Operating Manual
OM WGS-5
Water-Cooled Screw Compressor Chillers
Part Number: 331373701
Effective: November 2008
Supersedes: OM WGS-4
WGS 130AW to WGS 190AW, Packaged Water-Cooled Chiller
WGS 130AA to WGS 190AA, Chiller with Remote Condenser
120 to 200 Tons, 420 to 700 kW
R-134a, 60 Hz
Software Version WGSD30101H
Table of Contents
Introduction ....................................... 3
General Description..................................... 3
Nomenclature............................................... 3
Definitions .......................................... 4
Wiring Diagrams ............................... 8
Control Panel Layout ...................... 10
MicroTech II Controller.............. 13
System Architecture................................... 13
General Description................................... 14
Units of measure........................................ 14
Sequence of Operation .................... 16
Start-Up and Shutdown .................. 23
Pre Start-up................................................ 23
Start-up ...................................................... 23
Weekend or Temporary Shutdown ............ 24
Start-up after Temporary Shutdown .......... 24
Extended Shutdown................................... 24
Start-up after Extended Shutdown............. 25
Unit Controller................................. 28
Unit Inputs/Outputs ................................... 28
Unit Setpoints ............................................ 28
Circuit Controller............................ 31
Circuit Inputs and Outputs......................... 31
Circuit Setpoint Table ................................ 32
Alarms and Events .......................... 34
Unit Stop Alarms ....................................... 34
Unit Events ................................................ 36
Circuit Stop Alarms ................................... 36
Circuit Events ............................................ 38
Alarm Logging .......................................... 39
Event Logging ........................................... 40
Clearing Alarms......................................... 40
Unit Controller Functions............... 40
Unit Enable ................................................ 41
Unit Mode Selection .................................. 42
Unit States.................................................. 43
Evaporator Pump Control .......................... 44
Leaving Water Temperature (LWT) Reset . 45
Planned Unit Capacity Overrides .............. 47
Condenser Pump and Tower Control......... 48
Cooling Tower Control .............................. 49
Evaporative Condenser Control................. 51
Circuit Controller Functions.......... 54
Refrigerant Calculations ............................ 54
Compressor Control................................... 55
Internal Capacity Overrides ....................... 58
Slide Positioning........................................ 59
Expansion Valve Control ........................... 61
Oil Heater Control ..................................... 65
Starter Communications............................. 65
Condenser Fan Control .............................. 66
Condenser Fan VFD .................................. 68
Digital Output Control............................... 68
Using the Controller .................................. 69
Security...................................................... 71
Entering Passwords.................................... 71
Editing Setpoints........................................ 71
Clearing Alarms ......................................... 71
Menu Descriptions .......................... 72
Unit Controller........................................... 72
Circuit Controller....................................... 87
Editing Review .......................................... 93
BAS Interface .................................. 94
Unit Troubleshooting Chart ........... 95
2
Conform to the BACnet protocol
(ANSI/ASHRAE 135-2001).
Unit controllers are L ON M ARK certified with an optional L ON W ORKS communications module.
2008 McQuay International
Illustrations and data cover McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice.
The following are trademarks or registered trademarks of their respective companies:
BACnet from ASHRAE; L ON M ARK and L ON W ORKS from Echelon Corporation;
GeneSys, McQuay and MicroTech II from McQuay International.
WGS 130A to WGS 190A OM WGS-5
Introduction
General Description
McQuay Model WGS water chillers are designed for indoor installations and are available with factory-mounted water-cooled condensers (Model WGS AW), or arranged for use with remote air-cooled or evaporative condensers (Model WGS AA). Each water-cooled unit
(WGS-AW) is completely assembled and factory wired before factory evacuation, charging and testing. The units consist of two semi-hermetic rotary screw compressors, a two-circuit shell-and-tube evaporator, two shell-and-tube water-cooled condensers, and complete refrigerant piping.
Units manufactured for use with remote condensers (Models WGS-AA) have all refrigerant specialties factory-mounted and have two sets of connection points for refrigerant discharge and liquid lines to and from the remote condenser. Discharge valves are included
Each circuit’s liquid line components are manual liquid line shutoff valve, charging valve, filter-drier, liquid line solenoid valve, sight glass/moisture indicator, and electronic expansion valve.
The electrical control center includes a MicroTech II microprocessor control system and equipment protection and operating controls necessary for dependable, automatic operation.
The compressor circuits are equipped with individual circuit breakers and a unit disconnect switch is available as an option over the standard power block.
This software revision adds fixes several bugs in the IP/SI units logic, improves the operation of remote evaporator units in low ambient air temperatures, improves communications with the solid state starter and provides compressor electrical data at the supervisor port for building automation systems.
Nomenclature
W G S 130 - A W
Water-Cooled Condensing
Global
Rotary Screw Compressor
Nominal Capacity (Tons)
W = Water-Cooled Condenser
A = Unit Less Condenser
Design Vintage
OM WGS-5 WGS 130A to 190A 3
4
Definitions
Active Setpoint
The active setpoint is the setting in effect at any given moment. This variation occurs on setpoints that can be altered during normal operation. Resetting the chilled water leaving temperature setpoint by one of several methods, such as return water temperature, is an example.
Active Capacity Limit
The active setpoint is the setting in effect at any given moment. Any one of several external inputs can limit a compressor’s capacity below its maximum value.
Condenser Recirc Timer
A timing function, with a 30-second default, that holds off any reading of condenser water for the duration of the timing setting. This delay allows the water sensors (especially water temperatures) to take a more accurate reading of the condenser water system conditions.
Condenser Saturated Temperature Target
The saturated condenser temperature target is calculated by first using the following equation:
Sat condenser temp target raw = 0.833(evaporator sat temp) + 68.34
The “raw” value is the initial calculated value. This value is then limited to a range defined by the Condenser Saturated Temperature Target minimum and maximum setpoints. These setpoints simply cut off the value to a working range, and this range can be limited to a single value if the two setpoints are set to the same value.
CPU Error
These are problems caused by a malfunction of the central processing unit.
Dead Band
The dead band is a set of values associated with a setpoint such that a change in the variable occurring within the dead band causes no action from the controller. For example, if a temperature setpoint is 44 F and it has a dead band of 2 degrees, nothing will happen until the measured temperature is less than 42 F or more than 46 F.
DIN
Digital input, usually followed by a number designating the number of the input.
Discharge Superheat
Discharge superheat shall be calculated for each circuit using the following equation:
Discharge Superheat = Discharge Temperature – Condenser Saturated Temperature
Error
In the context of this manual, “Error” is the difference between the actual value of a variable and the target setting or setpoint.
Evaporator Approach
The evaporator approach is calculated for each circuit. The equation is as follows:
Evaporator Approach = LWT – Evaporator Saturated Temperature
WGS 130A to 190A OM WGS-5
OM WGS-5
Evap Recirc Timer
A timing function, with a 30-second default, that holds off any reading of chilled water for the duration of the timing setting. This delay allows the chilled water sensors (especially water temperatures) to take a more accurate reading of the chilled water system conditions.
EXV
Electronic expansion valve, used to control the flow of refrigerant to the evaporator, controlled by the circuit microprocessor.
High Saturated Condenser – Hold Value
High Cond Hold Value = Max Saturated Condenser Value – 5 F
This function prevents the compressor from loading whenever the pressures approach within 5 degrees of the maximum discharge pressure. The purpose is to keep the compressor online during periods of possibly temporary elevated pressures.
High Saturated Condenser – Unload Value
High Cond Unload Value = Max Saturated Condenser Value – 3 F
This function unloads the compressor whenever the pressures approach within 3 degrees of the maximum discharge pressure. The purpose is to keep the compressor online during periods of possibly temporary elevated pressures.
High Superheat Error
The degrees of temperature difference between 40 F and the actual discharge temperature.
Light load Stg Dn Point
The percent load point at which one of two operating compressors will shut off, transferring the unit load to the remaining compressor.
Load Limit
An external signal from the keypad, the BAS or a 4-20 ma signal that limits the compressor loading to a designated percent of full load. Frequently used to limit unit power input.
Load Balance
Load balance is a technique that equally distributes the total unit load among the running compressors.
Low Ambient Lockout
Prevents the unit from operating (or starting) at ambient temperatures below the setpoint.
Low Pressure Hold Setpoint
The psi evaporator pressure setting at which the controller will not allow further compressor loading.
Low/High Superheat Error
The difference between actual evaporator superheat and the superheat target.
LWT
Leaving water temperature. The “water” is any fluid used in the chiller circuit.
WGS 130A to 190A 5
6
LWT Error
Error in the controller context is the difference between the value of a variable and the setpoint. For example, if the LWT setpoint is 44 F and the actual temperature of the water at a given moment is 46 F, the LWT error is +2 degrees.
LWT Slope
The LWT slope is an indication of the trend of the water temperature. It is calculated by taking readings of the temperature every few seconds and subtracting them from the previous value, over a rolling one-minute interval.
ms
Milli-second
Maximum Saturated Condenser Temperature
The maximum saturated condenser temperature allowed is calculated based on the compressor operational envelope.
NC
Normally closed - usually refers to a contactor or valve.
NO
Normally open - usually refers to a contactor. or valve.
OAT
Outside ambient air temperature.
Offset
Offset is the difference between the actual value of a variable (such as temperature or pressure) and the reading shown on the microprocessor as a result of the sensor signal. See notes on page 33 for explanation of sensor off set.
pLAN
Peco Local Area Network is the proprietary name of the network connecting the control elements.
Rapid Stop
A compressor stop process that circumvents the normal pumpdown cycle.
Refrigerant Saturated Temperature
Refrigerant saturated temperature is calculated from the pressure sensor readings for each circuit. The pressure is fitted to an R-134a temperature/pressure curve to determine the saturated temperature.
Soft Load
Soft Load is a control sub-routine that allows the chiller to load up gradually. It requires setpoint inputs of selecting it by Yes or No inputs, by selecting the percent load to start ramping up, and by selecting the time to ramp up to full load (up to 60 minutes).
SP
Setpoint
SSS
Solid state starter as used on McQuay screw compressors.
Suction Superheat
Suction superheat is calculated for each circuit using the following equation:
Suction Superheat = Suction Temperature – Evaporator Saturated Temperature
WGS 130A to 190A OM WGS-5
Stage Up/Down Accumulator
The accumulator can be thought of as a bank storing occurrences that indicate the need for an additional fan.
Stageup/Stagedown Delta-T
Staging is the act of starting or stopping a compressor or fan when another is still operating.
Startup and Stop is the act of starting the first compressor or fan and stopping the last compressor or fan. The Delta-T is the “dead band” on either side the setpoint in which no action is taken.
Stage Up Delay
The time delay from the start of the first compressor to the start of the second.
Startup Delta-T
Number of degrees above the LWT setpoint required to start the first compressor.
Stop Delta-T
Number of degrees below the LWT setpoint required for the last compressor to stop.
VAC
Volts, Alternating current, sometimes noted as vac.
VDC
Volts, Direct current, sometimes noted as vdc.
VFD
Variable Frequency Drive, a device used to vary an electric motor’s speed.
OM WGS-5 WGS 130A to 190A 7
8
Wiring Diagrams
Figure 1, WGS 130AW – 190AW Field Wiring Diagram (Optional Single Point Connection)
DISCONNECT
(BY OTHERS)
UNIT MAIN
TERMINAL BLOCK
GND LUG
3 PHASE
POWER
SUPPLY
TO COMPRESSOR(S)
NOTE: ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1
WIRING SYSTEM WITH CONDUCTOR
RATED 600 VOLTS
FUSED CONTROL
CIRCUIT TRANSFORMER
FU4 FU5
FU7
120 VAC
TB1
(115 VAC)
TB1-2
1
2
82
2
N
CHWR
EVAP. PUMP RELAY #1
(BY OTHERS)
120 VAC 1.0 AMP MAX
120 VAC
120 VAC
CHWR
EVAP. PUMP RELAY #2
(BY OTHERS)
120 VAC 1.0 AMP MAX
85
2
N
120 VAC
CWR
COND. PUMP RELAY #1
(BY OTHERS)
120 VAC 1.0 AMP MAX
86
2
N
120 VAC
CWR
COND. PUMP RELAY #2
(BY OTHERS)
120 VAC 1.0 AMP MAX
87
2
N
N
120 VAC
M11
TOWER FAN #1
(BY OTHERS)
120 VAC 1.0 AMP MAX
88
2
120 VAC
M12
TOWER FAN #2
(BY OTHERS)
120 VAC 1.0 AMP MAX
89
2
N
COOLING TOWER BYPASS
(BY OTHERS)
78
77
0-10VDC
N
FACTORY SUPPLIED ALARM
FIELD WIRED
ALARM BELL
OPTION
ABR
ALARM BELL RELAY
(BY OTHERS)
80
79
81
75
0-10VDC
N
24 VAC
ALARM BELL
RELAY
1
BELL
2
COM NO
ALARM BELL OPTION
REMOTE STOP
SWITCH
(BY OTHERS)
ICE MODE
SWITCH
(BY OTHERS)
TIME
CLOCK
AUTO
OFF
ON
MANUAL
AUTO
OFF
ON
MANUAL
(24 VAC OR 30 VDC)
EVAP. FLOW
SWITCH
(BY OTHERS)
NOR. OPEN PUMP AUX.
CONTACTS (OPTIONAL)
*MANDATORY IF FACTORY FLOW SWITCH OPTION IS NOT SELECTED
TB1
60
66
60
68
60
67
897
COND. FLOW
SWITCH
(BY OTHERS)
NOR. OPEN PUMP AUX.
CONTACTS (OPTIONAL)
*MANDATORY IF FACTORY FLOW SWITCH OPTION IS NOT SELECTED
4-20MA FOR
EVAP. WATER RESET
(BY OTHERS)
+
-
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
+
-
60
76
72
70
71
70
GND
IF REMOTE STOP CONTROL
IS USED, REMOVE LEAD 897
FROM TERM. 40 TO 53.
DWG. 330588201 REV. 0B
WGS 130A to 190A OM WGS-5
OM WGS-5
Figure 2, WGS 130AA – 190AA Field Wiring Diagram (Remote Air-cooled Condenser)
DISCONNECT
(BY OTHERS)
UNIT MAIN
TERMINAL BLOCK
GND LUG
3 PHASE
TO COMPRESSOR(S)
POWER
SUPPLY
NOTE: ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1
WIRING SYSTEM WITH CONDUCTOR
RATED 600 VOLTS
FUSED CONTROL
CIRCUIT TRANSFORMER
FU4 FU5
FU7
120 VAC
TB1
(115 VAC)
TB1-2
1
2
82
2
N
FACTORY SUPPLIED ALARM
FIELD WIRED
ALARM BELL
OPTION ABR
ALARM BELL RELAY
CHWR
EVAP. PUMP RELAY #1
(BY OTHERS)
120 VAC 1.0 AMP MAX
CHWR
EVAP. PUMP RELAY #2
(BY OTHERS)
120 VAC 1.0 AMP MAX
85
2
81
75
N
120 VAC
120 VAC
24 VAC
ALARM BELL
RELAY
1
BELL
COM NO
2 ALARM BELL OPTION
CIRCUIT #1
TB6
92
M11
CONDENSER FAN
CONTACTOR COIL #1
93
98
M12
98
CONDENSER FAN
CONTACTOR COIL #2
94
98
M13
CONDENSER FAN
CONTACTOR COIL #3
144
145
146
145
148
145
98
95
150
145
M14
CONDENSER FAN
CONTACTOR COIL #4
96
152
145 M15
CONDENSER FAN
CONTACTOR COIL #5
97
98
M16
98
154
145
CONDENSER FAN
CONTACTOR COIL #6
NO1
2
NO2
2
NO5
2
NO6
2
NO3
2
C
C
NO4
2
N
N
N
N
N
N
120 VAC
120 VAC
120 VAC
J12
(LOCATED ON
CIRCUIT
CONTROLLER)
120 VAC
120 VAC
J13
(LOCATED ON
CIRCUIT
CONTROLLER)
120 VAC
REMOTE STOP
SWITCH
(BY OTHERS)
ICE MODE
SWITCH
(BY OTHERS)
TIME
CLOCK
AUTO
OFF
ON
MANUAL
AUTO
OFF
ON
MANUAL
60
68
EVAP. FLOW
SWITCH
(BY OTHERS)
NOR. OPEN PUMP AUX.
CONTACTS (OPTIONAL)
*MANDATORY IF FACTORY FLOW SWITCH OPTION IS NOT SELECTED.
4-20MA FOR
EVAP. WATER RESET
(BY OTHERS)
+
-
4-20MA FOR
DEMAND LIMIT
(BY OTHERS)
+
-
60
67
72
70
71
70
CIRCUIT #2
TB7
244
M21
98
CONDENSER FAN
CONTACTOR COIL #2
94
245
CONDENSER FAN
CONTACTOR COIL #1
93
98
246
M22
245
248
98
M23
92
245
CONDENSER FAN
CONTACTOR COIL #3
98
M24
CONDENSER FAN
CONTACTOR COIL #4
96
252
98
250
245
M25
95
245
CONDENSER FAN
CONTACTOR COIL #5
97
98
M26
254
245
CONDENSER FAN
CONTACTOR COIL #6
TB1
(24 VAC)
60
66
897
NO1
2
NO2
2
NO3
2
C
C
NO4
2
NO5
2
NO6
2
N
N
N
N
N
N
120 VAC
120 VAC
120 VAC
J12
(LOCATED ON
CIRCUIT
CONTROLLER)
120 VAC
120 VAC
J13
(LOCATED ON
CIRCUIT
CONTROLLER)
120 VAC
IF REMOTE STOP CONTROL
IS USED, REMOVE LEAD 897
FROM TERM. 40 TO 53.
GND
DWG. 330588101 REV. 0C
WGS 130A to 190A 9
Control Panel Layout
Figure 3, Outer (Microprocessor) Panel
T2, Unit Controller
T13, Circ#1 Controller
T14, Circ#1 Load Solenoid
T15, Circ#1 EXV Power
T23, Circ#2 Controller
T24, Circ#2 Load Solenoid
T25, Circ#2 EXV Power
Unit Controller
MHPR11 &12, Mechanical
High Pressure Relay
Circ#1 Controller
Circuit Breaker &
Switch Panel
External Disconnect Handle
Circ#1 & 2 EXV Drivers
Circ#2 Controller
10
TB3, Circ#2 Controller
Terminal Board
TB2, Circ#1 Controller
Terminal Board
TB1 Unit Controller
Terminal Board
NOTES:
1.
Transformers T2 through T25 are class 100, 120V to 12V.
2.
Switches for MHPR 11 and 12 (Mechanical High Pressure Switches) are located on the compressors.
3.
Mechanical High Pressure Switches Open at 310 psi, Close at 250 psi.
WGS 130A to 190A OM WGS-5
Figure 4, Inner (Power) Panel (Optional Single-Point Power with Disconnect Switches
Shown)
Circ#1 Solid State Starter
Circ#2 Solid State Starter
SSS1 Bypass Contactor
SSS2 Bypass Contactor
Secondary Fuses
External Disconnect Handle
Circ#1 Circuit Breaker
Circ#2 Circuit Breaker
Unit Disconnect Switch
W/ External Handle
T1, Supply Voltage to
120V Transformer
Primary Fuses
Outside (Microprocessor) Panel
OM WGS-5 WGS 130A to 190A 11
12
Figure 5, Circuit Breaker/Fuse Panel
Open Location
S1 Main Unit On-Off Switch
CS2, Circuit#2 On-Off Switch
CS1, Circuit#1 On-Off Switch
CB11 Circ#1 Circuit Breaker
CB12, Circ#1 Sump Heater
Open Location
CB21, Circ#2 Circuit
CB22, Circ#2 Sump Heater
Open Locations
Location for Optional
115V Receptacle
OUTER PANEL
T2 T13 T14 T15 T23 T24 T25
MHPR
1
MHPR
2
SINGLE
POINT
OR
CIR. #1
DS
HANDLE
(MULTI-
POINT)
UNIT
CONTROLLER
EXV.
DRIVER
#1
CIRCUIT CONTROLLER
#1
MODBUS CARD
CONVERTER BOARD
EXV.
DRIVER
#2
CIRCUIT CONTROLLER
#2
CS1
S
1
CS2
S
P
CB11
CB12
SP
CB21
CB22
SP
FU7
F3
CIR. #2
DS
HANDLE
(MULTI-
POINT)
REC
OPTION
TB1 TB11 TB21
SSS #1
INNER PANEL
SSS #2
D3
CONTR.
BRD.
THERM-
ISTOR
CARD
D3
CONTR.
BRD.
THERM-
ISTOR
CARD
CT3
CT2
CT1
BYPASS
CONTACTOR
CT3
CT2
CT1
BYPASS
CONTACTOR
F
U
6
T1
C
B
1
(DS1 DS2
MULTIPOINT
POWER)
C
B
2
F
U
4
F
U
5
DS1
G
N
D
WGS 130A to 190A
330589001 REV. 00 - Legend
OM WGS-5
MicroTech II
Controller
Software Version :WGSD30101E
Bios: 3.62
BOOT: 3.0F
System Architecture
The WGS MicroTech distributed control system consists of multiple microprocessorbased controllers that provide monitoring and control functions required for the controlled, efficient operation of the chiller. The system consists of the following components:
Unit Controller, one per chiller controls functions and settings that apply to the unit and communicates with the other controllers. It is located in the control panel and is labeled “UNIT CONTROL”.
Circuit Controllers for each compressor/circuit that control compressor functions and settings specific to the circuit. The controllers are located in the control panel and are labeled “CIRCUIT CONROL”.
In addition to providing all normal operating controls, the MicroTech II control system monitors equipment protection devices on the unit and will take corrective action if the chiller is operating outside of its normal design envelope. If an alarm condition develops, the controller will shut down the compressor, or entire unit, and activate an alarm output.
Important operating conditions at the time an alarm condition occurs are retained in the controller’s memory to aid in troubleshooting and fault analysis.
The system is protected by a password scheme that allows access only by authorized personnel. The operator must enter the operator password into the controller’s keypad before any setpoints can be altered.
Chiller
Solid
State
Starter
Solid
State
Starter
RS485 RS485
BAS Interface-
Modbus,
BACnet,
Lonworks
RS485/
LON
Unit Controller
4x20 LCD
Circuit Controller
4x20 LCD
Circuit Controller
4x20 LCD
Carel pLAN
OM WGS-5
PLAN Addressing
The pLAN (proprietary local area network) addressing is based on a commonly used scheme among all applications using pLAN networked MicroTech II controllers. Only three addresses are needed, and are designated as shown in the following table.
Controller Address Dip Sw 1 Position Dip Sw 2 Position Dip Sw 3 Position
Circuit 1
Circuit 2
1
2
Up
Down
Down
Up
Down
Down
The Dip switches are located on the upper front of the controller above the screen.
WGS 130A to 190A 13
14
General Description
The MicroTech II controller’s design permits the chiller to run more efficiently, and it simplifies troubleshooting if a system failure occurs. Every MicroTech II controller is programmed and tested prior to shipment to assist in a trouble-free start-up. The MicroTech
II controller can be used to cycle fans on remote air-cooled condensers for head pressure control when the setpoint Water Cooled=N is selected in one of the setpoint menu screens.
Water Cooled=Y sets the chiller for operation with the water-cooled condenser and activates settings for cooling tower control. Remote evaporative condensers will have to have selfcontained, on-board, head pressure control systems.
Units of measure
Version “C”, as described in this manual, supports metric (SI) units of measure.
Inch-Pound SI
F to 0.1
F psi to 0.1 psi
C to 0.1
C
KPa to 1.0 kPa
Distributed Control
The WGS units have three MicroTech II microprocessors, a Unit Controller plus a Circuit
Controller for each of the two circuits. The Circuit Controllers are independent such that either one will operate its circuit if the other Circuit Controller is out of service.
Operator-friendly
The MicroTech II controller menu structure is separated into three distinct categories, which provide the operator or service technician with a full description of the following:
1.
Current unit status
2.
Control parameters (setpoint settings and adjustment). Security protection prevents unauthorized changing of the setpoints and control parameters.
3.
Alarm notification and clearing
The MicroTech II controller continuously performs self-diagnostic checks, monitoring system temperatures, pressures and protection devices, and will automatically shut down a refrigerant circuit or the entire unit if a fault occurs. The cause of the shutdown and date stamp are retained in memory and can be easily displayed in plain English for operator review, which is an extremely useful feature for troubleshooting. In addition to displaying alarm diagnostics, the MicroTech II controller also provides the operator with a warning of pre-alarm limit conditions.
Staging
The two screw compressors are loaded and staged on and off as a function of leaving chilled water temperature, number of starts and run-hours. See Sequence of Operation beginning on page 16.
Equipment Protection
The unit is protected by alarms that shut it down and require manual reset, and also by limit alarms that limit unit operation in response to some out-of-ordinary condition. Shutdown alarms activate an alarm signal that can be wired to a remote device.
WGS 130A to 190A OM WGS-5
Unit Enable Selection
Enables unit operation from local keypad or digital input.
Unit Mode Selection
Selects standard cooling, ice, glycol, or test operation mode.
Keypad/Display
A 4-line by 20-character/line liquid crystal display and 6-key keypad is mounted on each controller. Its layout is shown below.
Figure 6, Keypad and Display in MENU Mode
Key to Screen Pathway
Red Alarm Light
Menu Key
Air Conditioning
<
<
<
ALARM
VIEW
SET
(4) Arrow Keys "Enter" Key and Green
Comp. Run Light
The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use.
1.
Scroll between data screens as indicated by the arrows (default mode).
2.
Select a specific data screen in a hierarchical fashion using dynamic labels on the right side of the display (this mode is entered by pressing the MENU key).
3.
Change field values in edit mode according to the following table:
UP Increment
These four edit functions are indicated by one-character abbreviations on the right side of the display (this mode is entered by pressing the ENTER key).
OM WGS-5 WGS 130A to 190A 15
Sequence of Operation
Compressor Heaters
With the control power on, 120V power is applied through the control circuit Fuse FU7 to the compressor oil separator heater (HTR-OIL SEP).
Startup/Compressor Staging
During Cool Mode the following must be true to start a circuit operating. The evaporator and condenser pump (WGS-AW only) outputs must be energized and flow must be established for a period of time defined by the evaporator recirculate setpoint. Established flow will be detected by evaporator and condenser water flow switches. The water temperature leaving the evaporator must be greater than the Active Leaving Water
Temperature setpoint, plus the Startup Delta-T, before a circuit will start. The first circuit to start is determined by sequence number. The lowest sequence numbered circuit will start first. If all sequence numbers are the same (default), then the circuit with the fewest number of starts will start first.
During operation, the slide valves for loading and unloading will be pulsed until the active leaving water temperature setpoint is maintained. The second circuit start will occur once the first circuit has loaded to 75% slide capacity or is in Capacity Limit and the water temperature leaving the evaporator is greater than the active leaving water temperature
Setpoint plus Stage Delta-T. The circuits will load or unload simultaneously through a continuous capacity control to maintain the evaporator leaving water temperature. If all sequence numbers are the same, the circuit with the most run hours will be shut down first.
The circuit with the most run hours will stop when the water temperature leaving the evaporator is less than the Active Leaving Water Temperature Setpoint minus Stage Delta-
T. The last remaining circuit will shut down when the water temperature leaving the evaporator is lower than the Active Leaving Water Temperature Setpoint minus the Stop
Delta-T.
Automatic Pumpdown
The Model WGS chiller has two separate refrigerant circuits so the refrigerant charge is stored in the condenser when the circuit is off. Pumpdown to the condenser helps keep refrigerant from migrating to the compressor. It also helps establish a pressure differential on start for oil flow. In a normal shutdown, each circuit will close its expansion valve, causing the evaporator pressure to reach a low-pressure setpoint. Once this setpoint is reached, or a specified amount of time has elapsed, the running circuit will be shut down.
Chilled Water and Condenser Water Pumps
The chiller’s MicroTech II controller has a total of four pump outputs, two for the evaporator and two for the condenser (WGS-AW only). There is a manual setting in the software for the user to select either pump output 1 or 2. It is recommended that the chiller’s outputs control the water pumps, as this will offer the most protection for the unit.
Cooling Tower Control
The MicroTech II controller can control the cooling tower fans and/or a tower bypass valve.
This provides a simple and direct method to control the unit’s discharge pressure.
Programming directions and the sequence of operation can be found on page 49. Some means of discharge pressure control is recommended and must be installed if the entering condenser water temperature to the condenser can fall below 60 F.
Condenser Fan Control
The MicroTech II controller can be programmed to cycle air-cooled condenser fans on and off based on the discharge pressure. Details are on page 66.
16 WGS 130A to 190A OM WGS-5
Low Ambient Start Logic
Low pressure operation at start (due to low ambient air temperature)is allowed for every start regardless of the condenser saturated temperature at start or condenser configuration
( water-cooled or remote condenser). This is called Start Logic. START Logic is active for a time period determined by the unit Startup Timer setpoint. This was called the Low OAT
Start Timer in previous software versions.
The Low OAT Restart Failure logic, which applies ONLY to units configured for remote condenser, still allows for three start attempts. If the condenser saturated temperature at start is less than 70 F, another start attempt is allowed until failure of the third attempt, which will generate an alarm.
Remote Condenser EXV Operation
For units configured for remote condensers, there is pre-open logic that allows the electronic expansion valve to open prior to starting the compressor. This allows the expansion valve to be in a better position for control at start-up. The factory mounted liquid line solenoid remains closed until the compressor starts. On units configured for remote condensers, if the evaporator pressure is greater than the condenser pressure at start, the pre-open logic is bypassed. NOTE: Pre-open logic also exists for units configured as packaged water cooled condensers.
Electronic expansion valve post-open logic has been added to help prevent hydraulic lock between the liquid line solenoid and the electronic expansion valve when a circuit cycles off. After the compressor performs a pump down and cycles off, the electronic expansion valve will re-open for 30 seconds and then return to its closed position.
OM WGS-5 WGS 130A to 190A 17
Unit Controller Sequence of Operation
Unit power up
Unit in Off state
Is unit enabled?
Yes
Evaporator pump output on
No
The chiller may be disabled via the unit switch, the remote switch, the keypad enable setting, or the BAS network. In addition, the chiller will be disabled if both circuits are disabled, either because of an alarm or the circuit pumpdown switch on each circuit, or if there is a unit alarm. If the chiller is disabled, the unit status display will reflect this and also show why it is disabled.
If the unit switch is off, the unit status will be Off:Unit Switch . If the chiller is disabled due to network command, the unit status will be Off:BAS Disable . When the remote switch is open, the unit status will be Off:Remote Switch . When a unit alarm is active, the unit status will be Off:Unit Alarm . In cases where no circuits are enabled, the unit status will be Off:All Cir Disabled .
If the chiller is enabled, then the unit will be in the Auto state and the evaporator water pump output will be activated.
No
Is flow present?
The chiller will then wait for the flow switch to close, during which time the unit status will be Auto:Wait for flow .
18
Yes
Wait for chilled water loop to recirculate.
After establishing flow, the chiller will wait some time to allow the chilled water loop to recirculate for an accurate reading of the leaving water temperature. The unit status during this time is Auto:Evap Recirc .
Keep evaporator pump output on while unit is enabled.
Is there enough load to start chiller?
No
The chiller is now ready to start if enough load is present. If the LWT is not high enough to start, the unit status will be Auto:Wait Evap Flow .
If the LWT is high enough to start, the unit status will be Auto .
Yes
WGS 130A to 190A OM WGS-5
Is unit watercooled?
If the unit is configured as watercooled, the condenser pump will need to be started.
Otherwise, the unit can start the first circuit at this point.
Yes
Condenser pump output on
If load is present, the condenser water pump output will be activated.
No
Is flow present?
No
The chiller will then wait for the condenser flow switch to close, during which time the unit status will be Auto:Wait Cond Flow .
Yes
Wait for condenser water loop to recirculate.
After establishing condenser flow, the chiller will wait some time to allow the condenser water loop to recirculate and guarantee consistent flow. The unit status during this time is Auto:Cond Recirc .
Once the condenser flow has been present for enough time, the unit status will become Auto . The tower control logic will start working to control the condenser water temperature, using outputs from the unit controller to control tower fans, bypass valves, and vfd's as determined by the tower set points.
Keep condenser pump output on while unit is enabled and load is present.
Start first circuit.
The first circuit to start is generally the one with the least number of starts, or circuit one if there is a tie. This circuit will go through its start sequence at this point.
A number of fans may be started with the compressor based on the OAT. Fan stages will be added/removed as needed to control condenser pressure. The EXV will begin controlling at this point as well. The compressor cannot start loading until it has at least 22 o discharge superheat for more than 30 seconds.
Load/unload as needed to satisfy load.
Is more capacity needed to satisfy load?
No
The first circuit will load and unload as needed in an attempt to satisfy the load. It will eventually get to a point where it is considered to be at full load. A circuit is at full load when it reaches 75% slide target, it reaches the max slide target setting, or it encounters a problem and is running in an inhibited state.
No
If a single circuit is not enough to satisfy the load, the second circuit will need to be started.
Yes
Has the stage up time delay expired?
A minimum time must pass between the start of the first circuit and the second circuit.
OM WGS-5
Yes
WGS 130A to 190A 19
20
Start second circuit.
Load/unload as needed to satisfy load.
The second circuit will go through its start sequence at this point.
A number of fans may be started with the compressor based on the OAT. Fan stages will be added/removed as needed to control condenser pressure. The EXV will begin controlling at this point as well. The compressor cannot start loading until it has at least 22 o discharge superheat for more than 30 seconds.
Both circuits will now load/unload as needed to satisfy the load. In addition, they will load balance so that both circuits are providing nearly equal capacity.
Can one circuit handle the load?
No
As the load drops off, the circuits will unload accordingly. If the LWT gets low enough, or both circuits unload enough, one circuit can shut off.
Yes
Shut down one circuit.
The first circuit to shut off is generally the one with the most run hours. The circuit will do a pumpdown by closing the EXV and continuing to run the compressor until it reaches the pumpdown pressure or exceeds the pumpdown time limit. Then, the compressor and all fans will be turned off.
Load/unload as needed to satisfy load.
The single running circuit will load/unload as needed to satisfy the load.
Is load satisfied?
No
With one circuit running, the load may drop off to the point where even minimum unit capacity is too much. The load has been satisfied when the LWT drops below the shutdown point. At this time the only running circuit can shut down.
Yes
Shut down last circuit.
Turn off condenser pump and tower control.
The last circuit running now shuts down. The circuit will do a pumpdown by closing the EXV and continuing to run the compressor until it reaches the pumpdown pressure or exceeds the pumpdown time limit. Then, the compressor and all fans will be turned off.
The unit should be ready to start again when the LWT gets high enough. The unit status at this time will be Auto:Wait for load .
The condenser pump and tower control outputs are turned off until the LWT is high enough to start again.
WGS 130A to 190A OM WGS-5
Unit power up
Circuit is in Off state
Circuit Controller Sequence of Operation
When the circuit is in the Off state the EXV is closed, compressor is off, and all fans are off. The oil heater will be on at this time as long as oil is detected in the separator.
If the compressor is ready to start when needed, the circuit status will be
Off:Ready . When the circuit switch is off, the circuit cannot start and the status will be Off:Pumpdown Switch .
No
Next on?
If this compressor has the least starts, the other compressor is disabled for some reason, or the other compressor is already running, then this compressor will be designated as the next one on.
No
Yes
Stage up now?
If there is a need for more cooling capacity, the compressor designated as next on can start.
Yes
Is unit watercooled?
If the unit is configured as watercooled, then the EXV preopen process must be performed. Otherwise, this is skipped and the compressor can be started.
Yes
Preopen EXV No
At this point, the EXV will perform a preopen. While the compressor is off, the EXV is opened for a period of time to prime the evaporator and avoid low pressure at startup. The circuit status will display EXV Preopen .
Start Compressor
When the compressor starts, the EXV will open (if not already open) and hold at
3000 steps for 15 seconds.
If the unit is aircooled, depending on the OAT, a number of fans may be started with the compressor to keep condenser pressure from climbing too fast.
The circuit status will normally be Run: Disc SH Low after the compressor starts.
OM WGS-5 WGS 130A to 190A 21
Run Compressor
Next off?
No
When in the Run state, the compressor will load/unload as needed to satisfy the load. The compressor will also load/unload to load balance with the other compressor if it is running and not in a limited condition. However, it cannot load up until the discharge superheat has been over 22 F for at least 30 seconds. After this, the circuit status will be Run:Normal .
The EXV will operate in either Pressure Control or Superheat Control. In Pressure
Control, the evaporator pressure is controlled to a target pressure, which is adjusted based on LWT and discharge superheat. In Superheat Control, the suction superheat is controlled to a target that varies with discharge superheat.
If unit is aircooled, fans will be staged on and off to control the condenser pressure.
The condenser pressure is controlled to a target that is based on evaporator pressure, with the target getting higher as the evaporator pressure gets higher.
No
If this compressor has the most run hours or the other compressor is already off, then this compressor will be designated as the next one off.
Yes
Stage down now?
Yes
Pumpdown circuit
If less cooling capacity is needed, the compressor designated as next off can shut down. This condition may arise when either the LWT has dropped far enough below the active set point or both circuits are running at a low capacity.
When the circuit does a normal shutdown, a pumpdown is performed. The EXV is closed while the compressor continues to run. As soon as the pumpdown is initiated, the compressor is unloaded to the minimum. The condenser fans continue to control normally during this process. The circuit status during this time is Run:Pumpdown .
After the evaporator pressure drops below the pumpdown pressure or enough time has passed, the compressor and fans are shut off to end the pumpdown process.
The circuit status will normally be Off:Cycle Timers at this time.
22 WGS 130A to 190A OM WGS-5
Start-Up and Shutdown
Pre Start-up
1.
Flush and clean the chilled-water system. Proper water treatment is required to prevent corrosion and organic growth. A 20-mesh strainer is required at the evaporator chilledwater inlet and should be cleaned after system flushing.
!
CAUTION
Failure to flush, clean and provide system water treatment can damage the unit.
2.
With the main disconnect open, check all electrical connections in control panel and starter to be sure they are tight and provide good electrical contact. Connections are tightened at the factory, but can loosen enough in shipment to cause a malfunction.
!
CAUTION
Lock and tag out all power sources when checking connections. Electrical shock can cause severe personal injury or death .
.
3.
Check and inspect all water piping. Make sure flow direction is correct and that piping is made to the correct connection on evaporator and condenser.
4.
Check that refrigerant piping on remote condensers is connected to the correct circuits and not crossed and has been properly leak tested and evacuated.
5.
Open all water flow valves to the condenser and evaporator.
6.
Flush the cooling tower and system piping to be sure the system is clean. Start evaporator pump and manually start condenser pump and cooling tower. Check all piping for leaks. Vent the air from the evaporator and condenser water circuit, as well as from the entire water system. The cooler circuit should contain clean, treated, noncorrosive water.
7.
Check to see that the evaporator water temperature sensor is securely installed.
8.
Make sure the unit control switch S1 is open OFF and the circuit switches CS1 and CS2 are open. Place the main power disconnect switch to ON. This will energize the compressor sump heaters. Wait a minimum of 12 hours before starting the unit.
9.
Measure the water pressure drop across the evaporator and condenser, and check that water flow is correct (on pages 26 and 27) per the design flow rates.
10.
Check the actual line voltage to the unit to make sure it is the same as called for on the compressor nameplate, within + 10%, and that phase voltage unbalance does not exceed
2%. Verify that adequate power supply and capacity is available to handle load.
11.
Make sure all wiring and fuses are of the proper size. Also make sure that all interlock wiring is completed per McQuay diagrams.
12.
Verify that all mechanical and electrical inspections by code authorities have been completed.
13.
Make sure all auxiliary load and control equipment is operative and that an adequate cooling load is available for initial start-up.
Start-up
1.
Open the compressor discharge shutoff valves until backseated. Replace valve seal caps.
2.
Open the two manual liquid line shutoff valves (king valves).
OM WGS-5 WGS 130A to 190A 23
24
3.
Verify that the compressor sump heaters have operated for at least 12 hours prior to start-up. Crankcase should be warm to the touch.
4.
Check that the MicroTech II controller is set to the desired chilled water temperature.
5.
Start the system auxiliary equipment for the installation by turning on the time clock, ambient thermostat and/or remote on/off switch and water pumps.
6.
Switch on the unit circuit breakers.
7.
Set circuit switches CS1 and CS2 to ON for normal operation.
8.
Start the system by setting the unit system switch S1 to ON.
9.
After running the unit for a short time, check the oil level in each compressor, rotation of condenser fans (if any), and check for flashing in the refrigerant sight glass.
Weekend or Temporary Shutdown
Move circuit switches CS1 and CS2 to the OFF pumpdown position. After the compressors have shut off, turn off the chilled water pump if not on automatic control from the chiller controller or building automation system (BAS). With the unit in this condition, it will not restart until these switches are turned back on.
Leave on the power to the unit (disconnect closed) so that the sump heaters will remain energized.
Start-up after Temporary Shutdown
1.
Start the water pumps.
2.
Check compressor sump heaters. Compressors should be warm to the touch.
3.
With the unit switch S1 in the ON position, move the circuit switches CS1 and CS2 to the ON position.
4.
Observe the unit operation for a short time, noting unusual sounds or possible cycling of compressors.
Extended Shutdown
1.
Close the manual liquid line shutoff valves.
2.
After the compressors have shut down, turn off the water pumps.
3.
Turn off all power to the unit.
4.
Move the unit control switch S1 to the OFF position.
5.
Close the discharge shutoff valves.
6.
Tag all opened disconnect switches to warn against start-up before opening the compressor suction and discharge valves.
7.
Drain all water from the unit evaporator, condenser and chilled water piping if the unit is to be shut down during the winter and exposed to below-freezing temperatures. To help prevent excessive corrosion, do not leave the vessels or piping open to the atmosphere over the shutdown period.
WGS 130A to 190A OM WGS-5
Start-up after Extended Shutdown
1.
Inspect all equipment to see that it is in satisfactory operating condition.
2.
Remove all debris that has collected on the surface of the condenser coils (remote condenser models) or check the cooling tower, if present.
3.
Open the compressor discharge valves until backseated. Always replace valve seal caps.
4.
Open the manual liquid line shutoff valves.
5.
Check circuit breakers. They must be in the OFF position.
6.
Check to see that the circuit switches CS1 and CS2 and the unit control switch S1 are in the OFF position.
7.
Close the main power disconnect switch. The circuit disconnects switches should be off.
8.
Allow the sump heaters to operate for at least 12 hours prior to start-up.
9.
Start the chilled water pump and purge the water piping as well as the evaporator in the unit.
10.
Start the system auxiliary equipment for the installation by turning on the time clock, ambient thermostat and/or remote on/off switch.
11.
Check that the MicroTech II controller is set to the desired chilled water temperature.
12.
Switch the unit circuit breakers to ON.
13.
Start the system by setting the system switch S1 and the circuit switches to ON.
!
CAUTION
Most relays and terminals in the control center are powered when S1 is closed and the control circuit disconnect is on. Therefore, do not close S1 until ready for start-up or serious equipment damage can occur .
14.
After running the unit for a short time, check the oil level in the compressor oil sight glass and check the liquid line sight glass for bubbles.
OM WGS-5 WGS 130A to 190A 25
26
Figure 7, Evaporator Pressure Drop WGS 130 – WGS 190
Flow Rate (L/s)
6 13 19 25 32 38 44 50 57 63
60
50
40
30
20
WGS 130, 140
126
180
150
120
90
60
WGS 160, 170, 190
10
9
8
7
6
5
4
30
27
24
21
18
15
12
3
100
WGS Model
200
Minimum Flow
Flow Rate Pressure Drop
300 400 500 600 7008009001000
Flow Rate (GPM)
Nominal Flow
Flow Rate Pressure Drop
2000
9
Maximum Flow
Flow Rate Pressure Drop
130AW/AA
140AW/AA
160AW/AA
170AW/AA
190AW/AA
195 12.3 5.8 17.4 312 19.7 13.5 40.4 520 32.9 33.9 101.1
211 13.4 6.7 20.0 338 21.4 15.6 46.6 563 35.6 39.0 116.5
235 14.9 4.6 13.8 376 23.8 10.8 32.3 627 39.7 27.3 81.6
254 16.1 5.3 15.9 407 25.8 12.5 37.3 678 42.9 31.6 94.2
273 17.3 6.1 18.1 437 27.7 14.2 42.5 728 46.1 35.9 107.2
Note: Minimum, nominal, and maximum flows are at a 16 F, 10 F, and 6 F chilled water temperature range respectively and at ARI tons.
WGS 130A to 190A OM WGS-5
Figure 8, Condenser Pressure Drop WGS 130 – WGS 190
Flow Rate (L/s)
6 13 19 25 32 38 44 50 57 63
60
50
40 WGS 170, 190 with Manifold
30
WGS 130, 140, 160 with Manifold
20
126
180
150
120
90
60
10
9
8
7
6
30
27
24
21
18
WGS
Model
5
4
3
WGS 170, 190 without Manifold
15
12
WGS 130, 140, 160 without Manifold
100 200 300 400 500 600 7008009001000
Flow Rate (GPM)
2000
9
Pressure Drop Without Optional Condenser Manifold
Minimum Flow
Flow Rate Pressure Drop
Nominal Flow
Flow Rate Pressure Drop
Maximum Flow
Flow Rate Pressure Drop
130AW
140AW
160AW
170AW
190AW
WGS
Model
304 19.2 4.1 12.2 390 24.7 6.5 19.3 650 41.1 16.0 47.9
304 19.2 4.1 12.2 422 26.7 7.4 22.2 704 44.5 18.5 55.1
304 19.2 4.1 12.2 470 29.8 9.0 26.9 784 49.6 22.4 66.8
372 23.5 4.3 12.8 509 32.2 7.9 23.7 848 53.7 19.8 59.1
372 23.5 4.3 12.8 546 34.6 9.0 26.9 911 57.6 22.5 67.1
Pressure Drop With Optional Condenser Manifold
Minimum Flow Nominal Flow
Flow Rate Pressure Drop Flow Rate Pressure Drop
Maximum Flow
Flow Rate Pressure Drop
130AW
140AW
160AW
170AW
190AW
304 19.2 4.7 14.0 390 24.7 7.4 22.0 650 41.1 18.5 55.1
304 19.2 4.7 14.0 422 26.7 8.5 25.3 704 44.5 21.3 63.5
304 19.2 4.7 14.0 470 29.8 10.3 30.7 784 49.6 25.8 77.1
372 23.5 5.3 15.8 509 32.2 9.4 28.1 848 53.7 23.8 71.1
372 23.5 5.3 15.8 546 34.6 10.7 32.0 911 57.6 27.1 80.9
OM WGS-5 WGS 130A to 190A 27
Unit Controller
Unit Inputs/Outputs
Table 1, Analog Inputs
# Description Signal Range
1
Condenser EWT or Outdoor
Ambient Temp.
2 Demand Limit
Thermister (10k@25°C)
4-20 mA Current
-58 to 212°F
3
4
5
Chilled Water Reset
Leaving Evaporator Water Temp.
Entering Evaporator Water Temp.
4-20 mA Current
Thermister (10k@25°C)
Thermister (10k@25°C)
0 to 100% limit
0 to 10 degrees
60 F max.
-58 to 212°F
-58 to 212°F
C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit
Table 2, Analog Outputs
# Description Output Range
1 Cooling Tower Bypass Valve Position
2 Cooling Tower VFD Speed
0 to 10 VDC
0 to 10 VDC
0 to 100%
0 to 100%
3 Open
4 Open
Table 3, Digital Inputs
# Description Signal Signal
1 Unit Switch
2 Remote Switch
3 Evaporator Water Flow Switch
4
5
Mode Switch
Condenser Water Flow Switch
0 VAC (Stop)
0 VAC (Stop)
0 VAC (No Flow)
0 VAC (Cool)
0 VAC (No Flow)
24 VAC (On)
24 VAC (Start)
24 VAC (Flow)
24 VAC (Ice)
24 VAC (Flow)
6 Open
7 Open
8 Open
Table 4, Digital Outputs
# Description
1 Evaporator Water Pump 1
2 Evaporator Water Pump 2
3 Condenser Water Pump 1
4 Condenser Water Pump 2
5 Tower Fan 1
6 Tower Fan 2
7 Remote Run Status
8 Alarm
Load
Pump Contactor
Pump Contactor
Pump Contactor
Pump Contactor
Fan Contactor
Fan Contactor
Remote Alarm
Output OFF Output ON
Pump OFF
Pump OFF
Pump OFF
Pump ON
Pump ON
Pump ON
Pump OFF
Fan OFF
Pump ON
Fan ON
Fan OFF Fan ON
All Circuits Off Any Circuit On
No alarm Stop alarm
Unit Setpoints
The following parameters are retained during power off, are factory set to the Default value, and can be adjusted to any value in the Range column.
The Type defines whether the setpoint is part of a coordinated set of duplicate setpoints in different controllers. Types are as follows:
N = Normal setpoint – Not copied from, or copied to, any other controller
M = Master setpoint – Setpoint is copied to all controllers in the “Sent To” column
The PW (password) column indicates the password level that must be active in order to change the setpoint. Passwords are as follows:
O = Operator [0100] M = Manager (8745)
28 WGS 130A to 190A OM WGS-5
OM WGS-5
Toggle: Setpoints that have two choices, such as ON and OFF are toggled between the two settings using the Up or Down keys on the controller.
NOTE : in some software versions the terms “inhibit” and “hold” are used interchangeably.
Table 5, Unit Controller Setpoints
Unit
Unit Enable
Unit Mode
Control source
Available Modes
Cool LWT
Ice LWT
Start Delta T
Stop Delta T
Stage Up Delta T
Stage Down Delta T
Max Pulldown
Evap Recirc Timer
Evap Pump Select
Cond Recirc Timer (watercooled only)
Cond Pump Select (watercooled only)
LWT Reset Type
Max Reset
Start Reset Delta T
Soft Load
Begin Capacity Limit
Soft Load Ramp
Demand Limit
Low OAT Operation
(air-cooled only)
Low Ambient Lockout (air cooled only)
Ice Time Delay
Clear Ice Timer
Evap LWT sensor offset
Evap EWT sensor offset
Cond EWT/OAT sensor offset
Cond LWT sensor offset
Units
BAS Protocol
Ident number
Baud Rate
Compressors
Sequence # Cir 1
Sequence # Cir 2
Max Comps ON
Start-start timer
Stop-start timer
Pumpdown Pressure
Pumpdown Time Limit
Light Load Stg Dn Point
Continued next page.
55 F
12
No
0
0
0
0
F/psi
Modbus
1
19200
1
1
2
20 min
5 min
25 psi
120 sec
25%
30
#1 Only
NONE
0 F
10 F
Off
40%
20 min
Off
OFF OFF, ON
Cool Cool, Ice, Test
Switches
Cool
44 F
25 F
10 F
1.5 F
2 F
1 F
Switches, Keypad, Network
Cool, Cool w/Glycol, Cool/Ice w/Glycol, ICE w/Glycol, TEST
30(40) to 60
20 to 38
0 to 10
0 to 3
0 to 3
0 to 3
F
F
F
F
F
F
5 F/min 0.5-5.0
30 0 to 300 seconds
#1 Only #1 Only, #2 Only, Auto
0 to 300 seconds
#1 Only, #2 Only, Auto
NONE, RETURN, 4-20mA, OAT
0 to 20 F
0 to 20 F
Off, On
20-100%
1-60 minutes
Off, On
-10(35) to 70 F
1-23 hours
No,Yes
-5.0 to 5.0 deg
-5.0 to 5.0 deg
-5.0 to 5.0 deg
-5.0 to 5.0 deg
F/psi, C/kPa
BACnet, LonWorks, Modbus
0-200
1200,2400,4800,9600,19200
1-2
1-2
1-2
15-60 minutes
3-20 minutes
10 to 40 psi
0 to 180 sec
20 to 50%
N
M
N
O
O
O
N T
N O
N O
M O
M O
M O
M O
M M
N M
N M
N M
N M
N M
N M
N M
N M
N M
N
N
M
M
M
M
N
M
M
M
M
M
N M
N
N
N
N
M
M
M
M
N
N
N
N
N
M
M
N M
M
M
M
M
M
M
M
M
M
M
M
WGS 130A to 190A 29
30
Stage Up Delay
Disc. Temp Sensor Type
Alarms
Low Evap Pressure-Unload
Low Evap Pressure-Hold
Low Oil Level Delay
High Oil Press Diff Delay
High Discharge Temperature
High Lift Pressure Delay
Evaporator Water Freeze
Evaporator Flow Proof
5 min
PT1000
28 psi
30 psi
120 sec
15 sec
200 F
5 sec
36 F
3 sec
Recirculate timeout 3 min
Startup Timer
Condenser Water Freeze
(water cooled only)
Condenser Flow Proof (water cooled only)
60 sec
38 F
3 sec
Cooling Tower(available for Water cooled only)
Tower Control None
Tower Stages
Stage #1 On
Stage #2 On
Stage Differential
Stage Up Time
2
70 F
75 F
3.0 F
2 min
Stage Down Time
Stage Fan Down @
Stage Fan Up @
5 min
20%
80%
Valve/VFD Control
Valve Type
Valve Setpoint
Valve Deadband
Minimum Start Position
Minimum Position @
Maximum Start Position
Maximum Position @
Valve Control Range (Min)
Valve Control Range(Max)
Error Gain
Slope Gain
None
NC to tower
65 F
2.0 F
0%
60 F
100%
90 F
10%
90%
25
25
0 to 60 min
NTC, PT1000
[0,26] to 45 psi
[0,28] to 45 psi
10-180 sec
0-90 sec
150 to 200 F
0 to 30 sec
15(36) to 42 F
3 to 10 sec
1 to 10 min.
20 to 90 sec.
34 to 42 F
3 to 10 sec
None, Temperature
0 to 2
40 to 120 F
40 to 120 F
1.0 to 10.0 F
1 to 60 min
1 to 60 min
0 to 100%
0 to 100%
None, Valve Setpoint, Valve Stage,
VFD Stage, Valve SP/VFD Stage
NC, NO
60 to 120 F
1.0 to 10.0 F
0 to 100%
0 to 100 F
0 to 100%
0 to 100 F
0 to 100%
0 to 100%
10 to 99
10 to 99
M
M
Auto Adjusted Ranges
The following settings have different ranges of adjustment based on other settings.
Table 6, Cool LWT
Unit Mode = Cool
Mode Range
Unit Mode = Cool w/Glycol, Ice w/ Glycol
40 to 60 o F
20 to 60 o F
Table 7, Evaporator Water Freeze
Unit Mode = Cool
Mode Range
Unit Mode = Cool w/Glycol, Ice w/ Glycol
34 to 42 o F
15 to 42 o F
M
M
M
M
M
M
M
M
M
M
M
M
M M
N M
N M
N
M
M
M
N M
N M
N
N
N
N
N
M
M
N M
N M
N M
N M
M
M
M
N M
N M
N M
N M
N M
N M
N M
N M
N
N
N
N
M
M
M
M
WGS 130A to 190A OM WGS-5
Table 8, Low Evaporator Pressure Inhibit
Mode Range
Unit Mode = Cool
Unit Mode = Cool w/Glycol, Ice w/ Glycol
30 to 45 Psig
15 to 45 Psig
Table 9, Low Evaporator Pressure Unload
Unit Mode = Cool
Unit Mode = Cool w/Glycol, Ice w/ Glycol
Circuit Controller
Mode Range
28 to 45 Psig
15 to 45 Psig
Circuit Inputs and Outputs
Table 10, Analog Inputs
# Description
1
2
Evaporator Pressure
Condenser Pressure
3 Open
4
5
Suction Temperature
Discharge Temperature
6 Open
7
8
Slide Load Indicator
Condenser LWT (circuit 1, water cooled only)
0.1 to 0.9 VDC
0.1 to 0.9 VDC
NTC Thermister (10k@25°C)
NTC Thermister (10k@25°C)
4 to 20 mA
NTC Thermister (10k@25°C)
Table 11, Analog Outputs
0 to 132 psi
3.6to 410 psi
-58 to 212°F
-58 to 212°F
0 to 100%
-58 to 212°F
1 Fan VFD (air cooled only)
2 Open
3 EXV Driver
4 Open
0 to 10 VDC
0 to 10 VDC
Table 12, Digital Inputs
# Description
Range
0 to 100% (1000 steps resolution)
0 to 6386 steps (1000 steps resolution)
1 Circuit Switch
2 Open
3 Open
4 VFD Fault
5 Oil Differential Pressure Switch
6 Mechanical High Pressure Switch
7 Open
8 Open
9 Oil Level Sensor
0 VAC (Off)
0 VAC (Fault)
0 VAC (Fault)
0 VAC (Fault)
0 VAC (Fault)
24 VAC (Auto)
24 VAC (No Fault)
24 VAC (No Fault)
24 VAC (No Fault)
24 VAC (No Fault)
10-14 Open
The status of digital inputs may be viewed on Circuit Status screen 5, on the circuit controllers only.
OM WGS-5 WGS 130A to 190A 31
32
Table 13, Digital Outputs
# Description
5
6
7
1
2
3
4
Fan 1 Contactor (air cooled only)
Fan 2 Contactor (air cooled only)
Fan 3 Contactor (air cooled only)
Fan 4 Contactor (air cooled only)
Fan 5 Contactor (air cooled only)
Fan 6 Contactor (air cooled only)
Load/Unload Pulse
9 Compressor SSS Contact
10 Open
11 Oil Heater
12 Interstage Injection (future use)
13 EXV Close Signal
Output OFF
Fan off
Fan off
Fan off
Fan off
Fan off
Fan off
Hold load slide
Unload
Compressor off
Heater off
Injection off
EXV follows
0 –10 VDC
Output ON
Fan on
Fan on
Fan on
Fan on
Fan on
Fan on
Move load slide
Load
Compressor on
Heater on
Injection on
EXV closed, ignores 0 –
10 VDC
Circuit Setpoint Table
The following parameters must be remembered during power off, are factory set to the
Default value, and can be adjusted to any value in the Range column.
The PW (password) column indicates the password that must be active in order to change the setpoint. Codes are as follows:
O = Operator (100)
Table 14, Circuit Setpoints
M = Manager
Compressor
Circuit Mode
Slide Control
Slide target
Compressor Size
Clear Cycle Timers
Full Load Amps
Rated load Amps
Service Factor
Ground Fault Enable
Ground Fault Trip Level
Overload Class
Initial Motor Current
Maximum Motor Current
Ramp Time
Up to Speed Time (UTS)
Stop Mode
Rated RMS Voltage
Over Voltage Trip Level
Under Voltage Trip Level
Ovr/Undr Volt Trip Delay
Current Unbalance Trip Level
Auto Fault Reset Time
CT Ratio
Maximum Slide Target
Continued next page enable auto
0
167
No
10
10
125%
1%
10
225%
300%
7 seconds
10 seconds
CoS
460 volts
10%
10%
1.0 seconds
15%
60 seconds
864:1
100.0
Disable, enable, test
Auto, manual
0-100
167, 179, 197
No, Yes
1 to 341 amps
1 to 341 amps
100 to 199%
1 to 100%
0 to 40
50 to 400% FLA
100 to 800%
0 to 300 seconds
1 to 900 seconds
Coast(CoS), volt decel(dcL)
100 to 1000 volts
1 to 40% rated volts
1 to 40% rated volts
0.1 to 90.0 seconds
5 to 40%
0 to 120 seconds
72-8000:1
0-100.0%
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
WGS 130A to 190A OM WGS-5
OM WGS-5
EXV
EXV control
Manual EXV position
Service Pumpdown
Preopen Timer (water cooled only)
Sensors (NOTE 1)
Evap pressure offset
Cond pressure offset
Suction temp offset
Discharge temp offset
Slide Minimum Position Offset
Slide Maximum Position Offset
Fans (available for air-cooled only)
Fan VFD enable
Number of fans
Saturated Condenser Temp Target Min
Saturated Condenser Temp Target Max
Stage 1 On Deadband
Stage 2 On Deadband
Stage 3 On Deadband
Stage 4 On Deadband
Stage 2 Off Deadband
Stage 3 Off Deadband
Stage 4 Off Deadband
Stage 5 Off Deadband
VFD Max Speed
VFD Min Speed
Forced Fantrol 1
Forced Fantrol 2
Forced Fantrol 3
0
0
0
0
0
0
Auto
0
No
20
16.0
11.0
8.0
100%
25%
2
3
4
On
4
90.0
110.0
8.0
10.0
11.0
12.0
20.0
Auto, manual
0-6386
No,Yes
20 to 120 seconds
-10.0 to 10.0 psi
-10.0 to 10.0 psi
-5.0 to 5.0 deg
-5.0 to 5.0 deg
-15 to 15%
-15 to 15%
M
M
M
M
M
M
M
M
M
M
Off, On M
4 to 6 M
80.0-110.0
o F M
90.0-120.0 o F M
1.0-20.0 o F M
1.0-20.0 o F M
1.0-20.0 o F M
1.0-20.0 o F M
1.0-25.0 o F M
1.0-25.0 o F M
1.0-25.0 o F M
1.0-25.0 o F M
90 to 110% M
20 to 60%
1 to 4
1 to 4
1 to 4
M
M
M
M
Notes :
1.
Offsets are used to fine-tune certain readings generated by sensors. For example, if the controller was showing a 125 psi value and a calibrated pressure gauge at the same location showed 127 psi, an offset of
+2 psi would be entered and the controller would then read the corrected value of 127 psi.
Table 15, RLA/FLA Values
Compressor 575V 460V 380V 230V 208V 400V
RLA
197
179
167
FLA
All
NOTE : Table values used for circuit controller input.
WGS 130A to 190A 33
Alarms and Events
Situations may arise that require some action from the chiller or that should be logged for future reference. A condition that causes a shutdown and requires manual reset is known as a stop alarm. Other conditions can trigger what is known as an event, which may or may not require an action in response. All stop alarms and events are logged.
Unit Stop Alarms
The alarm output and red button led shall be turned ON when any stop alarm occurs. They shall be turned off when all alarms have been cleared.
Evaporator Flow Loss
Alarm description (as shown on screen): Evap Water Flow Loss
Trigger:
1: Evaporator Pump State = Run AND Evaporator Flow Digital Input = No Flow for time >
Flow Proof Set Point AND at least one compressor running
2: Evaporator Pump State = Start for time greater than Recirc Timeout Set Point and all pumps have been tried
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared at any time manually via the keypad or via the BAS clear alarm signal.
If active via trigger condition 1:
When the alarm occurs due to this trigger, it can auto reset the first two times each day, with the third occurrence being manual reset.
For the auto reset occurrences, the alarm will reset automatically when the evaporator state is Run again. This means the alarm stays active while the unit waits for flow, then it goes through the recirculation process after flow is detected. Once the recirculation is complete, the evaporator goes to the Run state which will clear the alarm. After three occurrences, the count of occurrences is reset and the cycle starts over if the manual reset flow loss alarm is cleared.
If active via trigger condition 2:
If the flow loss alarm has occurred due to this trigger, it is always a manual reset alarm.
Condenser Flow Loss
Alarm description (as shown on screen): Cond Water Flow Loss
Trigger:
1: Condenser Pump State = Run AND Condenser Flow Digital Input = No Flow for time >
Flow Proof Set Point AND at least one compressor running
2: Condenser Pump State = Start for time greater than Recirc Timeout Set Point and all pumps have been tried
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared at any time manually via the keypad or via the BAS clear alarm signal.
If active via trigger condition 1:
34 WGS 130A to 190A OM WGS-5
OM WGS-5
The alarm will reset automatically when the condenser state is Run again. This means the alarm stays active while the unit waits for flow, then it goes through the recirculation process after flow is detected. Once the recirculation is complete, the condenser goes to the
Run state which will clear the alarm.
If active via trigger condition 2:
If the flow loss alarm has occurred due to this trigger, it is always a manual reset alarm.
Evaporator Water Freeze Protect
Alarm description (as shown on screen): Evap Water Freeze
Trigger: Evaporator LWT drops below evaporator freeze protect set point AND Unit State
= Auto AND Evaporator LWT Sensor Fault not active
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad or via the BAS clear alarm signal, but only if the alarm trigger conditions no longer exist.
Leaving Evaporator Water Temperature Sensor Fault
Alarm description (as shown on screen): Evap LWT Sens Fault
Trigger: Sensor shorted or open
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Entering Condenser Water Temperature Sensor Fault
Alarm description (as shown on screen): Cond EWT Sens Fault
Trigger: Sensor shorted or open
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
Outdoor Air Temperature Sensor Fault
Alarm description (as shown on screen): OAT Sensor Fault
Trigger: Sensor shorted or open AND unit is aircooled
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if the sensor is back in range.
pLAN Failure
Alarm description (as shown on screen): pLAN Failure
Trigger: No circuit controllers found on pLAN for 60 seconds
Action Taken: Rapid stop all circuits
Reset: This alarm can be cleared manually via the keypad, but only if at least one circuit is connected to pLAN.
WGS 130A to 190A 35
36
Unit Events
The following unit events are logged in the event log with a time stamp.
Entering Evaporator Water Temperature Sensor Fault
Event description (as shown on screen): Evap EWT Sens Fault
Trigger: Sensor shorted or open
Action Taken: Return water reset cannot be used.
Reset: Auto reset when sensor is back in range.
Leaving Condenser Water Temperature Sensor Fault
Event description (as shown on screen): Cond LWT Sens Fault
Trigger: Sensor shorted or open AND unit is watercooled
Action Taken: None
Reset: Auto reset when sensor is back in range.
Circuit Stop Alarms
All circuit stop alarms require shutdown of the circuit on which they occur. Rapid stop alarms do not do a pumpdown before shutting off. All other alarms will do a pumpdown.
The red button led on the circuit controller shall be turned on when any circuit stop alarm occurs. It shall be turned off when all circuit alarms have been cleared. In addition, the alarm status shall be sent to the unit control so the alarm output and the red button led on the unit controller can be energized while alarms are active.
Alarm descriptions apply to both circuits, the circuit number is represented by ‘N’ in the description.
Low Evaporator Pressure
Alarm description (as shown on screen): Evap Press Low N
Trigger : [Freezestat trip AND Compressor State = Run AND Low OAT Start not active
AND Evap Pressure Sensor Fault not active] OR [Evaporator Press < -10 psi AND startup timer complete AND Evap Pressure Sensor Fault not active] and the compressor has been running longer than the Startup Timer setting
Freezestat logic allows the circuit to run for varying times at low pressures. The lower the pressure, the shorter the time the compressor can run. This time is calculated as follows:
Freeze error = Low Evaporator Pressure Unload – Evaporator Pressure
Freeze time = 70 – 6.25 x freeze error, limited to a range of 20-70 seconds
When the evaporator pressure goes below the Low Evaporator Pressure Unload set point, a timer starts. If this timer exceeds the freeze time, then a freezestat trip occurs. If the evaporator pressure rises to the unload set point or higher, and the freeze time has not been exceeded, the timer will reset.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad if the evaporator pressure is above –10 psi.
WGS 130A to 190A OM WGS-5
OM WGS-5
High Lift Pressure
Alarm description (as shown on screen): Lift Pressure High N
Trigger: Condenser Saturated Temperature > Max Saturated Condenser Value for time >
High Lift Delay set point
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
Mechanical High Pressure
Alarm description (as shown on screen): Mech High Pressure N
Trigger: Mechanical High Pressure switch input is low
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad if the MHP switch input is high.
High Discharge Temperature
Alarm description (as shown on screen): Disc Temp High N
Trigger: Discharge Temperature > High Discharge Temperature set point AND compressor is running AND Discharge Temperature Sensor Fault is not active
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
Low Oil Level
Alarm description (as shown on screen): Oil Level Low N
Trigger: Oil Level Switch input is open for time greater than Low Oil Level Delay while compressor is in the Run state AND the Low Oil Level Event has occurred in the past hour.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
High Oil Pressure Difference
Alarm description (as shown on screen): Oil Pres Diff High N
Trigger: Oil DP switch input is low for time greater than High Oil Pressure Difference
Delay set point AND compressor is running
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
Low Evaporator Pressure Start
Alarm description (as shown on screen): LowPress StartFail N
Trigger: Saturated condenser temperature greater than 70°F at start and circuit failed a Start Logic attempt.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
No Evaporator Pressure Drop After Start
Alarm description (as shown on screen): No Evap Press Drop N
Trigger: After start of compressor, at least a 1 psi drop in evaporator pressure has not occurred after 15 seconds
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
WGS 130A to 190A 37
38
No Pressure Change At Start
Alarm description (as shown on screen): NoPressChgAtStart N
Trigger: After start of compressor, at least a 1 psi drop in evaporator pressure or 5 psi rise in discharge pressure has not occurred after 15 seconds.
Action Taken: Rapid stop circuit
Reset: This alarm can be cleared manually via the Unit Controller keypad.
Circuit Events
The following events limit operation of the circuit in some way as described in the Action
Taken column. The occurrence of a circuit event only affects the circuit on which it occurred. Circuit events are logged in the event log on the unit controller.
Low Evaporator Pressure - Hold
Event description (as shown on screen): EvapPress Low Hold N trigger: The low pressure events are not enabled until the compressor has started and the evaporator pressure has risen above the Low Evaporator Pressure - Hold set point. The unit mode must also be Cool. Then, while running, if evaporator pressure <= Low Evaporator
Pressure - Hold set point the event is triggered.
Action Taken: Inhibit loading by only allowing the slide target to be reduced.
Reset: While still running, the event will be reset if evaporator pressure > (Low Evaporator
Pressure - Hold SP + 2psi). The event is also reset if the unit mode is switched to Ice, or the compressor state is no longer Run.
Low Evaporator Pressure - Unload
Event description (as shown on screen): EvapPressLowUnload N
Trigger: The low pressure events are not enabled until the compressor has started and the evaporator pressure has risen above the Low Evaporator Pressure - Hold set point. The unit mode must also be Cool. Then, while running, if evaporator pressure <= Low Evaporator
Pressure - Unload set point the event is triggered.
Action Taken: Unload the compressor by decreasing the slide target 5% every five seconds until the evaporator pressure rises above the Low Evaporator Pressure – Unload set point.
Reset: While still running, the event will be reset if evaporator pressure > (Low Evaporator
Pressure - Hold SP + 2psi). The event is also reset if the unit mode is switched to Ice, or the compressor state is no longer Run.
High Lift Pressure - Hold
Event description (as shown on screen): LiftPressHigh Hold N
Trigger: While the compressor is running and unit mode is Cool, if saturated condenser temperature >= High Saturated Condenser - Hold Value, the event is triggered.
Action Taken: Inhibit loading by only allowing the slide target to be reduced.
Reset: While still running, the event will be reset if saturated condenser temperature <
(High Saturated Condenser - Hold Value – 10 o F). The event is also reset if the unit mode is switched to Ice, or the compressor state is no longer Run.
High Lift Pressure - Unload
Event description (as shown on screen): LiftPressHighUnloadN
Trigger: While the compressor is running and unit mode is Cool, if saturated condenser temperature >= High Saturated Condenser - Unload Value, the event is triggered.
Action Taken: Unload the compressor by decreasing the slide target 5% every five seconds until the condenser pressure drops below the High Saturated Condenser - Unload Value.
WGS 130A to 190A OM WGS-5
OM WGS-5
Reset: While still running, the event will be reset if saturated condenser temperature <
(High Saturated Condenser - Unload Value – 10 o F). The event is also reset if the unit mode is switched to Ice, or the compressor state is no longer Run.
Oil Level Low
Event description (as shown on screen): Oil Level Low Cir N
Trigger: Oil Level Switch input is open for time greater than Low Oil Level Delay while compressor is in the Run state AND the Low Oil Level Event has not occurred in the past hour .
Action Taken: Rapid stop circuit
Reset: Compressor state = off
Failed Pumpdown
Event description (as shown on screen): Pumpdown Fail Cir N
Trigger: Circuit state = pumpdown for time > Pumpdown Time set point
Action Taken: Shutdown circuit
Reset: N/A
Power Loss While Running
Event description (as shown on screen): Run Power Loss Cir N
Trigger: Circuit controller is powered up after losing power while compressor was running
Action Taken: Delay start of compressor by time equal to the Start-Start timer set point.
Reset: N/A
Condenser Freeze Protect
Event description (as shown on screen): Cond Frz Protect Cir N
Trigger: Cond Sat Refr Temp < Condenser Freeze SP AND Cond Pump State = Off AND unit is watercooled
Action Taken: Start condenser pump
Reset: Cond Sat Refr Temp > Condenser Freeze SP + 2 o F
VFD Fault
Event description (as shown on screen): VFD Fault Cir N
Trigger: VFD enabled and VFD fault input goes low
Action Taken: None
Reset: N/A
Slide Positioning Error
Event description (as shown on screen): Slide Pos Error Cir N
Trigger: [ Slide Position > Slide Target + 25% OR Slide Position < Slide Target – 25%] for time > 5 minutes
Action Taken: None
Reset: Circuit State = Off
Alarm Logging
When an alarm occurs, the alarm type, date, and time are stored in the active alarm buffer corresponding to that alarm (viewed on the Alarm Active screens) and also in the alarm history buffer (viewed on the Alarm Log screens). The active alarm buffers hold a record of all current alarms. The active alarms can be cleared by pressing the Edit key when the end of the list has been reached by scrolling. Active alarms may only be cleared if at least the
Operator password level is active.
WGS 130A to 190A 39
A separate alarm log stores the last 25 alarms to occur. When an alarm occurs, it is put into the first slot in the alarm log and all others are moved down one, dropping the last alarm. In the alarm log, the date and time the alarm occurred are stored, as well as a list of other parameters. These parameters include unit state, OAT, LWT, and EWT for all alarms. If the alarm is a circuit alarm, then the circuit state, refrigerant pressures and temperatures, EXV control state, EXV position, slide position, slide target, number of fans, and compressor run time on are also stored.
Event Logging
An event log similar to the alarm log holds the last 25 events to occur. When an event occurs, it is put into the first slot in the event log and all other entries are moved down one, dropping the last event. Each entry in the event log includes an event description as well as the time and date of the occurrence. No additional parameters are logged for events.
The event log shall only be accessible with the Manager password.
Clearing Alarms
Alarms may be cleared at the unit controller and no password is required. The BAS can clear evaporator flow loss, evaporator water freeze and pLAN failure regardless of what other alarms are active.
Unit Controller Functions
Calculations
LWT Slope
LWT slope is calculated such that the slope represents the change in LWT over a time frame of one minute.
Every 12 seconds, the current LWT is subtracted from the value 12 seconds back. This value is added to a buffer containing values calculated at the last five intervals. The final result is a slope value that is an average over the past 60 seconds.
Pulldown Rate
The slope value calculated above will be a negative value as the water temperature is dropping. For use in some control functions, the negative slope is converted to a positive value by multiplying by –1.
Unit Capacity
Unit capacity is estimated based on the slide target of each running circuit. The capacity of a running circuit is estimated with this equation:
Circuit capacity = 0.8(slide target) + 20
A circuit that is off is assumed to be at 0% capacity. The unit capacity is then calculated by this equation:
Unit capacity = (Circuit 1 capacity + Circuit 2 capacity)/2
40 WGS 130A to 190A OM WGS-5
OM WGS-5
Unit Enable
Enabling and disabling the chiller is controlled by the Unit Enable Setpoint with options of
OFF and ON. Enabling allows the unit to start if there is a call for cooling and also starts the evaporator pump.
This setpoint (in other words, enabling the unit to run) can be altered by the:
Unit OFF input (unit On/Off switch)
a field installed remote stop switch
a keypad entry
a BAS request
The Control Source Setpoint determines which sources can change the Unit Enable Setpoint with options of SWITCHES, KEYPAD or NETWORK.
Changing the Unit Enable Setpoint can be accomplished according to the following table.
NOTE : An “x” indicates that the entry is ignored.
Table 16, Unit Enable Combinations
Unit On/Off
Switch
Control Source
Setpoint
Remote
Stop Switch
Key-pad
Entry
BAS
Request
Resultant
Unit Enable
Status
ON/OFF SWITCHES OFF x x OFF
ON SWITCHES ON x x ON
ON NETWORK x x OFF OFF
ON NETWORK OFF x x OFF
ON NETWORK ON x ON ON
Example:
1.
If the Control Source is set to “Switches”, enabling is controlled by the field-installed remote stop switch. If the unit-mounted On/Off switch is either On or Off, the unit will be disabled if the remote switch is Off. If the unit-mounted On/Off switch is On, the unit will be enabled if the remote switch is On.
Chiller Control Source Options:
Set Unit Setpoints Screen #1 (shown below) has three fields: “Enable”, “Mode” and
“Source.”
Unit Setpoints
SET UNIT SPs (1)
Enable=On
Mode= COOL
Source = KEYPAD
The Enable field can only be used with Source = Keypad, to enable and disable the chiller through the key pad, any other control inputs including unit and pumpdown switches and
BAS controls are ignored. The Enable field toggles between On and Off using the Up or
Down key on the controller.
1.
The Mode field is an informational display, showing the active control mode of the chiller. It is used as an input only when the source is set to keypad, only then can this field be changed manually.
2.
The Source field has three options, “SWITCHES”(default), “KEYPAD”, and “BAS
NETWORK”.
WGS 130A to 190A 41
42 a.
Switches source is used when there is no BAS interface used. This allows the unit switches to function as pumpdown and shut down switches for the circuit. This option is also used with applications using the remote start/stop input and not using a BAS interface. b.
Keypad source is used to override BAS or remote start/stop commands. This would be used for servicing only. c.
BAS Network source would be used for those applications using “MODBUS”,
“BACnet”, or “LON” communications through a building automation system. BAS
Protocol is set at Set Unit Setpoints item #14.
All methods of disabling the chiller, except for the unit switch, will cause a normal pumpdown shutoff of any running circuits. Any time the unit switch is used to disable the chiller, all running circuits will shut down immediately, without pumping down.
Shutdown by the unit switch without going through the pumpdown cycle is undesirable and should only be used for an emergency shutdown or for manually and locally disabling the unit after both circuits have gone through a normal shutdown.
Unit Mode Selection
The overall operating mode of the chiller is set by the Unit Mode setpoint with options of
COOL, ICE and TEST. This setpoint can be altered by the keypad, BAS, and Mode input.
Changes to the Unit Mode Setpoint are controlled by two additional setpoints.
Available Modes setpoint: usually set during initial setup and determines the operational modes available at any time with options of:
COOL, cooling only operation, with setpoints available for normal chilled water temperatures
COOL w/Glycol, cooling only operation, allows lower setpoints than COOL
COOL/ICE w/Glycol, allows both cooling and ice mode operation, switchable by a field-installed remote ICE mode switch, by the BAS or through the keypad.
ICE w/Glycol, ice mode only, i.e., full load operation until LWT setpoint is reached
TEST
Control Source Setpoint: The setting determines the source that can change the Unit
Mode Setpoint with options of KEYPAD, NETWORK, or SWITCHES.
When the Control source is set to KEYPAD, the Unit Mode stays at its previous setting until changed by the operator. When the Control source is set to BAS, the most recent BAS mode request goes into effect, even if it changed while the Control source was set to
KEYPAD or DIGITAL INPUTS.
Changing the Unit Mode Setpoint can be accomplished according to the following table.
NOTE : An “x” indicates that the value is ignored.
Table 17, Unit Mode Setpoint Sources
Control Source
Setpoint
Remote
ICE Mode
Switch
Keypad Entry
BAS
Request
Available Modes
Setpoint
Resultant Unit
Mode x x x x COOL COOL x x x x COOL w/Glycol COOL w/Glycol
SWITCHES
SWITCHES
KEYPAD
NETWORK
OFF
ON x x x x
ICE w/Glycol x x x x
COOL
COOL/ICE w/Glycol
COOL/ICE w/Glycol
COOL/ICE w/Glycol
COOL/ICE w/Glycol
COOL w/Glycol
ICE w/Glycol
COOL w/Glycol
ICE w/Glycol
COOL w/Glycol
NETWORK x x x x x
ICE x
COOL/ICE w/Glycol
ICE w/Glycol
ICE w/Glycol
ICE w/Glycol x x x x TEST TEST
WGS 130A to 190A OM WGS-5
OM WGS-5
The Remote ICE Mode Switch (usually a time clock) is a field installed option and is used to switch from ice mode operation at night to cooling mode operation during the day. This requires that the Control Source be set to SWITCHES, which in this case refers to the
Remote ICE Mode Switch.
There are really only three operational modes for the unit, although they can be used in combination:
1.
COOL, the unit unloading and compressor staging is controlled by the Active LWT
Setpoint. COOL w/ Glycol is a special case, providing for lower setpoint ranges.
2.
ICE, the unit runs with all compressors fully loaded until the LWT (set for making ice) is reached, and the unit shuts off. The Ice Delay Timer can be set to prevent restarting until the next ice making cycle.
3.
TEST, manually energize controller outputs to test functionality.
Unit Test Mode
The unit test mode allows manual testing of controller outputs. Entering this mode shall require the following conditions.
Unit OFF input = OFF (i.e. entire chiller is shut down).
Technician password active.
Available Circuit Mode setpoint = TEST
A test menu can then be selected to allow activation of the outputs. It shall be possible to switch each digital output ON or OFF and set the analog outputs to any value.
Unit States
The unit will always be in one of three states.
Unit States
Power ON
OFF
T3
T4
T1
PUMPDOWN
T2
AUTO
Transitions:
T1 – Transition from Off to Auto
Requires all of the following
Unit enabled based on settings and switches
If unit mode is ice, the ice timer has expired
No unit alarms exist
At least one circuit is enabled and available to start
T2 – Transition from Auto to Pumpdown
Requires any of the following
Control source is keypad and the unit enable keypad setting is “off”
Control source is BAS and either the remote switch is “off” or the BAS command is
“off”
Control source is switches and the remote switch is “off”
WGS 130A to 190A 43
44
T3 – Transition from Pumpdown to Off
Requires any of the following
All circuits have finished pumpdown and are off
A unit alarm is active
Unit switch is “off”
T4 – Transition from Auto to Off
Requires any of the following
Unit switch is “off”
A unit alarm is active
All circuits are unavailable to start (cannot start even after any cycle timers have expired)
The unit mode is ice, all circuits are off, and the ice mode delay is active
Ice Mode Start Delay
An adjustable start to start ice delay timer will limit the frequency with which the chiller may start in Ice mode. The timer starts when the first compressor starts while the unit is in ice mode. While this timer is active, the chiller cannot restart in Ice mode. The time delay is user adjustable.
The ice delay timer may be manually cleared to force a restart in ice mode. A setpoint specifically for clearing the ice mode delay is available. In addition, cycling the power to the controller will clear the ice delay timer.
Evaporator Pump Control
The state-transition diagram shown below controls operation of the evaporator pump.
Evaporator Pump
States
Power ON
OFF
T3
T4
T1
T2
RUN
T5
START
Transitions:
T1 – Transition from Off to Start
Requires any of the following
Unit state = Auto AND [If Low OAT Lockout active then LWT <=40]
LWT < Freeze setpoint - 1
T2 – Transition from Start to Run
Flow ok for time > evaporator recirculate time
WGS 130A to 190A OM WGS-5
OM WGS-5
T3 – Transition from Run to Off
Requires any of the following
Unit state = Off AND LWT > Freeze setpoint
Low OAT Lockout is active AND No compressors running AND LWT > 70°F
T4 – Transition from Start to Off
Requires any of the following
Unit state = Off AND LWT > Freeze setpoint
Low OAT Lockout is active AND No compressors running AND LWT > 70°F
T5 – Transition from Run to Start
Requires all of the following
Evaporator water flow loss for time > flow proof
Pump Selection
The pump output used will be determined by the Evap Pump Control set point. This setting allows the following configurations:
#1 only – Pump 1 will always be used
#2 only – Pump 2 will always be used
Auto – The primary pump is the one with the least run hours, the other is used as a backup
#1 Primary – Pump 1 is used normally, with pump 2 as a backup
#2 Primary – Pump 2 is used normally, with pump 1 as a backup
Primary/Standby Pump Staging
The pump designated as primary will start first. If the evaporator state is start for a time greater than the recirculate timeout set point and there is no flow, then the primary pump will shut off and the standby pump will start. When the evaporator is in the run state, if flow is lost for more than half of the flow proof set point, the primary pump will shut off and the standby pump will start. Once the standby pump is started, the flow loss alarm logic will apply if flow cannot be established in the evaporator start state, or if flow is lost in the evaporator run state.
Auto Control
If auto pump control is selected, the primary/standby logic above is still used. When the evaporator is not in the run state, the run hours of the pumps will be compared. The pump with the least hours will be designated as the primary at this time.
Leaving Water Temperature (LWT) Reset
The Active Leaving Water variable shall be set to the current Leaving Water Temperature
(LWT) setpoint unless the unit is in COOL mode and any of the reset methods below are selected. The type of reset in effect is determined by the LWT Reset Type setpoint. The
Active Leaving Water variable is sent from the unit controller to all circuits for capacity control after the applicable reset is applied.
Reset Type – NONE
The Active Leaving Water variable is set equal to the current LWT setpoint.
Reset Type – RETURN
The Active Leaving Water variable is adjusted by the return water temperature.
WGS 130A to 190A 45
46
Return Reset
LWT set Point+Max Reset
(54)
Active
LWT
(
o
F)
Max Reset
(10)
LWT Set Point
(44)
0 Start Reset Delta T
Evap Delta T (
o
F)
The active setpoint is reset using the following parameters:
1.
Cool LWT setpoint
2.
Max Reset setpoint
3.
Start Reset Delta T setpoint
4.
Evap Delta T
Reset is accomplished by changing the Active Leaving Water variable from the Cool LWT setpoint to the Cool LWT set-point + Max Reset setpoint as the Evaporator EWT – LWT
(Evap Delta T) varies from the Start Reset Delta T setpoint to 0.
Referring to the above figure as an example, the LWT is 44 F and a 10-degree maximum reset value was selected. The Active LWT setpoint would range from the normal 44 F setting up to 54 F depending on the Evap Delta-T. The amount of reset would be at the maximum value (10 degrees) when the Evap Delta-T is zero and at the minimum value when the Evap Delta-T is at the Start Reset Delta T value and is proportional in between.
The Start Reset Delta T function is available so that the start of reset can be adjusted. For example, on a system with a 10-degree Delta-T, it may be desirable to not start the resetting until the evaporator Delta-T goes down to eight degrees (80% load), or some other value.
Reset Type – 4-20 mA
The Active Leaving Water setpoint is adjusted by the 4 to 20 mA reset analog input, using:
1.
Cool LWT setpoint
2.
Max Reset setpoint
3.
LWT Reset signal
Reset is 0 if the reset signal is less than or equal to 4 mA. Reset is equal to the Max Reset
Delta T setpoint if the reset signal equals or exceeds 20 mA. The amount of reset will vary linearly between these extremes if the reset signal is between 4 mA and 20 mA. An example of the operation of 4-20 reset in Cool mode is shown below.
WGS 130A to 190A OM WGS-5
OM WGS-5
4-20 mA Reset - Cool Mode
(54)
Active
LWT
(
o
F)
Max Reset
(10)
Cool LWT Set
Point (44)
0 4 20
Reset Signal (mA)
Reset Type – OAT
This reset can only be used if the unit is configured as air-cooled.
The Active Leaving Water variable is reset based on the outdoor ambient temperature.
Parameters used:
1.
Cool LWT setpoint
2.
Max Reset setpoint
3.
OAT
Reset is 0 if the outdoor ambient temperature is greater than 75 F. From 75 down to 60 F the reset varies linearly from no reset to the max reset at 60 F. At ambient temperatures less than 60 F, reset is equal to the Max Reset setpoint.
OAT Reset
Active
LWT
(
o
F)
Cool LWT+Max Reset
(54)
Max Reset
(10)
Cool LWT Set-Point
(44)
60 75
OAT (
o
F)
Planned Unit Capacity Overrides
Unit capacity limits can be used to limit total unit capacity in COOL mode only. Multiple limits may be active at any time, and the lowest limit is always used in the compressor capacity control.
The estimated unit capacity and the active capacity limit are sent to all circuits for use in compressor capacity control.
Soft Load
Soft Loading is a configurable function used to slowly ramp up the unit capacity over a given time. The setpoints that control this function are:
WGS 130A to 190A 47
48
Soft Load – (ON/OFF)
Begin Capacity Limit – (Unit %)
Soft Load Ramp – (seconds)
The Soft Load Unit Limit increases linearly from the Begin Capacity Limit setpoint to
100% over the amount of time specified by the Soft Load Ramp setpoint. If the option is turned off, the soft load limit is set to 100%.
Demand Limit
The maximum unit capacity can be limited by a 4 to 20 mA signal on the Demand Limit analog input at the unit controller. This function is only enabled if the Demand Limit setpoint is set to ON.
As the signal varies from 4 mA up to 20 mA, the maximum unit capacity changes linearly from 100% to 0%. Although the demand limit can call for 0% capacity, this signal will never cause a running compressor to shut down. Rather, all running compressors will be held at minimum load, and this may occur at a demand limit value that is actually less than
20mA.
Network Limit
The maximum unit capacity can be limited by a network signal. This function is only enabled if the unit control source is set to network. The signal will be received through the
BAS interface on the unit controller.
As the signal varies from 0% up to 100%, the maximum unit capacity changes linearly from
0% to 100%. Although the network limit can call for 0% capacity, this signal will never cause a running compressor to shut down. Rather, all running compressors will be held at minimum load, and this may occur at a network limit value that is actually less than more than 0%.
Condenser Pump and Tower Control
Condenser pump and cooling tower control logic requires that the unit be configured as water-cooled in order to be active. The unit controller controls water-cooled components such as condenser pumps and tower controls, since there is usually one tower per unit. Aircooled equipment, associated with the remote condenser option, is controlled by the circuit controllers. Remote evaporative condensers require a self-contained, on-board, discharge pressure control system.
Condenser Water Pump State Control
If the unit is configured as water-cooled, then the condenser pump is controlled by the statetransition diagram shown below.
Condenser Pump
States
Power ON
OFF
T3
T4
T1
RUN
T5
T2
WGS 130A to 190A
START
OM WGS-5
OM WGS-5
Transitions:
T1 – Transition from Off to Start
Requires any of the following
Unit state = Auto AND any circuit available AND LWT error > Startup Delta
Cond Water Freeze Alarm
T2 – Transition from Start to Run
Flow ok for time > cond recirculation timer setpoint
T3 – Transition from Run to Off
Requires all of the following
Unit state = Off OR No circuit available OR LWT error < Start Delta-1
Cond Water Freeze Alarm not active
No compressors running
T4 – Transition from Start to Off
Requires all of the following
Unit state = Off OR No circuit available OR LWT error < Start Delta
Cond Water Freeze Alarm not active
No compressors running
T5 – Transition from Run to Start
Requires all of the following
Condenser water flow loss for time > flow proof
All circuits in Off state
Pump Selection
The pump output used will be determined by the Condenser Pump Control setpoint. This setting allows the operator to select pump #1, pump #2, or auto. The first two selections will use a single pump output all the time. The auto selection will start the pump with the least run hours.
The selected output will be ON if the Evap State is set to START or RUN. Both outputs will be OFF if the Evap State is set to OFF.
Cooling Tower Control
Tower Fans
Tower fan control is active when the unit is set up as water-cooled, Tower Control is set to
Temperature, and the condenser pump is in the RUN state. Staging is based on Condenser
Entering Water Temperature. Operation depends on the following parameters.
Condenser pump state
Condenser EWT
Stage up and stage down timer values
Tower setpoints (Tower Control, Tower Stages, Stage Up Time, Stage Down Time,
Stage Differential, Stage #1 ON, Stage #2 ON, Stage Down @, Stage Up @)
When the condenser pump starts, the stage up timer shall start. The first stage shall turn ON when the following conditions are met:
The stage up timer completes
The Condenser EWT is > Stage #1 ON setpoint
Bypass valve position is > the Stage Up @ setpoint (only if Valve/VFD Control setpoint
= Valve Stage)
VFD Speed is > the Stage Up @ setpoint (only if Valve/VFD Control setpoint = VFD
Stage OR Valve SP/VFD Stage)
WGS 130A to 190A 49
50
Additional stages can turn on (up to the number specified by the Tower Stages setpoint) when above conditions are met for the next stage.
Down staging shall occur when the following conditions are met:
The stage down timer completes
The Condenser EWT is < Stage #X ON (Temp) setpoint – Stage Differential (Temp) setpoint
Bypass valve position is < the Stage Down @ setpoint (only if Valve/VFD Control setpoint = Valve Stage)
VFD Speed is < the Stage Down @ setpoint (only if Valve/VFD Control setpoint =
VFD Stage OR Valve SP/VFD Stage)
Each stage up or stage down event shall restart both the stage up and stage down timers.
Only one fan output shall be switched at a time (except that all outputs switch OFF when the condenser pump state equals OFF).
Cooling Tower Bypass Valve
When the Valve/VFD Control setpoint is set to None OR VFD Stage, this output shall be set to 0. Otherwise, it shall be controlled as described below.
Initial Valve Position
When the condenser pump is not in the RUN state, the valve output shall be set as a function of entering condenser water temperature (ECWT)) per the following graph.
Initial Valve Position
(values are examples only)
Max Position @
Set Point
(90°F)
Min Position @
Set Point
(60°F)
Min Start Position
Set Point (10%)
Max Start Position
Set Point (90%)
Operation After Start
When the condenser pump is in the RUN state, the valve output shall be controlled in one of two modes as specified by the Valve/VFD Control setpoint. The controlled parameter shall be the condenser entering water temperature. When the desired output signal varies from 0 to 100%, the output voltage shall vary as shown below.
0 to 10 VDC (Valve Type = NC to tower)
10 to 0 VDC (Valve Type = NO to tower)
Valve Setpoint Mode
This mode is operational when the Valve/VFD Control setpoint is set to Valve setpoint OR
Valve SP/VFD Stage. In this mode the valve output is varied with a proportional-derivative
WGS 130A to 190A OM WGS-5
OM WGS-5
(PD) algorithm (with deadband) in order to maintain the controlled parameter (CP) at the desired value. The output is always limited between the Valve Control Range (Min) setpoint and the Valve Control Range (Max) setpoint. A valve increment shall be computed once every 5 seconds according to the following equation.
Increment = [(Error) * (Error Gain setpoint)] + [(Slope) * (Slope Gain setpoint)] Where:
Error = ECWT – Valve Setpoint Slope = (Present CP) – (Previous CP)
When the Error is > the Valve Deadband setpoint, the valve position analog output (% of full scale) is updated according to the following equation.
New %Position = Old %Position + Increment/10.
Valve Stage Mode
This mode is only operational when the Valve/VFD Control setpoint is set to Valve Stage.
In this mode the valve output is controlled as for Valve setpoint mode (above) except that the active setpoint for the controlled parameter is selected according to the following table.
# of Fans ON Active Setpoint
0
1
2
Valve Setpoint
Stage #1 ON
Stage #2 ON
Cooling Tower Fan VFD
When the Valve/VFD Control setpoint is set to None, Valve Setpoint, OR Valve Stage, this output shall be set to 0. Otherwise, it shall be controlled in a manner identical to Valve
Stage Mode (above) except that (1) it shall be kept at zero until the first fan stage is ON and
(2) the following setpoints do not apply.
Valve Control Range (Min)
Valve Control Range (Max)
Valve Type
Evaporative Condenser Control
It is acceptable to use WGS-A chillers (less condenser) with evaporative condensers. It is the installer's responsibility to provide the evaporative condenser control because this condenser type is not available from McQuay. The WGS-A software does not directly support evaporative-cooled applications since there is a variety of fan configurations and pumps available from the manufacturers of evaporative condensers. In addition, the WGS software does not support the auxiliary functions of the evaporative condenser such as make up water valves, sump drain valves, electronic make up water valves, water freeze protection, variable frequency drives, damper controls or water treatment options. The
WGS software will provide equipment protection and operational limits as if it were a remote air-cooled condenser application. See other sections of this manual for complete descriptions.
The system must be comprised of two controls systems that operate together to make a complete system. First, the WGS-A software provided with the unit will control the indoor chiller section of the unit including compressor loading/unloading, equipment protection,
BAS interface (when applicable), and other functions as described in this manual without the condenser control. The WGS software setup shall be treated as a remote air-cooled application. The second control system is required to control the condenser and auxiliary functions. The best method for interfacing the two systems is through the "first on, last off" fan contacts as if the application was a remote air-cooled condenser. At start up of the compressors, the Fan 1 Contactor fan contacts will close and activate the condenser control
WGS 130A to 190A 51
52 system provided by others. At shut down, the reverse occurs where the condenser control will be deactivated when the compressor stops as the Fan 1 fan contacts open.
Special considerations must be given to the condenser control including (but not limited to) the following items.
1.
All WGS-A chillers have two refrigerant circuits and an evaporative condenser with two refrigerant circuits is also required.
2.
A control system for each refrigerant circuit is required. It is best to have separate fans and pumps for each refrigerant circuit to prevent "fighting" of control signals between the two refrigerant circuits.
3.
The control system shall maintain a minimum condenser pressure at all times.
4.
The normal control philosophy is to maintain the lowest possible condensing pressure above the minimum allowable to provide the best operating efficiency throughout the chiller's entire operating range.
5.
For a normal starting sequence, it is best to start the fans first with minimum airflow.
As the condenser pressure rises, increase the airflow by increasing the fan RPM, opening inlet vanes, opening outlet dampers, or other meaning of increasing airflow. If condensing pressure continues to rise after maximum airflow is reached, start the circulating pump (s). Reverse the sequence for the shut down procedure.
6.
Provide the maximum number of condenser staging steps as possible to provide as stable operation as possible.
7.
Recognize that condenser pressure will change drastically and rapidly, when the water pump starts and stops. This is the reason for starting the fan first in an increasing capacity situation and stopping the fan operation last with a shutdown procedure.
8.
It is important for the control pressure settings for the fans and pumps to have a large control band so that condenser component cycling does not occur. It is also good practice for the fan and pump control to "overlap". Overlap means that the control bands must be determined so that there is a pressure range between when a pump starts/ stops with fan operation. Use caution to be certain that fan & pump cycling does not occur which causes rapid changes in condensing pressure which causes instability in the refrigeration system.
9.
Refer to the installation, operation and maintenance manuals of the manufacturer of the evaporative condenser for their guidelines and recommendations. Give special consideration to preventing freezing conditions, make up water, and other functions common to evaporative condensers that should be described in those brochures.
!
CAUTION
Use water treatment with evaporative condensers. Failure to prevent microbiology growth, scaling and corrosion can damage the unit.
10.
Damage caused or contributed by improper water treatment may not be covered by
McQuay’s warranty.
WGS 130A to 190A OM WGS-5
11.
For recommendations and answers to system questions, contact the McQuay
Applications Group in Staunton, Virginia.
Building Automation System (BAS) interface and monitoring is an optional accessory required for many systems. The WGS-A interface options are communication cards supporting L ON W ORKS , BACnet or Modbus. Refer to the other McQuay brochures listed in this manual for a complete description of capabilities. As a general statement, the McQuay communication cards do NOT support the evaporative condenser. The desired interface points for the condenser must be provided by others and through the control system provided with the evaporative condenser. Use caution in the ability to change condenser setpoints through the BAS system as such changes can impact chiller operation.
OM WGS-5 WGS 130A to 190A 53
Circuit Controller Functions
54
Refrigerant Calculations
Refrigerant Saturated Temperature
Refrigerant saturated temperature is calculated from the pressure sensor readings for each circuit. The pressure will be fitted to a curve made up of 12 straight line segments. The points used to define these segments are shown in the following tables.
Table 18, Evaporator Pressure Conversion:
Pressure (PSI) Temperature ( o F)
0 -15.0
7.1 0
19.0 20.0
34.7 39.0
50.7 54.0
70.4 69.0
99.6 87.0
129.2 102.0
166.8 118.0
205.4 132.0
246.5 145.0
320.0 165.0
428.5 188.1
Table 19, Condenser Pressure Conversion:
Pressure (PSI) Temperature ( o F)
0 0.6
17.5 18.5
31.5 35.9
50.0 53.7
76.0 73.4
115.0 95.6
161.5 116.2
185.0 125.2
260.0 149.2
284.5 155.9
349.5 172.0
365.5 175.5
428.5 188.1
Circuit Operating Mode
The circuits on the chiller can each be individually enabled or disabled. Test mode on each circuit can also be entered independent of all other circuits. With the circuit switch on, the circuit mode setpoint offers settings of either enable or disable. This simply allows the circuit to be disabled through a keypad setting.
Circuit Test Mode
The circuit test mode allows manual testing of all controller outputs. Entering this mode requires the following conditions.
WGS 130A to 190A OM WGS-5
OM WGS-5
Circuit Switch = OFF
Technician password active
Circuit Mode setpoint = TEST
A test menu can then be selected to allow activation of the outputs. It is possible to switch each digital output ON or OFF and set the analog outputs to any value. Upon entering test mode, all outputs will always default to the off state. Upon leaving test mode, all outputs will automatically reset to the off state.
Compressors cannot be started in TEST mode.
Compressor Control
Multiple Compressor Staging
This section defines which compressor is the next one to start or stop. Compressors with fewer starts will normally start first, and compressors with more run hours will normally stop first.
Functions
Can start/stop compressors according to an operator defined sequence.
Can start compressors based on number of starts (run hours if starts are equal) and stop on run hours.
The above two modes can be combined, so that there are two or more groups, where all compressors in the first group are started (based on number of starts/hours) before any in the second group, etc. Conversely, all compressors in a group are stopped (based on run hours) before any in the preceding group, etc.
Multiple Compressor Start/Stop Timing – Cool Mode
This section defines when a compressor is to start or stop when the chiller is operating in cool mode.
Required Parameters
Startup Delta T setpoint.
Stage Up Delta T setpoint
Stage Down Delta T setpoint
Stop Delta T setpoint
LWT error (See definition under Compressor Capacity Control section.)
Full load indicator for each compressor
Full Load Indicator
A circuit is considered to be at full load in the compressor staging logic when any of the following occur:
Slide control = manual
A low or high pressure limit event has been active for 10 seconds
Slide target >= 75% AND max slide target > 75%
Slide target >= max slide target AND max slide target <= 75%
WGS 130A to 190A 55
56
Starting
A compressor will start (stage up):
IF LWT is above the Active LWT Setpoint plus the Startup Delta-T SP AND no compressors are running OR all running compressors are at full load
Stopping
A compressor will stop (stage down);
IF LWT is below the Active LWT Setpoint minus the Stop Delta-T SP AND other compressors are running or not;
OR IF LWT is below the Active LWT Setpoint minus the Stop Delta-T SP AND all other running compressor’s slide position is less than the light load stagedown setpoint.
Multiple Compressor Start/Stop Timing – Ice Mode
This section defines when a compressor is to start or stop when the chiller is operating in ice mode.
Required Parameters
Startup Delta T setpoint.
Stage Up Delta T setpoint
LWT error (See definition under Compressor Capacity Control section.)
Starting
A compressor will start (stage up):
IF LWT is above the Active LWT Setpoint plus the Startup Delta-T SP AND no compressors are running OR all running compressors are at full load.
Stopping
The compressor will stop.
IF LWT reaches the ICE LWT Setpoint
Compressor Capacity Control
Compressor capacity is determined by calculating a slide position target. Adjustment to the slide target for normal running conditions occurs every 5 seconds. For loading a maximum change of 1% is allowed, and for unloading a maximum change of 2% is allowed.
Required parameters
Count In Load Balance status for each compressor
Slide targets of all compressors
LWT error
LWT slope
LWT Error
LWT error compares the actual LWT to the active LWT setpoint. The equation is:
LWT error = LWT – active LWT setpoint
LWT Slope
LWT slope is calculated in the unit controller and sent to circuits via pLAN.
In the unit controller, this value is calculated such that the slope represents a time frame of one minute.
WGS 130A to 190A OM WGS-5
OM WGS-5
Every 12 seconds, the current LWT is subtracted from the value 12 seconds back. This value is added to a buffer containing values calculated at the last five intervals. The final result is a slope value that is an average over the past 60 seconds.
Count In Load Balance Flag
A circuit will be counted for load balancing only if all of the following are true:
Compressor state is run
Compressor is able to load up (no limits in effect due to pressure or superheat)
Slide control is auto
Slide position target is less than the max slide target setpoint
Cool Mode
When the chiller is in COOL mode, capacity of the compressor is adjusted to maintain leaving water temperature at the Active LWT setpoint while balancing the load between running circuits. Load balance offset, LWT error, and LWT slope are used to calculate a change in slide position as described below.
Load balance offset:
IF other compressor is flagged to be counted in load balance
THEN Load Balance Offset = slide target - (cir 1 target + cir 2 target)/2
ELSE Load Balance Offset = 0
LWT Error:
LWT Error = (Leaving Evaporator Water Temp) – (Active LWT setpoint).
LWT slope:
Slope (deg/minute) = sum of last five LWT changes as calculated every 12 seconds
Slide target adjustment = [LWT Error + (LWT Slope x 4) – Load Balance Offset] / #
Compressors Running
Ice Mode
In ICE mode, the compressor capacity is increased at the maximum rate continuously until reaching the maximum slide position. Load balancing, LWT error, and LWT slope are ignored.
Low OAT Start Logic
In order to avoid low pressure alarms at the start of a circuit, low OAT start logic allows for running at low pressures for a longer time than normal, as well as multiple start attempts.
This logic is only used for air-cooled operation.
A low OAT start is initiated if the condenser saturated temperature is less than 60 F when the compressor starts. Once this happens, the circuit is in the low OAT start state for a time equal to the low OAT start timer setpoint. During this time, the freezestat logic and the low pressure events are disabled. The absolute limit of –10 psi is still enforced.
At the end of the low OAT start, the evaporator pressure is checked. If the pressure is greater than, or equal to, the low evaporator pressure unload setpoint, the start is considered successful. If the pressure is less than the unload setpoint, the start is not successful and the compressor will stop. Three start attempts are allowed before tripping on the restart alarm; so if on the third attempt the start is not successful, the restart alarm is triggered.
The restart counter will be reset when either a start is successful or the circuit is off on an alarm.
WGS 130A to 190A 57
58
Internal Capacity Overrides
The following conditions override the automatic slide control when the chiller is in COOL mode or ICE mode. These overrides keep the circuit from entering a condition in which it is not designed to run. Any compressor running with capacity limits because of these conditions is considered to be at full load in the compressor staging logic.
Low Evaporator Pressure
If the evaporator pressure drops below the Low Evaporator Pressure Hold setpoint while the compressor is running, the Low Evaporator Pressure Inhibit (Hold) event is triggered.
When triggered, the compressor will not be allowed to increase in capacity.
If the evaporator pressure drops below the Low Evaporator Pressure Unload setpoint while the compressor is running, the Low Evaporator Pressure Unload event is triggered. When triggered, the compressor will begin reducing capacity. The maximum allowed slide target will be adjusted down 5% every 5 seconds until the evaporator pressure rises above the Low
Evaporator Pressure-Unload setpoint.
These events are logged to an event log when they occur. Both remain active until the evaporator pressure rises above the hold setpoint plus 2 psi, or the circuit goes to a state other than Run.
High Lift Pressure
If the compressor is running and the condenser pressure rises above the High Lift Pressure
Hold setpoint, the High Lift Pressure Inhibit event is triggered. When this happens, the compressor will not be allowed to increase capacity. This event is active until the condenser pressure drops 10 psi below the hold setpoint.
If the compressor is running above minimum load capacity and the condenser pressure rises above the High Lift Pressure Unload setpoint, the High Lift Pressure Unload event is triggered. When this happens, the compressor will begin reducing capacity. The maximum allowed slide target will be adjusted down 5% every 5 seconds until the condenser pressure drops below the High Condenser Pressure Unload setpoint. The compressor will not be allowed to increase in capacity until the condenser pressure drops to 10 psi below the unload setpoint.
Maximum LWT Pulldown Rate
The maximum rate at which the leaving water temperature can drop is limited by the
Maximum Rate setpoint, only when the LWT is less than 60 o F and the unit mode is Cool. A slope unload factor is used to reduce the slide target if the pulldown rate exceeds the
Maximum Rate setpoint.
Slope Unload Factor: Maximum Rate + LWT slope
If the pulldown rate is too fast, then the slide adjustment made will be equal to the slope unload factor.
High Water Temperature Capacity Limit
If the evaporator LWT exceeds 55 F, compressor slide position will be limited to a maximum of 75%. Compressors shall unload to 75% or less if running at greater than 75% slide position when the LWT exceeds the limit. This feature is to keep the circuit running within the capacity of the condenser coil.
WGS 130A to 190A OM WGS-5
OM WGS-5
Unit Capacity Overrides
Unit capacity limits override the automatic slide control when the chiller is in COOL mode only. The active capacity limit as well as the estimated unit capacity will be calculated in the unit controller and sent to all circuits.
If the unit capacity is greater than the active capacity limit, then no circuit will increase slide position. If the unit capacity is greater than the active limit plus 1%, the circuits will unload until the unit capacity is less than 1% greater than the active limit.
Pumpdown
When a circuit reaches a condition where the compressor needs to shut down normally, a pumpdown will be performed. The slide target will automatically go to 0 while pumping down, and the compressor will run until the pumpdown pressure has been reached, or the pumpdown time has been exceeded.
Service Pumpdown
If the option for a service pumpdown is enabled, then on the next pumpdown the pressure setpoint will be 5 psi. The circuit will pumpdown to this pressure and shut off. When the compressor has completed the service pumpdown, the setpoint is reset to No.
Slide Positioning
Slide Position Indicator
Each compressor estimates its slide load percentage from the present value of the slide position indicator. The percentage is based on the 4-20mA signal from the slide load indicator. A percentage value of 0 corresponds to approximately a 4mA signal, a percentage value of 100 corresponds to approximately a 20mA signal.
Slide Calibration Procedure
Slide Position is a relative capacity adjustment from 0.0%(Min load) to 100.0%(Max Load).
There are two MicroTech readings that apply to the indicator, Slide Target and Slide
Position. It is important to understand the difference between these. The Slide Target is the value in which the controller uses to display the calculated prediction of slide position, this value represents the destination or goal of pulsing the load and unload solenoid coils.
The slide target is used for direction of control for all load and unload operations, including alarm limit events. When putting a circuit in Manual mode, the slide target is the value that you will be adjusting. The controller will load or unload the chiller to match, with in about
3%, the target entered with the current slide position value. The second value is the Slide
Position (Pos) this is the slide position value which is the 4-20mA reading received from the position indicator. These values can be viewed at the circuit controller on screen
“VIEW CIR STATUS (1)”.
A slide target of 0.0% is fully unloaded and the unload solenoid will be constantly energized. A slide target of 100.0% means that the chiller is at full load and the load solenoid is continually energized. The chiller will regulate the slide position to infinite steps between 0% and 100% by pulsing the appropriate solenoid. Facing the discharge end of the compressor, looking along the left side, the solenoid coil on the top is for load (oil vent) and the solenoid coil on the side is for unload (oil feed). During normal operation, the controller makes decisions to move the Slide target, the calculated value, and pulses the proper solenoid in order to keep the actual and the target position with in a few percent.
WGS 130A to 190A 59
60
Figure 9, Slide Indicator and Coils
Load Coil
Unload Coil
Slide Indicator
Calibration Procedure:
1.
The circuit to be calibrated should be near normal operating temperatures. Note that the compressor requires sufficient oil pressure to unload the compressor while it is running, and may load up due to lack of oil feed pressure.
2.
On the Circuit controller, first verify what your current slide target is at screen “View
Circ Status (1)” and then go to screen “SET COMP SPs (2)” to switch circuit into manual slide control. Note: Some hold limits will be ignored but all alarm limits are still active while in manual slide control.
3.
Slowly take the circuit to 0% slide position. When the slide target is at 0%, verify that the unload coil is energized.
4.
Find the slide indicator device located on the left side of the compressor facing the discharge end. Unscrew the metal cap and press the calibrate button beside the LED.
The red LED will come on for about 30 seconds and then start to blink. The indicator is now calibrated at 0%.
5.
Now, slowly take the circuit to 100% slide position, watching that the suction pressure and other unit readings are OK. Always keep discharge superheat above 22°F. When the slide target is at 100%, verify that the load coil is energized. Press the calibrate button. The red LED will come on for about 30 seconds and then the green LED will come on. The indicator is now calibrated at 100%.
6.
The mechanical calibration is now complete for the compressor you are working with.
Replace the calibration cap.
7.
Once you have the mechanical slide calibration complete you may fine tune the calibration from the circuit controller, if necessary. On the circuit controller scroll all the way to the right, this is the calibration and offsets menu. Scroll down until you see
“SET SENSOR OFFSET(3)”. You will see an adjustment for Min Load and Max Load and on the bottom line you will see the value of actual slide position indicator. Add offset until value is within +/-.5% of the corresponding full load or minimum load position.
8.
Repeat calibration procedure until all circuits have min and max positions calibrated.
Note : The Slide Indicator Transducers may vary a considerable amount with temperature change, and therefore they need to be calibrated at typical running temperatures.
WGS 130A to 190A OM WGS-5
OM WGS-5
Manual Slide Control Mode
The slide position on each circuit can be controlled manually. A setting on the compressor setpoints screen in each circuit controller allows the operator to select manual slide control.
On the same screen, a slide target can be selected, from 0% to 100%.
Anytime a circuit is in manual slide control, it is considered to be at full load in the staging logic. It also will not be considered in load balancing calculations. None of the capacity limits outlined above will apply in manual slide control, but all stop alarms are still applicable.
Slide control will revert back to automatic control if a stop alarm occurs on the circuit or unit, or the slide control has been manual for four hours.
Slide Pulse
The slide pulse output moves the compressor slide in order to reach the capacity requested by the slide position target. The output will pulse for 200 ms every 6 seconds while the
Slide Pulse flag is true, that is, whenever there is a difference between the actual slide position and the requested position.
Expansion Valve Control
The EXV can be in one of four control states. Each state is described below.
Preopen
At the time of a start request, the EXV will perform a pre-open function. This mode applies to both remote air cooled and packaged water cooled condenser operation and helps prime the evaporator prior to starting as well as getting the EXV in a better starting position. For remote air-cooled condenser operation, this function is disabled should the condenser pressure be less than the evaporator pressure at start. For remote air-cooled condenser operation, the liquid line solenoid shall remain closed until the compressor starts. During pre-open, the EXV signal is held at 3000 steps.
For remote condenser configuration units that come equipped with a factory mounted liquid line solenoid, a post-open logic has been added to prevent hydraulic lock between the liquid line solenoid and the electronic expansion valve. After the compressor performs a pump down and cycles off, the electronic expansion valve will re-open for 30 seconds and then return to its closed position.
Pressure Control
In pressure control, the evaporator pressure is controlled by the EXV position. The pressure target varies based on evaporator LWT and discharge superheat values. PID logic will be used to control the pressure to the target value.
The base pressure target is calculated using the following formula:
Base target = 0.6(LWT) – 2
The base target is limited to a range from low pressure inhibit set point + 2 psi, to 52 psi.
The pressure control target may be adjusted if the discharge superheat is not within an acceptable range. If the superheat is less than 22oF, the base pressure target will be reduced by a value equal to the low superheat error. If the superheat is more than 40 F, the base pressure target will be increased by a value equal to the high superheat error. At any time, the adjusted target pressure cannot go below the low pressure inhibit set point or above 52 psi.
When the EXV transitions to the pressure control state, the target will start at the current evaporator pressure value. The pressure target will then decrement 0.2 psi every second until reaching the normal calculated target. If the pressure at transition is less than the calculated target, then pressure control will start immediately with the calculated target.
WGS 130A to 190A 61
62
Superheat Control
In superheat control, suction superheat is controlled directly by the EXV. The superheat target varies linearly from 6 to 10 degrees F as discharge superheat changes from 30 degrees F to 22 degrees F. PID logic controls the superheat to the target value.
When the EXV transitions to the superheat control state, the target will start at the current suction superheat value. This target will then decrement 0.1 degree F every second until reaching the normal target.
Closed
Any time the EXV is not in pressure control or superheat control, it will be in a closed state. At this time, the EXV position is 0 steps and the EXV close signal (digital output) is active.
After the compressor performs a pumpdown and cycles off, the electronic expansion valve will re-open for 30 seconds. After these 30 seconds, the expansion valve will return to its closed position. This logic has been added to help prevent hydraulic lock between the liquid line solenoid and the electronic expansion valve.
EXV State Transitions
The following state diagram shows the transitions between EXV control states for both packaged water-cooled and remote air-cooled condenser configurations. Preopen is not performed for remote air cooled condenser configurations when the evaporator pressure is greater than condenser pressure. See “EXV State Transitions – Aircooled” on page 63.
EXV States
Power ON
Closed
T1
Preopen
T5
T2
T7 T6
T3
Superheat Pressure
T4
Transitions:
T1 – Transition from Closed to Preopen
Requires all of the following
Unit State = Auto
Evap State = Run
Compressor is available
Compressor is next on
Stage up now flag is set
Compressor State = Off
OR (as in the case when a circuit cycles off)
Compressor State = Off and unit configured for remote air-cooled condenser,
(will perform a pre-open for 30 seconds (post open time) then return to Closed state)
T2 – Transition from Preopen to Pressure Control
Requires the following
WGS 130A to 190A OM WGS-5
OM WGS-5
EXV State has been Preopen for a time greater than the preopen timer set point
T3 – Transition from Pressure Control to Superheat Control
Requires all of the following
Suction Superheat > Superheat target
Evap LWT <= 60 F
EXV State = Pressure AND Discharge Superheat >= 22 F for at least 3 minutes
T4 – Transition from Superheat Control to Pressure Control
Requires any of the following
Evap LWT > 63 F
Low Evap Pressure Unload event active
Discharge Superheat < 22 F or > 40 F
T5 – Transition from Pre-open to Closed state
Compressor State = Off and unit configured for remote air-cooled condenser and EXV post open timer (non-field-adjustable at 30 seconds) has expired.
Compressor State not Run
T6, T7 – Transition from any state to Closed state
Requires the following
Compressor State not Run
EXV State Transitions – Aircooled
The following state diagram shows the transitions between EXV control states for remote air-cooled operation when evaporator pressure is greater than condenser pressure at start.
EXV States
Power ON
Closed
T5 T4 T1
T2
Superheat Pressure
T3
Transitions:
T1 – Transition from Closed to Pressure Control
Requires all of the following
Unit State = Auto
Evap State = Run
Compressor is available
Compressor is next on
Stage up now flag is set
Compressor State = Off
T2 – Transition from Pressure Control to Superheat Control
Requires all of the following
Suction Superheat >= Superheat target
Evap LWT <= 60 F
WGS 130A to 190A 63
64
EXV State = Pressure AND Discharge Superheat >= 22 degrees F for at least 3 minutes
Discharge Temperature <= 180 F
T3 – Transition from Superheat Control to Pressure Control
Requires any of the following
Evap LWT > 63 F
Low Evap Pressure Unload event active
Discharge Superheat < 22 F
Discharge Temperature > 185 F
T4, T5 – Transition from any state to Closed state
Requires the following
Compressor State not Run
EXV Control Range
The table below shows the EXV range for each size compressor at minimum and maximum capacity. The minimum and maximum values vary linearly with slide position, defining a new EXV control range for every change in slide position.
Compressor Size
EXV Slide %
167 179 197
Min 0 250 250 250
Max 0 3000 3000 3000
Min 100 870 1080 1300
Max 100 3400 4200 5000
Based on the values in the above table, the EXV control range varies as shown in the table below. The shaded area the control range.
EXV Control Range
Max EXV
@ 100%
EXV
Steps
Max EXV
@ 0%
Min EXV
@ 100%
Min EXV
@ 0%
0
Slide Position (%)
100
Manual EXV Control
The EXV position can be set manually. Manual control can only be selected when the compressor is in the run state. At any other time, the EXV control set point is forced to auto.
When EXV control is set to manual, the EXV position is equal to the manual EXV position setting. If set to manual when the compressor state transitions from run to another state, the control setting is automatically set back to auto.
WGS 130A to 190A OM WGS-5
OM WGS-5
Oil Heater Control
The oil heater shall be on when the compressor is not running AND the oil level input is closed for 15 seconds. This output will turn off immediately when either the oil level switch opens or the compressor state is no longer off.
Starter Communications
The Modbus protocol is used to establish communications between the compressor starter and the circuit controller on the supervisor port, with the circuit controller acting as the master and the starter as the slave.
Table 20, Parameters to be Read/Written:
Register Description R/W
R/W
R
R
Range
Bit Mask
0: Run/Stop
1: Fault Reset
Bit Mask
0: Ready
1: Running
2: UTS
3: Alarm
4: Fault
5: Lockout
Units
-
-
Amps
R Amps
R
R
R
R
R
R
R
-99 to 100 (in 16 bit two’s compliment signed format)
R
R
Amps
Amps
Volts
Volts
Volts
Volts
1037 PF
1038 KW
1039 KVA
0.01
KW
KVA
R/W 1-9999 Amps
1057 Ground Fault Trip Enable
R/W
R/W
1-9999
0: Disabled
1: Enabled
1-100
Amps
-
1058 Ground Fault Trip Level R/W % RLA
1078
Fault Code – Most Recent
Fault Log Entry
R -
Read-only parameters are displayed at the circuit controller, and sent over pLAN to the unit controller where they will also be displayed. Read/write parameters are accessible at the circuit controller only. These read/write parameters are changeable when the starter communication is working and the proper password is active.
Starter Faults
Starter faults can be viewed from the unit controller. Some starter faults will be implemented as unique alarms, and others are grouped into a generic starter fault alarm.
WGS 130A to 190A 65
66
The most recent fault code shall be stored in the alarm log parameter list. The fault reset signal is sent to the starter when the operator clears the active alarm on the unit controller.
The starter fault codes and their corresponding alarms are shown in the table below:
Table 21, Starter Fault Codes
94
95
96
97
51
52
60
61
71
37
38
39
40
47
48
50
15
21
22
23
24
25
26
01
02
10
12
13
UTS Time Limit Expired
Motor Thermal Overload Trip
Phase Rotation Error, not ABC
Low Line Frequency
High Line Frequency
Input power not three phase
Low Line L1-L2 Voltage
Low Line L2-L3 Voltage
Low Line L3-L1 Voltage
High Line L1-L2 Voltage
High Line L2-L3 Voltage
High Line L3-L1 Voltage
N/a
No Starter Transition
Compressor Current Overload Trip
Phase Reversal
Starter Fault
Starter Fault
Phase Loss
Undervoltage
Undervoltage
Undervoltage
Overvoltage
Overvoltage
Overvoltage
27 Phase Loss Phase Loss
Undervoltage
30 Instantaneous Compressor Current Overload Trip
31 Overcurrent Compressor Current Overload Trip
Current Imbalance
Ground Fault
No Current at Run
Shorted/Open SCR
Current Sensor Offset Error
Burden Switch Error
Thermistor Trip (on DIN#1)
Stack OT Switch Trip (on DIN#2)
Analog Input Trip
Motor Current Imbalance
Ground Fault Protection
Low Motor Current
Starter Fault
Stack Protection Fault Starter Fault
Bypass Contactor Fault (on Stop Input) No Starter Transition
Control Power Low Starter Fault
Starter Fault
Starter Fault
High Motor Temperature
Starter Fault
Starter Fault
Starter Fault (detected by circuit controller)
CPU Error – Software Fault Starter Fault
CPU Error – Parameter Storage Fault Starter Fault
CPU Error – Illegal Instruction Trap Starter Fault
CPU Error – Software Watchdog Fault Starter Fault
98
99
CPU Error – Spurious Attempt
CPU Error – Program Storage Fault
Starter Fault
Starter Fault
If a starter fault is active and the active alarms are cleared at the unit controller, the clear alarm signal will also be sent to the starter to clear the alarm status in the starter.
Loss of Starter Comm
If starter communication is lost for 10 seconds while the circuit is in a state other than Off or there is a start request, then the Starter Fault alarm will be triggered. Without communication, the fault code cannot be read from the starter so the code 82 will be automatically logged with the alarm.
Condenser Fan Control
Condenser fan control from the MicroTech II controller is used only for air-cooled condenser operation. Head pressure control, as part of the condenser, can be used instead.
WGS 130A to 190A OM WGS-5
OM WGS-5
Remote evaporative condensers require their own self-contained, on-board, head pressure controls. See page 51.
Fan Stages
There are up to 6 stages of Fantrol available. See the table below:
Table 22, Fantrol Staging
Fantrol Stage Fans On
1 1
2 1,2
3 1,2,3
4 1,2,3,4
5 1,2,4,5,6
6 1,2,3,4,5,6
Staging Up
The controller looks at high the discharge pressure is and how quickly it is rising by accumulating “points” in a collection bin called the “Stage Up Accumulator”.
There are four Stage Up deadbands that apply to the Fantrol stages. Stages one through three use their respective deadbands. Stage four to six share the fourth Stage Up dead band.
When the saturated condenser temperature is above the Target + the active deadband, a
Stage Up Error is accumulated.
Stage Up Error Step = Saturated Condenser Refrigerant temperature – (Target + Stage Up dead band). If the condensing temperature is high (rising quickly) relative to the Target plus the dead band, multiple Stage Up Error Steps will be accumulated. This will start a fan sooner than if the temperature is rising slowly.
The Stage Up Error Step is added to Stage Up Accumulator once every Stage Up Error
Delay seconds. When the Stage Up Error Accumulator is greater than the Stage Up Error
Setpoint, another stage is added.
When a stage up occurs or the saturated condenser temperature falls back within the Stage
Up deadband, the Stage Up Accumulator is reset to zero.
Forced Fan Stage At Start
Fans may be started simultaneously with the compressor based on outdoor ambient temperature. When the compressor starts, a Fantrol stage is forced based on the following table. Since this logic applies only to Fantrol fans, the VFD fan is not affected.
Table 23, Forced Fan Staging
> 75 o F
OAT
> 90 o F
> 105 o F
Fantrol Stage At Start
Forced Fantrol 1 SP
Forced Fantrol 2 SP
Forced Fantrol 3 SP
Staging Down
There are four Stage Down dead bands. Stages one through three use their respective deadbands. Stages four to eight share the fourth Stage Down deadband.
The Stage Down process is similar to the Stage Up except in reverse.
When the saturated condenser refrigerant temperature is below the Target – the active deadband, a Stage Down error is accumulated.
Stage Down Error Step = (Target - Stage Down dead band) - Saturated Condenser
Refrigerant temperature.
WGS 130A to 190A 67
The Stage Down Error Step is added to Stage Down Accumulator once every Stage Down
Error Delay seconds. When the Stage Down Error Accumulator is greater than the Stage
Down Error Setpoint, another stage of condenser fans turned off.
When a stage down occurs or the saturated temperature rises back within the Stage Down deadband, the Stage Down Error Accumulator is reset to zero. The accumulator is also held at zero after startup until either the outside ambient temperature is less than or equal to 75 F, or the saturated condenser temperature is greater than the condenser target less the active stage down deadband.
Condenser Fan VFD
Fan VFD operation is available for use with remote condenser units.
For units configured with remote condensers, there is an option to enable fan VFD operation.
Fan VFD speed and target are displayed.
Fan VFD minimum speed and maximum speed set points are available.
An input for fan VFD fault was added at digital input 4 on each circuit controller. VFD faults are logged in the event log, and notification sent on BAS interface.
Fan VFD speed is sent on BAS interface.
Digital Output Control
Each digital output is controlled according to the following rules. All outputs are initialized to OFF at power on.
Alarm – (Terminals J12 – NO1)
This output is turned ON when any Equipment Protection ALARM occurs. It is turned OFF when all alarms have been cleared.
Evaporator Pump – (Terminals J12 – NO2)
An Evaporator Water Pump output is ON if the Evap State is set to START or RUN.
Fan #1 to #8 (Air-Cooled Condensers)
[Water Cooled = N] - Condenser Fans Staging is based on condenser pressure as selected by
Fan Stage On & Off setpoints. Fans 1, 3, 5 and 7 are for circuit 1, and fans 2, 4, 6, and 8 are for circuit 2. Fans 1 and 2 start with the first compressor on the respective circuit when the ambient temperature is greater than 75 F. Below 75 F, these fans start when the condenser pressure gets up to the stage on setpoint.
68 WGS 130A to 190A OM WGS-5
OM WGS-5
Using the Controller
4x20 Display & Keypad
Layout
The 4-line by 20-character/line, liquid crystal display and 6-key keypad for both of the circuit controller and the unit controller is shown below.
Figure 10, Display (in MENU mode) and Keypad Layout
Left Arrow Key and
Red Alarm Light
MENU Key
Air Conditioning
<
<
<
ALARM
VIEW
SET
Key-to-Screen
ARROW Keys (4)
ENTER Key and Green
Compressor Run Light
Note that each ARROW key has a pathway to a line in the display. Pressing an ARROW key will activate the associated line when in the MENU mode. There is no display line associated with the Down Arrow.
Arrow Keys
The four arrow keys (UP, DOWN, LEFT, RIGHT) have three modes of use.
1.
Scroll between data screens as indicated by the arrows (default mode).
2.
Select a specific data screen in a hierarchical fashion using dynamic labels on the right side of the display (this mode is entered by pressing the MENU key).
3.
Change field values in edit mode according to the following table:
LEFT Default (D)
RIGHT Cancel (C)
UP Increment (+)
DOWN Decrement (-)
These four edit functions are indicated by one-character abbreviations on the right side of the display (this mode is entered by pressing the ENTER key).
Getting Started, Navigating -
Press the MENU key to get started. The navigating procedures are the same for both the unit controller and the circuit controller
.
MENU Key
The MENU key is used to switch between the MENU mode as shown in Figure 10 and the
SCROLL mode as shown in Figure 11. The MENU mode is basically a shortcut to specific groups of menus used for checking ALARMS, for VIEWING information, or to SET
WGS 130A to 190A 69
70 setpoint values. The SCROLL mode allows the user to move about the matrix (from one menu to another, one at a time) by using the four ARROW keys.
When in the MENU mode (as shown in Figure 10), pressing the LEFT ARROW key will select the ALARM menus, the RIGHT ARROW key will select the VIEW menus and the
UP key the SET menus. The controller will go the next lower menu in the hierarchy, and then other menus can be accessed by using the ARROW keys. Pressing the MENU key from any menu screen will automatically return to the MENU mode as shown in Figure 10.
Another way to navigate through the menus is to press the MENU key when in the MENU mode (as above). This will switch the controller to the SCROLL mode.
The controller will automatically go to the first screen as shown below (the upper-left menu on the menu matrix shown on pages 72 and 87. From there, the four ARROW keys can be used to scroll up, down, or across to any other menu.
Figure 11, Display in the Shortcut (SCROLL) Mode and Keypad Layout
Red light for fault indication
MENU Key
Air Conditioning
VIEW UNIT STATUS
Unit = COOL
Compr. #1/#2=OFF/OFF
Evap Pump = RUN
ARROW Keys (4) ENTER Key + Green light for comp. On
ENTER Key
Pressing the ENTER key changes the function of the ARROW keys to the editing function as shown below: setting.
UP Increment, increases the value of the setting
These four edit functions are indicated by one-character abbreviation on the right side of the display (this mode is entered by pressing the ENTER key).
Changing Setpoints
Most menus containing setpoint values have several different setpoints shown on one menu.
When in a setpoint menu, the ENTER key is used to proceed from the top line to the second line and on downward. The cursor will blink at the entry point for making a change. The
ARROW keys (now in the edit mode) are used to change the setpoint as described above.
When the change has been made, press the ENTER key to enter it. Nothing is changed until the ENTER key is pressed.
For example, to change the chilled water setpoint:
1.
Press MENU key to go to the MENU mode.
2.
Press SET (the UP Key) to go to the setpoint menus.
3.
Press UNIT SPs (the Right key) to go to setpoints associated with unit operation.
WGS 130A to 190A OM WGS-5
OM WGS-5
4.
Press the DOWN key to scroll down through the setpoint menus to the third menu which contains Evap LWT=XX.X
F.
5.
Press the ENTER key to move the cursor down from the top line to the second line in order to make the change.
6.
Use the ARROW keys (now in the edit mode as shown above) to change the setting.
7.
When the desired value is achieved, press ENTER to enter it and also move the cursor down.
At this point, the following actions can be taken:
1.
Change another setpoint in this menu by scrolling to it with the ENTER key.
2.
Using the ENTER key, scroll to the first line in the menu. From there, the ARROW keys can be used to scroll to different menus.
Security
All setpoints on the unit controller, as well as the circuit controllers, are protected using passwords. Two four-digit passwords provide OPERATOR and MANAGER levels of access to changeable parameters.
Entering Passwords
Passwords can be entered using the ENTER PASSWORD screen on the unit controller, which is the last screen in the Unit SPs column. The password is entered by pressing the
ENTER key, scrolling to the correct value with the UP and DOWN arrow keys, and pressing
ENTER again. The longer a key is held down, the faster it will increment. The entered password is not shown after the enter key is pressed. The operator password is 100.
Once the correct password has been entered, the ENTER PASSWORD screen indicates which password is active (none, operator, technician, or manager). If the wrong password is entered, a temporary message will appear so stating. If no valid password is active, the active password level displays “none”.
Entering an incorrect password while a password is active will render that password inactive. Entering a valid password that is not the same as the active password will result in the active password level being changed to reflect the new password level.
Editing Setpoints
After a valid password has been entered at the unit controller, setpoints on the circuit controllers and the unit controller can be changed. If the operator attempts to edit a setpoint for which the necessary password level is not active, no action will be taken.
Once a password has been entered, it remains valid for 60 minutes after the last key-press on the unit controller.
Clearing Alarms
Alarms are only shown on the unit controller and are cleared at the unit controller. No password is required.
To clear an alarm, go to the unit controller Alarm Log. Scroll down to the last alarm listed.
The screen will note “No More Alarms”. Press and hold ENTER for several seconds until the circuit controllers get a clear signal. If there are no active alarms, the red Alarm light will be off and alarms status will clear from the unit and circuit controllers.
WGS 130A to 190A 71
Menu Descriptions
Unit Controller
Various menus are shown in the controller display. Each menu screen shows specific information. In some cases menus are used only to view the status of the unit, in some cases they are used for checking and clearing alarms , and in some case they are used to set the setpoint values that can be changed.
The menus are arranged in a matrix of screens across a top horizontal row. Some of these top-level screens have sub-screens located under them. The content of each screen and its location in the matrix are shown in Unit Controller Menu Matrix. Each menu screen’s detailed description begins on page 73.
The ARROW keys on the controller are used to navigate through the menus. The keys are also used to change numerical setpoint values contained in certain menus.
As an alternate to selecting screens with the menu function, it is possible to scroll through all of them with the 4 arrow keys. For this use, the screens are arranged logically in a matrix as shown below.
Shortcut Menus
These menus are accessed by pressing the Menu button at any time. The hierarchical structure of the shortcut menus is shown below.
Table 24, Unit Controller Shortcut Menus
LEVEL 1 LEVEL 2
VIEW
UNIT
CIR STATUS
REFRIGERANT
LEVEL 3
STATUS
TEMP
CIR 1
CIR 2
CIR 1
CIR 2
ALARM
SET
TOWER
UNIT SPs
COMPRESSOR SPs
ALARM LIMITS
TOWER SPs
VIEW TOWER (1-2)/
SET UNIT SPs (1-15)
SET COMP SPs (1-4)
SET ALARM LIMITS (1-4)
SET TOWER SPs (1-8)
VIEW UNIT STATUS (1-4)
VIEW UNIT TEMP (1-3)
VIEW CIR 1 STATUS (1-5)
VIEW CIR 2 STATUS (1-5)
VIEW REFR CIR 1 (1-5)
VIEW REFR CIR 2 (1-5)
72 WGS 130A to 190A OM WGS-5
OM WGS-5
Unit Controller Menu Matrix
When scrolling through the screens, the following matrix is used:
VIEW
UNIT
STATUS
(1)
VIEW
UNIT
STATUS
(2)
VIEW
UNIT
TEMP
(1)
VIEW
UNIT
TEMP
(2)
VIEW
CIR 1
(1)
VIEW
CIR 1
(2)
“VIEW” SCREENS
VIEW
CIR 2
(1)
VIEW
CIR 2
(2)
VIEW
REFRG
CIR 1
(1)
VIEW
REFRG
CIR 1
(2)
VIEW
REFRG
CIR 2
(1)
VIEW
REFRG
CIR 2
(2)
VIEW
FANS
VIEW
TOWER
(1)
VIEW
TOWER
(2)
VIEW
UNIT
STATUS
(3)
VIEW
UNIT
STATUS
(4)
VIEW
UNIT
TEMP
(3)
VIEW
CIR 1
(3)
VIEW
CIR 1
(4)
VIEW
CIR 2
(3)
VIEW
CIR 2
(4)
VIEW
REFRG
CIR 1
(3)
VIEW
REFRG
CIR 1
(4)
VIEW
REFRG
CIR 2
(3)
VIEW
REFRG
CIR 2
(4)
VIEW
CIR 1
(5)
VIEW
CIR 2
(5)
VIEW
REFRG
CIR 1
(5)
VIEW
REFRG
CIR 2
(5)
“ALARM”
SCREENS
“SET SCREENS”
EVENT
LOG
(1)
EVENT
LOG
(25)
.
.
.
.
.
.
.
.
ALARM
LOG
(1)
ALARM
ACTIVE
(1)
SET UNIT
SPs
(1)
SET COMP
SPs
(1)
SET ALARM
LMTS
(1)
CONTINUED
BELOW
SET
TOWER
SPs (1)
TEST
TEST
UNIT
CONTINUATION
FROM ABOVE .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
SET COMP
SPs
(2)
SET COMP
SPs
(3)
SET ALARM
LMTS
(2)
SET ALARM
LMTS
(3)
.
.
.
.
.
.
.
.
ALARM
LOG
(25)
ALARM
ACTIVE
(n)
SET UNIT
SPs
(15)
SET COMP
SPs
(4)
SET ALARM
LMTS
(4)
SET
TOWER
SPs (8)
Selection can be made within the matrix by using the LEFT/RIGHT keys to move between columns and the UP/DOWN keys to move between rows.
Unit Controller Menu Descriptions
This section contains information on each screen of the unit controller. The menu screens are in order of the matrix above, going from left to right and also down when there are submenus. Many menus are self-explanatory. A Setpoint menu allows selection of whether the unit has a water-cooled condenser, Water-Cooled = Y (Yes) or a remote condenser, Water-
Cooled = N (No). This selection will alter some menus as appropriate to the type of condenser.
Screen Definitions – MENU
Top level menu:
< ALARM
< VIEW
< SET
<
WGS 130A to 190A 73
74
ALARM menu:
ALARM < ACTIVE
< LOG
<
<
VIEW menu:
Water-cooled Air-cooled
VIEW < UNIT VIEW < UNIT
< CIR STATUS < CIR STATUS
<REFRIGERANT <REFRIGERANT
< TOWER < FANS
VIEW UNIT menu:
VIEW < STATUS
UNIT < TEMP
<
<
VIEW CIRCUIT STATUS menu:
VIEW CIR < CIR 1
STATUS < CIR 2
<
<
VIEW REFRIGERANT menu:
VIEW REFR < CIR 1
< CIR 2
<
<
SET menu:
Water-cooled Air-cooled
SET < ALARM LIMITS SET < ALARM LIMITS
< UNIT SPs < UNIT SPs
< COMPRESSOR SPs < COMPRESSOR SPs
< TOWER SPs
Screen Definitions – VIEW
View Unit Status
Water-cooled: Air-cooled:
VIEW UNIT STATUS (1) VIEW UNIT STATUS (1)
{Unit Status} {Unit Status}
Evap Pump= {state} Evap Pump= {state}
Cond Pump= {state}
WGS 130A to 190A OM WGS-5
OM WGS-5
Unit Status will display one of the following:
Off:Unit Off:Keypad
Disable Off:Unit Mode
Auto:Wait for load Auto:Cond Recirc Auto:Evap Recirc
Auto:Wait Cond Flow Auto:Wait Evap Flow Auto:Pumpdown
Pump states include Off, Start, and Run. The condenser pump state is visible only for water-cooled operation.
VIEW UNIT STATUS (2)
Softload Limit=XXX.X
Demand Limit= XXX.X
Network Limit= XXX.X
VIEW UNIT STATUS (3)
Unit Capacity=XXX.X%
Ice Delay= XXh XXm
Ice Delay will be visible only when unit mode is ice. It prevents the unit from undesirable starts before the next day’s ice-making cycle.
VIEW UNIT STATUS (4)
1 2 3 4 5 6 8
D.O. X X X X X X X
D.I. X X X X X
The digital input and output status will show either a “0” or a “1” designating Off and On states respectively.
View Unit Temperature
VIEW UNIT TEMP (1)
Evap LWT= XXX.X
Evap EWT= XXX.X
o o
Active SP= XXX.X
F
F
o
F
VIEW UNIT TEMP (2)
LWT Pulldn= 0.0
o
F/m
Evap Delta T= XX.X
Water-cooled: Air-cooled:
VIEW UNIT TEMP (3) VIEW UNIT TEMP (3)
Cond EWT= XXX.X
o
Cond LWT= XXX.X
o
F
F
OAT= XXX.X
o
F
WGS 130A to 190A 75
76
View Circuit Status
In the following VIEW CIR screens, the N field indicates which circuit (#1, #2) is being viewed. Certain screens located in the circuit controller are also displayed here on the unit controller for convenience.
VIEW CIR N STATUS(1)
{Circuit Status}
Slide Pos= 000.0%
Slide Target=000.0%
Circuit Status will display one of the following:
Off:Keypad Disable Off:Pumpdown Switch
Off:Test EXV
Run:Normal
Run:High LWT Limit
Off:pLAN failure
Run:LWT PullDn Limit
Run:Evap Press Low
VIEW CIR N STATUS(2)
Hours = XXXXX
Starts = XXXXX
VIEW CIR STATUS (3)
Current (amps)
L1 L2 L3 Avg
XXX XXX XXX XXX
VIEW CIR STATUS (4)
Voltage
L1-2 L2-3 L3-1 Avg
XXX XXX XXX XXX
VIEW CIR STATUS (5)
PF= 0.XX %RLA=XXX.X
KW= XXX
KVA= XXX
Off:Alarm
Run:Unit Cap Limit
Run:Lift Press High
View Refrigerant
In the following VIEW REFR screens, the N field indicates which circuit (#1, #2) is being viewed.
VIEW REFR CIR N (1)
Evap Press=XXX.X psi
Cond Press=XXX.X psi
WGS 130A to 190A OM WGS-5
OM WGS-5
VIEW REFRG CIR N (2)
Sat Evap= XXX.X
F
Sat Cond= XXX.X
F
VIEW REFRG CIR N (3)
Suct Temp = XXX.X
F
Disc Temp = XXX.X
F
VIEW REFRG CIR N (4)
Suct SH= XXX.X
F
Disc SH= XXX.X
F
VIEW REFRG CIR N (5)
Evap Approach=XX.X
F
Cond Approach=XX.X
F
EXV position = XXXX
View Fans
This screen is only viewable when unit is configured for air-cooled.
VIEW FANS
Fans On, Cir 1= X
Fans On, Cir 2= X
View Tower
These screens is only viewable when unit is configured for water-cooled.
VIEW TOWER (1)
Fans On= X of X
Cond EWT= XXX.X
F
Set Point=XXX
F
VIEW TOWER (2)
Bypass Valve=XXX.X%
VFD Speed= XXX.X%
WGS 130A to 190A 77
78
Screen Definitions – ALARM
ALARM LOG: XX
{Alarm Description} hh:mm mm/dd/yy
{Parameters}
The most recent 25 alarms, either shutdown or limit, are shown in this menu and subsequent menus located under it. The last alarm is shown first. ARROW DOWN from this menu will go to the next-to-last alarm, ARROW DOWN again will go to the second from last, and so on through the last 25 occurrences. The screens are numbered (1), (2), (3), etc.
Alarm Description will indicate which alarm occurred. If the alarm is a circuit alarm, then the circuit for which the alarm occurred will also be indicated.
Parameters at the time of the alarm are shown on the bottom line of the screen one at a time.
These are scrolled through by pressing the edit key and using the up and down arrows to scroll through the list. Parameters include:
Starter Fault Code (will show “00” when the alarm logged is not a starter fault)
EVENT LOG: XX
{Event Description} hh:mm mm/dd/yy
*** ALARM ***
hh:mm mm/dd
{Alarm Description}
NO MORE ALARMS
Press ENTER to clear
If the unit is off on a shutdown alarm or running, but in a limit alarm condition, the cause and date will appear in the above screen. If there is a simultaneous occurrence of more than one alarm, the others will appear in additional screens below the first one, accessed by the
DOWN ARROW. Either type alarm will light a red light in back of the LEFT-ARROW
KEY. The light will go out when the fault is cleared. To clear the fault, scroll down to the last screen and press ENTER. If other faults have appeared, they will all be cleared at the same time.
WGS 130A to 190A OM WGS-5
OM WGS-5
Screen Definitions – SET
Unit Set Points
SET UNIT SPs (1)
Enable=On
Mode= COOL
Source = KEYPAD
Unit Enable settings can be OFF and ON as determined from the Unit Enable setpoint.
Unit Enable is an external signal or a keypad setting that keeps the unit off when the setting is OFF and allows it to run if there is a call for cooling when the setting is ON. The source for the signal is selected in the 4 th line and can be:
1.
KEYPAD, in which case the selection is made in line 2 and would be normally selected as ON. This is the normal setting when no external signals are controlling the unit.
2.
SWITCHES, in which an external switch is wired across terminals #60 and #66. (See wiring diagram page 8 or 9.)
3.
NETWORK, used with BAS signal, which is wired to the three communication ports.
Unit Mode settings can be
1.
COOL, normal setting used with chilled water air-condition applications.
2.
COOL w/GLYCOL, used with low temperature, glycol applications. It allows a lower
LWT setpoint to be used.
3.
ICE w/GLYCOL, used with ice storage systems, allows changing from chilled glycol operation to lower temperature ICE operation. In ICE, the unit runs at full load until the
ICE setpoint is reached, at which time the unit shuts off. A three-position switch wired to terminals #60 and #68 initiates the change from glycol cooling to making ice. (See wiring diagrams on page 8 or 9.)
Unit Mode settings can be COOL COOLw/Glycol, or ICEw/Glycol, as determined from the
Unit Mode setpoint.
Source settings can be KEYPAD, SWITCHES, or NETWORK as determined from the
Mode Source setpoint.
SET UNIT SPs (2)
Available Modes
= COOL
Select w/Unit Off
SET UNIT SPs (3)
Cool LWT = XX.X
F
Ice LWT = XX.X
F
StartDelta=XX.X
F
SET UNIT SPs (4)
StopDelta= X.X
F
Stg Up Delta= X.X
F
Stg Down Delta=X.X
F
WGS 130A to 190A 79
80
SET UNIT SPs (5)
Max Pulldn=X.X
F/min
EvapRecTimer=XXX sec
Evap Pump= #1 Only
Water-cooled: Air-cooled:
SET UNIT SPs (6) SET UNIT SPs (6)
Watercooled= Yes Watercooled= No
CondRecTimer=XXX sec
Cond Pump= #1 Only
SET UNIT SPs (7)
Reset Type= none
Max Reset = XX.X
F
StrtResetDT= XX.X
F
SET UNIT SPs (8)
Soft Load= Off
Begin Capacity= XXX%
SoftLoadRamp= XXmin
Water-cooled: Air-cooled:
SET UNIT SPs (9) SET UNIT SPs (9)
Demand limit= Off Demand limit= Off
LowOAT Operation=No
Low Amb Lock= XX.X
F
SET UNIT SPs (10)
Ice Time Delay=XXhrs
Clear Ice Timer=No
SET UNIT SPs (11)
Sensor Offset
Evap LWT= XX.X
F
Evap EWT= XX.X
F
WGS 130A to 190A OM WGS-5
OM WGS-5
SET UNIT SPs (12) SET UNIT SPs (12)
Sensor Offset
Cond EWT= XX.X
Cond LWT= XX.X
F
F
Sensor Offset
OAT= XX.X
F
SET UNIT SPs (13)
CLOCK
mm/dd/yyyy
hh:mm day
SET UNIT SPs (14)
Units =
F/psi
Lang = ENGLISH
After entering a valid manager password, selecting F/psi will provide IP units; selecting
C/kPa will provide SI units.
SET UNIT SPs (15)
Protocol=
Ident Number=
Baud Rate=
SET UNIT SPs (16)
Enter Password:0000
Active Password
Level:none
Compressor Set Points
SET COMP SPs (1)
Seq # Comp 1= X
Seq # Comp 2= X
SET COMP SPs (2)
Max Comps On = x
Start-Start =XX min
Stop-Start =XX min
This menu sets the anti-recycle timers. Stop-Start is the time required before starting a compressor after it has stopped . Start-Start is the time required before starting a compressor after the last time it has started . It is recommended that the default values of 5 minutes and
15 minutes not be changed. Max Comps On can be 1 or 2 with 2 being the default.
WGS 130A to 190A 81
82
SET COMP SPs (3)
Pumpdown
Pressure= XX.X psi
Time Limit= XXX sec
SET COMP SPs (4)
Light Load Stage
Down Point=XX% slide
Stg Up Delay= XX min
SET COMP SPs (5)
Discharge Temp
Sensor Type=PT1000
Alarm Set Points
SET ALARM LIMITS (1)
Low Evap Pressure
Hold=XX.Xpsi
Unload=XX.Xpsi
The LowEvPrHold (Low Evaporator Pressure Hold) and LowEvPrUnld (Low Evaporator
Pressure Unload) have the same default value of 59 psi. If two compressors are running, the
LowEvPrUnld is in effect and the lag compressor will be shut off to unload the unit. If one compressor is running, the LowEvPrHold is in effect and the lag compressor is prevented from starting, thereby holding the unit capacity.
The last action to take place is the shutoff of all compressors running when the
LowEvPrStop setting is reached (default is 58 psi). Reducing these time intervals will increase detrimental compressor cycling. It is recommended that these settings not be changed.
SET ALARM LIMITS (2)
LowOilDelay= XXX sec
HighOilDpDel=XXX sec
Water-cooled: Air-cooled
SET ALARM LIMITS (3) SET ALARM LIMITS (3
High Disc Temp=XXX
F High Disc Temp=XXX
F
HighLift Delay=XXsec HighLift Delay=XXsec
LowOATStartTmr=XXsec
:
SET ALARM LIMITS (4)
Evap Freeze= XX.X
F
Evap Flow Proof=XXXs
Recirc Timeout=xxmin
Evap Freeze (the unit freeze protection shutdown) is actually a stop alarm and shuts off the unit when the LWT reaches 36 F. It is cleared by going to the CLEAR ALARM menu in the ACTIVE ALARM hierarchy.
WGS 130A to 190A OM WGS-5
OM WGS-5
Evap/Cond FlowProof is the flow switch interlock. Closing the flow switch, and therefore proving the existence of chilled water flow, resets this trip. It is recommended that these settings not be changed.
SET ALARM LIMITS (5)
Cond Freeze= XX.X
F
Cond Flow Proof=XXXs
Set Alarm Limits (5) is accessible only if unit is configured as water-cooled.
Tower Setpoints
Tower set points are only available when the unit is configured as water-cooled.
The MicroTech II controller is capable of controlling cooling tower water temperature on chillers using water-cooled condensers. Output wiring connection points are shown on the field wiring diagrams beginning on page 8.
[Water Cooled = Y] - Condenser Pump on with first Compressor on. Tower fan control is active when the Tower Control setpoint is set to Temperature and the condenser pump is in the RUN state. Staging is based on Entering Condenser Water Temperature (ECWT).
Operation depends on the following parameters.
Condenser pump state
ECWT OR Lift pressure
Stage up and stage down timer values
Tower setpoints (Tower Control, Tower Stages, Stage Up Time, Stage Down Time,
Stage Differential, Stage #1 ON, Stage #2 ON, Stage Down @, Stage Up @)
When the condenser pump starts, the stage up timer shall start. The first stage shall turn ON when the following conditions are met:
The stage up timer completes
The ECWT is > Stage #1 ON setpoint
Bypass valve position is > the Stage Up @ setpoint (only if Valve/VFD Control setpoint
= Valve Stage)
Additional stages can turn on (up to the number specified by the Tower Stages setpoint) when above conditions are met for the next stage plus the following condition:
VFD Speed is > the Stage Up @ setpoint (only if Valve/VFD Control setpoint = VFD
Stage OR Valve SP/VFD Stage)
Down staging shall occur when the following conditions are met:
The stage down timer completes
The ECWT is < Stage #X ON (Temp) setpoint – Stage Differential (Temp) setpoint point
Bypass valve position is < the Stage Down @ setpoint (only if Valve/VFD Control setpoint = Valve Stage)
VFD Speed is < the Stage Down @ setpoint (only if Valve/VFD Control setpoint =
VFD Stage OR Valve SP/VFD Stage)
Each stage-up or stage-down event shall restart both the stage-up and stage-down timers.
Only one fan output shall be switched at a time (except that all outputs switch OFF when the condenser pump state equals OFF).
WGS 130A to 190A 83
84
SET TOWER SPs (1)
Tower Control=None
Tower Stages= 2
When Tower Control is None, the control of condenser water temperature is not by the
MicroTech II controller and assumed to be furnished elsewhere.
Tower Stages is the number of tower fans to be staged by the controller, choices are 0, 1, or
2. "0" indicates control will be by a bypass valve or variable speed pump controlled by the
MicroTech II controller.
StageUP/DN imposes a time delay between fan stages when turning on or turning off.
SET TOWER SPs (2)
Stage 1 On =XXX
Stage 2 On =XXX
StageDiff = XX.X
SET TOWER SPs (3)
Stage Up Tmr= XX min
Stage Dn Tmr= XX min
Stage Up/Dn=XXX/XXX%
StageDiff is the number of degrees below the Stage ON that will turn off the tower fans.
For example, if Stage ON #1 is 70 F and StageDiff is 5 F, tower fan #1 will stage off when the ECWT drops to 65 F and stage the fan on when the ECWT rises to 70 F. The same is true for fan #2.
Stage Up timer is the number of minutes that must elapse between the condenser pump starting (it starts with the unit) and fan #1 starting or the time between fan #1 starting and fan #2 starting.
StageDown is the elapsed time between staging down the fan motors.
SET TOWER SPs (4)
Valve/VFD Control=
None
Valve Type=NC to twr
Valve/VFD Control settings are None, Valve Setpoint, Valve Stage, VFD Stage, or
ValveSP/VFDStage. Default is None which results in no control of the tower from the
MicroTech II controller.
Valve Setpoint, the valve will control (bypass tower) to hold the minimum temperature as established by the Set Tower SPs in screen number 5 shown on the following page.
This mode is operational when the Valve/VFD Control setpoint is set to Valve Setpoint
OR Valve SP/VFD Stage. In this mode the valve output is varied with a proportionalderivative (PD) algorithm (with deadband) in order to maintain the controlled parameter
(CP) at the desired value. The output is always limited between the Valve Control
Range (Min) setpoint and the Valve Control Range (Max) setpoint. A valve increment shall be computed once every 5 seconds according to the following equation. (Error
Gain and Slope Gain are set in menu screen #8.)
WGS 130A to 190A OM WGS-5
OM WGS-5
Increment = [(Error) * (Error Gain setpoint)] + [(Slope) * (Slope Gain setpoint)]
Where: Error = ECWT – Valve Setpoint
Slope = (Present CP) – (Previous CP)
When the Error is > the Valve Deadband setpoint, the valve position analog output (% of full scale) is updated according to the following equation.
New %Position = Old %Position + Increment/10
Valve Stage, controls from the fan stage setpoint in use. It is recommended that the
Valve Setpoint method explained above be used rather than this mode.
This mode is only operational when the Valve/VFD Control setpoint is set to Valve
Stage. In this mode the valve output is controlled as for Valve Setpoint mode (above), except that the active setpoint for the controlled parameter is selected according to the following table.
# Of Fans ON Active Setpoint
1
2
3
4
Stage #1 ON
Stage #2 ON
Stage #3 ON
Stage #4 ON
VFD Stage, ValveSP/VFDStage, When the Valve/VFD Control setpoint is set to None,
Valve Setpoint, OR Valve Stage, this output is set to 0. Otherwise, it will be controlled in a manner identical to Valve Stage Mode (above) except that (1) it shall be kept at zero until the first fan stage is ON, and (2) the following setpoints do not apply.
Valve Control Range (Min)
Valve Control Range (Max)
Valve Type
Valve Type settings are NC (normally closed to tower) or NO (normally open).
These settings establish the operation of a tower bypass valve (must be a 3-way valve).
Initial Valve Position
When the condenser pump is not in the RUN state, the valve output shall be set as a function of entering condenser water temperature (ECWT) per the following graph.
Figure 12, Initial Valve Position
Initial Valve Position
(values are examples only)
Max Position @
Setpoint
(90°F)
Min Position @
Setpoint
(60°F)
Min Start Position
Setpoint (10%)
Max Start Position
Setpoint (90%)
WGS 130A to 190A 85
86
Operation After Start
When the condenser pump is in the RUN state, the valve output shall be controlled in one of two modes as specified by the Valve/VFD Control setpoint. The controlled parameter shall be the condenser entering water temperature. When the desired output signal varies from 0 to 100%, the output voltage shall vary as shown below.
0 to 10 VDC (Valve Type = NC)
10 to 0 VDC (Valve Type = NO)
SET TOWER SPs (5)
Valve SP=XXX
Valve DB=XX.X
Valve SP is the minimum tower water temperature acceptable, default is 65 F.
Valve DB is the dead-band in degrees, default is 2.0
F.
SET TOWER SPs (6)
Valve Start Position
Min= XXX% @XXX
Max= XXX% @XXX
The ValveStart position is the position of the valve when the unit starts. Default for minimum start position is 0%, and 100% for maximum position.
SET TOWER SPs (7)
Valve Control Range
Min= XXX%
Max= XXX%
Defaults are 10% minimum and 90% maximum.
SET TOWER SPs (8)
PD Control Loop
Error Gain=XX
Slope Gain=XX
Defaults are 25 for both error and slope.
Screen Definitions – TEST
TEST UNIT (1)
Alarm Out=Off
Evap Pump 1= Off
Evap Pump 2= Off
TEST UNIT (2)
Cond Pump 1= Off
Cond Pump 1= Off
TEST UNIT (3)
WGS 130A to 190A OM WGS-5
OM WGS-5
Tower Fan 1= Off
Tower Fan 2= Off
TEST UNIT (4)
Tower Bypass= XXX.X
Tower VFD Spd= XXX.X
Circuit Controller
The display on the circuit controller displays information about the circuit that it is controlling. Setpoint availability will be limited to setpoints that are unique to that circuit.
Other set points are changed at the Unit Controller.
Shortcut Menus
Pressing the Menu button at any time accesses these menus. The hierarchical structure of the shortcut menus is shown below.
LEVEL 1
VIEW
SET
LEVEL 2
UNIT
CIR STATUS
REFRIGERANT
FANS
COMPRESSOR SPs
EXV SPs
FAN SPs
SENSOR OFFSETS
LEVEL 3 (No. of Screens)
VIEW UNIT (1-2)
VIEW CIR STATUS (1-9)
VIEW REFRIGERANT (1-7)
VIEW FANS (1-2)
SET COMP SPs (1-4)
SET EXV SPs (1-2)
SET FANS (1-6)
SET SENSOR OFFSET (1-3)
Menu Matrix
When scrolling through the screens, the following matrix is used:
VIEW
UNIT (1)
VIEW
UNIT (2)
VIEW CIR
STATUS
(1)
VIEW CIR
STATUS
(2)
VIEW CIR
STATUS
(3)
VIEW
REFRG
(1)
VIEW
REFRG
(2)
VIEW
REFRG
(3)
VIEW
FANS
(1)
VIEW
FANS
(2)
SET
COMP SPs
(1)
SET
COMP SPs
(2)
SET
COMP SPs
(3)
SET
EXV
SPs (1)
SET
EXV
SPs (2)
SET
FANS
(1)
SET
FANS
(2)
SET
FANS
(3)
SET
SENSOR
OFFSETS
(1)
SET
SENSOR
OFFSETS
(2)
SET
SENSOR
OFFSETS
(3)
-
-
-
-
-
-
-
-
SET
COMP SPs
(4)
-
-
-
-
VIEW CIR
STATUS
(9)
VIEW
REFRG
(7)
SET
STARTER
SPs
(3-8)
SET
FANS
(5)
Screen Definitions – MENU
Top level menu:
< VIEW
< SET
<
<
View menu:
TEST
CIRCUIT
(1)
TEST
CIRCUIT
(2)
TEST
CIRCUIT
(3)
TEST
CIRCUIT
(4)
WGS 130A to 190A 87
88
VIEW < UNIT
< CIR STATUS
<REFRIGERANT
< FANS
Fan data is available only when unit is configured as air-cooled.
Set menu:
SET <COMPRESSOR SPs
< EXV SPs
< FAN SPs
<SENSOR OFFSETS
Fan setpoints are available only when unit is configured as air-cooled.
Screen Definitions – VIEW
View Unit Status
Water cooled: Air cooled:
VIEW UNIT (1) VIEW UNIT (1)
{Unit status} {Unit status}
Evap pump = {State} Evap pump = {State}
Cond pump = {State}
Unit Status will display one of the following:
Off:Unit Off:Keypad
Disable Off:Unit Mode
Auto:Wait for load
Auto:Wait Cond Flow
Pump states include Off, Start, and Run. The condenser pump state is visible only for water-cooled operation.
Auto:Cond Recirc
Auto:Wait Evap Flow
Auto:Evap Recirc
Auto:Pumpdown
VIEW UNIT (2)
Evap LWT= XXX.X
F
Active SP= XX.X
F
LWT pulldn= XX.X
F/m
View Circuit Status
VIEW CIR STATUS (1)
{Circuit Status}
Slide Pos= XXX.X%
Slide Target= XXX.X%
Circuit Status will display one of the following:
Off:Keypad Disable Off:Pumpdown Switch
Off:Test EXV
Run:Normal
Run:High LWT Limit
Off:pLAN failure
Run:LWT PullDn Limit
Run:Evap Press Low
Off:Stage Up Delay
Off:Alarm
Run:Unit Cap Limit
Run:Lift Press High
WGS 130A to 190A OM WGS-5
OM WGS-5
VIEW CIR STATUS (2)
Hours = XXXXX
Starts = XXXXX
KW Hours= XXXXXXX
A KW hours counter has been added to the Circuit control Circuit Status Screen. The KW
Hours field will display up to 9,999,999 kW-Hours.
VIEW CIR STATUS (3)
Current (amps)
L1 L2 L3 Avg
XXX XXX XXX XXX
VIEW CIR STATUS (4)
Voltage
L1-2 L2-3 L3-1 Avg
XXX XXX XXX XXX
VIEW CIR STATUS (5)
PF= 0.XX %RLA=XXX.X
KW= XXX
KVA= XXX
VIEW CIR STATUS (6)
Digital Outputs
1 2 3 4 5 6 7 8 9 10
X X X X X X X X X X
Status will be “0” for OFF and “!” for ON.
VIEW CIR STATUS (7)
Digital Outputs
11 12 13
X X X
VIEW CIR STATUS (8)
Analog Outputs
(volts X 100)
1=XXXX 3=XXXX
VIEW CIR STATUS (9)
Digital Inputs
1 3 4 5 6 9
X X X X X X
View Refrigerant
VIEW REFRIGERANT (1)
Evap Press=XXX.X psi
Cond Press=XXX.X psi
VIEW REFRIGERANT (2)
WGS 130A to 190A 89
90
Sat Evap = XXX.X
F
Sat Cond = XXX.X
F
VIEW REFRIGERANT (3)
Suct Temp = XXX.X
F
Disc Temp = XXX.X
F
VIEW REFRIGERANT (4)
Suct SH= XXX.X
F
Disc SH= XXX.X
F
VIEW REFRIGERANT (5)
Evap Approach=XX.X
F
Cond Approach=XX.X
F
VIEW REFRIGERANT (6)
MaxCondSatT= XXX.X
F
EXV Ctrl=Superheat
SH target= XX.X
F
VIEW REFRIGERANT (7)
EXV Steps= XXXX
EXV ctrl range:
XXXX – XXXX steps
View Fans
View Fans screens are only available when the unit is configured as air-cooled.
VIEW FANS (1)
Fans Running= X
Stage Up Err= XXX
Stage Dn Err= XXX
VIEW FANS (2)
Target Sat T=XXX.X
F
VFD Speed=XXX.X%
VFD Target=XX.X
F
Screen Definitions – SET
Compressor Set Points
SET COMP SPs (1)
WGS 130A to 190A OM WGS-5
OM WGS-5
Clear Cycle Tmr= no
Comp Size= XXX
Max Slide= XXX.X %
SET COMP SPs (2)
Circuit Mode=Enable
Slide Target= XXX.X%
Slide Control=auto
SET STARTER SPs (3)
Motor FLA= XXX amps
Motor RLA= XXX amps
The starter set points are stored in permanent memory on the starter and the Circuit control set points will be reset to the values stored on starter when the Circuit control is powered up.
When the Circuit control is powered up the starter set points MUST be adjusted from the
Circuit control.
Ground Fault Enable, Ground Fault Trip Level, Rated RMS Voltage and CT Ratio set points are NOT adjustable while the compressor is running.
SET STARTER SPs (4)
Ground Fault=No
GF Trip Level= XXX%
EXV Set Points
SET EXV SPs (1)
Manual EXV Pos= XXXX
EXV Control=auto
Service Pumpdown=No
SET EXV SPs (2)
Preopen Timer=XXXsec
Sensor Offsets
SET SENSOR OFFSET(1)
Evap Press= XX.X psi
Cond Press= XX.X psi
SET SENSOR OFFSET(2)
Suct Temp= X.X
F
Disch Temp= X.X
F
SET SENSOR OFFSET(3)
Slide min pos= XX%
Slide max pos= XX%
WGS 130A to 190A 91
92
Slide Pos= XXX.X%
Fan Set Points
SET FAN SPs (1)
Number of fans = X
Fan VFD = Enable
SET FAN SPs (2)
Stg On Deadband(
F)
Stg1=XX.X Stg2=XX.X
Stg3=XX.X Stg4=XX.X
SET FAN SPs (3)
Stg Off Deadband(
F)
Stg2=XX.X Stg3=XX.X
Stg4=XX.X Stg5=XX.X
SET FAN SPs (4)
VFD Min Speed= XX%
VFD Min Speed= XXX%
SET FAN SPs (5)
Cond Sat Temp Target
Max= XXX.X
F
Min= XXX.X
F
SET FAN SPs (6)
# Fans On At Startup
>75
F >90
F >105
F
X X X
Screen Definitions – TEST
TEST CIRCUIT (1)
Slide
Direction = Unload
Pulse = Off
TEST CIRCUIT (2)
Oil Heater= Off
EXV Closed= Off
WGS 130A to 190A OM WGS-5
OM WGS-5
TEST CIRCUIT (3)
EXV Position=XXXX
TEST CIRCUIT (4)
Condenser Fans:
1=Off 2=Off 3=Off
4=Off 5=Off 6=Off
Editing Review
Editing is be accomplished by pressing the ENTER key until the desired field is selected.
This field shall be indicated by a blinking cursor under it. The arrow keys shall then operate as defined below.
CANCEL (Right) ............. Reset the current field to the value it had when editing began.
DEFAULT (Left).............. Set value to original factory setting.
INCREMENT (Up).......... Increase the value or select the next item in a list.
DECREMENT (Down).... Decrease the value or select the previous item in a list.
During edit mode, the display shows a two-character wide menu pane on the right as shown below.
SET UNIT SPs (X) <D
(data) <C
(data) <+
(data) <-
Additional fields can be edited by pressing the ENTER key until the desired field is selected. When the last field is selected, pressing the ENTER key switches the display out of “edit” mode and returns the arrow keys to “scroll” mode.
Alarms
When an alarm occurs, the alarm type, limit value (if any), date, and time are stored in the active alarm buffer corresponding to that alarm (viewed on the Alarm Active screens) and also in the alarm history buffer (viewed on the Alarm Log screens). The active alarm buffers hold a record of the last occurrence of each alarm and whether or not it has been cleared. The alarm can be cleared by pressing the Edit key. A separate buffer is available for each alarm (High Cond Pressure, Evaporator Freeze Protect, etc.). The alarm history buffer holds a chronological account of the last 25 alarms of any type.
Security
Two four-digit passwords provide OPERATOR and MANAGER levels of access to changeable parameters. Either password can be entered using the ENTER PASSWORD screen which can be accessed either through the SET OTHER menu or by simply pressing the ENTER key while on one of the SET screens. The password can then be entered by pressing the ENTER key, scrolling to the correct value with the UP and DOWN arrow keys, and pressing ENTER again. Once the correct password has been entered, the previously selected screen will reappear. Once a password has been entered, it will remain valid for 15 minutes after the last key-press.
WGS 130A to 190A 93
BAS Interface
The MicroTech II controller is equipped with the Protocol Selectability feature, an exclusive McQuay feature that provides easy unit interface with a building automation system (BAS). If the unit will be tied into a BAS, the controller should have been purchased with the correct factory-installed interface module. The modules can also be added in the field during or after installation.
If an interface module was ordered, one of the following BAS interface installation manuals was shipped with the unit. Contact your local McQuay sales office for a replacement, if necessary or download from www.mcquay.com.
IM 735, L ON W ORKS
Communication Module Installation
IM 736, BACnet Communication Module Installation
IM 743, Modbus Communication Module Installation
ED 15062-0, MicroTech II Chiller Protocol Information – BACnet and L ON W ORKS
ED 15063-0, MicroTech II Chiller Unit Controller Protocol Information – Modbus
Unit Controller Setting
Settings are made in the unit controller. Set Unit Setpoints, Menu 1 is set to Source =
Network. The specific protocol being used is set in Set Unit Setpoints, menu 15.
Connection to Chiller
Connection to the chiller for all BAS protocols will be at the unit controller. An interface card will have to be installed in the unit controller depending on the protocol being used.
NOTE:
In this revision (D), the starter electric data in the table below is now available to the
Building Automation System at the unit control supervisor port:
Starter Parameter
Compressor Average Amps
Supervisor Type
Analog Output
Index Number
26
Compressor Kilowatts
Compressor Average Volts
Analog Output
Analog Output
27
29
94 WGS 130A to 190A OM WGS-5
Unit Troubleshooting Chart
!
WARNING
Troubleshooting can cause severe personal injury or death. Troubleshooting must be performed by trained, experienced technicians only.
PROBLEM POSSIBLE CORRECTIVE STEPS
Compressor Will
Not Run
POSSIBLE CAUSES
1. Main switch, circuit breakers open.
2. Fuse
3. Thermal overloads tripped or fuses blown.
4. Defective contactor or coil.
5. System shut down by equipment protection devices.
6. No cooling required.
7. Liquid line solenoid will not open.
8. Motor electrical trouble.
Compressor
Noisy or Vibrating
1. Flooding of refrigerant into compressor.
2. Improper piping support on suction or liquid line.
High Discharge
Pressure
Low Discharge
Pressure
1. Condenser water insufficient or temperature too high.
2. Fouled condenser tubes (water-cooled condenser). Clogged spray nozzles
(evaporative condenser). Dirty tube and fin surface (air cooled condenser).
3. Noncondensables in system.
4. System overcharge with refrigerant.
5. Discharge shutoff valve partially closed.
6. Condenser undersized (air-cooled).
7. High ambient conditions.
1. Faulty condenser temp. regulation.
2. Insufficient refrigerant in system.
3. Low suction pressure.
4. Condenser too large.
5. Low ambient conditions.
High Suction
Pressure
2. Expansion valve overfeeding.
Continued on next page.
2. Check electrical circuits and motor winding for shorts or grounds.
Investigate for possible overloading.
Replace fuse or reset breakers after fault is corrected.
3. Overloads are auto reset. Check unit closely when unit comes back on line.
4. Repair or replace.
5. Determine type and cause of shutdown and correct it before resetting protection switch.
6. None. Wait until unit calls for cooling.
7. Repair or replace coil.
8. Check motor for opens, short circuit, or burnout.
9. Check all wire junctions. Tighten all terminal screws.
1. Check superheat setting of expansion valve.
2. Relocate, add or remove hangers.
3. Replace.
1. Readjust temperature control or water regulating valve. Investigate ways to increase water supply.
2. Clean.
3. EPA purge the noncondensables.
4. Remove excess refrigerant.
6. Check condenser rating tables against the operation.
7. Check condenser rating tables against the operation.
1. Check condenser control operation.
2. Check for leaks. Repair and add charge.
3. See corrective steps for low suction pressure below.
4. Check condenser rating table against the operation.
5. Check condenser rating tables against the operation.
1. Reduce load or add additional equipment.
2. Check remote bulb. Regulate superheat.
OM WGS-5 WGS 130A to 190A 95
PROBLEM POSSIBLE CAUSES
1. Lack of refrigerant.
Low Suction
Pressure
Little or No Oil
Pressure
Compressor
Loses Oil
Motor Overload
Relays or Circuit
Breakers Open
3. Clogged liquid line filter-drier.
4. Expansion valve malfunctioning.
5. Condensing temperature too low.
6. Compressor will not unload.
7. Insufficient water flow.
1. Clogged suction oil strainer.
2. Excessive liquid in crankcase.
3. Low oil level.
4. Flooding of refrigerant into crankcase.
1. Lack of refrigerant.
2. Velocity in risers too low (A-C only).
3. Oil trapped in line.
1. Low voltage during high load conditions.
2. Defective or grounded wiring in motor or power circuits.
3. Loose power wiring.
4. High condensing temperature.
5. Power line fault causing unbalanced voltage.
6. High ambient temperature around the overload relay
Compressor
Thermal Switch
Open
Freeze Protection
Opens
2. Discharge valve partially shut.
1. Thermostat set too low.
2. Low water flow.
3. Low suction pressure.
POSSIBLE CORRECTIVE STEPS
1. Check for leaks. Repair and add charge. cartridge(s).
4. Check and reset for proper superheat.
Replace if necessary.
5. Check means for regulating condensing temperature.
6. See corrective steps for failure of compressor to unload.
1. Clean.
2. Check sump heater. Reset expansion valve for higher superheat. Check liquid line solenoid valve operation.
4. Adjust expansion valve.
1. Check for leaks and repair. Add refrigerant.
2. Check riser sizes.
3. Check pitch of lines and refrigerant velocities.
1. Check supply voltage for excessive line drop. compressor-motor.
3. Check all connections and tighten.
4. See corrective steps for high discharge pressure.
5. Check Supply voltage. Notify power company. Do not start until fault is corrected.
6. Provide ventilation to reduce heat.
1. Add facilities so that conditions are within allowable limits.
1. Reset to 42°F (6°C) or above. flow.
3. See “Low Suction Pressure.”
96 WGS 130A to 190A OM WGS-5
All McQuay equipment is sold pursuant to McQuay’s Standard Terms and Conditions of Sale and Limited Product Warranty. Consult your local McQuay Representative for warranty details. Refer to form 933-430285Y-00-A (09/08). To find your local representative, go to www.mcquay.com
This document contains the most current product information as of this printing. For the most up-to-date product information on this unit and others, please go to www.mcquay.com.
(800) 432-1342 www.mcquay.com OM WGS-5 (11/08)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Introduction
- 3 General Description
- 3 Nomenclature
- 4 Definitions
- 8 Wiring Diagrams
- 10 Control Panel Layout
- 13 Controller
- 13 System Architecture
- 14 General Description
- 14 Units of measure
- 16 Sequence of Operation
- 23 Start-Up and Shutdown
- 23 Pre Start-up
- 23 Start-up
- 24 Weekend or Temporary Shutdown
- 24 Start-up after Temporary Shutdown
- 24 Extended Shutdown
- 25 Start-up after Extended Shutdown
- 28 Unit Controller
- 28 Unit Inputs/Outputs
- 28 Unit Setpoints
- 31 Circuit Controller
- 31 Circuit Inputs and Outputs
- 32 Circuit Setpoint Table
- 34 Alarms and Events
- 34 Unit Stop Alarms
- 36 Unit Events
- 36 Circuit Stop Alarms
- 38 Circuit Events
- 39 Alarm Logging
- 40 Event Logging
- 40 Clearing Alarms
- 40 Unit Controller Functions
- 41 Unit Enable
- 42 Unit Mode Selection
- 43 Unit States
- 44 Evaporator Pump Control
- 47 Planned Unit Capacity Overrides
- 48 Condenser Pump and Tower Control
- 49 Cooling Tower Control
- 51 Evaporative Condenser Control
- 54 Circuit Controller Functions
- 54 Refrigerant Calculations
- 55 Compressor Control
- 58 Internal Capacity Overrides
- 59 Slide Positioning
- 61 Expansion Valve Control
- 65 Oil Heater Control
- 65 Starter Communications
- 66 Condenser Fan Control
- 68 Condenser Fan VFD
- 68 Digital Output Control
- 69 Using the Controller
- 71 Security
- 71 Entering Passwords
- 71 Editing Setpoints
- 71 Clearing Alarms
- 72 Menu Descriptions
- 72 Unit Controller
- 87 Circuit Controller
- 93 Editing Review
- 94 BAS Interface
- 95 Unit Troubleshooting Chart