Remote Automation Solutions Bristol Communications Interface ISTRAN / ISTRAN PLUS Owner's Manual
Quảng cáo
Quảng cáo
COMMUNICATION INTERFACE
IStran/IStran Plus
Instruction Manual
Bristol Babcock
CI-3530-IStran - Jan., 2006
NOTICE
Copyright Notice
The information in this document is subject to change without notice. Every effort has been made to supply complete and accurate information. However, Bristol Babcock assumes no responsibility for any errors that may appear in this document.
Request for Additional Instructions
Additional copies of instruction manuals may be ordered from the address below per attention of the Sales Order Processing Department. List the instruction book numbers or give complete model number, serial or software version number. Furnish a return address that includes the name of the person who will receive the material. Billing for extra copies will be according to current pricing schedules.
TeleFlow ™ is a trademark and Bristol Babcock ® is a registered trademark of Bristol
Babcock Inc. Other trademarks or copy-righted products mentioned in this document are for information only, and belong to their respective companies, or trademark holders.
Copyright © 2006 Bristol Babcock, 1100 Buckingham St., Watertown, CT 06795. No part of this manual may be reproduced in any form without the express written permission of
Bristol Babcock.
IMPORTANT! READ INSTRUCTIONS BEFORE STARTING!
Be sure that these instructions are carefully read and understood before any operation is attempted. Improper use of this device in some applications may result in damage or injury. The user is urged to keep this book filed in a convenient location for future reference.
These instructions may not cover all details or variations in equipment or cover every possible situation to be met in connection with installation, operation or maintenance. Should problems arise that are not covered sufficiently in the text, the purchaser is advised to contact Bristol Babcock for further information.
EQUIPMENT APPLICATION WARNING
The customer should note that a failure of this instrument or system, for whatever reason, may leave an operating process without protection. Depending upon the application, this could result in possible damage to property or injury to persons. It is suggested that the purchaser review the need for additional backup equipment or provide alternate means of protection such as alarm devices, output limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.
If additional information is required, the purchaser is advised to contact Bristol
Babcock.
RETURNED EQUIPMENT WARNING
When returning any equipment to Bristol Babcock for repairs or evaluation, please note the following: The party sending such materials is responsible to ensure that the materials returned to Bristol Babcock are clean to safe levels, as such levels are defined and/or determined by applicable federal, state and/or local law regulations or codes. Such party agrees to indemnify Bristol Babcock and save Bristol Babcock harmless from any liability or damage which Bristol Babcock may incur or suffer due to such party’s failure to so act.
ELECTRICAL GROUNDING
Metal enclosures and exposed metal parts of electrical instruments must be grounded in accordance with OSHA rules and regulations pertaining to "Design
Safety Standards for Electrical Systems," 29 CFR, Part 1910, Subpart S, dated: April
16, 1981 (OSHA rulings are in agreement with the National Electrical Code).
The grounding requirement is also applicable to mechanical or pneumatic instruments that include electrically-operated devices such as lights, switches, relays, alarms, or chart drives.
EQUIPMENT DAMAGE FROM ELECTROSTATIC DISCHARGE VOLTAGE
This product contains sensitive electronic components that can be damaged by exposure to an electrostatic discharge (ESD) voltage. Depending on the magnitude and duration of the ESD, this can result in erratic operation or complete failure of the equipment. Read supplemental document S14006 at the back of this manual for proper care and handling of ESD-sensitive components.
Bristol Babcock 1100 Buckingham Street, Watertown, CT 06795
Telephone (860) 945-2200
A.
B.
C.
D.
E.
F.
A.
B.
WARRANTY
Bristol warrants that goods described herein and manufactured by Bristol are free from defects in material and workmanship for one year from the date of shipment unless otherwise agreed to by Bristol in writing.
Bristol warrants that goods repaired by it pursuant to the warranty are free from defects in material and workmanship for a period to the end of the original warranty or ninety (90) days from the date of delivery of repaired goods, whichever is longer.
Warranties on goods sold by, but not manufactured by Bristol are expressly limited to the terms of the warranties given by the manufacturer of such goods.
All warranties are terminated in the event that the goods or systems or any part thereof are (i) misused, abused or otherwise damaged, (ii) repaired, altered or modified without Bristol’s consent, (iii) not installed, maintained and operated in strict compliance with instructions furnished by Bristol, or (iv) worn, injured or damaged from abnormal or abusive use in service time.
THESE WARRANTIES ARE EXPRESSLY IN LIEU OF ALL OTHER WAR-
RANTIES EXPRESS OR IMPLIED (INCLUDING WITHOUT LIMITATION WAR-
RANTIES AS TO MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE), AND NO WARRANTIES, EXPRESS OR IMPLIED, NOR ANY
REPRESENTATIONS, PROMISES, OR STATEMENTS HAVE BEEN MADE BY
BRISTOL UNLESS ENDORSED HEREIN IN WRITING. FURTHER, THERE ARE
NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION OF THE
FACE HEREOF.
No agent of Bristol is authorized to assume any liability for it or to make any written or oral warranties beyond those set forth herein.
REMEDIES
Buyer’s sole remedy for breach of any warranty is limited exclusively to repair or replacement without cost to Buyer of any goods or parts found by Seller to be defective if Buyer notifies Bristol in writing of the alleged defect within ten (10) days of discovery of the alleged defect and within the warranty period stated above, and if the Buyer returns such goods to Bristol’s Watertown office, unless Bristol’s Watertown office designates a different location, transportation prepaid, within thirty (30) days of the sending of such notification and which upon examination by Bristol proves to be defective in material and workmanship. Bristol is not responsible for any costs of removal, dismantling or reinstallation of allegedly defective or defective goods. If a Buyer does not wish to ship the product back to Bristol, the Buyer can arrange to have a Bristol service person come to the site. The Service person’s transportation time and expenses will be for the account of the Buyer. However, labor for warranty work during normal working hours is not chargeable.
Under no circumstances will Bristol be liable for incidental or consequential damages resulting from breach of any agreement relating to items included in this quotation from use of the information herein or from the purchase or use by Buyer, its employees or other parties of goods sold under said agreement.
How to return material for Repair or Exchange
Before a product can be returned to Bristol Babcock for repair, upgrade, exchange, or to verify proper operation, form (GBU 13.01) must be completed in order to obtain a RA
(Return Authorization) number and thus ensure an optimal lead time. Completing the form is very important since the information permits the Bristol Babcock Repair Dept. to effectively and efficiently process the repair order.
You can easily obtain a RA number by:
A. FAX
Completing the form (GBU 13.01) and faxing it to (860) 945-3875. A BBI Repair
Dept. representative will return call (or other requested method) with a RA number.
B. E-MAIL
Accessing the form (GBU 13.01) via the Bristol Babcock Web site
(www.bristolbabcock.com) and sending it via E-Mail to [email protected]
.
A BBI Repair Dept. representative will return E-Mail (or other requested method) with a RA number.
C. Mail
Mail the form (GBU 13.01) to
Bristol Babcock Inc.
Repair Dept.
1100 Buckingham Street
Watertown, CT 06795
A BBI Repair Dept. representative will return call (or other requested method) with a RA number.
D. Phone
Calling the BBI Repair Department at (860) 945-2442. A BBI Repair Department representative will record a RA number on the form and complete Part I, then send the form to the Customer via fax (or other requested method) for Customer completion of Parts II & III.
A copy of the completed Repair Authorization Form with issued RA number should be included with the product being returned. This will allow us to quickly track, repair, and return your product to you.
&VMWXSP&EFGSGO-RG6ITEMV%YXLSVM^EXMSR*SVQ
(Providing this information will permit BBI to effectively and efficiently process your return. Completion is required to receive optimal lead time. Lack of information may result in increased lead times.)
Date___________________ RA #___________________SH_ Line No.____________
Standard Repair Practice is as follows: Variations to this is practice may be requested in the “Special Requests” section.
•
Evaluate / Test / Verify Discrepancy
•
Repair / Replace / etc. in accordance with this form
•
Return to Customer
Part I
Please be aware of the Non warranty standard charge:
•
There is a $100 minimum evaluation charge, which is applied to the repair if applicable (
√
in “returned” B,C, or D of part III below)
Please complete the following information for single unit or multiple unit returns
Address No.
Bill to :
(office use only) Address No.
Ship to:
(office use only)
Purchase Order:
Phone: Fax:
Contact Name:____________________________________
E-Mail:
Part II Please complete Parts II & III for each unit returned
Model No./Part No.
Description
Range/Calibration
Reason for return : Failure Upgrade
S/N
Verify Operation Other
1.
Describe the conditions of the failure (Frequency/Intermittent, Physical Damage, Environmental Conditions,
Communication, CPU watchdog, etc.)
(Attach a separate sheet if necessary)
2. Comm. interface used: Standalone RS-485 Ethernet Modem (PLM (2W or 4W) or SNW) Other: ______________
3.
What is the Firmware revision? _____________________ What is the Software &version?
Part III If checking “replaced” for any question below, check an alternate option if replacement is not available
A.
If product is within the warranty time period but is excluded due to BBI’s warranty clause, would you like the product: repaired returned replaced scrapped?
B.
If product were found to exceed the warranty period, would you like the product:
C.
If product is deemed not repairable would you like your product:
D.
If BBI is unable to verify the discrepancy, would you like the product: repaired returned replaced scrapped?
returned replaced scrapped?
returned replaced *see below?
* Continue investigating by contacting the customer to learn more about the problem experienced? The person to contact that has the most knowledge of the problem is: _______________________________ phone
If we are unable to contact this person the backup person is: _________________________ phone
Special Requests:
Ship prepaid to: Bristol Babcock Inc., Repair Dept., 1100 Buckingham Street, Watertown, CT 06795
Phone: 860-945-2442 Fax: 860-945-3875
Form GBU 13.01
Rev. A
BLANK PAGE
Bristol Babcock
Training
GET THE MOST FROM YOUR BRISTOL
BABCOCK INSTRUMENT OR SYSTEM
• Avoid Delays and problems in getting your system on-line
• Minimize installation, start-up and maintenance costs.
• Make the most effective use of our hardware and software.
• Know your system.
As you know, a well-trained staff is essential to your operation. Bristol Babcock offers a full schedule of classes conducted by full-time, professional instructors. Classes are offered throughout the year at three locations: Houston, Orlando and our Watertown, CT headquarters. By participating in our training, your personnel can learn how to install, calibrate, configure, program and maintain any and all Bristol Babcock products and realize the full potential of your system.
For information or to enroll in any class, contact our training department in Watertown at
(860) 945-2343. For Houston classes, you can also contact our Houston office, at (713) 685-
6200.
A Few Words About Bristol Babcock
For over 100 years, Bristol 7 has been providing innovative solutions for the measurement and control industry. Our product lines range from simple analog chart recorders, to sophisticated digital remote process controllers and flow computers, all the way to turnkey
SCADA systems. Over the years, we have become a leading supplier to the electronic gas measurement, water purification, and wastewater treatment industries.
On off-shore oil platforms, on natural gas pipelines, and maybe even at your local water company, there are Bristol Babcock instruments, controllers, and systems running year-in and year-out to provide accurate and timely data to our customers.
Getting Additional Information
In addition to the information contained in this manual, you may receive additional assistance in using this product from the following sources:
Help Files / Release Notes
Many Bristol Babcock software products incorporate help screens. In addition, the software typically includes a ‘read me’ release notes file detailing new features in the product, as well as other information which was available too late for inclusion in the manual.
Contacting Bristol Babcock Directly
Bristol Babcock's world headquarters are located at 1100 Buckingham Street, Watertown,
Connecticut 06795, U.S.A.
Our main phone numbers are:
(860) 945-2200
(860) 945-2213 (FAX)
Regular office hours are Monday through Friday, 8:00AM to 4:30PM Eastern Time, excluding holidays and scheduled factory shutdowns. During other hours, callers may leave messages using Bristol's voice mail system.
Telephone Support - Technical Questions
During regular business hours, Bristol Babcock's Application Support Group can provide telephone support for your technical questions.
For technical questions about TeleFlow products call (860) 945-8604.
For technical questions about Control Wave call (860) 945-2394 or (860) 945-2286.
For technical questions regarding Bristol’s OpenEnterprise product, call (860) 945-3865 or e-mail: [email protected]
For technical questions regarding ACCOL products, OpenBSI Utilities , UOI and all other software except for Control Wave and OpenEnterprise products, call (860) 945-2286.
For technical questions about Network 3000 hardware, call (860) 945-2502.
You can e-mail the Application Support Group at: [email protected]
The Application Support Group maintains an area on our web site for software updates and technical information. Go to: www.bristolbabcock.com/services/techsupport/
For assistance in interfacing Bristol Babcock hardware to radios, contact Bristol Babcock’s
Communication Technology Group in Orlando, FL at (407) 629-9463 or (407) 629-
9464 .
You can e-mail the Communication Technology Group at: [email protected]
Telephone Support - Non-Technical Questions, Product Orders, etc.
Questions of a non-technical nature (product orders, literature requests, price and delivery information, etc.) should be directed to the nearest sales office (listed on the rear cover of this manual) or to your Bristol-authorized sales representative.
Please call the main Bristol Babcock number (860-945-2200) if you are unsure which office covers your particular area.
Visit our Site on the World Wide Web
For general information about Bristol Babcock and its products, please visit our site on the
World Wide Web at: www.bristolbabcock.com
Training Courses
Bristol Babcock’s Training Department offers a wide variety of courses in Bristol hardware and software at our Watertown, Connecticut headquarters, and at selected Bristol regional offices, throughout the year. Contact our Training Department at (860) 945-2343 for course information, enrollment, pricing, and scheduling.
CI-3530-IStran
IStran/IStran Plus
COMMUNICATION INTERFACE
TABLE OF CONTENTS
3.1
3.2
3.3
3.4
SECTION TITLE
1.1
1.2
1.2.1
GENERAL DESCRIPTION................................................................................. 1
PHYSICAL DESCRIPTION ................................................................................ 2
The IStran PCB.................................................................................................... 2
Section 2 - FUNCTION & ELECTRICAL CHARACTERISTICS
2.1
2.1.1
2.1.2
2.2
2.3
HAZARDOUS & NONHAZARDOUS CHARACTERISTICS............................. 4
Nonhazardous Interface ...................................................................................... 5
Hazardous Interface ............................................................................................ 6
SWITCHED & UNSWITCHED MODES............................................................ 6
NONHAZARDOUS POWER OUTPUT .............................................................. 7
INTRODUCTION TO SYSTEM WIRING .......................................................... 8
GROUNDING ...................................................................................................... 8
CABLE LENGTH................................................................................................. 8
FIELD WIRING DIAGRAMS.............................................................................. 9
4.1
4.2
INSTALLATION INTRODUCTION................................................................. 17
INSTALLATION NOTES.................................................................................. 17
5.1
5.2
ENVIRONMENT ............................................................................................... 19
OPERATING SPECIFICATION ....................................................................... 19
SUPPLEMENTAL INSTRUCTIONS
CARE AND HANDLING OF PC BOARDS
ESD-SENSITIVE COMPONENTS..................................................S14006
CI-3530-IStran (01/05/2006) Page 0-1 Table Of Contents
BLANK PAGE
Section 1
INTRODUCTION
1.1 GENERAL DESCRIPTION
IStran Communication Interfaces allow one or more intrinsically safe TeleFlow ® devices to communicate with a device located in a Division 2 or nonhazardous area.
IStran PCB assemblies have been designed to provide the following key features:
• Replaces six intrinsic safety barriers for RS-232 signals (3 in, 3 out)
• Replaces six intrinsic safety barriers for TeleFlow I/O signals (3 in, 3 out)
• Can provide 500V isolation between two devices
• Allows up to four devices to share a single radio or modem
• Operates at speeds up to 19,200bps
• The TeleFlow can receive power from outside the Division 1 area
• The TeleFlow can control power to a radio or modem located outside the Division 1 area
• IStran has been approved for use with TeleFlow EGMs (3530-10B) and TeleFlow
Correctors (3530-50B) (when equipped with approved intrinsically safe Battery/-
Solar Panel Power or when externally powered through the IStran). IStran has been approved for use with TeleFlow ECRs (3530-40B) when externally powered through the IStran).
Some of these features also make the IStran useful in applications where intrinsic safety is not required, such as providing isolation between two devices or allowing multiple devices to share a single radio or modem.
Figure 1-1 - IStran & IStran Plus Front View
CI-3530-IStran (01/05/2006) Page 1 Instruction Manual
1.2 PHYSICAL DESCRIPTION
The IStran assembly measures 6.25” in length by 4.50” in width by approximately 1” in depth while the IStran Plus assembly measures 6.25” in length by 4.50” in width by approximately 1.825” in depth (see Figures 1-2 & 1-3).
The IStran/IStran Plus assembly consists of the following major components:
• One IStran PCB for the IStran assembly; Two IStran PCBs for the IStran Plus
• Yellow Alodined Aluminum Base Plate (0.060” in thickness)
• Black Anodized Cover (Top) (0.090” in thickness)
1.2.1 The IStran PCB (see Figure 1-4)
IStran PCBs provide two interfaces which are designated hazardous and non-hazardous.
Eack interface can be configured independently to operate in switched or unswitched mode.
Switched mode can set the TX drivers into a high-impedance state to reduce power consumption. In cases where power consumption is not a key factor, the interfaces should be configured for unswitched mode. In unswitched mode, the TX drivers are always active and they always follow the corresponding RX inputs.
Figure 1-2 - Physical Dimensions - IStran/IStran Plus - Front View
Instruction Manual Page 2 CI-3530-IStran (01/05/2006)
Figure 1-3 - Physical Dimensions - IStran/IStran Plus - Edge (Side) View
Figure 1-4 - IStran PCB Mounted on Base Plate (Cover removed)
CI-3530-IStran (01/05/2006) Page 3 Instruction Manual
Section 2
FUNCTION & ELECTRICAL CHARACTERISTICS
2.1 HAZARDOUS & NONHAZARDOUS CHARACTERISTICS
Table 2-1 below provides the characteristics common to both the hazardous and nonhazardous IStran interfaces:
Table 2-1 - Common Characteristics for Hazardous & Nonhazardous Interfaces
DESCRIPTION
Data Rate
Propagation Delay, any RX to any TX
SPECIFICATION
Maximum: 19.2 Kbps
Maximum: 10 uS
Output Enable Delay
(Switched Mode, enable to TX valid)
RX Input High Level
RX Input Low Level
RX Input Load Resistance
Typical: < 10 uS uS
VDC
VDC
Typical:
VDC
VDC
3.01 Kohm
Quiescent Supply Current
(Both if in switched mode, all TX off)
Idle Supply Current
(Both if in unswitched mode, all TX low)
Active Supply Current
(Both if active, worst case)
Table 2-2 - Nonhazardous Interface Connector
POSITION NAME
NJ3-1 NPOUT
FUNCTION
Switched Power Output
NJ2-1 NPIN
(Return for NPOUT)
Power Supply Input
NJ1-1
NJ1-2
NJ1-3
NTX1
NTX2
NTX3
(Return for NPIN)
Signal Output (Follows HRX1)
Signal Output (Follows HRX2)
Signal Output (Follows HRX3)
Instruction Manual
NJ1-7 NGND
NJP1-1 SW Jumper to COM for Switched Mode
NJP1-2 COM Mode Selection Common
NJP1-3 UNSW Jumper to COM for Unswitched Mode
Page 4 CI-3530-IStran (01/05/2006)
2.1.1 Nonhazardous Interface
The nonhazardous interface typically connects to a radio or modem that is located with the
IStran Assembly in a nonhazardous or Division 2 rated area. Table 2-2 above identifies each connector position and the corresponding signal name, and provides a brief description of each I/O point on the nonhazardous interface. Table 2-3 below provides the characteristics of the nonhazardous interface.
Table 2-3 - Nonhazardous Interface Characteristics
DESCRIPTION SPECIFICATION
NPIN Voltage
(When HPOUT is not used)
NPIN Voltage
(When HPOUT is used)
VDC
VDC
VDC
VDC
NPIN Supply Current
(Switched Mode, Transmitters
Off)
Typical: < 500 uA at 12 VDC, 77 ° F (25 ° C) uA
NPIN Supply Current
(All TX Outputs High, 3 K W mA
NPOUT Leakage
NPIN to NPOUT On-Resistance
(NPIN ³ 12 V)
NRX3 to NPOUT On
NPOUT Load Current
NTX Output High Level
NTX Output Low Level
NJP1 Jumper Operation
Typical:
Typical:
Typical:
< 1 uA Maximum: 100 uA
< 0.3 ohm ohm
< 10 uS
Maximum: 1.8 A Continuous
Maximum: 3.0 A Intermittent (Max 60 Seconds, 50% duty)
Typical: 7.4 VDC into 3 Kohm Load
VDC
Maximum: 9.5
Typical: -4.9 VDC into 3 Kohm Load
VDC
Maximum: -3.0
If no Jumper is installed, or if a Jumper is installed between pins 1 and 2 (SW), the nonhazardous interface operates in switched mode. If a Jumper is installed between pins 2 and 3
(UNSW), the nonhazardous interface operates in unswitched mode.
Table 2-4 - Hazardous Interface Connector
POSITION NAME FUNCTION
HJ2-3
HJ2-1
HJ1-7
HPIN
CGND
Hazardous Power Input
HJ2-1 (CGND) for single supply applications
Enclosure Ground (Tied to NGND)
HPOUT Hazardous Power
CI-3530-IStran (01/05/2006) Page 5 Instruction Manual
Table 2-4 - Hazardous Interface Connector (Continued)
POSITION NAME FUNCTION
HJ1-3
HJ1-2
HJ1-1
HJP1-1
HJP1-2
HTX3 Signal Output (Follows NRX3)
HTX2 Signal Output (Follows NRX2)
HTX1 Signal Output (Follows NRX1)
SW Jumper to COM for Switched Mode
COM Mode Selection Common
HJP1-3 UNSW Jumper to COM for Unswitched Mode
2.1.2 Hazardous Interface
The hazardous interface typically connects either to an intrinsically safe device or to a network of up to four additional IStrans. Table 2-4 above identifies each connector position, the corresponding signal name, and briefly describes each input/output point on the hazardous interface. Table 2-5 below provides the characteristics of the hazardous interface.
Table 2-5 - Hazardous Interface Characteristics
DESCRIPTION
HPOUT Voltage
HPOUT Operating Current
SPECIFICATION
Typical 6.3 VDC (No Load)
Minimum: 5.9 VDC (Max. Load)
Maximum: 6.4 VDC (No Load)
Maximum: 16 VDC
HPOUT Current Limit Threshold
Minimum: 130 mA at 8 VDC
Maximum: 300 mA at 16 VDC
Maximum: 100 uF HPOUT Load Capacitance
HPIN Quiescent Supply Current
(Switched Mode, Transmitters Off)
HPIN Supply Current
(All TX Outputs High, 3 K W Load
HTX Output High Level
HTX Output Low Level
HJP1 Jumper Operation
Minimum: 4.5 VDC, Maximum: 5.0 VDC
Minimum: 0 VDC, Maximum: 0.1 VDC
If no Jumper is installed, or if a Jumper is installed between pins 1 and 2 (SW), the hazardous interface operates in switched mode. If a Jumper is installed between pins 2 and
3 (UNSW), the hazardous interface operates in unswitched mode.
2.2 SWITCHED & UNSWITCHED MODES
Each IStran interface can be configured independently to operate in switched or unswitched mode. In switched mode, the TX drivers can enter a high-impedance state to reduce power consumption. The outputs transition smoothly, without glitches, to and from the high-impedance state. Most modern device inputs will pull the high impedance IStran output to ground and interpret it as a low, or MARK state. Some devices may not properly interpret the high-impedance signal, and in some systems it may be impractical to operate either or both interfaces in switched mode. In these cases, or when power consumption is not a concern, the interface(s) should be configured for unswitched mode. In unswitched
Instruction Manual Page 6 CI-3530-IStran (01/05/2006)
mode, the TX drivers are always active and they always follow the corresponding RX inputs.
Switched mode is enabled or disabled for the nonhazardous interface by jumper position
NJP1, and for the hazardous interface by jumper position HJP1. When either interface is in switched mode, it is turned on or off by the RX3 (NRX3 or HRX3) input of the opposite interface.
To configure the nonhazardous interface for switched mode, place a shorting jumper in the
NJP1 position marked SW (short NJP1 pins 1 and 2). The nonhazardous interface is also in switched mode by default if no jumper is installed at NJP1. When the nonhazardous interface is configured for switched mode, the NTX outputs are in a high-impedance state when HRX3 is low (or negative), and the NTX outputs follow the HRX inputs normally when HRX3 is high (positive). To configure the nonhazardous interface for unswitched mode, place a shorting jumper in the position marked UNSW (short NJP1 pins 2 and 3). In unswitched mode, the NTX outputs are always turned on and they always follow the corresponding HRX inputs.
To configure the hazardous interface for switched mode, place a shorting jumper in the
HJP1 position marked SW (short HJP1 pins 1 and 2). The hazardous interface is also in switched mode by default if no jumper is installed at HJP1. When the hazardous interface is configured for switched mode, the HTX outputs are in a high-impedance state when
NRX3 is low (or negative), and the HTX outputs follow the NRX inputs normally when
NRX3 is high (positive). To configure the hazardous interface for unswitched mode, place a shorting jumper in the HJP1 position marked UNSW (short HJP1 pins 2 and 3) In unswitched mode, the HTX outputs are always turned on and they always follow the corresponding NRX inputs.
2.3 NONHAZARDOUS POWER OUTPUT
The nonhazardous power supply is routed through a FET (field effect transistor) from the power input to an output terminal. The power supply comes in on the NPIN terminal and switched power goes out on the NPOUT terminal. When hazardous interface signal input
HRX3 is at a high (positive) level, NPOUT is turned on and can supply power to an external device. When HRX3 is at a low (or negative) level, NPOUT is turned off. The voltage drop between NPIN and NPOUT can be determined by multiplying the NPOUT load current by the NPIN to NPOUT on-resistance. The resistance of the associated field wiring must also be taken into account when determining the total drop between the power supply and the load.
CAUTION
In order to minimize resistance between NPIN and NPOUT, no overcurrent protection is provided by the IStran. The user should install a fuse or other means of overcurrent protection at the power source to prevent damage to the IStran, power source, or load in case of a short circuit or other overcurrent condition.
CI-3530-IStran (01/05/2006) Page 7 Instruction Manual
Section 3
SYSTEM WIRING
3.1 INTRODUCTION TO SYSTEM WIRING
An IStran/IStran Plus unit connects a radio, modem, or other communications device to a
TeleFlow Model 3530-10B, 3530-40B or 3530-50B (flow computer). An IStran/IStran Plus unit can also provide an intrinsically safe interface between an external power supply,
Discrete I/O, Pulse Input, Analog Input and RS-232 signals associated with a radio, modem or TeleFlow (in a non-hazardous area) and a TeleFlow (in a Class I, Division 1 area).
3.2 GROUNDING
The IStran/IStran Plus can provide up to 500V of isolation between the hazardous and nonhazardous interfaces. When using the ground isolation capability of the IStran, devices on either side must have separate power sources, and each source must power the corresponding IStran interface. Refer to the field wiring diagrams in Section 3.4 for systems with independent power sources.
When isolation is not required, a single power source can also supply both IStran interfaces and, optionally, both connected devices. To power both IStran interfaces using a single power source, the power source must be connected between NPIN and NGND. Connector
HJ2 is then used as a jumper position to wire HPOUT to HPIN and HGND to CGND. Note that CGND and NGND are internally connected, and that CGND is connected to the IStran case. Refer to the field wiring diagrams in section 3.4 for systems with a single power source.
When a ground connection already exists between the power source and the TeleFlow or communications device, do not wire the ground terminal on the IStran communications connector (NJ1 or HJ1). The ground reference established on the IStran power connector
(NJ2 or HJ2) serves as both power supply return and signal ground reference. Wiring the communications connector ground terminal may introduce a ground loop and degrade the performance of the IStran under these circumstances. The wiring diagrams in Section 3.4 illustrate the recommended practices.
For intrinsic safety applications, redundant earth grounds are required.
Both grounds should measure less than one ohm to earth. The NGND terminal provides one ground, and the case provides the other. If the mounting panel does not provide a suitable ground path, connect a
12AWG or larger ground conductor to one of the IStran mounting screws.
3.3 CABLE LENGTH
The IStran is UL listed for use with cable lengths up to 25 feet on either or both interfaces.
Typically, the IStran is located in close proximity to the communications device (connected to the nonhazardous interface) and at some distance from the TeleFlow (connected to the hazardous interface). Because of cable capacitance and inductance, 25 feet is the maximum cable length allowable for use with a TeleFlow located in a Division 1 area.
Instruction Manual Page 8 CI-3530-IStran (01/05/2006)
Although the system is NOT TO BE OPERATED with cables that exceed 25 feet in length
(when a TeleFlow is located in a Division 1 area), the IStran will typically operate reliably with cables longer than 25 feet. The maximum reliable cable length is dependent on the type and grade of cable, the electrical interface of the device at the other end of the cable, ambient noise, and the performance characteristics of the UARTs (universal asynchronous receiver/transmitters) on both the Comm. device and the TeleFlow. Experimentation under favorable circumstances has yielded reliable operation of the IStran at 19,200 bps with up to 500 feet of cable.
WARNING
The cable length is NOT TO EXCEED 25 feet when the IStran is connected to a TeleFlow that is operating in a Division 1 area.
3.4 FIELD WIRING DIAGRAMS
Figure 3-1 below illustrates a typical radio or modem system. In this example, the modem and TeleFlow have independent power systems and their grounds are isolated from one another. Each interface of the IStran draws power from its associated supply. The power source to the nonhazardous interface must not use or generate more than 250V. If the
IStran is located in a Division 2 area, the power input and output connections must be made using Division 2 wiring methods as described in Section 4.1.
Figure 3-1 - Modem System with Independent Power Supply
Figure 3-2 is similar Figure 3-1, but in this example a single power source supplies both the modem and the TeleFlow. Note that the power supply input range for this con-figuration is
8 to 16V, and that the grounds of both devices are connected together through the IStran.
The TeleFlow or RTU power supply current must be 120mA or less, and it must operate down to 5.9V.
Figure 3-3 is similar to Figure 3-1, but shows connections to an MDS 2310 or similar radio.
In this example, radio power is switched on and off by the TeleFlow’s DTR signal (which works in conjunction with the TeleFlow’s Auxiliary Power Output). Radio communications parameters are setup in the application software resident on a PC (see Appendix F - Section F.8.5 of CI-3530-10B or CI-3530-50B). Figure 3-4 is similar to Figure 3-3, but with a single power source.
CI-3530-IStran (01/05/2006) Page 9 Instruction Manual
Figure 3-2 - Modem System with Single Power Source
Figure 3-3 - Radio with Independent Power Sources
Figure 3-4 - Radio System with Single Power Source
Instruction Manual Page 10 CI-3530-IStran (01/05/2006)
Figures 3-5 through 3-7 illustrate multidrop systems, connecting four TeleFlows to a single radio or modem. In the multidrop configuration, the TeleFlows cannot control radio/modem power. Note that one power source supplies power to the radio/modem and both interfaces of its associated IStran, as well as to the network (hazardous) interface of all of the other
IStrans. Each TeleFlow must have its own power source, and the radio/modem and
TeleFlow grounds are all isolated from each other. In this configuration, any or all of the
TeleFlows can be located in Division 1 areas, while the radio/modem and all of the IStrans are located in the nonhazardous or Division 2 area.
Figure 3-5 - Multidrop Radio System (Featuring MDS Radio)
(TeleFlows not situated in a Division 1 - Intrinsically Safe Area)
CI-3530-IStran (01/05/2006) Page 11 Instruction Manual
Figure 3-6 - Multidrop Radio System (Featuring FreeWave Radio)
(TeleFlows not situated in a Division 1 - Intrinsically Safe Area)
Instruction Manual Page 12 CI-3530-IStran (01/05/2006)
Figure 3-7 - Multidrop Modem System
(TeleFlows not situated in a Division 1 - Intrinsically Safe Area)
CI-3530-IStran (01/05/2006) Page 13 Instruction Manual
Figure 3-8 illustrates an externally powered TeleFlow (without a modem or radio). In this example, the external power source to the nonhazardous interface must not generate more than 16Vdc and must be able to supply at least 8Vdc. If the IStran is located in a Division 2 area, the power input and output connections must be made using Division 2 wiring methods as described in Section 4.1. Note: If a modem or radio is required, refer to
Figures 3-2 or 3-4. The only difference is that the 12V battery may be replaced by an external 8 to 16 Vdc power supply.
Figure 3-8 - TeleFlow with External Power Source
Figures 3-9A and 3-9B depict two methods of connecting an Intrinsically Safe Model 2808-
IXX Transmitter to the Analog Input of an Intrinsically Safe TeleFlow. Wiring connections to the IStran and TeleFlow are described in Section 4.
Figure 3-9A - Intrinsically Safe Model 2808-IXX
Connected to an Intrinsically Safe TeleFlow
IStran powers TeleFlow (via J8) - TeleFlow Connector J6 powers 2808-IXX
Analog Input Wiring Diagram
Instruction Manual Page 14 CI-3530-IStran (01/05/2006)
Figure 3-9B - Intrinsically Safe Model 2808-IXX
Connected to an Intrinsically Safe TeleFlow
IStran powers TeleFlow (via J8) and 2808-IXX
Analog Input Wiring Diagram
Note: Intrinsically Safe Model 2808 Transmitters are equipped with a Data Plate that states the model number as 2808-I-XX… If the ‘I’ isn’t present in the Model
Number, or if the Data Plate doesn’t explicitly state that the unit is intrinsically safe for Class 1, Div. 1 Groups C and D operation, the unit is not Intrinsically Safe and MUST NOT be used in a Class I Division 1 area.
Figure 3-10 illustrates an externally powered TeleFlow (situated in a hazardous area) that is interfaced via IStran Board #1 to Discrete I/O and a Pulse Input circuit (situated in a nonhazardous area) and an external RS-232 communications device (such as a modem or radio also situated in a nonhazardous area) that is interfaced via IStran Board #2.
In this example, the external power source to the nonhazardous interface, all I/O and communications equipment must reside in a nonhazardous area. If the IStran is located in a Division 2 area, the power input and output connections must be made using Division 2 wiring methods as described in Section 4.1.
CI-3530-IStran (01/05/2006) Page 15 Instruction Manual
Figure 3-10 Wiring Diagram
Intrinsically Safe Discrete I/O & Pulse Input Signals via IStran #1
Intrinsically Safe RS-232 Signals via IStran #2
Instruction Manual Page 16 CI-3530-IStran (01/05/2006)
Section 4
INSTALLATION
4.1 INSTALLATION INTRODUCTION
The IStran/IStran Plus and the communications device are located in a nonhazardous or
Division 2 rated area, while the TeleFlow can reside in a Division 1, 2, or nonhazardous area.
A suitable enclosure must be provided for the IStran/IStran Plus. When the IStran/IStran
Plus is mounted in a Division 2 area, the nonhazardous interface connections shall be made in accordance with Article 501-4(b) of the National Electrical Code NFPA 70.
CAUTION
When connecting the IStran to a TeleFlow mounted in a
Division 1 area, wire all circuits using wiring methods specified in article 504 of the National Electrical Code NFPA 70. Contact your IStran supplier for assistance.
WARNING
When the IStran is installed in a Division 2 area, ensure that the area is nonhazardous before connecting or disconnecting the nonhazardous interface.
4.2 INSTALLATION NOTES
Use four #6 screws with lockwashers to secure the IStran/IStran Plus to a grounded metal panel. Figures 1-2 and 1-3 show the physical dimensions of the IStran/IStran Plus units.
The four mounting holes/slots are 0.156" in diameter. Total height is approximately 1". The case material is 5052 aluminum with a black anodize finish. The thickness of the base is
0.060", and the top is 0.090". The case hardware is stainless steel.
The IStran/IStran Plus accepts stranded wires up to 14AWG. When two wires must be inserted in a single position, 18AWG is the maximum recommended size. The recommended strip length is 1/4 inch, and the insulation should not extend into the connector clamp.
Cables should use 26AWG or larger conductors and should not be configured as twisted pairs. If a shield is used, it should be connected only at one end, closest to the system ground reference. For optimum performance over long distances, use low-capacitance cables. In the multidrop configuration, all IStran units should be in close proximity.
All wiring should be secured before power is applied to the IStran or to the associated devices. For intrinsic safety applications, use a single cable to connect the IStran hazardous interface to the intrinsically safe device. Maintain a minimum 2” separation between the intrinsically safe wiring and all other wiring. The IStran hazardous interface should be physically located near the point where the intrinsically safe wiring exits the enclosure housing the IStran. No other wiring should pass through the same hole or share a cable or conduit with the intrinsically safe wiring. Secure the intrinsically safe wiring and limit
CI-3530-IStran (01/05/2006) Page 17 Instruction Manual
slack to ensure that, should one of the intrinsically safe wires become dislodged from an
IStran terminal, it must still maintain a 2” separation with either the IStran nonhazardous interface wiring or any other circuits except those on the IStran hazardous interface.
Refer to Figures 3-1 through 3-7 when connecting wires between an optional modem or radio and an IStran Assembly. Note: MDS and FreeWave radios utilize different
RXD/TXD naming conventions, i.e., MDS utilizes RXD and TXD to mean receive input and transmit output respectively, while FreeWave utilizes RXD for transmit output and TXD for receive input (see Figures 3-5 and 3-6).
Refer to Figure 3-8 when connecting wires between an externally powered TeleFlow CPU
Board and an IStran Assembly.
Refer to Figures 3-9A & 3-9B when connecting wires between an IStran Assembly and an
Intrinsically Safe Teleflow that is connected to an Intrinsically Safe Model 2808-IXX
Transmitter.
Note: Intrinsically Safe Model 2808 Transmitters are equipped with a Data Plate that states the model number as 2808-I-XX… If the ‘I’ isn’t present in the Model
Number, or if the Data Plate doesn’t explicitly state that the unit is intrinsically safe for Class 1, Div. 1 Groups C & D operation, the unit is not Intrinsically Safe and MUST NOT be used in a Class I Division 1 area.
Refer to Figure 3-10 when connecting wires associated with a Discrete Input, a Discrete
Output and a Pulse Input circuit (in a nonhazardous area) to an Intrinsically Safe Teleflow
(in a hazardous area) via one IStran Assembly while connecting wires associated with an
RS-232 device (situated in a nonhazardous area) to the same TeleFlow unit via a second
IStran Assembly.
Refer to PIP-EXP232TF when connecting wires to an IStran Assembly and an optional
Expansion Communications Port RS-232 Board.
Refer to Section 2.2 when configuring an IStran for Switched/Unswitched operation.
Instruction Manual Page 18 CI-3530-IStran (01/05/2006)
Section 5
SPECIFICATIONS
5.1 ENVIRONMENT
The IStran/IStran Plus Assembly has been designed for installation in a building or inside a weather-proof enclosure.
5.2 OPERATING SPECIFICATION
Table 5-1 below provides the operating specifications for the IStran Communication Interface.
Table 5-1 - Operating Specifications
DESCRIPTION SPECIFICATIONS
Operating Temperature Range -40 ° to +70 ° C (-40 ° to +158 ° F)
Operating Humidity Range 15% to 95% RH (non-condensing)
Transient Susceptibility
Vibration Effect
ESD Susceptibility
EMI Compatibility
Hazardous Locations
Field connected circuits are designed to meet the requirements of ANSI/IEEE C37.90.1-1989 (formerly IEEE 472) for surge withstand capability.
10 to 500 Hz at 1 g on any axis per SAMA PMC-31-1 without damage or impairment.
Field connected circuits are designed to meet the requirements of IEC 801-2 for ESD withstand capability up to 10KV.
Designed to meet the susceptibility requirements of IEC 801-3 level 2 (3V/M) from 500KHz to 500MHz.
Designed to meet FCC Rules Part J, Subpart 15, Class A for radiated emissions.
Designed to meet NFPA and UL requirements for installation in
Class I, Division 2, Groups C & D hazardous locations.
Designed to meet NFPA and UL requirements for connection to intrinsically safe devices located in Division 1 locations.
The intrinsically safe device must be designed and/or approved for the intended connection.
CI-3530-IStran (01/05/2006) Page 19 Instruction Manual
BLANK PAGE
ESDS Manual
S14006
4/15/92
CARE AND HANDLING
OF
PC BOARDS
AND
E SD-SENSITIVE
COMPONENTS
BRISTOL BABCOCK
BLANK PAGE
ESDS Manual
S14006
4/15/92
TABLE OF CONTENTS
PAGE
TOOLS AND MATERIALS REQUIRED 1
ESD-SENSITIVE COMPONENT HANDLING PROCEDURE 2
3. Protecting ESD-Sensitive Components 5
4. Static-Safe Field Procedure 6
TOOLS AND MATERIALS REQUIRED
1. Tools
Anti-Static Field kit. It is recommended that an anti-static field kit be kept on any site where solid-state printed circuit boards and other ESD-sensitive components are handled. These kits are designed to remove any existing static charge and to prevent the build-up of a static charge that could damage a PC board or
ESD-sensitive components. The typical anti-static field kit consists of the following components:
1. A work surface (10mm conductive plastic sheet with a female snap fastener in one corner for ground cord attachment).
2. A 15-foot long ground cord for grounding the work surface.
3. Wrist strap (available in two sizes, large and small, for proper fit and comfort) with a female snap fastener for ground cord attachment.
4. A coiled ground cord with a practical extension length of 10 feet for attachment to the wrist strap.
Toothbrush (any standard one will do)
1
ESDS Manual
#S14006
4/15/92
2.
Materials
Inhibitor (Texwipe Gold Mist ; Chemtronics Gold Guard, or equivalent)
Cleaner (Chemtronics Electro-Wash; Freon TF, or equivalent)
Wiping cloth (Kimberly-Clark Kim Wipes, or equivalent)
1.
ESD-SENSITIVE COMPONENT HANDLING PROCEDURE
Introduction
Microelectronic devices such as PC boards, chips and other components are electrostatic-sensitive. Electrostatic discharge (ESD) of as few as 110 volts can damage or disrupt the functioning of such devices. Imagine the damage possible from the 35,000 volts (or more) that you can generate on a dry winter day by simply walking across a carpet. In fact, you can generate as much as 6,000 volts just working at a bench.
There are two kinds of damage that can be caused by the static charge. The more severe kind results in complete failure of the PC board or component. This kind of damage is relatively simple, although often expensive, to remedy by replacing the affected item(s). The second kind of damage results in a degradation or weakening which does not result in an outright failure of the component. This kind of damage is difficult to detect and often results in faulty performance, intermittent failures, and service calls.
Minimize the risk of ESD-sensitive component damage by preventing static build-up and by promptly removing any existing charge. Grounding is effective, if the carrier of the static charge is conductive such as a human body. To protect components from
nonconductive carriers of static charges such as plastic boxes, place the component in static-shielding bags.
This manual contains general rules to be followed while handling ESD-sensitive components. Use of the anti-static field kit to properly ground the human body as well as the work surface is also discussed.
2
ESDS Manual
S14006
4/15/92
Table 1
Typical Electrostatic Voltages
Electrostatic Voltages
10-20 Percent
Relative Humidity
65-90 Percent
Relative Humidity
Means of Static
Generation
Walking across carpet
Walking over vinyl floor
Worker at bench
Vinyl envelopes for work instructions
Poly bag picked up from bench
Work chair padded with poly foam
35,000
12,000
6,000
7,000
20,000
18,000
1,500
250
100
600
1,200
1,500
2.
General Rules
(1) ESD-sensitive components shall only be removed from their static-shielding bags by a person who is properly grounded.
(2) When taken out of their static-shielding bags, ESD-sensitive components shall
never be placed over, or on, a surface which has not been properly grounded.
(3) ESD-sensitive components shall be handled in such a way that the body does not come in contact with the conductor paths and board components. Handle
ESD-sensitive components in such a way that they will not suffer damage from physical abuse or from electric shock.
(4) EPROMS/PROMS shall be kept in anti-static tubes until they are ready to use and shall be removed only by a person who is properly grounded.
(5) When inserting and removing EPROMS/PROMS from PC boards, use a chip removal tool similar to the one shown in the figure following. Remember, all work should be performed on a properly grounded surface by a properly-grounded person.
3
ESDS Manual
#S14006
4/15/92
4
Typical Chip Removal Tool
(6) It is important to note when inserting EPROMS/PROMS, that the index notch on the PROM must be matched with the index notch on the socket. Before pushing the chip into the socket, make sure all the pins are aligned with the respective socket-holes. Take special care not to crush any of the pins as this could destroy the chip.
(7) Power the system down before removing or inserting comb connectors/plugs or removing and reinstalling PC boards or ESD-sensitive components from card files or mounting hardware. Follow the power-down procedure applicable to the system being serviced.
(8) Handle all defective boards or components with the same care as new components. This helps eliminate damage caused by mishandling. Do not strip used PC boards for parts. Ship defective boards promptly to Bristol Babcock in a staticshielding bag placed inside static-shielding foam and a box to avoid damage during shipment.
ESDS Manual
S14006
4/15/92
CAUTION
Don't place ESD-sensitive components and paperwork in the same bag.
The static caused by sliding the paper into the bag could develop a charge and damage the component(s).
(9) Include a note, which describes the malfunction, in a separate bag along with each component being shipped. The repair facility will service the component and promptly return it to the field.
3.
Protecting ESD-Sensitive Components
(1) As stated previously, it is recommended that an electrically-conductive anti-static field kit be kept on any site where ESD-sensitive components are handled. A recommended ESD-protective workplace arrangement is shown on page 7. The anti-static safety kit serves to protect the equipment as well as the worker. As a safety feature, a resistor (usually of the one-megohm, 1/2-watt, current-limiting type) has been installed in the molded caps of the wrist strap cord and the ground cord. This resistor limits current should a worker accidently come in contact with a power source. Do not remove the molded caps from grounded cords. If a cord is damaged, replace it immediately.
(2) Be sure to position the work surface so that it does not touch grounded conductive objects. The protective resistor is there to limit the current which can flow through the strap. When the work surface touches a grounded conductive object, a short is created which draws the current flow and defeats the purpose of the current-limiting resistor.
(3) Check resistivity of wrist strap periodically using a commercially-available system tester similar to the one shown in the figure below:
5
ESDS Manual
#S14006
4/15/92
Note: If a system checker is not available, use an ohmmeter connected to the cable ends to measure its resistance. The ohmmeter reading should be 1 megohm +/-
15%. Be sure that the calibration date of the ohmmeter has not expired. If the ohmmeter reading exceeds 1 megohm by +/- 15%, replace the ground cord with a new one.
4.
Static-safe Field Procedure
(1) On reaching the work location, unfold and lay out the work surface on a convenient surface (table or floor). Omit this step if the table or floor has a built-in ESD-safe work surface.
(2) Attach the ground cord to the work surface via the snap fasteners and attach the other end of the ground cord to a reliable ground using an alligator clip.
(3) Note which boards or components are to be inserted or replaced.
(4) Power-down the system following the recommended power-down procedure.
(5) Slip on a known-good wristband, which should fit snugly; an extremely loose fit is not desirable.
(6) Snap the ground cord to the wristband. Attach the other end of the ground cord to a reliable ground using the alligator clip.
6
ESDS Manual
S14006
4/15/92
(7) The components can now be handled following the general rules as described in the instruction manual for the component.
(8) Place the component in a static-shielding bag before the ground cord is disconnected. This assures protection from electrostatic charge in case the work surface is located beyond the reach of the extended ground cord.
A
C
✰
R
R
D
E F
R
R
EARTH GROUND
B
G
FLOOR OF BUILDING
LEGEND
A - Chair with ground (optional)
B - ESD protective floor mat (optional)
C - Wrist strap
D - ESD protective trays, etc.
E - Ionizer
F - Other electrical equipment
G - Workbench with ESD protective table top
✰
NOTE: ALL RESISTORS 1M
Ω
+/-10% 1/2W
7
ESDS Manual
#S14006
4/15/92
(9) If a component is to undergo on-site testing, it may be safely placed on the grounded work surface for that purpose.
(10) After all component work is accomplished, remove the wrist straps and ground wire and place in the pouch of the work surface for future use.
5.
Cleaning And Lubricating
The following procedure should be performed periodically for all PC boards and when a PC board is being replaced.
CAUTION
Many PC board connectors are covered with a very fine gold-plate.
Do not use any abrasive cleaning substance or object such as a pencil eraser to clean connectors.
Use only the approved cleaner/lubricants specified in the procedure following.
WARNING
Aerosol cans and products are extremely combustible.
Contact with a live circuit, or extreme heat can cause an explosion.
Turn OFF all power and find an isolated, and ventilated area to use any aerosol products specified in this procedure.
(1) Turn the main line power OFF. Blow or vacuum out the component. This should remove potential sources of dust or dirt contamination during the remainder of this procedure.
8
ESDS Manual
S14006
4/15/92
(2) Clean PC board connectors as follows: a.
Review the static-safe field procedure detailed earlier.
b.
c.
Following the ESD-sensitive component handling procedures, remove the connectors from the boards and remove the PC boards from their holders.
Use cleaner to remove excessive dust build-up from comb connectors and other connectors. This cleaner is especially useful for removing dust.
d.
Liberally spray all PC board contacts with Inhibitor. The inhibitor:
Provides a long lasting lubricant and leaves a protective film to guard against corrosion e.
f.
Improves performance and reliability
Extends the life of the contacts
Is nonconductive, and is safe for use on most plastics
Clean the comb contacts using a lint-free wiping cloth.
Lightly mist all comb contacts again with Inhibitor.
NOTE: Do not use so much Inhibitor that it drips.
g.
Repeat the above procedure for the other PC boards from the device.
(3) Cleaning PC edge connectors a.
Use cleaner to remove excessive dust build-up from connectors. This cleaner is especially useful for removing dust.
b.
c.
Liberally spray the outboard connector with Inhibitor.
Lightly brush the outboard connector with a soft, non-metallic, bristle brush such as a toothbrush.
9
ESDS Manual
#S14006
4/15/92 d.
e.
Spray the connector liberally to flush out any contaminants.
Remove any excess spray by shaking the connector or wiping with either a toothbrush, or a lint-free wiping cloth.
6.
Completion
(1) Replace any parts that were removed.
(2) Make sure that the component cover is secure.
(3) Return the system to normal operation.
(4) Check that the component operates normally.
10
READER RESPONSE FORM
Please help us make our documentation more useful to you! If you have a complaint, a suggestion, or a correction regarding this manual, please tell us by mailing this page with your comments. It's the only way we know we're doing our job by giving you correct, complete, and useful documentation.
DOCUMENT NUMBER: CI-3530-IStran
TITLE: Communication Interface (IStran/IStran Plus) - Customer Instructions
ISSUE DATE: JAN., 2006
COMMENT/COMPLAINT:
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
______________________________________________________________________________
Mail this page to:
Bristol Babcock Inc.
1100 Buckingham Street
Watertown, CT 06795
Attn: Technical Publications Group, Dept. 315
U.S.A. Locations:
Northern Region
Bristol Babcock Inc.
1100 Buckingham Street
Watertown, CT 06795
Phone: +1 (860) 945-2381
Fax: +1 (860) 945-2525
Helicoid Instruments
1100 Buckingham Street
Watertown, CT 06795
Phone: +1 (860) 945-2218
Fax: +1 (860) 945-2213 [email protected]
Gulf Coast Region
Bristol Babcock Inc.
2000 Governor's Circle
Suite F
Houston, TX 77092-8731
Phone: +1 (713) 685-6200
Fax: +1 (713) 681-7331
Central Region
Bristol Babcock Inc.
300 North Coit Road
Suite 1300
Richardson, TX 75080
Phone: +1 (972) 238-8935
Fax: +1 (972) 238-8198 [email protected]
International Affiliates:
Canada
Bristol Babcock, Canada
6338 Viscount Rd.
Mississauga, Ont. L4V 1H3
Canada
PH: 905-362-0880
FAX: 905-362-0882 [email protected]
Calgary Office
Bristol Babcock, Canada
176 Country Hill Landing NW
Calgary, Alberta T3K 5P3
Canada
PH: 403-265-4808
FAX: 403-233-2914 [email protected]
Mexico
BBI, S.A. de C.V.
Homero No. 1343, 3er Piso
Col. Morales Polanco
11540 Mexico, D.F.
Mexico
PH: (52-55)-52-81-81-12
FAX: (52-55)-52-81-81-09
Villahermosa Office
BBI, S.A. de C.V.
Av. Plomo No.2
Bodega No. 1 - Ciudad
Industrial
Villahermosa, Tabasco 86010
Mexico
PH: 52-993-353-3142
FAX: 52-993-353-3145 [email protected]
RC Rev: 10-Jan-2006
Bristol Babcock
1100 Buckingham Street
Watertown, CT 06795
Phone: +1 (860) 945-2200
Fax: +1 (860) 945-2213
Website: www.bristolbabcock.com
Western Region
Bristol Babcock Inc.
1609 South Grove Avenue
Suites 106 & 107
Ontario, CA 91761
Phone: +1 (909) 923-8488
Fax: +1 (909) 923-8988
Rocky Mountain Region
Bristol Babcock Inc.
1910 Rustic Place
Farmington, NM 87401
Phone: +1 (505) 327-3271
Fax: +1 (505) 327-3273
United Kingdom
Bristol Babcock Ltd.
Blackpole Road
Worcester, WR3 8YB
United Kingdom
PH: +44 1905 856950
FAX: +44 1905 856969 [email protected]
Middle East
Bristol Babcock Ltd.
Blackpole Road
Worcester, WR3 8YB
United Kingdom
PH: +44 1905 856950
FAX: +44 1905 856969 [email protected]
Southeast Region
Bristol Babcock Inc.
317 S. North Lake Blvd.
Suite 1016
Altamonte Springs, FL 32701
Phone: +1 (407) 740-7084
Fax: +1 (407) 629-2106
Communications
Technology Group
Bristol Babcock Inc.
317 S. North Lake Blvd.
Suite 1016
Altamonte Springs, FL 32701
Phone: +1 (407) 629-9464
Fax: +1 (407) 629-2106 [email protected]
Asia Pacific
Bristol Babcock Inc.
22 Portofino Crescent, Grand
Canals
Bunbury, Western Australia
6230
Mail to: PO Box 1987 (zip
6231)
PH: +61 (8) 9725-2355
FAX: +61 (8) 8 9725-2955 [email protected]