Danfoss Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS Data Sheet


Add to my manuals
8 Pages

advertisement

Danfoss Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS Data Sheet | Manualzz

REFRIGERATION AND

AIR CONDITIONING

Check valve for EVRA, EVRAT and

PM valves in liquid lines

Type NRVS

Technical leafl et

Technical leaflet

Introduction

Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

Features

Technical data

Materials

NRVS

Check valve type NRVS has no damping feature and therefore can only be used for liquid line applications. NRVS is designed to be mounted directly to PM or solenoid valves EVRA/EVRAT.

Ensures correct direction of flow

Applicable to all common non flammable refrigerants including R717 and non corrosive gases/liquids dependent on sealing material compatability.

Temperature of medium:

–50°C → +140°C

Maximum working pressure

PS = 28 bar/406 psig

Valve housing made of Stainless Steel

Gaskets are non-asbestos

NRVS mounted on PM and EVRA valve

2 RD6NA302  Danfoss A/S (RC-CMS / HBS), 04 - 2004

Technical leaflet

Capacities

Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

Location of valve in system (marked with grey)

Hot gas by-pass & defrost line

Discharge line

Dry suction line

Wet suction line

Low pressure liquid line

NRVS

Liquid line without phase change Liquid line with or without phase change

Valve combination k v

(m 3 /h)

EVRA/EVRAT 10 +

NRVS 15

1.4

EVRA/EVRAT 15 +

NRVS 15

2.2

EVRA/EVRAT 20 +

NRVS 25

4.1

Evaporating temperature

T e

–40°C

–30°C

–20°C

–10°C

Pressure

∆ p (bar)

0.25

0.30

0.40

0.50

0.15

0.25

0.30

0.40

0.50

0.15

0.25

0.30

0.40

0.50

0.15

0.25

0.30

0.40

0.50

0.15

208

228

264

295

156

201

220

254

284

172

222

243

281

314

167

215

236

273

305

161

Note: The capacities in the table must be divided by the actual circulation rate, or the evaporator capacities must be multiplied with the actual circulation rate.

Minimum opening differential pressure:

EVRA/EVRAT 10 - 20 + NRVS

EVRA/EVRAT 25 + NRVS

0.07 bar

0.11 bar

Capacities (kW) Q

0

at circulation rate 1

R717

327

359

414

463

245

316

346

399

447

270

349

382

441

493

262

338

371

428

479

254

610

669

772

863

456

589

645

745

833

504

650

713

823

920

489

631

691

798

893

473

EVRA +

NRVS 25

7.0

Solution

290 × 4 = 1160 kW

EVRAT 25 + NRVS 25: Q

0

∆ p = 0.3 bar is chosen.

= 1180 kW, at

Precise valve capacities can be calculated for various refrigerants by using the “DIRcalc™”

(Danfoss Industrial Refrigeration calculation programme).

1042

1142

1319

1475

780

1005

1102

1271

1422

960

1110

1216

1405

1570

835

1078

1180

1363

1524

808

Example

An application has the following operating conditions:

Refrigerant: .................................................................R717

Evaporating temperature: ................................... –30°C

Evaporator capacity (Q

0

): ..................................290 kW

Circulation rate: ................................................................ 4

∆ p ≤ 0.3 bar

 Danfoss A/S (RC-CMS / HBS), 04 - 2004

RD6NA302 3

Technical leaflet

Capacities

(continued)

4

Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

Location of valve in system (marked with grey)

Hot gas by-pass & defrost line

Dry suction line

Discharge line

Wet suction line

Low pressure liquid line

NRVS

Liquid line without phase change Liquid line with or without phase change

Valve combination k v

(m 3 /h)

PM 15

NRVS 25

4.0

Evaporating temperature

T e

–50°C

–40°C

–30°C

–20°C

–10°C

Pressure

∆ p (bar)

0.25

0.30

0.40

0.50

0.40

0.50

0.15

0.25

0.30

0.40

0.50

0.15

0.15

0.25

0.30

0.40

0.50

0.15

0.25

0.30

0.15

0.25

0.30

0.40

0.50

Note: The capacities in the table must be divided by the actual circulation rate, or the evaporator capacities must be multiplied with the actual circulation rate.

575

629

727

812

779

871

-

595

653

753

852

-

-

635

695

803

897

-

615

675

-

653

715

825

923

Minimum opening differential pressure:

PM + NRVS will be fully open at ∆ p = 0.25 bar.

Precise valve capacities can be calculated for various refrigerants by using the “DIRcalc™”

(Danfoss Industrial Refrigeration calculation programme).

PM 20

NRVS 25

6.0

Capacities (kW) Q

0

at circulation rate 1

R717

1169

1306

-

894

979

1130

1264

-

862

944

1090

1219

-

951

1043

1204

1346

-

922

1011

-

979

1072

1238

1384

PM 25

NRVS 25

7.5

1460

1632

-

1114

1224

1412

1580

-

1075

1180

1362

1523

-

1188

1303

1506

1683

-

1152

1265

-

1224

1340

1547

1730

RD6NA302  Danfoss A/S (RC-CMS / HBS), 04 - 2004

Technical leaflet

Ordering

Check valve

Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

Flanges, gaskets and bolts 1 )

Valve type Code. no.

For valve type

NRVS 15

NRVS 25

020-2032

020-2033

EVRA/T 10, EVRA/T 15

EVRA/T 20, EVRA/T 25, PM 15, PM 20, PM 25

1) Consists of one standard and one special flange, one gasket and bolts.

2) Flange and bolts only.

Dimensions and weights

Code. no.

027N1255

027N1254

Weight 2 )

[kg]

0.7

1.1

Flange type

Connection size

3 /

4

in.

1 in.

Type

NRVS 15

NRVS 25

L mm

47.5

60.5

1 ) NRVS without flanges and bolts

B mm

78.0

96.0

Weight 1 ) kg

0.1

0.25

 Danfoss A/S (RC-CMS / HBS), 04 - 2004

RD6NA302 5

Technical leaflet Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

6 RD6NA302  Danfoss A/S (RC-CMS / HBS), 04 - 2004

Technical leaflet Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

 Danfoss A/S (RC-CMS / HBS), 04 - 2004

RD6NA302 7

Technical leaflet Check valve for EVRA, EVRAT and PM valves in liquid lines, type NRVS

8 RD6NA302  Danfoss A/S (RC-CMS / HBS), 04 - 2004

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement