Installation Instructions _____________ RKS Series Retrofit Kits

PRODUCT IDENTIFICATION

Product Models: All RKS Series Linear LED Retrofit Kits.

Product Description: LED retrofit kit, w/magnetic LED strip(s) and driver.

Models RKS1420, RKS2420, RKS2430, RKS3430, RKS2440, RKS3440, RKS2450, and RKS3450 - Suitable for field installation in any recessed linear fluorescent luminaire with minimum nominal overall dimensions of 48 in. long x 5 in. wide, by 1.5 in. deep .

Models RKS2220, RKS3220, RKS2230, and RKS3230 - Suitable for field installation in any recessed linear fluorescent luminaire with minimum nominal overall dimensions of 24 in. long x 5 in. wide, by 1.5 in. deep .

RKS MODEL NOMENCLATURE

RKSXXXX-XX where:

RKS = Retrofit Kit Standard

4 th digit = “1”, “2”, or “3”, indicating the number of linear LED packages, or “strips”.

5 th digit = “2” or “4”, indication nominal length of linear LED packages, or “strips”.

6 th digit = “20”, “30”, “40”, or “50”, indicating nominal system wattage

7 th and 8 th digit = “30”, “40,” or “50”, indicating nominal LED CCT or “Color Temperature”

ELECTRICAL SPECIFICATIONS:

Input voltage: 90-277VAC, 50-60Hz

Output voltage: 30-42VDC, (see Table 1)

SUITABLE FOR DAMP LOCATIONS

Classification Mark: LED RETROFIT LUMINAIRE CONVERSION FOR USE ONLY WITH LINEAR

FLUORESCENT LUMINAIRES IN ACCORDANCE WITH THE INSTRUCTIONS

PROVIDED WITH THIS RETROFIT KIT, E490740

COMPONENTS INCLUDED IN THIS KIT:

1.

(1) LED Driver with magnetic back and quick-connect output harness

2.

(1, 2 or 3) LED light strips with magnetic back and quick-connect plug (see Model Nomenclature paragraph on

Page 1)

3.

(1) “Y” harness or “Tri” harness with quick-connects to connect driver to LED strips

4.

Installation and Safety Instructions

5.

(1) Retrofit Kit Luminaire label with identifying model numbers

Table 1

1

Model

No.

Input

Volts(V)

RKS1420 120/277

RKS2420 120/277

RKS2430 120/277

RKS3430 120/277

RKS2440 120/277

RKS3440 120/277

RKS2450 120/277

RKS3450 120/277

RKS2220 120/277

RKS3220 120/277

RKS2230 120/277

Frequency

(Hz)

50/60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

System

Watts(W)

20

20

30

30

40

40

50

50

20

20

30

Output

Current(mA)

480

480

720

720

960

960

1200

1200

480

480

720

LED

Modules

1

2

2

3

2

3

2

3

2

3

2

LED

Drivers

1

1

1

1

1

1

1

1

1

1

1

Location Type

Damp

Damp

Damp

Damp

Damp

Damp

Damp

Damp

Damp

Damp

Damp

RKS3230 120/277 50/60 30 720 3 1 Damp

INSTALLATION INSTRUCTIONS

CRITICAL SAFETY NOTE: Read all instructions before beginning installation

WARNING – RISK OF FIRE OR ELECTRIC SHOCK. INSTALLATION OF THIS RETROFIT ASSEMBLY

REQUIRES A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE

LUMINAIRE ELECTRICAL SYSTEM AND THE HAZARD INVOLVED. IF NOT QUALIFIED, DO NOT

ATTEMPT INSTALLATION. CONTACT A QUALIFIED ELECTRICIAN

WARNING – RISK OF FIRE OR ELECTRIC SHOCK. INSTALL THIS KIT ONLY IN LUMINAIRES THAT

HAVE THE CONSTRUCTION FEATURES AND DIMENSIONS SPECIFIED, AND WHERE THE INPUT

RATING OF THE RETROFIT KIT DOES NOT EXCEED THE INPUT RATING OF THE LUMINAIRE

WARNING – RISK OF FIRE OR ELECTRIC SHOCK. LUMINAIRE WIRING AND ELECTRICAL PARTS

MAY BE DAMAGED WHEN DRILLING FOR INSTALLATION OF LED RETROFIT KIT. CHECK FOR

ENCLOSED WIRING AND COMPONENTS

WARNING – TO PREVENT WIRING DAMAGE OR ABRASION, DO NOT EXPOSE WIRING TO EDGES

OF SHEET METAL OR OTHER SHARP OBJECTS

THE RETROFIT IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF

THE COMBINATION SHALL BE DETERMINED BY AUTHORITIES HAVING JURISDICTION

 BRANCH-CIRCUIT CONDUCTORS WITHIN 75 MM (3 IN.) OF A LED DRIVER SHALL HAVE AN

INSULATION TEMPERATURE RATING NOT LOWER THAN 90°C (194°F) UNLESS SUPPLYING A

LUMINAIRE MARKED AS SUITABLE FOR A DIFFERENT INSULATION TEMPERATURE

2

INSTALLATION PROCEDURE:

1.

Shut off power to luminaire

2.

Open or remove luminaire lens or grille (if present).

3.

Remove fluorescent lamps and ballast cover(s). (See figure 1)

4.

Confirm that the branch circuit voltage of your electrical system is compatible with this kit

5.

Disconnect input power from ballast and remove existing ballast, sockets, brackets and socket wiring.

(see figure 2)

6.

Place driver inside the ballast box, allowing the magnet to hold it in place temporarily. (see figure 3)

7.

Connect power input wires to the input wires on the LED driver. IMPORTANT NOTE: TWIST-ON OR

PUSH-ON CONNECTORS MUST BE RATED FOR A MINIMUM OF 600V (see figure 4)

8.

Permanently secure driver to the luminaire body with #8 x ½” or shorter self-tapping screws, through the mounting flanges on the driver case. Be certain that there are no power wires in the path of the screws.

(see figure 5)

9.

Be certain that “Line” wire is connected to the black input wire of driver, and that “Neutral” wire is connected to the white input wire of driver.

10.

Be certain that the ground wire of the power circuit remains connected to the body of the luminaire.

11.

Connect the LED driver output to the “Y” harness, and reinstall the ballast cover(s), covering the driver and all electrical connections. Route the harnesses out the end of the ballast cover, in such a way as to not expose them to any sharp edges, or pinch them between any metal surfaces. (see figure 6)

12.

One at a time, plug the LED strip(s) into the “Y” harnesses and insert them into/onto the body of the luminaire. (see figure 7).

13.

At this time, you may temporarily turn on power to test retrofitted luminaire

14.

Permanently affix the Retrofit Kit label to the body of the luminaire in a conspicuous place, where it will be plainly visible when the fixture is opened for service

15. Close or reinstall the lens/grille/cover and restore power to luminaire