Notifier AFP- Installation Manual


Add to my manuals
42 Pages

advertisement

Notifier AFP- Installation Manual | Manualzz

Fire Alarm Control Panel

AFP-3030

Installation Manual

Australia Edition

Document DOC-01-031 Rev: H

2020-07-14 ECN: AUECN-282

2

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm control panel.

Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.

Verify that wire sizes are adequate

for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% voltage drop from the specified device voltage.

Like all solid state electronic devices,

this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries

prior to removing or inserting circuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies

prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location.

Do not tighten screw terminals

. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

This system contains static-sensitive components.

Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions

in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

The equipment must be correctly programmed and installed to suit the specific application.

Please ensure correct operational parameters are set prior to commissioning. If further details on programming options are required, please consult the programming manual or contact our helpful technical support personnel.

EMC Warning:

This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.

Electromagnetic Interface (EMI) tests are performed in accordance with Class A requirements of AS/NZS CISPR 22:2009

Documentation Feedback

Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.

Please include the following information:

• Product name and version number (if applicable)

• Printed manual or online Help

• Topic Title (for online Help)

• Page number (for printed manual)

• Brief description of content you think should be improved or corrected

• Your suggestion for how to correct/improve documentation

Send email messages to:

[email protected]

Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical

Services.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Table of Contents

Section 1: About This Manual .......................................................................................................................................... 5

1.1: Agency Approvals..............................................................................................................................................................................................5

1.2: Related Documents............................................................................................................................................................................................5

1.3: Cautions and Warnings ......................................................................................................................................................................................6

Section 2: System Overview............................................................................................................................................. 7

2.1: System Description............................................................................................................................................................................................7

2.1.1: Standard Features....................................................................................................................................................................................7

2.1.2: Options....................................................................................................................................................................................................7

2.1.3: System Limitations .................................................................................................................................................................................7

2.2: Specifications.....................................................................................................................................................................................................7

2.2.1: Supply Rating .........................................................................................................................................................................................7

2.2.2: Environmental Specifications.................................................................................................................................................................7

2.3: System Components ..........................................................................................................................................................................................8

2.3.1: Replacement Kits....................................................................................................................................................................................8

2.4: Product Diagram................................................................................................................................................................................................8

2.4.1: Main Power Supply ..............................................................................................................................................................................10

2.5: System Cabinets...............................................................................................................................................................................................10

2.6: Compatible Equipment ....................................................................................................................................................................................11

Section 3: Installation ..................................................................................................................................................... 12

3.1: Preparing for Installation .................................................................................................................................................................................12

3.2: Installation Checklist .......................................................................................................................................................................................12

3.2.1: Memory-Backup Battery ......................................................................................................................................................................13

3.3: Attaching Option Boards .................................................................................................................................................................................13

3.4: Connecting the Network Communications Module ........................................................................................................................................14

3.5: Connecting the Loop Control and Expander Modules ....................................................................................................................................15

3.5.1: Mounting Instructions...........................................................................................................................................................................15

3.5.2: Setting SLC Loop Number ...................................................................................................................................................................15

3.5.3: Installing a Multi-layer Module into the Chassis .................................................................................................................................15

3.6: Form-C Relays on the CPU .............................................................................................................................................................................17

3.7: Connecting Power Sources and Outputs..........................................................................................................................................................18

3.7.1: Overview...............................................................................................................................................................................................18

3.7.2: Connecting 240 V Mains Supply..........................................................................................................................................................18

3.7.3: Connecting Local and Remotely Powered Devices..............................................................................................................................19

3.7.4: Checking AC Power .............................................................................................................................................................................21

3.7.5: Auxiliary Power Supply Connections ..................................................................................................................................................22

3.8: Installing Printers.............................................................................................................................................................................................22

3.8.1: Printer Installation Sequence ................................................................................................................................................................22

3.8.2: Configuring the Printer .........................................................................................................................................................................22

3.9: Wiring a Signalling Line Circuit (SLC)...........................................................................................................................................................23

3.9.1: SLC Overview ......................................................................................................................................................................................23

3.9.2: SLC Capacity........................................................................................................................................................................................23

3.9.3: SLC Installation ....................................................................................................................................................................................24

3.10: Connecting a FAAST Intelligent Aspiration Detector ...................................................................................................................................24

3.11: Connecting a PC for Programming................................................................................................................................................................24

Section 4: Testing the System ....................................................................................................................................... 25

4.1: Operational Checks..........................................................................................................................................................................................25

4.2: Battery Checks and Maintenance ....................................................................................................................................................................25

4.2.1: PSI Status..............................................................................................................................................................................................26

Appendix A: Electrical Specifications ........................................................................................................................... 27

A.1: Operating Power .............................................................................................................................................................................................27

A.2: SLC Loops ......................................................................................................................................................................................................27

A.3: Notification Appliance Circuits ......................................................................................................................................................................27

A.4: Networks.........................................................................................................................................................................................................27

A.5: Wire Requirements .........................................................................................................................................................................................27

A.6: Power Supply Calculations.............................................................................................................................................................................28

A.6.1: Calculating the System Current Draws................................................................................................................................................28

A.6.2: How to Use the Calculating Tables .....................................................................................................................................................28

A.6.3: Calculation for Main Supply Current ..................................................................................................................................................29

A.6.4: Calculating the Maximum Secondary Power Quiescent Current Draw ..............................................................................................29

A.6.5: Calculating the Maximum Secondary Power Fire Alarm Current Draw.............................................................................................30

A.7: Calculating the Battery Requirements ............................................................................................................................................................30

A.7.1: Battery Power Equations ...................................................................................................................................................................30

A.7.2: Recommended Standby Battery Sizes .................................................................................................................................................30

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 3

Table of Contents

Appendix B: Cabinet and Mounting Information.......................................................................................................... 31

B.1: CAB650 Mounting Details ........................................................................................................................................................................31

B.2: CAB900 Mounting Details ........................................................................................................................................................................32

B.3: CAB 18U Cabinet Mounting Dimensions ................................................................................................................................................33

B.4: CAB 28U Cabinet Mounting Dimensions ......................................................................................................................................................34

B.5: CAB 40U Cabinet Mounting Dimensions ......................................................................................................................................................35

B.6: Laying Out Equipment in Cabinet and Chassis ..............................................................................................................................................36

B.7: Installing Replacement Equipment ................................................................................................................................................................36

B.7.1: Installing a replacement keypad...........................................................................................................................................................36

4

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Section 1: About This Manual

1.1 Agency Approvals

AS 7240.2-2004

Fire Detection and Alarm Systems

Part 2: Control and Indicating Systems

(ISO 7240.2:2003, MOD)

The AFP-3030 supports the following optional functions of AS7240.2:

– Output to fire alarm devices, to clause 7.8

– Control of fire alarm devices, to clause 7.9

– Output to fire protection equipment, Output Type B to clause 7.10

– Delays to outputs, to clause 7.11

– Dependency on more than one fire signal, Type A Dependency to clause 7.12

– Supervisory signal condition, to clause 8

– Fault signals from points, to clause 9.3

– Output to fault warning routing equipment, to clause 9.9

– Disabled condition, to clause 10

– Disablement of addressable points, to clause 10.5as well as these ancillary functions not required by AS7240.2:

– Any output may be programmed (at Access Level 3) to only respond to signals from one of the following: from any zone (Z000 to Z999), or from any logic zone (ZL1 to ZL1000), or from any release zone (ZR0 to ZR9), or from any special zone, or from any fault zone (ZT1 to ZT100)

– The ability to disable any input or output, not just those required by AS7240.2

– The PSI PCB has a terminal labelled ‘General Fault Input’, which is normally a closed circuit. Interrupting this circuit results in a “PSI EXT FLT MONITOR” fault warning.

– Outputs to automatic fire protection equipment (smoke control) may be configured so that they can be reset following an alarm by either: the ‘RESET’ control, or the ‘SMOKE CONTROL Reset’ control

– The fire panel retains a history of the last 4000 events.

– The ability to test the alarm devices by pressing the ‘Alarm Devices Test’ control.

AS 7240.4-2004

Fire Detection and Alarm Systems

Part 4: Power Supply Equipment

(ISO 7240.4:2003, MOD)

The AFP-3030 supports the following optional functions of AS7240.4:

– Battery function check, to clause 5.5

AS 4428.3-2010

Fire Detection, Warning, Control, and Intercom Systems - Control and Indicating Equipment

Part 3: Fire Brigade Panel

AS 1670.1-2004

Fire Detection Installations

Part 1: Fire Detection and Alarm Systems

1.2 Related Documents

The table below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices.

Off-line Programming Utility

VeriFire Tools Programming Utilities

Fire Alarm Control Panel (FACP) and Main Power Supply Installation

AFP-3030 Installation, Programming, and Operations Manuals

NPS (Notifier Power Supply) Installation Sheet

Battery Connection Installation Kit

Networking

Noti • Fire • Net Version 5.0 & Higher Manual

High-Speed Notifier Network Manual

Document Number

Available for download: www.notifier.com.au

Document Number

DOC-01-031

DOC-01-032

DOC-01-033

DOC-03-057

DOC-03-046

Document Number

51584

54013

Table 1.1 Related Documents (1 of 2)

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 5

About This Manual

HS-NCM Installation Document

System Components

ARE Interface Board Installation Sheet

Zone Mimic Manual

ACM-8RA Installation Sheet

Intrinsically Safe Barrier Manual

Annunciator Name Plate Installation Sheet

Extinguishing Agent release Module Manual

DA Series BOWS Manual

DVC Digital Voice Command Manual

DVC-RPU Manual

DAA2 and DAX Amplifiers Manual

DAL Devices Reference Document

Mass Notification Systems Configuration, Programming and Operations Manual

Annunciator Control System Manual

LCD2-80 Manual

LDM Series Lamp Driver Annunciator Manual

SCS Smoke Control Manual (Smoke and HVAC Control Station) Manual

SCS-8A/SCE-8A Installation Sheet

First Command Manual

XP10-M Ten Input Monitor Module Installation Document

XP6-C Supervised Control Module Installation Document

XP6-MA Six Zone Interface Module Installation Document

XP6-R Six Relay Control Module Installation Document

FSA-8000 FAAST Intelligent Aspiration Sensing Technology Document

SLC-IM Manual

Table 1.1 Related Documents (2 of 2)

NOTE:

Where used in this manual, the term CPU refers to the main circuit board for the fire alarm control panel’s central

processing unit (see Section 2.3 “System Components” for a more detailed list of part numbers.)

1.3 Cautions and Warnings

This manual contains cautions and warnings to alert the reader as follows:

!

CAUTION: SUMMARY IN BOLD

INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS,

RUNTIME ERRORS, OR EQUIPMENT DAMAGE.

!

WARNING: SUMMARY IN BOLD

INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE

DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA OR

PERSONAL INJURY.

Cautions and Warnings

54014

Document Number

DOC-03-062

DOC-01-028

DOC-03-052

DOC-01-029

DOC-03-060

DOC-01-005

DOC-01-004

52411

50107425-001

53265

52410

LS10063-000NF-E

15842

53242

15885

15712

LS10126-000AU-E

(DOC-03-086)

LS1001-001NF-E

I56-1803

I56-1805

I56-1806

I56-1804

I56-3903

LS10026-000NF-E

6

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Section 2: System Overview

2.1 System Description

2.1.1 Standard Features

• Connections to easily mount from one to ten Signalling Line Circuit (SLC) loops

• Network operation

• Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or CLIP families of detectors and modules

• Alarm, Fault, and Supervisory relays

• Support for 32 annunciator addresses with either 64 or 96 points each (depending on the capability of the annunciator)

• Supports Open (Style 4) and Closed (Style 6/7) SLC loops

• Logic Equations

• Multi-line display

• Ability to activate local sounder or relay bases in alarm or pre-alarm

• Supervisory duct and smoke detectors

• Supports Intelligent Sensing algorithms

• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic annunciators), TM-4 transmitter

• EIA-232 connection for printer

• Autoprogram feature for faster programming of new devices

• Easy connection to VeriFire® Tools programming utility

• The basic system power supply charges sealed lead-acid batteries ranging in capacity from 11 to 85 amp hours, and provides up to

5 amps of power for use by the CPU.

• Easy connection to auxiliary power supplies and battery chargers for custom design of very large systems.

• Ground fault detection

• Mass Notification System compatible

1

2.1.2 Options

Refer to Section 2.3 “System Components” for descriptions of the various optional modules.

• Rubberized keypad with a standard “QWERTY” keyboard layout, a 640-character LCD display, indicator LEDs, and switches.

• Separately ordered Loop Control Modules and Loop Expander Modules provide up to ten SLC loops.

• Optional equipment includes: ACS devices, ACM-8RA remote relay module to provide additional relay points, and audio/voice components.

2.1.3 System Limitations

System expansion must take into consideration the following:

1.

The physical limitations of the cabinet configuration.

2.

The electrical limitations of the system power supply.

3.

The capacity of the secondary power source (standby batteries).

2.2 Specifications

2.2.1 Supply Rating

Supply Rating Parameter

Input Fuse Rating

Input Voltage Rating

Output Ratings

Output Current

Output Ratings (Charger)

Charger Voltage

Details

M205 Fuse - 250V, 8.0A

NPS-5CHS: 100-240 V AC, 50-60 Hz, 0.8-2.5 A

NPS-11CHS: 100-240 V AC, 50-60 Hz, 1.5-5.0 A

Details

NPS-5CHS: 5.6 A @ 27.3 V DC

NPS-11CHS: 11.7 A @ 27.3 V DC

Details

27.3 V DC

2.2.2 Environmental Specifications

Environmental Specifications

Parameters

Environmental Limits

IP Rating

Details

0°C to 49°C dry heat

40°C @ 93% relative humidity

CAB650, CAB900: IP30

18U, 28U, 40U: IP52

1. Control Active LED is not supported.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 7

System Overview

System Components

2.3 System Components

Central Processing Unit (CPU) with Power Supply

The central processing unit for the AFP-3030 is a combination of the CPU and on board power supply (NPS-5CHS or NPS-11CHS). The power supply provides +24 V DC power and a battery charger for the basic system. Auxiliary power supplies and/or battery chargers are available to customize large systems.

Keypad/Display

The keypad with built in LCD display serves as a primary display for the AFP-3030.

Enclosures

Five cabinet sizes are available; CAB650, CAB900, 18U, 28U, and 40U. Refer to Section 2.5, “System Cabinets”, on page

10 for additional information.

SLC Loops: LCM-320, LEM-320

To provide one SLC loop, connect one LCM-320 to the panel. Connect an LEM-320 to the LCM-320 to provide a second loop. Up to five pairs of modules can be installed on the panel to provide a maximum of ten SLC loops.

Network Connection

Connect a wire or fibre version of the NCM or the HS-NCM to provide a connection to the Noti•Fire•Net (network version 5.0 or higher) or High-Speed Noti•Fire•Net.

Annunciators

The AFP-3030 supports ACM-24AT/ACM-48A (and their expanders) with either 64 or 96 points at an address, as well as

LDM-32 (and expanders) and Notifier’s other ACS devices. (See Section 2.6 “Compatible Equipment” if looking for specific ACS

devices.)

NOTE:

Annunciators for the AFP-1010, AM-2020, and AFP-2800 operate on a different baud rate and are not compatible with the AFP-3030.

Audio System

Voice evacuation applications are documented in the Audio System manuals:

DVC Digital Voice Command Manual,

DAA2 and DAX Amplifiers Manual, DS-DB Digital Series Board Manual, DVC-RPU Manual

and the

AA-series Audio Amplifiers Manual.

Mass Notification System

The AFP-3030 supports Mass Notification applications. Installation, programming and operation information for Mass Notification systems are documented in the

Mass Notification Manual

. Refer to the AFP-3030 programming and operation manuals for additional information.

NOTE:

The AFP-3030 does not support Control Active LED.

2.3.1 Replacement Kits

The system components that are available as replacement kits for the AFP-3030 are listed in Table 2.1.

Model Number

ASY-02-034

ASY-02-033

ASY-02-056

FG-50-011

ASY-01-035

FG-65-012

Description

NPS-5CHS 5.6 A Power Supply Replacement Kit

NPS-11CHS 11.7 A Power Supply Replacement Kit

CPU2-3030AU CPU Replacement Kit for Australian AFP-3030

DISP-3030AU Keypad Replacement Kit for Australian AFP-3030

Battery connection pack

3 V BR2335 23mm Lithium Battery

Table 2.1 Available Kits

2.4 Product Diagram

The control panel electronics are contained on one printed circuit board assembly that holds the central processing unit and power supply interface, collectively known as the CPU.

8

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Product Diagram

System Overview

The following figure illustrates the location of the various connections, switches, jumpers and LEDs on the circuit board. See Section 3

“Installation” for more details.

B-Type USB Connection

ACS (power-limited, supervised)

LCD2-80: RDP pins

LCD2-80: TOut pins

Printer (isolated)

Alarm Relay*

Supervisory Relay*

Fault Relay*

Mini USB

Connection

Alarm Relay*

CTX/CRX

CRT-2 or Keltron printer supervision

(TB5 CTX, REF No connection)

NUP Connection for

HS-NCM network communications

4K7 EOL

Resistors

24 V Power from PSU

NAC Connection

NAC Connection

Field ACM Communications Connection

Field Power Connection

Field Power Connection

Internal 24 V DC Connection

24 V DC Power from PSU for Door Holders

Panel MCP

Connection

General Fault Input

CPU Keypad

Interface

Local ACM Out

LCM Interface

Brigade Interface

(A.R.E. Connection)

Battery Power

Interface

Lithium battery for backup of on-board memory (See

Section 3.2.1

“Memory-Backup Battery”)

* For software versions prior to V23.12: Relay may energise at power up and should not be used for Alarm Signalling Equipment. Alternative connections are available via the Brigade Interface (A.R.E. Connection). See the

A.R.E. Interface Board Installation Sheet

for connection details.

Figure 2.1 CPU Connections

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 9

System Overview

The keyboard/display assembly is shown in Figure 2.3.

System Cabinets

Figure 2.2 AFP-3030 installed in a CAB650

Fire LED

Operating LED

Silence/Resound Alarm

Button

Alarm Scroll Button

Reset Button

Disable Button

System Fault LED

Fault Scroll Button and LED

Supervisory Scroll Button and

LED

Disable Scroll Button and LED

Other Scroll Button and LED

Pre Alarm LED

Alarm Routing LEDs

Alarm Routing Activated

LED

Silence Buzzer Button

Alarm Devices LEDs

Alarm Devices Test &

Disable Buttons & LEDs

Smoke Control Reset &

Disable Buttons & LEDs

Delays On/Off Button and LED

QWERTY Keyboard

Program, Status and Navigation

Figure 2.3 AFP-3030 Keypad

2.4.1 Main Power Supply

The NPS-5CHS or NPS-11CHS power supply provides a total of 5.6 A or 11.7 A to the CPU and has a built-in charger. During normal operation, the NPS can recharge batteries ranging in capacity from 7 to 85 amp-hours.

See Section 3.7, “Connecting Power Sources and Outputs”, on page 18 for basic power information.

2.5 System Cabinets

The CPU and modules are installed in a CAB650, CAB900 or U-Series backbox, holding up to four rows of equipment plus batteries (up to two 85AH batteries). Backboxes can be ordered with windowed or solid doors. The doors of the 28U and 40U can be mounted on the left or the right side of the cabinet. A trim ring option is available for semi-flush mounting.

External measurements for each cabinet backbox are provided in Appendix B, “Cabinet and Mounting Information”, on page 31. Refer

to the

CAB650

,

CAB900

, or

U-Series

documentation for dimensions and door mounting specifications.

10

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Compatible Equipment

System Overview

2.6 Compatible Equipment

Compatible Notifier and System Sensor equipment that connects directly to the CPU is listed below. These are the most common devices at time of publishing; the most complete list of compatible intelligent SLC loop devices is provided in the

SLC Wiring Manual

; for conventional non-addressable equipment see the

Device Compatibility Document

. Other control panels and their equipment can also be connected in a network, via Noti•Fire•Net version 5.0 or High-Speed Noti•Fire•Net; refer to the

Noti•Fire•Net Version 5.0 Installation

Manual

or the

High-Speed Noti•Fire•Net Installation Manual

for details. Some products are documented in a separate manual; see

Section 1.2 “Related Documents”.

ACM-24AT

ACM-48A

ACM-8RA

AEM-24AT

AEM-48A

ARM

LCD2-80

LDM-32

LDM-E32

LDM-R32

SCE-8A

SCS-8A

SCS-8LA

Annunciators

Annunciator (Control)

Annunciator (Control)

8-way Relay Output Annunciator

Annunciator (expander)

Annunciator (expander)

Agent Release Module Kit

LCD Annunciator Kit

Lamp Driver Kit

Lamp Driver Expander Kit

Lamp Driver Relay Kit

Smoke Control Annunciator

(Expander)

Smoke Control Annunciator

(Control)

Smoke Control Annunciator

(Control)

HS-NCM-MF

HS-NCM-MFSF

Network Control Modules

Network Control Module - Multimode optical fibre

Network Control Module - Multimode/ Single-mode optical fibre

HS-NCM-SF

HS-NCM-W

HS-NCM-WMF

HS-NCM-WSF

Network Control Module - Singlemode optical fibre

Network Control Module - Wire

Network Control Module -

Wire/Multi-mode optical fibre

Network Control Module - Wire/

Single-mode optical fibre

NCA-2AU

NCM-F

NCM-W

RPT-W

RPT-F

RPT-WF

BACNET-GW-3

DVC

MODBUS-GW

Network Control Annunciator

Network Control Module - Fibre

Network Control Module - Wire

NFN Wire-to-Wire Repeater

NFN MMOF-to-MMOF repeater

NFN Wire-to-MMOF repeater

Gateways

BACnet Gateway

Digital Voice Command

Modbus Gateway

NFN-GW-AU-EM-3

OnyxWorks

VESDA-HLI-GW

AIBS32

B501BI

NFN gateway (Embedded)

OnyxWorks Workstation with and without PC gateway

VESDA-Net gateway

Detector/Sounder Base

Intelligent Base Sounder with integrated isolator

Addressable Detector Base with isolator

B524IEFT

NFX-BF-IVR

NFX-BS-IV

NFXI-BS-IV

(Replaces B501)

Short Circuit Isolator Base

Addressable Strobe Base (NFX

Series)

Addressable Sounder Base (NFX

Series)

Addressable Sounder Base (NFX

Series)

NFX-BSF-IVR

NFX-WF-RR

NFX-WSF-RR

NFX-WS-R

NFX-WS-W

FS-WSO

FS-WSS

FS-WST

FS-BSO

FS-BSS

AAM

Addressable Sounder/Strobe Base

(NFX Series)

Addressable Strobe (NFX Series)

Addressable Sounder/Strobe (NFX

Series)

Addressable Sounder (NFX Series)

Addressable Sounder (NFX Series)

Wall Mount Sounder - Off White

Wall Mount Sounder and Strobe -

Red

Wall Mount Strobe - Red

Detector Base Sounder - Off White

Detector Base Sounder - Off White and Strobe - Red

Field Modules (FlashScan)

Addressable Alarm

Acknowledgement Module (HUSH)

Single Intelligent Control Module FCM-1

FDM-1

FDMR-1

FMM-1

FMM4-20

FRM-1

FZM-1

ISO-X

SLC-IM

XP-10M

XP-6C

XP-6MA

XP-6R

ZCM

M700X

FAPT-751AUS

FAPT-851AUS

FSB-200

FSB-200S

Dual Switch Input Module

Dual Input/Output Module

Single Switch Input Module

4-20mA Intelligent Interface Module

Single Intelligent Relay Output

Module

Single Conventional Zone Interface

Module

Loop (SLC) Isolator Module

Signalling Line Circuit-Integration

Module

10-way Switch Input Module

6-way Control output (NAC) Module

6-way Conventional Zone Interface

Module

6-way Relay Output Module

ZCM Conventional Zone

Conversion Module

Isolator Module in 200 series

Detectors (FlashScan)

Intelligent Photo-Heat (Acclimate)

Intelligent Photo-Thermal multisensor (Acclimate)

Beam Detector

Beam Detector with built-in test facility

FSD-751P

FSI-751AUS

FSL-751

FSP-751AUS

FSP-851AUS,

FSP-951AUS

FST-751AUS

Innovair DSU

Intelligent Ion

View™ High Sensitivity Laser

Sensor

Photoelectric Smoke Detector

Intelligent Photo Sensor

Temperature Sensor

Intelligent Fixed Temp. Detector

FST-851AUS, FST-

951AUS

FST-851RAUS, FST-

951RAUS

Intelligent Thermal Sensor

Intelligent Thermal Sensor (rate of rise)

FST-851HAUS,

FST-951HAUS

(rate of rise)

Intelligent Flash Scan High Heat

(Addressable)

DNRAUS

Photoelectric Smoke Sensors

FPTI-951AUS Multi-Criteria Photoelectric,

Thermal and Infrared Sensor

Duct Detector Housing for

Intelligent Detector

DNRW Weatherproof Duct Housing for

Intelligent Detector

FDX-751BAUS

FDX-751RBAUS

FDX-851AUS

FDX-851RAUS

IDX-751AE

Detectors (CLIP)

Intelligent Thermal Sensor

Intelligent Thermal Sensor

Intelligent Thermal Sensor

Intelligent Thermal Sensor

Intrinsically Safe Addressable

Photoelectric Detector

Intelligent Photo Sensor SDX-851AUS

Intelligent VESDA-E Detectors

VEP-A00-1P-NTF VESDA-E VEP 1-pipe with LEDs,

Plastic Enc.

VEP-A00-P-NTF

VEP-A10-P-NTF

VESDA-E VEP 4-pipe with LEDs,

Plastic Enc.

VESDA-E VEP with 3.5”Disp,

Plastic Enc.

VEU-A00-NTF

VEU-A10-NTF

VESDA-E VEU with LED display

VESDA-E VEU with 3.5" Display

Smoke Detector with LED Display

FSM-500K

NFX-MCP-GLASS

WCP-5A

Smoke Detector with 3.5”

Manual Call Point

Indoor Manual Call Point

Intelligent Manual Call Point (SS

India)

Outdoor Manual Call Point

Addressable loop powered Audio Visual Alarm devices

(CLIP)

VAD-PC-I02 NTF CLIP Pure White Strobe, white flash, clear lens, with Isolator

WSS-PC-I02

DSS-PC-I02

NTF CLIP Pure White

Sound/Strobe, red flash, clear lens, with isolator

NTF CLIP Pure White

Sound/Strobe, red flash, clear lens, with isolator and base.

FWSGAUS

FWD-200PAUS

FWD-

200ACCLIMATEAUS

Wireless Equipment

SWIFT FlashScan Wireless

Gateway

Wireless FlashScan Photo Detector

Wireless FlashScan Acclimate

Detector

FWH-200FIX135AUS Wireless FlashScan Fixed Heat

Detector

FW-MMAUS Wireless FlashScan Monitor

Module

W-USBAUS USB Adapter

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 11

Section 3: Installation

3.1 Preparing for Installation

Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate temperature. The area should be readily accessible with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely.

Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appropriate knockouts.

Before installing the fire alarm system, read the following:

• Review the installation precautions at the front of this manual.

Installers should be familiar with the standards and codes specified in Section 1.1 “Agency Approvals”.

• All wiring must comply with the National and Local codes for fire alarm systems.

• Do not draw wiring into the bottom 25 cm of the cabinet except when using a separate battery cabinet; this space is for internal battery installation.

Review installation instructions in Section 3.2 “Installation Checklist”.

!

WARNING: RISK OF IRREPARABLE EQUIPMENT DAMAGE

MAKE SURE TO INSTALL SYSTEM COMPONENTS IN THE SEQUENCE LISTED BELOW. FAILURE TO DO

SO CAN DAMAGE THE CONTROL PANEL AND OTHER SYSTEM COMPONENTS.

!

WARNING: RISK OF IRREPARABLE EQUIPMENT DAMAGE

WEAR A STATIC DISCHARGE STRAP ON WRIST TO PREVENT EQUIPMENT DAMAGE.

3.2 Installation Checklist

The checklist that follows contains references to information included in other manuals; see Section 1.2 “Related Documents” for docu-

ment part numbers.

1.

2.

3.

Task

Mount the cabinet backbox to the wall.

Wire relays

Attach & wire other system components

 Audio/Voice equipment

Refer to:

Appendix B, “Cabinet and Mounting Information”

Section 3.6 “Form-C Relays on the CPU”

4.

5.

6.

 Annunciators and other ACS devices

 Printer or other output device(s)

Network devices

Wire the Signalling Line Circuits (Notification

Appliance Circuits and Initiating Device Circuits)

Calculate the proper battery rating.

Install main power supply & batteries in separate enclosure. Run cable to main & optional power supplies, DC power outputs, relays, etc.

DVC Digital Voice Command Manual, DAA Digital Audio Amplifiers Manual,

DVC-RPU Manual

Installation document for the specific device (such as

ACS Manual, ACM-

8RA Install Sheet

, etc.)

Section 3.8 “Installing Printers”

Noti•Fire•Net Version 5.0 & Higher Manual/High-Speed Noti•Fire•Net

Manual,

and/or Installation document for specific device(s)

Section 3.9 “Wiring a Signalling Line Circuit (SLC)” and the SLC Wiring

Manual

Main Power Supply Manual

Section 3.7 “Connecting Power Sources and Outputs”

!

11.

12.

13.

7.

8.

9.

10.

Do not activate power at this time. Do NOT connect batteries.

 Main power supply.

 Auxiliary power supply and/or external battery charger

NPS Installation Sheet

Check that all mounting holes are secured to insure a proper Earth Ground connection.

Connect wire shielding to Earth Ground.

Remove insulator from lithium battery on CPU

Section 3.2.1 “Memory-Backup Battery”

Apply AC power to the control panel by placing the external circuit breaker to the ON position.

Do NOT connect batteries until AC power is checked (see next step).

Check AC power.

Section 3.7.4 “Checking AC Power”

Connect the batteries using interconnect cable as described in Section 3.7.3 “Connecting Local and Remotely Powered

Devices”.

Program the control panel.

Programming Manual.

Table 3.1 Installation Checklist

12

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Attaching Option Boards

Installation

3.2.1 Memory-Backup Battery

The lithium battery on the CPU provides backup of the CPU’s on-board memory during power loss. The CPU ships with an insulator to prevent the battery from discharging. To preserve the battery, the insulating tube should be left in place as long as possible before applying AC power.

If the insulator is

not

removed before applying AC power, the control panel will show a fault situation.

This battery’s shelf-life should exceed 10 years, but if for some reason it fails, the control panel will show a fault when powered up. To replace the lithium battery:

1.

Make a full backup of all system settings to prevent loss of all programming data.

2.

Disconnect all power sources.

3.

Lift clip gently using a hardware tool or screwdriver, and remove battery from under clip (use fingers, as screwdriver could damage components) before inserting new battery.

!

Lift clip gently while removing battery

Dotted line indicates location of insulator

CAUTION: BATTERY REPLACEMENT

THE BATTERY USED IN THIS DEVICE MAY PRESENT A RISK OF FIRE OR CHEMICAL BURN IF

MISTREATED.

DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 100°C, OR INCINERATE.

A REPLACEMENT 3 V BR2335 LITHIUM BATTERY CAN BE ORDERED FROM NOTIFIER BY QUOTING

THE PART NUMBER FG-65-012. USE OF ANY OTHER BATTERY MAY PRESENT A RISK OF FIRE OR

EXPLOSION.

4.

Follow system power-up procedures.

5.

Dispose of used battery promptly. Keep away from children. Do not disassemble and do not dispose of in fire.

3.3 Attaching Option Boards

If installing option boards into a CAB650, CAB900, or U-Series backbox, mount & connect those boards at this time. This section contains general instructions for mounting an option board; see the documentation that shipped with your board for any product-specific instructions.

To mount option boards against the CHS-3L or CHS-4L backplate, attach stand-offs to the chassis studs.

Slide tabs at bottom of option boards into the matching slot.

Figure 3.1 Mounting Option Boards in CHS-3L and CHS-4L

As described in Appendix B.6, “Laying Out Equipment in Cabinet and Chassis”, up to three option boards can be mounted in CHS-3L or

four option boards can be mounted in the CHS-4L; additional modules can be mounted in other chassis.

Mounting procedures: Chassis mount

1.

Install two 3/4 inch (19.05 mm) stand-offs onto the chassis as shown in Figure 3.1.

2.

Place the first option board over the stand-offs so that holes line up.

3.

If no more option boards will be mounted in that position, securely fasten all stand-offs with screws (provided with module). If mounting a second option board, attach another layer of stand-offs and repeat steps 2-3.

Note:

Set the switches on an option board before mounting another layer in front of it.

4.

If mounting a pair of SLC loop modules, refer to Section 3.5 “Connecting the Loop Control and Expander Modules” and to

Section 3.5.3 “Installing a Multi-layer Module into the Chassis”.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 13

Installation

Connecting the Network Communications Module

5.

For the top (second) layer of option boards, slide the tab at the bottom of the board into the slots on the chassis, and lay the board back onto the top of the chassis so that the studs line up with mounting holes on the option board. Securely fasten all stand-offs with screws provided with module.

NOTE:

Mounting two pairs of loop-control and -expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position.

Mounting procedures: Door mount

If mounting the option board in the door behind a blank dress plate, see Figure 3.2. This dress plate is suitable for option boards, which do not need to be visible or accessible when the door is closed.

Mount option board onto stand-offs

(included) to the blank plate

Mount single-space blank plate onto the door.

Fasten option board to the plate with four screws (included).

Figure 3.2 Door-Mounting Option Boards with a Single-space Blank Plate

3.4 Connecting the Network Communications Module

If networking two or more control panels (or network control annunciators), each one requires a Network Communications Module; a wire version and a fibre version are available. The wire and fibre versions on the NCM or HS-NCM can be installed on the CPU and power supply assembly. The preferred position is on top of the CPU assembly, as shown in Figure 3.3.

1.

Mount the NCM or HS-NCM in the selected position. (See Figure 3.3)

2.

Connect J1 on the CPU to J3 on the NCM or J6 on the HS-NCM using the network cable provided (P/N 75556). Do not connect two

NCMs via NUP ports (aka NUP to NUP).

3.

When installing an NCM:

Connect Channel A and/or Channel B as described in the

NCM Installation Document

.

When installing a HS-NCM:

Connect Channel A to Channel B as described in the

HS-NCM Installation Document

.

CPU

Assembly

NCM or

HS-NCM

14

Fasten the

NCM/HS-NCM to the CPU Assembly using the screws and standoffs included with your network card.

NUP Port connections:

Connect NUP cable from

NCM/HS-

NCM to J1 on the fire panel

Figure 3.3 Mounting an NCM/HS-NCM to the CPU Assembly

NOTE:

See the

Noti•Fire•Net Version 5.0 & Higher Manual

and the

NCM Installation Document

or the

High-Speed

Noti•Fire•Net Manual

for system configuration information.

NOTE:

Over-bending fibre-optic cable can damage it. Do not exceed a 8 cm minimum bend radius.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Connecting the Loop Control and Expander Modules

Installation

NOTE:

NCM hardware is not compatible with HS-NCM hardware and should not be mixed on the same network.

3.5 Connecting the Loop Control and Expander Modules

3.5.1 Mounting Instructions

Mount loop control and expander modules within the cabinet with the CPU. Typical mounting positions are in the row immediately below the fire panel. Follow the basic chassis-mounting instructions given for option boards. Loop-expander modules are mounted first;

Loop-control modules are mounted on top of those. Alternately, loop-control and loop-expander modules can be attached to each other and mounted as a pair to the chassis. See Figure 3.5 for connection instructions, connector locations and stand-off lengths.

If using loop control and expander modules in CHS-4L see Figure 3.6.

NOTE:

Mounting two pairs of loop control and expander modules in one chassis position may cause intermittent electrical interference. If this occurs, move one pair to a separate chassis position.

After all loop-control and loop-expander modules are mounted in the cabinet, connect the SLC loops to TB1 on each loop-control and loop-expander module as shown in Figure 3.8. Daisy-chain the loop-control modules as shown in Figure 3.7. The ribbon-cable connection runs from header J7 on the CPU to header J1 (“Data in”) on the first loop-control module, from J3 (“Data out”) on that unit to J1 on the next unit in the chain, and likewise for up to five loop-control modules. Each module should be assigned a unique SLC loop number

(see below); loop number does not need to match the module’s location in this daisy-chain.

FlashScan devices can operate in either FlashScan or, for retrofit applications, CLIP mode. Each LCM-320 or LEM-320 running a Flash-

Scan SLC can support up to 159 detectors and 159 modules. CLIP loops are limited to 99 detectors and 99 modules. These and other

capacity restrictions for CLIP mode loops are discussed in Section 3.9 “Wiring a Signalling Line Circuit (SLC)”. Refer to the

SLC Wiring Manual

for wiring requirements and specific details.

!

CAUTION: DO NOT EXCEED 99 ADDRESSES FOR CLIP

DO NOT PROGRAM MORE THAN 99 ADDRESSES ON A CLIP-MODE SLC LOOP, BECAUSE THIS WILL

SLOW THE SYSTEM DOWN AND COMPROMISE THE RESPONSE TIME OF THE PANEL TO DISPLAY

OFF-NORMAL EVENTS.

3.5.2 Setting SLC Loop Number

Assign a unique SLC loop number to the loop control module by setting SW1 on the module to 1, 3, 5, 7, or 9. The loop expander module which is mounted behind this loop control module will be assigned the next-higher even number. For example, if the LCM-320 is set to loop number 5, the LEM-320 mounted to it will be set to loop number 6.

3.5.3 Installing a Multi-layer Module into the Chassis

Follow the instructions illustrated in Figures 3.4 through 3.7 to install a pair of loop control/expander modules.

1.

Angle the module into the chassis so that the upper end of the rear board (or boards) fits into the top slot.

2.

Bring the module back down so that the lower board edges slip into the bottom slots.

3.

Secure the module to the chassis with the two module screws. Tighten securely.

4.

Connect the ribbon cable to the module.

TB1 SLC Loop

Connection

TB1 SLC

Loop

Connection

Stand-off locations

JP2 See note.

J3 Data Out to next LCM-320

JP1 See note.

J1 Data In from control panel or from previous LCM-320

Ground Fault LEDs:

D32 Loop Expander

Module Ground Fault

D28 Loop Control Module

Ground Fault

J2 LEM-320 Connection

LCM-320

Connection

SW1 Set to assign a unique

SLC loop number

LCM-320 LEM-320

NOTE:

Do not cut any jumpers on the LCM-320 or LEM-320.

Figure 3.4 LCM-320 and LEM-320 Diagram

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 15

Installation

Connecting the Loop Control and Expander Modules

!

WARNING: RISK

EQUIPMENT

DAMAGE.

USE SPECIFIED

STAND-OFF

MOUNTING

LOCATIONS ONLY.

SEE FIGURES 3.4

AND 3.5. DO NOT

USE CORNER

HOLES FOR

INSTALLATION

PURPOSES.

Loop

Control

Module

Loop

Expander

Module

Loop

Control

Module

J2

Loop

Expander

Module

J1

Stand-off locations

B+

SLC

BA- TB

J1

The long-pin end plugs directly into the back of the Loop Control

Module board.

The short-pin end plugs directly into the top of the

Loop Expander

Module

plug.

J1

J2 on LCM-320

“LEM-320 Data”

!

CAUTION:

IF THE STACKER-CONNECTOR IS

INSTALLED UPSIDE-DOWN, THE SHORT-

PIN END OF THE PLUG CAN FAIL TO MAKE

A SECURE CONNECTION WHEN PLUGGED

THROUGH THE LOOP CONTROL MODULE.

J2

Loop Expander Module mounted behind Loop Control Module

Figure 3.5 Connecting Loop Control Modules with Loop Expander Modules

NOTE:

Depending on system components, clearance may be tight. Do not force modules! Move the assembly around gently until you find the angle where components and mounting studs pass each other without scraping together.

Angle tab on loop control module into slot on CHS-4L

Use a slimline screwdriver (3/32”) to fasten down LEM-320 through the hole in the LCM-320 board.

For mounting in CHS-3L, see Figure 3.1

Figure 3.6 Inserting Pair of Loop Control and Expander Modules into CHS-4L

16

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Form-C Relays on the CPU

The red stripe on the ribbon cable is indicated by the dark line

J22 on PSU

Installation

NOTE:

The red stripe on the ribbon cable indicates position 1. Position 1 of the ribbon cable should line up with position 1 on J7 of the CPU and J1 and

J3 of the LCM-320.

!

WARNING:

INSTALL THE RIBBON CABLE

AS SHOWN. DO NOT FORCE

OR MODIFY THE CABLE TO

FIT ANY OTHER WAY.

EQUIPMENT DAMAGE CAN

RESULT FROM INCORRECT

ALIGNMENT.

3030LCMchainrv2.wmf

J1 on LCM-320

“Data in”

J3 on LCM-320

“Data out”

LCM-320 (in front) LEM-320 (in back)

Figure 3.8 SLC Loop Connections on Loop-Control and Loop-Expander Modules

3.6 Form-C Relays on the CPU

The panel provides a set of Form-C relays. These are rated for 1 A at 30 V DC (resistive):

• Alarm - TB4

• Fault - TB3

• Supervisory - TB2

• Alarm - TB1

Figure 3.9 Form-C Relay Connections

NOTE:

Form-C Relays may energize at power up and should not be used for Alarm Signalling Equipment. See the

A.R.E.

Interface Board Installation Sheet

for alternate connections for this purpose.

This is only applicable to software versions prior to V23.12. This operation was changed in V23.12 to not toggle the relays on start-up.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 17

Installation

Connecting Power Sources and Outputs

3.7 Connecting Power Sources and Outputs

!

WARNING: REMOVE POWER WHILE CONNECTING COMPONENTS TO THE SYSTEM

REMOVE ALL POWER SOURCES TO EQUIPMENT WHILE CONNECTING ELECTRICAL COMPONENTS. LEAVE

THE EXTERNAL, MAIN POWER BREAKER OFF UNTIL INSTALLATION OF THE ENTIRE SYSTEM IS COMPLETE.

!

WARNING: CHECK FOR SECONDARY POWER SOURCES

SEVERAL SOURCES OF POWER CAN BE CONNECTED TO THE CONTROL PANEL. BEFORE SERVICING THE

CONTROL PANEL, DISCONNECT ALL SOURCES OF INPUT POWER

INCLUDING THE BATTERY

. WHILE

ENERGISED, THE CONTROL PANEL AND ASSOCIATED EQUIPMENT CAN BE DAMAGED BY REMOVING AND/OR

INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES.

3.7.1 Overview

Complete all mounting procedures and check all wiring before applying power. Electrical connections include the following:

Primary power source.

+24 V DC, delivered through the NPS main power supply. For cabinet placement information see

Appendix B.6 “Laying Out Equipment in Cabinet and Chassis” and the

NPS Installation Sheet

.

Secondary power source.

+24 V DC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary

(battery) power is required to support the system during loss of primary power.

External power sources.

+24 V DC auxiliary power supplies.

Accessory power for peripheral devices.

The NPS provides +24 V DC power to devices within the same enclosure as the CPU. If those devices have outputs, the outputs must be power-limited. Power rating is limited by the NPS primary power source, which is

+24 V DC and 5.6 Amps (NPS-5CHS) or 11.7 Amps (NPS-11CHS) max.

NOTE:

The CPU ships with an insulator to prevents its lithium battery from discharging. To preserve the battery, this insulator should be left in place as long as possible before applying AC power. Some installers may find it convenient to remove the insulator before mounting all equipment.

NOTE:

If using multiple power supplies with one set of batteries, refer to main power supply documentation for connection requirements.

3.7.2 Connecting 240 V Mains Supply

!

WARNING: CHECK POWER SUPPLY TERMINATION POINTS BEFORE APPLYING POWER

240 V MAINS SUPPLY TERMINATION POINTS WILL DIFFER DEPENDING ON THE CABINET SIZE IN USE. VERIFY

CABINET SIZING AND MAINS TERMINATION POINT BEFORE APPLYING POWER.

NOTE:

The AFP-3030 (Main PS Node) should have the 240V mains supply termination and NCA-2 /Secondary CPU should always be powered by AFP-3030 PSI to monitor power supply / battery fault on the NCA-2 PSI CARD.

CAB650/CAB900

When installing a panel housed in a CAB650 or CAB900 cabinet, terminate the 240 V mains supply directly to the fused terminal block on the NPS-5CHS or NPS-11CHS power supply assembly.

AC SUPPLY

NEUTRAL

LIVE

EARTH

18

Figure 3.10 Fused terminal block on the NPS-xCHS power supply

U-series (18U, 28U, 40U)

An AFP-3030 panel in a U-series cabinet is fitted with a 240 V cable assembly terminated to the fused terminal block on the NPS-5CHS or NPS-11CHS.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Connecting Power Sources and Outputs

Installation

Terminate 240 V mains supply to the double GPO inside the cabinet, and use this GPO to provide power to the NPS-5CHS or NPS-

11CHS via the pre-terminated cable assembly.

FUSED

TERMINAL

BLOCK

240 V CABLE

ASSEMBLY

GPO

External mains terminates here in

U-series cabinets

Figure 3.11 GPO in U-series cabinets

3.7.3 Connecting Local and Remotely Powered Devices

Refer to Figure 3.12 for power connections for a locally powered device. Refer to Figures 3.13 and 3.14 for power connections to a

NCA-2 from a locally powered device.

To NPS

Power

Supply

Red

Red

Black

Black

To

Battery

Black

Red

Figure 3.12 Connecting a Locally Powered CPU to Power

NOTE:

The AFP-3030 (Main PS Node) should have the 240V mains supply termination and NCA-2 /Secondary CPU should always be powered by AFP-3030 PSI to monitor power supply / battery fault on the NCA-2 PSI CARD.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 19

Installation

Connecting Power Sources and Outputs

AFP-3030

(Locally Powered)

Remote NCA-2

Red (+)

Black (-)

Red (+)

Black (-)

Figure 3.13 Connecting a Remotely Powered NCA-2 to the Main CPU

20

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Connecting Power Sources and Outputs

Installation

Main CPU

(Locally Powered)

NCA-2

Red (+)

Black (-)

Red (+)

Black (-)

Figure 3.14 Connecting NCA-2 to the Main CPU within the same cabinet

NOTE:

The NCA-2 must be programmed with the Main PS Node number of the CPU from which it is drawing power. This node number must be separate from its own node number. Refer to the ‘SUPERVISION’ section of the AFP-3030 Programming Manual for more information.

3.7.4 Checking AC Power

Power up the fire panel by switching on the PSU switch. The device will be on when the PSU switch is illuminated (red).

PSU Switch

Figure 3.15 Location of the PSU Switch

Table 3.2 contains a checklist for checking the system with AC power applied to the main power supply:

!

CAUTION: CONFIRM BATTERIES ARE NOT CONNECTED

WHILE CHECKING AC POWER, MAKE SURE BATTERIES ARE NOT CONNECTED.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 21

Installation

Installing Printers

Component

CPU/PSU

Main power supply

Each auxiliary power supply

Status

The green Operating indicator will come on when power is coming from the main power supply.

The green Operating indicator will come on when AC is supplied.

Refer to the panel’s LCD display for any auxiliary power supply issues.

Table 3.2 AC Power Checklist

3.7.5 Auxiliary Power Supply Connections

If an optional auxiliary power supply is installed in the cabinet, connect it at this time. Follow the connection procedures specified by your auxiliary power supply.

3.8 Installing Printers

This section contains information on connecting a printer to the CPU and for setting the printer options. The basic steps are as follows:

1.

Make custom cable & connect it from printer to EIA-232 terminal on the CPU.

2.

Connect printer’s power supply.

3.

Configure printer settings as described in printer documentation.

Overview: PRN Printer

The PRN provides a printed record (80 columns on standard 9" x 11" tractor-feed paper) of all system events (alarm, trouble) and status changes within the system. The control panel can be configured to time-stamp the printout with the current time-of-day and date for each event. The printer can be located up to 15 metres from the control panel. Installation and configuration instructions follow.

3.8.1 Printer Installation Sequence

1.

Fabricate a custom cable to connect a printer to the system. Length of the cable will vary with each installation, but should not exceed a maximum length of 15 metres. Printer must be installed in the same room as panel. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25 Connector (provided) using the wiring specifications shown in

Figure 3.16.

NOTE:

Alternative wiring specifications are also shown in Figure 3.16 for a printer with a 9-pin connector. Refer to printer manual for detailed connection information.

2.

Tighten clamp on connector to secure cable. Connect the four open leads of the custom cable to the TB5 terminal block on the CPU as shown in Figure 3.16.

DB-9 connector for alternative printers

DB-25 connector on

PRN Series Printer

Note:

Outputs are power-limited but are not supervised.

TB5 on Control Panel

Figure 3.16 Printer Connections

3.

If installing a PRN series printer, plug it into your AC power source.

Note:

PRN printers require a 240 V AC, 50 Hz primary power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Because a secondary power source is not provided, use a separate Uninterruptible

Power Supply (UPS).

4.

Plug the DB-25 connector end of the custom cable into the EIA-232 port of your printer. Tighten securely.

5.

Configure the printer as described in Section 3.8.2 “Configuring the Printer”.

3.8.2 Configuring the Printer

Refer to the documentation supplied with the printer for configuration instructions.

22

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Wiring a Signalling Line Circuit (SLC)

PRN Printer Settings

Set the printer options (under the menu area) according to the settings listed in Table 3.3.

Option

L/R Adjust

Font

CPI

LPI

Skip

ESC Character

Emulate

Bidirectional Copy

I/O

Interface

Buffer

Serial

Baud

Format

Protocol *

CG-TAB

Character Set

Country

Select Zero

Auto-CR

Auto-LF

Option

Menu Lock

Language

Setting

0

HS Draft

10 CPI

6 LPI

0.0

ESC

FX-850

ON

Serial

40K

9600

8 Bit, None, 1 Stop

ENQ/STX

Graphic

Standard

E-USA ASCII

ON

OFF

OFF

Setting

ON

English

Paper

Single

Option

Form Adjust

Trac 1

Form Adjust

Trac 2

Form Adjust

Auto Sheet Feeder

Form Adjust

Auto Tear

F-Eject

Form Length

Trac 1

Lines

Standard

Trac 2

Lines

Standard

Barcode

Barmode

12/72

12/72

12/72

12/72

OFF

OFF

66

10.5”

Setting

66

10.5”

Off

Unsecured

*Protocol: When printing in graphics mode, set I/O

Serial Protocol to “Robust XON/OFF”.

Installation

Table 3.3 PRN Setup Options

3.9 Wiring a Signalling Line Circuit (SLC)

3.9.1 SLC Overview

Communication between the CPU and intelligent and addressable initiating, monitor, and control devices takes place through a Signalling Line Circuit (SLC). This manual provides requirements and performance details specific to this control panel; for installation information and general information, refer to the

SLC Wiring Manual.

For electrical specifications, see Appendix A.2 “SLC Loops”. For additional notes on SLC resistance values, see Section 4.1 “Operational Checks”.

3.9.2 SLC Capacity

The AFP-3030 supports up to five pairs of LCM-320 and LEM-320 modules, providing from one to ten SLC loops. Loop capacity depends on operating mode:

• Flash Scan: 01-159 intelligent detectors, 01-159 monitor and control modules

• CLIP: 01-99 intelligent detectors, 01-99 monitor and control modules

FlashScan devices can operate in either FlashScan or CLIP mode. Older models of CLIP devices only support addresses up to address

99. CLIP loops are limited to 99 detectors and 99 modules.

NOTE:

Response times for CLIP loops may vary. CLIP loops must be tested to assure that actuation of notification appliances occurs within 10 seconds after activation of an initiating device.

The following configuration guidelines may be used to improve the response times of CLIP loops:

1.

All manual pull stations must be assigned addresses from 1-20.

2.

Loops must be programmed for Rapid Poll (refer to the programming manual for specific instructions).

3.

Modules on a fully loaded loop must adhere to a ratio of two monitor modules to one control module.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 23

Installation

Connecting a FAAST Intelligent Aspiration Detector

3.9.3 SLC Installation

Install loop control and expander modules as described in Section 3.5 “Connecting the Loop Control and Expander Modules”. Note that

the unique SLC loop number assigned to a module does not need to match the module’s location in the cabinet. For details on designing, installing and configuring SLC loops, see the

SLC Wiring Manual

.

B+ A+ B- A-

TB1

SLC Loop Connections on Loop Control Modules

Channel

B

Channel

A

B+ A+ B- A-

TB1

SLC Loop #2 Connections on Loop Expander Module

Channel B (output loop)

Channel A (loop return)

B+ A+ B- A-

Open Wiring (Style 4)

SLC Loops

SLC loop connections are the same for Loop

Expander and

Control Modules

B+ A+ B- A-

Closed Wiring (Style 6/7)

SLC Loops

Use the isolation modules where

T-Tapping is required

Figure 3.17 SLC Loop Connections and Wiring

3.10 Connecting a FAAST Intelligent Aspiration Detector

The FAAST Intelligent Aspiration detector may be used to provide early warning fire protection using aspiration sensing technology.

FAAST Wiring:

Figure 3.18 shows the wiring for the FAAST detector to the AFP-

3030.

For additional installation information for the FAAST detector, refer the

FSA-8000 FAAST Installation and Maintenance Instruction

document (I56-3903) and the

SLC Wiring Manual

(51253).

SLC

Connection

To Next SLC Device -

From FACP or Previous Device -

To Next SLC Device +

From FACP or Previous Device +

24V External

Power

From Power Supply or Previous Device +

To Next Device -

From Power Supply or Previous Device -

Figure 3.18 FSA-8000A Connection to the FACP

3.11 Connecting a PC for Programming

A PC running the VeriFire® Tools programming utility can upload and download the operating program of the control panel when attached to J15 USB Connection, J1 Network/Service Connection (NUP) or to the second Network/Service connection on an attached wire or fibre version of the NCM or HS-NCM. Refer to the VeriFire® Tools CD for instructions.

24

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Section 4: Testing the System

4.1 Operational Checks

Between formal periodic testing and servicing intervals, the following operation checks should be performed monthly.

• Check that the green OPERATING LED lights.

• Check that all status LEDs are off.

• Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work.

• Before proceeding: a) notify the fire department and the central alarm receiving station if transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding devices are disregarded during the test period; and c) when necessary, disable activation of alarm notification appliances and speakers to prevent their sounding.

• Activate an Initiating Device Circuit using an alarm initiating device or an addressable initiating device on the SLC and check that all programmed active notification appliances function. Reset the alarm initiating device, the control panel, and any other associated equipment. In voice alarm applications, confirm that the proper tone(s) and/or messages sound during alarm conditions. Select the paging function and confirm that the message can be heard in the affected fire zones. Repeat the above step with each Initiating

Device Circuit and each addressable device.

NOTE:

SLC Resistance Values:

The total DC resistance of the SLC pair cannot exceed 50 ohms.

For instructions on how to measure the total DC resistance of a populated SLC pair, refer to the “Measuring Loop Resistance” section of the

SLC Wiring Manual

(P/N 51253).

The minimum DC resistance between conductors of an unpopulated SLC pair cannot be less than 1 K ohms.

Measure DC resistance on an unpopulated loop as shown in Figure 4.1 on page 25.

• Zero Ohms to ground will cause a ground fault.

• On systems equipped with a firefighter’s telephone circuit, make a call from a telephone circuit and confirm a ring indication.

Answer the call and confirm communication with the incoming caller. End the call and repeat for each telephone circuit in the system.

• Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or an addressable initiating device on the SLC, and check that programmed active notification appliances sound, and alarm indicators illuminate. Measure the battery voltage with notification appliances active. Replace any battery with a terminal voltage less than 21.6 V DC and reapply AC Power.

NOTE:

The battery test requires fully charged batteries. If batteries are new or discharged due to a recent power outage, allow the batteries to charge for 24 hours before testing.

• Return all circuits to their pretest condition.

• Check that all status LEDs are off and the green POWER LED is on.

• Notify fire, central station and/or building personnel when you finish testing the system.

Step 1. Disconnect the SLC channel B (Out) and SLC channel A (Return) at the control panel.

Step 2. Measure and record the resistance at SLC Out.

Step 3. Measure and record the resistance at SLC Return.

STEP 2

The minimum resistance is the lesser of two and three.

STEP 3

SLC Out

SLC Out

SLC Return

SLC Return

Figure 4.1 Measuring DC Resistance on an Unpopulated SLC Loop

4.2 Battery Checks and Maintenance

!

CAUTION:

THE MAXIMUM CURRENT RATING OF THE BATTERIES IS 11.6A. THE BATTERY CONNECTION IS FUSED. IF THE

FUSE NEEDS TO BE REPLACED, IT MUST BE REPLACED WITH A 20A BLADE FUSE.

Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water or electrolyte. These batteries are charged and maintained in a fully charged state by the main power supply's float charger during normal system operation. A discharged battery typically reaches the float voltage of 27.3 V DC within 24 hours.

Follow the manufacturer recommendations for battery replacement intervals. Minimal replacement battery capacity appears on the control panel marking label. Immediately replace a leaking or damaged battery. You can get replacement batteries from the manufacturer.

!

WARNING: BATTERIES CONTAIN SULFURIC ACID,

WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND DAMAGE TO FABRICS.

• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or eyes with water for at least 15 minutes.

Water and household baking soda provides a good neutralizing solution for Sulfuric Acid.

continued…

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 25

Testing the System

Battery Checks and Maintenance

• If Sulfuric Acid gets into eyes, seek immediate medical attention.

• Ensure proper handling of the battery to prevent short circuits.

• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools, bracelets, rings, and coins.

!

CAUTION:

SHORTING THE BATTERY LEADS CAN DAMAGE THE BATTERY, EQUIPMENT, AND COULD CAUSE

INJURY TO PERSONNEL.

!

CAUTION:

RISK OF EXPLOSION IF BATTERY IS REPLACED WITH INCORRECT TYPE.

DISPOSE OF BATTERY ACCORDING TO MANUFACTURER’S INSTRUCTIONS.

4.2.1 PSI Status

Pressing the PSI STATUS button will display the status of the local power supply. This information includes the supply voltage, battery voltage, PSI output voltage, which supply source the panel is running from (PSI or battery), whether a battery test is in progress and whether or not the battery test and charger have been disabled.

P S I S T A T U S

P S U V O L T A G E : 2 7 . 3 V

B A T T E R Y V O L T A G E : 2 4 . 2 V

P S I C O N T R O L S T A T U S :

P A N E L R U N N I N G F R O M P S I S U P P L Y

S T A R T B A T T E R Y T E S T

Figure 4.2 PSI Status Screen

B A C K

26

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Appendix A: Electrical Specifications

A.1 Operating Power

DC Power

The control panel requires connection to NPS-5CHS or NPS-11CHS, which is a 27.3 V DC regulated, power-limited power supply, that can supply 0.1 amps continuous for the CPU without the display (0.3 amps for CPU with the display).

A.2 SLC Loops

Listed below are specifications for a Signalling Line Circuit loop. Refer to the

SLC Wiring Manual

for more detailed specifications and specific device listings:

Item

Voltage

Maximum length

Maximum current

Maximum resistance

Value

24 V DC nominal, 27.6 V DC maximum

The maximum wiring distance of an SLC using 12 AWG (3.25 mm

2

) twisted-pair wire is 3810 m.

Note:

Refer to Appendix A.5 “Wire Requirements” for limitations.

130 mA: LCM-320

100 mA: LEM-320

400 mA max*: Single SLC loop; for battery calculations use 200 mA

*Max short circuit; circuit will shut down until short circuit condition is corrected.

50 ohms (supervised and power-limited). For additional notes on SLC resistance values, see Section 4.1

“Operational Checks”.

Table A.1

A.3 Notification Appliance Circuits

The power supply provides Notification Appliance Circuits. The maximum current rating for each NAC output is 1.0 A. Refer to the

Device Compatibility Document

for compatible devices and notification appliances.

A.4 Networks

Network Card

NCM-W

NCM-F

HS-NCM

Communication Parameters

Supports twisted-pair wire medium, data is regenerated at each node. 312.5K baud transmission rate.

Supports fibre-optic medium (62.5/125 or 50/125 micrometres – multimode). Single mode available. 312.5K baud transmission rate. Data is regenerated at each node.

High-speed data communications (12 Mb wire, 100 Mb MF/SF fibre). Multi-mode fibre optic

(MF), single-mode fibre optic (SF), wire (W), or a combination of W/MF/SF communications path.

Table A.2

A.5 Wire Requirements

Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to ensure proper circuit operation. The wire gauge of a particular circuit depends on the length of that circuit and the current traveling through it. Use the table below to determine the specific wiring requirements for each circuit.

Use twisted-pair shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in conduit. Use twistedpair unshielded wiring for SLC-loop wiring.

NOTE:

If running an SLC in conduit with Notification Appliance Circuits, you can reduce problems by exclusively using electronic sounders (such as the MA/SS-24 Series) instead of more electronically noisy notification appliances (such as electromechanical bells or horns).

Circuit Type

SLC

(power limited)

Circuit Function

Connects to intelligent and addressable modules.

or or

Wire Requirements

Twisted-unshielded pair, 12 to 18 AWG

(3.25 to 0.75mm

2

). 50 ohms, maximum per length of Closed (Style 6 & 7) loops.

50 ohms per branch maximum for Open

(Style 4) loops.

Twisted-shielded pair.

NOTE:

• Shields must be isolated from ground.

• Shields should be broken at each device.

Untwisted, unshielded wire, in conduit or outside of conduit.

3,810 m

2,896 m

Distance

(feet/meters)

1,829 m

1,128 m

1524 m

1,128 m

1524 m

1,128 m

NOTE:

Maximum total capacitance for

all

SLC wiring (both between conductors and from any conductor to ground) should not exceed 0.5 microfarads

Table A.3 Wire Requirements (1 of 2)

Typical Wire Type

12 AWG (3.31 mm

14 AWG (2.08 mm

16 AWG (1.31 mm

18 AWG (0.82 mm

2

)

2

)

2

)

2

)

12 to 16 AWG (3.31 mm

2

to 1.31 mm

2

)

18 AWG (0.82 mm

2

)

12 to 16 AWG (3.31 mm

2

to 1.31 mm

2

)

18 AWG (0.82 mm

2

)

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 27

Electrical Specifications

Power Supply Calculations

Circuit Type Circuit Function

EIA-485 ACS

Connection

(power limited)

EIA-485 RDP

Connection

(power limited)

EIA-232

(power limited)

IDC

Initiating Device

Circuit

NAC

Notification

Appliance Circuit

Connects to ACS devices such as annunciators and

UDACT/UDACT-2

Connects to RDP devices

Connects to Printers or PC.

FMM-1, FMM-101

(power limited)

FCM-1 (power limited)

Wire Requirements

Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG

(0.75mm

2

) minimum.

Distance

(feet/meters)

1829 m (max)

Twisted-shielded pair with a characteristic impedance of 120 ohms. 18 AWG

(0.75mm

2

) minimum.

Twisted-shielded pair. 18 AWG (0.75mm

2

) minimum.

12-18 AWG

Maximum circuit resistance is 20 ohms.

1219 m (max)

15.24 m without modem

Releasing

Module

FCM-1-REL

Typical Wire Type

16 AWG (1.31mm

2

16 AWG (1.31 mm

16 AWG (1.31

12 to 18 AWG mm

(3.31 to 0.82 mm

2

)

12-18 AWG. MPS-24A: At alarm current level, no more than a 1.2 V drop at the end of the circuit, or sized to provide the minimum rated operating voltage of the appliances used.

12-18 AWG. 5 ohms maximum per circuit for class A or B, or sized to provide the minimum rated operating voltage of the appliances used.

To meet 1.2 V drop, or sized to provide the minimum rated operating voltage of the appliances used.

To meet 5 ohms maximum circuit resistance, or sized to provide the minimum rated operating voltage of the appliances used.

12 to 18 AWG

(3.31 to 0.82 mm

2

)

12 to 18 AWG

(3.31 to 0.82 mm

2

)

2

2

)

)

)

24 VDC Power

Runs (powerlimited)

To TM-4 Transmitter,

Annunciator and

FCM-1 modules

12-18 AWG. Size wire so that no more than 1.2 V drop across wire run from supply source to end of any branch.

To meet 1.2 volt drop

Table A.3 Wire Requirements (2 of 2)

Relay Output circuits are “Common” 30 V DC, 2 A (see Section 3.6 “Form-C Relays on the CPU”).

12 to 18 AWG

(3.31 to 0.82 mm

2

)

A.6 Power Supply Calculations

Calculations must be done to determine standby and alarm DC current loads. Ampere-hour requirements must be calculated as well to determine battery size.

The NPS power supply provides filtered 24 V DC (nominal) power that may be used for operating external devices. The power for operating external devices is limited. Use Table A.4 to determine if external loading is within the capabilities of the power supply.

A.6.1 Calculating the System Current Draws

The NPS must be able to power all devices in the panel in either the alarm condition or quiescent condition. The NPS must also be able to provide enough current to charge the batteries when the panel is in the quiescent condition. Use column 1 in Table A.4 to calculate the

Quiescent Load on the power supply. Use column 2 in Table A.4 to calculate the additional current needed during the fire alarm condition.

A.6.2 How to Use the Calculating Tables

In the following section:

The term “secondary” refers to the system’s backup batteries

The term “primary” is reserved for the NPS’s primary source of power, 240 V AC 50 Hz

The term “standby” refers to the output current required when no fire alarm is present.

The term “alarm” refers to the output current required when a fire alarm is present.

The Primary Quiescent Current and Fire Alarm Current columns are DC current calculations. Use these calculations to confirm that the

NPS can provide enough current to support the system during Primary Quiescent and Fire Alarm conditions.

Quantities

List the number of devices powered by the MAIN 24 V Main Output on the NPS and any auxiliary 24 V Outputs. Use these quantities to calculate total current draw of each set of devices in calculation columns 1, 2, and 3.

Calculation Column 1 (Primary, Quiescent Current in amps)

Add the contents of Column 1 to get the current drawn from the NPS during a quiescent condition, with AC power applied.

Calculation Column 2 (Primary, Fire Alarm Current in amps)

Column 2 lets the system designer determine the current load that the

NPS must support during a fire alarm.

Typically, a system should contain capacity to activate all output circuits and relays, and support fire alarms on no less than 10% of Initiating Device Circuits.

If the system provides power for Notification Appliance Circuits, refer to the Device Compatibility Document for 24 V DC notification appliances.

NOTE:

A current calculation tool can also be found in the Download Centre on the Notifier website: http://www.notifier.com.au/

28

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Power Supply Calculations

Electrical Specifications

A.6.3 Calculation for Main Supply Current

Quantitie s

AFP-3030/NCA-2 with display

AFP-3030/NCA-2 without display

LCM-320 (refer to Doc. 51330,52544)

LEM-320 (refer to Doc. 51330,52544)

SLC Loop

*

NCM-W, NCM-F

HS-NCM-W/MF/MFSF/WMF/WSF

DVC components (Refer to DVC manual)

DVC-RPU components (Refer to DVC-RPU manual)

DA-30/DA-60/DA-120 (Refer to DOC-01-

004)

FSD-751RPL (Duct Detector)

FSA-8000/FSA-20000 (FAAST Detector)

ACM-24AT

ACM-48A

AEM-24AT

AEM-48A

Maximum number of LEDs illuminated on these annunciators during quiescent conditions:

SCS-8A (refer to Doc. 15712)

LCD2-80

ACM-8RA

LDM (refer to Doc. 15885)

ACM-ZM

AEM-ZM8

ARM (Refer to DOC-01-005)

ARE Interface

FZM-1, MMX-2

Four-Wire Smoke Detectors

Compatible Devices not listed above

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

[ ]

Calculation Column 1

Primary, Quiescent

Current (amps) x [0.205]= x [0.140]= x [0.130]= x [0.100]= x [0.200]= x [0.110]= x [0.400]= x [ ]= x [ ]= x [ ]= x [ ]= x [0.025]= x [0.465]= x [0.016]= x [0.016]= x [0.002]= x [0.002]= x [0.0054]= x [ ]= x [0.100]= x [ 0.020]= x [ ]= x [0.020]= x [0.005]= x [ ]= x [0.020]= x [0.0094]= x [ ]= x [ ]= x [ ]= x [ ]=

Calculation Column

2

Primary, Fire Alarm

Current (amps) x [0.225]= x [0.150]= x [0.130]= x [0.100]= x [0.200]= x [0.110]= x [0.400]= x [ ]= x [ ]= x [ ]= x [ ]= x [0.087]= x [0.493]= x [0.070]= x [0.070]= x [0.056]= x [0.056]= x [ ]= x [0.100]= x [0.035]= x [ ]= x [0.025]= x [0.025]= x [ ]= x [0.035]= x [0.090]= x [ ]= x [ ]= x [ ]= x [ ]=

Battery

Sum each column for totals

[ ]

Quiescent: x [AH

] x

[0.1]=

Primary,

Quiescent: alarm:

Primary, alarm:

Table A.4 System Draw Current Calculations

* Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current draws. Total device current cannot exceed 200 mA.

† Refer to manual and/or Device Compatibility Document.

‡ Value represents battery size in amp hours. Refer to

Appendix A.7, “Calculating the Battery Requirements”, on page 30

to determine battery size.

A.6.4 Calculating the Maximum Secondary Power Quiescent Current Draw

Use the table below to determine the maximum current requirements of the secondary power source during quiescent conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table A.5 to determine the size of the batteries needed for the fire alarm system.

Results taken from the table below assume that, while in a quiescent condition, batteries must feed the NPS (and any additional supplies) with the maximum rated power each supply can provide.

Device Quantity

Alarm Current

(in amps)

Alarm Current, from Table A.4, col 3

Additional Load [ ] X

=

=

Sum Column for Secondary Quiescent Load =

Total Current/Type

Table A.5 Maximum Secondary Power Quiescent Current Draw

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 29

Electrical Specifications

Calculating the Battery Requirements

A.6.5 Calculating the Maximum Secondary Power Fire Alarm Current Draw

Use the table below to determine the maximum current requirements of the secondary power source during fire alarm conditions. The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table A.6 to determine the size of the batteries needed for the fire alarm system.

Results taken from the table below assume that, while in a fire alarm condition, batteries must feed the NPS (and any additional supplies) with the maximum rated power each supply can provide.

Device Quantity

Alarm Current

(in amps)

Alarm Current, from Table A.4, col 2

Additional Load [ ] X

=

=

Sum Column for Secondary Fire Alarm Load =

Total Current/Type

Table A.6 Maximum Secondary Power Fire Alarm Current Draw

A.7 Calculating the Battery Requirements

A.7.1 Battery Power Equations

To calculate the battery size in accordance with AS 1670.0-2004, use the formula below:

C

20

= 1.25 [(I

Q

x T

Q

) + F

C

(I

A

x T

A

)]

Where:

C

20

I

Q

T

Q

F

C

I

A

T

A

1.25

=

=

=

=

=

=

= battery capacity in Ah at 20 h discharge rate total quiescent current quiescent standby power source time (normally 24 h) capacity de-rating factor total current in alarm state alarm load standby power source time (normally 0.5 h) compensation factor for expected battery deterioration

Where the load may vary, the worse case average over required period shall be used.

A.7.2 Recommended Standby Battery Sizes

When selecting and installing batteries, ensure that there is enough available current to charge the batteries while in quiescent mode. A list of available batteries and the minimum charging current required is shown in Table A.7, “Recommended Battery Specifications”.

NOTE:

Connect only sealed lead acid batteries.

Battery Description

Olympic, 12 AH 12 V Battery -

BATT/12 (CJ12-12)

Olympic, 18 AH 12 V Battery -

BATT/18 (CJ12-18)

Olympic, 26 AH 12 V Battery -

BATT/26 (CJ12-26)

Olympic, 33 AH 12 V Battery -

BATT/33 (CJ12-33)

Olympic 40 AH 12 V Battery -

BATT/40 (CJ12-40)

Olympic 85 AH 12 V Battery -

BATT/85 (CJ12-85)

Voltage

12

Capacity (Ah)

Minimum

Charging Current (A)

12 0.44

12

12

12

12

12

18

26

33

40

85

0.66

0.95

1.21

1.46

3.11

Table A.7 Recommended Battery Specifications

2

2

2

2

2

2

Quantity

30

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Appendix B: Cabinet and Mounting Information

B.1 CAB650 Mounting Details

450.0

192.0

170.0

10 x D50.0

Lasercut Knockout

5 on top, 5 on bottom

4 x D25.0

Lasercut Knockout

2 on top, 2 on bottom

4 x D10.0

Mounting Holes

4 x D5.0

Laser cut

Knockout

0.0

35.0

265.0

140.0

260.0

380.0

410.0

405.0

370.0

140.0

2 x D25.0

Laser cut

Knockout

610.0

212.0

4 x D50.0

Laser cut

Knockout

NOTE:

All dimensions in Millimetres

Figure B.1 CAB650 Mounting Details and Dimensions

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 31

Cabinet and Mounting Information

B.2 CAB900 Mounting Details

CAB900 Mounting Details

192

10 x D50.0

Laser cut knockouts

5 on top, 5 on bottom

4 x D25.0

Laser cut knockouts

2 on top, 2 on bottom

4 x D5.0

Laser cut

Knockouts

0.0

35.0

140.0

260.0

380.0

450.0

410.0

405.0

370.0

140.0

265.0

4 x D50

Laser cut

Knockouts

4 x D10

Mounting holes

4 x D25

Laser cut

Knockouts

515.0

860.0

212

NOTE:

All dimensions in Millimetres

Figure B.2 CAB900 Mounting Details and Dimensions

32

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

CAB 18U Cabinet Mounting Dimensions

B.3 CAB 18U Cabinet Mounting Dimensions

Cabinet and Mounting Information

35.0

105.0

286.0

16 x 50.0

Lasercut Knockout

8 on top, 8 on bottom

70.0

380.0

540.0

610.0

550.0

380.0

343.0

70.0

4 x 10.0

306.0

8 x 50.0

Laser cut

Knockout

NOTE:

All dimensions in Millimetres

Figure B.3 CAB 18U Mounting Details and Dimensions

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

767.0

271.9

817.0

887.0

2 x 25.0

Laser cut

Knockout

33

Cabinet and Mounting Information

B.4 CAB 28U Cabinet Mounting Dimensions

16 x 50.0

Lasercut Knockout

8 on top, 8 on bottom

CAB 28U Cabinet Mounting Dimensions

70.0

380.0

540.0

610.0

550.0

380.0

343.0

70.0

35.0

115.0

376.0

2 x 25.0

Laser cut

Knockout

175.1

1210.0

1260.0

1330.0

34

4 x 10.0

Mounting

Holes

8 x 50.0

Laser cut

Knockout

NOTE:

All dimensions in Millimetres

Figure B.4 CAB 28U Cabinet Mounting Details and Dimensions

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

CAB 40U Cabinet Mounting Dimensions

B.5 CAB 40U Cabinet Mounting Dimensions

Cabinet and Mounting Information

376.0

16 x 50.0

Lasercut Knockout

8 on top, 8 on bottom

8 x 50.0

Laser cut

Knockout

70.0

380.0

540.0

610.0

550.0

380.0

343.0

70.0

35.0

105.0

4 x 10.0

2 x 25.0

Laser cut

Knockout

1745.0

707.5

1795.0

1865.0

NOTE:

All dimensions in Millimetres

Figure B.5 CAB 40U Cabinet Mounting Details and Dimensions

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 35

Cabinet and Mounting Information

Laying Out Equipment in Cabinet and Chassis

B.6 Laying Out Equipment in Cabinet and Chassis

The AFP-3030 allows for flexible system design. It mounts in a CAB650 or CAB900 backbox using the CHS-3L or in a U-Series backbox using the CHS-4L. Follow these guidelines when deciding where to locate equipment in the backbox. The number of layers that can be mounted in each position of the chassis depends on the module size.

!

CAUTION:

IT IS CRITICAL THAT ALL MOUNTING HOLES OF THE FIRE ALARM CONTROL PANEL ARE SECURED

WITH A SCREW OR STAND-OFF TO INSURE CONTINUITY OF EARTH GROUND.

CHS-3L

The CPU and power supply assembly mount in the top row of the

CAB650 or CAB900 cabinet. The AFP-3030 keypad is door mounted in front of the CPU and power supply assembly. The CHS-

3L Chassis is mounted below the CPU and power supply assembly.

In the CAB900, a second CHS-3L Chassis can be installed below the first for additional equipment.

Three positions on chassis

CHS-3L

1

2

3

CHS-4L

The CPU and power supply assembly mount in the top row of the

U-Series cabinet. The AFP-3030 keypad is door mounted in front of the CPU and power supply assembly. The CHS-4L Chassis is mounted below the CPU and power supply assembly.

In the 28U and 40U cabinets, additional CHS-4L Chassis can be installed below the first for additional equipment.

Four positions on chassis

CHS-3L

Figure B.6 Chassis CHS-3L

1

2

3

4

Figure B.7 Chassis CHS-4L

B.7 Installing Replacement Equipment

B.7.1 Installing a replacement keypad

The keypad enables the user to operate and program the fire panel.

CAUTION: POWER DOWN THE FIRE PANEL BEFORE FITTING THE KEYPAD.

!

1.

Open the cabinet inner door and unplug the ribbon cable connecting the keypad to the CPU board.

2.

From the cabinet inner door, remove: a. The flanged nuts from the inner door studs.

36

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Installing Replacement Equipment

b. The keypad from the studs as per Figure B.8.

The AFP-3030 keypad

Cabinet and Mounting Information

Door studs

Cabinet inner door

Flanged nuts

Ribbon cable connecting the keypad to the fire panel CPU.

Figure B.8 Removing the fire panel keypad

3.

Replace keypad on door studs.

4.

Replace the Flanged nuts, fastening the keypad to the door.

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 37

Notes

38

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

Index

I

Numerics

2020-06-26 E159443 - ADD "with isolator"

A

Alarm Relays

BMP-1

36

C

D

Doors

8

,

10

Dress Panels

8

DS-DB

29

DVC-RPU

29

H

HS-NCM-W/F

Installation

L

see

B

Backboxes

8

,

10

Checklist

12

Preparation

Relays

E

Electrical Connections

18

Mounting

14

12

CPU

8

Drawing

8

Installation Steps

36

17

Battery

Battery Calculations

27

,

28

,

29

30

Battery Checks

25

Memory-Backup Battery

13

Cabinets,

also see

Backboxes

8

,

36

Chassis

CHS-3L

36

Circuit Board,

also see

CPU

8

Control Panel Circuit Board,

also see

CPU

8

Electrical Specifications

27

Indicating Device Circuits,

also see

NACs

27

LCM-320/LEM-320,

see

SLC Loop Modules

11

M

Main Power Supply

10

Maintenance

25

Manual Pull Station

23

Memory-Backup Battery

Insulator

13

N

NACs

Specifications

27

NCM-W/F

Mounting

14

Networking

14

Notification Appliance Circuits,

also see

NACs

27

O

Operating Power

27

Operational Checks

25

Output Relays,

also see

Form-C Relays

Specifications

17

P

PC Connection

24

Power

AC Power Checklist

21

Auxiliary Power

22

Installation Steps

18

Locally Powered Devices

19

Main Power Supply

10

Power Supply Calculations

27

,

28

,

29

30

PSU Switch

21

Remote Device Powered By Local Device

19

Specifications

18

Terminating mains supply

18

Printers

23

Installation

22

PRN Printer Settings

23

R

Related Documentation

5

S

Signalling Line Circuit,

also see

SLC

23

SLC Loop Modules

SLC Loop Number

15

SLC,

also see

SLC Wiring Manual

Specifications

27

Specifications

27

Environmental Specifications

7

Supply Ratings

7

Supervisory Relays,

also see

Relays

17

Supplemental Documentation

5

System

Features

7

Limitations

7

Options

7

System Description

7

System Current Draws

27

,

28

,

29

30

T

Testing

25

Trouble Relays,

also see

Relays

17

U

Upload/Download Software

24

V

VeriFire® Tools

24

W

Wiring,

also see

SLC

23

Wire Requirements

27

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14 39

Index

40

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

AFP-3030 Installation Manual —

P/N DOC-01-031:H 2020-07-14

New South Wales

(Head Office)

9 Columbia Way

Baulkham Hills NSW

2153 ph +61 (0)2 9894-1444 www.notifier.com.au

New Zealand

56 Cawley St Potts Street

AUCKLAND, NZ

1051 ph +64 (0)9 623-5275 www.notifier.co.nz

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement