Alkco UV-C Louvered Wall Guide

Add to My manuals
12 Pages

advertisement

Alkco UV-C Louvered Wall Guide | Manualzz

Step 03: Documentation and Deliverables

Deliverables:

1.

Mechanical / Electrical Installation report (reporting if the luminaires were correctly installed, following mounting instructions and design guidance)

2.

Visual / photographic inspection (confirming if all elements noted during the audit still valid)

3.

Confirmation that visual markers (stickers to be placed on the wall and luminaire) are proper placed as per mounting instructions.

4.

Irradiance measurements (in excel or PPT, preference typed, not scanned).

5.

Effectiveness measurements - In the beam (Step 01)

6.

Eye Level Safety and compliance - Out of the beam (Step 02) at

1.7m or the height used in the design.

7.

All documentation, including Acceptance Certificate signed by

Customer, is uploaded in the dedicated Customer Portal, that is available if there is a Service Contract in place (via C4CS ticket to the C-ROC).

08 2020-1130 Rev. 00 UV-C Upper Air Commissioning and (recurrent) Measurement Guidelines

Germicidal UV

Upper Air

Commissioning and

Ongoing Maintenance

Measurement Guidelines

November 30, 2020

Before You Begin:

Read and understand this entire guide, the luminaire installation instructions, and any sitespecific documents before attempting to install, commission or operate these luminaires.

Failure to read and follow all provided instructions may result in damage or injury.

It is the responsibility of the installer to ensure that persons will not be exposed to excessive UV radiation during equipment operation. This will require the installer to conduct an assessment of irradiance levels per the instructions listed in this document within the surrounding occupied spaces prior to occupancy and to repeat assessment whenever relamping is completed.

This document applies to following products:

Alkco U2C - Germicidal UV 2x2 Grid Ceiling Mount

Alkco UWL - Germicidal UV Louvered Wall Mount

General Instructions and Materials Required

Step 01: Establish Baseline

Step 02: Eye Level Safety measurements

Step 03: Documentation and Deliverables

Final Notes and Appendices

Germicidal UV 1

General Instructions and Materials Required

03

03

Upper Air Germicidal Radiation

Upper Air Germicidal

UV radiation measurements

Upon initial installation

Materials: room or upper air installation conditions

• Long sleeve shirt

• Whenever any reports or complaints of possible

Safety glasses with side panels

Trousers and closed toe shoes

Skin protecting gloves

• Ladder

Tripod

General Instructions and Materials must be taken:

General Instructions and Materials overexposure are received or reasonably expected field-of-view. - Gigahertz -Optik

Required Materials

Rev. 00

• etc.)

PPE:

• Tripod

• Measuring tape and documentation materials

Upper Air Germicidal Radiation

Measurements should be taken:

• Upon initial installation

• Upon initial installation

Upper Air Germicidal Radiation

• Ladder

Upon initial installation

Whenever new tubes are installed

PPE:

neck,face and other areas of exposed skin)

Personal protective equipment (PPE):

Whenever any complaints of possible overexposure are received

• Upon initial installation

• Whenever new tubes are installed

• etc.)

Materials:

PPE:

• Ladder

• Tripod

Long sleeve shirt

PPE:

2020-1130 field-of-view. - Gigahertz -Optik

neck,face and other areas of exposed skin) [1]

µW/cm² calibrated to second decimal (0.01 µW/cm²)

[1]

UV-3725-4 Radiometric Detector. UV-C 254nm irradiance with cosine corrected

Skin protecting gloves

neck,face and other areas of exposed skin) [1]

03

• Sunblock cream (containing either zinc oxide or titanium dioxide for head,

PPE:

Whenever modifications are made to the room or Upper Air installation conditions

(e.g. height, position, change of walls or ceiling material, room dimension changes,

• Skin protecting gloves

Sunblock cream (containing either zinc oxide or titanium dioxide for head,

neck,face and other areas of exposed skin) [1] field-of-view. - Gigahertz -Optik

[2][3][4]

UV- 3718Z-01 Detector Accy: 80° FOV adapter for UV-3718 detector

For output (Step 01): range of 1-50µW/cm², calibrated at first decimal (0.1 µW/cm²)

µW/cm² calibrated to second decimal (0.01 µW/cm²)

UV-3725-4 Radiometric Detector. UV-C 254nm irradiance with cosine corrected

Measuring tape and documentation materials

2020-1130 Rev. 00

• UV- 3718Z-01 Detector Accy: 80° FOV adapter for UV-3718 detector [2][3][4]

[2][3][4]

[1]

Figure 2 and 3 (bottom and right) are the detector head and the detector head with the 80 degree field-of-vision attachment. tachment.

UV- 3718Z-01 Detector Accy: 80° FOV adapter for UV-3718 detector

• For output (Step 01): range of 1-50µW/cm², calibrated at first decimal (0.1 µW/cm²)

• For safety assessments (Step 02): lower range, for measuring safety level at 0,2

µW/cm² calibrated to second decimal (0.01 µW/cm²)

[1]National Institute for Occupational Safety and Health. Atlanta, GA: National Institute for Occupational Safety and Health; 2009. Environmental control of tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings.

[2] ICNIRP (2007) Protecting Workers from Ultraviolet Radiation

[1]National Institute for Occupational Safety and Health. Atlanta, GA: National Institute for Occupational Safety and Health; 2009. Environmental control of tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings.

[2] ICNIRP (2007) Protecting Workers from Ultraviolet Radiation

[3] End TB Transmission (ETTI) (2019) Maintenance of Upper-Room Germicidal Ultraviolet (GUV) Air Disinfection Systems for TB Transmission Control, Stop

TB Partnership, Geneva, Switzerland. www.stoptb.org/wg/ett/resources.

[4]ACGIH. (2017). TLVs® and BEIs®. American Conference of Governmental Industrial Hygienists, Cincinnati, OH.

(sold separately) tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings.

[2] ICNIRP (2007) Protecting Workers from Ultraviolet Radiation

- Gigahertz - Optik dim

UV-C Upper Air Commissioning and (recurrent) Measurement Guidelines

[1]National Institute for Occupational Safety and Health. Atlanta, GA: National Institute for Occupational Safety and Health; 2009. Environmental control of

Calibrated X1-5 Optometer

TB Partnership, Geneva, Switzerland. www.stoptb.org/wg/ett/resources.

Figure 1 (above) are the recommended handheld radiometer and detector.

Figure 2 and 3 (bottom and right) are the detector head and the detector head with the 80 degree field-of-vision attachment.

Figure 1 (above) are the recommended handheld radiometer and detector.

Figure 2 and 3 (bottom and right) are the detector head and the detector head with the 80 degree field-of-vision at-

[1]National Institute for Occupational Safety and Health. Atlanta, GA: National Institute for Occupational Safety and Health; 2009. Environmental control of tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings.

[2][3][4] tachment.

TB Partnership, Geneva, Switzerland. www.stoptb.org/wg/ett/resources.

[4]ACGIH. (2017). TLVs® and BEIs®. American Conference of Governmental Industrial Hygienists, Cincinnati, OH.

[1]National Institute for Occupational Safety and Health. Atlanta, GA: National Institute for Occupational Safety and Health; 2009. Environmental control of tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings.

[2] ICNIRP (2007) Protecting Workers from Ultraviolet Radiation

[3] End TB Transmission (ETTI) (2019) Maintenance of Upper-Room Germicidal Ultraviolet (GUV) Air Disinfection Systems for TB Transmission Control, Stop en

Figure 1 (above) are the recommended handheld radiometer and detector.

Figure 2 and 3 (bottom and right) are the detector head and the detector head with the 80 degree field-of-vision at-

Measuring tape and documentation materials

2020-1130 Rev. 00 UV-C Upper Air Commissioning and (recurrent) Measurement Guidelines

• Safety glasses with side panels Ladder and Tripod

• Long sleeve shirt, long pants and closed toe shoes

• Step 1: For output range of

1-50μW/cm², calibrated at first decimal (0.1 μW/cm²)

• Skin protecting gloves

• Sunblock cream 1

(containing either zinc oxide or titanium dioxide for head, neck,face and other areas of exposed skin)

• Step 2: For measuring safety level at 0.2 μW/cm² calibrated to second decimal (0.01 μW/cm²)

UV-3725-4 Radiometric

Detector. UV-C 254nm irradiance with cosine corrected field-of-view.

Gigahertz -Optik

UV- 3718Z-01 Detector

Accy: 80° FOV adapter for UV-3718 detector 2,3,4

1. National Institute for Occupational Safety and Health. Atlanta, GA: National Institute for Occupational Safety and Health; 2009.

Environmental control of tuberculosis: basic upper-room ultraviolet germicidal irradiation guidelines for healthcare settings.

2. ICNIRP (2007) Protecting Workers from Ultraviolet Radiation

3. End TB Transmission (ETTI) (2019) Maintenance of Upper-Room Germicidal Ultraviolet (GUV) Air Disinfection Systems for TB Transmission Control, Stop TB Partnership, Geneva, Switzerland. www.stoptb.org/wg/ett/resources.

4. ACGIH. (2017). TLVs® and BEIs®. American Conference of Governmental Industrial Hygienists, Cincinnati, OH.

Premeasurement Actions

• Prior to the installation, Signify recommends 100hr burn-in of the lamps.

Once the burn-in is complete, the lamps will be stable and considered a baseline for commissioning measurement.

1 Failure to complete the 100hr burn-in could result in higher initial readings. The space should never be occupied by humans or pets prior to completing all measurements.

• Make sure you have the latest site documents including latest architectural and electrical drawings, simulated calculation report (if performed), list of surface materials and reflectance values (see Appendix B), site audit notes or previous measurements (if applicable) to compare with the current situation.

• Check if the usage of the space (occupant tasks, hours occupied, etc) is the same as it was when the system was designed. If there is a change, register it.

• Look for obstacles (hanging from the ceiling or higher objects from the floor) that may interfere with the UV-C light, register them.

• Check if there are nearby items (smoke detectors, alarms, projectors, wi-fi routers, etc.) with materials or paint that can be degraded by UV-C and advise the customer.

• Energize luminaires and allow to stabilize for 10 minutes prior to beginning any measurements.

• Thoroughly clean the sensor lens according to sensor manufacturer instructions or with Isopropyl Alcohol before beginning measurements.

• Look for standard luminaires installed in the ceiling directly in the irradiance path that may reflect light into the occupied zone. Signify recommends moving or removing these.

1. ASHRAE GPC 37 (Draft).

Germicidal UV 3

Step 01: Establish Baseline

Figure 1

Figure 1: The detector is raised and lowered to find maximum output (irradiance) of the UV beam for recording output. If allowed, permanent marker on the floor would facilitate repeat measurement. Or use a yard/meter stick between the face of the luminaire and the GUV radiometer’s detector.

Instructions for Measuring

1. Acquire all necessary PPE.

2. Zero the UV meter according to the meter manufacturer’s instructions.

3. Remove the cap and position the sensor 3ft (0.91m) from the center of the upper-room GUV luminaire.

1

4. Point the sensor probe vertically, aiming in the beam of the luminaire, the center of the sensor should be in the center of the UV-C beam.

5. Record the reading in the log book, this is the initial baseline output to be referenced by all future readings after replacement lamps are installed.

6. Repeat steps 1-5 at 6ft (1.83m) from the center of the upper-room GUV luminaire.

7. If measuring during relamping and after initial installation, compare results to baseline measurements. If value is less than baseline reading, take corrective action by cleaning the lamp and fixture. If value is more than baseline reading, make sure proper wattage lamp is being installed. .

1,2

Note: Upon luminaire relamping and/or cleaning, changes to site conditions

(painting, installation of new luminaire in the irradiance path, changing or resurfacing reflective surfaces, installation of obstructions in the irradiance path, etc.) and/or changes to site usage, repeat steps 1-7.

1. End TB Transmission (ETTI) (2019) Maintenance of Upper-Room Germicidal Ultraviolet (GUV)

Air Disinfection Systems for TB Transmission Control, Stop TB Partnership, Geneva, Switzerland. www.stoptb.org/wg/ett/resources.

2. Nardell EA, Bucher SJ, Brickner PW, Wang C, Vincent RL, Becan-McBride K, James MA, Michael

M, Wright JD. Safety of upper-room ultraviolet germicidal air disinfection for room occupants: results from the Tuberculosis Ultraviolet Shelter Study. Public Health Rep. 2008;123:52–60 w.

4 ALKCO

Step 02: Eye Level Safety measurements

Instructions for Measuring

1. Create a grid of measurements on the floor, placing the tripod at an equally-spaced distance

(see table to the right).

2. Place the tripod head at the default 6ft (1.83m) or acceptable eye level for the tasks that take place in the space.

3. Make sure to use the 80° field of view adapter on the detector for these measurements.

4. At each grid point, take five measurements.

• For the first measurement, orient the detector

(normal of the detector surface) horizontally

(pointed at ceiling).

• Next, orient the detector vertically, pointing straight ahead along the typical line of sight for measurements in all directions

(north, east, south, west).

5. Record the location of all measured points, clearly highlight if any measurement is higher than the maximum agreed upon value for the application

(based on the Maximum Permissible UV-C Exposure guidelines in Appendix A).

2 Corrective action needs to be taken and system should not be released for use until measurements are in alignment with

Appendix A dosage recommendations.

Measurement Grid

Space

Length

(ft/m)

Maximum grid spacing

(ft/m)

<6ft/<1.83m

6-24ft/2-7.5m

1.5ft/0.5m

3ft/0.91m

24-65ft/7.5-20m 4.5ft/1.5m

>65ft/>20m 6ft/1.83m

Minimum grid points

10

15

4

5

• The larger the area, the bigger the distance between measurement points.

• Grid should not align with luminaire layout.

• If a simulated calculation of the space has been provided, the measurement grid may follow the simulated grid points for correlation.

• Reduce grid distance:

- Where multiple luminaire are combining energy 3

- Wherever highly reflective surfaces might be found 4

- At task areas

Sensor Orientation

Horizontal

1. ICNIRP (2007) Protecting Workers from Ultraviolet Radiation.

2. See Appendix A.

3. End TB Transmission (ETTI) (2019) Maintenance of Upper-Room Germicidal Ultraviolet (GUV)

Air Disinfection Systems for TB Transmission Control, Stop TB Partnership, Geneva, Switzerland. www.stoptb.org/wg/ett/resources.

4. See Appendix B.

Vertical

Germicidal UV 5

Step 02: Eye Level Safety measurements

Figure 2

Figure 2: Technician checking eye level safety with GUV radiometer.

Searching for the hot-spots at eye level using a hand-held radiometer and sensor with 80 degree field-of-view cover to mimic the structure of the brow and eye.

Figure 3: A tape measure is recommended to set the tripod to

6ft (1.83m).

Figure 4: A tripod is recommended for easy repetitive measurements at 6ft (1.83m) along the grid.

Figure 5: Measuring along the line of eye sight of the occupant.

6 ALKCO

Figure 3

Figure 4

Figure 5

Step 03: Documentation and Deliverables

Deliverables:

1.

Mechanical / Electrical Installation report (reporting if the luminaires were correctly installed, following mounting instructions and design guidance)

2.

Visual / photographic inspection (confirming if all elements noted during the audit still valid)

3.

Confirmation that visual markers (stickers to be placed on the wall and luminaire) are proper placed as per mounting instructions.

4.

Irradiance measurements (in excel or PPT, preference typed, not scanned).

5.

Effectiveness measurements - In the beam (Step 01)

6.

Eye Level Safety and compliance - Out of the beam (Step 02) at

1.7m or the height used in the design.

7.

All documentation, including Acceptance Certificate signed by

Customer, is uploaded in the dedicated Customer Portal, that is available if there is a Service Contract in place (via C4CS ticket to the C-ROC).

08 2020-1130 Rev. 00 UV-C Upper Air Commissioning and (recurrent) Measurement Guidelines

Step 03: Documentation and Deliverables

1. Mechanical / Electrical Installation report

(reporting if the luminaires were correctly installed, following mounting instructions and design guidance).

2. Visual / photographic inspection

(confirming if all elements noted during the audit are still valid).

3. Irradiance measurements should be recorded and saved

(recorded in XLS, PPT or Word – not scanned handwritten values).

4. Baseline Measurements – in the beam (Step 01).

5. Eye Level Safety and compliance - Out of the beam (Step 02) at 6ft (1.83m) or the height used in the design.

6. All documentation should be made available to all parties involved

(installing/commissioning contractor, distributor, owner) and saved in a secure location for future reference.

Germicidal UV 7

Final Notes and Appendices

Dosing Recommendation

Maximum permissible UVC exposure

This international standard adopts the REL 1 maximum permissible UVC exposure values and the maximum permissible UVC exposure shall not exceed the ACGIH

TLH and NIOSH REL 1 of 6.0 mJ/cm 2 for an 8 hour day,

40 hour work week exposure to UV radiation at 254 nm.

2,3

Maximum permissible UVC exposure for radiation at 254 nm

Permissible UVC exposure time

24 hours

18 hours

12 hours

10 hours

8 hours

4 hours

2 hours

1 hour

30 minutes

15 minutes

10 minutes

5 minutes

1 minutes

30 seconds

15 seconds

5 seconds

1 second

Effective irradiance

µW/cm

0.07

0.4

0.8

1.8

3.3

0.09

0.14

0.17

0.2

6.7

10

20

100

200

400

1200

6000

2

<0.8 µW/cm operating

3 range for TLV assessments

>0.8 µW/cm is not allowable for design acceptance criteria and

3 commissioning

Threshold Limit Value ® (TLV ® ) consideration should be based on real-time occupancy of spaces treated by UVGI.

3

This recommendation is supported by recent UV monitoring data from First and Colleagues 4 , who founded that peak meter readings poorly predict actual exposure of room occupants.

1. CDC/NIOSH. Recommended Exposure Limit. REL, 2005

2. NIOSH. Criteria for a recommended standard: Occupational exposure to ultraviolet radiation

Publication 73-11009. National Institute for Occupational Safety and Health, Washington, D.C, 1972

3. ACGIH. 2007. TLVs® and BEIs®. American Conference of Governmental Industrial Hygienists,

Cincinnati, OH

4. First M.W., Weker R.A., Yasui S., Nardell E.A. Monitoring human exposures to upper-room germicidal ultraviolet irradiation. J. Occup. Environ. Hyg. 2005, 2 pp. 285–292

8 ALKCO

UVC radiation reflectance

Material Refl. (%)

Aluminium: untreated surface

Aluminium: treated surface

40-60

60-89

Aluminium: sputtered on glass

“ALZAK” treated aluminium

“DURALUMIN”

75-85

65-75

Stainless steel

/Tin plate

16

25-30

Chromium plating 39

Various white oil paints

3-10

Various white water paints

Aluminium paint

Zinc oxide paint

Black enamel

White baked enamel

10-35

40-75

4-5

5

5-10

White plastering 40-60

Magnesium oxide 55-60

Calcuim carbonate 75-88

Linen 70-80

Bleached wool

Bleached cotton

17

4

Wallpapers: Ivory 30

Wallpapers: white 31

Wallpapers: white 21-31

31 Wallpapers: red printed

Wallpapers: ivory printed

26

Wallpapers: brown printed

White notepaper

18

25

Reed NG, Wengraitis S, Ultraviolet Spectral

Reflectance of Ceiling Tiles, and Implications for the Safe Use of Upper-Room Ultraviolet

Germicidal Irradiation Photochemistry &

Photobiology 2012, 88: 1480-1488

Ceiling tiles reflectance values

ID

Incl specular

Excl specular

A 0.035±0.001

0.034

B 0.043±0.002 0.041

C 0.048±0.001

0.047

D 0.051±0.001

0.05

E 0.052±0.002 0.047

F 0.055±0.006 0.054

G 0.060±0.002 0.059

H 0.064±0.004 0.062

I 0.070±0.001

0.065

J 0.071±0.005

0.071

K 0.071±0.001

0.069

L 0.074±0.001

0.071

M 0.076±0.003 0.067

N 0.096±0.003 0.041

O 0.106±0.006 0.047

P 0.107±0.024

0.05

Q 0.122±0.007

0.047

R 0.151±0.008

0.054

S 0.152±0.009

0.059

T 0.165±0.021

0.062

U 0.237±0.011

0.065

V 0.240±0.033 0.071

W 0.240±0.063 0.069

X 0.244±0.023 0.071

Y 0.245±0.070 0.067

Z 0.260±0.048 0.288

AA 0.260±0.035 0.243

BB 0.273±0.007

0.274

CC 0.275±0.016

0.28

DD 0.276±0.013

0.283

EE 0.276±0.026 0.29

FF 0.282±0.029 0.306

GG 0.334±0.024 0.333

HH 0.353±0.031

0.363

II 0.362±0.028 0.364

JJ 0.423±0.103

0.41

KK 0.459±0.015

0.438

Final Notes and Appendices

Ceiling tile information

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Certain-Teed

Certain-Teed

Certain-Teed

Certain-Teed

Certain-Teed

USG

USG

Manufacturer Item Name

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Armstrong

Item No.

Materials Notable surface features ID

Armatuff

Ceramagurad

Cirrus

860

605

574

Cirrus (camel)

Cirrus (platinum)

Clean Room Mylar

Clean Room VL

Cortega

Crossgate

Dune

Endura

Fine Fissured School Zone 1714

Fine Fissured (camel) 1729

Fine Fissured (haze) 1729

589

589

1721

870

769

2625

1772

639

Wet-formed high-density mineral fiber Latex paint

Ceramic and mineral fiber composite

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Latex paint

Latex paint

Soil-resistant polyester film G

Vinyl-faced membrane K

S

X

Wet-formed mineral fiber

Wet-formed mineral fiber

Latex paint

Latex paint

Wet-formed mineral fiber Latex paint

Wet-formed high-density mineral fiber Vinyl latex paint

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Fine Fissured (techblack) 1729

Fine Fissured (white) 1729

Fine Fissured Open Plan

Georgian

1754

17

Graphis

Latitudes

Ledges

Mesa

Optima

1753

8005

8011

680

3151

Painted Nubby

Pebble

Random Fissured

Sansera

Shasta

Stratus

VL

Ecophon Gedina E

Fine Fissured High NRC

Symphony F

Theatre Black F

Vinyl Rock

Astro Climaplus

Brio Climaplus

3101

2989

2910

573

2906

531

871

454

134,2,4

1910,2 Fiberglass

1140,2-CRF-1 Gypsum

Mineral fiber

Mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Wet-formed mineral fiber

Fiberglass with acoustically transparent membrane

Fiberglass

Fiberglass

Fiberglass

Embossed wet-formed mineral fiber

Fiberglass

Wet-formed mineral fiber

Wet-formed mineral fiber

Fiberglass

Wet-felted mineral fiber

Fiberglass

Scrubbable plastic finish

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Latex paint

Acoustically transparent membrane and latex paint

Latex paint

Latex paint

Latex paint

Vinyl-faced membrane

Sound-resistant coating

R

KK

HH

FF

T

DD

V

AA

U

GG

EE

N

Scrubbable vinyl film facing F

Latex paint

Scrubbable vinyl film facing H

Latex paint

Laminate

Laminate

Scrubbable vinyl film facing

I

P

E

J

W

B

D

Z

II

CC

Y

JJ

L

BB

M

C

A

Q

Q

Note: All tiles are white unless noted in parentheses next to the model, or in the model name itself; ID used to identify specific tiles in Figures, Tables, and text.

Germicidal UV 9

© 2020 Signify Holding. All rights reserved. The information provided herein is subject to change, without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract, unless otherwise agreed by Signify.

All trademarks are owned by Signify Holding or their respective owners.

SGn-2032BR 01/21 www.signify.com/uv-c

Signify North America Corporation

200 Franklin Square Drive,

Somerset, NJ 08873

Telephone 855-486-2216

Signify Canada Ltd.

281 Hillmount Road,

Markham, ON, Canada L6C 2S3

Telephone 800-668-9008

advertisement

Related manuals

advertisement