- Computers & electronics
- Computer components
- Interface components
- Serial switch boxes
- Fujitsu
- ASAG09JGTA
- Installation manual
Fujitsu ASAG09JGTA Installation Manual
Add to My manuals12 Pages
Fujitsu ASAG09JGTA is a wall-mounted air conditioner designed to provide efficient and comfortable cooling and heating for your home. With its advanced features, this air conditioner offers a range of benefits to enhance your indoor environment.
advertisement
AIR CONDITIONER
Wall Mounted Type
Contents
1. SAFETY PRECAUTIONS .................................................................. 1
2. ABOUT THIS PRODUCT................................................................... 1
3. GENERAL SPECIFICATION ............................................................. 2
4. ELECTRICAL REQUIREMENT ......................................................... 2
5. SELECTING THE MOUNTING POSITION ....................................... 2
6. INSTALLATION WORK ..................................................................... 3
7. ELECTRICAL WIRING ..................................................................... 5
9. REMOVING AND REPLACING PARTS ............................................ 6
10. TEST RUN ......................................................................................... 7
11. REMOTE CONTROLLER INSTALLATION ........................................ 7
12. FUNCTION SETTING........................................................................ 7
13. OPTIONAL KIT INSTALLATION ........................................................ 9
14. SPECIAL INSTALLATION METHODS ............................................. 10
15. CUSTOMER GUIDANCE ................................................................ 10
16. ERROR CODES .............................................................................. 10
1. SAFETY PRECAUTIONS
• Be sure to read this manual thoroughly before installation.
• The warnings and precautions indicated in this manual contain important information pertaining to your safety. Be sure to observe them.
• Hand this manual, together with the operating manual, to the customer. Request the customer to keep them on hand for future use, such as for relocating or repairing the unit.
WARNING
Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that may result in minor or moderate injury or damage to property.
WARNING
• Installation of this product must be done by experienced service technicians or professional installers only in accordance with this manual. Installation by non-professional or improper installation of the product might cause serious accidents such as injury, water leakage, electric shock, or fire. If the product is installed in disregard of the instructions in this manual, it will void the manufacturer’s warranty.
• Do not turn on the power until all work has been completed. Turning on the power before the work is completed can cause serious accidents such as electric shock or fire.
• If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant is exposed to a direct flame, it may produce a toxic gas.
• Installation must be performed in accordance with regulations, codes, or standards for electrical wiring and equipment in each country, region, or the installation place.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
9387603033_IM.indd 1
INSTALLATION MANUAL
PART No. 9387603033
For authorized service personnel only.
CAUTION
• Read carefully all safety information written in this manual before you install or use the air conditioner.
• Install the product by following local codes and regulations in force at the place of installation, and the instructions provided by the manufacturer.
• This unit must be installed by qualified personnel with a capacity certificate for han dling refrigerant fluids. Refer to regulation and laws in use on installation place.
• This product is part of a set constituting an air conditioner. The product must not be installed alone or be installed with a device not authorized by the manufacturer.
• Always use a separate power supply line protected by a circuit breaker operating on all wires with a distance between contact of 3 mm for this product.
• To protect the persons, earth (ground) the product correctly, and use the power cable combined with an Earth Leakage Circuit Breaker (ELCB).
• This product is not explosion proof, and therefore should not be installed in an explosive atmosphere.
• To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 5 minutes or more before you touch the electrical components.
• This product contains no user-serviceable parts. Always consult experienced service technicians for repairing.
• When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the product.
• Do not touch the aluminum fins of heat exchanger built-in the indoor or outdoor unit to avoid personal injury when you install or maintain the unit.
• Do not place any other electrical products or household belongings under the product.
Condensation dripping from the product might get them wet, and may cause damage or malfunction to the property.
• Be careful not to scratch the air conditioner when handling it.
Precautions for using R410A refrigerant
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant
(R22) models, some of the piping and installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional refrigerant (R22) and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is 1/2-20 UNF.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant (R22) models. Also, when storing the piping ,securely seal the opening by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases. And always charge from the liquid phase where refrigerant composition is stable.
2. ABOUT THIS PRODUCT
2.1. Special tools for R410A
Tool name
Gauge manifold
Charge hose
Contents of change
Pressure is high and cannot be measured with a conventional (R22) gauge. To prevent erroneous mixing of other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals -0.1 to 5.3 MPa
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion value or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
En-1
21/11/2018 15:03:16
WARNING
Do not use the existing (for R22) piping and flare nuts.
If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause failure, injury, etc. (Use the special R410A materials.)
When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause failure, injury, etc.
2.2. For authorized service personnel only
WARNING
• For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
• Connect the indoor unit and outdoor unit with the air conditioner piping and cables available from your local distributor. This installation manual describes the correct connections using the installation set available from your local distributor.
• Installation work must be performed in accordance with national wiring standards by authorized personnel only.
• Do not turn on the power until all installation work is complete.
CAUTION
This installation manual describes how to install the indoor unit only.
To install the outdoor unit, refer to the installation manual included with the outdoor unit.
• Be careful not to scratch the air conditioner when handling it.
2.3. Accessories
The following installation accessories are supplied. Use them as required.
Name and Shape
Operating Manual
Q’ty Name and Shape
Filter holders
1
Q’ty
2
Installation Manual
(This manual)
Cloth tape
1 1
Remote controller Tapping screw (Large)
1 5
Remote controller holder Tapping screw (Small)
1 2
Air cleaning filter Battery
1 2
Air cleaning filter Wall hook bracket
1 1
The following items are necessary to install this air conditioner. (The items are not included with the air conditioner and must be purchased separately.)
Additional materials
Wall cap Connection pipe assembly
Connection cable (4-conductor)
Wall pipe
Decorative tape
Vinyl tape
Saddle
Drain hose
Tapping screws
Putty
2.4. Optional parts
Refer to each installation manual for the method of installing optional parts.
Parts name
Wired remote controller (*1)
External input and output PCB
Communication kit
WLAN adapter
Model No.
Application
UTY-RNR Z For air conditioner operation
UTY-RLR
(2-wired type)
UTY-XCSXZ2 For control input/output port
UTY-TWRXZ2 For the installation of optional parts
UTY-TFSXZ2 For wireless LAN control
*1: Optional Communication kit (UTY-TWRXZ2) is necessary for installation.
En-2
9387603033_IM.indd 2
3. GENERAL SPECIFICATION
This installation manual briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
3.1. Type of copper pipe and insulation material
CAUTION
Refer to the installation manual for the outdoor unit for description of allowable pipe length and height difference.
Gas pipe size (thickness) [mm]
Ø
9.52 (3/8 in.)
Liquid pipe size (thickness) [mm]
Ø
6.35 (1/4 in.)
CAUTION
• Wrap heat insulation around both gas pipe and liquid pipe.
No heat-insulation work or incorrect heat-insulation work may cause water leaks.
• In a reverse cycle model, use heat insulation with heat resistance above 120 °C.
• If expected humidity of the installation location of refrigerant pipes is higher than
70 %, wrap the heat insulation around the refrigerant pipes.
If the expected humidity is between 70 % and 80 %, use heat insulation that has a thickness of 15 mm or more.
If the expected humidity is higher than 80 %, use heat insulation that has a thickness of 20 mm or more.
• The use of thinner heat insulation than specified above, may cause a condensation on the surface of the insulation.
• Use heat insulation with thermal conductivity of 0.045 W/(m•K) or less, at 20 °C.
4. ELECTRICAL REQUIREMENT
The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate power source.
WARNING
Standard for electrical wiring and equipment differs in each country or region. Before you start electrical working, confirm related regulations, codes, or standards.
Cable
Connection cable
Conductor size [ mm 2 ]
1.5
Type Remarks
Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage drop is
2% or more.
5. SELECTING THE MOUNTING POSITION
Decide the mounting position with the customer as follows:
(1) Install the indoor unit level on a strong wall which is not subject to vibration.
(2) The inlet and outlet ports should not be obstructed: the air should be able to blow all over the room.
(3) Install the unit a dedicated electrical branch circuit.
(4) Do not install the unit where it will be exposed to direct sunlight.
(5) Install the unit where connection to the outdoor unit is easy.
(6) Install the unit where the drain pipe can be easily installed.
(7) Take servicing, etc. into consideration and leave the spaces shown in “6.1. Installation dimensions”. Also install the unit where the filter can be removed.
Correct initial installation location is important because it is difficult to move the unit after it is installed.
WARNING
Install the indoor unit where is capable to support the weight of the unit. Secure the unit firmly so that the unit does not topple or fall.
CAUTION
Do not install the unit in the following areas:
- Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
- Area filled with mineral oil or containing a large amount of splashed oil or steam, such as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.
- Area where is close to heat sources.
- Area that generates substances that adversely affect the equipment, such as sulfuric gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.
- Area that can cause combustible gas to leak, contains suspended carbon fibers or flammable dust, or volatile in flammables such as paint thinner or gasoline.
• If gas leaks and settles around the unit, it can cause a fire.
• Area where animals may urinate on the unit or ammonia may be generated.
• Do not use the unit for special purposes, such as storing food, raising animals, growing plants, or preserving precision devices or art objects. It can degrade the quality of the preserved or stored objects.
• Install the unit where drainage does not cause any trouble.
• Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote control cable at least 1 m away from a television or radio receivers. The purpose of this is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under some signal conditions.)
• If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
• Install the indoor unit on the wall where the height from the floor is more than 1.8 m.
21/11/2018 15:03:18
6. INSTALLATION WORK
WARNING
During transportation or relocation of the indoor unit, pipes shall be covered with the wall hook bracket for protection. Do not move the appliance by holding the indoor unit pipes.
(The stress applied to the pipe joints may cause the flammable gas to leak during operation.)
CAUTION
• Do not hit or push the human sensor. This may lead to damage or malfunction.
• Do not touch the human sensor. Any scratches or dirt may lead to incorrect detection.
• Do not place large objects near the human sensor. Also keep heating units outside the sensor’s detection area.
Detection range of the human sensor is as follows.
Vertical angle 90° (Side view) Horizontal angle 100° (Top view)
6 m
90°
50°
6 m
50°
6.1. Installation dimensions
Keep the distance between the wall hook bracket or indoor unit to the surrounding walls as indicated in the following figure.
Unit: mm
To lay the pipe out at the right, bottom, left bottom, or left outlet, remove the piping cut-out.
■ For right and left piping layout
(Ex.) For left piping layout
• Prepare the cut-out area with a utility knife and remove it using a nipper.
Cut-out
■ For bottom and left bottom piping
layout
• Remove the cut-out area using a nipper.
Remove
Under cover
(Ex.) For left bottom piping layout
Front panel
Under cover
Cut-out
Remove
6.3. Cutting the hole in the wall for connecting the pipes
(1) Cut a 65 mm diameter hole in the wall at the position shown in the following.
(2) Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.
(3) Always align the center of the wall hole. If misaligned, water leakage will occur.
(4) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap with vinyl tape, and stick the pipe through the hole.
(5) For left piping and right piping, cut the hole a little lower so that drain water will flow freely.
Wall hook bracket
Centering marks
65 mm hole
65 mm hole
(40 or more)
107 or more
Wall hook bracket
Outline of the indoor unit
1,500 or more
(70 or more)
183 or more
6.2. Indoor unit piping direction
The piping can be connected in the 6 directions indicated in the following.
When the piping is connected to direction (2) , (3) , (4) or (5) , cut along the piping groove on the side of the under cover with a hacksaw.
84 mm
Fasten with vinyl tape *
94 mm
5~10 mm
Wall cap * Wall pipe *
(Inside) Wall (Outside)
* Locally purchased
WARNING
Always use the wall pipe. If the wall pipe is not used, the cable that is connected between the indoor unit and the outdoor unit may touch metal, and cause an electric discharge.
6.4. Installing the wall hook bracket
(1) Install the wall hook bracket so that it is correctly positioned horizontally and vertically.
If the wall hook bracket is titled, water will drip to the floor.
(2) Install the wall hook bracket so that it is strong enough to support the weight of the unit.
• Fasten the wall hook bracket to the wall with 5 or more screws through the holes near the outer edge of the bracket.
• Check that there is no rattle at the wall hook bracket.
Screws (Large, accessories)
(2) Right outlet (1) Rear outlet
(3) Bottom outlet
(Rear)
(5) Left outlet
(6) Left rear outlet
(4) Left bottom outlet
Wall hook bracket
Under cover
Piping groove
Under cover
(inside view)
9387603033_IM.indd 3
En-3
21/11/2018 15:03:20
• For left piping, left bottom piping and left rear piping, align the marks on the wall hook bracket and shape the connection pipe.
• Bend the connection piping at a bend radius of 70 mm or more and install no more than 35 mm from the wall
Connection pipe small Align the marks
Bend R70 mm with a pipe bender
Connection pipe large
CAUTION
Install the wall-hook bracket both horizontally and vertically aligned.
Misaligned installation may cause water leakage.
6.5. Forming the drain hose and pipe
■ Rear piping, Right piping, Bottom piping
• Install the indoor unit piping in the direction of the wall hole and bind the drain hose and pipe together with vinyl tape.
• Install the piping so that the drain hose is at the bottom.
• Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.
■ For Left rear piping (Drain hose), Left piping (Drain hose)
Interchange the drain cap and the drain hose.
CAUTION
• Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.
• When inserting the drain hose, no other material than water should be applied.
Application of other material than water will cause deterioration of the hose, and may cause water leakage.
• After you remove a drain hose, be sure to attach the drain cap.
• When you secure the piping and drain hose with tape, arrange the drain hose so that it is at the bottom of the piping.
• For drain hose piping in low temperature environment, you need to apply freeze protection to prevent a frozen drain hose.
After cooling operation is performed in low temperature environment (when outdoor temperature under 0 °C), water in the drain hose could be frozen. Frozen drain water will block the water flow in the hose, and may cause water leakage at the indoor unit.
Removing the drain hose
Remove the screw at the left of drain hose and pull out drain hose.
Installing the drain hose
Vertically insert the drain hose toward the inside, so that the drain fixture (white) can accurately align with the screw hole around the drain cock.
After inserting and before replacing, please reinstall and fix the removed screws.
Screw hole Drain cock
Drain hose
Drain hose
Screw Drain fixture
• Please hold around the joint of the drain hose during work.
• As the screw is inside, be sure to use screwdrivers treated with magnet.
Screw
Drain fixture
Installing the drain cap
Use a hexagonal wrench 4 mm at opposite side to insert the drain cap, till the drain cap contacts the tip of the drain cock.
No gap
Hexagonal wrench
Drain cock
Drain cap
• After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
CAUTION
Insert the drain hose and drain cap into the drain port, making sure that it comes in contact with the back of the drain port, and then mount it. If the drain hose is not connected properly, leaking will occur.
■ Installing the indoor unit
• Hang the indoor unit from the hooks at the top of the wall hook bracket.
• Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate the bottom of the indoor unit from the wall.
Center of upper rail Top hooks
Indoor unit
(Spacer)
(Rear)
Bind with vinyl tape
Refrigerant pipes (top)
Right piping
Bottom piping
Rear piping
Indoor unit drain hose (bottom)
(Rear)
Indoor unit drain hose
For left outlet piping
(Drain hose), cut off the piping outlet cutting groove with a hacksaw.
Drain cap
Remove the drain cap by pulling at the projection at the end of the cap with pliers, etc.
(Fittings) Bottom hooks Wall hook bracket
• After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the bottom hooks while lowering the unit and pushing it against the wall.
6.6. Pipe connection
CAUTION
Tighten the flare nuts with a torque wrench using the specified tightening method.
Otherwise, the flare nuts could break after a prolonged period, causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame.
6.6.1. Flaring
Use special pipe cutter and flare tool designed for R410A pipework.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor unit(s) and outdoor unit or branch box respectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conventional flare tool. Leakage of refrigerant may result if other flare nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from entering the pipes.
B
Check if [L] is flared uniformly and is not cracked or scratched.
Die
A
Pipe
L
En-4
9387603033_IM.indd 4 21/11/2018 15:03:21
Pipe outside diameter
[mm (in.)]
Dimension A [mm]
Flare tool for R410A, clutch type
Dimension B [mm]
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
19.05 (3/4)
0 to 0.5
9.1
13.2
16.6
19.7
24.0
When using conventional flare tools to flare R410A pipes, the dimension A should be approximately 0.5 mm more than indicated in the table (for flaring with R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the dimension A.
Width across flats
Pipe outside diameter [mm (in.)]
6.35 (1/4)
9.52 (3/8)
12.70 (1/2)
15.88 (5/8)
19.05 (3/4)
Width across flats of Flare nut [mm]
17
22
26
29
36
6.6.2. Bending pipes
CAUTION
• To prevent breaking of the pipe, avoid sharp bends.
• If the pipe is bent repeatedly at the same place, it will break.
• The pipes are shaped by your hands. Be careful not to collapse them.
• Bend R70 mm or more with a pipe bender.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difficult to bend or stretch them anymore.
• Do not bend or stretch the pipes more than 3 times.
• When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case,
Insulating
Pipe
Pipe cut the insulating pipe with a sharp cutter as shown on the right, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulating pipe back on the pipe, and secure it with tape.
Cutter
Cut line
6.6.3. Flare connection
WARNING
The flare connection shall not be performed indoors.
CAUTION
• Be sure to install the pipe against the port on the indoor unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
• Do not remove the flare nut from the indoor unit pipe until immediately before con necting the connection pipe.
• Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to tighten the flare nut correctly.
• Tighten the flare nuts with a torque wrench using the specified tightening method.
Otherwise, the flare nuts could break after a prolonged period, causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame.
• Connect the piping so that the control box cover can easily be removed for servicing when necessary.
• In order to prevent water from leaking into the control box, make sure that the piping is well insulated.
When the flare nut is tightened properly by your hand, hold the body side coupling with a wrench, then tighten with a torque wrench. (See the following table for the flare nut tightening torques.)
Tighten with 2 wrenches.
Holding wrench
Torque wrench
Flare nut
7. ELECTRICAL WIRING
WARNING
• Before connecting the wires, make sure the power supply is OFF.
• Every wire must be connected firmly.
• No wire should be allowed to touch refrigerant tubing, the compressor, or any moving part.
• Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
• Connect wires to the matching numbers of terminals.
CAUTION
Be careful not to generate a spark as follows for using a flammable refrigerant.
• Do not remove the fuse while the power is on.
• Do not disconnect the wiring while the power is on.
• It is recommended to position the outlet connection in a high position. Place the cords so that they do not get tangled.
7.1. Wiring system diagram
INDOOR UNIT
TERMINAL
Type 60245 IEC57
Cable size 1.5 mm
2
(Inter-unit) Power line
OUTDOOR UNIT
7.2. Indoor unit wiring
(1) Remove the intake grille. (Refer to “9.1. Intake grille removal and installation”.)
(2) Remove the tapping screw for the wire cover and the wire cover. (Wire covers A and B come off together.)
Wire cover
Control line Please connect to the specified terminal.
Earth (Ground) line
Screw
(3) Remove the tapping screw and while minding the cable clamp hook, remove the cable clamp.
Cable clamp
Screw
Indoor unit pipe
(Body side)
Flare nut [mm (in.)]
6.35 (1/4) dia.
9.52 (3/8) dia.
12.70 (1/2) dia.
15.88 (5/8) dia.
19.05 (3/4) dia.
Connection pipe
Tightening torque [N·m (kgf·cm)]
16 to 18 (160 to 180)
32 to 42 (320 to 420)
49 to 61 (490 to 610)
63 to 75 (630 to 750)
90 to 110 (900 to 1,100)
Do not remove the cap from the connection pipe before connecting the pipe.
9387603033_IM.indd 5
En-5
21/11/2018 15:03:22
7.3. How to connect wiring to the terminals
Caution when wiring cable
To strip off the insulation of a lead wire, always use a special tool such as a wire stripper.
If there is no special tool, carefully strip off the insulation by using a knife or other utensil.
(1) Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal block.
(2) Securely clamp the ring terminals to the wires by using an appropriate tool so that the wires do not come loose.
Strip : 10 mm
Ring terminal
Sleeve
(3) Connect specified wires securely, and fasten them so that there is no stress applied on the terminals.
(4) Use a screwdriver with an appropriate bit size to tighten the terminal screws. Using of screwdriver with inappropriate bit size will damage the screw heads, and the screws will not be tightened properly.
(5) Do not overtighten the terminal screws. Otherwise, the screws may break.
Screw with special washer
Screw with special washer
Wire
Ring terminal
Ring terminal
Terminal blocks
Wire
(6) See the table for the terminal screw tightening torques.
M4 screw
Tightening torque [N·m (kgf·cm)]
1.2 to 1.8 (12 to 18)
CAUTION
• Match the terminal block numbers and connection cable colors with those of the outdoor unit. Incorrect wiring may cause a fire.
• Connect the connection cables firmly to the terminal block. Imperfect installation may cause a fire.
• When fixing the connection cable with the cable clamp, always fasten the cable at the plastic jacket portion, but not at the insulator portion. If the insulator is chafed, electric leakage may occur.
• Always connect the earth (ground) wire. Improper earthing (grounding) work can cause electric shocks.
• Do not use the earth (ground) screw for the indoor unit to the outdoor unit unless it is specified.
8. FINISHING
(1) Insulate between pipes.
• Insulate suction and discharge pipes separately.
• For rear, right, and bottom piping, overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(Wrap to about 1/3 the width of the tape from the bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
(6) Check the drainage.
Outside wall cap*
Saddle*
Sealer putty*
GOOD
Mounting shaft
Drain hose
Saddle
Lifted up
PROHIBITED
Wave End in water
9. REMOVING AND REPLACING PARTS
9.1. Intake grille removal and installation
Intake grille removal
(1) Hold the intake grille with both hands at the side, then pull to the front until it becomes hooked.
(2) Keeping the intake grille in a horizontal position, pull the mounting shaft on the left and right to release.
Intake grille
Mounting shaft
Intake grille installation
(1) Attach the left and right mounting shaft in the direction of the arrow to the panel top bearing while supporting the intake grille horizontally. Press this until it clicks so that each shaft snaps into place.
Mounting shaft
Bearing
Mounting shaft
Bearing
(2) Press and close the intake grille.
Press here
9.2. Front panel / control cover removal and installation
* In this description, the intake grille and wire cover already has been removed.
9.2.1. Front panel / control cover / under cover removal
(1) Remove the under covers. (Press down on the markings on the side, then slide down.)
(2) Remove the screw covers (2 places) on the bottom of the front panel, and then remove the screws (4 places).
(3) Push down on the markings (2 places) on top of the front panel to release the hooks
(3 places), then pull the front panel towards you.
(4) Pinch the tab on the control cover to release the hook, then open.
(Outdoors)
Pipe Wall
Overlap the insulation
Connection pipe
(heat insulation)
Bind the pipes together so that there is no gap.
Pipe
*Locally purchased
Indoor unit pipe
(heat insulation)
Vinyl tape*
Drain hose
Wrap with cloth tape.
Cloth tape (accessory)
En-6
9387603033_IM.indd 6 21/11/2018 15:03:23
Screws (4 places)
Screw covers
Markings
(triangle)
Markings (triangle)
Under covers
Markings (triangle)
Hook (3 places)
Markings (triangle)
11. REMOTE CONTROLLER INSTALLATION
Check that the indoor unit correctly receives the signal from the remote controller, then install the remote controller holder.
CAUTION
Do not install the remote controller holder in the following conditions:
• Any places exposed in direct sunlight
• Positions affected by the heat from a stove or heater
11.1. Remote controller holder installation
• Install the remote controller a maximum distance of 7 m from the remote control signal receiver. After installing the remote controller, check that it operates correctly.
• Install the remote controller holder to a wall, pillar, etc. with the tapping screw.
Remote controller holder
Tapping screws
(Small, accessories)
Remote controller
(1) Set
(2) Down
Tab
Control cover
9.2.2. Front panel / control cover / under cover installation
Reverse the procedures in “9.2.1. Front panel / control cover / under cover removal”.
* Be sure to replace the screws (4 places) and screw cover (2 places).
CAUTION
Please take caution when removing or installing the front panel. If the front panel falls, there is a risk of injury.
9.3. Uninstalling the indoor unit
Remove the indoor unit from the wall hook bracket as follows.
(1) Remove the under covers. (See “9.2.1. Front panel / control cover / under cover removal”.)
(2) Insert your fingers in the opening shown in the figure.
While pushing down on the lower part of the opening, release the hooks (2 places).
(3) Pull the indoor unit towards you.
Hooks (rear side)
Markings (triangle)
10. TEST RUN
Check items
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
• Do not operate the air conditioner in test run for a long time.
[Operation method]
Before starting the test run, wait for 1 minute after connecting the power supply.
By the wireless remote controller
• To start the test run, press the [START/STOP ( )], and press the [TEST RUN] on the remote controller by using the tip of a ballpoint pen or other small object.
By the indoor unit
• To start the test run, keep on pressing the indoor unit button for more than 10 seconds.
• To end test operation, press the [START/STOP ( )].
(When the air conditioner is running by pressing the [TEST RUN], the “OPERATION”
Lamp and “TIMER” Lamp will simultaneously flash slowly.)
11.2. Remote controller custom setting
Use the following steps to select the custom code of the remote controller. (Note that the air conditioner cannot receive a signal if the air conditioner has not been set for the matching custom code.)
(1) Press the [START/STOP ( )] until only the clock is displayed on the remote controller display.
(2) Press the [MODE] for at least 5 seconds to display the current custom code (initially set to A).
(3) Press the [TEMP. ( / )] to change the custom code between
A↔B↔C↔D
.
Match the code on the display to the air conditioner custom code.
(4) Press the [MODE] again to return to the clock display.
The custom code will be changed.
• If no buttons are pressed within 30 seconds after the custom code is displayed, the system returns to the original clock display. In this case, start again from step 1.
• The air conditioner custom code is set to A prior to shipment.
12. FUNCTION SETTING
Perform the Function Setting according to the installation conditions using the remote controller.
CAUTION
• Confirm whether the wiring work for outdoor unit has been finished.
• Confirm that the cover for the electrical enclosure on the outdoor unit is in place.
• This procedure changes to the Function Settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit to malfunction.
• After the power is turned on, perform the Function Setting according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function Number or Setting
Value.
• Settings will not be changed if invalid numbers or setting values are selected.
9387603033_IM.indd 7
En-7
21/11/2018 15:03:27
Selecting the Function Number and Setting Value
(1) While pressing the [POWERFUL] and [TEMP. ( )] simultaneously, press the [RESET] to enter the Function Setting mode.
(2) Press the [ECONOMY].
(3) Press the [TEMP. ( / )] to select the function number. (Press the [ECONOMY] to switch between the left and right digits.)
(4) Press the [POWERFUL] to proceed to setting value. (Press the [POWERFUL] again to return to the function number selection.)
Function
Number
(5) Press the [TEMP. ( / )] to select the setting value. (Press the [ECONOMY] to switch between the left and right digits.)
(6) Press the [MODE] once. Please confirm the beeping sound.
(7) Next, please press the [START/STOP ( confirm the beeping sound.
)] once to fix the Function Setting. Please
(8) Press the [RESET] to cancel the Function Setting mode.
(9) After completing the Function Setting, be sure to disconnect the power supply and then reconnect it.
CAUTION
After disconnecting the power supply, wait 30 seconds or more before reconnecting it.
The Function Setting will not become active unless the power supply is disconnected and then reconnected.
12.1. Function Details
Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room.
If the indication is not required, select “No indication” (03).
(♦... Factory setting)
Function
Number
11
Setting
Value
00
01
02
03
Setting Description
Standard (400 hours)
Long interval (1000 hours)
Short interval (200 hours)
No indication ♦
Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the “Standard setting” (00)
(manufacturer’s recommended value).
(♦... Factory setting)
Function
Number
Setting Description
30
Setting
Value
00
01
02
08
09
10
11
12
03
04
05
06
07
13
14
15
16
17
Standard setting
No correction 0.0 °C (0 °F)
-0.5 °C (-1 °F)
-1.0 °C (-2 °F)
-1.5 °C (-3 °F)
-2.0 °C (-4 °F)
-2.5 °C (-5 °F)
-3.0 °C (-6 °F)
-3.5 °C (-7 °F)
-4.0 °C (-8 °F)
+0.5 °C (+1 °F)
+1.0 °C (+2 °F)
+1.5 °C (+3 °F)
+2.0 °C (+4 °F)
+2.5 °C (+5 °F)
+3.0 °C (+6 °F)
+3.5 °C (+7 °F)
+4.0 °C (+8 °F)
♦
More
Cooling
Less
Cooling
Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to “Both” (01).
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
(♦... Factory setting)
Function
Number
Setting Description
35
Setting
Value
00
01
02
11
12
13
08
09
10
03
04
05
06
07
14
15
16
17
No correction
No correction 0.0 °C (0 °F)
-0.5 °C (-1 °F)
-1.0 °C (-2 °F)
-1.5 °C (-3 °F)
-2.0 °C (-4 °F)
-2.5 °C (-5 °F)
-3.0 °C (-6 °F)
-3.5 °C (-7 °F)
-4.0 °C (-8 °F)
+0.5 °C (+1 °F)
+1.0 °C (+2 °F)
+1.5 °C (+3 °F)
+2.0 °C (+4 °F)
+2.5 °C (+5 °F)
+3.0 °C (+6 °F)
+3.5 °C (+7 °F)
+4.0 °C (+8 °F)
♦
More
Cooling
Less
Cooling
(♦... Factory setting)
Function
Number
40
Setting
Value
00
01
Setting Description
Enable
Disable
♦
* Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
Room temperature sensor switching
(Only for wireless remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” (01).
(♦... Factory setting)
Function
Number
42
Setting
Value
00
01
Setting Description
Indoor unit
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller
♦
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
(♦... Factory setting)
Function
Number
44
Setting
Value
00
01
02
03
Setting Description
A
B
C
D
♦
External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(♦... Factory setting)
Function
Number
46
Setting
Value
00
01
02
03
Setting Description
Operation/Stop mode 1
(Setting prohibited)
Forced stop mode
Operation/Stop mode 2
♦
En-8
9387603033_IM.indd 8 21/11/2018 15:03:28
Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to “Wired remote controller” (01). This function will only work if the function setting 42 is set at “Both” (01).
(♦... Factory setting)
Function
Number
48
Setting
Value
00
01
Setting Description
Both
Wired remote controller
♦
Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation.
(♦... Factory setting)
Function
Number
49
Setting
Value
00
01
Setting description
Disable
Enable
♦
02 Remote controller
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for cooling function, or when connecting a single split converter, the setting cannot be made by using the remote controller. Set to (00) or (01).
To confirm if the remote controller has this function, refer to the operating manual of each remote controller.
Switching functions for external output terminal
Functions of the external output terminal can be switched.
(♦... Factory setting)
Function
Number
60
Setting
Value
00
01 to 08
09
10
11
Setting Description
Operation status
(Setting prohibited)
Error status
Indoor unit fan operation status
(Setting prohibited)
♦
Setting record
Record any changes to the settings in the following table.
Setting Description
Filter sign
Room temperature control for indoor unit sensor
Room temperature control for wired remote controller sensor
Auto restart
Room temperature sensor switching
Remote controller custom code
External input control
Room temperature sensor switching (Aux.)
Indoor unit fan control for energy saving for cooling
Switching functions for external output terminal
Setting Value
After completing the Function Setting, be sure to disconnect the power supply and then reconnect it.
13. OPTIONAL KIT INSTALLATION
13.1. Installing the WLAN adapter
(1) Remove the intake grille from panel, and control cover. Refer to “9. REMOVING AND
REPLACING PARTS”.
(2) Remove the connector cable from CN6 connector, and connect the WLAN adapter cable with connector.
(3) Hook the removed connector cable to the control box.
Fix it with a cable tie.
WLAN adapter cable with connector
13.2. Installing the External input/output PCB
(1) Remove the Intake grille, front panel, and control cover. Refer to “9. REMOVING AND
REPLACING PARTS”.
(2) Insert the PCB to the clasps (2 places). Push the PCB down until the clasp on the left is set.
Clasp
Clasps
(2 places)
External input/ output PCB
(3) Disconnect the WLAN adapter wire (CN6), then replace it with the wire for External input/output PCB.
(4) Hook the WLAN adapter wire to the control box. Fix it with a cable tie.
Cable tie
External input/ output PCB wire
Connector
(CN6)
(5) Replace the control cover, front panel, and Intake grille.
13.3. Installing the Communication kit
(1) Remove the Intake grille, front panel, and control cover. Refer to “9. REMOVING AND
REPLACING PARTS”.
(2) Insert the PCB to the clasps (2 places). Push the PCB down until the clasp on the bottom is set.
(3) Connect the wire with EMI core to the terminal board.
Clasps
Clasp
Communication
PCB
(4) Attach the terminal board to the indoor unit with 1 screw (accessory for option).
(5) Connect the wire with EMI core to the communication PCB, then fix it with the cable tie (accessory for option).
(6) Connect the communication kit and main PCB.
(7) Connect the wired remote controller cable to the terminal board as shown in the figure.
Screw (accessory for option)
Cable tie
Communication wire
Connector
(CN13)
Cable clamp
Tab
Wired remote controller cable
(8) Replace the control cover, front panel, and Intake grille.
Connector (CN6)
Cable tie
NOTES: Options connecting to CN6 cannot be used at the same time.
(4) Replace the control cover, front panel, and intake grille.
9387603033_IM.indd 9
En-9
21/11/2018 15:03:30
14. SPECIAL INSTALLATION METHODS
Group control system
A number of indoor units can be operated at the same time using a single remote controller.
*When different types of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
(1) Connect up to 16 indoor units in a system.
I.U.
I.U.
I.U.
I.U.
B
A
Remote controller
A, B, C, D, E : Remote controller cable.
A+B+C+D+E ≤ 500 m.
C
Example of wiring method
Indoor unit 1 Indoor unit 2
D E
Indoor unit 3 Indoor unit 4
1 2
R W
Remote controller cable
Bus wire
Remote controller
(2) Set the R.C. address (Function setting)
• Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial setting of (00).
• Only set addresses manually when using different numbers for addresses.
Set the R.C. address of each indoor unit using the function setting. (See “Remote controller address setting”.)
Also set the R.C. address for the remote controller. For details, please refer to the remote controller installation manual.
* In manual setting, connect up to 15 indoor units in a system.
Example Example of wiring method
Indoor unit 1
RC AD
01
Indoor unit 2
RC AD
02
Indoor unit 3
RC AD
03
Indoor unit 4
RC AD
04
Remote controller
Remote controller address setting
(♦... Factory setting)
Function
Number
00
Setting
Value
00
01
02 ~ 13
14
15
Setting Description
(For automatic setting)
Unit no. 1
Unit no. 2 ~ Unit no. 13
Unit no. 14
Unit no. 15
♦
* Do not use the same setting value.
* After completing the Function Setting, be sure to disconnect the power supply and then reconnect it.
15. CUSTOMER GUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, airflow switching, and other remote control unit operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.
16. ERROR CODES
If you use a wireless remote controller, the lamp on the photo detector unit will output error codes by way of blinking patterns. If you use a wired remote controller, error codes will appear on the remote control display. See the lamp blinking patterns and error codes in the table. An error display is displayed only during operation.
Error display
OPERATION lamp
(green)
TIMER lamp
(orange)
ECONOMY lamp
(green)
Error code
(1) (1)
Description
Serial communication error
(1)
(1)
(1)
(1)
(2)
(5)
(6)
(8)
• Wired remote controller communication error
• Server room control communication error
Check run unfinished
Automatic airflow adjustment error
Peripheral unit transmission PCB connection error
External communication error
(2)
(2)
(1)
(2)
Unit number or Refrigerant circuit address setting error
[Simultaneous Multi]
Indoor unit capacity error
(2) (3)
Combination error
(2)
(2)
(4)
(6)
• Connection unit number error (indoor secondary unit)
[Simultaneous Multi]
• Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
Indoor unit address setting error
(2)
(2)
(3)
(7)
(9)
(1)
Primary unit, secondary unit setup error [Simultaneous Multi]
Connection unit number error in wired remote controller system
Power supply interruption error
(3)
(3)
(3)
(2)
(3)
(5)
Indoor unit PCB model information error
Indoor unit motor electricity consumption detection error
Manual auto switch error
(3)
(3)
(4)
(9)
(10)
(1)
Indoor unit power supply error for fan motor
Indoor unit communication circuit
(wired remote controller) error
Room temp. sensor error
(4)
(4)
(2)
(4)
Indoor unit heat ex. middle temp. sensor error
Human sensor error
(5) (1)
Indoor unit fan motor error
(5) (3)
Drain pump error
●
●
(5)
(5)
(5)
●
●
(4)
(5)
(7)
Electric air cleaner reverse VDD error
Filter set error
Damper error
●
(5)
●
(8)
Intake grille error
● (5) ● (9)
Indoor unit fan motor 2 error
(Left side fan)
En-10
9387603033_IM.indd 10 21/11/2018 15:03:33
Error display
OPERATION lamp
(green)
TIMER lamp
(orange)
ECONOMY lamp
(green)
Error code
● (5) ● (10)
(5) (15)
Description
Indoor unit fan motor 3 error
(Right side fan)
Indoor unit error
(6)
(6)
(6)
(1)
(2)
(3)
Outdoor unit reverse/missing phase and wiring error
Outdoor unit main PCB model information error or communication error
Inverter error
(6) (4)
Active filter error, PFC circuit error
(6) (5)
Trip terminal L error
(6)
(6)
(7)
(8)
(10)
(1)
Outdoor unit rush current limiting resister temp. rise error
Display PCB microcomputers communication error
Discharge temp. sensor error
(7)
(2)
Compressor temp. sensor error
(7)
(7)
(3)
(4)
Outdoor unit Heat Ex. liquid temp. sensor error
Outdoor temp. sensor error
(7) (5)
Suction Gas temp. sensor error
(7)
(7)
(6)
(7)
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error
Heat sink temp. sensor error
(8)
(8)
(2)
(3)
• Sub-cool Heat Ex. gas inlet temp. sensor error
• Sub-cool Heat Ex. gas outlet temp. sensor error
Liquid pipe temp. sensor error
(8)
(4)
Current sensor error
(8)
(9)
(6)
(4)
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
Trip detection
(9)
(9)
(5)
(7)
Compressor rotor position detection error (permanent stop)
Outdoor unit fan motor 1 error
(9) (8)
Outdoor unit fan motor 2 error
(9) (9)
4-way valve error
(9) (10)
Coil (expansion valve) error
(10) (1)
Discharge temp. error
(10) (3)
Compressor temp. error
(10) (4)
High pressure error
(10)
(5)
Low pressure error
(13) (2)
Branch boxes error
[Flexible Multi]
Display mode
●
: 0.5s ON / 0.5s OFF
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
[Troubleshooting with the indoor unit display]
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
ECONOMY indicator lamp (green)
9387603033_IM.indd 11
En-11
21/11/2018 15:03:37
9387603033_IM.indd 12 21/11/2018 15:03:37
advertisement
Key Features
- Cools and heats efficiently, maintaining a comfortable temperature in your room.
- Advanced air purification system removes allergens and pollutants, improving air quality.
- Quiet operation ensures a peaceful and undisturbed indoor environment.
- Compact and sleek design seamlessly integrates with your home decor.
- Energy-efficient performance helps reduce energy consumption and save on electricity bills.
- Easy-to-use remote control allows you to adjust settings and monitor performance remotely.
- Automatic modes adjust cooling or heating based on room conditions, ensuring optimal comfort.
- Anti-mold function prevents mold and mildew growth, maintaining a healthy indoor environment.
- Self-diagnosis feature detects and reports any issues, making maintenance effortless.
- Durable construction ensures long-lasting performance and reliability.
Related manuals
Frequently Answers and Questions
Can I use the air conditioner for both cooling and heating?
How does the air conditioner improve air quality?
Is the air conditioner energy-efficient?
How do I control the air conditioner?
What is the self-diagnosis feature?
advertisement
Table of contents
- 1 1. SAFETY PRECAUTIONS
- 1 2. ABOUT THIS PRODUCT
- 2 3. GENERAL SPECIFICATION
- 2 4. ELECTRICAL REQUIREMENT
- 2 5. SELECTING THE MOUNTING POSITION
- 3 6. INSTALLATION WORK
- 5 7. ELECTRICAL WIRING
- 6 9. REMOVING AND REPLACING PARTS
- 7 10. TEST RUN
- 7 11. REMOTE CONTROLLER INSTALLATION
- 7 12. FUNCTION SETTING
- 9 13. OPTIONAL KIT INSTALLATION
- 10 14. SPECIAL INSTALLATION METHODS
- 10 15. CUSTOMER GUIDANCE
- 10 16. ERROR CODES