the
outside to the burner. Also, the flue gases must be
vented directly to the outdoors (through wall or roof).
3.Do not install venting system components on the
exterior of building except as specifically required by
these instructions
-Vent terminals must be at least 1 foot from any door,
window, or gravity inlet into the building.
-Maintain the correct clearance and orientation
between the vent and air intake terminals.
The vent and air intake terminals must be at the
same height and their center lines must be spaced
apart 12˝ minimum.
-The bottom of the vent and air intake terminal must
be at least 12˝ above the normal snow line. In no
case should they be less than 12˝ above grade
level.
-Do not install the vent terminal directly over
windows or doors.
-Air intake terminal must not terminate in areas that
might contain combustion air contaminates, such
as near swimming pools.
-For sidewall venting, the minimum horizontal
distance between any adjacent individual Module
(Boiler) vent terminations is twelve (12) inches. It
is better to be far more than 12 inches for avoiding
frost damage to building surfaces where vent
terminations are placed.
-The minimum horizontal distance between any
adjacent individual module (boiler) roof vent
endpiece is one (1) foot.
Page 22
SECTION 4. Installation
4.6 Locations for Vent Pipe Terminator
*For clearances not specified in ANSI Z224.1 / NFPA 54 or CAN/CSA-B 149.1, please use clearances in
accordance with local installation codes and the requirement of the gas supplier.
4.6.1 Direct Venting Clearances
Description
US Direct Vent Instal- Canadian Direct Vent
lations
Installations
A
Clearance above grade, veranda, porch, deck, or balcony
12 in (30 cm)
12 in (30 cm)
B
Clearance to window or door that may be opening
12 in (30 cm)
36 in (91 cm)
C
Clearance to permanently closed window
*
*
D
Vertical clearance to ventilated soffit located above the terminal
within
a horizontal distance of 2 feet from the center line of the terminal
*
*
E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
*
*
G
Clearance to inside corner
*
*
H
Clearance to each side of center line extended above meter/
regulator assembly
*
3 ft (91 cm) within a
height 15 ft (457 cm)
above the meter/
regulator assembly
I
Clearance to service regulator vent outlet
*
3 ft (91 cm)
J
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance
12 in (30 cm)
36 in (91 cm)
K
Clearance to a mechanical air supply inlet
3 ft (91 cm) above if
within 10 ft (3 m) horizontally
6 ft (1.83 m)
L
Clearance above paved sidewalk or paved driveway located on
public property
*
7 ft (2.13 m)
M
Clearance under veranda, porch, deck, or balcony
*
12 in (30 cm)
Table 4.
Direct Vent Clearances
Page 23
The FT Series Floor Standing, Combination Boiler
4.6.2 Non-Direct Venting (Single Pipe) Clearances
Description
A
US Non-Direct
Canadian Non-Direct
Clearance above grade, veranda, porch, deck, or balcony
12 in (30 cm)
12 in (30 cm)
B
Clearance to window or door that may be opening
48 in (120 cm) below
or to side of opening;
12 in (30 cm) above
opening
36 in (91 cm)
C
Clearance to permanently closed window
*
*
D
Vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 2 feet from the center line of the
terminal
*
*
E
Clearance to unventilated soffit
*
*
F
Clearance to outside corner
*
*
G
Clearance to inside corner
*
*
H
Clearance to each side of center line extended above meter/
regulator assembly
*
36 in (91 cm) within a
height 15 ft (4.57 m)
above the meter/ regulator assembly
I
Clearance to service regulator vent outlet
*
36 in (91 cm)
J
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other appliance
48 in (120 cm) below
or to side of opening;
12 in (30 cm) above
opening
36 in (91 cm)
K
Clearance to a mechanical air supply inlet
36 in (91 cm) above
if within 10 ft (3 m)
horizontally
6 ft (1.83 m)
L
Clearance above paved sidewalk or paved driveway located on
public property
*
7 ft (2.13 m)
M
Clearance under veranda, porch, deck, or balcony
*
12 in (30 cm)
Table 5.
Non-Direct Vent Clearances
Page 24
SECTION 4. Installation
4.6.3 V
enting Requirements in the
Commonwealth of Massachusetts
In Massachusetts the following items are required if
the side-wall exhaust vent termination is less than
seven (7) feet above finished grade in the area
of the venting, including but not limited to decks
and porches. From Massachusetts Rules and
regulations 248 CMR 5.08
1.
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall
vented gas fueled appliance, the installing plumber
or gasfitter shall observe that a hard-wired carbon
monoxide detector with an alarm battery back-up is
installed on the floor level where the gas appliance
is to be installed. In addition, the installing plumber
or gasfitter shall observe that a battery operated or
hard-wired carbon monoxide detector with an alarm
is installed on each additional level of the dwelling,
building or structure served by the side-wall
horizontally vented gas fueled equipment. It shall
be the responsibility of the property owner to secure
the services of qualified licensed professionals
for installation of hard-wired carbon monoxide
detectors.
a. In the event that the side-wall horizontally
vented gas fueled equipment is installed in a crawl
space or an attic, the hard-wired carbon monoxide
with alarm and battery back-up may be installed on
the next adjacent floor level.
b. In the event that the requirements of the
subdivision cannot be met at the time of completion
of installation, the owner shall have a period of thirty
(30) days to comply with the above requirements,
provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector
with an alarm be installed.
2.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply
with NFPA 720 and be ANSI/UL 2034 listed and IAS
certified.
3. Signage. A metal or plastic identification plate
shall be permanently mounted to the exterior of
the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in
print no less than one-half (1/2) inch in size: “GAS
VENT DIRECTLY BELOW, KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. Inspection The state or local gas inspector of
the side-wall horizontally vented gas fueled appliance
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a) 1-4.
Page 25
The FT Series Floor Standing, Combination Boiler
NOTICE
DO NOT COMMON VENT FT UNITS.FT units are
never permitted to share a vent with Category I
appliances.
AVIS
NE PAS ÉVENT COMMUNE FT UNITÉS. FT unités
ne sont jamais autorisés à partager un évent
Catégorie I avec les appareils.
Common Vent Test
NOTE: This section does not describe a method for
common venting FT units. It describes what must
be done when an existing unit is removed from a
common vent system.
NOTICE
At the time of removal of an existing boiler, the following steps
shall be followed with each appliance remaining connected to
the common venting system placed in operation, while the other
appliances remaining connected to the common venting system
are not in operation.
1. Seal any Not Used openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances
remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the common
venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at
maximum speed.
4. Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so the appliance will
operate continuously.
5. Operate the main burner for 5 minutes then, determine if the
cut-draw overflows to the discharge opening. Use the flame
of a match or a candle or the smoke of a cigarette, a cigar or
a pipe
6. Once it has been determined, according to the method
indicated above, that each device connected to the drainage
system is placed in the open air in an adequate manner.
Install the doors and windows, fans, the registers of chimneys
and gas appliances to their original position
7. Any malfunction of the venting system should be corrected so
that the installation conforms to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and (or) the installation codes CAN/
CSA-B149.1. If the size of a section of the evacuation system
must be changed, the system should be modified to comply
with the minimum values of the relevant tables of appendix F
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and
(or) the installation codes CAN/CSA-B149.1
AVIS
Au moment du retrait d'une chaudière existante, les mesures
suivantes doivent être prises pour chaque appareil toujours raccordé
au système d'évacuation commun et qui fonctionne alors que
d'autres appareils toujours raccordés au système d'évacuation ne
fonctionnent pas:
1. Sceller toutes les ouvertures non utilisées du système
d'évacuation.
2. Inspecter de façon visuelle le système d'évacuation pour
déterminer la grosseur et l'inclinaison horizontale qui conviennent
et s'assurer que le système est exempt d'obstruction,
d'étranglement, de fuite, de corrosion et autres défaillances qui
pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les portes et les
fenêtres du bâtiment et toutes les portes entre l'espace où les
appareils toujours raccordés au système d'évacuation sont
installés et les autres espaces du bâtiment. Mettre en marche
les sécheuses, tous les appareils non raccordés au système
d'évacuation commun et tous les ventilateurs d'extraction comme
les hottes de cuisinière et les ventilateurs des salles de bain.
S'assurer que ces ventilateurs fonctionnent à la vitesse maximale.
Ne pas faire fonctionner les ventilateurs d'été. Fermer les registres
des cheminées.
4. Mettre l'appareil inspecté en marche. Suivre les instructions
d'allumage. Régler le thermostat de façon que l'appareil fonctionne
de façon continue.
5. Faire fonctionner le brûleur principal pendant 5 min ensuite,
déterminer si le coupe-tirage déborde à l'ouverture de décharge.
Utiliser la flamme d'une allumette ou d'une chandelle ou la fumée
d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode indiquée cidessus, que chaque appareil raccordé au système d'évacuation
est mis à l'air libre de façon adéquate. Remettre les portes et
les fenêtres, les ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.
7. Tout mauvais fonctionnement du système d'évacuation commun
devrait être corrigé de façon que l'installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d'installation CAN/CSA-B149.1. Si la grosseur d'une section
du système d'évacuation doit être modifiée, le système devrait
être modifié pour respecter les valeurs minimales des tableaux
pertinents de l'appendice F du National Fuel Gas Code, ANSI
Z223.1/NFPA 54 et (ou) les codes d'installation CAN/CSA-B149.1
Page 26
SECTION 4. Installation
4.7 Air Supply and Vent Connections at the Appliance
Combination Boiler Model
FTCF140/199
Table 6.
3˝ Combustion Air / Vent Pipe
2˝ Combustion Air / Vent Pipe
Max
Elbow Max
Max
100´ (30M)
6
50´ (15M )
*
Elbow Max
*
4
Maximum Vent / Air Pipe Lengths for either 3” or 2 “ Pipes
*Propane models are limited to 25 equivalent feet of 2” vent
NOTE : For additional elbows, reduce maximum allowable length
• 5 feet (1.5M) for each additional 3-inch 90-degree elbow
• 2.5 feet (0.75M) for each additional 3-inch 45-degree elbow
• 8 feet (2.4M) for each additional 2-inch 90-degree elbow
• 4 feet (1.2M) for each additional 2-inch 45-degree elbow
• The thickness of the wall vents installed : Min 4˝ ~ Max 20˝
NOTE: When using a 2” vent pipe, DIP Switch 4 must be in the OFF position.
For 3” Pipe vent, the default setting for DIP 4 is ON.
Refer to Section 4.19
4.7.2 Direct Venting
The boiler uses 3˝ or 2˝ diameter exhaust
and 3˝ or 2˝diameter intake air ducts. To
ensure the draw of air directly from and
exhaust of air directly to the outside of the
building, create an airtight seal from the
boiler collar to the vent termination.
(For installations in Canada) field-supplied
plastic vent piping must comply with CAN/
CSA B149.1 (latest edition) and be certified
by the Standard For Type BH Gas Venting
Systems, ULC-S636. Components of this
listed system must not be interchanged
with other vent systems or unlisted pipes or
fittings. All plastic components and specified
primers and glues of the certified vent system
must be from a single system manufacturer
and must not be intermixed with another
system manufacturer’s parts.
Tightening — Boiler Collar (Socket) to
Vent Pipe & Inlet Pipe
-Clean and dry your selected PVC, CPVC
vent pipe and boiler collar (socket).
-You can select to the size of vent pipe(2˝ &
3˝), according to the installation conditions.
-Push the pipe into the collar (socket) until
it touches the bottom of the socket fitting.
-For 2” installations, install using the
supplied 3” to 2” adaptor. Adaptor must be
installed in vertical section of piping only.
3” pipe
Shown is the FTCF140. The
inlet and outlet are reversed
on the FTCF199.
2” pipe connected, using an adapter
3” to 2”
adapter
is NOT
included.
The FT Series Floor Standing, Combination Boiler
Page 27
4.7.3 Indoor Combustion Air
Read and Follow Sections 4.3 Guidelines First.
Shown is the FTCF140. The
inlet and outlet are reversed
on the FTCF199.
1. Insert the termination end cap into the intake air duct.
2. Provide two openings to allow for circulation of
combustion air as specified by ANSI Z224.1/NFPA 54.
In Canada refer to CAN/CSA B-149.1
Model
FTCF140
FTCF140
Maximum Input (BTU/H)
140,000
199,000
Indoor make up air is provided, a
minimum free area of 1 in2 per
1,000 BTU/H
140 in2 13 1/4"
199 in2 13 1/4"
(W) x 13 1/4" (H) (W) x 13 1/4" (H)
NOTE: The FT needs fresh air for safe operation and
must be installed so there are provisions for
adequate combustion and ventilation air.
4.8 Vent / Air Pipe Termination
Note : For using pipe more than 1 elbow,
reduce maximum allowable length
• 5 feet (1.5M) for each additional 3-inch
90-degree elbow
• 2.5 feet (0.75M) for each additional 3-inch
45-degree elbow
• 8 feet (2.4M) for each additional 2-inch
90-degree elbow
• 4 feet (1.2M) for each additional 2-inch
45-degree elbow
• The thickness of the wall vents installed : Min
4˝ ~ Max 20˝
Horizontal Vent Termination
• Direct Vent - Sidewall Terminations
Vent Termination
1. Rodent Screen Installation
• Install Rodent Screen and Vent Terminal
(additional purchase), see Figure for appropriate
configuration.
• After connecting vent/air inlet terminal, it is
required to install screen for the terminal to
prevent incoming of rodent, which might cause
damage to the unit. (Extra purchase accessory
2/3˝ screen vent 1/4˝ mesh)
Page 28
SECTION 4. Installation
4.8 Vent Pipe Termination (cont)
Horizontal Vent Termination (cont)
•Direct Vent - Optional Sidewall
Snorkel Terminations
Vertical Vent Termination
• Direct Vent - Vertical Terminations
with Sloped Roof
Concentric Vent Termination
•Direct Vent - Optional Horizontal
and Vertical Concentric Vent
Side wall Vent
(2"or 3")
Roof Vent
(2"or 3")
Side wall Vent
(2"or 3")
Page 29
The FT Series Floor Standing, Combination Boiler
4.9
Gas Supply and Piping
Gas piping should be supported by suitable hangers or
floor stands, not the appliance.
Review the following instructions before proceeding with
the installation.
1.Verify that the appliance is fitted for the proper type
of gas by checking the rating plate. FT will function
properly at elevations up to 10,000 feet
(3050 m). Refer to Section 4.12 for High Altitude
Settings.
2.The maximum inlet gas pressure must not exceed
13" W.C. (3.2kPa). The minimum inlet gas pressure
is 3.5" W.C. (1.0kPa).
WARNING:
Open flame can cause gas to ignite and result in
property damage, severe injury, or loss of life.
NOTE: The FT appliance and all other gas appliances
sharing the gas supply line must be firing at maximum
capacity to properly measure the inlet supply pressure.
The pressure can be measured at the supply pressure
port on the gas valve. Low gas pressure could be an
indication of an undersized gas meter, undersized gas
supply lines and/or an obstructed gas supply line.
3.Refer to Table 7, Table 8, and Table 9 to size piping.
4.Run gas supply line in accordance with all
applicable codes.
5.Locate and install manual shutoff valves in
accordance with state and local requirements.
6.A sediment trap must be provided upstream of the
gas controls.
7.All threaded joints should be coated with piping
compound resistant to action of liquefied petroleum
gas.
8.The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG (3.45kPa).
9.The unit must be isolated from the gas supply
system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2
PSIG (3.45kPa).
10.The appliance and its gas connection must be leak
tested before placing it in operation.
11. Purge all air from gas lines.
CAUTION
PRV (included) must be installed immediately at the
top of boiler outlet to PRV, with no valves between.
Refer to Section 4.15
__________________________________________
ATTENTION
PRV (inclus) doit être installé immédiatement en haut
de la chaudière sortie de PRV, sans les vannes entre.
Se reporter à la Section 4.15
__________________________________________
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
UNDILUTED PROPANE
NOMINAL PIPE SIZE @ 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP
SIZE
LENGTH
HOUR
1/2"
3/4"
1"
MAXIMUM CAPACITY IN THOUSANDS OF BTU PER
20
200
418
787
40
137
287
541
60
-
231
434
80
-
197
372
100
-
175
330
NOTES: 1. Follow all local and national propane gas codes for line sizing and
equipment requirements. 2. Verify that inlet gas pressure remains between
4 and 13 inches of water column before and during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.
Table 7.
Nominal Pipe Size, Propane
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS
NOMINAL PIPE SIZE @ 0.30" W.C. PRESSURE DROP
LENGTH
FT
3/4"
1"
CUBIC FEET OF GAS PER HOUR
20
190
350
40
130
245
60
105
195
80
90
170
100
Table 8.
Nominal Pipe Size, Natural Gas
EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS
NOMINAL PIPE SIZE
FITTING
90° ELBOW
TEE
Table 9.
1/2"
3/4"
1"
3.6
4.4
5.2
4.2
5.3
6.6
LINEAR FEET
Equivalent Pipe Lengths
Page 30
SECTION 4. Installation
4.9 Gas Supply and Piping
The gas connection fitting on the unit is
1/2”(FTCF140) or 3/4”(FTCF199) female NPT.
The supply line must be sized for the maximum
output of the combination boiler model being
installed. If there are additional gas appliances
from the main supply line, you must measure
sizes of the supply line according to the
COMBINED total maximum BTUH draw for the
appliances as if they were all operating at the
same time.
Measure the length of the gas supply line from
the gas meter to the Combination boiler.
Use the tables in this manual or refer to the gas
line manufacturers sizing information to determine
the correct supply pipe size.
The gas shut-off valve in the gas supply line
should be installed close to the unit.
To facilitate any future maintenance, it is also
recommended that an approved gas union fitting
be installed in the supply line between the shut-off
valve and the 3/4” female NPT connection on the
Combination boiler.
1)Install an approved gas line pipe to gas line
connection to the combination boiler.
Include manual shut off valve and gas union
connection, as shown.
2)Test gas pressure to make sure it meets the
minimum standards and does not exceed .the
maximum standards for the combination boiler.
3)Leak test the gas line pipe before placing the
unit in operation. Use approved leak detector
liquid solutions only to check for leaks.
Do not operate the combination boiler until all
connections have been completed and the heat
exchanger is filled with water.
FTCF140
Closed Position
Manual Shut-Off Valve
Gas Pipe (1/2")
FTCF199
Closed Position
Gas Pipe (3/4")
Manual Shut-Off Valve
Page 31
The FT Series Floor Standing, Combination Boiler
4.9 Gas Supply and Piping
AUTODESK � � � � � � � � � �
Combination boiler must be installed downstream of the gas meter for adequate gas supply.
Combination boiler gas connection pipe not less than a 1/2” (FTCF140) or 3/4” (FTCF199).
Suggested Natural Gas (NG) Layout
AUTODESK � � � � � � � � � �
AUTODESK � � � � � � � � � �
Capacity : Not less than 'total capacity of connected appliances'
G
Gas meter
Other appliance
AUTODESK � � � � � � � � � �
Sediment Trap
Suggested Propane Gas (LP) Layout
Gas Regulator (21bar)
Gas Regulator (supply press 12")
LP GAS TANK
Other appliance
Sediment Trap
AUTODESK � � � � � � � � � �
AUTODESK � � � � � � � � � �
AUTODESK � � � � � � � � � �
1/2" pipe
3/4"
AUTODESK � � � � � � � � � �
Capacity : not less than 'total capacity of connected appliances'
Page 32
SECTION 4. Installation
4.10 Gas Supply Pressure
The minimum and maximum inlet gas line pressures must be
LP Gas
Natural Gas
Maximum Pressure
13.0" WC
Maximum Pressure
10.5" WC
Minimum Pressure
8.0" WC
Minimum Pressure
3.5" WC
CAUTION
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Loosen the pressure port bolts before you check the gas inlet pressure.
FTCF199
FTCF140
Inlet Gas Pressure Port
4.11 Gas Setup and Adjustment
For the Step by step process to measure CO2 values on the FT, please refer to Section 4.13 of
this Installation Manual. Step 11 thru Step 23 will guide you on how to combustion test your FT
The FT Series Floor Standing, Combination Boiler
4.12 High Altitude Installations. 2,000’ to 10,000’
The FT is shipped with a default factory setting for installation at an
altitude of 0 to 2000’ (approx). For maximum efficiencies at higher
altitudes (2,000’ to 10,000’), the FT does have an adjustment in the
Installer Parameters Mode.
Follow these instructions if your installation is at 2,000’ - 10,000’.
1. With the Power
turned OFF, press the 'Modes
button'
for 5 seconds to get into the Installer
Parameters Mode.
2. Turn the dial (E) until ‘28:HA’ appears.
3. Press the dial (E).
4. Set the high altitude value by turning the dial.
Refer to table.
#
Altitude of Installation
0
0~1999 ft (0~609 m)
1
2,000~4,499 ft (610~1,645 m)
2
4,500~7,699 ft (1,646~2,346 m)
4
7,700~10,000 ft (2,347~3,048 m)
5. Press the dial again (E) to save the setting.
6. Press the ‘Modes button’
for one second, to
Save the number and to go back to initial status.
Page 33
Page 34
SECTION 4. Installation
The Natural
FT Series,
Gas Conversion
Kit #4290
4.13
Gas Floor-Standing,
to Propane Conversion
Kit Document
Kit # R20771
Document 4290B
Top Access Panel
Front Panel Knob
The FT Series, floor standing, condensing boiler is configured
for Natural Gas (NG) from the factory. A Natural Gas to Propane
Front Panel
Conversion Kit is included with every FT. The gas conversion kit will
show you how to convert your FT boiler to propane gas. If your FT
does not have the bag containing the conversion kit, a replacement kit can be
obtained. Contact the manufacturer and request a replacement conversion kit.
NOTICE
If your installation altitude is greater than 2000 ft, please check that the ‘High Altitude’
Installer Setting has been adjusted to suit your installation altitude. Refer to Section
4.12 of the Installation and Operation Instructions (Document 1320).
WARNING
This gas conversion kit shall be installed by a qualified service
agency in accordance with the manufacturer’s instructions and
all applicable codes and requirements of the authority having
jurisdiction. The information in these instructions must be
followed to minimize the risk of fire or explosion or to prevent
property damage, personal injury or death. The qualified service
agency is responsible for the proper installation of this kit. The
installation is not proper and complete until the operation of the
converted appliance is checked as specified in the manufacturer’s
instructions supplied with the kit.
Installation must conform to local codes and the latest edition
of the National Fuel Gas Code, ANSI Z223.1 and CAN-B149.1.
Failure to follow instructions could result in serious injury or
property damage.
The qualified agency performing this work assumes
responsibility for gas conversion.
Steps 1 thru 26
To convert from Natural Gas to Propane Gas
1.
2.
CAUTION
Turn OFF the FT.
The ON / OFF button is
located at the bottom left of the Control Display.
Turn OFF the GAS and WATER supply to the
FT (valves are located on the plumbing pipes.)
Natural Gas
(NG) Part #
Propane Gas
(LP) Part #
FTCF140
FT1722
FT1722P
FTCF199
FT1780
FT1802
Orifice
Table A
H2373900B
WARNING
This conversion shall be installed by a qualified service
agency in accordance with the manufacturer's instructions
and all applicable codes and requirements of the authority
having jurisdiction. If the information in these instructions
is not followed exactly, a fire, an explosion or production
of carbon monoxide may result causing property damage,
personal injury or loss of life. The qualified service agency is
responsible for the proper and complete installation of this kit.
The installation is not proper and complete until the operation
of the converted appliance is checked as specified in the
manufacturer's instruction supplied with the kit.
Nozzle
AVERTISSEMENT
Ce conversion doit être installé par un organisme de service
conformément aux instructions du fabricant et tous les
codes et les exigences de l’autorité compétente. Si les
informations contenues dans ces instructions n’est pas suivi
à la lettre, un incendie, une explosion ou de la production de
monoxyde de carbone mais résultat causant des dommages
matériels, des blessures ou des pertes de vie. Le service est
responsable pour la bonne et complète l’installation de ce kit.
L’installation n’est pas correcte et complète jusqu’à ce que
le fonctionnement de l’appareil converti est vérifiée comme
spécifié dans le manuel d’instruction fourni avec le kit.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 1 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
.18
This combination boiler has already been set to burn
natural gas, but can be converted to burn LP gas. Before
placing the combination boiler into operation, verify that
your fuel source is natural gas. Or verify that your fuel
source is propane if you are converting this combination
unit to propane.
Figure A
ON / OFF
Page 35
The FT Series Floor Standing, Combination Boiler
The FT Series, Floor-Standing, Gas Conversion Kit
3.
4.
5.
Document 4290B
Using a Phillips screwdriver, remove the 4 screws on the Top Access Panel, and then lift out the Top Access Panel.
Unthread the Front Panel Knob at the top of the front panel and then remove the entire panel. See Figure A.
With the internal components exposed, locate the gas inlet pipe of your model. See Figure B.
FTCF199
FTCF140
GAS INLET PIPE
GAS VALVE
Figure B
GAS VALVE
GAS INLET PIPE
6.
Loosen the hex-nuts on the Gas Inlet Pipe and remove the nozzle or orifice (See Figure C). Save the Packing
for re-use with the replacement Gas Orifice.
FTCF199
FTCF140
NOZZLE
PACKING
ORIFICE
Figure C
7.
PACKING
Remove the existing natural gas nozzle or orifice. If your unit is a FTCF199, note that the conical end of the orifice
is towards the valve. Save the packing for re-use. See Figure C.
Replace the old Nozzle (or Orifice) with the new one for LP (propane). Re-use the packing from previous.
8.
9. Return the Gas Inlet Pipe to its original position and tighten the Brass Fittings.
10. Per Table B, set DIP Switch 5 to the ‘OFF’ setting (the #5 DIP switch setting for LP Propane is the OFF side).
11. Turn ON the GAS and WATER supply to the FT.
12. Turn ON the FT.
13. Connect a manometer to the Manifold Pressure Port. See Figure E. For dual port manometers, use the
14.
positive pressure side. Check for proper manifold gas pressure. Refer to Table C on next page.
Establish a call for heat. You may need to disconnect the outdoor reset if you are making this gas conversion
during warm weather.
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 2 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Page 36
SECTION
4. Installation
The FT Series,
Floor-Standing, Gas Conversion Kit
Document 4290B
4.13 Natural Gas to Propane Conversion
ON
OFF
MIN Fire
Normal Operation
MAX Fire
Normal Operation
NG Natural
LP Propane
3” Vent Size
2” Vent Size
ON
E
REF
MBH
R
CE
ENON
OFF
OFF
ON
N/A
140
Y.
ONL
OFF
ON
DO
OFF
OT
NON
N/A
ON
GE
N
A
C H ON
ON
199
Table B DIP Switch Settings
15.
Setup your combustion analyser and place the sensor
into the combustion test port
16.
Per Table B for Max Fire, change dip switch 6 to ON and 7 to OFF.
The unit will cycle up to MAX fire.
17.
WAIT for your combustion analyser to stabilize. This may take up to 3 minutes depending on your combustion
18.
19.
Figure D
analyser. Then check the CO2 measurement for MAX fire. Refer to Table D for acceptable MAX fire
combustion readings. At this point, just record the CO2 readings at MAX Fire. Do NOT attempt to adjust
CO2 at MAX Fire. ONLY in MIN Fire, so...
Per Table B for MIN Fire, change dip switch 6 to OFF and 7 to ON. The unit will cycle down to MIN Fire.
WAIT for your combustion analyser to stabilize. Then check the CO2 measurement at MIN fire. Refer to
Table D for acceptable MIN fire combustion readings.
20.
If CO2 readings in Max Fire and MIN fire are acceptable, then skip ahead to Step 23. If not, then open the
21.
Gas Valve Adjustment Port by removing the cap screw with a 4mm Allen wrench. See Figure E.
Then use the 4 mm Allen wrench to make a minor adjustment (1/8 turn) to either increase or decrease CO2.
Manifold pressure
FTCF140
FTCF199
‘NG’ type combustibility
‘LP’ type combustibility
2" VENT
3" VENT
2" VENT
3" VENT
MAX Fire
-0.15" WC
-0.216" WC
-0.15" WC
-0.216" WC
MIN Fire
0” WC
0.002” WC
0.1” WC
0.079” WC
MAX Fire
-0.134” WC
-0.173” WC
MIN Fire
-0.015” WC
-0.015” WC
‘NG’ type combustibility
‘LP’ type combustibility
Table C
CO2 value
FTCF140
FTCF199
Table D
2" VENT
3" VENT
2" VENT
3" VENT
MAX Fire
8.5~10.5%
9.5~11 %
MIN Fire
8~10%
9~10.5 %
MAX Fire
8.5~10.0%
9.5~11 %
800.900.9276
• Fax 800.559.1583 (Customer
Service,
8~10%
9~10.5
% Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 3 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
MIN Fire
www.Laars.com
Page 37
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
The FT Series, Floor-Standing, Gas Conversion Kit
Document 4290B
4.13 Natural Gas to Propane Conversion
FTCF199
FTCF140
-
Manifold
Pressure Port
Figure E
22.
+
+
Gas Valve
Adjustment Port
(under the cap
screw)
-
It may be necessary to go back and forth between HI Fire and LOW Fire several times (and making
adjustments ONLY at LOW Fire), before CO2 at both are within acceptable levels. Be sure to put the
cap screw back onto the gas valve adjustment port when done.
23. Once the CO2 and manifold pressure measurements for both MIN and MAX Fire are acceptable per
H2373900B
Table D, set DIP switches 6 and 7 to the OFF position for Nominal Fire (normal operation). The FT is
now operating in it’s normal mode.
24. Write in the correct Conversion Date and the Technicians Name to the included gas conversion sticker.
See Figure F. Then apply that sticker adjacent to the rating plate.
25. Remove your combustion analyser from the combustion test port and be sure to thread the test port plug
back into position.
26. Re-connect outdoor reset if it was disconnected previously in this conversion and put the Front Panel
and Top Access Panel back on. Tighten them into place using the knob and 4 fasteners that you
disassembled in Step 3.
This unit was converted on ____/____/___to _____gas
with kit #____________by______________________
(name and company __________________________
accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz
en utilisant le kit numéro _____
par______________
(nom et société_________________________________
responsable)___________________________________
_____________________________________________
Figure F (Conversion label)
800.900.9276 • Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 4 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com
Page 38
SECTION 4. Installation
4.14 Plumbing Guidelines
External Plumbing and Water Connection
Guidelines
-Ensure pipe material meets local codes and
industry standards.
-The pipe end must be clean and free of debris.
-Do not apply torch heat within 12˝ of the bottom
connections of the unit.
-The size of the DHW pipe should be 3/4˝
diameter and central heating water pipe should
be 1˝ diameter.
-Isolation valves(Shutoff valve) will be used.
-All piping should be insulated.
CAUTION
se at least the MINIMUM pipe size for the entire
U
boiler loop piping (connecting boiler to and from
the primary/secondary connection). Use only
primary/secondary piping as shown.
Failure to follow these guidelines could result in
system problems.
CH pipe minimum size : 1˝
DWH pipe minimum size : 3/4˝
Applicable Backflow Preventer
-Apply a backflow preventer valve in the DHW
supply inlet (water Inlet) to the unit as required by
local codes.
Isolation valve
Backflow preventer
Pressure relief valve
Closed type Expansion tank
-Apply 1" pipe to the expansion tank to allow air
within the system for exhausting.
-Pitch any horizontal piping up towards tank 1
inch per 5 feet of piping.
-DO NOT install automatic air vents on closed
type expansion tank systems. Air must remain
in the system and return to the tank to provide
its air cushion.
-DO NOT use a closed type expansion tank in a
system with the FT Combination Boiler. (Automatic air vent has been installed inside of the
boiler.)
-If the combination boiler is installed in a closed
water supply system, such as one having
a
Isolation valve
backflow preventer in the cold water supply line,
it will control thermal expansion. Backflow preventer
Pressure relief valve
Ball valve
CAUTION
Anti-scald rated
Mixing Valve
Scalding Risk: Manufacturer recommends
the use of a thermostatic mixing
valve at domestic hot water
outlet (boiler location) to
reduce potential for scalding.
Contact Manufacturer for
recommended models.
__________________________________________
Ball valve
Anti-scald rated
Mixing Valve
3/4" PIPE
(GAS INLET)
3/4" PIPE
(DHW
OUTLET)
3/4" PIPE
Backflow preventer (DHW INLET)
Page 39
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
4.14 Plumbing Guidelines
Diaphragm Type Expansion Tank
-The air in a diaphragm-type expansion tank is separated from the water by a flexible rubber membrane.
When the tank is installed in and connected to the piping of the system, water enters the other side of the
tank chamber and presses down on the diaphragm.
-You should always install an ‘Automatic Air Vent (Under figure ‘A’)’ on the top of the air separator to remove
residual air from the system.
- Automatic air vent has been installed on the inside of the FT combination boiler.
- The installation of additional air vent is optional.
-If the combination boiler is installed in a closed water supply system, such as one having a backflow
preventer in the cold water supply line, it will control thermal expansion.
- Pump for primary loop is included with FT for < 15 ft.
CAUTION
PRV
Scalding Risk: Manufacturer recommends
the use of a thermostatic mixing
valve at domestic hot water
outlet (boiler location) to
reduce potential for scalding.
Contact Manufacturer for
recommended models.
1" PIPE
(CH SUPPLY)
3/4" PIPE
Expansion tank
(Closed type)
(DHW
OUTLET)
Air separator
__________________________________________
Circulation pump
Backflow
preventer
Check valve
3/4" PIPE
(DHW INLET)
Pressure relief valve
EXPANSION TANK
Ball valve
Isolation valve
Anti-scald rated
Mixing Valve
1" PIPE < 15 ft
(CH RETURN)
PRIMARY LOOP
(SPACE HEATING)
Do not exceed 12" apart
PRIMARY/SECONDARY
CONNECTION
SECONDARY LOOP (SPACE HEATING)
CAUTION
PRV (included) must be installed immediately at the
top of boiler outlet to PRV, with no valves between.
Refer to Section 4.15
__________________________________________
ATTENTION
PRV (inclus) doit être installé immédiatement en haut
de la chaudière sortie de PRV, sans les vannes entre.
Se reporter à la Section 4.15
__________________________________________
Page 40
SECTION 4. Installation
4.14 Plumbing Guidelines
Zoning with Circulation Pump
-Each heating zone of a pump based system has its own circulator pump which runs when the zone needs it.
- Each zone thermostat goes to a controller which controls the pumps.
Isolation valve
1" PIPE
(CH SUPPLY)
Backflow preventer
Pressure relief valve
3/4" PIPE
(DHW
OUTLET)
Ball valve
Anti-scald rated
Mixing Valve
Backflow
preventer
3/4" PIPE
(DHW INLET)
EXPANSION TANK
1" PIPE
(CH RETURN)
< 15 ft
PRIMARY LOOP
(SPACE HEATING)
Do not exceed 12" apart
ZONE 1
ZONE 2
ZONE 3
FLOOR HEATING
SECONDARY LOOP (SPACE HEATING)
Page 41
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
4.14 Plumbing Guidelines
Zoning with Zone Valve
-In a valve based system, there is one circulator pump at the boiler and each heating zone has a zone
valve which opens when the zone.
-Each thermostat is wired directly to the corresponding zone valve. Contacts in the zone valves provide a
proper signal to the boiler when the valve is opened.
CAUTION
1" PIPE
(CH SUPPLY)
Scalding Risk: Manufacturer recommends
the use of a thermostatic mixing
valve at domestic hot water
outlet (boiler location) to
reduce potential for scalding.
Contact Manufacturer for
recommended models.
3/4" PIPE
(DHW
OUTLET)
__________________________________________
Backflow
preventer
3/4" PIPE
(DHW INLET)
EXPANSION TANK
1" PIPE
(CH RETURN)
< 15 ft
PRIMARY LOOP
(SPACE HEATING)
PRIMARY/SECONDARY
CONNECTION
Do not exceed 12" apart
SECONDARY LOOP (SPACE HEATING)
ZONE 1
ZONE 2
ZONE 3
FLOOR HEATING
CAUTION
PRV (included) must be installed immediately at the
top of boiler outlet to PRV, with no valves between.
Refer to Section 4.15
__________________________________________
ATTENTION
PRV (inclus) doit être installé immédiatement en haut
de la chaudière sortie de PRV, sans les vannes entre.
Se reporter à la Section 4.15
__________________________________________
Page 42
SECTION 4. Installation
4.15 Pressure Relief Valves
External pressure relief valves must be installed.
Observe the following. Failure to comply with the
guidelines on installing the pressure relief valve and
discharge piping can result in personal injury, death
or substantial property damage.
WARNING
Do not operate this combination boiler before
installing a Pressure Relief Valve (PRV) that
is rated in accordance with the ASME Rating
Plate on the boiler.
This hot water boiler is provided with 30 psi safety relief
valve that complies with the ANSI/ASME Boiler and
Pressure Vessel Code, Section IV (“Heating Boilers).
(Model : CASE ACME F-82)
This safety relief valve (30 psi) is shipped loose for field
installation.
An approved ASME HV Pressure Relief Valve must be
installed on the DHW supply line as close to the unit
as possible. Valve size 3/4”, maximum 150 psi. Not
included with boiler.
For safety, the relief valve(s) must be installed into it’s
designed location and not be removed or plugged.
Failure to comply with the guidelines on installing the
pressure relief valves and discharge piping can result in
personal injury, death or substantial property damage.
Direct the discharge piping of the pressure relief valve
so that hot water will not splash on anyone or any
nearby equipment. Attach the discharge line to the
pressure relief valve and run the end of the line within
6-12″ (150-300mm) of the floor.
3/4" 30psi
Relief Valve
3/4" 150psi
Relief Valve
Shown is the model 140.
The model 199 is very similar.
WARNING
DO NOT install a CH pipe line relief valve with a
pressure higher than 30psi and DHW pipe line relief
valve with a pressure higher than 150psi. This is
the maximum allowable relief valve setting for the
combination boiler.
Test the operation of the valve after filling and
pressurizing system by lifting the lever. Make sure the
valve discharges freely. If the valve fails to operate
correctly, replace it with a new relief valve. Ensure that
the discharge capacity of the pressure relief valve is
equal to or greater than the maximum pressure rating
of the combination boiler.
Ensure that the maximum BTU/H rating on the
pressure relief valve is equal to or greater than the
maximum input BTU/H rating of the combination
boiler.
Pressure Relief Valve must be installed on the CH
supply line & DHW outlet line as close to the unit as
possible. (CH supply line: maximum 30psi, DHW
outlet line : maximum 150psi). No other valves should
be placed between the pressure relief valve and the
appliance.
This appliance has a high-temperature shut off switch
built in as a standard safety feature .Therefore a
“pressure only” relief valve is required.
Page 43
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
4.16 Disposal of Condensate
High efficiency gas condensing Boilers create
condensation when operating. Condensation has
acidic (pH) of approximately 4-5.
Condensate must be drained in accordance with all
local regulations. Follow your local code with regards
to the disposal of condensation.
One of 4 disposal methods must be followed
1. to floor drain
2. to neutralizer (optional kit)
3. to laundry tub
4. to condensate pump (field supplied)
If a neutralizer is installed, periodic replacement of the
lime stone (or neutralizing agent) will be required. The
rate of depletion of the lime stone varies upon usage
of the boiler. During the first year of operation, please
check the neutralizer every few months for depletion.
Apply only corrosion-resistant materials for the
condensate drain lines such as 1/2˝ PVC, CPVC,
Polypropylene pipe or included plastic hose.
NOTICE
For Category II and IV boilers, be installed so as to
prevent accumulation of condensate; and
Condensate Trap and Drain Pipe
For Category II and IV boilers, where necessary, have
means provided for drainage of condensate.
(viewed from left front corner and as if
the side and front panel are
semi-transparent).
AVIS
les chaudières de catégories II et IV doivent être
installées de façon à empêcher l'accumulation de
condensat; et
si nécessaire, les chaudières de catégories II et IV
doivent être pourvues de dispositifs d'évacuation du
condensat.
CAUTION
Condensate is mildly acidic (pH=5), and may harm
some floor drains and/or pipes, particularly those
that are metal. Ensure that the drain, drainpipe, and
anything that will come in contact with the condensate
can withstand the acidity, or neutralize the condensate
before disposal. Damage caused by failure to install
a neutralizer kit or to adequately treat condensate
will not be the manufacturer’s responsibility.
Contact the factory to order
Neutralizer Kit# A2123601
_________________________________________
2
1
3
4
Page 44
SECTION 4. Installation
4.17 Electrical Wiring Connections
WARNING
Install wiring and electrically ground boiler in accordance with authority having jurisdiction or, in the
absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1
Electrical Code-Part 1 in Canada.
ELECTRICAL SHOCK HAZARD — For your safety, turn off electrical power supply at service
entrance panel before making any electrical connections to avoid possible electric shock hazard.
Failure to do so can cause severe personal injury or death.
This appliance must be electrically grounded. Ensure the electrical receptacle that the combination boiler will
be plugged into, is properly grounded; if wiring directly.
Do not attach the ground wire to either the gas or the water piping as plastic pipe or dielectric unions may
isolate the Combination boiler electrically.
The wiring diagrams contained in this manual are for reference purposes only.
Refer to these diagrams and diagrams from external controls used with this appliance. Read, understand,
and follow all wiring instructions.
Do not disconnect the power supply when the unit is in normal operation. Damage caused by freezing is
not covered under the warranty.
Manual(Rocker) switch maximum allowable current for each circulator is 16 amps at 125VAC.
( Housing : Nylon #66 UL 94V-2 , Rocker : Nylon #66 UL 94V-2, Terminal : Copper Alloy )
Terminal block (External power connector) :
DFT-20A-10P (20 amps at 300VAC)
R
L N G L N G
Main Power
Manual
Power
Switch
CH/Boiler
Pump
W
0-10V
INPUT
0 - 10V
External
Input
Terminal Block
TT
O/S
Thermostat
Connection
Outdoor
Sensor
Page 45
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
4.18 DIP Switches
The FT Series, Floor-Standing, Gas Conversion Kit
DIP switches 6 and 7 have to be set in the OFF position when the boiler is running normally.
E
REF
MBH
R
ON
OFF
MIN Fire
Normal Operation
MAX Fire
Normal Operation
NG Natural
LP Propane
3” Vent Size
2” Vent Size
ON
OFF
.
NLY
OFFO
OFF
N/A
140
CE
ENON
ON
DO
ON
OFF
OT
NON
N/A
Document 4290B
ON
GE
N
A
C H ON
ON
199
Table B DIP Switch Settings
15.
Setup your combustion analyser and place the sensor
into the combustion test port
16.
Per Table B for Max Fire, change dip switch 6 to ON and 7 to OFF.
The unit will cycle up to MAX fire.
17.
WAIT for your combustion analyser to stabilize. This may take up to 3 minutes depending on your combustion
Figure D
analyser.
ThenSetting
check the CO2 measurement for MAX fire. Refer to Table D for acceptable MAX fire
System
Control
combustion readings. At this point, just record the CO2 readings at MAX Fire. Do NOT attempt to adjust
Maximum
flame
detecting
voltageFire, so...
2.4V
CO2 at MAX
Fire.
ONLY
in MIN
18.
19.
Pre-purge
time (Tp)dip switch 6 to OFF and 7 to ON. The
Maximum
minimum
Per Table B for MIN
Fire, change
unit will10s,
cycle
down 1s
to MIN Fire.
Safety Time (igniting time) (Ts)
3s
Igniting interval time
10s
Post-purge time (Tip)
120S (1st : 60s + 2nd 60s)
Over-heating 1,2,3 protection detection time
<3s
WAIT for your combustion analyser to stabilize. Then check the CO2 measurement at MIN fire. Refer to
Table D for acceptable MIN fire combustion readings.
20.
If CO2 readings in Max Fire and MIN fire are acceptable, then skip ahead to Step 23. If not, then open the
21.
Gas Valve Adjustment Port by removing the cap screw with a 4mm Allen wrench. See Figure E.
Pump1 post circulating time (T1pv)
60s
Then use the 4 mm Allen wrench to make a minor adjustment (1/8 turn) to either increase or decrease CO2.
Pump2 post circulating time (T1pv)
60s
High & Low Water Level detection time
‘NG’ type combustibility
Manifold
pressure
High
& Low Water
Level Recover time
2" VENT
3" VENT
FTCF140
FTCF199
<6s
‘LP’ type combustibility
<6s
2" VENT
3" VENT
MAX Fire
-0.15" WC
-0.216" WC
-0.15" WC
-0.216" WC
MIN Fire
0” WC
0.002” WC
0.1” WC
0.079” WC
MAX Fire
-0.134” WC
-0.173” WC
MIN Fire
-0.015” WC
-0.015” WC
‘NG’ type combustibility
‘LP’ type combustibility
Table C
CO2 value
FTCF140
FTCF199
Table D
2" VENT
3" VENT
2" VENT
3" VENT
MAX Fire
8.5~10.5%
9.5~11 %
MIN Fire
8~10%
9~10.5 %
MAX Fire
8.5~10.0%
9.5~11 %
800.900.9276
• Fax 800.559.1583 (Customer
Service,
MIN Fire
8~10%
9~10.5
% Service Advisors)
20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355 (Applications Engineering)
pg 3 of 4
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
Page 46
SECTION 4. Installation
4.19 Control Board, Electrical Diagram
Page 47
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
HOT
4A
4.20 Ladder Diagram
NEUTRAL
Relay 1
Pump1
Relay 2
Pump2
Relay 6
Pump3
Relay 4
Relay
3
Gas Valve
5
Ignitor
2A
EMI
FILTER
Relay
Power Detector
PWM
Primary
SMPS
F/B
Secondary
FAN
DC 30V
Speed Control
DC 14 V
DC 5V
Water
Level
Sensor
Driver
Air Pressure Sensor
Gas Sensor
Low level Sensor
AD Test
Flow_SENSOR
High Limit
Fire _SENSOR
Burner Limit
OP Water
Unuse(JUMP)
TEMP
Unuse(JUMP)
DHW_TEMP
Return _TEMP
Exhaust _TEMP
Over Heat
Driving Circuit
MCU
TEMP
Storage TEMP
Power Display
Relay
4
Relay
5
Relay
1
Relay
2
Relay
3
Heat Demand
Dry contact
input On/Off
DHM
Driving
circuit
External terminals
DISPLAY CONTROL
External terminals
O/S
Fan RPM Sensor
0-10V
Page 48
SECTION 4. Installation
4.21 Electrical Connections
Connector
#, Location, Type
CN9
65001WS-12
CN4
LWD1140-06D
HT
SELV
Label
1
-
GROUND
2
L
Power Supply Line
3
CP1
4
IT
5
HEAT/CP2
6
GV
7
-
8
N
Power Supply Neutral
HT (120V~)
9-12
N
AC Power COM Line
HT (120V~)
HT (120VAC)
Mixing Pump
HT (120V~)
Igniter
HT (120V~)
Central Heating Pump
HT (120V~)
Gas Valve
HT (120V~)
-
-
1
Unuse
2
GND
SELV (26VDC)
VDD
SELV (14VDC)
Fan power(start coil)
SELV (26VDC)
5
Fan power(end coil)
SELV (26VDC)
6
Fan speed feedback signal
SELV (14VDC)
3
4
1
8
2
10
3
11
4
CN11
LWD1140-16
Description
PIN
12
5
13
6
14
7
15
8
16
FAN
-
HWL
Unuse
SELV (12V~)
LWL
Low Water Level Leakage Sensor
SELV (12V~)
HD
Central Heating Demand
SELV (5V)
TH
Connect to the Display
Control(Thermostat)
SELV (14V)
APS
Jump (not used)
SELV (14V)
EL
Jump (not used)
SELV (14V)
BL
Burner Limit
SELV (14V)
HL
Condensate Block
SELV (14V)
Page 49
The FT Series Floor Standing, Combination Boiler
SECTION 4. Installation
4.21 Electrical Connections
Connector
#, Location, Type
PIN
1
SELV (5VDC)
OP.S
Operation water temperature sensor
SELV (5VDC)
DH.S
DHW temperature sensor
SELV (5VDC)
CH Return sensor
SELV (5VDC)
BG.S
Exhaust temperature sensor
SELV (5VDC)
ST.S
Storage water temperature sensor
SELV (5VDC)
SP.S
Over heat temperature sensor
SELV (5VDC)
1
GND
SELV (14VDC)
2
DHM Stepper motor position
SELV (14VDC)
3
VDD
SELV (14VDC)
4
DHM Stepper motor coil X phase
SELV (14VDC)
DHM Stepper motor coil Y phase
SELV (14VDC)
6
VDD
SELV (14VDC)
7
DHM Stepper motor coil /X phase
SELV (14VDC)
8
DHM Stepper motor coil /Y phase
SELV (14VDC)
9
Unuse
2
9
3
10
4
11
5
12
6
13
7
14
CN14
SMW250-09D
5
1
2
CN3
SMW250-06D
3
F.S
HT
SELV
Flame Detect Sensor
8
CN7
LWD1140-14
Description
Label
I.S
IWM
APS
SENSOR
4
5
6
FLUX1
-
VCC
SELV (5V)
GND
SELV (5V)
Voltage input
SELV (5V)
VCC
SELV (5VDC)
Water Flow Sensor
SELV (5VDC)
GND
SELV (5VDC)
Page 50
SECTION 5. Control Display and Operation
5.1 Control Dial and Buttons
The Control Display
Status Light
(constant green
when operating
normally)
The Control Display has a Control Dial (E), 4 buttons (A, B, C, D), and a Liquid
Crystal Display (with 72 back-lit segments). This section of this manual gives
instruction on how to navigate into the many functions of the FT and to change
temperature set points, set system variables and controller parameters.
Buttons
A
Display Power
Functionality
PRESS (Tap)
Turns Control Display
PRESS and HOLD (5 seconds)
ON / OFF
Tap to return to menu
(If Display Power was On ) Status Display Mode
(If Display Power was Off ) Installer Mode
Hot Water
DHW Set-Point LOW Range
DHW Set-Point HIGH Range
D
Central Heat
CH set-point mode (boiler only)
Toggle (°C / °F)
E
Scroll / Select
B
Modes
C
95 - 120°F (35 - 49°C)
Turn to scroll, tap to select
(clockwise or counterclockwise)
• Temperature Specifications
Operating ambient Temperature Range : -10 to 60°C.
Operating Relative Humidity up to: 90% at 40°C.
Shipping & Storage Temperature Range of : -20 to 80°C.
121 - 140°F (49.5 - 60°C)
Page 51
The FT Series Floor Standing, Combination Boiler
SECTION 5. Control Display and Operation
CH
Central
Heat
Anti-Freeze
Mode
Storage
Heating
5.2 LCD Overview
Lock
Communicating
Status and
Installer
Modes
Summer Mode
(warm
weather
shutdown)
Flame
Signal
Outside
Temp Mode
or 0-10V
Domestic Hot Water Mode
Pump
Numeric Display
CH mode
Central Heat mode icon can be adjusted
Anti-freeze mode
Anti-freeze mode icon
Storage Heating mode
Stored Water Being Heated, can be adjusted
Lock mode
Buttons-locked mode icon
Communication
Communication icon
Summer mode
Only DHW Mode, can be adjusted (warm weather shutdown)
Status and Installer mode
The Status Mode or the Installer Mode is Active (all parameters)
Flame signal
Flame Signal icon
Pump icon
Water pump operation (CH or DHW) icon
Numeric Display
Number and character display, to display all parameters
DHW mode
Combination boiler Set Point, can be adjusted
Outside temp or 0-10 V mode
Operating by outside temperature or 0-10V
The LCD will illuminate when a user action is detected (a button is pressed) and will turn
back off after 20 seconds.
* NOTE: The display will not allow changes when the lock mode
To exit the Lock mode, press the
WARNING
button.
Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of
the control system and any gas control that may have
been under water.
is activated.
Page 52
SECTION 5. Control Display and Operation
5.3 Operating Mode
Operating Mode
After the Power is turned on, and/or the Control Display is turned on
, the Control Display
will go through a ‘Start Up’ checklist and briefly show a sequence of diagnostic codes before
entering into the ‘Operating Mode. It will then display the following information.
Indicate
Current Operating Temperature
Temperature sign Celsius or Fahrenheit letter
Display and Controller are communicating
If flame detected
If pump is operating
Outdoor sensor or 0-10V
Example
110°F
°C or °F
Page 53
The FT Series Floor Standing, Combination Boiler
SECTION 5. Control Display and Operation
5.4 Status Display Mode
Digital Display
Status Display Parameter
Description
O:ot
Outdoor temperature
Current Outdoor temperature
A: Li or A: GA Flow unit
Current flow value(Li: L/m, GA: GPM)
b: It
CH Return Water Temperature
Current Return Water Sensor Temperature
C: Fr
Fan rpm
Current fan rpm value
d: Lc
Lock mode
Lock mode ON/OFF
E: oP
OP temperature
Current OP temperature
F: dH
DHW temperature
Current DHW temperature
H: Eh
Exhaust temperature
Current Exhaust temperature
I : St
Storage Temperature
Current Storage Temperature
J: oH
Overheat temperature
Current Overheat temperature
Supply power
time
Supply power time x 100 hour
Burner
operation time
Burner operation time x 1 hour
Burner
operation time
Burner operation time x 1,000 hour
4: It
Ignition cycles
Ignition cycles x 10 times
5: IH
Ignition cycles
Ignition cycles x 10,000 times
1: PH
2: rh
L: rt
3: rH
Burner
Operation
Time
Displays output condition for
internal primary pump and
three way valve.
P: Ou
1st Icon
2nd Icon
3rd Icon
Internal
Pump
CH
Pump
Not Used
- Off
- On
To change any of the above listed Status Parameters,
Press and Hold Button B
to get into the Status Display Mode.
Rotate Dial E until you find the Parameter that you wish to change. Tap Dial E to enter that Parameter.
All other modes except d:Lc (Lock mode) are to display current status, therefore you need to check the
current setting and press button to exit.
Page 54
SECTION 5. Control Display and Operation
5.5 DHW Set Point Change Mode
AUTODESK � � � � � � � � � �
DHW Set Point Change Modes
When the button D
is pressed (for more
than 5 seconds), temperature unit will toggle
between °C and °F.
AUTODESK � � � � � � � � � �
Changing between Celsius and Fahrenheit
AUTODESK � � � � � � � � � �
The display shows the following
information when changing water heating
temperature set points.
AUTODESK � � � � � � � � � �
Indicate
Example
Current DHW set-point temperature
125°F
Temperature sign Celsius or Fahrenheit letter
°C or °F
If display is communicating with the main controller normally, the
communication icon will be indicated.
When DHW set-point range is high : from 121°F (49.5°C) to 140°F (60.0°C)
When changing DHW setpoint, the DHW icon will flash
H . 140°F
S24
* Default DHW set-point is 125°F (51°C)
• DHW 95-120°F (35 - 49°C) LOW range (Default)
-To change LOW range, press the C Button. The DHW icon and current DHW LOW will flash (a
flashing value means it can be changed).
-Turn dial E clockwise to increase and counterclockwise to decrease until desired temperature is reached.
-Press dial E to save setpoint changes.
• DHW 121 - 140°F (49.5 - 60°C) HIGH range
-To change HIGH range, press and HOLD the C button for more than 5 seconds. The DHW icon
and current DHW HIGH will flash (a flashing value means it can be changed).
-Turn dial E clockwise to increase and counterclockwise to decrease until desired temperature is reached.
-Press dial E to save setpoint changes and to Exit.
DANGER
Scalding may occur within 5 seconds at a setting of 140°F (60°C). Water temperatures
over 125°F can cause severe burns, or death from scalding. Children, disabled,
and elderly are at highest risk of being scalded. Read all instructions before setting
temperature at appliance. Feel water before bathing or showering.
Page 55
The FT Series Floor Standing, Combination Boiler
SECTION 5. Control Display and Operation
5.6 CH Set Point Change Mode
Changing between Celsius and Fahrenheit
When the button D
is pressed (for more than
5 seconds), temperature unit will toggle between
°C and °F.
Indicate
Current Operating Temperature
Temperature sign Celsius or Fahrenheit letter
Example
110°F
°C or °F
Display and Controller are communicating
If flame detected
If pump is operating
When changing CH Setpoint, the CH Icon will flash
Default CH set-point is 120°F (49°C)
CH set-point range is 86 - 180°F (30.0 ~ 82.0°C)
To c
hange CH Setpoint, press the button D
button. The CH Icon and
current CH Setpoint will flash.
Turnthe E dial clockwise to increase, and counterclockwise to decrease CH setpoint, until
desired temperature is reached.
Press E dial to save changes and to Exit.
5.7 Storage Mode
Indicate
Current Operating Temperature
Temperature sign Celsius or Fahrenheit letter
Example
110°F
°C or °F
Display and Controller are communicating
If flame detected
Storage mode indication
If Pump is operating
To change Storage Mode Temp, First turn OFF the power to the Control Display.
Then Press and Hold Button B
to get into the Installer Mode.
Rotate Dial E until you find 24:SF Tap Dial E to enter Storage Mode. Storage Mode indicates that the
boiler is heating the water held in the internal storage tank. When Storage Mode is active, the display
will appear as shown.
Turn the E dial clockwise to increase, and counterclockwise to decrease setting.
Press E dial to save changes and to Exit.
Page 56
SECTION 5. Control Display and Operation
5.8 Installer Mode
AUTODESK � � � � � � � � � �
AUTODESK � � � � � � � � � �
AUTODESK � � � � � � � � � �
These changes are to be made only by a qualified technician.
AUTODESK � � � � � � � � � �
To change any of the Installer Parameters, Start by turning OFF the Power
to the Display Control.
Then, with the power to the Display Control OFF, Press and HOLD (more than 5 seconds) the Button B
to get into the Installer Mode.
Rotate Dial E until you find the Installer Parameter (full list on facing page) that you wish to change.
Tap Dial E to enter that Parameter.
Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.
Finish by pressing button B
Page 57
The FT Series Floor Standing, Combination Boiler
SECTION 5. Control Display and Operation
Index
5.8 Installer Mode
Parameter
Description
1: EH
History entry
History fault code (E0~E9)
2: cE
Clear Error History
Clearing of error History buffer
3: In
System initialize
System initialize to default
4: Fu
Flow unit
gallon / liter
5: St
Heat storage function
Heat storage function On/Off
6: OH
Maximum Outdoor
Temperature
When used with an outdoor sensor, sets the maximum outdoor design temperature for the system
design. Warm weather shut down will disable the appliance if the programmed outdoor temperature is
exceeded. Maximum outdoor temperature must be set 9°F above the minimum outdoor temperature.
Range: (Minimum Outdoor Temperature + 9°F) to 110°F Default 68°F (20°C)
7: OL
Minimum Outdoor
Temperature
Sets the minimum outdoor design temperature for the system. Minimum outdoor
temperature must be set 9°F below the maximum outdoor temperature.
Range: -4°F to (Maximum Outdoor Temperature - 9°F)
8: FH
Max fan
Adjusts Maximum Fan Speed
Range: -30 - +30
9: FL
Min fan
Adjusts Minimum Fan Speed
Range: -30 -+30
10: dr
Delete running time
Delete running time
11: dI
Delete igniting times
Delete igniting times
12: bt
Outside Unit Function
Delay Time (boost time)
When heating in the outside unit function for the first time, there will be a delay.
(0~120 min, Default 0)
13: Ft
Delay time for heating
burner operation
Burner does not operate during the delay time when the burner is turned off due to the
temperature during heating operation. (0~20 min, Default 1 min)
14: bo
Setting temperature of
burner ON.
Heating temperature setting during heating operation –
Operate in burner ON temperature setting Range:
-12.7°C(9°F)~-2.7°C(27°F), Default 2.7°C(27°F)
15: OF
Warm Weather Shutdown
This warm weather temperature setting will shut down CH Mode 10°C(50°F)~43°C(110°F),
Default 38°C (100°F)
16:cH
Setting for Heating
Maximum Temperature
Range:[Minimum Temperature -12.7°C(9°F)]~82°C(180°F), Default 82°C(180°F)
17:cL
Setting for Heating
Minimum Temperature
Range: 30°C(86°F)~[Maximum Temperature-12.7°C(-9°F)],Default 30°C(86°F)
18:dH
Setting for Hot Water
Maximum Temperature
49°C(120°F)~60°C(140°F), Default 60°C(140°F)
19:cb
Heating Combustion Rate
50%~100%, Default 100%
20:db
Hot Water Combustion Rate 50%~100%, Default 100%
21:PP
Pump Post-Purge Time
(Heating Pump) 1min ~ 60min, Default 40min
22:Po
Pump on Time
(Heating Pump Repeat ON Time) 1 min ~60 min, Default 5 min
23:PF
Pump off Time
(Heating Pump Repeat Off Time) 0min ~60 min, Default 10 min
24:SF
Heat storage off
Temperature
60°C(140°F)~75°C(167°F),Default(70°C)158°F
25:So
Heat storage on
Temperature.
(off Temperature-Setting Temperature) -12.7°C(9°F)~2.2°C(36°F),
Default (-2.7°C) 27°F
26:dt
Delay time when switching
from DHW mode to CH
Range: 0 – 2 minutes,Default 2min
mode
27:PE
Internal CH Pump PostPurge Time,
T/T Satisfied
Allows the user to set the appliance pump post purge time once the appliance CH setpoint
and thermostat are satisfied. Range: 1-5 minutes,Default 1min
28: HA
High Altitude setting
(Normal)0<1<2<4 (High)
Internal CH Pump and
3-way valve Pump Test
Mode
This function sets the time to run both the Internal CH and 3-way valve pumps to purge
air from the system. Range: 1 – 30 minutes ,Default 5min
Internal CH Pump and
3-way valve Pump Test
Mode
Turn this function on to activate Internal CH and 3-way valve pump testing.
Only works in installation mode. Turns off when in normal mode. Default OFF
DHW Timeout Feature
Range: 0~12 Hours, '0' OFF, Default: 4 Hours
29: AP
30: dP
The Full List of Installer Mode Parameters
Page 58
Outdoor Reset varies the control setpoint based on
the outdoor temperature. The reset function works
as shown in Figure ‘CH Outdoor Reset’. When the
outdoor air temperature reaches 6:OH “high outdoor
temperature setpoint”, the control point setting is
adjusted to 17:cL “low boiler temperature setpoint”.
When the outdoor air temperature reaches 7:OL “low
outdoor temperature setpoint” the control setpoint is
adjusted to 16:cH “high boiler temperature”.
Default outdoor reset setpoint is 100°F (38°C)
The Outdoor Temperature Mode Icon on the display
will flash if an Outdoor Sensor or 0-10 Volt is not
connected to the appliance.
To check the CH Target Temperature while using
Outdoor Temperature Mode, press the
button
while the appliance is operational and the display
panel is powered on.
5.9 Outdoor Reset Adjustment
Op
er
at
ing
co
nd
itio
n
CH Outdoor Reset
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp
setpoint simultaneously.
5.10 External Set Point Temperature Control
A signal from a building management system may be connected to the appliance to enable remote
control. This signal should be a 0-10 volt DC signal. When this input is enabled, a building control
system can be used to control the set point temperature of the appliance.
The control interprets the 0-10 volt signal as follows; when the signal is between 0 and 1.5 volts, the
appliance will be in standby mode, not firing.
When the signal rises above 1.5 volts, the appliance will ignite. As the signal continues to rise
towards its maximum of 10 volts, the appliance will increase in set point temperature. Adjust 16:cH
and 17:cL to set MIN and MAX boiler water temperatures respectively.
Connect a building management system or other auxiliary control signal to the terminals marked
for this purpose on the appliance terminal block (shown in Piping Diagrams, this manual). Caution
should be used to ensure that the 0-10 VOLT + connection does not become connected to ground.
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp
setpoint simultaneously.
(warm weather shutdown)
SECTION 5. Control Display and Operation
Page 59
The FT Series Floor Standing, Combination Boiler
5.11 Error Mode
Flashing
Indicate
Example
Error ‘ Er : ’ will flash
Er:11
Error Code
Er:11
Display and Controller are communicating
NOTE: When communication between the Control Display and the main controller is lost, the
will not be displayed.
Page 60
SECTION 6. Error Codes
Error
Code
Error Code
Description
Possible Remedies
Recover
methods
Flame has
Extinguished 8 (Eight)
Times
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is
between 3.5 and 14” WC.
2. Check gas valve wire. Ensure connection is secure.
3. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check vent terminations. Ensure there are no blockages.
5. Assure that the flame is stable when lit.
6. If the problem persists, replace the main control.
Hard
Lock
Ignition has Failed 10
(Ten) Times
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is
between 3.5 and 14” WC.
2. Check gas valve wire. Ensure connection is secure.
3. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check igniter transformer for proper connection.
5. Clean the spark igniter with steel wool to remove oxides. Ensure proper separation (3-4 mm).
6. Replace the spark igniter if damaged.
7. Assure that the flame is stable when lit.
8. If the problem persists, replace the main control.
Hard
Lock
Operating
Temperature Sensor
detects Water
Temperature Greater
than 203°F (95°C)
Press the Power button to clear the Error Code.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for
normal operation.
2. Check if CH inlet pipe is blocked. Ensure there is enough water flowing to the
appliance.
3. Check Operating Temperature sensor at CH heat exchanger outlet. If resistance is
zero, replace the sensor.
4. If the problem persists, replace the main control
Hard
Lock
Condensate – Closed
is Normal, Open is
Fault (Condensate
Drain Trap)
Press the Power button to clear the Error Code.
1. Check Condensate and main controller connections. Ensure all are secure.
2. Check Condensate sensor resistance. If resistance is zero, replace the switch.
3. Check Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check Vent Pipe for blockages.
6. If the problem persists, replace the main control.
Hard
Lock
28
Overheat Sensor Open
or Short
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check overheat temperature sensor. Ensure connections are secure.
2. Check overheat sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
30
DHW Storage
Temperature Sensor
Open or Short
This error Code will go away when outlet stroage temperature decreases.
If Error happens again:
1. Check stroage temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
32
DHW Sensor Open or
Short
This Error Code will go away when outlet DHW temperature decreases.
If Error happens again:
1. Check DHW outlet temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
CH Temperature
Sensor Open or Short
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check CH temperature sensor. Ensure connections are secure.
2. Check CH sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Soft Lock
10
11
16
20
33
The FT Series Floor Standing, Combination Boiler
Page 61
SECTION 6. Error Codes (continued)
Error
Code
Error Code Description
Possible Remedies
Recover
methods
Venting (Exhaust) Sensor
Open or Short
This Error Code will go away when exhaust temperature decreases.
If Error happens again:
1. Check Venting (exhaust) temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. Check vent pipes for blockage.
4. If the problem persists, replace the main control
Soft Lock
Abnormal Supply Voltage
Supply voltage is too low to operate. This Error Code will go away when supply
voltage returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the
requirements on the rating plate.
2. If problem persists, replace the main control
Soft Lock
37
Abnormal Supply Frequency
Supply frequency is too high to operate. This Error Code will go away when
supply frequency returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the
requirements on the rating plate.
2. If problem persists, replace the main control.
Soft Lock
38
Error Appears When Control
Stores Data, but Data is not
Saved
Press the Power button to clear the Error Code.
Replace the main control.
Hard Lock
Gas Leakage is Detected for
Greater than 5 seconds, or
three times within 10 minutes
IMPORTANT: If you smell gas, STOP! Follow the instructions on page 2, this
manual, and call a qualified service technician or the fuel gas utility.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the appliance cover. Ensure it is secure.
2. Check gas connections for leakage with a soapy solution. Fix any leaks.
3. Check condition of the burner assembly.
4. If the problem persists, replace the main control.
Hard Lock
Fan Speed too High with
Flame On
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the vent connections for blockages.
2. Check the burner assembly.
3. C
heck fan operation. If fan appears to be operating normally but RPMs are too
high, replace the fan.
4. If the problem persists, replace the main control.
Hard Lock
42
Jumped Wire Disconnected
Press the Power button to clear the Error Code.
If Error happens again:
1. Ensure the jumped wire is properly connected.
2. If the problem persists, replace the main control.
Soft Lock
43
Burner Overheat Switch
Open
Press the Power button to clear the Error Code.
If Error happens again:
1. Check burner overheat switch connections. Ensure connections are secure.
2. Check switch resistance. If resistance is zero, replace the switch.
3. If the problem persists, replace the main control.
Hard Lock
44
Air Pressure Sensor (APS)
Fault
Press the power button to reset
If error happens again:
1. Check the vent pipe for blockages.
2. Check the vent pipe for blockages.
3. If error do not clear, replace the APS
4. If the problem persists, replace the main control.
Hard Lock
45
Air Pressure Sensor (APS)
Open
Check the aps connection.
1.If APS is closed and connections are secure, check APS connection.
2. If the problem is not happen, replace the APS
3. If the problem persists, replace the main control.
Soft Lock
Fan Speed Feedback Signal
Abnormal
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the connections to the fan. Ensure all are secure.
2. If the fan does not rotate during the ignition sequence, check for AC8V~26.5V
power at the fan connection. If AC8V~26.5V power is present at the control,
replace the fan. If the blower does not have AC8V~26.5V power, check power at
the control. If AC8V~26.5V power is not present at the control, replace the control.
3. If the problem persists, replace the main control.
Soft Lock
35
36
40
41
61
Page 62
SECTION 6. Error Codes (continued)
Error
Code
Error Code Description
66
Mixing Valve Initial Value
Error
(Mixing Valve Cannot Return
to Initial Position)
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. Check wiring connections to mixing valve. Ensure all are secure.
3. Replace mixing valve.
4. If the problem persists, replace the main control.
Soft Lock
68
Mixing Valve Operation Error
(Mixing Valve Stuck in Initial
Position)
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. Check wiring connections to mixing valve. Ensure all are secure.
3. Replace mixing valve.
4. If the problem persists, replace the main control.
Soft Lock
70
Register, Ram, Rom, I/O
Port, AD Abnormal, Important
EPROM Data or Safe Data
Abnormal
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. If the problem persists, replace the main control.
Soft Lock
Flame Signal Detected before
Ignition
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the appliance cover. Ensure it is secure. Flame detection sensor can detect
an external light source.
2. Check flame detection sensor. Ensure connections are secure. Normal operating
settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
3. If the problem persists, replace the main control.
Soft Lock
Poor Communication
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check connections from main control to display panel.
2. If the problem persists, replace the display and/or the main control.
Soft Lock
Low Water Level Sensor
(Low Water Level Detected
Four (4) Consecutive times)
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Ensure all valves are open to the appliance and there are no leaks.
2. Ensure all air has been purged from the system.
3. Check wiring connections to low water level sensor. Ensure all are secure.
4. Check low water level sensor resistance. If resistance is zero, replace the sensor.
5. If the problem persists, replace the main control.
Soft Lock
Low Water Level Circuit
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Ensure all valves are open to the appliance and there are no leaks.
2. Check wiring connections to low water level sensor. Ensure all are secure.
3. Check low water level sensor resistance. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control.
Soft Lock
Freeze Protection
(Appliance has detected
water temperature below
34°F(1°C)
This Error Code will go away when the freezing condition is remedied.
If Error happens again:
1. Ensure appliance is located in a mechanical room protected from freezing conditions.
2. Ensure all valves are open to the appliance, there are no leaks.
2. Check wiring connections to low water level sensor. Ensure all are secure.
3. Check low water level sensor resistance. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control.
Soft Lock
Exhaust Sensor detects Vent
Temperature is Greater than
190°F (88°C)
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for
normal operation.
2. Check exhaust temperature sensor. Ensure connections are secure.
3. Check sensor resistance. If resistance is zero, replace the sensor.
4. Check exhaust vent for blockage.
5. If the problem persists, replace the control.
6. If the problem persists, replace the heat exchanger.
Soft Lock
72
76
80
81
85
94
Possible Remedies
Recover
methods
The FT Series Floor Standing, Combination Boiler
6.2 Fault Tree Analysis
1. Flame detection
Page 63
Page 64
6.2 Fault Tree Analysis
2. Gas Detection
3. ‘Storage’, ‘DHW’, ‘OP’, ‘CH overheat’, ‘Exhaust heat’ Sensor detects
Error code
contents
E30
DHW Storage Temperature Sensor open or short
E32
DHW NTC open or short
E33
OP NTC open or short
E35
Exhaust NTC open or short
Page 65
The FT Series Floor Standing, Combination Boiler
SECTION 7. Trouble Shooting
Question
7.1 Diagnostics
Answer
Make sure that the ON/OFF button on the Control Panel has been turned ON.
If the monitor on the Control Panel is blank, make sure the power cord is
plugged and 4A fuses on the main controller in the units are good.
Burner dose not ignite
when the hot water is
opened.
Make sure that there is water supplied to the unit. The unit activates once
the inlet water flow is over 0 gpm.
Make sure the cold and hot water lines are not plumbed in reverse side.
Make sure that the cold water and gas supply lines are opened.
Make sure that the water lines are not frozen.
Check that the setting temperature on the unit is not too low
Make sure that the filter in the cold water supply line is not clogged with
debris.
Water is not hot enough. Make sure that the gas supply type is correct.
Check the supply and manifold gas pressures are in accordance with
specifications.
Make sure that the water flow sensor with three wires has been properly
connected on the top of heat exchanger.
Make sure that the setting temperature on the unit is not too hot.
Water is too hot.
Make sure that the filter in the cold water supply line is not clogged with
debris.
Make sure that the gas supply type is correct.
Make sure that the filter in the cold water supply line is clean.
Hot water temperature
fluctuates at the opened
tap.
Make sure that the gas supply type is correct.
Check the supply gas pressure is sufficient.
The blower is still
operating after the
combustion stops.
This is normal because the blower keeps operating for 1 minute to vent
(exhaust) the flue gas from the chamber once the combustion has
stopped.
Temperature Rise
too Quickly
Occurs when supply water temperature in heat exchanger rises faster
than 2°F per second during the first two minutes the burner is on.
Automatically resets after a few minute delay or using manual reset on
control panel. See message displayed TEMPERATURE SENSOR and
follow procedure for loose connections.
Abnormal sounds come
from unit during operation.
A leak of combustion gas between sealed chamber and exhaust tube
inside the unit. Call a qualified service technician for evaluation.
Improper venting termination, make sure that the venting termination
complies with specification.
Check the supply gas pressure is sufficient. Insufficient gas pressure will
cause unstable burner flame and noise.
Page 66
SECTION 7. Trouble Shooting (continued)
7.2 Suggested Corrective Actions
This controller is able to record information about the boiler’s condition at the time of the five previous faults or
errors. Refer to the Section ‘5.10 Error Mode’ of this manual.
Display
Nothing shown
on display control
panel and blower
running at full
speed.
Nothing is shown
in display control
panel and no
other boiler
components are
operating.
Nothing is shown
on
control panel, but
boiler is
operating.
Condition
Control is not
receiving power.
Control is not
receiving 120V power.
Occurs when the
communication is lost
from the control to the
display.
Diagnostic
Corrective Action(s)
Check wiring for short
circuit or incorrect
wiring.
Correct wiring per wiring diagram
including connection of transformer to
the control.
Check transformer
connection to the
control per wiring
diagram. Check for
12V output of
transformer.
Replace transformer if it is receiving
120V, but not outputting 12Vac.
Check service switch
and/or circuit breaker
to boiler turned is on.
Turn on service switch to power boiler.
Is there 120 Volts at
the service switch?
Troubleshoot and correct the power
supply to the manual switch.
Is the ON/OFF
POWER
SWITCH (inside boiler
case) turned on?
Turn ON the manual power switch
inside the boiler case.
Check for 120 volts at
the line voltage
terminal block located
inside the boiler case.
Correct wiring inside the boiler case
using the wiring diagram in this
manual.
Inspect the fuse.
Replace if necessary.
Replace the fuse with proper part
found in the replacement part section
of this manual. If fuse blows again
recheck wiring per diagram.
Check for loose
connections and
proper pin alignment/
engagement on the
Control's plug.
Check for continuity on the wire
harness from the display to the control.
See repair parts section for proper
replacement part.
Cycle power off and on
Replace with new display module. See
using boiler power
repair parts section for proper
switch and check for
replacement part.
operation.
Page 67
The FT Series Floor Standing, Combination Boiler
7.2 Suggested Corrective Actions (continued)
Fault
TEMPERATURE
SENSOR
FLAME FAULT
Condition
Occurs when a
temperature
sensor has
electrically
shorted
(SHORT) or has
become
disconnected
(OPEN).
Occurs when
flame is
detected when
there should be
no flame.
Diagnostic
Corrective Action(s)
Check all the temperature readings of
the boiler on the DIAGNOSTICS
- TEMPERATURES menu to determine
if any sensors are currently displayed
as SHORT or OPEN.
Reset using manual
Check wire harness for loose
reset screen on control
connections and pin engagement at
panel. (Power button)
sensor Connection and Control
module.
If problem persists after checking items
above replace Control. Refer to repair
parts section for kit number.
Reset using manual
reset screen on control
panel.
(Power button)
Burner may be operating too hot due
to incorrect combustion. Inspect flame
and conduct combustion test.
Check for flame at burner via flame
current with burner off. Turn boiler off
and watch flame through observation
port. If flame continues after shutdown
replace gas valve.
Check wire harness for loose
connections and pin engagement at
blower.
Connections.
BLOWER FAULT
IGNITION
FAULT
Blower unable
to reach
required speed
or does not
reach 0 RPM
when turned off.
Even if boiler
went through 8
ignitron
attempts, but
cannot detect
flame
Boiler in standby mode and blower not
running. If BLOWER SPEED is not 0
RPM then replace blower.
Reset using manual
reset screen on control
panel.
If blower does not rotate during ignition
(Power button)
sequence check for 120V power at
blower connection. If 120Vac power at
blower motor and it doesn't start
replace blower. Check power at
Control. If 120Vac is not present at
Control when boiler is powered replace
Control.
Dirty burner and/or heat exchanger will
cause high back pressure and poor
ignition.
Visual inspection of flue ways often will
not be able to diagnose condition.
Power off and on.
Check incoming gas pressure with
boiler off and at Max fire. Adjust within
limits on rating label.
Check for flue pipe and intake pipe
restrictions or blockage
Check burner fasteners and gaskets
Check air intake pipe and proper
propane orifice
GAS VALVE
FAULT
The Control has
detected a
problem with it
gas valve
output circuit.
Check wire harness connections
Reset using manual
between gas valve and Control.
reset screen on control
panel.
If lockout re-occurs replace Control.
(Power button)
Page 68
SECTION 8. Maintenance
Regular Maintenance
-This Manual should be placed in a safe and dry
location near the Combination boiler. Maintenance
instructions should be carried out by the following
guidelines.
Maintenance procedures [ Daily ]
- Check that the boiler casing is closed.
Check if there is any problem with the Combination
boiler casing and the two upper and lower screws
are tightened well. Combination boiler casing must
be closed while it is running.
WARNING
To prevent potential severe personal injury,
death or substantial property damage,
remove all contaminated materials.
If contaminants are found:
Remove products immediately from the area.
In order to check the status of Combination
boiler, call a qualified service technician to
inspect the Combination boiler for possible
damage from acid corrosion.
WARNING
O NOT store combustible materials, gasoline
D
or any other flammable vapors or liquids near
the Water Heater. Remove them immediately or
store them other places.
8.1 Annual startup & general maintenance
- Check the power source.
Make sure that the power cord is correctly
connected. The main power line is connected to
the manual switch box inside a Combination boiler.
(Power line through the strain relief in the bottom of
the combination boiler casing and fix it.)
- Check the status of the control panel
Check status of the power supply. Please check for
any debris on the button.
Maintenance procedures [ Monthly ]
- Check the vent pipe.
Visually inspect the flue gas vent piping for detecting
any signs of blockage, leakage or deterioration
of the piping. Please contact a qualified service
technician immediately if you find any problem.
- Check the air inlet pipe.
Visually inspect the air inlet to be sure it is
unobstructed. Inspect entire length of air piping
for ensuring that piping is intact and all joints
are properly sealed. Call your qualified service
technician if you notice any problems.
- Check the relief valve.
Inspect the Combination boiler relief valve and
the relief valve discharge pipe for any signs
of weeping or leakage. If the relief valve often
weeps, immediately contact your qualified service
technician for inspecting the Combination boiler and
system.
- Check the condensate outlet.
While the Combination boiler is running, check the
discharge end of the condensate drain tubing.
Make sure that no flue gas is escaping from the
condensate drain tubing.
If flue gas is continuously escaping, it is a serious
problem. Call your qualified service technician for
inspecting the Combination boiler and condensate
line. Also, refill the condensate trap if problem
persists regularly.
- Check the vent terminal screen vent (rodent
screen).
If you encounter a problem of combustion
specifications, visually inspect the terminal screen.
And then replace it with spare parts or clean the
screens.
Page 69
The FT Series Floor Standing, Combination Boiler
SECTION 8. Maintenance
- Check the air vent
If the air vent valve seems to work freely without
leaking, replace cap “A” by twisting all the way on.
Loosen cap “A” one turn to allow vent to operate.
If vent does not operate correctly, replace the vent.
8.1 Annual startup & general maintenance
- Check the pressure relief valve
WARNING
Leaks must be fixed by a qualified service technician
immediately. Failure to comply with this instruction
could result in severe personal injury, death or
substantial property damage. This discharge line
must be installed by a qualified heating installer or a
service technician.
A
FTCF 140
A
FTCF 199
Maintenance procedures [Every 6 Months]
- Check the boiler piping (gas and water)
Visually inspect for leaks around internal water
piping. Also inspect external water piping,
circulators, relief valve and fittings. Immediately
call a qualified service technician to repair any
leaks. Leaks must be fixed by a qualified service
technician immediately.
Failure to comply with this instruction could result in
severe personal injury, death or substantial property
damage.
Before proceeding, verify that relief valve outlet has
been piped to a safe place of discharge, avoiding
any possibility of scalding from hot water. If water
flows freely, release the lever and allow the valve
to seat. Watch the end of the relief valve discharge
pipe to ensure that the valve does not weep after
the line has had time to drain. If the valve weeps, lift
the seat again to attempt to clean the valve seat. If
the valve continues to weep, contact your qualified
service technician for inspecting the valve and
system. If water does not flow from the valve even
though you have lifted the lever completely, the valve
or discharge line may be blocked. Shut down the
Combination boiler immediately. Call your qualified
service technician to inspect the combination boiler
and system.
- Check the burner state
You can clean the exterior of burner. However, if you
need to clean the inside of the burner stage, you should
call a qualified service technician.
Page 70
8.2 Flushing or Draining
Flushing the Heat Exchanger is a complicated procedure that should only be done by an authorized technician or
licensed professional. Keep in mind that improper maintenance can void your warranty.
V1
V3
V4
V2
1. Disconnect electric power to the combination boiler.
2. Close the shutoff valves on both hot water outlet
and cold water inlet lines. (V1 & V2)
3. Connect one hose “D1” to the valve “V3” and place
the free end in the bucket. Connect one of the
hoses “D3” to the circulation pump outlet and the
cold water inlet line at the valve “V4”. Connect other
hose “D2” to the circulation pump inlet and place
the free end in the bucket.
4. Pour the cleaning solution into the bucket. Place the drain hose
(D1) and the hose (D2) to the pump inlet into the cleaning solution.
5. Open service valves (V3 & V4) on the hot water outlet and cold
water inlet lines.
6. Turn on the circulation pump (Operate the pump and allow the
cleaning solution to circulate through the combination boiler for at
least 1 hour at a rate of 4 gallons per minute.)
7. Rinse the cleaning solution from the combination boiler as
follows:
-R
emove the free end of the drain hose (D1) from the
bucket.
-C
lose service valve, (V4), and open shut off valve, (V2).
Do not open shut off valve, (V1).
- Allow water to flow through the combination boiler for 5
minutes.
- Close shut off valve (V2).
D1
D3
D2
8. Disconnect all hoses.
9. Remove the cold water inlet filter from the combination boiler and clean out any residues.
10. Connect electrical power to the combination boiler.
Draining the Combination Boiler.
1. Place a bucket under the appliance to collect the residual water inside the combination boiler.
2. Press Power button on the front control panel to turn OFF the electrical power to the combination boiler.
3. Turn off the gas valve.
4. Close water supply valve on the inlet to the appliance. If there is no valve, turn off main water valve.
5. Open the hot water faucets completely.
6. To refill the combination boiler, follow the steps of “Draining the Combination Boiler ” in reverse.
Page 71
The FT Series Floor Standing, Combination Boiler
Section 9 – Installation Check
9.1 Quick View
Before Installing
-Make sure that there is enough space for
installing Water and gas line.
Verify vent/air termination is located as required.
-All models need for propane Conversion which
requires a separate gas conversion manual.
Install Water Piping
-Boiler loop piping must be sized to the minimums
listed in the Boiler manual. Using smaller piping
will cause performance problems.(page 35)
Install Vent & Air Piping
-Slide the air inlet pipe and vent pipe into the
Boiler pipe connector.
-Make sure the terminations are placed as
required in the manual and that air intakes are at
least 12 inches above normal snow line.
-Refer to the material check list in this guide for a
list of items needed.
Install Condensate Piping / Tubing &
Components
-Fill out the material check list in this guide to
ensure you have the tubing or PVC pipe and all
components needed for the condensate piping.
-Connect internal components that are supplied
with the Boiler.
Install Gas Piping
-Install a union and shutoff valve.
Wire the Boiler
-Connect power wiring and control wiring per
boiler manual wiring diagram.(Section 4.19)
Start up, Adjust & Test
-Follow the Boiler manual instructions to clean
the system if needed, then fill and check water
chemistry.
9.2 Final Check Lists
Final check : Installation Conditions.
• Is the Boiler properly mounted on the wall?
• Is there space for a drain which is close to the
Boiler?
•Are there any combustible materials near the
Boiler and vent pipe?
•Is the air supply sufficient for proper operation of
the Boiler?
•Are the proper service clearances maintained?
•Is the distance between the Boiler and point of
vent termination minimized?
•Is the proper distance from windows, doors, and
other intake vents maintained?
Final check : Gas pipe installation
•Is the gas supply line equipped with a manual
shut off valve?
•Is the gas supply line a minimum of 3/4˝ inner
diameter?
•Is the gas supply line length and diameter
adequate to deliver the required BTU’s?
•Has the gas supply line pressure been
measured?
•Does the supply gas type match the type
indicated on the boiler rating plate?
Final check: Air/Vent pipe installation
•Has the Boiler been vented with 3˝ or 2” PVC,
CPVC, Polypropylene or BH Special
Gas Vent (S636 PVC, CPVC) for Category IV
appliances in accordance with this manual and/or
your local code?
•Is the vent termination at least 12˝ above the
exterior grade?
•Is the total vent length within the maximum vent
length restriction?
•Have you checked the air/vent piping for leaks?
•Have you properly supported the vent
termination?
•Are all vent runs properly supported?
•Is the vent sloped upward toward the vent
termination at a rate of 1/4˝ per foot (2% grade)?
Final check : Condensate drain installation
•Have you installed a condensate drain line from
the Boiler to a drain or laundry tub?
Final check : Setting the DIP switches
•Are all DIP switches correctly set on the main
board?
Page 72
9.2 Final Check Lists (continued)
Final check : Connecting the power supply
• Please check that the power is 120V AC.
• Have you checked the polarity of the electrical connection?
Final check : Pressure relief valve
• Have you installed an approved pressure relief valve on the boiler?
• Is the pressure relief valve of CH Plumbing at least 1˝ in diameter?
• Is the pressure relief valve of DHW Plumbing at least 3/4˝ in diameter?
• Have you installed the pressure relief valve on the hot water outlet pipe near the Boiler?
Final check : Burner flame
• The burner flame must be checked periodically for a constant proper blue color.
• If the flame does not appear normal, the burner may need to be cleaned.
• If the burner needs to be cleaned, it must be performed by a qualified service technician.
Sight Glass
Blue flame
The FT Series Floor Standing, Combination Boiler
Page 73
Page 74
SECTION 6. Parts List and Illustrations. CASE
FTCF140
16
15
16-1
16-2
1
16-3
15-1
16-4
16-5
16-6
17
15-2
16-7
16
15
18
19
20
35
21
22
23
36
25
26
37
24
38
28
29
27
40
41
42
43
31
44
32
30
45
34
33
39
The FT Series Floor Standing, Combination Boiler
1-Jul-15
For IOM
No.
1
15
15-1
15-2
16
16-1
16-2
16-3
16-4
16-5
16-6
16-7
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
2
4
Description
O-Ring, P7
Air Inlet Duct Assembly
Air Inlet Duct
Air Inlet Adaptor
Exhaust Vent Duct Assembly
Stainless band
Packing
Exhaust Vent Duct
Exhaust vent testing cap
O-Ring P85
Exhaust vent adaptor (out)
O-Ring P75
Top Access Panel
Bolt
Air Pressure Sensor
PCB
PCB Bracket
Terminal Block
Bracket
Control Display
Power switch
DHW Tank Cover bracket
Casing Shelf
Front Cover (upper)
Threaded Knob
Display cover/window
Air pressure switch
Pressure Gauge DHW 150 PSI
Pressure Gauge 60 PSI
Lower Front Cover
Case Assembly
Gas inlet connector
Wire adaptor
CH supply connector
CH Return sensor
CH return adaptor
DHW adaptor
Outlet sensor
DHW inlet connector
Stainless connector
Drain Adaptor
O-Ring P14
O-Ring P16
Part
Number
FT1601
FT1002
FT1611
FT1612
FT1010
FT1603
FT1604
FT1605
FT1606
FT1607
FT1608
FT1609
FT1613
FT1614
FT1015
FT1616
FT1617
FT1618
FT1619
FT1620
FT1020
FT1622
FT1623
FT1624
FT1625
FT1024
FT1627
FT1628
FT1629
FT1630
FT1631
FT1632
FT1633
FT1634
FT1635
FT1636
FT1637
FT1638
FT1639
FT1640
FT1641
FT1642
FT1643
Page 75
Page 76
Heat Exchanger
FTCF140
37
Wire adaptor
FT1633
38
CH supply connector
FT1634
39
CH
Return
sensor
FT1635
The FT Series Floor Standing, Combination
Boiler
40
CH return adaptor
FT1636
41
DHW adaptor
FT1637
42
Outlet sensor
FT1638
1-Jul-15
For IOM
43
DHW
inlet connector
FT1639
Part
44
Stainless connector
FT1640
No.
Description
Number
45
Drain Adaptor
FT1641
1
O-Ring,P14
P7
FT1601
2
O-Ring
FT1642
15
Air Inlet P16
Duct Assembly
FT1002
4
O-Ring
FT1643
15-1
Air Inlet P22
Duct
FT1611
6
O-Ring
FT1644
15-2
Air Inlet
Adaptor
FT1612
7
1/2"
Packing
FT1645
16
Exhaust
Vent Duct Assembly
FT1010
9
3/4"
Packing
FT1646
16-1
Stainless
band
FT1603
12
Flow
Sensor
Clip
FT1208
16-2
Packing
FT1604
59
Air
Vent Pipe
FT1648
16-3
Exhaust
Vent Duct
FT1605
62
Heat
Exchanger
bracket
FT1649
16-4
Exhaust
FT1606
63
Air
Vent vent testing cap
FT1321
16-5
O-Ring P85
FT1607
64
Exhaust
sensor
FT1307
16-6
vent adaptor
(out)
FT1608
65
Exhaust sensor
bracket
FT1652
16-7
O-Ring P75
FT1609
66
Bolt
FT1653
17
Top Access
FT1613
67
Exhaust
pipePanel
FT1654
18
Bolt Exchanger Assembly
FT1614
68
Heat
FT1655
19
Air Pressure
Sensor
FT1015
68-1
Burner
Assembly
FT1656
20
PCB
FT1616
68-2
Overheat
sensor
FT1310
21
PCB
Bracket
FT1617
68-3 Burner upper case
FT1658
22
Terminal paper
Block
FT1618
68-4
Ceramic
FT1659
23
Bracket
FT1619
68-5
Burner
FT1660
24
Control case
Display
FT1620
68-6
Burner
sealing O-Ring
FT1661
25
Power switch
FT1020
68-7
Ignitor
FT1315
26
DHW Tank
Cover bracket
FT1622
68-8
Burner
gasket
FT1663
27
Casing downside
Shelf
FT1623
68-9
Burner
case
FT1664
28
Front Cover (upper)
FT1624
68-10
Refractory
FT1665
29
ThreadedforKnob
FT1625
69
Packing
internal pipe (lower)
FT1666
30
Display
cover/window
FT1024
70
Low level sensor
FT1325
31
Air pressure
switch
FT1627
71
Flame
detector
sensor
FT1327
32
Pressure
GaugeBK
DHW 150 PSI
FT1628
72
Flame
detector
FT1669
33
Pressure
Gauge 60 PSI
FT1629
73
Temp.
sensor
FT1324
34
LowerforFront
Cover
FT1630
74
Pipe
internal
circulation (upper)
FT1671
35
Case Assembly
FT1631
75
Pump
FT1672
36
Gas inlet
connector
FT1632
76
Pipe
for internal
ciruculation (lower)
FT1673
37
Wireoutlet
adaptor
FT1633
77
CH
pipe (upper)
FT1674
38
supplypipe
connector
FT1634
78
CH return
(lower)
FT1675
39
CH
Return
sensor
FT1635
79
outlet pipe (lower)
FT1676
40
CH return
adaptor
FT1636
80
Clamp
Ø 34
FT1677
41
DHW adaptorhose (EPDM)
FT1637
81
Condensate
FT1678
42
Outlet sensor
FT1638
82
Clamp
Ø 40
FT1679
43
DHW
inlet
connector
FT1639
83
Condensate Trap Assembly
FT1328
44
Stainless connector
FT1640
84
Condensate
outlet hose
FT1681
45
Drain Adaptor
FT1641
85
Clamp
Ø 23
FT1682
2
O-Ring P14 outlet fitting
FT1642
86
Condensate
FT1683
4
P16
FT1643
2
O-Ring P14
FT1642
3
O-Ring P15
FT1685
4
O-Ring P16
FT1643
5
O-Ring P18
FT1687
6
O-Ring P22
FT1644
7
1/2" Packing
FT1645
8
3/4" Packing
FT1646
Page 77
Page 78
Domestic Hot Water
FTCF140
1-Jul-15
63
64
65
66
67
68
68-1
68-2
68-3
68-4
68-5
68-6
68-7
68-8
68-9
68-10
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
No.
86
2
1
3
15
4
15-1
5
15-2
6
16
7
16-1
8
16-2
9
16-3
13
16-4
14
16-5
46
16-6
47
16-7
48
17
49
18
50
19
51
20
52
21
53
22
54
23
55
24
56
25
57
26
58
27
59
28
60
29
61
30
10
31
11
32
87
33
88
34
89
Air Vent
Exhaust sensor
Exhaust sensor bracket
Bolt
Exhaust pipe
Heat Exchanger Assembly
Burner Assembly
Overheat sensor
Burner upper case
Ceramic paper
Burner
Burner case sealing O-Ring
Ignitor
Burner gasket
Burner downside case
Refractory
Packing for internal pipe (lower)
Low level sensor
Flame detector sensor
Flame detector BK
Temp. sensor
Pipe for internal circulation (upper)
Pump
Pipe for internal ciruculation (lower)
CH outlet pipe (upper)
CH return pipe (lower)
CH outlet pipe (lower)
Clamp Ø 34
Condensate hose (EPDM)
Clamp Ø 40
Condensate Trap Assembly
For
IOM
Condensate
outlet hose
Clamp Ø 23
Description
Condensate outlet fitting
O-Ring
O-Ring,P14
P7
O-Ring
Air Inlet P15
Duct Assembly
O-Ring
Air Inlet P16
Duct
O-Ring
Air Inlet P18
Adaptor
O-Ring
ExhaustP22
Vent Duct Assembly
1/2"
Packing
Stainless
band
3/4"
Packing
Packing
1"
Packing
Exhaust
Vent Duct
Clip
for Cold
inlet
Exhaust
ventwater
testing
cap1
Clip
for
Cold
water
inlet
2
O-Ring P85
DHW
Tank
Exhaust vent adaptor (out)
Temperature
O-Ring P75 sensor
DHW
Tank bracket
Top Access
Panel
Stainless
band
Bolt
Water
Storage
Tank Cover
Air Pressure
Sensor
DHW
Outlet
Pipe
PCB
15
O-Ring
adapter
PCB
Bracket
Mixing
valve
Terminal
Block
16
O-Ring adapter
Bracket
Cold
water
inlet pipe
Control
Display
18
O-Ring
adapter
Power switch
Flow sensor
DHW Tank Cover bracket
Storage tank outlet pipe
Casing Shelf
Drain Pipe connector
Front Cover (upper)
Drain valve
Threaded Knob
Drain Pipe connector
Display cover/window
Packing 1
Air pressure switch
Packing 2
Pressure Gauge DHW 150 PSI
Intake Hose
Pressure Gauge 60 PSI
Intake silicon adaptor
Lower Front Cover
Fan Assembly
FT1321
FT1307
FT1652
FT1653
FT1654
FT1655
FT1656
FT1310
FT1658
FT1659
FT1660
FT1661
FT1315
FT1663
FT1664
FT1665
FT1666
FT1325
FT1327
FT1669
FT1324
FT1671
FT1672
FT1673
FT1674
FT1675
FT1676
FT1677
FT1678
FT1679
FT1328
FT1681
Part
FT1682
Number
FT1683
FT1642
FT1601
FT1685
FT1002
FT1643
FT1611
FT1687
FT1612
FT1644
FT1010
FT1645
FT1603
FT1646
FT1604
FT1691
FT1605
FT1692
FT1606
FT1693
FT1607
FT1694
FT1608
FT1695
FT1609
FT1696
FT1613
FT1697
FT1614
FT1698
FT1015
FT1699
FT1616
FT1700
FT1617
FT1116
FT1618
FT1702
FT1619
FT1703
FT1620
FT1704
FT1020
FT1115
FT1622
FT1706
FT1623
FT1648
FT1624
FT1708
FT1625
FT1709
FT1024
FT1710
FT1627
FT1710
FT1628
FT1712
FT1629
FT1713
FT1630
FT1714
The FT Series Floor Standing, Combination Boiler
Blower
FTCF140
1-Jul-15
9
13
14
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
No.
61
1
10
15
11
15-1
87
15-2
88
16
89
16-1
89-1
16-2
89-2
16-3
89-3
16-4
89-4
16-5
89-5
16-6
90
16-7
91
17
92
18
92
19
93
20
94
21
94-1
22
94-2
23
94-3
24
94-4
25
95
26
96
27
28
29
1" Packing
Clip for Cold water inlet 1
Clip for Cold water inlet 2
DHW Tank
Temperature sensor
DHW Tank bracket
Stainless band
Water Storage Tank Cover
DHW Outlet Pipe
15 O-Ring adapter
Mixing valve
16 O-Ring adapter
Cold water inlet pipe
18 O-Ring adapter
Flow sensor
Storage tank outlet pipe
For
IOM
Drain
Pipe connector
Drain valve
Description
Drain Pipe connector
O-Ring, P7
Packing
1
Air Inlet Duct
Assembly
Packing
2
Air InletHose
Duct
Intake
Air Inletsilicon
Adaptor
Intake
adaptor
Exhaust
Vent Duct Assembly
Fan
Assembly
Stainless band
Fan
Packing
Fan
sealing O-Ring
Exhaust
Vent Duct
Air
Gas Mixer
Exhaust
vent testing cap
Intake
Orifice
O-Ring P85
Bolt
Exhaust
vent adaptor (out)
Mesh
(screen)
O-Ring
P75
Rubber gasket
Top Access
Panel
Nozzle
NG (Natural)
Bolt
Nozzle
LP (Propane)
Air Pressure
Sensor
Gas
pipe (upper)
PCB Valve Assembly
Gas
PCB Valve
Bracket
Gas
Terminal
Gas
ValveBlock
bracket
Bracket
Gas
valve O-Ring
Control
Display
Gas
valve
inlet adaptor
Power
switch
Gas pipe (lower)
DHW Tank
Cover bracket
Ignition
Transformer
Casing Shelf
Front Cover (upper)
Threaded Knob
FT1691
FT1692
FT1693
FT1694
FT1695
FT1696
FT1697
FT1698
FT1699
FT1700
FT1116
FT1702
FT1703
FT1704
FT1115
FT1706
FT1648
Part
FT1708
Number
FT1709
FT1601
FT1710
FT1002
FT1710
FT1611
FT1712
FT1612
FT1713
FT1010
FT1714
FT1603
FT1715
FT1604
FT1716
FT1605
FT1717
FT1606
FT1718
FT1607
FT1719
FT1608
FT1720
FT1609
FT1721
FT1613
FT1722
FT1614
FT1722P
FT1015
FT1723
FT1616
FT1724
FT1617
FT1725
FT1618
FT1726
FT1619
FT1727
FT1620
FT1728
FT1020
FT1729
FT1622
FT1016
FT1623
FT1624
FT1625
Page 79
Page 80
CASE
FTCF199
13
12
12-1
12-2
12-4
13-1
12-3
12-5
12-6
12-7
No.
Description
Part #
12
Exhaust Vent Duct Assembly
FT1010
12-1
Stainless band Ø100 (16-1)
FT1603
12-2
Duct Packing (larger)
FT1604
12-3
Exhaust Vent Duct
FT1605
12-4
O-Ring P7
FT1601
12-5
Exhaust testing cap(16-4)
FT1606
12-6
O-Ring P85
FT1607
12-7
Port adaptor
FT1608
12-8
O-Ring P7
FT1609
12-8
13
14
B-26
B-6
12
B-6
B-5
15
B-3
16
B-3
17
B-23
B-4
32
18
19
20
31
B-8
33
26
B-24
25
27
B-3
22
21
B-23
B-3
B-23
36
B-13
B-23
23
37
B-23
24
B-3
38
28
39
B-23
29
34
35
B-7
40
30
Q’ty
Pr
1
$7
5
$1
Page 81
The FT Series Floor Standing, Combination Boiler
No.
Description
Part #
Q’ty
Price
13
Air Inlet Duct Assembly
FT1002
1
$8.50
Air inlet Duct
FT1611
14
Top access panel
FT1613
15
Air pressure sensor
FT1804
16
Bracket
FT1617
17
Control (PCB)
FT1616
1
$55.0
18
Terminal blocks
FT1827
1
$2.0
19
Bracket
FT1619
20
Power switch
FT1020
5
$2.0
21
Brackets
FT1828
22
Control Display
FT1620
1
$20.0
23
Bracket
FT1828
24
Air pressure switch
FT1627
1
$4.0
25
Front cover (upper)
FT1829
26
Threaded Knob
FT1830
27
Display cover/window
FT1024
28
Pressure gauge DHW 150 PSI
FT1628
5
$10.0
29
Pressure gauge 60 PSI
FT1629
5
$10.0
30
Front lower cover
FT1831
31
Case Assembly
FT1832
32
Gas inlet connector
FT1632
33
Wire adaptor
FT1633
34
CH supply connector
FT1634
5
$3.5
35
CH Return sensor
FT1635
36
CH return adaptor
FT1636
1
$3.5
37
Outlet sensor
FT1638
5
$3.0
38
DHW connector
FT1637
1
$5.0
39
Cold water inlet connector
FT1639
1
$5.0
40
Stainless connector
FT1640
5
$5.0
41
Drain adaptor
FT1641
1
$2.0
13-1
Heat Exchanger & Pump_
Page 82
Feature&List
Heat Exchanger
FTCF199
No.
Description
Part #
1
O-Ring P7
FT1601
3
O-Ring P16
FT1643
5
O-Ring P 22
FT1644
Q’ty
Price
nsor
Page 83
The FT Series Floor Standing, Combination Boiler
No.
Description
Part #
Q’ty
Price
1
O-Ring P7
FT1601
3
O-Ring P16
FT1643
5
O-Ring P22
FT1644
8
1" Packing
FT1691
10
Description
Clip
for flow sensor
Part #
FT1208
Q’ty
Price
56
Exhaust sensor
FT1307
5
$5.0
57
Exhaust sensor bracket
FT1306
58
Exhaust adaptor
FT1784
59
Exhaust pipe
FT1823
1
$9.0
60
packing for internal pipe (bottom)
FT1836
61
Heat exchanger
FT1837
1
$55.0
5
$3.50
1
$15.0
61-1 Burner Assembly
FT1796
61-2 Burner upper case
FT1760
61-3 Burner packing
FT1824
61-4 Burner
Ft1838
61-5 Ignitor
FT1763
61-6 Burner gasket
FT1663
61-7 Overheat sensor
FT1310
61-8 Burner lower side case
FT1764
61-9 Refractory
FT1826
62
Flame detector
FT1669
63
Flame sensor cover
FT1069
64
Infrared light sensor
FT1327
65
Low level sensor
FT1325
66
Temperature Sensor
FT1324
67
Pipe for internal circulation (upper)
68
Circulation pump
FT1839
69
Pipe for internal circulation (lower)
FT1840
1
$12.0
70
CH return pipe (lower)
FT1841
1
$11.0
71
CH return pipe (upper)
FT1842
72
CH outlet pipe (lower)
FT1843
1
$11.0
73
Clamp Ø34
FT1677
74
Condensate EPDM hose
Q’ty 5
$2.0
75
Clamp Ø40
76
Condensate trap
1
$35.0
10
$2.0
5
$14.0
Part #
FT1601
FT1643
76-1 Condensate trap brackets
77
Condensate outlet hose
78
Clamp Ø 23
Condensate hose adaptor
(condensate outlet fitting)
79
FT1644
FT1691
FT1208
FT1844
Price
FT1679
FT1328
FT1845
FT1681
FT1682
FT1683
Page 84
Domestic Hot Water
FTCF199
DHW Tank _
DHW Tank _
List
No.
Description
Part #
2
O-Ring P15
FT1685
3
O-Ring P16
FT1643
4
O-Ring P18
FT1687
6
1/2" packing
FT1645
Q’ty 7
Price
3/4"
packing
FT1646
List
Q’ty
No.
Description
Part #
2
O-Ring P15
FT1685
8
1" packing
FT1691
3
O-Ring P16
FT1643
10
Clip for flow sensor
FT1208
4
O-Ring P18
FT1687
11
Clip for Cold water / outlet
FT1692
6
1/2" packing
FT1645
42
DHW Tank
FT1694
7
3/4" packing
FT1646
43
DHW Tank bracket
FT1696
8
1" packing
FT1691
44
Stainless band
FT1697
10
10
Clip for flow sensor
FT1208
45
Temperature sensor
FT1695
5
11
Clip for Cold water / outlet
FT1692
46
Water storage tank cover
FT1698
1
42
DHW Tank
FT1694
47
Air vent
FT1321
43
DHW Tank bracket
FT1696
48
Upper pipe for internal circulation
FT1833
1
44
Stainless band
FT1697
10
45
Temperature sensor
FT1695
5
FT1834
1
46
Water storage tank cover
FT1698
1
47
Air vent
FT1321
48
Upper pipe for internal circulation
FT1833
1 53
49
DHW outlet pipe
FT1834
1 54
50
Mixing valve
FT1701
55
51
Cold water inlet pipe
FT1835
52
Flow sensor
FT1115
1
51
$0.5
DHW outlet pipe
$3.0
Mixing valve
$5.0
Cold water inlet pipe
52
Flow sensor
FT1115
$12.0
Drain
pipe connector
FT1648
1
½”$5.5
Ball valve
FT1708
1
Drain pipe
FT1709
1
49
50
$5.5
FT1701
FT1835
1
Page 85
The FT Series Floor Standing, Combination Boiler
Blower
FTCF199
Fan & Gas Valve _
No.
Fan & Gas Valve _
No.
Description
List
Part #
Description
List
Part #
Q’ty
9
1/2" Packing
FT1710
10
80
Fan Guide
FT1769
3
81
Flapper Packing
FT1770
5
82
Damper Body
FT1081
5
83
Air Blow Rubber Pad
FT1082
5
84
Fan Guide Packing
FT1772
5
85
Fan Assembly
FT1799
1
85-1 Fan
FT1803
1
85-2 Fan Sealing O-Ring
ST1038
5
85-3 AGM Venturi
FT1773
85-4 AGM O-Ring
FT1774
10
85-5 AGM Body
FT1775
1
Q’ty 86
Price
Stainless Band Ø100
FT1603
9
1/2" Packing
FT1710
10
87
$0.5 Hose
Intake
FT1846
1
80
Fan Guide
FT1769
3
88
$5.5
Stainless
Band Ø89
FT1777
10
81
Flapper Packing
FT1770
5
89
$0.3 Hose Distributor
APS
FT1821
82
Damper Body
FT1081
5
90
$1.0Valve Assembly
Gas
FT1847
83
Air Blow Rubber Pad
FT1082
5
$0.5Valve bracket
90-1 Gas
FT1848
84
Fan Guide Packing
FT1772
5
$0.5Inlet Adaptor
90-2 Gas
FT1417
3
85
Fan Assembly
FT1799
1
90-3 $42.0
Gas Valve O-ring
FT1727
10
85-1 Fan
FT1803
FT1416
1
85-2 Fan Sealing O-Ring
ST1038
90-4 $22.0
Gas Valve
$0.5
5 90-5 Gas Outlet Adaptor
FT1414
3
85-3 AGM Venturi
FT1773
85-4 AGM O-Ring
FT1774
10
85-5 AGM Body
FT1775
1
1
86
Stainless Band Ø100
FT1603
87
Intake Hose
FT1846
1
88
Stainless Band Ø89
FT1777
10
89
APS Hose Distributor
FT1821
Nozzle, Natural
FT1780
Nozzle,
$0.3 Propane
FT1802
92
Gas pipe 1
$10.0
FT1849
1
93
Gas pipe 2
FT1850
1
94
Ignition Transformer
$3.0
ST1006
1
91
$0.3
Notes:
For Product and
Service VIDEOS
H2373000C
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
20 Industrial Way, Rochester, NH, USA 03867
1708 Document 1320C

advertisement

Related manuals

advertisement