OWNER’S & INSTALLATION
MANUAL
AIR CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly..
WIRED REMOTE CONTROLLER
PREMTB100, PREMTBB10, CREMTB100
MFL69312302
Rev.10_073019
www.lg.com
Copyright © 2016 - 2019 LG Electronics Inc. All Rights Reserved.
2
TIPS FOR SAVING ENERGY
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below:
• Do not cool excessively indoors. This may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the air flow or reduce the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
3
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product
!
WARNING
This symbol indicates potentially hazardous situation which, if not avoided could result in death or serious injury.
!
CAUTION
This symbol indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
!
WARNING
Installation
• For electrical work, contact the dealer, seller, a qualified electrician, or an authorized service Center.
- Do not disassemble or repair the product. There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• Request to the service center or installation specialty store when reinstalling the installed product.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• Do not disassemble, fix, and modify products randomly.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury.
• The product shall be installed according to the national standards and local code.
• Apply totally enclosed noncombustible conduit in case of local building code requiring plenum.
• Use appropriate unit mounting procedures.
• Avoid direct sunlight.
• Avoid moist areas.
In-Use
• Do not place flammable objects close to the product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Do not allow product to get wet.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Avoid dropping the product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• If product gets wet, contact your dealer or authorized service center.
- There is risk of fire, electric shock, explosion, equipment malfunction, or injury. If the instructions are not followed, it may cause death or severe injury of the user.
• Do not use sharp or pointed objects on product.
- There is risk of fire, electric shock, explosion, equipment malfunction or injury.
• Do not touch or pull the lead wire with wet hands.
- There is risk of product breakdown or electric shock.
4
IMPORTANT SAFETY INSTRUCTIONS
!
CAUTION
In-use
• Do not clean using powerful detergents like solvent but use soft cloths.
There is risk of fire, electric shock, explosion, equipment malfunction or deformation.
• Do not press the screen using powerful pressure.
There is risk of product break-down or malfunction.
TABLE OF CONTENTS
5
TABLE OF CONTENTS
2
TIPS FOR SAVING ENERGY
3
IMPORTANT SAFETY IN-
STRUCTIONS
9
8
DESCRIPTION
9
READ BEFORE OPERATING
THE CONTROLLER
Menu Structure
15
15
16
17
17
14
DESCRIPTION OF THE OP-
ERATION
14
14
Main screen
Menu screen
Setting screen
Popup screen
Monitoring / Sub function screen
Interface screen
Returning to the screen
23
24
25
25
18
19
20
21
22
18
OPERATION SETTING
18 On / Off
Operation mode
Cooling Operation
Heating Operation
Dry Operation
Fan Only Operation
AI / Auto operation
Dual setpoint auto operation
Power Cool Operation
Power Heat Operation
26
OPERATION SETTING -
VENTILATOR
26 Operation mode
27
TEMPERATURE SETTING
27 Controlling Desired Temperature
28 Check Room Temperature
29
WIND SETTING
29 Fan speed control
29
29
Fan speed control - ventilation
Air flow control
30
HOME LEAVE SETTING
30 Home leave (Unoccupied Mode)
31
HOLD SETTING
31 Hold
32
ADDITIONAL OPERATION –
VENTILATION
32 Additional operation
33
EXTERNAL EQUIPMENT
CONTROL SETTING
33 External equipment control
34
PLASMA PURIFICATION
SETTING
34 Plasma Purification
35
OVERRIDE CONTROL SET-
TING
35 Override control
36
MONITORING SCREEN
36 How to enter fine dust status screen
37 Fine dusts status
43
44
45
46
40
41
42
38
SUB FUNCTION SETTING
38
39
Sub function entrance and setting method
Energy Saving Setting
Plasma Purification Setting
Fan Auto Setting
Humidification setting
Electric Heater Setting
Robot Cleaning Setting
Ventilation kit Setting
Comfort Cooling Setting
47
ZONE CONTROL SETTING
47 Zone Control
48
LOCK SETTING
48 How to enter lock setting
48 Lock setting – all, on/off, mode, temperature range lock
6
TABLE OF CONTENTS
50
51
52
53
49
TIMER SETTING
49 Timer entrance and setting method
Simple timer
Sleep timer
Turn-off Reservation
Turn-on Reservation
55
56
57
58
54
SCHEDULE SETTING
54 How to enter schedule
Daily Schedule
Schedules & Edit
Schedules & Edit – Add schedule
Exception day
60
61
63
64
65
59
ENERGY (air conditioner /
DX ventilator)
59 How to enter energy
Instantaneous power check
Energy consumption
Energy saving - Temperature Setback Timer
Energy saving - Time Limit Control
Energy setting - outdoor unit capacity setting
66 Energy setting - target instantaneous power setting
67
68
69
70
Energy setting - target power consumption
Energy setting - target operation time
Energy setting - Alarm Popup Setting
Energy setting – Usage data initialization
76
77
78
79
80
72
73
74
75
75
81
82
83
71
FUNCTION SETTING
71 How to enter function setting
Function Setting
Vane angle control setting
Elevation grill setting
Robot cleaning setting
Auto dry setting
Filter sign check and initialization
Change temperature setting
Dead Band
Wi-Fi pairing setting
Zone Name setting
Override Set Time Setting
Home Leave Set Temperature Setting
Comfort cooling setting
88
89
90
91
83
84
85
86
87
92
92
ODU Refrigerant Noise Reduction setting
Defrost mode setting
Smart load control(SLC) setting
Low noise mode time setting
Advanced fan speed “Auto” setting
Delay time (exclusive for ventilation)
Midnight air cooling (ventilation interface)
Human detection mode setting
Discharge direction
CO
2
Fan Control(general ventilator)
Economizer setting
93
USER SETTING
93 How to enter user setting
96
97
97
98
98
93
94
95
User Setting
Language setting
Setpoint Type Setting
Temperature unit setting
Screen saver timer setting
LCD brightness in idle setting
External device setting
External device use
99 External device types
100 On condition / Off condition
101 Date setting
102 Time setting
103 Summer time setting
104 Password setting
105 Schedule initialization
106 Theme setting
107 Humidity display
108 System restart
109
SERVICE SETTING
109 How to enter service setting
109 Service setting
110 Service contact
111 Model information
112 RMC Version Information
113 Error history
114 Open source license
115
INSTALLATION
115 Installation of Remote Controller
117 Group control
TABLE OF CONTENTS
7
119
INSTALLATION METHOD
TO USE EXTERNAL DEVICE
119 Cable connection method to use external device
120
AIR CONDITIONER AND
VENTILATION INTERFACE
121
INSTALLER SETTING
121 How to enter installer setting
122 Installer setting – air conditioner
124 Installer setting - ventilator
125 Test run setting (air conditioner / DX ventilator)
126 Central control address setting (air conditioner / general, DX ventilator)
127 ESP setting (air conditioner / general, DX ventilator)
128 Temperature sensor(2TH) setting (air conditioner / DX ventilator)
129 Ceiling height setting (air conditioner)
130 Static pressure setting(air conditioner)
131 Remote controller master / slave setting (air conditioner / General, DX ventilator)
132 Override Master/Slave setting (air conditioner / General, DX ventilator)
133 Dry contact mode setting (air conditioner /
DX ventilator)
134 Fixed air volume (air conditioner / DX ventilator)
135 Zone Type Setting(air conditioner)
135 Zone Number Setting(air conditioner)
136 Emergency heater setting (air conditioner)
137 Function control during group Control setting (air conditioner)
138 External devices of indoor unit setting (air conditioner)
139 Expand of Temperature Range (air conditioner)
140 Indoor unit address verification (air conditioner / DX ventilator)
141 Static pressure step setting (air conditioner)
142 Guard timer(air conditioner)
143 Fan speed in Cooling thermal off (air conditioner)
144 Primary heater setting(air conditioner)
145 Air conditioner Fan operation interlocked with ventilation setting (air conditioner)
146 Indoor unit Auto-Start setting (air conditioner / DX ventilator)
147 Occupancy duration time setting(air conditioner)
148 CN_CC setting (air conditioner)
149 CN_EXT setting (air conditioner / DX ventilator)
150 Outdoor unit function master setting (air conditioner / DX ventilator)
151 Fan continuous operation setting (air conditioner)
152 Low Noise Mode Priority setting (air conditioner / DX ventilator)
153 Human detection sensor (air conditioner)
154 Humidity sensing position (air conditioner)
155 ODU cycle priority (air conditioner)
157 Outdoor temp. for heating stages (air conditioner)
158 Estimated energy display (air conditioner)
158 CN_PTC setting (air conditioner)
159 Password initialization (air conditioner / general, DX ventilator)
160 Product direction (general ventilator)
161 Express ventilation priority (general , DX ventilator)
162 Humidification of stand-alone ventilation mode (general , DX ventilator)
163 Humidification of ventilation with heating operation (DX ventilator)
164 Ventilation Fan Speed Alignment (general ventilator)
164 Filter check alarm(general ventilator)
165
GUIDE TO DIFFERENT
MODE OPERATION/OPEN
SOURCE SOFTWARE
165 Different mode operation
165 Open Source Software Notice Information
8
DESCRIPTION
DESCRIPTION
NEW STANDARD REMOTE CONTROLLER
Operation display window
Back button
Up/Down/Left/Right
Button
OK
On/Off Button
OK Button
Operation display window
Back button
Up/down/left/right button
OK button
On/Off button
Operation and Settings status display
When you move to the previous stage from the menu’s setting stage
When you change the menu’s setting value
When you save the menu’s setting value
When you turn ON/OFF the air conditioner
Accessories
Connecting Cable DO Port Remote controller fixing screws
(4 EA)
Quick Guide User/Installation
Manual
READ BEFORE OPERATING THE CONTROLLER
9
READ BEFORE OPERATING THE CONTROLLER
Menu Structure
Menu
Override
Fine Dust
......................................................................................................................35
......................................................................................................................36
Sub function
Zone Control
Energy Saving
..............................................................................39
Plasma Purification
..............................................................................40
Fan Auto ..............................................................................41
Humidification ..............................................................................42
Electric Heater
..............................................................................43
Robot Cleaning
..............................................................................44
Ventilation Kit
..............................................................................45
Comfort Saving
..............................................................................46
......................................................................................................................47
Lock
All Lock
..............................................................................48
On/Off Lock
..............................................................................48
Mode Lock
..............................................................................48
Set temp range lock
..............................................................................48
Timer
Simple Timer
..............................................................................50
Sleep Timer
..............................................................................51
Turn-off reservation
..............................................................................52
Turn-on reservation
..............................................................................53
Schedule
Daily Schedule
..............................................................................55
Schedules & Edit
..............................................................................56
Exception Day
..............................................................................58
10
READ BEFORE OPERATING THE CONTROLLER
Energy
Setting
Instantaneous Power
.........................................................................60
Energy Consumption
Year-on-year Usage
..........................61
..........................61
Weekly Usage
Monthly Usage
Yearly Usage
..........................61
..........................61
Energy Saving
Temp Setback Timer
..........................63
Time Limit control
..........................64
Energy Setting
Outdoor Unit Capacity
..........................65
Target Instantaneous Power
................66
Target Power Consumption
................67
Target Operation Time
..........................68
Alarm Popup
..........................69
Usage Data Initialization
..........................70
Function
Vane Angle Control
..........................73
Elevation Grill
..........................74
Robot Cleaning
..........................75
Auto Dry
Wi-Fi Paring
..........................75
Filter Sign
Dead Band
..........................76
Change Temperature
..........................77
..........................78
..........................79
User
READ BEFORE OPERATING THE CONTROLLER
11
Zone Naming
...............................80
Override Set Time
Comfort Cooling
...............................81
Home Leave Set Temp
...............................82
...............................83
ODU Refrigerant Noise
Reduction
...............................83
Defrost Mode
...............................84
Smart Load Control
...............................85
Low Noise Mode Time
...............................86
Advanced fan speed “Auto”
....................87
Delay Time(Ventilator)
...............................88
Midnight Air Cooling (Ventilator)
.................89
Human detection mode
...............................90
Discharge direction
...............................92
CO
2 fan control(Ventilator) ........................92
Language
Humidity display
...............................94
Setpoint type
Theme
...............................95
Temperature Unit
Schedule Initialization
...............................96
Screen Saver Timer
Password
...............................97
LCD Brightness In Idle
...............................97
External Device
...............................98
Date
.............................101
Time
.............................102
Summer Time
.............................103
.............................104
.............................105
.............................106
.............................107
System Reboot
.............................108
12
READ BEFORE OPERATING THE CONTROLLER
Service
Installer
Service Contact
Model Information
RMC Version Information
Error History
Open Source License
..........................110
..........................111
..........................112
..........................113
..........................114
Test Run
Dry Contact Mode
..........................125
Central Control Address
Override Master/Slave
..........................126
ESP
RMC Master/Slave
..........................127
Temperature Sensor(2TH)
..........................128
Ceiling Height Selection
..........................129
Static Pressure
..........................130
..........................131
..........................132
..........................133
Fixed Air Volume
..........................134
Zone Type
..........................135
Zone Number
..........................135
Emergency Heater
..........................136
Function Control During Group ..........................137
Control
External devices of indoor unit
..........................138
Expand of Temperature Range
..........................139
IDU Address Verification
..........................140
Static Pressure Step
..........................141
Guard Timer
..........................142
Fan Speed In Cooling Thermal off
..........................143
READ BEFORE OPERATING THE CONTROLLER
13
Primary Heater
.............................144
AC Fan Operation Interlocked
With Ventilation
.............................145
IDU Auto-Start
.............................146
Occupancy Duration Time
.............................147
CN_CC
.............................148
CN_EXT
.............................149
ODU Function Master
.............................150
Fan Continuous Operation
.............................151
Low Noise Mode Priority
.............................152
.............................153
Human detection sensor
Humidity sensing position
.............................154
ODU cycle priority
Outdoor temp. for heating stages
.............................155
.............................157
Estimated energy display
.............................158
CN_PTC
.............................158
Password Initialization
.............................159
Product direction(ventilator)
.............................160
Express ventilation priority(Ventilator)
.............................161
Humidification of stand-alone ventilation mode(Ventilator)
.............................162
Humidification of ventilation with heating operation(Ventilator)
.............................163
Ventilation Fan Speed Alignment(Ventilator)
.............................164
Filter check alarm
(Ventilator)
.............................164
Notice
• Some functions may not work in some indoor unit products.
14
DESCRIPTION OF THE OPERATION
DESCRIPTION OF THE OPERATION
Main screen
In the main screen, press [<, >(left/right)] button to select the category to set, and you can control by pressing [
∧
,
∨
(up/down)] button.
< Air conditioner main screen> <Genernal Ventilation main screen>
Menu screen
<Dx Ventilation main screen>
In the main screen, press [<, >(left/right)] button to select the menu and press [OK] button to move to menu screen.
DESCRIPTION OF THE OPERATION
15
Setting screen
Select the category to set using [
∧
,
∨
(up/down)] button.
In each detail screen of the menu, as in the box in the left figure, when “<,>” icons are displayed at the same time, you can immediately apply the setting value by pressing [<, >(left/right)] button.
※
For the values that can be set in each category, refer to the detail manual for each function.
In each detail screen of the menu, as in the box in the left figure, if only “>” icon is displayed, you can move to the detail setting screen by pressing [>(right) or OK] button.
※
For the values that can be set in each category, refer to the detail manual for each function.
Popup screen
The toast message is the message displayed at the bottom of the screen when an operation is turned On/Off or if a function is set / cancelled.
The popup message is mainly displayed when an error occurred in the product.
In the menu screen, press [<, >(left/right)] button to select the category to set, and press [OK] button to move to the detail screen.
< Toast message > < Popup message >
16
DESCRIPTION OF THE OPERATION
Monitoring / Sub function screen
In the main screen, you can enter the monitoring / sub function screen by pressing [Back] button and then pressing [<, >(left/right)] button.
- In the monitoring screen, you can check the indoor temperature and outdoor unit monitoring information.
- In the sub function screen, you can turn on or off the sub function supported by the product.
DESCRIPTION OF THE OPERATION
17
Interface screen
Select the product (air conditioner or ventilation) to set using [<, >(left/right)] button.
When you control the air conditioner and the ventilation product with one remote controller, the screen is displayed as in the side figure. You can set the air conditioner by pressing [<(left)] button and pressing [OK] button to move to the air conditioner screen.
When you control the air conditioner and the ventilation product with one remote controller, the screen is displayed as in the side figure. You can set the ventilation by pressing [>(right)] button and pressing [OK] button to move to the ventilation screen.
Returning to the screen
In the main screen, after moving to the category by pressing [<, >(left/right)] button, if there is no remote controller operation, after 10 seconds, it returns to the main screen basic position. (basic position: indoor temperature display part)
In the screens except the main screen, if there is no remote controller operation for 1 minute, it moves to the main screen.
18
OPERATION SETTING
OPERATION SETTING
On / Off
Air conditioner and ventilator will be turned on or off.
Press the remote controller’s (On/Off) button.
- If the product is in operation, On/Off button will be illuminated.
If the product is in off, On/Off button backlight will be off.
OPERATION SETTING
19
Cooling Operation
Cooling operation’s minimum setting temperature is 18°C (16°C).
For some types of the indoor units, the desired temperature can be controlled in the units of 1°C or 0.5°C.
- Set the desired temperature lower than the indoor temperature.
- Indoor temperature is displayed on the default screen of the remote controller.
- If the setpoint is set higher than the room temperature, then the unit will remain in the cool mode but will not begin to cool unit the room temperature exceeds the setpoint.
- If you unit is operating in cooling mode and you press the [On/Off] button the cooling operation will shut off.
Operation mode
You can easily control the desired operation mode.
In the main screen, press [<,>(left/right)] button to select the operation mode or home leave or hold category, and press [
∧
,
∨
(up/down)] button to set the operation mode.
※
Some products may not support some operation modes.
Mode
Cool
Dry
Heat
AI / Auto
Fan
Power Cool
Power heating
Description
Cool the room to the desired temperature.
It removes the moisture with cooling.
Heats the room to the desired room temperature.
The product automatically provides the appropriate fan speed based on the temperature of the room.
Fan only operation, no cooling or heating.
It provides strong cooling in short time.
Power heating increases indoor temperature quickly.
What is 3 minute delay function?
After the cooling stops, when the product is started right away, the reason that the cold wind does not come out is that it is the function to protect the compressor.
The compressor starts after 3 minutes and the cold wind comes out.
!
NOTE
The compressor starts after 3 minutes and the cold wind comes out.
In the cooling operation, you can select the desired temperature in the range of 18°C ~ 30°C
(16°C ~ 30°C).
The favorable temperature difference between the indoor temperature and the outdoor temperature is 5°C.
For some types of the indoor units, you can select the desired temperature in the range of
16°C ~ 30°C.
20
OPERATION SETTING
Heating Operation
The heating operation’s minimum setting temperature is 16°C.
For some types of the indoor units, the desired temperature can be controlled in the units of 1°C or 0.5°C.
- Set the desired temperature higher than the indoor temperature.
- Indoor temperature is displayed on the default screen of the remote controller.
- When the desired temperature is set lower than the indoor temperature, warm air doesn't come out, but for some products, the fan will recirculate room air, or stop altogether.
- If you unit is operating in heating mode and you press the [On/Off] button the heatling operation will shut off.
OPERATION SETTING
21
Dry Operation
Dry operation’s initial fan speed is “Low”.
Dry operation does not have a separate desired temperature.
- If you unit is operating in dehumidification mode and you press the [On/Off] button the dehumidification operation will shut off.
!
NOTE
If you use it in the rainy season, or when the humidity is high, you can have both the effective dehumidification and cooling operation at the same time.
!
NOTE
In the heating operation, you can select the desired temperature in the range of 16°C ~ 30°C.
Heating operation is operated only in cooling/heating model. The heating is not operated in cooling exclusive model.
22
OPERATION SETTING
Fan Only Operation
Fan only operation’s initial wind strength is “High”.
Fan only operation does not have a separate desired temperature.
- If you unit is operating in fan only mode and you press the [On/Off] button the the unit will stop.
OPERATION SETTING
23
AI / Auto operation
Auto operation’s initial desired temperature is 25°C.
The cooling exclusive model’s initial desired temperature is “It’s Fine”.
Cooling/heating model’s desired temperature can be controlled in the units of 1°C or 0.5°C.
For cooling exclusive model, the value can be controlled from “hot” stage to “cold” stage.
- Hot
- A little hot
- It’s fine
- A little cold
- Cold
- If you unit is operating in ai/auto mode and you press the [On/Off] button the ai/auto operation will shut off.
!
NOTE
It provides the Fan only operation without temperature control, with recirculation of indoor air.
!
NOTE
If the product is a cooling/heating model, in the auto operation, the desired temperature can be selected in the range of 18°C ~ 30°C.
If it does not operate as you wish, select another operation mode.
24
OPERATION SETTING
Dual setpoint auto operation
The indoor unit automatically manages room temperature with extended heating and cooling setting temperature ranges.
Dual setpoint auto mode can be set in the USER SETTING. This is recommended in North America region.
OPERATION SETTING
25
Power Cool Operation
Power cooling quickly lowers the indoor temperature.
Desired temperature: 18°C
Fan speed : Power fan speed
Fan direction: Current fan direction
- During the power cooling, if fan speed or desired temperature is changed, the power cooling is cleared, and it operates in the cooling operation mode.
- During the power cooling, if you press [On/Off] button, the power cooling operation stops, and when you press [On/Off] button again, it operates in the cooling operation mode.
!
NOTE
• Auto heating function only operates on cooling and heating models.
• Auto heating function doesn’t operate on cooling only models.
• When remote controller has a connection with indoor unit that does not support 'dual setpoint', thermal operation function of indoor unit is replaced with ON/Off control from the wired remote, when the user sets target temperatures in the below ranges.
- cooling target temp. range : 87~99 °F (30.5~37.5 °C)
- heating target temp. range : 40~59 °F (4~15.5 °C).
Power Heat Operation
Power heating increases indoor temperature quickly.
Desired temperature: 30 °C
Fan speed: Power fan speed
Fan direction: Current fan direction
- If you adjust the fan speed or the desired temperature during power heating, the function is disabled and heating operation mode is activated.
- If you press [On/Off] button during power heating, the function stops and if you press [On/Off] button again, heating operation mode is activated.
26
OPERATION SETTING - VENTILATOR
OPERATION SETTING - VENTILATOR
Operation mode
Ventilation (general and direct cooling type ventilation) operation mode supports the following operation modes.
※
Some products may not support some operation modes.
Mode
Auto
Classification Description
It measures the ventilation system’s indoor temperature and the outdoor temperature for the automatic operation in the optimal ventilation mode state.
Heat Exchange
Ventilation operation mode – commonly supported by ventilation products
Bypass
Cool
Heat
Auto
It is the mode of ventilation with both supply/discharge through the heat exchanger. It is adequate to use in summer/winter where the indoor/outdoor temperature difference is big.
It is the ventilation where the exhausted air is ventilated without going through the exchanger. It is adequate to use in spring/fall or when the indoor contamination is severe.
Cools down the room to desired temperature.
It provides warm air to the room.
Air conditioner operation mode – supports direct cooling type ventilation
The product automatically provides the appropriate fan speed based on the temperature of the room.
Stop It stops the product’s air conditioner operation.
In the main screen, press [<,>(left/right)] button to select the operation mode category, and press
[
∧,∨
(up/down)] button to set the operation mode.
TEMPERATURE SETTING
27
TEMPERATURE SETTING
Controlling Desired Temperature
You can easily control to the desired temperature.
• In the main screen, press [<,>(left/right)] button to select the desired temperature category, and press [
∧
,
∨
(up/down)] button to set the desired temperature.
- In the cooling, heating, and AI/auto mode, the desired temperature control is possible.
Mode
Cool
Heat
AI / Auto
Description
If the desired temperature is higher than the indoor temperature, the cooling is not performed.
Set the desired temperature lower than the indoor temperature.
You can select in the range of 18°C ~ 30°C (16°C ~ 30°C).
If the desired temperature is lower than the indoor temperature, the heating is not performed.
Set the desired temperature higher than the indoor temperature.
You can select in the range of 16°C ~ 30°C.
For cooling/heating product, you can select in the range of 18°C ~ 30°C.
For cooling exclusive product, you can select Hot, A little hot, Adequate,
A little Cold, and Cold.
!
NOTE
The favorable temperature difference between the indoor temperature and the outdoor temperature is 5°C.
※
The direct cooling type ventilation’s air conditioner operation mode is composed separately from the ventilation operation mode.
28
TEMPERATURE SETTING
Check Room Temperature
You can check the current indoor temperature.
• In the remote controller’s the main screen, you can check the indoor temperature.
WIND SETTING
29
WIND SETTING
Fan speed control
From the main screen, press [<,>(left/right)] button to select the fan speed category, and press
[
∧
,
∨
(up/down)] button to set the fan speed control the desired fan speed.
- It circulates in the order of Slow
↔
Low
↔
Medium
↔
High
↔
Power
↔
Auto.
!
NOTE
The temperature distribution in the remote controller installation space is not uniform, so there can be a little difference between the temperature you actually feel and the remote controller’s room temperature display
According to Control type setting value
• Single setpoint
Fahrenheit: 52~99 °F
- below 52 °F: display ‘LO’
- over 99 °F: display ‘HI’
Celsius: 10.5~39.5 °C
- below 10.5 °C: display ‘LO’
- over 39.5 °C: display ‘HI’
• Dual setpoints
Fahrenheit: 34~99 °F
- below 34 °F: display ‘LO’
- over 99 °F: display ‘HI’
Celsius: 0.5~39.5 °C
- below 0.5 °C: display ‘LO’
- over 39.5 °C: display ‘HI’
- For indoor temperature below 50 °F (10 °C), the value perceived by the Thermostat(with cable) is displayed.
• Because of location of Temperature sensing, the real room temperature and the this displayed value can be different.
※
For some product some fan speed may not be available.
Fan speed control - ventilation
You can easily control the desired fan speed.
• In the main screen, press [<,>(left/right)] button to select the fan speed category, and press
[
∧
,
∨
(up/down)] button to set the fan speed.
- It circulates in the order of low ↔ high ↔ power ↔ auto.
※
The auto Fan can be used only when the air contamination (CO
2
) sensor is installed.
Air flow control
You can easily control the desired air flow
• In the main screen, press [<,>(left/right)] button to select the air flow category, and press
[
∧
,
∨
(up/down)] button to set the air flow.
- It circulates in the order of Off
↔
Up/Down swing
↔
Left/Right swing
↔
Up/Down/Left/Right swing
↔
Swirl
↔
Indirect wind
↔
Direct wind
↔
Human detection direct wind
↔
Human detection indirect wind
↔
Power&Indirect
↔
Focus Mode.
※
For some product some air flow settings may not be available.
30
HOME LEAVE SETTING
HOME LEAVE SETTING
Home leave (Unoccupied Mode)
The "Home Leave" function enables proper operation of indoor unit when a space is left for a period of time.
This feature can only be used when Control type setting is set to the Dual Set Point Control mode
HOLD SETTING
31
HOLD SETTING
Hold
User can use this function when they want to manage indoor unit as home leave control mode only.
!
NOTE
User can not change indoor unit status with wired remote controller while set 'home leave mode' except for 'home leave mode' release control.
• Home leave mode will be released if indoor unit operation was changed by commands of other controllers(central controller, drycontact and wireless remote controller).
• When occupied schedule event occurs while operate a home leave mode, home leave mode will be released and indoor unit status follow the occupied schedule event.
• Indoor unit operation change as below when the home leave mode is released.
- The setpoints and operation mode values are reflected in the control events of the scheduled events that are currently applied.
- If there are no schedule events, the setpoint shall be applied as last setpoints before the home leave operation.
- If there are no setpoints before the 'home leave' operation(dehumidification or fan mode), default values will be applied to the setpoints.
- Default values : dual setpoint auto , heat 60 °F(16 °C), cool 86 °F(30 °C)
!
NOTE
Can not change indoor unit status with wired remote controller while set ‘hold mode' except for ‘hold mode' release control.
• Hold mode will be released if indoor unit operation was changed by commands of other controllers(central controller, drycontact and wireless remote controller).
• A scheduled event is not applied to the indoor unit during a hold mode, even if a scheduled event is set.
32
ADDITIONAL OPERATION –VENTILATION
ADDITIONAL OPERATION –VENTILATION
Additional operation
You can change the additional operation of the ventilation product.
• In the main screen, press [<,>(left/right)] button to select the additional operation category, and press [
∧
,
∨
(up/down)] button to set the additional operation.
EXTERNAL EQUIPMENT CONTROL SETTING
33
EXTERNAL EQUIPMENT CONTROL SETTING
External equipment control
It is the function to set the contact point output of the external equipment control mode.
• In the main screen, press [<,>(left/right)] button to select the external equipment control category, and press [
∧
,
∨
(up/down)] button to set the contact point output.
Additional Operation
Fast
Description
It ventilates in short period of time.
It is the function to operate the ventilation function more efficiently through the express setting which is an additional operation of the ventilation product.
Energy saving It performs the energy saving function while ventilating efficiently.
!
NOTE
The general ventilation and the direct cooling type ventilation’s additional operation are the same.
The ventilation product’s additional functions (air cleaning / heater / humidification / fan auto) setting methods are the same as the air conditioner.
Mode
On
Off
Auto
Description
When it is set to “On”, it always performs the contact point output.
When you set it to “Off”, it does not perform the contact point output in any case.
When it is set to “auto”, the contact point output is decided according to the user setting’s external equipment logic setting value.
!
NOTE
Please use the corresponding function when the external equipment is actually connected.
When the external equipment is not set, please maintain “Off” status.
For the detail external equipment control condition setting, refer to the user setting - external equipment logic setting.
34
PLASMA PURIFICATION SETTING
PLASMA PURIFICATION SETTING
Plasma Purification
It cleans and makes pleasant indoor air.
1 . Plasma Purification - single operation
If plasma purification is turned on in operation Off state, plasma purification single operation is performed.
OVERRIDE CONTROL SETTING
35
OVERRIDE CONTROL SETTING
Override control
In dual setpoint setting, wired remote controller can manages indoor unit status based on programmed control events which have occupancy option.
Override control function switches between ‘occupied’ and ‘unoccupied’, and vice-versa.
User can set timer option which can return to original schedule event in override function menu.
OK
In case of plasma purification single operation, it operates in fan mode / automatic wind state, and the wind direction operated before the plasma purification single operation is turned off.
There are 3 ways to end the plasma purification single operation.
1) Input of On/Off button during plasma purification single operation
2) Select plasma purification OFF
3) Change operation mode during plasma purification single operation
2 . Plasma purification - additional operation
!
NOTE
• If mode is changed during plasma purification single operation, it is switched to the air cleaning additional operation.
• Air cleaning operation may not be displayed or performed in some products.
!
NOTE
• If there are no 'occupied' schedule event when operate 'override' control, wired remote controller change indoor unit operation as below default setting value.
- operation mode : Auto
- target temperature : 86 °F(30 °C)(cool), 60 °F(16 °C)(heat)
• If there are no ‘unoccupied' schedule event when operate 'override' control, wired remote controller change indoor unit operation as 'home leave' mode default value.
- operation mode : Auto
- target temperature: 'home leave' target temperature.
• If wired remote controller received command from other controller, ‘Override’ operation will be released.
• When schedule event occurs while operating an override mode, override mode will be released and indoor unit status follow the schedule event.
36
MONITORING SCREEN
MONITORING SCREEN
How to enter fine dust status screen
• In the main screen, press [Back] button to move to monitoring/additional functions screen, and press [<, > (left/right)] button to move to fine dust status screen. (Method 1)
• In the menu screen, press [<, > (left/right)] button to select the fine dust screen category, and press [OK] button to move to the fine dust status screen. (Method 2)
MONITORING SCREEN
37
Fine dusts status
It is the function to monitor dust value measured by the dust sensor mounted inside the air conditioner.
• In the fine dust status screen, you can check fine dust, ultra fine dust, and super ultra fine dust concentration values.
• The overall index displays the worst dust status value among the three dust status values.
!
NOTE
• The fine dust status may not be displayed in some products.
• Fine dust status can be checked only when the product is in operation.
38
SUB FUNCTION SETTING
SUB FUNCTION SETTING
Sub function entrance and setting method
In the menu screen, press [<,>(left/right)] button to select the sub function category, and press
[OK] button to move to the sub function setting list screen.
In the sub function setting list screen, if you press [<, >(left/right)] button, you can turn on/off the corresponding sub function. (method 1)
In the main screen, press [Back] button to move to the monitoring/sub function screen, and press
[<,>(left/right)] button to move to the sub function screen. In the sub function screen, select the sub function category to set, and if you press [OK] button, you can turn on/off the corresponding function. (method 2)
SUB FUNCTION SETTING
39
Energy Saving Setting
The energy saving cooling function is the function to control the desired temperature during the cooling operation to improve the comfort of the user and to improve the power saving performance.
!
NOTE
The energy saving function is an additional function, and it may not be displayed/operated in some products.
The energy saving function is possible only when the product is in the cooling operation.
40
SUB FUNCTION SETTING
Plasma Purification Setting
It makes the indoor air clean and pleasant.
SUB FUNCTION SETTING
41
Fan Auto Setting
Select fan operation after performing thermal control of indoor units.
If set to 'ON', fan operation keeps on after thermal operation of indoor units.
!
NOTE
The air cleaning function is an additional function, and it may not be displayed/operated in some products.
The air cleaning function is possible only when the product is in operation.
If you want air cleaning single operation, set air cleaning in the wind only operation.
!
NOTE
The fan auto function is an additional function, and it may not be displayed/operated in some products.
42
SUB FUNCTION SETTING
Humidification setting
It is the function to activate the humidifier installed in the product when the indoor air is dry.
SUB FUNCTION SETTING
43
Electric Heater Setting
It is the function to reinforce the heating capability by turning on the electric heater during the heating operation.
!
NOTE
The humidification function is an additional function, and it may not be displayed/operated in some products.
!
NOTE
It can be set only in the heating operation.
The heater function is an additional function, and it may not be displayed/operated in some products.
44
SUB FUNCTION SETTING
Robot Cleaning Setting
Robot cleaning function is the function to automatically perform the filter cleaning with the cleaner in the product when the air conditioner is used for certain period of time.
SUB FUNCTION SETTING
45
Ventilation kit Setting
Function enables operation of an optional ventilation kit with indoor units
!
NOTE
It can be set 30 seconds after the operation stopped.
The robot cleaning function is an additional function, and it may not be displayed/operated in some products.
!
NOTE
The ventilation kit function is an additional function, and it may not be displayed/operated in some products.
46
SUB FUNCTION SETTING
Comfort Cooling Setting
The comfort cooling is the function to automatically control the cooling strength to maintain the pleasant feeling without turning off the product after the indoor temperature reached the desired temperature.
ZONE CONTROL SETTING
Zone Control
A function to control zone with duct type indoor units.
Wired Remote controller can control maximum 8 zones.
ZONE CONTROL SETTING
47
OK
!
NOTE
The comfort cooling function is an additional function, and it may not be displayed/operated in some products.
The comfort cooling function is only possible when the product is in the cooling operation.
!
NOTE
According to installation setting value
• If no function is supported this entry can not function.
• Old type
- Zone control is currently only available to monitor.
• New type(4zone or 8Zone)
- Any number of zones is installed is displayed on the screen can be controlled.
48
LOCK SETTING
LOCK SETTING
How to enter lock setting
• In the menu screen, press [<,>(left/right)] button to select “lock setting” category, and press
[OK] button to move to the lock setting list screen.
• In the lock setting list, if you press [
∧
,
∨
(up/down)] button, you can turn on/off the corresponding lock function.
TIMER SETTING
49
TIMER SETTING
Timer entrance and setting method
• In the menu screen, press [<,>(left/right)] button to select the timer category, and press [OK] button to move to the timer setting list screen.
• In the timer setting list screen, press [
∧
,
∨
(up/down)] button to select the timer to set, and press [OK] button to move to the detail screen.
• After setting the value, when you press [OK] button, the timer is activated.
• After setting the value, if you press [Back] button, the changed value will not be applied.
OK
OK
Lock setting – all, on/off, mode, temperature range lock
• It is the function to lock the button operation of the remote controller so that children or other persons cannot use it without permission.
• It is the function to limit the desired temperature range that can be set in the wired remote controller.
Lock
All lock
On/Off lock
Mode lock
Temperature range lock
Description
It locks all button operation of the remote controller.
It locks the On/Off button operation of the remote controller.
It locks the operation mode button operation of the remote controller.
It is the function that can limit the range of the desired temperature that can be set in the wired remote controller.
- Single: Lower limit : 16~30 °C (60~86 °F)
Upper limit : 16/18~30 °C (60/64~86 °F)
- Dual : Cooling : 50~99 °F (10~37.5 °C)
Heating : 40~90 °F (4~32 °C)
!
NOTE
In the central controller, when the central control temperature range lock is set, the wired remote controller’s temperature lock setting is cleared.
The temperature change by external equipment is reflected regardless of the remote controller temperature range lock.
50
TIMER SETTING
Simple timer
You can easily set the timer in the range of 1~7 hours in the units of 1 hour.
TIMER SETTING
51
Sleep timer
Sleep timer is the function to operate the air conditioner in sleep mode before going to sleep for certain hours and stop the operation.
OK
OK
!
NOTE
If the product operation is On, the easy timer turns off the operation after the corresponding time.
If the product operation is Off, the easy timer turns on the operation after the corresponding time.
If the easy timer operation is turned On/Off before the timer operation, the set timer will be cleared.
!
NOTE
You can set the sleep timer while the product is in operation.
If the sleep timer operation is turned On before the timer operation, the set timer will be cleared.
52
TIMER SETTING
Turn-off Reservation
The product is automatically turned Off at the set timer time.
OK
Turn-on Reservation
The product is automatically turned On at the set timer time.
TIMER SETTING
53
OK
!
NOTE
Even if the Turn-off Reservation operation is turned On/Off after the setting and before the timer operation, the set timer is not cleared.
!
NOTE
Even if the Turn-on Reseravation operation is turned On/Off after the setting and before the timer operation, the set timer is not cleared.
54
SCHEDULE SETTING
SCHEDULE SETTING
How to enter schedule
• In the menu screen, press [<,>(left/right)] button so select the schedule category, and press
[OK] button to move to the schedule setting list screen.
• In the schedule setting list screen, press [
∧
,
∨
(up/down)] button to select the menu to set, and press [OK] button to move to the detail screen.
SCHEDULE SETTING
55
Daily Schedule
It is the function that can check the status of the timer (schedule) saved in the remote controller.
• In the schedule list, select the daily schedule status category, and press [OK] button to move to the detail daily schedule status screen.
• You can use the remote controller’s [<,>(left/right)] button to check the timer information of other dates.
• You can use the remote controller’s [
∧
,
∨
(up/down)] button to check the corresponding date’s other timer information.
OK
• Select the timer information, and press [OK] button to move to the corresponding timer’s edit screen.
!
NOTE
In the daily schedule status screen, even if the timer (schedule) is set, if the corresponding date is designated as an exception date, the schedule will not be performed.
Less than 5 schedules per day is recommended.
56
SCHEDULE SETTING
Schedules & Edit
It is the function that can check the status of the timer (schedule) saved in the remote controller.
• In the schedule list, select the daily schedule status category, and press [OK] button to move to the daily schedule status detail screen.
• You can use the remote controller’s [<,>(left/right)] button to check other date’s timer information.
You can check the set timer’s operation information (operation
On/Off, operation mode, desired temperature), timer time, period, and day of week.
• You can edit the saved schedule’s timer information.
- Select the schedule to edit using [
∧
,
∨
(up/down)] button, and press [OK] button to move to the edit screen.
Schedules & Edit – Add schedule
Description of each stage in Add schedule
SCHEDULE SETTING
57
Stage 1. Period setting Stage 2. Day of week setting
Stage 3. Time setting Stage 4. Operation setting
• Select the timer information, and press [OK] button to move to the corresponding timer’s edit screen.
< If schedule is changed > < If schedule is deleted >
Add schedule is completed
In ‘Stage 1’, it sets the period to perform the timer.
In ‘Stage 2’, it sets the day of week to perform the timer.
- You can select ‘Everyday / Weekend / Weekdays / Individual selection’.
In ‘Stage 3’, it sets the start time for the timer.
In ‘Stage 4’, it sets the timer operation information.
- If ‘Stop’ is selected, you cannot set the mode / temperature / fan speed.
When stages 1~4 are completed, along with the message of ‘schedule is added’, it moves to
View and edit schedule screen.
58
SCHEDULE SETTING
Exception day
It is the function to automatically stop the operation on the set timer day.
• In the schedule list, select the exception day category, and press [OK] button to move to the
Exception day designation detail screen.
• In the exception day, you can check, and add/change/delete the exception day information saved in the remote controller.
- To add an exception day, in the Exception day registration detail screen, designate year/month/day, and press [OK] button to save the Exception day.
- Select the Exception day to edit using [
∧
,
∨
(up/down)] button, and press [OK] button to move to the edit screen.
ENERGY
59
ENERGY (air conditioner / DX ventilator)
How to enter energy
• In the menu screen, press [<,>(left/right)] button to select the energy category, and press [OK] button to move to the energy list.
OK
- In the exception day edit screen, you can check, delete/change the corresponding exception day’s setting contents.
- When you change the exception day information, you need to save it after the change.
60
ENERGY
Instantaneous power check
It is the function that can check the product’s instantaneous power.
※
There may be some error with the actual instantaneous power, so use it only for reference.
• In the energy list, select the “Instantaneous power” category, and press [OK] button to move to the detail screen.
ENERGY
61
Energy consumption
You can check the energy consumption (operation time, power consumption).
※
There may be some error with the actual consumption, so use it only for reference.
• In the energy list, select the “energy consumption” category, and press [OK] button to move to the detail screen.
OK
OK
• In the detail screen, press [<,>(left/right)] button to move to the power consumption and operation time screen.
• The target and the value of all can be set in the energy setting.
• The usage ratio compared to the target is the value expressed in current/target * 100.
※
For how to set the energy, refer to the energy setting.
!
NOTE
Instantaneous power: It is the power currently used in the product.
<, >
62
ENERGY
• Operation time unit is time (hr.), and power consumption unit is kWh.
• The power consumption display can be checked when it is connected to the indoor unit that supports the power consumption information display function.
List
Year On Year Usage
Description
Power consumption
You can see the power consumption compared to the same month of the previous year.
Operation time
You can see the operation time compared to the same month of the previous year.
Weekly usage
Monthly usage
Yearly usage
It displays the daily power consumption of the current month.
It displays the weekly power consumption of the current month.
It displays the daily operation time of the current month.
It displays the weekly operation time of the current month.
It displays the monthly power consumption of the current year.
It displays the monthly operation time of the current year.
ENERGY
63
Energy saving - Temperature Setback Timer
It is the function to return to the desired temperature after the set time after the product operation for energy saving.
• In the energy list, select “Energy saving” category, and press [OK] button to move to the energy saving screen.
• In the energy saving list, select “Temperature Setback Timer” category, and press [OK] button to move to the Temperature Setback Timer setting screen.
OK
OK
• When it is set to On, you can set the time (10 minutes ~ 120 minutes, 10 minutes unit) and the temperature (18°C ~ 30°C), and after the setting, when you press [OK] button, the set value is saved.
• When the desired temperature setback timer setting is set to “On”, after the set time, the desired temperature is recovered to the set temperature.
!
NOTE
When it is set at the same time with the remote controller desired temperature range lock or the central control temperature range lock, it may not return to the desired temperature.
64
ENERGY
Energy saving - Time Limit Control
It is the function to stop the product operation after the set time after starting the product operation for the energy saving.
• In the energy saving list, select “time limit control” category, and press [OK] button to move to the time limit control setting screen.
ENERGY
65
Energy setting - outdoor unit capacity setting
It is the function that can set the outdoor unit capacity.
• In the energy list, select “energy setting” category, and press [OK] button to move to the energy setting screen.
• In the energy setting list, select “outdoor unit capacity setting” category, and press [OK] button to move to the outdoor unit capacity setting screen.
OK
OK
• In the detail screen, you can select “On/Off” to turn on and off the time limit control function.
When it is set to On, you can set the time (30 minutes ~ 540 minutes, 30 minutes unit), and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press [Back] button, it moves to the list screen without saving the set value.
• If the time limit control is set to “On”, the operation stops after the set time.
!
NOTE
If it is set at the same time with the remote controller operation lock, the time limit control will not be performed.
OK
OK
• In the detail screen, you can select “On/Off” to set the outdoor unit capacity. If it is set to On, you can set the outdoor unit capacity (minimum 1kW), and after the setting, if you press [OK] button, the set value is saved. If you do not press [OK] button but press “Back’ button, it moves to the list screen without saving the set value.
• If the capacity setting is set to “On”, in the Instantaneous power screen, it is displayed as “all” capacity.
• For the outdoor unit capacity, refer to the label of the outdoor unit product.
- For Single product and Multi product, the first 3 digits of the model name is the outdoor unit capacity. ex) For ABC1019…, it is 10.1kW
- For Multi-V product, the first 2 digits of the model name < 0.75 is the outdoor unit capacity. ex) For ABCD101.…, it is 10 * 0.75 = 7.5kW
• For TMS users, refer to the all capacity displayed on TMS.
!
NOTE
According to the user input, there may be difference to the actual product capacity.
66
ENERGY
Energy setting - target instantaneous power setting
It is the function that can set the Instantaneous power’s target value.
You can set the target value to find the power consumption status.
• In the energy setting list, select “target Instantaneous power” category, and press [OK] button to move to the target Instantaneous power setting screen.
ENERGY
67
Energy setting - target power consumption
It is the function to set the target power consumption per hour.
• In the energy setting list, select “target power consumption” setting category, and press [OK] button to move to the target power consumption setting screen.
OK
OK
• In the detail screen, you can select “On/Off” to set the target Instantaneous power.
If it is set to On, you can set the target Instantaneous power (minimum 1kW), and after the setting, if you press [OK] button, the set value is saved.
- If the outdoor unit capacity is set, the maximum value is the outdoor unit capacity
- If the outdoor unit capacity is not set, the maximum value is 9999kW
If you do not press [OK] button but press “Back’ button, it moves to the list screen without saving the set value.
• When the target Instantaneous power setting is set to “On”, in the Instantaneous power screen, it is displayed as “all” capacity.
OK
OK
• In the detail screen, you can select “On/Off” to set the target power consumption.
When it is set to On, you can set the target power consumption (minimum 1kWh, maximum
100kWh), and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press “Back’ button, it moves to the list screen without saving the set value.
• If the target power consumption setting is set to “On”, it is displayed as the energy consumption’s power consumption target value.
- Daily target consumption: Weekly usage’s daily target
- Weekly target consumption: Monthly usage’s weekly target (daily target * 7)
- Monthly target consumption: Yearly usage’s monthly target (daily target * 31)
68
ENERGY
Energy setting - target operation time
It is the function that can set the Instantaneous power’s target value.
You can find the power consumption status by setting the target value.
• In the energy setting list, select “target operation time” category, and press [OK] button to move to the target operation time setting screen.
OK
OK
• In the detail screen, you can select “On/Off” to set the target operation time.
When it is set to On, you can set the target operation time (minimum 1hr. and maximum 24hr.), and after the setting, if you press [OK] button, the set value is saved.
If you do not press [OK] button but press “Back’ button, it moves to the list screen without saving the set value.
• If the target operation time setting is set to “On”, it is displayed as the energy consumption’s operation time target value.
- Daily target : Weekly usage’s daily target
- Weekly target : Monthly usage’s weekly target (daily target * 7)
- Monthly target : Yearly usage’s monthly target (daily target * 31)
ENERGY
69
Energy setting - Alarm Popup Setting
It is the function to set whether to use the target power consumption and the target operation time notice popup window.
• In the energy setting list, select “target operation time” category, and press [OK] button to move to the target operation time setting screen.
• In the notice popup list, select “target power consumption notice or target operation time notice” category, and press [OK] button to move to the detail setting screen.
OK
OK
OK
• You can set the notice popup as “daily”, “weekly”, “monthly”.
After the setting, if you press [OK] button, the setting is saved and moves to the previous screen.
• When the target power consumption notice is set to “On, daily”
If the daily target power consumption’s 80%, 90%, 95%, and 100% power is used a day, the popup screen appears.
• When the target operation time notice is set to “On, daily”
When the product is operated at the daily target operation time’s 80%, 90%, 95%, and 100%, the popup screen appears.
!
NOTE
The popup message appears once every hour.
70
ENERGY
Energy setting – Usage data initialization
It is the function to initialize all of the power consumption and operation time information.
• In the energy setting list, select “consumption data initialization” category, and press [OK] button to move to the consumption data initialization setting screen.
OK
OK
OK
• In the initialization popup screen, if you press “check” button, all previously saved power consumption and operation time are deleted.
FUNCTION SETTING
71
FUNCTION SETTING
How to enter function setting
To enter the menu displayed at the bottom, you need to enter the function setting menu as follows.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK] button to move to the setting list.
• In the setting list, select the function setting category, and press [OK] button to move to the function setting list.
OK
72
FUNCTION SETTING
Function Setting
Menu
Auto dry setting
Description
Vane angle control setting You can control the wind blowing angle.
Elevation grill setting It is the function to operate the Elevation grill for the indoor unit filter cleaning.
Robot cleaning setting
Robot cleaning function is the function to automatically perform the filter cleaning with the cleaner of the product when the air conditioner is used for certain time period. It sets the manual or automatic operation of the robot cleaning. You can set it 30 seconds after the stopping of the operation.
Auto dry function is the function to remove mold and moisture by drying the inside of the indoor unit after the cooling operation and when the product is turned off.
Filter sign check and initialization
When it becomes the time for the indoor unit filter cleaning, the filter cleaning display appears, and it is the function to remove the display.
Change Temperature setting
Dead Band
Change Temperature is the function to set the temperature for the automatic conversion between cooling and heating according to the temperature in AI operation mode.
When heating and cooling desired temperatures have been changed, the set value will maintain a difference between the heating and cooling desired temperature.
Wi-Fi pairing
It is the function to perform the pairing function of the Wi-Fi module connected to the indoor.
Zone Name setting Zone name settings allow you to select zone name.
Override set time setting When timed override is used, the set time will be a default value.
Home leave set temperature setting
When customer operate as home leave mode, this setting temperature value will be applied.
Comfort cooling setting It is the function to set the outdoor unit Comfort saving operation stage value.
ODU Refrigerant Noise
Reduction setting
It is the function to set the outdoor unit’s refrigerant noise reduction function.
Defrost Mode setting It is the function to set the outdoor unit’s defrost mode operation.
Smart load control setting
Low noise mode time setting
It is the function to set the outdoor unit’s smart load control stage value.
(Smart load control is the function to calculate the necessary performance with the indoor and outdoor air temperature and humidity and operate.)
It is the function to set the start and end time of the outdoor unit’s low noise mode operation.
Advanced fan speed “Auto” It is the function to set the indoor unit’s fan auto by temperature.
Delay time setting
(exclusive for ventilation)
It is the function to set the ventilation operation to start after the delay time.
Midnight air cooling
(ventilation interface)
It is the function to discharge indoor air and supply cool outdoor air into the indoor during summer nights to save energy.
Human detection mode It is the function to set the operation of human detection mode.
Discharge direction
This is a function to set the usage of the upper and lower vanes when operating the product.
CO
2 fan control
Economizer setting
A function that controls the fan when the product is turned ON/OFF, based on the CO
2 concentration in the ventilation product.
Provides outside air to a room to save energy and improve the air quality indoors.
FUNCTION SETTING
73
Vane angle control setting
You can control the wind blowing angle.
- In the function setting list screen, press [
∧
,
∨
(up/down)] button to select the vane angle control category, and press [OK] button to move to the up/down vane angle detail screen.
OK
• In the detail screen, press [
∧
,
∨
(up/down)] button to select “individual control, overall control, standard”.
• Use [<,>(left/right)] button to select the vane.
- The selected vane is moving. Check the moving vane.
• Press [
∧
,
∨
(up/down)] button to select the desired wind angle, and press [OK] button to save the setting.
- The wind angle’s setting range can be changed to 5 stages or 6 stages according to the product.
※
If you do not press [OK] button, the selected wind angle will not be reflected.
Control
Each
All
Standard
Description
It sets the vane angle individually.
It sets the vane angle of all the vanes of the product at once.
It sets the vane angle to the factory initialization state.
!
NOTE
For some product types, there are products with only 1 or 2 vanes.
74
FUNCTION SETTING
Elevation grill setting
It is the function to operate the Elevation grill for the indoor unit filter cleaning.
- While the product operation is stopped, if you use [<,>(left/right)] button to select the setting value, the grill operation status changes.
FUNCTION SETTING
75
Robot cleaning setting
Robot cleaning function is the function to perform the automatic filter cleaning with the cleaner of the product when the conditioner is used for certain period of time. It sets the manual or automatic operation of the robot cleaning.
- It can be set 30 seconds after the operation stop.
• You can use [<,>(left/right)] button to set the following setting values as follows.
Value
Up
Stop
Down
Description
Raises the Elevation grill toward the product
Stops the movement of the Elevation grill
Lowers the Elevation grill toward the floor
!
NOTE
The Elevation grill setting function may not work in some products.
Value
Auto
Manual
Description
It automatically performs the robot cleaning when the accumulated indoor unit operation time passes 30 hours
It manually performs the robot cleaning.
!
NOTE
The robot cleaning setting function may not work in some products.
Auto dry setting
Auto dry function is the function to remove mold and moisture by drying inside the indoor unit after the cooling operation and when the product is turned off.
• You can use [<,>(left/right)] button to set the following setting values as follows.
Value
Use
Not Use
Use auto dry function
Not use auto dry function
Description
!
NOTE
Auto dry setting function may not work in some products.
76
FUNCTION SETTING
Filter sign check and initialization
When it becomes the time for the indoor unit filter cleaning, the filter cleaning message appears, and it is the function to remove the message.
• In the function setting list, select the Filter sign check and initialization category, and press [OK] button to display the detail screen.
FUNCTION SETTING
77
Change temperature setting
Change Temperature is the function to set the automatic Change Temperature between cooling and heating operation according to the temperature in AI operation mode.
• In the function setting list, select the Change Temperature category, and press [OK] button to move to the detail screen.
OK
OK
Filter sign
Good
Normal
Caution
Bad
Usage time is 70% or less
Usage time is 71~80%
Usage time is 81~99%
Usage time is 100%
Description
- When it becomes time to the filter clean, “Filter cleaning or replacement is required.” message is displayed. Enter the Filter sign check and initialization detail screen.
- If the product has the function to display the time remaining until the filter cleaning, even if the filter cleaning message is not displayed, you can enter the Filter sign check and initialization.
- If there is a remaining time display function, when you enter the Filter sign detail screen, you can see the consumption and the remaining time.
!
NOTE
• Some products have a Filter Time Remaining function that can be accessed with Filter Sign check.
• Dirty filters will increase the cost to cool or heat the conditioned space.
• The filter check message is cleared after certain time without a separate clearing.
Value
1~7°C(Default : 2°C)
It is the function that can be used only in cooling/heating product.
Example of using Change Temperature
Condition
1) Mode: AI mode
2) temperature: 22°C
3) Change Temperature: 3°C
→
Change Temperature 3°C difference
※
In case of the above conditions, it operates as in the graph.
Temp( ഒ )
ڸ ڸ
25 ഒ
22 ഒ
19 ഒ
ڸ : Cooling operation start
ڹ : Heating operation start
ڹ
!
NOTE
The Change Temperature setting function may not work in some products.
78
FUNCTION SETTING
Dead Band
Dead Band function is used with a dual setpoint mode.
When heating and cooling desired temperatures have been changed, the set value will maintain a difference between the heating and cooling desired temperature.
• In the function setting list, select the dead band category, and press [OK] button to move to the detail screen.
FUNCTION SETTING
79
Wi-Fi pairing setting
It is the function to perform the pairing function of the Wi-Fi module connected to the indoor unit.
• In the function setting list, select the Wi-Fi pairing category, and press [OK] button to move to the detail screen.
- After selecting “Apply”, if you press [OK] button, the Wi-Fi pairing popup window is created, select “check” and press [OK] button to request the Wi-Fi pairing.
OK
OK
!
NOTE
Dead Band function only can use in dual setpoint mode.
• When changing the desired cooling temperature, in case of that the difference with the heating temperature becomes lesser than its minimal value of difference, it lowers the desired heating temperature automatically.
• When changing the desired heating temperature, in case of that the difference with the heating temperature becomes lesser than its minimal value of difference, it raises the desired cooling temperature automatically.
!
NOTE
The Wi-Fi setting function may not work in some products.
80
FUNCTION SETTING
Zone Name setting
Zone name settings allow you to select zone name.
OK
OK
!
NOTE
Zone name setting function may not work in some indoor unit products.
FUNCTION SETTING
81
Override Set Time Setting
Override Set Time function can only be used in Dual Setpoint Control mode.
When timed override is used, the set time will be a default value.
OK
!
NOTE
Override Set Time function can only be used in a dual setpoint control mode.
82
FUNCTION SETTING
Home Leave Set Temperature Setting
Home Leave Set Temperature function is used in Dual Setpoint Control mode.
When customer operate as home leave mode, this setting temperature value will be applied.
Comfort cooling setting
It is the function to set the outdoor unit Comfort saving operation value.
• You can set the following values using [<,>(left/right)] button.
FUNCTION SETTING
83
OK
!
NOTE
Home Leave Set Temperature function can only be used in a dual setpoint control mode.
Value
Step 1
Step 2
Step 3
!
NOTE
The Comfort cooling function does not work in the group control.
Comfort cooling setting function is only available in some products.
ODU Refrigerant Noise Reduction setting
It is the function to set the outdoor unit’s refrigerant noise reduction function.
• You can use [<,>(left/right)] button to set the following setting values as follows.
Value
Step 0
Step 1
Step 2
Description
Not use
Outdoor unit noise mode 1
Outdoor unit noise mode 2
!
NOTE
The ODU Refrigerant Noise Reduction function can be set only when the installer setting’s outdoor unit function M/S setting is set to “Master”.
ODU Refrigerant Noise Reduction function is only available in some products.
84
FUNCTION SETTING
Defrost mode setting
Change the outdoor unit’s defrost mode operation.
• Select value using [<,>(left/right)] button.
FUNCTION SETTING
85
Smart load control(SLC) setting
Change the outdoor unit’s Smart Load Control stage value.
(Smart load control is the function to calculate the indoor air temperature, outdoor air temperature, and humidity to operate effectivly.)
• In the function setting list, select the Smart load control category, and press [OK] button to move to the detail screen.
Value
Step 0
Step 1
Step 2
Step 3
Not use
Forced snow removal
Quick defrost
Forced snow removal + quick defrost
!
NOTE
The Defrost mode setting function can be set only when the installer setting’s outdoor unit function M/S setting is set to “Master”.
Defrost mode setting function is only available in some products.
OK
Value
Off
On
Step 0
Step 1
Step 2
Step 3
Step 4
- When SLC is Operating, on the expanded screen’s monitoring information, ‘In Smart load control’ is displayed.
!
NOTE
Smart load control function can be set only when the installer setting’s outdoor unit function
M/S setting is set to “Master”.
Smart load control function is only available in some products.
Step4 settings may not be available on some indoor unit products.
86
FUNCTION SETTING
Low noise mode time setting
It is the function to set the start and end time of the outdoor unit’s low noise mode operation.
• In the function setting list, select the Low Noise Mode Time category, and press [OK] button to move to the detail screen.
- After setting the start time and the end time, press [OK] button to move to the upper level list.
- If the start time and the current time are the same, it enters the outdoor unit low noise operation mode, and in the monitoring screen, ‘in outdoor unit low noise operation mode’ message is displayed.
- If the end time and the current time are the same, the outdoor unit low noise operation mode is cleared.
FUNCTION SETTING
87
Advanced fan speed “Auto” setting
It is the function to set the indoor unit’s temperature based auto fan usage.
It is the function to automatically change the fan speed according to the difference between the indoor temperature and the desired temperature.
• You can set the following setting values using [<,>(left/right)] button.
OK
Value
Set
Clear
Description
Change the fan speed automatically
Do not change the fan speed automatically
!
NOTE
Advanced fan speed “Auto” setting function is only available in some products.
!
NOTE
Low noise mode time setting function can be set only when the installer setting’s outdoor unit function M/S setting is set to “Master”.
Low noise mode time setting function is only available in some products.
!
CAUTION
If the function is not used, please set it to Off.
When you enter the low noise operation, the cooling capacity may be degraded.
88
FUNCTION SETTING
Delay time (exclusive for ventilation)
It is the function to set the ventilation operation to start after the delay time.
• In the function setting list, select the delay time category, and press [OK] button to move to the detail screen.
- After setting the minute, press [OK] button to move to the upper level list.
FUNCTION SETTING
89
Midnight air cooling (ventilation interface)
It is the function to discharge indoor air and supply cool outdoor air into the indoor during summer nights to save energy.
• In the function setting list, if you select midnight outdoor air cooling category and press [OK] button, it moves to the detail screen.
- When you set the start and end time and press [OK] button, it saves and moves to the upper level list.
OK
OK
Value
0 ~ 60 Minutes
!
NOTE
Whether to run the midnight air cooling is decided only when both air conditioner and ventilation are stopped.
• Even if it is the set midnight air cooling time, it enters the midnight air cooling only when the outdoor temperature conditions is met.
• During the midnight air cooling operation, “in midnight outdoor air cooling” message is displayed on the monitoring screen.
• Midnight air cooling function may not work in some products.
!
CAUTION
If you do not use the function, please set it as off.
90
FUNCTION SETTING
Human detection mode setting
It is the function that enables energy saving through the human detection power saving operation and wind direction setting.
In the function setting list, select human detection operation mode category and press [OK] button to move to the lower level setting list.
FUNCTION SETTING
91
OK
After selecting human detection wind direction category, you can set the following setting values using [<,> (left/right)] button.
Value
OFF
Direct
Indirect
Description
Do not use human detection wind direction control
Human detection direct wind operation
Human detection indirect wind operation
!
NOTE
Human detection operation setting function may not work in some products.
Discharge direction
This is a function to set the usage of the upper and lower vanes when operating the product.
You can set the following setting values using [<,>(left/right)] button.
After selecting human detection power saving mode category, if you press [OK] button, it moves to the detail screen.
You can select OFF
← →
On/Off Power saving
← →
Temperature power saving for mode value.
You can set the time value when you select On/Off power saving or Temperature power saving.
Discharge direction
Concurrency (whole)
Top
Bottom
!
NOTE
Discharge direction setting function may not be available on some products.
92
FUNCTION SETTING
CO
2
Fan Control(general ventilator)
A function that controls the fan when the product is turned ON/OFF, based on the CO
2 concentration in the ventilation product.
1 . After selecting “CO
2 fan control” in the Function settings list, press the [OK] button to go to the detail screen.
2 . After selecting “Fan control during operation on” or “Fan control during operation off” in the "
CO
2
Fan Control" list, you can set the following values using [<,>(left/right)] button.
OK
Condition 1
Operation on
Operation off
Condition 2
Off
Low
Periodic
Off
Periodic
Economizer setting
Provides outside air to a room to save energy and improve the air quality indoors.
USER SETTING
93
USER SETTING
How to enter user setting
To enter the menu displayed at the bottom, you need to enter the user setting menu as follows.
• Select the setting category, and press [OK] button to move to the setting list.
• Select the user setting category, and press [OK] button to move to the user setting list.
OK
Value
Off
Auto
Step 1
Step 2
Description
Disable the economizer function to keep the outside air damper closed.
If the outside air temperature is lower than the air temperature indoors when cooling is being operated, outside air is supplied to the room to save energy.
Opens the outside air damper opening by one stage to improve the indoor air quality by introducing fresh air into the room.
Opens the outside air damper opening by two stages to improve the indoor air quality by introducing fresh air into the room.
!
NOTE
Economizer setting function may not be available on some products.
User Setting
• You can set the product user functions.
• Some functions may not be available in some product types.
Menu
Language setting
Description
Set the language to be displayed on the remote controller.
Setpoint Type Setting It is the function to set GUI type on the remote controller.
Temperature unit setting Set the temperature unit displayed on the remote controller.
Screen saver timer setting Adjust the screen Off time of the remote controller.
LCD brightness in idle setting Adjust the remote controller’s screen brightness.
External device setting Set the name of external equipment and equipment logic setting
Date setting
Time setting
Set the date displayed on the remote controller.
Set the time displayed on the remote controller.
Summer time setting
Password setting
Schedule initialization
Theme setting
Humidity display
Set the summer time in the remote controller.
Set the password to prevent unauthorized change to remote controller settings.
Initialize all timer settings in the remote controller.
Set the theme of the remote controller screen.
It is the function to decide whether to display humidity on the main screen and additional information screen.
System reboot Restart the remote controller.
94
USER SETTING
Language setting
Set the language to be displayed on the remote controller.
• In the user setting list, select the language category, and press [OK] button to move to the detail screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous screen.
USER SETTING
95
Setpoint Type Setting
It is the function to set GUI type on the remote controller.
* Dual setpoint type is a function that makes it possible to set the cooling and heating target temperature simultaneously. It is recommended for customers accustomed to using North American thermostats.
We recommend that you use it only in the region (North America).
If select dual setpoint option, target temperature ranges will be expanded and activated override, home leave, hold mode and occupancy information based schedule.
OK
<Dual setpoint> <Single setpoint>
한국어
Deutsche
Русский
中文
Language
English
Italiano
Polski
Čeština
Français
Español
Português
96
USER SETTING
Temperature unit setting
Set the temperature unit displayed on the remote controller.
• In the user setting list, select the temperature unit setting category, and press [OK] button to move to the detail screen.
Screen saver timer setting
Adjust the screen Off time of the remote controller.
• Select the following setting values using [<,>(left/right)] button.
USER SETTING
97
OK
15sec
Value
30sec (default)
!
CAUTION
Selecting longer stand by screen will decrease LCD lifespan.
1min
LCD brightness in idle setting
Adjust the remote controller’s screen brightness.
• Select the following setting values using [<,>(left/right)] button.
Value
Celsius
Fahrenheit
1°C
0.5°C
!
CAUTION
The temperature unit function may not work or work differently in some products.
You cannot set the temperature unit in the slave wired remote controller.
0%
10%
(default)
Value
20%
!
CAUTION
Selecting brighter stand by screen will decrease LCD lifespan.
30%
98
USER SETTING
External device setting
Set the name of external equipment and equipment logic setting
• In the user setting list, select the external device setting category, and press [OK] button to move to the detail screen.
USER SETTING
99
External device types
It is the function to set the name of the External device attached to the remote controller.
• You can set the following setting values using [<,>(left/right)] button.
OK
External device use
• In the external device setting list, select “External device use” category, and press [OK] button to move to the external device use setting screen.
- If external device use setting value is use, you can see the control unit of external device in main screen.
Motor Lighting Fan
Value
Heater Pump Others
Not use
Value
Use
100
USER SETTING
On condition / Off condition
It is the function to set to use the information managed by the wired remote controller as the contact point control condition to widen the usage of the contact point (Digital Output) installed in the remote controller.
• In the external device setting list, select the On/Off condition setting category, and press [OK] button to move to the detail screen.
USER SETTING
101
Date setting
Set the date displayed on the remote controller.
• In the user setting list, select the date category, and press [OK] button to move to the detail screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous screen.
OK
OK
Condition 1
None
Aircon
Current Temp.
Condition 2
Deactivate
On
Off
Cool mode
Heat mode
Fan mode
Dry mode
Auto mode
1°C~ 39.5°C
Condition 3
-
-
-
-
-
-
-
-
Over
Under
Condition 4
Deactivate
External device name On
External device name Off
• The External device operates as the operation set in the conditions 1~3.
• If the External device is set to auto while both ON condition and OFF condition are not set, contact point OFF is output.
• If the ON condition and OFF condition are the same, it is finally processed as OFF condition.
102
USER SETTING
Time setting
Set the time displayed on the remote controller.
• In the user setting list, select the time category, and press [OK] button to move to the detail screen.
• After the setting, if you press [OK] button, the setting is saved and moves to the previous screen.
USER SETTING
103
Summer time setting
Set the daylight savings time dates in the remote controller.
• In the user setting list, select the summer time setting category, and press [OK] button to move to the detail screen.
- Summer time: The system to advance the time by 1 hour from the spring when the day is longer and return back in the fall when the day gets shorter.
- When it becomes AM 02:00 on the DST start date, the current time changes to AM 03:00, and when it becomes AM 02:00 of the DST end date, the current time changes to AM 01:00.
OK
OK
104
USER SETTING
Password setting
Set the password to prevent unauthorized change to remote controller settings.
• Select the user password setting category, and press [OK] button to move to the detail screen.
- If the password is set, when you enter “menu – setting”, you need to input password to enter the setting list.
- When you forgot the password, you can initialize the password using the installer setting’s
“password initialization”.
The initialized password is “0000”.
USER SETTING
105
Schedule initialization
Initialize all timer settings in the remote controller.
• In the user setting list, select the schedule initialization setting category, and press [OK] button to move to the detail screen.
- Press the check button to initialize the sleep/simple timer, on/off timer, schedule and exception date in the remote controller.
OK
OK
106
USER SETTING
Theme setting
Set the theme of the remote controller screen.
• Select either white or black using [<,>(left/right)] button.
USER SETTING
107
Humidity display
It is the function to decide whether to display humidity on the main screen and additional information screen.
You can use [<, > (left/right)] button to set the setting values (On or Off).
Setting value
ON
OFF
Display humidity.
Do not display humidity.
!
NOTE
If humidity display is `ON`, the displayed humidity is different according to the humidity detection location setting (installer setting).
• Remote controller: remote controller humidity display.
• Indoor unit: If it receives indoor unit humidity, it displays the indoor unit humidity, and if it does not receive indoor unit humidity, it does not display humidity.
108
USER SETTING
System restart
Restart the remote controller.
• In the user setting list, select the system restart setting category, and press [OK] button to move to the detail screen.
- In the detail screen, when you press [OK] button, a popup message is displayed, press the check button, to restart the system.
- For forced reset, press down [On/Off + Back] button for 5 seconds to restart the system.
OK
SERVICE SETTING
109
SERVICE SETTING
How to enter service setting
To enter the menu displayed at the bottom, you need to enter the service setting menu as follows.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press [OK] button to move to the setting list.
• In the setting list, select the service setting category, and press [OK] button to move to the service setting list.
OK
Service setting
• You can set the product service functions.
• Some functions may not be displayed/operated in some product types.
Menu
Service contact
Description
Check and input the service center phone number that you can call when there is service issue.
Model Information
Check the indoor/outdoor product group and capacity information to which the remote controller is connected.
RMC Version Information Check the remote controller model name and software version.
Error History View the connected indoor unit’s error history.
Open Source License View the remote controller’s open source license.
110
SERVICE SETTING
Service contact
Check and input the service center phone number that you can call when there is service issue.
• In the service setting list, select the service contact point and press [OK] button to move to the detail screen.
• While “edit” button is selected, press [OK] button to move to the edit screen, change it, and press [OK] button to change the service contact point.
SERVICE SETTING
111
Model information
Check the indoor/outdoor product group and capacity information to which the remote controller is connected.
• In the service setting list, select the indoor/outdoor model information category, and press [OK] button to move to the detail screen.
• Indoor unit capacity
- 1kWh = 1kBtu * 0.29307
kWh is the result calculated based on Btu, There may be a small difference between calculated and actual capacity.
Ex) If the indoor unit capacity is 18kBtu, it is displayed as 5kWh.
OK
OK
OK
112
SERVICE SETTING
RMC Version Information
Check the indoor/outdoor product group and capacity information to which the remote controller is connected.
• In the service setting list, select the remote controller version information check category, and press [OK] button to move to the detail screen.
SERVICE SETTING
113
Error history
View the connected indoor unit’s error history.
• In the service setting list, select ‘check error history’ category, and press [OK] button to move to the detail screen.
- You can view up to 20 error instances sorted by date occurred.
OK
OK
114
SERVICE SETTING
Open source license
View the remote controller’s open source license.
• In the service setting list, select the open source license category, and press [OK] button to move to the detail screen.
OK
INSTALLATION
115
INSTALLATION
Installation of Remote Controller
• After fixing the remote controller installation plate on the desired location, fix it firmly with the provided screws.
- If the installation plate is not flat on the surface, it may result in the controller being twisted and cause a defect.
- If there is a mounting box, install the remote controller installation plate using the fixings holes which suit, as in the below diagrams.
- Do not leave a gap with the wall or product loose after the installation.
• The wired remote controller cable can be installed in 4 directions. Install to the suitable direction according to the installation environment.
- Installation direction: Rear entry, top side, right side, left side.
- When you install the remote controller cable at the top, right and left side, remove the remote controller cable guide hole before the installation.
※
Use a long nose pliers to remove the guide hole.
• After removing the hole, trim the cut surface neatly.
ں Left side guide groove
ڹ Top side guide groove
ڻ Right side
ڹ Top side guide groove guide groove
ڸ Rear cable entry
ڻ Right side guide groove
ڹ Top side guide groove
ں Left side guide groove
• When installing the remote control cable on the left side, be sure to install it in the following guide.
1. Make the cable to "
ㄱ
" shape as shown below.
2. Fit the bent "
ㄱ
" cable into the upper center piece of case.
3. Tighten the installation plate with preventing interference with the surrounding guide structure.
※
If the cable is assembled in a shape other than "
ㄱ
", it may not be fastened to the installation plate due to interference with the structure of case.
Reference. the bent cable shape The Upper center boss for fixing the bent cable
116
INSTALLATION
• After fixing the remote controller top side on the installation plate attached to the wall as in the following figure, press the bottom side to combine with the installation plate.
- Do not leave a gap in the top, bottom, left, and right side of the remote controller and the installation plate after combining them.
- Before combining with the installation plate, arrange the cables to avoid interference with the circuit parts.
<Order of Combining>
Wall Wall
• When you remove the remote controller from the installation plate, insert a small flat head screwdriver into the bottom side separation hole and turn clockwise to separate the remote controller.
- There are 2 separation holes at the bottom part. Slowly separate one by one.
- Be careful not to damage the internal parts during the removal.
<Order of Separation>
• Use the connection cables to connect the indoor unit with the remote controller.
DC 12 V Red
Signal Yellow
GND Black
Please check if connector is normally connected.
OK
Indoor
Unit side
Connecting cable
• For the following cases, separately purchase and use the cables suitable for the situation.
- Do not install the cable over 50 m. (It may cause communication issues.)
- If the distance between the wired remote controller and the indoor unit is 10 m or more : 10 m extension cable (model name: PZCWRC1)
- If you control several indoor unit products with one wired remote controller : Group control cable (model name: PZCWRCG3)
!
NOTE
During the wired remote controller installation, do not bury it in the wall. (It may cause temperature sensor failure.)
Do not install the cable over 50 m. (It may cause communication defect.)
When you install the extension cable, carefully check the direction of the connectors on the remote controller side and the product side before the installation.
Specification of extension cable: AWG 24, 3 conductor or above.
INSTALLATION
117
Group control
• It connects and controls 2 or more air conditioner indoor units(Maximum number of IDU : 16ea) to one wired remote controller.
※
Connect using the group control cable.
Indoor unit 1
Master
RED(12V)
YELLOW(SIG)
BLACK(GND)
Indoor unit Main PCB
Indoor unit 2
Slave
YELLOW(SIG)
BLACK(GND)
Indoor unit 3
Slave
YELLOW(SIG)
BLACK(GND)
OK
①
Group control cable (PZCWRCG3): Connect to indoor unit’s wired remote controller connector
②
Extension cable (PZCWRC1): Connect to No.
① cable and slave indoor unit’s wired remote controller connector
While No.
① cable is connected, connect No.
② cable.
1 2
!
NOTE
• Connect only GND and signal cable to the indoor unit set as slave. (If power cable is also connected, it may cause loss of communication)
• Inquiries related to the purchase of the cable shall be directed to the specialized company and the service center.
• After checking the existence of the event communication in the product manual, change master/slave of the remote controller.
※
For details, refer to ‘remote controller master/slave’ contents.
• Change master/slave of the indoor unit.
- For ceiling cassette and duct product group, change the setting with the indoor unit PCB switch.
Master Slave Slave
GND
Signal cable
12V
Black
Yellow
Red
No. 3 switch OFF: master (factory ship-out based)
GND Signal cable
No. 3 switch ON: slave
OK
Yellow
118
INSTALLATION
- For the details on the wireless remote controller master/slave setting changes, refer to the wireless remote controller manual.
- After completing the master/slave setting in the indoor unit product, turn Off the power of the indoor unit product, and turn On the power after 1 minute.
!
NOTE
• During the group control, set only 1 indoor unit as master.
• During the group control, some functions other than the basic operation setting, fan speed
Low/Med/High, remote controller lock setting, and time setting may be limited.
• During the individual control, if the master indoor unit Dip switch is set to slave, malfunction may occur.
INSTALLATION METHOD TO USE EXTERNAL DEVICE
119
INSTALLATION METHOD TO USE EXTERNAL
DEVICE
Cable connection method to use external device
1) Wired remote controller-cable connection method.
- In the wired remote controller, connect the part marked in the following figure (J02C, DO-
Port) to the cable.
- According to the installation environment, there are 3 directions (Rear entry, top side, and right side) for the installation.
2) Cable extension connection method
- Among the cables connected to the wired remote controller, cut the remaining connectors on the other side, and then extend and connect the cables
- Extension cable specification: 24~26AWG.
!
CAUTION
For the External device connection, use the cable insulated with sheath for the extension connection.
Before combining with the installation plate, arrange the cables to avoid interference with the internal parts.
RMC
DO-Port 30cm
2 (GND_Black)
3 (DC 12 V_Red)
Remote controller product composition
Field connection
• Output specification
- Voltage : DC 11~12V
- Current : 5mA
120
AIR CONDITIONER AND VENTILATION INTERFACE
AIR CONDITIONER AND VENTILATION IN-
TERFACE
• It controls using the wired remote controller at a place where the air conditioner indoor unit and the ventilation product are connected and installed at the same time.
- When the power is applied, the remote controller recognizes the product and operates normally.
Independent operation
[general ventilation independent operation]
Interfaced operation
[General ventilation interfaced operation]
General ventilation
General ventilation
Air conditioner indoor unit
General ventilation
OK
WIRED
REMOTE
CONTROLLER
[Direct ventilation independent operation]
OK
WIRED
REMOTE
CONTROLLER
[Direct ventilation interfaced operation]
General ventilation
General ventilation Direct ventilation
Air conditioner indoor unit
OK
WIRED
REMOTE
CONTROLLER
OK
WIRED
REMOTE
CONTROLLER
※
The wiring method is the same as the air conditioner user manual. (Refer to the remote controller manual group control page contents)
※
Ventilation product means general ventilation product and direct cooling type ventilation product.
INSTALLER SETTING
121
INSTALLER SETTING
How to enter installer setting
!
CAUTION
The installer setting mode is the mode to set the remote controller’s detail function. If the installer setting mode is incorrectly set, it may cause product failure, user’s injury, or property damage. It must be set by the installation specialist with the installation license, and if it is installed or changed without installation license, all problems caused will be the responsibility of the installer, and may void the LG warrenty.
• In the menu screen, press [<,>(left/right)] button to select the setting category, and press
[ ∧ (up)] button for 3 seconds to enter the password input screen for the installer setting.
• Input the password and press [OK] button to move to the installer setting list.
OK OK
※
Installer setting password
Main screen
→ menu
→ setting
→ service
→
RMC version information
→
SW Version
Example) SW version : 1.00.1 a
In the above case, the password is 1001.
!
NOTE
Some categories of the installer setting menu may not be available depending on the product function or the menu name may be different.
122
INSTALLER SETTING
Installer setting – air conditioner
• You can set the product user functions.
• Some functions may not be displayed/operated in some product types.
Menu
Test run setting
Central control address
Setting
ESP setting
Temperature sensor setting
Ceiling height setting
Static pressure setting
Description
It is the function to set the trial operation at the initial product installation.
It is the function to set the central control address of the indoor unit during the central controller connection.
It is the function to set the wind amount value corresponding to each wind amount for easy installation.
It is the function to select the temperature sensor that will decide the indoor temperature.
It is the function to control the wind amount stage according to the ceiling height for the ceiling type products.
The fixed pressure setting can be set only in the duct products.
It cannot be set in other products.
RMC master/slave setting It is the function to set group control or 2-remote controller control.
Override master/slave setting
The operation master / slave selection function is to avoid other mode operations, and it is the function to prevent the selection of the opposite mode of the indoor unit set as master by the indoor units set as slaves.
Dry contact mode setting
Fixed air volume
Zone Type Setting
Zone Number Setting
Emergency Heater setting
Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
It is the function to apply different fan speeds automatically for each thermal control status.
It is possible to setup zone new type or old one of the product which is available to install the damper controller.
Zone Number is to set the number of installed zones. It's possible to control only in zone new type.
It is the function to set whether to use emergency heater control function and the usage environment.
It is the function to set common functions or some functions to be controlled by the master indoor unit standard during the group control.
Func. control during grp.
Control setting
Option Kit – Plasma / Heater /
Humidification / Elevation grill
/ Ventilation / Refrigerant leakage detection sensor
It is the function to set whether to mount option unit (Plasma / Humidification / Heater / Ventilation / Elevation grill / Aux Heater / Refrigerant leakage detection sensor) when it is additionally installed or removed after the mass production.
Expand of Temperature Range This function is used for select setting temperature range option.
Indoor unit address verification
This function allows you to check the address of the indoor unit designated by the outdoor unit.
Static pressure step setting
This is the function that static pressure of the product is divided in 11 steps for setting.
INSTALLER SETTING
123
Menu
Guard timer
Description
It is a function that sets the minimum running time of outdoor unit cycle mode when switching from cooling mode to heating mode and vice versa during Auto Operation mode.
Fan speed in Cooling thermal off
It is a function that sets the indoor unit fan movement, in cooling mode, when thermal is off.
Primary heater setting
It is the function to set the heater usage to have higher priority over the outdoor unit cycle during the indoor unit heating operation.
Air conditioner Fan operation interlocked with ventilation setting
It is the function to set whether to operate the air conditioner fan during the interface operation of the air conditioner and the ventilation product.
Indoor unit Auto-Start setting
Occupancy duration time setting
CN_CC setting
CN_EXT setting
It is a function that sets whether to restore the indoor unit operation by resuming the previous power-on state or as power-off state in the power failure compensation.
It is the function to set the occupied decision maintaining time among the occupied sensor values.
It is the function to set whether to install (use) Dry Contact.
(It is not a function for Dry Contact installation, but it is a function to set the usage of the indoor unit’s CN_CC port.)
It is the function to set the indoor unit’s Dry Contact Port to control external input and output according to DI/DO set by the customer. (It is the function to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
ODU function master setting It is the function to set the outdoor unit’s function Master / Slave.
Fan continuous operation setting
It is the function to set the indoor unit’s continued Fan function usage.
It is the function to maximize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation longer than the previous operation method.
Low noise mode priority setting
It is the function to set the main agent of the low noise mode control.
(It is the function to set only one of the outdoor unit / remote controller can control the low noise operation.)
Human detection sensor setting
It is the function to set whether to install human detection sensor and operation standard value.
Humidity sensing position It is the function to set the location to detect humidity.
ODU cycle priority This function can select standby mode or priority cooling.
Outdoor temp. for heating stages
This function can select outdoor temperature values for use reference point of heater and heating mode operation.
Estimated energy display
CN_PTC setting
Password initialization
This function can set to display energy data which ODU estimated.
This is a function to set PTC Port of indoor unit.
It is the function to initialize (0000) the password when you forgot the password set in the remote controller.
124
INSTALLER SETTING
Installer setting - ventilator
• You can set the product user functions.
• Some functions may not be displayed/operated in some product types.
Menu Applied products Description
Test run setting
Central control address Setting
Air supply ESP
Air discharge ESP
Temperature sensor setting
DX(Direct Exchanger) Type It is the function to set the trial operation at the initial product installation.
General
General/DX Type
DX Type
It is the function to set the central control address of the indoor unit during the central controller connection.
It is the function to set the fan speed value corresponding to the air supply side fan speed.
It is the function to set the fan speed value corresponding to the air discharge side fan speed.
It is the function to select the temperature sensor that will decide the indoor temperature.
Product direction
Express ventilation priority
RMC master/slave setting
General
General/DX Type
It is the function to set the ventilation indoor unit’s installation direction.
It is the function to set the priority of the air supply and discharge during the express ventilation operation.
It is the function to set group control or 2-remote controller control.
Override master/slave setting
Dry contact mode setting
Fixed fan speed setting
Hum. Of Stand-alone Vent.
Mode
Hum. Of Vent. With Heating
Oper.
Vent. Fan Speed Alignment
Indoor unit address verification
Indoor unit Auto-Start setting
CN_EXT setting
ODU function master setting
Low noise mode priority setting
Filter check alarm
DX Type
DX Type
DX Type
General/DX Type
DX Type
General
DX Type
DX Type
DX Type
DX Type
DX Type
General
The operation master / slave selection function is to avoid other mode operations, and it is the function to prevent the selection of the opposite mode of the indoor unit set as master by the indoor units set as slaves.
Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
It is the function to set the indoor unit’s fan speed option to variable or fixed.
It is the function to set whether to use the humidification function in the direct cooling type ventilation’s ventilation single operation.
It is the function to set the direct cooling type ventilation’s heating humidification function as auto or manual.
It is the function to increase/decrease ventilation’s standard fan speed from the current status according to the field environment.
This function allows you to check the address of the indoor unit designated by the outdoor unit.
It is a function that sets whether to restore the indoor unit operation by resuming the previous power-on state or as power-off state in the power failure compensation.
It is the function to set the indoor unit’s Dry Contact Port to control external input and output according to DI/DO set by the customer. (It is the function to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
It is the function to set the outdoor unit’s function Master / Slave.
It is the function to set the main agent of the low noise mode control. (It is the function to set only one of the outdoor unit / remote controller can control the low noise operation.)
This function sets the filter check alarm of the ventilation product.
INSTALLER SETTING
125
Test run setting (air conditioner / DX ventilator)
After product installation, the Test run must be performed. For Test run related details, refer to the product manual.
• In the installer setting list, select the Test run setting category, and press [OK] button to move to the detail screen.
- You can select ‘cooling Test run / heating Test run’
- During the Test run, if you start the following functions, the Test run stops.
☞
Operation mode, desired temperature, fan speed, wind direction, start/stop
OK
126
INSTALLER SETTING
Central control address setting (air conditioner / general, DX ventilator)
It is the function to set the central control address of the indoor unit to allow communication with a central controller,
• In the installer setting list, select the central control address setting category, and press [OK] button to move to the detail screen.
- Select a hex value between 00 and FF.
Value 1: group address setting / value 2: indoor unit address setting
INSTALLER SETTING
127
ESP setting (air conditioner / general, DX ventilator)
It is the function to set the fan speed value corresponding to each fan speed for easy installation.
OK
OK
!
NOTE
If ESP is incorrectly set, the air conditioner may malfunction.
This function must be set by the installation specialist that holds an installation license.
For ventilation products, separate ESP values are used for the supply and exhaust fans.
• In the installer setting list, select the ESP setting category, and press [OK] button to move to the detail screen.
Product value
Air conditioner
Ventilation
ESP fan speed
Slow
Low
Med
High
Power
Low
High
Power
0 ~ 255
!
NOTE
Be especially careful not to switch ESP values corresponding to each fan speed.
Engineering manuals have ESP setting tables that reference air flow and corresponding value setting to achieve the flow.
The ESP values that can be set may be different for each product and capacity.
128
INSTALLER SETTING
Temperature sensor(2TH) setting (air conditioner / DX ventilator)
It is the function to select the temperature sensor to decide the indoor temperature.
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
129
Ceiling height setting (air conditioner)
It is the function to control the fan speed stage according to the ceiling height in the ceiling type product.
• You can set the following setting values using [<,>(left/right)] button.
Temperature sensor location
Remote controller
Indoor Unit
Cool
Description
Operate the system with wired remote controller’s temperature sensor
Operate the system with indoor unit’s temperature sensor
Compare the temperatures of the indoor unit and the wired remote controller and operate with the higher temperature
(There are system operated with lower temperature)
2TH
Heat
Compare the temperatures of the indoor unit and the wired remote controller and operate with the lower temperature
• 2TH function’s operation characteristics may be different for each product.
Ceiling height
Low
Standard
High
Very high
Description
Fan speed operates one step slower than the default value.
Operates at the default fan speed
Fan speed operates one step faster than the default value.
Fan speed operates two steps faster than the default value.
!
NOTE
When group control is enabled some functions are limited depending on product type.
130
INSTALLER SETTING
Static pressure setting(air conditioner)
Static pressure setting can be set only in the duct products. (It cannot be set in other products.)
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
131
Remote controller master / slave setting
(air conditioner / General, DX ventilator)
This function sets configuration for the master/slave setting through the remote controller.
• Change setting values using [<,>(left/right)] button.
Static pressure
Variable high static pressure
Fixed high static pressure
Variable low static pressure
Fixed low static pressure
V-H
F-H
V-L
F-L
Variable / Fixed
Variable
Fixed
Variable
Fixed
Description
ESP default value
High static pressure(High)
High static pressure(High)
Low static pressure(Low)
Low static pressure(Low)
• 2TH function’s operation characteristics may be different for each product.
M/S
Master (default)
Slave
Description
Using group control, the indoor units are operated based on the remote controller.
Using group control, all remote controllers except 1 master remote controller are set as slaves.
• 2TH function’s operation characteristics may be different for each product.
132
INSTALLER SETTING
Override Master/Slave setting (air conditioner / General, DX ventilator)
The operation master / slave selection function is to avoid other mode operations, and it is the function to prevent the selection of opposite mode of the indoor unit master by the indoor units set as slaves.
• Change setting values using [<,>(left/right)] button.
INSTALLER SETTING
133
Dry contact mode setting (air conditioner / DX ventilator)
Dry contact function is the function that can be used only when the dry contact devices is separately purchased and installed.
• Change setting values using [<,>(left/right)] button.
M/S
Master
Slave
Description
Using group control, this master sets the mode of slave IDU’s.
For the indoor unit set as slave, it can only select the some operation mode of the master indoor unit cycle.
Ex) Master is in cooling cycle, Slave can select cooling, dehumidification, auto, and wind only
Master is in heating cycle, Slave can select auto, heating, and wind only
!
NOTE
Override M/S setting function is only available in some products.
Value
Auto manual
!
NOTE
For dry contact mode related detail functions, refer to the individual dry contact manual.
What is dry contact?
It means the contact point signal input when the hotel card key, human body detection sensor, etc. are interfacing with the air conditioner.
Added system functionality by using external inputs (dry contacts and wet contacts).
134
INSTALLER SETTING
Fixed air volume (air conditioner / DX ventilator)
It is the function to apply different fan speeds automatically for each thermal control status.
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
135
Zone Type Setting(air conditioner)
This function is only available on some products.
This function select a type of zone control type which indoor unit support as 'new type' or 'old type'.
Value
Variable
Fixed
Comp on
Set fan speed
Set fan speed
Comp off
Low
Set fan speed
Value
Old
New(4 Zone)
New(8 Zone)
Zone Number Setting(air conditioner)
This function is only available on some products.
Zone Number is to set the number of installed zones. It's possible to control only in zone new type.
Value
New(4 zone) : 2~4
New(8 zone) : 2~8
136
INSTALLER SETTING
Emergency heater setting (air conditioner)
Enable the emergency heater control function and the usage environment.
• In the installer setting list, select the emergency heater setting category, and press [OK] button to move to the detail screen.
- In case of an error, it sets whether the emergency heater can be used / outdoor temperature standard heater operation usage setting and temperature step value setting / and during the emergency heater operation, whether to use the indoor unit fan operation.
INSTALLER SETTING
137
Function control during group Control setting (air conditioner)
This function enables the control of the common functions or some functions based on the master indoor unit during the group control.
• Change setting values using [<,>(left/right)] button.
OK
Value
Not use
Use
Description
Common function,
Use expanded function which is based on master indoor unit
!
NOTE
Common functions and some indoor unit master standard setting shall be set only during the group control with the same type indoor units.
During the group control with different indoor unit types, set it as ‘000’ to use the existing group control method.
Value
Not use
Outdoor temperature standard heater operation
-
Fan operation in emergency control
-
Use
Emergency heater
Extended emergency heater
Step 0 ~ 3
Step 0 ~ 15
On/Off
!
NOTE
This function setting must be carried out by a certified-technician.
138
INSTALLER SETTING
External devices of indoor unit setting (air conditioner)
At the Code field, select when air cleaner/heater/humidifier/elevation grill/ventilation KIT/Aux
Heater/refrigerant leakage detection sensor are newly installed to the indoor unit or when an installed KIT is removed.
• You can set the following setting values using [<,>(left/right)] button.
Expand of Temperature Range (air conditioner)
This function using in dual setpoint control mode.
This function is used for select setting temperature range option.
INSTALLER SETTING
139
Function
Plasma purification
Heater
Humidifier
Elevation grill
Ventilation Kit
Aux Heater
Refrigerant leakage detection sensor
Value
Not install / Install
Value
Clear : 60~86 °F / 16~30 °C (default)
Set : 40~99 °F / 4~37.5 °C
!
NOTE
When the set values are changed, the items below will be initialized.
- Target temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
'home leave' temperature (default: Cooling: 86 °F(30 °C)/ Heating: 60 °F(16 °C))
In case of the setting expanded temperature range (set), please note that the setting of the wired remote controller can be altered under below circumstances.
- In case of cooling at 30~37.5 °C(64~99 °F), it is changed to cooling at 86 °F(30 °C).
- In case of heating at 4~15.5 °C(40~86 °F), it is changed to heating at 60 °F(16 °C).
- If set on dual setpoint, it is changed to the current operation mode(cooling or heating) of the indoor unit.
Situation where changes in the setting occur a. Operates the Auto address work and pipe search in situations such as product installment and service.
b. Occurrence of errors and deactivation.
c. Command generated by the central control, outdoor unit, Dry contact, Remote controller, indoor unit switch.
140
INSTALLER SETTING
Indoor unit address verification (air conditioner / DX ventilator)
This function allows you to check the address of the indoor unit designated by the outdoor unit.
• In the installer setting list, select the indoor unit address check category, and press [OK] button to move to the detail screen.
INSTALLER SETTING
141
Static pressure step setting (air conditioner)
It is the function to subdivide and set the product’s Static pressure to 11 stages.
• Change setting values using [<,>(left/right)] button.
OK
Value
Step 0 ~ Step 11
!
NOTE
If Static pressure step setting is used, the Static pressure setting is not used.
For the Static pressure step value for each stage, refer to the indoor unit product manual
142
INSTALLER SETTING
Guard timer(air conditioner)
It is a function that sets the minimum running time of outdoor unit cycle mode when switching from cooling mode to heating mode and vice versa during Auto Operation mode.
Under the condition of cooling/heating switching, it switches between cooling and heating mode after operation during the time scheduled in the Guard timer.
INSTALLER SETTING
143
Fan speed in Cooling thermal off (air conditioner)
Indoor unit fan, in cooling mode, during thermal off condition.
• Select value using [<,>(left/right)] button.
Step
0
1
2
3
4
Value
0 minute
15 minutes
30 minutes
45 minutes
60 minutes
Low
Off
Setting
Value
Fan speed low
Fan off fan speed setting value
144
INSTALLER SETTING
Primary heater setting(air conditioner)
It is the function to set the air conditioner fan operation if the ventilation is operated while the air conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other.
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
145
Air conditioner Fan operation interlocked with ventilation setting
(air conditioner)
It is the function to set the air conditioner fan operation if the ventilation is operated while the air conditioner operation is stopped when the air conditioner and the ventilation are installed to interface with each other.
• You can set the following setting values using [<,>(left/right)] button.
Value Description
Not use During the heating, heater is set to be used as secondary
Use During the heating, heater is set to be used as main
Value
Off
On
Description
The air conditioner indoor unit Fan is Off during the ventilation interface
The air conditioner indoor unit operates in very weak wind during the ventilation interface
- When the air conditioner operation is Off, if the ventilation product is in operation, the air conditioner fan shall be operated, and when the fan is in operation, dust may fall, so it is the function to set the air conditioner fan operation status in case of ventilation interface through the setting.
146
INSTALLER SETTING
Indoor unit Auto-Start setting (air conditioner / DX ventilator)
It is a function that sets whether to restore the indoor unit operation by resuming the previous power-on state or as power-off state in the power failure compensation.
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
147
Occupancy duration time setting(air conditioner)
It is a function that sets the light-on/occupancy duration after motion is detected when installing an occupancy sensor.
• You can set the following setting values using [<,>(left/right)] button.
Value
Use
Not use
Description
Use indoor unit auto restart
Not use indoor unit auto restart
Value
0 Minute
10 Minutes
30 Minutes
60 Minutes
148
INSTALLER SETTING
CN_CC setting (air conditioner)
It is the function to set the usage of the indoor unit’s CN_CC port.
• Select CN_CC setting category, and press [OK] button to move to the detail screen.
INSTALLER SETTING
149
CN_EXT setting (air conditioner / DX ventilator)
It is the function to set to control the external input and output according to DI/DO set by the customer using the indoor unit’s Dry Contact Port. (It is the function to decide the usage of the contact point port (CN_EXT) mounted in the indoor unit PCB.)
• In the installer setting list, select CN_EXT setting category, and press [OK] button to move to the detail screen.
OK
OK
Value
DC auto install
(default)
Description
When power is applied to the product, indoor unit when the contact point is on in Dry Contact installed state recognizes Dry Contact installation
DC manual not install Do not use (install) Dry Contact
DC manual install Use (install) Dry Contact
Programmable DI/DO Use as Programmable DI/DO (Simple On/Off)
!
NOTE
CN_CC is the device connected to the indoor unit to recognize and control the external contact point.
Value Description
Not use (default) Use installer code No. 41 setting value (simple Dry Contact setting value)
Simple operation control
Simple operation On/Off
Single emergency stop Indoor unit single emergency stop
Occupied / Unoccupied Occupied / Unoccupied
All emergency stop
Window contact
Window contact lock
Indoor unit all emergency stop
※
It can be set only when there is indoor unit emergency stop function.
Window contact
※
It can be set only when there is window contact function.
Window contact with lock
※
It can be set only when there is window contact lock function.
150
INSTALLER SETTING
Outdoor unit function master setting (air conditioner / DX ventilator)
It is the function to set the outdoor unit’s function Master / Slave.
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
151
Fan continuous operation setting (air conditioner)
It is the function to set the indoor unit’s continued fan function usage. (It is the function to maximize the cooling/heating efficiency by the outdoor unit operating the indoor unit fan operation longer than the previous operation method.)
• You can set the following setting values using [<,>(left/right)] button.
Value
Slave
Master
Description
Cannot enter the Smart load control function setting
Cannot enter the low noise operation time setting
Cannot enter the refrigerant noise reduction setting
Cannot enter the defrost mode setting
Smart load control function setting is possible
Low noise operation time setting is possible
Refrigerant noise reduction setting is possible
Low noise operation control main agent setting is possible
Defrost mode setting is possible
!
CAUTION
※
When you change the outdoor unit function master setting from master to slave, check the operation status of the outdoor unit function (outdoor unit low noise operation, smart load control) and make sure to stop the outdoor unit function before the change.
Value
Clear
Set
Description
Do not use continued fan usage
Use continued fan usage
152
INSTALLER SETTING
Low Noise Mode Priority setting (air conditioner / DX ventilator)
It is the function to set the low noise mode control main agent. (It is the function to set that only one of the outdoor unit / remote controller can control the low noise operation.)
• You can set the following setting values using [<,>(left/right)] button.
INSTALLER SETTING
153
Human detection sensor (air conditioner)
It is the function to set whether to install human detection sensor and operation standard value.
• In the installer setting list, after selecting human detection sensor setting category, if you press
[OK] button, it moves to the detail screen.
Value
RMC
ODU(default)
Description
Ignore the outdoor unit PCB’s low noise operation Switch Setting value
- Function setting – remote controller low noise operation time menu deactivation
It is controlled in the outdoor unit itself according to the outdoor unit
PCB’s low noise operation Switch Setting value
- Function setting – remote controller low noise operation time menu deactivation
• You can set the following setting values for each category using [<,> (left/right)] button.
Value
Installation status
Detection result sending cycle
Sensitivity setting
Temperature control option
Description
Not installed, basic installation, 90º rotation installation
5 s, 30 s, 1 min., 3 min.
Standard, low sensitivity, high sensitivity
Step 0 : Keeps the product running and uses the temperature power saving function.
Step 1 : The operation of indoor units is stopped by using the temperature power saving function.
154
INSTALLER SETTING
Humidity sensing position (air conditioner)
It is the function to set the location to detect humidity.
You can use [<, > (left/right)] button to set the following setting values.
Value
Remote controller (default value)
Indoor unit
Description
Humidity sensor of the remote controller itself
Humidity received from indoor unit
INSTALLER SETTING
155
ODU cycle priority (air conditioner)
This function can set cycle priority of outdoor unit.
Multi V Heat Pump system does not support mixed mode therefore wired remote controller can not show opposite operation mode for select option while ODU operate cooling or heating cycle.
Set this function user can select opposite operation mode with wired remote controller and indoor units enter to ‘standby’ status or outdoor unit can support cooling first and operate heating with heater.
OK
156
INSTALLER SETTING
Option
Not use
Standby
Cool
Description
Does not support opposite cycle operation using wired remote controller
- When ODU operate as cooling cycle selectable operation modes with wired remote controller are cool, auto, dehumidification and fan.
- When ODU operate as heating cycle selectable operation modes with wired remote controller are heat, auto and fan
When user set opposite operation mode using wired remote controller indoor unit stop thermal operation and fan.
Cooling cycle has a priority.
When user change operation mode of specific indoor unit to cooling on heating cycle, outdoor unit change cycle to cooling and Indoor unit keep heating operation using heater.
h
Please set emergency heater and aux heater function before using this option h
When user select cooling option, additional setting menu will be activated.
The additional timer setting menu is for setting minimum cooling operation period.
Once outdoor unit change over to cooling by cooling priority, outdoor unit can change over to heating after set time.
Setting value
Step 0
Step 1
Step 2
Step 3
Step 4
Cooling operation time
45 min.(default)
30 min.
60 min.
90 min.
120 min.
INSTALLER SETTING
157
Outdoor temp. for heating stages (air conditioner)
It is a function that sets outdoor temperature values for two stage heating.
if user set outdoor temperature T1 and T2, Indoor unit will select heating stage between Indoor unit operation and heater operation.
OK
SW Version
~2.08.2a
Setting value
Not Use
Use
Not Use
Auto
Option
-
-
-
-
T1 value
-
-23 ~ 16 °C
(-10 ~ 60 °F)
-
-23 ~ 16 °C
(-10 ~ 60 °F)
T2 value
-
-23 ~ 51 °C
(-10 ~ 130 °F)
-
-23 ~ 51 °C
(-10 ~ 130 °F)
2.09.0a~
Manual
Heat pump
Heater
Heater + H/P
-
※
Even if the remote control version is 2.09.0a or more, Features may not be supported.
158
INSTALLER SETTING
Estimated energy display (air conditioner)
This function can set to display energy data which outdoor unit estimated power consumption data without wattmeter.
INSTALLER SETTING
159
Password initialization (air conditioner / general, DX ventilator)
It is the function to initialize (0000) when you forgot the password set in the remote controller.
• In the installer setting list, select the password initialization setting category, and press [OK] button to move to the detail screen.
• When you press “initialization” button, a popup screen appears, and when you press “check” button, password initialization starts, and the user password is changed to 0000.
Setting value
Use
Not Use
Description
Display energy consumption data which outdoor unit estimated
Not display energy consumption data which outdoor unit estimated
CN_PTC setting (air conditioner)
This is a function to set PTC Port of indoor unit.
OK
Setting value
Normal
Special
Description
Auxiliary heating interlock deactivated
Auxiliary heating interlock activated
160
INSTALLER SETTING
Product direction (general ventilator)
It is the function to set the direction of the ventilation product.
• Select value using [<,>(left/right)] button.
Normal
Value
Reverse
INSTALLER SETTING
161
Express ventilation priority (general , DX ventilator)
It is the function to set the priority of the air supply and air discharge during the express ventilation operation.
• Select value using [<,>(left/right)] button.
Priority in air supply
Value
Priority in air discharge
162
INSTALLER SETTING
Humidification of stand-alone ventilation mode (general , DX ventilator)
It is the function to set whether to use the humidification function during the ventilation product single operation.
• Select value using [<,>(left/right)] button.
INSTALLER SETTING
163
Humidification of ventilation with heating operation
(DX ventilator)
It is the function to set the heating humidification function of the direct ventilation to be automatic or manual.
• Select value using [<,>(left/right)] button.
Not use
Value
Use Not use
Value
Use
164
INSTALLER SETTING
Ventilation Fan Speed Alignment (general ventilator)
It is the function to change the standard fan speed of the ventilation product.
• Select value using [<,>(left/right)] button.
Default value 10% increase
Value
10% decrease 20% decrease
Filter check alarm(general ventilator)
This function sets the filter check alarm of the ventilation product.
• Select value using [<,>(left/right)] button.
GUIDE TO DIFFERENT MODE OPERATION/OPEN SOURCE SOFTWARE
165
GUIDE TO DIFFERENT MODE
OPERATION/OPEN SOURCE SOFTWARE
Different mode operation
Different mode operation is the case when the indoor units’ operation modes are different when multiple indoor units are installed to one outdoor unit. (Different mode operation doesn’t happen in the cooling exclusive model.)
• Example of different mode operation
- When one indoor unit is operated in heat while several indoor units one outdoor unit are operated in cooling, the heating operation is not performed.
- With one outdoor unit, while several indoor units are in heat mode, if one indoor unit requests in cooling or dehumidification, the operation is not performed.
Open Source Software Notice Information
To obtain the source code under GPL, LGPL, MPL, and other open source licenses, that is contained in this product, please visit http://opensource.lge.com. In addition to the source code, all referred license terms, warranty disclaimers and copyright notices are available for download. LG
Electronics will also provide open source code to you on CD-ROM for a charge covering the cost of performing such distribution (such as the cost of media, shipping, and handling) upon email request to [email protected]. This offer is valid for a period of three years after our last shipment of this product. This offer is valid to anyone in receipt of this information.
Value
Step 0 - 5