Westinghouse FSA1BF Installation Instruction


Add to my manuals
20 Pages

advertisement

Westinghouse FSA1BF Installation Instruction | Manualzz
SPLIT SYSTEM AIR CONDITIONER
16 SEER
INSTALLATION INSTRUCTIONS
*SA1BF4M2SN - 24K, 36K, 48K, & 60K (2, 3, 4, & 5 TON) SERIES - SINGLE PHASE MODELS
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better
than your customer. This includes being able
to install the product according to strict safety
guidelines and instructing the customer on how
to operate and maintain the equipment for the
life of the product. Safety should always be the
deciding factor when installing this product and
using common sense plays an important role as
well. Pay attention to all safety warnings and any
other special notes highlighted in the manual.
Improper installation of the unit or failure to follow
safety warnings could result in serious injury,
death, or property damage.
These instructions are primarily intended to assist
qualified individuals experienced in the proper
installation of this appliance. Some local codes
require licensed installation/service personnel for
this type of equipment. Please read all instructions
carefully before starting the installation. Return
these instructions to the customer’s package for
future reference.
DO NOT DESTROY. PLEASE READ CAREFULLY &
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT SAFETY INFORMATION.......................... 2
AIR CONDITIONER INSTALLATION............................. 3
General Information....................................................... 3
Before You Install this Unit............................................. 3
Locating the Air Conditioner........................................... 3
Packaging Removal....................................................... 3
Ground Level................................................................. 3
Roof Mount.................................................................... 3
Connecting Refrigerant Tubing Between the Indoor
& Outdoor Unit............................................................... 3
ELECTRICAL WIRING................................................... 4
Pre-Electrical Checklist.................................................. 4
Line Voltage................................................................... 4
CoreSenseTM Diagnostics Module................................. 4
Compressor Protection................................................. 5
Resetting Alert Codes................................................... 5
Grounding...................................................................... 5
Thermostat Connections................................................ 5
START UP & ADJUSTMENTS....................................... 6
Pre-Start Check List....................................................... 6
Start-Up Procedures...................................................... 6
Air Circulation - Indoor Blower...................................... 6
System Cooling............................................................. 6
System Heating (optional)............................................ 6
AIR CONDITIONER MAINTENANCE............................. 6
Panel Removal............................................................... 6
Panel Installation............................................................ 6
REFRIGERANT CHARGING.......................................... 7
Charging the Unit in AC mode....................................... 8
If the outdoor temperature is 65 degrees F or higher:.. 8
If the outdoor temperature is below 65 degrees F:....... 8
WIRING DIAGRAMS & TABLES.................................... 9
Figure 6. Wiring Diagram for *SA1BF4M2SN
(2 Ton Units Without CoreSenseTM)............... 9
Figure 7. Wiring Diagram for *SA1BF4M2SN
(2 Ton Units With CoreSenseTM).................... 10
Figure 8. Wiring Diagram for *SA1BF4M2SN
(3 Ton Units Without CoreSenseTM)............... 11
Figure 9. Wiring Diagram for *SA1BF4M2SN
(3 Ton Units With CoreSenseTM).................... 12
Figure 10. Wiring Diagram for *SA1BF4M2SN
(4 & 5 Ton Units Without CoreSenseTM)...... 13
Figure 11. Wiring Diagram for *SA1BF4M2SN
(4 & 5 Ton Units With CoreSenseTM)........... 14
CORESENSETM TROUBLESHOOTING......................... 15
Table 1. CoreSenseTM LED Diagnostics........................ 15
INSTALLATION CHECKLIST......................................... 20
REPLACEMENT PARTS................................................ 20
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury or
death. CAUTION indicates a potentially hazardous situation
that if not avoided, may result in minor or moderate injury or
property damage.
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical power
to the equipment.
• When servicing controls, label all wires prior
to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
WARNING:
This split system air conditioner is shipped
charged with R410A refrigerant and ready
for installation. If repairs make it necessary
for evacuation and charging, it should only
be attempted by qualified trained personnel
thoroughly familiar with this equipment. Under
no circumstances should the owner attempt to
install and/or service this equipment. Failure to
comply with this warning could result in property
damage, personal injury, or death.
WARNING:
Unless noted otherwise in these instructions,
only factory authorized parts or accessory
kits may be used with this product. Improper
installation, service, adjustment, or maintenance
may cause explosion, fire, electrical shock or
other hazardous conditions which may result in
personal injury or property damage
2
CAUTION:
This unit uses R-410A refrigerant. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.
WARNING:
The information listed below and the next page
must be followed during the installation, service,
and operation of this furnace. Failure to follow
safety recommendations could result in possible
damage to the equipment, serious personal
injury or death.
• The installer must comply with all local codes and
regulations which govern the installation of this type of
equipment. Local codes and regulations take precedence
over any recommendations contained in these instructions.
Consult local building codes and the National Electrical
Code (ANSI CI) for special installation requirements.
• All electrical wiring must be completed in accordance with
local, state and national codes and regulations and with
the National Electric Code (ANSI/NFPA 70) or in Canada
the Canadian Electric Code Part 1 CSA C.22.1.
• This equipment contains liquid and gaseous refrigerant
under high pressure. DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by
qualified trained personnel thoroughly familiar with this
type equipment.
• Fully annealed, refrigerant grade copper tubing should
be used when installing the system. Refrigerant suction
line tubing should be fully insulated.
• Installation of equipment may require brazing operations.
Installer must comply with safety codes and wear
appropriate safety equipment (safety glasses, work
gloves, fire extinguisher, etc.) when performing brazing
operations.
• Follow all precautions in the literature, on tags, and on
labels provided with the equipment. Read and thoroughly
understand the instructions provided with the equipment
prior to performing the installation and operational checkout
of the equipment.
• Refrigerant and electrical line should be routed through
suitably waterproofed openings to prevent water from
leaking into the structure.
• This unit is designed for outdoor installations only and
should be positioned as shown on page 3.
AIR CONDITIONER INSTALLATION
6” from Building
or Structure
General Information
The *SA1BF4M2SN series air conditioner is designed only
for outdoor rooftop or ground level installations. This unit
has been tested for capacity and efficiency in accordance
with AHRI Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and create
unsafe hazards.
To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain mechanical
skills and tools.
24" for
Service Access
12" or 18”
See Note
DO NOT
OBSTRUCT
TOP OF UNIT
12" or 18”
See Note
NOTE: Units require full perimeter clearances.
Installer must maintain 18” between two units
or 12” between single unit and structure.
Before You Install this Unit
√ The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
√ Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
√ The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to the
indoor unit's installation instructions for installation details.
√ All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior
to installing the equipment at the job site. Verify coil fins
are straight. If necessary, comb fins to remove flattened
or bent fins. Claims for damage (apparent or concealed)
should be filed immediately with the carrier.
√ Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read all
instructions before installing the unit.
Locating the Air Conditioner
• Survey the job site to determine the best location for
mounting the outdoor unit.
• The outdoor unit should be installed no closer than 18
inches from the outside walls of the facility and in an area
free from overhead obstructions to ensure unrestricted
airflow through the outdoor unit.
• Sufficient clearance for unobstructed airflow through the
outdoor coil must be maintained in order to achieve rated
performance. See Figure 1 for minimum clearances to
obstructions.
• Overhead obstructions (Figure 1), poorly ventilated areas,
and areas subject to accumulation of debris should be
avoided.
• Consideration should be given to availability of electric
power, service access, noise, and shade.
Packaging Removal
NOTE: To prevent damage to the tubing connections, carefully
remove the carton and user’s manual from the equipment.
Discard the shipping carton.
Ground Level
Ground level installations must be located according to local
building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown in
Figure 1.
48”
2” Mounting Pad
Figure 1. Clearance Requirements
• A suitable mounting pad (Figure 1) must be provided and
separate from the building foundation. The pad must be
level and strong enough to support the weight of the unit.
The slab height must be a minimum of 2” (5 cm) above
grade and with adequate drainage.
Roof Mount
• The method of mounting should be designed so that it
does not overload roof structures or transmit noise to
the interior of the structure. The roof must be structurally
capable of handling the weight of the unit.
• Full perimeter support is required under the unit. Support
must be made of weather resistant materials and installed
prior to unit installation.
• The support must be built to raise the unit 6" above the
roof.
Connecting Refrigerant Tubing Between the Indoor
& Outdoor Unit
CAUTION:
When servicing, cover or seal openings to
minimize the exposure of the refrigerant system
to air to prevent accumulation of moisture and
other contaminants.
After outdoor and indoor unit placement has been determined,
route refrigerant tubing between the equipment in accordance
with sound installation practices.
3
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be flowing through the
joints during brazing to prevent internal oxidation and
scaling.
• Refrigerant tubing should be routed in a manner that
minimizes the length of tubing and the number of bends
in the tubing. If precise forming of refrigerant lines is
required, a copper tubing bender is recommended. Avoid
sharp bends and contact of the refrigerant lines with metal
surfaces.
• Refrigerant tubing should be supported in a manner
that the tubing will not vibrate or abrade during system
operation.
• Tubing should be kept clean of foreign debris during
installation.
• Every effort should be made by the installer to ensure
that the field installed refrigerant containing components
of the system have been installed in accordance with
these instructions and sound installation practices to
insure reliable system operation and longevity.
• The maximum recommended interconnecting refrigerant
line lengths is 75 ft. and the vertical elevation difference
between the indoor and outdoor sections should not
exceed 20 ft.
• A filter dryer is provided with the unit and must be
installed in the liquid line of the system. If the installation
replaces a system with a filter dryer already present in the
liquid line, the filter dryer must be replaced with the one
supplied with the unit. The filter dryer must be installed
in strict accordance with the manufacturer’s installation
instructions.
• Optional equipment such as liquid line solenoid valves,
low ambient, etc., should be installed in strict accordance
with the manufacturer’s installation instructions.
ELECTRICAL WIRING
WARNING:
To avoid risk of electrical shock, personal
injury, or death, disconnect all electrical power
to the unit before performing any maintenance
or service. The unit may have more than one
electrical supply.
Label all wires prior to disconnection when
servicing the unit. Wiring errors can cause
improper and dangerous operation.
• All electrical connections must be in compliance with
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
√ Verify that the voltage, frequency, and phase of the supply
source match the specifications on the unit rating plate.
√ Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper voltage wiring.
4
√ Verify factory wiring is in accordance with the unit wiring
diagram See Figure 6 (page 9), Figure 7 (page 10),
Figure 8 (page 11), Figure 9 (page 12), Figure 10
(page 13), & Figure 11 (page 14). Inspect for loose
connections.
Line Voltage
• A wiring diagram is located on the inside cover of the
electrical box of the outdoor unit. The installer should
become familiar with the wiring diagram before making
any electrical connections to the outdoor unit.
• An electrical disconnect must be located within sight
of and readily accessible to the unit. This switch shall
be capable of electrically de-energizing the outdoor unit.
• Line voltage to the unit should be supplied from a dedicated
branch circuit containing the correct fuse or circuit breaker
for the unit. Incoming field wiring and minimum size of
electrical conductors and circuit protection must be in
compliance with information listed on the outdoor unit
data label. Any other wiring methods must be acceptable
to authority having jurisdiction.
• The outdoor unit requires both power and control circuit
electrical connections. Refer to the wiring diagram /
schematic for identification and location of outdoor unit
field wiring interfaces See Figure 6 (page 9), Figure 7
(page 10), Figure 8 (page 11), Figure 9 (page 12),
Figure 10 (page 13), & Figure 11 (page 14). Make
all electrical connections in accordance with all applicable
codes and ordinances.
• Overcurrent protection must be provided at the branch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes. See
the unit rating plate for minimum circuit ampacity and
maximum overcurrent protection limits.
• Provide power supply for the unit in accordance with the
unit wiring diagram, and the unit rating plate. Connect the
line-voltage leads to the terminals on the contactor inside
the control compartment.
• Use only copper wire for the line voltage power supply to
this unit in strict accordance of the NEC (ANSI/NFPA 70),
applicable local codes, and the instructions provided with
the equipment. Use proper code agency listed conduit
and a conduit connector for connecting the supply wires
to the unit. Use of rain tight conduit is recommended.
• 208/230 Volt units are shipped from the factory wired for
230 volt operation. For 208V operation, remove the lead
from the transformer terminal marked 240V and connect
it to the terminal marked 208V.
• Optional equipment requiring connection to the power or
control circuits must be wired in strict accordance of the
NEC (ANSI/NFPA 70), applicable local codes, and the
instructions provided with the equipment.
CoreSenseTM Diagnostics Module
(Select Models Only)
The CoreSenseTM Diagnostics Module (Figure 2) is a
breakthrough innovation for troubleshooting heat pump and
air conditioning system failures. The module installs easily
in the electrical box of the outdoor unit near the compressor
contactor.By using the compressor as a sensor, CoreSense
Diagnostics helps the service technician more accurately
troubleshoot system and compressor fault conditions.
A flashing LED indicator communicates the ALERT code
and a diagnostic key is also imprinted on the side of the
module to quickly direct the technician to the root cause of
a problem. Alert identification codes are also listed in Table
1, (page 15).
Compressor Protection
The CoreSenseTM Diagnostics module utilizes proprietary
algorithms to protect the compressor and system from
repeated trips of system pressure controls and the compressor
internal overload. The protection terminal of the module should
be wired in series with the system low pressure and high
pressure cutouts, as well as the compressor contactor. When
the module detects a series of trips as described below, it
will activate a lockout feature that opens the normally closed
protection contacts in the module, thereby cutting power to
the contactor and shutting off the compressor.
Power LED
Y2 (Thermostat 2nd Stage Demand)
Y (Thermostat Demand)
Data Port
Resetting Alert Codes
When the CoreSenseTM Diagnostics module has detected a
series of adverse conditions that have caused it to lockout
the compressor, and after the issue has been resolved, it
is necessary to manually reset the module in order to clear
the present alert code.
The primary way of clearing the code and resetting the alert
is to press the reset button located on the module.
NOTE: Pressing the reset will require a pin or a mini electronics
screwdriver. This button must be pressed and held for a
minimum of one second for the module to be reset. Pressing
the reset button clears the immediate lock code and the seven
day operating history. It will not clear the permanent module
history. In the case of the three-wire module, the codes can
be reset or cleared by cycling power to the module. This can
be done by disengaging the Common (C) terminal. This will
not clear the seven day operating history.
Grounding
WARNING:
L (Alert)
R (24VAC)
C (Common)
Prot (Contactor Cutout)
DC SOL (2nd Stage Solenoid Power)
Alert LED (Yellow)
Trip / Lock LED (Red)
Figure 2. CoreSenseTM Diagnostics Module
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground!
This unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical
Code. Use the grounding lug provided in the control box for
grounding the unit.
Thermostat Connections
Thermostat
O Y2 Y G RC RH C W2 W/E
R
C
C
Y/Y2
Y/Y2
Y1
Y1
G
Air Conditioner
OD Section
(Without CoreSense)
W2
W1
Furnace
• Thermostat connections should be made in accordance
with the instructions supplied with the thermostat and the
indoor equipment. Typical AC and thermostat hookups
are shown in Figure 3.
• The outdoor unit is designed to operate from a 24 VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/NFPA
70) and with applicable local codes having jurisdiction.
• The low voltage wires must be properly connected to the
units low voltage terminal block.
• The thermostat should be mounted about 5 feet above the
floor on an inside wall. DO NOT install the thermostat on
an outside wall or any other location where its operation
may be adversely affected by radiant heat from fireplaces,
sunlight, or lighting fixtures, and convective heat from
warm air registers or electrical appliances. Refer to the
thermostat manufacturer’s instruction sheet for detailed
mounting and installation information.
NOTE: FOR THE MATCH
*SA1BF4MN2SN24K + C6B(A,H)-X30(C,U)-C + *G7T-C
*SA1BF4MN2SN24K + C6B(A,H)-X30(C,U)-C + *G7S-C+*SHE
Only connect Y2 from thermostat to OD Y2
Figure 3. Typical 2-Stage Air Conditioner
(without CoreSense) with Gas Furnace
5
START UP & ADJUSTMENTS
AIR CONDITIONER MAINTENANCE
Pre-Start Check List
√ Verify the indoor unit is level and allows proper condensate
drainage.
√ Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/control
panels are in place.
√ Verify air filters are cleaned and properly installed.
√ Verify duct work is sealed to prevent air leakage.
√ Verify line voltage power leads are securely connected
and the unit is properly grounded.
√ Verify low voltage wires are securely connected to the
correct leads on the low voltage terminal strip.
√ Verify power supply branch circuit overcurrent protection
is sized properly.
√ Verify the thermostat is wired correctly.
Start-Up Procedures
The thermostat's function mode should be set to OFF and
the fan mode should be set to AUTO. Close all electrical
disconnects to energize the sy stem.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan mode
to ON.
2. Verify the blower runs continuously. Check the air delivery
at the supply registers and adjust register openings for
balanced air distribution. If insufficient air is detected,
examine ductwork for leaks or obstructions.
3. Set the thermostat fan mode to AUTO and verify the blower
stops running.
WARNING:
To prevent electrical shock, personal injury, or
death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical supply.
Proper maintenance is important to achieve optimum
performance from the air conditioner. The ability to properly
perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these
skills, contact your dealer for maintenance. Consult your
local dealer about the availability of maintenance contracts.
Routine maintenance should include the following:
• Inspect and clean or replace air filters at the beginning
of each heating and cooling season, or more frequently
if required.
• Inspect the condensate drain and outdoor coil at the
beginning of each cooling season. Remove any debris.
Clean the outdoor coil and louvers as necessary using a
mild detergent and water. Rinse thoroughly with water.
• Inspect the electrical connections for tightness at the
beginning of each heating and cooling season. Service
as necessary.
• To access the internal compnents of the unit, refer to Figure
4 for panel removal and Figure 5 for panel installation.
CAUTION:
System Cooling
1. Set the thermostat’s system mode to COOL and the
fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and verify
the outdoor unit and indoor blower energize.
2. Verify blower wheel is spinning in direction indicated by
arrow. Feel the air being circulated by the indoor blower
and verify that it is cooler than ambient temperature. Listen
for any unusual noises. If unusual sounds occur, determine
the source of the noise and correct as necessary.
3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes and then
set the temperature selector above room temperature.
Verify the fan and compressor cycle off with the thermostat.
NOTE: The blower should also stop unless fan mode is
set to the ON position.
System Heating (optional)
1. Set the thermostat's system mode to HEAT and the
temperature mode above room temperature.
2. Verify the optional heating equipment (furnace or electric
heat) and indoor blower energize. Feel the air being
circulated by the indoor blower and verify that it is warmer
than ambient temperature. Listen for any unusual noises.
If unusual sounds occur, determine the source of the noise
and correct as necessary.
6
The unit should never be operated without a
filter in the return air system. Replace disposable
filters with the same type and size.
• Do not attempt to add additional oil to motors unequipped
with oil tubes. The compressor is hermetically sealed at
the factory and does not require lubrication.
• To access the internal compnents of the unit, refer to Figure
4 for panel removal and Figure 5 for panel installation.
Panel Removal
1. Remove screws securing the panel.
2. Slide the panel up towards the top pan in order to clear
the bottom flange from the base pan. See Figure 4.
3. Swing the bottom of the panel out and pull the panel down
to remove it from the unit.
Panel Installation
1. Insert the top corners of side panel flanges into the corner
post channels as shown in Detail A in Figure 5.
2. Slide the panel up into the top pan. (You may need to push
on the center of the panel at the top in order to clear the
top pan edge).
3. Swing the panel in and push down until the panel is resting
on the top edge of the base pan wall as shown in Detail
B.
4. Insert screws into the panel to secure it to the unit.
REFRIGERANT CHARGING
WARNING:
*SA1BF4M2SN Split System Air Conditioners
are shipped charged with R410A refrigerant
and ready for installation. If repairs make it
necessary for evacuation and charging, it should
only be attempted by qualified trained personnel
thoroughly familiar with this equipment. Under
no circumstances should the owner attempt to
install and/or service this equipment. Failure to
comply with this warning could result in property
damage, personal injury, or death.
Figure 4. Panel Removal
DETAIL A
DETAIL B
Figure 5. Panel Installation
After refrigerant line connections are completed, it is required
that you leak check and evacuate the indoor section and all
line connections (using proper methods) before finalizing the
full system refrigerant charge.
• *SA1BF4M2SN outdoor units with non-AHRI listed indoor
coils are not recommended. Deviations from rated airflows
or non-listed combinations may require modification to the
expansion device and refrigerant charging procedures for
proper and efficient system operation.
• The refrigerant charge can be checked and adjusted
through the service ports provided external to the outdoor
unit. Use only gage line sets which have a “Schrader”
depression device present to actuate the valve.
• A high-pressure switch is factory-installed and located in the
liquid line internal to the outdoor unit.The switch is designed
to protect the system when very high pressures occur
during abnormal conditions. Under normal conditions,
the switch is closed. If the liquid pressure rises above
575 psig, then the switch will open and de-energize the
outdoor unit. The switch will close again once the liquid
pressure decreases to 460 psig. Please note that the
switch interrupts the thermostat inputs to the unit. Thus,
when the switch opens and then closes, there may be a
5 minute short cycling delay before the outdoor unit will
energize.
• On select models a low-pressure switch is factory-installed
and located in the suction line internal to the outdoor unit.
The switch is designed to protect the compressor from
a loss of charge. Under normal conditions, the switch is
closed. If the suction pressure falls below 5 psig, then the
switch will open and de-energize the outdoor unit. The
switch will close again once the suction pressure increases
above 20 psig. Please note that the switch interrupts the
thermostat inputs to the unit. When the switch opens and
then closes, there will be a 5 minute short cycling delay
before the outdoor unit will energize.
7
Charging the Unit in AC mode
If the outdoor temperature is 65 degrees F or higher:
After completing the refrigerant line connections, leak checking the system, and evacuating the indoor section and all line
connections (using proper methods), perform the following steps:
1. Determine the recommended charge addition (if applicable) for the system being installed. This information is in the
unit’s QRD (Quick Reference Data sheet).
2. Calculate the amount of additional refrigerant needed for the line set length of the actual installation. This information
is on the first page of the unit’s QRD (Quick Reference Data sheet).
3. Weigh in the additional charge amounts determined by step 1 and 2 above.
4. Adjust the charge to match the superheat (for fixed orifice systems) or subcooling (for TXV systems). There are three
different resources for doing this:
a.) The chargecalculator.com website. This will walk you through the charging process step by step.
b.) The charging tables on the inside of the outdoor unit’s electrical box cover panel. These tables provide superheat
targets for fixed orifice systems and subcooling targets for TXV systems. The system should be charged so that
the measured superheat/subcooling are within 1 degree F of the target listed in the table.
For fixed orifice systems:
• If your measured superheat at the suction valve is LESS THAN the recommended superheat value in the table
then REMOVE refrigerant.
• If your measured superheat at the suction valve is GREATER THAN the recommended superheat value in the
table then ADD refrigerant.
For TXV systems:
• If your measured subcooling at the liquid valve is LESS THAN the recommended subcooling value in the table
then ADD refrigerant.
• If your measured subcooling at the liquid valve is GREATER THAN the recommended subcooling value in the
table then REMOVE refrigerant.
c.) The charging tables in the Supplemental Charging Information, can be found online in the literature library. The
tables can also be accessed by scanning the QR code on the unit’s electrical panel. The pressures listed in these
tables are for reference only and are to be used in troubleshooting a system. The system should be charged to
match the superheat or subcooling targets as previously noted and not to match the system pressures.
Follow the same procedure described in 4b above.
If the outdoor temperature is below 65 degrees F:
After completing the refrigerant line connections, leak checking the system, and evacuating the indoor section and all line
connections (using proper methods), perform the following steps:
1. Determine the recommended charge addition (if applicable) for the system being installed. This information is in the
unit’s QRD (Quick Reference Data sheet).
2. Calculate the amount of additional refrigerant needed for the line set length of the actual installation. This information
is on the first page of the unit’s QRD (Quick Reference Data sheet).
3. Weigh in the additional charge amounts determined by step 1 and 2 above.
4. Return to the system when the outdoor temperature is 65 degrees F or higher and follow the steps defined in step 4 of
the “If the outdoor temperature is 65 degrees F or higher” section above.
8
Y
CSC
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
LEGEND:
24 VOLT FIELD
CONNECTIONS
Y2
C
COMPRESSOR
SOLENOID COIL
T1
L1
F
C
LPS
CC- Contactor Coil
CCH - Crankcase Heater
LPS - Low Pressure Switch
HPS - High Pressure Switch
CSC - Compressor Solenoid Coil
HPS
H
CAPACITOR
208/230V
CC
S
R
S
R
CCH
C
C
OUTDOOR FAN
MOTOR
COMPRESSOR
T2
C D
TERMINAL
BLOCK
L2
BLUE
Y2
Y
YELLOW
C
R
YELLOW/
BLACK
OUTDOOR
FAN MOTOR
C
S
COMPRESSOR
ORANGE
208/230V
FIELD SUPPLY
C
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
COMPRESSOR
CONTACTS
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 °C
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
Two Stage Split System Air Conditioner (Outdoor Section)
With Single Speed Fan Motor
R
S
BLACK
BLACK
BLUE
C
YELLOW
GROUNDING
SCREW
BLACK
H
F
L1
L1
T1
L2
L2
T2
LOW PRESSURE
SWITCH
YELLOW
RT
LFT
CONTACTOR
1209
7110140
YELLOW
SINGLE PHASE
FIELD SUPPLY
GRND
YELLOW
CAPACITOR
Single Phase / 60 Hz.
¢711014e¤
YELLOW/
BLACK
YELLOW
BLACK
BLACK
RED
BLACK
HIGH PRESSURE
SWITCH
CCH
WIRING DIAGRAM
WIRING DIAGRAMS & TABLES
Figure 6. Wiring Diagram for *SA1BF4M2SN (2 Ton Units Without CoreSenseTM)
9
Y
Figure 7. Wiring Diagram for *SA1BF4M2SN (2 Ton Units With CoreSenseTM)
CSC
P
C
C
R
L
CORESENSE
F
Y
Y2
LPS
CC- Contactor Coil
CCH - Crankcase Heater
LPS - Low Pressure Switch
HPS - High Pressure Switch
CSC - Compressor Solenoid Coil
SOL
DC
HPS
H
CAPACITOR
208/230V
CC
S
R
S
R
C
C
OUTDOOR FAN
MOTOR
COMPRESSOR
T2
COMPRESSOR
CONTACTS
L2
DC SOL
P
C
R
L
Y
Y2
CORESENSE
MODULE
Code 10; Red Flash 10
Code 9; Yellow Flash 9
Code 8; Yellow Flash 8
Code 7; Red Flash 7
Code 4; Yellow Flash 4
Code 5; Yellow Flash 5
Code 6; Red Flash 6
Code 3; Yellow Flash 3
Code 2; Yellow Flash 2
Code 1; Yellow Flash 1
BLUE
Y2
Long Run Time. Compressor running extremely long run cycle. (disabled in HP mode.)
Lockout Level
N/A
N/A
Lockout Indication
N/A
N/A
Single Phase / 60 Hz.
RED
R
C
Y
C
YELLOW
BLACK
BLACK
FIELD SUPPLY
HIGH PRESSURE
SWITCH
R
S
YELLOW/
BLACK
GRAY
BLUE
ROUTE THIS WIRE THROUGH “R”
OPENING IN CORESENSE MODULE
R
YELLOW/
BLACK
OUTDOOR
FAN MOTOR
C
S
H
C
YELLOW
GROUNDING
SCREW
BLACK
ROUTE THIS WIRE THROUGH
“S” OPENING IN
CORESENSE MODULE
RED
BLACK
F
L1
T1
L2
L2
T2
YELLOW
10/13
7112070
LOW PRESSURE
SWITCH
YELLOW
RT
LFT
CONTACTOR
Red: Flash 10
N/A
N/A
Red: Flash 7
SINGLE PHASE
FIELD SUPPLY
GRND
YELLOW
CAPACITOR
L1
1 Occurrence
Over Current Protection. PROT terminal has >2A input for more than 40ms
COMPRESSOR
N/A
Low Voltage. Control circuit <17 VAC.
ORANGE
N/A
ROUTE THIS WIRE THROUGH “C” OPENING
IN CORESENSE MODULE
1 Occurrence
Welded Contactor. Compressor always runs.
10 consecutive
Red: Flash 4
4 cons, 10x total Red: Flash 5
Red: Flash 6
1 Occurrence
Locked Rotor.
Compressor Moderate Run. Compressor runs >15min, then trips >7min.
Open Start Circuit. Current only in run circuit.
Open Start Circuit. Current only in start circuit.
4 cons, 10x total Red: Flash 3
Short Cycling. Compressor is running only briefly.
Comprsesor Pressure Trip. Disch. or suct. pressure out of limits or compressor overloaded. 4 cons, 10x total Red: Flash 2
BLACK
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
LEGEND:
24 VOLT FIELD
CONNECTIONS
C
R
Y2
COMPRESSOR
SOLENOID COIL
T1
L1
CCH
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 °C
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
7. Couper le courant avant de faire letretien.
8. Employez uniquement des conducteurs en cuivre.
9. Ne convient pas aux installations de plus de 150 volt a la terre.
Two Stage Split System Air Conditioner (Outdoor Section)
208/230V
Status LED Description
Status LED
With Single Speed Fan Motor
Normal Run; Solid Green Normal Operation, no trip
WIRING DIAGRAM
CCH
10
YELLOW
Y
F
C
CC- Contactor Coil
CCH - Crankcase Heater
LPS - Low Pressure Switch
HPS - High Pressure Switch
CSC - Compressor Solenoid Coil
OFR - Outdoor Fan Relay Coil
HPS
H
CAPACITOR
LPS
FAN MOTOR
L
OFR
CC
S
H
S
R
C
C
COMPRESSOR
FAN RELAY
T2
L2
BLUE
COMPRESSOR
CONTACTS
Y2
BLUE
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
CSC
24 VOLT FIELD
CONNECTIONS
Y2
C
COMPRESSOR
SOLENOID COIL
LEGEND:
T1
L1
208/230V
C
D
Y
TO THERMOSTAT
C
C
YELLOW/
BLACK
R
H
RED
COM
C
F
YELLOW
GROUNDING
SCREW
BLACK
BLACK
H
L1
L2
L2
T2
LOW PRESSURE
SWITCH
YELLOW
RT
LFT
CONTACTOR
1209
7110150
YELLOW
SINGLE PHASE
FIELD SUPPLY
GRND
L1
T1
YELLOW
CAPACITOR
Single Phase / 60 Hz.
¢711015k¤
YELLOW/
BLACK
BLACK
FAN
RELAY
NC
NO
BLUE
YELLOW
BLACK
BLACK
BLUE
RED
BLACK
BLACK
HIGH PRESSURE
SWITCH
L
S
ORANGE
S
COMPRESSOR
TERMINAL
BLOCK
OUTDOOR
FAN MOTOR
C
208/230V
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
CCH
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
Two Stage Split Air Conditioner (Outdoor Section)
With Two Speed Outdoor Fan Motor
CCH
WIRING DIAGRAM
BLACK
Figure 8. Wiring Diagram for *SA1BF4M2SN (3 Ton Units Without CoreSenseTM)
11
Figure 9. Wiring Diagram for *SA1BF4M2SN (3 Ton Units With CoreSenseTM)
CSC
LEGEND:
24 VOLT FIELD
CONNECTIONS
C
R
Y2
COMPRESSOR
SOLENOID COIL
Y
F
C
P
C
R
L
CORESENSE
Y
Y2
LPS
FAN MOTOR
CC- Contactor Coil
CCH - Crankcase Heater
LPS - Low Pressure Switch
HPS - High Pressure Switch
CSC - Compressor Solenoid Coil
OFR - Outdoor Fan Relay Coil
SOL
DC
HPS
H
CAPACITOR
L
OFR
CC
S
H
S
R
C
C
COMPRESSOR
FAN RELAY
T2
L2
P
DC SOL
C
R
L
Y
Y2
CORESENSE
MODULE
COMPRESSOR
CONTACTS
Code 10; Red Flash 10
Code 9; Yellow Flash 9
Code 8; Yellow Flash 8
Code 7; Red Flash 7
Code 4; Yellow Flash 4
Code 5; Yellow Flash 5
Code 6; Red Flash 6
Code 3; Yellow Flash 3
Code 2; Yellow Flash 2
BLUE
Y2
Lockout Indication
N/A
N/A
BLUE
OUTDOOR
FAN MOTOR
C
1 Occurrence
Over Current Protection. PROT terminal has >2A input for more than 40ms
RED
R
C
C
Y
S
H
H
RED
BLACK
COM
YELLOW/
BLACK
GRAY
FAN
RELAY
NC
NO
BLUE
C
F
YELLOW
GROUNDING
SCREW
Red: Flash 10
L1
L2
L2
T2
YELLOW
10/13
7112080
YELLOW
RT
LFT
CONTACTOR
LOW PRESSURE
SWITCH
SINGLE PHASE
FIELD SUPPLY
GRND
L1
T1
YELLOW
CAPACITOR
BLACK
BLACK
ROUTE THIS WIRE THROUGH “R”
OPENING IN CORESENSE MODULE
YELLOW
BLACK
HIGH PRESSURE
SWITCH
L
S
TO THERMOSTAT
YELLOW/
BLACK
R
BLACK
N/A
N/A
ROUTE THIS WIRE THROUGH “C” OPENING
IN CORESENSE MODULE
ROUTHE THIS WIRE THROUGH “S”
OPENING IN CORESENSE MODULE
RED
N/A
Low Voltage. Control circuit <17 VAC.
COMPRESSOR
N/A
Welded Contactor. Compressor always runs.
BLACK
1 Occurrence
Open Start Circuit. Current only in start circuit.
ORANGE
10 consecutive
Red: Flash 4
4 cons, 10x total Red: Flash 5
1 Occurrence
Red: Flash 6
Locked Rotor.
Compressor Moderate Run. Compressor runs >15min, then trips >7min.
Open Start Circuit. Current only in run circuit.
Red: Flash 7
4 cons, 10x total Red: Flash 3
Short Cycling. Compressor is running only briefly.
Comprsesor Pressure Trip. Disch. or suct. pressure out of limits or compressor overloaded. 4 cons, 10x total Red: Flash 2
Lockout Level
N/A
N/A
Single Phase / 60 Hz.
Status LED Description
Normal Run; Solid Green Normal Operation, no trip
Long Run Time. Compressor running extremely long run cycle. (disabled in HP mode.)
Code 1; Yellow Flash 1
208/230V
BLACK
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
T1
L1
208/230V
CCH
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
7. Couper le courant avant de faire letretien.
8. Employez uniquement des conducteurs en cuivre.
9. Ne convient pas aux installations de plus de 150 volt a la terre.
Two Stage Split Air Conditioner (Outdoor Section)
Status LED
With Two Speed Outdoor Fan Motor
WIRING DIAGRAM
CCH
12
YELLOW
C
Y
CC
CC- CONTACTOR COIL
CCH - CRANKCASE HEATER
LPS - LOW PRESSURE SWITCH
HPS - HIGH PRESSURE SWITCH
CSC - COMPRESSOR SOLENOID COIL
LPS
C
T2
L2
COMPRESSOR
CONTACTS
C
TO UNIT
GROUND
LUG
D
L2
TERMINAL
BLOCK
C
Y1
R
L1
Y
C
YELLOW
YELLOW
BLACK
BLACK
HIGH PRESSURE
SWITCH
YELLOW/
BLACK
RED
BLACK
208/230V
S
ECM
TO THERMOSTAT
Y2
Y2
WHITE
OUTDOOR
FAN MOTOR
C
COMPRESSOR
1. Couper le courant avant
de faire letretien.
2. Employez uniquement des
conducteurs en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
BLUE
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
LEGEND:
24 VOLT FIELD
CONNECTIONS
Y2
C
HPS
S
R
COMPRESSOR
C
L2
Y2
Y1
L1
208/230V
ECM
OUTDOOR
FAN MOTOR
CSC
H
CAPACITOR
COMPRESSOR
SOLENOID COIL
T1
L1
CCH
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 °C
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
Two Stage Split System Air Conditioner (Outdoor Section)
With ECM Outdoor Motor
WIRING DIAGRAM
GREEN
CCH
YELLOW
Figure 10. Wiring Diagram for *SA1BF4M2SN (4 & 5 Ton Units Without CoreSenseTM)
13
YELLOW/
BLACK
BLACK
BLUE
BROWN
C
BLACK
H
YELLOW
YELLOW
CAPACITOR
L1
L2
L2
L1
0312
LOW PRESSURE
SWITCH
YELLOW
RIGHT
LEFT
711013A
(Replaces 7110130)
YELLOW
SINGLE PHASE
FIELD SUPPLY
GRN
T2
T1
CONTACTOR
Single Phase / 60 Hz.
C
Y
Figure 11. Wiring Diagram for *SA1BF4M2SN (4 & 5 Ton Units With CoreSenseTM)
P
C
R
L
CORESENSE
Y
CC
Y2
CC- CONTACTOR COIL
CCH - CRANKCASE HEATER
LPS - LOW PRESSURE SWITCH
HPS - HIGH PRESSURE SWITCH
CSC - COMPRESSOR SOLENOID COIL
SOL
DC
LPS
C
T2
L2
COMPRESSOR
CONTACTS
1 Occurrence
Over Current Protection. PROT terminal has >2A input for more than 40ms
Code 10; Red Flash 10
DC SOL
P
C
R
L
Y
Y2
CORESENSE
MODULE
BLUE
R
RED
Y2
C
R
YELLOW
BLACK
BLACK
ROUTE THIS WIRE THROUGH “S”
OPENING IN CORESENSE MODULE
RED
L2
L1
ECM
Y1
Y
C
HIGH PRESSURE
SWITCH
YELLOW/
BLACK
YELLOW
GRAY
YELLOW/
BLACK
BLACK
BLUE
BROWN
ROUTE THIS WIRE THROUGH “R” OPENING
IN CORESENSE MODULE
TO THERMOSTAT
Y2
WHITE
OUTDOOR
FAN MOTOR
C
S
N/A
Low Voltage. Control circuit <17 VAC.
Code 9; Yellow Flash 9
COMPRESSOR
N/A
Welded Contactor. Compressor always runs.
Code 8; Yellow Flash 8
C
1 Occurrence
Open Start Circuit. Current only in start circuit.
Code 7; Red Flash 7
H
10 consecutive
Red: Flash 4
4 cons, 10x total Red: Flash 5
1 Occurrence
Red: Flash 6
Locked Rotor.
Compressor Moderate Run. Compressor runs >15min, then trips >7min.
Open Start Circuit. Current only in run circuit.
BLACK
4 cons, 10x total Red: Flash 3
Short Cycling. Compressor is running only briefly.
Code 4; Yellow Flash 4
Code 5; Yellow Flash 5
Code 6; Red Flash 6
YELLOW
YELLOW
CAPACITOR
L1
L2
L2
L1
YELLOW
YELLOW
RIGHT
LEFT
10/13
7112090
LOW PRESSURE
SWITCH
SINGLE PHASE
FIELD SUPPLY
GRN
T2
T1
CONTACTOR
ROUTE THIS WIRE THROUGH “C” OPENING
IN CORESENSE MODULE
Red: Flash 10
N/A
N/A
Red: Flash 7
Comprsesor Pressure Trip. Disch. or suct. pressure out of limits or compressor overloaded. 4 cons, 10x total Red: Flash 2
Lockout Indication
N/A
N/A
Code 3; Yellow Flash 3
Lockout Level
N/A
N/A
Single Phase / 60 Hz.
Code 2; Yellow Flash 2
Normal Run; Solid Green Normal Operation, no trip
Long Run Time. Compressor running extremely long run cycle. (disabled in HP mode.)
Code 1; Yellow Flash 1
BLACK
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
LEGEND:
24 VOLT FIELD
CONNECTIONS
C
R
Y2
HPS
S
R
COMPRESSOR
C
L2
Y2
Y1
L1
ECM
OUTDOOR
FAN MOTOR
CSC
H
CAPACITOR
COMPRESSOR
SOLENOID COIL
T1
L1
208/230V
CCH
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 °C
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
7. Couper le courant avant de faire letretien.
8. Employez uniquement des conducteurs en cuivre.
9. Ne convient pas aux installations de plus de 150 volt a la terre.
Two Stage Split System Air Conditioner (Outdoor Section)
208/230V
With ECM Outdoor Motor
Status LED Description
Status LED
WIRING DIAGRAM
CCH
14
YELLOW
CORESENSETM TROUBLESHOOTING
STATUS LED
Solid Green
“RUN”
Solid Red
“TRIP”
STATUS LED DESCRIPTION
STATUS LED TROUBLESHOOTING INFORMATION
Module has power and
operating normally
Supply voltage is present at module terminals
Thermostat demand signal Y is
present, but the compressor is not
running
1. Compressor protector is open
• Check for high head pressure
• Check compressor supply voltage
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. High pressure switch open if present in system
6. Compressor contactor has failed open
ALERT FLASH CODES
Yellow “ALERT”
Flash Code 1
Long Run Time
Low Refrigerant Charge
Compressor is running extremely
long run cycles
Yellow “ALERT”
Flash Code 2
Compressor (Pressure) Trip
High Refrigerant Charge
Discharge pressure out of limits or
compressor overloaded
Yellow “ALERT”
Flash Code 3
Pressure Switch Cycling
Compressor is running only briefly
due to pressure switch cycling
Yellow “ALERT”
Flash Code 4
Locked Rotor
Yellow “ALERT”
Flash Code 5
Compressor (Moderate Run)
Trip
1. Low refrigerant charge
2. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
3. Evaporator coil is frozen
• Check for low suction pressure
• Check for excessively low thermostat setting
• Check evaporator airfl ow (coil blockages or return air fi lter)
• Check ductwork or registers for blockage
4. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
5. Liquid line restriction (fi lter drier blocked if present in system)
6. Thermostat is malfunctioning
• Check thermostat sub-base or wiring for short circuit
• Check thermostat installation (location, level)
1. Condenser fan is not running
• Check fan capacitor
• Check fan wiring and connectors
• Check fan motor for failure or blockage
2. High head pressure
• Check high pressure switch if present in system
• Check if system is overcharged with refrigerant
• Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
• Measure compressor oil level
1. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
2. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Table 1. CoreSenseTM LED Diagnostics
15
STATUS LED
STATUS LED DESCRIPTION
STATUS LED TROUBLESHOOTING INFORMATION
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor always runs
1. Compressor contactor has failed closed
2. Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Supply Voltage
Voltage below 18V
1. Control Circuit transformer is overloaded
2. Low line voltage (contact utility if voltage at disconnect is low)
LOCKOUT FLASH CODES
Red
“LOCKOUT”
Flash Code 2
Yellow Off
Compressor (Pressure) Trip
Compressor is locked out
after 4 consecutive or 10 total
compressor (pressure) trip events
1. Condenser fan is not running
• Check fan capacitor
• Check fan wiring and connectors
• Check fan motor for failure or blockage
2. High head pressure
• Check high pressure switch if present in system
• Check if system is overcharged with refrigerant
• Check for non-condensable in system
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Return air duct has substantial leakage
Red
“LOCKOUT”
Flash Code 3
Yellow Off
Pressure Switch Cycling
Compressor is locked out after 4
consecutive or 10 total pressure
cycling events
1. Time delay relay or control board defective
2. If high pressure switch present go to Flash Code 2 information
Red
“LOCKOUT”
Flash Code 4
Yellow Off
Locked Rotor
Compressor is locked out after 10
consecutive locked rotor events
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
• Measure compressor oil level
Red
“LOCKOUT”
Flash Code 5
Yellow Off
Compressor (Moderate Run)
Trip
1. Evaporator blower is not running
• Check blower relay coil and contacts
• Check blower motor capacitor
• Check blower motor for failure or blockage
• Check evaporator blower wiring and connectors
• Check indoor blower control board
• Check thermostat wiring for open circuit
2. Faulty metering device
• Check TXV bulb installation (size, location and contact)
• Check if TXV/fi xed orifi ce is stuck closed or defective
3. Condenser coil poor air circulation (dirty, blocked, damaged)
4. Low refrigerant charge
Red
“LOCKOUT”
Flash Code 6
Yellow Off
Open Start Circuit
Current only in run circuit
1. Run capacitor has failed
2. Open circuit in compressor start wiring or connections
• Check wiring and connectors between supply and the compressor “S” terminal
3. Compressor start winding is damaged
• Check compressor motor winding resistance
Red
“LOCKOUT”
Flash Code 7
Yellow Off
Open Run Circuit
Current only in start circuit
1. Open circuit in compressor run wiring or connections
• Check wiring and connectors between supply and the compressor “R” terminal.
Confirm proper wire routing as shown in Figure 3 (page 5).
2. Compressor run winding is damaged
• Check compressor motor winding resistance
Red
“LOCKOUT”
Flash Code 10
Over Current Protection
Current to PROT is greater than
2A mps
1. Check for contactor shorted to ground
2. Check for mis-wiring to the PROT terminal
* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. Trip and alert LED’s flashing at same time
means control circuit voltage is too low for operation.
Table 1. CoreSenseTM Diagnostics & Troubleshooting - Continued
16
17
18
19
INSTALLATION CHECKLIST
ELECTRICAL SYSTEM
INSTALLATION ADDRESS:
CITY:
STATE:
Electrical connections tight?
YES
NO
Line voltage polarity correct?
YES
NO
Has the thermostat been calibrated?
YES
NO
Is the thermostat level?
YES
NO
Is the heat anticipator setting
correct? (If Applicable)
YES
NO
Rated Voltage:
UNIT MODEL #:
Max. deviation of voltage from avg. volts:
UNIT SERIAL #:
Unit Installed Minimum clearances
per Figure 1 (page 3)?
YES
NO
INSTALLER NAME:
CITY:
REPLACEMENT PARTS
Replacement parts are available through your distributor.
Please have the complete model and serial number of the
unit when ordering replacement parts.
STATE:
REFRIGERATION SYSTEM
Was unit given 24 hr warm up
period for crankcase heaters?
YES
NO
Stage-1 Liquid Pressure (high side):
Stage-1 Suction Pressure (low side):
ELECTRICAL:
Capacitors
Temperature Limit Switches
Compressors
Thermostats
Contactors
Time Delay Relays
Pressure Switches
Transformers
Relays
Has the owner’s information been
reviewed with the customer?
YES
NO
Has the Literature Package been
left with the unit?
YES
NO
MOTORS:
Blower Motor
Fan Motor
COMPONENTS:
Blower Assembly
Fan Grille
Cabinet Panels
Filter/Driers
Expansion Valves
Specifications & illustrations subject to change without notice or incurring obligations (12/18).
O’Fallon, MO, © Nortek Global HVAC LLC 2018. All Rights Reserved.
10252510
(Replaces 1016543)

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals