Trane Force-Flo, UniTrane Installation, Operation And Maintenance Instructions
Trane Force-Flo is a fan-coil and air conditioner designed for commercial applications. It is available in a range of models with capacities from 200 to 1,200 cfm. The Force-Flo is designed for easy installation and maintenance, and it features a number of energy-saving features.
Advertisement
Advertisement
Installation, Operation, and
Maintenance
UniTrane™ Fan-Coil and
Force-Flo™ Air Conditioners
200 to 1,200 cfm
Models FC and FF
“ZO” and later design sequence
Low vertical models FCKB and FCLB
“SO” and later design sequence
July 2010
UNT-SVX07B-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices.
Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION:
Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully.
WARNING:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION:
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
:
Indicates a situation that could result in equipment or property-damage only accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants-including industry replacements for
CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
© 2010 Trane All rights reserved UNT-SVX07B-EN
Warnings, Cautions and Notices
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
• Before installing/servicing this unit, technicians MUST put on all Personal Protective
Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
• If there is a risk of arc or flash, technicians MUST put on all necessary Personal Protective
Equipment (PPE) in accordance with NFPA70E for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow code could result in death or serious injury.
UNT-SVX07B-EN
Trademarks
Force-Flo, Trane, the Trane logo, and UniTrane are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
3
4
Table of Contents
Model Number Descriptions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
General Information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pre-Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Jobsite Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pre-Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Dimensions and Weights
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Factory-Installed Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Vertical Concealed, Model A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Vertical Cabinet, Model B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Horizontal Concealed, Model C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Horizontal Cabinet, Model D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Horizontal Recessed, Model E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Vertical Wall Hung Cabinet, Model F (Force-Flo Units Only) . . . . . . . . . . 23
Vertical Recessed, Model H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Vertical Slope Top, Model J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Low Vertical Concealed, Model K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Low Vertical Cabinet, Model L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Inverted Vertical Cabinet, Model M (Force-Flo Units Only) . . . . . . . . . . . 28
Inverted Vertical Recessed, Model N (Force-Flo Units Only) . . . . . . . . . . 29
Fan-Coil Coil Connections, Vertical Units . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fan-Coil Coil Connections, Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . 30
Force-Flo Coil Connections, Vertical Units . . . . . . . . . . . . . . . . . . . . . . . . 31
Force-Flo Coil Connections, Horizontal Units . . . . . . . . . . . . . . . . . . . . . . 31
Force-Flo Coil Connections, Inverted Units . . . . . . . . . . . . . . . . . . . . . . . . 32
Fresh Air Opening Locations, Horizontal Units—Models C, D, and E . . . 33
Fresh Air Opening Locations, Vertical Units—Models A, B, F, H, J, K, L, M, and N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Wall Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Projection Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Installation—Mechanical
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Piping Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Installation—General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Installing the Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Vertical Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Cabinet Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Recessed Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Installation Checklist
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
UNT-SVX07B-EN
UNT-SVX07B-EN
Installation—Controls
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
General Information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Control Options (Including Factory-Installed) . . . . . . . . . . . . . . . . . . . . . . 52
Installing Wall-Mounted Wired Sensors
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Fan Mode Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Wired Zone Sensor Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Installing Wall-Mounted Wireless Zone Sensors
. . . . . . . . . . . . . . . . . . . . . . 56
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Location Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Mounting the Sensor Back Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Replacing the Sensor Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Installation—Electrical
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Unit Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Supply Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Electrical Grounding Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Wall-Mounted Control Interconnection Wiring . . . . . . . . . . . . . . . . . . . . . 60
Controls Interface
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Wired Controllers—Communication Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . 67
Units with Tracer ZN510 and ZN520 Only . . . . . . . . . . . . . . . . . . . . . . . . . 67
Device Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Recommended Communication Wiring Practices . . . . . . . . . . . . . . . . . . 67
Wireless Temperature Sensor
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Address Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Observing the Receiver for Readiness to Associate . . . . . . . . . . . . . . . . . 69
Associating the Sensor to the Receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Testing Signal Strength and Battery Status . . . . . . . . . . . . . . . . . . . . . . . 70
Configuring the Wireless Display Sensor (Model WDS only) . . . . . . . . . 71
Replacing the Sensor Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Sensor Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Wireless Sensor Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Pre-Start
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Pre-Startup Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Start-Up
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Tracer™ ZN510 & ZN520 Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Fan Mode Switch Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Tracer ZN010 & ZN510 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Tracer ZN520 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Sequence of Operation: Tracer ZN010 and ZN510
. . . . . . . . . . . . . . . . . . . . . 86
Binary Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
5
6
Binary Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Tracer ZN520 Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Cooling Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Fan Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Maintenance
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Maintenance Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Periodic Maintenance Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Diagnostics
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Troubleshooting the Relay (Daughter) Board . . . . . . . . . . . . . . . . . . . . . 113
Troubleshooting Wireless Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Troubleshooting Tracer ZN010, ZN510, and ZN520 . . . . . . . . . . . . . . . . 124
Wiring Diagrams
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
CSTI Fan Speed Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
CSTI Non Fan Speed Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Line Voltage Fan Speed Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Tracer ZN010 with Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Tracer ZN510 with Main and Auxiliary Valves . . . . . . . . . . . . . . . . . . . . 130
ZN520 with 2-Stage Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
UNT-SVX07B-EN
Model Number Descriptions
Each UniTrane fan-coil and Force-Flo cabinet heater has a multiple character model number unique to that particular unit. To determine a unit’s specific options, reference the model number on the unit nameplate on the fan scroll. The unit nameplate also identifies the serial number, sales order number, and installation and operating specifications.
Following is a complete description of the fan-coil model number. Each digit in the model number has a corresponding code that identifies specific unit options.
Note:
Not all options are available on all cabinet styles. Contact your local Trane sales representative for more information.
Digits 1, 2 — Unit Type
FC = Fan-Coil
FF = Force-Flo
Digit 3 — Cabinet Type
A = Vertical Concealed
B = Vertical Cabinet
C = Horizontal Concealed
D = Horizontal Cabinet
E = Horizontal Recessed
H = Vertical Recessed
J = Vertical Cabinet Slope Top
K = Low Vertical Concealed
L = Low Vertical Cabinet
M = Inverted Vertical Cabinet
N = Inverted Vertical Recessed
Digit 4 — Development
Sequence “B”
Digits 5, 6, 7 — Unit Size
020
030
120
040
060
080
100
Digit 8 — Unit Voltage
1 = 115/60/1
2 = 208/60/1
3 = 277/60/1
4 = 230/60/1
9 = 220–240/50/1
Digit 9 — Piping System/
Placement
A = No piping, RH, No Auxiliary Drain
Pan
B = No piping, LH, No Auxiliary Drain
Pan
C = No piping, RH, with Auxiliary
Drain Pan
D = No piping, LH, with Auxiliary
Drain Pan
E = No piping, RH, No Auxiliary Drain
Pan, Extended End Pocket
F = No piping, LH, No Auxiliary Drain
Pan, Extended End Pocket
G = No piping, RH, with Auxiliary
Drain Pan, Extended End Pocket
H = No piping, LH, with Auxiliary
Drain Pan, Extended End Pocket
J = With piping package, RH
K = With piping package, LH
L = With piping package, RH,
Extended End Pocket
M = With piping package, LH,
Extended End Pocket
Digits 10, 11 — Design Sequence
Digit 12 — Inlets
A = Front Toe Space
B = Front Bar Grille
C = Front Stamped Louver
D = Bottom Stamped Louver
E = Bottom Toe Space
F = Back Duct Collar
G = Back Open Return
H = Back Stamped Louver
Digit 13 — Fresh Air Damper
0 = None
A = Manual, Bottom Opening
B = Manual, Back Opening
C = Manual, Top Opening
D = Auto, 2-Position, Bottom Opening
E = Auto, 2-Position, Back Opening
F = Auto, 2-Position, Top Opening
G = Auto, Economizer, Bottom
Opening
H = Auto, Economizer, Back Opening
J = Auto, Economizer, Top Opening
K = No Damper, Bottom Opening
L = No Damper, Back Opening
M = No Damper, Top Opening
Digit 14 — Outlets
A = Front Duct Collar
B = Front Bar Grille
C = Front Stamped Louver
D = Front Quad Grille
G = Top Quad Grille
H = Top Bar Grille
J = Top Duct Collar
Digit 15 — Color
0 = No Paint (Concealed Units Only)
1 = Deluxe Beige
2 = Soft Dove
3 = Cameo White
4 = Driftwood Grey
5 = Stone Grey
6 = Rose Mauve
Digit 16 — Tamperproof Locks/
Leveling Feet
0 = None
B = Keylock Access Door
C = Keylock Panel and Access Door
D = Leveling Feet
F = Keylock Access Door with
Leveling Feet
G = Keylock Panel and Access Door with Leveling Feet
Digit 17 — Motor
A = Free Discharge
B = High Static
Digit 18 — Coil
A = 2-Row Cooling/Heating
B = 3-Row Cooling/Heating
C = 4-Row Cooling/Heating
D = 2-Row Cooling/1-Row Heating
E = 2-Row Cooling/2-Row Heating
F = 3-Row Cooling/1-Row Heating
G = 2-Row Cooling Only
H = 3-Row Cooling Only
J = 4-Row Cooling Only
K = 2-Row Cooling/Heating with
Electric Heat
L = 3-Row Cooling/Heating with
Electric Heat
M = 4-Row Cooling/Heating with
Electric Heat
P = 2-Row Cooling/Heating with
1-Row Heating
Q = 2-Row Cooling/Heating with
2-Row Heating
R = 3-Row Cooling/Heating with
1-Row Heating
X = 2-Row Cooling Only, Electric Heat
Y = 3-Row Cooling Only, Electric Heat
Z = 4-Row Cooling Only, Electric Heat
Digit 19 — Drain Pan Material
3 = Polymer Drain Pan
4 = Stainless Steel Main Drain Pan
Digit 20 — Coil Air Vent
A = Automatic Air Vent
M = Manual Air Vent
UNT-SVX07B-EN 7
Model Number Descriptions
Digits 21, 22, 23 — Electric Heat kW — ( ) = 208 V Derate
000 = No Electric Heat
010 = 1.0 kW (0.75 kW)
015 = 1.5 kW (1.1 kW)
020 = 2.0 kW (1.5 kW)
025 = 2.5 kW (1.9 kW)
030 = 3.0 kW (2.3 kW)
040 = 4.0 kW (3.0 kW)
050 = 5.0 kW (3.8 kW)
060 = 6.0 kW (4.5 kW)
070 = 7.0 kW (5.3 kW)
080 = 8.0 kW (6.0 kW)
100 = 10.0 kW
Digit 24 — Reheat Coil
0 = None
A = Steam Coil
B = Hot Water Coil
D = High Capacity Hot Water Coil
Digit 25 — Disconnect Switch
0 = None
D = Disconnect Switch
Digit 26 — Filter
0 = None
1 = 1” Throwaway Filter
2 = 1” Throwaway MERV 8 Filter
3 = 1” Throwaway, 1 Extra
4 = 1” Throwaway MERV 8, 1 Extra
5 = 1” Throwaway, 2 Extras
6 = 1” Throwaway MERV 8, 2 Extras
7 = 1” Throwaway, 3 Extras
8 = 1” Throwaway MERV 8, 3 Extras
Digit 27 — Main Control Valve
0 = None
A = 2-Way, 2-Position, NO (30 psig)
B = 3-Way, 2-Position, NO (28 psig)
C = 2-Way, 2-Position, NC (30 psig)
D = 3-Way, 2-Position, NC (20 psig)
E = 2-Way, 2-Position, NO (50 psig)
F = 3-Way, 2-Position, NO (28 psig)
G = 2-Way, 2-Position, NC (50 psig)
H = 3-Way, 2-Position, NC (28 psig)
J = 2-Way, Modulating, 0.6 Cv
(60 psig)
K = 3-Way, Modulating, 0.6 Cv
(60 psig)
L = 2-Way, Modulating, 1.1 Cv
(60 psig)
M = 3-Way, Modulating, 1.1 Cv
(60 psig)
N = 2-Way, Modulating, 2.3 Cv
(60 psig)
P = 3-Way, Modulating, 2.7 Cv
(60 psig)
Q = 2-Way, Modulating, 3.3Cv
(60 psig)
R = 3-Way, Modulating, 3.8 Cv
(60 psig)
X = Field-supplied, NO
Y = Field-supplied, NC
Z = Field-supplied 3-Wire Modulating
Digit 28 — Auxiliary Control
Valve
0 = None
A = 2-Way, 2-Position, NO (30 psig)
B = 3-Way, 2-Position, NC (28 psig)
C = 2-Way, 2-Position, NC (30 psig)
D = 3-Way, 2-Position, NC (20 psig)
E = 2-Way, 2-Position, NO (50 psig)
F = 3-Way, 2-Position, NO (28 psig)
G = 2-Way, 2-Position, NC (50 psig)
H = 3-Way, 2-Position, NC (28 psig)
J = 2-Way, Modulating, 0.6 Cv
(60 psig)
K = 3-Way, Modulating, 0.6 Cv
(60 psig)
L = 2-Way, Modulating, 1.1 Cv
(60 psig)
M = 3-Way, Modulating, 1.1 Cv
(60 psig)
N = 2-Way, Modulating, 2.3 Cv
(60 psig)
P = 3-Way, Modulating, 2.7 Cv
(60 psig)
Q = 2-Way, Modulating, 3.3Cv
(60 psig)
R = 3-Way, Modulating, 3.8 Cv
(60 psig)
X = Field-supplied, NO
Y = Field-supplied, NC
Z = Field-supplied 3-Wire Modulating
Digit 29 — Piping Packages
0 = None
A = Basic Ball Valve Supply and
Return
B = Basic Ball Valve Supply/Manual
Circuit Setter
C = Basic Ball Valve Supply and
Return with Auto Circuit Setter
D = Deluxe Ball Valve Supply and
Return
E = Deluxe Ball Valve Supply/Manual
Circuit Setter
F = Deluxe Ball Valve Supply and
Return with Auto Circuit Setter
Digit 30 — Control Type
A = Fan Mode Switch
E = Tracer ZN010
F = Tracer ZN510
G = Tracer ZN520
H = Customer Supplied Thermostat
Interface (CSTI)
Digit 31 — Control Option
D = Unit-Mounted Fan Mode Switch
K = Wall-Mounted Fan Mode Switch
V = Unit-Mounted Fan Speed Switch w/Setpoint Dial Zone Sensor
W = Wall-Mounted Fan Speed Switch w/Setpoint Dial Zone Sensor
X = Unit-Mounted Fan Speed Switch w/Wall-Mounted Setpoint Dial
Zone Sensor
Y = Unit-Mounted Fan Speed Switch
& Wall-Mounted Setpoint Dial w/Comm.
Z = Unit-Mounted Fan Speed Switch,
On/Cancel, Setpoint Dial w/ Comm.
1 = Wall-Mounted On/Cancel w/ Comm.
2 = Wall-Mounted Fan Speed Switch,
Setpoint Dial, On/Cancel w/ Comm.
0 = Without Control Option
3 = Unit-Mounted Low Voltage Fan
Speed Switch (Off /Hi /Med /Low)
4 = Wall-Mounted Digital Zone
Sensor (OALMH, Setpoint,
On/Cancel, Comm Jack)
5 = Wall-Mounted Digital Zone
Sensor (On/Cancel, Comm Jack)
6 = Wireless Zone Sensor
7 = Wireless Display Sensor, Unit-
Mounted Receiver
Digit 32 - IAQ Options
0 = Without IAQ Options
1 = Dehumidification
4 = Dehumidification w/ Sensor
Digits 33, 34 —Future Control
Functions
Digit 35 — Control Function #3
0 = None
2 = Condensate Overflow Detection
8 UNT-SVX07B-EN
Digit 36 — Control Function #4
0 = None
2 = Low Temperature Detection
Digits 37, 38 — Future Control
Functions
Digit 39 — Projection Panels and
Falsebacks
0 = None
A = 5/8” Standard Recessed Panel
(Vertical Recessed Units Only)
B = 2” Projection Panel
C = 2.5” Projection Panel
D = 3” Projection Panel
E = 3.5” Projection Panel
F = 4” Projection Panel
G = 4.5” Projection Panel
H = 5” Projection Panel
J = 5.5” Projection Panel
K = 6” Projection Panel
L = 2”Falseback
M = 3” Falseback
N = 4” Falseback
P = 5” Falseback
Q = 6” Falseback
R = 7” Falseback
T = 8” Falseback
Digit 40 — Main Autoflow Gpm
0 = None
A = 0.5
B = 0.75
C = 1.0
D = 1.5
E = 2.0
F = 2.5
G = 3.0
H = 3.5
J = 4.0
K = 4.5
L = 5.0
M = 6.0
N = 7.0
P = 8.0
Digit 41 — Auxiliary Autoflow
Gpm
0 = None
A = 0.5
B = 0.75
C = 1.0
D = 1.5
E = 2.0
F = 2.5
G = 3.0
H = 3.5
J = 4.0
K = 4.5
L = 5.0
M = 6.0
N = 7.0
P = 8.0
Digit 42 — Subbases
0 = None
A = 2” Subbase
B = 3” Subbase
C = 4” Subbase
D = 5” Subbase
E = 6” Subbase
F = 7” Subbase
Digit 43 — Recessed Flange
0 = None
A = Recessed Flange
Digit 44 — Wall Boxes
0 = None
A = Anodized Wall Box
UNT-SVX07B-EN
Model Number Descriptions
9
General Information
UniTrane fan-coil and Force-Flo units are intended for single zone applications. These units have load capabilities of 200 to 1200 cfm. See Figure 1 for unit components. Fan-coil units are available as two-pipe, with or without electric heat (one hydronic circuit) or four-pipe (two hydronic circuits).
Force-Flo units feature two-pipe hydronic, electric heat only, or steam only. Also, these units feature a variety of factory mounted piping packages.
Units with the three-speed fan switch only, are available with the switch mounted on the unit, or shipped separately, to be mounted in the occupied space. The unit mounted three-speed switch option can be ordered with a low voltage (24 vols AC) transformer and three fan speed relays. The three-speed switch option, which ships separately, comes with a low voltage (24 volt AC) transformer and three fan speed relays.
The Tracer ZN010, ZN510, and ZN520 controllers are included inside the units control box assembly.
These controllers utilize analog signals from a unit-mounted control device or from a control device mounted in the occupied space.
The controls interface option, includes a 24 volt AC transformer, and an interface terminal board.
Controls provided by an external source can be tied into the interface terminal board utilizing 1/4” female spade connectors.
Figure 1.
UniTrane fan-coil unit components (vertical cabinet model is shown)
Factory installed and tested controls
Smaller unit footprint
Quiet operation
Two, three, or four-row coils
Factory assembled, installed and tested piping package with IAQ drain pan to collect condensate
Removable, noncorrosive, positively-sloped drain pan that’s easy to clean
Easy to remove fan assembly
16-gage steel construction
Easy filter access without front panel removal
Cleanable closedcell insulation (nonfiberglass)
Damper allows up to 100% fresh air
10 UNT-SVX07B-EN
Pre-Installation
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Receiving and Handling
Upon delivery, inspect all components for possible shipping damage. See “Receiving Checklist”
(below) for detailed instructions. Trane recommends leaving units and accessories in their shipping packages/skids for protection and ease of handling until installation.
Shipping Package
UniTrane fan-coil and Force-Flo cabinet heaters ship in individual cartons for handling and storage ease. Each carton has tagging information such as the model number, sales order number, serial number, unit size, piping connections, and unit style to help properly locate the unit in the floor plan. If specified, the unit will ship with tagging designated by the customer.
Receiving Checklist
Complete the following checklist immediately after receiving unit shipment to detect possible shipping damage.
Inspect individual cartons before accepting. Check for rattles, bent carton corners, or other visible indications of shipping damage.
If a unit appears damaged, inspect it immediately before accepting the shipment. Manually rotate the fan wheel to ensure it turns freely. Make specific notations concerning the damage on the freight bill. Do not refuse delivery.
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery.
Report concealed damage to the freight line within the allotted time after delivery. Check with the carrier for their allotted time to submit a claim.
Do not move damaged material from the receiving location. It is the receiver’s responsibility to provide reasonable evidence that concealed damage did not occur after delivery.
Do not continue unpacking the shipment if it appears damaged. Retain all internal packing, cartons, and crate. Take photos of damaged material.
Notify the carrier’s terminal of the damage immediately by phone and mail. Request an immediate joint inspection of the damage by the carrier and consignee.
Notify your Trane representative of the damage and arrange for repair. Have the carrier inspect the damage before making any repairs to the unit.
Compare the electrical data on the unit nameplate with the ordering and shipping information to verify the correct unit is received.
Jobsite Storage
This unit is intended for indoor use only. Store the unit indoors to protect the unit from damage due to the elements. If indoor storage is not possible, make the following provisions for outdoor storage:
1.
Place the unit(s) on a dry surface or raised off the ground to assure adequate air circulation beneath unit and to assure that no portion of the unit contacts standing water at any time.
UNT-SVX07B-EN 11
Pre-Installation
2.
Cover the entire unit with a canvas tarp
only.
Do not
use clear, black or plastic tarps as they may cause excessive moisture condensation and equipment damage.
Installation Preparation
Before installing the unit, consider the following unit location recommendations to ensure proper unit operation.
1.
Clearances: Allow adequate service and code clearances as recommended in “Service Access”
(the next section). Position the unit and skid assembly in its final location.
2. Structural support: Ensure the structural support is strong enough to adequately support the unit. The installer is responsible for supply support rods for installation of ceiling units.
3. Level: Verify the floor or foundation is level. Shim or repair as necessary. To ensure proper unit operation, install the unit level (zero tolerance) in both horizontal axes. Failure to level the unit properly can result in condensate management problems, such as standing water inside the unit.
4. Condensate line & piping: Consider coil piping and condensate drain requirements. Verify condensate line is continuously pitched 1 inch per 10 feet of condensate line run to adequately drain condensate.
5. Wall & ceiling openings: Vertical recessed/concealed units require wall/ceiling openings. Refer to submittal for specific dimensions before attempting to install. Horizontal recessed/concealed units must meet the requirements of the National Fire Protection Association (NFPA) Standard
90A or 90B concerning the use of concealed ceiling spaces as return air plenums. Refer to the submittal for specific dimensions of ceiling openings.
6. Exterior: Touch up painted panels if necessary. If panels need paint, sanding is not necessary.
However, clean the surface of any oil, grease, or dirt residue so the paint will adhere. Purchase factory approved touch up epoxy paint from your local Trane Service Parts Center and apply.
Service Access
Service access is available from the front on vertical units and from the bottom on horizontal units.
Cabinet and recessed units have removable front or bottom panels to allow access into the unit.
See Figure 2, p. 13 for recommended service and operating clearances.
12 UNT-SVX07B-EN
Pre-Installation
Figure 2.
Recommended service clearances
24"
12" both sides
8.5" both sides model B, vertical cabinet model L, low vertical cabinet
3" model A, vertical concealed model K, low vertical concealed model H, vertical recessed
12" both sides
24" front discharge
8.5" both sides
36"
28"
28" model D, horizontal cabinet model C, horizontal concealed model E, horizontal recessed
Units have either right or left hand piping. Reference piping locations by facing the front of the unit
(airflow discharges from the front). The control panel is always on the end opposite the piping.
The fan board assembly and main drain pan are easily removable for cleaning. See “Maintenance,” p. 101 for more details on servicing.
Pre-Installation Checklist
Complete the following checklist before beginning unit installation.
Verify the unit size and tagging with the unit nameplate.
Make certain the floor or foundation is level, solid, and sufficient to support the unit and accessory weights. See “Dimensions and Weights,” p. 14 . Level or repair the floor before positioning the unit if necessary.
Allow minimum recommended clearances for routine maintenance and service. Refer to unit submittals for dimensions.
Allow one and one half fan diameters above the unit before the discharge ductwork makes any turns.
UNT-SVX07B-EN 13
Dimensions and Weights
Table 1.
Fan-coil component data
Unit Size
Coil Data
Face Area — ft
2
(cm
2
)
LxDxH — in. (cm)
02
0.8 (743)
03
0.8 (743)
04
1.1 (1020)
06
1.6 (1490)
08
2.1 (1950)
10
3.2 (2970)
12
3.2 (2970)
2-Row
3-Row
4-Row
15 x 1.7 x 8 15 x 1.7 x 8 20 x 1.7 x 8 29.5 x 1.7 x 8 38 x 1.7 x 8 57 x 1.7 x 8 57 x 1.7 x 8
(38 x 4 x 20) (38 x 4 x 20) (51 x 4 x 20) (75 x 4 x 20) (97 x 4 x 20) (145 x 4 x 20) (145 x 4 x 20)
15 x 2.6 x 8 15 x 2.6 x 8 20 x 2.6 x 8 29.5 x 2.6 x 8 38 x 2.6 x 8 57 x 2.6 x 8 57 x 2.6 x 8
(38 x 7 x 20) (38 x 7 x 20) (51 x 7 x 20) (75 x 7 x 20) (97 x 7 x 20) (145 x 7 x 20) (145 x 7 x 20)
15 x 3.5 x 8 15 x 3.5 x 8 20 x 3.5 x 8 29.5 x 3.5 x 8 38 x 3.5 x 8 57 x 3.5 x 8 57 x 3.5 x 8
(38 x 9 x 20) (38 x 9 x 20) (51 x 9 x 20) (75 x 9 x 20) (97 x 9 x 20) (145 x 9 x 20) (145 x 9 x 20)
Volume — gal (L)
1-Row (Heat)
2-Row
3-Row
0.06 (0.23)
0.12 (0.45)
0.18 (0.68)
0.24 (0.91)
0.06 (0.23)
0.12 (0.45)
0.18 (0.68)
0.24 (0.91)
0.08 (0.30)
0.15 (0.57)
0.23 (0.87)
0.30 (1.14)
0.11 (0.42)
0.22 (0.83)
0.33 (1.25)
0.44 (1.67)
0.14 (0.53)
0.28 (1.06)
0.42 (1.59)
0.56 (2.12)
0.21 (0.79)
0.42 (1.59)
0.62 (2.35)
0.83 (3.14)
0.21 (0.79)
0.42 (1.59)
0.62 (2.35)
0.83 (3.14) 4-Row
Fins/ft (cm)
2-Row
3-Row
144 (4.7)
144 (4.7)
144 (4.7)
144 (4.7)
4-Row 144 (4.7) 144 (4.7)
Reheat Coil Data (1-Row), Standard or High-Capacity
(a)
Hot Water or Steam
Face Area — ft
2
(cm
2
) 0.6
0.6
L x D x H — in. (cm)
(557)
15 x 1.5 x 6
(557)
15 x 1.5 x 6
144 (4.7)
144 (4.7)
144 (4.7)
0.8
(743)
20 x 1.5 x 6
144 (4.7)
144 (4.7)
144 (4.7)
1.2
(1120)
144 (4.7)
144 (4.7)
144 (4.7)
1.6
(1490)
29.5 x 1.5 x 6 38 x 1.5 x 6
144 (4.7)
144 (4.7)
144 (4.7)
2.4
(2230)
57 x 1.5 x 6
144 (4.7)
144 (4.7)
144 (4.7)
2.4
(2230)
57 x 1.5 x 6
Volume — gal (L)
(38 x 4 x 15) (38 x 4 x 15) (51 x 4 x 15) (75 x 4 x 15) (97 x 4 x 15) (145 x 4 x 15) (145 x 4 x 15)
0.12 (0.45)
Standard Capacity
(a)
Fins/ft (cm) 48 (1.6)
High-Capacity
(a)
Fins/ft (cm) 144 (4.7)
0.12 (0.45)
48 (1.6)
144 (4.7)
0.15 (0.57)
48 (1.6)
144 (4.7)
0.22 (0.83)
48 (1.6)
144 (4.7)
0.28 (1.06)
48 (1.6)
144 (4.7)
0.42 (1.59)
48 (1.6)
144 (4.7)
0.42 (1.59)
48 (1.6)
144 (4.7)
Fan/Motor Data
Fan Quantity
Size — Dia” x Width” (cm)
Size — Dia” x Width” (cm)
1
6.31 x 4
(16 x 10)
1
6.31 x 6.5
(16 x 17)
1
6.31 x 7.5
(16 x 19)
2
6.31 x 6.5
(16 x 17)
2
6.31 x 7.5
(16 x 19)
3 3
(1) 6.31 x 7.5 6.31 x 7.5
(16 x 19) (16 x 19)
(2) 6.31 x 6.5
(16 x 6.5)
2 2 Motor Quantity
Filter Data
1” (cm) TA and Pl. Media
Quantity
Size — in. (cm)
1 1 1 1 1
1 1 1 1 1 1 1
8-7/8 x 19-1/8 8-7/8 x 19-1/8 8-7/8 x 24-1/8 8-7/8 x 33-5/8 8-7/8 x 42-1/8 8-7/8 x 61-1/8 8-7/8 x 61-1/8
(23 x 49) (23 x 49) (23 x 61) (23 x 85) (23 x 107) (23 x 155) (23 x 155)
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)
Quantity 1 1 1 1 1
Size — in. (cm)
1 1
5-1/2 x 19-1/8 5-1/2 x 19-1/8 5-1/2 x 24-1/8 5-1/2 x 33-5/8 5-/2 x 42-1/8 5-1/2 x 61-1/8 5-1/2 x 61-1/8
(14 x 49) (14 x 49) (14 x 61) (14 x 85) (14 x 107) (14 x 156) (14 x 156)
(a) Standard and high-capacity reheat coils share the same component data except that standard capacity reheat coils have 48 fins/ft (1.6 fins/cm) while high-capacity reheat coils have 144 fins/ft (4.7 fins/cm).
14 UNT-SVX07B-EN
UNT-SVX07B-EN
Dimensions and Weights
Table 2.
Low vertical fan-coil component data
Unit Size 03 04 06
Coil Data
Face Area — ft
2
(cm
2
)
L x D x H — in. (cm)
2-Row
3-Row
Volume — gal (L)
1-Row (Heat)
2-Row
1.1 (1020)
20 x 1.7 x 8 (51 x 4 x 20)
20 x 2.6 x 8 (51 x 7 x 20)
0.08 (0.30)
0.15 (0.57)
0.23 (0.87) 3-Row
Fins/ft
2-Row
3-Row
144 (4.7)
144 (4.7)
Fan/Motor Data
Fan Quantity 1
Size — Dia”x Width” (cm) 5 x 23 (13 x 59)
Motor Quantity 1
1.6 (1490)
29.5 x 1.7 x 8 (75 x 4 x 20) 38 x 1.7 x 8 (97 x 4 x 20)
29.5 x 2.6 x 8 (75 x 7 x 20) 38 x 2.6 x 8 (97 x 7 x 20)
0.11 (0.42)
0.22 (0.83)
0.33 (1.25)
144 (4.7)
144 (4.7)
1
5 x 32 (13 x 83)
1
2.1 (1950)
0.14 (0.53)
0.28 (1.06)
0.42 (1.59)
144 (4.7)
144 (4.7)
1
5 x 41 (13 x 105)
1
Filter Data
1” (2.5 cm) TA
Quantity
Size — in. (cm)
1
8-7/8 x 24-1/8 (23 x 61)
1
8-7/8 x 33-5/8 (23 x 85)
1
8-7/8 x 42-1/8 (23 x 107)
15
Dimensions and Weights
Available Models
Model A: Vertical Concealed Model B: Vertical Short Model C: Horizontal Concealed
Model D: Horizontal Cabinet Model E: Horizontal Recessed Model F: Wall Hung Cabinet
(Force-Flo units only)
Model L: Low Vertical Concealed Model K: Low Vertical Cabinet Model H: Vertical Recessed
Model J: Slope-Top Cabinet
16
Model M: Inverted Vertical Cabinet
(Force-Flo units only)
Model N: Inverted Vertical Recessed
(Force-Flo units only)
UNT-SVX07B-EN
Factory-Installed Piping Packages
Dimensions and Weights
Auto Circuit Setter (C)
UNT-SVX07B-EN
Note:
This figure shows piping package components and basic arrangement. It is not an accurate picturial of what factory-installed piping packages look like.
17
Dimensions and Weights
Vertical Concealed, Model A
18
Vertical Concealed Unit Dimensions (in.) and Weights (lb)
Unit Size 02–03 04 06 08 10–12
A
B
C
D
E
Operating
Weight
Shipping
Weight
32-11/16”
21-5/16”
22-13/16”
17-5/16”
19-5/16”
81
68
37-11/16”
26-5/16”
27-13/16”
22-5/16”
24-5/16”
109
96
47-3/16”
35-13/16”
37-5/16”
31-13/16”
33-13/16”
139
123
55-11/16”
44-5/16”
45-13/16”
40-5/16”
42-5/16”
147
131
74-11/16”
63-5/16”
64-13/16”
59-5/16”
61-5/16”
200
182
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
UNT-SVX07B-EN
Vertical Cabinet, Model B
Dimensions and Weights
UNT-SVX07B-EN
Vertical Cabinet Unit Dimensions (in.) and Weights (lb)
Unit Size 02–03 04 06 08 10–12
A
B
C
D
E
F
Operating
Weight
Shipping
Weight
33-5/16”
21-5/16”
7-5/8”
18”
19-5/16”
41-5/16”
97
84
38-5/16”
26-5/16”
7-1/8”
24”
24-5/16”
46-5/16”
125
112
47-13/16”
35-13/16”
8-7/8”
30”
33-13/16”
55-3/16”
155
139
56-5/16”
44-5/16”
7-1/8”
42”
42-5/16”
64-5/16”
164
148
75-5/16”
63-5/16”
7-5/8”
60”
61-5/16”
83-5/16”
218
200
Notes:
1. Coil connections are always on the drain pan side and opposite the control box and unit control.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
19
Dimensions and Weights
Horizontal Concealed, Model C
20
Horizontal Concealed Unit Dimensions (in.) and Weights (lb)
Unit Size 02–03 04 06 08 10–12
A
B
C
D
E
F
Operating
Weight
Shipping
Weight
32-11/16”
21-5/16”
22-13/16”
19-3/8”
18-1/8”
19-5/16”
81
68
37-11/16”
26-5/16”
27-13/16”
24-3/8”
23-1/8”
24-5/16”
109
96
47-3/16”
35-13/16”
37-5/16”
33-7/8”
32-5/8”
33-13/16”
139
123
55-11/16”
44-5/16”
45-13/16”
42-3/8”
41-1/8”
43-5/16”
147
131
74-11/16”
63-5/16”
64-13/16”
61-3/8”
60-1/8”
61-5/16”
200
182
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 33 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
UNT-SVX07B-EN
Horizontal Cabinet, Model D
Dimensions and Weights
UNT-SVX07B-EN
Horizontal Cabinet Unit Dimensions (in.) and Weights (lb)
Unit Size
A
02–03
33-5/16”
04
38-5/16”
06
47-3/16”
08
56-5/16”
10–12
75-5/16”
D
E
F
B
C
G
H
J
Operating
Weight
Shipping
Weight
21-5/16”
7-5/8”
18”
17-1/4”
41-5/16”
8-5/8”
16”
19-3/4”
97
84
26-5/16”
7-1/8”
24”
22-1/4”
46-5/16”
8-1/8”
22”
23-3/4”
125
112
35-13/16”
8-7/8”
30”
31-3/4”
55-3/16”
9-7/8”
28”
31-3/4”
155
139
44-5/16”
7-1/8”
42”
40-1/4”
64-5/16”
8-1/8”
40”
39-3/4”
164
148
63-5/16”
7-5/8”
60”
59-1/4”
83-5/16”
8-5/8”
58”
59-3/4”
218
200
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 33 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
21
Dimensions and Weights
Horizontal Recessed, Model E
22
Horizontal Recessed Unit Dimensions
Unit Size 02–03 04 06
C
D
A
B
E
F
G
H
Operating
Weight
Shipping
Weight
35-13/16”
21-5/16”
40-13/16”
262-5/16”
22-13/16” 273-13/16”
19-3/8” 24-3/8”
18-1/8”
32-7/16”
23-1/8”
37-7/16”
34-5/16”
19-3/4”
39-5/16”
23-3/4”
78
68
88
78
50-5/16”
35-13/16”
37-5/16”
33-7/8”
32-5/8”
46-15/16”
48-13/16”
31-3/4”
128
118
08
48-13/16”
44-5/16”
45-13/16”
42-3/8”
41-1/8”
55-7/16”
57-5/16”
39-3/4”
139
129
253
243
Notes:
1. Coil connections are always on the drain pan side.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 33 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
6. Side View, Inlet option view gives dimensions for the telescoping panel.
10–12
77-13/16”
63-5/16”
64-13/16”
61-3/8”
60-1/8”
74-7/16”
76-5/16”
59-3/4”
UNT-SVX07B-EN
Vertical Wall Hung Cabinet, Model F (Force-Flo Units Only)
Dimensions and Weights
UNT-SVX07B-EN
Vertical Wall Hung Cabinet Unit Dimensions (in.) and Weights
(lb)
Unit Size 02–03 04 06 08 10–12
A
B
C
D
E
F
Operating
Weight
Shipping
Weight
33-5/16”
21-5/16”
7-5/8”
18”
19-5/16”
19-3/4”
97
84
38-5/16”
26-5/16”
7-1/8”
24”
24-5/16”
23-3/4”
125
112
47-13/16”
35-13/16”
8-7/8”
30”
33-13/16”
31-3/4”
155
139
56-5/16”
44-5/16”
7-1/8”
42”
42-5/16”
39-3/4”
164
148
75-5/16”
63-5/16”
7-5/8”
60”
61-5/16”
59-3/4”
218
200
Notes:
1. Coil connections are always opposite the control box side.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
23
Dimensions and Weights
Vertical Recessed, Model H
Vertical Recessed Unit Dimensions (in.) and Weights (lb)
Unit Size 02–03 04 06 08 10–12
E
F
G
H
A
B
C
D
J
Operating
Weight
Shipping
Weight
32-11/16”
21-5/16”
22-13/16”
17-5/16”
47”
30”
2-3/8”
42”
26-1/2”
78
68
37-11/16”
26-5/16”
27-13/16”
22-5/16”
51”
30”
2-3/8”
48”
26-1/2”
88
78
47-3/16”
35-13/16”
37-5/16”
31-13/16”
63”
30”
2-3/8”
57”
26-1/2”
128
118
55-11/16”
44-5/16”
45-13/16”
40-5/16”
65-1/2”
33-1/2”
4-1/8”
63”
27-1/2”
139
129
74-11/16”
63-5/16”
64-13/16”
59-5/16”
89-1/2”
33-1/2”
4-1/8”
87”
27-1/2”
253
243
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
24 UNT-SVX07B-EN
Vertical Slope Top, Model J
Dimensions and Weights
UNT-SVX07B-EN
Vertical Slope Top Unit Dimensions (in.) and Weights (lb)
Unit Size 02–03 04 06 08 10–12
C
D
A
B
E
F
Operating
Weight
Shipping
Weight
33-5/16”
21-5/16”
7-5/8”
18”
19-5/16”
41-5/16”
97
84
38-5/16”
26-5/16”
7-1/8”
24”
24-5/16”
46-5/16”
125
112
47-13/16”
35-13/16”
8-7/8”
30”
33-13/16”
55-13/16”
155
139
56-5/16”
44-5/16”
7-1/8”
42”
42-5/16”
64-5/16”
164
148
75-5/16”
63-5/16”
7-5/8”
60”
61-5/16”
83-5/16”
218
200
Notes:
1. Coil connections are always on the drain pan side and opposite the control box and unit control.
2. Coil connections are 5/8” O.D. sweat. See p. 30 and p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
25
Dimensions and Weights
Low Vertical Concealed, Model K
12-1/2 "
12-1/4 "
2-3/8 "
2-9/16 "
3-3/8 "
9-5/16 "
1-1/16
"
12-9/16"
2-11/16"
10-11/16"
1-1/8
"
1-13/16"
1-1/16
"
1-13/16
"
3-9/16
"
7-1/4 "
13-1/4
"
6-1/4
"
Low Vertical Concealed Unit Dimensions
(in.) and Weights (lb)
Unit Size 03 04 06
A
B
C
D
E
Operating
Weight
Shipping
Weight
41-7/16”
26-1/4”
27-15/16”
22-5/16”
24-1/4”
109
96
50-15/16”
35-3/4”
36-13/16”
31-13/16”
339-3/4”
139
123
59-7/16”
44-1/4”
45-15/16”
40-5/16”
42-1/4”
147
131
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
14-1/2
"
3-1/4
"
6-7/16 "
14-1/4 "
1-15/16
"
13-1/2 "
1-5/16
"
14 "
26 UNT-SVX07B-EN
Dimensions and Weights
Low Vertical Cabinet, Model L
10-15/16"
4-7/16"
8-1/2"
1-13/16"
10-15/16"
12-1/2"
12-1/4"
3-1/16"
2-3/8"
3-7/8"
7-1/2"
9 -13/16"
1-13/16"
13-3/16"
2-11/16"
3-1/4"
6-7/16"
11-5/16" 11-5/16"
1-5/16"
14-1/2"
1-1/8"
1-15/16"
13-1/2"
Low Vertical Cabinet Unit Dimensions (in.) and Weights (lb)
Unit Size
A
03
46-15/16”
04
56-7/16”
06
64-15/16”
B
C
D
E
Operating
Weight
Shipping
Weight
26-1/4”
11-7/16”
24”
24-1/4”
125
112
35-3/4”
13-5/16”
30”
33-3/4”
155
139
44-1/4”
11-7/16”
42”
42-1/4”
164
148
Notes:
1. Coil connections are always on the drain pan side and opposite the control box.
2. Coil connections are 5/8” O.D. sweat.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
5. Serviceability for some components within this unit may require panel or drain pan removal.
UNT-SVX07B-EN 27
Dimensions and Weights
Inverted Vertical Cabinet, Model M (Force-Flo Units Only)
28
Inverted Vertical Cabinet Unit Dimensions (in.) and Weights (lb)
Unit Size 02–03 04 06 08 10–12
C
D
A
B
E
F
Operating
Weight
Shipping
Weight
33-5/16”
21-5/16”
7-5/8”
18”
19-5/16”
19-3/4”
97
84
38-5/16”
26-5/16”
7-1/8”
24”
24-5/16”
23-3/4”
125
112
47-13/16”
35-13/16”
8-7/8”
30”
33-13/16”
31-3/4”
155
139
56-5/16”
44-5/16”
7-1/8”
42”
42-5/16”
39-3/4”
164
148
75-5/16”
63-5/16”
7-5/8”
60”
61-5/16”
59-3/4”
218
200
Notes:
1. Coil connections are always opposite the control box side.
2. Coil connections are 5/8” O.D. sweat. See p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
UNT-SVX07B-EN
Dimensions and Weights
Inverted Vertical Recessed, Model N (Force-Flo Units Only)
Inverted Vertical Recessed Unit Dimensions (in.) and Weights
(lb)
Unit Size 02–03 04 06 08 10–12
C
D
E
A
B
F
G
H
Operating
Weight
Shipping
Weight
27-7/8”
21-5/16”
22-13/16”
2-3/8”
47”
30”
26-1/2”
42”
78
68
32-7/8”
26-5/16”
27-13/16”
2-3/8”
51”
30”
26-1/2”
48”
88
78
42-3/8”
35-13/16”
37-5/16”
2-3/8”
63”
30”
26-1/2”
57”
128
118
50-7/8”
44-5/16”
45-13/16”
4-1/8”
65-1/2”
33-1/2”
27-1/2”
63”
139
129
69-7/8”
63-5/16”
64-13/16”
4-1/8”
89-1/2”
33-1/2”
27-1/2”
87”
253
243
Notes:
1. Coil connections are always opposite the control box side.
2. Coil connections are 5/8” O.D. sweat. See p. 31 for locations.
3. All duct collar dimensions are to the outside of the collar.
4. See p. 34 for dimensions for outside air openings.
UNT-SVX07B-EN 29
Dimensions and Weights
Fan-Coil Coil Connections, Vertical Units
Fan-Coil Coil Connections, Horizontal Units
30 UNT-SVX07B-EN
Force-Flo Coil Connections, Vertical Units
Dimensions and Weights
Force-Flo Coil Connections, Horizontal Units
UNT-SVX07B-EN 31
Dimensions and Weights
Force-Flo Coil Connections, Inverted Units
32 UNT-SVX07B-EN
Dimensions and Weights
Fresh Air Opening Locations, Horizontal Units—Models C, D, and E
Fresh air opening dimensions, horizontal units
Unit Size
A
B
02–03
1’ 6”
04
1’ 11”
06
2’ 8-1/2”
08
3’ 5”
10–12
5’ 0”
1’ 9-5/16” 2’ 2-5/16” 2’ 11-13/16” 3’ 8-5/16” 5’ 3-5/16”
UNT-SVX07B-EN 33
Dimensions and Weights
Fresh Air Opening Locations, Vertical Units—Models A, B, F, H, J, K, L, M, and N
Fresh air opening dimensions, vertical units
Unit Size
A
B
02–03
1’ 6”
04
1’ 11”
06
2’ 8-1/2”
08
3’ 5”
10–12
5’ 0”
1’ 9-5/16” 2’ 2-5/16” 2’ 11-13/16” 3’ 8-5/16” 5’ 3-5/16”
34 UNT-SVX07B-EN
Dimensions and Weights
Wall Box
1/8”
Continuous
Mortar Ribs
Top and
Bottom
1/8”
1/2”
3/4”
1/2”
4”
Clearance for
Drainage
1-3/8”
1/8”
Woven Aluminum
Insect Screen
Wall box dimensions
Unit Size, Ref. only Dimensions A x B Internal Supports
02–03 24-3/8 x 4- 3/4 1
04
06
24-3/8 x 7-1/2
33-1/8 x 7-1/2
1
2
08
10–12
37-1/2 x 7-1/2
58-1/4 x 7-1/2
3
4
Continuous Drip Lip
Top and Bottom
Additional Internal
Supports Equally Spaced
Not to Exceed 12” O.C.
5/8”
UNT-SVX07B-EN 35
Dimensions and Weights
Projection Panel
Unit to Wall—Top View
Front View ISO
Rear View ISO
Projection panel dimensions
Unit Size
A
B
02–03
3’ 11”
2’ 6”
04
4’ 3”
2’ 6”
Projection panel, all unit sizes
C
D
E
2”
1-1/8”
8-5/8”
2-1/2”
1-5/8”
8-1/8”
06
5’ 3”
2’ 6”
3”
2-1/8”
7-5/8”
08
5’ 5-1/2”
2’ 9-1/2”
10–12
7’ 5-1/2”
2’ 9-1/2”
3-1/2”
2-5/8”
7-1/8”
4”
3-1/8”
6-5/8”
4-1/2”
3-5/8”
6-1/8”
5”
4-1/8”
5-5/8”
5-1/2”
4-5/8”
5-1/8”
6”
5-1/8”
4-5/8”
2”
1-1/8”
8-5/8”
36 UNT-SVX07B-EN
Installation—Mechanical
Duct Connections
Install all air ducts according to National Fire Protection Association standards for the Installation of Air Conditioning and Ventilating Systems (NFPA 90A and 90B).
Install all air ducts according to the National Fire Protection Association standards for the
“Installation of Air Conditioning and Ventilation Systems other than Residence Type (NFPA 90A) and Residence Type Warm Air Heating and Air Conditioning Systems (NFPA 90B).
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
The unit’s airflow configuration varies dependent on the model and options ordered. A one-inch duct collar is provided on units with a ducted return and/or discharge to attach ductwork to the unit.
Trane recommends using galvanized sheet metal ductwork with fan-coil and cabinet heater units.
Slide the sheetmetal duct over the duct collar flange of the unit, seal the joint and fasten with sheetmetal screws.
Note:
Do not run screws through the removable front panel on concealed units.
Ductwork Recommendations
Follow the general recommendations listed below when installing ductwork for the unit.
1.
Discharge ductwork should run in a straight line, unchanged in size or direction, for a minimum equivalent distance of three fan diameters from the unit (approximately 20 inches).
2. When making duct turns and transitions avoid sharp turns and use proportional splits, turning vanes, and air scoops when necessary.
3. When possible, construct, and orient supply ductwork turns in the same direction as the fan rotation.
Piping Considerations
Hydronic Coil Piping
Before installing field piping to the coil, consider the following .
• All coil connections are 5/8-inch O.D. (or 1/2-inch nominal) female copper connections.
• The supply and return piping should not interfere with the auxiliary drain pan or condensate line. See “Connecting the Condensate Drain” section for more detailed information.
• The installer must provide adequate piping system filtration and water treatment.
• Exterior condensate may be an issue (fan-coils only) if field piping does not have a control valve. Refer to the supply and return header locations in the “Dimensions and Weights” section.
Note:
When using a field supplied piping package in a fan-coil unit, allow sufficient room to install the auxiliary drain pan. In addition, piping package must not extend over edges of auxiliary drain pan.
Connecting Field Piping to Coil
1.
Remove the auxiliary drain pan, if it is in place, to prevent exposureto dripping solder or excessive temperatures.
UNT-SVX07B-EN 37
Installation—Mechanical
2. Slide a 1/2-inch sweat connection coupling (installer provided) onto the coil headers.
Note:
For vertical fan-coil units, push the main condensate drain hose and overflow condensate drain hose through the inside of the chassis end panel to prevent them from getting burned when making sweat connections. Be sure to pull the hoses back through and route to the auxiliary drain pan when the end panel has cooled.
3. Solder the joint using bridgit lead-free solder (ASTM B32-89) to provide a watertight connection. Avoid overheating factory soldered joints when soldering field connections to the coil to prevent leakage from occurring.
4. Insulate all piping to coil connections as necessary after connections are complete.
Note:
Maintain a minimum distance of one foot between the reduction fitting for the
1
/
2
-inch diameter line and the fan-coil unit piping connections.
5. Install the optional auxiliary drain pan, which ships in the accessory packet.
Water Piping Connections to Factory-Installed Piping Package
Before installing water piping supply and return lines to factory piping package, note the following items.
• All piping connections are 5/8-inch O.D. (1/2-inch nominal) female copper connections.
• The fan-coil supply and return piping should not interfere with the auxiliary drain pan or condensate line. See “Condensate Drain,” p. 38 for more information.
• The installer must provide adequate piping system filtration and water treatment.
• If the unit has a factory deluxe piping package, the piping includes a strainer with a 20-mesh size screen, which allows minimal protection from debris. Therefore, clean the strainer regularly.
Note:
Maintain a minimum distance of one foot between the reduction fitting for the
1
/
2
-inch diameter line and the fan-coil piping connections.
1.
The factory piping package ships with brackets to adequately support the piping during shipment. Remove these brackets before connecting water piping to the unit.
2. Close the piping end valves to the fully open position to prevent damage to the valve seat during brazing.
3. Remove the auxiliary drain pan, if it is in place, to prevent exposure to dripping solder or excessive temperatures.
4. Solder water piping connections to supply and return end connections. Avoid overheating factory soldered joints to prevent the possibility of leakage.
5. Insulate fan-coil piping to auxiliary drain pan connections and any piping that is not above the auxiliary drain pan.
Condensate Drain
1.
De-burr the pipe end before making the connection to the drain pan.
2. Connect a 7/8-inch O.D. copper pipe or tube, with a 0.20 inch wall thickness, to the auxiliary drain pan. This should be a mechanical connection that allows easy removal of the auxiliary drain pan when servicing the piping end pocket.
3. Slide the copper pipe over the drain pan nipple and tighten the collar on the pipe with a hose clamp (installer supplied).
Maintain a continuous drain line pitch of one inch per ten feet of drain line run to provide adequate condensate drainage. Extend the drain line straight from the drain pan a minimum distance of six inches before making any turns. The installer must provide proper support for the drain line to prevent undue stress on the auxiliary drain pan.
38 UNT-SVX07B-EN
Installation—Mechanical
Install a secondary overflow drain line if necessary by punching out the overflow drain nipple on the auxiliary drain pan. Next, place a
3
/
8
-inch inside diameter flexible plastic tube over the nipple and secure with a field supplied hose clamp.
Note:
The installer is responsible for adequately insulating field piping. See the “External
Insulating Requirements section for more information.
Condensate Overflow Detection Device
The condensate overflow detection device is an option on fan-coil units with either a Tracer ZN010,
ZN510, ZN520, or the customer-supplied control interface. The float switch, mounting bracket, and coiled leads ship attached inside the piping end pocket of the unit. Install the switch by placing the hole or slot in the bracket over the condensate overflow drain (of the auxiliary drain pan) with the switch float extending over the pan. Secure the drain pan by attaching the pan’s bracket with the factory provided clip. See Figure 3 and Figure 4 .
Figure 3.
Condensate float switch installed in horizontal auxiliary drain pan
Figure 4.
Condensate float switch installed in vertical auxiliary drain pan
UNT-SVX07B-EN
Automatic Changeover Sensor
Two-pipe changeover units with either the Tracer ZN010, ZN510, and ZN520 controls have an automatic changeover sensor that determines heating or cooling mode based on the supply water temperature. On units with a factory piping package, the factory straps the changeover sensor to the piping supply water pipe. See Figure 5, p. 40 and Figure 6, p. 40 .
39
Installation—Mechanical
Figure 5.
Attach the changeover sensor to the entering water pipe as shown for changeover to work properly
Figure 6.
Close-up view of the changeover sensor
40
If the unit does not have a factory piping package, the factory attaches the sensor and coiled lead wires to the piping side end panel. The installer should attach the sensor parallel to and in direct contact with the supply water pipe.
Note:
The installer is responsible to ensure the changeover sensor is installed in a location that can sense active water temperature. Otherwise, the unit may fail to sense the correct operating mode and disable temperature control.
When using field supplied three-way valves, install the changeover sensor upstream of the valve on the supply water pipe. When using field supplied two-way control valves, install the changeover sensor in a location that will detect active water temperature.
The unit must always be able to sense the correct system water temperature, regardless of the control valve position.
Note:
The maximum length of the automatic changeover wire cannot exceed ten feet from the control panel. If the sensor extends beyond the unit chassis, use shielded conductors to eliminate radio frequency interference (RFI).
Automatic Electric Heat Lockout Switch
Two-pipe fan-coil units with auxiliary electric heat have an automatic electric heat lockout switch that disengages the electric heat when hydronic heat enables. If the unit has a factory piping package and electric heat, the factory attaches the switch to the supply water pipe. When the lockout switch detects the supply water temperature above 95°F, it disengages the electric heat. This eliminates electric heat and hydronic heat working simultaneously.
UNT-SVX07B-EN
UNT-SVX07B-EN
Installation—Mechanical
If the fan-coil unit does not have a factory piping package, the switch and coiled lead wires ship inside the piping side end panel. The installer should position the lockout switch on the supply water line of the unit by sliding its spring connector over the pipe. See Figure 7 .
Figure 7.
Electric heat lock out switch installed
Venting the Hydronic Coil
The hydronic coil contains a vent, either manual or automatic, to release air from the unit. This vent is not sufficient for venting the water piping system in the building.
The coil air vent is on the piping side, above the coil connections on the unit. See Figure 8 and
Figure 9 . Perform the following steps to vent the coil after installing the unit.
Figure 8.
Manual coil air vent with set screw
41
Installation—Mechanical
Figure 9.
Manual coil air vent with Shrader fitting
42
1.
Pressurize the building piping system with water and vent any trapped air at system vents.
2. For units with manual air vents, back the set screw out to expel air from the unit and then retighten the set screw.
The automatic air vent should require no adjustment for the coil to vent. However, if the coil does not vent immediately, unscrew the outer portion of the fitting to expel air from the port.
If debris has become trapped in the vent, completely remove the outer portion of the fitting and clean.
External Insulating Requirements
Insulate and vapor seal surfaces colder than surrounding air dew-point a to prevent unplanned condensation. Trane recommends field-insulation of the following areas to prevent potential condensate problems:
1.
Supply and return water piping connections
2. Condensate drain lines and connections
3. Fresh air intake duct connections
4. Discharge duct connections
5. Wall boxes
Balancing The Manual Circuit Setter Valve
The manual circuit setter valve is an optional end valve supplied on the return pipe of the factory piping package. The valve allows the operator to regulate water flow through the hydronic coil, balance the water flow through the unit with other units in the piping system, and serves as a shutoff or end valve. See Figure 10 .
UNT-SVX07B-EN
Figure 10. Manual circuit setter valve
Figure 11. Automatic circuit setter valve
Installation—Mechanical
Figure 12. Automatic circuit setter valve
UNT-SVX07B-EN
Perform the following procedure to set maximum water flow through the coil:
1.
Establish water flow through the coil. Perform an open override of the valve if the control valve is closed to the coil, either manually or by Tracer.
If the piping package has two-position, normally closed valves: Drive open the valve using a
24 V signal.
If the piping package has two-position, normally open valves: Manually drive open the valve by removing power to the valve.
43
Installation—Mechanical
If the piping package has modulating valves: To manually drive the valve open, depress the button stem on top of the valve and push the lever located on the side of the valve to the full open position.
2. For presetting, use the appropriate valve curve shown in Figure 13, p. 45 to determine which setting is necessary to achieve the appropriate pressure drop. The “M” line is the appropriate line.
3. Carefully remove the Schrader pressure port connection caps on the manual circuit setter, since they will be at the same temperature as the pipeline.
4. Bleed all air from the hoses and meter before reading the pressure drop. Refer to the gauge operating instructions.
5. Adjust the circuit setter valve by turning the valve stem until the appropriate pressure drop is achieved.
6. After achieving the proper setting, slightly loosen the two socket head cap screws and rotate the memory stop around until it touches the back side of the indicator. Then tighten the screws to securely set the open memory position. The memory stop indicates the last set open position.
7.
If using a three-way valve: close the control valve to the coil, with the differential pressure meter still connected. This will divert flow to the bypass side of a three-way valve.
Adjust the balancing fitting to obtain the same pressure drop across the circuit setter valve as in step two when the control valve was open to the coil.
44 UNT-SVX07B-EN
Figure 13. Manual circuit setter valve, differential pressure vs. flow
Installation—Mechanical
UNT-SVX07B-EN 45
Installation—Mechanical
Note:
Instructions for using this chart appear on the preeding page. For the manual circuit setter provided with fan-coil or Force-Flo units, use the ‘M’ .
NOTICE
Coil Damage!
In all steam coil installations, the condensate return connections must be at the low point of the coil to ensure condensate flows freely from the coil at all times. Failure to do so could cause physical coil damage from water hammer, unequal thermal stresses,freeze-up and/or corrosion.
1.
Make piping connections to the steam coil as shown in Figure 15 . Cap the unused connection.
2. The coil is already pitched within the unit to provide proper pitch to drain condensate out of the coil. Verify that the unit has been properly leveled.
3. Install a 1/2-inch, 15-degree swing check vacuum breaker in the unused condensate return tapping as close as possible to the coil.
4. Vent the vacuum breaker line to atmosphere or connect it into the return main at the discharge side of the steam trap.
5. Pitch all steam supply and return mains down a minimum of one inch per ten feet in the direction of flow.
6. Do not drain the steam mains or take-off through the coils. Drain the mains ahead of the coils through a steam trap to the return line.
7.
Overhead returns require one psig of pressure at the steam trap discharge for each two-feet elevation to ensure continuous condensate removal.
8. Proper steam trap selection and installation is necessary for satisfactory coil performance and service life. For installation, use the following steps: a. Position the steam trap discharge at least 12 inches below the condensate return connection.
This provides sufficient hydrostatic head pressure to overcome trap losses and ensure complete condensate removal.
b. Trane recommends using flat and thermostatic traps because of gravity drain and continuous discharge operation.
c. Use float and thermostatic traps with atmospheric pressure gravity condensate return, with automatic controls or where the possibility of low pressure supply steam exists.
d. Always install strainers as close as possible to the trap inlet side. Reference Figure 14 for an example of a properly piped steam coil.
46 UNT-SVX07B-EN
Installation—Mechanical
Figure 14. Typical piping for steam coils
Code of System Components in Piping Diagram
FT Float and thermostatic steam trap
BT Bucket steam trap
GV Gate valve
OV Automatic two-position (on-off) control valve
TV Automatic three-way control valve
VB Vacuum breaker
CV Check valve
ST Strainer
AV Automatic or manual air vent
Figure 15. Main steam coil connection diagram
v ac uum bre a ker ( if des i red) ste a m supply plugged c ondens a te return
UNT-SVX07B-EN 47
Installation—General
Installing the Unit
Follow the procedures below to install the unit properly. Refer to “Dimensions and Weights,” p. 14 for specific unit dimensions and mounting hole locations.
Vertical Units
NOTICE
Electrical Wiring!
Do not allow electrical wire to fall between the unit and installation surface. Failure to comply may result in electrical shorts or difficulty accessing wires.
Install vertical units in an upright position using the 5/8-inch diameter double key slot hanger holes, located on the back of unit. The hanger holes allow a maximum shank size of 5/16-inch diameter threaded rods or lag screws (installer provides).
1.
Prepare wall openings for recessed units. Reference unit submittal for each unit size dimensions. When installing vertical units, consideration should be given for units with an outside air intake.
2. If the unit has leveling legs, adjust them correctly to level unit.
3. Mark the position of the keyslot hanger holes on the wall according to the dimensions given in “Dimensions and Weights,” p. 14 for each unit model and size. Align the hole locations evenly.
4. Insert the threaded rods or lag screws in the wall before setting the unit in place.
5. Remove the front panel (cabinet unit only) by lifting it upward.
6. Position the hanger holes, located on the back of the unit, over the rod or lag screw heads, pushing the unit downward to properly position.
7.
Complete piping and wiring connections, in addition to any necessary ductwork to the unit as instructed in the following sections. Ensure that the auxiliary drain pan is in position on fan-coil units.
8. Install the front panel before starting the unit.
On cabinet units, replace the front panel by aligning the bottom tabs on the unit with the respective slots on the panel bottom. Slide the front panel down onto the tabs while holding the panel close as possible to the cabinet. While the bottom tabs are engaged, slide the front panel upward enough to allow the top engaging edge of the front panel to lap over the engaging edge of the unit. This should allow the panel to drop down and lock into position.
On recessed units, install the front panel by aligning and locking together the interlocking support channel of the panel and unit. While holding the panel against the unit, tighten the screws at the top of the panel until it fits tight against the unit’s front. Do not over tighten the screws.
NOTICE
Motor Overload!
All unit panels and filters must be in place prior to unit startup. Failure to have panels and filters in place may cause motor overload.
Horizontal Units
Install horizontal units suspended from the ceiling using the four 5/8-inch diameter double key slot hanger holes, located on the top of the unit. The hanger holes allow a maximum shank size of
5/16-inch diameter threaded rods or lag screws (installer provided). Follow the installation procedure below.
48 UNT-SVX07B-EN
Installation—General
Note:
Follow the requirements of National Fire Protection Association (NFPA) Standard 90A or
90B, concerning the use of concealed ceiling spaces as return air plenums.
1.
Prepare the ceiling opening for recessed units. Reference the unit submittals for dimensions.
2. Position and install the suspension rods or a suspension device (supplied by installer) according to the unit model and size in “Dimensions and Weights,” p. 14 .
3. On cabinet units, remove the bottom panel by using a 5/32-inch Allen wrench to unscrew fasteners. Swing the panel down and lift outward.
4. Level the unit by referencing the chassis end panels. Adjust the suspension device.
5. Complete piping and wiring connections, in addition to any necessary ductwork as instructed in the following sections. Ensure that the auxiliary drain pan is in position on fan-coil units.
6. Install the bottom panel before starting the unit.
7.
Ensure condensate drain line is pitched one inch per ten feet of pipe away from the fan-coil unit.
Cabinet Units
Install the bottom panel by placing the hinged end on the unit’s hinged end (always at the return end of the unit). Refer to “Dimensions and Weights,” p. 14 for keyslot hanger hole locations. Swing the panel upward into position. Secure the panel with the fasteners provided. Do not overtighten the fasteners.
Recessed Units
Refer to “Dimensions and Weights,” p. 14 for mounting locations and unit weights. Follow the procedure below and see Figure 16, p. 50 .
1.
Insert the mounting bolts through the panel brackets of the trim ring and secure to the hanger holes on the unit. Tighten the mounting bolts to pull the trim ring snug against the finished ceiling.
2. Install the bottom panel by placing the hinged end on the trim ring hinged end (always at the unit’s return end).
3. Adjust the expansion collar’s inner duct (only on fan-coil units with a bottom return) to ensure a tight fit against the insulation located on the perimeter of the bottom panel’s return louver.
4. Close the s-hook on each end of safety chain assembly. Insert s-hooks through holes in unit and door. Close s-hook on door.
5. Insert retaining screws through bottom panel door and place retaining rings on screws.
6. Swing the bottom panel upward into position. Hook the safety chain to the bottom panel and the unit. Tighten the panel to the unit with the fasteners provided.
NOTICE
Unit Leveling!
All unit panels and filters must be in place prior to unit start-up. Failure to have panels and filters in place may cause motor overload.
UNT-SVX07B-EN 49
Installation—General
Figure 16. Installing the trim ring assembly on horizontal recessed units
Notes:
•
The trim ring assembly cannot accomodate unlevel ceilings.
•
On sizes 8, 10, and 12 center installation position and use 2- or 3.5-inch bolts, whichever is best suited for installation. Also, install two safety chains assemblies on these sizes.
•
Expansion collar is furnished with fan-coil with bottom return only. The collar is not necessary for Force-Flo units.
Installation Checklist
The following checklist is only an abbreviated guide to the detailed installation procedures given in this manual. Use this list to ensure all necessary procedures are complete. For more detailed information, refer to the appropriate sections in this manual.
50 UNT-SVX07B-EN
UNT-SVX07B-EN
Installation—General
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
1.
Inspect the unit for shipping damage.
2. Level installation location to support the unit weight adequately. Make all necessary wall or ceiling openings to allow adequate air flow and service clearances.
3. Ensure the unit chassis is installed level.
NOTICE
Unit Leveling!
The unit must be installed level (zero tolerance) in both horizontal axis for proper operation. Do not use the coil or drain pan as the reference point because the coil may be pitched and the drain pan has an inherent positive slope to provide proper drainage.
4. Verify that wall and ceiling openins are properly cut per the unit submittals.
5. Verify that installation of horizontal concealed units meets the national Fire Protection
Association (N.F.P.A.) Standard 90A or 90B concerning the use of concealed ceiling spaces as return air plenums. Verify correct ceiling opening dimensions on unit submittals.
Secure the unit and any accessory items properly to the wall or ceiling support rods.
6. Complete all piping connections correctly.
7.
Check field sweat connections for leaks and tighten the valve stem packing, and piping pkg unions if necessary.
8. Install the auxiliary drain pan properly under piping package on fan-coil units.
9. Complete condensate drain line connections on fan-coil units.
10. Pitch condensate drain line away from fan-coil one-inch drop per ten feet of pipe.
11. Install automatic changeover sensor option on the supply water line, if applicable.
12. Install automatic electric heat lockout switch option on the supply water line, if applicable.
13. Install condensate overflow switch option correctly on the auxiliary drain pan, if applicable.
14. Ensure the low temperature detection device option is correctly installed.
15. Complete all necessary duct connections.
16. Complete all interconnection wiring for the wall-mounted fan mode switch or zone sensor per the wiring schematic and guidelines established in “Wall-Mounted Control
Interconnection Wiring,” p. 60 .
17. Install the wall-mounted fan mode switch, or zone sensor module options properly.
For wireless zone sensors, be sure to set the address (see “Address Setting,” p. 68 ).
18. Connect electrical supply power according to the NEC and unit wiring diagrams.
19. Remove any miscellaneous debris, such as sheetrock dust, that may have infiltrated the unit during construction.
20. Replace the air filter as required.
51
Installation—Controls
Control sensor options include both unit-mounted (factory-installed) and wall-mounted sensors.
Installation instructions for the wall-mounted sensors are provided in this chapter.
General Information
Control Options (Including Factory-Installed)
Tracer ZN010 Options
Unit-mounted zone sensor:
Digit 30 = E and Digit 31 = V
X13790843-01
Tracer ZN510 and ZN520 Options
Wall-mounted zone sensor:
Digit 30 = F or G and Digit 31 = 1
X13511530-01 (wall)
X13651467-02 (comm)
Wall-mounted zone sensor:
Digit 30 = E and Digit 31 = W
X13790841-01
Wall-mounted zone sensor:
Digit 30 = F or G and Digit 31 = 2
X13790842-01 (wall)
X13651467-02 (comm)
Split-mounted zone sensor, unit-mounted fan mode and wall-mounted setpoint dial:
Digit 30 = E and Digit 31 = X
X13511529-01 (wall)
X13790849-01 (unit)
Split-mounted zone sensor, unit-mounted fan mode and wall-mounted setpoint dial:
Digit 30 = F or G and Digit 31 = Y
X13511527-01 (wall)
X13790849-01 (unit)
X13651467-02 (comm)
Unit-mounted zone sensor:
Digit 30 = F or G and Digit 31 = Z
X13790844-01
52 UNT-SVX07B-EN
Installation—Controls
Tracer ZN510 and ZN520 Options (continued)
Wall-mounted wired display sensor with setpoint adjustment:
Digit 30 = F or G and Digit 31 = 4
X13790886-04 (wall)
Wall-mounted wireless temperature sensor (WTS)
(setpoint adjustment, no fan speed adjustment) and unit-mounted receiver:
Digit 30 = F or G and Digit 31 = 6
X13790821-01 (wall)
X13790860-02 (unit)
Wall-mounted wireless display sensor (WDS) and unit-mounted receiver:
Digit 30 = F or G and Digit 31 = 7
X13790822-04 (wall)
X13790860-02 (unit)
Installing Wall-Mounted Wired Sensors
Reference the wall-mounted zone sensor dimensions in Figure 17, p. 54 . Position the sensor on an inside wall three to five feet above the floor and at least 18 inches from the nearest outside wall.
Installing the sensor at a lower height may give the advantage of monitoring the temperature closer to the zone, but it also exposes the sensor to airflow obstructions. Ensure that air flows freely over the sensor.
UNT-SVX07B-EN 53
Installation—Controls
Figure 17. Wall-mounted zone sensor dimensions
0.31 in (8 mm)
TYP R.07 in (R1.9) mm
2.9 in (73.5 cm)
TYP 0.24 in (6 mm)
1.08 in (27.5 mm)
0.12 in (3 mm)
54
3.39 in (86 mm)
4.68 in (118.9 mm)
0.63 in (15.9 mm)
1.45 in (36.8 mm)
2.48 in (63 mm)
2.62 in (66.5 mm)
Sensor
When selecting a sensor location, avoid the following:
• Areas of direct sunlight
• Areas in the direct airstream of air diffusers
• Exterior walls and other walls that have a temperature differential between the two sides
• Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heat-generating equipment
• Drafty areas
• Dead spots behind doors, projection screens, or corners
• Walls that are subject to high vibration
• Areas with high humidity
• High traffic areas (to reduce accidental damage or tampering)
• Metal barriers between the receiver and the sensor (for example, plastered walls with metal lathe or metal roof decks)
• Thick, solid concrete walls between the receiver and the sensor
• Placing the sensor inside metal enclosures
UNT-SVX07B-EN
Installation—Controls
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 inches above the floor.
If a parallel approach by a person in a wheelchair is required, reduce the maximum height to
48 inches.
Note:
Consult section 4.27.3 of the 2002 ADA (Americans with Disability Act) guideline, and local building codes, for further details regarding wheelchair requirements.
Mounting Surfaces
Using the hardware provided, mount the back plate of the sensor to a flat surface such as sheetrock or plaster, or an electrical junction box. The sensor must be mounted plumb for accurate temperature control and to ensure proper air movement through the sensor.
• If mounting onto sheetrock or plaster, use the plastic threaded anchors (pre-drilling holes is not usually necessary) and the two M3.5 x 20 mm mounting screws.
• For mounting onto an electrical junction box, use the two 6-32 x 3/4 in. screws.
Before beginning installation, consider the location considerations below. Also, refer to the unit wiring schematic for specific wiring details and point connections.
Location Considerations
Avoid mounting the sensor in an area subject to the following conditions:
• Dead spots, such as behind doors or in corners that do not allow free air circulation.
• Air drafts from stairwells, outside doors, or unsectioned hollow walls.
• Radiant heat from the sun, fireplaces, appliances, etc.
• Airflow from adjacent zones or other units.
• Unheated or uncooled spaces behind the controller, such as outside walls or unoccupied spaces.
• Concealed pipes, air ducts, or chimneys in partition spaces behind the controller.
Fan Mode Switch Installation
The fan mode switch ships loose inside the unit accessory bag. Follow the steps below to install the fan mode switch.
Items needed:
2 x 4 electrical junction box
1.
Remove the brown wire if not using a field-supplied damper.
2. Remove the terminals, cut and strip wires as required for installation.
3. Level and position a 2 x 4 electrical junction box.
4. Follow the instructions given in “Wall-Mounted Control Interconnection Wiring,” p. 60 and route the wires as shown in the wiring diagram. Refer to the typical wiring diagram or to the unit specific diagram on the unit.
5. Position the fan mode switch over the junction box with the two screws supplied.
Wired Zone Sensor Installation
Follow the procedure below to install the wired zone sensor module.
1.
Note the position of the setpoint adjustment knob and gently pry the adjustment knob from the cover using the blade of a small screwdriver.
2. Insert the screwdriver blade behind the cover at the top of the module and carefully pry the cover away from the base.
3. To mount the sensor back plate:
UNT-SVX07B-EN 55
Installation—Controls
a. Hold the back plate against the mounting surface and mark the screw locations.
b. Secure the back plate against the mounting surface using included hardware.
4. To install the zone sensor module to a standard junction box: a. Level and install a 2“ x 4” junction box (installer supplied) vertically on the wall.
b. Pull the control wires through the cutout. Attach the module to the wall using the screws provided.
5. Strip the insulation on the interconnection wires back 0.25-inch and connect to TB1.
6. Screw down the terminal blocks.
7.
To replace the cover: a. Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover until it snaps in place.
b. Install the security screw into the bottom of the cover (if desired).
If installing a Tracer ZN510 or Tracer ZN520 zone sensor, see “Tracer ZN510 and ZN520 Options,” p. 52 and p. 53 for more information.
Installing Wall-Mounted Wireless Zone Sensors
General Information
This section provides a description of the sensors, as well as part numbers and dimensions.
Product Description
Trane
®
wireless sensor sets are compatible with any Trane unit controller that uses a standard 10 k
Ω
temperature input. The sets include sensor, receiver, wiring harness, and two AA lithium batteries. No further software or hardware is necessary for site evaluation, installation, or maintenance. Zone temperature is standard on all models.
Note:
A service tool cannot be connected to a Trane wireless sensor.
Trane wireless sensors include the following models:
Wireless Display Sensor (Model WDS)
This configurable sensor has an LCD display. It provides the same functions as many currently available Trane wired sensors. Configurable features for fan-coils include:
• Temperature units: Fahrenheit (ºF) or Celsius (ºC)
• Temperature resolution: 1.0, 0.5, or 0.1 degrees
• Ability to display setpoint only (zone temperature does not display)
• Single or no setpoint
• Fan settings: high, medium, low, auto, off
• Timed override request function
• Lockable settings to protect agains unauthorized use
• Service pin request
Wireless Temperature Sensor (Model WTS)
This sensor measures and transmits the zone temperature only.
Dimensions
The following illustration provides specific dimension details. The dimensions are the same for all wireless sensor models.
56 UNT-SVX07B-EN
Installation—Controls
0.31 in (8 mm)
TYP R.07 in
(R1.9 mm)
2.9 in (73.5 mm)
0.12 in (3 mm)
TYP 0.24 in (6 mm)
1.08 in (27.5 mm)
3.39 in (86 mm)
4.68 in (118.9 mm)
0.63 in (15.9 mm)
1.45 in (36.8 mm)
2.62 in (66.5 mm)
Location Considerations
Placement of the sensor is critical to proper operation (the receiver is factory mounted on fan-coil units). For most installations, barriers limit proper radio signal strength more than distance. For best radio transmission range and reliability, mount the receiver and sensor in line of sight. Where this is not possible, try to minimize the number of barriers between the pair of devices. In general, sheetrock walls and ceiling tiles offer little restriction to the transmission of the radio signal throughout the building.
The transmission range for the sensor is as follows:
• Open range: 2,500 ft (762 m) (packet error rate = 2%)
• Usable range: 200 ft (61 m)
• Typical range: 75 ft (23 m)
Mounting the Sensor Back Plate
To mount the sensor back plate:
1.
Hold the back plate against the mounting surface and mark the screw locations.
2. Secure the back plate against the mounting surface using included hardware.
The following figure shows an example of mounting the back plate of the sensor into sheetrock or plaster.
UNT-SVX07B-EN 57
Installation—Controls
Replacing the Sensor Cover
To replace the cover:
1.
Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover until it snaps in place.
2. Install the security screw into the bottom of the cover (if desired).
58
Security screw
UNT-SVX07B-EN
Installation—Electrical
Unit Wiring Diagrams
Specific unit wiring diagrams, based on unit options ordered, are provided inside each unit and can be easily removed for reference. Use these diagrams for connections or trouble analysis. Wiring diagrams are attached on the inside of the front panel of vertical cabinet and recessed models and on the fan and motor panel of vertical concealed and all horizontal models.
Supply Power Wiring
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Refer to the unit nameplate to obtain the minimum circuit ampacity (MCA) and maximum fuse size
(MFS) or maximum circuit breaker (MCB) to properly size field supply wiring and fuses or circuit breakers.
Refer to the unit operating voltage listed on the unit wiring schematic, submittal, or nameplate.
Reference the wiring schematic for specific wiring connections.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Note:
All field wiring should conform to NEC and all applicable state and local code requirements.
The control panel box is always on the end opposite the piping connections. Access the control box by removing the two screws that secure the front cover. This will allow the panel to be removed, to provide access to the electrical components.
WARNING
Hazardous Electrical Shorts!
Insulate all power wire from sheet metal ground. Failure to do so may cause electrical shorts that could result in death or serious injury.
If the unit does not have a disconnect switch, the power leads and capped ground wire are inside the control panel.
If the unit has a disconnect switch, the power leads are wired to the junction box switch on the control panel. Pull the capped ground wire into the junction box.
Electrical Grounding Restrictions
All sensor and input circuits are normally at or near ground (common) potential. When wiring sensors and other input devices to the Tracer controller, avoid creating ground loops with grounded conductors external to the unit control circuit. Ground loops can affect the measurement accuracy of the controller.
UNT-SVX07B-EN 59
Installation—Electrical
NOTICE
Equipment Damage!
Unit transformer IT1 provides power to fan-coil unit only. Field connections to the transformer
IT1 may create immediate or premature unit component failure.
All input/output circuits (except isolated relay contacts and optically isolated inputs) assume a grounded source, either a ground wire at the supply transformer to control panel chassis, or an installer supplied ground.
Wall-Mounted Control Interconnection Wiring
The installer must provide interconnection wiring to connect wall-mounted devices such as a fan mode switch or zone sensor module.
Refer to the unit wiring schematic for specific wiring details and point-to-point wiring connections.
Dashed lines indicate field wiring on the unit wiring schematics. All interconnection wiring must conform to NEC Class 2 wiring requirements and any state and local requirements.
Refer to Table 3 for the wire size range and maximum wiring distance for each device.
Table 3.
Maximum wiring distances for low voltage controls (ft)
Fan Speed Switch
Zone Sensor
14–22 AWG
16–22 AWG
500
200
Recommendation: Do not bundle or run interconnection wiring in parallel with or in the same conduit with any high-voltage wires (110 V or greater). Exposure of interconnection wiring to high voltage wiring, inductive loads, or RF transmitters may cause radio frequency interference (RFI).
In addition, improper separation may cause electrical noise problems. Therefore, use shielded wire
(Beldon 83559/83562 or equivalent) in applications that require a high degree of noise immunity.
Connect the shield to the chassis ground and tape at the other end.
Note:
Do not connect any sensor or input circuit to an external ground connection.
Table 4.
Low vertical free-discharge motors, 115 volt
Size
03
04
FLA
0.7
0.8
HP (kW)
0.03 (0)
0.03 (0)
H
RPM
1090
M 770
L
H
560
1090
M 750
L 560
06 1.1
0.03 (0) H 1115
M 760
L 560
Note:
Actual rpm will vary with application and configuration
Table 5.
Decimal to fractional HP (kW) conversion
FC
02
Decimal
0.03
Fraction
1/30
03
0.07
0.04
0.05
0.08
1/15
1/25
1/20
1/12
Note:
Fractional HP (kW) values are approximate values and not necessarily actual HP (kW).
60 UNT-SVX07B-EN
UNT-SVX07B-EN
Installation—Electrical
Table 5.
Decimal to fractional HP (kW) conversion (continued)
FC Decimal Fraction
04
06
0.05
0.06
0.10
0.13
0.07
0.12
0.16
0.24
1/20
1/16
1/10
1/8
1/15
1/8
1/6
1/4
08
10
12
0.05
0.06
0.10
0.13
0.05
0.06
0.10
0.12
0.13
0.24
0.07
0.12
0.16
0.24
0.12
0.13
0.24
1/20
1/16
1/10
1/8
1/20
1/16
1/10
1/8
1/8
1/4
1/15
1/8
1/6
1/4
1/8
1/8
1/4
0.13
0.24
1/8 1/4
Low Vertical - 03, 04, 06 0.03
1/30
Note:
Fractional HP (kW) values are approximate values and not necessarily actual HP (kW).
Table 6.
Free-discharge motors on units with two-row, electric, or steam coils
Unit
Size
02
FLA
0.60
115 Volt hp (kW)
0.03 (0.02)
208–230 Volt
FLA hp (kW)
0.3
0.03 (0.02)
277–480 Volt
FLA hp (kW)
0.2
0.03 (0.02)
H
980
03
04
06
08
10
0.70
0.90
1.20
1.40
0.90
1.20
0.04 (0.02)
0.05 (0.04)
0.07 (0.05)
0.12 (0.09)
0.05 (0.04)
0.07 (0.05)
0.4
0.5
0.6
0.9
0.5
0.6
0.04 (0.02)
0.05 (0.04)
0.07 (0.05)
0.12 (0.09)
0.05 (0.04)
0.07 (0.05)
0.3
0.4
0.5
0.6
0.4
0.5
0.04 (0.02)
0.05 (0.04)
0.07 (0.05)
0.12 (0.09)
0.05 (0.04)
0.07 (0.05)
12 0.90
0.05 (0.04) 0.5
0.05 (0.04) 0.4
0.05 (0.04) 1050
1.40
0.12 (0.09) 0.9
0.12 (0.09) 0.6
0.12 (0.09) 108
Note:
Actual rpm will vary with application and configuration. Size 10 and 12 units have two motors.
980
1050
1030
1080
1050
1030
rpm
M
840
780
780
780
800
780
780
780
800
L
655
580
580
580
600
580
580
580
600
Table 7.
High-static motors on units with two-row, electric, or steam coils
Unit
Size
2
FLA
1.10
115 Volt hp (kW)
0.07 (0.05)
FLA
0.6
208–230 Volt hp (kW)
0.07 (0.05) 0.5
277–480 Volt
FLA hp (kW)
0.07 (0.05)
H
1480
6
8
3
4
10
1.40
1.60
2.60
3.40
0.08 (0.06)
0.10 (0.07)
0.16 (0.12)
0.24 (0.18)
0.7
0.8
1.2
1.4
0.08 (0.06)
0.10 (0.07)
0.16 (0.12)
0.24 (0.18)
0.6
0.7
1
1.1
0.08 (0.06)
0.10 (0.07)
0.16 (0.12)
0.24 (0.18)
1400
1475
1400
1475
12
1.60
2.60
1.60
3.40
0.10 (0.07)
0.16 (0.12)
0.10 (0.07)
0.24 (0.18)
0.8
1.2
0.5
0.9
0.10 (0.07)
0.16 (0.12)
0.10 (0.07)
0.24 (0.18)
0.7
1
0.7
1.1
0.10 (0.07)
0.16 (0.12)
0.10 (0.12)
0.24 (0.18)
1475
1400
1475
1475
Note:
Actual rpm will vary with application and configuration. Size 10 and 12 units have two motors.
rpm
M
1110
1175
1315
1070
1285
1315
1070
1315
1285
L
865
860
1070
855
975
1070
855
1240
975
61
Installation—Electrical
Table 8.
Free-discharge motors on units with three- and four-row coils
Unit
Size FLA
115 Volt hp (kW)
208–230 Volt
FLA hp (kW)
277–480 Volt
FLA hp (kW) H
2
3
4
0.60
0.80
1.00
0.03 (0.02)
0.05 (0.04)
0.06 (0.04)
0.3
0.5
0.6
0.03 (0.02)
0.05 (0.04)
0.06 (0.04)
0.2
0.4
0.5
0.03 (0.02)
0.05 (0.04)
0.06 (0.04)
980
1080
1080
6
8
10
1.40
1.70
1.00
1.40
1.00
0.12 (0.09)
0.13 (0.10)
0.06 (0.04)
0.12 (0.09)
0.06 (0.04)
0.9
1.0
0.6
0.9
0.6
0.12 (0.09)
0.13 (0.10)
0.06 (0.04)
0.12 (0.09)
0.06 (0.04)
0.6
0.8
0.5
0.6
0.5
0.12 (0.09)
0.13 (0.10)
0.06 (0.04)
0.12 (0.09)
0.06 (0.04)
1080
1080
1080
1080
1080 12
1.70
0.13 (0.10) 1.0
0.13 (0.10) 0.8
0.13 (0.10) 1080
Note:
Actual rpm will vary with application and configuration. Size 10 and 12 units have two motors.
rpm
M
840
800
800
800
800
800
800
800
800
L
655
600
600
600
600
600
600
600
600
Table 9.
High-static motors on units with three- and four-row coils
Unit
Size FLA
115 Volt hp (kW)
208–230 Volt
FLA hp (kW)
277–480 Volt
FLA hp (kW) H
4
6
2
3
1.10
1.30
2.10
3.40
0.07 (0.05)
0.08 (0.06)
0.13 (0.10)
0.24 (0.18)
0.6
0.7
0.9
1.4
0.07 (0.05)
0.08 (0.06)
0.13 (0.10)
0.24 (0.18)
0.5
0.5
0.7
1.1
0.07 (0.05)
0.08 (0.06)
0.13 (0.10)
0.24 (0.18)
1480
1500
1580
1475
8
10
3.40
2.10
3.40
2.10
0.24 (0.18)
0.13 (0.10)
0.24 (0.18)
0.13 (0.10)
1.4
0.9
1.4
0.9
0.24 (0.18)
0.13 (0.10)
0.24 (0.18)
0.13 (0.10)
1.1
0.7
1.1
0.7
0.24 (0.18)
0.13 (0.10)
0.24 (0.18)
0.13 (0.10 )
1475
1580
1475
1580 12
3.40
0.24 (0.18) 1.4
0.24 (0.18) 1.1
0.24 (0.18) 1475
Note:
Actual rpm will vary with application and configuration. Size 10 and 12 units have two motors.
rpm
M
1110
1355
1375
1285
1285
1375
1285
1375
1285
L
865
1110
1240
975
975
1240
975
1240
975
Table 10. Fan-coil electric heat kW
Unit Size Unit Voltage kW
02 115 1.0
03
04
230
277
208
115
230
277
208
115
230
277
208
1.0
1.0
0.8
1.0
1.0
1.0
0.8
kW
1.5
1.5
1.5
1.1
1.5
1.5
1.5
1.1
kW
2.0
2.0
2.0
1.5
2.0
2.0
2.0
1.5
2.0
2.0
2.0
1.5
kW kW kW kW kW kW kW kW
1.9
2.5
2.5
2.5
1.9
1.9
2.5
2.5
2.5
2.3
3.0
3.0
3.0
2.3
3.0
62 UNT-SVX07B-EN
UNT-SVX07B-EN
Installation—Electrical
Table 10. Fan-coil electric heat kW (continued)
Unit Size Unit Voltage kW
06 115
08
10
12
230
277
208
115
230
277
208
230
277
208
115
230
277
208
115
kW kW
2.0
2.0
2.0
1.5
2.0
2.0
2.0
1.5
kW kW
3.0
3.0
3.0
2.3
3.0
3.0
3.0
2.3
3.0
3.0
2.3
3.0
3.0
3.0
2.3
3.0
kW kW kW kW kW kW
4.0
4.0
3.0
4.0
4.0
3.0
4.0
4.0
3.0
4.0
4.0
3.0
5.0
5.0
3.8
5.0
5.0
3.8
5.0
5.0
3.8
5.0
5.0
3.8
6.0
6.0
4.5
6.0
6.0
4.5
6.0
6.0
4.5
6.0
6.0
4.5
5.3
7.0
7.0
5.3
7.0
7.0
5.3
7.0
7.0
5.3
6.0
8.0
8.0
6.0
8.0
8.0
6.0
10.0
10.0
Table 11. Electric heat kW, low vertical fan-coil
Unit Size
3.0
Unit Voltage
115.0
kW
1.0
kW
1.5
kW
2.0
4.0
6.0
115.0
115.0
1.0
1.0
1.5
1.5
2.0
2.0
Note:
Low vertical units are only available with electric heat in combination with the two-row cooling coil.
kW
2.5
2.5
Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations for Fan-Coils with Single Phase Electric Heat
Heater amps = (heater kW x 1000)/heater voltage
Note:
Use 120 V heater voltage for 115 V units. Use 240 V heater voltage for 230 V units.
MCA = 1.25 x (heater amps + all motor FLAs)
MFS or HACR type circuit breaker = (2.25 x largest motor FLA) + second motor FLA + heater amps
(if applicable)
HACR (heating, air-conditioning and refrigeration) type circuit breakers are required in the branch circuit wiring for all fan-coils with electric heat.
Select a standard fuse size or HACR type circuit breaker equal to the MCA. Use the next larger standard size if the MCA does not equal a standard size.
Standard fuse sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60 amps
Fan-coil electric heat MBh = (heater kW) (3.413)
63
Installation—Electrical
64
Table 12. Force-Flo single-stage, max kW electric heat
Unit Size Volts Hz Phase Wires Heater kW Heater amps/ph
02
03
04
277.0
208.0
240.0
480.0
208.0
240.0
277.0
208.0
208.0
240.0
277.0
208.0
240.0
480.0
208.0
240.0
60
60
60
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
2.25
3.0
3.0
2.25
3.0
3.0
4.5
6.0
6.0
4.5
6.0
6.0
5.7
7.5
7.5
5.7
06
240.0
480.0
208.0
240.0
60 1
1
3
3
2
2
3
4
7.5
7.5
18.1
9.1
7.9
38.0
10.5 43.8
277.0
208.0
240.0
480.0
1
3
3
3
2
3
3
4
10.5 38.0
7.9
10.5 25.3
10.5 12.7
Note:
All data based on individual units. Electric heat will operate only with fan at high speed.
21.9
21.7
12.6
14.5
7.3
27.5
31.3
27.1
15.9
10.9
12.5
10.9
6.3
7.3
3.7
21.7
25.0
Table 13. Force-Flo single stage, low kW electric heat
Unit Size Voltage # Wires
02
03
04
208/60/1
240/60/1
277/60/1
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
3
3
4
2
2
4
2
3
3
2
2
2
2
2
2
kW
3.0
2.3
3.0
3.0
2.3
3.0
3.0
3.0
3.0
2.3
3.0
0.8
1.0
1.0
2.3
amps/ph
3.7
10.9
12.5
10.9
6.3
7.3
3.7
3.7
4.2
3.7
10.9
12.5
10.9
6.3
7.3
kW
1.5
2.0
2.0
amps/ph
7.3
8.4
7.3
kW amps/ph
UNT-SVX07B-EN
UNT-SVX07B-EN
Installation—Electrical
Table 13. Force-Flo single stage, low kW electric heat (continued)
Unit Size Voltage # Wires
06 208/60/1 2
kW
2.3
amps/ph
10.9
kW
3.3
amps/ph
15.9
08
10
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
480/60/3
208/60/1
240/60/1
277/60/1
208/60/3
240/60/3
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
3.0
3.0
2.3
3.0
3.0
2.3
3.0
3.0
2.3
3.0
3.0
2.3
3.0
3.0
2.3
3.0
12.5
10.9
6.3
7.3
3.7
10.9
12.5
10.9
6.3
7.3
3.7
10.9
12.5
10.9
6.3
7.3
4.5
4.5
3.3
4.5
4.5
3.3
4.5
4.5
3.3
4.5
4.5
3.3
4.5
4.5
3.3
4.5
12
480/60/3
208/60/1
240/60/1
277/60/1
2
2
4
2
3.0
2.3
3.0
3.0
3.7
10.9
12.5
10.9
4.5
3.3
4.5
4.5
5.5
15.9
18.8
16.3
208/60/3
240/60/3
3
3
2.3
3.0
6.3
7.3
3.3
4.5
9.2
10.9
480/60/3 4 3.0
3.7
4.5
5.5
Note:
All data based on individual units. Electric heat will operate only with fan at high speed.
9.2
10.9
5.5
15.9
18.8
16.3
9.2
10.9
18.8
16.3
9.2
10.9
5.5
15.9
18.8
16.3
kW
7.5
6.6
9.0
9.0
7.5
7.5
5.7
7.5
4.5
6.0
6.0
4.5
6.0
6.0
5.7
6.6
9.0
9.0
amps/ph
Table 14. Force-Flo two-stage electric heat
Unit Size
02
03
Volts
208
480
208
240
277
240
277
208
240
208
240
480
Hz
60
60
Phase
1
1
1
3
1
3
3
1
1
3
3
3
Wires
2
2
2
4
2
3
3
2
2
3
3
4
1st Stage kW Total kW Total amps/ph
0.8
2.3
10.9
1.0
1.5
2.0
2.0
1.0
1.0
0.8
1.0
1.5
2.0
2.0
3.0
4.5
6.0
6.0
3.0
3.0
2.3
3.0
4.5
6.0
6.0
12.5
10.9
6.3
7.3
3.7
21.7
25.0
21.7
12.6
14.5
7.3
31.3
27.1
15.9
18.1
9.1
31.8
37.5
32.5
21.7
25.0
21.7
12.5
14.5
7.3
27.5
18.4
21.7
10.9
65
Installation—Electrical
Table 14. Force-Flo two-stage electric heat (continued)
Unit Size
04
Volts
208
Hz
60
Phase
1
Wires
2
1st Stage kW Total kW Total amps/ph
1.9
5.7
27.5
06
08
240
277
208
240
208
240
480
208
480
208
240
277
240
277
208
240
60
60
3
3
1
1
3
1
3
3
1
1
3
1
3
3
1
1
3
3
2
2
4
2
3
3
2
2
4
2
3
3
2
2
6.0
6.0
4.5
6.0
3.4
4.5
4.5
4.5
2.5
3.4
4.5
4.5
2.5
2.5
1.9
2.5
7.9
10.5
10.5
10.1
13.5
13.5
10.1
13.5
7.5
7.9
10.5
10.5
7.5
7.5
5.7
7.5
10
12
208
240
480
208
480
208
240
277
60
60
3
1
3
3
1
1
3
1
4
2
3
3
2
2
4
2
6.0
8.0
8.0
6.8
6.0
6.0
8.0
8.0
13.5
13.5
18.0
18.0
13.5
18.0
18.0
15.0
16.3
65.0
75.0
65.0
37.6
43.3
21.7
72.3
240
277
208
240
1
1
3
3
2
2
3
3
9.0
9.0
6.8
9.0
20.0
20.0
15.0
20.0
83.4
72.3
41.7
48.2
480 3 4 9.0
20.0
24.1
Note:
When both stages are on, the electric heat will operate only when fan is in high speed. All data based on individual units.
21.9
25.3
12.7
48.8
56.3
48.8
28.2
32.5
31.3
27.1
15.9
18.1
9.1
38.0
43.8
38.0
66 UNT-SVX07B-EN
Controls Interface
Wired Controllers—Communication Wiring
Units with Tracer ZN510 and ZN520 Only
Communications
Tracer ZN510 and ZN520 controllers are LonTalk
®
devices that interface with the Trane Tracer
Summit building management system. Reference the unit wiring diagram or submittals.
Ground shields at each Tracer ZN510 and ZN520, taping the opposite end of each shield to prevent any connection between the shield and anther ground. Refer to the most recent version of Trane publication CNT-SVX04A-EN (
Tracer ZN.520 Unit Controller: Installation, Operation and
Programming Guide
) for the communication wiring diagram.
Communication wire must conform to the following specification:
1.
Shielded twisted pair 18 AWG
2. Capacitance 23 (21–25) picofarads (pF) per foot
3. Listing/Rating—300 V 150C NEC 725-2 (b) Class 2 Type CL2P
4. Trane Part No. 400-20-28 or equivalent, available through Trane BAS Buying Group Accessories catalog.
Note:
Communication link wiring is a shielded, twisted pair of wire and must comply with applicable electrical codes.
Follow these general guidelines when installing communication wiring on units with a Tracer
ZN510 or ZN520 controller:
• Maintain a maximum 5000 ft. aggregate run.
• Install all communication wiring in accordance with the NEC and all local codes.
• Solder the conductors and insulate (tape) the joint sufficiently when splicing communication wire. Do not use wire nuts to make the splice.
• Do not pass communication wiring between buildings because the unit will assume different ground potentials.
• Do not run power in the same conduit or wire bundle with communication link wiring.
Note:
You do not need to observe polarity for LonTalk communication links.
Device Addressing
LonTalk devices are given a unique address by the manufacturer. This address is called a Neuron
ID. Each Tracer ZN510 and ZN520 controller can be identified by its unique Neuron ID, which is printed on a label on the controller’s logic board. The Neuron ID is also displayed when communication is established using Tracer Summit or Rover service tool. The Neuron ID format is 00-01-64-1C-2B-00.
Wire Characteristics
Controller communication-link wiring must be low capacitance, 18-gage, shielded, twisted pair with stranded, tinned-copper conductors. For daisy chain configurations, limit the wire run length to 5,000 ft. Truck and branch configurations are significantly shorter. LonTalk wire length limitations can be extended through the use of a link repeater.
Recommended Communication Wiring Practices
The following guidelines should be followed while installing communication wire.
• LonTalk is not polarity sensitive. Trane recommends that the installer keep polarity consistent throughout the site.
• Only strip away two inches maximum of the outer conductor of shielded cable.
UNT-SVX07B-EN 67
Controls Interface
• Make sure that the 24 Vac power supplies are consistent in how they are grounded. Avoid sharing 24 Vac between LonTalk UCMs.
• Avoid over-tightening cable ties and other forms of cable wraps. A tight tie or wrap could damage the wires inside the cable.
• Do not run LonTalk cable alongside or in the same conduit as 24 Vac power.
• In an open plenum, avoid lighting ballasts, especially those using 277 Vac.
• Do not use a trunk and branch configuration, if possible. Trunk and branch configurations shorten the distance cable can be run.
Wireless Temperature Sensor
Note:
Receivers ship installed on the unit. To remove the receiver, press in the retention tabs on the underside of the receiver enclosure (see Figure 18, p. 68 ) and push upward.
Figure 18. Retention tabs on underside of receiver enclosure
Address Setting
The process of establishing communication between a receiver and sensor is referred to as
association
. The following limitations apply:
• Each associated receiver/sensor set that communicates within the reception range of the wireless system must have a unique address.
It is not possible to associate more than one sensor to a receiver, nor is it possible to associate more than one receiver to a sensor.
To associate a receiver and sensor, the two devices must have their rotary address switches set to the same address.
Important:
Set the addresses before applying power to the receiver and before removing the insulation strip ( Figure 19, p. 69 ) from the sensor.
To set the receiver and sensor addresses:
1.
Using a small screwdriver, set the three rotary address switches (locations S1, S2, S3) on the receiver to an address between 001 and 999 (see Figure 19, p. 69 ). You do not have to remove the covers to access the rotary address switches.
Note:
Do not use 000 as an address. An address of 000 returns the receiver outputs to their factory defaults (zone temperature and setpoint outputs: 72.5°F [22.5°C]), removes all association knowledge, and prevents association with a sensor.
68 UNT-SVX07B-EN
Controls Interface
Figure 19. Setting the rotary address switches on the receiver and the sensor
Do not remove the insulation strip yet.
B1 +
LED1
LED2
LED3
SIGNAL
LED5
S1 S2
S3
POWER
S5
C33 C34
J1
S5
HEATING SET
FAN/SYSTEM
SETPOINT
ZONE
GND
24VAC/DC
GND
COMM +
COMM -
Receiver
LE
A
L
S4
C35
R77
Pb
Pb-FREE
LED1
LED2
LED3
SIGNAL
LED5
BATTERY
STATUS
S1 S2
ADDRESS
S3
STATUS
S4
WIRELESS
INSTALL
Sensor
2. Set the three rotary address switches (locations S1, S2, S3) on the sensor
to the same address as the receiver
(see Figure 19 ).
Note:
Do not use 000 as an address. An address of 000 removes all association knowledge, reverts the sensor to a low-power hibernation mode, and sends a disassociation request to the receiver.
3. Record the address and location of the receiver and sensor pair.
Observing the Receiver for Readiness to Associate
After initial power up, the receiver conducts a channel scan for 20 seconds. During this time, the receiver selects from 16 available channels the clearest channel on which to operate. LED1, LED2, and LED3 flash rapidly in succession (round-robin style) while the channel scan is in progress, as shown in part 1 of the illustration.
Important:
Do not attempt association (leave the insulation strip in place) until the channel scan is finished.
After the channel scan is finished, LED3 begins blinking (one-blink pattern) to show that the receiver is ready to be associated with a sensor (see part 2 of the following figure).
1
2
0
Sec.
20
LED3
UNT-SVX07B-EN 69
Controls Interface
Associating the Sensor to the Receiver
To associate the sensor to the receiver:
1.
Remove the sensor cover by firmly pressing the thumb tab at the bottom of the cover and pulling the cover away from the back plate.
2. Verify that the sensor is set to the same address as the receiver it is to be associated with.
3. Power the sensor by removing the insulation strip from between the two batteries.
Association is automatically initiated between the sensor and the receiver. When LED3 on the receiver stops blinking, association has been established.
If the first association attempt is unsuccessful, the sensor automatically re-attempts association with the receiver every 10 minutes.
Note:
An associated sensor that has lost communication with the receiver will transmit an association request every 50 minutes. You can manually initiate association (see “Manual
Association,” p. 120 ”).
Testing Signal Strength and Battery Status
To verify that the association process was successful and that the batteries have adequate charge:
1.
Firmly press and release the Test button on the bottom of the sensor (as illustrated below).
2. For model WTS, view LED1, LED2, and LED3 to determine the signal strength. View LED5 to determine the battery status (see the following figure for model WTS sensors).
Note:
The LEDs will turn Off after 5 seconds to conserve battery strength.
For model WDS, determine the signal strength and battery status by viewing the symbols on the sensor display (see the following figure for model WDS sensors).
3. Record the results in your commissioning statement.
Note:
For more information, see “Testing Signal Strength,” p. 117 and “Testing Battery Status,” p. 118 .
70 UNT-SVX07B-EN
Controls Interface
Model WDS sensor
Model WTS sensor
LED1
LED2
LED3
LED5
Test button
Test button
Push firmly, then release
Push firmly, then release
Configuring the Wireless Display Sensor (Model WDS only)
Note:
Sensors shipped with the fan-coil are pre-configured for three speeds.
The configuration of the sensor determines which system features can be accessed and changes can be made by the tenant (for example, changes to cooling/heating mode, setpoint, or fan speed.
Verify system and associated unit features before configuring the sensor.
The building owner or operator may choose to limit tenant access to certain features. This can be done through configuration. Or, if a sensor is configured to match all control capabilities of the building automation system, the locking feature can be used to restrict the tenant from making changes.
Configuration Procedure
To configure settings on the model WDS sensor, follow this procedure in the order presented.
1.
Press the configuration button for 3 seconds.
UNT-SVX07B-EN 71
Controls Interface
Configuration button
The display will change to configuration mode. When the sensor is in configuration mode, a wrench symbol appears on the display and the menus are separated by lines, as illustrated below.
2. Press the center button on the keypad to begin the configuration process.
Center button
72 UNT-SVX07B-EN
Controls Interface
3. Configure the sensor options in the order shown in the table.
•
Press or to scroll to the next selection (as illustrated).
•
Press or to move to the next menu (as illustrated).
Setting
Temperature
• Choose Fahrenheit or Celsius
• Choose the degree resolution
(whole degrees, half degrees, or tenths of degrees).
Configuration Options
.
.
.
.
.
Setpoint
.
no setpo i nt s i ngle setpo i nt du a l setpo i nt
System
Fan
Note:
Not all fan options are available for all systems.
no system opt i ons en a bled a uto/o ff a uto/o ff / low/h i gh
(Default) a uto/o ff /low med/h i gh
Occupancy (timed override)
o ff /h i gh (on) o ff /low/h i gh o ff /low/ med/h i gh no fa n opt i ons en a bled
UNT-SVX07B-EN
4. Review the display to ensure that you have selected the correct configuration.
5. To return the display to operating mode, press the configuration button (see Step 1 , p. 71 ).
Note:
The sensor will revert to operating mode if no buttons are pressed for 10 minutes.
73
Controls Interface
Optional Features
Displaying Setpoint or Temperature.
You can configure the sensor to display either the temperature (default) or setpoint. To select either option:
1.
Verify that the sensor is in operating mode and at the home screen.
2. Press the up and down arrows for 3 seconds. The arrow indicates setpoint display, as shown in the figure.
Arrow indicates setpoint is shown on display
Locking or Unlocking Settings.
You can lock or unlock the setpoint, system, or fan setting to prevent changes.
To lock or unlock a setting:
1.
Verify that the sensor is in operating mode and at the home screen.
2. Choose a setting to lock or unlock:
•
Select the setpoint by pressing the up or down arrow.
Setpoint
•
From the system menu press the down arrow to select the fan menu. Use the left or right arrow to choose the setting.
Fan menu
3. Press the left and right arrows for 4 seconds.
74 UNT-SVX07B-EN
Controls Interface
Note:
If you try to access a feature that is locked, the locked symbol will appear on the display.
If you press a keypad button to try change a locked setting, the locked symbol will flash.
Replacing the Sensor Cover
To replace the cover:
1.
Hook the cover over the top of the back plate. Apply light pressure to the bottom of the cover until it snaps in place.
2. Install the security screw into the bottom of the cover (if desired).
Security screw
Sensor Operations
Temporary Occupancy (Timed Override)
Temporary occupancy (timed override) is available on model WDS. Temporary occupancy is selected for after-business-hours adjustment of temperature setting, fan settings, or heat/cool settings, when the system has changed to unoccupied mode. System control will revert to unoccupied after a pre-determined time period.
Note:
Not all systems support the occupancy function.
Model WDS Sensor
To request and cancel temporary occupancy on a model WDS sensor, see “Requesting Temporary
Occupancy,” p. 78 .
End-of-Range Temperature Values
Receiver:
The end-of-range temperature limits of the receiver for
all models
are 32°F to 122°F (0°C to 50°C). The receiver cannot replicate temperature values outside this range. If the sensor transmits a temperature value to the receiver that is out of the receiver replication range, the receiver will “freeze” the output at the end-of-range values. This value will remain frozen until the transmitted temperature moves to between the end-of-range temperature limits.
Sensor:
The end-of-range temperature setpoint limits for the
model WDS sensor
is 50°F (10°C) to
89.6°F (32°C).
UNT-SVX07B-EN 75
Controls Interface
76
Receiver Power-up Sequence
When power is applied to the receiver, one of the following sequences occurs. The sequence is dependent on the address setting and the association status of the receiver.
Address set to 000 and receiver is not associated with a sensor
• LED5 is constantly On, indicating power is applied and the receiver is functional.
• All models: Zone temperature and cooling setpoint default to 72.5°F (22.5°C).
WDS only: The heating setpoint defaults to 70.5°F (21.4°C) and the fan/system output will be
2230
Ω
(see “Output Values—Failure and Default Modes of Operation,” p. 122 ).
• Status LED3 will display a 2-blink pattern diagnostic ( Table 39, p. 117 ).
Address set from 001 to 999 and receiver is not associated with a sensor
• LED5 is constantly On, indicating power is applied and the receiver is functional.
• All models: Zone temperature and cooling setpoint default to 72.5°F (22.5°C).
WDS only: The heating setpoint defaults to 70.5°F (21.4°C) and the fan/system output will be
2230
Ω
(see “Output Values—Failure and Default Modes of Operation,” p. 122 ).
• The receiver conducts an energy scan for 20 seconds to determine the clearest channel on which to operate.
• LED3 flashes On every 2 seconds when it is ready to accept a sensor association request. When an association request is made by a sensor, the receiver instructs the sensor on which power level to operate. Then the receiver and sensor begin operation at the appropriate channel and power level (see “Observing the Receiver for Readiness to Associate,” p. 69 ).
Address set from 001 to 999 (and not changed since most recent power-up) and receiver is associated with a sensor
• LED5 is constantly On, indicating power is applied and the receiver is functional.
• Zone temperature and setpoint default to 72.5°F (22.5°C). WDS only: Heating setpoint defaults to 70.5°F (21.4°C), Fan = Auto, System = Off.
• The receiver waits for a broadcast transmission from its associated sensor. When a transmission is received, the receiver positions its zone temperature and setpoint outputs appropriately.
• If the receiver does not receive a communicated signal from its associated sensor within 35 minutes, zone temperature and setpoint outputs fail, generating a unit controller alarm (see
“Output Values—Failure and Default Modes of Operation,” p. 122 ).
Note:
Once a receiver communicates to a WTS sensor, the receiver disables (opens) its zone setpoint output indefinitely.
Sensor Transmission Time and Temperature Variables
Sensor transition time variables are as follows:
• The maximum time between sensor temperature transmissions is 15 minutes.
• The minimum time between sensor temperature transmissions is 30 seconds.
• The minimum time for transmitting temperature setpoint changes is 10 seconds.
Note:
If a sensor transmits a message to the receiver and the receiver does not reply, the sensor will retransmit the message to the receiver every 30 seconds until communication to the receiver is re-established.
Sensor temperature time variables are as follows:
• The minimum change in zone temperature required to force a sensor transmission is:
– 0.2°F (0.11°C) when the temperature range is between 60°F (15.6°C) and 80°F (26.7°C)
– 0.5°F (0.28°C) when the temperature range is between 32°F (0°C) and 60°F (15.6°C) or between 80°F (26.7°C) and 122°F (50°C))
UNT-SVX07B-EN
Controls Interface
• The minimum change in temperature setpoint required to force a sensor transmission is:
– 0.1°C for a model WDS sensor
Operating Mode (Model WDS)
This section describes how to operate the Trane wireless sensor, model WDS. Figure 20 shows an example of a model WDS that has been configured and is in operating mode.
Figure 20. Wireless sensor (model WDS) in operating mode
Temperature
System settings (not available for fan-coil or Force-Flo units)
Fan settings
Test symbols (appear only when Test button is pushed
Occupancy indicator/Error code
Keypad
.
.
Test button
Changing Room Temperature
This symbol shows the current room temperature, or your setpoint selection while you are making an adjustment.
When you select a setpoint, this symbol appears.
1.
To increase the room temperature, press .
To decrease the room temperature, press
2. To confirm, press to the home screen.
.
or wait 5 seconds. The display will return
Changing Heating and Cooling Room Temperature Settings (applies to some systems)
Some systems allow you to select both heating and cooling room temperature settings. If your system has this option, this symbol appears when you adjust the temperature setting.
1.
Press or to select the heating/cooling setting.
2. If in cooling mode, press to change to heating mode. If in heating mode, press to change to cooling mode.
When you adjust the cooling setting, the top arrow and snowflake flash.
3. Press or to select the heating/cooling setting.
4. To confirm, press or wait 5 seconds. The home screen will
When you adjust the heating setting, the bottom arrow and flame flash.
appear.
UNT-SVX07B-EN 77
Controls Interface
Changing the Fan Setting
Indicates that the fan will operate as needed to reach the selected temperature.
1.
From the home screen, activate the fan setting menu by pressing
and then .
Indicates that the fan setting is On.
The number of arrows indicates fan speed
(3: high, 2: medium, 1: low).
The example shown indicates a fan on high speed. Not all systems offer all three speeds.
2. Press or choice by
to choose the desired fan setting.
3. When the symbol for the desired setting appears, confirm your
Indicates that the fan setting is Off.
•
Pressing (the home screen will appear), or
•
Pressing or
•
Waiting five seconds.
(the next menu will appear), or
Select to request occupancy
Select to cancel occupancy
Requesting Temporary Occupancy
• If you need heating or cooling after normal business hours, you can “request” temporary occupancy by pressing and holding it for 2 seconds. The occupied symbol remains on the screen and the unoccupied symbol disappears. After 30 seconds, the unoccupied symbol will re-appear.
• To cancel temporary occupancy, press and hold for 2 seconds. The unoccupied symbol will remain on the screen and the occupied symbol will disappear. After
30 seconds, the occupied symbol will re-appear.
Error Codes
Indicates an error code
If an error code (E0–E7) is displayed, technical assistance may be required.
Indicates that a setting is locked
Lock Symbol
The lock symbol appears if you try to adjust a setting that cannot be changed.
Testing Signal Strength
Indicates excellent signal strength
Indicates satisfactory signal strength
Indicates poor signal strength
Press the Test button to display the signal strength symbols.
Testing Battery Status
Indicates full battery power
Indicates 50% of battery life left.
Indicates 25% of battery life left.
Replace batteries.
Flashing symbol indicates that approximately 14 days of operation remain.
Press the Test button to display the battery status symbols.
Use only UL-listed non-rechargeable 1.5 V lithium AA batteries (Trane p/n X13770035010 or equivalent).
Wireless Sensor Specifications
The following table presents specifications for all models of the wireless sensor sets.
78 UNT-SVX07B-EN
UNT-SVX07B-EN
Controls Interface
Sensor operating temperature
Receiver operating temperature
Storage temperature
Storage and operating humidity range
Accuracy
Resolution
Setpoint functional range (WDS only)
Receiver voltage
Receiver power consumption
Housing
Mounting
Sensor battery
Range
(a)
Output power
Radio frequency
Radio channels
Address range
Minimum time between transmissions
Maximum time between transmissions
32ºF to 122ºF (0ºC to 50ºC)
-40ºF to 158ºF (-40ºC to 70ºC)
-40ºF to 185ºF (-40ºC to 85°C)
5% to 95%, non-condensing
0.5°F over a range of 55ºF to 85°F (12.8ºC to 29.4°C)
0.125ºF over a range of 60ºF to 80ºF (15.56ºC to 26.67°C)
0.25ºF when outside this range
50ºF to 89.6ºF (10ºC to 32ºC)
24 V nominal ac/dc ±10%
<1 VA
Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating, suitable for application in a plenum
3.24 in (8.26 cm) for 2 mounting screws (supplied)
(2) AA, 1.5 V, 2800 mAh, lithium, 5-year life, UL listed
Open range: 2,500 ft (762 m) (packet error rate = 2%)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
100 mW
2.4 GHz (IEEE Std 802.15.4-2003 compliant)
(2405 to 2480 MHz, 5 MHz spacing)
16
000 to 999
30 seconds
15 minutes
(a) Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and must be determined during site evaluation.
79
Controls Interface
United States compliance
(all models)
Canada compliance
(all models)
The following table presents agency compliance information for wireless sensor set models as shown.
IEEE compliance for radio frequency range
(all models)
UL listed: UL 94-5VA Flammability rating
UL 916: Energy management equipment
FCC CFR47, Section 15.247 & Subpart E Digital Modulation Transmission with no SAR (FCC Identification TFP-
13651127)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired operation.
Warning:
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
20 cm separation distance:
To comply with FCC’s RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.
CSA22.2 No. 205-M1983 Signal Equipment
Industry Canada (Certification no: IC: 6178A-13651127)
Industry Canada statement: the term “IC” before the certification/registration number signifies only that the Industry Canada technical specifications were met.
Section 14 of RSS-210:
The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not emit RF field in excess of Health Canada limits for the general population.
IEEE 802.15.4-2003, IEEE Standard for Information Technology—Telecommunications and information exchange between systems—Local and metropolitan area networks—Specific requirements, Part 15.4:
Wireless Medium Access Control (MAC) and Physical Layer (PHY) Specifications for Low Rate Wireless
Personal Area Networks (LR-WPANs)
80 UNT-SVX07B-EN
Pre-Start
Pre-Startup Checklist
Complete this checklist after installing the unit to verify all recommended installation procedures are complete before unit startup. This does not replace the detailed instructions in the appropriate sections of this manual. Disconnect electrical power before performing this checklist. Always read the entire section carefully to become familiar with the procedures.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Receiving
Inspect unit and components for shipping damage. File damage claims immediately with the delivering carrier.
Check unit for missing material. Look for ship-with options and sensors that may be packaged separately from the main unit (see “Receiving and Handling,” p. 11 ).
Check nameplate unit data so that it matches the sales order requirements.
Unit Location
1.
Ensure the unit location is adequate for unit dimensions, ductwork, piping, and electrical connections.
2. Ensure access and maintenance clearances around the unit are adequate.
Unit Mounting
1.
Ensure unit is installed level.
Component Overview
1.
Ensure the fan rotates freely in the correct direction.
2. Ensure all unit access panels and air grilles are in place.
3. Verify that a clean air filter is in place.
4. Properly set the damper position to meet the fresh air requirement.
Unit Piping
1.
Properly vent the hydronic coil to allow water flow through the unit.
2. Units with deluxe piping package: Tighten unions adequately.
3. Set water flow to the unit properly if unit piping has the circuit setter valve.
4. Check strainers (if supplied) for debris after apply system water.
5. Install the auxiliary drain pan and route the main drain pan hoses to the auxiliary drain pan on vertical fan-coil units.
6. Verify the condensate drain piping is complete for the unit drain pan.
7.
Ensure the drain pan and condensate line are not obstructed. Remove any foreign matter that may have fallen into the drain pan during installation.
UNT-SVX07B-EN 81
Pre-Start
Electrical
Check all electrical connections for tightness.
Note:
Some circumstances may require the unit to run before building construction is complete.
These operating conditions may be beyond the design parameters of the unit and may adversely affect the unit.
82 UNT-SVX07B-EN
Start-Up
Tracer™ ZN510 & ZN520 Unit Startup
Refer to the Trane publication, CNT-IOP-1 (
ComfortLink 10 Controller: Installation, Operation and
Programming Guide
) for Tracer ZN510 and CNT-SVX04A-EN for Tracer ZN520. The factory preprograms the Tracer ZN510 and ZN520 with default values to control the temperature and unit airflow. Use Tracer Summit building automation system or Rover™ software to change the default values.
Follow the procedure below to operate the Tracer ZN510 or ZN520 in a stand-alone operation:
1.
Turn power on at the disconnect switch option.
2. Position the fan mode switch to either high, medium, low, or the auto position.
3. Rotate the setpoint dial on the zone sensor module to 55°F for cooling or 85°F for heating.
The appropriate control valve will actuate assuming the following conditions:
1.
Room temperature should be greater than 55°F and less than 85°F.
2. For a 2-pipe fan-coil unit with an automatic changeover sensor, the water temperature input is appropriate for the demand placed on the unit. For example, cooling operation is requested and cold water (5° lower than room temperature) flows into the unit.
3. Select the correct temperature setpoint.
Note:
Select and enable zone sensor temperature settings to prevent freeze damage to unit.
General Information
Relay (Daughter) Board
The relay board is a new component on all models (except those with a unit-mounted, line-voltage fan speed switch) that replaces all the loose wires in the control box. It consolidates many control components onto one board, therefore making it easy to troubleshoot in the field. There is an LED on the board that indicates when power is supplied to the board. All connections are made to match up only with the applicable component to, thus prevent miswiring. Factory switches are pre-set and locked in place with lock-tight. The switch settings can be broken if field-modifications are needed.
However, switches must be properly set for the unit to operate safely and properly. See Figure 21 .
Figure 21. Relay board
UNT-SVX07B-EN
Manual Fan Mode Switch
The manual fan mode switch is available with a four-position switch (off-hi-med-lo) allows manual fan mode selection and is available unit- or wall-mounted. See Figure 22 .
83
Start-Up
Figure 22. Fan speed switch
The unit-mounted option operates on line voltage. The wall-mounted option is low-voltage and has three 24-volt relays using a factory-wired transformer and relays to control the fan motor.
Tracer ZN010 & ZN510
Tracer ZN010 is a stand-alone device that controls fan-coils and cabinet heaters. Tracer ZN510 can be stand-alone or use peer-to-peer communications.
The controller is easily accessible in the control end panel for service. The control end panel is on the end of the unit opposite the piping. See Figure 23 .
Figure 23. Tracer ZN010 board
Fan Mode Switch Operation
Off
Fan is turned off, two-position damper option spring-returns closed.
Hi, Med, Lo
Fan runs continuously at the selected speed. The two-position damper option opens to an adjustable mechanical stop position.
Tracer ZN010 & ZN510 Operation
Off
Fan is off; control valves and fresh air damper option close. Low air temperature detection option is still active.
84 UNT-SVX07B-EN
Start-Up
Auto (Fan Cycling)
Fan and fresh air damper cycle with control valve option to maintain setpoint temperature. In cooling mode, the fan cycles from off to medium and in heating mode it cycles from off to low.
When no heating or cooling is required, the fan is off and the fresh air damper option closes.
Low/Med/High (Continuous Fan)
Fan operates continuously while control valve option cycles to maintain setpoint temperature.
Fresh air damper option is open.
Tracer ZN520 Operation
Off
Fan is off; control valve options and fresh air damper options close. The low air temperature detection option is still active.
Auto
Fan speed control in the auto setting allows the modulating (3-wire floating point) or 2–position control valve option and three-speed fan to work cooperatively to meet precise capacity requirement, while minimizing fan speed (motor/energy/acoustics ) and valve position (pump energy, chilled water reset ). As the capacity requirement increases at low fan speed, the water valve opens. When the low fan speed capacity switch point is reached, the fan switches to medium speed and the water valve repositions to maintain an equivalent capacity. The reverse sequence takes place with a decrease in required capacity.
Low/Med/High
The fan runs continuously at the selected speed and the valve option will cycle to meet setpoint.
UNT-SVX07B-EN 85
Start-Up
Sequence of Operation: Tracer ZN010 and ZN510
Note:
This section applies only to units with a Tracer ZN010 or ZN510 controller.
Power-Up Sequence
When 24 Vac power is initially applied to the Tracer ZN010 or ZN510, the following sequence occurs:
1. All outputs are controlled off.
2. Tracer ZN010 and ZN510 reads all input values to detemine initial values.
3. The random start time (0-25 seconds) expires.
4. Normal operation begins.
Entering Water Temperature Sampling Function
Both Tracer ZN010 and ZN510 use an entering water temperature sampling function to test for the correct water temperature for the unit operating mode. For all applications not involving changeover, the water temperature does not affect unit operation.
The entering water temperature sampling function opens the main hydronic valve, waits no more than three minutes to allow the water temperature to stabilize, then measures the entering water temperature to see if the correct water temperature is available.
The entering water must be five degrees or more above the space temperature to allow hydronic heating and five degrees or more below the space temperature to allow hydronic cooling.
If the correct water temperature is available, the unit begins normal heating or cooling operation.
If the measured entering water temperature is too low or high, the controller closes the valve and waits 60 minutes before attempting to sample the entering water. Refer to Table 15 .
Table 15. Unit mode as related to water temperature
Unit Type
2-pipe changeover
EWT Sensor Required?
Yes
4-pipe changeover
2-pipe heating only
2-pipe cooling only
4-pipe heat/cool
Yes
No
No
No
Coil Water Temperature
COOLS if: Space temp - EWT ≥ 5°F
HEATS if: EWT - space temp ≥ 5°F
COOLS if: Space temp - EWT ≥ 5°F
HEATS if: EWT - space temp ≥ 5°F
Hot water assumed
Cold water assumed
Cold water assumed in main coil
Hot water assumed in aux. coil
Binary Inputs
BIP1: Low Temperature Detection Option
The factory hard wires the low temperature detection sensor to binary input #1 (BIP1) on the Tracer
ZN010 and ZN510. The sensor defaults normally closed (N.C.), and will trip off the unit on a low temperature diagnostic when detecting low temperature. In addition, the Tracer ZN010 and ZN510 control unit devices as listed below:
Fan: Off
Valves: Open
Electric heat: Off
Damper: Closed
Note:
See “Diagnostics,” p. 107 for more information.
86 UNT-SVX07B-EN
Start-Up
BIP2: Condensate Overflow Detection Option
The factory hard wires the condensate overflow sensor to binary input #2 (BIP2) on the Tracer
ZN010 and ZN510. The sensor defaults normally closed (N.C.), and will trip off the unit on a condensate overflow diagnostic if condensate reaches the trip point. In addition, the Tracer ZN010 and ZN510 control unit devices as listed below:
Fan: Off
Valves: Closed
Electric heat: Off
BIP3: Occupancy Sensor
Binary input #3 (BIP3) on Tracer ZN010 and ZN510 is available for field- wiring an occupancy sensor, such as a binary switch or a timeclock, to detect occupancy. The sensor can be either normally open or normally closed. Refer to Table 16 .
Table 16. Occupancy sensor state table
Sensor Type
Normally open
Normally open
Normally closed
Normally closed
Sensor Position
Open
Closed
Open
Closed
Unit Occupancy Mode
Occupied
Unoccupied
Unoccupied
Occupied
Binary Outputs
Refer to Table 17 for the Tracer ZN010 and ZN510’s six binary outputs.
Table 17. Binary outputs
Binary output
BOP1
BOP2
BOP3
BOP4
BOP5
BOP6
Description
Fan high speed
Fan medium speed
Fan low speed
Main valve
Auxiliary valve/electric heat
2-position fresh air damper
Notes:
1. In a four-pipe application, BOP4 is used for cooling and BOP5 is used for heating.
2. If no valves are ordered with the unit, the factory defaults for the Tracer ZN010 and ZN510 controller are:
BOP4 configured as normally closed
BOP5 configured as normally open
3. If the fresh air damper option is not ordered on the unit, BOP6 will be configured as none.
Pin
J1-1
J1-2
J1-4
J1-5
J1-6
J1-7
Both Tracer ZN010 and ZN510 accept a maximum of five analog inputs. Refer to Table 18, p. 88 .
UNT-SVX07B-EN 87
Start-Up
88
Table 18. Analog inputs
Analog Input
Zone
Set
Fan
Analog input 1 (AI1)
Analog input 2 (AI2)
Description
Space temperature
Local setpoint
Fan mode input
Entering water temperature
Discharge air temperature
Application
Space temperature detection
Thumbwheel setpoint
Zone sensor fan switch
Entering water temperature detection
Discharge air temperature detection
Notes:
1. 1.The zone sensor, entering water temperature sensor, and the discharge air temperature sensor are 10 K Ω thermistors.
Figure 28, p. 113 provides the resistance-temperature curve for these thermistors.
2. Zone sensor:
Wall-mounted sensors include a thermistor soldered to the sensor’s circuit board
Unit mounted sensors include a return air sensor in the unit’s return air stream.
3. Changeover units include an entering water temperature sensor.
Zone Sensors
The zone sensors available with the Tracer ZN010 and ZN510 provide up to three different inputs
1.
Space temperature measurement (10 K
Ω
thermistor)
2. Local setpoint
3. Fan mode switch
Wall-mounted zone sensors include a thermistor as a component of the internal printed circuit board. Unit mounted zone sensors use a sensor placed in the unit’s return air stream.
Each zone sensor is equipped with a thumbwheel for setpoint adjustment.
Fan Mode Switch
The zone sensor may be equipped with a fan mode switch. The fan mode switch offers selections of off, low, medium, high, or auto.
Supply Fan Operation
Refer to Table 19 for fan mode operation. Tracer ZN010 and ZN510 will operate in either continuous fan or fan cycling mode. The fan cycles when the fan mode switch is placed in auto. The fan runs continuous when placed in the high, medium, or low position. Use Rover, Trane’s installation and service tool, to change auto defaults.
Table 19. Fan mode operation
Heating Mode
Fan mode
Off
Low
Medium
High
Auto
Continuous
Cycling off/heat default
Occupied
Off
Low
Medium
High
Heat default
Cooling Mode
Unoccupied
Off
Off/high
(a)
Off/high
(a)
Off/high
(a)
Off/high
(a)
Off/high
(a)
Occupied
Off
Low
Medium
High
Cool default
Off/cool default
Unoccupied
Off
Off/high
(a)
Off/high
(a)
Off/high
(a)
Off/high
Off/high
(a)
(a)
Notes:
1. During the transition from off to any fan speed but high, Tracer ZN010 and ZN510 automatically starts the fan on high speed and runs for three seconds before transitioning to the selected speed (if it is other than high). This provides enough torque to start all fan motors from the off position.
2. When the heating output is controlled off, Tracer ZN010 and ZN510 automatically controls the fan on for an additional 30 seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.
UNT-SVX07B-EN
Start-Up
(a) Whenever two states are listed for the fan:
The first state (off) applies when there is not a call for heating or cooling.
The second state (varies) applies when there is a call for heating or cooling.
The heat default is factory configured for low fan speed, and the cool default is medium.
Table 20. Valid operating range and factory default setpoints
Setpoint/parameter
Unoccupied cooling setpoint
Occupied cooling setpoint
Occupied heating setpoint
Unoccupied heating setpoint
Cooling setpoint high limit
Cooling setpoint low limit
Heating setpoint high limit
Heating setpoint low limit
Power-up control wait
Default Setting
85°F
74°F
71°F
60°F
110°F
40°F
105°F
40°F
0 sec
Valid Operating Range
40°F to 115°F
40°F to 115°F
40°F to 115°F
40°F to 115°F
40°F to 115°F
40°F to 115°F
40°F to 115°F
40°F to 115°F
0 sec to 240 sec
Tracer ZN520 Sequence of Operation
The Tracer ZN520 operates the fan in the following modes:
1.
occupied
2. unoccupied
3. occupied standby
4. occupied bypass
5. Tracer Summit with supply fan control
Occupied
When the controller is in the occupied mode, the unit attempts to maintain the space temperature at the active occupied heating or cooling setpoint, based on the measured space temperature, the discharge air temperature, the active setpoint, and the proportional/integral control algorithm. The modulating control algorithm used when occupied or in occupied standby is described in the following sections. Additional information related to the handling of the controller setpoints can be found in the previous Setpoint operation section.
Unoccupied Mode
When the controller is in the unoccupied mode, the controller attempts to maintain the space temperature at the stored unoccupied heating or cooling setpoint, based on the measured space temperature, the active setpoint and the control algorithm, regardless of the presence of a hardwired or communicated setpoint. Similar to other configuration properties of the controller, the locally stored unoccupied setpoints can be modified using Rover™ service tool.
In unoccupied mode, a simplified zone control algorithm is run. During the cooling mode, when the space temperature is above the cool setpoint, the primary cooling capacity operates at 100%.
If more capacity is needed, the supplementary cooling capacity turns on (or opens to 100%). During the heating mode, when the space temperature is below the heat setpoint, the primary heating capacity turns on. All capacity is turned off when the space temperature is between the unoccupied cooling and heating setpoints. Note that primary heating or cooling capacity is defined by unit type and whether heating or cooling is enabled or disabled. For example, if the economizer is enabled and possible, it will be the primary cooling capacity. If hydronic heating is possible, it will be the primary heating capacity.
UNT-SVX07B-EN 89
Start-Up
90
Occupied Standby Mode
The controller can be placed into the occupied standby mode when a communicated occupancy request is combined with the local (hardwired) occupancy binary input signal. When the communicated occupancy request is unoccupied, the occupancy binary input (if present) does not affect the controller’s occupancy. When the communicated occupancy request is occupied, the controller uses the local occupancy binary input to switch between the occupied and occupied standby modes.
During occupied standby mode, the controller’s economizer damper position goes to the economizer standby minimum position. The economizer standby minimum position can be changed using Rover service tool.
In the occupied standby mode, the controller uses the occupied standby cooling and heating setpoints. Because the occupied standby setpoints typically cover a wider range than the occupied setpoints, the Tracer ZN520 controller reduces the demand for heating and cooling the space. Also, the outdoor air economizer damper uses the economizer standby minimum position to reduce the heating and cooling demands.
When no occupancy request is communicated, the occupancy binary input switches the controller’s operating mode between occupied and unoccupied. When no communicated occupancy request exists, the unit cannot switch to occupied standby mode.
Occupied Bypass Mode
The controller can be placed in occupied bypass mode by either communicating an occupancy request of Bypass to the controller or by using the timed override On button on the Trane zone sensor.
When the controller is in unoccupied mode, you can press the On button on the zone sensor to place the controller into occupied bypass mode for the duration of the bypass time (typically
120 minutes).
Occupancy Sources
There are four ways to control the controller’s occupancy:
• Communicated request (usually provided by the building automation system or peer device)
• By pressing the zone sensor’s timed override On button
• Occupancy binary input
• Default operation of the controller (occupied mode)
A communicated request from a building automation system or another peer controller can change the controller’s occupancy. However, if communication is lost, the controller reverts to the default operating mode (occupied) after 15 minutes (configurable, specified by the “receive heartbeat time”), if no local hardwired occupancy signal exists.
A communicated request can be provided to control the occupancy of the controller. Typically, the occupancy of the controller is determined by using time-of-day scheduling of the building automation system. The result of the time-of-day schedule can then be communicated to the unit controller.
Tracer Summit with Supply Fan Control
If the unit is communicating with Tracer Summit and the supply fan control programming point is configured for Tracer (the factory configures as local), Tracer Summit will control the fan regardless of the fan mode switch position.
When the fan mode switch is set to Off or when power is restored to the unit, all Tracer ZN520 lockouts (latching diagnostics) are manually reset. The last diagnostic to occur is retained until the unit power is disconnected. Refer to Trane publication, CNT-SVX04A-EN (
Tracer ZN.520 Unit
Controller: Installation, Operation and Programming Guide
) for specific instructions regarding the procedure for running the Tracer ZN520.
UNT-SVX07B-EN
Start-Up
Cooling Operation
The heating and cooling setpoint high and low limits are always applied to the occupied and occupied standby setpoints. During the cooling mode, the Tracer ZN520 controller attempts to maintain the space temperature at the active cooling setpoint. Based on the controller’s occupancy mode, the active cooling setpoint is one of the following:
• Occupied cooling setpoint
• Occupied standby cooling setpoint
• Unoccupied cooling setpoint
The controller uses the measured space temperature, the active cooling setpoint, and discharge air temperature along with the control algorithm to determine the requested cooling capacity of the unit (0%–100%). The outputs are controlled based on the unit configuration and the required cooling capacity. To maintain space temperature control, the Tracer ZN520 cooling outputs
(modulating hydronic valve, two-position hydronic valve, or outdoor air economizer damper) are controlled based on the cooling capacity output.
The cooling output is controlled based on the cooling capacity. At 0% capacity, all cooling capacities are off and the damper is at minimum position. Between 0% and 100% capacity, the cooling outputs are controlled according to modulating valve logic (modulating valves) or cycled on (2-position valves). As the load increases, modulating outputs open further and binary outputs are energized longer. At 100% capacity, the cooling valve or damper is fully open (modulating valves) or on continuously (and 2-position valves).
Unit diagnostics can affect fan operation, causing occupied and occupied standby fan operation to be defined as abnormal. Refer to the Troubleshooting section for more information about abnormal fan operation.
The Tracer ZN520 controller operates the supply fan continuously when the controller is in the occupied and occupied standby modes, for either heating or cooling. The controller only cycles the fan off with heating and cooling capacity in the unoccupied mode.
The economizer is used for cooling purposes whenever the outdoor temperature is below the economizer enable setpoint and there is a need for cooling. The economizer is used first to meet the space demand, and other forms of cooling are used if the economizer cannot meet the demand alone. See modulating outdoor air damper operation for additional information.
Cascade cooling control initiates a discharge air tempering function if the discharge air temperature falls below the discharge air temperature control low limit, all cooling capacity is at minimum, and the discharge control loop determines a need to raise the discharge air temperature.
The controller then provides heating capacity to raise the discharge air temperature to its low limit.
Discharge Air Tempering
The discharge air tempering function enables when cold outdoor air is brought in through the outdoor air damper, causing the discharge air to fall below the discharge air temperature control low limit. The controller exits the discharge air tempering function when heat capacity has been at 0% for five minutes.
Heating Operation
During heating mode, the Tracer ZN520 controller attempts to maintain the space temperature at the active heating setpoint. Based on the occupancy mode of the controller, the active heating setpoint is one of the following:
• Occupied heating
• Occupied standby heating
• Unoccupied heating
During dehumidification in the heating mode, the controller adjusts the heating setpoint up to the cooling setpoint. This reduces the relative humidity in the space with a minimum of energy usage.
UNT-SVX07B-EN 91
Start-Up
The controller uses the measured space temperature, the active heating setpoint, and discharge air temperature, along with the control algorithm, to determine the requested heating capacity of the unit (0%–100%). The outputs are controlled based on the unit configuration and the required heating capacity.
Unit diagnostics can affect the Tracer ZN520 controller operation, causing unit operation to be defined as abnormal. Refer to the Troubleshooting section for more information about abnormal unit operation.
The heating output is controlled based on the heating capacity. At 0% capacity, the heating output is off continuously. Between 0% and 100% capacity, the heating output is controlled according to modulating valve logic (modulating valves) or cycled on (two-position valves). As the load increases, modulating outputs open further and binary outputs are energized longer. At 100% capacity, the heating valve is fully open (modulating valves) or on continuously (two-position valves).
The Tracer ZN520 fan output(s) normally run continuously during the occupied and occupied standby modes, but cycle between high and off speeds with heating/cooling during the unoccupied mode. When in the occupied mode or occupied standby mode and the fan speed is set at the high, medium, or low position, the fan runs continuously at the selected speed. Refer to the
Troubleshooting section for more information on abnormal fan operation.
When the unit’s supply fan is set to auto, the controller’s configuration determines the fan speed when in the occupied mode or occupied standby mode. The fan runs continuously at the configured heating fan speed or cooling fan speed. For all fan speed selections except off, the fan cycles off during unoccupied mode.
The economizer outdoor air damper is never used as a source of heating. Instead, the economizer damper (when present) is only used for ventilation; therefore, the damper is at the occupied minimum position in the occupied mode. The damper control is primarily associated with occupied fan operation.
Fan Mode Operation
For multiple fan speed applications, the Tracer ZN520 controller offers additional fan configuration flexibility. Separate default fan speeds for heating and cooling modes can be configured. The fan runs continuously for requested speeds (off, high, medium, or low). When the fan mode switch is in the Auto position or a hardwired fan mode input does not exist, the fan operates at the default configured speed. See Table 21 for default fan configuration for heat and cool mode. During unoccupied mode, the fan cycles between high speed and off with heating and cooling fan modes.
If the requested speed is off, the fan always remains off.
Table 21. Fan configuration
Heating
Auto Fan Operation
Continuous
Cooling Continuous
Fan Speed Default
Off
Low
Medium
High
Off
Low
Medium
High
During dehumidification, when the fan is on Auto, the fan speed can switch depending on the error.
Fan speed increases as the space temperature rises above the active cooling setpoint.
Additional flexibility built into the controller allows you to enable or disable the local fan switch input. The fan mode request can be either hardwired or communicated to the controller. When both
92 UNT-SVX07B-EN
Start-Up
UNT-SVX07B-EN are present, the communicated request has priority over the hardwired input. See Table 22 ,
Table 23 , and Table 24 .
Table 22. Local fan switch enabled
Communicated Fan Speed Input Fan Switch (Local)
Off
Low
Medium
High
Auto
Low
Medium
High
Ignored
Ignored
Ignored
Ignored
Off
Auto
Low
Medium
High
Off
Auto (configured default, determined by heat/cool mode)
Fan Operation
Off
Low
Medium
High
Table 23. Fan operation in heating and cooling modes
Fan Mode
Off
Low
Medium
High
Auto
Occ.
Off
Low
Med
High
Default fan sp.
Heating
Unocc.
Off
Off/high
Off/high
Off/high
Off/high
Cooling
Occ. Unocc.
Off
Low
Med
High
Default fan sp.
Off
Off/high
Off/high
Off/high
Off/high
Table 24. Local fan switch disabled or not present
Communicated Fan Speed Input
Off
Low
Medium
High
Auto (or not present)
Fan Operation
Off
Low
Medium
High
Auto (fan runs at the default speed)
Continuous Fan Operation
During occupied and occupied standby modes, the fan normally is on. For multiple speed fan applications, the fan normally operates at the selected or default speed (off, high, medium, or low).
When fan mode is auto, the fan operates at the default fan speed.
During unoccupied mode, the controller controls the fan off. While unoccupied, the controller heats and cools to maintain the unoccupied heating and cooling setpoints. In unoccupied mode, the fan is controlled on high speed only with heating or cooling.
The unit fan is always off during occupied, occupied standby, and unoccupied modes when the unit is off due to a diagnostic or when the unit is in the off mode due to the local zone sensor module, a communicated request, or the default fan speed (off).
93
Start-Up
94
If both a zone sensor module and communicated request exist, the communicated request has priority.
Fan Cycling Operation
Tracer ZN520 does not support fan cycling in occupied mode.
The fan cycles between high speed and off in the unoccupied mode only. The controller’s cascade control algorithm requires continuous fan operation in the occupied mode.
Fan Off Delay
When a heating output is controlled off, the Tracer ZN520 controller automatically holds the fan on for an additional 30 seconds. This 30-second delay gives the fan time to blow off any residual heat from the heating source, such as a steam coil. When the unit is heating, the fan off delay is normally applied to control the fan; otherwise, the fan off delay does not apply.
Fan Start on High Speed
On a transition from off to any other fan speed, the Tracer ZN520 controller automatically starts the fan on high speed and runs the fan at high speed for 0.5 seconds. This provides the ample torque required to start all fan motors from the off position.
Entering Water Temperature Sampling Function
Only units using the main hydronic coil for both heating and cooling (2-pipe changeover and 4-pipe changeover units) use the entering water temperature sampling function. Two-pipe changeover and 4-pipe changeover applications allow the main coil to be used for heating and for cooling; therefore, these applications require an entering water temperature sensor.
When three-way valves are ordered with a Tracer ZN520 control, the controller is factoryconfigured to disable the entering water temperature sampling function, and the entering water sensor is mounted in the proper location. Disabling entering water temperature sampling eliminates unnecessary water flow through the main coil when three-way valves are used.
The controller invokes entering water temperature sampling only when the measured entering water temperature is too cool to heat or too warm to cool. Entering water is cold enough to cool when it is five degrees below the measured space temperature. Entering water is warm enough to heat when it is five degrees above the measured space temperature.
When the controller invokes the entering water temperature sampling function, the unit opens the main hydronic valve for no more than three minutes before considering the measured entering water temperature. An initial stabilization period is allowed to flush the coil. This period is equal to 30 seconds plus 1/2 the valve stroke time. Once this temperature stabilization period has expired, the controller compares the entering water temperature against the effective space temperature
(either hardwired or communicated) to determine whether the entering water can be used for the desired heating or cooling. If the water temperature is not usable for the desired mode, the controller continues to compare the entering water temperature against the effective space temperature for a maximum of three minutes.
The controller automatically disables the entering water temperature sampling and closes the main hydronic valve when the measured entering water exceeds the high entering water temperature limit (110°F). When the entering water temperature is warmer than 110°F, the controller assumes the entering water temperature is hot because it is unlikely the coil would drift to a high temperature unless the actual loop temperature was very high.
If the entering water temperature is unusable — too cool to heat or too warm to cool — the controller closes the hydronic valve and waits 60 minutes before initializing another sampling. If the controller determines the entering water temperature is valid for heating or cooling, it resumes normal heating/cooling control and effectively disables entering water temperature sampling until it is required.
UNT-SVX07B-EN
Start-Up
UNT-SVX07B-EN
Electric Heat Operation
The Tracer ZN520 controller supports one or two-stage electric heat operation for heating. To control the space temperature, electric heat is cycled to control the discharge air temperature. The rate of cycling is dependent upon the load in the space and the temperature of the incoming fresh air from the economizer (if any). Two-pipe changeover units with electric heat use the electric heat only when hot water is not available.
Manual Fresh Air Damper
Units with the manual fresh air damper option ship with the damper in the closed position, which is adjustable from zero to 100% in 25% increments. To adjust the position, first remove the air filter to expose the damper stop screw on the control panel end. Relocate the stop screw to the appropriate position. Then loosen the stop screw wingnut and adjust the linkage.
Economizer Damper Option
With a valid outdoor air temperature (either hardwired or communicated), Tracer ZN520 uses the modulating economizer damper as the highest priority source of cooling. Economizer operation is only possible through the use of a modulating damper.
Economizing is possible during the occupied, occupied standby, unoccupied, and occupied bypass modes.
The controller initiates the economizer function if the outdoor air temperature is cold enough to be used as free cooling capacity. If the outdoor air temperature is less than the economizer enable setpoint (absolute dry bulb), the controller modulates the outdoor air damper (between the active minimum damper position and 100%) to control the amount of outdoor air cooling capacity. When the outdoor air temperature rises 5°F above the economizer enable point, the controller disables economizing and moves the outdoor air damper back to its predetermined minimum position based on the current occupancy mode or communicated minimum damper position.
Table 25. Relationship between outdoor temperature sensors and damper position
Outdoor Air Temp.
Modulating Outdoor Air Damper
None or invalid
Occupied or
Occupied Bypass
Open to occupied minimum position
Occupied Standby
Open to occupied standby minimum position
Failed Open to occupied minimum position
Present and economizing feasible
Economizing minimum postion to 100%
Present & economizing not feasible
Open to occupied minimum position
Open to occuied standby minimum position
Economizing between occupied standby minimum position to 100%
Open to occupied standby minimum position
Unoccupied
Closed
Closed
Open & economizing when unit is operating, closed
Closed
Dehumidification
Dehumidification is possible when mechanical cooling is available, the heating capacity is located in the reheat position, and the space relative humidity setpoint is valid.The controller starts dehumidifying the space when the space humidity exceeds the humidity setpoint.
The controller continues to dehumidify until the sensed humidity falls below the setpoint minus the relative humidity offset.The controller uses the cooling and reheat capacities simultaneously to dehumidify the space. While dehumidifying, the discharge air temperature is controlled to maintain the space temperature at the current setpoint.
A typical scenario involves high humidity and high temperature load of the space.The controller sets the cooling capacity to 100% and uses the reheat capacity to warm the discharge air to maintain space temperature control. Dehumidification may be disabled via Tracer or configuration.
Note:
If the unit is in the unoccupied mode, the dehumidification routine will not operate.
95
Start-Up
96
Data Sharing
Because this controller utilizes LonWorks™ technology, the controller can send or receive data
(setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other controllers on the communication link, with or without the existence of a building automation system. This applies to applications where multiple unit controllers share a single space temperature sensor (for rooms with multiple units but only one zone sensor) for both standalone (with communication wiring between units) and building automation system applications. For this application you will need to use the Rover service tool. For more information on setup, refer to the Trane publication
EMTX-SVX01G-EN, or the most recent version.
Binary Inputs
The Tracer ZN520 controller has four available binary inputs (see Table 26 ). Normally, these inputs are factory-configured for the following functions:
• Binary input 1: Low temperature detection (freezestat)
• Binary input 2: Condensate overflow
• Binary input 3: Occupancy/ Generic
• Binary input 4: Fan status
Note:
The generic binary input can be used with a Tracer Summit® building automation system only.
Each binary input default configuration (including normally open/closed) is set at the factory.
However, you can configure each of the four binary inputs as normally open or normally closed.
The controller will be set properly for each factory-supplied binary input end-device. When no device is connected to the input, configure the controller’s input as not used.
Table 26. Binary input configurations
Binary Input
BI 1
BI 2
BI 3
BI 3
Description
Low temperature detection
(a)
Condensate overflow
(a)
Occupancy
Generic binary input
Fan status
(a)
Configuration
Controller Operation
Contact Closed Contact Open
Normally closed
Normally closed
Normally open
Normally open
Normal
Normal
Unoccupied
Normal
(c)
Diagnostic
(b)
Diagnostic
Occupied
Normal
(c)
(b)
Normally open Normal Diagnostic
(d)
BI 4
Note:
The occupancy binary input is for standalone unit controllers as an occupied/unoccupied input. However, when the controller receives a communicated occupied/unoccupied request, the communicated request has priority over the hardwired input.
(a) During low temperature, condensate overflow, and fan status diagnostics, the Tracer ZN520 control disables all normal unit operation of the fan, valves, and damper.
(b) Table 27, p. 97 shows the controller’s response to low temperature detection, condensate overflow, and fan status diagnostics.
(c) The generic binary input does not affect unit operation. A building automation system reads this input as a generic binary input.
(d) If the fan mode input is in the off position or the controller is in the unoccupied mode with the fan off, the fan status input will be open. A diagnostic will not be generated when the controller commands the fan off. A diagnostic will only be generated if the fan status input does not close after one minute from energizing a fan output or any time the input is open for one minute. The controller waits up to one minute after energizing a fan output to allow the differential pressure to build up across the fan.
Binary Outputs
Binary outputs are configured to support the following:
• Three fan stages (when one or two fan stages are present, medium fan speed can be configured as exhaust fan)
• One hydronic cooling stage
• One hydronic heating stage (dehumidification requires this to be in the reheat position)
UNT-SVX07B-EN
UNT-SVX07B-EN
Start-Up
• One DX cooling stage
• One or two-stage electric heat (dehumidification requires this to be in the reheat position)
• Face and bypass damper
• Modulating outdoor air damper
• One baseboard heat stage
For more information, see Table 27 .
Table 27. Binary output configuration
Binary Output Configuration
J1-1
J1-2
J1-3
J1-4
J1-5
J1-6
J1-9
J1-10
Fan high
Fan medium
Fan low
(Key)
Cool valve—open, or 2-position valve
(a)
Cool valve—close Note 1
Heat valve—open, or 2 position valve, or 1st electric heat stage
(a)
Heat valve—close or 2nd Electric heat stage
(a)
J1-11
J1-12
TB4-1
TB4-2
Fresh air damper—open
Fresh air damper—close
Generic/baseboard heat output
24 Vac
(a) For Tracer ZN520 units configured and applied as 2-pipe hydronic heat/cool changeover, terminals J1-5 and J1-6 are used to control the primary valve for both heating and cooling. For Tracer ZN520 units configured and applied as 2-pipe hydronic heat/cool changeover with electric heat, terminals J1-5 and J1-6 are used to control the primary valve (for both cooling and heating), and terminals J1-9 and J1-10 are used only for the electric heat stage. For those 2-pipe changeover units, electric heat will not be energized while the hydronic supply is hot (5° or more above the space temperature).
97
Start-Up
98
Table 28. Analog inputs
Description
Zone
Ground
Set
Fan
Ground
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Ground
Terminals
TB3-1
TB3-2
TB3-3
B3-4
TB3-6
J3-1
J3-2
J3-3
J3-4
J3-5
J3-6
J3-7
J3-8
J3-9
Function Range
Space temperature input
Analog ground
Setpoint input
Fan switch input
5°F to 122°F (-15°C to 50°C)
NA
40°F to 115°F (4.4°C to 46.1°C)
4821 to 4919 W (off)
2297 to 2342 W (auto)
10593 to 10807 W (low)
13177 to 13443 W (medium)
15137 to 16463 W (high)
Analog ground
Entering water temperature
Analog ground
Discharge air temperature
Analog ground
Fresh air temp/generic temp
Analog ground
Universal input
NA
-40°F to 212°F (-40°C to 100°C)
NA
-40°F to 212°F (-40°C to 100°C)
NA
-40°F to 212°F (-40°C to 100°C)
NA
0% to 100%
Generic 4–20mA
Humidity
0% to 100%
0 to 2000 ppm
CO
2
Analog ground NA
Analog ground NA
Notes:
1. The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air temperature sensor are
10K Ω thermistors.
2. Zone sensor: Wall-mounted sensors include a thermistor soldered to the sensor’s circuit board. Unit mounted sensors include a return air sensor in the units return air stream.
3. Changeover units include an entering water temperature sensor.
Zone Sensor
The Tracer ZN520 controller accepts the following zone sensor module inputs:
• Space temperature measurement (10k
Ω
thermistor)
• Local setpoint (either internal or external on the zone sensor module)
• Fan switch
• Timed override (On) and Cancel timed override
• Communication jack
Space Temperature Measurement
Trane zone sensors use a 10k
Ω
thermistor to measure the space temperature. Typically, zone sensors are wall-mounted in the room and include a space temperature thermistor. As an option, the zone sensor can be unit-mounted with a separate space temperature thermistor located in the unit’s return air stream. If both a hardwired and communicated space temperature value exist, the controller ignores the hardwired space temperature input and uses the communicated value.
External Setpoint Adjustment
Zone sensors with an external setpoint adjustment (1k
Ω
) provide the Tracer ZN520 controller with a local setpoint (50°F to 85°F or 10°C to 29.4°C). The external setpoint is exposed on the zone sensor’s front cover.
UNT-SVX07B-EN
UNT-SVX07B-EN
Start-Up
When the hardwired setpoint adjustment is used to determine the setpoints, all unit setpoints are calculated based on the hardwired setpoint value, the configured setpoints, and the active mode of the controller. The hardwired setpoint is used with the controller’s occupancy mode (occupied, occupied standby, or unoccupied), the heating or cooling mode, the temperature deadband values, and the heating and cooling setpoints (high and low limits) to determine the controller’s active setpoint.
When a building automation system or other controller communicates a setpoint to the controller, the controller ignores the hardwired setpoint input and uses the communicated value. The exception is the unoccupied mode, when the controller always uses the stored default unoccupied setpoints. After the controller completes all setpoint calculations, based on the requested setpoint, the occupancy mode, the heating and cooling mode, and other factors, the calculated setpoint is validated against the following setpoint limits:
• Heating setpoint high limit
• Heating setpoint low limit
• Cooling setpoint high limit
• Cooling setpoint low limit
These setpoint limits only apply to the occupied and occupied standby heating and cooling setpoints. These setpoint limits do not apply to the unoccupied heating and cooling setpoints stored in the controller’s configuration.
When the controller is in unoccupied mode, it always uses the stored unoccupied heating and cooling setpoints.The unit can also be configured to enable or disable the local (hardwired) setpoint. This parameter provides additional flexibility to allow you to apply communicated, hardwired, or default setpoints without making physical changes to the unit.
Similar to hardwired setpoints, the effective setpoint value for a communicated setpoint is determined based on the stored default setpoints (which determines the occupied and occupied standby temperature deadbands) and the controller’s occupancy mode.
Fan Switch
The zone sensor fan switch provides the controller with an occupied (and occupied standby) fan request signal (Off, Low, Medium, High, Auto). If the fan control request is communicated to the controller, the controller ignores the hardwired fan switch input and uses the communicated value.
The zone sensor fan switch input can be enabled or disabled through configuration using the Rover service tool. If the zone sensor switch is disabled, the controller resorts to its stored configuration default fan speeds for heating and cooling, unless the controller receives a communicated fan input.
When the fan switch is in the off position, the controller does not control any unit capacity. The unit remains powered and all outputs drive to the closed position. Upon a loss of signal on the fan speed input, the controller reports a diagnostic and reverts to using the default fan speed.
On/Cancel Buttons
Momentarily pressing the on button during unoccupied mode places the controller in occupied bypass mode for 120 minutes. You can adjust the number of minutes in the unit controller configuration using Rover service tool. The controller remains in occupied bypass mode until the override time expires or until you press the Cancel button.
Communication Jack
Use the RJ-11 communication as the connection point from Rover™ service tool to the communication link—when the communication jack is wired to the communication link at the controller. By accessing the communication jack via Rover™, you can access any controller on the link.
99
Start-Up
Communications
Tracer ZN520 controller communicates via Trane’s LonTalk protocol. Typically, a communication link is applied between unit controllers and a building automation system. Communication also is possible via Rover, Trane’s service tool. Peer-to-peer communication across controllers is possible even when a building automation system is not present. You do not need to observe polarity for
LonTalk communication links.
The controller provides six 0.25-inch quick-connect terminals for the LonTalk communication link connections, as follows:
• Two terminals for communication to the board
• Two terminals for communication from the board to the next unit (daisy chain)
• Two terminals for a connection from the zone sensor back to the controller
Table 29. Zone sensor wiring connections
4
5
2
3
6
TB1
1
Description
Space temperature
Common
Setpoint
Fan mode
Communications
Communications
100 UNT-SVX07B-EN
Maintenance
Maintenance Procedures
Perform the following maintenance procedures to ensure proper unit operation.
WARNING
Live Electrical Components!
During installation, testing, servicing, and troubleshooting this equipment, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who is properly trained in handling live electrical components perform these tasks. Failure to follow all electrical components could result in death or serious injury.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Air Filters
Change or clean air filters at least twice a year. Filters require more frequent care under high load or dirty air conditions since a clogged filter reduces airflow. Table 1, p. 14 lists filter size and quantity by unit size. Throwaway and pleated media filters are available for all units. Follow the instructions below to replace the disposable filters.
All Models Except Vertical Cabinets
Remove the front panel of the vertical recessed unit and open the bottom panel door of the horizontal cabinet and horizontal recessed unit to access the filter. The front panel of the vertical cabinet unit does not require removal to change the filter.
Note:
Vertical recessed, horizontal cabinet, and horizontal recessed units with a bottom return have filter guides to secure the filter in position. Also, if these unit types have a fresh air opening, they require an additional filter for the fresh air opening.
NOTICE
Replace All Panels and Filters Properly!
All unit panels and filters must be in place prior to unit startup. Failure to have panels and filters in place could result in equipment damage.
Inspecting and Cleaning Drain Pans
Clean the fan-coil unit’s main and auxiliary drain pans to ensure the unit drains condensate properly.
Check the condensate drain pan and drain line to assure the condensate drains properly at least every six months or as dictated by operating experience.
If evidence of standing water or condensate overflow exists, immediately identify and remedy the cause.
Clean the drain pans of any moisture or debris.
UNT-SVX07B-EN 101
Maintenance
Auxiliary Drain Pan
1.
To remove the auxiliary drain pan, loosen the hose clamp (installer supplied) around the drain connection collar and disconnect the drain line.
2. Remove the overflow drain line to the auxiliary drain pan if it was installed.
3. Remove the condensate overflow switch option from the auxiliary drain pan.
4. Slide the pan horizontally towards the end of the large groove of the mounting slots in the chassis end panel and remove pan from unit (see Figure 24 ).
Figure 24. Insert the auxiliary drain pan tabs into these slots in the fan-coil’s chassis end panel
(horizontal unit shown).
Aux. Drain Pan Attaches to These Slots
Main Drain Pan
See Figure 25 to replace main drain correctly.
Figure 25. When replacing the fan-coil’s main drain pan, install it correctly under the z-bar.
Co i l
M ai n Dr ai n
Z-B a r
Side
Vertical Units.
To remove the main drain pan on vertical fan-coil units, disconnect the clips holding the pan to the fanboard. Disconnect the main and overflow drain hoses and slide pan forward to remove (see Figure 26, p. 103 ).
102 UNT-SVX07B-EN
Maintenance
Figure 26. To remove the main drain pan on vertical fan-coil units, disconnect the clips holding the pan to the fanboard.
Clips Hold Drain Pan in Place
Horizontal Units.
To remove the main drain pan on a horizontal fan-coil unit, peel the insulation from the edges of the pan’s underside to access the mounting screws. Remove the screws and lower the end of the drain pan closest to the control box. Remove the drain spout by pulling it from the hole in the chassis end panel (see Figure 27 ).
Figure 27. To remove the main drain pan on horizontal fan-coil units, peel the insulation from the edges of the pan’s underside to access the mounting screws.
Mounting Screw
UNT-SVX07B-EN
Note:
Do not operate the fan-coil unit without the main and auxiliary drain pans in place to prevent condensate leakage.
Coil Maintenance
Keep coils clean to maintain maximum performance. For operation at its highest efficiency, clean the coil often during periods of high demand or when dirty conditions prevail. Clean the coil a minimum of once a year to prevent dirt buildup in the coil fins, where it may not be visible.
Remove large debris from the coils and straighten fins before cleaning. Remove filters before cleaning.
Clean the coil fins using steam with detergent, hot water spray and detergent, or a commercially available chemical coil cleaner. Be sure to rinse coils thoroughly after cleaning.
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper handling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data
Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury.
103
Maintenance
104
Inspecting and Cleaning Coils
Coils become externally fouled as a result of normal operation. Dirt on the coil surface reduces it’s ability to transfer heat that can result in comfort problems, increased airflow resistance and thus increased operating energy costs. If the coil surface dirt becomes wet, which commonly occurs with cooling coils, microbial growth (mold) may result, causing unpleasant odors and serious health-related indoor air quality problems.
Inspect coils at least every six months or more frequently as dictated by operating experience.
Cleaning frequently is dependent upon system operating hours, filter maintenance, and efficiency and dirt load. Follow the suggested methods in the following paragraphs.
Steam and Hydronic Coil Cleaning Procedure
1.
Disconnect all electrical power to the unit.
2. Don the appropriate personal protective equipment (PPE).
3. Access both sides of the coil.
4. Use a soft brush to remove loose debris from both sides of the coil.
5. Use a steam cleaning machine, starting from the top of the coil and working downward. Clean the leaving air side of the coil first, then the entering air side. Use a block-off to prevent steam from blowing through the coil and into a dry section of the unit.
6. Repeat step five as necessary. Confirm that the drain line is open following completion of the cleaning process.
7.
Allow the unit to dry thoroughly before putting the system back into service.
8. Straighten any coil fins that may be damaged with a fin rake.
9. Replace all panels and parts and restore electrical power to the unit.
Winterizing the Coil
Make provisions to drain coils that are not in use, especially when subjected to freezing temperatures.
To drain the coil, blow the coil out with compressed air. Next, fill and drain the tubes with fullstrength ethylene glycol several times. Drain the coil as completely as possible.
NOTICE
Coil Freeze-up Damage!
Failure to properly drain and vent coils when not in use during freezing temperatures may result in coil freeze-up damage.
Fan Board Assembly Removal
Follow the procedure below when replacing the coil or making repairs to the fan or motor.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Vertical Units.
UNT-SVX07B-EN
Maintenance
1.
Remove the front panel of cabinet and recessed units.
2. Pull the main and overflow drain hoses of the main drain pan into the inside of the fan-coil chassis end panel.
3. Remove the two fanboard mounting screws.
4. Slide the fanboard out horizontally to remove.
Horizontal Units.
1.
Open the bottom panel of cabinet and recessed models.
2. Remove the main drain pan following the instructions given under the drain pan section above for horizontal fan-coil units.
3. While supporting the fanboard in place, remove the two fanboard mounting screws which secure the fanboard to the unit.
NOTICE
Heavy Object!
Support the fanboard when removing it from the unit. Failure to properly support fanboard may result in minor to moderate personal injury.
Replacing the Motor
The capacitor for all unit motors can be replaced should it fail. Contact the local Trane service department to replace the motor capacitor in the event it fails. However, the motor itself cannot be repaired or rewound. If the motor fails, record the model number from the unit nameplate and present to the local Trane Service Parts Center to purchase a replacement. The motor bearings are permanently lubricated and do not require any further oiling.
After removing the fanboard assembly from the unit, disconnect the fan wheel/wheels from the motor shaft by loosening the Allen head setscrew on the fan wheel hub collar. Next, remove the mounting bolts holding the fan motor plate to the mounting bracket of the fanboard. Then remove the motor by sliding the fan shaft from the fan wheel hub.
During re-assembly, make certain the fan wheel(s) is/are properly centered in the fan housing to prevent the fan wheel from contacting the housing on either side. After the unit has been reassembled, verify that no unusual noise or vibration is present at startup.
Control Device Replacement
To order control components such as relays, contactors, transformers, low temperature detection devices, condensate overflow detection devices, differential pressure switches, sensors, control valves and actuators, contact the local Trane Service Parts Center. To order, the Trane parts center will need the unit model number (which can be found on the unit nameplate), the serial number, and the part name or ID.
Periodic Maintenance Checklists
Monthly Checklist
The following check list provides the recommended maintenance schedule to keep the unit running efficiently.
WARNING
Live Electrical Components!
During installation, testing, servicing, and troubleshooting this equipment, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who is properly trained in handling live electrical components perform these tasks. Failure to follow all electrical components could result in death or serious injury.
UNT-SVX07B-EN 105
Maintenance
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Monthly Maintenance
1.
Inspect unit air filters. Clean or replace if airflow is blocked or if filters are dirty.
2. Check the main and auxiliary drain pans on fan-coil units to be sure the pans are clean and do not impede the condensate flow through the drain line.
Annual Maintenance
Check and tighten all set screws, bolts, locking collars and sheaves.
1.
Inspect the unit cabinetry for chips or corrosion. Clean or repair to provide unit protection.
2. Inspect the fan wheel and housing for damage. Rotate the fan wheel manually to be sure movement is not blocked by obstructions.
3. Inspect the coil fins for excessive dirt or damage. Remove dirt and straighten fins.
4. Clean and tighten all electrical connections.
5. Inspect the strainer option for debris trapped in the filter screen.
106 UNT-SVX07B-EN
Diagnostics
Table 30. Tracer ZN520 diagnostics
Diagnostic Fan
Condensate overflow
Low temperature detection
Low air flow - fan failure
Space temperature failure
Entering water temp failure On
Discharge air temp low limit Off
Discharge air temp failure
Fresh air temp failure
Off
On
Off
Off
Off
Off
Relative humidity failure
Generic 4–20mA failure
CO
2
Input failure
Maintenance required
Local fan mode failure
Local setpoint failure
Invalid unit configuration
Normal—power up
On
On
Off
On
On
On
On
On
Other Outputs
(a)
Valves Closed, Fresh air damper Closed, Electric heat Off, Baseboard heat Off
Valves Open, Fresh air damper Closed, Electric heat Off, Baseboard heat Off
Valves Closed, Fresh air damper Closed, Electric heat Off, Baseboard heat Off
Valves Closed, Fresh air damper Closed, Electric heat Off, Baseboard heat Off
Valves Enabled
(b)
, Fresh air damper Enabled
(b)
, Electric heat Enabled
(b)
, Baseboard heat Off
Valves Open, Fresh air damper Closed, Electric heat Off, Baseboard heat Off
Valves Closed, Fresh air damper Closed, Electric heat Off, Baseboard heat Off
Valves Enabled, Fresh air damper Minimum position
(c)
, Electric heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled, Baseboard heat Enabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled, Baseboard heat Enabled
Valves Disabled, Fresh air damper Disabled, Electric heat Disabled, Baseboard heat Disabled
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled
(a) The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.
(b) When the entering water temperature is required but not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition.
The controller automatically clears the diagnostic once a valid entering water temperature value is present (non-latching diagnostic). When the entering water temperature sensor fails, the controller prohibits all hydronic cooling operation, but allows the delivery of heat when heating is required. In the
Cool mode, all cooling is locked-out, but normal fan and outdoor air damper operation is permitted.
(c) When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid outdoor air temperature value is present (non-latching diagnostic). When the outdoor air temperature sensor fails or is not present, the controller prohibits economizer operation.
Translating Multiple Diagnostics
The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they occur.
Possible diagnostics include:
• Low temperature detection
• Condensate overflow
• Low air flow—fan status
• Discharge air temp limit
• Space temperature failure
1
• Entering water temp failure
1
• Discharge air temp failure
1
• Outdoor air temp failure
1
• Local setpoint failure
1
• Local fan mode failure
1
• CO
2
sensor failure
1
• Generic AIP failure
1
• Humidity input failure
1
• Defrosting compressor lockout
1
• Maintenance required
• Invalid unit configuration
1
Non-latching diagnostics automatically reset when the input is present and valid.
UNT-SVX07B-EN 107
Diagnostics
• Generic temperature failure
• Discharge air low limit
Resetting Diagnostics
There are a number of ways in which diagnostics are reset:
1.
Automatic reset by the controller
2. By initiating a manual output test at the controller
3. By cycling power to the controller
4. Through Rover™, Trane’s service tool
5. Tracer ZN520: by using any other communicating device ab le to access the controller’s diagnostic reset input.
6. Tracer ZN520: by cycling the fan switch from Off to any speed setting.
Automatic Reset by the Controller
The controller includes an automatic diagnostic reset function that attempts to automatically restore the unit when a low temperature diagnostic occurs.
Note:
The controller implements the automatic diagnostic reset function only once every
24 hours. For the controller to increment the 24 hour timer, you must maintain power to the controller. Cycling power resets all timers and counters.
After the controller detects the first special diagnostic, the unit waits 30 minutes before invoking the automatic diagnostic reset function. The automatic diagnostic reset function clears the special diagnostic and attempts to restore the controller to normal operation. The controller resumes normal operation until another diagnostic occurs.
Note:
The automatic diagnostic reset function does not operate during the manual output test sequence.
If a special diagnostic occurs within 24 hours after an automatic diagnostic reset, the controller must be manually reset. Other possible methods of resetting diagnostics are described in the sections that follow.
Manual Output Test
To verify proper end device operation, press the controller’s Test button. This exercise will verify all outputs in a predefined sequence, the first of which will attempt to reset the controller diagnostics if any are present.
Cycling Power to the Controller
After removing and reapplying the 24 Vac power from the board, the unit cycles through a powerup sequence. By default, the controller attempts to reset all diagnostics present at power-up.
Diagnostics present at power-up and those that occur after power-up are handled according to
Table 31, p. 109 .
108 UNT-SVX07B-EN
UNT-SVX07B-EN
Diagnostics
Table 31. Tracer ZN510 controller diagnostics
Diagnostic
Auxiliary temp. failure
Condensate overflow detection
Entering water temp. failure
Fan mode failure
Invalid unit configuration failure
Low temp. detection
Maintenance required
Setpoint
Zone temp. failure
Latching?
Yes
Yes
Yes
No
No
No
Yes
No
No
Fan
Enabled
Off
Enabled
Enabled
Disabled
Off
Enabled
Enabled
Off
Valves
No action
Closed
Enabled
Enabled
Disabled
Open
No action
No action
Closed
Elec Heat
No action
Off
Enabled
Enabled
Disabled
Off
No action
No action
Off
Damper
No action
Closed
Enabled
Enabled
Disabled
Closed
No action
No action
Closed
Notes:
1. Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics affect unit operation according to priority level.
2. Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic automatically resets when the input is present and valid.
3. Enabled: End device is allowed to run if there is a call for it to run.
4. Disabled: End device is not allowed to run even if there is a call for it to run.
5. No Action: The diagnostic has no affect on the end device.
Using Trane’s Service Tool, Rover™
Rover™, Trane’s service tool, can reset diagnostics present in the controller and troubleshoot the unit. For more information, refer to the Trane publication EMTX-SVX01G-EN (
Rover Service Tool:
Installation, Operation, and Programming Guide
).
Diagnostic Reset
Any device that can communicate the network variable nviRequest (enumeration “clear_alarm”) can reset diagnostics in the Tracer ZN520 controller.The controller also attempts to reset diagnostics whenever power is cycled.
Cycling the Fan Switch
Cycle the fan speed switch from Off to any speed and the controller resets all diagnostics.
Diagnostics may recur immediately if the problem still exists.
109
Diagnostics
Table 32. Fan outputs do not energize
Probable Cause
Random start
Power-up control wait
Cycling fan operation
Unoccupied operation
Fan mode off
Requested mode: off
Diagnostic present
No power to the controller
Manual output test
Unit wiring
Explanation
After power-up, the controller always observes a random start that varies observed between 0 and 25 seconds. The controller remains off until the random start time expires.
When power-up control wait is enabled (non-zero time), the controller remains off until one of two conditions occurs:
1. The controller exits power-up control wait once it receives communicated information.
2. The controller exits power-up control wait once the power-up control wait time expires.
When the fan mode switch is in the auto postion, the unit fan cycles off when there is no call for heating or cooling.
The heating/cooling sources cycle on or off periodically with the unit fan to match the capacity according to pulsewidth-modulation (PWM) logic.
The fan cycles with capacity when the unit is in unoccupied mode. This occurs even if the unit is in continuous fan operation. While unoccupied, the fan cycles on or off with heating/cooling to provide varying amounts of heating or cooling to the space to match the to pulse-width-modulation (PWM) logic.
When using the local fan mode switch to determine the fan operation, the off position controls the unit fan to off.
It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When “off” is communicated to the controller, the unit controls the fan to off. The unit is not capable of heating or cooling when the controller is in this mode.
A specific list of diagnostics effects fan operation. For more information, see “Diagnostics,” p. 107 .
If the controller does not have power, the unit fan will not operate. For the controller to operate normally, it must have an input voltage of 24 Vac. When the green LED is off continuously, the controller does not have sufficient power or the controller has failed.
The controller includes a manual output test sequence to verify binary output operation and the associated wiring.
However, based on the current step in the test sequence, the unit fan may not be powered on. Refer to “Manual Output
Test,” p. 108 .
The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan operation. Refer to the typical unit wiring diagrams (see “Wiring Diagrams,” p. 126 ).
Table 33. Valves stay closed
Probable Cause
Normal operation
Requested mode: off
Valve override
Manual output test
Diagnostic present
Sampling logic
Unit configuration
No power to the controller
Unit wiring
Explanation
The controller opens and closes the valves to meet the unit capacity requirements.
It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When off is communicated to the controller, the unit controls the fan to off. The unit is not capable of heating or cooling when the controller is in this mode.
The controller can communicate a valve override request. This request affects the valve operation.
The controller includes a manual output test sequence to verify analog and binary output operation and the associated wiring. However, based on the current step in the test sequence, the valves may not be open. Refer to “Manual Output
Test,” p. 108 .
A specific list of diagnostics affects valve operation. For more information, see “Diagnostics,” p. 107 .
The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe changeover. It determines when the entering water temperature is either too cool or too hot for the desired heating or cooling mode. Refer to “Entering Water Temperature Sampling Function,” p. 86 .
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the valves may not work correctly.
If the controller does not have power, the valves do not operate. For the controller controller to operate normally, it must have an input voltage of 24 Vac. When the green LED is off continuously, the controller does not have sufficient power,or the controller has failed.
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation.
Refer to the typical unit wiring diagrams (see “Wiring Diagrams,” p. 126 ).
110 UNT-SVX07B-EN
Diagnostics
Table 34. Valves stay open
Probable Cause
Normal operation
Valve override
Manual output test
Diagnostic present
Sampling logic
Unit configuration
Unit wiring
Explanation
The controller opens and closes the valves to meet the unit capacity requirements.
The controller can communicate a valve override request to affect the valve operation.
The controller includes a manual output test sequence that verifies analog and binary output operation and the associated wiring. However, based on the current step in the test sequence, the valves may be open. Refer to “Manual
Output Test,” p. 108 .
A specific list of diagnostics affects valve operation. For more information, see “Diagnostics,” p. 107 .
The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe changeover to determine if the entering water temperature is correct for the unit operating mode. Refer to “Entering
Water Temperature Sampling Function,” p. 86 .
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the valves may not work correctly.
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation.
Refer to the typical unit wiring diagrams (see “Wiring Diagrams,” p. 126 ).
Table 35. Electric heat not operating
Probable Cause
Normal operation
Requested mode: off
Communicated disable
Manual output test
Diagnostic present
Unit configuration
No power to the controller
Unit wiring
Explanation
The controller cycles electric heat on and off to meet the unit capacity requirements.
It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the controller, the units shuts off the electric heat.
Numerous communicated requests may disable electric heat, including an auxiliary heat enable input and the heat/ cool mode input. Depending on the state of the communicated request, the unit may disable electric heat.
The controller includes a manual output test sequence that verifies analog and binary output operation and associated output wiring. However, based on the current step in the test sequence, the electric heat may not be on. Refer to
“Manual Output Test,” p. 108 .
A specific list of diagnostics affects electric heat operation. For more information, see “Diagnostics,” p. 107 .
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the electric heat may not work properly.
If the controller does not have power, electric heat does not operate. For the controller to operate normally, a 24 Vac input voltage must be applied. When the green LED is off continuously, the controller does not have sufficient power or has failed.
The wiring between the controller outputs and the electric heat contacts must be present and correct for normal electric heat operation. Refer to the typical unit wiring diagrams (see “Wiring Diagrams,” p. 126 ).
Table 36. Fresh air damper stays open
Probable Cause
Normal operation
Manual output test
Unit configuration
Unit wiring
Explanation
The controller opens and closes the fresh air damper based on the controller’s occupancy mode and fan status.
Normally, the fresh air damper is open during occupied mode when the fan is running and closed during unoccupied mode.
The controller includes a manual output test sequence that verifies analog and binary output operation and associated output wiring. However, based on the current step in the test sequence, the fresh air damper may not be open. Refer to “Manual Output Test,” p. 108 .
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the damper may not work correctly.
The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer to the typical unit wiring diagrams (see “Wiring Diagrams,” p. 126 ).
UNT-SVX07B-EN 111
Diagnostics
Table 37. Fresh air damper stays closed
Probable Cause
Normal operation
Warmup and cooldown
Requested mode: off
Manual output test
Diagnostic present
Unit configuration
No power to the controller
Unit wiring
Explanation
The controller opens and closes the fresh air damper based on the controller’s occupancy mode and fan status.
Normally, the fresh air damper is open during occupied mode when the fan is running and closed during unoccupied mode.
The controller includes both a warmup and cooldown sequence to keep the fresh air damper closed during the transition from unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible.
It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the controller, the unit closes the fresh air damper.
The controller includes a manual output test sequence that verifies analog and binary output operation and associated output wiring. However, based on the current step in the test sequence, the fresh air damper may not be open. Refer to “Manual Output Test,” p. 108 .
A specific list of diagnostics effects fresh air damper operation. For more information, see “Diagnostics,” p. 107 .
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does not match the actual end device, the damper may not work correctly.
If the controller does not have power, the fresh air damper does not operate. For the controller to operate normally, a 24 Vac input voltage must be applied. When the green LED is off continuously, the controller does not have sufficient power or has failed.
The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer to the typical unit wiring diagrams (see “Wiring Diagrams,” p. 126 ).
112 UNT-SVX07B-EN
Diagnostics
Troubleshooting
Troubleshooting the Relay (Daughter) Board
The relay board serves as a common interface to all of the standard end devices, and has an LED that indicates power to the board. Factory switches are pre-set and locked in place with LocTite
®
.
However, these seals can be broken if field-modifications are needed.
If the board needs replacement, the switches on the new board must be field-set in the same positions as the old board, as shown in the unit wiring diagram.
Note:
SW3 and SW4 affect safety functionality, and they are factory secured. When replacing a board with SW3 and SW4, be sure to affix the switch positions with 3M 3764Q or equivalent.
Board switches are factory set based on unit control options. Figure 29 shows a relay board detail.
Additional information on switch settings follows.
Figure 28. Resistance temperature curve for the zone sensor, entering water temperature sensor, and discharge air sensor (thermistor = 10k
Ω
at 77°F)
UNT-SVX07B-EN 113
Diagnostics
114
Figure 29. Relay board detail
LED Indicates Power
Interface to Tracer ZN Controller
Configuration Switches
(Factor Pre-set)
Connection to Valve and
Piping Sensor Crossover
Harness
Do Not Adjust These
Switch Positions
Because it May Result in a Safety Hazard!
Note: HAZARDOUS Voltage in
Dashed Area of Board!
Switch SW1: Controller Type
SW1 determines the unit control type.
Position 1 indicates one of the following:
• generic field controller
• low-voltage fan speed switch
• Tracer ZN010
• Tracer ZN510
Position 2 indicates Tracer ZN520.
Switch SW2: Electric Heat
SW2 determines if the unit has electric heat.
Switch SW3: High-Speed Interlock
SW3 determines if the unit will have a safety-mandated “high-speed interlock” with electric heat.
High-speed interlock ensures heat dissipates in a manner that keeps the unit in a safe operating condition. SW3 configures the unit to actuate high-speed interlock if the first or second stage is on.
SW3 is a three-position slide switch that actuates high-speed interlock to operate with specific electric heat coils.
• Position 1: default position and for low vertical units with electric heat
• Position 2: single-stage electric heat, model number digit 18 = N
• Position 3: two-stage electric
Switch SW4: Electric Heat Lockout
SW4 allows the unit to use the electric heat lockout function when hydronic heat is in operation.
Electric heat lockout prevents electric heat from enabling when hydronic heating is available. This
UNT-SVX07B-EN
Diagnostics
feature is on models with both hydronic and electric heat. Low vertical models with electric heat, switch SW4 to position 2 (on).
Troubleshooting Wireless Controls
Locations of LEDs, Test button, Test Symbols, and Error Codes
The receiver for all models has four LEDs: LED1, LED2, LED3, and LED5. Figure 30 shows their locations.
Note:
To view LEDs on a flush mount receiver on a fan-coil unit, the front panel of the unit must be removed.
Figure 30. LED locations on the receiver
LED1
LED2
LED3
LED5
The sensor for model WTS have four LEDs: LED1, LED2, LED3, and LED5. The sensor for model
WDS has test symbols and error codes that appear on the display. All three sensor models have a Test button. Figure 31 shows their locations.
UNT-SVX07B-EN 115
Diagnostics
Figure 31. LED, Test button, and symbol locations on the sensor
LED1
LED2
LED3
LED5
.
Test symbols
Error code
Test button
Test button
WTS sensor WDS sensor
Diagnostics
LED1, LED2, and LED3, located on the sensor of model WTS respond to diagnostics by exhibiting specific blinking patterns. View their response by pressing the Test button (see Table 38 ).
Error codes appear on the display of the model WDS sensor when diagnostics occur (see Table 38 ).
Table 38. Diagnostics on the sensor
LED state when Test button is pressed
(WTS sensor)
N/A
Error code (WDS sensor display)
E0, E5, E7
Indicates...
Sensor failure
• Replace sensor
Disassociated
• Sensor is not associated with a receiver.
LED1: Off
LED2: Off
LED3
(a)
: 1-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3
(a)
: 2-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3
(a)
: 3-blink pattern repeated 3 times
LED1: Off
LED2: Off
LED3
(a)
: 4-blink pattern repeated 3 times
E1
E2
E3
E4
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
Address set to 000
• Address not set to between 001–999.
Software error
• Replace sensor
Input voltage too high
• No RF transmission is permitted with an input battery voltage greater than 3.9 V.
116 UNT-SVX07B-EN
Diagnostics
LED1, LED2, and LED3, located on the receiver of all models, respond to diagnostics by exhibiting specific blinking patterns. They respond independently of any user action (see Table 39 ).
Table 39. Diagnostics on the receiver
LED state Indicates...
LED1: Off
LED2: Off
LED3: 1-blink pattern repeated continuously
(a)
Disassociated
• Receiver is not associated, waiting for a sensor.
• Receiver lost communication with sensor.
• Receiver has no devices on its wireless personal area network.
• Association with a device has been manually removed.
Address set to 000
• Address not set to between 001–999.
LED1: Off
LED2: Off
LED3: 2-blink pattern repeated continuously
(a)
LED1: Off
LED2: Off
LED3: 3-blink pattern repeated continuously
(a)
Not configured
• Receiver configuration properties not properly set (defective receiver).
(a) Blink pattern is On for 1/4 s, Off for 1/4 s, with 2 s Off between repetitions.
Testing Signal Strength
To initiate a signal strength test, push the Test button on the sensor (see location of Test button in
Figure 31, p. 116 ).
•
Models WTS:
LED1, LED2, and LED3 respond by indicating signal strength. You can view them on the sensor ( Table 40 ) and the receiver ( Table 41, p. 118 ).
•
Model WDS:
Test symbols on the sensor display indicate signal strength ( Table 40 ). LED1, LED2, and LED3, on the receiver, respond by indicating signal strength ( Table 41, p. 118 ).
Table 40. Observing signal strength on the sensor
User action LED state (WTS sensors)
None LED1: Off
LED2: Off
LED3: Off
Press Test button on the sensor
LED1: Off
LED2: Off
LED3: Off
Symbol (WDS sensor display)
No Test symbols appear
Indicates...
Normal state
• No Test button press.
Associated; no communication with receiver
• Associated, but no signal from the receiver after pressing Test button.
LED1: On
LED2: On
LED3: On
Displays for 5 seconds, then constantly
Off
LED1: Off
LED2: On
LED3: On
Displays for 5 seconds, then constantly
Off
LED1: Off
LED2: Off
LED3: On
Displays for 5 seconds, then constantly
Off
Excellent signal strength
• Good signal margin for reliable communication.
Satisfactory signal strength
• Adequate signal strength for reliable communication.
• Moving sensor or receiver may improve signal strength.
• Increased channel switching may reduce battery life.
Poor signal strength
• Unreliable communication.
• Strongly recommend moving the sensor or receiver to a better location.
UNT-SVX07B-EN 117
Diagnostics
Table 41. Observing signal strength on the receiver
User action LED state (receiver, all models)
None LED1: Off
LED2: Off
LED3: Off
Press Test button on the sensor
LED1: On
LED2: On
LED3: On
Displays for 5 seconds, then constantly Off
LED1: Off
LED2: On
LED3: On
Displays for 5 seconds, then constantly Off
LED1: Off
LED2: Off
LED3: On
Displays for 5 seconds, then constantly Off
Indicates...
Normal state
• No Test button press.
Excellent signal strength
• Good signal margin for reliable communication.
Satisfactory signal strength
• Adequate signal strength for reliable communication.
• Moving sensor or receiver may improve signal strength.
• Increased channel switching may reduce battery life.
Poor signal strength
• Unreliable communication
• Strongly recommend moving the sensor or receiver to a better location
Testing Battery Status
Initiate a battery status test as follows:
• On model WTS, push the Test button on the sensor (see location on Figure 31, p. 116 ). LED5 on the sensor responds by indicating the level of battery strength, as shown in Table 42 .
• On model WDS, push the Test button on the sensor (see location on Figure 31, p. 116 ). In response, a battery test symbol appears on the display. The symbol shown indicates battery life expectancy (see Table 43, p. 118 ).
Table 42. Battery status: LED5 on model WTS sensors
User action LED state (WTS)
Press Test button Solid green for 5 seconds
Indicates...
Battery is adequate for proper operation.
None
Solid red for 5 seconds
No light
25% battery life left. Batteries should be replaced.
Batteries life expired or not installed properly, or sensor is defective.
Blinking red: 1-blink pattern
(a)
repeated 5 times.
Cycle repeats every 15 minutes.
Approximately 14 days of operation remain before the battery is too weak to power the sensor.
(a) Blink pattern is On for 1/4 s, Off for 3/4 s, with 2 s Off between repetitions.
Table 43. Battery status: Battery symbol on model WDS sensor display
User action
Press Test button
Battery test symbol Indicates...
Full battery power.
50% battery life left.
25% battery life left. Replace batteries.
Flashing symbol indicates that approximately 14 days of operation remain before the battery is too weak to power the sensor.
118 UNT-SVX07B-EN
UNT-SVX07B-EN
Diagnostics
24 V Power Status Indicator
LED5 on the receiver of all models ( Figure 30, p. 115 ) lights and stays constantly On when 24 V power is normal.
Using the Wireless Sensor System to Check Signal Strength on a Site
Follow these steps to check the signal strength on a site:
1.
Power up a receiver with a 24 V transformer (user supplied)
2. Associate the sensor to a receiver of the same model intended for the job
3. Place the receiver at the desired location
4. Place or hold the sensor at the desired location
5. Press the Test button (S5) on the sensor and observe the signal strength as indicated by LED1,
LED2, and LED3 on model WTS, and on the display on model WDS ( Figure 31, p. 116 ).
For more information on interpreting the LEDs and the display symbols that indicate signal strength, see “Testing Signal Strength,” p. 117 .
Replacing Sensor Batteries
Sensor battery type, length of life, and installation are addressed in this section.
Battery Type
NOTICE
Equipment Damage!
The batteries are manufactured in a ready-to-use state. They are not designed for recharging.
Recharging can cause battery leakage or, in some cases, can cause the safety release vent to open.
NOTICE
Equipment Damage!
Do not attempt to hook up the sensor to a power supply. Equipment damage may result.
Use two non-rechargeable 1.5 V lithium AA batteries in the sensor. To maintain UL rating, use only
UL-listed lithium batteries. The sensor ships with Energizer™ L91 batteries already installed.
Replacement batteries are available at Trane Service Parts Centers (p/n X13770035010) or other local suppliers.
Battery Life
Battery life is five years under normal conditions. If the sensor is not used for an extended period of time, do one of the following:
• Set the sensor address to 000 to place the sensor into a low-power hibernation mode.
• Remove the batteries
Notes:
•
If lithium batteries are temporarily unavailable, alkaline batteries can be used. However, alkaline battery life is very short by comparison.
•
The battery life for a model WDS may decrease with extended LCD display activity.
119
Diagnostics
120
Battery Installation
WARNING
Prevent Injury!
Batteries can explode or leak and cause burns if installed backwards, disassembled, charged, or exposed to water, fire, or high temperature.
WARNING
Prevent Injury!
Keep away from small children. If swallowed, contact your local poison control center immediately.
6. Observe the polarity indicators that are molded into the cover.
7.
Install two batteries (of the type specified in “Battery Type,” p. 119 ) in the battery-holding slot that is molded into the sensor cover.
The sensor has been designed to prevent damage if the batteries are installed backwards, to reduce the potential for injury.
Manual Association
Before attempting manual or automatic association, the receiver must indicate readiness to associate (one blink pattern of LED3 on receiver). Refer to “Observing the Receiver for Readiness to Associate,” p. 69 .
At any time, the manual association method can be used to associate the receiver with the sensor.
If an association was previously established between a receiver and a sensor and needs to be reestablished, the manual association process may be used. If an association has not yet been established, the automatic association process is recommended (see “Associating the Sensor to the Receiver,” p. 70 ).
8. Using a small screwdriver, set the three rotary address switches ( Figure 19, p. 69 , locations S1,
S2, S3) on the receiver to an address between 001 and 999.
Notes:
•
An address can be changed without powering down the receiver or sensor.
•
An address can be changed at any time after initial association has been established.
9. Set the three rotary address switches ( Figure 19, p. 69 , locations S1, S2, S3) on the sensor to the same address as the receiver.
10. Record the address and location of the receiver and sensor pair.
•
After verifying that the receiver and sensor are powered up, press the Test button on the sensor to establish that the signal strength ( “Testing Signal Strength,” p. 117 ) and the battery life “Testing Battery Status,” p. 118 ) are adequate for proper functioning.
Disassociation
The receiver disassociates from the sensor (by removing all stored association information), conducts a channel scan, and restarts itself, if any of the following are true:
• The receiver address is changed from its current setting (001–999)
• The receiver receives a disassociation notification from its associated sensor
• The receiver does not receive a communication from its associated sensor within 50 minutes.
• The sensor and receiver are associated and communicating at the time the sensor is set to 000 and the Test button is pressed.
Note:
A disassociated sensor will transit an association request every 10 minutes.
UNT-SVX07B-EN
UNT-SVX07B-EN
Diagnostics
Sensor/Receiver Compatibility
Version 1.5 (p/n X13790854 and X13790855) and higher receivers are compatible with all sensors models and support all functions. Receivers released prior to version 1.5 are compatible with only model WTS.
Replacing a Failed Sensor or Receiver
Note:
Receivers ship installed on the unit. To remove the receiver, press in the retention tabs on the underside of the receiver enclosure (see Figure 18, p. 68 ) and push upward.
To replace a failed sensor or receiver:
11. Confirm that the device is disassociated (see Table 38 and Table 39, p. 117 ).
12. Set the rotary address switch of the new device to match the address of the remaining sensor or receiver.
Note:
There is no need to remove power from the remaining device.
13. Apply power to the new device. Association between the new and the remaining devices will automatically occur.
Note:
When replacing a WDS sensor, the receiver (version 1.5 or higher) will automatically configure the sensor to match the last stored configuration, if the sensor has not been placed into configuration mode and the factory default configuration is still valid. If the sensor configuration does not match the desired system features, it can be manually configured (see “Manual Association,” p. 120 ).
Servicing and Testing
If the wireless sensor system is not working as expected, use the tools and procedure described in this section.
Servicing and Testing Tools
No special tools or software are necessary to service and test the wireless sensor system. Test the system by using:
• The LEDs on the receiver, LEDs on the model WTS sensor, and the display on the model WDS sensor
• The Test button on the sensor
• The address test mode on the receiver
• A common volt-ohm meter
Procedure for Testing the Wireless Sensor System
If the wireless sensor system is not working as expected:
1.
Observe LED5 on the receiver. LED5 is On solid green whenever the receiver is powered.
2. Verify that the receiver is properly grounded. Both the GND-SIGNAL (black) wire and the GND-
POWER (yellow) wire must be grounded.
3. Press the Test button on the sensor.
•
Model WTS: LED5 should turn On solid green, indicating proper battery strength. LED1,
LED2, and LED3 will indicate signal strength.
Note:
When checking signal strength, both LED1 and LED3 on the receiver and sensor illuminate in unison if the sensor and receiver are associated. Use this feature to confirm association.
•
Model WDS: Battery life ( “Testing Battery Status,” p. 118 ) and signal strength ( “Testing
Signal Strength,” p. 117 ) are indicated on the display.
121
Diagnostics
Procedure for Testing the Receiver
If the receiver is not working as expected:
1.
Verify that the receiver is powered.
2. Set the receiver address to 000 to force the zone temperature output and zone temperature setpoint output to their default mode values (see “Output Values—Failure and Default Modes of Operation,” p. 122 ).
3. Measure the receiver output resistance (see “Measuring Output Resistance,” p. 122 ).
4. When the test is complete, reset the receiver address to its previous setting.
5. Press the Test button on the sensor to force re-association.
6. Confirm association and communication by noting LED1, LED2, and LED3 as described in
“Testing Signal Strength,” p. 117 .
Forcing a Sensor to Transmit
To force a wireless sensor to transmit during servicing, press the Test button on the sensor.
Output Power Level
The maximum output power level of a wireless sensor set is controlled by software and restricted by channel of operation and agency requirements per country or region. The sensor has a default maximum power level of 10 mW, but the receiver determines the ultimate output power level of the sensor.
Output Values—Failure and Default Modes of Operation
The following table provides output values for failure and default modes of operation, which can be used for troubleshooting.
Table 44. Output values
Situation
Zone temperature output
Zone setpoint output
Heating setpoint output
Fan/System output
Receiver address = 000
Receiver address = 001 to 999 and:
Receiver is powered up, but not is associated, or
Receiver has received a disassociation request from the associated sensor.
11.17 k Ω , 72.5°F
(22.5°C), indefinitely
451 Ω , 72.5°F
(22.5°C), indefinitely
501 Ω , 70.5°F
(21.4°C), indefinitely
2320 Ω
Fan = Auto
System = Off
11.17 k
Receiver address = 001 to 999 and receiver has not received a communication within 35 minutes from the associated sensor.
Open
Receiver has no power.
Open
Ω , 72.5°F
(22.5°C) Hold for 15 minutes, then open
Thermistor in sensor has failed to either open or close.
Open
Setpoint potentiometer has failed to either open or close.
Normal value
451 Ω , 72.5°F
(22.5°C),
Hold for 15 minutes, then open
Open
Open
Normal value
Open
501 Ω , 70.5°F
(21.4°C), indefinitely
Open
Open
Normal value
Open
2320 Ω
Fan = Auto
System = Off
Open
Open
N/A
N/A
Measuring Output Resistance
To measure the resistance of receiver outputs for zone temperature and setpoints for all models, and heating setpoint and fan/system for the WDS:
1.
Ensure that the GND-SIGNAL (black) wire and the GND-POWER (yellow) wire are grounded to the transformer.
2. Disconnect the ZONE (white) and SETPOINT (RED) wires from the controller. Disconnect the
HEAT SETPOINT (brown) and FAN/SYSTEM (green) wires from the controller, if applicable.
3. Measure resistance as follows:
122 UNT-SVX07B-EN
UNT-SVX07B-EN
Diagnostics
a. All models: Measure between the grounded GND-SIGNAL (black) wire and either the
SETPOINT (red) or ZONE (white) wire. Compare resistance measurements to those in
Table 45 .
b. WDS only: Measure between the grounded GND-SIGNAL (black) wire and the FAN/SYSTEM
(green) wire. Compare resistance measurements to those given in Table 46 .
Note:
The output circuits are not electrically powered; consequently, resistance can be measured without risk of damage to the volt-ohm meter.
Table 45. Receiver resistance table for all models
Zone or setpoint temperature
55°F (12.8°C)
60°F (15.6°C)
65°F (18.3°C)
70°F (21.1°C)
75°F (23.9°C)
80°F (26.7°C
85°F (29.4°C)
Nominal zone temperature output resistance
17.47 k Ω
15.3 k Ω
13.49 k Ω
11.9 k Ω
10.5 k Ω
9.3 k Ω
8.25 k Ω
Nominal setpoint and heating setpoint output resistance
792 Ω
695 Ω
597 Ω
500 Ω
403 Ω
305 Ω
208 Ω
Table 46. Receiver resistance table for model WDS
Fan command
High
Med
Low
Auto
Off
Nominal output resistance
16,130 Ω
13,320 Ω
10,770 Ω
2320 Ω
4870 Ω
Cleaning the Sensor
NOTICE
Equipment damage!
Spraying glass cleaner or any other solution directly on the sensor may damage it.
You can clean the sensor by applying glass cleaner to a soft, non-abrasive cloth, and gently wiping the face, including the buttons and LCD display. Use of a pre-moistened towelette designed for lens or screen cleaning is also acceptable.
Avoid inadvertent pressing of the Occupied/Unoccupied buttons on the keypad on the WDS sensor as this may result in an unwanted timed override or settings change.
123
Diagnostics
Troubleshooting Tracer ZN010, ZN510, and ZN520
124
Green STATUS LED
Indicates Whether the
Controller is Powered On
(24 Vac Supplied)
Yellow COMM LED
Indicates if
Communication is
Functioning
Red SERVICE LED
Indicates if Service is
Needed
Red SERVICE LED
During normal operation, the LED is off continuously when power is applied to the controller.
If the LED is on continuously, even when power is applied to the controller means that someone is pressing the SERVICE button or that the controller has failed.
If the LED flashes once every second, use Rover™, Trane’s service tool, to restore the unit to normal operation. Refer to the Rover™ product literature for more information.
Note:
If the Service button is held down for more than 15 seconds on the Tracer ZN520 controller, it will uninstall itself from the ICS communication network and shut down all unit operation.
Green STATUS LED
During normal operation, the LED is on continuously.
If the LED blinks once, the controller is in Manual output test mode.
If the LED blinks twice the controller is in Manual output test mode, with one or more diagnostics present.
If the LED blinks (1/4 second on, 1/4 second off for 10 seconds) the controller is in the “Wink” mode.
Note:
The “wink” feature allows the identification of a particular controller. When sending a request from a device, such as Rover™, the controller will “wink” to indicate it received the signal.
If the LED is off, either the power is off, an abnormal condition is present or the TEST button is pressed.
Yellow COMM LED
If the LED is off continuously, the controller is not detecting any communication. This is normal for units in standalone applications.
If the LED blinks, the controller detects communication.
If the LED is on continuously, this indicates an abnormal condition.
UNT-SVX07B-EN
UNT-SVX07B-EN
Diagnostics
Manual Output Test
The purpose of the manual output test sequence is to verify output and end device operation. Use the manual output test to:
• Verify output wiring and operation without using Rover™, service tool
• Force the water valve to open and balance the hydronic system
Note:
The manual output test is not an automatic cycle. You must press the TEST button to proceed through each step.
The controller observes all diagnostics that occur during the test sequence. Although an automatic diagnostic reset sequence exists as part of the controller’s normal operation, the automatic diagnostic reset feature is not active during the test sequence.
If left in an individual test step, the controller remains in test mode for 60 minutes and then exits to normal operation.
Many service calls are due to unit diagnostics. The test sequence resets unit diagnostics and attempts to restore normal unit operation prior to testing the outputs. If the diagnostics remain after a reset, the STATUS LED indicates the diagnostic condition is still present (two blinks).
Manual Output Test Procedure
Follow the procedure below to test the Tracer ZN010, ZN510, and ZN520 controllers.
1.
Press and hold the TEST button for at least two seconds (not exceeding 5 seconds), and then release, to start the test mode.
2. The test sequence will turn off all outputs and then attempt to clear all diagnostics.
3. Press the TEST button several more times (no more than once per second) to advance through the test sequence.
The outputs are not subject to minimum times during the test sequence. However, the test sequence only permits one step per second which limits minimum output time.
The green LED is turned off when the TEST button is pressed. To begin the manual output test mode, press and hold the TEST button (turning off the green LED) for at least two seconds.The green LED will begin to blink, indicating the controller is in test mode.
Table 47. Test sequence for 1-heat/1-cool configurations
Steps
Fan
BOP1-3
Cool Output
BOP4
(a)
Heat Output
BOP5
Damper
BOP6
1. Off
2. Fan High
3. Fan Medium
4. Fan Low
Off
High
Off
Off
Medium Off
Low Off
Off
Off
Off
Off
Closed
Closed
Closed
Closed
5. Cool
6. Heat
7. Fresh Air Damper
(b)
8. Exit
High
High
High
(c)
On
Off
Off
Off
On
Off
Closed
Closed
Open
Note:
For all 1-heat/1-cool applications including 2-pipe changeover, BOP4 energizes in the cooling test stage and BOP5 energizes in the heat test stage.This occurs even though during normal 2-pipe changeover operation BOP4 controls the unit valve for both cooling and heating.
(a) At the beginning of the Fan High step, the controller attempts to clear all diagnostics.
(b) The fresh air damper (BOP6) only energizes during this step if binary output 6 has been configured as a fresh air damper.
(c) After the Fresh Air Damper step, the test sequence performs the Exit step.This initiates a reset and attempts to return the controller to normal operation.
125
Wiring Diagrams
CSTI Fan Speed Switch
UNT-SVX07B-EN 126
CSTI Non Fan Speed Switch
Wiring Diagrams
UNT-SVX07B-EN 127
Wiring Diagrams
Line Voltage Fan Speed Switch
128 UNT-SVX07B-EN
Tracer ZN010 with Electric Heat
Wiring Diagrams
UNT-SVX07B-EN 129
Wiring Diagrams
Tracer ZN510 with Main and Auxiliary Valves
130 UNT-SVX07B-EN
ZN520 with 2-Stage Electric Heat
Wiring Diagrams
UNT-SVX07B-EN 131
www.trane.com
For more information, contact your local Trane office or e-mail us at [email protected]
Literature Order Number
Date
Supersedes
UNT-SVX07B-EN
July 2010
UNT-SVX07A-EN (April 2005)
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this literature.
Download
Advertisement
Key features
Energy-saving features help reduce operating costs
Easy to install and maintain
Wide range of capacities available
Frequently asked questions
Dimensions vary depending on the model. Please refer to the product literature for specific dimensions.
Weight also varies depending on the model. Please refer to the product literature for specific weights.
This information is not available in the provided document.