advertisement
Temperature Controller
SA200
Initial Setting Manual
®
RKC INSTRUMENT INC.
IMR01D03-E4
All Rights Reserved, Copyright 1999, RKC INSTRUMENT INC.
Thank you for purchasing the RKC instrument. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
: This mark indicates precautions that must be taken if there is danger of electric shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken, damage to the instrument may result.
!
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
!
WARNING
An external protection device must be installed if failure of this instrument could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
IMR01D03-E4 i-1
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or equipment.
All wiring must be in accordance with local codes and regulations.
To prevent instrument damage or failure, protect the power line and the input/output lines from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front panel with a hard object.
NOTICE
This manual is written for RKC service engineers or qualified technicians. This manual is also prepared especially for readers who already have a fundamental knowledge of electricity, control, computer and communication.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC. i-2
IMR01D03-E4
CONTENTS
Page
1. MODE TRANSFER ............................................................... 1
1.1 Transfer to Engineering Mode .........................................................................1
1.2 End of Engineering Mode ................................................................................3
2. SETTING............................................................................... 4
2.1 Display Flowcharts in Mode ............................................................................4
2.2 Example of Changing the S etting....................................................................5
2.3 Attention Items in Setting................................................................................7
2.4 Details of Each Function Block .....................................................................12
2.4.1 F10 (Setting for display screen) ........................................................................ 12
2.4.2 F21 (Setting for input)........................................................................................ 14
2.4.3 F30 (Setting for output) ..................................................................................... 21
2.4.4 F41 (Setting for alarm 1) ................................................................................... 23
2.4.5 F42 (Setting for alarm 2) ................................................................................... 25
2.4.6 F51 (Setting for control action) .......................................................................... 27
2.4.7 F61 (Communication protocol selection)........................................................... 27
2.4.8 F71 (Setting change rate limiter setting) ........................................................... 28
2.4.9 F91 (Displayed for maintenance information) ................................................... 28
3. INITIALIZE COMMUNICATION DATA............................... 29
IMR01D03-E4 i-3
MEMO
1. MODE TRANSFER
Initialization is to set parameters relating to instrument specifications (input type, input range, alarm type, etc.) and those relating to instrument characteristics (setting limiter, alarm differential gap, etc.).
1.1 Transfer to Engineering Mode
1. Turn on the power to this instrument. Thus, the input type, input range and PV/SV display change in this order.
2. Press the SET key for two seconds change the instrument to parameter setting mode.
For details on parameter setting mode, see SA200 Instruction Manual (IMR01D01-E ) .
3. Press the SET key to change to the set data lock function display ( LCK ).
4. Press the <R/S key to blink the thousands digit on the set value (SV) display.
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Set data lock function display
5. Press the UP key to change 0 to 1 in the thousands digit.
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Set data lock function display
Set value
0: Engineering mode locked
1: Engineering mode unlocked
Continued on the next page.
IMR01D03-E4
1
2
1. TRANSFER TO MODE
6. Press the SET key to change to the next parameter. Thus, the data in engineering mode is unlocked.
PV SV PV SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
AT
OUT1
OUT2
SV2
ALM1
ALM2
SET
SA200
R/S
Set data lock function display
SET
SA200
R/S
AL1 setting display
The parameter to be displayed varies depending on the specification.
7. Press the SET key for two seconds to change to the PV/SV display mode.
8. Press the <R/S key for one second to change the operation mode from RUN mode to STOP mode.
PV SV
SET
SA200
R/S
AT
OUT1
OUT2
STOP mode display
SV2
ALM1
ALM2
Before the setting is changed in engineering mode, it is necessary to set the operation mode to the STOP mode.
If “Set value” is set to 0002 (no selection from RUN to STOP by the front key can be made) by SPCH (STOP display selection) corresponding to F10 (P. 12), perform the operation in item “ 9.
” instead of performing the operation in item “ 8.
”
The operation in item “ 9.
” forcibly results in the STOP state.
The parameter to be displayed varies depending on the specification.
9. Press the <R/S key while pressing the SET key for two seconds to change the instrument to engineering mode. Thus, the symbol F10 for function block is displayed first.
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
STOP mode display
SV2
ALM1
ALM2
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Function block symbol displayed engineering mode
IMR01D03-E4
1. TRANSFER TO MODE
1.2 End of Engineering Mode
1. Transfer to function block symbol display ( F ) after each parameter is set.
2. Press the <R/S key while pressing the SET key for two seconds transfer to PV/SV display mode.
3. Press the SET key for two seconds in the PV/SV display mode state to transfer to parameter setting mode.
4. Press the SET key to transfer to the set data lock function display ( LCK ).
5. Press the <R/S key to blink the thousands digit on the set value (SV) display .
See 1.1 Transfer to Engineering Mode (P.1) .
6. Press the DOWN key to set the numeric value corresponding to the thousands digit to 0 from 1 .
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Set data lock function display
7. Press the SET key to transfer to the next parameter. As a result, the engineering mode lock state setting becomes effective.
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Set data lock function display
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
AL1 setting display
SV2
ALM1
ALM2
The parameter to be displayed varies depending on the specification.
IMR01D03-E4 3
2. SETTING
2.1 Display Flowcharts in Mode
Display flowcharts in engineering mode are shown in the following. For the details of engineering mode selection, see 1.1 Transfer to Engineering Mode (P. 1).
Display flowcharts
Parameter setting mode PV/SV display mode
Press the SET key for 2 seconds (Press the <R/S key for 1 second)
(F10)
(F21)
(F30)
(F41)
(F42)
(F51)
(F61)
(F51)
(F91)
STOP display screen selection
(SPCH)
Input type selection
Monitor display configuration selection
(dCHG)
Display unit selection
Set the STOP mode.
Press the <R/S key while pressing the SET key for 2 seconds
MV display selection
Engineering mode
Return to the
F10
(MVd)
Decimal point position setting
Setting limiter
[high limit]
Setting limiter
[low limit]
Return to the F21
(InP)
Selection of output logic calculation
(UnIT)
Return to the
F30
(LoGC)
(PGdP) (SLH) (SLL)
Alarm 1 type selection
(AS1)
Alarm 2 type selection
Alarm 1 hold action
(AHo1)
Alarm 2 hold action
Alarm 1 differential gap
(AH1)
Alarm 2 differential gap
Alarm 1 process abnormality action
(AEo1)
Alarm 2 process abnormality action
Return to the
F41
Return to the
F42
(AS2)
Control action type selection
(AHo2)
ON/OFF action differential gap
(AH2) (AEo2)
Return to the
F51
(oS1)
Communication protocol selection
(oH)
Return to the
F61
(CMPS)
Setting change rate limiter Used/Unused
(SVrS)
ROM version
Setting change rate limiter time
Return to the
F71
(SVrT)
Integrated operating time
Holding peak ambient temperature
Return to the
F91
(E227) (WT) (TCJ)
Explaining the arrow mark
: Press the SET key
: Press the UP key or
DOWN key
2. SETTING
2.2 Example of Changing the Setting
When the display unit shows InP (Input type selection) in function block F21 , the following procedure is for changing the input type from “K” to “J.”
1. Change the instrument to the function block symbol display.
See 1.1 Transfer to Engineering Mode (P. 1) .
PV SV
SET
SA200
R/S
AT
OUT1
OUT2
SV2
ALM1
ALM2
Function block symbol display
2. As InP belongs to the F21 , press the UP key to change the display from F10 to F21 .
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Function block symbol display
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Function block symbol display
3. Press the SET key to change to InP .
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
SV2
ALM1
ALM2
Function block symbol display
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
Input type selection
SV2
ALM1
ALM2
Continued on the next page.
IMR01D03-E4
5
2. SETTING
4. Press the UP key to enter 1 in the units digit of the set value (SV) display.
AT
OUT1
OUT2
SV2
ALM1
ALM2
SET R/S
SA200
Input type selection
InP (Input type selection)
AT
OUT1
OUT2
SV2
ALM1
ALM2
Set value
0 0
0 1
0 2
SET
SA200
R/S
Input type selection
5. Press the SET key to change to the next parameter. Thus, the set value is registered.
Input type
K
J
R
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
Input type selection
SV2
ALM1
ALM2
PV
SET
SA200
R/S
SV
AT
OUT1
OUT2
Display unit selection
SV2
ALM1
ALM2
6
IMR01D03-E4
2. SETTING
2.3 Attention Items in Setting
If any of the following settings is changed, the relevant set value is initialized or is automatically converted.
Before changing the set values, always record all of them (SV setting mode, parameter setting mode and engineering mode).
After changing the set values, always check all of them (SV setting mode, parameter setting mode and engineering mode).
When the input type or engineering unit is changed
The set value is initialized.
Default
Temperature input
Voltage/current inputs
Decimal point position (PGdF) 0 (Without decimal point)
Setting limiter [high limit] (SLH) Maximum settable value
Setting limiter [low limit] (SLL)
Alarm 1 hold action selection
(AHo1)
Minimum settable value
1
100.0
0.0
0 (Without alarm hold action)
Engineering mode Alarm 1 differential gap (AH1)
Alarm 1 process abnormality action
(AEo1)
Alarm 2 hold action selection
(AHo2)
2 ° C [ ° F] 0.2 % of span
Alarm 1 not provided or LBA: 0 (Normal)
Alarm 1 provided: 1 (Forcibly turned on)
0 (Without alarm hold action)
Alarm 2 differential gap (AH2)
Alarm 2 process abnormality action
(AEo2)
2 ° C [ ° F] 0.2 % of span
Alarm 2 not provided: 0 (Normal)
Alarm 2 provided: 1 (Forcibly turned on)
ON/OFF action differential gap
(oH)
2 ° C [ ° F] 0.2 % of span
Alarm 1 set value (ALM1)
Alarm 2 set value (ALM2)
Control loop break alarm (LBA)
LBA deadband (LBD)
Heat-side proportional band (P)
Integral time (I)
Parameter setting Derivative time (D)
50 ° C [ ° F] 5.0 % of span
8.0 minutes
0 ° C [ ° F] 0.0
30 ° C [ ° F] 3.0 % of span
240 seconds
60 seconds mode Anti-reset windup (ARW) 100 %
Cool-side proportional band (Pc)
PV bias (Pb)
Digital filter (dF)
100 %
0 ° C [ ° F] 0.0
0 second (off)
Continued on the next page.
IMR01D03-E4 7
2. SETTING
Continued from the previous page.
Default
Parameter setting mode
Analog output scale high (AHS)
Analog output scale low (ALS)
PV/SV display mode,
Setting change rate limiter [up]
(SVrU)
Setting change rate limiter [down]
(SVrd)
Set value (SV) STEP function not provided
SV setting mode Set value (SV1) STEP function
Set value (SV2) provided
Maximum settable value inputs
100.0
Minimum settable value
0.0
0 ° C [ ° F] 0.0
0
0
°
°
C [
C [
°
°
F] 0.0
F] 0.0
8
IMR01D03-E4
2. SETTING
When the setting limiter is changed
If the setting limiter [high limit] (SLH) or setting limiter [low limit] (SLL) is changed as follows, the related set values are changed. (See Table 1)
Only for temperature input:
• If SLH is set to SLH < SLL, it is changed to SLH=SLL.
Example : If SLL is set to 200 with SLH set to 100, SLH is changed to 200.
• If SLL is set to SLH < SLL, it is changed to SLH=SLL.
Example : If SLH is set to 100 with SLL set to 200, SLL is changed to 100.
For temperature input, voltage/current inputs:
If the setting is made so that the span becomes narrower, there may be a case where the related set value becomes smaller or 0 .
Table 1
Mode Description
Engineering mode
Alarm 1 differential gap (AH1)
Alarm 2 differential gap (AH2)
ON/OFF action differential gap (oH)
Alarm 1 set value (ALM1)
Alarm 2 set value (ALM2)
LBA Deadband (LBD)
Parameter setting mode
PV/SV display mode,
SV setting mode
Heat-side proportional band (P)
PV bias (Pb)
Analog output scale high (AHS)
Analog output scale low (ALS)
Setting change rate limiter [up] (SVrU)
Setting change rate limiter [down] (SVrd)
Set value (SV)
Set value (SV1)
Set value (SV2)
STEP function not provided
STEP function provided
IMR01D03-E4 9
2. SETTING
When the position of the decimal point is changed
The set value is automatically converted.
• After the position of the decimal point is changed, conduct automatic conversion so that the following values may not be changed.
Engineering mode: Setting limiter [high limit] (SLH)
Setting limiter [low limit] (SLL)
Parameter setting mode:
Alarm 1 differential gap (AH1)
Alarm 2 differential gap (AH2)
ON/OFF action differential gap (oH)
Alarm 1 set value (ALM1)
Alarm 2 set value (ALM2)
LBA deadband (LBD)
Heat-side proportional band (T)
Deadband (dB)
PV bias (Pb)
Analog output scale high (AHS)
Analog output scale low (ALS)
Setting change rate limiter [up] (SVrU)
Setting change rate limiter [down] (SVrd)
PV/SV display/SV setting mode: Set value (SV) [STEP function not provided]
Set value (SV1)
Set value (SV2) [STEP function provided]
Example : When the position of the decimal point changed from 0 to 1 with SLH set to 800 ° C.
(SLH) (SLH)
Changed from 800 to 800.0
.
• If the setting range is not between − 1999 and + 9999 regardless of the position of the decimal point, it is limited by the range from − 1999 to + 9999.
Example : When SLH is 1372 ° C with no decimal position, and the decimal position is changed from 0 to 1 (one decimal position), SLH will become 999.9.
(SLH)
• If the number of digits below the decimal point is changed in the decreasing direction, the decreased number of digits is omitted.
Example : When SHL is 99.99 with two decimal positions, and the decimal position is changed from
2 to 0 , SLH will become 99 by discarding the digits below the decimal point.
(SLH)
(SLH)
(SLH)
10
IMR01D03-E4
2. SETTING
When the type of alarm is changed
The set value is initialized.
Temperature input
Voltage/current inputs
Engineering mode
Parameter setting mode
Alarm 1 hold action selection
Alarm 1 differential gap
Alarm 1 process abnormality action
Alarm 2 hold action selection
Alarm 2 differential gap
Alarm 2 process abnormality action
Alarm 1 set value
Alarm 2 set value
2 ° C [ °
0 (Without alarm hold action)
F] or 2.0 ° C [ ° F] 0.2 % of span
Alarm 1 not provided or LBA: 0 (Normal)
Alarm 1 provided: 1 (Forcibly turned on)
0 (Without alarm hold action)
2 ° C [ ° F] or 2.0 ° C [ ° F] 0.2 % of span
Alarm 2 not provided: 0 (Normal)
Alarm 2 provided: 1 (Forcibly turned on)
50 ° C [ ° F] or 50.0 ° C [ ° F] 5.0 % of span
IMR01D03-E4 11
2. SETTING
2.4 Details of Each Function Block
2.4.1 F10 (Setting for display screen)
(1) SPCH (STOP display screen selection)
Factory set value: 0000
Set value Description
0 STOP is displayed on the PV display unit. (TYPE 1)
1 STOP is displayed on the SV display unit. (TYPE 2)
2 No selection from RUN to STOP by the front key can be made. *
0 0 0 “000 ” Fixed
* If “Set value” is set to 0002, no selection from RUN to STOP can be made, but selection from STOP to RUN can be made. In addition, RUN/STOP can be selected via communication or by contact input regardless of the SPCH setting.
Displays in the STOP mode become as follows.
(SV) (SV)
TYPE 1
(SPCH=0)
(KSTP) (dSTP)
(KSTP) (dSTP)
TYPE 2
(SPCH=1)
(PV) (PV)
(2) dCHG (Monitor display configuration selection)
(SToP)
(PV)
(SV)
(SToP)
Factory set value: 0000
Set value Description
1 Only PV display
2 Only SV display
0 0 0 “000 ” Fixed
Displays become as follows.
PV/SV display
(dCHG=0)
Only PV display
(dCHG=1)
(PV)
(PV)
Only SV display
(dCHG=2)
(SV)
(SV)
TYPE 1
(SPCH=0)
(SV)
(SToP)
(SToP)
(SToP)
TYPE 2
(SPCH=1)
(SToP)
(PV)
(PV)
(SV)
(SToP)
(SToP)
12
IMR01D03-E4
2. SETTING
(3) MVd (MV display selection)
For the SA200 Z-1045 specification, always set “1: MV display provided.”
Factory set value: 0000
Set value
0 MV display not provided
1 MV display provided
0 0 0 “000 ” Fixed
Description
IMR01D03-E4
13
2. SETTING
2.4.2 F21 (Setting for input)
(1) InP (Input type selection)
Set value
0 0
0 1
0 2
0 3
0 4
0 5
0 6
0 7
0 8
0 9
1 0
1 1
K
J
R
S
B
E
N
T
W5Re/W26Re
U
L
Factory set value varies depending on the input type.
Input type
(TC)
1 2
1 3
Pt100
JPt100
1
1
1
4
5
6
1 4
1 5
0 to 5 V DC
1 to 5 V DC
0 to 10 V DC
0 to 20 mA DC
4 to 20 mA DC
Voltage input 1
Current input 1, 2
0 0 “00 ” Fixed
1 Input type (TC/RTD to voltage/current inputs or voltage/current inputs to TC/RTD) cannot be changed because the hardware is different.
2 For the current input specification, a resistor of 250 Ω must be connected between the input terminals.
See 2.3 Attention Items in Setting (P. 7) .
14
IMR01D03-E4
2. SETTING
(2) UnIT (Display Unit selection)
Set value
Factory set value: 0000
Description
0 0 0 “000 ” Fixed
The invalidity in case of the voltage/current inputs.
See 2.3 Attention Items in Setting (P. 7) .
(3) PGdP (Decimal point position setting)
Factory set value varies depending on the instrument specification.
Set value
0 No digit below decimal point (
1 1 digit below decimal point (
Description
. )
)
2 2 digits below decimal point ( .
)
3 3 digits below decimal point ( .
)
0 0 0 “000 ” Fixed
See 2.3 Attention Items in Setting (P. 7) .
IMR01D03-E4 15
2. SETTING
(4) SLH (Setting limiter [high limit])
Factory set value varies depending on the instrument specification.
Input type Setting range
K + 1372 ° C ( − 326 to + 2502 ° F)
− 199.9 to + 999.9 ° C ( − 199.9 to + 999.9 ° F)
J + 1200 ° C ( − 326 to + 2192 ° F)
R
S
− 199.9 to + 999.9 ° C ( − 199.9 to + 999.9 ° F)
0 to 1769 ° C (0 to 3216 ° F)
0 to 1769 ° C (0 to 3216 ° F)
TC
B
E
N
0 to 1820 ° C (0 to 3308 ° F)
0 to 1000 ° C (0 to 1832 ° F)
0 to 1300 ° C (0 to 2372 ° F)
0 to 999.9 ° C (0 to 999.9 ° F)
T + 400 ° C ( − 326 to + 752 ° F)
W5Re/W26Re
PL II
− 199.9 to + 400.0 ° C ( − 199.9 to + 752.0 ° F)
0 to 2320 ° C (0 to 4208 ° F)
0 to 1390 ° C (0 to 2534 ° F)
U + 600 ° C ( − 326 to + 1112 ° F)
L
− 199.9 to + 600.0 ° C ( − 199.9 to + 999.9 ° F)
0 to 900 ° C (0 to 1652 ° F)
(JIS/IEC)
199.9 to + 649.0 ° C ( − 199.9 to + 999.9 ° F)
Voltage 2
Current 2, 3
0 to 5 V DC
1 to 5 V DC
0 to 10 V DC
0 to 20 mA DC
− 1999 to + 9999
(programmable scale)
− 1999 to + 9999
4 to 20 mA DC (programmable scale)
1 IEC ( International Electrotechnical Commission ) is equivalent to JIS, DIN and ANSI .
2 In case of voltage/current inputs, SLH can be set below SLL.
3 For the current input specification, a resistor of 250 Ω must be connected between the input terminals.
Set the setting limiter [high limit] referring to the Input range table (P. 18) .
See 2.3 Attention Items in Setting (P. 7) .
16
IMR01D03-E4
2. SETTING
(5) SLL (Setting limiter [low limit])
Factory set value varies depending on the instrument specification.
Input type Setting range
K + 1372 ° C ( − 326 to + 2502 ° F)
− 199.9 to + 999.9 ° C ( − 199.9 to + 999.9 ° F)
J + 1200 ° C ( − 326 to + 2192 ° F)
R
S
− 199.9 to + 999.9 ° C ( − 199.9 to + 999.9 ° F)
0 to 1769 ° C (0 to 3216 ° F)
0 to 1769 ° C (0 to 3216 ° F)
TC
B
E
N
0 to 1820 ° C (0 to 3308 ° F)
0 to 1000 ° C (0 to 1832 ° F)
0 to 1300 ° C (0 to 2372 ° F)
0 to 999.9 ° C (0 to 999.9 ° F)
T + 400 ° C ( − 326 to + 752 ° F)
W5Re/W26Re
− 199.9 to + 400.0 ° C ( − 199.9 to + 752.0 ° F)
0 to 2320 ° C (0 to 4208 ° F)
PL II 0 to 1390 ° C (0 to 2534 ° F)
U + 600 ° C ( − 326 to + 1112 ° F)
L
− 199.9 to + 600.0 ° C ( − 199.9 to + 999.9 ° F)
0 to 900 ° C (0 to 1652 ° F)
(JIS/IEC)
199.9 to + 649.0 ° C ( − 199.9 to + 999.9 ° F)
Voltage 2
Current 2, 3
0 to 5 V DC
1 to 5 V DC
0 to 10 V DC
0 to 20 mA DC
− 1999 to + 9999
(programmable scale)
− 1999 to + 9999
4 to 20 mA DC (programmable scale)
1 IEC ( International Electrotechnical Commission ) is equivalent to JIS , DIN and ANSI .
2 In case of voltage/current inputs, SLH can be set below SLL.
3 For the current input specification, a resistor of 250 Ω must be connected between the input terminals.
Set the setting limiter [low limit] referring to the Input range table (P. 18) .
See 2.3 Attention Items in Setting (P. 7) .
IMR01D03-E4 17
2. SETTING
Input range table
TC
J
K
0 to 200 ° C
0 to 400 ° C
K01
K02
0 to 600 ° C K03
0 to 800 ° C K04
0 to 1000 ° C
0 to 1200 ° C
K05
K06
J
0 to 1372 ° C
0 to 100 ° C
K07
K13
0 to 300 ° C K14
0 to 450 ° C
0 to 500 ° C
K17
K20
− 199.9 to + 300.0 ° C
0.0 to 400.0 ° C
0.0 to 800.0 ° C
0.0 to 200.0 ° C
K08
K09
K10
K29
R
0.0 to 600.0 ° C
− 199.9 to + 800.0 ° C
0 to 800 ° F
0 to 1600 ° F
0 to 2502 ° F
20 to 70 ° F
0.0 to 800.0 ° F
− 199.9 to + 999.9 ° F
0 to 200 ° C
K37
K38
KA1
KA2
KA3
KA9
KA4
KB2
S
B
J01 E
0 to 400 ° C
0 to 600 ° C
0 to 800 ° C
0 to 1000 ° C
J02
I03
J04
J05
0 to 1200 ° C
0 to 450 ° C
− 199.9 to + 300.0 ° C
0.0 to 400.0 ° C
J06
J10
J07
J08
N
0.0 to 800.0 ° C J09
0.0 to 200.0 ° C J22
0.0 to 600.0 ° C J23
− 199.9 to + 600.0 ° C J30
0 to 800 ° F JA1
0 to 1600 ° F JA2
0 to 2192 ° F JA3
0 to 400 ° F JA6
0.0 to 800.0 ° F JB6
− 199.9 to + 999.9 ° F JB9
0 to 1600 ° C *
0 to 1769 ° C *
R01
R02
0 to 1350 ° C *
0 to 3200 ° F *
0 to 3216 ° F *
0 to 1600 ° C *
R04
RA1
RA2
S01
0 to 1769 ° C *
0 to 3200 ° F *
0 to 3216 ° F *
S02
SA1
RA2
400 to 1800 ° C B01
0 to 1820 ° C * B02
800 to 3200 ° F BA1
0 to 3308 ° F * BA2
0 to 800 ° C E01
0 to 1000 ° C E02
0 to 1600 ° F EA1
0 to 1832 ° F EA2
0 to 1200 ° C N01
0 to 1300 ° C N02
0.0 to 800.0 ° C N06
0 to 2300 ° F NA1
0 to 2372 ° F NA2
0.0 to 999.9 ° F NA5
* Accuracy is not guaranteed between 0 to 399 ° C (0 to 751 ° F)
Continued on the next page.
18
IMR01D03-E4
2. SETTING
Continued from the previous page.
Type
T
W5Re/
W26Re
PL II
Input range Code Type Input range Code
− 199.9 to + 400.0 ° C *
− 199.9 to + 100.0 ° C *
T01
T02
− 199.9 to + 600.0 ° C *
− 199.9 to + 100.0 ° C *
U01
U02
− 100.0 to + 200.0 ° C T03
TA2
U 0.0 to 400.0 ° C U03
−
0.0 to 350.0
199.9 to +
°
752.0
C T04
° F * TA1
199.9 to + 999.9 ° F * UA1
− 100.0 to + 200.0 ° F UA2
− 100.0 to + 200.0 ° F 0.0 to 999.9 ° F UA3
− 100.0 to + 400.0 ° F
0.0 to 450.0 ° F
0.0 to 752.0 ° F
TA3
TA4 L
TA5
0 to 2000 ° C W01
0 to 2320 ° C W02
0 to 400 ° C L01
0 to 800 ° C L02
0 to 800 ° F LA1
0 to 1600 ° F LA2
0 to 4000 ° F WA1
0 to 1300 ° C A01
0 to 1390 ° C A02
0 to 1200 ° C A03
0 to 2400 ° F AA1
0 to 2534 ° F AA2
* Accuracy is not guaranteed between − 199.9 to − 100.0 ° C ( − 199.9 to − 148.0 ° F)
IMR01D03-E4 19
2. SETTING
RTD
Voltage input
Pt100 (JIS/IEC)
JPt100 (JIS)
− 199.9 to + 649.0 ° C D01
− 199.9 to + 200.0 ° C D02
− 100.0 to + 50.0 ° C D03
− 100.0 to + 100.0 ° C D04
− 100.0 to + 200.0 ° C D05
0.0 to 50.0 ° C D06
−
0.0 to 100.0 ° C D07
0.0 to 200.0 ° C D08
0.0 to 300.0 ° C D09
0.0 to 500.0 ° C D10
− 199.9 to + 999.9 ° F DA1
− 199.9 to + 400.0 ° F DA2
− 199.9 to + 200.0 ° F DA3
− 100.0 to + 100.0 ° F DA4
− 100.0 to + 300.0 ° F DA5
0.0 to 100.0 ° F DA6
0.0 to 200.0 ° F DA7
0.0 to 400.0 ° F DA8
0.0 to 500.0 ° F DA9
− 199.9 to + 649.0 ° C P01
− 199.9 to + 200.0 ° C P02
− 100.0 to + 50.0 ° C P03
− 100.0 to + 100.0 ° C P04
100.0 to + 200.0
0.0 to 50.0 ° C P06
0.0 to 100.0 ° C P07
0.0 to 200.0 ° C P08
0.0 to 300.0 ° C P09
0.0 to 500.0 °
° C P05
C P10
Current input
0 to 5 V DC
0 to 10 V DC
1 to 5 V DC
0.0 to 100.0
401
501
601
0 to 20 mA DC *
4 to 20 mA DC *
0.0 to 100.0 701
801
* For the current input specification, a resistor of 250 Ω must be connected between the input terminals.
20
IMR01D03-E4
2. SETTING
2.4.3 F30 (Setting for output)
(1) LoGC (Output logic operation selection)
Match the setting with the instrument specification. Otherwise malfunction may result.
No heat-side or cool-side proportional cycle (T or t) corresponding to a parameter setting mode made may not be displayed depending on the selected output allocation code.
• Not displayed when no control output is selected.
• Not displayed when control output corresponds to current output.
Factory set value varies depending on the instrument specification.
Logic circuit number
OUT1 OUT2 Remarks
Control OR output of Alarm 1 and
Alarm 2 (Energized)
PID action + No Alarm function *
PID action + Alarm 1 *
PID action + OR output of
Alarm 1, Alarm 2 *
Heat/cool PID action *
(W or A type) output (In case of direct action or reverse action, it is OFF).
0 3 Control output Alarm 1 output
(De-energized)
Control AND output of Alarm 1 and
Alarm 2 (Energized)
Control OR output of Alarm 1 and
Alarm 2 (De-energized)
Control AND output of Alarm 1 and
Alarm 2 (De-energized)
0 7 Control output Not output
(The Alarm state can be checked via communication or by lamp lighting).
0 8 Control output Alarm 1 output (Energized)
(Alarm 2 can be checked via communication or by lamp lighting).
* Standard output when no output code is specified.
PID action + Alarm 1
PID action + Alarm 1, Alarm 2
PID action + Alarm 1, Alarm 2 or
Alarm 1 only
PID action + Alarm 1, Alarm 2
Continued on the next page.
IMR01D03-E4 21
2. SETTING
Continued from the previous page.
Factory set value varies depending on the instrument specification.
Logic circuit number
OUT1 OUT2
0 9 Alarm 1 output
(Energized)
Alarm 2 output
(Energized)
Alarm 1 +
Remarks
Alarm 2
(The PID operation can choose
(Energized)
Alarm 2 output
(De-energized) only F type.)
1 1 Alarm 1 output
(De-energized)
Alarm 2 output
(De-energized)
Control output output output
OR output of Alarm 1 and
Alarm 2 (Energized)
Transmission output + PID action
(Z-1033 specification)
Transmission output + Alarm 1,
Alarm 2 (Z-1033 specification) output output output
OR output of Alarm 1 and
Alarm 2 (De-energized)
AND output of Alarm 1 and
Alarm 2 (Energized)
AND output of Alarm 1 and
Alarm 2 (De-energized) output output
Alarm 1 output
(Energized)
Alarm 1 output
(De-energized)
Transmission output + Alarm 1
(Z-1033 specification) output (In case of direct action or reverse action, it is OFF).
0 “0 ” Fixed
Heat/cool PID action *
(W or A type)
(Z-1033 specification)
* Cool-side control output: Current output only
Heat-side control output: Relay contact output or voltage pulse output
22
IMR01D03-E4
2. SETTING
2.4.4 F41 (Setting for alarm 1)
(1) AS1 (Alarm 1 type selection)
Set value
Factory set value varies depending on the instrument specification.
Description
0 Alarm not provided
1 SV high alarm
2 SV low alarm
3 Process high alarm
4 Process low alarm
5 Deviation high alarm
6 Deviation low alarm
7 Deviation high/low alarm
9 Control loop break alarm ( LBA)
0 0 0 “000 ” Fixed
See 2.3 Attention Items in Setting (P. 7) .
(2) AHo1 (Alarm 1 hold action selection)
Factory set value varies depending on the instrument specification.
Set value Description
0 Without alarm hold action
1 Effective when the power is turned on, or operation is changed from STOP to
RUN.
2 Effective when the power is turned on, or operation is changed from STOP to
RUN or the SV is changed.
0 0 0 “000 ” Fixed
The alarm hold action function can not be added to the SV alarm.
See 2.3 Attention Items in Setting (P. 7) .
IMR01D03-E4
23
2. SETTING
(3) AH1 (Alarm 1 differential gap setting)
Setting range:
TC and RTD inputs, Voltage/current inputs: 0 (0.0) to span
Factory set value:
TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F]
Voltage/current inputs: 0.2 % of span
See 2.3 Attention Items in Setting (P. 7) .
(4) AEo1 (Alarm 1 process abnormality action selection)
Set value Description
1 Forcibly turned on when abnormal 2
0 0 0 “000 ” Fixed
1 The alarm action set by AS1 (Alarm 1 type selection) is taken even if the input is abnormal.
2 The alarm is forcibly turned on regardless of the alarm type set by AS1 (Alarm 1 type selection) when the input is abnormal.
However, for a voltage input of 0 to 5 V DC or 0 to 10 V DC, or a current input of 0 to 20 mA DC, as over-scale or underscale does not occur when the input breaks, no alarm is turned on.
It is judged that the input is abnormal when over-scale or underscale occurs.
Factory set value:
Alarm 1 not provided or LBA: 0 (Normal processing)
Alarm 1 provided: 1 (Forcibly turned on when abnormal)
See 2.3 Attention Items in Setting (P. 7) .
24
IMR01D03-E4
2. SETTING
2.4.5 F42 (Setting for alarm 2)
(1) AS2 (Alarm 2 type selection)
Set value
Factory set value varies depending on the instrument specification.
Description
0 Alarm not provided
1 SV high alarm
2 SV low alarm
3 Process high alarm
4 Process low alarm
5 Deviation high alarm
6 Deviation low alarm
7 Deviation high/low alarm
0 0 0 “000 ” Fixed
See 2.3 Attention Items in Setting (P. 7) .
(2) AHo2 (Alarm 2 hold action selection)
Set value
Factory set value varies depending on the instrument specification.
Description
0 Without alarm hold action
1 Effective when the power is turned on, or operation is changed from STOP to
RUN.
2 Effective when the power is turned on, or operation is changed from STOP to
RUN or the SV is changed.
0 0 0 “000 ” Fixed
The alarm hold action function can not be added to the SV value alarm.
See 2.3 Attention Items in Setting (P. 7) .
IMR01D03-E4 25
2. SETTING
(3) AH2 (Alarm 2 differential gap setting)
Setting range:
TC and RTD inputs, Voltage/current inputs: 0 (0.0) to span
Factory set value:
TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F]
Voltage/current inputs: 0.2 % of span
See 2.3 Attention Items in Setting (P. 7) .
(4) AEo2 (Alarm 2 process abnormality action selection)
Set value Description
1 Forcibly turned on when abnormal 2
0 0 0 “000 ” Fixed
1 The alarm action set by AS2 (Alarm 2 type selection) is taken even if the input is abnormal.
2 The alarm is forcibly turned on regardless of the alarm type set by AS2 (Alarm 2 type selection) when the input is abnormal.
However, for a voltage input of 0 to 5 V DC or 0 to 10 V DC, or a current input of 0 to 20 mA DC, as over-scale or underscale does not occur when the input breaks, no alarm is turned on.
It is judged that the input is abnormal when over-scale or underscale occurs.
Factory set value:
Alarm 2 not provided: 0 (Normal processing)
Alarm 2 provided: 1 (Forcibly turned on when abnormal)
See 2.3 Attention Items in Setting (P. 7) .
26
IMR01D03-E4
2. SETTING
2.4.6 F51 (Setting for control action)
(1) oS1 (Control action type selection)
Match the setting with the instrument specification. Otherwise malfunction may result.
Factory set value varies depending on the instrument specification.
Set value Description
0 D type: PID action with autotuning (Direct action)
1 F type: PID action with autotuning (Reverse action)
2 W type: Heat/cool PID action with autotuning (Water cooling)
3 A type: Heat/cool PID action with autotuning (Air cooling)
0 0 0 “000 ” Fixed
(2) oH (ON/OFF action differential gap setting)
Setting range:
TC and RTD inputs, Voltage/current inputs: 0 (0.0) to span
Factory set value:
TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F]
Voltage/Current inputs: 0.2 % of span
See 2.3 Attention Items in Setting (P. 7) .
2.4.7 F61 (Communication protocol selection)
CMPS (Communication protocol selection)
If the protocol is changed, always turn the power on again. Otherwise no communication is made by using the protocol thus changed.
Factory set value: 0000
Set value Description
RKC protocol
0 0 0 “000 ” Fixed
IMR01D03-E4 27
2. SETTING
2.4.8 F71 (Setting change rate limiter setting)
(1) SVrS (Setting change rate limiter Used/Unused)
For the SA200 Z-1045 specification, always set “1: Used.”
Set value Description
Factory set value: 0000
28
0 0 0 “000 ” Fixed
(2) SVrT (Setting change rate limiter time)
If the “Setting change rate limiter time Used” is selected, set the unit time of change rate limiter.
Setting range: 1 to 3600 seconds
Factory set value: 60 seconds
2.4.9 F91 (Displayed for maintenance information)
Only displayed for the F91 function block.
(1) E227 (ROM version displayed)
Display the version of loading software.
(2) WT (Integrated operating time)
Display product calculation operating time.
However, as the integral time is increments by 1 when the power is turned on or off.
Display range: 0 to 9999
Display resolution: 1 hour
(3) TCJ (Holding peak ambient temperature)
The maximum ambient temperature on the rear terminal board of the instrument is stored and displayed on the set value (SV) display.
Display range: 0.0 to 999.9
Display resolution: 0.1 ° C
IMR01D03-E4
3.
INITIALIZE COMMUNICATION DATA
RKC standard protocol
The number of digits for data is 6.
For details on the structure of communication data, see SA200 Communication Instruction
Manual ( IMR01D02-E ) .
Name Iden- Attrib tifier set value -ute
STOP display screen selection
(SPCH)
0
Monitor display configuration selection (dCHG)
MV display selection (MVd)
DX 0: It makes display “STOP” in PV display.
1: It makes display “STOP” in SV display.
2: No selection from RUN to STOP by the front key can be made.
DW 0: PV/SV display
1: Only PV display
2: Only SV display
DV 0: MV display not provided
1: MV display provided
0
0
XI 0 to 16 (See P. 14 ) Note Input type selection (InP)
Display unit selection (UnIT)
Decimal point position setting
(PGdP)
Setting limiter [high limit]
(SLH)
Setting limiter [low limit]
(SLL)
Selection of output logic calculation (LoGC)
Alarm 1 type selection (AS1)
Alarm 1 differential gap
(AH1)
Alarm 1 process abnormality action (AEo1)
1: ° F
0
RO *
XU 0 to 3 (See P. 15 ) Note
XV See
XW
LO
XA
HA
OA
1 to 19 (See
0 to 9 (See
0 to span
P. 21
P. 23
0: Normal processing
1: Forcibly turned on when abnormal
1
) Note
) Note
Note 2
Note 3
* In STOP mode, it is possible to write (Normal, read only ).
Note 1 Factory set value varies depending on the instrument specification.
Note 2 TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F] Voltage/current inputs: 0.2 % of span
Note 3 Alarm 1 not provided: 0
Alarm 1 provided: 1
If the alarm 1 type is control loop break alarm (LBA): 0
Continued on the next page.
IMR01D03-E4
29
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Iden- Attrib tifier set value -ute
Alarm 1 hold action (AHo1) Note 1 WA 0: Without alarm hold action
1: To wait only when STOP changes to RUN at power on.
2: To wait again when STOP changes to RUN at power on or set value (SV) is changed.
XB 0 to 8 (See P. 25 ) Note Alarm 2 type selection
(AS2)
Alarm 2 differential gap
(AH2)
ALM2 process abnormality action (AEo2)
Alarm 2 hold action
(AHo2)
HB 0 to span Note 2
Note 3
Note 1
RO *
Control action type selection
(oS1)
OB 0: Normal processing
1: Forcibly turned on when abnormal
WB 0: Without alarm hold action
1: To wait only when STOP changes to RUN at power on.
2: To wait again when STOP changes to RUN at power on or set value (SV) is changed.
XE 0: Direct action
1: Reverse action
2: Heat/cool action (Water cooling)
3: Heat/cool action (Air cooling)
MH 0 to span
Note 1
Note 2 ON/OFF action differential gap (oH)
Setting change rate limiter
Used/Unused (SVrS)
Setting change rate limiter time (SVrT)
TA
1: Used
1 to 3600 seconds
0
60
* In STOP mode, it is possible to write (Normal, read only ).
Note 1 Factory set value varies depending on the instrument specification.
Note 2 TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F] Voltage/current inputs: 0.2 % of span
Note 3 Alarm 2 not provided: 0
Alarm 2 provided: 1
If the alarm 2 type is control loop break alarm (LBA): 0
30
IMR01D03-E4
3. INITIALIZE COMMUNICATION DATA
MODBUS communication protocol
For details on the structure of communication data, see SA200 Communication Instruction
Manual ( IMR01D02-E ) .
Monitor display configuration selection
(dCHG)
MV display selection
(MVd)
Name Address
STOP display screen selection (SPCH)
30H 0: It makes display “STOP” in PV display.
1: It makes display “STOP” in SV display.
2: No selection from RUN to STOP by the front key can be made.
31H 0: PV/SV display
1: Only PV display
2: Only SV display
32H 0: MV display not provided
1: MV display provided set value -ute
0
0
0
33H 0 to 16 (See P. 14 ) Note Input type selection (InP)
Display unit selection
(UnIT)
Decimal point position setting (PGdP)
Setting limiter [high limit]
(SLH)
Setting limiter [low limit]
(SLL)
1: ° F
0
RO *
35H 0 to 3 (See P. 15 ) Note
36H See Input range table (
37H
P. 18 ) Note
38H 1 to 19 (See P. 21 ) Note Selection of output logic calculation (LoGC)
Alarm 1 type selection
(AS1)
Alarm 1 differential gap
(AH1)
Alarm 1 process abnormality action (AEo1)
39H
3AH
3BH
0 to 9 (See
0 to span
P. 23 ) Note
0: Normal processing
1: Forcibly turned on when abnormal
Note 2
Note 3
* In STOP mode, it is possible to write (Normal, read only ).
Note 1 Factory set value varies depending on the instrument specification.
Note 2 TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F] Voltage/current inputs: 0.2 % of span
Note 3 Alarm 1 not provided: 0
Alarm 1 provided: 1
If the alarm 1 type is control loop break alarm (LBA): 0
IMR01D03-E4 31
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Address
Alarm 1 hold action
(AHo1) set value
Note 1
-ute
3CH 0: Without alarm hold action
1: To wait only when STOP changes to RUN at power on.
2: To wait again when STOP changes to RUN at power on or set value (SV) is changed.
3DH 0 to 8 (See P. 25 ) Note Alarm 2 type selection
(AS2)
Alarm 2 differential gap
(AH2)
Alarm 2 process abnormality action (AEo2)
Alarm 2 hold action
(AHo2)
3EH
3FH
40H
0 to span
0: Normal processing
1: Forcibly turned on when abnormal
0: Without alarm hold action
1: To wait only when STOP changes to RUN at power on.
2: To wait again when STOP changes to RUN at power on or set value (SV) is changed.
Note 2
Note 3
Note 1
RO *
Control action type selection (oS1)
41H 0: Direct action
1: Reverse action
2: Heat/cool action (Water cooling)
3: Heat/cool action (Air cooling)
42H 0 to span
Note 1
Note2 ON/OFF action differential gap (oH)
Setting change rate limiter
Used/Unused (SVrS)
Setting change rate limiter time (SVrT)
44H
1: Used
1 to 3600 seconds
0
60
* In STOP mode, it is possible to write (Normal, read only ).
Note 1 Factory set value varies depending on the instrument specification.
Note 2 TC and RTD inputs: 2 ° C [ ° F] or 2.0 ° C [ ° F] Voltage/current inputs: 0.2 % of span
Note 3 Alarm 2 not provided: 0
Alarm 2 provided: 1
If the alarm 2 type is control loop break alarm (LBA): 0
32
IMR01D03-E4
The first edition: NOV. 1999
The forth edition: MAY 2005
RKC INSTRUMENT INC.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799)
FAX: 03-3751-8585 (+81 3 3751 8585)
IMR01D03-E4 MAY
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement