Broan HRV90HT Air Cleaner Installation Guide
Advertisement
Advertisement
INSTALLATION INSTRUCTIONS
HRV90H AND ERV90HC
Model no.: HRV90HT
(HRV with ports on top)
Model no.: HRV90HS
(HRV with ports on sides)
VB0082
Model no.: ERV90HCT
(ERV with ports on top)
VB0081
Model no.: ERV90HCS
(ERV with ports on sides)
VB0080 VB0079
RESIDENTIAL USE ONLY
READ AND SAVE THESE INSTRUCTIONS
06010C rev. H
ABOUT THIS MANUAL
Because of the large amount of models covered by this publication, the illustrations are typical ones. Some details of your unit may be slightly different than the ones shown.
Please take note that this manual uses the following symbols to emphasize particular information:
!
WARNING
Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.
We welcome any suggestions you may have concerning this manual and/or the unit, and we would appreciate hearing your comments on ways to better serve you. Please contact us by phone at 1-800-558-1711.
ABOUT THESE UNITS
LIMITATION
For residential (domestic) installation only. This unit must be installed in accordance with all national and local regulations, building codes and safety codes.
!
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
1.
Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed in the warranty.
2.
Before servicing or cleaning the unit, disconnect power cord from electrical outlet.
3.
This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
4.
When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
5.
Do not use this unit with any solid-state speed control device other than main optional wall control VT4W, and no other optional auxiliary wall controls than 60-minute crank timer and/or 20-minute lighted push button and/or Humidity Control.
6.
This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged into a mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances.
Do not remove the ground prong. Do not use an extension cord.
7.
Do not install this unit in a cooking area or connect directly to any appliances.
8.
Do not use to exhaust hazardous or explosive materials and vapors.
9.
When performing installation, servicing or cleaning these units, it is recommended to wear safety glasses and gloves.
10.
Due to the weight of the unit, two installers are recommended to perform installation.
11.
When the federal, provincial or state legislation comprises more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expenses.
CAUTION
1.
To avoid prematurate clogged filters, turn OFF the unit during construction or renovation.
2.
Please read specification label on product for further information and requirements.
3.
Be sure to duct air outside – Do not intake / exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage.
4.
Intended for residential installation only in accordance with the requirements of NFPA 90B.
5.
Do not run any air ducts directly above or closer than 2 ft (0.61 m) to any furnace or its supply plenum, boiler, or other heat producing appliance. If a duct has to be connected to the furnace return plenum, it must be connected not closer than 9’10” (3 m) from this plenum connection to the furnace.
6.
The ductwork is intended to be installed in compliance with all local and national codes that are applicable.
7.
When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit operates adequately.
8.
If the ductwork passes through an unconditioned space (e.g.: attic), the unit must operate continuously except when performing maintenance and/or repair. Also, the ambient temperature of the house should never drop below 18°C (65°F).
- 2 -
TABLE OF CONTENTS
1.
T
ECHNICAL
D
ATA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-6
1.1 A
IR
D
ISTRIBUTION
(N
ORMAL
O
PERATION
) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.2 A
IR
D
ISTRIBUTION
(R
ECIRCULATION OR
D
EFROST
M
ODE
) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.3 S
PECIFICATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.4 P
ERFORMANCE
C
HARTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.5 D
IMENSIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.6 C
ONTROLS AND
L
INKAGE
P
OSSIBILITY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
2.
T
YPICAL
I
NSTALLATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8
2.1 F
ULLY
D
UCTED
S
YSTEM
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.2 C
ENTRAL
D
RAW
P
OINT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.3 S
IMPLIFIED
I
NSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.4 I
NSTALLATION FOR
ERV U
NITS
O
NLY
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.
I
NSTALLATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-16
3.1 I
NSPECT THE
C
ONTENT OF THE
B
OX
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.2 L
OCATING THE
U
NIT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.3 U
NIT
P
REPARATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.4 H
OW TO
H
ANG THE
U
NIT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.5 P
LANNING OF THE
D
UCTWORK
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3.6 I
NSTALLING THE
D
UCTWORK AND
R
EGISTERS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-12
3.7 C
ONNECTING THE
D
UCT TO THE
U
NIT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3.8 I
NSTALLING THE
T
ANDEM
® T
RANSITION
K
IT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-15
3.9 I
NSTALLING
2 E
XTERIOR
H
OODS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
4.
C
ONTROLS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-19
4.1 I
NTEGRATED
C
ONTROL
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
4.2 E
LECTRICAL
C
ONNECTION TO
O
PTIONAL
W
ALL
C
ONTROLS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17-18
4.3 VT4W O
PTIONAL
M
AIN
W
ALL
C
ONTROL
O
PERATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
4.4 O
PTIONAL
A
UXILIARY
W
ALL
C
ONTROLS
O
PERATION
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
5.
E
LECTRICAL
C
ONNECTION TO THE FURNACE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
6.
W
IRING
D
IAGRAM
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
7.
B
ALANCING THE UNIT
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
8.
C
ONNECTING THE
D
RAIN
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
9.
M
AINTENANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-24
9.1 B
IANNUAL
M
AINTENANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23-24
9.2 A
NNUAL
M
AINTENANCE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
10.
S
ERVICE
P
ARTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
11.
T
ROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
- 3 -
1. TECHNICAL DATA
1.1 A
IR
D
ISTRIBUTION
(N
ORMAL
O
PERATION
)
HRV
E
XHAUST AIR
FROM BUILDING
F
RESH AIR
FROM OUTSIDE
E
XHAUST AIR
FROM BUILDING
F
RESH AIR
TO BUILDING
E
XHAUST AIR
TO OUTSIDE
F
RESH AIR
TO BUILDING
VF00 3 9
VF00 38
1.2 A
IR
D
ISTRIBUTION
(R
ECIRCULATION OR
D
EFROST
M
ODE
)
HRV
E
XHAUST AIR
FROM BUILDING
E
XHAUST AIR
FROM BUILDING
ERV
ERV
F
RESH AIR
FROM OUTSIDE
E
XHAUST AIR
TO OUTSIDE
F
ILTERED AIR
TO BUILDING
VF00 3 6
Outside Temperature
Celcius (°C)
-5 to -27
-27 and less
Fahrenheit (°F)
23 to -17
-17 and less
1.3 S
PECIFICATIONS
M
ODEL
W
EIGHT
O
VAL
P
ORTS
D
RAIN
D
IAMETER
I
NSTALLATION
M
OTOR
S
PEEDS
E
LECTRICAL SUPPLY
P
OWER
C
ONSUMPTION
F
ILTERED AIR
TO BUILDING
VF00 3 7
HRV and ERV Defrost Cycles
Defrosting (min.)
9
10
Operation time (min.) between each defrost cycle
23
22
HRV
42 lb (19 kg)
ERV
45
LB
(20.4
KG
)
F
IT
5” (127
MM
)
DUCTS
1/2” (12
MM
)
F
IT
5” (127
MM
)
DUCTS
N/A
C
HAINS
,
SPRINGS AND HOOKS
(
PROVIDED WITH THE UNIT
)
H
IGH AND LOW SPEED
120 V, 60 H
Z
120 V, 60 H
Z
150
WATTS
160
WATTS
- 4 -
1. TECHNICAL DATA
(CONT’D)
1.4 P
ERFORMANCE
C
HARTS
1.4.1
HRV U
NITS
V
ENTILATION
P
ERFORMANCE
E
XT
. S
TATIC
P
RESSURE
N
ET
A
IR
S
F
UPPLY
LOW
G
S
UPPLY
ROSS AIR FLOW
E
XHAUST
P
A IN
.
W
.
G
.
L
/
S CFM M
³/
H L
/
S CFM M
³/
H L
/
S CFM M
³/
H
25
50
.1
.2
52
50
110
106
187
180
52
50
110
106
187
180
58
55
122
116
205
198
75 .3
100 .4
125 .5
150 .6
175 .7
200 .8
48 101 173 48 102 173 53 113 191
45 96 162 46 97 166 50 107 180
43 92 155 43 92 155 49 103 173
41 87 148 41 87 148 45 96 162
38 81 138 38 81 137 43 91 155
35 75 126 36 76 130 40 85 144
NOTE: A
LL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
.
E
NERGY
P
ERFORMANCE
S
UPPLY
T
EMPERATURE
N
ET AIR FLOW
°C °F
L
/
S CFM M
³
/
H
P
OWER
S
ENSIBLE
A
PPARENT
CONSUMED RECOVERY
W
ATTS
SENSIBLE
EFFICIENCY EFFECTIVENESS
L
ATENT
RECOVERY
/
MOISTURE
TRANSFER
H
EATING
0 32 23 48 82
0 32 30 63 108
68
82
0 32 44 93 157 116
66
65
59
78
76
68
0.07
0.04
0.04
-25 -13 30 63 108 110 55 81 0.08
C
OOLING
35 95 -
-
-
-
-
-
-
-
T
OTAL RECOVERY EFFICIENCY
N
OT TESTED
1.4.2
ERV U
NITS
V
ENTILATION
P
ERFORMANCE
E
XT
. S
TATIC
P
RESSURE
N
ET
A
IR
S
F
UPPLY
LOW
S
G
UPPLY
ROSS AIR FLOW
E
XHAUST
P
A IN
.
W
.
G
.
L
/
S CFM M
³/
H L
/
S CFM M
³/
H L
/
S CFM M
³/
H
25
50
.1
.2
75 .3
100 .4
125 .5
150 .6
175 .7
200 .8
55 116 197 56 119 202 59 125 212
53 113 192 55 116 197 57 121 206
50 107 182 52 111 189 54 115 195
49 104 177 50 107 182 53 112 190
46 98 166 48 101 172 50 105 178
44 94 160 46 97 165 47 100 170
42 88 150 43 91 155 45 95 161
39 82 139 40 84 143 42 90 153
NOTE: A
LL SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
.
E
NERGY
P
ERFORMANCE
S
UPPLY
T
EMPERATURE
N
ET AIR FLOW
°C °F
L
/
S CFM M
³
/
H
P
OWER
W
ATTS
H
EATING
0 32 13 28 48 73
0 32 45 96 163 137
S
ENSIBLE
CONSUMED RECOVERY
A
PPARENT
SENSIBLE
EFFICIENCY EFFECTIVENESS
69
62
94
74
L
ATENT
RECOVERY
/
MOISTURE
TRANSFER
0.68
0.48
102 -25 -13 25 54 92
C
OOLING
35 95 14 29 49
-
70
-
54 83 0.58
T
OTAL RECOVERY EFFICIENCY
54
- 5 -
1. TECHNICAL DATA
(CONT’D)
1.5 D
IMENSIONS
1.5.1
D
IMENSIONS FOR
P
ORTS ON
S
IDES
U
NITS
4 ” (102 mm)
6 ”
(152 mm)
HRV
27 /
16
” (6 88 mm)
22 /
16
” (574 mm)
VK0055A
4 ” (102 mm)
2 ” (51 mm)
ERV
27 /
16
” (6 88 mm)
22 /
16
” (574 mm)
6 ”
(152 mm)
2 ” (51 mm)
VK0057A
1.5.2
D
IMENSIONS FOR
P
ORTS ON
T
OP
U
NITS
HRV
1 3 ¾ ”
( 3 49 mm)
19 /
16
” (50 3 mm)
19 /
16
” (50 3 mm)
12 /
16
”
( 3 10 mm)
12 /
16
”
( 3 10 mm)
ERV
4 ’’ (102 mm) 4 ’’ (102 mm)
19
16
”
(50 3 mm)
19
16
”
(50 3 mm)
6 ’’ (152 mm) 6 ’’ (152 mm)
22
16
” (574 mm)
2 3 ¾ ” (60 3 mm)
22
16
” (574 mm)
2 3 ¾ ” (60 3 mm)
2½ ”
(64 mm)
2½ ”
(64 mm)
16¼ ”
(41 3 mm)
12
16
”
( 3 10 mm)
VK0056A
1.6 C
ONTROLS AND
L
INKAGE
P
OSSIBILITY
M
AIN
C
ONTROL
• VT4W
A
UXILIARY
C
ONTROLS
• 20-
MINUTE
P
USH
B
UTTON
T
IMER
• 60-
MINUTE
C
RANK
T
IMER
• H
UMIDITY
C
ONTROL
16¼ ”
(41 3 mm)
VK005 8 A
12
16
”
( 3 10 mm)
L
INKAGE
P
OSSIBILITY
• A
IR
H
ANDLER
I
NTERLOCK
(
USED WITH FORCED AIR SYSTEM
)
- 6 -
2. TYPICAL INSTALLATIONS
Installations may vary according to the type of unit and the ports configuration (top or sides). Use the following illustrations as guidelines to help you decide on how the unit will be installed.
All the units should be hung from the joists.
In every case, bathroom fans and a range hood should be used to exhaust stale air. Also, for homes with more than one level, we recommend one exhaust register at the highest level.
There are 3 installation methods: Fully ducted, Central Draw Point and Simplified Installation.
NOTE: An electrical outlet has to be available within 3 feet of the unit.
2.1 F
ULLY
D
UCTED
S
YSTEM
(P
RIMARILY FOR HOMES WITH RADIANT HOT WATER OR ELECTRIC BASEBOARD HEATING
)
Stale air coming from the registers located at the highest level of the house is exhausted to the outside. Fresh air from outside is filtered and supplied by the register located in the lowest liveable level.
Homes with more than one level require at least one exhaust register at the highest level.
See figure at right.
2.2 C
ENTRAL
D
RAW
P
OINT
(C
ONNECTION TO A FORCED AIR SYSTEM
)
VH0055
Stale air coming from the registers located at the highest level of the house is exhausted to the outside. Fresh air from outside is filtered and supplied to the return (plenum) or the supply duct of the forced air unit. See figure at right.
For this type of installation, it is not essential that the forced air system blower runs when the unit is in operation, but we recommend it.
NOTE: Home with multiple forced air systems should have one unit on each system.
VH0056
2.3 S
IMPLIFIED
I
NSTALLATION
(C
ONNECTION TO A FORCED AIR SYSTEM
)
Stale air is exhausted to the outside. Fresh air from outside is filtered and supplied to the return (plenum) or the supply duct of the forced air unit. See figure at right.
To avoid cross-contamination and achieve the highest efficiencies, the forced air system blower must always be ON.
NOTE: Home with multiple forced air systems should have one unit on each system.
- 7 -
VH0057
2. TYPICAL INSTALLATIONS
(CONT’D)
2.4 I
NSTALLATION FOR
ERV U
NITS
O
NLY
2.4.1
G
EOGRAPHICAL
L
OCATION
The ERV units are created to meet specific requirements related to geographical locations. Take a look at the map below; the shaded area shows the limits where the ERV unit can be installed. However, there is no geographical limitation for installing an HRV unit.
ANCHORAGE
WHITEHOR S E
JUNEAU
YELLOWKNIFE
HAY RIVER
FORT S MITH
FORT MCMURRAY
Prince R u pert
GRANDE PRAIRIE
GOO S E BAY
JA S PER
EDMONTON
PRINCE ALBERT
LABRADOR CITY
VICTORIA
OLYMPIA
S ALEM
RENO
S ACRAMENTO
BOI S E
S A S KATOON
KAMLOOP S
PENTICTON
CALGARY
LETHBRIDGE
HELENA
S ALT LAKE CITY
REGINA
BI S
WINNIPEG
MARCK
S T. PAUL
TIMMIN S
CHIBOUGAMAU
S UDBURY
S AULT S TE MARIE
CHICOUTIMI
VAL-DOR
MATANE
BATHUR S T
QUEBEC
GA S PÉ
CHARLOTTETOWN
OTTAWA
TORONTO
S
S EPT-ILE S
T-JOHN
HALIFAX
S T JOHN ’S
MADI S ON
DETROIT
DE S MOINE S
BO S TON
DENVER
TOPEKA
HARTFORD
S
INDIANAPOLI S
PRINGFIELD
HARRI S
COLUMBU S
BURG
WA S HINGTON
S ANTA FE
OKLAHOMA CITY
NA S HVILLE
RALEIGH
PHOENIX
ATLANTA
COLUMBIA
AU S TIN BATON ROUGE
VN0006
NOTE: The ERV unit is designed to assist in the management of humidity introduced into the home.
During cooling season, in extreme humidity conditions, the use of additional dehumidification unit may be required to quickly remove all excess moisture. During heating season, in extreme dryness conditions, the use of a humidifier may be required if the indoor air is still too dry.
2.4.2
ERV U
NITS
A
TTIC
I
NSTALLATION
All 3 types of installations can be used in the attic (Fully ducted system, Central Draw Point or Simplified). The example shown below is a Simplified installation (connection to a forced air system).
CAUTION
Due to the potential temperature difference between the attic and the rest of the house, all unit ducts must be insulated.
CAUTION
The attic temperature must always be above 0°C (32°F).
Stale air is exhausted to the outside. Fresh air from outside is filtered and supplied to the return (plenum) of the forced air unit.
See figure at right.
To avoid cross-contamination and achieve the highest efficiencies, the forced air system blower must always be ON.
NOTE: Home with multiple forced air systems should have 1 unit on each system.
VH005 8
- 8 -
3. INSTALLATION
3.1 I
NSPECT THE
C
ONTENTS OF THE
B
OX
• Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door latches, power cord, etc.
A
• Remove and discard the 2 transport brackets (
A
) and open the door. Discard the styrofoam fillers (ERV units only) and remove the hardware kit from the unit. Inspect the interior of the unit for damage. Ensure that heat or energy recovery core, core filters, insulation, dampers, etc.
are all intact.
VD01 83
3.2 L
OCATING THE
U
NIT
C
HOOSE AN APPROPRIATE LOCATION FOR THE UNIT
.
• Within an area of the house where the ambient temperature is between 10°C (50°F) and 65°C (149°F) (basement, furnace room, closet, etc.).
• So as to provide easy access to the interior of the unit, for maintenance.
• Close to an exterior wall, so as to limit the length of the insulated flexible duct to and from the unit.
• Away from hot chimneys and other fire hazards.
• Allow for a power source (standard 3-prong grounding outlet).
• For HRV units ONLY: Close to a drain. If no drain is close by, use a pail to collect run-off.
3.3 U
NIT
P
REPARATION
Both HRV and ERV units are equipped with 2 ports having integrated balancing damper. Turn the thumb screw (
A
)
clockwise
to manually open and adjust the damper (
B
).
HRV units
: Set the Fresh air to building port to wide open position, and adjust the Exhaust air to outside port to 3rd notch.
NOTE: If the unit needs to be balanced, adjust the damper of the Exhaust air to outside port to wide open position. See Section 7.
ERV units
: Set both Fresh air to building port and Exhaust air to outside port to wide open position.
A
VJ00 3 2
P
ORT WITH INTEGRATED
BALANCING DAMPER
- T
OP VIEW
The door latches location can be changed from sides to front of the unit, according to the installation needs.
B
VD0176
L
ATCHES ON SIDES OF THE UNIT
L
ATCHES IN FRONT OF THE UNIT
To do so, turn the unit upside down. Open the latches and unscrew them from the unit. Install the latches on their new locations.
VO0089
VO0090
- 9 -
VO0094
3. INSTALLATION
(CONT’D)
3.4 H
OW TO
H
ANG THE
U
NIT
Hang the unit with the 4 chains, hooks and springs provided.
VD01 8 5
VD0184
CAUTION
Make sure the unit is level.
3.5 P
LANNING OF THE
D
UCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of insulated ducts to a minimum.
• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would cause clogging of the filters and recovery module.
• If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
3.6 I
NSTALLING THE
D
UCTWORK AND
R
EGISTERS
0
!
WARNING
Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas furnace, a gas water heater or a fireplace.
3.6.1
F
ULLY
D
UCTED
S
YSTEM
(
AS ILLUSTRATED IN
S
ECTION
2.1)
Stale air exhaust ductwork
• Install the stale air exhaust registers where the contaminants are produced: kitchen, living room, etc. Position the registers as far from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.
• If a register is installed in the kitchen, it must be located at least 4 feet (1.2 m) from the range.
• Install the registers 6 in. to 12 in. (152 mm to 305 mm) from the ceiling on an interior wall OR install them in the ceiling.
Fresh air distribution ductwork
• Install the fresh air distribution registers in bedrooms, dining rooms, living room and basement.
• Keep in mind that the fresh air registers must be located as far as possible from the stale air registers.
• Install the registers in the ceiling or 6 in. to 12 in. (152 mm to 305 mm) from the ceiling on an interior wall. The duct length should be at least 15’ (4.6 m). (The fresh air will then flow through the room and mix with room air, ensuring a continuous renewed airflow.)
• If a register must be floor installed, direct the airflow up the wall.
- 10 -
3. INSTALLATION
(CONT’D)
3.6 I
NSTALLING THE
D
UCTWORK AND
R
EGISTERS
(
CONT
’
D
)
3.6.2
C
ENTRAL
D
RAW
P
OINT
S
YSTEM
(
AS ILLUSTRATED IN
S
ECTION
2.2)
Stale air exhaust ductwork
Same as for Fully Ducted System, described on point 3.6.1.
Fresh air distribution ductwork
0
!
WARNING
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and safety regulations. Please refer to your local building code.
CAUTION
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the HRV/ERV. Also, use a steel duct. It is recommended that the HRV/ERV is running when the furnace is in operation to prevent backdrafting inside HRV/ERV.
There are 2 methods for connecting the unit to the furnace/air handler:
Method 1: Supply side connection
• Cut an opening into the furnace supply duct at least 18 inches (0.5 m) from the furnace/air handler.
• Connect this opening to the Fresh air to building port of the HRV/ERV (use steel duct, see figure beside).
• Make sure the HRV/ERV duct form an elbow inside the furnace/air handler ductwork.
• If desired, interlock (synchronize) the furnace/air handler blower operation (see
Section 5).
S
TEEL DUCT
VJ00 3 6
M
INIMUM
18”
(0.5
M
)
Method 2: Return side connection
• Cut an opening into the furnace return duct not less than 10 feet (3.1 m) from the furnace/air handler (A+B).
• Connect this opening to the Fresh air to building port of the HRV/ERV
(see figure beside).
NOTE: For Method 2, it is not essential that the furnace/air handler runs when the unit is operation, but we recommend it. If desired, interlock (synchronize) the furnace/air handler blower operation (see Section 5).
VJ00 3 5
A
A+B= N
OT LESS
THAN
10’ (3.1
M
)
B
- 11 -
3. INSTALLATION
(CONT’D)
3.6 I
NSTALLING THE
D
UCTWORK AND
R
EGISTERS
(
CONT
’
D
)
3.6.3
S
IMPLIFIED
I
NSTALLATION
(
AS ILLUSTRATED IN
S
ECTION
2.3)
0
!
WARNING
When performing duct connections, always use approved tools and materials. Respect all corresponding laws and/or safety regulations. Please refer to your local building code.
CAUTION
When performing duct connections to the furnace supply duct, this duct must be sized to support the additional airflow produced by the HRV/ERV. Also, use a steel duct. For a Return-Return installation, the furnace blower must be in operation when the HRV/ERV is in operation.
There are 2 methods for connecting the unit to the furnace/air handler:
Method 1: Supply-return connection Method 2: Return-return without
S
TEEL DUCT
M
INIMUM
18”
(0.5
M
)
M
INIMUM
3’
(0.9
M
)
A+B= N
OT LESS
THAN
10’ (3.1
M
)
A
B
A
B
A+B= N
OT LESS
THAN
10’ (3.1
M
)
VJ00 38
VJ00 3 7
Stale air intake
• Cut an opening into the furnace/air handler return duct not less than 10 feet (3.1 m) from the furnace/air handler (A+B).
• Connect this opening to the Exhaust air from building port of the HRV/ERV.
Fresh air distribution
• Same instructions as for Method 1 or Method 2, Section 2.6.2.
For Method 2 (Return-return), make sure there is a distance of at least 3 feet (0.9 m) between the 2 connections to the furnace/air handler.
NOTE: For Method 1, it is not essential to synchronize the furnace blower operation with the unit operation, but we recommend it.
CAUTION
If using Method 2, make sure the furnace/air handler blower operation is synchronized with the unit operation!
See Section 5.
- 12 -
3.
INSTALLATION
(CONT’D)
3.7 C
ONNECTING THE DUCTS TO THE UNIT
Insulated flexible ducts
Use the following procedure for connecting the insulated flexible ducts to the port of the unit (
Exhaust air to outside
and
Fresh air from outside
ports).
CAUTION
Make sure the balancing dampers are set to their appropriate position before connecting the ducts to the ports.
See Section 3.3.
VJ004 3 VJ0041
VJ0042
VJ00 3 9
Pull back the insulation to expose the flexible duct.
VJ0040
Attach the flexible duct to the port using tie wrap.
Pull the insulation over the joint and tuck in between the inner and outer rings of the double collar.
Pull the vapor barrier over the insulation and over the outer ring of the double collar.
CAUTION
Make sure the vapor barrier on the insulated ducts does not tear during installation to avoid condensation within the ducts.
Apply duct tape to the joint making an airtight seal. Avoid compressing the insulation when pulling the tape tightly around the joint.
Compressed insulation loses its R value and causes water dripping due to condensation on the exterior surface of the duct.
Rigid ducts
CAUTION
Do not use screws to connect the rigid ducts to the ports.
Use a small length of flexible duct to connect the rigid duct to the ports in order to avoid vibration transmissions. Use tie-wraps to perform connections.
3.8 I
NSTALLING THE
T
ANDEM
® T
RANSITION
* K
IT
Use the following procedure for connecting the insulated flexible ducts to the Tandem Transition (
Exhaust air to outside and Fresh air from outside).
9¾ ”
24 8 mm
NOTE: The joist opening needed to install the Tandem transition must be
9¾” (248 mm) minimum. Also, the maximum height of the Tandem transition is
8¾” (222 mm). See Tandem Transition end view beside. If the joists are perpendicular to the ducts, or if the connection to the exterior hood is in a limited area, your installation will need two exterior hoods instead of one. In this case, do not use the Tandem Transition kit. See next Section 3.9 I
NSTALLING
2
EXTERIOR
H
OODS
.
8 ¾ ”
222 mm
*Patented.
VD011 8 A
- 13 -
3. INSTALLATION
(CONT’D)
3.8 I
NSTALLING THE
T
ANDEM
T
RANSITION
K
IT
(
CONT
’
D
)
3.8.1
C
ONNECTION TO
T
ANDEM
T
RANSITION
1.
For each duct, pull back the insulation to expose the interior flexible duct.
2.
Connect the interior flexible duct to the smaller part of the Tandem Transition (5” oval) using a tie wrap.
3.
Pull the insulation over the joint. Pull the vapor barrier over the insulation.
4.
Apply duct tape gently to the joint in order to make an airtight seal. See figures below.
1
E
XHAUST AIR TO OUTSIDE
DUCT ON TOP
2
3
VJ0025
4
VJ0022
VJ0023
3.8.2
A
SSEMBLING
D
UAL
E
XTERIOR
H
OOD
*
VJ0024
Exterior dual hood is coming in separate parts. Using 2 no. 8 x 3/4” screws, assemble the top metal screen and the plastic grille to the dual exterior hood. Then, slide the bottom metal screen to the dual exterior hood. See illustration beside.
*P
ATENTED
.
VO0024
3.8.3
L
OCATING THE
D
UAL
E
XTERIOR
H
OOD
The dual exterior hood must be installed at a minimum distance of 18 inches (457 mm) from the ground. See illustration beside.
!
WARNING
Make sure this hood is at least 6 feet (1.8 m) away (or more, as per applicable building codes or standards) from sources of contamination such as:
• High efficiency furnace vent
• Any exhaust from a combustion source
• Gas meter exhaust, gas barbecue-grill
• Garbage bin
3.8.4
C
ONNECTING
T
ANDEM
T
RANSITION TO THE
D
UAL EXTERIOR
H
OOD
VD00 83 A
1 8”
(457 mm)
1
1.
Using a jig saw, cut a 6” diameter hole in the exterior wall and insert the Tandem transition through this hole.
VD0084
1) E
XHAUST AIR TO OUTSIDE DUCT
CAUTION
The Tandem Transition must be inserted in such a way that the Exhaust air to outside duct will be located on the top.
- 14 -
3. INSTALLATION
(CONT’D)
3.8 I
NSTALLING THE
T
ANDEM
T
RANSITION
K
IT
(
CONT
’
D
)
3.8.4
C
ONNECTING
T
ANDEM
T
RANSITION TO THE
D
UAL EXTERIOR
H
OOD
(
CONT
’
D
)
2.
Join the end of the Tandem Transition to the rear of the exterior backplate. Secure with
2 Xmas tree pins and seal properly with duct tape.
CAUTION
The exterior backplate must be installed with the word “TOP” pointing upward.
VD0085
3.
Using 4 no. 8 x 1½” screws, mount the the exterior backplate to the exterior wall. Seal the outline with caulking.
VD0086
4.
Snap the assembled exterior hood on its backplate and secure with 2 provided screws
(no. 8 x 3/4” long).
X
MAS TREE PIN
VD0087
S
CREW
- 15 -
3. INSTALLATION
(CONT’D)
3.9 I
NSTALLING
2 E
XTERIOR
H
OODS
Choose an appropriate location to install the exterior hoods:
• There must be a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination
• There must be a minimum distance of 18 inches (457 mm) from the ground
!
WARNING
Make sure the intake hood is at least 6 feet (1.8 m) away (or more, as per applicable building codes or standards) from sources of contamination such as:
• High efficiency furnace vent
• Any exhaust from a combustion source
• Gas meter exhaust, gas barbecue-grill
• Garbage bin
Refer to figure below for connecting insulated ducts to the exterior hoods. An “Anti-gust intake hood” should be installed in regions where a lot of snow is expected to fall.
E
XHAUST HOOD
6” Ø
(152
MM
)
18”
(457
MM
)
6’
(1.8
M
)
I
NTAKE HOOD
18”
(457
MM
)
6’
(1.8
M
)
18” (457
MM
)
O
PTIONAL
DUCT LOCATION
T
APE AND DUCT TIE
VD002 8
- 16 -
4. CONTROLS
4.1 I
NTEGRATED
C
ONTROL
All units are equipped with an integrated control, located under the unit, in front of the electrical compartment. Use the push button (
1
) to control the unit. The LED (
2
) will then show which mode the unit is in.
WARNING s k of electric s hock. Before performin g any maintenance or s ervicin g , alway s di s connect the unit from it s power s ource.
AVERTI SS EMENT
Dan g er d ’ électrocution. Débranchez
l ’ appareil avant d ’ entreprendre de s travaux d entretien ou de réparation.
CAUTION ATTENTION
Un s crew both s crew s to open the electrical compartment. To completely remove, detach er le s deux vi pour ouvrir le compartiment
électrique. Pour retirer complètement, le
from it s retention wire in s ide. détacher de s on fil de rétention intérieur.
No light OFF or remote controled
Am b er light LOW s peed
Green ligh HIGH s peed
Blinking light ee U s er M a n ua l
Sa n s l u mière Arrêté o u contrôlé
p
L u mière a m b a r contrôle m re B e vite u r ss a l e
L u mière verte H au te vite ss e
Clignot a nt Voir g u ide d ’u tili sa tion
VD01 8 2
1 2
Refer to table below to see how to operate the unit using its integrated control.
P
RESS ON PUSH BUTTON
O
NCE
T
WICE
T
HREE
T
IMES
LED C
OLOR
A
MBER
G
REEN
N
O
L
IGHT
R
ESULTS
U
NIT IS ON
L
OW
S
PEED
U
NIT IS ON
H
IGH
S
PEED
U
NIT IS
OFF
If a problem occurs during the unit operation, its integrated control LED (
2
) will blink. The color of the blinking light depends on the type of error detected. Refer to Section 11 Troubleshooting on last page for further details.
4.1.1
B
OOT SEQUENCE
The unit boot sequence is similar to a personnal computer boot sequence. Each time the unit is plugged in after being unplugged, or after a power failure, the unit will perform a 30-second booting sequence before starting to operate. During the booting sequence, the integrated control LED will light GREEN or AMBER for 5 seconds, and then will shut off for 2 seconds. After that, the LED will light RED for the rest of the booting sequence. During this RED light phase, the unit is checking and resetting the motorized damper position. Once the motorized damper position is completely set, the RED light turns off and the booting sequence is done.
NOTE: No command will be taken until the unit is fully booted.
4.2 E
LECTRICAL
C
ONNECTION TO
O
PTIONAL
W
ALL
C
ONTROLS
For more convenience, this unit can also be controlled using an optional main wall control.
NOTES: 1. The integrated control must be turned OFF to use an optional main control.
2. If an optional auxiliary control is used, if activated, this auxiliary control will override the optional main control.
0
!
WARNING
Always disconnect the unit before making any connections. Failure in disconnecting power could result in electrical shock or damage of the wall control or electronic module inside the unit.
CAUTION
Never install more than one optional main wall control per unit. Make sure that the wires do not short-circuit between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce electrical interference (noise) potential, do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.
Use the terminal connector included in the installation kit to perform the electrical connection for main and optional wall controls. Check if all wires are correctly inserted in their corresponding holes in the terminal block. (A wire is correctly inserted when its orange receptacle is lower than another one without wire. On picture beside, wire
A
is correctly inserted, but not wire
B
.)
A
VE0106
- 17 -
B
4. CONTROLS
(CONT’D)
4.2 E
LECTRICAL
C
ONNECTION TO
O
PTIONAL
W
ALL
C
ONTROLS
(
CONT
’
D
)
4.2.1
E
LECTRICAL
C
ONNECTION TO
VT4W M
AIN
W
ALL
C
ONTROL
NO C NC I OC OL Y R G B
M
AIN WALL
LITE-TOUCH CON S TRUCTO
CONTROL nd
VT4W
S IMPLE-TOUCH CON S TRUCTO
REAR VIEW
Y G B
OC G B
VE0100A
4.2.2
E
LECTRICAL
C
ONNECTION TO
O
PTIONAL
A
UXILIARY
W
ALL
C
ONTROLS
HUMIDITY CONTROL
NOTE: If an optional auxiliary wall control is activated and then, the
Humidity Control is being
NO C NC I OC OL Y R G B activated, the Humidity Control will override the auxiliary wall control commands.
HUMIDITY
CONTROL
20%
25%
%
REL
ATIVE HUMIDIT
Y
O
FF
30%
COM
40%
50%
70%
60%
60-MINUTE
CRANK TIMER
20-MINUTED LIGHTED PU S H BUTTON
(5 MAXIMUM)
VE0110A
Once the wall control(s) connections have been made, insert the terminal connector in the bottom of the unit, on the electrical compartment front face.
WARNING s k of electric s hock. Before performin g any maintenance or s ervicin g , alway s di s connect the unit from it s power s ource.
AVERTI SS EMENT
Dan g er d ’ électrocution. Débranchez s l ’ appareil avant d ’ entreprendre de s travaux d entretien ou de réparation.
CAUTION
Un s crew both s crew s to open the electrical compartment. To completely remove, detach
from it s retention wire in s ide.
ATTENTION ss er le s s pour ouvrir le compartiment
électrique. Pour retirer complètement, le détacher de s on fil de rétention intérieur.
No light OFF or remote controled
Am b er light LOW s peed
Green ligh HIGH
Blinking light ee U s s peed er M a n ua l
Sa n s l u mière Arrêté o u contrôlé
p a r contrôle m u r a l
L u
L u mière a m b re B ass e vite ss e mière verte H au te vite e
Clignot a nt Voir g u ide d ’u tili sa tion
T
ERMINAL
CONNECTOR
VD01 8 2
4.3 VT4W O
PTIONAL
M
AIN
W
ALL
C
ONTROL
O
PERATION
C
OLOR
M
ODE
S
UGGESTED
U
SE
G
REEN
I
NTERMITTENT
S
ELECT THIS MODE WHEN YOU ARE AWAY FROM THE HOUSE
FOR A FEW DAYS
. A
LSO
,
WHEN YOU DEEM THE INSIDE AIR IS
TOO DRY IN HEATING SEASON
,
OR TOO HUMID DURING
COOLING SEASON
. I
N THIS MODE
,
THE UNIT IS
OFF
FOR
40
MINUTES PER HOUR AND VENTILATES AT MINIMUM SPEED
THE REMAINING
20
MINUTES OF THE HOUR
.
F
OR NORMAL DAILY OPERATION
.
Y
ELLOW
M
IN
S
PEED
V
ENTILATION
R
ED
M
AX
S
PEED
V
ENTILATION
(
F
OR EXCESS POLLUTANTS AND
PARTIES
,
ODORS
,
SMOKE
,
ETC
H
.).
UMIDITY
MAX
MIN
INTERMITTENT
VT4W
VC0070
- 18 -
4. CONTROLS
(CONT’D)
4.4
O
PTIONAL
A
UXILIARY
W
ALL
C
ONTROLS
O
PERATION
4.4.1
20-M
INUTE
L
IGHTED
P
USH
-B
UTTON
T
IMER
Set the push-button timer to ON. The fan motors will then operate at high speed for 20 minutes and the indicator will light up.
To stop activation, push one time; the unit will then get back to previous selection.
4.4.2
60-M
INUTE
C
RANK
T
IMER
VC00 8 4
ON
This control makes the system operate at high speed for periods varying from 10 to 60 minutes.
TURN
PAST
20
OFF
10
20
60
50
40
30
4.4.3
H
UMIDITY
C
ONTROL
Setting during the fall, winter and spring months:
Adjust knob to the desired maximum humidity level.
Setting during summer:
Adjust knob to the OFF positon.
VC0017
HUMIDITY
CONTROL
20%
%
REL
ATIVE HUMIDIT
Y
O
FF
25%
70%
30%
COM
FOR T ZO
NE
40%
50%
60%
CAUTION
Do not select a humidity level below 30%. This could lead to excessive dryness in the air causing discomfort for the occupants.
VC00 8 5
5. ELECTRICAL CONNECTION TO THE FURNACE
0
!
WARNING
Never connect a 120-volt AC circuit to the terminals of the furnace interlock (standard wiring). Only use the low voltage class 2 circuit of the furnace blower control.
For a furnace connected to a cooling system:
On some older thermostats, energizing the “R” and “G” terminals at the furnace has the effect of energizing “Y” at the thermostat and thereby turning on the cooling system. If you identify this type of thermostat, you must use the alternate furnace interlock wiring.
Standard furnace interlock wiring Alternate furnace interlock wiring
FOUR
WIRE S
TWO WIRE S he a ting only
W
R
G
C
Y
FURNACE
24-VOLT
TERMINAL BLOCK
W R G Y
THERMO S TAT
TERMINAL S
TWO WIRE S
VE010 8 A
COOLING S Y S TEM
- 19 -
4 WIRE S
2 WIRE S he a ting only
W
G
C
FURNACE
24-VOLT
TERMINAL BLOCK
THERMO S TAT
TERMINAL wiring
n u t s
NO
NC
C
2 WIRE S
COOLING S Y S TEM
6. WIRING DIAGRAM
!
WARNING
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
JU1 JU1
7 6 5 4 2 1
BL
1 2
JU1
1 2
W
- 20 -
Y YELLOW nc no
7. BALANCING THE UNIT
To avoid balancing, the difference between stale air ducts total length and fresh air ducts total length must not exceed 50 ft. However, even if the stale air ducts and fresh air ducts lengths are almost equal, your local building codes may require balancing the unit.
If the unit does not need to be balanced, shut all the pressure taps (located on the unit door) with the small plastic plugs included in the hardware kit.
7.1 W
HAT YOU
N
EED TO
B
ALANCE THE
U
NIT
• A magnehelic gauge capable of measuring 0 inch to 0.5 inch of water (0 Pa to 125 Pa) and
2 plastic tubes.
• The balancing chart located on the unit door.
VP0009
7.2 P
RELIMINARY
S
TAGES TO
B
ALANCE THE
U
NIT
• Seal all the unit ductwork with tape. Close all windows and doors.
• Turn off all exhaust devices such as range hood, dryer and bathroom fans.
• Make sure the integrated balancing dampers are fully open. Turn the thumb screw (
A
)
clockwise
to manually open the dampers. Both are located on the Exhaust air to outside port and on
Fresh air to building port.
• Make sure all filters are clean (if it is not the first time you balance the unit).
A
VJ00 3 2
P
ORT WITH INTEGRATED BALANCING
DAMPER
- T
OP VIEW
7.3 B
ALANCING
P
ROCEDURE
1.
Set the unit to high speed.
Make sure that the furnace/air handler blower is ON if the installation is in any way connected to the ductwork of the cold air return. If not, leave furnace/air handler blower
OFF. If the outside temperature is below 0°C / 32°F, make sure the unit is not running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.).
2.
Place the magnehelic gauge on a level surface and adjust it to zero.
3.
Connect tubing from gauge to EXHAUST air flow pressure taps (see diagram beside).
Be sure to connect the tubes to their appropriate high/low fittings. If the gauge drops below zero, reverse the tubing connections.
B
ALANCING
C
HART
1 12 12 11
1 12 12 11
3 1 3 33 3
1 12 12 11
1 12 12 11
3 1 3 33 3
F
RESH AIR FLOW
E
XHAUST AIR FLOW
NOTE: It is suggested to start with the exhaust air flow reading because the exhaust has typically more restriction than the fresh air, especially in cases of fully ducted installations or source point ventilation.
VP0015
Place the magnehelic gauge upright and level. Record equivalent AIR FLOW of the reading according to the balancing chart.
4.
Move tubing to FRESH air flow pressure taps (see diagram). Adjust the fresh air balancing damper until the fresh air flow is approximately the same as the EXHAUST air flow. If fresh air flow is less than exhaust air flow, then go back and adjust the exhaust balancing damper to equal the fresh air flow.
5.
Secure both dampers thumb screw in place with tape.
6.
Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, your name, phone number and business address).
NOTE: The unit is considered balanced even if there is a difference of ±10 cfm (or ± 5 l/s or 17 m³/h) between the two air flows.
- 21 -
8. CONNECTING THE DRAIN (HRV UNITS ONLY)
A
VD0181
From the inner side of the unit door, using the provided drain tube, punch out both drain holes (
A
).
VO0091
In order to keep the drain pan intact, hand tighten the 2 plastic drain fittings to the unit door using the gaskets and nuts as shown.
VO0092
Cut 2 sections of plastic tubing, about 12”
(305 mm) long and attach them to each drain fitting. Join the 2 short sections to the “T” junction and main tube as shown.
T
IE
-
WRAP
T
O DRAIN
VO009 3
Make a water trap loop in the tube to prevent the unit from drawing unpleasant odors from the drain source. Make sure this loop is situated BELOW the “T” as shown. This will prevent water from being drawn back up into the unit in case of negative pressure. Run the tube to the floor drain or to an alternative drain pipe or pail. Be sure there is a slight slope for the run-off.
- 22 -
9. MAINTENANCE
!
WARNING
Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
Since this guide covers both HRV and ERV units, top and side ports, the illustrations shown in the maintenance procedures are typical.
The following procedures applies for both HRV and ERV units.
Refer to pictures below to identify the inner parts of your unit.
3
3
3 3
4
4
2 2 2 2
1
1
VB0078
1) HRV
CORE
3) F
OAM FILTER BRACKETS
2) C
ORE RETAINERS
4) F
OAM CORE FILTERS
9.1 S
EMI
-A
NNUAL
M
AINTENANCE
VB0077
1) ERV
CORE
3) F
OAM FILTER BRACKETS
2) C
ORE RETAINERS
4) F
OAM CORE FILTERS
1.
Unplug the unit.
VD0005
!
!
WARNING
Be careful before opening the door; water or small debris could fall out. For HRV unit, always wait one minute after disconnecting the unit before opening the door in order to allow water to drain out from the unit.
2.
Unlatch the door and open it. Clean the inner side of the door with a damp cloth, then wipe with a dry one. Disengage the door from its hinge by sliding it from left to right and set aside.
VD0179
!
WARNING
Always hold the core when rotating the 2 core retainers; failure to do so will cause the core to fall out.
1
3.
Lift both foam filters bracket (
1
) and remove the foam filters from the core. While holding the core, rotate the 2 core retainers (
2
) and slide out the core from the unit.
2
1
VD0177
- 23 -
9. MAINTENANCE
(CONT’D)
9.1 S
EMI
-A
NNUAL
M
AINTENANCE
(
CONT
’
D
)
4.
Clean the inside walls of the unit with a clean damp cloth, then wipe with a clean dry one.
5.
Wash the 2 core filters under hot water with mild soap. Rinse thoroughly and let dry completely before reinstalling on the core.
6.
Remove the dust on the core using a vacuum cleaner and a soft brush attachment.
!
WARNING
Once the core reinstalled in the unit, always rotate both core retainers to their initial position; failure to do so will cause the core to fall out.
7.
Slide the core in the unit. Secure the core by rotating both core retainers to their initial positions.
VD0178
NOTE: Once the core reinstalled in the unit, the arrows (
A
) on its sticker label must be pointing towards the unit motors.
A
VB0078
8.
Reinstall both foam filters and secure them to the core by pulling down the 2 foam filter brackets. Reinstall the door.
9.
Close the door and plug the unit.
NOTE: The unit will return to its previous setting after a 30-second delay for boot sequence.
9.2 A
NNUAL
M
AINTENANCE
Do the same operations as the Semi-Annual Maintenance ( Section 9.1).Then, clean the exterior hood(s).
- 24 -
10. SERVICE PARTS
3
1
2
7
4
5
6
4
13
12
11
10
3
9
8
VL0019
I
TEM
D
ESCRIPTION
1 O
VAL PORT
(
FITS
5”
DIAMETER DUCTS
)
2 D
OOR LATCH WITH SCREWS
3 O
VAL PORT WITH INTEGRATED BALANCING DAMPER
4
M
OTOR
&
WHEEL ASSEMBLY
(
MOTOR CAPACITOR AND INLET RING INCLUDED
)
5 C
APACITOR
3 µ
F
6 E
LECTRONIC BOARD
7 ERV
FOAM FILTER
8 ERV
CORE
(
WITH
2
FILTERS
)
9 D
RAIN CONNECTOR KIT
10 D
OOR ASS
’
Y
11 HRV
CORE
(
WITH
2
FILTERS
)
12 HRV
FOAM FILTER
13 M
OTORIZED DAMPER PORT ASS
’
Y
14* T
RANSFORMER
15* G
REEN TERMINAL BLOCK
* P
ART NOT SHOWN
.
P
ART
N
UMBER
V16040
V16035
V16041
HRV90HS
(P
ORTS ON SIDES
)
1
2
2
HRV90HT
(P
ORTS ON TOP
)
1
2
2
ERV90HCS
(P
ORTS ON SIDES
)
1
2
2
ERV90HCT
(P
ORTS ON TOP
)
1
2
2
V16024
V17024
V16038
V16031
V16037
V03203
V16096
V16044
V16032
V16029
V16567
V16416
2
2
1
N/A
N/A
1
1
1
2
1
1
1
2
2
1
N/A
N/A
1
1
1
2
1
1
1
2
2
1
2
1
N/A
1
N/A
N/A
1
1
1
2
2
1
2
1
N/A
1
N/A
N/A
1
1
1
- 25 -
11. TROUBLESHOOTING
If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on the unit the problem occurs.
LED flashes GREEN.
LED flashes AMBER.
LED flashes RED.
• Thermistor error.
• Damper error.
• The door is open and the unit is not unplugged.
• Exhaust motor error.
Replace the entire port assembly (fresh air from outside port).
Go to Point 6.
Close the door and press once on the integrated control push button to reset the unit.
Go to Point 5.
Problems
1. Unit does not work.
2. The damper actuator does not work.
3. The wall control does not work OR the indicators flash.
4. The Humidity Control does not work OR the
20-minute push-button timer does not work OR its indicator light does not stay on.
5. The supply and/or exhaust motor do not work.
6. The defrost cycle does not work (the fresh air duct is frozen OR the fresh air distributed is very cold.
7. The integrated control push button does not work.
Possible causes
• The circuit board may be defective.
• The damper actuator or the integrated damper port mechanism may be defective.
You should try this
• Unplug the unit. Disconnect the main control and the auxiliary control(s) (if need be).
Jump G and B terminals. Plug the unit
NO C NC I OC OL Y R G B back and wait about 10 seconds. If the motors run on high speed and the
VE0097 damper opens, the circuit board is not defective.
• Unplug the unit. Disconnect the main control and the optional control(s) (if need be). Wait 10 seconds and plug the unit back. Check if the damper opens. If not, use a multimeter and check for 24V AC on J12-1 and J12-2
(in electrical compartment). If there is 24V AC, replace the entire port assembly.
NOTE: It is normal to experience a small delay (7-8 seconds) before detecting the 24V AC signal at starting-up. This signal will stay during 17-18 seconds before disappearing.
• If there is no 24V AC, replace the circuit board.
• The circuit board may be defective.
• The wires may be in reverse position.
• The wires may be broken.
• The wire in the wall OR the wall control may be defective.
• The wires may be in reverse position.
• The Humidity Control or push button may be defective.
• The circuit board may be defective.
• The motor(s) may be defective.
• Ensure that the color coded wires have been connected to their appropriate places.
• Inspect every wire and replace any that are damaged.
• Remove the wall control and test it right beside the unit using another shorter wire. If the wall control works there, change the wire. If it does not, change the wall control.
• Ensure that the color coded wires have been connected to their appropriate places.
• Jump the OL and OC terminals. If the unit switches to high speed, remove the
Humidity Control or push button and test it right beside the unit using another shorter
NO C NC I OC OL Y R G B wire. If it works here, change the wire. If it
VE009 8 doesn’t, change the Humidity Control or the push button.
• Press on the integrated control push button until the unit turn on low speed
(the LED will light AMBER). Using a multimeter, check the voltage on J4-1 and J4-2 (for supply motor), and on J5-1 and J5-2 (for exhaust motor). The reading must be ± 68 V AC. Then set the unit on high speed by pressing on the integrated control 1 more time (the LED will light GREEN). Using a multimeter, check the voltage on J4-1 and J4-2 (for supply motor), and on
J5-1 and J5-2 (for exhaust motor). The reading must be ± 120 V AC if the fan motor speed setting is Low-High, or ± 90 V AC if the fan motor speed setting is Low-Medium. If all the readings correspond to the right voltage values, the circuit board is not defective. If one or both readings are different, change the circuit board.
• Using a multimeter, check the ohms value on each motor connectors. For
BLUE and BLACK motor wires, the right value is ± 52 ohms. For BLUE and
BROWN motor wires, the right value is ± 72 ohms. For BROWN and BLACK motor wires, the right value is ± 124 ohms. If the ohm values are the same, the motor is not defective. Replace the motor capacitor.
• Ice deposits may be hindering the damper operation.
• The damper rod or the port damper itself may be broken.
• The damper actuator or circuit board may be defective.
• Remove the ice.
• Inspect these parts and replace if necessary.
• See point 2.
• The 30-second boot sequence is not completed.
• See Section 4.1.1 Boot Sequence.
- 26 -
Download
Advertisement