Service Manual Modular Crescent Cuber Serenity Series Model KMS-2000MLJ Including Condensing Unit Models SRK-20J/3 hoshizakiamerica.com Number: 73225 Issued: 6-15-2018 Revised: 7-24-2019 WARNING Only qualified service technicians should install and service the appliance. To obtain the name and phone number of your local Hoshizaki Certified Service Representative, visit www.hoshizaki.com. No installation or service should be undertaken until the technician has thoroughly read this Service Manual. Likewise, the owner/manager should not proceed to operate the appliance until the installer has instructed them on its proper operation. Failure to install, operate, and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. Proper installation is the responsibility of the installer. Product failure or property damage due to improper installation is not covered under warranty. Hoshizaki provides this manual primarily to assist qualified service technicians in the installation, maintenance, and service of the appliance. Should the reader have any questions or concerns which have not been satisfactorily addressed, please call, send an e-mail message, or write to the Hoshizaki Technical Support Department for assistance. Phone: 1-800-233-1940; (770) 487-2331 Fax: 1-800-843-1056; (770) 487-3360 E-mail: [email protected] 618 Highway 74 South Peachtree City, GA 30269 Attn: Hoshizaki Technical Support Department NOTE: To expedite assistance, all correspondence/communication MUST include the following information: • Model Number • Serial Number • Complete and detailed explanation of the problem. 2 IMPORTANT This manual should be read carefully before the appliance is serviced. Read the warnings and guidelines contained in this manual carefully as they provide essential information for the continued safe use, service, and maintenance of the appliance. Retain this manual for any further reference that may be necessary. CONTENTS Important Safety Information.................................................................................................. 5 I. Construction and Water/Refrigeration Circuit Diagram........................................................ 7 A. Construction.................................................................................................................. 7 1. Icemaker................................................................................................................... 7 2. Condensing Unit ...................................................................................................... 8 B. Water Circuit and Refrigeration Circuit........................................................................... 9 II. Sequence of Operation and Service Diagnosis................................................................ 10 A. Sequence of Operation Flow Chart.............................................................................. 10 1. Operation Flow Chart ............................................................................................. 10 2. Shutdown Flow Chart..............................................................................................11 3. Freeze-Time Correction Chart................................................................................ 12 B. Service Diagnosis........................................................................................................ 13 C. Freeze-Time Correction Cycle (90 min.)...................................................................... 20 D. Control Board Check.................................................................................................... 22 E. Bin Control Check........................................................................................................ 24 F. Float Switch Check and Cleaning................................................................................. 26 G. Thermistor Check......................................................................................................... 28 H. Switches....................................................................................................................... 29 1. Control Switch......................................................................................................... 29 2. Service Switch........................................................................................................ 29 I. Diagnostic Tables........................................................................................................... 30 J. Freeze-Up Check List................................................................................................... 34 III. Controls and Adjustments................................................................................................ 35 A. Control Board Layout................................................................................................... 36 B. LED Lights and Audible Alarm Safeties........................................................................ 37 C. Settings and Adjustments............................................................................................. 38 1. Default Dip Switch Settings..................................................................................... 38 2. Harvest Timer (S4 dip switch 1 & 2)....................................................................... 39 3. Pump-Out Timer/Harvest Time During Pump-Out (S4 dip switch 3 & 4)................ 39 4. Pump-Out Frequency Control (S4 dip switch 5)...................................................... 40 5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6)............................ 40 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7).... 41 7. Factory Use (S4 dip switch 8)................................................................................. 42 8. Freeze Timer (S4 dip switch 9 & 10)....................................................................... 42 9. Float Switch Control Selector (S5 dip switch 1)...................................................... 42 10. Refill Counter (S5 dip switch 2 and 3)................................................................... 43 11. Minimum Harvest Time (S5 dip switch 4).............................................................. 43 12. Anti-Slush (S5 dip switch 5).................................................................................. 43 3 IV. Refrigeration Circuit and Component Service Information.............................................. 44 A. Refrigeration Circuit Service Information..................................................................... 44 B. Component Service Information................................................................................... 47 V. Maintenance................................................................................................................. 48 VI. Preparing the Appliance for Periods of Non-Use......................................................... 49 VII. Disposal.......................................................................................................................... 51 VIII. Technical Information..................................................................................................... 52 A. Specification and Performance Data Sheets................................................................ 52 1. KMS-2000MLJ with SRK-20J................................................................................. 52 2. KMS-2000MLJ with SRK-20J3............................................................................... 53 3. SRK-20J................................................................................................................. 54 4. SRK-20J3............................................................................................................... 55 B. Wiring Diagrams........................................................................................................... 56 1. Wire Harness Connections...................................................................................... 56 2. KMS-2000MLJ with SRK-20J................................................................................. 57 3. KMS-2000MLJ with SRK-20J3............................................................................... 58 4 Important Safety Information Throughout this manual, notices appear to bring your attention to situations which could result in death, serious injury, damage to the appliance, or damage to property. WARNING Indicates a hazardous situation which could result in death or serious injury. NOTICE Indicates a situation which could result in damage to the appliance or property. IMPORTANT Indicates important information about the use and care of the appliance. WARNING This appliance should be destined only to the use for which it has been expressly conceived. Any other use should be considered improper and therefore dangerous. The manufacturer cannot be held responsible for injury or damage resulting from improper, incorrect, and unreasonable use. Failure to service and maintain the appliance in accordance with this manual will adversely affect safety, performance, component life, and warranty coverage and may result in costly water damage. To reduce the risk of death, electric shock, serious injury, or fire, follow basic precautions including the following: • Only qualified service technicians should install and service this appliance. • This appliance must be installed in accordance with applicable national, state, and local codes and regulations. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage to the appliance. • To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands. • Before Servicing the KMS or SRK: To reduce the risk of electric shock, move the control switch to the "OFF" position and turn off the power supply to the SRK condensing unit. Place the KMS disconnect (if applicable) in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently. • Do not make any alterations to the appliance. Alterations could result in electric shock, injury, fire, or damage to the appliance. • This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. • Children should be properly supervised around this appliance. • Do not climb, stand, or hang on the appliance or allow children or animals to do so. Serious injury could occur or the appliance could be damaged. • Do not use combustible spray or place volatile or flammable substances near the appliance. They might catch fire. • Keep the area around the appliance clean. Dirt, dust, or insects in the appliance could cause harm to individuals or damage to the appliance. 5 WARNING, continued For KMS • Risk of electric shock. Control switch in "OFF" position does not de-energize all loads. • Power supply and ground connection are supplied from the SRK remote condensing unit via the wire harness provided. Do not connect the wire harness leads to an external power source. • Wire harness routing (conduit) and disconnect (if required) must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage to the appliance. • THE APPLIANCE MUST BE GROUNDED. Failure to properly ground the appliance could result in death, serious injury, or damage to the appliance. For SRK • Electrical connection must be hard-wired and must meet national, state, and local electrical code requirements. Failure to meet these code requirements could result in death, electric shock, serious injury, fire, or damage to the appliance. • The remote condensing unit requires an independent power supply of proper capacity. See the nameplate for electrical specifications. Failure to use an independent power supply of proper capacity can result in a tripped breaker, blown fuses, damage to existing wiring, or component failure. This could lead to heat generation or fire. • THE REMOTE CONDENSING UNIT MUST BE GROUNDED. Failure to properly ground the remote condensing unit could result in death, serious injury, or damage to the appliance. NOTICE • Follow the instructions in this manual carefully to reduce the risk of costly water damage. • In areas where water damage is a concern, install in a contained area with a floor drain. • Install the appliance in a location that stays above freezing. Normal operating ambient temperature must be within 45°F to 100°F (7°C to 38°C). • Do not leave the appliance on during extended periods of non-use, extended absences, or in sub-freezing temperatures. To properly prepare the appliance for these occasions, follow the instructions in "VI. Preparing the Appliance for Periods of Non-Use." • Do not place objects on top of the appliance. • The dispenser unit/storage bin is for ice use only. Do not store anything else in the dispenser unit/storage bin. 6 I. Construction and Water/Refrigeration Circuit Diagram A. Construction 1. Icemaker Top Panel Top Insulation Inlet Water Valve Spray Guides Wash Valve Hot Gas Valve Strainer Suction Line Shutoff Valve Spray Tubes Insulation Panel Evaporator Thermostatic Expansion Valves Liquid Line Shutoff Valve Thermistor Control Box Drier Liquid Line Valve Pump Motor Drain Valve Float Switch Front Panel Bin Control Control Box Switch Cover Control Switch Service Switch Fuse (KMS) Switch Mount Extension Bracket Bin Control 7 Left Side Panel Switch Bracket 2. Condensing Unit Top Panel Main Transformer (Three Phase Only) Condenser Right Side Panel Control Box Suction Line Shutoff Valve Liquid Line Shutoff Valve Fan Motors Liquid Line Shutoff Valve 2 High-Pressure Switch Compressor Crankcase Heater Junction Box Louver Panel Front Panel Discharge Line Thermostat Liquid Line Valve Strainers Left Side Upper Panel Right Left Side Upper Panel Hot Gas Valves Headmaster (C.P. R.) Accumulator Receiver Left Side Lower Panel 8 Water Tank Evaporator Pump Motor Spray Tube Drain 9 Drain Valve Float Switch Check Valves Receiver Headmaster (C.P. R.) Discharge Line Compressor Suction Line Fans Condenser SRK-20J/3 Strainer Accumulator Hot Gas Valve Strainer Drier Liquid Line Valve Suction Line Shutoff Valves Liquid Line Shutoff Valves Liquid Line Valve Thermostatic Expansion Valves Thermistor Heat Exchanger Wash Valve Inlet Water Valve Water Supply KMS-2000MLJ High-Pressure Switch Liquid Line Shutoff Valve 2 Strainers Hot Gas Valves Access Valve Check Valve Discharge Line Thermostat B. Water Circuit and Refrigeration Circuit F/S open 10 Legend: BC-bin control Comp-compressor DV-drain valve FMRs-fan motors-remote F/S-float switch HGVs-hot gas valves (KMS and SRK) LLVs-liquid line valves (KMS and SRK) PM-pump motor WV-inlet water valve FS closed 5-min. minimum freeze timer in control Comp continues FMRs continue PM continues LLVs energized HGVs de-energized Anti-Slush Thermistor temperature drops to 36°F (2.2°C) (5.8 kΩ or more). PM de‑energizes for 10 sec. Comp continues FMRs continue HGVs energized DV energized PM de-energizes for 2 sec., then energized for 10/20 sec. LLVs de-energized When freeze time differential exceeded, freeze-time correction cycle starts. See "II.A.3. Freeze-Time Correction Chart." FS opens or freeze timer terminates FS in control • Factory set for every 10th cycle. (S4 dip switch 5) • Pump motor stops for 2 sec., then energized for 10/20 sec. (S4 dip switch 3 & 4) 4. Pump-Out Cycle Power is supplied to the pump motor and drain valve. This drains the water tank. Power is supplied to the pump motor only. This operation can be used to circulate cleaner and sanitizer over the outside surface of the evaporator for extended periods of time. Power is supplied to the pump motor and wash valve. This operation is used to circulate cleaner and sanitizer over both the inside and outside surfaces of the evaporator. DRAIN CIRC. WASH When in the "SERVICE" position, the control switch supplies power to the service switch and the icemaker is in service mode. The service switch has three positions: "DRAIN," "CIRC." and "WASH." See the information below for details of each function. Components Energized when the Control Switch is in the "SERVICE" Position If F/S is open, Comp and FMRs de-energize and cycle returns to 1-minute fill cycle F/S open F/S check 50 sec. Harvest Pump Timer 1 to 3-min. timer in control (S4 dip switch 1 & 2) • Minimum freeze time: 5 min. • Maximum freeze time: freeze timer setting (S4 dip switch 9 & 10) 3. Freeze Cycle 1. Operation Flow Chart PM energized WV continues WV de-energized Comp energized FMRs energized Thermistor temperature HGVs energized reaches 48°F (9°C) (3.9 kΩ or less) Harvest timer starts. F/S closed Thermistor in control HPT settings (S4 dip switch 6), whichever is shorter. • Maximum harvest time: 20 min. 1. 1-Minute 2. Harvest Cycle • WV time: 6 min. or the length of harvest minus Fill Cycle Startup begins F/S check here after 5-sec. delay WV energized Cycle Steps Operation Flow Chart II. Sequence of Operation and Service Diagnosis A. Sequence of Operation Flow Chart BC Operation Shutdown and Restart 11 Legend: BC–bin control BC open (BC actuator paddle engaged) Green "BC CLOSED" LED off Yellow "BC OPEN" LED on All components de-energized. 2. Icemaker Off BC closed (BC actuator paddle disengaged) Green "BC CLOSED" LED on Yellow "BC OPEN" LED off To 1. 1-Minute Fill Cycle Icemaker starts at "1. 1-Minute Fill Cycle." 3. Ice Level Lowered Control board retains freeze-time correction count data between bin control restarts. Yellow "BC OPEN" LED continues. All components de‑energized. Shutdown Delay: • Fill Cycle–15 sec. after activation. • Harvest Cycle–At the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the end of the harvest cycle. • Freeze Cycle– 15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle protection timer terminates. Otherwise, at the end of the next harvest cycle. 1. Bin Full Shutdown Flow Chart 2. Shutdown Flow Chart 12 254 309 349 380 406 427 446 462 3 4 5 6 7 8 9 10 Note: When 1st freeze-time correction cycle is initiated, CB "POWER OK" LED starts blinking. On 2nd freeze-time correction cycle, if CB "POWER OK" LED has been reset, CB "POWER OK" LED starts blinking. If CB "POWER OK" had not been reset after 1st freeze-time correction cycle CB "POWER OK" LED continues to blink. After 3rd freeze‑time correction cycle in 36 hours, CB yellow "EXT HARVEST" LED starts blinking. Appliance continues to operate and LEDs continue to blink until ALARM RESET button is pressed with power on. Differential Value in Sec. Number of Freeze Cycles Freeze Time Differential Exceeded. Minimum and Maximum Freeze times have exceeded differential parameters. Freeze-Time Correction function is enabled when S4 Dip Switch 7 is in the "ON" position. CB monitors freeze time. After 3 freeze cycles, CB compares the minimum and maximum differential of the 3 freeze cycle times. Every freeze cycle time after the third freeze cycle time is added to the minimum/ maximum calculation. Example: After 8 cycles, if the differential between the shortest cycle (minimum) and the longest cycle (maximum) is equal to or greater than 427 sec. a freeze-time correction cycle is initiated: Comp energized FMRs energized HGVs energized PM energized WV energized Appliance Cycle Reset and Alarm Reset: Cycle Reset: Power Supply or Control Switch Turned Off and On again: Appliance turns off, then re-starts at 1.Fill Cycle. Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time correction cycle with power supply on: Appliance continues cycle with no interruption or reset. CB red "POWER OK" LED blinking: CB red "POWER OK" LED resets to solid. CB yellow "EXT HARVEST" LED blinking: CB yellow "EXT HARVEST: LED turns off. WV energized Comp de-energized FMRs de-energized HGVs de-energized PM de-energized 2. 10-Minute Fill/ Overflow After 5th 10-Minute Harvest Pump Cycle with WV Freeze-Time Correction Cycle Complete. Go to Step "3. Freeze Cycle" in Operation Flow Chart. • Do not adjust S4 dip switch 7 out of the factory position. • After step 2 completes 4th sequence (80 min. completed), repeat step 1 for 5th and final time. 1. 10-Minute Harvest Cycle with WV Legend: Comp–compressor FM–fan motor FMRs–fan motor-remote HGVs–hot gas valve PM–pump motor WV–inlet water valve Start Cycle Steps Steps 1 and 2 repeat 4 times (total 80 min.), then step 1 repeats for a 5th time to complete Freeze‑Time Correction Cycle. Freeze-Time Correction Flow Chart 3. Freeze-Time Correction Chart B. Service Diagnosis WARNING • The appliance should be diagnosed and repaired only by qualified service personnel to reduce the risk of death, electric shock, serious injury, or fire. • Risk of electric shock. Control switch in "OFF" position does not de‑energize all loads. Use extreme caution and exercise safe electrical practices. • Moving parts (e.g., fan blade) can crush and cut. Keep hands clear. • Before servicing the appliance, move the control switch to the "OFF" position and turn off the power supply. • CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin. • Make sure all food zones in the appliance and dispenser unit/ice storage bin are clean after service. 1. Diagnostic Procedure The diagnostic procedure is a sequence check that allows you to diagnose the electrical system and components. Before proceeding, check for correct installation, proper voltage per nameplate, and adequate water supply. Note: • When checking high voltage (115VAC), always choose a neutral (W) to establish a good neutral connection. • On 3-phase models, the neutral (W) is provided through MT. To confirm a good neutral (W), check for 60VAC from neutral (W) to ground (GND). If 60VAC is present, neutral (W) is good. If 60VAC is not present, check 208-230VAC main power supply to MT. If 208-230VAC is present, check MT continuity. • When checking voltage from the CB K1 connector (10 pin connector), pull CB K1 connector out slightly to allow room for multimeter test leads contact. 1) Turn off the power supply, then access the control box. Clear any ice from BC. 2) Check that the 115VAC 10A fuses in the KMS and SRK are good. Confirm that the location meets installation requirements: KMS-2000MLJ: • The appliance is not intended for outdoor use. Normal operating ambient temperature should be within 45°F to 100°F (7°C to 38°C). • Allow 6" (15 cm) clearance at sides, rear, and top of the appliance for proper air circulation and ease of maintenance and service. • The appliance should not be located in a corrosive environment. SRK-20J/3: • A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for proper air circulation and ease of maintenance and/or service should they be required. 13 3) Power On: Turn on the power supply, then move the control switch to the "ICE" position. A 5‑sec. delay occurs. CB red "POWER OK" LED and CB green "BC CLOSED" LED turn on. If CB yellow "BC OPEN" LED is on (indicating a full bin), check CB K4 red jumper. Move ice away from BC bulb. Note: • CB red "POWER OK" LED remains on unless the 10.5VAC power supply is interrupted (K2 connector). • Check CB using the steps in "II.D. Control Board Check." a) Power On Diagnosis: If CB red "POWER OK" LED is off, confirm 10A fuse on both the KMS and the SRK are good. Confirm wire harness is connected and not damaged. Next, check SRK switches. Check for 115VAC at both HPS wires (BR) to neutral (W). If 115VAC is present on one and not the other, HPS is open. If HPS is open, see "b) HPS Diagnosis" below. If HPS is closed, check for 115VAC at both DLT wires (BR) to neutral (W). If 115VAC is present on one and not the other, DLT is open. If DLT is open, see "c) DLT Diagnosis" below. If DLT is closed, go to KMS and check for 115VAC at BC wires (BR) to neutral (W). If 115VAC is present on one and not the other, BC is open. See "II.E. Bin Control Check." If BC is closed, check for 115VAC at control switch #1 (BR) to neutral (W) then at control switch #2 (BK) to neutral (W). If 115VAC is present on #1 (BR) and not on #2 (BK), replace control switch. If 115VAC is present on control switch #2 (BK), check for 10.5VAC at CB K2 #1 red wire to CB K2 #2 red wire. If 10.5VAC is not present, check CT wire connections and CT continuity. If open, replace CT. b) HPS Diagnosis: Check that all shutoff valves (4 total) are open and the condenser coil is not clogged or restricted. Let refrigeration circuit pressures equalize. If HPS does not reset and pressures are equalized, replace HPS. If pressures are not equalized, reclaim refrigerant and diagnose refrigeration circuit restriction. Check that there are no restrictions in the refrigeration circuit. Harvest Cycle: HGVs, strainer, or check valve. Freeze Cycle: FMRs, TXV, HM, LLVs, strainer, check valve, drier, and damaged line set or fitting. c) DLT Diagnosis: Check that the condenser coil is not clogged or restricted. Let discharge line thermostat cool, if DLT does not close, replace DLT. Once closed, restart appliance, once Comp starts, check voltage and amp draw. See "5a),a) Comp Diagnosis" below. 4) 1-Min. Fill Cycle – LED 4 is on. WV and X11 relay energize. After 1 min., CB checks for a closed FS. If FS is closed, the harvest cycle begins. If harvest cycle begins (Comp, HGVs, and FMRs energized), continue to step 5a. If FS is open, WV remains energized until FS closes (low water safety protection during initial start up and at the end of each harvest). Diagnosis: Check that water enters the water tank. If not, check that the water supply line shut-off valve is open and screens or external filters are clear. Check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, and WV does not energize, check for 115VAC at WV. If 115VAC is present, check WV coil continuity. If open, replace WV. If the water tank fills, but the appliance fails to start harvest (Comp energized), check for open FS. See "II.F. Float Switch Check and Cleaning." If FS is closed and CB fails to start the harvest cycle after 1 min., replace CB. 14 5a) Initial Harvest Cycle – LEDs 1, 4, and 2 are on. WV and X11 relay continue. Comp, FMRs, HGVs, and X10 relay energize. CB monitors the warming of the evaporator via the thermistor located on the suction line. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). WV and X11 relay are energized during harvest for a maximum of 6 min. or the length of harvest minus HPT setting (S4 dip switch 6), whichever is shorter. See step 5b below. a) Comp Diagnosis: Check that evaporator is warming. If not, confirm that Comp energizes. If not, check for 115VAC at CB K1 #1 (V) to neutral (W). If 115VAC is not present, check for 115VAC at CB K1 #10 (BR) to neutral (W). If 115VAC is present at #10 (BR) and not at #1 (V), replace CB. If 115VAC is present, check for 115VAC at MC solenoid (SRK). If 115VAC not present, check wire harness connections. If 115VAC is present, confirm contacts are closed. If not, replace MC. If MC contacts are closed, check Comp start and run capacitors, start relay (single phase), and Comp motor winding. b) HGVs Diagnosis: If Comp is energized and evaporator is not warming, check that HGVs energizes and open. Check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, check for 115VAC at HGVs coil (KMS and SRK) and check HGVs coils continuity. Replace as needed. c) LLVs Diagnosis: Confirm that both LLVs are de-energized (KMS and SRK) and closed (not bypassing). If energized, replace CB. If de-energized and bypassing, replace LLVs (KMS and SRK). 5b) Harvest Pump Timer – LEDs 1, 3, and 2 are on. When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). When WV de-energizes, LED 4 turns off, X11 relay de-energizes and LED 3 turns on. PM and X12 relay energize. Comp, FMRs, HGVs, and X10 relay continue. Diagnosis: Place a thermometer on the suction line next to the thermistor. Has it warmed to 48°F (9°C) or warmer? Confirm thermistor status. See "II.G. Thermistor Check." If the thermistor reading is in proper range, dip switch 7 is on, and PM does not energize before harvest terminates, replace CB. If WV continues, check for 115VAC at CB K1 #6 (O). If 115VAC is present, and LED 4 is off, replace CB. If 115VAC is not present, and WV continues, check WV diaphragm for leaking by. Clean or replace. If LED 3 is on and PM is not energized, check for 115VAC at CB K1 #5 (DBU). If 115VAC is not present, replace CB. If 115VAC is present and PM is not energized, check for 115VAC at X10 relay terminal #8 (Y) to neutral (W). If 115VAC is not present, check for 115VAC at X10 relay terminal #4 (P) to neutral (W) and X10 relay terminal #6 (Y) to neutral (W). If 115VAC is present on terminal #4 (P) and not on terminal #6 (Y), replace X10 relay. If 115VAC is present on X12 relay terminal #8 (P) and PM is not energized, check for 115VAC at X12 relay terminal #4 (W/R) to neutral (W) and terminal #6 (DBU) to neutral (W). If 115VAC is present on terminal #6 (DBU) and not on terminal #4 (W/R), replace X12 relay. If 115VAC is present on X12 relay terminal #4 (W/R). If 115VAC is present between X12 relay terminal #4 (W/R) and neutral (W), check PM capacitor and motor winding continuity. 15 5c) Initial Harvest Cycle Termination Diagnosis: When the thermistor reaches 48°F (9°C), CB reads 3.9 kΩ from the thermistor and turns harvest termination over to the harvest timer (S4 dip switch 1 & 2 and S5 dip switch 4). Check discharge line temperature. For a thermistor check, see "II.G. Thermistor Check." If 1-min. fill cycle starts after harvest timer terminates, check that FS is clean and operating properly, see "II.F. Float Switch Check and Cleaning." If FS is closed, CB proceeds to the next cycle. If not, replace CB. Note: The minimum total time allowed by CB for a complete harvest cycle is based on S5 dip switch 4. Maximum harvest time allowed is 20 min. NOTICE! S4 dip switch 7 must remain on. Otherwise, PM will not energize during the last seconds of harvest. 6) Freeze Cycle – LED 1 is on. Comp, FMRs, and PM continue. LLVs energize. HGVs, X10 and X12 relays de‑energize. Appliance is held in freeze by a 5-min. short cycle protection timer. After 5-min. short cycle protection timer terminates and FS opens, freeze cycle terminates. Note: PM power supply switches from CB K1 #5 (DBU) in HPT to K1 #4 (R) in freeze. Anti-Slush: When anti-slush is enabled (S5 dip switch 5 "ON"), PM de-energizes when thermistor reaches 36°F (2.2°C) (5.8 kΩ) for 10 sec. then, energizes for the remainder of the freeze cycle. a) Freeze Cycle Diagnosis: Confirm Comp, FMRs, and PM continue. Confirm that LLVs energize. Next, confirm HGVs, X10 and X12 relays de-energize. During the first 5 min. of freeze, confirm evaporator is cooling. If not, confirm WV de-energized (not leaking by), HGVs de-energized (not bypassing), LLVs energizes, TXV and HM operate correctly, Comp is efficient, and refrigerant charge is correct. See "VIII.A. Specification and Performance Data Sheets." b) Comp and FMRs Diagnosis: If Comp and FMRs de-energize once freeze begins, check that appliance has not shut off on HPS or DLT ("POWER OK" LED off). If so, check "3)b) HPS Diagnosis" or "3)c) DLT Diagnosis" above. If CB "POWER OK" LED is on (KMS), check for 115VAC at CB K1 #9 (V) to neutral (W). If 115VAC is not present and LED 1 is on, replace CB. If 115VAC is present, check for 115VAC at MC coil (SRK). If 115VAC is not present, check wire harness connections. Next, check for 115VAC at MC coil. If 115VAC is present, check MC coil and contacts continuity. Replace as needed. If MC is okay, check Comp start relay and start and run capacitors (single phase). Next, check Comp motor winding continuity. If Comp is energized but evaporator is not cooling, check for an inefficient Comp. See "VIII.A. Specification and Performance Data Sheets." FMRs Diagnosis: If Comp is energized but FMRs are not, check for 115VAC at MC terminal "NO" black (BK) wire to neutral (W). If 115VAC is not present, and MC is energized replace MC. If 115VAC is present, check FMRs capacitors, motor windings, and fan blades for binding. 16 c) WV and HGVs Diagnosis: If WV is energized, check for 115VAC at CB K1 #6 (O) to neutral (W). If 115VAC is present after PM energizes in harvest cycle, replace CB. If 115VAC is not present, replace WV (bypassing). If HGVs (KMS and SRK) did not de‑energize at the end of harvest, check for 115VAC at CB K1 #2 (P) to neutral (W). If 115VAC is present 50 sec. after PM energizes, replace CB. If 115VAC is not present, replace HGV(s) (bypassing). d) PM Diagnosis: Confirm water is flowing over evaporator from PM and not WV. If PM de-energizes once freeze begins (except for anti-slush), check for 115VAC at CB K1 #4 (R) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present and PM is de-energized, check for 115VAC at control switch #5 (W/R) to neutral (W). If 115VAC is present at CB K1 #4 (R) and not at control switch #5 (W/R), check control switch continuity between #5 (W/R) and #4 (R). Replace as needed. If 115VAC is present at control switch #5 (W/R) to neutral (W), check PM capacitor and motor winding continuity. e) LLVs Diagnosis: If LLVs does not energize, check for 115VAC at CB K1 #3 (BK) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present, check coil voltage and continuity. f) Refrigerant Pressures, HM, and TXV Diagnosis: If evaporator is still not cooling, check refrigerant pressures. See "VIII.A. Specification and Performance Data Sheets." Next, check HM operation. If refrigeration pressures are above HM setpoint and HM is bypassing, replace HM. Check TXV for proper operation. Remove TXV bulb and hold it in your hand, refrigerant low-side pressure should rise, place TXV bulb in ice water, refrigerant low-side pressure should drop. A 10 to 15 pound pressure swing between warm and cold conditions indicate a good TXV. If a 10 to 15 pound swing is not present, replace TXV. g) Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.F. Float Switch Check and Cleaning." Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions. Cycle times and pressures should follow performance data provided in this manual. See "VIII.A. Specification and Performance Data Sheets." h) Short Freeze Cycle Diagnosis: Confirm water tank fills and overflows during 1 min. fill and harvest cycles. If not, check water supply filters, shut-off valve, WV screen. If water tank empties before 5 min. timer terminates and freeze cycle is short, check that DV is not leaking by or energized (water flowing through DV). If DV is leaking by, remove and clean DV, replace as needed. If water tank is full, see "II.F. Float Switch Check and Cleaning." for erratic operating FS. 17 7) Pump-Out Cycle – LEDs 1, 3, and 2 are on (10/20 second pump-out). Timing of the first pump-out is determined by S4 dip switch 5. See the table below. Control Board Settings S4 Dip Switch Setting Pump-Out Frequency Control Board OFF Every 10 cycles After 11th freeze cycle ON Every cycle After 2nd freeze cycle No. 5 Comp and FMRs continue, HGVs energize. Note: If S4 dip switch 3 & 4 are set to 3 off and 4 on, LED 4 turns on and WV and X11 relay energize, energizing X10 relay. NOTICE! S4 dip switch 3 & 4 must not be set to 3 off and 4 on. Otherwise, LED 4 turns on energizing WV and X11 relay. X11 relay energizes X10 relay. Once X10 relay energizes, X12 relay cannot energize. Preventing DV from energizing. LLVs de‑energize. PM stops for 2 sec., then restarts for 10/20 sec. depending on pump‑out timer (S4 dip switch 3 & 4) setting. When the pump‑out timer terminates, pump‑out is complete. The pump-out frequency control (S4 dip switch 5) is factory set, and generally no adjustment is required. However, the pump‑out frequency control can be set to have a pump-out occur every 10 cycles or every cycle. For details, see "III.C.4. Pump‑Out Frequency Control (S4 dip switch 5)." a) Pump-Out Diagnosis: In the freeze cycle before pump-out (see table above), after 5 min. of freeze disconnect CB black K5 connector (FS connector). Check that CB LEDs 1, 3, and 2 are on, PM stops, then restarts, DV energizes, and water is flowing down the drain through DV. b) CB Diagnosis: Confirm LLVs de-energize. If LLVs are energized with LEDs 1, 3, and 2 on, replace CB. If PM does not stop and restart and DV does not energize, check that CB LEDs 1, 3, and 2 are on. If not, replace CB. If LEDs 1, 3, and 2 are on and X12 relay is not energized, check for 115VAC at CB K1 #5 (DBU) to neutral (W). If 115VAC is not present, replace CB. If 115VAC is present at CB K1 #5 (DBU) and X12 relay is not energized, continue to "c) X12 Relay Diagnosis:" below. If X12 relay is energized and DV are not energized, check for 115VAC at CB K1 #2 (P) to neutral (W). If LED 2 is on and 115VAC is not present at CB K1 #2 (P), replace CB. c) X12 Relay Diagnosis: If 115VAC is present at CB K1 #5 (DBU) and CB K1 #2 (P) and X12 relay and DV are not energized, check for 115VAC at X12 relay #8 (P) to neutral (W). If 115VAC is not present, check wiring connections from CB K1 #5 (DBU) to X12 relay #6 (DBU), then at X12 relay #4 (W/R). If 115VAC is present at X12 relay #6 (DBU) and not at X12 relay #4 (W/R), confirm X12 relay is de-energized, if X12 relay is de-energized, replace X12 relay (sticking contacts). If 115VAC is present at X12 relay #5 (DBU) to neutral (W), and X12 is de‑energized, check relay coil continuity. Replace as needed. 18 d) PM Diagnosis: Check for 115VAC at X12 relay #6 (DBU) to neutral (W). If 115VAC is not present, see "b) CB Diagnosis" above. Next, check for 115VAC at X12 relay #4 (W/R) to neutral (W). If 115VAC is not present, confirm X12 relay is energized. If X12 relay is de-energized, see "c) X12 Relay Diagnosis:" above. If X12 relay is energized and 115VAC is present at X12 relay #6 (DBU) and not at X12 relay #4 (W/R), replace X12 relay. If 115VAC is present at X12 relay #4 (W/R) and PM is de‑energized, check PM capacitor, motor winding, wiring connections, and impeller for binding. e) DV Diagnosis: Check for 115VAC at X12 relay #5 (DBU) to neutral (W) and at X12 relay #3 (GY) to neutral (W). If 115VAC is not present at X12 relay #5 (DBU), see "b) CB Diagnosis:" above. If 115VAC is present at X12 relay #5 (DBU) and not at X12 relay #3 (GY), confirm X12 relay is energized. If X12 relay is de-energized, see "c) X12 Relay Diagnosis:" above. If X12 relay is energized and 115VAC is present at X12 relay #5 (DBU) and not at X12 relay #3 (GY), replace X12 relay. If 115VAC is present at X12 #3 (GY) and DV is de-energized, check DV coil continuity, make sure the drain line is not clogged and that DV is clean and operating properly. 8) Normal Harvest Cycle – Same as the initial harvest cycle. Return to step 5a) above. Note: Appliance continues to cycle until BC is satisfied or power is switched off. The appliance always restarts at the 1-min. fill cycle 2. Shutdown Diagnosis When BC is activated (BC open), the yellow "BC OPEN" LED comes on. The icemaker then shuts down as outlined in the table below. Cycle at Bin Shutdown Control Activation Fill Cycle 15 seconds after activation. Harvest Cycle At the end of the harvest cycle, or up to 15 seconds into the freeze cycle if activated at the end of the harvest cycle. Freeze Cycle 15 seconds after activation if activated at least 15 seconds before the 5-minute short cycle protection timer terminates. Otherwise, at the end of the next harvest cycle. 3. Freeze-Time Correction Cycle Diagnosis 1) See "II.C. Freeze-Time Correction Cycle (90 min.)." Legend: BC–bin control; CB–control board; Comp–compressor; CT–control transformer; CV–cleaning valve; DV–drain valve; FMRs–fan motor remote; FS–float switch; HGVs–hot gas valves; HM–headmaster (C.P.R.); HPS–high-pressure switch; LLVs–liquid line valves; MC–magnetic contactor: MT–main transformer; PM–pump motor; TXV–thermostatic expansion valve; WV–inlet water valve 19 C. Freeze-Time Correction Cycle (90 min.) Freeze-Time Correction function is enabled when S4 Dip Switch 7 is in the "ON" position and initiates when the minimum and maximum freeze times have exceeded differential parameters. Freeze-time correction timer and count starts at the beginning of the 2nd freeze cycle after startup from power off condition. Freeze-time correction timer and count continues and retains its freeze-time correction timer and count during a BC off cycle and resumes its freeze‑time correction timer and count on the 2nd freeze cycle after BC restart. If freeze‑time differential is exceeded (see table below), freeze‑time correction cycle starts and CB red "POWER OK" LED blinks. When freeze‑time correction cycle occurs 3 or more times within a 36 hour period, CB yellow "EXT HARVEST" LED blinks with CB red "POWER OK" LED. Appliance starts in freeze cycle after a freeze‑time correction cycle. To reset CB LEDs, press ALARM RESET button on CB with power on. CB resets LEDs and appliance continues cycle without interruption. 1) Freeze Time Differential Initiation: CB starts monitoring freeze times on the second freeze time. After 3 freeze cycles (4th total), CB begins to compare minimum and maximum freeze time cycles. Every freeze cycle time after the first freeze cycle time is added to the freeze time list. Minimum and maximum freeze time differential comparisons begin on the third cycle and are monitored up to 10 cycles. On the 11th cycle the first freeze cycle time is dropped to maintain the 10 maximum number of cycles. Example: After 8 cycles (excluding first cycle), if the differential between the shortest cycle (minimum) and the longest cycle (maximum) is equal to or greater than 427 sec. a freeze-time correction cycle is initiated: Number of Freeze Cycles Differential Value in Sec. 3 4 5 6 7 8 9 10 254 309 349 380 406 427 446 462 2) Freeze-Time Correction Sequence: First occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Second occurrence within 36 hr., minimum and maximum freeze times have exceeded differential parameters. If not reset, CB "POWER OK" LED continues blinking. If reset from first occurrence, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. 20 Third occurrence within 36 hr. minimum and maximum freeze times have exceeded differential parameters. CB yellow "EXT HARVEST" LED starts blinking. Also, If not reset, CB "POWER OK" LED continues blinking. If reset, CB "POWER OK" LED starts blinking. Freeze-Time Correction Cycle starts. Total freeze-time correction cycle last for 90 min. At the end of 80 min., the final step initiates and final Harvest Pump Time (Harvest Assist) with WV (10‑min.) starts. Once the final Harvest Pump Time (Harvest Assist) with WV (10-min.) terminates (90 min. complete), normal freeze cycle begins. 2a) 10-Min. Harvest Pump Time (Harvest Assist) with WV: CB "POWER OK" LED blinking. CB LEDs 1, 4, 3, and 2 are on and Comp, FMRs, HGVs, PM, and WV energize. 10-min. timer starts. Once 10‑min. timer terminates, CB LEDs 1, 3, and 2 turn off and Comp, FMRs, HGVs, and PM de-energize. WV continues. 2b) 10-Min. Fill: CB LED 4 on and WV energized. 10-min. timer starts. 2c) Final 10-Min. Harvest Pump Time (Harvest Assist) with WV: CB "POWER OK" LED blinking. Once 10‑min. timer terminates, CB LEDs 1, 4, 3, and 2 are on and Comp, FMRs, HGVs, and PM energizes. WV continues. 10-min. timer starts. Once 10-min. timer terminates, normal freeze cycle begins. CB LED 1 on and Comp, FMRs, and PM continue. HGVs and WV de-energize. Note: After 3rd Freeze-Time Correction Cycle in 36 hours, CB signals with blinking CB yellow "EXT HARVEST" LED. Appliance continues normal operation. CB "POWER OK" LED and CB yellow "EXT HARVEST" LED continue blinking in normal operation sequence. 3) Appliance Cycle Reset and CB Alarm Reset: Cycle Reset: Power supply or control switch turned off and on again: Appliance turns off, then restarts at 1-min. fill cycle. Alarm Reset: CB "ALARM RESET" pressed during or after a freeze-time correction cycle with power supply on: Appliance continues cycle with no interruption or reset. CB red "POWER OK" LED blinking: CB red "POWER OK" LED resets to solid. CB yellow "EXT HARVEST" LED blinking: CB yellow "EXT HARVEST: LED turns off. Legend: BC–bin control; CB–control board; Comp–compressor; CT–control transformer; CV–cleaning valve; DV–drain valve; FMRs–fan motor remote; FS–float switch; HGVs–hot gas valves; HM–headmaster (C.P.R.); HPS–high-pressure switch; LLVs–liquid line valves; MC–magnetic contactor: PM–pump motor; TXV–thermostatic expansion valve; WV–inlet water valve 21 D. Control Board Check Before replacing CB that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis. Alarm Reset: If CB is in alarm (beeping), press the "ALARM RESET" button on CB while CB is beeping. WARNING! Risk of electric shock. Care should be taken not to touch live terminals. Once reset, the icemaker starts at the 1-minute fill cycle. For audible alarm information, see "III.B. LED Lights and Audible Alarm Safeties." 1) Check the dip switch settings to assure that S4 dip switch 3, 4, 6, 7, 8, 9, 10 and S5 dip switch 1 through 5 are in the factory default position. S4 dip switch 1, 2, and 5 are cleaning adjustments and the settings are flexible. For factory default settings, see "III.C.1. Default Dip Switch Settings." 2) Move the control switch to the "ICE" position. If the red "POWER OK" LED is on, control voltage is good, continue to step 3. If the "POWER OK" LED is off, check CT secondary circuit. CT output is 10.5VAC at 115VAC primary input. If the secondary circuit has proper voltage and the red LED is off, replace CB. If the secondary circuit does not have proper voltage (10.5VAC), check CT primary circuit. Check for 115VAC at control switch terminal #1 (BR) and control switch terminal #2 (BK) to neutral (W). If 115VAC is present at control switch terminal #1 (BR) and not at control switch terminal #2 (BK), replace control switch. If 115VAC is present at control switch terminal #2 (BK), check CT coil continuity. Replace as needed. For additional checks, see "II.I.1. No Ice Production." 3) The "OUTPUT TEST" button provides a relay sequence test. Make sure the control switch is in the "ICE" position, then press the "OUTPUT TEST" button. For the correct lighting sequence, see the table below. Note that the order of the LEDs from the outer edge of the control board is 1, 4, 3, 2. Components (e.g., compressor) cycle during the test. Control Correct LED Board Lighting Sequence 1, 4, 3, 2 Following the test, the appliance begins operation at the 1-minute fill cycle for both. If the LEDs do not light as described above, replace CB. 22 4) To verify voltage output from CB to the components, slide the CB K1 connector out far enough to allow multimeter lead contact. With the icemaker in the cycle to be tested, check output voltage from the corresponding pin on CB K1 connector to a neutral (W). If output voltage is not found and the appropriate LED is on, replace CB. 5) Check CB control connectors K3, K4, and K5 for correct VDC per table below. Note: Pin #1 is DC ground (GND) on each connector. Legend: CB–control board; CT–control transformer K3 Thermistor K4 Bin Control K5 Float Switch VDC Pin # VDC Pin # VDC #1 to #2 5VDC #1 to #2 5VDC #1 to #2 1.2VDC #1 to #3 5VDC #1 to #3 5VDC #1 to #3 2VDC #2ALARM to #3 RESET 0VDC #2 to #3 0VDC #2 to #3 1.2VDC S3 3 1 Thermistor 1 2 3 4 5 K5 S5 1 ON BLACK 3 Float Switch 9 8 7 6 ALP X3 LED 4 C 5 4 3 X2 LED 3 2 1 K1 POWER OK RED 3 K4 1 Bin Control LED 2 K6 P/N 2A3792-01 K7 K3 BC OPEN BC CLOSED ON CB WHITE S4 OUTPUT TEST 1 2 3 4 5 6 7 8 9 10 S2 Pin # 10 X4 LED 1 K2 2 3 X1 1 23 E. Bin Control Check 1. Bin Control Check This appliance uses a lever-actuated proximity switch to control the ice level in the storage bin. No adjustment is required. To check BC, follow the steps below. 1) Turn off the power supply. 2) Remove the front panel, then move the control switch to the "OFF" position. 3) Remove the control box cover. 4) Remove the base cover and clear any ice away from BC. 5) Disconnect BC connector from CB K4 connector. 6) Check for continuity across the wires of BC connector. When the actuator paddle is not engaged, BC switch is closed. If open, check that the actuator paddle is not sticking. Clean if necessary. See "II.E.2. Bin Control Cleaning." If BC switch still reads open, replace BC. BC Connector Bin Control Bracket 7) Press and hold the actuator paddle; check for continuity across the wires of BC connector. When the actuator paddle is engaged, BC switch is open. If closed, check that the actuator paddle is not restricted. Clean if necessary. See "II.E.2. Bin Control Cleaning." If BC switch still reads closed, replace BC. BC Actuator Paddle Fig. 1 8) Reconnect BC connector to CB K4 connector, then move the control switch to the "ICE" position. Turn on the power supply. 9) Check that CB green "BC CLOSED" LED is on. 10) Allow the appliance to cycle on. Press and hold the actuator paddle. CB yellow "BC OPEN" LED should turn on and the icemaker should shut down according to the chart below. If it does not, replace CB. Cycle at Bin Shutdown Control Activation Fill Cycle 15 sec. after activation. Harvest Cycle At the end of the harvest cycle, or up to 15 sec. into the freeze cycle if activated at the end of the harvest cycle. Freeze Cycle 15 sec. after activation if activated at least 15 sec. before the 5-min. short cycle protection timer terminates. Otherwise, at the end of the next harvest cycle. Legend: BC–bin control; CB–control board 24 2. Bin Control Cleaning Scale may build up on BC. Scale can cause the actuator paddle and magnet to stick. In this case, BC should be cleaned. WARNING CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the appliance is serviced. Make sure that none have fallen into the dispenser unit/storage bin. 1) Turn off the power supply. 2) Remove the front panel, then move the control switch to the "OFF" position. To Control Board K4 (red) Connector 3) Remove the top and right side panels. Remove the control box cover, then clear any ice away from BC. Bin Control 4) Disconnect BC connector from CB K4 (red) connector, then remove BC from the icemaker. Proximity Switch Actuator Paddle 5) Remove the actuator paddle from the switch mount. See Fig. 2. 6) Wipe down BC with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Rinse the parts thoroughly with clean water. 7) Reassemble BC and replace it in its correct position. Note: If the magnet was removed for cleaning, be sure to replace it in its Bin Control Proximity Switch Closed correct position. 8) Reconnect BC connector to CB K4 (red) connector. Bin Control Proximity Switch Open (bin full, icemaker off or shutting down) (calling for ice) 9) Move the control switch to the "ICE" position. 10) Replace the control box cover, right side, top, and front panels in their correct positions. Switch Mount 11) Turn on the power supply to start the automatic icemaking process. Actuator Paddle Magnet Fig. 2 25 F. Float Switch Check and Cleaning F/S is used to determine that there is sufficient water in the water tank after the 1‑minute fill cycle and after each harvest cycle. F/S is also used to determine that the appropriate volume of water has been converted into ice before switching out of the freeze cycle. No adjustment is required. 1. Float Switch Check To check F/S, follow the steps below. 1) Turn off the power supply. 2) Remove the front panel. 3) Place the control switch in the "SERVICE" position. Then place the service switch in the "DRAIN" position. 4) Replace the front panel in its correct position, then turn on the power supply for 2 minutes. 5) Turn off the power supply. 6) Remove the front panel, then move the control switch to the "OFF" position. 7) Remove the top and right side panels. 8) Remove the control box cover, then disconnect F/S connector from CB K5 (black) connector. 9) Check for continuity across F/S leads. With the water tank empty, F/S should be open. If open, continue to step 10. If closed, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning F/S, check it again. Replace if necessary. 10) Reconnect F/S connector to CB K5 (black) connector, then replace the control box cover, right side, and top panels in their correct positions. 11) Move the control switch to "ICE" position. Replace the front panel. 12) Turn on the power supply. 13) As water fills the water tank, F/S contacts should close. After 1-min., the 1-min. fill cycle should end and the initial harvest cycle should begin. 14) Once the harvest cycle starts, turn off the power supply. 15) Remove the front panel, then move the control switch to the "OFF" position. 16) Remove the top and right side panels. 17) Remove the control box cover, then disconnect F/S connector from CB K5 (black) connector. 18) Check for continuity across F/S leads. With the water tank full, F/S should be closed. If F/S is closed and the icemaker will not switch from the 1-min. fill cycle to the initial harvest cycle, replace CB. 19) If open, confirm that the water tank is full. If the water tank is not full, check the water supply, water filters, and inlet water valve. If the water tank is full, follow the steps in "II.F.2. Float Switch Cleaning." After cleaning F/S, check it again. Replace if necessary. 26 20) Reconnect F/S connector to CB K5 (black) connector, then replace the control box cover, right side, and top panels in their correct positions. 21) Move the control switch to the "ICE" position. 22) Replace the front panel in its correct position. 23) Turn on the power supply to start the automatic icemaking process. Legend: CB–control board; F/S–float switch 2. Float Switch Cleaning Depending on local water conditions, scale may build up on F/S. Scale can cause F/S to stick. In this case, F/S should be cleaned. 1) Turn off the power supply. 2) Remove the front panel. 3) Place the control switch in the "SERVICE" position. Then place the service switch in the "DRAIN" position. 4) Replace the front panel in its correct position, then turn on the power supply for 2 minutes. 5) Turn off the power supply. 6) Remove the front, top, and right side panels, then move the control switch to the "OFF" position. 7) Disconnect the vent tube and the flush tube from the top of F/S housing, then remove F/S assembly. Remove the rubber boot from the bottom of F/S assembly. See Fig. 3. 8) Remove the retainer rod from the bottom of F/S assembly, then remove the float. Be careful not to bend the retainer rod excessively when removing it. 9) Wipe down F/S assembly's housing, shaft, float, and retainer rod with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts warm water. Clean the inside of the rubber boot and hose with cleaning solution. Rinse the parts thoroughly with clean water. 10) Reassemble F/S assembly and replace it and the rubber boot in their correct positions. Reconnect the vent tube and the flush tube. Flush Tube Vent Tube 11) Replace the right side and top panels in their correct positions. Shaft 12) Move the control switch to the "ICE" position. Float Switch Housing 13) Replace the front panel in its correct position. 14) Turn on the power supply to start the automatic icemaking process. Float Retainer Rod Legend: CB–control board; F/S–float switch Rubber Boot and Hose Fig. 3 27 G. Thermistor Check To check thermistor resistance, follow the steps below. 1) Turn off the power supply. 2) Remove the front panel, then move the control switch to the "OFF" position. 3) Remove the top and right side panels, then remove the control box cover. 4) Remove the thermistor. 5) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3 minutes. 6) Disconnect the thermistor connector from CB K3 (white) connector and check resistance between thermistor leads. Normal range is 4.7 to 6.2 kΩ. If outside the normal range, replace the thermistor. See "IV.B. Component Service Information." If within the normal range, continue to next step. 7) Replace the thermistor in its correct position. See "IV.B. Component Service Information." 8) Reconnect the thermistor connector to CB K3 (white) connector. 9) Replace the control box cover, right side, and top panels in their correct positions. 10) Move the control switch to the "ICE" position. 11) Replace the front panel in its correct position. 12) Turn on the power supply. 13) Once the harvest cycle starts (Comp energizes), begin timing the harvest cycle. 14) The harvest timer and harvest cycle should terminate within 2 to 5 minutes. If the harvest cycle does not terminate within 2 to 5 minutes, replace CB. Legend: CB–control board; Comp–compressor Thermistor Lead Foam Insulation Fig. 4 28 Cable Tie Thermistor Holder H. Switches Two control switches are used to control operation. These switches are referred to as the "control switch" and the "service switch" and are located on the control box. 1. Control Switch The control switch has three positions: "OFF" for power off, "ICE" for icemaking, and "SERVICE" to activate the service switch. WARNING! Moving control switch to "OFF" position does not de-energize all components. 2. Service Switch When the control switch is in the "SERVICE" position, the control switch supplies power to the service switch and water pump. The machine is in service mode. The service switch has three positions: "DRAIN", "CIRCULATE", and "WASH." See the information below for details of each function. Note: 1. When the service switch is activated, power is supplied to the water pump in all three positions. 2. When the control switch is in the "OFF" position or in the "ICE" position, the service switch has no power and can be left in any position. a) DRAIN This appliance utilizes a pump-out drain system. When the service switch is active and placed in the "DRAIN" position, power is supplied to the drain valve. b) CIRCULATE When the service switch is active and placed in the "CIRCULATE" position, power is supplied to the pump only. This operation can be used to circulate cleaner for extended periods of time over the outside surface of the evaporator. c) WASH This appliance utilizes a solenoid operated wash (bypass) valve. When the service switch is active and placed in the "WASH" position, power is supplied to the water pump and the wash valve. This operation is used to circulate cleaner and sanitizer over both the inside and outside of the evaporator. 29 I. Diagnostic Tables Before consulting the diagnostic tables, check for correct installation, proper voltage per nameplate, and adequate water pressure (10 to 113 PSIG). Check control board using the steps in "II.D. Control Board Check." 1. No Ice Production No Ice Production - Possible Cause 1. Power Supply a) Off, blown fuse, or tripped breaker. b) Not within specifications. 2. Main Transformer (3 phase SRK) (208-230VAC/115VAC) a) Voltage tap switch not set to proper voltage. 3. Water Supply a) Water supply off or improper water pressure. b) No neutral. White (W) wire to ground 0VAC. (White (W) wire to ground should be 60VAC). b) External water filters clogged. 4. Fuse (SRK Control Box) a) Blown. 5. High-Pressure Switch (SRK) a) Dirty condenser. b) Condensing unit fan(s) not operating. c) Headmaster (C.P.R.) open. d) Refrigerant overcharged. e) Bad contacts. f) Refrigerant lines or components plugged. 6. Discharge Line Thermostat (SRK) a) Ambient temperature too warm. b) Compressor or compressor components faulty. c) Defective. d) Hot gas valves open. e) Dirty condenser. f) Condensing unit fan(s) not operating. 7. Wire Harness (From SRK to KMS) a) Disconnected or loose connection. 8. Fuse (KMS Control Box) a) Blown. 9. Control Switch a) In "SERVICE" or "OFF" position. b) Bad contacts. 10. Control Transformer (115VAC/10.5VAC) a) Coil winding open or shorted. 11. Bin Control See "II.E. Bin Control Check" a) Tripped with bin filled with ice. b) Ambient temperature too cool. c) Bulb out of position. d) Set too warm. e) Defective. 12. Control Board See "II.D. Control Board Check" a) In alarm. b) Yellow "BC OPEN" LED on (jumper loose or missing). c) Defective. 13. Inlet Water Valve a) Screen or orifice clogged. b) Coil winding open. c) Water valve open in freeze cycle. 30 No Ice Production - Possible Cause - continued 14. Float Switch a) Float does not move freely. See "II.F. Float Switch Check and b) Defective. Cleaning" 15. Compressor a) Magnetic contactor contacts bad or coil winding open. b) Start capacitor or run capacitor defective (1 phase SRK). c) Start relay contacts bad or coil winding open (1 phase SRK). d) Internal protector open. e) Compressor defective. 16. Hot Gas Valves (KMS & SRK) a) Closed in harvest cycle. b) Open in freeze cycle. 17. Thermistor See "II.G. Thermistor Check" a) Loose, disconnected, or defective. 18. Pump Motor a) Motor winding open. b) Bearing worn out or locked rotor. c) Defective capacitor. 19. Thermostatic Expansion Valve a) Bulb loose. b) Operating erratically. 20. Liquid Line Valves (KMS & SRK) a) Closed in freeze cycle. b) Open in harvest cycle. 21. Fan Motors-Remote a) Motor winding open. b) Bearing worn out or locked rotor. c) Defective capacitor. 22. Headmaster a) Defective. 23. Water System a) Water leaks causing short freeze time. 31 2. Freeze-Up Defrost and clean the icemaker prior to diagnosing freeze-up. Fill out a freeze-up checklist. See "II.J. Freeze Up Check List," the Hoshizaki America Technician's Pocket Guide, or contact your local distributor for a copy of the freeze-up checklist. Freeze-Up - Possible Cause Harvest Cycle 1. Evaporator a) Scaled up. b) Damaged. 2. Cube Guides a) Out of position. b) Damaged. 3. Spray Tubes and/or Spray Guides or Splash Curtain a) Dirty. 4. Water Supply a) Low water pressure. b) Out of position. b) External water filters clogged. c) Insufficient water line size. Minimum 3/8" nominal ID copper water tubing or equivalent. 5. Inlet Water Valve a) Defective. 6. Float Switch a) Float does not move freely. See "II.F. Float Switch Check and b) Defective. Cleaning" 7. Refrigerant Charge a) Low. 8. Control Board See "III. Controls and Adjustments" and "II.D. Control Board Check" a) Harvest timer (S4 dip switch 1 & 2) set too short. 9. Bin Control See "II.E. Bin Control Check" a) Bulb out of position. b) Harvest pump timer (S4 dip switch 7) not in factory default position. c) Defective. b) Defective. 10. Thermistor See "II.G. Thermistor Check" a) Loose, disconnected, or defective. 11. Thermostatic Expansion Valve a) Defective. 12. Hot Gas Valves (KMS & SRK) a) Closed or restricted. 13. Liquid Line Valves (KMS & SRK) a) Open. Freeze Cycle 1. Evaporator a) Scaled up. b) Damaged. 2. Spray Tubes, Spray Guides, and a) Dirty. Splash Guard or Splash Curtain b) Out of position. 3. Refrigerant Charge a) Low. 4. Control Board See "II.D. Control Board Check" a) Freeze timer (S4 dip switch 9 & 10) set incorrectly. 5. Inlet Water Valve a) Leaking by. b) Defective. 6. Float Switch a) Float does not move freely. See "II.F. Float Switch Check and b) Defective. Cleaning" 7. Pump Motor a) RPM too slow. b) Impeller damaged. 32 Freeze-Up - Possible Cause 8. Thermostatic Expansion Valve a) Bulb loose or defective. 9. Headmaster a) Defective. 10. Liquid Line Valves (KMS & SRK) a) Restricted. 3. Low Ice Production Low Ice Production - Possible Cause Long Harvest Cycle 1. Evaporator a) Scaled up. 2. Spray Tubes and/or Spray Guides or Splash Curtain a) Dirty. 3. Refrigerant Charge a) Low. 4. Water Supply a) Low water pressure. b) Out of position. b) External water filters clogged. c) Insufficient water line size. Minimum 3/8" nominal ID copper water tubing or equivalent. d) Too cold. 5. Control Board See "II.D. Control Board Check" a) Thermistor connection loose (K3). 6. Thermistor See "II.G. Thermistor Check" a) Loose, disconnected, or defective. 7. Hot Gas Valves (KMS & SRK) a) Erratic or closed. 8. Inlet Water Valve a) Screen or orifice clogged. 9. Compressor a) Inefficient or off. b) Defective. 10. Liquid Line Valves (KMS & SRK) a) Erratic or open. 11. Thermostatic Expansion Valve (TXV) a) Defective. 12. Headmaster (C.P.R.) a) Defective. Long Freeze Cycle 1. Evaporator a) Scaled up, dirty. 2. Float Switch a) Scaled up, dirty. See "II.F. Float Switch Check and b) Float sticking. Cleaning" c) Defective switch. 3. Inlet Water Valve a) Leaking by. 4. Hot Gas Valves (KMS & SRK) a) Erratic or open. 5. Condenser a) Clogged. 6. Control Board See "II.D. Control Board Check" a) Float switch connection loose (K5). 7. Refrigerant Charge a) Low. 8. Thermostatic Expansion Valve (TXV) a) Bulb loose. 9. Compressor a) Inefficient or off. 10. Pump Motor b) Defective. b) Defective. a) RPM too slow. 11. Liquid Line Valves (KMS & SRK) a) Erratic or restricted. 12. Headmaster (C.P.R.) a) Defective. 33 J. Freeze-Up Check List Freeze-Up Check List Please Complete When Diagnosing a Freeze-Up, Refrigerant Leak, or Low Charge Technical Support Fax #: 770-487-3360 Make Copies And Use As Needed Model #___________________________ Serial # _________________________Install Date______________Fail Date___________ List model and manufacture of bin or dispenser__________________________. Date appliance was last cleaned:__________. Appliance Operation Freeze-Up Defrost YES NO [ ] [ ] 1) After defrosting, was the appliance leak checked? [ ] [ ] 2) Were any leaks found? If so where?_____________________. [ ] [ ] 3) Was any refrigerant added to the unit? If so, how much?_________________. Set Up [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] Fill YES NO [ ] [ ] 4) Is the appliance stacked? 5) Is water line independent? 6) Is water line correct size? If not________”. 3/8" Nominal ID Copper Water Tubing or Equivalent. 7) What is water pressure?___________. Water Temperature_________. 8) Does appliance have any water filtration? If yes please list the following: Filter brand___________________. Model________________. Filter pressure gauge reading during the fill cycle___________. Date filter was last replaced?__________________________. GPM or LPM flow rate of filter system?__________________. 9) Ambient temperature at appliance? ______________. At remote condenser (if applicable)?________. Appliance Status [ ] [ ] 10) Is the appliance and/or float switch dirty? 11) List the S4 (1-10) and S5 (1-5) DIP switch settings. S4: 1___2___3___4___5___6___7___8___9___10____ S5: 1_____2_____3_____4_____5______ [ ] [ ] 12) Is DIP switch number 7 ON (harvest pump time (harvest assist) all models and freeze-time correction models with control board 2A7664-02? [ ] [ ] 13) Is the cube guide positioned correctly? [ ] [ ] 14) Are the evaporator separators positioned properly? [ ] [ ] 15) Is the thermistor properly mounted, tight, and insulated? [ ] [ ] 16) Is the TXV bulb properly mounted, tight, and insulated? [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] [ ] 17) Does the water tank fill and overflow? 60-90 sec. Note: Larger models may take up to 120 seconds to overflow when empty. 18) If NO in step 17, is water flow 5GPM for larger? 19) Does the appliance utilize re-fill (S5 dip switch 2 and 3)? Harvest 20) Is the hot gas valve opening? 21) Is harvest pump time (harvest assist) utilized (S4dip switch 7)? 22) Is hot gas valve opening in harvest? 23) Does water valve close completely when deenergized? 24) What was length of harvest?___________. Freeze 25) Is pump motor energized in freeze cycle except during 10-sec. anti-slush. If activated (S5 dip switch 5 on)? 26) Water-cooled condenser outlet temperature 5-min. into freeze? ______________°F. 27) What was length of freeze?____________. 28) Is the cube size consistent from inlet to outlet of evaporator? 29) Is ice still dropping when next freeze cycle starts? 30) What is the ice drop weight?___________. 31) What is head pressure? Freeze_________Harvest_______. (Freeze pressure should be taken 5 minutes into the cycle). 32) What is suction pressure? Freeze______Harvest_______. (Freeze pressure should be taken 5 minutes into the cycle). 33) When activating bin control, did appliance shutdown within 15 seconds in the first 5 minutes of freeze cycle? Freeze-Time Correction Operation [ ] [ ] 34) Has Freeze-Time Correction been activated? ("POWER OK" LED blinking). [ ] [ ] 35) Has more than 1 Freeze-Time Correction been activated? (POWER OK" LED and "EXT HARVEST" LED blinking). Note: Make copies of this form and use it when diagnosing a freeze up condition. Submit a completed copy of the checklist along with the freeze-up labor claim form. 1 34 III. Controls and Adjustments • A Hoshizaki exclusive control board is employed in the KMS-2000MLJ series. • All models are pretested and factory adjusted. • For a control board check procedure, see "II.D. Control Board Check." NOTICE • Fragile, handle very carefully. • The control board contains integrated circuits, which are susceptible to failure due to static discharge. It is especially important to touch the metal part of the icemaker when handling or replacing the control board. • Do not touch the electronic devices on the control board or the back of the control board. • Do not change wiring and connections. Do not misconnect terminals. • Do not short out power supply to test for voltage. • Always replace the whole control board assembly if it goes bad. 35 A. Control Board Layout Control Board • Bin Control Switch Closed LED (green) • "ALARM RESET" Button • S4 Dip Switch • K3 (white) Connector Thermistor (harvest control and high temperature safety) • Bin Control Switch Open LED (yellow) • Alarm Buzzer • K4 (red) Connector Bin Control • S5 Dip Switch • Ext. Harvest LED (yellow) (blinks when 3rd occurrence of freeze time correction initiates within 36 hr.) • K5 (black) Connector Float Switch (water level) • POWER OK LED (red) (lights when 10.5VAC is supplied to K2 connector) • Part Number • K1 Connector Pins #1 through #10 #1, 9 Magnetic Contactor #2 Hot Gas Valve, X10, X12 Relay #3 Liquid Line Valves #4 Pump Motor #5 Pump Motor (harvest pump timer and pump-out), DV (in pump-out) #6 Inlet Water Valve, X11 Relay #7, 10 Component Power Supply #8 Open • Relay LEDs (4) (indicate which relays are energized and which K1 connector pins are energized • LED 2 (X2 Relay) LED 2 on: K1 Connector Pin #2 LED 2 off: K1 Connector Pin #3 • LED 3 (X3 Relay) LED 3 on: K1 Connector Pin #5 LED 3 off: K1 Connector Pin #4 (energized in freeze) • LED 4 (X4 Relay) K1 Connector Pin #6 • LED 1 (X1 Relay) K1 Connector Pin #1, #9 • "OUTPUT TEST" Button (used to test relays on control board) • K2 Connector Control Transformer (10.5VAC) Control Board Part Number 2A7664-04 36 B. LED Lights and Audible Alarm Safeties Beep occurs and red CB "POWER OK" LED turns on when control switch is moved to "ICE" position. Sequence Green LEDs 1 through 4 turn on and sequence from initial startup as listed in the table below. Order of green LEDs from the outer edge of control board is 1, 4, 3, 2. Sequence Step Energized Components LED Time LEDs are On Min. Max. 1-Minute Fill Cycle Harvest Cycle Harvest Pump Time (harvest assist) Freeze Cycle 4 1, 4, 2 1, 3, 2 WV Comp, FM*, FMRs, HGVs, WV Comp, FM*, FMRs, HGVs, PM 1 minute 20 minutes 0 seconds 50 seconds 1 Comp, FM/FMRs, PM, LLVs 5 minutes Anti-Slush Control 1, 3 Comp, FM/FMRs, LLVs Pump-Out Cycle 1, 4†, 3, 2 Comp, FM*, FMRs, HGVs, PM, WV †, DV *FM energized if on K1 Connector Pin #9; †pump-out timer setting freeze timer setting If S5 dip switch 5 on, PM off 10 sec. when thermistor at 36°F (2.2°C) 10 seconds 20 seconds Alarms Type 1 Beep 2 Beep Alarm High Evaporator Temp. (temperature > 127°F) (53°C) Harvest Backup Timer (harvest > 20 min. for two cycles in a row) Freeze Timer (freeze > freeze timer setting for two cycles in a row) Freeze-Time Correction (maximum freeze time differential exceeded) Notes Check for harvest problem (stuck HGV or relay), hot water entering unit, stuck HM, or shorted thermistor. Check thermistor (open), HGV not opening, TXV or LLV leaking by, low charge, inefficient Comp, or WRV leaking by. 3 Check FS stuck closed (up), WV leaking by, HGV leaking Beep by, PM not pumping, TXV defective, LLV not opening, low charge, HM not bypassing, or inefficient Comp. LED Blink Red POWER OK LED blinks. After 3 freeze‑time correction cycles in 36 hours, yellow EXT HARVEST LED also blinks. Fill out freeze-up checklist. See "II.J. Freeze-Up Check List." To reset above safeties, press "ALARM RESET" button with power supply on. 6 Low Voltage Red POWER OK LED turns off if voltage protection (92Vac±5% or less) operates. Control voltage safeties automatically reset when voltage 7 High Voltage is corrected. (147Vac±5% or more) Legend: Comp–compressor; FM–fan motor; FMR–fan motor remote; FS–float switch; HGVs–hot gas valves; HM–headmaster (C.P.R.); LLVs–liquid line valves; PM–pump motor; TXV–thermostatic expansion valve; WRV–water regulating valve; WV–inlet water valve Test To perform output test, move control switch to "ICE" position. Press "OUTPUT TEST" button. Correct green LED lighting sequence is 1, 4, 3, 2. Components (e.g., compressor) cycle during test. Following test, appliance resumes operation. Dip switches must be adjusted per unit’s service manual or Hoshizaki Technical Support recommendation. S4 dip switch 8 must remain off. 37 C. Settings and Adjustments NOTICE Dip switches are factory set. Failure to maintain factory settings may adversely affect performance and warranty coverage. For more information, contact Hoshizaki Technical Support at 1-800-233-1940. 1. Default Dip Switch Settings The dip switches are factory-adjusted to the following positions: S4 Dip Switch Dip Switch No. KMS-2000MLJ 1 2 3 4 5 6 7 8 9 10 OFF OFF OFF OFF OFF OFF ON OFF OFF OFF S5 Dip Switch (Do Not Adjust) Dip Switch No. KMS-2000MLJ 1 2 3 4 5 OFF OFF OFF OFF OFF S4 Dip Switch Factory Use (8) Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (7) (Do Not Adjust) Harvest Pump Time (Harvest Assist Duration) (6) (Do Not Adjust) Pump-Out Frequency Control (5) Pump-Out Time/Harvest Time During Pump-Out (3 & 4) Harvest Timer (1 & 2) S5 Dip Switch 1 2 3 4 5 Do Not Adjust ON 1 2 3 4 5 6 7 8 9 10 ON Freeze Timer (9 & 10) Anti-Slush (5) Minimum Harvest Time (4) Refill Counter (2 and 3) Float Switch Selector (1) 38 2. Harvest Timer (S4 dip switch 1 & 2) The harvest timer starts counting when the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest timer is factory set, and generally no adjustment is required. However, a setting longer than the factory setting may be advised in cases where the drain provided at harvest needs to be prolonged for extra cleaning. Before changing this setting, contact Hoshizaki Technical Support at 1‑800‑233-1940 for recommendations. Keep in mind that setting the harvest timer to a longer setting decreases 24-hour production. Note that the pump-out timer (S4 dip switch 3 & 4) acts in place of the harvest timer during cycles with a pump out. For details, see "III.C.3. Pump-Out Timer/Harvest Time During Pump-Out (S4 dip switch 3 & 4)." Note: On models with a pump-out every cycle, the harvest timer is only relevant during the initial harvest cycle since a pump out occurs every cycle thereafter. S4 Dip Switch Setting No. 1 No. 2 Time (sec.) OFF OFF 60 ON OFF 90 OFF ON 120 ON ON 180 3. Pump-Out Timer/Harvest Time During Pump-Out (S4 dip switch 3 & 4) NOTICE On models with harvest pump timer, do not adjust 3 off and 4 on. Pump does not run in pump-out rotation in this setting. When a pump-out is called for, the pump motor stops for 2 sec. After 2 sec. the drain valve and pump motor energize. Water is removed from the bottom of the water tank and sent down the drain. The pump‑out drains the water tank for the time determined by the pump‑out timer. The pump‑out timer also acts in place of the harvest timer during cycles with a pump‑out. The pump-out timer is factory set, and generally no adjustment is required. However, where water quality is bad and the icemaker needs a longer pump‑out time, the pump‑out timer can be adjusted. The pump‑out timer control can be set to pump-out for 10 or 20 sec. S4 Dip Switch Setting Time (sec.) T1 No. 3 No. 4 OFF OFF ON Inlet Water Valve T2 S5-4 OFF S5-4 ON S5-4 OFF S5-4 ON 10 150 100 Closed Closed OFF 10 180 130 Closed Closed OFF ON 10 120 70 Open Closed ON ON 20 180 180 Closed Closed T1: Time to drain the water tank T2: Harvest timer at pump out 39 4. Pump-Out Frequency Control (S4 dip switch 5) The pump-out frequency control is factory set to drain the water tank every 10 cycles. Generally no adjustment is required. However, where water quality is bad and the icemaker needs a pump-out more often, the pump‑out frequency can be adjusted. The pump-out frequency control can be set to have a pump‑out occur every cycle, or every 10 cycles. The first pump-out is dependent on S4 dip switch 5. See the table below. S4 Dip Switch Setting Pump-Out Frequency 1st Pump-Out OFF Every 10 cycles After 11th freeze cycle ON Every cycle After 2nd freeze cycle No. 5 5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6) NOTICE Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance. Harvest pump time (harvest assist duration) is only active when S4 dip switch 7 is in the "ON" position. In the factory default position, the harvest pump time (harvest assist duration) starts with 50 sec. left to go in harvest cycle (S4 dip switch 6) and after the thermistor reaches 48°F (9°C) at the evaporator outlet and the control board reads 3.9 kΩ from the thermistor. The harvest pump time (harvest assist duration) is factory set, and no adjustment is required. S4 Dip Switch Setting Harvest Pump Time (Harvest Assist Duration) No. 6 S5-4 OFF S5-4 ON OFF 50 sec. 25 sec. ON 25 sec. 15 sec. 40 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7) NOTICE Factory set for proper operation. Do not adjust. Adjustment outside of the factory default setting may result in damage to the appliance. a) Harvest Pump Time (Harvest Assist) Depending on S4 dip switch 7 setting, the pump motor either stays off or is energized during the last seconds of the harvest cycle. When the pump motor is energized (S4 dip switch 7 on), water circulates over the evaporator. The harvest water valve is open during harvest for a maximum of 6 minutes or the length of harvest minus the harvest pump time value (S4 dip switch 6), whichever is shorter. When S4 dip switch 7 is in the on position and harvest begins, X11 and X10 relays energize. A latching circuit is created through the X11 and X10 relays. For further details, see "VIII.B. Wiring Diagram." In the factory default position, 50 sec. before harvest termination, LED 4 turns off, inlet water valve and X11 relay de‑energize. X10 relay remains energized through the latching circuit. Next, LED 3 turns on and control board K1 connector pin #5 (DBU wire) energizes, energizing the pump motor for the last seconds of harvest. Harvest pump time adjusted by S4 dip switch 1 & 2 and S5 dip switch 4 settings. Contact Technical Support before adjusted these settings. b) Freeze-Time Correction When S4 dip switch 7 is in the on position, freeze-time correction enabled. See "II.C. Freeze-Time Correction Cycle (90 min.)." S4 Dip Switch Setting Harvest Pump Time (Harvest Assist) No. 7 Freeze-Time Correction OFF Disabled ON Enabled 41 7. Factory Use (S4 dip switch 8) Factory set for proper operation. Do not adjust. This must be left in the factory default position. 8. Freeze Timer (S4 dip switch 9 & 10) NOTICE Adjust to proper specification, or the icemaker may not operate correctly. The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of the freeze timer, the control board initiates the harvest cycle or pump-out cycle. After 2 consecutive freeze timer terminations, the control board shuts down the icemaker. In this case, see "II.I.3. Low Ice Production" for possible solutions. The freeze timer is factory set and no adjustment is required. Before changing this setting, contact Hoshizaki Technical Support at 1‑800‑233-1940 for recommendations. S4 Dip Switch Setting No. 9 No. 10 Time (min.) OFF OFF 60 OFF ON 50 ON OFF 70 ON ON 75 9. Float Switch Control Selector (S5 dip switch 1) NOTICE Do not adjust. This must be left in the factory default position or the icemaker will not operate correctly. This dip switch setting allows use of this control board in single and dual float switch models. This model uses a single float switch style. S5 Dip Switch Setting Upper or Lower Float Switch No. 1 Control OFF Lower Float Switch Enabled ON Upper Float Switch Enabled 42 10. Refill Counter (S5 dip switch 2 and 3) NOTICE Do not adjust. These must be left in the factory default position or the icemaker will not operate correctly. S5 Dip Switch Setting Refill Counter No. 2 No. 3 OFF OFF 0 OFF ON 1 refill ON OFF 9 refills ON ON 10 refills 11. Minimum Harvest Time (S5 dip switch 4) NOTICE Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance. S5 Dip Switch Setting No. 4 Minimum Harvest Timer OFF 120 sec. ON 70 sec. 12. Anti-Slush (S5 dip switch 5) NOTICE Factory set for proper operation. Do not adjust. Adjustment outside the factory default setting may result in damage to the appliance. This dip switch setting provides anti-slush control during the freeze cycle. When the evaporator temperature reaches 36°F (2.2°C) the control board reads a 5.8 kΩ signal from the thermistor and de-energizes the water pump for 10 sec. to melt ice slush and prevent ice slush from blocking the water supply tubing, causing irregular freeze patterns. S5 Dip Switch Setting No. 5 Anti-Slush OFF Disabled ON Enabled 43 IV. Refrigeration Circuit and Component Service Information WARNING • This appliance should be diagnosed and repaired only by qualified service personnel to reduce the risk of death, electric shock, serious injury, or fire. • Before servicing the KMS or SRK: Move the KMS control switch to the "OFF" position and turn off the power supply to the SRK condensing unit. Place the KMS disconnect (if applicable) in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently. • CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after the icemaker is serviced. Make sure that none have fallen into the dispenser unit/ice storage bin. • Make sure all food zones in the icemaker and dispenser unit/ice storage bin are clean after service. A. Refrigeration Circuit Service Information WARNING • Repairs requiring the refrigeration circuit to be opened must be performed by properly trained and EPA-certified service personnel. • Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R‑404A as a mixture with pressurized air for leak testing. NOTICE • Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere. • Do not leave the system open for longer than 15 min. when replacing or servicing parts. The Polyol Ester (POE) oils used in R-404A applications can absorb moisture quickly. Therefore it is important to prevent moisture from entering the system when replacing or servicing parts. • Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant flow. • When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C). 1. Refrigerant Recovery The condensing unit and icemaker are provided with refrigerant shutoff valves. Using proper refrigerant practices, recover the refrigerant. Recovery via the condensing unit's refrigerant shutoff valves is recommended. Store the refrigerant in an approved container. Do not discharge the refrigerant into the atmosphere. 44 2. Brazing WARNING • R-404A itself is not flammable at atmospheric pressure and temperatures up to 176°F (80°C). • R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open flames), R-404A can be decomposed to form hydrofluoric acid and carbonyl fluoride both of which are hazardous. • Do not use silver alloy or copper alloy containing arsenic. 1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG. Note: Because the pipes in the evaporator case are specially coated to resist corrosion, it is important to make connections outside the evaporator case when possible. If it is necessary to braze inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components. NOTICE • Always install a new drier every time the sealed refrigeration system is opened. • Do not replace the drier until after all other repair or replacement has been made. Install the new drier with the arrow on the drier in the direction of the refrigerant flow. • When brazing, protect the drier by using a wet cloth to prevent the drier from overheating. Do not allow the drier to exceed 250°F (121°C). 2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of refrigerant to the system (if using an electronic leak detector), and then raise the pressure using nitrogen gas (140 PSIG). Do not use R-404A as a mixture with pressurized air for leak testing. 3. Evacuation and Recharge (R-404A) The condensing unit and icemaker are provided with refrigerant shutoff valves. Evacuation and recharge via the condensing unit's refrigerant shutoff valves is recommended. 1) Attach a vacuum pump to the system. Be sure to connect the charging hoses to both high and low-side refrigerant shutoff valves. IMPORTANT The vacuum level and vacuum pump may be the same as those for current refrigerants. However, the rubber hose and gauge manifold to be used for evacuation and refrigerant charge should be exclusively for POE oils. 2) Turn on the vacuum pump. Open the gauge manifold valves, then open the high and low-side refrigerant shutoff valves. Never allow the oil in the vacuum pump to flow backwards. 45 3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends on pump capacity. 4) Close the low-side valve and high-side valve on the gauge manifold. 5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a refrigerant service cylinder. Remember to loosen the connection and purge the air from the hose. For the required refrigerant charge, see the nameplate on the condensing unit or the rating label inside the icemaker. Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI Standard 700 (latest edition) be used. 6) A liquid charge is required when charging an R-404A system (to prevent fractionation). Place the service cylinder on the scales; if the service cylinder is not equipped with a dip tube, invert the service cylinder, then place it on the scales. Open the high-side valve on the gauge manifold. 7) Allow the system to charge with liquid until the proper charge weight is met. 8) If necessary, add any remaining charge to the system through the low-side. NOTICE! To prevent compressor damage, use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side shutoff valve with the icemaker running. 9) Close the high and low-side shutoff valves. Close the high and low-side gauge manifold valves, then disconnect the gauge manifold hoses. 10) Cap the shutoff valves to prevent a possible leak. 46 B. Component Service Information NOTICE When replacing a component listed below, see the notes to help ensure proper operation. Component Notes Compressor 1 Phase SRK: Install a new start capacitor, run capacitor, and start relay. 3 Phase SRK: Install a new magnetic contactor. Thermostatic Expansion Valves • Attach the thermostatic expansion valve bulb to the suction line in the same location as the previous bulb. • The bulb should be between the 10 and 2 o'clock positions on the tube. • Secure the bulb with the clamp and holder, then insulate it. Hot Gas Valves Liquid Line Valves • Replace the strainer if applicable. • Use copper tube of the same diameter and length when replacing valve lines. Fan Motors Install a new capacitor. Pump Motor Install a new capacitor. 47 V. Maintenance The maintenance schedule below is a guideline. More frequent maintenance may be required depending on water quality, the appliance's environment, and local sanitation regulations WARNING • Only qualified service technicians should service the appliance. • To reduce the risk of electric shock, do not touch the control switch or service switch with damp hands • Before servicing the KMS or SRK: Move the KMS control switch to the "OFF" position and turn off the power supply to the SRK condensing unit. Place the KMS disconnect (if applicable) in the "OFF" position. Lockout/Tagout to prevent the power supply from being turned back on inadvertently. • CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are securely in place after any maintenance is done to the icemaker. Make sure that none have fallen into the dispenser unit/ice storage bin. Maintenance Schedule Frequency Area Task Daily Scoop Monthly Clean the ice scoop using a neutral cleaner. Rinse thoroughly after cleaning. Check for proper pressure and change if necessary. External Water Filters Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a neutral cleaner to wipe off oil or dirt build up. Clean any chlorine staining (rust colored spots) using a non-abrasive cleanser. Icemaker and Clean and sanitize per the cleaning and sanitizing instructions provided Dispenser Unit/Ice in the instruction manual or maintenance label on the icemaker. Storage Bin Liner Water Supply Inlet Close the icemaker water supply line shut‑off valve and drain the water system. Clean the water supply inlet screen. Condenser Inspect. Clean if necessary by using a brush or vacuum cleaner. More frequent cleaning may be required depending on location. Water Hoses Inspect the water hoses and clean/replace if necessary. Yearly 48 VI. Preparing the Appliance for Periods of Non-Use NOTICE • When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below to prevent damage. • To prevent damage to the water pump, do not operate the appliance with the control switch in the "SERVICE" position when the water tank is empty. When the appliance is not used for two or three days under normal conditions, it is sufficient to move the control switch to the "OFF" position. When storing the appliance for an extended time or in sub-freezing temperatures, follow the instructions below. 1. Remove the water from the icemaker water lines: 1) Turn off the power supply, then remove the front panel, right side panel, and control box cover. 2) Move the control switch to the "OFF" position. Confirm the service switch is in the "CIRC" position. 3) Close the icemaker water supply line shut-off valve and open the icemaker water supply line drain valve. Allow the line to drain by gravity. 4) Attach a compressed air or carbon dioxide supply to the icemaker water supply line drain valve. 5) Turn on the power supply, then move the control switch to the "ICE" position. Confirm that the bin control switch is closed and calling for ice. The "POWER OK" LED should be on and not flashing. 6) Blow the icemaker water supply line out using the compressed air or carbon dioxide supply. This will clear water from the inlet water valve. 7) Move the control switch to the "OFF" position. 8) Disconnect the wash valve hose from the inlet water valve tee, then unplug the water pump connector at the water pump. See Fig. 5. 9) Move the service switch to the "WASH" position, then move the control switch to the "SERVICE" position. 10) From the wash valve hose, blow out the wash valve using the compressed air or carbon dioxide supply. Reconnect the wash valve hose. 11) Move the service switch to the "CIRC" position, then move the control switch to the "OFF" position. 12) Disconnect the float switch vent hose from the drain hose tee. Move the service switch to the "DRAIN" position, then move the control switch to the "SERVICE" position. 13) From the drain hose tee, blow out the drain valve using the compressed air or carbon dioxide supply. Reconnect the float switch vent hose. 14) Move the service switch to the "CIRC" position, then move the control switch to the "OFF" position. 15) Turn off the power supply, then reconnect the water pump connector. 16) Close the icemaker water supply line drain valve. 49 2. Remove the water from the water tank: 17) Remove the insulation panel and front frame. 18) Disconnect the hoses connected to the water tank. Allow the tank and hoses to drain completely. See Fig. 6. 19) Remove all ice from the dispenser unit/storage bin and clean the dispenser unit/storage bin liner using a neutral cleaner. Rinse thoroughly after cleaning. 20) Reconnect the hoses to the water tank. 21) Replace all removed parts and panels in their correct positions. Front View Inlet Water Valve Tee Wash Valve Hose Inlet Water Valve Wash Valve Float Switch Vent Hose Drain Valve Bottom View Drain Hose Tee Fig. 5 Drain Pipe Pump Suction Hose Float Connection Hose Water Tank Drain Hose Water Tank Fig. 6 50 VII. Disposal The appliance contains refrigerant and must be disposed of in accordance with applicable national, state, and local codes and regulations. Refrigerant must be recovered by properly certified service personnel. 51 VIII. Technical Information We reserve the right to make changes in specifications and design without prior notice. A. Specification and Performance Data Sheets Pressure data is recorded at 5 min. into freezing cycle. The data not in bold should be used for reference only. 1. KMS-2000MLJ with SRK-20J Specification Sheet AC SUPPLY VOLTAGE AMPERAGE MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE SIZE ELECTRIC & WATER CONSUMPTION ELECTRIC W (kWH/100 lbs.) WATER gal./24HR (gal./100 lbs.) ICE PRODUCTION PER CYCLE BIN CONTROL SYSTEM REFRIGERANT CHARGE Performance Data Sheet APPROXIMATE ICE PRODUCTION PER 24 HR. lbs./day kg./day APPROXIMATE ELECTRIC CONSUMPTION watts APPROXIMATE WATER CONSUMPTION PER 24 HR. gal./day m3/day FREEZING CYCLE TIME min. HARVEST CYCLE TIME min. HEAD PRESSURE PSIG kg/cm2G SUCTION PRESSURE PSIG kg/cm2G 208-230/60/1 23.3 A ( 5 Min. Freeze AT 104°F / WT 80°F) 30 A 30 A 90/70°F 70/50°F 3470 (4.50) 3310 (4.12) 369 (20.0) 965 (50.1) 29 lbs. (13.2 kg) 1560pcs. Mechanical Bin Control TOTAL R404A, 27 lb. 5.4 oz. (12400g) ICEMAKER, 0 lb. 7.1 oz. (200g) CONDENSER, 26 lb. 14.3 oz. (12200g) AMBIENT TEMP. (ºF/ºC) 70/21 80/27 90/32 100/38 70/21 80/27 90/32 100/38 70/21 80/27 90/32 100/38 70/21 80/27 90/32 100/38 70/21 80/27 90/32 100/38 70/21 80/27 90/32 100/38 70/21 80/27 90/32 100/38 1926 1909 1904 1849 965 832 791 591 50/10 3310 3346 3357 3366 197 205 208 210 40 41 41 42 TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR CONDENSER VOLUME 18 19 19 19 4.7 4.1 4.0 3.2 873 866 863 839 3.65 3.15 2.99 2.24 13.9 14.4 14.6 14.8 2.8 2.9 2.9 3.0 WATER TEMP. (ºF/ºC) 70/21 1904 863 1874 850 1850 839 1815 823 3357 3419 3470 3483 791 2.99 561 2.12 369 1.40 359 1.36 19 19 20 21 4.0 3.1 2.3 2.2 208 14.6 223 15.7 235 16.5 238 16.7 41 2.9 43 3.0 44 3.1 45 3.1 1784 1705 1699 1560 699 552 323 281 221 235 248 260 44 46 47 50 90/32 3415 3473 3527 3580 20 21 22 24 3.6 3.1 2.1 2.0 809 773 771 708 2.65 2.09 1.22 1.06 15.6 16.5 17.4 18.3 3.1 3.2 3.3 3.5 31,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] 4,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] 964 CU. IN. SRK-20J 52 2. KMS-2000MLJ with SRK-20J3 Specification Sheet AC SUPPLY VOLTAGE AMPERAGE MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE SIZE ELECTRIC & WATER CONSUMPTION ELECTRIC W (kWH/100 lbs.) WATER gal./24HR (gal./100 lbs.) ICE PRODUCTION PER CYCLE BIN CONTROL SYSTEM REFRIGERANT CHARGE 208-230/60/3 13 A ( 5 Min. Freeze AT 104°F / WT 80°F) 30 A 30 A 90/70°F 70/50°F 3400 (4.30) 3170 (3.93) 379 (20.0) 913 (47.1) 30 lbs. (13.6 kg) 1560pcs. Mechanical Bin Control TOTAL R404A, 27 lb. 5.4 oz. (12400g) ICEMAKER, 0 lb. 7.1 oz. (200g) CONDENSER, 26 lb. 14.3 oz. (12200g) Performance Data Sheet APPROXIMATE ICE PRODUCTION PER AMBIENT TEMP. (ºF/ºC) 24 HR. 70/21 80/27 90/32 lbs./day kg./day 100/38 70/21 APPROXIMATE ELECTRIC 80/27 CONSUMPTION 90/32 watts 100/38 70/21 APPROXIMATE WATER 80/27 CONSUMPTION PER 24 HR. 90/32 gal./day m3/day 100/38 70/21 FREEZING CYCLE TIME 80/27 90/32 min. 100/38 70/21 HARVEST CYCLE TIME 80/27 90/32 min. 100/38 70/21 HEAD PRESSURE 80/27 90/32 PSIG kg/cm2G 100/38 70/21 SUCTION PRESSURE 80/27 90/32 2 PSIG kg/cm G 100/38 1938 1930 1927 1878 913 794 757 577 197 207 210 210 40 41 41 42 TOTAL HEAT OF REJECTION FROM CONDENSER TOTAL HEAT OF REJECTION FROM COMPRESSOR CONDENSER VOLUME 50/10 3170 3221 3237 3297 18 19 19 19 4.3 3.8 3.7 3.0 879 875 874 852 3.46 3.01 2.87 2.18 13.9 14.6 14.8 14.8 2.8 2.9 2.9 3.0 WATER TEMP. (ºF/ºC) 70/21 1927 874 1912 867 1900 862 1870 848 3237 3326 3400 3446 757 2.87 551 2.09 379 1.44 369 1.40 19 20 20 21 3.7 2.9 2.2 2.2 210 14.8 228 16.0 242 17.0 244 17.2 41 2.9 43 3.1 45 3.2 46 3.2 1826 1764 1770 1650 674 541 336 297 221 235 251 260 44 46 48 50 90/32 3407 3539 3598 3780 20 21 22 24 3.4 2.9 2.1 2.0 828 800 803 748 2.55 2.05 1.27 1.12 15.6 16.5 17.7 18.3 3.1 3.2 3.3 3.5 30,800 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] 4,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] 964 CU. IN. SRK-20J3 ENG.F-011.1.0205 53 3. SRK-20J Specification Sheet AC SUPPLY VOLTAGE AMPERAGE MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE SIZE EXTERIOR DIMENSIONS (WxDxH) DIMENSIONS INCLUDING LEGS (WxDxH) SHIPPING DIMENSIONS (LxWxH) EXTERIOR FINISH WEIGHT CONNECTIONS - ELECTRIC - REFRIGERATION CIRCUIT COMPRESSOR CONDENSER COMPRESSOR PROTECTION FAN MOTOR PROTECTION REFRIGERANT CIRCUIT PROTECTION REFRIGERANT CONTROL REFRIGERANT CHARGE DESIGN PRESSURE OPERATING CONDITIONS ACCESSORIES -SUPPLIED -REQUIRED 208-230/60/1 ( 3 wire with neutral for 115V ) (115VAC Supplied to KMS via Factory Wire Harness) 23.3 A ( 5 Min. Freeze AT 104°F / WT 80°F ) 30 A 30 A 59-3/4" x 17" x 30" (1518 x 432 x 762 mm) 62" x 21" x 45" (1575 x 533 x 1142 mm) 64" x 22-1/8" x 34-3/8" (1626 x 562 x 873 mm) Galvanized steel Net 280 lbs. (127 kg), Shipping 325 lbs. (147 kg) Main Power Supply: Permanent Connection SRK to KMS: Wire Harness Connection Suction line - 3/4" Brazed Connections Liquid line - 1/2" Brazed Connections Hermetic, Model CS24K6E-PFV Air Cooled, Fin and Tube Type Auto-Reset Overload Protector (Internal) Thermal Protection Auto-Reset High-Pressure Switch Condensing Pressure Regulator TOTAL R404A, 27 lb. 5.4 oz. (12400g) ICEMAKER, 0 lb. 7.1 oz. (200g) CONDENSER, 26 lb. 14.3 oz. (12200g) High 467 PSIG, Low 230 PSIG VOLTAGE RANGE AMBIENT TEMP. (Outdoor use) Legs and hardware 187-253VAC -20-122°F Compatible KMS-2000MLJ icemaker Line set HS-0243, HS-0244, HS-0245 TOTAL HEAT OF REJECTION FROM CONDENSER 31,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] TOTAL HEAT OF REJECTION FROM COMPRESSOR 4,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 964 CU. IN. ENG.F-032.1.0205 54 4. SRK-20J3 Specification Sheet AC SUPPLY VOLTAGE AMPERAGE MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE SIZE EXTERIOR DIMENSIONS (WxDxH) DIMENSIONS INCLUDING LEGS (WxDxH) SHIPPING DIMENSIONS (LxWxH) EXTERIOR FINISH WEIGHT CONNECTIONS - ELECTRIC - REFRIGERATION CIRCUIT COMPRESSOR CONDENSER COMPRESSOR PROTECTION FAN MOTOR PROTECTION REFRIGERANT CIRCUIT PROTECTION REFRIGERANT CONTROL REFRIGERANT CHARGE DESIGN PRESSURE OPERATING CONDITIONS ACCESSORIES -SUPPLIED -REQUIRED 208-230/60/3 (115VAC Supplied to KMS via Factory Wire Harness) 13.0 A ( 5 Min. Freeze AT 104°F / WT 80°F ) 20 A 20 A 59-3/4" x 17" x 30" (1518 x 432 x 762 mm) 62" x 21" x 45" (1575 x 533 x 1142 mm) 64" x 22-1/8" x 34-3/8" (1626 x 562 x 873 mm) Galvanized steel Net 283 lbs. (128 kg), Shipping 328 lbs. (149 kg) Main Power Supply: Permanent Connection SRK to KMS: Wire Harness Connection Suction line - 3/4" Brazed Connections Liquid line - 1/2" Brazed Connections Hermetic, Model CS24K6E-TF5 Air Cooled, Fin and Tube Type Auto-Reset Overload Protector (Internal) Thermal Protection Auto-Reset High-Pressure Switch Condensing Pressure Regulator TOTAL R404A, 27 lb. 5.4 oz. (12400g) ICEMAKER, 0 lb. 7.1 oz. (200g) CONDENSER, 26 lb. 14.3 oz. (12200g) High 467 PSIG, Low 230 PSIG VOLTAGE RANGE AMBIENT TEMP. (Outdoor use) Legs and hardware 187-253VAC -20-122°F Compatible KMS-2000MLJ icemaker Line set HS-0243, HS-0244, HS-0245 TOTAL HEAT OF REJECTION FROM CONDENSER 31,200 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] TOTAL HEAT OF REJECTION FROM COMPRESSOR 4,300 BTU/h [AT 90ºF (32ºC) / WT 70ºF (21ºC)] CONDENSER VOLUME 964 CU. IN. ENG.F-032.1.0205 55 56 V V P P BK BK W GR GR Neutral W HGV LLV Contactor Fuse 10A BR BR Wire Color Code: BK-black BR-brown GR-green P-pink V-violet W-white GND SRK Condensing Unit (field connected) Legend: CB-control board GND-ground HGV-hot gas valve LLV-liquid line valve GND V CB BR Fuse 10A BR GR V P P HGV KMS Icemaker Unit (factory connected) Wire Harness Connections LLV BK BK W Neutral W B. Wiring Diagrams 1. Wire Harness Connections W/BK COM C1 W/BK W 57 W WIRE COLOR CODE BK -BLACK BR -BROWN DBU -DARK BLUE GR -GREEN GY -GRAY O -ORANGE P -PINK R -RED V -VIOLET W -WHITE Y -YELLOW W/BR -WHITE/BROWN W/R -WHITE/RED W/BK -WHITE/BLACK W W BK L1 W BR C2 NC (BK) V GY W W W W WASH VALVE V V WASH 3 W W V GY GY VALVE DRAIN 1 CIRC R GY DRAIN W/BR W/BR W W (BR) FAN (BK) BK CAP. 10MFD BR (W) V R O GY CAP. 10MFD BR W W (BR) FAN (BK) BK R R R W W (Y) (R) 2 5 GY (DBU) DBU 4 5 R PUMP W (BK) (R) W (Y) 1 BR GY W W/R BK BK BK 3 OFF BR GND 10 SER BR GR W R R GY O W W O GY INLET WATER VALVE O GND W BK BK O BK BR DBU O W W W (Y) (R) BK LINE VALVE R GY GY W W 1 3 5 7 2 4 R DBU W 426±22 0 PSIG 341±22 PSIG Cut-out Cut-in O DBU Y P BR W W BK W V Y P Y DBU (R) P BR BK R P W W (BK) W (BR) (Y) (R) R V FLOAT SW. (R) R R V BK P R DBU O K2 K1 K5 BLACK K4 RED K3 WHITE CONTROL TRANSFORMER 1 2 3 1 3 2 6 5 4 7 9 8 10 3 2 1 1 2 3 1 2 3 CONTROL BOARD 10 VAC @ 115 VAC BR V BR (R) (BK) (BK) (BK) (O) (O) OFF NO. 10 THERMISTOR OFF NO. 9 BIN CONTROL DBU O V OFF NO. 8 HOT GAS 6 8 X10 VALVE Y Y BK P P P 1 3 5 7 2 4 P P R BR BR ON NO. 7 Cut-in Cut-out 239°F±9°F (115°C±5°C) 266°F±9°F (130°C± 5°C) 1A4787-011 Switch ** Discharge Line Thermostat DBU DBU DBU DBU O V V OFF OFF NO. 6 NO. 5 OFF NO. 5 6 8 X11 Y O BK 1 3 5 7 P P BK BR OFF NO. 4 OFF NO. 4 6 8 X12 2 4 W/R DBU P W/R P BK W BK * High-Pressure Switch W/R 10 9 7 BK BK 7 W 9 P P 5 P BR P 5 W FUSE 10A V BR V 1 TERMINAL BLOCK OFF NO. 3 OFF NO. 3 3 BR WIRING HARNESS OFF NO. 2 OFF NO. 2 V ICE W OFF KMS-2000MLJ X10 - HARVEST PUMP RELAY X11 - X10 CONTROL RELAY X12 - PUMP OUT RELAY NO. 1 OFF KMS-2000MLJ S5 DIP SWITCH SETTING NO. 1 S4 DIP SWITCH SETTING V 3 1 BR BK CONTROL SWITCH 2 SER W/R R (R) 6 OFF W/BR CAP. 10MFD ICE W (Y) C BK TERMINAL BLOCK R COMP. S HOT GAS LINE VALVE VALVE V R BR 40 MFD (R) HOT GAS VALVE P CAP. RUN BK LINE THERMOSTAT ** DISCHARGE START RELAY BK 1 (W) BR HI-PRESSURE SWITCH START CAP. 189-227MFD BR SERVICE SWITCH 2 W (BK) CRANKCASE HEATER W W BK NO BK T1 R FUSE 10A MAGNETIC CONTACTOR T3 L3 BR L2 T2 BR BK W BR L2 BK N W BR GND * BK L1 208-230/60/1 SRK (1 PHASE) 2. KMS-2000MLJ with SRK-20J MAIN W W W W C1 WIRE COLOR CODE BK -BLACK BR -BROWN DBU -DARK BLUE GR -GREEN GY -GRAY O -ORANGE P -PINK R -RED V -VIOLET W -WHITE Y -YELLOW W/BR -WHITE/BROWN W/R -WHITE/RED W/BK -WHITE/BLACK TRANSFORMER W BR BK 208V 0V BR V C2 NC BK (BK) GY GY BR 58 W W W W BK WASH VALVE W W V WASH 3 (BK) BK DRAIN 1 GY CIRC W W W GY GY DRAIN VALVE BR BR BR CAP. 10MFD V GY W (BR) DBU 4 BR 6 OFF W/R 5 W (Y) P R (R) PUMP W (BK) 7 9 BK W BR ICE 1 W/R GY W BK BK 3 OFF GND CONTROL SWITCH 2 BK R SER W (Y) BR 5 P W 3 10 1 V BR BR BR TERMINAL BLOCK (R) HOT GAS LINE VALVE VALVE V R BR CAP. W/R 10MFD ICE (DBU) R R W W (Y) (R) R HOT GAS VALVE P COMP. (R) S C LINE **DISCHARGE THERMOSTAT BK FAN (BK) BK BK BR BR CAP. 10MFD (W) R HI-PRESSURE SWITCH BR FAN (BR) (W) BR SERVICE SWITCH 2 W (BK) CRANKCASE HEATER V COM W/BK NO T1 L1 T3 BK BR R FUSE 10A MAGNETIC CONTACTOR BR T2 BR GND L3 L2 R L2 R VOLTAGE TAP SW. BR N 115V BK BK BK 230V BK BR * BK L1 208-230/60/1 SRK (3 PHASE) KMS-2000MLJ W/R R GND P BK BK W R O BK W W GY W W (Y) BK BR DBU P O DBU W W W V P BK BR OFF P BK BK O OFF NO. 4 OFF NO. 4 BK R NO. 3 OFF NO. 3 Y P BR BR GY 426±22 0 PSIG 341±22 PSIG Cut-in W 1 3 5 7 GY DBU W DBU DBU BK W DBU BK Y P P P P P BR OFF V P R BK O DBU W 1 3 5 7 DBU W W (Y) (BK) (BR) (R) R V FLOAT SW. (R) R R P V R BK O DBU K2 K1 K5 BLACK K4 RED K3 WHITE 10 VAC @ 115 VAC 1 2 3 1 3 2 6 5 4 7 9 8 10 3 2 1 1 2 3 1 2 3 CONTROL BOARD CONTROL TRANSFORMER BR V BR (R) (BK) BK BK (O) (O) OFF NO. 10 THERMISTOR OFF NO. 9 BIN CONTROL (BK) (BK) NO. 8 (R) P Y Y HOT GAS 2 4 6 8 X10 VALVE P R BR BR ON NO. 7 Cut-in Cut-out 239°F±9°F (115°C±5°C) 266°F±9°F (130°C± 5°C) Switch ** Discharge Line Thermostat1A4787-011 W 1 3 5 7 W Y P DBU V DBU O V V DBU OFF OFF NO. 6 NO. 5 OFF NO. 5 W/R DBU P P Y O 2 4 6 8 X12 2 4 6 8 X11 W/R FUSE 10A * High-Pressure Switch GY V LINE INLET O WATER VALVE (R) VALVE O O W BR TERMINAL BLOCK OFF OFF Cut-out R SER GR 9 W 10 7 5 3 1 BK V P BR WIRING HARNESS X10 - HARVEST PUMP RELAY X11 - X10 CONTROL RELAY X12 - PUMP OUT RELAY NO. 2 OFF NO. 2 NO. 1 OFF KMS-2000MLJ S5 DIP SWITCH SETTING NO. 1 S4 DIP SWITCH SETTING 3. KMS-2000MLJ with SRK-20J3
advertisement