- Industrial & lab equipment
- Measuring, testing & control
- Danfoss
- VLT AutomationDrive FC 302
- Operating instructions
advertisement
▼
Scroll to page 2
of
158
ENGINEERING TOMORROW Operating Guide VLT® AutomationDrive FC 302 90–315 kW, Enclosure Size D1h–D8h vlt-drives.danfoss.com Contents Operating Guide Contents 1 Introduction 4 1.1 Purpose of the Manual 4 1.2 Additional Resources 4 1.3 Manual and Software Version 4 1.4 Approvals and Certifications 4 1.5 Disposal 4 2 Safety 5 2.1 Safety Symbols 5 2.2 Qualified Personnel 5 2.3 Safety Precautions 5 3 Product Overview MG34U502 7 3.1 Intended Use 7 3.2 Power Ratings, Weight, and Dimensions 7 3.3 Interior View of D1h Drive 9 3.4 Interior View of D2h Drive 10 3.5 View of Control Shelf in D1h–D8h Drives 11 3.6 Extended Options Cabinets 12 3.7 Local Control Panel (LCP) 13 3.8 LCP Menus 15 4 Mechanical Installation 16 4.1 Items Supplied 16 4.2 Tools Needed 17 4.3 Storage 17 4.4 Operating Environment 17 4.5 Installation and Cooling Requirements 18 4.6 Lifting the Drive 19 4.7 Mounting the Drive 20 5 Electrical Installation 23 5.1 Safety Instructions 23 5.2 EMC-compliant Installation 23 5.3 Wiring Schematic 26 5.4 Connecting to Ground 27 5.5 Connecting the Motor 29 5.6 Connecting the AC Mains 31 5.7 Connecting Regen/Load Share Terminals 33 5.8 Terminal Dimensions 35 Danfoss A/S © 09/2018 All rights reserved. 1 Contents VLT® AutomationDrive FC 302 5.9 Control Wiring 6 Pre-start Check List 67 7 Commissioning 68 7.1 Applying Power 68 7.2 Programming the Drive 68 7.3 Testing Before System Start-up 70 7.4 System Start-up 70 7.5 Parameter Setting 71 8 Wiring Configuration Examples 72 8.1 Programming a Closed-loop Drive System 72 8.2 Wiring Configurations for Automatic Motor Adaptation (AMA) 72 8.3 Wiring Configurations for Analog Speed Reference 73 8.4 Wiring Configurations for Start/Stop 73 8.5 Wiring Configuration for an External Alarm Reset 75 8.6 Wiring Configuration for Speed Reference Using a Manual Potentiometer 75 8.7 Wiring Configuration for Speed Up/Speed Down 75 8.8 Wiring Configuration for RS485 Network Connection 76 8.9 Wiring Configuration for a Motor Thermistor 76 8.10 Wiring Configuration for a Relay Set-up with Smart Logic Control 77 8.11 Wiring Configuration for Mechanical Brake Control 77 8.12 Wiring Configuration for the Encoder 78 8.13 Wiring Configuration for Torque and Stop Limit 79 9 Maintenance, Diagnostics, and Troubleshooting 80 9.1 Maintenance and Service 80 9.2 Heat Sink Access Panel 80 9.3 Status Messages 81 9.4 Warning and Alarm Types 83 9.5 List of Warnings and Alarms 84 9.6 Troubleshooting 94 10 Specifications 2 63 96 10.1 Electrical Data 96 10.2 Mains Supply 102 10.3 Motor Output and Torque Data 102 10.4 Ambient Conditions 102 10.5 Cable Specifications 103 10.6 Control Input/Output and Control Data 103 10.7 Fuses and Circuit Breakers 106 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Contents Operating Guide 10.8 Fastener Tightening Torques 108 10.9 Enclosure Dimensions 109 11 Appendix 144 11.1 Abbreviations and Conventions 144 11.2 International/North American Default Parameter Settings 145 11.3 Parameter Menu Structure 145 Index MG34U502 151 Danfoss A/S © 09/2018 All rights reserved. 3 1 1 Introduction VLT® AutomationDrive FC 302 1 Introduction 1.1 Purpose of the Manual 1.4 Approvals and Certifications This operating guide provides information for safe installation and commissioning of the VLT® drives. The operating guide is intended for use by qualified personnel. To use the unit safely and professionally, read and follow this operating guide. Pay particular attention to the safety instructions and general warnings. Always keep the operating guide with the drive. More approvals and certifications are available. Contact the local Danfoss office or partner. Drives of voltage 525–690 V are UL certified for only 525–600 V. VLT® is a registered trademark. 1.2 Additional Resources Other resources are available to understand advanced drive functions and programming. • Table 1.2 Approvals and Certifications The programming guide provides greater detail on working with parameters and many application examples. • The design guide provides detailed information about capabilities and functionality to design motor control systems. • Instructions provide information for operation with optional equipment. Supplementary publications and manuals are available from Danfoss. See drives.danfoss.com/knowledge-center/ technical-documentation/ for listings. 1.3 Manual and Software Version This manual is regularly reviewed and updated. All suggestions for improvement are welcome. Table 1.1 shows the version of the manual and the corresponding software version. Manual version Remarks Software version MG34U5xx Replaces MG34U4xx 8.12 The drive complies with UL 61800-5-1 thermal memory retention requirements. For more information, refer to the section Motor Thermal Protection in the product-specific design guide. NOTICE OUTPUT FREQUENCY LIMIT Due to export control regulations, the output frequency of the drive is limited to 590 Hz. For demands exceeding 590 Hz, contact Danfoss. 1.4.1 Compliance with ADN For compliance with the European Agreement concerning International Carriage of Dangerous Goods by Inland Waterways (ADN), refer to ADN-compliant Installation in the design guide. 1.5 Disposal Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation. Table 1.1 Manual and Software Version 4 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Safety Operating Guide 2 Safety UNINTENDED START The following symbols are used in this guide: WARNING Indicates a potentially hazardous situation that could result in death or serious injury. CAUTION Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices. NOTICE Indicates important information, including situations that can result in damage to equipment or property. When the drive is connected to the AC mains, DC supply, or load sharing, the motor can start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition. To prevent unintended motor start: • Press [Off/Reset] on the LCP before programming parameters. • • 2.2 Qualified Personnel Correct and reliable transport, storage, installation, operation, and maintenance are required for the troublefree and safe operation of the drive. Only qualified personnel are allowed to install or operate this equipment. Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the personnel must be familiar with the instructions and safety measures described in this manual. 2.3 Safety Precautions WARNING HIGH VOLTAGE Drives contain high voltage when connected to AC mains input, DC supply, load sharing, or permanent motors. Failure to use qualified personnel to install, start up, and maintain the drive can result in death or serious injury. • 2 2 WARNING 2.1 Safety Symbols Disconnect the drive from the mains. Completely wire and assemble the drive, motor, and any driven equipment before connecting the drive to the AC mains, DC supply, or load sharing. WARNING DISCHARGE TIME The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury. • • Stop the motor. • • Disconnect or lock PM motor. • Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors are fully discharged. Only qualified personnel must install, start up, and maintain the drive. Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other drives. Wait for the capacitors to discharge fully. The minimum waiting time is 20 minutes. WARNING LEAKAGE CURRENT HAZARD Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury. • MG34U502 Ensure the correct grounding of the equipment by a certified electrical installer. Danfoss A/S © 09/2018 All rights reserved. 5 2 2 Safety VLT® AutomationDrive FC 302 NOTICE WARNING MAINS SHIELD SAFETY OPTION EQUIPMENT HAZARD Contact with rotating shafts and electrical equipment can result in death or serious injury. • Ensure that only trained and qualified personnel install, start up, and maintain the drive. • Ensure that electrical work conforms to national and local electrical codes. • Follow the procedures in this guide. A mains shield option is available for enclosures with a protection rating of IP21/IP54 (Type 1/Type 12). The mains shield is a cover installed inside the enclosure to protect against the unintended touch of the power terminals, according to BGV A2, VBG 4. WARNING UNINTENDED MOTOR ROTATION WINDMILLING Unintended rotation of permanent magnet motors creates voltage and can charge the unit, resulting in death, serious injury, or equipment damage. • Ensure that permanent magnet motors are blocked to prevent unintended rotation. WARNING INTERNAL FAILURE HAZARD Under certain circumstances, an internal failure can cause a component to explode. Failure to keep the enclosure closed and properly secured can cause death or serious injury. • Do not operate the drive with the door open or panels off. • Ensure that the enclosure is properly closed and secured during operation. CAUTION HOT SURFACES The drive contains metal components that are still hot even after the drive has been powered off. Failure to observe the high temperature symbol (yellow triangle) on the drive can result in serious burns. 6 • Be aware that internal components, such as busbars, can be extremely hot even after the drive has been powered off. • Exterior areas marked by the high-temperature symbol (yellow triangle) are hot while the drive is in use and immediately after being powered off. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Product Overview Operating Guide 3 Product Overview 3.1 Intended Use 3 3 The drive is an electronic motor controller that converts AC mains input into a variable AC waveform output. The frequency and voltage of the output are regulated to control the motor speed or torque. The drive is designed to: • Regulate motor speed in response to system feedback or to remote commands from external controllers. • • Monitor system and motor status. Provide motor overload protection. The drive is designed for industrial and commercial environments in accordance with local laws and standards. Depending on configuration, the drive can be used in standalone applications or form part of a larger system or installation. NOTICE In a residential environment, this product can cause radio interference, in which case supplementary mitigation measures can be required. Foreseeable misuse Do not use the drive in applications which are non-compliant with specified operating conditions and environments. Ensure compliance with the conditions specified in chapter 10 Specifications. 3.2 Power Ratings, Weight, and Dimensions For enclosure sizes and power ratings of the drives, refer to Table 3.1. For more dimensions, see chapter 10.9 Enclosure Dimensions. Enclosure size Rated power [kW] IP NEMA Shipping Height dimensions [mm Width (inch)] Depth D1h D2h 45–55 kW 75–150 kW (200–240 V) (200–240 V) 90–132 kW 160–250 kW (380–500 V) (380–500 V) 90–132 kW 160–315 kW (525–690 V) (525–690 V) 21/54 Type 1/12 21/54 Type 1/12 D3h D4h 45–55 kW (200–240 V) 90–132 kW (380–500 V) 37–132 kW (525–690 V) 75–150 kW (200–240 V) 160–250 kW (380–500 V) 160–315 kW (525–690 V) 20 Chassis 20 Chassis D3h D4h With regen or load share terminals1) 20 Chassis 20 Chassis 587 (23) 587 (23) 587 (23) 587 (23) 587 (23) 587 (23) 997 (39) 1170 (46) 997 (39) 1170 (46) 1230 (48) 1430 (56) 460 (18) 535 (21) 460 (18) 535 (21) 460 (18) 535 (21) 893 (35) 1099 (43) 909 (36) 1122 (44) 1004 (40) 1268 (50) Height Drive dimensions [mm Width (inch)] Depth 325 (13) 420 (17) 250 (10) 350 (14) 250 (10) 350 (14) 378 (15) 378 (15) 375 (15) 375 (15) 375 (15) 375 (15) Maximum weight [kg (lb)] 98 (216) 164 (362) 98 (216) 164 (362) 108 (238) 179 (395) Table 3.1 Power Ratings, Weight, and Dimensions, Enclosure Sizes D1h–D4h 1) Regen, load share, and brake terminal options are not available for 200–240 V drives. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 7 3 3 Product Overview VLT® AutomationDrive FC 302 Enclosure size D5h D6h D7h D8h 90–132 kW (380–500 V) 90–132 kW (525–690 V) 90–132 kW (380–500 V) 90–132 kW (525–690 V) 160–250 kW (380–500 V) 160–315 kW (525–690 V) 160–250 kW (380–500 V) 160–315 kW (525–690 V) 21/54 Type 1/12 21/54 Type 1/12 21/54 Type 1/12 21/54 Type 1/12 Height 1805 (71) 1805 (71) 2490 (98) 2490 (98) Width 510 (20) 510 (20) 585 (23) 585 (23) Depth 635 (25) 635 (25) 640 (25) 640 (25) Height 1324 (52) 1665 (66) 1978 (78) 2284 (90) Rated power [kW] IP NEMA Shipping dimensions [mm (inch)] Drive dimensions [mm (inch)] Maximum weight [kg (lb)] Width 325 (13) 325 (13) 420 (17) 420 (17) Depth 381 (15) 381 (15) 386 (15) 406 (16) 449 (990) 449 (990) 530 (1168) 530 (1168) Table 3.2 Power Ratings, Weight, and Dimensions, Enclosure Size D5h-D8h 8 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Product Overview Operating Guide 3.3 Interior View of D1h Drive 5 6 e30bg269.10 Illustration 3.1 shows the D1h components relevant to installation and commissioning. The D1h drive interior is similar to that of the D3h, D5h, and D6h drives. Drives with the contactor option also contain a contactor terminal block (TB6). For the location of TB6, see chapter 5.8 Terminal Dimensions. 1 2 7 8 3 4 9 10 1 LCP (local control panel) 6 Mounting holes 2 Control terminals 7 Relays 1 and 2 3 Mains input terminals 91 (L1), 92 (L2), 93 (L3) 8 Motor output terminals 96 (U), 97 (V), 98 (W) 4 Ground terminals for IP21/54 (Type 1/12) 9 Cable clamps 5 Lifting ring 10 Ground terminals for IP20 (Chassis) Illustration 3.1 Interior View of D1h Drive (similar to D3h/D5h/D6h) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 9 3 3 Product Overview VLT® AutomationDrive FC 302 3.4 Interior View of D2h Drive 3 3 6 1 7 e30bg271.10 Illustration 3.2 shows the D2h components relevant to installation and commissioning. The D2h drive interior is similar to that of the D4h, D7h, and D8h drives. Drives with the contactor option also contain a contactor terminal block (TB6). For the location of TB6, see chapter 5.8 Terminal Dimensions. 2 3 8 9 4 10 11 5 12 1 Fieldbus top entry kit (optional) 7 Mounting hole 2 LCP (local control panel) 8 Relays 1 and 2 3 Control terminals 9 Terminal block for anti-condensation heater (optional) 4 Mains input terminals 91 (L1), 92 (L2), 93 (L3) 10 Motor output terminals 96 (U), 97 (V), 98 (W) 5 Cable clamps 11 Ground terminals for IP21/54 (Type 1/12) 6 Lifting ring 12 Ground terminals for IP20 (Chassis) Illustration 3.2 Interior View of D2h Drive (Similar to D4h/D7h/D8h) 10 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Product Overview Operating Guide 3.5 View of Control Shelf in D1h–D8h Drives 6 1 e30bg270.10 The control shelf holds the keypad, known as the local control panel or LCP. The control shelf also includes the control terminals, relays, and various connectors. 7 8 2 9 3 10 4 5 11 12 1 Local control panel (LCP) 7 Mounting holes 2 RS485 termination switch 8 LCP connector 3 USB connector 9 Analog switches (A53, A54) 4 RS485 fieldbus connector 10 Analog I/O connector 5 Digital I/O and 24 V supply 11 Relay 1 (01, 02, 03) on power card 6 Lifting rings 12 Relay 2 (04, 05, 06) on power card Illustration 3.3 View of Control Shelf MG34U502 Danfoss A/S © 09/2018 All rights reserved. 11 3 3 Product Overview VLT® AutomationDrive FC 302 e30bg830.10 3.6 Extended Options Cabinets If a drive is ordered with any of the following options, it is supplied with an extended options cabinet to contain the optional components. 3 3 • • • • • • • • • 1 Brake chopper. Mains disconnect. Contactor. Mains disconnect with contactor. Circuit breaker. Regeneration terminals. Load sharing terminals. Oversized wiring cabinet. Multiwire kit. Illustration 3.4 shows an example of a drive with an options cabinet. Table 3.3 lists the variants of the drive that include these options. Drive model Possible options D5h Brake, disconnect D6h Contactor, contactor with disconnect, circuit breaker D7h Brake, disconnect, multiwire kit D8h Contactor, contactor with disconnect, circuit breaker, multiwire kit 2 Table 3.3 Overview of Extended Options The D7h and D8h drives include a 200 mm (7.9 in) pedestal for floor mounting. There is a safety latch on the front cover of the options cabinet. If the drive includes a mains disconnect or circuit breaker, the safety latch locks the cabinet door while the drive is energized. Before opening the door, open the disconnect or circuit breaker to de-energize the drive, and remove the cover of the options cabinet. For drives purchased with a disconnect, contactor or circuit breaker, the nameplate label includes a type code for a replacement drive that does not include the options. If the drive is replaced, it can be replaced independently of the options cabinet. 3 1 Drive enclosure 2 Extended options cabinet 3 Pedestal Illustration 3.4 Drive with Extended Options Cabinet (D7h) 12 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Product Overview Operating Guide 3.7 Local Control Panel (LCP) The local control panel (LCP) is the combined display and keypad on the front of the drive. The LCP is used to: • • • 3 3 Control the drive and motor. Access drive parameters and program the drive. Display operational data, drive status, and warnings. A numeric local control panel (NLCP) is available as an option. The NLCP operates in a manner similar to the LCP, but there are differences. For details on how to use the NLCP, see the product-specific programming guide. A1.2 Status 0 RPM A1.1 1(1) 0.00 kW 0.00 A 0.0 Hz 0.0 % A1.3 A2 A3 Off Remote Stop Status Quick Menu Main Menu Alarm Log B2 B3 ck Ba OK Warn. D3 Alarm E1 Info On D2 Hand On C2 el nc Ca C1 D1 B4 C3 C4 C5 Off Auto On Reset E3 E4 E2 130BF155.11 B1 Illustration 3.5 Local Control Panel (LCP) A. Display area Each display readout has a parameter associated with it. See Table 3.4. The information shown on the LCP can be customized for specific applications. Refer to chapter 3.8.1.2 Q1 My Personal Menu. Callout Parameter A1.1 Parameter 0-20 Display Line 1.1 Small Default setting A1.2 Parameter 0-21 Display Line 1.2 Small Motor current [A] A1.3 Parameter 0-22 Display Line 1.3 Small Power [kW] A2 Parameter 0-23 Display Line 2 Large Frequency [Hz] A3 Parameter 0-24 Display Line 3 Large Reference [%] Speed [RPM] Table 3.4 LCP Display Area MG34U502 Danfoss A/S © 09/2018 All rights reserved. 13 3 3 Product Overview VLT® AutomationDrive FC 302 B. Menu keys Menu keys are used to access the menus for setting up parameters, toggling through status display modes during normal operation, and viewing fault log data. Callout Key B1 Status B2 Function Shows operational information. Quick Menu Allows access to parameters for initial set-up instructions. Also provides detailed application steps. Refer to chapter 3.8.1.1 Quick Menus. B3 Main Menu Allows access to all parameters. Refer to chapter 3.8.1.8 Main Menu Mode. B4 Alarm Log Shows a list of current warnings and the last 10 alarms. D. Indicator lights Indicator lights are used to identify the drive status and to provide a visual notification of warning or fault conditions. Callout Indicator Indicator Function light D1 On Green Lights when the drive receives power from the mains voltage or a 24 V external supply. D2 Warn. Yellow Lights when warning conditions are active. Text appears in the display area identifying the problem. D3 Alarm Red Lights during a fault condition. Text appears in the display area identifying the problem. Table 3.5 LCP Menu Keys Table 3.7 LCP Indicator Lights C. Navigation keys Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local (hand) operation. The display brightness can be adjusted by pressing [Status] and [â–²]/[â–¼] keys. Callout E. Operation keys and reset key The operation keys and reset key are found toward the bottom of the local control panel. Callout Key E1 Hand on Key Function C1 Back Reverts to the previous step or list in the menu structure. C2 Cancel Cancels the last change or command as long as the display mode has not changed. E2 Off C3 Info Shows a definition of the selected function. E3 Reset C4 OK Accesses parameter groups or enables an option. E4 Auto on C5 ▲▼ â—„ â–º Moves between items in the menu. Table 3.6 LCP Navigation Keys Function Starts the drive in local control. An external stop signal by control input or serial communication overrides the local [Hand On]. Stops the motor but does not remove power to the drive. Resets the drive manually after a fault has been cleared. Puts the system in remote operational mode so it can respond to an external start command by control terminals or serial communication. Table 3.8 LCP Operation Keys and Reset 14 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Product Overview Operating Guide 3.8.1.6 Q6 Loggings 3.8 LCP Menus 3.8.1.1 Quick Menus Q1 Q2 Q4 Q5 0.00 A 1(1) My Personal Menu Quick Setup Smart Setup Changes Made Parameter 0-20 Display Line 1.1 Small Speed [RPM] Parameter 0-21 Display Line 1.2 Small Motor Current Parameter 0-22 Display Line 1.3 Small Power [kW] Parameter 0-23 Display Line 2 Large Frequency Parameter 0-24 Display Line 3 Large Reference % Table 3.9 Logging Parameter Examples Illustration 3.6 Quick Menu View 3.8.1.7 Q7 Motor Setup 3.8.1.2 Q1 My Personal Menu Use My Personal Menu to determine what is shown in the display area. Refer to chapter 3.7 Local Control Panel (LCP). This menu can also show up to 50 pre-programmed parameters. These 50 parameters are manually entered using parameter 0-25 My Personal Menu. 3.8.1.3 Q2 Quick Setup The parameters found in Q2 Quick Setup contain basic system and motor data that are always necessary for configuring the drive. See chapter 7.2.3 Entering System Information for the set-up procedures. 3.8.1.4 Q4 Smart Setup Q4 Smart Setup guides the user through typical parameter settings used to configure 1 of the following 3 applications: • • • Q6 Loggings Mechanical brake. The parameters found in Q7 Motor Setup contain basic and advanced motor data that are always necessary for configuring the drive. This option also includes parameters for encoder set-up. 3.8.1.8 Main Menu Mode The Main Menu mode lists all the parameter groups available to the drive. Select the Main Menu mode by pressing the [Main Menu] key. The resulting readout appears on the LCP display. 0 RPM Main Menu 0.00 A 1(1) e30bg272.10 0 RPM Quick Menus e30bf243.11 The Quick Menus mode provides a list of menus used to configure and operate the drive. Select Quick Menus by pressing the [Quick Menu] key. The resulting readout appears on the LCP display. Use Q6 Loggings for fault finding. To get information about the display line readout, select Loggings. The information is shown as graphs. Only parameters selected in parameter 0-20 Display Line 1.1 Small through parameter 0-24 Display Line 3 Large can be viewed. It is possible to store up to 120 samples in the memory for later reference. O-** Operation / Display 1-** Load and Motor 2-** Brakes 3-** Reference / Ramps Illustration 3.7 Main Menu View Conveyor. Pump/fan. The [Info] key can be used to display help information for various selections, settings, and messages. All parameters can be changed in the main menu. Option cards added to the unit enable extra parameters associated with the option device. 3.8.1.5 Q5 Changes Made Select Q5 Changes Made for information about: • The 10 most recent changes. • Changes made from default setting. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 15 3 3 Mechanical Installation VLT® AutomationDrive FC 302 4.1 Items Supplied VLT Items supplied can vary according to product configuration. • • Make sure the items supplied and the information on the nameplate correspond to the order confirmation. Illustration 4.1 and Illustration 4.2 show sample nameplates for a D-sized drive either with or without an extended options cabinet. VLT R AutomationDrive www.danfoss.com 1 2 T/C: FC-302N250T5E20H2XGCXXXSXXXXAXBPCXXXXDX P/N: 136G0205 S/N: 123456H058 3 4 5 250 kW / 350 HP, High Overload IN: 3x380-500V 50/60Hz 463/427 A OUT: 3x0-Vin 0-590Hz 480/443 A AutomationDrive www.danfoss.com 1 2 T/C: FC-302N250T5E54H2XGC3XXSXXXXALBXCXXXXDX P/N: 134L8251 S/N: 123456H123 3 4 5 250 kW / 350 HP, High Overload Use the following Typecode to order Drive-only replacement: T/C: FC-302N250T5E54H2XGC7XXSXXXXALBXCXXXXDX IN: 3x380-500V 50/60Hz 463/427 A OUT: 3x0-Vin 0-590Hz 480/443 A 315 kW / 450 HP, Normal Overload IN: 3x380-500V 50/60Hz 567/516 A OUT: 3x0-Vin 0-590Hz 588/535 A Type 12 / IP54 Tamb. 45 C/113 F at Full Output Current Check the packaging and the drive visually for damage caused by inappropriate handling during shipment. File any claim for damage with the carrier. Retain damaged parts for clarification. e30bg282.10 4 4 R SCCR 100 kA at UL Voltage range 380-500 V ASSEMBLED IN USA Listed 36U0 E70524 IND. CONT. EQ. UL Voltage range 380-500 V Danfoss A/S 6430 Nordborg Denmark CAUTION - ATTENTION: See manual for special condition / mains fuse ` Voir manuel de conditions speciales / fusibles WARNING - AVERTISSEMENT: 6 Stored charge, wait 20 min. Charge residuelle, attendez 20 min. ` 1 Type code 315 kW / 450 HP, Normal Overload 2 Part number and serial number IN: 3x380-500V 50/60Hz 567/516 A OUT: 3x0-Vin 0-590Hz 588/535 A 3 Power rating CHASSIS/IP20 Tamb. 45 C/113 F at Full Output Current SCCR 100 kA at UL Voltage range 380-500 V ASSEMBLED IN USA Listed 36U0 E70524 IND. CONT. EQ. UL Voltage range 380-500 V Danfoss A/S 6430 Nordborg Denmark 089 CAUTION - ATTENTION: e30bg281.10 4 Mechanical Installation 4 Input voltage, frequency, and current 5 Output voltage, frequency, and current 6 Discharge time Illustration 4.2 Example Nameplate for Drive with Extended Options Cabinet (D5h–D8h) See manual for special condition / mains fuse ` Voir manuel de conditions speciales / fusibles WARNING - AVERTISSEMENT: 6 Stored charge, wait 20 min. Charge residuelle, attendez 20 min. ` NOTICE LOSS OF WARRANTY 1 Type code 2 Part number and serial number Do not remove the nameplate from the drive. Removing the nameplate can result in loss of warranty. 3 Power rating 4 Input voltage, frequency, and current 5 Output voltage, frequency, and current 6 Discharge time Illustration 4.1 Example Nameplate for Drive Only (D1h–D4h) 16 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Mechanical Installation Operating Guide 4.2 Tools Needed For detailed ambient conditions specifications, refer to chapter 10.4 Ambient Conditions. Receiving/unloading • • I-beam and hooks rated to lift the weight of the drive. Refer to chapter 3.2 Power Ratings, Weight, and Dimensions. Crane or other lifting aid to place the unit into position. Installation • Drill with 10 mm (0.39 in) or 12 mm (0.47 in) drill bits. • • Tape measurer. CONDENSATION Moisture can condense on the electronic components and cause short circuits. Avoid installation in areas subject to frost. Install an optional space heater when the drive is colder than the ambient air. Operating in standby mode reduces the risk of condensation as long as the power dissipation keeps the circuitry free of moisture. NOTICE Various sizes of Phillips and flat bladed screwdrivers. EXTREME AMBIENT CONDITIONS • Wrench with relevant metric sockets (7–17 mm/ 0.28–0.67 in). • • • • Wrench extensions. • NOTICE Torx drives (T25 and T50). Hot or cold temperatures compromise unit performance and longevity. • Do not operate in environments where the ambient temperature exceeds 55 °C (131 °F). • The drive can operate at temperatures down to -10 °C (14 °F). However, proper operation at rated load is only guaranteed at 0 °C (32 °F) or higher. • If temperature exceeds ambient temperature limits, extra air conditioning of the cabinet or installation site is required. Sheet metal punch for conduits or cable glands. I-beam and hooks to lift the weight of the drive. Refer to chapter 3.2 Power Ratings, Weight, and Dimensions. Crane or other lifting aid to place the drive onto pedestal and into position. 4.3 Storage 4.4.1 Gases Store the drive in a dry location. Keep the equipment sealed in its packaging until installation. Refer to chapter 10.4 Ambient Conditions for recommended ambient temperature. Periodic forming (capacitor charging) is not necessary during storage unless storage exceeds 12 months. 4.4 Operating Environment 4.4.2 Dust NOTICE In environments with airborne liquids, particles, or corrosive gases, ensure that the IP/type rating of the equipment matches the installation environment. Failure to meet requirements for ambient conditions can reduce the lifetime of the drive. Ensure that requirements for air humidity, temperature, and altitude are met. Voltage [V] Altitude restrictions 200–240 At altitudes above 3000 m (9842 ft), contact Danfoss regarding PELV. 380–500 At altitudes above 3000 m (9842 ft), contact Danfoss regarding PELV. 525–690 At altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV. Table 4.1 Installation at High Altitudes MG34U502 Aggressive gases, such as hydrogen sulfide, chlorine, or ammonia can damage the electrical and mechanical components. The unit uses conformal-coated circuit boards to reduce the effects of aggressive gases. For conformalcoating class specifications and ratings, see chapter 10.4 Ambient Conditions. When installing the drive in dusty environments, pay attention to the following: Periodic maintenance When dust accumulates on electronic components, it acts as a layer of insulation. This layer reduces the cooling capacity of the components, and the components become warmer. The hotter environment decreases the life of the electronic components. Keep the heat sink and fans free from dust buildup. For more service and maintenance information, refer to chapter 9 Maintenance, Diagnostics, and Troubleshooting. Cooling fans Fans provide airflow to cool the drive. When fans are exposed to dusty environments, the dust can damage the fan bearings and cause premature fan failure. Also, dust Danfoss A/S © 09/2018 All rights reserved. 17 4 4 4 4 Mechanical Installation VLT® AutomationDrive FC 302 can accumulate on fan blades causing an imbalance which prevents the fans from properly cooling the unit. 4.4.3 Potentially Explosive Atmospheres 4.5 Installation and Cooling Requirements NOTICE MOUNTING PRECAUTIONS Improper mounting can result in overheating and reduced performance. Observe all installation and cooling requirements. WARNING EXPLOSIVE ATMOSPHERE Do not install the drive in a potentially explosive atmosphere. Install the unit in a cabinet outside of this area. Failure to follow this guideline increases risk of death or serious injury. Systems operated in potentially explosive atmospheres must fulfill special conditions. EU Directive 94/9/EC (ATEX 95) classifies the operation of electronic devices in potentially explosive atmospheres. Installation requirements • Ensure unit stability by mounting vertically to a solid flat surface. • Ensure that the strength of the mounting location supports the unit weight. Refer to chapter 3.2 Power Ratings, Weight, and Dimensions. • Ensure that the mounting location allows access to open the enclosure door. See chapter 10.9 Enclosure Dimensions. • Class d specifies that if a spark occurs, it is contained in a protected area. • • Ensure that there is adequate space around the unit for cooling airflow. Class e prohibits any occurrence of a spark. • Place the unit as near to the motor as possible. Keep the motor cables as short as possible. See chapter 10.5 Cable Specifications. • Ensure that the location allows for cable entry at the bottom of the unit. Motors with class d protection Do not require approval. Special wiring and containment are required. Motors with class e protection When combined with an ATEX–approved PTC monitoring device like the VLT® PTC Thermistor Card MCB 112, the installation does not need an individual approval from an approbated organization. Motors with class d/e protection The motor itself has an e ignition protection class, while the motor cabling and connection environment is in compliance with the d classification. To attenuate the high peak voltage, use a sine-wave filter at the drive output. When using a drive in a potentially explosive atmosphere, use the following: • • • • Motors with ignition protection class d or e. PTC temperature sensor to monitor the motor temperature. Short motor cables. Cooling and airflow requirements • Ensure that top and bottom clearance for air cooling is provided. Clearance requirement: 225 mm (9 in). • Consider derating for temperatures starting between 45 °C (113 °F) and 50 °C (122 °F) and elevation 1000 m (3300 ft) above sea level. See the product-specific design guide for detailed information. The drive uses back-channel cooling to circulate the heat sink cooling air. The cooling duct carries approximately 90% of the heat out of the back channel of the drive. Redirect the back-channel air from the panel or room by using: • Duct cooling. Back-channel cooling kits are available to direct the air away from the panel when an IP20/chassis drive is installed in a Rittal enclosure. Use of a kit reduces the heat in the panel and smaller door fans can be specified on the enclosure. • Cooling out the back (top and base covers). The back-channel cooling air can be ventilated out of the room so that the heat from the back channel is not dissipated into the control room. Sine-wave output filters when shielded motor cables are not used. NOTICE MOTOR THERMISTOR SENSOR MONITORING Drives with the VLT® PTC Thermistor Card MCB 112 option are PTB-certified for potentially explosive atmospheres. 18 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Mechanical Installation Operating Guide NOTICE 4.6 Lifting the Drive Ensure that the fans supply adequate airflow over the heat sink. To select the appropriate number of fans, calculate the total required airflow. The flow rate is shown in Table 4.2. Enclosure size Door fan/ top fan Power size Heat sink fan D1h/D3h/D5h/ 102 m3/hr D6h (60 CFM) 90–110 kW, 380–500 V 420 m3/hr (250 CFM) 75–132 kW, 525–690 V 420 m3/hr (250 CFM) 132 kW, 380–500 V 840 m3/hr (500 CFM) All, 200–240 V 840 m3/hr (500 CFM) D2h/D4h/D7h/ 204 D8h (120 CFM) m3/hr 160 kW, 380–500 V 420 (250 CFM) 160 kW, 525–690 V 420 m3/hr (250 CFM) Always lift the drive using the dedicated eye bolts at the top of the drive. See Illustration 4.3. WARNING HEAVY LOAD Unbalanced loads can fall or tip over. Failure to take proper lifting precautions increases risk of death, serious injury, or equipment damage. • Move the unit using a hoist, crane, forklift, or other lifting device with the appropriate weight rating. See chapter 3.2 Power Ratings, Weight, and Dimensions for the weight of the drive. • Failure to locate the center of gravity and correctly position the load can cause unexpected shifting during lifting and transport. For measurements and center of gravity, see chapter 10.9 Enclosure Dimensions. • The angle from the top of the drive module to the lifting cables affects the maximum load force on the cable. This angle must be 65° or greater. Refer to Illustration 4.3. Attach and dimension the lifting cables properly. • • Never walk under suspended loads. m3/hr All, 200–240 V 840 m3/hr (500 CFM) Table 4.2 D1h–D8h Airflow Rates To guard against injury, wear personal protective equipment such as gloves, safety glasses, and safety shoes. 65° min 130BE566.11 One or more door fans are required on the enclosure to remove heat not contained in the back channel of the drive. The fans also remove any additional losses generated by other components inside the drive. Illustration 4.3 Lifting the Drive MG34U502 Danfoss A/S © 09/2018 All rights reserved. 19 4 4 4.7 Mounting the Drive 1 Depending on the drive model and configuration, the drive can floor-mounted or wall-mounted. 2 Drive models D1h–D2h and D5h–D8h can be floor mounted. Floor-mounted drives require space below the drive for airflow. To provide this space, the drives can be mounted on a pedestal. The D7h and D8h drives come with a standard pedestal. Optional pedestal kits are available for other D-sized drives. Drives in enclosure sizes D1h–D6h can be wall-mounted. Drive models D3h and D4h are P20/Chassis drives, which can be mounted on a wall or on a mounting plate within a cabinet. • 1 Plastic tabs 2 Tabs removed for cable access Illustration 4.5 Cable Openings in Plastic Gland Plate Creating cable openings Before attaching the pedestal or mounting the drive, create cable openings in the gland plate and install it at the bottom of the drive. The gland plate provides access for AC mains and motor cable entry while maintaining IP21/IP54 (Type 1/Type 12) protection ratings. For gland plate dimensions, see chapter 10.9 Enclosure Dimensions. • 130BF662.10 VLT® AutomationDrive FC 302 Attaching the drive to the pedestal To install a standard pedestal, use the following steps. To install an optional pedestal kit, refer to the instructions that shipped with the kit. See Illustration 4.6. If the gland plate is a metal plate, punch cable entry holes in the plate with a sheet metal punch. Insert cable fittings into the holes. See Illustration 4.4. If the gland plate is plastic, punch out plastic tabs to accommodate the cables. See Illustration 4.5. e30bg284.10 4 4 Mechanical Installation 1. Unfasten 4 M5 screws, and remove the pedestal front cover plate. 2. Secure 2 M10 nuts over the threaded studs at the back of the pedestal, securing it to the drive back channel. 3. Fasten 2 M5 screws through the back flange of the pedestal into the pedestal mounting bracket on the drive. 4. Fasten 4 M5 screws through the front flange of the pedestal and into the gland plate mounting holes. 1 2 1 Cable entry hole 2 Metal gland plate Illustration 4.4 Cable Openings in Sheet Metal Gland Plate 20 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 1 e30bg484.10 Mechanical Installation 2 3 4 4 4 5 6 7 200 (7.9) 8 9 10 1 Pedestal wall spacer 6 Back flange of pedestal 2 Fastener slots 7 M5 screw (fasten through back flange) 3 Mounting flange at drive top 8 Front flange of pedestal 4 Mounting holes 9 Front cover plate of pedestal 5 M10 nuts (fasten to threaded posts) 10 M5 screw (fasten through front flange) Illustration 4.6 Pedestal Installation in D7h/D8h Drives MG34U502 Danfoss A/S © 09/2018 All rights reserved. 21 VLT® AutomationDrive FC 302 Floor mounting the drive To secure the pedestal to the floor (after attaching the drive to the pedestal), use the following steps. 1. Fasten 4 M10 bolts in the mounting holes at the bottom of the pedestal, securing it to the floor. See Illustration 4.7. 2. Reposition the pedestal front cover plate, and fasten with 4 M5 screws. See Illustration 4.6. 3. Slide the pedestal wall spacer behind the mounting flange at the top of the drive. See Illustration 4.6. 4. Fasten 2–4 M10 bolts in the mounting holes at the top of the drive, securing it to the wall. Use 1 bolt for each mounting hole. The number varies with enclosure size. See Illustration 4.6. 1. Fasten 2 M10 bolts in the wall to align with the fastener slots at the bottom of drive. 2. Slide the fastener slots over the M10 bolts. 3. Tip the drive against the wall, and secure the top with 2 M10 bolts in the mounting holes. 1 e30bg289.10 4 4 Wall mounting the drive To wall mount a drive, use the following steps. Refer to Illustration 4.8. e30bg288.10 Mechanical Installation 1 2 1 Mounting holes 2 Bottom of pedestal Illustration 4.7 Pedestal-to-floor Mounting Holes 2 1 Top mounting holes 2 Lower fastener slots Illustration 4.8 Drive-to-wall Mounting Holes 22 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 5 Electrical Installation CAUTION 5.1 Safety Instructions See chapter 2 Safety for general safety instructions. WARNING INDUCED VOLTAGE Induced voltage from output motor cables from different drives that are run together can charge equipment capacitors even with the equipment turned off and locked out. Failure to run output motor cables separately or use shielded cables could result in death or serious injury. • Run output motor cables separately or use shielded cables. • Simultaneously lock out all the drives. WARNING SHOCK HAZARD The drive can cause a DC current in the ground conductor and thus result in death or serious injury. • When a residual current-operated protective device (RCD) is used for protection against electrical shock, only an RCD of Type B is allowed on the supply side. Failure to follow the recommendation means that the RCD cannot provide the intended protection. Overcurrent protection • Additional protective equipment such as shortcircuit protection or motor thermal protection between drive and motor is required for applications with multiple motors. • Input fusing is required to provide short circuit and overcurrent protection. If fuses are not factory-supplied, the installer must provide them. See maximum fuse ratings in chapter 10.7 Fuses and Circuit Breakers. Wire type and ratings • All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements. • Power connection wire recommendation: Minimum 75 °C (167 °F) rated copper wire. See chapter 10.5 Cable Specifications for recommended wire sizes and types. MG34U502 PROPERTY DAMAGE Protection against motor overload is not included in the default setting. To add this function, set parameter 1-90 Motor Thermal Protection to [ETR trip] or [ETR warning]. For the North American market, the ETR function provides class 20 motor overload protection in accordance with NEC. Failure to set parameter 1-90 Motor Thermal Protection to [ETR trip] or [ETR warning] means that motor overload protection is not provided and, if the motor overheats, property damage can occur. 5.2 EMC-compliant Installation To obtain an EMC-compliant installation, follow the instructions provided in: • Chapter 5.3 Wiring Schematic. • Chapter 5.4 Connecting to Ground. • Chapter 5.5 Connecting the Motor. • Chapter 5.6 Connecting the AC Mains. NOTICE TWISTED SHIELD ENDS (PIGTAILS) Twisted shield ends (pigtails) increase the shield impedance at higher frequencies, reducing the shield effect and increasing the leakage current. To avoid twisted shield ends, use integrated shield clamps. • For use with relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current loops. • Convey the currents back to the unit using a metal mounting plate. Ensure good electrical contact from the mounting plate through the mounting screws to the drive chassis. • Use shielded cables for motor output cables. An alternative is unshielded motor cables within metal conduit. NOTICE SHIELDED CABLES If shielded cables or metal conduits are not used, the unit and the installation do not meet regulatory limits on radio frequency (RF) emission levels. Danfoss A/S © 09/2018 All rights reserved. 23 5 5 5 5 Electrical Installation VLT® AutomationDrive FC 302 • Ensure that motor and brake cables are as short as possible to reduce the interference level from the entire system. • Avoid placing cables with a sensitive signal level alongside motor and brake cables. • For communication and command/control lines, follow the particular communication protocol standards. Danfoss recommends use of shielded cables. • Ensure that all control terminal connections are PELV. NOTICE EMC INTERFERENCE Use separate shielded cables for motor and control wiring, and separate cables for mains wiring, motor wiring, and control wiring. Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance. Minimum 200 mm (7.9 in) clearance between mains, motor, and control cables is required. NOTICE INSTALLATION AT HIGH ALTITUDE There is a risk of overvoltage. Isolation between components and critical parts could be insufficient, and not comply with PELV requirements. Reduce the risk of overvoltage by using external protective devices or galvanic isolation. For installations above 2000 m (6500 ft) altitude, contact Danfoss regarding PELV compliance. NOTICE PELV COMPLIANCE Prevent electric shock by using protective extra low voltage (PELV) electrical supply and complying with local and national PELV regulations. 24 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 6 e30bf228.11 Electrical Installation 7 8 5 5 9 10 11 1 12 90 13 2 14 3 15 u 4 v 4 16 w 4 PE L1 L2 L3 PE 17 5 18 1 PLC 10 Mains cable (unshielded) 2 Minimum 16 11 Output contactor and similar options 3 Control cables 12 Cable insulation stripped 4 Required minimum separation of 200 mm (7.9 in) between control cables, motor cables, and mains cables 13 Common ground busbar (Follow local and national requirements for enclosure grounding) 5 Mains supply 14 Brake resistor 6 Bare (unpainted) surface 15 Metal box 7 Star washers 16 Connection to motor 8 Brake cable (shielded) 17 Motor 9 Motor cable (shielded) 18 EMC cable gland mm2 (6 AWG) equalizing cable Illustration 5.1 Example of Proper EMC Installation MG34U502 Danfoss A/S © 09/2018 All rights reserved. 25 Electrical Installation VLT® AutomationDrive FC 302 230 V AC 50/60 Hz TB5 R1 e30bf111.12 5.3 Wiring Schematic Space heater (optional) 5 5 3-phase power input 91 (L1) 92 (L2) 93 (L3) 95 PE Load share (optional) 88 (-) 89 (+) +10 V DC Switch mode power supply 10 V DC 24 V DC 15 mA 200 mA + + - 50 (+10 V OUT) Regen + (R+) 82 (R-) 81 Regen 83 ON A53 U-I (S201) 53 (A IN) ON A54 U-I (S202) 54 (A IN) 1 2 -10 V DC to +10 V DC 0/4-20 mA (U) 96 (V) 97 (W) 98 (PE) 99 1 2 -10 V DC to +10 V DC 0/4-20 mA = = = TB6 Contactor 1) Relay1 ON=0/4-20 mA OFF=0 to ±10 V 03 02 55 (COM A IN) 240 V AC, 2A 400 V AC, 2A Relay2 06 13 (+24 V OUT) 05 P 5-00 18 (D IN) 24 V (NPN) 0 V (PNP) 04 19 (D IN) 24 V (NPN) 0 V (PNP) (COM A OUT) 39 (A OUT) 42 20 (COM D IN) 24 V (NPN) 0 V (PNP) ON 24V S801/Bus Term. OFF-ON ON=Terminated 1 OFF=Open 1 2 24V 0V 29 (D IN/OUT) Brake resistor (optional) Regen (optional) 01 12 (+24 V OUT) 27 (D IN/OUT) Motor 2 5V 240 V AC, 2A 400 V AC, 2A Analog output 0/4-20 mA Brake temperature (NC) 24 V (NPN) 0 V (PNP) S801 0V 32 (D IN) 24 V (NPN) 0 V (PNP) 33 (D IN) 24 V (NPN) 0 V (PNP) RS485 interface 0V (P RS485) 68 RS485 (N RS485) 69 (COM RS485) 61 (PNP) = Source (NPN) = Sink 37 (D IN)2) Illustration 5.2 Basic Wiring Schematic 1) TB6 contactor is found only in D6h and D8h drives with a contactor option. 2) Terminal 37 (optional) is used for Safe Torque Off. Refer to the VLT® FC Series - Safe Torque Off Operating Guide for installation instructions. 26 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 5.4 Connecting to Ground WARNING LEAKAGE CURRENT HAZARD Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury. • Ensure the correct grounding of the equipment by a certified electrical installer. For electrical safety • Ground the drive in accordance with applicable standards and directives. • • • • • • 5 5 Use a dedicated ground wire for input power, motor power, and control wiring. Do not ground 1 drive to another in a daisy chain fashion. Keep the ground wire connections as short as possible. Follow motor manufacturer wiring requirements. Minimum cable cross-section: 10 mm2 (6 AWG) (or 2 rated ground wires terminated separately). Tighten the terminals in accordance with the information provided in chapter 10.8.1 Fastener Torque Ratings. For EMC-compliant installation • Establish electrical contact between the cable shield and the drive enclosure by using metal cable glands or by using the clamps provided on the equipment. • • Reduce burst transient by using high-strand wire. Do not use twisted shield ends (pigtails). NOTICE POTENTIAL EQUALIZATION There is a risk of burst transient when the ground potential between the drive and the control system is different. Install equalizing cables between the system components. Recommended cable cross-section: 16 mm2 (5 AWG). MG34U502 Danfoss A/S © 09/2018 All rights reserved. 27 VLT® AutomationDrive FC 302 e30bg266.10 Electrical Installation 5 5 Illustration 5.3 Ground Terminals (D1h shown) 28 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 5.5 Connecting the Motor WARNING INDUCED VOLTAGE Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned off and locked out. Failure to run output motor cables separately or use shielded cables could result in death or serious injury. • Comply with local and national electrical codes for cable sizes. For maximum wire sizes, see chapter 10.5 Cable Specifications. • • • Follow motor manufacturer wiring requirements. 5 5 Motor wiring knockouts or access panels are provided at the base of IP21 (NEMA1/12) and higher units. Do not wire a starting or pole-changing device (for example Dahlander motor or slip ring asynchronous motor) between the drive and the motor. Procedure 1. Strip a section of the outer cable insulation. 2. Position the stripped wire under the cable clamp, establishing mechanical fixation and electrical contact between the cable shield and ground. 3. Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions provided in chapter 5.4 Connecting to Ground. See Illustration 5.4. 4. Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W). See Illustration 5.4. 5. Tighten the terminals in accordance with the information provided in chapter 10.8.1 Fastener Torque Ratings. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 29 VLT® AutomationDrive FC 302 e30bg268.10 Electrical Installation 5 5 Illustration 5.4 Motor Terminals (D1h shown) 30 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 5.6 Connecting the AC Mains • • Size the wiring according to the input current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data. Comply with local and national electrical codes for cable sizes. Procedure 1. Strip a section of the outer cable insulation. 2. Position the stripped wire under the cable clamp, establishing mechanical fixation and electrical contact between the cable shield and ground. 3. Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions provided in chapter 5.4 Connecting to Ground. 4. Connect the 3-phase AC input power wiring to terminals R, S, and T. See Illustration 5.5. 5. Tighten the terminals in accordance with the information provided in chapter 10.8.1 Fastener Torque Ratings. 6. When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] Off to avoid damage to the DC link and to reduce ground capacity currents. 5 5 NOTICE OUTPUT CONTACTOR Danfoss does not recommend using an output contactor on 525–690 V drives that are connected to an IT mains network. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 31 VLT® AutomationDrive FC 302 e30bg267.10 Electrical Installation 5 5 Illustration 5.5 AC Mains Terminals (D1h shown). For a detailed view of terminals, see chapter 5.8 Terminal Dimensions. 32 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 5.7 Connecting Regen/Load Share Terminals The optional regeneration/load share terminals are found at the top of the drive. For drives with IP21/IP54 enclosures, the wiring is routed through a cover surrounding the terminals. Refer to Illustration 5.5. • • Size the wiring according to the current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data. Comply with local and national electrical codes for cable sizes. Procedure 1. Remove 2 plugs (for either top entry or side entry) from the terminal cover. 2. Insert cable fittings into the terminal cover holes. 3. Strip a section of the outer cable insulation. 4. Position the stripped cable through the fittings. 5. Connect the DC(+) cable to the DC(+) terminal, and secure with 1 M10 fastener. 6. Connect the DC(-) cable to the DC(-) terminal, and secure with 1 M10 fastener. 7. Tighten the terminals in accordance with chapter 10.8.1 Fastener Torque Ratings. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 5 5 33 VLT® AutomationDrive FC 302 e30bg485.10 Electrical Installation 6 1 7 2 8 3 5 5 32 (1.3) 9 244 (9.6) 4 14 (0.6) 16 (0.6) 10 125 (4.9) 101 (4.0) 11 95 (3.7) 236 (9.3) 125 (4.9) 87 (3.4) 5 12 1 Top openings for regen/load share terminals 7 DC(+) terminal 2 Terminal cover 8 DC(-) terminal 3 Side opening for regen/load share terminals 9 Hole for M10 fastener 4 Top view 10 Close-up view 5 Side view 11 Regen/load share terminals 6 View without cover 12 Front view Illustration 5.6 Regen/Load Share Terminals in Enclosure Size D 34 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 5.8 Terminal Dimensions 130BF342.10 5.8.1 D1h Terminal Dimensions 5 5 1 3 200 (7.9) 94 (3.7) 88 (3.5) 2 1 Mains terminals 3 Motor terminals 2 Ground terminals – – 293 (11.5) 263 (10.4) 224 (8.8) 185 (7.3) 163 (6.4) 140 (5.5) 101 (4.0) 62 (2.4) 33 (1.3) 0.0 0.0 Illustration 5.7 D1h Terminal Dimensions (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 35 VLT® AutomationDrive FC 302 130BF343.10 Electrical Installation 1 2 0.0 244 (9.6) 272 (10.7) 0.0 5 5 M10 M10 13 (0.5) 13 (0.5) 32 (1.3) 1 32 (1.3) Mains terminals 2 Motor terminals Illustration 5.8 D1h Terminal Dimensions (Side Views) 36 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF345.10 5.8.2 D2h Terminal Dimensions 1 3 331 (13.0) 5 5 211 (8.3) 2 168 (6.6) 168 (6.6) 143 (5.6) 143 (5.6) 1 Mains terminals 3 Motor terminals 2 Ground terminals – – 378 (14.9) 354 (13.9) 300 (11.8) 246 (9.7) 184 (7.2) 126 (5.0) 68 (2.7) 42 (1.6) 0.0 0.0 Illustration 5.9 D2h Terminal Dimensions (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 37 VLT® AutomationDrive FC 302 130BF346.10 Electrical Installation 1 2 0.0 255 (10.0) 0.0 284 (11.2) 5 5 M10 M10 15 (0.6) 15 (0.6) 19 (0.8) 18 (0.7) 35 (1.4) 38 (1.5) 1 Mains terminals 2 Motor terminals Illustration 5.10 D2h Terminal Dimensions (Side Views) 38 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF341.10 217 (8.5) 152 (6.0) 5.8.3 D3h Terminal Dimensions 292 (11.5) 5 5 2 1 3 188 (7.4) 83 (3.3) 0.0 223 (8.8) 184 (7.2) 145 (5.7) 101 (4.0) 62 (2.4) 22 (0.9) 0.0 4 1 Mains terminals 3 Motor terminals 2 Brake terminals 4 Ground terminals Illustration 5.11 D3h Terminal Dimensions (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 39 VLT® AutomationDrive FC 302 130BF344.10 Electrical Installation 1 2 3 0.0 244 (9.6) 290 (11.4) 272 (10.7) 0.0 5 5 M10 6 12 (0.5) 4 0 38 (1.5) 3X M8x18 182 (7.2) 145 (5.7) 59 (2.3) 0 10 (0.4) M10 M10 5 7 13 (0.5) 13 (0.5) 32 (1.3) 32 (1.3) 1 and 6 Bottom brake/regen terminals 3 and 5 Mains terminals 2 and 7 Motor terminals 4 Ground terminals Illustration 5.12 D3h Terminal Dimensions (Side Views) 40 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF347.10 237 (9.3) 293 (11.5) 5.8.4 D4h Terminal Dimensions 5 5 376 (14.8) 1 2 319 (12.6) 3 200 (7.9) 0.0 319 (12.6) 265 (10.4) 211 (8.3) 149 (5.8) 91 (3.6) 33 (1.3) o.o 4 1 Mains terminals 3 Motor terminals 2 Brake terminals 4 Ground terminals Illustration 5.13 D4h Terminal Dimensions (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 41 VLT® AutomationDrive FC 302 130BF348.10 Electrical Installation 1 2 3 0.0 255 (10.0) 0.0 284 (11.2) 306 (12.1) 5 5 M10 4 6 0 259 (10.2) 200 (7.9) 91 (3.6) 0 13 (0.5) 19 (0.7) 3X M10X20 16 (0.6) 32 (1.3) M10 M10 5 22 (0.9) 15 (0.6) 19 (0.8) 7 18 (0.7) 38 (1.5) 35 (1.4) 1 and 6 Brake/regen terminals 3 and 5 Mains terminals 2 and 7 Motor terminals 4 Ground terminals Illustration 5.14 D4h Terminal Dimensions (Side Views) 42 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF349.10 5.8.5 D5h Terminal Dimensions 5 5 3 1 227 (9.0) 221 (8.7) 196 (7.7) 4 2 148 (5.8) 118 (4.6) 90 (3.6) 249 (9.8) 260 (10.2) 221 (8.7) 182 (7.2) 193 (7.6) 146 (5.8) 153 (6.0) 99 (3.9) 46 (1.8) 45 (1.8) 0.0 0.0 1 Mains terminals 3 Brake terminals 2 Ground terminals 4 Motor terminals Illustration 5.15 D5h Terminal Dimensions with Disconnect Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 43 VLT® AutomationDrive FC 302 130BF350.10 Electrical Installation 5 5 2 1 1 Mains terminals 3 Motor terminals 2 Brake terminals – – 0.0 113 (4.4) 0.0 206 (8.1) 3 Illustration 5.16 D5h Terminal Dimensions with Disconnect Option (Side Views) 44 Danfoss A/S © 09/2018 All rights reserved. MG34U502 130BF351.10 293 (11.5) 256 (10.1) 263 (10.4) 224 (8.8) 185 (7.3) 191 (7.5) 163 (6.4) 140 (5.5) 101 (4.0) Operating Guide 62 (2.4) 33 (1.3) 0.0 Electrical Installation 2 727 (28.6) 1 623 (24.5) 5 5 3 517 (20.4) 511 (20.1) 4 0.0 1 Mains terminals 3 Motor terminals 2 Brake terminals 4 Ground terminals Illustration 5.17 D5h Terminal Dimensions with Brake Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 45 VLT® AutomationDrive FC 302 130BF352.10 Electrical Installation 1 2 3 1 Brake terminals 3 Motor terminals 2 Mains terminals – – 0.0 246 (9.7) 293 (11.5) 0.0 274 (10.8) 5 5 Illustration 5.18 D5h Terminal Dimensions with Brake Option (Side Views) 46 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF353.10 5.8.6 D6h Terminal Dimensions 1 5 5 458 (18.0) 3 4 227 (8.9) 195 (7.7) 2 5 153 (6.0) 123 (4.8) 96 (3.8) 249 (9.8) 260 (10.2) 221 (8.7) 182 (7.2) 193 (7.6) 147 (5.8) 99 (3.9) 146 (5.8) 50 (2.0) 46 (1.8) 0.0 0.0 1 Mains terminals 4 Brake terminals 2 Ground terminals 5 Motor terminals 3 TB6 terminal block for contactor – – Illustration 5.19 D6h Terminal Dimensions with Contactor Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 47 VLT® AutomationDrive FC 302 e30bf354.10 Electrical Installation 1 5 5 2 1 Mains terminals 3 Motor terminals 2 Brake terminals – – 0.0 113 (4.4) 206 (8.1) 286 (11.2) 0.0 3 Illustration 5.20 D6h Terminal Dimensions with Contactor Option (Side Views) 48 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF355.10 Electrical Installation 5 5 3 1 4 225 (8.9) 5 2 153 (6.0) 99 (3.9) 45 (1.8) 0.0 0.0 1 Mains terminals 4 Brake terminals 2 Ground terminals 5 Motor terminals 3 TB6 terminal block for contactor – – Illustration 5.21 D6h Terminal Dimensions with Contactor and Disconnect Options (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 49 VLT® AutomationDrive FC 302 130BF356.10 Electrical Installation 5 5 1 2 286 (11.2) 0.0 3 1 Brake terminals 3 Motor terminals 2 Mains terminals – – Illustration 5.22 D6h Terminal Dimensions with Contactor and Disconnect Options (Side Views) 50 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF357.10 Electrical Installation 5 5 1 467 (18.4) 3 4 2 145 (5.7) 99 (3.9) 52 (2.1) 0.0 0.0 1 Mains terminals 3 Brake terminals 2 Ground terminals 4 Motor terminals Illustration 5.23 D6h Terminal Dimensions with Circuit Breaker Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 51 VLT® AutomationDrive FC 302 130BF358.10 Electrical Installation 1 5 5 2 0.0 163 (6.4) 3 1 Mains terminals 3 Motor terminals 2 Brake terminals – – Illustration 5.24 D6h Terminal Dimensions with Circuit Breaker Option (Side Views) 52 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF359.10 5.8.7 D7h Terminal Dimensions 1 545 (21.4) 2 515 (20.3) 5 5 3 412 (16.2) 395 (15.6) 372 (14.7) 4 368 (14.5) 346 (13.6) 292 (11.5) 238 (9.4) 198 (7.8) 195 (7.7) 151 (5.9) 131 (5.1) 95 (3.7) 49 (1.9) 66 (2.6) 0.0 0.0 1 Mains terminals 3 Motor terminals 2 Brake terminals 4 Ground terminals Illustration 5.25 D7h Terminal Dimensions with Disconnect Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 53 VLT® AutomationDrive FC 302 130BF360.10 Electrical Installation 1 2 3 276 (10.9) 119 (4.7) 0.0 5 5 1 Mains terminals 3 Motor terminals 2 Brake terminals – – Illustration 5.26 D7h Terminal Dimensions with Disconnect Option (Side Views) 54 Danfoss A/S © 09/2018 All rights reserved. MG34U502 130BF361.10 351 (13.8) 375 (14.8) 243 (9.6) 269 (10.6) 297 (11.7) 325 (12.8) 181 (7.1) 123 (4.9) 40 (1.6) 66 (2.6) Operating Guide 0.0 Electrical Installation 1260 (49.6) 1 3 4 1202 (47.3) 1082 (42.6) 2 5 5 1034 (40.7) 1009 (39.7) 0.0 1 Mains terminals 3 Brake terminals 2 Ground terminals 4 Motor terminals Illustration 5.27 D7h Terminal Dimensions with Brake Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 55 130BF362.10 0.0 257 (10.1) 309 (12.1) VLT® AutomationDrive FC 302 290 (11.4) 0.0 Electrical Installation 1 3 2 5 5 1 Brake terminals 3 Motor terminals 2 Mains terminals – – Illustration 5.28 D7h Terminal Dimensions with Brake Option (Side Views) 56 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Electrical Installation Operating Guide 130BF367.10 5.8.8 D8h Terminal Dimensions 1 898 (35.3) 5 5 4 5 2 521 (20.5) 3 418 (16.5) 401 (15.8) 378 (14.9) 378 (14.9) 346 (13.6) 292 (11.5) 238 (9.4) 177 (7.0) 198 (7.8) 151 (5.9) 95 (3.7) 123 (4.9) 49 (1.9) 69 (2.7) 0.0 0.0 1 Mains terminals 4 TB6 terminal block for contactor 2 Brake terminals 5 Motor terminals 3 Ground terminals – – Illustration 5.29 D8h Terminal Dimensions with Contactor Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 57 VLT® AutomationDrive FC 302 130BF368.10 Electrical Installation 1 5 5 1 Mains terminals 3 Motor terminals 2 Brake terminals – – 0.0 127 (5.0) 3 252 (9.9) 119 (4.7) 0.0 2 Illustration 5.30 D8h Terminal Dimensions with Contactor Option (Side Views) 58 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF369.10 Electrical Installation 4 5 5 1 567 (22.3) 5 2 3 188 (7.4) 123 (4.9) 58 (2.3) 0.0 0.0 1 Mains terminals 4 TB6 terminal block for contactor 2 Brake terminals 5 Motor terminals 3 Ground terminals – – Illustration 5.31 D8h Terminal Dimensions with Contactor and Disconnect Options (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 59 VLT® AutomationDrive FC 302 130BF370.10 Electrical Installation 5 5 1 2 246 (9.7) 0.0 3 1 Mains terminals 3 Motor terminals 2 Brake terminals – – Illustration 5.32 D8h Terminal Dimensions with Contactor and Disconnect Options (Side View) 60 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF371.10 Electrical Installation 5 5 1 605 (23.8) 4 2 3 224 (8.8) 154 (6.1) 85 (3.3) 0 0 1 Mains terminals 3 Ground terminals 2 Brake terminals 4 Motor terminals Illustration 5.33 D8h Terminal Dimensions with Circuit Breaker Option (Front View) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 61 VLT® AutomationDrive FC 302 130BF372.10 Electrical Installation M10 1 5 5 20 (0.8) 15 (0.6) 40 (1.6) 1 2 3 M10 2 15 (0.6) 16 (0.6) 32 (1.3) 3 M10 20 (0.8) 14 (0.5) 35 (1.4) 0.0 202 (8.0) 18 (0.7) 1 Mains terminals 3 Motor terminals 2 Brake terminals – – Illustration 5.34 D8h Terminal Dimensions with Circuit Breaker Option (Side View) 62 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 5.9 Control Wiring 130BF145.10 Electrical Installation 1 All terminals to the control cables are inside the drive below the LCP. To access the control terminals, either open the door (D1h/D2h/D5h/D6h/D7h/D8h) or remove the front panel (D3h/D4h). 61 68 69 39 42 50 53 54 55 3 2 12 13 18 19 27 29 32 33 20 37 5.9.1 Control Cable Routing • • • • Isolate control wiring from high-power components in the drive. 1 Serial communication terminals Tie down all control wires after routing them. 2 Digital input/output terminals 3 Analog input/output terminals Connect shields to ensure optimum electrical immunity. When the drive is connected to a thermistor, ensure that the thermistor control wiring is shielded and reinforced/double insulated. A 24 V DC supply voltage is recommended. Fieldbus connection Connections are made to the relevant options on the control card. For more detail, see the relevant fieldbus instruction. The cable must be tied down and routed along with other control wires inside the unit. Illustration 5.36 Terminal Numbers Located on the Connectors Terminal Parameter Default setting Description 61 – – Integrated RC-filter for cable shield. ONLY for connecting the shield to correct EMC problems. 68 (+) Parameter group 8-3* FC Port Settings – 69 (-) Parameter group 8-3* FC Port Settings – RS485 interface. A switch (BUS TER.) is provided on the control card for bus termination resistance. See Illustration 5.40. 5.9.2 Control Terminal Types 130BF144.10 Illustration 5.35 shows the removable drive connectors. Terminal functions and default settings are summarized in Table 5.1 – Table 5.3. Illustration 5.35 Control Terminal Locations MG34U502 5 5 Table 5.1 Serial Communication Terminal Descriptions Digital input/output terminals Terminal Parameter Default setting Description 12, 13 – +24 V DC 24 V DC supply voltage for digital inputs and external transducers. Maximum output current 200 mA for all 24 V loads. 18 Parameter 5-10 Terminal 18 Digital Input [8] Start 19 Parameter 5-11 Terminal 19 Digital Input [10] Reversing 32 Parameter 5-14 Terminal 32 Digital Input [0] No operation 33 Parameter 5-15 Terminal 33 Digital Input [0] No operation Danfoss A/S © 09/2018 All rights reserved. Digital inputs. 63 VLT® AutomationDrive FC 302 Digital input/output terminals Terminal Parameter Default setting 27 Parameter 5-12 Terminal 27 Digital Input [2] Coast inverse 29 Parameter 5-13 Terminal 29 Digital Input [14] JOG 20 – – 37 – STO 5 5 Description For digital input or output. Default setting is input. Common for digital inputs and 0 V potential for 24 V supply. Analog input/output terminals Parameter Default setting 39 – – 42 Parameter 6-50 Terminal 42 Output [0] No operation 50 – +10 V DC NOTICE Minimize interference by keeping control wires as short as possible and separate from high-power cables. Connecting wire to control terminals 1. Strip 10 mm (0.4 in) of the outer plastic layer from the end of the wire. 2. Insert the control wire into the terminal. When not using the optional STO feature, a jumper wire is required between terminal 12 (or 13) and terminal 37. This set-up allows the drive to operate with factory default programming values. Table 5.2 Digital Input/Output Terminal Descriptions Terminal Either solid or flexible wire can be connected to the control terminals. Use the following procedures to connect or disconnect the control wires. Description 3. • For a solid wire, push the bare wire into the contact. See Illustration 5.37. • For a flexible wire, open the contact by inserting a small screwdriver into the slot between the terminal holes and push the screwdriver inward. See Illustration 5.38. Then, insert the stripped wire into the contact, and remove the screwdriver. Pull gently on the wire to ensure that the contact is firmly established. Loose control wiring can be the source of equipment faults or reduced performance. Common for analog output. 12 13 18 19 27 29 32 33 Programmable analog output. 0–20 mA or 4–20 mA at a e30bg283.10 Electrical Installation Parameter group 6-1* Analog Input 1 Reference 54 Parameter group 6-2* Analog Input 2 Feedback 55 – – (0. mm 10 Illustration 5.37 Connecting Solid Control Wires Analog input. For voltage or current. Switches A53 and A54 select mA or V. 12 13 18 19 27 29 32 33 Common for analog input. 1 (0. 10 mm 5.9.3 Wiring to Control Terminals The control terminals are located near the LCP. The control terminal connectors can be unplugged from the drive for convenience when wiring, as shown in Illustration 5.35. 64 2 4) Table 5.3 Analog Input/Output Terminal Descriptions 130BD546.11 53 10 V DC analog supply voltage for potentiometer or thermistor. 15 mA maximum. 4) maximum of 500 Ω. Illustration 5.38 Connecting Flexible Control Wires Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide Disconnecting wires from the control terminals 1. 2. To open the contact, insert a small screwdriver into the slot between the terminal holes and push the screwdriver inward. Pull gently on the wire to free it from the control terminal contact. See chapter 10.5 Cable Specifications for control terminal wiring sizes and chapter 8 Wiring Configuration Examples for typical control wiring connections. card documentation for installation and operation instructions. • For basic serial communication set-up, perform the following steps: 1. Connect RS485 serial communication wiring to terminals (+)68 and (-)69. 5.9.4 Enabling Motor Operation (Terminal 27) A jumper wire is required between terminal 12 (or 13) and terminal 27 for the drive to operate when using factory default programming values. • Digital input terminal 27 is designed to receive 24 V DC external interlock command. • When no interlock device is used, wire a jumper between control terminal 12 (recommended) or 13 to terminal 27. This wire provides an internal 24 V signal on terminal 27. • • 5.9.5 Configuring RS485 Serial Communication RS485 is a 2-wire bus interface compatible with multi-drop network topology, and it contains the following features: • Either Danfoss FC or Modbus RTU communication protocol, which are internal to the drive, can be used. • 1a Use shielded serial communication cable (recommended). 1b See chapter 5.4 Connecting to Ground for proper grounding. Select the following parameter settings: 2a Protocol type in parameter 8-30 Protocol. 2b Drive address in parameter 8-31 Address. 2c Baud rate in parameter 8-32 Baud Rate. 61 68 + RS485 69 When factory-installed optional equipment is wired to terminal 27, do not remove that wiring. The drive cannot operate without a signal on terminal 27, unless terminal 27 is reprogrammed using parameter 5-12 Terminal 27 Digital Input. • 2. When the status line at the bottom of the LCP reads AUTO REMOTE COAST, the unit is ready to operate, but is missing an input signal on terminal 27. NOTICE • A switch (BUS TER) is provided on the control card for bus termination resistance. See Illustration 5.40. 130BB489.10 Electrical Installation Functions can be programmed remotely using the protocol software and RS485 connection or in parameter group 8-** Communications and Options. Selecting a specific communication protocol changes various default parameter settings to match the specifications of the protocol, making more protocol-specific parameters available. Option cards for the drive are available to provide more communication protocols. See the option MG34U502 Illustration 5.39 Serial Communication Wiring Diagram 5.9.6 Wiring Safe Torque Off (STO) The Safe Torque Off (STO) function is a component in a safety control system. STO prevents the unit from generating the voltage required to rotate the motor. To run STO, more wiring for the drive is required. Refer to Safe Torque Off Operating Guide for further information. 5.9.7 Wiring the Space Heater The space heater is an option used to prevent condensation from forming inside the enclosure when the unit is turned off. It is designed to be field wired and controlled by an external system. Specifications • Nominal voltage: 100–240 • Wire size: 12–24 AWG Danfoss A/S © 09/2018 All rights reserved. 65 5 5 VLT® AutomationDrive FC 302 5.9.8 Wiring the Auxiliary Contacts to the Disconnect 5.9.10 Selecting Voltage/Current Input Signal The disconnect is an option that is installed at the factory. The auxiliary contacts, which are signal accessories used with the disconnect, are not installed at the factory to allow more flexibility during installation. The contacts snap into place without the need for tools. The analog input terminals 53 and 54 allow setting of input signal to voltage (0–10 V) or current (0/4–20 mA). Contacts must be installed in specific locations on the disconnect depending on their functions. Refer to the datasheet included in the accessory bag that comes with the drive. • Terminal 54: Feedback signal in closed loop (see parameter 16-63 Terminal 54 Switch Setting). NOTICE Disconnect power to the drive before changing switch positions. Specifications • Ui/[V]: 690 Uimp/[kV]: 4 1. Remove the LCP. See Illustration 5.40. Pollution degree: 3 2. Remove any optional equipment covering the switches. 3. Set switches A53 and A54 to select the signal type (U = voltage, I = current). Ith/[A]: 16 Cable size: 1...2x0.75...2.5 mm2 Maximum fuse: 16 A/gG 130BF146.10 • • • • • • Default parameter setting: • Terminal 53: Speed reference signal in open loop (see parameter 16-61 Terminal 53 Switch Setting). NEMA: A600, R300, wire size: 18–14 AWG, 1(2) 5.9.9 Wiring the Brake Resistor Temperature Switch 3b Normally open. Connect to terminals 104 and 105. N O N O 2 66 Normally closed. Connect to terminals 104 and 106. 1 4. 3a 2 Remove the jumper and wire the brake resistor temperature switch in 1 of the following configurations: 1 3. 2 Remove the M3 screws that hold the jumper to the power card. A53 A54 U- I U- I 1 2. BUS TER. OFF-ON 2 Locate the brake resistor terminal block (terminals 104–106) on the power card. See Illustration 3.3. 1 1. N O The brake resistor terminal block is found on the power card and allows for the connection of an external brake resistor temperature switch. The switch can be configured as normally closed or normally open. If the input changes, a signal trips the drive and shows alarm 27, Brake chopper fault on the LCP display. At the same time, the drive stops braking and the motor coasts. N O 5 5 Electrical Installation Illustration 5.40 Location of Terminal 53 and 54 Switches Secure the switch wires with the M3 screws. Torque to 0.5–0.6 Nm (5 in-lb). Danfoss A/S © 09/2018 All rights reserved. MG34U502 Pre-start Check List Operating Guide 6 Pre-start Check List Before completing installation of the unit, inspect the entire installation as detailed in Table 6.1. Check and mark the items when completed. ☑ Inspect for Description Motor Confirm continuity of the motor by measuring ohm values on U–V (96–97), V–W (97–98), and W–U (98–96). Auxiliary equipment • • • • Check function and installation of any sensors used for feedback to the drive. Cable routing • • • • • • • • • • • • • • Check for broken or damaged wires and loose connections. Switches Control wiring Input and output power wiring Grounding Fuses and circuit breakers Cooling clearance Ambient conditions Interior of the drive Vibration Confirm that the supply voltage matches the voltage of the drive and the motor. Ensure that all switch and disconnect settings are in the proper positions. Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that reside on the input power side of the drive or output side to the motor. Ensure that they are ready for full-speed operation. 6 6 Remove any power factor correction caps on motor. Adjust any power factor correction caps on the mains side and ensure that they are dampened. Ensure that motor wiring, brake wiring (if equipped), and control wiring are separated or shielded, or in 3 separate metallic conduits for high-frequency interference isolation. Check that control wiring is isolated from high-power wiring for noise immunity. Check the voltage source of the signals, if necessary. Use shielded cable or twisted pair and ensure that the shield is terminated correctly. Check for loose connections. Check that motor and mains are in separate conduit or separated shielded cables. Check for good ground connections that are tight and free of oxidation. Grounding to conduit, or mounting the back panel to a metal surface, is not a suitable grounding. Check for proper fusing or circuit breakers. Check that all fuses are inserted firmly and are in operational condition and that all circuit breakers (if used) are in the open position. • • Look for any obstructions in the airflow path. • • • • • • Check that requirements for ambient conditions are met. See chapter 10.4 Ambient Conditions. Measure top and bottom clearance of the drive to verify adequate airflow for cooling, see chapter 4.5 Installation and Cooling Requirements. Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion. Verify that all installation tools have been removed from unit interior. For D3h and D4h enclosures, ensure that the unit is mounted on an unpainted, metal surface. Check that the unit is mounted solidly, or that shock mounts are used, if necessary. Check for an unusual amount of vibration. Table 6.1 Pre-start Check List MG34U502 Danfoss A/S © 09/2018 All rights reserved. 67 7 7 Commissioning VLT® AutomationDrive FC 302 7 Commissioning 7.2 Programming the Drive 7.1 Applying Power 7.2.1 Parameter Overview WARNING UNINTENDED START When the drive is connected to AC mains, DC supply, or load sharing, the motor can start at any time, causing risk of death, serious injury, and equipment, or property damage. The motor can start by activation of an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault. To prevent unintended motor start: • Press [Off] on the LCP before programming parameters. • Disconnect the drive from mains whenever personal safety considerations make it necessary to avoid unintended motor start. • Check that the drive, motor, and any driven equipment are in operational readiness. Parameters contain various settings that are used to configure and operate the drive and motor. These parameter settings are programmed into the local control panel (LCP) through the different LCP menus. For more detail on parameters, see the product-specific programming guide. Parameter settings are assigned a default value at the factory, but can be configured for their unique application. Each parameter has a name and number that remain the same regardless of the programming mode. In the Main Menu mode, the parameters are divided into groups. The 1st digit of the parameter number (from the left) indicates the parameter group number. The parameter group is then broken down into sub-groups, if necessary. For example: NOTICE 0-** Operation/Display Parameter group MISSING SIGNAL 0-0* Basic Settings Parameter sub-group If the status at the bottom of the LCP reads AUTO REMOTE COASTING, or alarm 60, External interlock is shown, it indicates that the unit is ready to operate but is missing an input signal on, for example, terminal 27. See chapter 5.9.4 Enabling Motor Operation (Terminal 27). Parameter 0-01 Language Parameter Parameter 0-02 Motor Speed Unit Parameter Parameter 0-03 Regional Settings Parameter Apply power to the drive using the following steps: 1. Confirm that the input voltage is balanced within 3%. If not, correct the input voltage imbalance before proceeding. Repeat this procedure after the voltage correction. 2. 68 Ensure that any optional equipment wiring matches the installation requirements. Table 7.1 Example of Parameter Group Hierarchy 7.2.2 Parameter Navigation Use the following LCP keys to navigate through the parameters: • • 3. Ensure that all operator devices are in the OFF position. 4. Close and securely fasten all covers and doors on the drive. • • 5. Apply power to the unit, but do not start the drive. For units with a disconnect switch, turn the switch to the ON position to apply power to the drive. • • Press [â–²] [â–¼] to scroll up or down. Press [â—„] [â–º] to shift a space to the left or right of a decimal point while editing a decimal parameter value. Press [OK] to accept the change. Press [Cancel] to disregard the change and exit edit mode. Press [Back] twice to show the status view. Press [Main Menu] once to go back to the main menu. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Commissioning Operating Guide NOTICE 7.2.3 Entering System Information MISSING INPUT SIGNAL NOTICE SOFTWARE DOWNLOAD For commissioning via PC, install MCT 10 Set-up Software. The software is available for download (basic version) or for ordering (advanced version, code number 130B1000). For more information and downloads, see www.danfoss.com/en/service-and-support/downloads/dds/ vlt-motion-control-tool-mct-10/. The following steps are used to enter basic system information into the drive. Recommended parameter settings are intended for start-up and checkout purposes. Application settings vary. NOTICE Although these steps assume that an asynchronous motor is used, a permanent magnet motor can be used. For more information on specific motor types, see the product-specific programming guide. 1. Press [Main Menu] on the LCP. 2. Select 0-** Operation/Display and press [OK]. 3. Select 0-0* Basic Settings and press [OK]. 4. Select parameter 0-03 Regional Settings and press [OK]. 5. Select [0] International or [1] North America as appropriate and press [OK]. (This action changes the default settings for some basic parameters). 6. Press [Quick Menus] on the LCP and then select 02 Quick Setup. 7. Change the following parameters settings listed in Table 7.2 if necessary. The motor data is found on the motor nameplate. Parameter Default setting Parameter 0-01 Language English Parameter 1-20 Motor Power [kW] 4.00 kW Parameter 1-22 Motor Voltage 400 V Parameter 1-23 Motor Frequency 50 Hz Parameter 1-24 Motor Current 9.00 A Parameter 1-25 Motor Nominal Speed 1420 RPM Parameter 5-12 Terminal 27 Digital Input Coast inverse Parameter 3-02 Minimum Reference 0.000 RPM Parameter 3-03 Maximum Reference When the LCP shows AUTO REMOTE COASTING or alarm 60, External Interlock, the unit is ready to operate but is missing an input signal. See chapter 5.9.4 Enabling Motor Operation (Terminal 27) for details. 7.2.4 Configuring Automatic Energy Optimization Automatic energy optimization (AEO) is a procedure that minimizes voltage to the motor, reducing energy consumption, heat, and noise. 1. Press [Main Menu]. 2. Select 1-** Load and Motor and press [OK]. 3. Select 1-0* General Settings and press [OK]. 4. Select parameter 1-03 Torque Characteristics and press [OK]. 5. Select either [2] Auto Energy Optim CT or [3] Auto Energy Optim VT and press [OK]. 7 7 7.2.5 Configuring Automatic Motor Adaptation Automatic motor adaptation is a procedure that optimizes compatibility between the drive and the motor. The drive builds a mathematical model of the motor for regulating output motor current. The procedure also tests the input phase balance of electrical power. It compares the motor characteristics with the data entered in parameters 1-20 to 1-25. NOTICE If warnings or alarms occur, see chapter 9.5 List of Warnings and Alarms. Some motors are unable to run the complete version of the test. In that case, or if an output filter is connected to the motor, select [2] Enable reduced AMA. Run this procedure on a cold motor for best results. 1. Press [Main Menu]. 2. Select 1-** Load and Motor and press [OK]. 1500.000 RPM 3. Select 1-2* Motor Data and press [OK]. Parameter 3-41 Ramp 1 Ramp Up Time 3.00 s 4. Parameter 3-42 Ramp 1 Ramp Down Time 3.00 s Select parameter 1-29 Automatic Motor Adaptation (AMA) and press [OK]. Parameter 3-13 Reference Site Linked to Hand/ Auto 5. Select [1] Enable complete AMA and press [OK]. 6. Press [Hand On] and then [OK]. The test runs automatically and indicates when it is complete. Parameter 1-29 Automatic Motor Adaptation Off (AMA) Table 7.2 Quick Set-up Settings MG34U502 Danfoss A/S © 09/2018 All rights reserved. 69 7 7 Commissioning VLT® AutomationDrive FC 302 7.3 Testing Before System Start-up NOTICE NEGATIVE FEEDBACK WARNING MOTOR START Failure to ensure that the motor, system, and any attached equipment are ready for start can result in personal injury or equipment damage. Before start, • Ensure that equipment is safe to operate under any condition. • Ensure that the motor, system, and any attached equipment are ready for start. If the feedback is negative, the encoder connection is wrong. Use either parameter 5-71 Term 32/33 Encoder Direction or parameter 17-60 Feedback Direction to inverse the direction, or reverse the encoder cables. Parameter 17-60 Feedback Direction is only available with the VLT® Encoder Input MCB 102 option. 7.4 System Start-up WARNING MOTOR START 7.3.1 Motor Rotation Failure to ensure that the motor, system, and any attached equipment are ready for start can result in personal injury or equipment damage. Before start, NOTICE If the motor runs in the wrong direction, it can damage equipment. Before running the unit, check the motor rotation by briefly running the motor. The motor runs briefly at either 5 Hz or the minimum frequency set in parameter 4-12 Motor Speed Low Limit [Hz]. 1. Press [Hand On]. 2. Move the left cursor to the left of the decimal point by using the left arrow key, and enter an RPM that slowly rotates the motor. 3. Press [OK]. 4. If the motor rotation is wrong, set parameter 1-06 Clockwise Direction to [1] Inverse. 7.3.2 Encoder Rotation If encoder feedback is used, perform the following steps: 1. Select [0] Open Loop in parameter 1-00 Configuration Mode. 2. Select [1] 24 V encoder in parameter 7-00 Speed PID Feedback Source. 3. Press [Hand On]. 4. Press [â–º] for positive speed reference (parameter 1-06 Clockwise Direction at [0] Normal). 5. In parameter 16-57 Feedback [RPM], check that the feedback is positive. • Ensure that equipment is safe to operate under any condition. • Ensure that the motor, system, and any attached equipment are ready for start. The procedure in this section requires user-wiring and application programming to be completed. The following procedure is recommended after application set-up is completed. 1. Press [Auto On]. 2. Apply an external run command. Examples of external run commands are a switch, key, or programmable logic controller (PLC). 3. Adjust the speed reference throughout the speed range. 4. Ensure that the system is working as intended by checking sound and vibration level of the motor. 5. Remove the external run command. If warnings or alarms occur, see chapter 9.5 List of Warnings and Alarms. For more information on the encoder option, refer to the option manual. 70 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Commissioning Operating Guide 7.5 Parameter Setting 7.5.2 Restoring Factory Default Settings NOTICE NOTICE REGIONAL SETTINGS Some parameters have different default settings for international or North America. For a list of the different default values, see chapter 11.2 International/North American Default Parameter Settings. Establishing the correct programming for applications requires setting several parameter functions. Details for parameters are provided in the programming guide. Parameter settings are stored internally in the drive, allowing the following advantages: • Parameter settings can be uploaded into the LCP memory and stored as a back-up. • Multiple units can be programmed quickly by connecting the LCP to the unit and downloading the stored parameter settings. • Settings that are stored in the LCP are not changed when restoring factory default settings. • Changes made to default settings as well as any programming entered into parameters are stored and available for viewing in the quick menu. See chapter 3.8 LCP Menus. 7.5.1 Uploading and Downloading Parameter Settings The drive operates using parameters stored on the control card, which is located within the drive. The upload and download functions move the parameters between the control card and the LCP. 1. Press [Off]. 2. Go to parameter 0-50 LCP Copy and press [OK]. 3. Select 1 of the following: 3a To upload data from the control card to the LCP, select [1] All to LCP. 3b To download data from the LCP to the control card, select [2] All from LCP. 4. Press [OK]. A progress bar shows the uploading or downloading process. 5. Press [Hand On] or [Auto On]. LOSS OF DATA Loss of programming, motor data, localization, and monitoring records occurs when restoring default settings. To create a back-up, upload data to the LCP before initialization. Refer to chapter 7.5.1 Uploading and Downloading Parameter Settings. Restore the default parameter settings by initializing the unit. Initialization is carried out through parameter 14-22 Operation Mode or manually. Parameter 14-22 Operation Mode does not reset settings such as the following: • Running hours. • • • Personal menu settings. Fault log, alarm log, and other monitoring functions. Recommended initialization 1. Press [Main Menu] twice to access parameters. 2. Go to parameter 14-22 Operation Mode and press [OK]. 3. Scroll to Initialization and press [OK]. 4. Remove power to the unit and wait for the display to turn off. 5. Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal. 6. After alarm 80, Drive initialized to default value appears, press [Reset]. Manual initialization Manual initialization resets all factory settings except for the following: • Parameter 15-00 Operating hours. • • • Parameter 15-03 Power Up's. Parameter 15-04 Over Temp's. Parameter 15-05 Over Volt's. To perform manual initialization: 1. Remove power to the unit and wait for the display to turn off. 2. MG34U502 7 7 Serial communication options. Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until an audible click sounds and the fan starts). Start-up takes slightly longer than normal. Danfoss A/S © 09/2018 All rights reserved. 71 VLT® AutomationDrive FC 302 8 Wiring Configuration Examples • Parameter settings are the regional default values unless otherwise indicated (selected in parameter 0-03 Regional Settings). • Parameters associated with the terminals and their settings are shown next to the drawings. • Switch settings for analog terminals A53 or A54 are shown where required. • For STO, a jumper wire may be required between terminal 12 and terminal 37 when using factory default programming values. 130BT865.10 The examples in this section are intended as a quick reference for common applications. Brake resistor Transmission 8.1 Programming a Closed-loop Drive System A closed-loop drive system usually consists of the following: • Motor • • • • • • • Motor Encoder Gearbox Load Mechanical brake Illustration 8.1 Basic Set-up for FC 302 Closed-loop Speed Control Drive Encoder as feedback system Mechanical brake Brake resistor for dynamic braking Transmission 8.2 Wiring Configurations for Automatic Motor Adaptation (AMA) Gear box Parameters Load FC Applications demanding mechanical brake control typically need a brake resistor. +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 +10 V A IN 50 A IN 54 COM 55 A OUT 42 COM 39 53 130BB929.10 8 8 Wiring Configuration Exampl... Function Setting Parameter 1-29 [1] Enable Automatic Motor complete AMA Adaptation (AMA) Parameter 5-12 T [2]* Coast erminal 27 inverse Digital Input *=Default value Notes/comments: Set parameter group 1-2* Motor Data according to motor nameplate. Table 8.1 Wiring Configuration for AMA with T27 Connected 72 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Wiring Configuration Exampl... Operating Guide Parameters FC +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 +10 V A IN 50 A IN 54 COM 55 A OUT 42 COM 39 Setting Parameter 1-29 [1] Enable Automatic Motor complete AMA Adaptation (AMA) FC +10 V A IN 50 A IN 54 COM 55 *=Default value A OUT 42 Notes/comments: Set parameter group 1-2* Motor Data according to motor nameplate. COM 39 Parameter 5-12 T [0] No erminal 27 operation Digital Input 53 e30bb927.11 130BB930.10 Parameters Function 53 Setting Parameter 6-12 T 4 mA* erminal 53 Low Current Parameter 6-13 T 20 mA* erminal 53 High Current + - Function Parameter 6-14 T 0 RPM 4 - 20mA erminal 53 Low Ref./Feedb. Value Parameter 6-15 T 1500 RPM erminal 53 High Ref./Feedb. Value U-I A53 *=Default value Notes/comments: Table 8.4 Wiring Configuration for Analog Speed Reference (Current) 8.4 Wiring Configurations for Start/Stop Table 8.2 Wiring Configuration for AMA without T27 Connected e30bb926.11 Parameters +10 V A IN 50 A IN 54 COM 55 A OUT 42 COM 39 U-I A53 53 + - Function Setting Parameter 6-10 0.07 V* Terminal 53 Low Voltage Parameter 6-11 Terminal 53 High Voltage 10 V* Parameter 6-14 0 RPM Terminal 53 Low 0 – 10 V Ref./Feedb. Value Parameter 6-15 1500 RPM Terminal 53 High Ref./Feedb. Value FC +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 +10 50 A IN 53 A IN 54 COM 55 A OUT 42 COM 39 130BB802.10 Parameters 8.3 Wiring Configurations for Analog Speed Reference FC 8 8 Function Setting Parameter 5-10 T [8] Start* erminal 18 Digital Input Parameter 5-12 T [0] No erminal 27 operation Digital Input Parameter 5-19 T [1] Safe erminal 37 Safe Torque Off Stop Alarm *=Default value Notes/comments: If parameter 5-12 Terminal 27 Digital Input is set to [0] No operation, a jumper wire to terminal 27 is not needed. *=Default value Notes/comments: Table 8.5 Wiring Configuration for Start/Stop Command with Safe Torque Off Table 8.3 Wiring Configuration for Analog Speed Reference (Voltage) MG34U502 Danfoss A/S © 09/2018 All rights reserved. 73 130BB805.12 VLT® AutomationDrive FC 302 Speed Start/Stop (18) Illustration 8.2 Start/Stop with Safe Torque Off Parameters Function FC [9] Latched Start [6] Stop Inverse +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 Parameter 5-12 Terminal 27 Digital Input D IN 29 *=Default value D IN 32 Notes/comments: If parameter 5-12 Terminal 27 Digital Input is set to [0] No operation, a jumper wire to terminal 27 is not needed. D IN 33 D IN 37 +10 V 50 A IN 53 A IN 54 COM 55 A OUT 42 COM 39 Parameter 5-11 Terminal 19 Digital Input [10] Reversing* [0] No operation 12 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 Parameter 5-12 Terminal 27 Digital Input +10 V A IN 50 Parameter 5-14 Terminal 32 Digital Input [16] Preset ref bit 0 A IN 54 COM 55 [17] Preset ref bit 1 A OUT 42 Parameter 5-15 Terminal 33 Digital Input COM 39 Setting Parameter 5-10 Terminal 18 Digital Input [8] Start +24 V 53 130BB934.11 Function FC Setting Parameter 5-10 Terminal 18 Digital Input +24 V Parameters Parameter 3-10 Preset Reference Preset Preset Preset Preset ref. ref. ref. ref. 0 1 2 3 25% 50% 75% 100% *=Default value Notes/comments: 130BB803.10 Table 8.7 Wiring Configuration for Start/Stop with Reversing and 4 Preset Speeds Table 8.6 Wiring Configuration for Pulse Start/Stop Speed 130BB806.10 8 8 Wiring Configuration Exampl... Latched Start (18) Stop Inverse (27) Illustration 8.3 Latched Start/Stop Inverse 74 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 8.5 Wiring Configuration for an External Alarm Reset Parameters Function FC Setting +24 V 12 +24 V 13 D IN 18 Parameter E-02 T [1] Reset erminal 19 Digital Input D IN 19 *=Default value COM 20 Notes/comments: D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 +10 V A IN 50 A IN 54 COM 55 A OUT 42 COM 39 53 (Using a Manual Potentiometer) 8.7 Wiring Configuration for Speed Up/ Speed Down Parameters Function FC +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 Setting Parameter 5-10 [8] Start* Terminal 18 Digital Input Parameter 5-12 [19] Freeze Terminal 27 Reference Digital Input Parameter 5-13 [21] Speed Up Terminal 29 Digital Input e30bb804.12 Wiring Configuration Exampl... Parameter 5-14 [22] Speed Terminal 32 Down Digital Input 130BB928.11 *=Default value 8 8 Notes/comments: Speed Reference Table 8.8 Wiring Configuration for an External Alarm Reset Start (18) 8.6 Wiring Configuration for Speed Reference Using a Manual Potentiometer Freeze ref (27) Speed up (29) Speed down (32) e30bb683.11 Parameters FC +10 V A IN 50 A IN 54 COM 55 A OUT 42 COM 39 U-I A53 53 ≈ 5kΩ 130BB840.12 Table 8.10 Wiring Configuration for Speed Up/Speed Down Function Setting Parameter 6-10 Terminal 53 Low Voltage 0.07 V* Parameter 6-11 Terminal 53 High Voltage 10 V* Parameter 6-14 Terminal 53 Low Ref./Feedb. Value 0 RPM Illustration 8.4 Speed Up/Speed Down Parameter 6-15 1500 RPM Terminal 53 High Ref./Feedb. Value *=Default value Notes/comments: Table 8.9 Wiring Configuration for Speed Reference MG34U502 Danfoss A/S © 09/2018 All rights reserved. 75 VLT® AutomationDrive FC 302 8.8 Wiring Configuration for RS485 Network Connection 130BB685.10 Parameters FC +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 Function Setting Parameter 8-30 Protocol FC* Parameter 8-31 Address 1* Parameter 8-32 Baud Rate 9600* *=Default value Notes/comments: Select protocol, address, and baud rate in the parameters. 8.9 Wiring Configuration for a Motor Thermistor NOTICE Thermistors must use reinforced or double insulation to meet PELV insulation requirements. Parameters Function VLT +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN [2] Thermistor trip [1] analog input 53 50 D IN 29 *=Default value 53 D IN 32 A IN 54 D IN 33 COM 55 D IN 37 A OUT 42 COM 39 +10 V A IN 50 01 A IN 54 02 COM 55 03 A OUT 42 COM 39 05 53 U-I RS-485 06 61 68 69 A53 + - Table 8.11 Wiring Configuration for RS485 Network Connection 76 Notes/comments: If only a warning is wanted, set parameter 1-90 Motor Thermal Protection to [1] Thermistor warning. 130BB686.12 R1 27 +10 V A IN 04 Setting Parameter 1-90 Motor Thermal Protection Parameter 1-93 Thermistor Source R2 8 8 Wiring Configuration Exampl... Table 8.12 Wiring Configuration for a Motor Thermistor Danfoss A/S © 09/2018 All rights reserved. MG34U502 Wiring Configuration Exampl... Operating Guide 8.10 Wiring Configuration for a Relay Set-up with Smart Logic Control 8.11 Wiring Configuration for Mechanical Brake Control 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 +10 V A IN 50 A IN 54 COM 55 A OUT 42 COM 39 53 R1 01 02 03 R2 04 05 06 Parameter 4-31 Motor Feedback Speed Error 100 RPM Parameter 4-32 Motor Feedback Loss Timeout 5s FC +24 V 12 +24 V 13 D IN 18 D IN 19 COM 20 D IN 27 D IN 29 D IN 32 D IN 33 D IN 37 +10 V A IN 50 Parameter 17-11 1024* Resolution (PPR) A IN 54 COM 55 Parameter 13-00 [1] On SL Controller Mode A OUT 42 COM 39 Parameter 7-00 S [2] MCB 102 peed PID Feedback Source Parameter 13-01 [19] Warning Start Event 53 01 02 03 Parameter 13-02 [44] Reset key Stop Event Parameter 13-10 [21] Warning Comparator no. Operand Parameter 13-11 [1] ≈ (equal)* Comparator Operator Parameter 13-12 90 Comparator Value Parameter 13-51 [22] SL Controller Comparator 0 Event Parameter 13-52 [32] Set digital SL Controller out A low Action Parameter 5-40 F [80] SL digital unction Relay output A *=Default value Notes/comments: If the limit in the feedback monitor is exceeded, warning 90, Feedback Mon. is issued. The SLC monitors warning 90, Feedback Mon. and if the warning becomes true, relay 1 is triggered. External equipment may require service. If the feedback error goes below the limit again within 5 s, the drive continues and the warning disappears. Reset relay 1 by pressing [Reset] on the LCP. 04 Function Setting Parameter 5-40 F [32] Mech. unction Relay brake ctrl. Parameter 5-10 T [8] Start* erminal 18 Digital Input Parameter 5-11 T [11] Start erminal 19 reversing Digital Input Parameter 1-71 S 0.2 tart Delay Parameter 1-72 S [5] VVC+/ tart Function FLUX Clockwise Parameter 1-76 S tart Current Im,n 8 8 Parameter 2-20 Release Brake Current Application dependent Parameter 2-21 Activate Brake Speed [RPM] Half of nominal slip of the motor 05 *=Default value 06 Notes/comments: Table 8.14 Wiring Configuration for Mechanical Brake Control 130BB842.10 13 D IN Setting [1] Warning 130BB841.10 +24 V Function Parameter 4-30 Motor Feedback Loss Function R1 12 Parameters R2 FC +24 V 130BB839.10 Parameters 1-76 Current Speed 1-71 Time 2-21 1-71 2-21 Start (18) Start reversing (19) Relay output Open Closed Illustration 8.5 Mechanical Brake Control Table 8.13 Wiring Configuration for a Relay Set-up with Smart Logic Control MG34U502 Danfoss A/S © 09/2018 All rights reserved. 77 8 8 Clockwise (CW) direction means channel A is 90 electrical degrees before channel B. • Counterclockwise (CCW) direction means channel B is 90 electrical degrees before A. 12 13 18 19 27 29 33 20 130BA090.12 32 37 130BA646.10 • GND The direction of the encoder, identified by looking into the shaft end, is determined by which order the pulses enter the drive. See Illustration 8.6. B 8.12 Wiring Configuration for the Encoder A VLT® AutomationDrive FC 302 +24 V DC Wiring Configuration Exampl... CW A B CCW A B Illustration 8.6 Determining Encoder Direction 24 V or 10–30 V encoder Illustration 8.7 Wire Configuration for the Encoder NOTICE Maximum cable length 5 m (16 ft). 78 Danfoss A/S © 09/2018 All rights reserved. MG34U502 If a stop command is active via terminal 18 and the drive is not at the torque limit, the motor ramps down to 0 Hz. If the drive is at the torque limit and a stop command is activated, the system activates terminal 29 output (programmed to [27] Torque limit & stop). The signal to terminal 27 changes from logic 1 to logic 0 and the motor starts to coast. This process ensures that the hoist stops even if the drive itself cannot handle the required torque, for example due to excessive overload. 12 13 18 19 32 33 External 24 V DC + 02 MG34U502 03 Relay output [0] (Relay 1) (Parameter 5-40 Function Relay [32] Mechanical Brake Control). Mechanical brake Relay 1 • 8 8 P 5-40 [0] [32] 01 Terminal 29 output (Parameter 5-02 Terminal 29 Mode [1] Terminal 29 Mode Output and parameter 5-31 Terminal 29 Digital Output [27] Torque limit & stop). 37 Imax 0.1 Amp - Quick stop via terminal 27 (Parameter 5-12 Terminal 27 Digital Input [2] Coasting Stop, Inverse). • 20 Start To program the stop and torque limit, connect to the following terminals: • Start/stop via terminal 18 (Parameter 5-10 Terminal 18 Digital Input [8] Start). • 130BA194.11 29 GND 27 P 5-31 [27] P 5-02 [1] In applications with an external electro-mechanical brake, such as hoisting applications, it is possible to stop the drive via a standard stop command and simultaneously activate the external electro-mechanical brake. Illustration 8.8 shows the programming of these drive connections. P 5-12 [2] 8.13 Wiring Configuration for Torque and Stop Limit P 5-10 [8] Operating Guide +24 V Wiring Configuration Exampl... connection Illustration 8.8 Wire Configuration for Torque and Stop Limit Danfoss A/S © 09/2018 All rights reserved. 79 9 9 Maintenance, Diagnostics, a... VLT® AutomationDrive FC 302 9 Maintenance, Diagnostics, and Troubleshooting • • • 130BD430.10 This chapter includes: • Maintenance and service guidelines. Status messages. Warnings and alarms. Basic troubleshooting. 9.1 Maintenance and Service Under normal operating conditions and load profiles, the drive is maintenance-free throughout its designed lifetime. To prevent breakdown, danger, and damage, examine the drive at regular intervals depending on the operating conditions. Replace worn or damaged parts with original spare parts or standard parts. For service and support, refer to www.danfoss.com/en/contact-us/contacts-list/?filter=type %3Adanfoss-sales-service-center%2Csegments%3ADDS. WARNING UNINTENDED START When the drive is connected to AC mains, DC supply, or load sharing, the motor can start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition. To prevent unintended motor start: • Press [Off/Reset] on the LCP before programming parameters. • • Disconnect the drive from the mains. Completely wire and assemble the drive, motor, and any driven equipment before connecting the drive to AC mains, DC supply, or load sharing. Illustration 9.1 Heat Sink Access Panel NOTICE DAMAGE TO HEAT SINK Using fasteners that are longer than those originally supplied with the heat sink panel can damage the heat sink cooling fins. 1. Remove power from the drive and wait 20 minutes for the capacitors to discharge completely. Refer to chapter 2 Safety. 2. Position the drive so that the back of the drive is accessible. 3. Remove the screws (3 mm [0.12 in] internal hex) connecting the access panel to the back of the enclosure. There are 5 or 9 screws depending on the size of the drive. 4. Inspect the heat sink for damage or dust buildup. 5. Remove dust and debris with a vacuum. 6. Replace the panel and secure it to the back of the enclosure with the screws previously removed. Tighten the fasteners according to chapter 10.8 Fastener Tightening Torques. 9.2 Heat Sink Access Panel 9.2.1 Removing the Heat Sink Access Panel The drive can be ordered with an optional access panel in the back of the unit. This panel provides access to the heat sink and allows the heat sink to be cleaned of any dust buildup. 80 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Maintenance, Diagnostics, a... Operating Guide AC brake When the drive is in status mode, status messages automatically appear in the lowest line of the LCP display. Refer to Illustration 9.2. Status messages are defined in Table 9.1 – Table 9.3. AC brake was selected in parameter 2-10 Brake Function. The AC brake overmagnetizes the motor to achieve a controlled slow-down. AMA finish OK Automatic motor adaptation (AMA) was carried out successfully. AMA ready AMA is ready to start. To start, press [Hand On]. AMA running AMA process is in progress. Braking The brake chopper is in operation. The brake resistor absorbs the generative energy. Braking max. The brake chopper is in operation. The power limit for the brake resistor defined in parameter 2-12 Brake Power Limit (kW) has been reached. Coast • [2] Coast inverse was selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal is not connected. • Coast activated by serial communication. Status 799RPM 7.83A 1(1) 36.4kW 0.000 130BB037.11 9.3 Status Messages 53.2% Auto Hand Off 1 Remote Local 2 3 1 Ramping Stop Running Jogging . . . Stand-by Where the stop/start command originates. Refer to Table 9.1. 2 Where the speed control originates. Refer to Table 9.2. 3 Provides the drive status. Refer to Table 9.3. Ctrl. ramp-down [1] Ctrl. ramp-down was selected in parameter 14-10 Mains Failure. • The mains voltage is below the value set in parameter 14-11 Mains Fault Voltage Level at mains fault. Illustration 9.2 Status Display • The drive ramps down the motor using a controlled ramp-down. NOTICE Current high In auto/remote mode, the drive requires external commands to execute functions. The drive output current is above the limit set in parameter 4-51 Warning Current High. Current low The drive output current is below the limit set in parameter 4-52 Warning Speed Low. DC hold DC hold is selected in parameter 1-80 Function at Stop and a stop command is active. The motor is held by a DC current set in parameter 2-00 DC Hold Current. DC stop The motor is held with a DC current (parameter 2-01 DC Brake Current) for a specified time (parameter 2-02 DC Braking Time). • DC brake is activated in parameter 2-03 DC Brake Cut In Speed [RPM] and a stop command is active. Table 9.1 to Table 9.3 define the meaning of the shown status messages. Off The drive does not react to any control signal until [Auto On] or [Hand On] is pressed. Auto The start/stop commands are sent via the control terminals and/or the serial communication. Hand The navigation keys on the LCP can be used to control the drive. Stop commands, reset, reversing, DC brake, and other signals applied to the control terminals override local control. • DC brake (inverse) is selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal is not active. • The DC brake is activated via serial communication. Table 9.1 Operating Mode Remote The speed reference is given from: • External signals. • • Local Serial communication. The sum of all active feedbacks is above the feedback limit set in parameter 4-57 Warning Feedback High. Feedback low The sum of all active feedbacks is below the feedback limit set in parameter 4-56 Warning Feedback Low. Internal preset references. The drive uses reference values from the LCP. Table 9.2 Reference Site MG34U502 Feedback high Danfoss A/S © 09/2018 All rights reserved. 81 9 9 9 9 Maintenance, Diagnostics, a... Freeze output VLT® AutomationDrive FC 302 The remote reference, which holds the present speed, is active. • [20] Freeze Output was selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal is active. Speed control is only possible via the terminal functions speed up and speed down. • Protection md Protection mode is active. The unit has detected a critical status (an overcurrent or overvoltage). • To avoid tripping, the switching frequency is reduced to 1500 kHz if parameter 14-55 Output Filter is set to [2] Sine-Wave Filter Fixed. Otherwise, the switching frequency is reduced to 1000 Hz. Hold ramp is activated via serial communication. • If possible, protection mode ends after approximately 10 s. Freeze output request A freeze output command has been given, but the motor remains stopped until a run permissive signal is received. • Protection mode can be restricted in parameter 14-26 Trip Delay at Inverter Fault. Freeze ref. [19] Freeze Reference was selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal is active. The drive saves the actual reference. Changing the reference is now only possible via terminal functions speed up and speed down. Jog request Jogging Motor check OVC control Power unit off 82 A jog command has been given, but the motor is stopped until a run permissive signal is received via a digital input. The motor is running as programmed in parameter 3-19 Jog Speed [RPM]. • [14] Jog was selected as function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal (for example, terminal 29) is active. • The jog function is activated via the serial communication. • The jog function was selected as a reaction for a monitoring function (for example, No signal). The monitoring function is active. In parameter 1-80 Function at Stop, [2] Motor Check was selected. A stop command is active. To ensure that a motor is connected to the drive, a permanent test current is applied to the motor. Overvoltage control was activated in parameter 2-17 Over-voltage Control, [2] Enabled. The connected motor is supplying the drive with generative energy. The overvoltage control adjusts the V/Hz ratio to run the motor in controlled mode and to prevent the drive from tripping. (For drives with a 24 V DC external supply installed only.) Mains supply to the drive is removed, but the control card is supplied by the 24 V DC external supply. QStop The motor is decelerating using parameter 3-81 Quick Stop Ramp Time. • [4] Quick stop inverse was selected as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal is not active. • The quick stop function was activated via serial communication. Ramping The motor is accelerating/decelerating using the active ramp up/down. The reference, a limit value, or a standstill is not yet reached. Ref. high The sum of all active references is above the reference limit set in parameter 4-55 Warning Reference High. Ref. low The sum of all active references is below the reference limit set in parameter 4-54 Warning Reference Low. Run on ref. The drive is running in the reference range. The feedback value matches the setpoint value. Run request A start command has been given, but the motor is stopped until a run permissive signal is received via digital input. Running The drive is driving the motor. Sleep mode The energy saving function is enabled. This function being enabled means that the motor has stopped, but that it restarts automatically when required. Speed high The motor speed is above the value set in parameter 4-53 Warning Speed High. Speed low The motor speed is below the value set in parameter 4-52 Warning Speed Low. Standby In auto-on mode, the drive starts the motor with a start signal from a digital input or serial communication. Start delay In parameter 1-71 Start Delay, a delay starting time was set. A start command is activated and the motor starts after the start delay time expires. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide Start fwd/rev [12] Enable Start Forward and [13] Enable Start Reverse were selected as functions for 2 different digital inputs (parameter group 5-1* Digital Inputs). The motor starts in forward or reverse depending on which corresponding terminal is activated. Stop The drive has received a stop command from 1 of the following: • LCP. Trip Digital input. Serial communication. An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, reset the drive using 1 of the following: • Pressing [Reset]. • • Remotely by control terminals. Via serial communication. Pressing [Reset] or remotely by control terminals or via serial communication. Trip lock An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, cycle power to the drive. Reset the drive manually by 1 of the following: • Pressing [Reset]. • • Trip lock When trip locking, the drive suspends operation to prevent damage to the drive and other equipment. When a trip lock occurs, the motor coasts to a stop. The drive logic continues to operate and monitor the drive status. The drive starts a trip lock only when serious faults occur that can damage the drive or other equipment. After the faults are fixed, cycle the input power before resetting the drive. Warning and alarm displays • A warning is shown in the LCP along with the warning number. • An alarm flashes along with the alarm number. Status 0.0Hz Remotely by control terminals. Via serial communication. Earth Fault [A14] Auto Remote Trip Table 9.3 Operation Status 9.4 Warning and Alarm Types Illustration 9.3 Alarm Example The drive software issues warnings and alarms to help diagnose issues. The warning or alarm number appears in the LCP. In addition to the text and alarm code in the LCP, there are 3 status indicator lights. Ba ck el nc Ca Warning A warning indicates that the drive has encountered an abnormal operating condition that leads to an alarm. A warning stops when the abnormal condition is removed or resolved. On OK Warn. Alarm Press [Reset]/[Off/Reset]. Warning indicator light Digital reset input command. Info Alarm An alarm indicates a fault that requires immediate attention. The fault always triggers a trip or trip lock. Reset the drive after an alarm. Reset the drive in any of 4 ways: • • • • 1(1) 0.00A 0.000kW 0.0Hz 0 130BB467.11 • • Trip When tripping, the drive suspends operation to prevent damage to the drive and other equipment. When a trip occurs, the motor coasts to a stop. The drive logic continues to operate and monitor the drive status. After the fault condition is remedied, the drive is ready for a reset. 130BP086.12 Maintenance, Diagnostics, a... Alarm indicator light Warning On Off Serial communication reset input command. Alarm Off On (flashing) Auto reset. Trip lock On On (flashing) Illustration 9.4 Status Indicator Lights MG34U502 Danfoss A/S © 09/2018 All rights reserved. 83 9 9 9 9 Maintenance, Diagnostics, a... VLT® AutomationDrive FC 302 9.5 List of Warnings and Alarms The following warning and alarm information defines each warning or alarm condition, provides the probable cause for the condition, and details a remedy or troubleshooting procedure. WARNING 1, 10 Volts low The control card voltage is less than 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloaded. Maximum 15 mA or minimum 590 Ω. A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition. Troubleshooting • Remove the wiring from terminal 50. If the warning clears, the problem is with the wiring. If the warning does not clear, replace the control card. WARNING/ALARM 2, Live zero error This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this condition. Troubleshooting • Check connections on all analog mains terminals. - Control card terminals 53 and 54 for signals, terminal 55 common. - VLT® General Purpose I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common. - VLT® Analog I/O Option MCB 109 terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common. • Check that the drive programming and switch settings match the analog signal type. • Perform an input terminal signal test. WARNING/ALARM 3, No motor No motor has been connected to the output of the drive. This warning or alarm appears only if programmed in parameter 1-80 Function at Stop. Troubleshooting • Check the connection between the drive and the motor. WARNING/ALARM 4, Mains phase loss A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in parameter 14-12 Response to Mains Imbalance. Troubleshooting • Check the supply voltage and supply currents to the drive. 84 WARNING 5, DC link voltage high The DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still active. WARNING 6, DC link voltage low The DC-link voltage (DC) is lower than the low-voltage warning limit. The limit depends on the drive voltage rating. The unit is still active. WARNING/ALARM 7, DC overvoltage If the DC-link voltage exceeds the limit, the drive trips after a certain time. Troubleshooting • Connect a brake resistor. • • • Extend the ramp time. • Increase parameter 14-26 Trip Delay at Inverter Fault. • If the alarm/warning occurs during a power sag, use kinetic back-up (parameter 14-10 Mains Failure). Change the ramp type. Activate the functions in parameter 2-10 Brake Function. WARNING/ALARM 8, DC under voltage If the DC-link voltage drops below the undervoltage limit, the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is connected, the drive trips after a fixed time delay. The time delay varies with unit size. Troubleshooting • Check that the supply voltage matches the drive voltage. • • Perform an input voltage test. Perform a soft-charge circuit test. WARNING/ALARM 9, Inverter overload The drive has run with more than 100% overload for too long and is about to cut out. The counter for electronic thermal inverter protection issues a warning at 98% and trips at 100% with an alarm. The drive cannot be reset until the counter is below 90%. Troubleshooting • Compare the output current shown on the LCP with the drive rated current. • Compare the output current shown on the LCP with the measured motor current. • Show the thermal drive load on the LCP and monitor the value. When running above the drive continuous current rating, the counter increases. When running below the drive continuous current rating, the counter decreases. WARNING/ALARM 10, Motor overload temperature According to the electronic thermal protection (ETR), the motor is too hot. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Maintenance, Diagnostics, a... Operating Guide Select 1 of these options: • The drive issues a warning or an alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options. • The drive trips when the counter reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options. The fault occurs when the motor runs with more than 100% overload for too long. Troubleshooting • Check for motor overheating. • • Check if the motor is mechanically overloaded. Check that the motor current set in parameter 1-24 Motor Current is correct. • Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. • If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan. • Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the drive to the motor more accurately and reduces thermal loading. WARNING/ALARM 11, Motor thermistor overtemp Check whether the thermistor is disconnected. Select whether the drive issues a warning or an alarm in parameter 1-90 Motor Thermal Protection. Troubleshooting • Check for motor overheating. • • Check if the motor is mechanically overloaded. • When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. Select the terminal to use in parameter 1-93 Thermistor Resource. When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 or 54 is set for voltage. Check that parameter 1-93 Thermistor Resource selects terminal 53 or 54. WARNING/ALARM 12, Torque limit The torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an alarm. Troubleshooting • If the motor torque limit is exceeded during ramp-up, extend the ramp-up time. • If the generator torque limit is exceeded during ramp-down, extend the ramp-down time. • If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque. • Check the application for excessive current draw on the motor. WARNING/ALARM 13, Over current The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts approximately 1.5 s, then the drive trips and issues an alarm. Shock loading or quick acceleration with high-inertia loads can cause this fault. If the acceleration during ramp-up is quick, the fault can also appear after kinetic back-up. If extended mechanical brake control is selected, a trip can be reset externally. Troubleshooting • Remove power to the drive. • • • • Check that the motor shaft can be turned. 9 9 Check that the motor size matches the drive. Check that the motor data is correct in parameters 1-20 to 1-25. For parallel drive systems, check for output cable imbalances in size and length between phases and between drive modules. ALARM 14, Earth (ground) fault There is current from the output phase to ground, either in the cable between the drive and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the drive and current going into the drive from the motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the drive must be the same as the current going into the drive. Troubleshooting • Remove power to the drive and repair the ground fault. • Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter. • Reset any potential individual offset in the 3 current transducers in the drive. Perform the manual initialization or perform a complete AMA. This method is most relevant after changing the power card. ALARM 15, Hardware mismatch A fitted option is not operational with the present control card hardware or software. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 85 9 9 Maintenance, Diagnostics, a... VLT® AutomationDrive FC 302 Record the value of the following parameters and contact Danfoss. • Parameter 15-40 FC Type. • • • • • • • • Parameter 15-41 Power Section. Parameter 15-42 Voltage. Parameter 15-43 Software Version. Parameter 15-45 Actual Typecode String. Parameter 15-49 SW ID Control Card. Parameter 15-50 SW ID Power Card. Parameter 15-60 Option Mounted. Parameter 15-61 Option SW Version (for each option slot). There is short-circuiting in the motor or motor wiring. WARNING HIGH VOLTAGE Drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury. ALARM 16, Short circuit Troubleshooting • Remove the power to the drive and repair the short circuit. • Check that the drive contains the correct current scaling card and the correct number of current scaling cards for the system. WARNING/ALARM 17, Control word timeout There is no communication to the drive. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0] Off. If parameter 8-04 Control Word Timeout Function is set to [5] Stop and trip, a warning appears, and the drive ramps down to a stop and shows an alarm. Troubleshooting • Check the connections on the serial communication cable. • Increase parameter 8-03 Control Word Timeout Time. • Check the operation of the communication equipment. • Verify that proper EMC installation was performed. WARNING/ALARM 20, Temp. input error The temperature sensor is not connected. WARNING/ALARM 21, Parameter error The parameter is out of range. The parameter number is shown in the display. 86 Troubleshooting • Set the affected parameter to a valid value. WARNING/ALARM 22, Hoist mechanical brake The value of this warning/alarm indicates the cause:. 0 = The torque reference was not reached before timeout (parameter 2-27 Torque Ramp Up Time). 1 = Expected brake feedback was not received before timeout (parameter 2-23 Activate Brake Delay, parameter 2-25 Brake Release Time). WARNING 23, Internal fan fault The fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled). There is a feedback sensor mounted in the fan. If the fan is commanded to run and there is no feedback from the sensor, this alarm appears. This alarm also shows if there is a communication error between the fan power card and the control card. Check the alarm log for the report value associated with this warning. If the report value is 2, there is a hardware problem with 1 of the fans. If the report value is 12, there is a communication problem between the fan power card and the control card. Fan troubleshooting • Cycle power to the drive and check that the fan operates briefly at start-up. • Check for proper fan operation. Use parameter group 43-** Unit Readouts to show the speed of each fan. Fan power card troubleshooting • Check the wiring between the fan power card and the control card. • • Fan power card may need to be replaced. Control card may need to be replaced. WARNING 24, External fan fault The fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled). A feedback sensor is mounted in the fan. If the fan is commanded to run and there is no feedback from the sensor, this alarm appears. This alarm also shows if there is a communication error between the power card and the control card. Check the alarm log for the report value associated with this warning. If the report value is 1, there is a hardware problem with 1 of the fans. If the report value is 11, there is a communication problem between the power card and the control card. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Maintenance, Diagnostics, a... Operating Guide Fan troubleshooting • Cycle power to the drive and check that the fan operates briefly at start-up. • Check for proper fan operation. Use parameter group 43-** Unit Readouts to show the speed of each fan. Power card troubleshooting • Check the wiring between the power card and the control card. • • Power card may need to be replaced. Control card may need to be replaced. WARNING 25, Brake resistor short circuit The brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled and the warning appears. The drive is still operational, but without the brake function. Troubleshooting • Remove the power to the drive and replace the brake resistor (refer to parameter 2-15 Brake Check). • In parallel drive systems, check the brake parallel connections. WARNING/ALARM 26, Brake resistor power limit The power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run-time. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-16 AC brake Max. Current. The warning is active when the dissipated braking power is higher than 90% of the brake resistor power. If option [2] Trip is selected in parameter 2-13 Brake Power Monitoring, the drive trips when the dissipated braking power reaches 100%. The brake transistor is monitored during operation, and if a short circuit occurs, the brake function is disabled, and a warning is issued. The drive is still operational, but since the brake transistor has short-circuited, substantial power is transmitted to the brake resistor, even if it is inactive. WARNING OVERHEATING RISK A surge in power can cause the brake resistor to overheat and possibly catch fire. Failure to remove power to the drive and remove the brake resistor can cause equipment damage. Troubleshooting • Remove power to the drive. • • Troubleshooting • Check parameter 2-15 Brake Check. ALARM 29, Heat sink temp The maximum temperature of the heat sink has been exceeded. The temperature fault does not reset until the temperature drops below a defined heat sink temperature. The trip and reset points are different based on the drive power size. Troubleshooting Check for the following conditions: • Ambient temperature too high. • • • • • Motor cable too long. Incorrect airflow clearance above and below the drive. Blocked airflow around the drive. Damaged heat sink fan. Dirty heat sink. For drives in enclosure sizes D and E, this alarm is based on the temperature measured by the heat sink sensor mounted inside the IGBT modules. 9 9 Troubleshooting • Check fan resistance. • • Check soft charge fuses. Check IGBT thermal. ALARM 30, Motor phase U missing Motor phase U between the drive and the motor is missing. WARNING HIGH VOLTAGE Drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury. • Only qualified personnel must perform installation, start-up, and maintenance. • Before performing any service or repair work, use an appropriate voltage measuring device to make sure that there is no remaining voltage on the drive. Troubleshooting • Remove the power from the drive and check motor phase U. ALARM 31, Motor phase V missing Motor phase V between the drive and the motor is missing. Remove the brake resistor. Troubleshoot the short circuit. WARNING/ALARM 28, Brake check failed The brake resistor is not connected or not working. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 87 9 9 Maintenance, Diagnostics, a... VLT® AutomationDrive FC 302 WARNING HIGH VOLTAGE Drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury. • Only qualified personnel must perform installation, start-up, and maintenance. • Before performing any service or repair work, use an appropriate voltage measuring device to make sure that there is no remaining voltage on the drive. WARNING/ALARM 36, Mains failure This warning/alarm is only active if the supply voltage to the drive system is lost and parameter 14-10 Mains Failure is not set to option [0] No Function. • Check the fuses to the drive system and the mains supply to the unit. • Check that mains voltage conforms to product specifications. • Check that the following conditions are not present: Alarm 307, Excessive THD(V), alarm 321, Voltage imbalance, warning 417, Mains undervoltage, or warning 418, Mains overvoltage is reported if any of the listed conditions are true: Troubleshooting • Remove the power from the drive and check motor phase V. ALARM 32, Motor phase W missing Motor phase W between the drive and the motor is missing. WARNING HIGH VOLTAGE Drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury. • Only qualified personnel must perform installation, start-up, and maintenance. • Before performing any service or repair work, use an appropriate voltage measuring device to make sure that there is no remaining voltage on the drive. Troubleshooting • Remove the power from the drive and check motor phase W. ALARM 33, Inrush fault Too many power-ups have occurred within a short time period. Troubleshooting • Let the unit cool to operating temperature. • Check potential DC-link fault to ground. WARNING/ALARM 34, Fieldbus communication fault The fieldbus on the communication option card is not working. WARNING/ALARM 35, Option fault An option alarm is received. The alarm is option-specific. The most likely cause is a power-up or a communication fault. 88 - The 3-phase voltage magnitude drops below 25% of the nominal mains voltage. - Any single-phase voltage exceeds 10% of the nominal mains voltage. - Percent of phase or magnitude imbalance exceeds 8%. - Voltage THD exceeds 10%. ALARM 37, Phase imbalance There is a current imbalance between the power units. ALARM 38, Internal fault When an internal fault occurs, a code number defined in Table 9.4 is shown. Troubleshooting • Cycle power. • • Check that the option is properly installed. Check for loose or missing wiring. It may be necessary to contact the Danfoss supplier or service department. Note the code number for further troubleshooting directions. Number Text 0 The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss Service Department. 256–259, 266, 268 The power EEPROM data is defective or too old. Replace the power card. 512–519 Internal fault. Contact the Danfoss supplier or Danfoss Service Department. 783 1024–1284 Parameter value outside of minimum/maximum limits. Internal fault. Contact the Danfoss supplier or Danfoss Service Department. 1299 The option SW in slot A is too old. 1300 The option SW in slot B is too old. 1301 The option SW in slot C0 is too old. 1302 The option SW in slot C1 is too old. 1315 The option SW in slot A is not supported (not allowed). Danfoss A/S © 09/2018 All rights reserved. MG34U502 Maintenance, Diagnostics, a... Number Operating Guide Text 1316 The option SW in slot B is not supported (not allowed). 1317 The option SW in slot C0 is not supported (not allowed). 1318 The option SW in slot C1 is not supported (not allowed). 1360–2819 Internal fault. Contact the Danfoss supplier or Danfoss Service Department. 2561 Replace control card. 2820 LCP stack overflow. 2821 Serial port overflow. 2822 USB port overflow. 3072–5122 Parameter value is outside its limits. 5123 Option in slot A: Hardware incompatible with control board hardware. 5124 Option in slot B: Hardware incompatible with control board hardware. 5125 Option in slot C0: Hardware incompatible with control board hardware. 5126 Option in slot C1: Hardware incompatible with control board hardware. 5127 Illegal option combination (2 options of the same kind mounted, or encoder in E0 and resolver in E1 or similar). 5168 Safe stop/safe torque off was detected on a control card that does not have safe stop/safe torque off. 5376–65535 Internal fault. Contact the Danfoss supplier or Danfoss Service Department. Table 9.4 Internal Fault Codes ALARM 39, Heat sink sensor No feedback from the heat sink temperature sensor. The signal from the IGBT thermal sensor is not available on the power card. Troubleshooting • Check the ribbon cable between the power card and gatedrive card. • • Check for a defective power card. Check for a defective gatedrive card. WARNING 40, Overload of digital output terminal 27 Check the load connected to terminal 27 or remove the short-circuit connection. Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode. WARNING 41, Overload of digital output terminal 29 Check the load connected to terminal 29 or remove the short-circuit connection. Also check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode. WARNING 42, Overload of digital output on X30/6 or overload of digital output on X30/7 For terminal X30/6, check the load connected to terminal X30/6 or remove the short-circuit connection. Also check parameter 5-32 Term X30/6 Digi Out (MCB 101) (VLT® General Purpose I/O MCB 101). For terminal X30/7, check the load connected to terminal X30/7 or remove the short-circuit connection. Check parameter 5-33 Term X30/7 Digi Out (MCB 101) (VLT® General Purpose I/O MCB 101). ALARM 43, Ext. supply VLT® Extended Relay Option MCB 113 is mounted without external 24 V DC. Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC, [0] No. A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle. ALARM 45, Earth fault 2 Ground fault. Troubleshooting • Check for proper grounding and loose connections. • • 9 9 Check for proper wire size. Check the motor cables for short circuits or leakage currents. ALARM 46, Power card supply The supply on the power card is out of range. There are 4 supplies generated by the switch mode power supply on the power card: • 48 V. • • • 24 V. 5 V. ±18 V. When powered with VLT® 24 V DC Supply MCB 107, only the 24 V and 5 V supplies are monitored. When powered with 3-phase mains voltage, all 4 supplies are monitored. Troubleshooting • Check for a defective power card. • • • Check for a defective control card. • Check D-sized drives for a defective heat sink fan, top fan, or door fan. • Check E-sized drives for a defective mixing fan. Check for a defective option card. If a 24 V DC supply is used, verify proper supply power. WARNING 47, 24 V supply low The supply on the power card is out of range. There are 4 supplies generated by the switch mode supply (SMPS) on the power card: MG34U502 Danfoss A/S © 09/2018 All rights reserved. 89 9 9 Maintenance, Diagnostics, a... • • • • VLT® AutomationDrive FC 302 48 V. 24 V. 5 V. ±18 V. Troubleshooting • Check for a defective power card. WARNING 48, 1.8 V supply low The 1.8 V DC supply used on the control card is outside of the allowable limits. The supply is measured on the control card. Troubleshooting • Check for a defective control card. • If an option card is present, check for overvoltage. WARNING 49, Speed limit The warning is shown when the speed is outside of the specified range in parameter 4-11 Motor Speed Low Limit [RPM] and parameter 4-13 Motor Speed High Limit [RPM]. When the speed is below the specified limit in parameter 1-86 Trip Speed Low [RPM] (except when starting or stopping), the drive trips. ALARM 50, AMA calibration failed Contact the Danfoss supplier or Danfoss service department. ALARM 51, AMA check Unom and Inom The settings for motor voltage, motor current, and motor power are wrong. Troubleshooting • Check the settings in parameters 1-20 to 1-25. ALARM 52, AMA low Inom The motor current is too low. Troubleshooting • Check the settings in parameter 1-24 Motor Current. ALARM 53, AMA motor too big The motor is too large for the AMA to operate. ALARM 54, AMA motor too small The motor is too small for the AMA to operate. ALARM 55, AMA parameter out of range The AMA cannot run because the parameter values of the motor are outside of the acceptable range. ALARM 56, AMA interrupted by user The AMA is manually interrupted. ALARM 57, AMA internal fault Try to restart the AMA. Repeated restarts can overheat the motor. ALARM 58, AMA Internal fault Contact the Danfoss supplier. 90 WARNING 59, Current limit The current is higher than the value in parameter 4-18 Current Limit. Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit. WARNING 60, External interlock A digital input signal indicates a fault condition external to the drive. An external interlock has commanded the drive to trip. Clear the external fault condition. To resume normal operation, apply 24 V DC to the terminal programmed for external interlock, and reset the drive. WARNING/ALARM 61, Feedback error An error is detected between calculated speed and speed measurement from feedback device. Troubleshooting • Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function. • Set the tolerable error in parameter 4-31 Motor Feedback Speed Error. • Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout. WARNING 62, Output frequency at maximum limit If the output frequency reaches the value set in parameter 4-19 Max Output Frequency, the drive issues a warning. The warning ceases when the output drops below the maximum limit. If the drive is unable to limit the frequency, it trips and issues an alarm. The latter may happen in the flux mode if the drive loses control of the motor. Troubleshooting • Check the application for possible causes. • Increase the output frequency limit. Ensure that the system can operate safely at a higher output frequency. ALARM 63, Mechanical brake low The actual motor current has not exceeded the release brake current within the start delay time window. WARNING 64, Voltage limit The combination of load and speed requires a motor voltage higher than the actual DC-link voltage. WARNING/ALARM 65, Control card over temperature The cutout temperature of the control card is 85 °C (185 °F). Troubleshooting • Check that the ambient operating temperature is within the limits. • • • Check for clogged filters. Check the fan operation. Check the control card. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Maintenance, Diagnostics, a... Operating Guide WARNING 66, Heat sink temperature low The drive is too cold to operate. This warning is based on the temperature sensor in the IGBT module. Increase the ambient temperature of the unit. Also, a trickle amount of current can be supplied to the drive whenever the motor is stopped by setting parameter 2-00 DC Hold/Preheat Current to 5% and parameter 1-80 Function at Stop. ALARM 67, Option module configuration has changed One or more options have either been added or removed since the last power-down. Check that the configuration change is intentional and reset the unit. ALARM 68, Safe Stop activated Safe Torque Off (STO) has been activated. To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal (via bus, digital I/O, or by pressing [Reset]). ALARM 69, Power card temperature The temperature sensor on the power card is either too hot or too cold. Troubleshooting • Check that the ambient operating temperature is within limits. • • • Check for clogged filters. Check fan operation. Check the power card. ALARM 70, Illegal FC configuration The control card and power card are incompatible. To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers of the cards. WARNING/ALARM 71, PTC 1 Safe Stop Safe Torque Off (STO) has been activated from the VLT® PTC Thermistor Card MCB 112 because the motor is too warm. Once the motor cools and the digital input from the MCB 112 is deactivated, normal operation can resume when the MCB 112 applies 24 V DC to terminal 37 again. When the motor is ready for normal operation, a reset signal is sent (via serial communication, digital I/O, or by pressing [Reset] on the LCP). If automatic restart is enabled, the motor can start when the fault is cleared. ALARM 72, Dangerous failure STO with trip lock. An unexpected combination of STO commands has occurred: • VLT® PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled. • MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 1 warning in parameter 5-19 Terminal 37 Safe Stop), STO is activated, and X44/10 is not activated. WARNING 73, Safe Stop auto restart Safe Torque Off (STO) activated. With automatic restart enabled, the motor can start when the fault is cleared. MG34U502 ALARM 74, PTC Thermistor Alarm related to VLT® PTC Thermistor Card MCB 112. The PTC is not working. ALARM 75, Illegal profile sel. Do not write the parameter value while the motor is running. Stop the motor before writing the MCO profile to parameter 8-10 Control Word Profile. WARNING 76, Power unit setup The required number of power units does not match the detected number of active power units. If the power card connection is lost, the unit also triggers this warning. Troubleshooting • Confirm that the spare part and its power card are the correct part number. • Ensure that the 44-pin cables between the MDCIC and power cards are mounted properly. WARNING 77, Reduced power mode This alarm applies to only multi-drive systems. The system is operating in reduced power mode (fewer than the allowed number of drive modules). This warning is generated on power cycle when the system is set to run with fewer drive modules and remains on. ALARM 78, Tracking error The difference between setpoint value and actual value exceeds the value in parameter 4-35 Tracking Error. Troubleshooting • Disable the function or select an alarm/warning in parameter 4-34 Tracking Error Function. • Investigate the mechanics around the load and motor. Check feedback connections from motor encoder to drive. • Select motor feedback function in parameter 4-30 Motor Feedback Loss Function. • Adjust the tracking error band in parameter 4-35 Tracking Error and parameter 4-37 Tracking Error Ramping. ALARM 79, Illegal power section configuration The scaling card has an incorrect part number or is not installed. Also, the MK101 connector on the power card could not be installed. ALARM 80, Drive initialised to default value Parameter settings are initialized to default settings after a manual reset. To clear the alarm, reset the unit. ALARM 81, CSIV corrupt CSIV file has syntax errors. ALARM 82, CSIV parameter error CSIV failed to initialize a parameter. ALARM 83, Illegal option combination The mounted options are incompatible. ALARM 84, No safety option The safety option was removed without applying a general reset. Reconnect the safety option. Danfoss A/S © 09/2018 All rights reserved. 91 9 9 9 9 Maintenance, Diagnostics, a... VLT® AutomationDrive FC 302 ALARM 88, Option detection A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has been changed. • To apply the change, enable option layout changes in parameter 14-89 Option Detection. • Alternatively, restore the correct option configuration. WARNING 89, Mechanical brake sliding The hoist brake monitor detects a motor speed exceeding 10 RPM. ALARM 90, Feedback monitor Check the connection to encoder/resolver option and, if necessary, replace VLT® Encoder Input MCB 102 or VLT® Resolver Input MCB 103. ALARM 91, Analog input 54 wrong settings Set switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54. ALARM 96, Start delayed The motor start has been delayed due to short-cycle protection. Parameter 22-76 Interval between Starts is enabled. Troubleshooting • Troubleshoot the system and reset the drive after clearing the fault. WARNING 97, Stop delayed Stopping the motor has been delayed because the motor has been running for less than the minimum time specified in parameter 22-77 Minimum Run Time. WARNING 98, Clock fault Time is not set, or the RTC clock has failed. Reset the clock in parameter 0-70 Date and Time. ALARM 99, Locked rotor The rotor is blocked. WARNING/ALARM 104, Mixing fan fault The fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The mixing-fan fault can be configured as a warning or an alarm trip in parameter 14-53 Fan Monitor. Troubleshooting • Cycle power to the drive to determine if the warning/alarm returns. WARNING/ALARM 122, Mot. rotat. unexp. The drive performs a function that requires the motor to be at standstill, for example DC hold for PM motors. ALARM 144, Inrush Supply A supply voltage on the inrush card is out of range. See the bit field result report value for more details. • • 92 Bit 2: Vcc high. • • Bit 4: Vdd high. Bit 5: Vdd low. ALARM 145, External SCR disable The alarm indicates a series DC-link capacitor voltage imbalance. WARNING/ALARM 146, Mains voltage Mains voltage is outside valid operating range. The following report values provide more details. • • Voltage too low: 0=R-S, 1=S-T, 2=T-R Voltage too high: 3=R-S, 4=S-T, 5=T-R WARNING/ALARM 147, Mains frequency Mains frequency is outside valid operating range. Report value provides more details. • • 0: frequency too low. 1: frequency too high. WARNING/ALARM 148, System temp One or more of the system temperature measurements is too high. WARNING 163, ATEX ETR cur.lim.warning The drive has run above the characteristic curve for more than 50 s. The warning is activated at 83% and deactivated at 65% of the allowed thermal overload. ALARM 164, ATEX ETR cur.lim.alarm Operating above the characteristic curve for more than 60 s within a period of 600 s activates the alarm, and the drive trips. WARNING 165, ATEX ETR freq.lim.warning The drive is running for more than 50 s below the allowed minimum frequency (parameter 1-98 ATEX ETR interpol. points freq.). ALARM 166, ATEX ETR freq.lim.alarm The drive has operated for more than 60 s (in a period of 600 s) below the allowed minimum frequency (parameter 1-98 ATEX ETR interpol. points freq.). WARNING 200, Fire mode The drive is operating in fire mode. The warning clears when fire mode is removed. Refer to the fire mode data in the alarm log. WARNING 201, Fire mode was active The drive has entered fire mode. Cycle power to the unit to remove the warning. Refer to the fire mode data in the alarm log. WARNING 202, Fire mode limits exceeded While operating in fire mode, 1 or more alarm conditions that would normally trip the unit have been ignored. Operating in this condition voids unit warranty. Cycle power to the unit to remove the warning. Refer to the fire mode data in the alarm log. Bit 3: Vcc low. Danfoss A/S © 09/2018 All rights reserved. MG34U502 Maintenance, Diagnostics, a... Operating Guide WARNING 203, Missing motor With a drive operating multi-motors, an underload condition was detected. This condition can indicate a missing motor. Inspect the system for proper operation. ALARM 246, Power card supply This alarm is only for multi-drive systems. It is equivalent to alarm 46, Power card supply. The report value in the alarm log indicates which drive module generated the alarm: WARNING 204, Locked rotor With a drive operating multi-motors, an overload condition was detected. This condition can indicate a locked rotor. Inspect the motor for proper operation. WARNING 219, Compressor interlock At least 1 compressor is inversely interlocked via a digital input. The interlocked compressors can be viewed in parameter 25-87 Inverse Interlock. ALARM 243, Brake IGBT This alarm is only for multi-drive systems. It is equivalent to alarm 27, Brake chopper fault. The report value in the alarm log indicates which drive module generated the alarm. This IGBT fault can be caused by any of the following: • • • 1 = Left drive module. 2 = Second drive module from left. 3 = Third drive module from left (in 4-module module systems). 4 = Fourth drive module from left (in 4-module module systems). ALARM 247, Power card temperature This alarm is only for multi-drive systems. It is equivalent to alarm 69, Power card temperature. The report value in the alarm log indicates which drive module generated the alarm: 1 = Left drive module. The DC fuse is blown. 2 = Second drive module from left. The brake jumper is not in position. 3 = Third drive module from left (in 4-module module systems). The Klixon switch opened due to an overtemperature condition in the brake resistor. The report value in the alarm log indicates which drive module generated the alarm: 1 = Left drive module. 2 = Second drive module from left. 3 = Third drive module from left (in 4-module module systems). 4 = Fourth drive module from left (in 4-module module systems). ALARM 248, Illegal power section configuration This alarm is only for multi-drive systems. It is equivalent to alarm 79, Illegal power section configuration. The report value in the alarm log indicates which drive module generated the alarm: 1 = Left drive module. 4 = Fourth drive module from left (in 4-module module systems). ALARM 245, Heat sink sensor No feedback from the heat sink temperature sensor. The signal from the IGBT thermal sensor is not available on the power card. This alarm is equivalent to alarm 39, Heat sink sensor. The report value in the alarm log indicates which drive module generated the alarm: 2 = Second drive module from left. 3 = Third drive module from left (in 4-module module systems). 4 = Fourth drive module from left (in 4-module module systems). Troubleshooting Check the following: 4 = Fourth drive module from left (in 4-module module systems). Troubleshooting Check the following: The current scaling cards on the MDCIC. WARNING 250, New spare part The power or switch mode supply has been exchanged. Restore the drive type code in the EEPROM. Select the correct type code in parameter 14-23 Typecode Setting according to the label on the drive. Remember to select Save to EEPROM at the end. WARNING 251, New type code The power card or other components have been replaced and the type code has been changed. Power card. Gatedrive card. Ribbon cable between the power card and the gatedrive card. MG34U502 3 = Third drive module from left (in 4-module module systems). • 1 = Left drive module. • • • 2 = Second drive module from left. Troubleshooting • Reset to remove the warning and to resume normal operation. Danfoss A/S © 09/2018 All rights reserved. 93 9 9 Maintenance, Diagnostics, a... VLT® AutomationDrive FC 302 9.6 Troubleshooting Symptom Possible cause Test Solution Display dark/No function Missing input power. See Table 6.1. Check the input power source. Missing or open fuses. See Open power fuses in this table for possible Follow the recommendations provided. causes. No power to the LCP. Check the LCP cable for proper connection or Replace the faulty LCP or connection damage. cable. Shortcut on control voltage Check the 24 V control voltage supply for (terminal 12 or 50) or at control terminal 12/13 to 20–39, or 10 V supply for terminals. terminals 50–55. Wire the terminals properly. Incompatible LCP (LCP from – Use only LCP 101 (P/N 130B1124) or LCP 102 (P/N 130B1107). – Press [Status] + [â–²]/[â–¼] to adjust the VLT® 2800 or 5000/6000/8000/ FCD or FCM). Wrong contrast setting. contrast. Display (LCP) is defective. Test using a different LCP. Internal voltage supply fault or SMPS is defective. – Replace the faulty LCP or connection cable. Contact supplier. Intermittent display Overloaded supply (SMPS) due To rule out a problem in the control wiring, If the display stays lit, the problem is in to improper control wiring or a disconnect all control wiring by removing the the control wiring. Check the wiring for fault within the AC drive. terminal blocks. shorts or incorrect connections. If the display continues to cut out, follow the procedure for Display dark/No function. Motor not running Service switch open or missing Check if the motor is connected and the motor connection. connection is not interrupted by a service switch or other device. Connect the motor and check the service switch. No mains power with 24 V DC option card. If the display is functioning, but there is no output, check that mains power is applied to the AC drive. Apply mains power. LCP Stop. Check if [Off] has been pressed. Press [Auto On] or [Hand On] (depending on operating mode). Missing start signal (Standby). Check parameter 5-10 Terminal 18 Digital Input Apply a valid start signal. for correct setting for terminal 18. Use default setting. Motor coast signal active (Coasting). Check parameter 5-12 Terminal 27 Digital Input Apply 24 V on terminal 27 or program for correct setting for terminal 27 (use default this terminal to [0] No operation. setting). Wrong reference signal source. Check reference signal: • Local. 9 9 • • • • • Motor running in wrong direction Preset reference active? Terminal connection correct? Scaling of terminals correct? Reference signal available? Motor rotation limit. Check that parameter 4-10 Motor Speed Direction is programmed correctly. Active reversing signal. Check if a reversing command is programmed Deactivate reversing signal. for the terminal in parameter group 5-1* Digital inputs. Wrong motor phase connection. 94 Remote or bus reference? Program correct settings. Check parameter 3-13 Reference Site. Set preset reference active in parameter group 3-1* References. Check for correct wiring. Check scaling of terminals. Check reference signal. – Danfoss A/S © 09/2018 All rights reserved. Program correct settings. See chapter 7.3.1 Warning - Motor Start. MG34U502 Maintenance, Diagnostics, a... Operating Guide Symptom Possible cause Test Motor is not reaching maximum speed Frequency limits set wrong. Check output limits in parameter 4-13 Motor Program correct limits. Speed High Limit [RPM], parameter 4-14 Motor Speed High Limit [Hz], and parameter 4-19 Max Output Frequency. Reference input signal not scaled correctly. Check reference input signal scaling in parameter group 6-0* Analog I/O mode and parameter group 3-1* References. Motor speed unstable Possible incorrect parameter settings. Check the settings of all motor parameters, Check settings in parameter group 1-6* including all motor compensation settings. Load Depen. Setting. For closed-loop For closed-loop operation, check PID settings. operation, check settings in parameter group 20-0* Feedback. Motor runs rough Possible overmagnetization. Check for incorrect motor settings in all motor parameters. Check motor settings in parameter groups 1-2* Motor data, 1-3* Adv Motor Data, and 1-5* Load Indep. Setting. Motor does not brake Possible incorrect settings in the brake parameters. Rampdown times may be too short. Check brake parameters. Check ramp time settings. Check parameter groups 2-0* DC Brake and 3-0* Reference Limits. Open power fuses Phase-to-phase short. Motor or panel has a short phase-to-phase. Check motor and panel phases for shorts. Eliminate any shorts detected. Motor overload. Motor is overloaded for the application. Perform start-up test and verify that motor current is within specifications. If motor current is exceeding the nameplate full load current, the motor can run only with reduced load. Review the specifications for the application. Loose connections. Mains current imbalance greater than 3% Solution Perform pre-start-up check for loose connections. Program correct settings. Tighten loose connections. Problem with mains power (see Rotate input power leads into the 1 position: alarm 4, Mains phase loss A to B, B to C, C to A. description). If imbalanced leg follows the wire, it is a power problem. Check the mains supply. Problem with the AC drive. If the imbalanced leg stays on same input terminal, it is a problem with the AC drive. Contact supplier. Motor current Problem with motor or motor imbalance wiring. greater than 3% Problem with AC drive. Rotate input power leads into the AC drive 1 position: A to B, B to C, C to A. Rotate output motor cables 1 position: U to V, If the imbalanced leg follows the wire, the V to W, W to U. problem is in the motor or motor wiring. Check motor and motor wiring. Rotate output motor cables 1 position: U to V, If the imbalanced leg stays on same V to W, W to U. output terminal, it is a problem with the unit. Contact supplier. AC drive acceleration problems Motor data are entered incorrectly. If warnings or alarms occur, see chapter 9.5 List of Warnings and Alarms. Check that motor data are entered correctly. Increase the ramp-up time in parameter 3-41 Ramp 1 Ramp Up Time. Increase current limit in parameter 4-18 Current Limit. Increase torque limit in parameter 4-16 Torque Limit Motor Mode. AC drive deceleration problems Motor data are entered incorrectly. If warnings or alarms occur, see chapter 9.5 List of Warnings and Alarms. Check that motor data are entered correctly. Increase the ramp-down time in parameter 3-42 Ramp 1 Ramp Down Time. Enable overvoltage control in parameter 2-17 Over-voltage Control. Table 9.5 Troubleshooting MG34U502 Danfoss A/S © 09/2018 All rights reserved. 95 9 9 10 10 Specifications VLT® AutomationDrive FC 302 10 Specifications 10.1 Electrical Data 10.1.1 Electrical Data for Enclosures D1h–D4h, 3x200–240 V N45K VLT® AutomationDrive FC 302 N55K High/normal overload (High overload=150% current during 60 s. Normal overload=110% current during 60 s) HO NO HO Typical shaft output at 230 V [kW] 45 55 55 75 Typical shaft output at 230 V [hp] 60 75 75 100 Enclosure size NO D1h/D3h Output current (3-phase) Continuous (at 230 V) [A] 160 190 190 240 Intermittent (60 s overload) (at 230 V) [A] 240 209 285 264 Continuous kVA (at 230 V) [kVA] 64 76 76 96 154 183 183 231 Maximum input current Continuous (at 230V) [A] Maximum number and size of cables per phase Mains, motor, brake, and load share [mm2 (AWG)] 2x95 (2x3/0) 2x95 (2x3/0) 315 350 Maximum external mains fuses [A]1) Estimated power loss at 230 V 1482 [W]2), 3) 1505 0.97 Efficiency3) Output frequency [Hz] 1794 2398 0.97 0–590 0–590 Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) Control card overtemperature trip [°C (°F)] 75 (167) 75 (167) Table 10.1 Electrical Data for Enclosures D1h/D3h, Mains Supply 3x200–240 V AC 1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers. 2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W. 3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency. 96 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide N75K VLT® AutomationDrive FC 302 High/normal overload (High overload=150% current during 60 s. Normal overload=110% current during 60 s) HO N90K NO N110 N150 HO NO HO NO HO NO Typical shaft output at 230 V [kW] 75 90 90 110 110 150 150 160 Typical shaft output at 230 V [hp] 100 120 120 150 150 200 200 215 Enclosure size D2h/D4h Output current (3-phase) Continuous (at 230 V) [A] 240 302 302 361 361 443 443 535 Intermittent (60 s overload) (at 230 V) [A] 360 332 453 397 542 487 665 589 Continuous kVA (at 230 V) [kVA] 96 120 120 144 144 176 176 213 231 291 291 348 348 427 427 516 Maximum input current Continuous (at 230 V) [A] Maximum number and size of cables per phase Mains, motor, brake, and load share [mm2 (AWG)] Maximum external mains fuses 2x185 (2x400 mcm) Estimated power loss at 230 V [W]2), 3) 2x185 (2x400 mcm) 2x185 (2x400 mcm) 2x185 (2x400 mcm) 400 [A]1) 1990 550 2623 2613 630 3284 3195 800 4117 4103 5209 0.97 0.97 0.97 0.97 0–590 0–590 0–590 0–590 Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) 110 (230) Control card overtemperature trip [°C (°F)] 80 (176) 80 (176) 80 (176) 80 (176) Efficiency3) Output frequency [Hz] Table 10.2 Electrical Data for Enclosures D2h/D4h, Mains Supply 3x200–240 V AC 1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers. 2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W. 3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 97 10 10 10 10 Specifications VLT® AutomationDrive FC 302 10.1.2 Electrical Data for Enclosures D1h–D8h, 3x380–500 V N90K VLT® AutomationDrive FC 302 High/normal overload (High overload=150% current during 60 s. Normal overload=110% current during 60 s) N110 HO NO N132 HO NO HO NO Typical shaft output at 400 V [kW] 90 110 110 132 132 160 Typical shaft output at 460 V [hp] 125 150 150 200 200 250 Typical shaft output at 500 V [kW] 110 132 132 160 160 200 Enclosure size D1h/D3h/D5h/D6h Output current (3-phase) Continuous (at 400 V) [A] 177 212 212 260 260 315 Intermittent (60 s overload) (at 400 V)[A] 266 233 318 286 390 347 Continuous (at 460/500 V) [A] 160 190 190 240 240 302 Intermittent (60 s overload) (at 460/500 V) [kVA] 240 209 285 264 360 332 Continuous kVA (at 400 V) [kVA] 123 147 147 180 180 218 Continuous kVA (at 460 V) [kVA] 127 151 151 191 191 241 Continuous kVA (at 500 V) [kVA] 139 165 165 208 208 262 Continuous (at 400 V) [A] 171 204 204 251 251 304 Continuous (at 460/500 V) [A] 154 183 183 231 231 291 Maximum input current Maximum number and size of cables per phase - Mains, motor, brake, and load share [mm2 (AWG)] 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 315 350 400 Maximum external mains fuses [A]1) [W]2), 3) 2031 2559 2289 2954 2923 3770 Estimated power loss at 460 V [W]2), 3) 1828 2261 2051 2724 2689 3628 Estimated power loss at 400 V 0.98 Efficiency3) Output frequency [Hz] 0.98 0.98 0–590 0–590 0–590 Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) Control card overtemperature trip [°C (°F)] 75 (167) 75 (167) 75 (167) Table 10.3 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x380–500 V AC 1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers. 2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W. 3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency. 98 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide N160 VLT® AutomationDrive FC 302 N200 N250 High/normal overload (High overload=150% current during 60 s. Normal overload=110% current during 60 s) HO NO HO NO HO NO Typical shaft output at 400 V [kW] 160 200 200 250 250 315 Typical shaft output at 460 V [hp] 250 300 300 350 350 450 Typical shaft output at 500 V [kW] 200 250 250 315 315 355 Enclosure size D2h/D4h/D7h/D8h Output current (3-phase) Continuous (at 400 V) [A] 315 395 395 480 480 588 Intermittent (60 s overload) (at 400 V)[A] 473 435 593 528 720 647 Continuous (at 460/500 V) [A] 302 361 361 443 443 535 Intermittent (60 s overload) (at 460/500 V) [kVA] 453 397 542 487 665 589 Continuous kVA (at 400 V) [kVA] 218 274 274 333 333 407 Continuous kVA (at 460 V) [kVA] 241 288 288 353 353 426 Continuous kVA (at 500 V) [kVA] 262 313 313 384 384 463 Continuous (at 400 V) [A] 304 381 381 463 463 567 Continuous (at 460/500 V) [A] 291 348 348 427 427 516 Maximum input current Maximum number and size of cables per phase 2x185 (2x400 mcm) - Mains, motor, brake, and load share [mm2 (AWG)] Maximum external mains fuses Estimated power loss at 400 V [W]2), 3) 3093 [W]2), 3) 2872 Estimated power loss at 460 V 2x185 (2x400 mcm) 550 [A]1) 630 4116 4039 3569 3575 0.98 Efficiency3) Output frequency [Hz] 2x185 (2x400 mcm) 800 5137 5004 4566 4458 0.98 6674 5714 0.98 0–590 0–590 0–590 Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) Control card overtemperature trip [°C (°F)] 80 (176) 80 (176) 80 (176) 10 10 Table 10.4 Electrical Data for Enclosures D2h/D4h/D7h/D8h, Mains Supply 3x380–500 V AC 1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers. 2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W. 3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 99 10 10 Specifications VLT® AutomationDrive FC 302 10.1.3 Electrical Data for Enclosures D1h–D8h, 3x525–690 V N55K VLT® AutomationDrive FC 302 N75K N90K NO High/normal overload (High overload=150% current during 60 s. Normal overload=110% current during 60 s) HO NO HO Typical shaft output at 525 V [kW] 45 55 55 75 75 Typical shaft output at 575 V [hp] 60 75 75 100 100 Typical shaft output at 690 V [kW] 55 75 75 90 90 110 Enclosure size HO N110 NO N132 HO NO HO NO 90 90 110 110 132 125 125 150 150 200 110 132 132 160 D1h/D3h/D5h/D6h Output current (3-phase) Continuous (at 525 V) [A] 76 90 90 113 113 137 137 162 162 201 Intermittent (60 s overload) (at 525 V) [A] 114 99 135 124 170 151 206 178 243 221 Continuous (at 575/690 V) [A] 73 86 86 108 108 131 131 155 155 192 Intermittent (60 s overload) (at 575/690 V) [A] 110 95 129 119 162 144 197 171 233 211 Continuous kVA (at 525 V) [kVA] 69 82 82 103 103 125 125 147 147 183 Continuous kVA (at 575 V) [kVA] 73 86 86 108 108 131 131 154 154 191 Continuous kVA (at 690 V) [kVA] 87 103 103 129 129 157 157 185 185 230 Continuous (at 525 V) [A] 74 87 87 109 109 132 132 156 156 193 Continuous (at 575/690 V) 70 83 83 104 104 126 126 149 149 185 Maximum input current Maximum number and size of cables per phase - Mains, motor, brake, and load share 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 2x95 (2x3/0) 160 315 315 315 315 [mm2 (AWG)] Maximum external mains fuses [A]1) [W]2), 3) 1098 1162 1162 1428 1430 1740 1742 2101 2080 2649 Estimated power loss at 690 V [W]2), 3) 1057 1204 1205 1477 1480 1798 1800 2167 2159 2740 Estimated power loss at 575 V Efficiency3) Output frequency [Hz] 0.98 0.98 0.98 0.98 0.98 0–590 0–590 0–590 0–590 0–590 Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) 110 (230) 110 (230) Control card overtemperature trip [°C 75 (167) 75 (167) 75 (167) 75 (167) 75 (167) (°F)] Table 10.5 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC 1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers. 2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W. 3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency. 100 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide N160 VLT® AutomationDrive FC 302 N200 N250 N315 High/normal overload (High overload=150% current during 60 s. Normal overload=110% current during 60 s) HO NO HO NO HO NO HO NO Typical Shaft output at 525 V [kW] 132 160 160 200 200 250 250 315 Typical Shaft output at 575 V [hp] 200 250 250 300 300 350 350 400 Typical Shaft output at 690 V [kW] 160 200 200 250 250 315 315 400 Enclosure size D2h/D4h/D7h/D8h Output current (3-phase) Continuous (at 525 V) [A] 201 253 253 303 303 360 360 418 460 Intermittent (60 s overload) (at 525 V)[A] 301 278 380 333 455 396 540 Continuous (at 575/690 V) [A] 192 242 242 290 290 344 344 400 Intermittent (60 s overload) (at 575/690 V) [A] 288 266 363 319 435 378 516 440 Continuous kVA (at 525 V) [kVA] 183 230 230 276 276 327 327 380 Continuous kVA (at 575 V) [kVA] 191 241 241 289 289 343 343 398 Continuous kVA (at 575/690 V) [kVA] 229 289 289 347 347 411 411 478 Continuous (at 525 V) [A] 193 244 244 292 292 347 347 403 Continuous (at 575/690 V) 185 233 233 279 279 332 332 385 Maximum input current Maximum number and size of cables per phase - Mains, motor, brake, and load share [mm2 2x185 (2x400) 2x185 (2x400) 2x185 (2x400) 2x185 (2x400) (AWG)] 550 Maximum external mains fuses [A]1) Estimated power loss at 575 V [W]2), 3) 2361 [W]2), 3) 2446 Estimated power loss at 690 V 550 3074 3012 3175 3123 550 3723 3642 3851 3771 550 4465 4146 4614 4258 5028 5155 0.98 0.98 0.98 0.98 0–590 0–590 0–590 0–590 Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) 110 (230) Control card overtemperature trip [°C (°F)] 80 (176) 80 (176) 80 (176) 80 (176) Efficiency3) Output frequency [Hz] 10 10 Table 10.6 Electrical Data for Enclosures D2h/D4h/D7h/D8h, Mains Supply 3x525–690 V AC 1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers. 2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W. 3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 101 10 10 Specifications VLT® AutomationDrive FC 302 10.2 Mains Supply Mains supply (L1, L2, L3) Supply voltage 200–240 V, 380–500 V ±10%, 525–690 V ±10% Mains voltage low/mains voltage drop-out (for 380–500 V and 525–690 V only): During low mains voltage or a mains drop-out, the drive continues until the DC-link voltage drops below the minimum stop level, which corresponds typically to 15% below the lowest rated supply voltage of the drive. Power-up and full torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage of the drive. Supply frequency Maximum imbalance temporary between mains phases True power factor (λ) Displacement power factor (cos Φ) near unity Switching on input supply L1, L2, L3 (power-ups) Environment according to EN60664-1 50/60 Hz ±5% 3.0% of rated supply voltage1) ≥0.9 nominal at rated load (>0.98) Maximum 1 time/2 minute Overvoltage category III/pollution degree 2 The drive is suitable for use on a circuit capable of delivering up to 100 kA short circuit current rating (SCCR) at 240/480/600 V. 1) Calculations based on UL/IEC61800-3. 10.3 Motor Output and Torque Data Motor output (U, V, W) Output voltage Output frequency Output frequency in flux mode Switching on output Ramp times 0–100% of supply voltage 0–590 Hz1) 0–300 Hz Unlimited 0.01–3600 s 1) Dependent on voltage and power. Torque characteristics Starting torque (constant torque) Overload torque (constant torque) Maximum 150% for 60 s1), 2) Maximum 150% for 60 s1), 2) 1) Percentage relates to the nominal current of the drive. 2) Once every 10 minutes. 10.4 Ambient Conditions Environment D1h/D2h/D5h/D6h/D7h/D8h enclosure IP21/Type 1, IP54/Type 12 D3h/D4h enclosure IP20/Chassis Vibration test (standard/ruggedized) 0.7 g/1.0 g Relative humidity 5–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation) Aggressive environment (IEC 60068-2-43) H2S test Class Kd Aggressive gases (IEC 60721-3-3) Class 3C3 Test method according to IEC 60068-2-43 H2S (10 days) Ambient temperature (at SFAVM switching mode) - with derating Maximum 55 °C (131 °F)1) - with full output power of typical EFF2 motors (up to 90% output current) Maximum 50 °C (122 °F)1) - at full continuous FC output current Maximum 45 °C (113 °F)1) Minimum ambient temperature during full-scale operation 0 °C (32 °F) Minimum ambient temperature at reduced performance -10 °C (14 °F) Temperature during storage/transport -25 to +65/70 °C (13 to 149/158 °F) Maximum altitude above sea level without derating 1000 m (3281 ft) Maximum altitude above sea level with derating 3000 m (9842 ft) 1) For more information on derating, see the design guide. 102 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide EMC standards, Emission EMC standards, Immunity Energy efficiency class1) EN 61800-3 EN 61800-3 IE2 1) Determined according to EN 50598-2 at: • • • • Rated load. 90% rated frequency. Switching frequency factory setting. Switching pattern factory setting. 10.5 Cable Specifications Cable lengths and cross-sections for control cables1) Maximum motor cable length, shielded/armored Maximum motor cable length, unshielded/unarmored Maximum cross-section to motor, mains, load sharing, and brake Maximum cross-section to control terminals, rigid wire Maximum cross-section to control terminals, flexible cable Maximum cross-section to control terminals, cable with enclosed core Minimum cross-section to control terminals. 150 m (492 ft) 300 m (984 ft) See chapter 10.1 Electrical Data 1.5 mm2/16 AWG (2x0.75 mm2) 1 mm2/18 AWG 0.5 mm2/20 AWG 0.25 mm2/23 AWG 1) For power cables, see electrical data tables in chapter 10.1 Electrical Data. 10.6 Control Input/Output and Control Data Digital inputs Programmable digital inputs Terminal number Logic Voltage level Voltage level, logic 0 PNP Voltage level, logic 1 PNP Voltage level, logic 0 NPN Voltage level, logic 1 NPN Maximum voltage on input Input resistance, Ri 4 (6) 18, 19, 32, 33 PNP or NPN 0–24 V DC <5 V DC >10 V DC >19 V DC <14 V DC 28 V DC Approximately 4 kΩ 271), 291), All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 1) Terminals 27 and 29 can also be programmed as outputs. Analog inputs Number of analog inputs Terminal number Modes Mode select Voltage mode Voltage level Input resistance, Ri Maximum voltage Current mode Current level Input resistance, Ri Maximum current Resolution for analog inputs Accuracy of analog inputs MG34U502 2 53, 54 Voltage or current Switches A53 and A54 Switch A53/A54=(U) -10 V to +10 V (scaleable) Approximately 10 kΩ ±20 V Switch A53/A54=(I) 0/4 to 20 mA (scaleable) Approximately 200 Ω 30 mA 10 bit (+ sign) Maximum error 0.5% of full scale Danfoss A/S © 09/2018 All rights reserved. 103 10 10 10 10 Specifications VLT® AutomationDrive FC 302 Bandwidth 100 Hz PELV isolation +24 V 18 Control 37 Mains High voltage 130BA117.10 The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Motor Functional isolation DC-bus RS485 Illustration 10.1 PELV Isolation Pulse inputs Programmable pulse inputs 2 Terminal number pulse 29, 33 Maximum frequency at terminal 29, 33 (push-pull driven) 110 kHz Maximum frequency at terminal 29, 33 (open collector) 5 kHz Minimum frequency at terminal 29, 33 4 Hz Voltage level See Digital Inputs in chapter 10.6 Control Input/Output and Control Data Maximum voltage on input 28 V DC Input resistance, Ri Approximately 4 kΩ Pulse input accuracy (0.1–1 kHz) Maximum error: 0.1% of full scale Analog output Number of programmable analog outputs Terminal number Current range at analog output Maximum resistor load to common at analog output Accuracy on analog output Resolution on analog output 1 42 0/4–20 mA 500 Ω Maximum error: 0.8% of full scale 8 bit The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control card, RS485 serial communication Terminal number Terminal number 61 68 (P, TX+, RX+), 69 (N, TX-, RX-) Common for terminals 68 and 69 The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the supply voltage (PELV). Digital output Programmable digital/pulse outputs Terminal number Voltage level at digital/frequency output Maximum output current (sink or source) Maximum load at frequency output Maximum capacitive load at frequency output Minimum output frequency at frequency output Maximum output frequency at frequency output Accuracy of frequency output Resolution of frequency outputs 2 27, 291) 0–24 V 40 mA 1 kΩ 10 nF 0 Hz 32 kHz Maximum error: 0.1% of full scale 12 bit 1) Terminals 27 and 29 can also be programmed as inputs. The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 104 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide Control card, 24 V DC output Terminal number Maximum load 12, 13 200 mA The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs. Relay outputs Programmable relay outputs Maximum cross-section to relay terminals Minimum cross-section to relay terminals Length of stripped wire Relay 01 terminal number Maximum terminal load (AC-1)1) on 1–2 (NO) (Resistive load)2), 3) Maximum terminal load (AC-15)1) on 1–2 (NO) (Inductive load @ cosφ 0.4) Maximum terminal load (DC-1)1) on 1–2 (NO) (Resistive load) Maximum terminal load (DC-13)1) on 1–2 (NO) (Inductive load) Maximum terminal load (AC-1)1) on 1–3 (NC) (Resistive load) Maximum terminal load (AC-15)1) on 1–3 (NC) (Inductive load @ cosφ 0.4) Maximum terminal load (DC-1)1) on 1–3 (NC) (Resistive load) Maximum terminal load (DC-13)1) on 1–3 (NC) (Inductive load) Minimum terminal load on 1–3 (NC), 1–2 (NO) Environment according to EN 60664-1 Relay 02 terminal number Maximum terminal load (AC-1)1) on 4–5 (NO) (Resistive load)2), 3) Maximum terminal load (AC-15)1) on 4–5 (NO) (Inductive load @ cosφ 0.4) Maximum terminal load (DC-1)1) on 4–5 (NO) (Resistive load) Maximum terminal load (DC-13)1) on 4–5 (NO) (Inductive load) Maximum terminal load (AC-1)1) on 4–6 (NC) (Resistive load) Maximum terminal load (AC-15)1) on 4–6 (NC) (Inductive load @ cosφ 0.4) Maximum terminal load (DC-1)1) on 4–6 (NC) (Resistive load) Maximum terminal load (DC-13)1) on 4–6 (NC) (Inductive load) Minimum terminal load on 4–6 (NC), 4–5 (NO) Environment according to EN 60664-1 2 2.5 (12 AWG) 0.2 mm2 (30 AWG) 8 mm (0.3 in) 1–3 (break), 1–2 (make) 400 V AC, 2 A 240 V AC, 0.2 A 80 V DC, 2 A 24 V DC, 0.1 A 240 V AC, 2 A 240 V AC, 0.2 A 50 V DC, 2 A 24 V DC, 0.1 A 24 V DC 10 mA, 24 V AC 2 mA Overvoltage category III/pollution degree 2 4–6 (break), 4–5 (make) 400 V AC, 2 A 240 V AC, 0.2 A 80 V DC, 2 A 24 V DC, 0.1 A 240 V AC, 2 A 240 V AC, 0.2 A 50 V DC, 2 A 24 V DC, 0.1 A 24 V DC 10 mA, 24 V AC 2 mA Overvoltage category III/pollution degree 2 mm2 The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV). 1) IEC 60947 part 4 and 5. 2) Overvoltage Category II. 3) UL applications 300 V AC 2 A. Control card, +10 V DC output Terminal number Output voltage Maximum load 50 10.5 V ±0.5 V 25 mA The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Control characteristics Resolution of output frequency at 0–1000 Hz System response time (terminals 18, 19, 27, 29, 32, 33) Speed control range (open loop) Speed accuracy (open loop) ±0.003 Hz ≤2 m/s 1:100 of synchronous speed 30–4000 RPM: Maximum error of ±8 RPM All control characteristics are based on a 4-pole asynchronous motor. Control card performance Scan interval MG34U502 5 M/S Danfoss A/S © 09/2018 All rights reserved. 105 10 10 10 10 Specifications VLT® AutomationDrive FC 302 Control card, USB serial communication USB standard USB plug 1.1 (full speed) USB type B device plug NOTICE Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB connector on the drive or an isolated USB cable/converter. 10.7 Fuses and Circuit Breakers 10.7.1 Fuse Selection Installing fuses on the supply side ensures that potential damage is contained inside the drive enclosure if a component breakdown (first fault) occurs inside the drive. Use the recommended fuses to ensure compliance with EN 50178, refer to Table 10.7, Table 10.8, and Table 10.9. NOTICE Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations. D1h–D8h recommended fuses Model Bussmann part number N45K 170M2620 N55K 170M2621 N75K 170M4015 N90K 170M4015 N110 170M4016 N150 170M4018 Table 10.7 D1h–D8h Power/Semiconductor Fuse Options, 200–240 V Model Bussmann part number N90K 170M2619 N110 170M2620 N132 170M2621 N160 170M4015 N200 170M4016 N250 170M4018 Table 10.8 D1h–D8h Power/Semiconductor Fuse Options, 380–500 V Model Bussmann part number N55K 170M2616 N75K 170M2619 N90K 170M2619 N110 170M2619 N132 170M2619 N160 170M4015 N200 170M4015 N250 170M4015 N315 170M4015 Table 10.9 D1h–D8h Power/Semiconductor Fuse Options, 525–690 V 106 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide Type aR fuses are recommended for drives in enclosure sizes D3h–D4h. See Table 10.10. Model 200–240 V 380–500 V 525–690 V N45K ar-350 – – N55K ar-400 – ar-160 N75K ar-500 – ar-315 N90K ar-500 ar-315 ar-315 N110 ar-630 ar-350 ar-315 N132 – ar-400 ar-315 N150 ar-800 – – N160 – ar-500 ar-550 N200 – ar-630 ar-550 N250 – ar-800 ar-550 N315 – – ar-550 Table 10.10 D3h–D4h Power/Semiconductor Fuse Sizes Bussmann Rating LPJ-21/2SP 2.5 A, 600 V Table 10.11 D1h–D8h Space Heater Fuse Recommendation For UL compliance, use the Bussmann 170M series fuses for units supplied without a disconnect, contactor, or circuit breaker option. If a disconnect, contactor, or circuit breaker option is supplied with the drive, see Table 10.12 to Table 10.15 for SCCR ratings and UL fuse criteria. 10.7.2 Short-circuit Current Rating (SCCR) The short-circuit current rating (SCCR) represents the maximum level of short-circuit current that the drive can safely withstand. If the drive is not supplied with a mains disconnect, contactor, or circuit breaker, the SCCR of the drive is 100000 A at all voltages (200–690 V). If the drive is supplied with a mains disconnect only, the SCCR of the drive is 100000 amps at all voltages (200–600 V). See Table 10.12. If the drive is supplied with a contactor only, refer to Table 10.13 for the SCCR. If the drive contains both a contactor and disconnect, see Table 10.14. If the drive is supplied with a circuit breaker only, the SCCR depends on the voltage. Refer to Table 10.15. Enclosure size ≤ 600 V IEC/UL D5h 100000 A1) D7h 100000 A2) Table 10.12 D5h and D7h Drives Supplied with a Disconnect Only 1) With an upstream branch protection Class J fuse with maximum rating of 600 A. 2) With an upstream branch protection Class J fuse with maximum rating of 800 A. Enclosure size 415 V 480 V 600 V 690 V IEC1) UL2) UL2) IEC1) 100000 A D6h 100000 A 100000 A 100000 A D8h (excluding N250 380-500V model) 100000 A 100000 A 100000 A 100000 A D8h (N250 380-500V model only) 100000 A Contact Danfoss Not applicable Not applicable Table 10.13 D6h and D8h Drives Supplied with a Contactor Only 1) With gL/gG fuses: 425 A maximum fuse size for D6h, and 630 A maximum fuse size for D8h. 2) With external upstream Class J fuses: 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h. MG34U502 Danfoss A/S © 09/2018 All rights reserved. 107 10 10 10 10 Specifications VLT® AutomationDrive FC 302 Enclosure size 415 V 480 V 600 V IEC1) UL2) UL2) D6h 100000 A 100000 A 100000 A D8h (excluding N250 380-500V model) 100000 A 100000 A 100000 A D8h (N250 380-500V model only) 100000 A Contact Danfoss Not applicable Table 10.14 D6h and D8h Drives Supplied with a Disconnect and Contactor 1) With gL/gG fuses: 425A maximum fuse size for D6h, and 630A maximum fuse size for D8h. 2) With external upstream Class J fuses: 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h. 415 V 480 V 600 V 690 V D6h Enclosure size 120000 A 100000 A 65000 A 70000 A D8h 100000 A 100000 A 42000 A 30000 A Table 10.15 D6h and D8h Drives Supplied with a Circuit Breaker Only 10.8 Fastener Tightening Torques Apply the correct torque when tightening fasteners in the locations that are listed in Table 10.16. Too low or too high torque when fastening an electrical connection results in a bad electrical connection. To ensure correct torque, use a torque wrench. Location Bolt size Torque [Nm (in-lb)] Mains terminals M10/M12 19 (168)/37 (335) Motor terminals M10/M12 19 (168)/37 (335) Ground terminals M8/M10 9.6 (84)/19.1 (169) Brake terminals M8 9.6 (84) Load sharing terminals M10/M12 19 (168)/37 (335) Regeneration terminals (Enclosures D1h/D2h) M8 9.6 (84) Relay terminals _ 0.5 (4) Door/panel cover M5 2.3 (20) Gland plate M5 2.3 (20) Heat sink access panel M5 3.9 (35) Serial communication cover M5 2.3 (20) Table 10.16 Fastener Torque Ratings 108 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide 10.9 Enclosure Dimensions 130BE982.10 10.9.1 D1h Exterior Dimensions 99 (3.9) 164 (6.5) 10 10 500 (19.7) 667 (26.3) Illustration 10.2 Front View of D1h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 109 VLT® AutomationDrive FC 302 130BF797.10 Specifications 378 (14.9) 82 (3.2) 18 (0.7) 20 (0.8) 148 (5.8) 844 (33.2) 10 10 561 (22.1) Illustration 10.3 Side View of D1h 110 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 325 (12.8) 130BF798.10 Specifications A 33 (1.3) 246 (9.7) 25 (1.0) 180 (7.1) A 11 (0.4) 123 (4.8) 130 (5.1) 78 (3.1) 200 (7.9) 893 (35.2) 844 (33.2) 10 10 656 (25.8) B 63 (2.5) 11 (0.4) 20 (0.8) B 200 (7.9) 9 (0.3) 24 (0.9) Illustration 10.4 Back View of D1h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 111 VLT® AutomationDrive FC 302 130BF669.10 Specifications 298 (11.7) 105 404 (15.9) 10 10 274 (10.8) 27 (1.0) 1 137 (5.4) 2 130BF607.10 Illustration 10.5 Door Clearance for D1h 138 (5.4) 205 (8.1) 1 Mains side 2 Motor side Illustration 10.6 Gland Plate Dimensions for D1h 112 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide 130BF321.10 10.9.2 D2h Exterior Dimensions 96 (3.8) 211 (8.3) 10 10 871 (34.3) 602 (23.7) Illustration 10.7 Front View of D2h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 113 Specifications VLT® AutomationDrive FC 302 130BF799.10 378 (14.9) 142 (5.6) 18 (0.7) 20 (0.8) 148 (5.8) 1050 (41.3) 10 10 718 (28.3) Illustration 10.8 Side View of D2h 114 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF800.10 Specifications 420 (16.5) 346 (13.6) 280 (11.0) A 33 (1.3) A 130 (5.1) 11 (0.4) 107 (4.2) 213 (8.4) 1099 (43.3) 320 (12.6) 1051 (41.4) 10 10 857 (33.7) 75 (2.9) B 11 (0.4) 20 (0.8) 24 (0.9) 9 (0.3) 271 (10.7) B Illustration 10.9 Back View of D2h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 115 130BF670.10 VLT® AutomationDrive FC 302 395 (15.6) 105 523 (20.6) Illustration 10.10 Door Clearance for D2h 369 (14.5) 27 (1.0) 185 (7.3) 2 1 130BF608.10 10 10 Specifications 145 (5.7) 196 (7.7) 1 Mains side 2 Motor side Illustration 10.11 Gland Plate Dimensions for D2h 116 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide 130BF322.10 10.9.3 D3h Exterior Dimensions 61 (2.4) 128 (5.0) 10 10 660 (26.0) 495 (19.5) Illustration 10.12 Front View of D3h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 117 VLT® AutomationDrive FC 302 130BF801.10 Specifications 375 (14.8) 82 (3.2) 39 (1.5) 18 (0.7) 20 (0.8) 10 10 844 (33.2) 148 (5.8) Illustration 10.13 Side View of D3h 118 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 250 (9.8) 180 (7.1) 130BF802.10 Specifications A A 33 (1.3) M10 123 (4.8) 130 (5.1) 25 (1.0) 909 (35.8) 11 (0.4) 78 (3.1) 200 (7.9) 889 (35.0) 844 (33.2) 10 10 656 (25.8) B 25 (1.0) 11 (0.4) M10 B 20 (0.8) 24 (0.9) 200 (7.9) 9 (0.3) Illustration 10.14 Back View of D3h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 119 Specifications VLT® AutomationDrive FC 302 130BF323.10 10.9.4 D4h Enclosure Dimensions 59 (2.3) 176 (6.9) 10 10 868 (34.2) 611 (24.1) Illustration 10.15 Front View of D4h 120 Danfoss A/S © 09/2018 All rights reserved. MG34U502 39 (1.5) Operating Guide 375 (14.8) 18 (0.7) 142 (5.6) 130BF803.10 Specifications 20 (0.8) 148 (5.8) 10 10 1050 (41.3) Illustration 10.16 Side View of D4h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 121 VLT® AutomationDrive FC 302 130BF804.10 Specifications 350 (13.8) 280 (11.0) A A 33 (1.3) 130 (5.1) 11 (0.4) 25 (1.0) 107 (4.2) 1122 (44.2) 213 (8.4) 320 (12.6) 1096 (43.1) 1051 (41.4) 10 10 857 (33.7) B 11 (0.4) B 40 (1.6) 24 (0.9) 20 (0.8) 9 (0.3) 271 (10.7) Illustration 10.17 Back View of D4h 122 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide 130BF324.10 10.9.5 D5h Exterior Dimensions 149 (5.9) 1107 (43.6) 10 10 733 (28.9) Illustration 10.18 Front View of D5h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 123 10 10 Specifications VLT® AutomationDrive FC 302 130BF805.10 381 (15.0) 115 (4.5) 23 (0.9) 161 (6.3) 1277 (50.3) Illustration 10.19 Side View of D5h 124 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF806.10 Specifications 325 (12.8) 306 (12.1) 276 (10.9) 180 (7.1) A A 63 (2.5) 123 (4.8) 15 (0.6) M10 130 (5.1) 78 (3.1) 25 (1) 4X 200 (7.9) 11 (0.4) 1324 (52.1) 10 10 1276 (50.2) 1111 (43.7) 123 (4.8) B 64 (2.5) 130 (5.1) 11 (0.4) 78 (3.1 M10 220 (8.7) 200 (7.9) B 20 (0.8) 9 (0.3) 24 (0.9) 200 (7.9) Illustration 10.20 Back View of D5h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 125 10 10 VLT® AutomationDrive FC 302 130BF828.10 Specifications 433 (17.0) 218 (8.6) 670 (26.4) Illustration 10.21 Heat Sink Access Dimensions for D5h 126 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF669.10 Specifications 298 (11.7) 105 404 (15.9) 130BF609.10 Illustration 10.22 Door Clearance for D5h 242 (9.5) 121 (4.8) 43 (1.7) 1 2 224 (8.8) 111 (4.4) 1 Mains side 2 Motor side Illustration 10.23 Gland Plate Dimensions for D5h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 127 10 10 Specifications VLT® AutomationDrive FC 302 130BF325.10 10.9.6 D6h Exterior Dimensions 159 (6.3) 1447 (57.0) 10 10 909 (35.8) Illustration 10.24 Front View of D6h 128 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF807.10 Specifications 381 (15.0) 115 (4.5) 23 (0.9) 181 (7.1) 1617 (63.7) 10 10 Illustration 10.25 Side View of D6h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 129 VLT® AutomationDrive FC 302 130BF808.10 Specifications 325 (12.8) 306 (12.1) 276 (10.9) 180 (7.1) A 63 (2.5) A 130 (5.1) 123 (4.8) M10 15 (0.6) 25 (1) 78 (3.1) 4X 200 (7.9) 11 (0.4) 1663 (65.5) 1615 (63.6) 1452 (57.2) 10 10 123 (4.8) 130 (5.1) 78 (3.1) B 200 (7.9) 11 (0.4) 64 (3.0) 559 (22.0) B M10 20 (0.8) 9 (0.1) 24 (0.9) 200 (7.9) Illustration 10.26 Back View of D6h 130 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF829.10 Specifications 433 (17.0) 218 (8.6) 1009 (39.7) 10 10 Illustration 10.27 Heat Sink Access Dimensions for D6h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 131 VLT® AutomationDrive FC 302 130BF669.10 Specifications 298 (11.7) 105 404 (15.9) 10 10 130BF609.10 Illustration 10.28 Door Clearance for D6h 242 (9.5) 121 (4.8) 43 (1.7) 1 2 224 (8.8) 111 (4.4) 1 Mains side 2 Motor side Illustration 10.29 Gland Plate Dimensions for D6h 132 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide 130BF326.10 10.9.7 D7h Exterior Dimensions 209 (8.2) 1754 (69.1) 10 10 1282 (50.5) Illustration 10.30 Front View of D7h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 133 VLT® AutomationDrive FC 302 130BF809.10 Specifications 386 (15.2) 156 (6.2) 23 (0.9) 25 (1.0) 161 (6.3) 193 (76.0) 10 10 Illustration 10.31 Side View of D7h 134 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF810.10 Specifications 420 (16.5) 411 (16.2) 374 (14.7) A A 280 (11.0) 70 (2.8) 23 (0.9) 130 (5.1) 107 (4.2) 4X 25 (1.0) 11 (0.4) 213 (8.4) 320 (12.6) M10 1953 (76.9) 10 10 978 (77.9) 1760 (69.3) B 130 (5.1) 71 (2.8) 107 (4.2) 385 (15.2) 213 (8.4) 320 (12.6) 668 (26.3) 235 (9.3) 25 (1.0) 14 (0.6) B Illustration 10.32 Back View of D7h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 135 10 10 VLT® AutomationDrive FC 302 130BF830.10 Specifications 591 (23.3) 316 (12.4) 1168 (46.0) Illustration 10.33 Heat Sink Access Dimensions for D7h 136 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF832.10 Specifications 1731 (68.1) 1537 (60.5) 10 10 468 (18.4) 271 (10.7) 2X 11 (0.4) 23 (0.9) Illustration 10.34 Wall Mount Dimensions for D7h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 137 130BF670.10 VLT® AutomationDrive FC 302 395 (15.6) 105 523 (20.6) Illustration 10.35 Door Clearance for D7h 130BF610.10 10 10 Specifications 337 (13.3) 1 2 169 (6.6) 43 (1.7) -A- 222 (8.7) 115 (4.5) 1 Mains side 2 Motor side Illustration 10.36 Gland Plate Dimensions for D7h 138 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Specifications Operating Guide 130BF327.10 10.9.8 D8h Exterior Dimensions 215 (8.5) 1699 (66.9) 10 10 767 (30.2) 1400 (55.1) 112 (4.4) Illustration 10.37 Front View of D8h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 139 10 10 VLT® AutomationDrive FC 302 130BF811.10 Specifications 406 (16.0) 156 (6.2) 23 (0.9) 25 (1.0) 162 (6.4) 2236 (88.0) Illustration 10.38 Side View of D8h 140 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF812.10 Specifications 420 (16.5) 411 (16.2) 374 (14.7) A 280 (11.0) A 130 (5.1) 70 (2.8) 107 (4.2) 23 (0.9) 4X 213 (8.4) 11 (0.4) 25 (1.0) 320 (12.6) M10 2259 (88.9) 130 (5.1) 2284 (89.9) 10 10 2065 (81.3) 107 (4.2) 213 (8.4) B 72 (2.8) 320 (12.6) 973 (38.3) 385 (15.2) 235 (9.3) 25 (1.0) 14 (0.6) B Illustration 10.39 Back View of D8h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 141 10 10 VLT® AutomationDrive FC 302 130BF831.10 Specifications 591 (23.3) 316 (12.4) 1473 (58.0) Illustration 10.40 Heat Sink Access Dimensions for D8h 142 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Operating Guide 130BF670.10 Specifications 395 (15.6) 105 523 (20.6) 10 10 130BF610.10 Illustration 10.41 Door Clearance for D8h 337 (13.3) 1 2 169 (6.6) 43 (1.7) -A- 222 (8.7) 115 (4.5) 1 Mains side 2 Motor side Illustration 10.42 Gland Plate Dimensions for D8h MG34U502 Danfoss A/S © 09/2018 All rights reserved. 143 11 11 Appendix VLT® AutomationDrive FC 302 11 Appendix 11.1 Abbreviations and Conventions mV Millivolts °C Degrees Celsius NEMA National Electrical Manufacturers Association °F Degrees Fahrenheit NTC Negative temperature coefficient Ω Ohm PM,N Nominal motor power AC Alternating current PCB Printed circuit board AEO Automatic energy optimization PE Protective earth Application control processor PELV Protective extra low voltage AMA Automatic motor adaptation PID Proportional integral derivative AWG American wire gauge PLC Programmable logic controller CPU Central processing unit P/N Part number CSIV Customer-specific initialization values PROM Programmable read-only memory CT Current transformer PS Power section DC Direct current PTC Positive temperature coefficient DVM Digital voltmeter PWM Pulse width modulation EEPROM Electrically erasable programmable read-only memory Rs Stator resistance RAM Random-access memory ACP EMC Electromagnetic compatibility RCD Residual current device EMI Electromagnetic interference Regen Regeneration terminals ESD Electrostatic discharge RFI Radio frequency interference ETR Electronic thermal relay RMS Root means square (cyclically alternating electric current) Revolutions per minute fM,N Nominal motor frequency HF High frequency RPM HVAC Heating, ventilation, and air conditioning SCR Silicon controlled rectifier Hz Hertz SMPS Switch mode power supply ILIM Current limit S/N Serial number Rated inverter output current STO Safe Torque Off IINV IM,N Nominal motor current TLIM Torque limit IVLT,MAX Maximum output current UM,N Nominal motor voltage IVLT,N Rated output current supplied by the drive V Volt International electrotechnical commission VVC Voltage vector control IGBT Insulated-gate bipolar transistor Xh Motor main reactance I/O Input/output IP Ingress protection kHz Kilohertz kW Kilowatt IEC Ld Motor d-axis inductance Lq Motor q-axis inductance LC Inductor-capacitor LCP Local control panel LED Light-emitting diode LOP Local operation pad mA Milliamp MCB Table 11.1 Abbreviations, Acronyms, and Symbols Conventions • Numbered lists indicate procedures. • Bullet lists indicate other information and description of illustrations. • Italicized text indicates: - Cross reference - Link Miniature circuit breakers - Footnote MCO Motion control option - Parameter name MCP Motor control processor MCT Motion control tool - Parameter group name MDCIC Multi-drive control interface card - Parameter option 144 • All dimensions are in mm (inch). Danfoss A/S © 09/2018 All rights reserved. MG34U502 Appendix Operating Guide 11.2 International/North American Default Parameter Settings Setting parameter 0-03 Regional Settings to [0] International or [1] North America changes the default settings for some parameters. Table 11.2 lists those parameters that are affected. Parameter International default parameter value North American default parameter value Parameter 0-03 Regional Settings International North America Parameter 0-71 Date Format DD-MM-YYYY MM/DD/YYYY Parameter 0-72 Time Format 24 h 12 h Parameter 1-20 Motor Power [kW] 1) 1) Parameter 1-21 Motor Power [HP] 2) 2) Parameter 1-22 Motor Voltage 230 V/400 V/575 V 208 V/460 V/575 V Parameter 1-23 Motor Frequency 50 Hz 60 Hz Parameter 3-03 Maximum Reference 50 Hz 60 Hz Parameter 3-04 Reference Function Sum External/Preset 1500 RPM 1800 RPM 50 Hz 60 Hz Parameter 4-13 Motor Speed High Limit [RPM]3) Parameter 4-14 Motor Speed High Limit [Hz]4) Parameter 4-19 Max Output Frequency Parameter 4-53 Warning Speed High Parameter 5-12 Terminal 27 Digital Input Parameter 5-40 Function Relay Parameter 6-15 Terminal 53 High Ref./Feedb. Value Parameter 6-50 Terminal 42 Output 100 Hz 120 Hz 1500 RPM 1800 RPM Coast inverse External interlock Alarm No alarm 50 60 Speed 0-HighLim Speed 4-20 mA Manual reset Infinite auto reset 1500 RPM 1800 RPM Parameter 22-86 Speed at Design Point [Hz] 50 Hz 60 Hz Parameter 24-04 Fire Mode Max Reference 50 Hz 60 Hz Parameter 14-20 Reset Mode Parameter 22-85 Speed at Design Point 11 11 [RPM]3) Table 11.2 International/North American Default Parameter Settings 1) 2) 3) 4) Parameter 1-20 Motor Power [kW] is only visible when parameter 0-03 Regional Settings is set to [0] International. Parameter 1-21 Motor Power [HP] is only visible when parameter 0-03 Regional Settings is set to [1] North America. This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [0] RPM. This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [1] Hz. 11.3 Parameter Menu Structure MG34U502 Danfoss A/S © 09/2018 All rights reserved. 145 146 Danfoss A/S © 09/2018 All rights reserved. 0-7* 0-70 0-71 0-72 0-73 0-74 0-76 0-77 0-** 0-0* 0-01 0-02 0-03 0-04 0-09 0-1* 0-10 0-11 0-12 0-13 0-14 0-15 0-2* 0-20 0-21 0-22 0-23 0-24 0-25 0-3* 0-30 0-31 0-32 0-33 0-37 0-38 0-39 0-4* 0-40 0-41 0-42 0-43 0-44 0-45 0-5* 0-50 0-51 0-6* 0-60 0-61 0-65 0-66 0-67 0-68 0-69 Operation / Display Basic Settings Language Motor Speed Unit Regional Settings Operating State at Power-up (Hand) Performance Monitor Set-up Operations Active Set-up Edit Set-up This Set-up Linked to Readout: Linked Set-ups Readout: Edit Set-ups / Channel Readout: actual setup LCP Display Display Line 1.1 Small Display Line 1.2 Small Display Line 1.3 Small Display Line 2 Large Display Line 3 Large My Personal Menu LCP Custom Readout Unit for User-defined Readout Min Value of User-defined Readout Max Value of User-defined Readout Source for User-defined Readout Display Text 1 Display Text 2 Display Text 3 LCP Keypad [Hand on] Key on LCP [Off] Key on LCP [Auto on] Key on LCP [Reset] Key on LCP [Off/Reset] Key on LCP [Drive Bypass] Key on LCP Copy/Save LCP Copy Set-up Copy Password Main Menu Password Access to Main Menu w/o Password Quick Menu Password Access to Quick Menu w/o Password Bus Password Access Safety Parameters Password Password Protection of Safety Parameters Clock Settings Date and Time Date Format Time Format Time Zone Offset DST/Summertime DST/Summertime Start DST/Summertime End 11.3.1 Software 8.12 0-79 0-81 0-82 0-83 0-84 0-85 0-86 0-89 1-** 1-0* 1-00 1-01 1-02 1-03 1-04 1-05 1-06 1-07 1-1* 1-10 1-11 1-14 1-15 1-16 1-17 1-18 1-2* 1-20 1-21 1-22 1-23 1-24 1-25 1-26 1-29 1-3* 1-30 1-31 1-33 1-34 1-35 1-36 1-37 1-38 1-39 1-40 1-41 1-44 1-45 1-46 1-47 1-48 1-49 1-5* 1-50 1-51 1-52 1-53 1-54 Clock Fault Working Days Additional Working Days Additional Non-Working Days Time for Fieldbus Summer Time Start for Fieldbus Summer Time End for Fieldbus Date and Time Readout Load and Motor General Settings Configuration Mode Motor Control Principle Flux Motor Feedback Source Torque Characteristics Overload Mode Local Mode Configuration Clockwise Direction Motor Angle Offset Adjust Special Settings Motor Construction Motor Model Damping Gain Low Speed Filter Time Const. High Speed Filter Time Const. Voltage filter time const. Min. Current at No Load Motor Data Motor Power [kW] Motor Power [HP] Motor Voltage Motor Frequency Motor Current Motor Nominal Speed Motor Cont. Rated Torque Automatic Motor Adaptation (AMA) Adv. Motor Data Stator Resistance (Rs) Rotor Resistance (Rr) Stator Leakage Reactance (X1) Rotor Leakage Reactance (X2) Main Reactance (Xh) Iron Loss Resistance (Rfe) d-axis Inductance (Ld) q-axis Inductance (Lq) Motor Poles Back EMF at 1000 RPM Motor Angle Offset d-axis Inductance Sat. (LdSat) q-axis Inductance Sat. (LqSat) Position Detection Gain Torque Calibration Inductance Sat. Point q-Axis Inductance Saturation Point Load Indep. Setting Motor Magnetisation at Zero Speed Min Speed Normal Magnetising [RPM] Min Speed Normal Magnetising [Hz] Model Shift Frequency Voltage reduction in fieldweakening 1-9* 1-90 1-91 1-93 1-94 1-95 1-96 1-97 1-98 1-99 2-** 2-0* 2-00 2-01 2-02 2-03 2-04 2-05 2-06 2-07 2-1* 2-10 2-11 2-12 2-13 2-15 2-16 2-17 1-55 1-56 1-58 1-59 1-6* 1-60 1-61 1-62 1-63 1-64 1-65 1-66 1-67 1-68 1-69 1-7* 1-70 1-71 1-72 1-73 1-74 1-75 1-76 1-8* 1-80 1-81 1-82 1-83 1-84 1-85 U/f Characteristic - U U/f Characteristic - F Flying Start Test Pulses Current Flying Start Test Pulses Frequency Load Depen. Setting Low Speed Load Compensation High Speed Load Compensation Slip Compensation Slip Compensation Time Constant Resonance Damping Resonance Damping Time Constant Min. Current at Low Speed Load Type Motor Inertia System Inertia Start Adjustments Start Mode Start Delay Start Function Flying Start Start Speed [RPM] Start Speed [Hz] Start Current Stop Adjustments Function at Stop Min Speed for Function at Stop [RPM] Min Speed for Function at Stop [Hz] Precise Stop Function Precise Stop Counter Value Precise Stop Speed Compensation Delay Motor Temperature Motor Thermal Protection Motor External Fan Thermistor Resource ATEX ETR cur.lim. speed reduction Thermistor Sensor Type Thermistor Sensor Resource Thermistor Threshold level ATEX ETR interpol. points freq. ATEX ETR interpol points current Brakes DC-Brake DC Hold Current DC Brake Current DC Braking Time DC Brake Cut In Speed [RPM] DC Brake Cut In Speed [Hz] Maximum Reference Parking Current Parking Time Brake Energy Funct. Brake Function Brake Resistor (ohm) Brake Power Limit (kW) Brake Power Monitoring Brake Check AC brake Max. Current Over-voltage Control 11 11 2-18 2-19 2-2* 2-20 2-21 2-22 2-23 2-24 2-25 2-26 2-27 2-28 2-29 2-3* 2-30 2-31 2-32 2-33 3-** 3-0* 3-00 3-01 3-02 3-03 3-04 3-1* 3-10 3-11 3-12 3-13 3-14 3-15 3-16 3-17 3-18 3-19 3-4* 3-40 3-41 3-42 3-45 3-46 3-47 3-48 3-5* 3-50 3-51 3-52 3-55 3-56 3-57 3-58 3-6* 3-60 3-61 3-62 3-65 3-66 3-67 Brake Check Condition Over-voltage Gain Mechanical Brake Release Brake Current Activate Brake Speed [RPM] Activate Brake Speed [Hz] Activate Brake Delay Stop Delay Brake Release Time Torque Ref Torque Ramp Up Time Gain Boost Factor Torque Ramp Down Time Adv. Mech Brake Position P Start Proportional Gain Speed PID Start Proportional Gain Speed PID Start Integral Time Speed PID Start Lowpass Filter Time Reference / Ramps Reference Limits Reference Range Reference/Feedback Unit Minimum Reference Maximum Reference Reference Function References Preset Reference Jog Speed [Hz] Catch up/slow Down Value Reference Site Preset Relative Reference Reference Resource 1 Reference Resource 2 Reference Resource 3 Relative Scaling Reference Resource Jog Speed [RPM] Ramp 1 Ramp 1 Type Ramp 1 Ramp Up Time Ramp 1 Ramp Down Time Ramp 1 S-ramp Ratio at Accel. Start Ramp 1 S-ramp Ratio at Accel. End Ramp 1 S-ramp Ratio at Decel. Start Ramp 1 S-ramp Ratio at Decel. End Ramp 2 Ramp 2 Type Ramp 2 Ramp Up Time Ramp 2 Ramp Down Time Ramp 2 S-ramp Ratio at Accel. Start Ramp 2 S-ramp Ratio at Accel. End Ramp 2 S-ramp Ratio at Decel. Start Ramp 2 S-ramp Ratio at Decel. End Ramp 3 Ramp 3 Type Ramp 3 Ramp up Time Ramp 3 Ramp down Time Ramp 3 S-ramp Ratio at Accel. Start Ramp 3 S-ramp Ratio at Accel. End Ramp 3 S-ramp Ratio at Decel. Start 3-68 3-7* 3-70 3-71 3-72 3-75 3-76 3-77 3-78 3-8* 3-80 3-81 3-82 3-83 3-84 3-89 3-9* 3-90 3-91 3-92 3-93 3-94 3-95 4-** 4-1* 4-10 4-11 4-12 4-13 4-14 4-16 4-17 4-18 4-19 4-2* 4-20 4-21 4-23 4-24 4-25 4-26 4-3* 4-30 4-31 4-32 4-34 4-35 4-36 4-37 4-38 4-39 4-4* 4-43 4-44 4-45 4-5* 4-50 4-51 4-52 Ramp 3 S-ramp Ratio at Decel. End Ramp 4 Ramp 4 Type Ramp 4 Ramp up Time Ramp 4 Ramp Down Time Ramp 4 S-ramp Ratio at Accel. Start Ramp 4 S-ramp Ratio at Accel. End Ramp 4 S-ramp Ratio at Decel. Start Ramp 4 S-ramp Ratio at Decel. End Other Ramps Jog Ramp Time Quick Stop Ramp Time Quick Stop Ramp Type Quick Stop S-ramp Ratio at Decel. Start Quick Stop S-ramp Ratio at Decel. End Ramp Lowpass Filter Time Digital Pot.Meter Step Size Ramp Time Power Restore Maximum Limit Minimum Limit Ramp Delay Limits / Warnings Motor Limits Motor Speed Direction Motor Speed Low Limit [RPM] Motor Speed Low Limit [Hz] Motor Speed High Limit [RPM] Motor Speed High Limit [Hz] Torque Limit Motor Mode Torque Limit Generator Mode Current Limit Max Output Frequency Limit Factors Torque Limit Factor Source Speed Limit Factor Source Brake Check Limit Factor Source Brake Check Limit Factor Power Limit Motor Factor Source Power Limit Gener. Factor Source Motor Speed Mon. Motor Feedback Loss Function Motor Feedback Speed Error Motor Feedback Loss Timeout Tracking Error Function Tracking Error Tracking Error Timeout Tracking Error Ramping Tracking Error Ramping Timeout Tracking Error After Ramping Timeout Speed Monitor Motor Speed Monitor Function Motor Speed Monitor Max Motor Speed Monitor Timeout Adj. Warnings Warning Current Low Warning Current High Warning Speed Low Appendix VLT® AutomationDrive FC 302 MG34U502 4-53 4-54 4-55 4-56 4-57 4-58 4-59 4-6* 4-60 4-61 4-62 4-63 4-8* 4-80 4-81 4-82 4-83 4-9* 4-90 4-91 4-92 4-93 4-94 4-95 4-96 5-** 5-0* 5-00 5-01 5-02 5-1* 5-10 5-11 5-12 5-13 5-14 5-15 5-16 5-17 5-18 5-19 5-20 5-21 5-22 5-23 5-24 5-25 5-26 5-3* 5-30 5-31 5-32 5-33 5-4* 5-40 5-41 5-42 5-5* 5-50 Warning Speed High Warning Reference Low Warning Reference High Warning Feedback Low Warning Feedback High Missing Motor Phase Function Motor Check At Start Speed Bypass Bypass Speed From [RPM] Bypass Speed From [Hz] Bypass Speed To [RPM] Bypass Speed To [Hz] Power Limit Power Limit Func. Motor Mode Power Limit Func. Generator Mode Power Limit Motor Mode Power Limit Generator Mode Directional Limits Directional Limit Mode Positive Speed Limit [RPM] Positive Speed Limit [Hz] Negative Speed Limit [RPM] Negative Speed Limit [Hz] Positive Torque limit Negative Torque limit Digital In/Out Digital I/O mode Digital I/O Mode Terminal 27 Mode Terminal 29 Mode Digital Inputs Terminal 18 Digital Input Terminal 19 Digital Input Terminal 27 Digital Input Terminal 29 Digital Input Terminal 32 Digital Input Terminal 33 Digital Input Terminal X30/2 Digital Input Terminal X30/3 Digital Input Terminal X30/4 Digital Input Terminal 37 Safe Stop Terminal X46/1 Digital Input Terminal X46/3 Digital Input Terminal X46/5 Digital Input Terminal X46/7 Digital Input Terminal X46/9 Digital Input Terminal X46/11 Digital Input Terminal X46/13 Digital Input Digital Outputs Terminal 27 Digital Output Terminal 29 Digital Output Term X30/6 Digi Out (MCB 101) Term X30/7 Digi Out (MCB 101) Relays Function Relay On Delay, Relay Off Delay, Relay Pulse Input Term. 29 Low Frequency 5-51 5-52 5-53 5-54 5-55 5-56 5-57 5-58 5-59 5-6* 5-60 5-62 5-63 5-65 5-66 5-68 5-7* 5-70 5-71 5-8* 5-80 5-9* 5-90 5-93 5-94 5-95 5-96 5-97 5-98 6-** 6-0* 6-00 6-01 6-1* 6-10 6-11 6-12 6-13 6-14 6-15 6-16 6-2* 6-20 6-21 6-22 6-23 6-24 6-25 6-26 6-3* 6-30 6-31 6-34 6-35 6-36 6-4* 6-40 6-41 6-44 Term. 29 High Frequency Term. 29 Low Ref./Feedb. Value Term. 29 High Ref./Feedb. Value Pulse Filter Time Constant #29 Term. 33 Low Frequency Term. 33 High Frequency Term. 33 Low Ref./Feedb. Value Term. 33 High Ref./Feedb. Value Pulse Filter Time Constant #33 Pulse Output Terminal 27 Pulse Output Variable Pulse Output Max Freq #27 Terminal 29 Pulse Output Variable Pulse Output Max Freq #29 Terminal X30/6 Pulse Output Variable Pulse Output Max Freq #X30/6 24V Encoder Input Term 32/33 Pulses Per Revolution Term 32/33 Encoder Direction I/O Options AHF Cap Reconnect Delay Bus Controlled Digital & Relay Bus Control Pulse Out #27 Bus Control Pulse Out #27 Timeout Preset Pulse Out #29 Bus Control Pulse Out #29 Timeout Preset Pulse Out #X30/6 Bus Control Pulse Out #X30/6 Timeout Preset Analog In/Out Analog I/O Mode Live Zero Timeout Time Live Zero Timeout Function Analog Input 1 Terminal 53 Low Voltage Terminal 53 High Voltage Terminal 53 Low Current Terminal 53 High Current Terminal 53 Low Ref./Feedb. Value Terminal 53 High Ref./Feedb. Value Terminal 53 Filter Time Constant Analog Input 2 Terminal 54 Low Voltage Terminal 54 High Voltage Terminal 54 Low Current Terminal 54 High Current Terminal 54 Low Ref./Feedb. Value Terminal 54 High Ref./Feedb. Value Terminal 54 Filter Time Constant Analog Input 3 Terminal X30/11 Low Voltage Terminal X30/11 High Voltage Term. X30/11 Low Ref./Feedb. Value Term. X30/11 High Ref./Feedb. Value Term. X30/11 Filter Time Constant Analog Input 4 Terminal X30/12 Low Voltage Terminal X30/12 High Voltage Term. X30/12 Low Ref./Feedb. Value 6-45 6-46 6-5* 6-50 6-51 6-52 6-53 6-54 6-55 6-6* 6-60 6-61 6-62 6-63 6-64 6-7* 6-70 6-71 6-72 6-73 6-74 6-8* 6-80 6-81 6-82 6-83 6-84 7-** 7-0* 7-00 7-01 7-02 7-03 7-04 7-05 7-06 7-07 7-08 7-09 7-1* 7-10 7-12 7-13 7-16 7-18 7-19 7-2* 7-20 7-22 7-3* 7-30 7-31 7-32 7-33 7-34 7-35 7-36 7-38 7-39 Term. X30/12 High Ref./Feedb. Value Term. X30/12 Filter Time Constant Analog Output 1 Terminal 42 Output Terminal 42 Output Min Scale Terminal 42 Output Max Scale Term 42 Output Bus Ctrl Terminal 42 Output Timeout Preset Analog Output Filter Analog Output 2 Terminal X30/8 Output Terminal X30/8 Min. Scale Terminal X30/8 Max. Scale Terminal X30/8 Bus Control Terminal X30/8 Output Timeout Preset Analog Output 3 Terminal X45/1 Output Terminal X45/1 Min. Scale Terminal X45/1 Max. Scale Terminal X45/1 Bus Control Terminal X45/1 Output Timeout Preset Analog Output 4 Terminal X45/3 Output Terminal X45/3 Min. Scale Terminal X45/3 Max. Scale Terminal X45/3 Bus Control Terminal X45/3 Output Timeout Preset Controllers Speed PID Ctrl. Speed PID Feedback Source Speed PID Droop Speed PID Proportional Gain Speed PID Integral Time Speed PID Differentiation Time Speed PID Diff. Gain Limit Speed PID Lowpass Filter Time Speed PID Feedback Gear Ratio Speed PID Feed Forward Factor Speed PID Error Correction w/ Ramp Torque PI Ctrl. Torque PI Feedback Source Torque PI Proportional Gain Torque PI Integration Time Torque PI Lowpass Filter Time Torque PI Feed Forward Factor Current Controller Rise Time Process Ctrl. Feedb Process CL Feedback 1 Resource Process CL Feedback 2 Resource Process PID Ctrl. Process PID Normal/ Inverse Control Process PID Anti Windup Process PID Start Speed Process PID Proportional Gain Process PID Integral Time Process PID Differentiation Time Process PID Diff. Gain Limit Process PID Feed Forward Factor On Reference Bandwidth MG34U502 7-48 7-49 7-5* 7-50 7-51 7-52 7-53 7-56 7-57 8-** 8-0* 8-01 8-02 8-03 8-04 8-05 8-06 8-07 8-08 8-1* 8-10 8-13 8-14 8-17 8-19 8-3* 8-30 8-31 8-32 8-33 8-34 8-35 8-36 8-37 8-4* 8-40 8-41 8-42 8-43 8-45 8-46 8-47 8-48 8-49 8-5* 8-50 8-51 8-52 8-53 8-54 7-4* 7-40 7-41 7-42 7-43 7-44 7-45 7-46 Adv. Process PID I Process PID I-part Reset Process PID Output Neg. Clamp Process PID Output Pos. Clamp Process PID Gain Scale at Min. Ref. Process PID Gain Scale at Max. Ref. Process PID Feed Fwd Resource Process PID Feed Fwd Normal/ Inv. Ctrl. PCD Feed Forward Process PID Output Normal/ Inv. Ctrl. Adv. Process PID II Process PID Extended PID Process PID Feed Fwd Gain Process PID Feed Fwd Ramp up Process PID Feed Fwd Ramp down Process PID Ref. Filter Time Process PID Fb. Filter Time Comm. and Options General Settings Control Site Control Word Source Control Word Timeout Time Control Word Timeout Function End-of-Timeout Function Reset Control Word Timeout Diagnosis Trigger Readout Filtering Ctrl. Word Settings Control Word Profile Configurable Status Word STW Configurable Control Word CTW Configurable Alarm and Warningword Product Code FC Port Settings Protocol Address FC Port Baud Rate Parity / Stop Bits Estimated cycle time Minimum Response Delay Max Response Delay Max Inter-Char Delay FC MC protocol set Telegram Selection Parameters for Signals PCD Write Configuration PCD Read Configuration BTM Transaction Command BTM Transaction Status BTM Timeout BTM Maximum Errors BTM Error Log Digital/Bus Coasting Select Quick Stop Select DC Brake Select Start Select Reversing Select 8-55 8-56 8-57 8-58 8-8* 8-80 8-81 8-82 8-83 8-9* 8-90 8-91 9-** 9-00 9-07 9-15 9-16 9-18 9-19 9-22 9-23 9-27 9-28 9-44 9-45 9-47 9-52 9-53 9-63 9-64 9-65 9-67 9-68 9-70 9-71 9-72 9-75 9-80 9-81 9-82 9-83 9-84 9-85 9-90 9-91 9-92 9-93 9-94 9-99 10-** 10-0* 10-00 10-01 10-02 10-05 10-06 10-07 10-1* 10-10 Set-up Select Preset Reference Select Profidrive OFF2 Select Profidrive OFF3 Select FC Port Diagnostics Bus Message Count Bus Error Count Slave Messages Rcvd Slave Error Count Bus Jog Bus Jog 1 Speed Bus Jog 2 Speed PROFIdrive Setpoint Actual Value PCD Write Configuration PCD Read Configuration Node Address Drive Unit System Number Telegram Selection Parameters for Signals Parameter Edit Process Control Fault Message Counter Fault Code Fault Number Fault Situation Counter Profibus Warning Word Actual Baud Rate Device Identification Profile Number Control Word 1 Status Word 1 Edit Set-up Profibus Save Data Values ProfibusDriveReset DO Identification Defined Parameters (1) Defined Parameters (2) Defined Parameters (3) Defined Parameters (4) Defined Parameters (5) Defined Parameters (6) Changed Parameters (1) Changed Parameters (2) Changed Parameters (3) Changed Parameters (4) Changed Parameters (5) Profibus Revision Counter CAN Fieldbus Common Settings CAN Protocol Baud Rate Select MAC ID Readout Transmit Error Counter Readout Receive Error Counter Readout Bus Off Counter DeviceNet Process Data Type Selection Appendix Operating Guide Danfoss A/S © 09/2018 All rights reserved. 147 11 11 10-11 10-12 10-13 10-14 10-15 10-2* 10-20 10-21 10-22 10-23 10-3* 10-30 10-31 10-32 10-33 10-34 10-39 10-5* 10-50 10-51 12-** 12-0* 12-00 12-01 12-02 12-03 12-04 12-05 12-06 12-07 12-08 12-09 12-1* 12-10 12-11 12-12 12-13 12-14 12-18 12-19 12-2* 12-20 12-21 12-22 12-23 12-24 12-27 12-28 12-29 12-3* 12-30 12-31 12-32 12-33 12-34 12-35 12-37 12-38 12-4* Process Data Config Write Process Data Config Read Warning Parameter Net Reference Net Control COS Filters COS Filter 1 COS Filter 2 COS Filter 3 COS Filter 4 Parameter Access Array Index Store Data Values Devicenet Revision Store Always DeviceNet Product Code Devicenet F Parameters CANopen Process Data Config Write. Process Data Config Read. Ethernet IP Settings IP Address Assignment IP Address Subnet Mask Default Gateway DHCP Server Lease Expires Name Servers Domain Name Host Name Physical Address Ethernet Link Parameters Link Status Link Duration Auto Negotiation Link Speed Link Duplex Supervisor MAC Supervisor IP Addr. Process Data Control Instance Process Data Config Write Process Data Config Read Process Data Config Write Size Process Data Config Read Size Master Address Store Data Values Store Always EtherNet/IP Warning Parameter Net Reference Net Control CIP Revision CIP Product Code EDS Parameter COS Inhibit Timer COS Filter Modbus TCP 12-40 12-41 12-42 12-5* 12-50 12-51 12-59 12-6* 12-60 12-62 12-63 12-66 12-67 12-68 12-69 12-8* 12-80 12-81 12-82 12-83 12-84 12-85 12-89 12-9* 12-90 12-91 12-92 12-93 12-94 12-95 12-96 12-97 12-98 12-99 13-** 13-0* 13-00 13-01 13-02 13-03 13-1* 13-10 13-11 13-12 13-1* 13-15 13-16 13-2* 13-20 13-4* 13-40 13-41 13-42 13-43 13-44 13-5* 13-51 13-52 13-9* Status Parameter Slave Message Count Slave Exception Message Count EtherCAT Configured Station Alias Configured Station Address EtherCAT Status Ethernet PowerLink Node ID SDO Timeout Basic Ethernet Timeout Threshold Threshold Counters Cumulative Counters Ethernet PowerLink Status Other Ethernet Services FTP Server HTTP Server SMTP Service SNMP Agent Address Conflict Detection ACD Last Conflict Transparent Socket Channel Port Advanced Ethernet Services Cable Diagnostic Auto Cross Over IGMP Snooping Cable Error Length Broadcast Storm Protection Inactivity timeout Port Config QoS Priority Interface Counters Media Counters Smart Logic SLC Settings SL Controller Mode Start Event Stop Event Reset SLC Comparators Comparator Operand Comparator Operator Comparator Value RS Flip Flops RS-FF Operand S RS-FF Operand R Timers SL Controller Timer Logic Rules Logic Rule Boolean 1 Logic Rule Operator 1 Logic Rule Boolean 2 Logic Rule Operator 2 Logic Rule Boolean 3 States SL Controller Event SL Controller Action User Defined Alerts 13-90 13-91 13-92 13-9* 13-97 13-98 13-99 14-** 14-0* 14-00 14-01 14-03 14-04 14-06 14-1* 14-10 14-11 14-12 14-14 14-15 14-16 14-2* 14-20 14-21 14-22 14-23 14-24 14-25 14-26 14-28 14-29 14-3* 14-30 14-31 14-32 14-35 14-36 14-37 14-4* 14-40 14-41 14-42 14-43 14-5* 14-50 14-51 14-52 14-53 14-55 14-56 14-57 14-59 14-6* 14-60 14-61 14-62 14-7* 14-72 14-73 Alert Trigger Alert Action Alert Text User Defined Readouts Alert Alarm Word Alert Warning Word Alert Status Word Special Functions Inverter Switching Switching Pattern Switching Frequency Overmodulation Acoustic Noise Reduction Dead Time Compensation Mains Failure Mains Failure Mains Fault Voltage Level Response to Mains Imbalance Kin. Back-up Time-out Kin. Back-up Trip Recovery Level Kin. Back-up Gain Trip Reset Reset Mode Automatic Restart Time Operation Mode Typecode Setting Trip Delay at Current Limit Trip Delay at Torque Limit Trip Delay at Inverter Fault Production Settings Service Code Current Limit Ctrl. Current Lim Ctrl, Proportional Gain Current Lim Ctrl, Integration Time Current Lim Ctrl, Filter Time Stall Protection Field-weakening Function Fieldweakening Speed Energy Optimising VT Level AEO Minimum Magnetisation Minimum AEO Frequency Motor Cosphi Environment RFI Filter DC-Link Compensation Fan Control Fan Monitor Output Filter Capacitance Output Filter Inductance Output Filter Actual Number of Inverter Units Auto Derate Function at Over Temperature Function at Inverter Overload Inv. Overload Derate Current Compatibility Legacy Alarm Word Legacy Warning Word 11 11 14-74 14-8* 14-80 14-88 14-89 14-9* 14-90 15-** 15-0* 15-00 15-01 15-02 15-03 15-04 15-05 15-06 15-07 15-1* 15-10 15-11 15-12 15-13 15-14 15-2* 15-20 15-21 15-22 15-3* 15-30 15-31 15-32 15-33 15-4* 15-40 15-41 15-42 15-43 15-44 15-45 15-46 15-47 15-48 15-49 15-50 15-51 15-53 15-54 15-58 15-59 15-6* 15-60 15-61 15-62 15-63 15-70 15-71 15-72 15-73 15-74 Leg. Ext. Status Word Options Option Supplied by External 24VDC Option Data Storage Option Detection Fault Settings Fault Level Drive Information Operating Data Operating hours Running Hours kWh Counter Power Up's Over Temp's Over Volt's Reset kWh Counter Reset Running Hours Counter Data Log Settings Logging Source Logging Interval Trigger Event Logging Mode Samples Before Trigger Historic Log Historic Log: Event Historic Log: Value Historic Log: Time Fault Log Fault Log: Error Code Fault Log: Value Fault Log: Time Fault log: Date and Time Drive Identification FC Type Power Section Voltage Software Version Ordered Typecode String Actual Typecode String Frequency Converter Ordering No Power Card Ordering No LCP Id No SW ID Control Card SW ID Power Card Frequency Converter Serial Number Power Card Serial Number Config File Name Smart Setup Filename Filename Option Ident Option Mounted Option SW Version Option Ordering No Option Serial No Option in Slot A Slot A Option SW Version Option in Slot B Slot B Option SW Version Option in Slot C0/E0 15-75 15-76 15-77 15-8* 15-80 15-81 15-89 15-9* 15-92 15-93 15-98 15-99 16-** 16-0* 16-00 16-01 16-02 16-03 16-05 16-06 16-09 16-1* 16-10 16-11 16-12 16-13 16-14 16-15 16-16 16-17 16-18 16-19 16-20 16-21 16-22 16-23 16-24 16-25 16-3* 16-30 16-31 16-32 16-33 16-34 16-35 16-36 16-37 16-38 16-39 16-40 16-41 16-42 16-43 16-45 16-46 16-47 16-48 16-49 Slot C0/E0 Option SW Version Option in Slot C1/E1 Slot C1/E1 Option SW Version Operating Data II Fan Running Hours Preset Fan Running Hours Configuration Change Counter Parameter Info Defined Parameters Modified Parameters Drive Identification Parameter Metadata Data Readouts General Status Control Word Reference [Unit] Reference % Status Word Main Actual Value [%] Actual Position Custom Readout Motor Status Power [kW] Power [hp] Motor Voltage Frequency Motor current Frequency [%] Torque [Nm] Speed [RPM] Motor Thermal Thermistor Sensor Temperature Motor Angle Torque [%] High Res. Torque [%] Motor Shaft Power [kW] Calibrated Stator Resistance Torque [Nm] High Drive Status DC Link Voltage System Temp. Brake Energy /s Brake Energy Average Heatsink Temp. Inverter Thermal Inv. Nom. Current Inv. Max. Current SL Controller State Control Card Temp. Logging Buffer Full Performance Measurements Service Log Counter Timed Actions Status Motor Phase U Current Motor Phase V Current Motor Phase W Current Speed Ref. After Ramp [RPM] Current Fault Source Appendix 148 VLT® AutomationDrive FC 302 Danfoss A/S © 09/2018 All rights reserved. MG34U502 16-5* 16-50 16-51 16-52 16-53 16-57 16-6* 16-60 16-61 16-62 16-63 16-64 16-65 16-66 16-67 16-68 16-69 16-70 16-71 16-72 16-73 16-74 16-75 16-76 16-77 16-78 16-79 16-8* 16-80 16-82 16-84 16-85 16-86 16-87 16-89 16-9* 16-90 16-91 16-92 16-93 16-94 16-95 16-96 17-** 17-1* 17-10 17-11 17-2* 17-20 17-21 17-22 17-24 17-25 17-26 17-34 17-5* 17-50 17-51 17-52 Ref. & Feedb. External Reference Pulse Reference Feedback[Unit] Digi Pot Reference Feedback [RPM] Inputs & Outputs Digital Input Terminal 53 Switch Setting Analog Input 53 Terminal 54 Switch Setting Analog Input 54 Analog Output 42 [mA] Digital Output [bin] Freq. Input #29 [Hz] Freq. Input #33 [Hz] Pulse Output #27 [Hz] Pulse Output #29 [Hz] Relay Output [bin] Counter A Counter B Prec. Stop Counter Analog In X30/11 Analog In X30/12 Analog Out X30/8 [mA] Analog Out X45/1 [mA] Analog Out X45/3 [mA] Fieldbus & FC Port Fieldbus CTW 1 Fieldbus REF 1 Comm. Option STW FC Port CTW 1 FC Port REF 1 Bus Readout Alarm/Warning Configurable Alarm/Warning Word Diagnosis Readouts Alarm Word Alarm Word 2 Warning Word Warning Word 2 Ext. Status Word Ext. Status Word 2 Maintenance Word Position Feedback Inc. Enc. Interface Signal Type Resolution (PPR) Abs. Enc. Interface Protocol Selection Resolution (Positions/Rev) Multiturn Revolutions SSI Data Length Clock Rate SSI Data Format HIPERFACE Baudrate Resolver Interface Poles Input Voltage Input Frequency 17-53 17-56 17-59 17-6* 17-60 17-61 17-7* 17-70 17-71 17-72 17-73 17-74 18-** 18-0* 18-00 18-01 18-02 18-03 18-2* 18-27 18-28 18-29 18-3* 18-36 18-37 18-38 18-39 18-4* 18-43 18-44 18-45 18-5* 18-55 18-56 18-6* 18-60 18-7* 18-70 18-71 18-72 18-75 18-9* 18-90 18-91 18-92 18-93 22-** 22-0* 22-00 23-** 23-0* 23-00 23-01 23-02 23-03 23-04 23-0* 23-08 23-09 Transformation Ratio Encoder Sim. Resolution Resolver Interface Monitoring and App. Feedback Direction Feedback Signal Monitoring Position Scaling Position Unit Position Unit Scale Position Unit Numerator Position Unit Denominator Position Offset Data Readouts 2 Maintenance Log Maintenance Log: Item Maintenance Log: Action Maintenance Log: Time Maintenance Log: Date and Time Motor Readouts Safe Opt. Est. Speed Safe Opt. Meas. Speed Safe Opt. Speed Error Analog Readouts Analog Input X48/2 [mA] Temp. Input X48/4 Temp. Input X48/7 Temp. Input X48/10 PGIO Data Readouts Analog Out X49/7 Analog Out X49/9 Analog Out X49/11 Active Alarms/Warnings Active Alarm Numbers Active Warning Numbers Inputs & Outputs 2 Digital Input 2 Rectifier Status Mains Voltage Mains Frequency Mains Imbalance Rectifier DC Volt. PID Readouts Process PID Error Process PID Output Process PID Clamped Output Process PID Gain Scaled Output Appl. Functions Miscellaneous External Interlock Delay Time-based Functions Timed Actions ON Time ON Action OFF Time OFF Action Occurrence Timed Actions Settings Timed Actions Mode Timed Actions Reactivation MG34U502 30-25 30-26 30-27 30-5* 30-50 30-8* 30-80 30-81 30-83 30-84 30-9* 30-90 30-91 30-92 30-93 30-94 30-95 30-96 30-97 31-** 31-00 31-01 31-02 31-03 31-10 31-11 31-19 23-1* 23-10 23-11 23-12 23-13 23-14 23-1* 23-15 23-16 30-** 30-0* 30-00 30-01 30-02 30-03 30-04 30-05 30-06 30-07 30-08 30-09 30-10 30-11 30-12 30-19 30-2* 30-20 30-21 30-22 30-23 30-24 Maintenance Maintenance Item Maintenance Action Maintenance Time Base Maintenance Time Interval Maintenance Date and Time Maintenance Reset Reset Maintenance Word Maintenance Text Special Features Wobbler Wobble Mode Wobble Delta Frequency [Hz] Wobble Delta Frequency [%] Wobble Delta Freq. Scaling Resource Wobble Jump Frequency [Hz] Wobble Jump Frequency [%] Wobble Jump Time Wobble Sequence Time Wobble Up/ Down Time Wobble Random Function Wobble Ratio Wobble Random Ratio Max. Wobble Random Ratio Min. Wobble Delta Freq. Scaled Adv. Start Adjust High Starting Torque Time [s] High Starting Torque Current [%] Locked Rotor Protection Locked Rotor Detection Time [s] Locked Rotor Detection Speed Error [%] Light Load Delay [s] Light Load Current [%] Light Load Speed [%] Unit Configuration Heat Sink Fan Mode Compatibility (I) d-axis Inductance (Ld) Brake Resistor (ohm) Speed PID Proportional Gain Process PID Proportional Gain Wifi LCP SSID Channel Password Security type IP address Submask Port Wifi Timeout Action Bypass Option Bypass Mode Bypass Start Time Delay Bypass Trip Time Delay Test Mode Activation Bypass Status Word Bypass Running Hours Remote Bypass Activation Danfoss A/S © 09/2018 All rights reserved. 32-72 32-73 32-74 32-8* 32-80 32-81 32-82 32-83 32-84 32-** 32-0* 32-00 32-01 32-02 32-03 32-04 32-05 32-06 32-07 32-08 32-09 32-10 32-11 32-12 32-13 32-14 32-15 32-3* 32-30 32-31 32-32 32-33 32-35 32-36 32-37 32-38 32-39 32-40 32-43 32-44 32-45 32-5* 32-50 32-51 32-52 32-6* 32-60 32-61 32-62 32-63 32-64 32-65 32-66 32-67 32-68 32-69 32-70 32-71 MCO Basic Settings Encoder 2 Incremental Signal Type Incremental Resolution Absolute Protocol Absolute Resolution Absolute Encoder Baudrate X55 Absolute Encoder Data Length Absolute Encoder Clock Frequency Absolute Encoder Clock Generation Absolute Encoder Cable Length Encoder Monitoring Rotational Direction User Unit Denominator User Unit Numerator Enc.2 Control Enc.2 node ID Enc.2 CAN guard Encoder 1 Incremental Signal Type Incremental Resolution Absolute Protocol Absolute Resolution Absolute Encoder Data Length Absolute Encoder Clock Frequency Absolute Encoder Clock Generation Absolute Encoder Cable Length Encoder Monitoring Encoder Termination Enc.1 Control Enc.1 node ID Enc.1 CAN guard Feedback Source Source Slave MCO 302 Last Will Source Master PID Controller Proportional factor Derivative factor Integral factor Limit Value for Integral Sum PID Bandwidth Velocity Feed-Forward Acceleration Feed-Forward Max. Tolerated Position Error Reverse Behavior for Slave Sampling Time for PID Control Scan Time for Profile Generator Size of the Control Window (Activation) Size of the Control Window (Deactiv.) Integral limit filter time Position error filter time Velocity & Accel. Maximum Velocity (Encoder) Shortest Ramp Ramp Type Velocity Resolution Default Velocity 32-85 32-86 32-87 32-88 32-89 32-9* 32-90 33-** 33-0* 33-00 33-01 33-02 33-03 33-04 33-1* 33-10 33-11 33-12 33-13 33-14 33-15 33-16 33-17 33-18 33-19 33-20 33-21 33-22 33-23 33-24 33-25 33-26 33-27 33-28 33-29 33-30 33-31 33-32 33-33 33-34 33-4* 33-40 33-41 33-42 33-43 33-44 33-45 33-46 33-47 33-5* 33-50 33-51 33-52 33-53 33-54 33-55 33-56 33-57 33-58 Default Acceleration Acc. up for limited jerk Acc. down for limited jerk Dec. up for limited jerk Dec. down for limited jerk Development Debug Source MCO Adv. Settings Home Motion Force HOME Zero Point Offset from Home Pos. Ramp for Home Motion Velocity of Home Motion Behaviour during HomeMotion Synchronization Sync Factor Master Sync Factor Slave Position Offset for Synchronization Accuracy Window for Position Sync. Relative Slave Velocity Limit Marker Number for Master Marker Number for Slave Master Marker Distance Slave Marker Distance Master Marker Type Slave Marker Type Master Marker Tolerance Window Slave Marker Tolerance Window Start Behaviour for Marker Sync Marker Number for Fault Marker Number for Ready Velocity Filter Offset Filter Time Marker Filter Configuration Filter Time for Marker Filter Maximum Marker Correction Synchronisation Type Feed Forward Velocity Adaptation Velocity Filter Window Slave Marker filter time Limit Handling Behaviour atEnd Limit Switch Negative Software End Limit Positive Software End Limit Negative Software End Limit Active Positive Software End Limit Active Time in Target Window Target Window LimitValue Size of Target Window I/O Configuration Terminal X57/1 Digital Input Terminal X57/2 Digital Input Terminal X57/3 Digital Input Terminal X57/4 Digital Input Terminal X57/5 Digital Input Terminal X57/6 Digital Input Terminal X57/7 Digital Input Terminal X57/8 Digital Input Terminal X57/9 Digital Input Appendix Operating Guide 149 11 11 33-59 33-60 33-61 33-62 33-63 33-64 33-65 33-66 33-67 33-68 33-69 33-70 33-8* 33-80 33-81 33-82 33-83 33-84 33-85 33-86 33-87 33-88 33-9* 33-90 33-91 33-94 33-95 34-** 34-0* 34-01 34-02 34-03 34-04 34-05 34-06 34-07 34-08 34-09 34-10 34-2* 34-21 34-22 34-23 34-24 34-25 34-26 34-27 34-28 34-29 34-30 34-4* 34-40 34-41 34-5* 34-50 34-51 34-52 34-53 34-54 Terminal X57/10 Digital Input Terminal X59/1 and X59/2 Mode Terminal X59/1 Digital Input Terminal X59/2 Digital Input Terminal X59/1 Digital Output Terminal X59/2 Digital Output Terminal X59/3 Digital Output Terminal X59/4 Digital Output Terminal X59/5 Digital Output Terminal X59/6 Digital Output Terminal X59/7 Digital Output Terminal X59/8 Digital Output Global Parameters Activated Program Number Power-up State Drive Status Monitoring Behaviour afterError Behaviour afterEsc. MCO Supplied by External 24VDC Terminal at alarm Terminal state at alarm Status word at alarm MCO Port Settings X62 MCO CAN node ID X62 MCO CAN baud rate X60 MCO RS485 serial termination X60 MCO RS485 serial baud rate MCO Data Readouts PCD Write Par. PCD 1 Write to MCO PCD 2 Write to MCO PCD 3 Write to MCO PCD 4 Write to MCO PCD 5 Write to MCO PCD 6 Write to MCO PCD 7 Write to MCO PCD 8 Write to MCO PCD 9 Write to MCO PCD 10 Write to MCO PCD Read Par. PCD 1 Read from MCO PCD 2 Read from MCO PCD 3 Read from MCO PCD 4 Read from MCO PCD 5 Read from MCO PCD 6 Read from MCO PCD 7 Read from MCO PCD 8 Read from MCO PCD 9 Read from MCO PCD 10 Read from MCO Inputs & Outputs Digital Inputs Digital Outputs Process Data Actual Position Commanded Position Actual Master Position Slave Index Position Master Index Position 34-55 34-56 34-57 34-58 34-59 34-60 34-61 34-62 34-64 34-65 34-66 34-7* 34-70 34-71 35-** 35-0* 35-00 35-01 35-02 35-03 35-04 35-05 35-06 35-1* 35-14 35-15 35-16 35-17 35-2* 35-24 35-25 35-26 35-27 35-3* 35-34 35-35 35-36 35-37 35-4* 35-42 35-43 35-44 35-45 35-46 36-** 36-0* 36-03 36-04 36-05 36-4* 36-40 36-42 36-43 36-44 36-45 36-5* 36-50 36-52 36-53 Curve Position Track Error Synchronizing Error Actual Velocity Actual Master Velocity Synchronizing Status Axis Status Program Status MCO 302 Status MCO 302 Control SPI Error Counter Diagnosis readouts MCO Alarm Word 1 MCO Alarm Word 2 Sensor Input Option Temp. Input Mode Term. X48/4 Temperature Unit Term. X48/4 Input Type Term. X48/7 Temperature Unit Term. X48/7 Input Type Term. X48/10 Temperature Unit Term. X48/10 Input Type Temperature Sensor Alarm Function Temp. Input X48/4 Term. X48/4 Filter Time Constant Term. X48/4 Temp. Monitor Term. X48/4 Low Temp. Limit Term. X48/4 High Temp. Limit Temp. Input X48/7 Term. X48/7 Filter Time Constant Term. X48/7 Temp. Monitor Term. X48/7 Low Temp. Limit Term. X48/7 High Temp. Limit Temp. Input X48/10 Term. X48/10 Filter Time Constant Term. X48/10 Temp. Monitor Term. X48/10 Low Temp. Limit Term. X48/10 High Temp. Limit Analog Input X48/2 Term. X48/2 Low Current Term. X48/2 High Current Term. X48/2 Low Ref./Feedb. Value Term. X48/2 High Ref./Feedb. Value Term. X48/2 Filter Time Constant Programmable I/O Option I/O Mode Terminal X49/7 Mode Terminal X49/9 Mode Terminal X49/11 Mode Output X49/7 Terminal X49/7 Analogue Output Terminal X49/7 Min. Scale Terminal X49/7 Max. Scale Terminal X49/7 Bus Control Terminal X49/7 Timeout Preset Output X49/9 Terminal X49/9 Analogue Output Terminal X49/9 Min. Scale Terminal X49/9 Max. Scale 36-54 36-55 36-6* 36-60 36-62 36-63 36-64 36-65 40-** 40-4* 40-40 40-41 40-42 40-43 40-44 40-45 40-46 40-5* 40-50 40-51 42-** 42-1* 42-10 42-11 42-12 42-13 42-14 42-15 42-17 42-18 42-19 42-2* 42-20 42-21 42-22 42-23 42-24 42-3* 42-30 42-31 42-33 42-35 42-36 42-37 42-4* 42-40 42-41 42-42 42-43 42-44 42-45 42-46 42-47 42-48 42-49 42-5* 42-50 42-51 42-52 Terminal X49/9 Bus Control Terminal X49/9 Timeout Preset Output X49/11 Terminal X49/11 Analogue Output Terminal X49/11 Min. Scale Terminal X49/11 Max. Scale Terminal X49/11 Bus Control Terminal X49/11 Timeout Preset Special Settings Extend. Fault Log Fault Log: Ext. Reference Fault Log: Frequency Fault Log: Current Fault Log: Voltage Fault Log: DC Link Voltage Fault Log: Control Word Fault Log: Status Word Advanced Control Settings Flux Sensorless Model Shift Flux Sensorless Corr. Gain Safety Functions Speed Monitoring Measured Speed Source Encoder Resolution Encoder Direction Gear Ratio Feedback Type Feedback Filter Tolerance Error Zero Speed Timer Zero Speed Limit Safe Input Safe Function Type Discrepancy Time Stable Signal Time Restart Behaviour General External Failure Reaction Reset Source Parameter Set Name S-CRC Value Level 1 Password Level 1 Password Buffer SS1 Type Ramp Profile Delay Time Delta T Deceleration Rate Delta V Zero Speed Ramp Time S-ramp Ratio at Decel. Start S-ramp Ratio at Decel. End SLS Cut Off Speed Speed Limit Fail Safe Reaction 11 11 42-53 Start Ramp 42-54 Ramp Down Time 42-6* Safe Fieldbus 42-60 Telegram Selection 42-61 Destination Address 42-8* Status 42-80 Safe Option Status 42-81 Safe Option Status 2 42-82 Safe Control Word 42-83 Safe Status Word 42-85 Active Safe Func. 42-86 Safe Option Info 42-87 Time Until Manual Test 42-88 Supported Customization File Version 42-89 Customization File Version 42-9* Special 42-90 Restart Safe Option 43-** Unit Readouts 43-0* Component Status 43-00 Component Temp. 43-01 Auxiliary Temp. 43-02 Component SW ID 43-1* Power Card Status 43-10 HS Temp. ph.U 43-11 HS Temp. ph.V 43-12 HS Temp. ph.W 43-13 PC Fan A Speed 43-14 PC Fan B Speed 43-15 PC Fan C Speed 43-2* Fan Pow.Card Status 43-20 FPC Fan A Speed 43-21 FPC Fan B Speed 43-22 FPC Fan C Speed 43-23 FPC Fan D Speed 43-24 FPC Fan E Speed 43-25 FPC Fan F Speed 600-** PROFIsafe 600-22 PROFIdrive/safe Tel. Selected 600-44 Fault Message Counter 600-47 Fault Number 600-52 Fault Situation Counter 601-** PROFIdrive 2 601-22 PROFIdrive Safety Channel Tel. No. Appendix 150 VLT® AutomationDrive FC 302 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Index Operating Guide Index C A ADN compliance..................................................................................... 4 Cables Cable length and cross-section................................................ 103 Installation warning........................................................................ 23 Maximum number and size per phase.............................. 96, 98 Opening............................................. 109, 113, 123, 128, 133, 139 Routing......................................................................................... 63, 67 Shielded............................................................................................... 23 Specifications.......................................................... 96, 98, 100, 103 Alarm reset.............................................................................................. 75 Capacitor storage................................................................................. 17 Alarms List of............................................................................................. 14, 84 Log.................................................................................................. 14, 93 Types of................................................................................................ 83 Circuit breakers...................................................................................... 67 Ambient conditions Specifications.................................................................................. 102 Condensation......................................................................................... 17 Abbreviations...................................................................................... 144 AC mains.................................................................................................. 31 see also Mains Additional resources.............................................................................. 4 Analog Input specifications...................................................................... 103 Output specifications................................................................... 104 Wiring configuration for speed reference............................... 73 Analog input/output Descriptions and default settings.............................................. 64 Approvals and certifications............................................................... 4 ATEX monitoring................................................................................... 18 Auto on.............................................................................................. 14, 81 Automatic energy optimization...................................................... 69 Automatic motor adaptation (AMA) Configuring........................................................................................ 69 Warning............................................................................................... 90 Wiring configuration....................................................................... 72 Auxiliary contacts................................................................................. 66 B Clearance requirement....................................................................... 18 Closed loop............................................................................................. 72 Control Characteristics................................................................................ 105 Wiring................................................................................................... 27 Control card Overtemperature trip point.................................................. 96, 98 RS485 specifications..................................................................... 104 Specifications.................................................................................. 105 Warning............................................................................................... 90 Control input/output Descriptions and default settings.............................................. 63 Control shelf........................................................................................... 11 Control wiring.......................................................................... 63, 64, 67 Cooling Check list............................................................................................. 67 Dust warning..................................................................................... 17 Cooling..................................................................................................... 18 Current Input..................................................................................................... 66 Limit...................................................................................................... 95 Brake Control................................................................................................. 85 Resistor................................................................................................ 84 Status message................................................................................. 81 Terminal torque rating................................................................. 108 Current scaling card............................................................................. 86 Brake resistor Warning............................................................................................... 87 Wiring................................................................................................... 66 Wiring schematic............................................................................. 26 D2h interior view.................................................................................. 10 Braking Electro-mechanical brake............................................................. 79 Wiring configuration for mechanical brake............................ 77 Burst transient....................................................................................... 27 Bus termination switch....................................................................... 65 D D1h interior view..................................................................................... 9 Definitions Status messages............................................................................... 81 Derating Specifications.................................................................................. 102 Digital Input specifications...................................................................... 103 Output specifications................................................................... 104 Digital input/output Descriptions and default settings.............................................. 64 Dimension, shipping......................................................................... 7, 8 MG34U502 Danfoss A/S © 09/2018 All rights reserved. 151 Index VLT® AutomationDrive FC 302 Dimensions D1h exterior..................................................................................... 109 D1h terminal...................................................................................... 35 D2h exterior..................................................................................... 113 D2h terminal...................................................................................... 37 D3h exterior..................................................................................... 117 D3h terminal...................................................................................... 39 D4h exterior..................................................................................... 120 D4h terminal...................................................................................... 41 D5h exterior..................................................................................... 123 D5h terminal...................................................................................... 43 D6h exterior..................................................................................... 128 D6h terminal...................................................................................... 47 D7h exterior..................................................................................... 133 D7h terminal...................................................................................... 53 D8h exterior..................................................................................... 139 D8h terminal...................................................................................... 57 Discharge time......................................................................................... 5 Disconnect.............................................................................................. 66 Disconnect switch................................................................................ 68 Disposal instruction............................................................................... 4 Door clearance..................................... 112, 116, 127, 132, 138, 143 Door/panel cover Torque rating................................................................................... 108 Drive Definition............................................................................................... 7 Initialization....................................................................................... 71 Lifting................................................................................................... 19 Status.................................................................................................... 81 E Efficiency Specifications.................................................................... 96, 98, 100 External alarm reset wiring configuration................................... 75 F Factory default settings...................................................................... 71 Fan power card Troubleshooting............................................................................... 86 Fans Servicing.............................................................................................. 17 Warning........................................................................................ 86, 92 Fault log................................................................................................... 14 Fieldbus.................................................................................................... 63 Filter........................................................................................................... 17 Fire mode................................................................................................. 92 Fuses Overcurrent protection.................................................................. 23 Pre-start check list........................................................................... 67 Specifications.................................................................................. 106 Troubleshooting............................................................................... 95 G Galvanic isolation............................................................................... 104 Gases......................................................................................................... 17 Gland plate D1h dimensions............................................................................. 112 D2h dimensions............................................................................. 116 D5h dimensions............................................................................. 127 D6h dimensions............................................................................. 132 D7h dimensions............................................................................. 138 D8h dimensions............................................................................. 143 Torque rating................................................................................... 108 Electronic thermal relay (ETR).......................................................... 23 Ground Check list............................................................................................. 67 Floating delta.................................................................................... 31 Grounded delta................................................................................ 31 Grounding.......................................................................................... 29 Isolated main..................................................................................... 31 Terminal torque rating................................................................. 108 Warning............................................................................................... 89 EMC.............................................................................................. 23, 24, 25 Ground wire............................................................................................ 27 Electrical specifications 200–240 V................................................ 97 Electrical specifications 380–500 V................................................ 99 Electrical Specifications 525–690 V............................................. 100 Electro-mechanical brake.................................................................. 79 Encoder.................................................................................................... 70 Encoder Configuration.................................................................................... 78 Determining encoder direction.................................................. 78 Energy efficiency class...................................................................... 102 Environment........................................................................................ 102 Explosive atmosphere......................................................................... 18 Exterior dimensions D1h..................................................................................................... D2h..................................................................................................... D3h..................................................................................................... D4h..................................................................................................... D5h..................................................................................................... D6h..................................................................................................... D7h..................................................................................................... D8h..................................................................................................... 152 109 113 117 120 123 128 133 139 H Hand on............................................................................................. 14, 81 Heat sink Access.................................................................... 126, 131, 136, 142 Access panel torque rating........................................................ 108 Alarm.................................................................................................... 89 Cleaning.............................................................................................. 17 Overtemperature trip point.................................................. 96, 98 Warning............................................................................................... 91 Heater Usage.................................................................................................... 17 Wiring of.............................................................................................. 65 Wiring schematic............................................................................. 26 High voltage.................................................................................... 87, 88 High voltage warning............................................................................ 5 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Index Operating Guide Humidity.................................................................................................. 17 MCT 10 Set-up Software.................................................................... 69 I Mechanical brake Wiring configuration....................................................................... 77 Indicator lights....................................................................................... 83 Input Power.................................................................................................... 27 Voltage................................................................................................. 68 Input specifications........................................................................... 103 Installation Check list............................................................................................. 67 Electrical.............................................................................................. 23 EMC-compliant................................................................................. 25 Initialization....................................................................................... 71 Qualified personnel........................................................................... 5 Quick set-up....................................................................................... 69 Start up................................................................................................ 70 Tools needed..................................................................................... 17 Installation................................................................................ 18, 20, 22 Installation environment................................................................... 17 Interference EMC....................................................................................................... 24 Radio....................................................................................................... 7 Menu Descriptions of.................................................................................. 15 Keys....................................................................................................... 14 Motor Cable.............................................................................................. 23, 29 Class protection................................................................................ 18 Connection......................................................................................... 29 Data....................................................................................................... 95 Output specifications................................................................... 102 Overheating....................................................................................... 85 Power.................................................................................................... 27 Rotation............................................................................................... 70 Setup.................................................................................................... 15 Terminal torque rating................................................................. 108 Thermistor wiring configuration................................................ 76 Troubleshooting........................................................................ 94, 95 Unintended motor rotation............................................................ 6 Warning................................................................................. 84, 85, 87 Wiring schematic............................................................................. 26 Mounting................................................................................... 18, 20, 22 Interlock device..................................................................................... 65 N Internal fault........................................................................................... 89 Nameplate............................................................................................... 16 Navigation keys.............................................................................. 14, 68 L LCP Display................................................................................................. 13 Indicator lights.................................................................................. 14 Menu..................................................................................................... 15 Troubleshooting............................................................................... 94 O Leakage current................................................................................ 5, 27 Overcurrent............................................................................................. 85 Lifting................................................................................................. 17, 19 Overcurrent protection...................................................................... 23 Load share Terminal dimensions....................................................................... 34 Terminal torque rating................................................................. 108 Terminals...................................................................................... 12, 33 Warning........................................................................................... 5, 88 Wiring schematic............................................................................. 26 Overvoltage............................................................................................ 95 Load share.......................................................................................... 7, 33 Local control panel (LCP)................................................................... 13 P Parameters.............................................................................. 15, 71, 145 Pedestal.................................................................................................... 20 PELV......................................................................................................... 104 Periodic forming................................................................................... 17 Phase loss................................................................................................ 84 M Main menu.............................................................................................. 15 Mains Shield...................................................................................................... 6 Supply specifications................................................................... 102 Terminal torque rating................................................................. 108 Warning............................................................................................... 88 Maintenance.................................................................................... 17, 80 Manual Version number................................................................................... 4 MCT 10...................................................................................................... 69 MG34U502 Optional equipment..................................................................... 65, 68 Output Specifications.................................................................................. 104 Pigtails...................................................................................................... 23 Potential equalization......................................................................... 27 Potentiometer................................................................................. 64, 75 Power Connection......................................................................................... 23 Leakage............................................................................................... 27 Losses................................................................................... 96, 98, 100 Ratings................................................................................. 96, 98, 100 Power card Warning............................................................................................... 91 Programming......................................................................................... 14 Danfoss A/S © 09/2018 All rights reserved. 153 Index VLT® AutomationDrive FC 302 Pulse Input specifications...................................................................... 104 Wiring configuration for start/stop........................................... 74 Q Qualified personnel................................................................................ 5 Quick menu..................................................................................... 14, 15 Short-circuit current rating............................................................. 107 Sleep mode............................................................................................. 82 Smart logic control Wiring configuration....................................................................... 77 Software version number.................................................................... 4 Specifications electrical..................................................... 96, 98, 100 R Speed Wiring configuration for speed reference............................... 75 Wiring configuration for speed up/down............................... 75 Ramp-down time.................................................................................. 95 Start/stop wiring configuration............................................... 73, 74 Ramp-up time........................................................................................ 95 Status message definitions............................................................... 81 Recycling.................................................................................................... 4 Storage..................................................................................................... 17 Reference Speed input........................................................................................ 73 Switches A53 and A54.................................................................................... 103 A53/A54............................................................................................... 66 Brake resistor temperature........................................................... 66 Bus termination................................................................................ 65 Regen................................................................................................... 7, 33 Regen Terminal dimensions....................................................................... 34 Terminals........................................................................ 12, 33, 40, 42 Regeneration Terminal torque rating................................................................. 108 Regional settings......................................................................... 71, 145 Relay Specifications.................................................................................. 105 Reset..................................................................................... 14, 83, 85, 91 RFI............................................................................................................... 31 Rotor Warning............................................................................................... 92 T Temperature........................................................................................... 17 Terminal dimensions D1h........................................................................................................ 35 D2h........................................................................................................ 37 D3h........................................................................................................ 39 D4h........................................................................................................ 41 D5h........................................................................................................ 43 D6h........................................................................................................ 47 D7h........................................................................................................ 53 D8h........................................................................................................ 57 RS485 Configuring........................................................................................ 65 Terminal description....................................................................... 63 Wiring configuration....................................................................... 76 Wiring schematic............................................................................. 26 Terminals Analog input/output...................................................................... 64 Control locations.............................................................................. 63 Digital input/output........................................................................ 64 Serial communication.................................................................... 63 Terminal 37.................................................................................. 64, 65 S Thermal protection................................................................................ 4 Safe Torque Off Terminal location............................................................................. 64 Warning............................................................................................... 91 Wiring configuration....................................................................... 73 Wiring of.............................................................................................. 65 Wiring schematic............................................................................. 26 Thermistor Cable routing..................................................................................... 63 Terminal location............................................................................. 64 Warning............................................................................................... 91 Wiring configuration....................................................................... 76 Safety instructions................................................................................ 23 Torque Characteristic.................................................................................. 102 Fastener rating................................................................................ 108 Limit............................................................................................... 85, 95 Wiring configuration for torque and stop limit..................... 79 Serial communication Cover torque rating...................................................................... 108 Descriptions and default settings.............................................. 63 Service...................................................................................................... 80 Set-up....................................................................................................... 14 Shielding Clamps................................................................................................. 23 Mains....................................................................................................... 6 Twisted ends...................................................................................... 23 Tools.......................................................................................................... 17 Transducer............................................................................................... 63 Trip Points for 200–240 V drives.......................................................... 96 Points for 380–500 V drives.......................................................... 98 Points for 525–690 V drives........................................................ 100 Shipping dimension.......................................................................... 7, 8 Short circuit............................................................................................ 86 154 Danfoss A/S © 09/2018 All rights reserved. MG34U502 Index Operating Guide Troubleshooting Fuses..................................................................................................... 95 LCP......................................................................................................... 94 Mains.................................................................................................... 95 Motor............................................................................................. 94, 95 Warnings and alarms...................................................................... 84 U UL certification......................................................................................... 4 Unintended start.............................................................................. 5, 80 USB Specifications.................................................................................. 106 V Voltage Imbalance........................................................................................... 84 Input..................................................................................................... 66 W Warnings List of............................................................................................. 14, 84 Types of................................................................................................ 83 Weight.................................................................................................... 7, 8 Windmilling............................................................................................... 6 Wire size................................................................................................... 29 Wiring control terminals.................................................................... 64 Wiring schematic Drive...................................................................................................... 26 Typical application examples...................................................... 72 MG34U502 Danfoss A/S © 09/2018 All rights reserved. 155 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com 130R0291 MG34U502 *MG34U502* 09/2018
advertisement