Red Lion Graphite Edge Controller Industrial Controllers & RTUs Product Manual

Add to my manuals
8 Pages

advertisement

Red Lion Graphite Edge Controller Industrial Controllers & RTUs Product Manual | Manualzz

 

Inside US: +1 (877) 432-9908

Outside US: +1 (717) 767-6511 www.redlion.net

Bulletin No. GRAC1-D

Drawing No. LP0994

Released 2018-11-30

MODEL

 

GRAC0001

 ‐ 

Graphite®

 

Edge

 

Controller

 

With

 

Plug

In

 

I/O

 

Module

 

and

 

Protocol

 

Conversion

 

Capability

• RUGGED CONTROLLER WITH BUILT-IN CONTROL ENGINE

• PROTOCOL CONVERSION FEATURE CONVERTS 13

PROTOCOLS SIMULTANEOUSLY

• OVER 300 BUILT-IN DRIVERS ALLOWS EASY DATA MAPPING

TO PLCs, PCs, AND SCADA SYSTEMS

• BUILT-IN WEB SERVER ALLOWS REMOTE VIEW OR CONTROL

FROM ANY INTERNET-CONNECTED PC OR SMART PHONE

• SYNCS DATA LOGS TO FTP SERVERS AND MICROSOFT SQL

SERVER ®

• PROVIDES EMAIL AND SMS TEXT MESSAGE ALERTS

(SMS Requires GMHSPA00 module)

• CONFIGURED USING CRIMSON ® 3 SOFTWARE WITH CRIMSON

CONTROL

• 3 FULLY ISOLATED SERIAL COMMUNICATION PORTS

(1 RS232 and 2 RS422/485)

• 2 10 BASE T/100 BASE-TX ETHERNET CONNECTIONS CAN

CONNECT TO AN UNLIMITED NUMBER OF DEVICES VIA TEN

PROTOCOLS SIMULTANEOUSLY

• INTEGRATED GRAPHITE RACK EXPANSION PORT. ADD UP TO

4 GEXRACK2 3 PORT EXPANSION RACKS.

• CAST ALUMINUM CASE CONSTRUCTION SUPPORTS DIN RAIL

AND PANEL MOUNT

C

R

UL

C US

LISTED

IND.CONT. EQ.

E317425

FOR USE IN HAZARDOUS LOCATIONS:

Class I, Division 2, Groups A, B, C, and D

T4

II 3 G Ex nA IIC T4 Gc

-40°C ≤ T

AMB

≤ 70°C

DEMKO 14 ATEX 1387X

IECEx UL 15.0035X

US LISTED

IND. CONT. EQ.

E302106

GENERAL

 

DESCRIPTION

The Graphite ® Edge Controller is designed to remotely connect, monitor and control equipment in process applications. At the core of the product is Crimson ® 3 featuring an embedded IEC61131 control engine, that can be configured via Ladder, Function Block, Structured Text, and

Instruction List. Additionally, the Graphite Edge Controller is optimized for multi-vendor environments with powerful protocol conversion, built-in data logging and a virtual operator interface for remotely viewing equipment and processes. The Edge Controller can be expanded to meet almost any application requirement through the use of plug-in digital and analog I/O modules that leverage the Graphite Expansion

Racks. The integrated rack port supports 4 GEXRACK2 bases (12 modules). An additional 12 modules can be added using the USB host port (GEXRACK1, 3 GEXRACK2).

Red Lion’s industry leading protocol library offers access to over 300 drivers including PLCs, drives, cameras, bar code readers and many other devices providing easy data mapping to PLCs, PCs, and SCADA

Systems. In addition, the Edge Controller can convert over 13 protocols simultaneously, seamlessly connecting and communicating with disparate devices. Graphite Edge Controllers offer numerous communication ports including high-speed RS-232/485 and 10/100Base-

T(X) Ethernet ports. Additionally, the Edge Controller features built-in

USB host ports for fast downloads of configuration files and access to trending and data logging information. Eliminate the need for external protocol converters and use an Edge Controller to connect and control to all your devices.

The Graphite Edge Controller can be programmed with Red Lion’s

Crimson 3 software using a simple drag and drop interface to configure data tags, virtual displays, protocol conversion and data logging in minutes. Embedded in Crimson 3 software platform is the IEC 61131 control engine, Crimson Control which can be written in 4 programming languages including Ladder, Function Block, Structured Text, and

Instruction List. The controller comes with Crimson Control functionality enabled, without the need for additional equipment or modules.

Red Lion’s Edge Controller is housed in an all-aluminum housing, which provides reliable operation that can withstand even the most demanding environments. The result is an industrially-hardened solution that connects, monitors, and controls disparate equipment in multivendor applications.

CONTENTS

 

OF

 

PACKAGE

- Graphite Edge Controller

- Terminal block for connecting power.

- (1) Module port cover

- Downstream port cover

- User Bulletin

ORDERING

 

INFORMATION

DESCRIPTION

Graphite Edge Controller

PART NUMBER

GRAC0001

A listing of the entire Graphite family of products and accessories can be found at www.redlion.net.

SAFETY

 

SUMMARY

All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the unit.

-1-

  Bulletin No. GRAC1-D

Drawing No. LP0994

CAUTION: Risk of Danger.

Read complete instructions prior to installation

OR AREA IS KNOWN TO BE NON-HAZARDOU

Released 2018-11-30

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT

EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF

OR AREA IS KNOWN TO BE NON-HAZARDOUS.

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF

COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,

DIVISION 2.

SPECIFICATIONS

1.

POWER REQUIREMENTS :

Must use a Class 2 circuit according to National Electrical Code (NEC),

NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a

Limited Power Supply (LPS) according to IEC 60950-1 or Limitedenergy circuit according to IEC 61010-1.

Power connection via removable three position terminal block.

Supply Voltage: 10-30 VDC

GRAC0001 POWER RATINGS

(WATTS)

Input Voltage 10 V

Typical Power GRAC0001 only: 4 W

12 V

4 W

24 V

5 W

30 V

5 W

Maximum Power GRAC0001 only: 9 W

Available Power for Modules:

9 W

55 W

10 W 10 W

Max Power GRAC0001 With Module(s): 64 W 64 W 67 W 67 W

2.

BATTERY : Lithium coin cell. Typical lifetime of 6 years, nominal.

3.

MEMORY :

On Board User Memory: 256 Mbyte of non-volatile Flash memory.

Memory Card: SD slot accepts standard capacity cards.

4.

COMMUNICATION CAPABILITIES :

USB Port : Adheres to USB specification 2.0 (high speed, full speed) only using Type B connection.

WARNING - DO NOT CONNECT OR DISCONNECT CABLES

WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE

NON-HAZARDOUS.

USB Host Ports : Comply with Universal Serial Bus Specification Rev

2.0. Support data transfers at (high speed, full speed). Hardware over current protected (0.5 A max per port).

Serial Ports : Ports are individually isolated. Format and Baud Rates for each port are individually software programmable up to 115,200 baud.

PGM Port: RS232 port via RJ12.

COMMS Ports: RS422/485 ports via RJ45

DH485 TXEN: Transmit enable; open collector, V

OH

V

OL

= 0.5 V @ 25 mA max.

= 15 VDC,

Port to Port Isolation: 500 Vrms for 1 minute. Signal Isolation: 50 V.

Ethernet Ports : 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).

Isolation from Ethernet network to GRAC0001: 1500 Vrms

5.

ENVIRONMENTAL CONDITIONS :

Operating Temperature Range: -40 to 70 °C, or lowest range among equipment used in your Graphite system. Consult the user manual or www.redlion.net/OpTemp for further details.

Storage Temperature Range: -40 to 85 °C

Panel Mount Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g

Panel Mount Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/ relays)

DIN Rail Mount Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g

DIN Rail Mount Shock to IEC 68-2-27: Operational 15 g (10 g, modules w/relays)

Requires DIN Rail type: DIN 1010, DIN 1065, or DIN 3065.

Operating and Storage Humidity: 0 to 85% max. RH non-condensing

Altitude: Up to 2000 meters

Installation Category II, Pollution Degree 2 as defined in IEC/EN 60664-1.

6.

CERTIFICATIONS AND COMPLIANCES :

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

ATEX Approved

II 3 G Ex nA IIC T4 Gc

DEMKO 14 ATEX 1387X

EN 60079-0, -15

IECEx Approved

Ex nA IIC T4 Gc

IECEx UL 15.0035X

IEC 60079-0, -15

UL Listed: File #E302106

UL Hazardous: File #E317425

ABS Type Approval for Shipboard Applications

7.

CONNECTIONS : High compression cage-clamp terminal block

Wire Strip Length: 0.3" (7.5 mm)

Wire Gauge Capacity: One 14 AWG (1.63 mm) solid, two 18 AWG (1.02 mm) or four 20 AWG (0.81 mm)

Torque: 4.43-5.31 inch-lbs (0.5-0.6 N-m)

8.

CONSTRUCTION : Cast aluminum.

9.

WEIGHT : 2 lb 4.2 oz. (1.03 Kg)

DIMENSIONS

 

In

 

inches

 

(mm)

8.07 (205) *

4.11 (104.5)

6.35

(161.4)

5.95

(151.1)

2.79

(70.8)

2.97 (76)

4.40 (112)

Optional

GEXRACK2 unit

* +3.96 for each additional base

Module sold separately

-2-

  Released 2018-11-30 Bulletin No. GRAC1-D

Drawing No. LP0994

GRAPHITE

 

EDGE

 

CONTROLLER

 

INSTALLATION

PANEL

 

MOUNTING

 

INSTRUCTIONS

The Controller can be mounted on a DIN rail for normal environments, or bolted to a panel for high vibration environments. Refer to the diagram for the panel mount hole spacing.

2.75

(69.8)

1.72 (43.6) 2.13 (54)

1.83 (46.6)

2.13 (54)

5.12

(130)

Captive Screws to fasten the bases together

Optional GEXRACK2 units

DIN

 

RAIL

 

MOUNT

 

AND

 

CAM

 

OPERATION

DIN rail mounting is only recommended in low vibration environments.

Refer to the Specifications section for details.

1. Using a screwdriver, push in and fully rotate the Cam counterclockwise to push the DIN clip downward against spring pressure locking it open

2. Place the controller on the DIN rail

3. Using a screwdriver, push in and rotate the Cam 90 degrees clockwise to release the DIN clip to engage the DIN rail

4. Rotate the Cam an additional 90 degrees clockwise to lock the DIN clip in the closed position.

UNLOCK

LOCK

For hazardous location installation the following shall be taken into consideration:

- When used in a Zone 2 environment, the device shall be panel mounted in at least Zone 2 IECEx/ATEX-Certified tool accessible enclosure with a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60529.

- The equipment shall only be used in an environment of not more than

Pollution Degree 2, as defined in IEC/EN 60664-1.

- Must be wired using Division 2 wiring methods as specified in article

501-4(b), 502-4(b), and 503-3(b) of the National Electric Code, NFPA

70 for installation within the United States, or as specified in section

19-152 of Canadian Electrical Code for installation in Canada.

CONNECTING TO EARTH GROUND

The third pin of the power connector of the Edge Controller is chassis ground for the unit. Your unit should be connected to earth ground.

The chassis ground is not connected to signal common of the unit.

Maintaining isolation between earth ground and signal common is not required to operate your unit. But, other equipment connected to this unit may require isolation between signal common and earth ground. To maintain isolation between signal common and earth ground care must be taken when connections are made to the unit.

For example, a power supply with isolation between its signal common and earth ground must be used. Also, plugging in a USB cable may connect signal common and earth ground.

1

1 USB’s shield may be connected to earth ground at the host. USB’s shield in turn may also be connected to signal common.

POWER SUPPLY REQUIREMENTS

The Graphite Edge Controller requires a 10-30 VDC power supply.

Your unit may draw considerably less than the maximum rated power depending upon the features being used, and the applied voltage. As additional features are used your unit will draw increasing amounts of power. Items that could cause increases in current are modules, additional on-board communications, SD card, and other features programmed through Crimson software.

Note: Modules connected via a GEXRACK1 to the Edge Controller, are powered by the GEXRACK1 and not the Edge Controller

To ensure you do not exceed the capacity of your Graphite host power supply, calculate the total power consumption required for all of your planned modules. Each module’s maximum power consumption is listed in the Specifications of their Product Bulletin. The total power available for modules is listed in the specifications of the Graphite host.

In any case, it is very important that the power supply is mounted correctly if the unit is to operate reliably. Please take care to observe the following points:

– Voltage range stated is at the power connector, not at the power source.

– The power supply must be mounted close to the unit, with usually not more than 6 feet (1.8 m) of cable between the supply and the operator interface. Ideally, the shortest length possible should be used.

– The wire used to connect the operator interface’s power supply should be at least 22-gage wire suitably rated for the temperatures of the environment to which it is being installed. If a longer cable run is used, a heavier gage wire should be used. The routing of the cable should be kept away from large contactors, inverters, and other devices which may generate significant electrical noise.

– A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV rating is to be used. This type of power supply provides isolation to accessible circuits from hazardous voltage levels generated by a mains power supply due to single faults. SELV is an acronym for

“safety extra-low voltage.” Safety extra-low voltage circuits shall exhibit voltages safe to touch both under normal operating conditions and after a single fault, such as a breakdown of a layer of basic insulation or after the failure of a single component has occurred. A suitable disconnect device shall be provided by the end user.

– Peak efficiency (GRAC0001) occurs at the low side of the voltage range (approx. 12 V), recommended for high temperature applications.

EMC

 

INSTALLATION

 

GUIDELINES

Although Red Lion Controls products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into a unit may be different for various installations. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMI guidelines for a successful installation in an industrial environment.

1. A unit should be mounted in a metal enclosure, which is properly connected to protective earth.

2. Use shielded cables for all Signal and Control inputs. The shield connection should be made as short as possible. The connection point

-3-

  Bulletin No. GRAC1-D

Drawing No. LP0994 for the shield depends somewhat upon the application. Listed below are the recommended methods of connecting the shield, in order of their effectiveness.

a. Connect the shield to earth ground (protective earth) at one end where the unit is mounted.

b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is over 1 MHz.

3. Never run Signal or Control cables in the same conduit or raceway with

AC power lines, conductors, feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be run through metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter.

Also, Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.

4. Long cable runs are more susceptible to EMI pickup than short cable runs.

5. In extremely high EMI environments, the use of external EMI suppression devices such as Ferrite Suppression Cores for signal and control cables is effective. The following EMI suppression devices (or equivalent) are recommended:

Fair-Rite part number 0443167251 (Red Lion Controls #FCOR0000)

Line Filters for input power cables:

Schaffner # FN2010-1/07 (Red Lion Controls #LFIL0000)

6. To protect relay contacts that control inductive loads and to minimize radiated and conducted noise (EMI), some type of contact protection network is normally installed across the load, the contacts or both. The most effective location is across the load.

a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide varistor (MOV) across an AC inductive load is very effective at reducing EMI and increasing relay contact life.

b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor switch, care must be taken not to exceed the breakdown voltage of the transistor when the load is switched. One of the most effective ways is to place a diode across the inductive load. Most

Red Lion products with solid state outputs have internal zener diode protection. However external diode protection at the load is always a good design practice to limit EMI. Although the use of a snubber or varistor could be used.

Red Lion part numbers: Snubber: SNUB0000

Varistor: ILS11500 or ILS23000

COMMUNICATING

 

WITH

 

THE

 

CONTROLLER

CONFIGURING

 

AN

 

EDGE

 

CONTROLLER

The Controller is configured using Crimson ® software. Crimson software is available as a no charge download from Red Lion’s website.

Crimson updates for new features and drivers are posted on the website as they become available. By configuring the Edge Controller using the latest Crimson version, you are assured that your unit has the most up to date feature set. Crimson software can configure the controller through the RS232 PGM port, USB port, ethernet port or SD card.

The USB port is connected using a standard USB cable with a Type B connector. The driver needed to use the USB port will be installed as part of Crimson configuration.

The RS232 PGM port uses a programming cable made by Red Lion to connect to the DB9 COM port of your computer. If you choose to make your own cable, use the “Graphite Edge Controller Port Pin Out Diagram” for wiring information.

The SD card can be used to program a controller by placing a configuration file and firmware on the SD card. The card is then inserted into the target controller and powered. Refer to the Crimson literature for more information on the proper names and locations of the files.

SYSTEM LEDs

COLOR

GREEN (STS)

GREEN (SD)

STATUS

Bootloader/Power

File system SD Card

Released 2018-11-30

7. Care should be taken when connecting input and output devices to the instrument. When a separate input and output common is provided, they should not be mixed. Therefore a sensor common should NOT be connected to an output common. This would cause EMI on the sensitive input common, which could affect the instrument’s operation.

Visit www.redlion.net/emi for more information on EMI guidelines,

Safety and CE issues as they relate to Red Lion products.

8. For GEXRACK1 connection, recommend Tripp Lite Model: U023-006 6 ft cable.

I/O

 

MODULE

 

INSTALLATION

The physical order of all installed modules must match the modules order as set in Crimson database. Torque screws to 6.0 pound-force inch

[96 ounce-force inch] (0.68 Nm).

WARNING: Disconnect all power to the unit before installing or removing modules.

USB HOST LEDs

COLOR

OFF

RED

GREEN

STATUS

Not operational

Error

Normal operation

REMOVE RUBBER

MODULE PLUG

USB,

 

DATA

 

TRANSFERS

 

FROM

 

THE

 

SD

 

CARD

WARNING - DO NOT CONNECT OR DISCONNECT CABLES

WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE

NON-HAZARDOUS.

In order to transfer data from the SD card via the USB port, a driver must be installed on your computer. This driver is installed with Crimson software and is located in the folder C:\Program Files\Red Lion

Controls\Crimson 3.0\Device\ after installation. This may have already been accomplished if your controller was configured using the USB port.

Once the driver is installed, connect the controller to your PC with a

USB cable, and follow “Mounting the SD” instructions in the Crimson 3.0

user manual.

-4-

  Released 2018-11-30

INSERTION/REMOVAL

 

OF

 

THE

 

SD

 

CARD

Insert the SD card into the slot provided with the card oriented as shown.

The card is inserted properly when the end of the card is flush with the Edge

Controller case. To remove the SD card, push in slightly on the card.

Warning: Do not remove the SD card while power is applied.

Bulletin No. GRAC1-D

Drawing No. LP0994

RS422/485

 

COMMS

 

PORT

The controller has two RS422/485 ports. These ports can be configured to act as either RS422 or RS485.

RS422/485 4-WIRE

CONNECTIONS

RS485 2-WIRE

CONNECTIONS

5V

5V

130K

130K 7

1

TxB

7

1

TxB

TX/RX

TX

130K

8

2

TxA

130K

8

2

TxA

5 TxEN (OC)

5 TxEN (OC)

6 COMM

5V

130K

RX

130K

4 RxB

3 RxA

6 COMM

CABLES

 

AND

 

DRIVERS

Red Lion has a wide range of cables and drivers for use with many different communication types. A list of these drivers and cables along with pin outs is available from Red Lion’s website. New cables and drivers are added on a regular basis. If making your own cable, refer to the “Port Pin Outs” that corresponds to your specific model for wiring information.

ETHERNET

 

COMMUNICATIONS

Ethernet communications can be established at either 10 BASE-T or

100 BASE-TX. The Graphite unit’s RJ45 jack is wired as a NIC (Network

Interface Card). It auto-detects remote transmit and receive pairs and correctly assigns the transmit and receive pairs. This feature enables the user to use whichever type of cable (cross-over or straight) is available.

The Ethernet connector contains two LEDs. A yellow LED in the upper right, and a green LED in the upper left. The LEDs represent the following statuses:

LED COLOR

YELLOW solid

YELLOW flashing

GREEN (OFF)

GREEN (ON)

DESCRIPTION

Link established.

Data being transferred.

10 BASE-T Communications

100 BASE-TX Communications

A 12-digit MAC address label is provided for each Ethernet port. Refer to the Crimson manual and Red Lion’s website for additional information on Ethernet communications.

RS232

 

PORTS

 

The Edge Controller has a single RS232 port. The port can be used for either master or slave protocols with any

Graphite configuration.

GRAPHITE RS232 TO A PC

Gxx:

RJ12

Name

PC:

DB9

Name

4

5

2

COMM

Tx

Rx

N/C

1

2

3

4

DCD

Rx

Tx

DTR

3

1

6

COMM

N/C

CTS

RTS

N/C

7

8

5

6

9

GND

DSR

RTS

CTS

RI

Note: All Red Lion devices connect A to A and B to B. Refer to www.redlion.net

for additional information.

Examples

 

of

 

RS485

 

2

Wire

 

Connections

GRAPHITE TO RED LION RJ11

Gxx:RJ45 Name RLC:RJ11 Name

5 TxEN 2 TxEN

6 COMM 3 COMM

1

2

TxB

TxA

5

4

B-

A+

DH485

 

COMMUNICATIONS

  

The Graphite Edge Controller’s RS422/485 COMMS port can also be used for Allen Bradley DH485 communications.

GRAPHITE TO AB SLC 500

RJ45: RLC Name RJ45: A-B Name

1

2

TxB

TxA

1

2

A

B

3, 8

4, 7

5

6

4, 7

3, 8

RxA

RxB

TxEN

COMM

TxB

TxA

-

-

5

4

-

-

24V

COMM

TxEN

SHIELD

COMM

24V

-5-

  Bulletin No. GRAC1-D

Drawing No. LP0994

USB

TYPE B

STATUS LED

STATUS

USB HOST

STATUS

ETHERNET 1

(NIC)

ETHERNET 2

(NIC)

GRAPHITE EDGE CONTROLLER PORT PIN OUTS

RTS (PIN 6)

Tx

COMM

COMM

Rx

CTS (PIN 1)

TxA (PIN 8)

TxB

COMM

TxEN

RxB

RxA

TxA

TxB (PIN 1)

TxA (PIN 8)

TxB

COMM

TxEN

RxB

RxA

TxA

TxB (PIN 1)

RS232

PGM PORT

RS485 - A

COMMS PORT

RS485 - B

COMMS PORT

SD STATUS LED

FACTORY RESET BUTTON

Released 2018-11-30

POWER

CONNECTOR

SOFTWARE/UNIT

 

OPERATION

CRIMSON ®

 

SOFTWARE

Crimson software is available as a no charge download from Red

Lion’s website. The latest version of the software is always available from the website, and updating your copy is free.

FACTORY

 

RESET

 

BUTTON

The factory reset button is located on the front of the unit. Refer to

Crimson 3 System Menu Technical Note at www.redlion.net/TNIA22 for access procedure and available options.

GRAPHITE

 

TROUBLESHOOTING

If for any reason you have trouble operating, connecting, or simply have questions concerning your new Graphite unit, contact Red Lion’s technical support.

Email: [email protected]

Website: www.redlion.net

Inside US: +1 (877) 432-9908

Outside US: +1 (717) 767-6511

BATTERY

 

&

 

TIME

 

KEEPING

 

WARNING - EXPLOSION HAZARD - DISCONNECT POWER AND

ENSURE THE AREAS IS KNOWN TO BE NON-HAZARDOUS

BEFORE SERVICING/REPLACING THE UNIT AND BEFORE

INSTALLING OR REMOVING I/O WIRING AND BATTERY.

A battery is used to keep time when the unit is without power. Typical accuracy (at 25°C) of the time keeping is less than one minute per month drift. This battery does not affect the unit’s memory, all configurations and data is stored in non-volatile memory.

Changing   the   Battery

To change the battery, first remove power to the unit. Remove all cables from the unit and any external module if installed. Remove the four

TORX screws holding the metal cover to the unit, two per side. Slide the metal cover forward to gain access to the battery. Remove the old battery* from the holder and replace with the new battery. Replace metal cover with the four TORX screws. Reinstall external module if equipped, reconnect cables and re-apply power. Using Crimson software, enter the correct time and date.

Remove 4 Torx

T10 screws

* Please note that the old battery must be disposed of in a manner that complies with your local waste regulations. The battery must not be disposed of in fire, or in a manner whereby it may be damaged and its contents could come into contact with human skin.

The battery used by the Graphite Edge Controller is an industrial temperature grade (-40°C to 85°C) lithium type BR2032.

-6-

 

Released 2018-11-30 Bulletin No. GRAC1-D

Drawing No. LP0994

This page intentionally left blank

-7-

  Bulletin No. GRAC1-D

Drawing No. LP0994

LIMITED WARRANTY

(a) Red Lion Controls Inc., (the “Company”) warrants that all Products shall be free from defects in material and workmanship under normal use for the period of time provided in “Statement of Warranty Periods” (available at www.redlion.net) current at the time of shipment of the Products (the “Warranty Period”). EXCEPT FOR THE ABOVE-

STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE

PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR A

PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY

RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE OF

PERFORMANCE, USAGE OF TRADE OR OTHERWISE.

Customer shall be responsible for determining that a

Product is suitable for Customer’s use and that such use complies with any applicable local, state or federal law.

(b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer’s failure to store, install, commission or maintain the Product according to specifications; (ii) Customer alters or repairs such Product without the prior written consent of Company.

(c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if

Company so requests, Customer shall, at Company’s expense, return such Product to Company.

(d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER’S SOLE AND EXCLUSIVE

REMEDY AND COMPANY’S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH

IN PARAGRAPH (a).

-8-

Released 2018-11-30

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement