Data Sheet
FHM-CN Mixing Shunt
Application
Ordering
The Danfoss mixing shunts are used for regulation of flow and supply temperature in hydronic floor heating systems. The compact, flexible design allows mounting the mixing shunt directly to the manifold on both left and right side, with the primary pipe connection from the side or below.
The FHM-CN mixing shunts can be mounted directly to the Danfoss manifold system without the use of special equipment.
By using Danfoss floor heating controls all expectations of a professional floor heating system are fullfilled.
A self-acting proportional regulator is used to regulate the supply temperature. The regulator ensures that the desired supply temperature to the underfloor heating system always remains constant.
Product
FHM-CN Mixing Shunt
Pump
RA-C Valve
FTC Floor Heating Sensor
Automatic Bypass Control AVDO
Specifications
130 mm in length
G1 external thread (inlet and outlet)
DN20
Setting range 35 to 70 °C
Setting range 15 to 50 °C
DN15
-
Code No.
088U0680
013G3096
013G5080
013G5081
003L6020
Technical Specifications
Primary connection
Max. differential pressure
Max. working pressure
Max. flow temperature
Supply and return flow thermometer
3/4" internal thread
0.6 bar
PN10
90 °C
0 to 60 °C
Danfoss Heating Solutions VDIKB102 © Danfoss 12/2013 1
Data Sheet
Accessories FH-ST55 Safety Thermostat
FHM-CN Mixing Shunt
Body, unions and other meal parts
O-rings
Brass
EPDM
Heat capacity [kW]
T supply
/T return at primary side [°C]
24
28
* based on kv (Xp = 4K) with FTC
70/40
80/40
T supply
/T return at second side [°C]
50/40
50/40
DP at RA-C DN20* [kPa]
12.6
9.6
2
230V / 16A
T
S
55°C
Fig. 1: Electrical connection
The FH-ST safety thermostat is fixed on the tube and protects floor and system against too high temperatures, especially important for wooden floors. The FH-ST thermostat switches off the power supply of the floor heating base unit, when the temperature reaches 55 °C. By switching off the power supply of the floor heating base unit, the actuators (NC) will close automatically and the floor heating system is protected. The
FH-TC can also be connected to a pump or a zone valve.
Note!
The electrical installation must be carried out by an authorized installer only (230 V DC).
Code no.
Shut-off temperature
Switch difference
Classification
Tab. 1: Technical Specifications
088U0301
55 °C
4 K
IP 40 (mounted)
VDIKB102 © Danfoss 12/2013 Danfoss Heating Solutions
Data Sheet
System
FHM-CN Mixing Shunt
FHM-CN
Dimensions
252
93
25
48.5
23
Fig. 2: Vertical
80
252
93
48.5
23
120
25
Danfoss Heating Solutions
150
Fig. 3: Horizontal
80
VDIKB102 © Danfoss 12/2013
120
3
Data Sheet FHM-CN Mixing Shunt
Danfoss A/S
Heating Solutions
Haarupvaenget 11
8600 Silkeborg
Denmark
Phone: +45 7488 8000
Fax: +45 7488 8100
Email: [email protected]
www.heating.danfoss.com
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.
4 VDIKB102 © Danfoss 12/2013 Danfoss Heating Solutions