Operation Details
(1) The function of main control
1. Time Delay Safety Control
« 3min--- The compressor is ceased for minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
« 28ec + The indoor fan is ceased for 2sec. to prevent relay noise.
(Protection of fan relay and micro chip)
» 30sec - The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the
Heating operation is OFF or switched to the other operation mode.
2. Airflow Direction Control
* This function is to swing the louver up and down automatically and to set it at the desired position.
* The procedure is as the following.
1st; Press the ON/OFF Button to operate the product.
2nd; Press the Airflow Direction Control Button to swing the louver up and down automatically.
3rd; Repress the Airflow Direction Control Button to set the louver as the desired position.
Operating Mode Louver Position Horizontal 67
Coolin Start 2 Cooling 2 (Close)
9 Auto. Swing 174
| Start 5
heating Auto. Swing 3; 6 Heating 5
3. Cooling Mode Operation
* When selecting the Cooling (sk ) Mode Operation, the unit will operate according to the setting by the remote
controller and the operation diagram is as following.
Intake Air temp.
I NN
COMP. ON > TN
(SET TEMP.+0.5°C)
COMP. OFF
(SET TEMP.-0.5°C) More than More than
3 minutes 3 minutes
Selecting | Selectig Selecting
ow Low
INDOOR FAN SPEED fan speed fan speed fan speed
COMPRESSOR ON OFF ON OFF ON
4. Cooling or Heating Mode with Sleep Mode Auto Operation
* When selecting the Cooling( 3k ) or the Heating( 3¢ ) combined with the Sleep Mode Auto Operation( s& ),
the operation diagram is as following.
- 12 -
* Cooling Mode with the Sleep Mode
fUThe setting temperature will be raised by 1 C 30minutes later and by 2°C 1 hour later.
fU The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
30 minutes 30 minutes
< pig
Intake Air temp. + di
|] A
1%
COMP. ON > Ny : SA
(SET TEMP. +0.5°C JS
COMP. OFF e
(SET TEMP. -0.5°C More than More than
3 minutes 3 minutes
INDOOR FAN SPEED Low Low Low Low Low
COMPRESSOR ON OFF ON OFF ON
» Heating Mode with the Sleep Mode.
fU The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.
SETTING TEMP. +3°C >
(COMPRESSOR OFF)
SETTING TEMP.
(COMPRESSOR ON)
INDOOR FAN SPEED Med. Low or OFF Med. Low or OFF Med. Low or OFF
COMPRESSOR ON OFF ON OFF ON OFF
- 13 -
5. Auto Operation
* The operation procedure is as following.
| Press Start/Stop Button |
Y
| Select Auto Operation Mode |
Y
| Check the Room temperature |
y
Operation mode
Indoor fan speed
Setting temperature —
—are automatically decided by Fuzzy rule.
Intake-air Over - below
temperature below 21°C 21°C 24°C Over 24%
Operation Mode Heating Soft Dry Cooling
* If initial mode is decided, that mode is continued despite of the room temperature changing.
S Fuzzy Operation for Cooling
Operation Condition
Intake-air Temperature
Setting Temperature
Fan Speed
Air DirectionControl
When Auto Operation
initial start
Over 26°C
25°C
Over 24 C-below 26°C
Intake air -1 °C
Qver 22°C~below 24°C
Intake air -0.5°C
1/f rhythm
Over 20°G-below 22% | Intake air temperature | Controlled by
below 20°C 20°C Fuzzy logic
Over 20°C~below 30°C Fuzzy control
When Switch to Auto
Operation below 20°C 20°C
over 30°C 30°C
Intake Air temp. ——
Setting Temp. +0.5°C р» ZT
(Compressor OFF)
Setting Temp. -0.5°C
(Compressor ON)
INDOOR FAN SPEED Fuzzy Speed
COMPRESSOR ON OFF ON OFF
- 14 -
m Auto Operation for Soft Dry
The Setting temperature will be set to the same that of the current intake-air temperature.
- Compressor ON temperature; Setting temperature +1°C
- Compressor OFF temperature; Setting temperature -0.5°C
m Auto Operation for Heating
Intake Air temp.
below 20°C
Over 20°C~below 21°C
Setting temp.
20°C
Intake air temperature +0.5°C
- 15 -
. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol-
lowing.
For 7K, 9K, 12K Models
Intake Air temp. J
Setting temp. +3°C pl
(Compressor OFF)
Setting temp. IL N
(Compressor ON) = N
minimum minimum minimum
et
10sec. 10sec. 10sec.
Hot
Start
Selecting Selecting
INDOOR FAN SPEED OFF fan speed LOW OFF LOW fan speed LOW OFF
COMPRESSOR ON OFF ON OFF
* А point; The indoor pipe temperature to be 35°C.
The indoor fan operates minimum 10sec. even if falls lower than 35°C.
* В point; The indoor pipe temperature to be 35°C.
The indoor fan operates minimum 10sec. even if falls lower than 35°C.
. Hot-Start Control
* The indoor fan stops until the evaporator piping temperature will be reached at 28°C. (BY TEMPERATURE)
« The operation diagram is as following.
PIPE
TEMP 28°C
60 sec.
INDOOR
OFF LOW SELECTING
FAN SPEED FAN SPEED
COMPRESSOR ON
HOT-START BY TEMPERATURE
- 16 -
8. Deice Control
FU Deicing operation is controlled by timer and sensing the indoor pipe temperature.
fU Deicing operation checks the indoor pipe temperature and Intake-air temperature at 25 minutes and 60 minutes
on starting of heating operation, and discriminates by temperature difference.
fu When the heating operation passed 25 minutes, the temperature (; T1=TE1-TR1) is checked and memorized
with checking the indoor pipe temperture (TE1) and the indoor Intake-air temperature (TR1).
fU When the heating operation passed 60 minutes, deicing operation checks the indoor pipe temperature (TE2)
and the indoor Intake-air temperature (1TR2), and checks indoor pipe temperature(TE2), the temperature
difference (; T2=1E2-1R2) and the temperature difference ; Td(=; T1-; T2)of ; T1, ; T2.
If temperature of indoor pipe is below 32°C Deicing function operates at the priority | condition.
If temperature of indoor pipe is over 32°C Deicing function operates at the priority || condition.
If the temperature difference (; Td) become more than the option temperature, deicing operation starts.
fU At that time, deicing operation time is decided.
fU The deicing operation time starts after deicing operation started.
FU If deicing operation start, above heating operation time is reset, so if deicing operation is finished, the heating
operation time is recounted.
fU The deicinig time and the operation diagram are as following.
60 minutes
TEMP °C -
25 mins 25 mins
TE1
TE?
AT AT2 AT? AT
Pipe Temp. >
Intake Air Pp» Hot
Temp. Е
Heating Deicing | Start Heating
FO - mm mm mmm ja -------——— Doll -- e ------———---"----essssss ss =
COMPRESSOR ON ON ON ON
4-WAY VALVE ON(Heating Operation) OFF ON ON
OUTDOOR FAN ON OFF ON ON
INDOOR FAN ON OFF ON
DEICE LED OFF ON OFF
(DEICING DIAGRAM)
Y L Priority |
TE? below 30°C 30-31 © 31-32 C Over 32°C
Deicing Time 12mins 11mins 10mins Heating Operation
YMPriority Il
SET 1-SEI 2=SEI d Over 3.5°C 3.0; »3.5°C 2.5; »3.0°C 2.0; ›2.5°С below 2.0°C
Deicing Time 12mins 11mins 10mins 9mins Heating Operation
- 17 -
9. Soft Dry Operation.
During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor
OFF temperature is the setting temperature minus 0.5°C.
* When the room temperature rises over the compressor ON temperature, the operation mode is switched to the
cooling mode.
* When the room temperature falls between the compressor ON temperature and OFF temperature, the operation
mode is switched to the Soft Dry Operation.
In this temperature range, 10min. Dry operation, 5.5min operation OFF, 1.5min. only fan operation repeat. During
10min Dry operation, even if the room temperature falls below compressor OFF temperature, 10min(MAX)
Compressor ON from starting of Dry operation which includes 4 min. Compressor ON operation below the com-
pressor OFF temperature.
< IN micom dehumidify mode, control of fan speed is as following.
Operation
ROOM TEMP. Cooling Dry operation
| ef | >
SETTING TEMP.+1°C №
(COMP. ON) maximum
4 minutes
SETTING TEMP.-0.5°C
(COMP. OFF) 1 minutes 10 1.5 minutes
| minutes |
2 minutes i maximum
5.5 minutes 10 minutes
Selectin
INDOOR FAN SPEED fan speed OFF ¡LOW LOW OFF LOW LOW
COMPRESSOR ON OFF ON OFF ON
10. Forced operation
* |f you lose wireless remote controller, you can operate the unit with forced operation switch.
* The standard conditions are as following.
Heat pump Model
Cooling Model
Room Temp ¡;* 24% | 21% ; Room Temp- 24°C Room Temp - 21%
Operation Mode Cooling Cooling Soft Dry Heating
Indoor Fan Speed High High Low High
Setting Temp. 22°C 22°C Room Temp. 24°C
- 18 -
Operation
(1) Name and Function-Remote Control
1) Cooling Model
Remote Controller
Signal trasmitter
Transmits the signals
to the room air conditioner.
ДЖО АЕ 3+
22086.
Gussie. ©
ONE OFFER N
On:
18:88 ;-18:88
-AOperation display
Displays the operation conditions.
~BStart/Stop Button
Operation starts when this button is pressed, and
stops when the button is pressed again.
-COperation Mode Selection Button
Used to select the operation mode.
* Cooling Operation Mode.
* Soft Dry Operation Mode.
* Auto Operation Mode.
-DON Timer Button
Used to set the time of starting operation.
“E OFF Timer Button
Used to set the time of stopping operation.
-F Time Setting Button
Used to adjust the time.
-GTimer Set Button
Used to set the timer when the desired time is
obtained.
~HTimer CANCEL Button
Used to cancel the timer operation.
~1 Sleep Mode Auto Button
Used to set Sleep Mode Auto Operation.
~J Fan Operation Button
Used to circulate room air without cooling.
-K Room Temperature Checking Button
Used to check the room temperature.
~1. Vertical Airflow Direction Control Button
Used to set the desired vertical airflow direction.
~M Reset Button
- 38 -
2) Heating Model
Remote Controller
Signal trasmitter
Transmits the signals
to the room air conditioner.
За В.
ONE OFF EE < ||
10:88 = 16:66
-AOperation display
Displays the operation conditions.
~BStart/Stop Button
Operation starts when this button is pressed, and
stops when the button is pressed again.
-COperation Mode Selection Button
Used to select the operation mode.
* Cooling Operation Mode.
* Soft Dry Operation Mode.
* Auto Operation Mode.
* Heating Operation Mode.
~DON Timer Button
Used to set the time of starting operation.
~EQOFF Timer Button
Used to set the time of stopping operation.
"Fr Time Setting Button
Used to adjust the time.
~G Timer Set Button
Used to set the timer when the desired time is
obtained.
~HTimer CANCEL Button
Used to cancel the timer operation.
-ISleep Mode Auto Button
Used to set Sleep Mode Auto Operation.
~J Fan Operation Button
Used to circulate room air without heating.
-KRoom Temperature Checking Button
Used to check the room temperature.
~1, Vertical Airflow Direction Control Button
Used to set the desired vertical airflow direction.
~1 Reset Button