OUTDOOR UNITS SDV5-XXXEAI
COMMERCIAL AIR CONDITIONERS SDV5
Original instructions
IMPORTANT NOTE:
Read this manual carefully before installing or operating
your new air conditioning unit. Make sure to save this
manual for future reference.
CONTENTS
If this unit exhibits any abnormal behavior (such as emitting
smoke) there is danger of serious injury or death. Disconnect
the power supply and contact your dealer or service engineer
immediately.
PAGE
IMPORTANT SAFETY INFORMATION.................................................... 1
PARTS NAMES...................................................................................... 2
This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have
been given supervision or instruction concerning
OPERATION AND PERFORMANCE......................................................... 2
TROUBLES AND CAUSES...................................................................... 3
MALFUNCTION..................................................................................... 4
use of the appliance in a safe way and understand the hazards
involved.
Button FUNCTION.................................................................................. 5
AFTER-SALES SERVICE........................................................................ 8
1.
If sufficient quantity of refrigerant leaks into a room oxygen
levels can fall dangerously low, which can cause serious injury
or death. The refrigerant used in this unit is heavier than air, so
this danger can be greater in basements or other underground
spaces. In the event of refrigerant leakage contact your dealer
or service engineer immediately.
IMPORTANT SAFETY INFORMATION
Do not use paint, varnish, hair spray, other flammable sprays or
other liquids that may give off flammable fumes/vapor near this
unit, as doing so can cause fire.
To gain full advantage of the unit’s functions and to avoid malfunction
due to mishandling, we recommend that you read this instruction
manual carefully before use.
Do not touch the unit with wet or moist hands, as doing so can
lead to electric shock.
Take anti-lightning measures in areas subject to thunderstorms.
The precautions described herein are classified as WARNING and
CAUTION. They both contain important information regarding safety.
Be sure to observe all precautions without fail.
This appliance is intended to be used by expert or trained users
in shops, in light industry and on farms, or for commercial use
by lay persons
WARNING
Failure to follow these instructions properly may result in
personal injury or loss of life.
CAUTION
CAUTION
This unit is designed to provide space cooling and/or
space heating in spaces designed for human occupation
and should only be used for these purposes. This unit
should not be used to provide refrigeration or cooling for
food, plants, animals, machinery, equipment or artworks.
Failure to observe these instructions properly may result in
property damage or personal injury, which may be serious
depending on the circumstances.
After reading, keep this manual in convenient place so that you can
refer to it whenever necessary. If the equipment is transferred to a
new user, be sure also to hand over the manual.
Ask your supplier or installation engineer for guidance
about cleaning the unit. Incorrect cleaning methods can
damage plastic components, which can lead to electric
shock or leakage of water. Disconnect the power supply
before wiping or dusting the unit, otherwise electric shock
or injury may result. Use a dry or slightly damp cloth only
when wiping or dusting the unit. Do not use a wet cloth,
as doing so can lead to electric shock or fire.
WARNING
This unit should only be serviced and maintained by a
professional air conditioning service engineer. Incorrect
servicing or maintenance can cause electric shock, fire or
leakage of water. Contact your dealer for servicing and
maintenance.
Do not insert fingers or other objects into the unit’s air
inlet or air outlet, as touching the fan can cause injury or
damage equipment.
The appliance must be installed in accordance with national
wiring regulations.
Do not remove the unit’s panel as doing so causes
danger when the fan is operating at high speed.
Ensure that the power supply is disconnected before any
servicing or maintenance is carried out.
The fins on the unit’s heat exchanger are sharp and can
cause injury if touched. When the unit is being serviced,
gloves should be worn or the heat exchanger should be
covered to prevent injury.
Ensure that the unit is properly grounded, otherwise electric
shock or fire may result. Electrical surges (such as those that
can be caused by lightning) can damage electrical equipment.
Ensure that suitable surge protectors and circuit breakers are
properly installed, otherwise electric shock or fire may result.
After long-term use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.
When replacing a fuse, ensure that the replacement fuse is of
the correct rating.
Arrange the drain hose to ensure smooth drainage.
Incomplete drainage may cause the building or furniture
to become wet.
Do not attempt to inspect or repair this unit yourself. Engage a
professional air conditioning engineer to carry out all servicing
and maintenance.
1
Ensure the air inlet and outlet are not blocked or performance
may suffer or it may activate protection, which will stop the
unit from running.
3.
OPERATION AND PERFORMANCE
The cooling and heating operation in a VRF system
In extremely strong winds, please prevent the air from flowing
backwards into the outdoor unit.
● Each indoor unit can be controlled alone. The indoor units in the
same system cannot run cooling and heating at the same time.
Choose an appropriate place where the noise and hot or cold
wind blown out of the outdoor unit will not cause
inconvenience to your neighbors or affect the growth of an
animal or plant.
● Explanation of priority mode operation
Priority mode can only be set on the master unit. When an indoor
unit is in mode conflict with the outdoor units the unit displays the
mode conflict error.
Do not place appliances that have naked flames under or
near the unit, as heat from the appliance can damage the
unit.
1.
Auto priority mode (default): In auto priority mode, the
outdoor unit will operate in heating priority mode or cooling
priority mode according to the outdoor ambient temperature.
Do not allow children to play near this unit, as doing so risks
injury.
2.
Heating priority mode:
a)
During cooling operation: If an indoor unit requests
heating, the outdoor units stop and then restart in
heating mode after 7 minutes. Indoor units requesting
heating then start in heating mode and indoor units
requesting cooling display the mode conflict error.
b)
During heating operat ion: If an indoor unit requests
cooling, the outdoor units ignore the request and
continue to run in heating mode. The indoor unit
requesting cooling displays the mode conflict error. If all
the indoor units requesting heating are later turned off
and one or more indoor units are still requesting cooling,
the outdoor units restart in cooling mode after 7 minutes
and any indoor units requesting cooling then start in
cooling mode.
This unit should not be operated by children or by adults that
are not capable of operating the unit safely.
When disposing of this unit, ensure that all applicable
legislation regarding the disposal of refrigerant, oil and other
materials is adhered to.
Leave the power on for a minimum of 12 hours prior to
running the system to ensure that the crankcase heaters
have heated the compressor oil sufficiently.
3.
2.
PARTS NAMES
4
4
1
1
3
1
2
Refrigerant piping and wiring connection port
3
Fixed foot
4
Air outlet
NOTE
All pictures in this manual are for explanation purposes only.
They may be slightly different from the air conditioner you
purchased (depend on model).
2
During heating operation: If an indoor unit requests
cooling, the outdoor units stop and then restart in
cooling mode after 7 minutes. Indoor units requesting
cooling then start in cooling mode and indoor units
requesting heating display the mode conflict error.
b)
During cooling operation: If an indoor unit requests
heating, the outdoor units ignore the request and
continue to run in cooling mode. The indoor unit
requesting heating displays the mode conflict error. If all
the indoor units requesting cooling are later turned off
and one or more indoor units are still requesting heating,
the outdoor units restart in heating mode after 7 minutes
and any indoor units requesting heating then start in
heating mode.
VIP priority mode or voting priority mode : 63 is the VIP
address. If the VIP indoor unit is operating, the outdoor units
operate in the mode of the VIP indoor unit. Indoor units that
are in a mode different to that of the VIP unit display the mode
conflict error. If there is no unit with address 63 or the unit at
address 63 is in standby, the outdoor units operate in voting
priority mode. In voting priority mode, the outdoor units
operate in whichever of heating and cooling modes is being
requested by the larger number of indoor units.
5.
Heating only mode : The outdoor units only operate in
heating mode. Indoor units requesting heating operate in
heating mode. Indoor units requesting cooling or in fan only
mode display the mode conflict error.
6.
Cooling only mode: The outdoor units only operate in
cooling mode. Indoor units requesting cooling operate in
cooling mode; indoor units in fan only mode operate in fan
only mode. Indoor units requesting heating display the mode
conflict error.
Fig.2-1
Air inlets (left, right, rear and front ( 24-32HP )
a)
4.
2
1
Cooling priority mode:
4.
Explanation of heating operation
● It may take longer to reach the set temperature for general
heating operation than for cooling operation.
TROUBLES AND CAUSES
CAUTION
The following operation is performed in order to prevent the
heating capacity from dropping or cold air from blowing
This unit should only be serviced and maintained by a
professional air conditioning service engineer. Incorrect
servicing or maintenance can cause electric shock, fire or
leakage of water. If the unit displays protection or error code,
contact your dealer for servicing and maintenance.
● Defrost operation
a) When the system is running in heating mode, the outdoor unit
may frost in low ambient temperature. To increase efficiency,
the unit will start defrosting automatically (after 2-10 minutes),
and then water will drained out from the outdoor unit.
b) In order to prevent cold air from blowing out of an indoor unit
at the start of heating operation, the indoor fan is automatically stopped. It may take some time before the fan starts. This is
not a malfunction.
Please read following information before asking for maintenance.
4.1 Symptoms that are not air conditioner troubles
Symptom 1: Outdoor unit makes a hiss noise
Protection mode
● In protection mode the system will stop automatically and the
outdoor main PCB will display the specified protection code. If
the unit displays protection or error code, contact your dealer for
servicing and maintenance.
● A slight hiss noise is caused by the heat-expansion and
cold-contraction of the heat exchanger as the temperature
changes.
● At the beginning or end of the defrosting process, a slight
hiss noise is caused by the four-way valve action.
● Error
When the system has error, the system will stop automatically
and the outdoor main PCB will display the specified error code. If
the unit displays protection or error code, contact your dealer for
servicing and maintenance.
● At the beginning or end of the running process, a sound
like water flowing in the valve occurs, which will be
amplified after 3-15 minutes. This sound may be caused by
refrigerant flow or discharge the drain water.
NOTE
Symptom 2: Outdoor unit heat exchanger discharge mist or water
Please switch off the power supply when protection or error
occurs. Do not restart until the problems are solved.
● Outdoor unit is defrosting.
Symptom 3: Indoor unit emit foreign smell
● The foreign smell is from indoor furniture, cigarettes or
cosmetics which adhere to the unit.
Operation range
Use the system in the following temperature and humidity ranges
for safe and effective operation.
Symptom 4: Indoor unit operation indicator flash
● Power supply resumes after an abnormal power off
Table.3-1
Temperature
Outdoor
temperature
Indoor
temperature
Cooling mode
-5°C ~ 48°C
17°C ~ 32°C
Heating mode
-23°C ~ 24°C
15°C ~ 30°C
Mode
● In mode conflict
Indoor room’s
relative
humidity
● Fan stops to prevent sending cold air
Symptom 5: Automatically start-up or stop
Room
below 80%
● Timer setting is activated.
Symptom 6: System does not operate
● Power supply is off
● Power manual switch is off
NOTE
● Fuse is blown
The temperature should below 55°C during transporing
● Timer setting time is activated
The protection function may occur if the unit operates beyond
above conditions, the unit will stop running.
Symptom 7: Insufficient cooling or heating capacity
● Dirty heat exchanger
● Unit inlet, outlet or filter is blocked
● Fan speed is low
● In fan only mode
● Temperature setting is not suitable
3
5.
MALFUNCTION
Malfunction display of the outdoor unit’s DSP1
Error
code
Table.5-1
Error description
Remarks
E0
Communication error between outdoor units
Only displayed on the slave unit with the error
E1
Phase sequence error
E4
Communication error between indoor and
master unit
T3/T4 Temp. sensor error
Displayed on the unit with the error
E2
E5
Abnormal power supply voltage
Displayed on the unit with the error
E6
Reserved
Reserved
E7
Discharge Temp. sensor error
Displayed on the unit with the error
E8
Only displayed on the master unit with the error
Displayed on the unit with the error
Outdoor unit address error
Displayed on the unit with the error
xE9
EEPROM mismatch of compressor
Displayed on the unit with the error
xF1
DC bus voltage error
Displayed on the unit with the error
F3
T6B Temp. sensor error
Displayed on the unit with the error
F5
T6A Temp. sensor error
Displayed on the unit with the error
F6
Electronic expansion valve connection error
Displayed on the unit with the error
Displayed on the unit with the error
H2
Communication error between main board
and compressor drive board
Qty. of outdoor unit decreases error
H3
Qty. of outdoor unit increases error
Only displayed on the master unit with the error
Inverter-module protection
Displayed on the unit with the error
H5
3 times of P2 protection in 60 minutes
Displayed on the unit with the error
H6
3 times of P4 protection in 100 minutes
Displayed on the unit with the error
H7
Qty. of indoor units mismatching
Only displayed on the master unit with the error
H8
High pressure sensor error
Displayed on the unit with the error
H9
10 times of P9 protection in 120 minutes
Displayed on the unit with the error
yHd
Slave unit malfunction(y=1,2 . e.g ,1Hd
stands for slave unit 1 error)
Only displayed on the master unit with the error
C7
3 times of PL protection in 100 minutes
Displayed on the unit with the error
xH0
xH4
P1
P2
xP3
Only displayed on the master unit with the error
High pressure protection or discharge
Temp. switch protection
Low pressure protection
Displayed on the unit with the error
Displayed on the unit with the error
Compressor current protection
Displayed on the unit with the error
P4
Discharge Temp. protection
Displayed on the unit with the error
P5
High Temp. protection of condenser
Displayed on the unit with the error
xP9
Fan module protection
Displayed on the unit with the error
xPL
Inverter module Temp. protection
Displayed on the unit with the error
xL0
Compressor discharge insufficient superheat
protection
Inverter compressor module error
xL1
DC bus low voltage protection
Displayed on the unit with the error
xL2
DC bus high voltage protection
Displayed on the unit with the error
PP
Displayed on the unit with the error
Displayed on the unit with the error
XL4
MCE error
Displayed on the unit with the error
xL5
Zero speed protection
Displayed on the unit with the error
xL7
Phase sequence protection
Displayed on the unit with the error
xL8
xL9
Compressor frequency variation greater than
15Hz within one second protection
Actual compressor frequency differs from target
frequency by more than 15Hz protection
Displayed on the unit with the error
Displayed on the unit with the error
Note:
1. 'x' is a placeholder for the compressor system (compressor and related electrical components),with 1 representing compressor system A and 2 representing
compressor system B. 'y' is a placeholder for the address (1or2) of the slave unit with the error.
2. For some error codes,a manual restart is required before the system can resume operation.
4
6.
BUTTON FUNCTION
DSP1
SW5
MENU
Table 6-1
MENU
DSP2
SW4
DOWN
SW3
UP
SW6
OK
6.1 Button switch function
1) MENU: Long press 5 seconds to enter menu function mode,
short press return to the previous menu
2) OK:Short press to enter the next level menu or confirm the
selection
3) UP/DOWN:
a) Select different menus in menu function mode.
b) System check when it is not menu function mode.
6.2 Menu function mode
Only master unit has the full menu functions, slaves units only
have error codes check and cleaning menu functions.
1. Long press “MENU” button 5 seconds, then display “n1”, and
enter the menu function mode.
a) Use “UP” and “DOWN” to select a different level 1 menu
(for example,n3)
b) Press “OK” to enter a level 2 menu (for example,n31)
2. At level 2 menu status
a) Use “UP” and “DOWN” to select different level 2 menu (for
example,n32)
b) Use “OK” to confirm the specified level 2 menu
Description
Note
n14
Debug mode 1
1
n15
Debug mode 2
2
n16
Maintenance mode
3
n24
Reserved
n25
Reserved
n26
Backup run
n27
Vacuum mode
n31
History codes
n32
Cleaning history error
n33
Reserved
n34
Restore factory settings
5
n41
Power limitation mode 1
6
n42
Power limitation mode 2
7
n43
Power limitation mode 3
8
n44
Power limitation mode 4
9
n45
Power limitation mode 5
10
n46
Power limitation mode 6
11
n47
Power limitation mode 7
12
nb1
Fahrenheit degree (°F)
Only available for master unit
nb2
Celsius degree (°C)
Only available for master unit
nb3
Exit auto power save mode
Only available for master unit
nb4
Enter auto power save mode
Only available for master unit
nb5
Auto snow-blowing mode 1
nb6
Auto snow-blowing mode 2
nb7
Exit auto snow-blowing mode
nb8
VIP address setting
nF1
Reserved
nF2
Reserved
4
Display“R006”
1
Only available for master unit(all indoor units running in cooling mode)
2
Only available for master unit(if all the indoor unit in the system are the
2nd generation indoor units, all the indoor units will run in heating mode.
Once there is one or more old indoor unit in the system, all the indoor
units will run in force cooling mode)
Only available for the master unit, the system does not check the indoor
units’ number.
4 Only available for outdoor unit with two compressors. If one of the two
compressors is fail, the other compressor will keep running for up to 4
days and then stop automatically.
3
5
Only available for the master unit
6
Only available for the master unit, 100% capacity output
7
Only available for the master unit, 90% capacity output
Only available for the master unit, 80% capacity output
Only available for the master unit, 70% capacity output
Only available for the master unit, 60% capacity output
Only available for the master unit, 50% capacity output
Only available for the master unit, 40% capacity output
8
9
10
11
12
5
Menu function mode flowchart
Start
Press “menu”
Long press “menu” 5 seconds
Display “-n1”
Press “up” or “down” to choose “X”
Display “-nX”
Press “menu”
Press “OK” to confirm “X”
Press “OK” to confirm “Y”
Press “menu”
Press “menu”
Press “up” or “down” to choose “Y”
Display “-nXY”
Press “OK” to confirm “Y”
Press “OK” to confirm “Y”
Display “-nXY”
Confirm “-nXY”
6
6.3 System check table
Press UP/DOWN button to enter system check mode when it is not in menu function mode.
DSP1
content
Remarks
Parameters displayed on DSP2
0
Unit address
1
Unit capacity
Table 6-2
0-2
8-32HP
2
Number of outdoor units
1
3
Number of indoor units as set on PCB
1
4
Total capacity of outdoor unit
2
5
Total capacity requirement of indoor units
1
6
Total capacity requirement correction of master unit
1
7
Operating mode
3
8
9
Outdoor unit actual operating capacity
Fan A speed index
10
Fan B speed index
11
T2/T2B average Temp (°C)
12
Main heat exchanger pipe(T3) temperature (°C)
13
Outdoor ambient(T4) temperature (°C)
14
Plate heat exchanger cooling refrigerant inlet (T6A) temperature (°C)
15
Plate heat exchanger cooling refrigerant outlet (T6B) temperature (°C)
16
Discharge Temp. of compressor A (°C)
17
Discharge Temp. of compressor B (°C)
18
Inverter-module heatsink Temp. A (°C)
19
Inverter-module heatsink Temp. B (°C)
20
Plate exchanger degree of superheat (°C)
21
Discharge superheat degree
22
Inverter compressor A current (A)
23
Inverter compressor B current (A)
24
EXVA position
4
25
EXVB position
4
26
EXVC position
5
27
Compressor discharge pressure (MPa)
28
Reserved
29
Number of indoor units currently in communication with master unit
30
Number of indoor units currently operating
1
31
Priority mode
7
32
Silent mode
8
33
Static pressure mode
9
34
Reserved
35
Reserved
36
DC bus voltage A
10
37
DC bus voltage B
10
38
Reserved
39
Address of VIP indoor unit
40
Reserved
41
Reserved
42
Refrigerant state
43
Reserved
44
Power mode
45
Most recent error or protection code
--
6
Reserved
11
12
Check end
--
7
1
2
3
4
5
6
7
8
9
10
11
12
7.
Available for master unit
Only available for master unit, displayed on slave units has no
sense;
Operation mode: 0-OFF; 2-Cooling; 3-Heating;4-Forced cooling
Opening angle of EEV: Actual value=Display value*4(480P) or
Actual value=Display value*24(3000P)
Opening angle of EEV: Actual value=Display value*4(480P)
High pressure: Actual value=Display value*0.1MPa
Priority mode: 0-Auto priority, 1-cooling priority, 2-VIP priority or
voting priority, 3-Heating only, 4-Cooling only
Silent mode: 0-Night silent time is 6h/8h, 1-Night silent time is
6h/12h, 2-Night silent time is 8h/10h, 3-Night silent time is
8h/12h, 7-Silent mode 3,8-Super silent mode 1, 9-Super silent
mode 2, 10-Super silent mode 3, 11-Super silent mode 4;
Static pressure mode: 0-Standard static pressure, 1-Low Static
pressure, 2-Medium static pressure, 3-High static pressure,
4-Super high static pressure;
DC bus voltage: Actual value=Display value*10 V
Refrigerant quantity: 0-Normal, 1-Slightly excessive, 2-Significantly excessive, 11-Slightly insufficient, 12-Significantly
insufficient, 13-Critically insufficient.
0-100% capacity output, 1-90% capacity output, 2-80% capacity
output, 3-70% capacity output, 4- 60% capacity output, 5-50%
capacity output, 6- 40% capacity output. 10-Auto power save
mode, 100% capacity output. 11-Auto power save mode, 90%
capacity output, 12-Auto power save mode, 80% capacity
output, 13-Auto power save mode, 70% capacity output,
14-Auto power save mode, 60% capacity output, 15-Auto power
save mode, 50% capacity output, 16-Auto power save mode,
40% capacity output.
AFTER-SALE SERVICE
This unit should only be serviced and maintained by a professional
air conditioning service engineer. Incorrect servicing or maintenance
can cause electric shock, fire or leakage of water. If the unit displays
protection or error code, contact your dealer for servicing and
maintenance.
NOTE
The temperature should below 55°C during transporing
The protection function may occur if the unit operates beyond
above conditions, the unit will stop running.
8