Allen-Bradley 1734 User Manual
Below you will find brief information for 1734 POINT I/O 1734-AENT. It provides connectivity to EtherNet/IP networks for POINT I/O modules and serves as a bridge between these modules and the network. It offers features like EtherNet/IP messaging within TCP/UDP/IP, a common application layer with ControlNet and DeviceNet and communication via Category 5 cable.
Advertisement
Advertisement
User Manual
1734 POINT I/O EtherNet/IP Adapters
Catalog Number 1734-AENT, Series B
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/ ) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, ArmorPOINT, ControlLogix, Logix5000, POINT I/O, RSLinx, RSLogix 5000, Studio 5000, Studio 5000 Automation Engineering & Design Environment, Studio 5000 Logix
Designer, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
New and Updated
Information
Summary of Changes
This manual contains new and updated information. Changes throughout this revision are marked by change bars, as shown to the right of this paragraph.
This table contains the changes made to this revision.
Topic
Added Thumbwheel Settings section.
Updated Set the Chassis Size section with a new example and information on the different ways you can set the chassis size.
Added Set the Chassis Size by Using the Thumbwheels section.
Updated Set the Network Address section with information about how to use a pen tip to set the thumbwheels.
Page
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 iii
Summary of Changes
Notes:
iv Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Table of Contents
Summary of Changes
Preface
About the Example Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Common Techniques Used in this Manual . . . . . . . . . . . . . . . . . . . . . . . . . xii
Chapter 1
Overview of the 1734 POINT I/O
EtherNet/IP Adapter
Empty Slots and RIUP Situations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Up a System for the First Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Use of the Common Industrial Protocol (CIP) . . . . . . . . . . . . . . . . . . . . . . . 8
Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . . . . . . 9
Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Support for Rack-optimization, Enhanced Rack-optimization, and Direct
Mixing Rack-optimization, Enhanced Rack-optimization, and Direct
Determine Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Install Your 1734 POINT I/O
EtherNet/IP Adapter
Chapter 2
Mount the POINT I/O Adapter on a DIN Rail. . . . . . . . . . . . . . . . . 14
Install POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Remove POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Wire a POINT I/O Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 v
Table of Contents
Chapter 3
Configure the Adapter with
RSLogix 5000 or Logix Designer
Software
Set the Network Address for POINT I/O Adapters . . . . . . . . . . . . . 24
Use the Rockwell BootP/DHCP Utility. . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Use DHCP Software to Configure Your Adapter . . . . . . . . . . . . . . . . . . . 29
Chapter 4
Configure the Adapter for Direct
Connection in RSLogix 5000 or
Logix Designer Software
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 35
Add the POINT I/O Adapter to the I/O Configuration. . . . . . . . . . . . . 38
Add the POINT I/O Modules to the I/O Configuration . . . . . . . . 41
Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Configure the Adapter with Fixed IP Address. . . . . . . . . . . . . . . . . . . . . . . 52
Recover From an Overloaded Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 5
Configure the Adapter for Direct
Connection, Rack Optimization, and Enhanced Rack
Optimization in RSLogix 5000 or
Logix Designer Software
Set Up the POINT I/O Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 58
Add the POINT I/O Adapter to the I/O Configuration. . . . . . . . . . . . . 61
Add the POINT I/O Modules and Configure for Rack-optimization
vi Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Table of Contents
Troubleshoot the Adapter
Specifications
Add the POINT I/O Module and Configure For Direct Connection
Download the Program to the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Chapter 6
Status Indicators for POINT I/O Adapters. . . . . . . . . . . . . . . . . . . . . 82
Appendix A
Adapter Web Dialogs
Appendix B
Use the Diagnostic Overview Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Use the Network Settings Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Use the Ethernet Statistics Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Use the I/O Connections Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Use the Advanced Diagnostics Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Work with the Configuration Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Use the Network Configuration Page . . . . . . . . . . . . . . . . . . . . . . . . . 103
Work with the Browse Chassis Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Appendix C
Configure the RSLinx Ethernet
Communication Driver
Configure the AB_ETH Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Configure the AB_ETHIP Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 vii
Table of Contents
Index
viii Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Preface
Who Should Use this
Manual
Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use series B 1734 POINT I/O ™
EtherNet/IP Adapter modules.
Purpose of this Manual
This manual is a reference guide for the 1734-AENT/B POINT I/O
EtherNet/IP Adapter, a communications adapter for POINT I/O modules. It describes the procedures you use to install, wire, configure, troubleshoot, and use your adapter module.
ATTENTION: You must only use series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
About the Example Applications
This manual presents two example applications that demonstrate the procedures for configuring and communicating with POINT I/O modules using the
1734-AENT/B adapter. We intend the example applications as building blocks to help you get your own system up and running. We recommend that you set up and run the example applications and use them as guides.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 ix
Preface x
Here is the type of system you’ll be setting up.
1734-AENT
10.88.70.2
Slot 0 1 2 3
Local chassis
Data
L63 controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Switch
10.88.70.26
Programming terminal
0 0 2
1734-AENT Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
Slot 0 1 2 3 4
POINT I/O
31393
System Components
We used the following components for the example applications. You need the same or similar components to set up your own control system using POINT I/O modules on an EtherNet/IP network.
Quantity Product Name
Hardware
1
1
1
1
1
1
1
1
1
1
1
Catalog Number
POINT I/O EtherNet/IP adapter 1734-AENT
POINT I/O 24V DC sink output module 1734-OV4E/C
POINT I/O relay output module
DIN rail
1734-OW2/C
199-DR1 or equivalent
ControlLogix® chassis
ControlLogix power supply
1756-A4 (or 1756-A7, 1756-A13,1756-A17)
1756-PA72 (or 1756-PB72)
L63 controller 1756-L63
ControlLogix EtherNet/IP bridge module 1756-ENBT
Personal computer that supports
RSLogix 5000® software
Any appropriate model running Windows NT
4.0, Service Pack 6A or higher
Ethernet switch
24V DC power supply
Refer to manufacturer’s specifications
1734-EP24DC
Associated media and connectors as needed
Software
1 RSLinx communications software, version 2.31.00 or later
9355-WAB, 9355-WABOEM, 9355-WABC
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Preface
Quantity Product Name
1 RSLogix 5000 programming software, version 17 or later
Catalog Number
9324-RLD300ENE
Related Documentation
The following documents contain additional information concerning Rockwell
Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.
Resource
1734 POINT I/O ® Selection Guide, publication 1734-SG001
Description
A description and overview of the 1734 series I/O modules and compatible control platforms.
Using EtherNet/IP for Industrial Control.
EtherNet/IP Design Considerations Reference Manual, publication
ENET-RM002 .
EtherNet/IP Modules in Logix5000 ™ Control Systems User Manual, publication ENET-UM001
EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005
A manual describing how to use EtherNet/IP modules with Logix5000 controllers and communicate with various devices on the Ethernet network.
Describes how to install, configure, and maintain linear and device-level Ring
(DLR) networks using Rockwell Automation EtherNet/IP devices with embedded switch technology.
ControlLogix ™ Chassis and Power Supplies Installation
Instructions, publication 1756-IN005 .
Describes how to install and troubleshoot standard and ControlLogix-XT versions of the 1756 chassis and power supplies, including redundant power supplies.
ControlLogix EtherNet/IP Bridge Module installation instructions.
ControlLogix EtherNet/IP Bridge Module Installation Instructions, publication 1756-IN019
ControlLogix System User Manual, publication 1756-UM001 Detailed information on how to install, configure and troubleshoot the
ControlLogix Sequence of Events module in your ControlLogix application.
RSLinx ® Classic Getting Results Guide, publication LINX-GR001 Information on how to install and navigate the RSLinx Classic software. It explains how to access and navigate the help, and how to effectively use the
RSLinx Classic software.
Installation instructions for installing the 1734 POINT I/O EtherNet/IP Adapter.
1734 POINT I/O EtherNet/IP Adapter Installation Instructions, publication 1734-IN042
Allen-Bradley Industrial Automation Glossary, publication
AG-QR071
Industrial Automation Wiring and Grounding Guidelines, publication 1770-IN041 .
EtherNet/IP Media Planning and Installation Manual (ODVA) .
A glossary of industrial automation terms and abbreviations.
Detailed information on proper wiring and grounding techniques.
Installing an EtherNet/IP network
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 xi
Preface
Common Techniques Used in this Manual
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
Rockwell Software products contain extensive tutorials and help screens. We recommend that you use these tutorials and help screens to learn about the products.
For more information about Rockwell Software products, visit the Rockwell
Software website at http://www.rockwellautomation.com/software/ .
Studio 5000 Environment
The Studio 5000 Automation Engineering & Design Environment® combines engineering and design elements into a common environment. The first element is the Studio 5000 Logix Designer® application. The Studio 5000 Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix5000™ controllers for discrete, process, batch, motion, safety, and drive-based solutions.
xii
The Studio 5000® environment is the foundation for the future of Rockwell
Automation® engineering design tools and capabilities. The Studio 5000 environment is the one place for design engineers to develop all elements of their control system.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview
Adapter Features
Chapter
1
Overview of the 1734 POINT I/O EtherNet/IP
Adapter
This chapter provides an overview of the POINT I/O Series B EtherNet/IP adapter, its primary features, and how to use it. You need to understand the concepts discussed in this chapter to configure your adapter and use it in an
EtherNet/IP control system.
The following table lists where to find specific information.
Topic
Physical Features of Your Adapter
Hardware/Software Compatibility
Important Adapter Considerations
Empty Slots and RIUP Situations
Power Up a System for the First Time
Use of the Common Industrial Protocol (CIP)
Understand the Producer/Consumer Model
Specify the Requested Packet Interval (RPI)
Support for Rack-optimization, Enhanced Rack-optimization, and Direct
Mixing Rack-optimization, Enhanced Rack-optimization, and Direct
Page
The POINT I/O adapters provide connectivity to EtherNet/IP networks for
POINT I/O modules. The POINT I/O adapter is for the I/O backplane that provides connectivity through an RJ-45 connector.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 1
2
Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter
Some of the module’s features are as follows:
• EtherNet/IP messages encapsulated within standard TCP/UDP/IP protocol
• Common application layer with ControlNet and DeviceNet networks
• Interfacing via Category 5 rated twisted pair cable
• Half/full duplex 10 Mbit or 100 Mbit operation
• DIN rail mounting
• Communication to and from other POINT I/O modules on the same
DIN rail
• Communication supported by RSLinx software
• IP address assigned via standard DHCP tools
• I/O configuration via RSLogix 5000 or Logix Designer software
• No network scheduling required
• No routing tables required
• Support of connections from multiple controllers simultaneously
You must use RSLogix 5000 to configure these features. For more details on
configuration, see Configuration Requirements in Chapter 3 .
What the Adapter Does
The I/O adapters perform the following primary tasks:
• Control of real-time I/O data (also known as implicit messaging) - the adapter serves as a bridge between I/O modules and the network
L
6
3
B
T
E
N
EtherNet/IP Network
A
E
N
T
POINT
I/O
B
T
E
N
ControlLogix
I/O
Other
Network
Devices
• Support of messaging data for configuration and programming information (also known as explicit messaging)
• Support of Output hold in all output modules during Program mode and
Fault mode. Note that the option is not available for Program Download mode.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview of the 1734 POINT I/O EtherNet/IP Adapter Chapter 1
Physical Features of Your
Adapter
The 1734 Adapters have the following components:
• Removable Terminal Block (RTB);
• Network address Thumbwheel
• Connector (one RJ45 EtherNet/IP connector)
• Status indicators (Module Status; Network Status; POINTBus Status;
Network Activity; System Power; Field Power)
Physical Features of the 1734-AENT Series B Adapters
Status indicators
RTB removal handle
1734-AENT Series B
POINT I
O
Status
Network
Activity
Network
Status
Status
Network address thumbwheel
EtherNet network
RJ45 connector
0
0 2
Removable Terminal
Block (RTB)
DIN rail locking screw
(orange)
Hardware/Software
Compatibility
31533
The I/O adapters and the applications described in this manual are compatible with the following firmware revisions and software releases.
Contact Rockwell Automation if you need software or firmware upgrades to use this equipment
Product Firmware Revision/ Software Release
(2)
1734-AENT Series B adapter
1756-ENBT module
1768-ENBT module
Logix controller
RSLogix 5000 software
(1)
RSLinx software
4.002 or later
4.006 or later
2.003 or later
17 or later
17 or later
2.56 or later
(1) From version 21 onwards, RSLogix 5000 is known as Logix Designer.
(2) Installation of the Add-on Profile (AOP) for the adapter is required.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 3
Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter
The Enhanced Rack-Optimization option is only supported in the following.
Product Firmware Revision/ Software Release
(2)
1734-AENT Series B adapter
Logix controller
RSLogix 5000 software
(1)
RSLinx software
5.012 or later
20 or later
20 or later
2.56 or later
(1) From version 21 onwards, RSLogix 5000 is known as Logix Designer.
(2) Installation of the Add-on Profiles (AOP) for the adapter and I/O module are required.
4
Important Adapter
Considerations
Before you begin using your adapter, note the following important considerations.
ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
Thumbwheel Settings
You can set the thumbwheels on the adapter to perform different functions. Refer to the following table to see the valid thumbwheel settings and the corresponding function.
Setting
001...254
801...864
888
Function
Sets the network address.
Refer to
Set the Network Address on page 24 for more information.
Sets the chassis size.
Refer to
Set the Chassis Size by Using the Thumbwheels on page 5
for more information.
Restores default factory settings.
If the thumbwheels are set to an invalid number, the adapter checks to see if
DHCP is enabled. If DHCP is enabled, the adapter requests an address from a
DHCP server. The DHCP server also assigns other Transport Control Protocol
(TCP) parameters.
Set the Chassis Size
The I/O adapters for EtherNet/IP require configuration of their chassis size before you can make any I/O connections. The factory default setting for the chassis size is one slot, which represents the adapter by itself.
You must set the chassis size to a number equaling one slot for the adapter plus one slot for each I/O module present in the backplane of the adapter.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview of the 1734 POINT I/O EtherNet/IP Adapter Chapter 1
For example, if your system consists of one adapter and four I/O modules, set the chassis size to 5.
One adapter
Four I/O modules
Chassis size = 5
0 0 2 1734-AENT Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
The adapter stores this chassis size setting in non-volatile memory.
Each time the adapter is powered up, the adapter compares the number of I/O modules present on its backplane to the chassis size value from non-volatile memory. The adapter does not allow any I/O connection until the number of
I/O modules present equals the chassis size value minus one for the adapter itself.
You can set the chassis size by using the following:
Tool
Studio 5000 Logix Designer application Addon Profile
Description
Refer to Add the POINT I/O Adapter to the I/O
Chassis Size on page 49 for more information.
RSLinx Classic software, version 2.56 or later Log on to http://www.rockwellautomation.com/ knowledgebase and search for information on changing or configuring the chassis size of POINT
I/O adapters.
Web dialog
Thumbwheels
(Firmware revision 5.015 or later)
Refer to for
Use the Identity Page on page 102
more information.
Refer to Set the Chassis Size by Using the
for more information.
Set the Chassis Size by Using the Thumbwheels
For firmware revision 5.015 or later, you can set the chassis size without a computer by using the thumbwheels on the adapter.
1.
Make sure that the adapter is not powered.
2.
Set the thumbwheels to 8 xx where xx
is the chassis size value from 01...64.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 5
Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter
For example, set the thumbwheels to 802 to set the chassis size to 2, 803 to set the chassis size to 3, and so on up to 864 to set the chassis size to 64.
TIP Press a pen tip into the center and perpendicular to the + or the - button to change the number. You only need a small amount of force to press the button (approximately 2N).
3.
Power up the adapter.
4.
Observe the status indicators.
The following table describes the status indicators of the adapter when the adapter is powered up while the thumbwheels are set a value from
801...864:
Indicator
Module Status
Network Activity
Network Status
POINTBus Status
Status
Flashing red
Off
Off
The POINTBus Status indicator flashes red initially and then either changes to solid green or continues to flash red depending on the connection result.
• Solid green – if the configured chassis size and number of physical nodes present match
• Flashing red – if the configured chassis size and number of physical nodes present do not match
Note:
Communication on all Ethernet ports are disabled while the thumbwheels are set to 8 xx .
5.
If the POINTBus Status indicator changes to solid green, skip to Step 9.
6.
If the POINTBus Status indicator continues to flash red, determine the cause of the error.
The cause of error may be one of the following:
Error
Chassis size mismatch
Module fault
Action
Make sure that the chassis size value matches the total number of the adapter plus the I/O modules.
For example, if you have 1 adapter and 10 I/O modules, then the chassis size is 11. Therefore, the thumbwheels must be set to 811.
Refer to the installation instructions publication for the affected module for information on how to interpret its status indicators.
7.
Remove power from the adapter and then address the error accordingly.
8.
Once you have addressed the error, repeat Steps 1...5.
9.
Once you have set the chassis size by using the thumbwheels, remove power from the adapter and then set the thumbwheels according to the IP address setting that you need.
6 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview of the 1734 POINT I/O EtherNet/IP Adapter Chapter 1
For more information, see
Set the Network Address for POINT I/O
Adapter Replacement
Note that during a connection request from the controller, the chassis size setting is not communicated to the adapter. You must always set this chassis size using a separate operation. This includes situations when you are replacing an adapter.
The adapter does not allow any I/O connections until it is configured with the appropriate chassis size and the proper number of POINT I/O modules are present.
Empty Slots and RIUP Situations
The POINT I/O system cannot detect an empty terminal base. For this reason, there are numerous situations in which you can potentially configure a system that is unusable or one that exercises unintended control.
In an attempt to address these situations, you must observe the following rules for
I/O system construction and the removal and reinsertion of modules.
• A correct I/O system does not have any empty terminal bases.
• After you cycle power, the adapter will not allow any I/O connections until the number of modules comprising the chassis plus one for the adapter equals the stored chassis size.
– It cannot assume any safe operation until there is a match between the number of modules indicating their presence in the chassis and what the adapter has saved in non-volatile memory because it cannot detect empty terminal bases.
– Actual module identification (such as, electronic keying) is done when connection establishment requests are received from the controller or controllers.
• A POINT I/O module removed under power does not disrupt operation of the other I/O modules. On the other hand, ArmorPOINT I/O modules are not intended to be removed under power.
– When you remove a module, the adapter detects what changed.
– Whenever you remove a module with an active connection from the
POINT I/O system, the adapter indicates this by flashing the
POINTBus Status LED red and reports a minor recoverable fault.
• If more than one contiguous module is removed under power, connections to all modules in the contiguous missing module set are disallowed until all modules are replaced. Because the adapter cannot detect an empty base, it does not know the physical positioning of the modules until all the missing modules are replaced.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 7
Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter
• If a module separating two sets of contiguous missing modules is removed, the two sets merge into a single set. All the modules must be replaced before connections are permitted to any module in the set.
• If modules of different types are removed and returned to the wrong locations, attempts to connect to these modules will fail during verification of the electronic ID (providing that keying has not been disabled).
• If modules of the same type are removed and returned to the wrong locations, they accept connections from the controller or controllers and reconfigure with the correct data once they pass their electronic keying check.
• These removal and return situations exist whether the system is under power or not. If the system is under power, the situation arises immediately.
If the system is not under power, the situation arises in the next power cycle.
Power Up a System for the First Time
When you power the I/O for the first time, the adapter must assign slot addresses to every module in the backplane. All I/O modules ship configured at the same address.
When you first apply power, we expect that all but one module on the backplane exhibits a solid red Module Status LED.
One by one the adapter resets these modules and addresses them appropriately.
The amount of time that this operation takes is proportional to the size of your I/
O system.
8
Use of the Common
Industrial Protocol (CIP)
The adapter uses the Common Industrial Protocol (CIP). CIP is the application layer protocol specified for EtherNet/IP, the Ethernet Industrial Protocol, as well as for ControlNet and DeviceNet networks. It is a message-based protocol that implements a relative path to send a message from the producing device in a system to the consuming devices.
The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not store it.
This has the following significant benefits:
• You do not need to configure routing tables in the bridging modules, which greatly simplifies maintenance and module replacement.
• You maintain full control over the route taken by each message, which enables you to select alternative paths for the same end device.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview of the 1734 POINT I/O EtherNet/IP Adapter Chapter 1
Understand the Producer/
Consumer Model
The CIP producer and consumer networking model replaces the old source and destination (master and slave) model. The producer and consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system, input modules are not polled by a controller. Instead, they produce (multicast or unicast) their data either upon a change of state (COS) or periodically.
Multicast is the default mode for version 17 Logix and earlier controllers and unicast is the default for version 18 with multicast as a selectable option.
The frequency of update depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data, and the controller is a consumer of the data.
The controller also produces data for other controllers to consume. The produced and consumed data is accessible by multiple controllers and other devices over the EtherNet/IP network. This data exchange conforms to the producer and consumer model.
Specify the Requested
Packet Interval (RPI)
The Requested Packet Interval or RPI is the update rate specified for a particular piece of data on the network. The RPI can be specified for the adapter and include all of the I/O modules in the I/O system (using a rack-optimization or enhanced rack-optimization connection) or specified for a particular module
(using direct connection).
When you add a module or an adapter to the I/O configuration of a controller, you must enter the RPI as a parameter. This value specifies how often to produce the data for that device. For example, if you specify an RPI of 50 ms, it means that every 50 ms the device should send its data to the controller and the controller should send the consumed (output) data to the device.
Use RPIs only for devices that exchange data. For example, a ControlLogix
EtherNet/IP bridge module in the same chassis as the controller does not require an RPI, because it is not a data-producing member of the system. Its use is only as a bridge to remote racks.
Support for Rackoptimization, Enhanced
Rack-optimization, and
Direct Connections
The I/O adapters supports direct, rack-optimization, and enhanced rackoptimization connections. A direct connection is a real-time data transfer link between the controller and the module occupying the slot that the configuration data references.
Direct I/O connections occur at a cyclic rate specified by the RPI during configuration. A rack-optimization connection is a grouping of data from one or more digital I/O modules into a single block of data sent over a single connection at the same data rate.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 9
Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter
Analog, safety, and specialty modules cannot participate in the rack-optimization connection; these modules require an enhanced rack-optimization or direct I/O connection.
Enhanced rack-optimization connections reduce the total number of connections needed to transfer data when using many digital and analog, or specialty modules in a system.
Rack-optimization connections reduce the total number of connections needed to transfer data when using many digital I/O modules in a system. The following example illustrates the benefit of rack-optimization connections.
Assume you set up a system that contains eight digital I/O modules interfaced to an adapter. If you use direct connections to transfer data to each of the these I/O modules, you need eight connections to transfer all of the data, one to each of the eight I/O modules. If you use a rack-optimization connection to transfer the data, you only need a single connection – the connection to the I/O adapter.
IMPORTANT Although rack-optimization and enhanced rack-optimization connections offer an efficient way to use resources, there are a few limitations on their use:
• You can use only rack-optimization or enhanced rack-optimization connections to send data to and from digital I/O modules.
• Safety modules, IO link modules, and third-party I/O modules can not participate in enhanced rack-optimization connections.
• Enhanced rack-optimization does not support a listen only connection. Do not use enhanced rack-optimization if your application requires a connection for monitoring.
• All data is sent at the same time as the RPI rate of the I/O adapters.
If the update rate required for a digital module is different from the
RPI of the rack-optimization or enhanced rack-optimization connection, a direct connection to that I/O module is required.
See the EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005 , for more information on connections.
Mixing Rack-optimization, Enhanced Rack-optimization, and
Direct Connections
You can mix communication formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization or enhanced rack-optimization communicate at the rate of the RPI configured for the adapter. I/O modules configured for direct communication communicate at their own individual RPIs and ignore the rack-optimization RPI.
10 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Before You Begin
Chapter Summary
Overview of the 1734 POINT I/O EtherNet/IP Adapter Chapter 1
To effectively use your adapter, note the following considerations.
Determine Compatibility
If using the adapter with a 1756-ENBT module or 1768-ENBT module, use the following required firmware revisions for these bridge modules:
• 1756-ENBT firmware revision 4.006 or later
• 1768-ENBT firmware revision 2.003 or later
Understand Messaging
Class 3 (Explicit Message) requests through the 1734-AENT adapter to a specific
POINT I/O module may not always receive a response from the I/O modules. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a timeout.
Configure Autobaud
The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed communication rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the adapter.
In this chapter, you were introduced to the features of the POINT I/O Adapter, and considerations for its installation and usage.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 11
Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter
Notes:
12 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview
Chapter
2
Install Your 1734 POINT I/O EtherNet/IP
Adapter
This chapter describes how to physically install the POINT I/O Series B
EtherNet/IP adapter; and how to connect the adapter to your EtherNet/IP network. The only tools you require are a flat or Phillips head screwdriver and a drill.
This chapter includes the following topics:
Topic
Mount the POINT I/O Adapter on a DIN Rail
Page
ATTENTION: You must only use Series C and above POINT I/O modules with POINT I/O Adapters. Series A or Series B POINT I/O modules do not work with POINT I/O Adapters (does not apply to POINTGuard modules).
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 13
Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter
Mount the POINT I/O Adapter on a DIN Rail
1.
Make sure the DIN rail locking screw (orange) is in horizontal position.
2.
Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm) top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number
199-DR1; 46277-3
).
3.
Press down firmly to install the adapter on the DIN rail, noting that the locking mechanism locks the adapter to the DIN rail.
ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent equipment for adequate ventilation.
4.
Set the network address thumbwheel switches to the desired value. See
in chapter
3 for details on setting the IP address.
5.
Slide the safety end cap up to remove it, exposing the backplane and power interconnections.
74.00
(2.91)
75.30
(2.96)
B
52.23
(2.06)
1734-AENT Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
132.72
(5.23)
35.55
(1.40)
A
14
A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)
WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
45174
ATTENTION: Do not remove or replace an Adapter Module while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Install Your 1734 POINT I/O EtherNet/IP Adapter Chapter 2
Install POINT I/O Modules
The following instructions explain how to install your POINT I/O Modules onto the DIN rail.
1.
Position the mounting base vertically above the DIN rail.
2.
Make certain the adapter DIN rail locking screw (orange) is in the horizontal position.
3.
Slide the I/O module mounting base down, allowing the interlocking side pieces to engage the adjacent mounting base/adapter.
4.
Press down firmly to install the I/O module mounting base on the DIN rail. A locking mechanism locks the mounting base to the DIN rail.
5.
Rotate the keyswitch on the I/O module mounting base clockwise until the appropriate number for the module you are installing (listed on the module label) aligns with the correct notch in the base.
6.
Position the I/O module vertically above its mounting base.
7.
Slide the module down until it engages the latching mechanism. You will hear a clicking sound when the I/O module is properly engaged. The locking mechanism locks the module to its mounting base.
Remove POINT I/O Modules
To remove a module from its mounting base:
1.
Put a flat-blade screwdriver into the slot of the orange latching mechanism in the mounting base of the I/O module to be removed.
2.
Push the screwdriver toward the I/O module to disengage the latch.
The module lifts up off the mounting base.
3.
Pull the module off the mounting base.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 15
Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter
Replace An Adapter
16
Use these procedures to install a replacement POINT I/O adapter to an existing system.
1.
Disconnect the Ethernet connector(s) from the adapter.
2.
Pull up on the Removable Terminal Block (RTB) handle to remove the terminal block.
3.
Remove the adjacent module from its mounting base.
4.
Use a small bladed screwdriver to rotate the DIN rail locking screw
(orange) to a vertical position. This releases the locking mechanism.
5.
Lift the adapter straight up to remove.
6.
Slide the safety end cap up to remove it, which exposes the backplane and power connections.
ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail.
Failure to do so could result in equipment damage or injury from electric shock.
WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
7.
Position the replacement adapter vertically above the DIN rail, making certain the DIN rail locking screw (orange) is in the horizontal position.
8.
Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module.
9.
Press firmly to seat the adapter on the DIN rail, noting that the adapter locking mechanism will snap into place.
10.
Set the network address on the network address thumbwheel.
11.
Insert the end of the Removable Terminal Block opposite the handle into the Removable Terminal Block base unit, noting that this end has a curved section that engages with the base unit.
12.
Rotate the Removable Terminal Block into the wiring base until it locks into place.
13.
Replace the adjacent module in its mounting base.
14.
Reconnect the Ethernet cable(s) to the adapter.
15.
Set the IP Address for this module (see
Set the Network Address in chapter 3
).
16.
Configure the adapter’s chassis size.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Wire the Adapter
Install Your 1734 POINT I/O EtherNet/IP Adapter Chapter 2
The POINT I/O adapter uses RJ45 EtherNet/IP connectors for its EtherNet/ IP connection. Connect the cord set you selected for your module to the appropriate port.
Wire a POINT I/O Adapter
Refer to the following illustration to wire the adapter.
Network address thumbwheels
RJ45 EtherNet/IP
Connector
0 0 2
C
V
NC
Chas
43264
This DC supply connects to the internal power bus.
NC = No Connection
Chas Gnd = Chassis Ground
C = Common
V = Supply
V DC
0
NC
4
2
Chas
Gnd
C
6
V
NC
1
3
Chas
Gnd
5
C
V
7
ATTENTION: Do not connect 120/240V AC power to this supply. This
DC supply will be connected to the internal power bus.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 17
Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter
Chapter Summary
ATTENTION: Do not wire more than two conductors on any single terminal.
WARNING: When you connect or disconnect the Removable Terminal
Block (RTB) with field side power applied, an electrical arc can occur.
This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
WARNING: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with the following:
Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
In this chapter, you learned how to install and wire your POINT I/O adapter module. The following chapter describes how to configure your POINT I/O adapter module to communicate on the EtherNet/IP network by providing an IP address, gateway address, and Subnet mask.
18 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Introduction
Chapter
3
Configure the Adapter with RSLogix 5000 or
Logix Designer Software
This chapter guides you through the steps required to configure your modules using the RSLogix 5000 or Logix Designer
(1)
software. Note that the modules presented in this chapter can be configured using RSLogix 5000 software, version
17, or later.
Before using your adapter in an EtherNet/IP network, you need to configure it with an IP address, subnet mask, and optional Gateway address. This chapter describes these configuration requirements and the procedures for providing them. Here are ways you can do this:
• Use the Rockwell BootP/DHCP utility, version 2.3
or later, that ships with RSLogix 5000 or RSLinx software.
– You can also use this utility to reconfigure a device with an IP address you must change.
• Use a third party DHCP server.
• Use the Network Address thumbwheel switches.
• Have your network administrator configure the adapter via the network
DHCP server.
See the table for where to find information in this chapter.
Topic
Set the Network Address for POINT I/O Adapters
Use the Rockwell BootP/DHCP Utility
Use DHCP Software to Configure Your Adapter
Page
(1) From version 21 onwards, RSLogix 5000 is known as Logix Designer.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 19
Chapter 3 Configure the Adapter with RSLogix 5000 or Logix Designer Software
Configuration
Requirements
Before you can use your adapter, you must configure its IP address, its subnet mask, and, optionally, a gateway address. You can use the Rockwell BootP/
DHCP utility, version 2.3 or later, to perform the configuration. You can also use a DHCP server or the network address switches to configure these parameters.
ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
If you need to reset the adapter to factory defaults, see
in Appendix
.
0
0
2
17
3
4-AENT
POINT I
O
S erie s
B
Mo
Stat du le us
Netwo
Activity rk
Netwo
Stat us rk
Poi
Stat nt B us us
System
Powe
Fiel d r r
20
IMPORTANT
IP address Ethernet address (MAC)
43519
If you set the thumbwheels on the adapter to the value 888 and then power cycle the module, the following will occur.
·
The DHCP Enabled function is enabled (set to True).
·
The Ethernet link is negotiated automatically (the Auto Negotiate function will be set to True).
·
The web server is enabled (the Disabled Web Server function is disabled).
·
The password for this page resets to the factory default (the word password is the factory default password).
Note the value of the switches before you enter the 888 value, because you return the adapter to those values once this process is complete.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter with RSLogix 5000 or Logix Designer Software Chapter 3
IMPORTANT If using the BootP/DHCP utility, you need to know the Ethernet hardware address of your adapter. Rockwell Automation assigns each
1734-AENT adapter a unique 48-bit hardware address at the factory.
The address is printed on a label on the side of your 1734-AENT adapter as shown in the figure. It consists of six hexadecimal digits separated by colons. This address is fixed by the hardware and cannot be changed.
If you change or replace the 1734-AENT adapter, you must enter the new Ethernet hardware address of the adapter when you configure the new adapter.
IP Address
The IP address identifies each node on the IP network (or system of connected networks). Each TCP/IP node on a network (including the adapter) must have a unique IP address.
Class A
Class B
Class C
0
0
0
10
The IP address is 32 bits long and has a Network ID part and Host ID part.
Networks are classified A, B, C, (or other). The class of the network determines how an IP address is formatted
.
7 8 31
Network ID
Network ID
15 16
Host ID
Host ID
31
0
110 Network ID
23 24
Host ID
31
You can distinguish the class of the IP address from the first integer in its dotteddecimal IP address as follows:
Range of first integer Class Range of first integer Class
0 1…127
128…191
A
B
192…223
224… 255
C other
Each node on the same physical network must have an IP address of the same class and must have the same network ID. Each node on the same network must have a different Host ID thus giving it a unique IP address.
IP addresses are written as four decimal integers (0…255) separated by periods where each integer gives the value of one byte of the IP address
.
EXAMPLE For example, the 32-bit IP address:
10000000 00000001 00000000 00000001 is written as
128.1.0.1
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 21
Chapter 3 Configure the Adapter with RSLogix 5000 or Logix Designer Software
Gateway Address
This section applies to multi-network systems. If you have a single network system, refer to the next section.
The Gateway Address is the default address of a network. It provides a single domain name and point of entry to the site. Gateways connect individual physical networks into a system of networks.
When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks. The figure shows gateway G connecting Network 1 with Network 2.
A
128.1.0.1
Network 1 128.1.0.2
G
B C
128.2.0.1
128.2.0.2
Network 2
128.2.0.3
When host B with IP address 128.2.0.1 communicates with host C, it knows from C’s IP address that C is on the same network. in an Ethernet environment, B can then resolve C’s IP address into a hardware address (MAC address) and communicate with C directly.
When host B communicates with host A, it knows from A’s IP address that A is on another network (the network IDs are different). In order to send data to A, B must use the IP address of the gateway connecting the two networks. In this example, the gateway’s IP address on Network 2 is 128.2.0.3.
The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be used by hosts on Network 1 and the second must be used by hosts on Network 2.
To be usable, a gateway of a host must be addressed using a network ID matching its own.
22 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter with RSLogix 5000 or Logix Designer Software Chapter 3
Subnet Mask
The subnet mask is used for splitting IP networks into a series of subgroups, or subnets. The mask is a binary pattern that is matched up with the IP address to turn part of the Host ID address field into a field for subnets
.
EXAMPLE Take Network 2 (a Class B network) in the previous example and add another physical network. Selecting the following subnet mask would add two additional network ID bits, allowing for four physical networks:
11111111 11111111 11 000000 00000000 = 255.255.192.0
These two bits of the Host ID are used to extend the network ID.
Two bits of the Class B host ID are used to extend the network ID. Each unique combination of bits in the part of the Host ID where subnet mask bits are 1 specifies a different physical network.
The new configuration is:
A
128.1.0.1
Network 1 128.1.0.2
G
B C
128.2.64.3
128.2.64.1
128.2.64.2
Network 2.1
D E
G2
128.2.128.3
128.2.128.1
128.2.128.2
Network 2.2
A second network with Hosts D and E was added. Gateway G2 connects
Network 2.1 with Network 2.2.
Hosts D and E will use Gateway G2 to communicate with hosts not on
Network 2.2.
Hosts B and C will use Gateway G to communicate with hosts not on
Network 2.1.
When B is communicating with D, G (the configured Gateway for B) will route the data from B to D through G2.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 23
Chapter 3 Configure the Adapter with RSLogix 5000 or Logix Designer Software
Set the Network Address
The adapters ship DHCP-enabled and with the pen-push Network address thumbwheels set to
999
. You can set the network Internet Protocol (IP) address as follows.
Set the Network Address for POINT I/O Adapters
• Use the pen-push thumbwheels located on the adapter. Press either the + or - button with a pen tip to change the number and assign the IP address.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from non-volatile memory.
Network address thumbwheel
Press either the + or - button with a pen tip to change the number.
0 0 2
24
43264
The adapter reads the thumbwheels first to determine if the thumbwheels are set to a valid number. You set the node address by using the 3-position pen-push thumbwheel using a pen tip.
Note:
Press a pen tip into the center and perpendicular to the + or the - button to change the number. You only need a small amount of force to press the button
(approximately 2N).
Valid settings range from
001…254
. When you use the thumbwheel to assign an address and set it to
001
, the adapter gateway address is set to
0.0.0.0
. and the subnet mask is set to
255.255.255.0.
When you use the thumbwheel to assign an
IP address between
002...254
, the adapter gateway address is set to
192.168.1.1
.
The adapter does not have a host name assigned, or use any Domain Name
System when using the thumbwheel settings.
If the thumbwheels are set to an invalid number (for example, 000 or a value greater than 254 excluding 888), the adapter checks to see if DHCP is enabled. If
DHCP is enabled, the adapter requests an address from a DHCP server. The
DHCP server also assigns other Transport Control Protocol (TCP) parameters.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter with RSLogix 5000 or Logix Designer Software Chapter 3
If DHCP is not enabled, the adapter uses the IP address, along with other TCP configurable parameters, stored in non-volatile memory.
WARNING: When you change thumbwheels settings while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Use the Rockwell BootP/
DHCP Utility
The 1734-AENT/B adapter should be configured using only DHCP. The
Rockwell BootP/DHCP utility is a standalone program that incorporates the functionality of standard BootP software with a user-friendly graphical interface.
It is located in the
Utils
directory on the RSLogix5000 software installation CD.
The adapter must have DHCP enabled (factory default and the network address switches set to an invalid value) to use the utility.
To configure your adapter using the BootP utility, perform the following steps:
1.
Run the BootP software.
In the BOOTP Request History panel you see the hardware addresses of devices issuing BootP requests.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 25
Chapter 3 Configure the Adapter with RSLogix 5000 or Logix Designer Software
2.
Double-click the hardware address of the device you want to configure.
The New Entry dialog appears with the device’s Ethernet Address (MAC).
26 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter with RSLogix 5000 or Logix Designer Software Chapter 3
3.
Enter the IP Address you want to assign to the device and click OK. The device is added to the Relation List, displaying the Ethernet Address
(MAC) and corresponding IP Address, Hostname, and Description (if applicable).
When the address displays in the IP Address column in the Request
History section, the IP address assignment has been made.
4.
To make this configuration static in the device, highlight the device in the
Relation List panel, and click the Disable BOOTP/DHCP button.
When power is cycled to the device, it uses the configuration saved in nonvolatile memory and will not issue a DHCP request.
5.
To enable DHCP for a device with DHCP disabled, highlight the device in the Relation List, and click the Enable DHCP button.
You must have an entry for the device in the Relation List panel to reenable DHCP.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 27
Chapter 3 Configure the Adapter with RSLogix 5000 or Logix Designer Software
Save the Relation List
You can save the Relation List for later use. To save the Relation List, perform the following steps:
1.
Select Save As... from the File menu.
28
The Save As dialog appears.
2.
Select the folder where you want to save the Relation List.
3.
Enter a File name for the Relation List, for example, control system configuration, and click Save.
You can leave the Save as type at the default setting: Bootp Config Files
(*.bpc).
You now have the option to open the file containing the Relation List at a later session.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter with RSLogix 5000 or Logix Designer Software Chapter 3
Use DHCP Software to
Configure Your Adapter
DHCP (Dynamic Host Configuration Protocol) software automatically assigns
IP addresses to client stations logging onto a TCP/IP network.
DHCP is based on BootP and maintains some backward compatibility. The main difference is that BootP was designed for manual configuration, while DHCP allows for dynamic allocation of network addresses and configurations to newly attached devices.
Be cautious about using DHCP software to configure your adapter. A DHCP server typically assigns a finite lease time to the offered IP address.
When 50% of the leased time has expired, the adapter attempts to renew its IP address with the DHCP server.
The possibility exists that the adapter will be assigned a different IP address, which would cause the adapter to cease communicating with the ControlLogix controller.
See Configure the Adapter with Fixed IP Address in Chapter 4
to configure the adapter with a fixed IP address.
ATTENTION: To avoid unintended control or loss of control, the
I/O adapter must be assigned a fixed IP address. A dynamically provided
IP address should be used only at initial configuration. If a DHCP server is used, it must be configured to assign the same IP address to your adapter.
Failure to observe this precaution may result in unintended machine motion or loss of process control.
Chapter Summary
This chapter provided instructions on how to configure POINT I/O Adapter modules through the RSLogix 5000 software and included information on configuration requirements and setting the network address.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 29
Chapter 3 Configure the Adapter with RSLogix 5000 or Logix Designer Software
Notes:
30 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview
Chapter
4
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
This chapter guides you through the steps required to configure your modules using the RSLogix 5000 or Logix Designer
(1)
software.
In this example, a ControlLogix controller communicates with I/O modules via the adapter using a direct connection.
The adapter makes a direct connection to each of the modules referenced by the data. The modules presented in this chapter use RSLogix 5000 software, version
17, or later.
Topic
Create the Example Application
Add the Local EtherNet/IP Bridge to the I/O Configuration
Add the POINT I/O Adapter to the I/O Configuration
Add the POINT I/O Modules to the I/O Configuration
Download the Program to the Controller
Verify the Module Chassis Size
Configure the Adapter with Fixed IP Address
Recover From an Overloaded Adapter
Page
ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
(1) From version 21 onwards, RSLogix 5000 is known as Logix Designer.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 31
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
Set Up the Hardware
The following section describes how to set up the I/O Hardware.
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3. The 1734-AENT adapter is mounted on a
DIN rail in slot 0, with a 1734-OW2/C relay output module in slot 1, a 1734-
OV4E/C sink output module in slot 2, and a power supply (not shown).
To work along with this example, set up your system as shown in the figure.
Slot 0 1 2 3
1734-AENT
10.88.70.2
0 0 2
1734-AENT Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I/O
Local chassis
Data
L63 controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Switch
10.88.70.26
Slot 0 1 2 3 4
Programming terminal
31393
• In the example application, we assume that the L63 controller and
1756-ENBT module (firmware revision 4.006, or later) are in the slots shown in the figure.
• Verify the IP addresses for your programming terminal, 1756-ENBT module, and adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you connected all wiring and cabling properly.
• Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software, as described in
in this manual.
32 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Create the Example
Application
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
Perform the following steps to create the example application:
1.
Start RSLogix 5000 Enterprise Series software to open the RSLogix 5000 main dialog.
2.
From the File menu, select New.
3.
The New Controller dialog opens.
4.
Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 33
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
5.
Select the correct Revision, Chassis Type, and Slot number of the L63 controller, and the folder where you want to save the RSLogix 5000 file
(Create In). The Description is optional.
Note: RSLogix 5000 software Revision 18, and later, lets you enable redundancy. To use redundancy in your system, check the Redundancy
Enabled checkbox in the Redundancy tab when using the said Revision or later.
6.
Click OK.
Configure the I/O Modules
You now add the POINT I/O modules to the controller’s I/O configuration performing these procedures:
• Add the local 1756-ENBT Bridge module to the I/O configuration.
• Add the 1734-AENT/B adapter as a child of the 1756-ENBT module on the Ethernet network.
• Add the POINT I/O modules as children of the AENT/B adapter.
IMPORTANT Click the Help button on the configuration dialogs shown in this section if you need assistance in selecting and setting the parameters.
34 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
Add the Local EtherNet/IP Bridge to the I/O Configuration
1.
Right-click the I/O Configuration folder in the project dialog, and select
New Module.
The Select Module Type dialog opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 35
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
2.
Select the appropriate Module Type filter Category (for the example we selected Communication), and Module Type Vendor (for the example we selected Allen-Bradley).
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
Note: to select only one category you will need to unselect those already selected.
3.
From the list of adapters displayed, select the 1756-ENBT EtherNet/IP
Bridge and click Create.
4.
The New Module dialog opens.
36
5.
Enter values for Name, IP Address, and Slot, noting that we used the following values:
Name
IP Address
Slot
Local_ENBT
10.88.70.4
3
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking the Change button. Some of the properties cannot be modified while pending edits exists.
To change the default module properties,
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
6.
Click Change...
The Module Definition dialog opens.
7.
Enter or select values for Revision, Electronic Keying, Rack Connection, and Time Sync Connection, noting that we used the following values:
Series
Revision
Electronic Keying
Rack Connection
Time Sync Connection
A
5.1
Compatible Module
None
None
8.
Click OK to accept the configuration.
The module appears indented under the I/O Configuration folder.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 37
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
Add the POINT I/O Adapter to the I/O Configuration
Next, you must add the POINT I/O adapter as a child of the local 1756-ENBT module.
1.
In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
The Select Module Type dialog opens.
2.
Select the appropriate Module Type filter Category (for the example we selected Communication), and Module Type Vendor (for the example we selected Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
38
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
3.
Select your adapter from the list and click Create.
The New Module dialog opens.
4.
Select the General Tab and enter the module details, noting that we used the following values.
Name
IP Address
POINT IO Adapter
10.88.70.2
IMPORTANT Note that the slot field is disabled because the slot is automatically 0 for the 1734-AENT/B adapter.
5.
Click Change...
The Module Definition dialog opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 39
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
6.
Choose values for Series, Revision, Electronic Keying, Connection, and
Chassis Size, noting that we used the following values:
Series
Connection
Chassis Size
Electronic Keying
Revision
B
None
5
Compatible Module
4.3
IMPORTANT The chassis size value equals 1 for the adapter plus the number of I/O modules installed (physically present on the I/O backplane).
Connection choices are the following:
• None – the adapter only makes a direct connection to each of the modules referenced by the data. RPI is disabled in this case.
• Rack optimization – digital I/O data is collected into a rack image. This rack image does not include analog or specialty I/O modules.
• Enhanced rack optimization – digital, analog, and specialty I/O data is collected into a rack image.
• Listen only - rack optimization – read or verify input data only, but does not control the modules. When you have multiple controllers, one controller is used to control and the other controllers are used to monitor. When the owning controller of rack-optimization connection closes the connection, the Listen-Only data will also stop.
7.
Choose None as Connection, because we are only making direct connections, then click OK.
Note
: There is no need to have a rack-optimization connection if all I/O connections to the POINT I/O modules are directly connected.
A dialog box opens.
8.
Click Yes.
40 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
9.
In the New Module screen click OK to accept the new configuration.
The 1734-AENT/B adapter appears indented under the local
1756-ENBT bridge module in the I/O Configuration folder.
Note: The requested packet interval (RPI) is disabled because you have chosen None as the Connection.
Add the POINT I/O Modules to the I/O Configuration
You now add POINT I/O modules to the I/O Configuration List under the adapter.
In this example, you add a 1734-OW2 relay output module and a 1734-OV4E sink output module with standard configurations. Use these steps as a guide when configuring different I/O modules for your system.
TIP This example application uses I/O module default configurations.
For more information, refer to the POINT I/O Selection Guide, publication 1734-SG001 .
Add the Digital Relay Output Module
1.
Highlight the 1734-AENT/B adapter under the I/O Configuration folder, right-click and select New Module.
The Select Module Type dialog opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 41
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
2.
Select the appropriate filter for Module Type Category (for the example we selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
3.
From the modules listed select the 1734-OW2 digital relay output module and click Create.
The New Module dialog opens.
42
4.
Enter values for Name and Slot, noting that we used the following values.
Name
Slot
POINT_Relay_Output
1
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
5.
Choose the Connection tab to set the RPI value.
RPI is selectable since it is a direct connection.
Note that the RPI is selectable on the screen and has a default value.
Because we are making a direct connection to each I/O module, we must specify an RPI to determine how often the data is exchanged with the
1734-AENT adapter for each module.
6.
Enter 50 for requested packet interval (RPI) to set how often you exchange data with the I/O adapters.
IMPORTANT To avoid overloading the I/O adapters, we recommend that RPI be no less than 10 ms for rack-optimization and enhanced rackoptimization connections, and 50 ms for direct connections.
7.
Click OK to save the configuration.
The relay output module appears under Ethernet.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 43
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
Add the Digital Output Module
1.
Highlight the 1734-AENT/B adapter under the I/O Configuration folder, right-click and select New Module.
The Select Module Type dialog opens.
2.
Select the appropriate Module Type Category Filter (for the example we selected Digital) and Module Type Vendor (for the example, we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
44
3.
From the modules listed select the 1734-OV4E sink output module and click Create.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
The New Module dialog opens.
4.
Enter values for Name and Slot, noting that we used the following values.
Name
Slot
POINT_Digital_Output
2
5.
Choose the Connection tab to set the RPI value.
The RPI is selectable since it is a direct connection.
Note that the RPI is selectable and has a default value. Because we are making a direct connection to each I/O module, we must specify an RPI to determine how often the data is exchanged with the adapter for each module.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 45
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
6.
Enter 10 ms as the RPI for the 1734-OV4E module.
IMPORTANT To avoid overloading the I/O adapters, we recommend that RPI be no less than 10 ms for rack-optimization and enhanced rackoptimization connections, and 50 ms for direct connections.
7.
Click OK to save the configuration.
The module appears in the I/O configuration folder indented under
Ethernet.
46 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Edit the Controller Tags
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
When you add modules to the I/O configuration the system creates tags for those modules to use in the application program.
For the example application you need to add one more controller tag.
1.
Double-click the Controller Tags folder in the project dialog.
The Controller Tags dialog opens. You see the tags created for the
1734-AENT adapter and its digital I/O modules.
Tags created by the system
Enter the new tag here
2.
Click the Edit Tags tab at the bottom of the Controller Tags dialog.
3.
Create the following tag:
Tag
Parts_Count
4.
Close the Controller Tags dialog.
Type
Counter
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 47
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
Create the Ladder Program
Create the example ladder program to test the I/O.
1.
Under the Main Program folder, double-click Main Routine.
2.
Enter the following ladder program using the tags previously created.
3.
Save the program.
Download the Program to the Controller
Follow this procedure to download the program you just saved to the
ControlLogix controller.
1.
From the main menu, choose Communications>Who-Active.
The Who Active dialog opens.
48
2.
Navigate to select the slot where the controller is located in the chassis.
3.
Choose Set Project Path.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
4.
Choose Download.
The Download dialog opens with a reminder of the following.
• The controller is in Remote Run mode.
• The mode changes to Remote Program prior to download.
5.
From the Download dialog, choose Download
The RSLogix 5000 software dialog opens.
6.
Notice that the 1756-ENBT Bridge is now online.
If yellow triangles are present, see the following section.
Verify the Module Chassis
Size
You have now built the I/O tree in the RSLogix 5000 software, and the
RSLogix 5000 software used the chassis size from the 1734-AENT General tab.
Now you need to download this new chassis size value into the 1734-AENT adapter hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENT adapter hardware.
1.
Verify that the RSLogix 5000 software is online.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 49
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
2.
In the Project dialog, right-click the 1734-AENT adapter under I/O
Configuration.
3.
Select Properties.
4.
Click the Connection tab.
The Module Fault error code displays.
50
Value from
Module Properties
General Tab
5.
Click the Chassis Size tab.
6.
Click Set Chassis Size in Module .
Value currently stored in 1734-
AENT adapter
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
7.
Read and acknowledge the warning dialog.
8.
Click OK to continue.
Notice the chassis size stored in the module has been changed to 3.
At this point, your POINTBus status LED should be solid green. All the yellow triangles in your I/O configuration should be gone.
9.
Click OK.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 51
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
Configure the Adapter with
Fixed IP Address
To configure the adapter with a fixed IP address to prevent the adapter from ceasing to communicate with the ControlLogix controller:
1.
All controllers with I/O connections to the AENT and/or the modules in its backplane need to be in program mode.
2.
In the Module Properties dialog, click the Internet Protocol tab.
52
3.
If it is not selected, select Manually configure IP settings.
4.
Enter values for Physical Module IP Address, and Subnet Mask, noting we used the following values:
Physical Module IP Address 192.168.1.29
Subnet Mask 255.255.255.0
5.
Click Set
6.
Read and acknowledge the warning.
7.
Click Yes.
8.
Click the Refresh communication button to verify the changes.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Recover From an
Overloaded Adapter
Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software Chapter 4
Each I/O connection established with the I/O adapter consumes a portion of microprocessor bandwidth. The amount of bandwidth used by a connection depends on several variables, such as the requested packet interval (RPI), number of I/O modules involved in the connection, and rate of change of the I/O.
The AENT adapter continuously monitors this bandwidth and rejects requests for new I/O connections when there is insufficient bandwidth available to support the new connection.
The condition where the I/O adapters cannot support the connection due to a limit of the bandwidth of the microprocessor is shown on the Connection tab of the Module Properties dialog.
If you encounter this condition, the only action you can take is to alter the existing connections to reduce the amount of microprocessor bandwidth consumed. The most likely fixes for this condition include the following:
• Increase the RPI.
• Decrease the number of connections.
• Remove modules from the rack-optimization I/O connection.
• Remove the rack-optimization connection if there are no modules participating in it.
Chapter Summary
This chapter provided instructions on how to configure the POINT I/O
Adapter for Direct Connection through the RSLogix 5000 software. It included information about setting up the hardware and configuring the I/O, adding the adapter to the configuration, and configuring the adapter with a fixed IP address.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 53
Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 or Logix Designer Software
Notes:
54 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Overview
Chapter
5
Configure the Adapter for Direct Connection,
Rack Optimization, and Enhanced Rack
Optimization in RSLogix 5000 or Logix
Designer Software
This chapter guides you through the steps required to configure your AENT adapter with direct, rack-optimization, and enhanced rack-optimization I/O connections using RSLogix 5000 or Logix Designer
(1)
software.
You can mix I/O connection formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization or enhanced rack optimization communicate at the rate of the RPI configured for the adapter.
I/O modules controlled by a direct I/O connection communicate at their own set
RPI. The RPI of the rack-optimization or enhanced rack-optimization I/O connection has no bearing on the direct I/O connections. The modules presented in this chapter have a configuration using RSLogix 5000 software, version 17 or later. The chapter contains the following main sections
.
Topic
Create the Example Application
Add the Local EtherNet/IP Bridge to the I/O Configuration
Add the POINT I/O Adapter to the I/O Configuration
Add the POINT I/O Modules and Configure for Rack-optimization Connection 65
Add the POINT I/O Modules and Configure for Enhanced Rack-optimization
Page
Add the POINT I/O Module and Configure For Direct Connection
Download the Program to the Controller
Verify the Module Chassis Size
(1) From version 21 onwards, RSLogix 5000 is known as Logix Designer.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 55
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
Set Up the Hardware
56
The following section describe how to set up the I/O Hardware.
Set Up the POINT I/O Hardware
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3. In this example, we mounted the
1734-AENT adapter on a DIN rail in slot 0, with a 1734-OW2/C relay output module in slot 1, a 1734-OV4E/C sink output module in slot 3, and two other
POINT I/O modules which will not be controlled by this Logix controller in slots 2 and 4.
Slot 0 1 2 3
1734-AENT
10.88.70.2
0 0 2
1734-AENT Series B
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Status
System
Power
Field
Power
POINT I/O
Local chassis
Data
L63 controller (slot 1)
1756-ENBT
10.88.70.4 (slot 3)
Switch
10.88.70.26
Slot 0 1 2 3 4
Programming terminal
31393
To work along with this example, set up your system as shown in the figure.
• Note that in the example application, the Logix controller and
1756-ENBT module (firmware revision 4.006 or later) we assume are in the slots shown in the figure.
• Verify the IP addresses for your programming terminal, 1756-ENBT module, and I/O adapter.
• Verify the position (slot) of the I/O modules on the DIN rail.
• Verify that you properly connected all wiring and cabling.
• Make sure you configured your communication driver (such as
AB_ETH-1 or AB-ETHIP-1) in the RSLinx software. See
RSLinx Ethernet Communication Driver in Appendix C
.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Create the Example
Application
Perform the following steps to create the example application:
1.
Start the RSLogix 5000 Enterprise Series software.
The RSLogix 5000 software main dialog opens.
2.
From the File menu, select New.
3.
The New Controller dialog opens.
4.
Enter an appropriate Name for the Controller, for example,
POINT_IO_Controller.
5.
Select the following:
– Revision
– Chassis Type
– Slot number
– Description (optional)
Note: RSLogix 5000 software, revision 18 and later includes enable redundancy. To use redundancy in your system, select the Redundancy
Enabled checkbox. This example does not use redundancy.
6.
Complete the Create In entry by selecting the folder where you want to save the file.
7.
Click OK
.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 57
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
Configure the I/O Modules
You now add the I/O modules to the controller I/O configuration. To do this, first add the local 1756-ENBT Bridge module to the I/O configuration. Next, add the I/O adapter as a child of the 1756-ENBT module, and then add the I/O modules as children of the adapter.
IMPORTANT Click the Help button on the configuration dialog shown in this section if you need assistance in selecting and setting the parameters.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1.
Right-click the I/O Configuration folder in the project dialog and select
New Module.
58 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
The Select Module Type dialog opens.
2.
Select the appropriate Module Type filter Category (for the example we selected Communication), and Module Type Vendor (for the example we selected Allen-Bradley).
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
Note: to select only one category you will need to unselect those already selected.
3.
From the list of adapters displayed, select the 1756-ENBT EtherNet/IP
Bridge and click Create.
The New Module dialog opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 59
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
4.
Enter values for Name, IP Address, and Slot, noting that we used the following values:
Name
IP Address
Slot
Local_ENBT
10.88.70.4
3
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking the Change button. Some of the properties cannot be modified while pending edits exists.
To change the default module properties,
5.
Click Change...
The Module Definition dialog opens.
60
6.
Enter or select values for Series, Revision, Electronic Keying, Rack
Connection, and Time Sync Connection, noting that we used the following values:
Series
Revision
Electronic Keying
Rack Connection
Time Sync Connection
A
5.1
Compatible Module
None
None
7.
Click OK to accept the configuration.
The module appears indented under the I/O Configuration folder.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Add the POINT I/O Adapter to the I/O Configuration
Next, you must add the POINT I/O adapter as a child of the local 1756-ENBT module.
1.
In the Project dialog, right-click the local 1756-ENBT module under the
I/O Configuration folder, and select New Module from the dialog.
The Select Module Type dialog opens.
2.
Select the appropriate Module Type filter Category (for the example we selected Communication), and Module Type Vendor (for the example we selected Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 61
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
3.
Select your adapter (in this example, we use the 1734-AENT/B) from the list and click Create.
The New Module dialog opens.
62
4.
Select the General Tab and enter the module details, noting that we used the following values.
Name
IP Address
POINT_IO_Adapter
10.88.70.2
IMPORTANT Note that the slot field is disabled because the slot is automatically
0 for the 1734-AENT/B adapter.
5.
Click Change...
The Module Definition dialog opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
6.
Enter or select values for Series, Revision, Electronic Keying, Connection, and Chassis Size, noting that we used the following values:
Series
Connection
Chassis Size
Electronic Keying
Revision
B
Rack Optimization
5
Compatible Module
4.3
IMPORTANT The chassis size value equals 1 for the adapter plus the number of I/O modules installed (physically present on the I/O backplane).
Connection choices include:
• None – the adapter makes a direct connection to each of the modules referenced by the data. RPI is disabled in this case.
• Rack optimization– digital I/O data is collected into a rack image. This does not include analog or specialty I/O modules.
• Enhanced rack optimization – digital, analog, and specialty I/O data is collected into a rack image.
• Listen only - rack optimization– read or verify data only, but does not control the modules. When you have multiple controllers - one controller is used to control and the other controllers are used to monitor.
7.
Because we are making a mixed connection (both a direct connection and rack-optimization connection), choose Rack Optimization as the
Connection for the 1734-AENT/B adapter and click OK.
A dialog box opens.
8.
Click Yes.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 63
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
9.
In the New Module screen select the Connection Tab.
10.
Verify that the Requested Packet Interval (RPI) used for the rackoptimization connection to the I/O modules is appropriate for your system (20.0 ms for this example). If not, change it to the correct value.
IMPORTANT To avoid overloading the adapter, it is recommended that the RPI be no less than 10.0 ms for rack-optimization and enhanced rackoptimization connections, and 50.0 ms for direct connections.
11.
Click OK to accept the configuration.
The 1734-AENT/B adapter appears indented under the local
1756-ENBT bridge module in the I/O Configuration folder.
64 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Add the POINT I/O Modules and Configure for Rack-optimization
Connection
You must now add the POINT I/O modules to the I/O Configuration List under the adapter. In this example, the digital input and output modules are configured for rack optimization.
Add the Digital Relay Output Module
1.
Right-click the POINT I/O Chassis in the I/O Configuration folder and select New Module
…
The Select Module Type dialog displays.
2.
Select the appropriate filter for Module Type Category (for the example we selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 65
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
3.
From the modules listed select the 1734-OW2 digital relay output module and click Create.
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
The New Module dialog opens.
66
4.
Enter values for Name and Slot, noting that we used the following values.
Name
Slot
POINT_Relay_Output
1
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking the Change... button. Some of the properties cannot be modified while pending edits exist.
5.
Select Change...
The Module Definition dialog displays.
6.
Change the Connection from Data to Rack Optimization and click OK.
Note that the requested packet interval (RPI) is the same as was chosen by the adapter. You use this value for the rack-optimization connection to the
I/O modules.
IMPORTANT To avoid overloading the I/O adapter, we recommend that the RPI be no less than 10 ms for rack-optimization and enhanced rackoptimization connections, and 50 ms for direct connections.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 67
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
7.
In the New Module screen select the Connection tab and verify that the
Requested Packet Interval (RPI) used for the rack-optimization connection to the I/O modules is appropriate for your system (20.0 ms for this example). If not, change it to the correct value.
8.
Click OK to accept the configuration.
The digital output module appears indented under the local
1734-AENT/B adapter in the I/O Configuration folder.
68 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Add the POINT I/O Modules and Configure for Enhanced Rackoptimization Connection
You must now add the POINT I/O modules to the I/O Configuration List under the adapter. In this example, the digital input and output modules are configured for enhanced rack optimization.
Add the Digital Relay Output Module
1.
Right-click the POINT I/O Chassis in the I/O Configuration folder and select New Module
…
The Select Module Type dialog displays.
2.
Select the appropriate filter for Module Type Category (for the example we selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 69
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
3.
From the modules listed select the 1734-OW2 digital relay output module and click Create.
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
The New Module dialog opens.
70
4.
Enter values for Name and Slot, noting that we used the following values.
Name
Slot
POINT_Relay_Output
1
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties by clicking the Change... button. Some of the properties cannot be modified while pending edits exist.
5.
Select Change...
The Module Definition dialog displays.
6.
Note that the requested packet interval (RPI) is the same as was chosen by the adapter. You use this value for the enhanced rack-optimization connection to the I/O modules.
IMPORTANT To avoid overloading the I/O adapter, we recommend that the RPI be no less than 10 ms for rack-optimization and enhanced rackoptimization connections, and 50 ms for direct connections.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 71
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
7.
Click OK to accept the configuration.
The digital input module appears indented under the local
1734-AENT/B adapter in the I/O Configuration folder.
72
Add the POINT I/O Module and Configure For Direct Connection
Add The Digital Sink Output Module
1.
Right-click the POINT I/O Chassis in the I/O Configuration folder and select New Module
.
The Select Module Type dialog opens.
2.
Select the appropriate filter for Module Type Category (for the example we selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already selected.
IMPORTANT If you exceed the adapter chassis size trying to add more modules than you configured, the New Module selection appears dim and is disabled. Increase the adapter chassis size to add more I/O modules.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
3.
From the modules listed select the 1734-OV4E/C Digital Sink Output module and click Create.
TIP In the Select Module Type dialog, you have options to search for a specific module, add modules to a Favorites list, filter by Category and/or Vendor, Hide and Show Filters, use Module Discovery, sort by vendor, or access your Favorites list.
The New Module dialog opens.
4.
From the New Module dialog, complete the following:
– Enter a value for Name.
– Enter a value for Slot.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 73
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
5.
Select Change...
The Module Definition dialog displays.
6.
For Connection, select Data and click OK.
This configures the controller to make a Direct I/O Connection to the module.
7.
From the New Module dialog, select the Connection tab to set the RPI value. RPI is selectable since it is a direct connection.
74 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Note that the RPI is selectable and has a default value. Because we are making a direct connection to each I/O module, we must specify an RPI to determine how often the data is exchanged with the adapter for each module
IMPORTANT To avoid overloading the I/O adapter, we recommend that the RPI be no less than 10 ms for rack-optimization and enhanced rackoptimization connections, and 50 ms for direct connections.
8.
From the New Module dialog, enter 50 for the Requested Packet Interval
(RPI).
9.
Keep the following unchecked.
a. Inhibit Module b. Major Fault on Controller If Connection fails While in Run Mode
10.
Click OK.
11.
Choose File
Save and enter the name and location of the file.
Download the Program to the Controller
Follow this procedure to download the program we just saved to the
ControlLogix controller.
1.
From the main menu, choose Communications>Who Active.
2.
From the Who Active dialog, navigate to select the slot where the controller is located in the chassis.
3.
Click Set Project Path.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 75
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
4.
Click Download.
The Download dialog opens.
5.
From the Download dialog, click Download.
The Downloading dialog displays the download progress.
Notice that the 1756-ENBT Bridge is now online.
Verify the Module
Chassis Size
76
If yellow triangles are present, see the following section.
You have now built the I/O tree and the RSLogix 5000 software uses the chassis size from the General tab of the adapter for the rack-optimization I/O connection. Now you need to configure this new chassis size value into the adapter non-volatile memory. This procedure synchronizes the chassis size value from the RSLogix 5000 software into the adapter hardware. You must be online to perform this procedure.
1.
Verify that the RSLogix 5000 software is online.
2.
Right-click the name of the adapter under I/O Configuration in the
Project dialog.
3.
Select Properties.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
4.
Click the Connection tab.
The Module Fault error code displays at the bottom of the
Connection tab.
5.
Click the Chassis Size tab.
6.
Click Set Chassis Size in Module.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 77
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
7.
Read and acknowledge the warning dialog.
8.
Click OK to continue.
9.
Notice the chassis size in the module is modified to 5.
78
10.
Click OK.
At this point, your POINTBus status LED should be solid green. All the yellow triangles in your I/O configuration should be gone.
11.
Click OK to close the dialog.
12.
Click File
Save to save the project.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software Chapter 5
Access Module Data
Use the following information to use the I/O adapter data in the ladder logic program:
• POINT_IO_Adapter — the name you gave to your EtherNet adapter
• # — slot number of POINT I/O module
• C — configuration, I = input, O = output
Chapter Summary
Use the controller tags in your ladder program to read input data or write output data.
• For ControlLogix controller information, refer to ControlLogix System
User Manual, publication 1756-UM001 .
• Slot Status Bits: The Slot Status bits display the connection status for each of the POINT I/O modules that use a rack-optimization connection.
– Bit 0 is reserved for the adapter and always reports a value of 1.
– Each of the other bits (1 to 63) correspond to a POINT I/O module that you install in the POINT I/O backplane.
– In this example, we configured the 1734-AENT adapter for both rackoptimization and direct connections.
The slot status bits indicate that we installed the module in slot 2 with it operating correctly:
0 = module participating with no errors and
1 = module not participating or connection error (typically, module removed/missing)
This chapter provided instructions on configuring an AENT Adapter for Direct
Connection, Rack-Optimization, and Enhanced Rack-Optimization in
RSLogix 5000 Software. It included information about hardware setup; configuring the I/O Modules; adding an I/O adapter to the I/O configuration; configuring for rack-optimization connections; configuring for direct connections; and accessing module data.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 79
Chapter 5 Configure the Adapter for Direct Connection, Rack Optimization, and Enhanced Rack Optimization in RSLogix 5000 or Logix Designer Software
80 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Chapter
6
Troubleshoot the Adapter
Interpret the Status
Indicators
This chapter describes the different status indicators available in the 1734
POINT I/O EtherNet/IP adapter and how to interpret these indicators to help troubleshoot the module.
The following table lists where to find specific information
Topic
Interpret the Status Indicators
Status Indicators for POINT I/O Adapters
Page
ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
The 1734 POINT I/O EtherNet/IP adapters have the following status indicators:
• Module Status,
• Network Activity,
• Network Status
• POINTBus Status
• System Power
• Field Power
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 81
Chapter 6 Troubleshoot the Adapter
Status Indicators for POINT I/O Adapters
The following describes the status indicators on the 1734-AENT.
0 0 2
Module Status
Network Activity
Network Status
POINTBus Status
System Power
Field Power
43264
Status Indicators for 1734-AENT Adapter
Indicator
Module Status
Status
Off
Flashing green
Solid green
Flashing Red
Solid red
Network Activity Off
Flashing green/Off
Network Status
Steady green
Off
Flashing green
Green
Flashing red
Solid red
Flashing red/green
Description
No power applied to device
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Device is operating normally.
Recoverable fault. Complete firmware update, verify address switches.
Unrecoverable fault has occurred:
• Self-test failure present (checksum failure, or RAMtest failure at cycle power).
• Firmware fatal error.
No link established.
Transmit or receive activity present.
Link established.
Device not initialized. The module does not have an IP address.
No CIP connections present. Device has an IP address, but no CIP connections are established.
CIP connections present. Device online and has an IP address, and CIP connections are established.
One or more CIP connections in timed-out state. Check for I/O module failure and controller operation.
Note: This does not apply to POINTGuard I/O connection timeout.
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
The module is performing a self-test (only occurs during cycle power test).
82 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Troubleshoot the Adapter Chapter 6
Status Indicators for 1734-AENT Adapter
Indicator Status
POINTBus Status Off
Flashing red/green
Flashing red
System Power
Field Power
Solid red
Flashing green
Solid green
Off
Solid green
Off
Solid green
Description
Device not powered – check module status indicator.
LED cycle power test present.
Recoverable fault occurred:
• At cycle power the number of expected modules does not equal the number of modules present
• A module is missing
• Node fault (I/O connection timeout) occurred.
Unrecoverable fault occurred – the adapter is bus off.
Firmware (NVS) update in progress.
Adapter online with connections established (normal operation,
Run mode).
Not active; field power is off or DC-DC converter problem present.
System power is on; DC-DC converter is active (5V).
Not active; field power is off.
Power is on; 24V DC is present.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 83
Chapter 6 Troubleshoot the Adapter
Notes:
84 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Appendix
A
Specifications
General Specifications
The 1734-AENT adapters have the following general specifications.
General Specifications
Attributes
Expansion I/O capacity, max
POINTBus current requirements, max
Description
•63 modules
•Up to 5 rack-optimization (for digital modules only) and/or enhanced rack-optimization (for digital, analog, and specialty modules) connections
•31 direct connections
(1)
•Backplane current output = 1.0 A.
•Actual number of modules can vary.
•Add together the current requirements for the modules you want to use to make sure they do not exceed the amperage limit of 1.0 A for the adapter.
•Backplane current can be extended beyond 1.0 A by 1734-EP24DC or 1734-EPAC backplane extension power supplies.
•Add multiple 1734-EP24DC or 1734-EPAC modules to reach the 63 module max.
•50 mA (Catalog number 1734-IB4D)
•75 mA (Catalog numbers 1734-IB2, 1734-IB4, 1734-IB8, 1734-IV2,
1734-IV4, 1734-OB2, 1734-OB4, 1734-OB8, 1734-OB2E,
1734-OB2EP, 1734-OB4E, 1734-OB8E, 1734-OV2E, 1734-OV4E,
1734-232ASC, 1734-485ASC, 1734-ARM, 1734-IV8, 1734-OV8E,
1734-IE4C, 1734-IE8C, 1734-OE4C, 1734-IA4, 1734-IM4, 1734-OA4,
1734-IR2E, 1734-IE2C, 1734-OE2C, 1734-IE2V, 1734-OE2V,
1734-IA2, 1734-IM2, 1734-OA2)
•80 mA (Catalog number 1734-OW2, 1734-OW4)
•100mA (Catalog numbers 1734-OX2, 1734-8CFG, 1734-4IOL)
•110mA (Catalog number 1734-SSI)
•160mA (Catalog numbers 1734-IJ2, 1734-IK2)
•175mA (Catalog number 1734-IT2I)
•180mA (Catalog numbers 1734-VHSC5, 1734-VHSC24)
•220 mA (Catalog number 1734-IR2, 1734-IR2E)
Starter module – left side of the system.
Module location
(1) Maximum 31 direct connections for standard I/O or maximum 20 direct connections if any safety I/O module resides in the backplane.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 85
Appendix A Specifications
Power Supply
86
General Specifications
Attributes
Status indicators
Wire Size
Wiring category
(1)
Description
3 red/green status indicators (on CPU):
• – Module status
• – Network status
• – POINTBus status
1 green status indicator on CPU:
• – Network activity
2 green power supply status indicators on DC-DC Converter:
• – System power (5V DC to POINTBus Out)
• – Field power (24V DC from Field In)
Power connections:
0.34... 2.1 mm
(22...14 AWG) solid or stranded copper wire rated
@ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max or
90 °C (194 °F) for ControlLogix.
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702.
1 – on communications ports
1 – on power ports
Power consumption, max
Power dissipation, max
Input overvoltage protection
Thermal dissipation, max
Isolation voltage
4.5W @ 28.8V DC
15.5W @ 28.8V DC
Reverse polarity protected
9.5 BTU/hr @ 28.8V DC
50V (continuous), Reinforced Insulation Type, between all circuits.
Type tested @ 500V AC for 60 s
Field power supply
Field power output
10...28.8V DC @ 10A
10...28.8V DC @ 9A
Module input 10...28V DC @ 1000 mA
Dimensions (HxWxD), approx.
76.2 x 54.9 x 133.4 mm
(3.0 x 2.16 x 5.25 in.)
Enclosure type rating
Terminal base screw torque
Weight, approx.
None (open-style)
0.8 Nm (7 lb-in)
255 g (0.56 lb)
(1) Use this Conductor Category information for planning conductor routing. Refer to the Industrial Automation
Wiring and Grounding Guidelines, publication 1770-IN041 and to the appropriate System Level Installation
Manual.
The 1734-AENT modules have the following power supply specifications:
Power Supply Specifications
Attributes
Input voltage rating
Input voltage, range
Field side power, max
Inrush current, max
Description
24V DC @ 10 A
10...28.8V DC
24V DC @ 400mA
6.0 A for 10 ms
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Specifications Appendix A
Power Supply Specifications
Attributes
Input overvoltage protection
POINTBus output, max
Interruption
Description
Reverse polarity protected
5V DC @ 1.0 A
Output voltage stays within specifications when input drops out for 10 ms @ 10V with max load
EtherNet Communication
The 1734-AENT adapter modules have the following EtherNet communication specifications.
EtherNet Communication Specifications
Attributes
Ethernet communication rate
Ethernet port
Ethernet network topologies supported
Ethernet connectors
Ethernet cable
Ethernet wire connections, max
Description
10/100 Mbits/s, half or full-duplex
1
Star, Tree
RJ-45, Category 5
Category 5: shielded or unshielded
See Wire Size on page 86
Environmental
Specifications
The 1734-AENT EtherNet/IP Adapter modules have the following environmental specifications.
Environmental Specifications
Attributes
Temperature, operating
Description
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
Temperature, nonoperating
Temperature, surrounding air, max 55 °C (131 °F)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
Vibration
IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40...85 °C (-40...185 °F)
Shock, operating
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 87
Appendix A Specifications
Environmental Specifications
Attributes
Emissions
ESD immunity
Radiated RF immunity
EFT/B immunity
Surge transient immunity
Conducted RF immunity
North American temp code
IEC Temp Code
Description
CISPR 11:
Group 1, Class A
IEC61000-4-2:
6 kV contact discharges
8 kV air discharges
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 30...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±3 kV @ 5 kHz on communications ports
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communications ports
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80% AM from 150kHz...80MHz
T4A
T4
88 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Certifications
Specifications Appendix A
The 1734-AENT EtherNet/IP Adapter modules have the following
Certifications.
Certifications
Certification
(when product is marked)
(1) c-UL-us
1734-AENT, Series B
UL Listed Industrial Control Equipment, certified for US and Canada. See UL
File E65584.
CE
C-Tick
Ex
KC
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR11; Industrial Emissions
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection “n”
EN 60079-0; General Requirements
II 3 G Ex nA IIC T4 Gc
DEMKO 04 ATEX 0330347X
Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3
ODVA conformance tested to EtherNet/IP specifications EtherNet/IP
(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification/ for
Declaration of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 89
Appendix A Specifications
Notes:
90 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Appendix
B
Adapter Web Dialogs
Overview
The Web dialog of the I/O adapter offers extensive internal and network diagnostics. To view the Web dialogs, enter the IP address of the I/O adapters into your browser
.
For Information About
Work with the Diagnostics Pages
Use the Diagnostic Overview Page
Use the Ethernet Statistics Page
Use the Advanced Diagnostics Page
Work with the Configuration Pages
Use the Network Configuration Page
Work with the Browse Chassis Page
Page
Work with the Home Page
Use the adapter diagnostics home page to access other adapter diagnostics web pages and see the following information.
• Host Name
• Module Name
• Module Description
• Module Location
• IP Address
• Ethernet Address (MAC)
• DHCP Enabled
• Status
• Serial Number
• Product Revision
• Firmware Version Date
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 91
Appendix B Adapter Web Dialogs
Enter the adapter IP address to see the home page.
To display and work with the adapter diagnostics home page, follow these procedures.
IMPORTANT Make sure that your PC Internet LAN setting and your TCP/IP settings are configured to access the subnet on which your adapter communicates.
1.
From your web browser, enter the adapter IP address to see the Home page.
92
Click Expand to show options.
2.
From the Home page, click Expand to show options, or minimize to see
Diagnostics, Configuration, and Browse Chassis options without the expansion.
3.
From the Home page, complete one of these, as desired.
• Click one of the following to access www.ab.com
.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Adapter Web Dialogs Appendix B
– Allen-Bradley logo at the top of the page
– Visit ab.com
for additional information statement under Resources
• Click Rockwell Automation at the top right to go to www.rockwellautomation.com
.
• Click the following to see additional diagnostics web pages.
– Diagnostics - Diagnostic overview, Network Settings,
Ethernet Statistics, I/O Connections, Advanced Diagnostics
– Configuration - Identity, Network, Services
– Browse Chassis
Work with the Diagnostics
Pages
To work with the Diagnostics options, follow these procedures.
1.
From the Home page, click Diagnostics or Expand to see the following diagnostics options from the panel at the left.
• Diagnostic overview
• Network settings
• Ethernet statistics
• I/O connections
• Advanced Diagnostics
2.
In the Refresh Rate field, you can type a refresh rate, noting that the default rate is 15 seconds.
3.
From the panel at the left or tabs at the top of the page, click one of the diagnostics options to see the corresponding page
.
Click tabs to see the corresponding page.
Click from this panel to see the corresponding page.
Type a refresh rate.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 93
Appendix B Adapter Web Dialogs
Use the Diagnostic Overview Page
To use the Diagnostic Overview page for general diagnostics information, follow this procedure.
1.
Click Diagnostic Overview from the tab at the top of the page or panel on the left.
The Diagnostic Overview page opens.
94
Download EDS files for your adapter
2.
From the Diagnostic Overview page, view the following:
• Ring Status
– Network Topology
– Network Status
– Ring Supervisor
• System Resource Utilization
– CPU Utilization
– Module Uptime
• CIP Connection Statistics
– Current CIP MSG Connections
– CIP MSG Connection Limit
– Max Msg Connections Observed
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Adapter Web Dialogs Appendix B
– Current CIP I/O Connections
– CIP I/O Connection Limit
– Max I/O Connections Observed
– Conn Opens
– Open Errors
– Conn Closes
– Close Errors
– Conn Timeout
– Status
• Module Settings
– Chassis Size
– Switches
Use the Network Settings Page
To use the Network Settings page for network related information, follow this procedure.
1.
Click Network Settings from the tab at the top of the page or panel on the left.
This opens the Network Settings page.
2.
From the Network Settings page, view the following:
• Network Interface
– Ethernet Address (MAC)
– IP Address
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 95
Appendix B Adapter Web Dialogs
– Subnet Mask
– Default Gateway
– Primary Name Server
– Secondary Name Server
– Default Domain Name
– Host Name
– Name Resolution
• Ethernet Interface Configuration
– How the Network Configuration was obtained - Static or Dynamic
• Ethernet Port 1
– Interface State
– Link Status
– Media Speed
– Duplex
– Autonegotiate Status
• Ethernet Port 2
– Interface State
– Link Status
– Media Speed
– Duplex
– Autonegotiate Status
Use the Ethernet Statistics Page
To use the Ethernet Statistics page for information about the Ethernet link and interface and media counters, use this procedure.
1.
Click the Ethernet Statistics tab at the top of the page or on the left panel.
96 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
The Ethernet Statistics page opens.
Adapter Web Dialogs Appendix B
2.
From the Ethernet Statistics page, view the following:
• Ethernet Link
– Media Speed, Half or Full Duplex, Autonegotiate Status
• Interface Counters
– In Octets, In UCast Packets, In NUcast Packets,
In Discards, In Errors, In Unknown Protos,
Out Octets, Out Ucast Packets, Out NUcast Packets,
Out Discards, Out Errors
• Media Counters
– Alignment Errors
– FCS Errors
– Single Collisions
– Multiple Collisions
– SQE Test Errors
– Deferred Transmissions
– Late Collisions
– Excessive Collisions
– MAC Transmit Errors
– Carrier Sense Errors
– Frame Too Long
– MAC Receive Errors
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 97
Appendix B Adapter Web Dialogs
Use the I/O Connections Page
To use the I/O Connections page for CIP I/O (Class 1) connection information, follow this procedure.
1.
Click I/O Connections from the tab at the top of the page or panel on the left.
The I/O Connections page opens.
The top value in this column representing Lost shows the number of packets from the missing source.
98
The value for Slot shows the slot number of the I/O module this connection is controlling.
2.
From the I/O Connections page, view the following:
• Connection Number
• Uptime
• Receive and Transmit (Rcv/Xmt)
• Connection ID
• Source IP Address with an indication of the following:
– (O) for originator
– (T) for target
• Destination IP Address
• Multicast Address
• Requested Packet Interval (RPI)
• Lost/Slot that shows the number of lost packets and the slot number for the connection, with a slot value of 0 indicating that this is a rackoptimization connection
• Size of data in bytes
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Adapter Web Dialogs Appendix B
Use the Advanced Diagnostics Page
To use the Advanced Diagnostics page to review message services, use this procedure.
1.
Click Advanced Diagnostics from the tab at the top of the page or panel on the left. The Advanced Diagnostics page opens.
2.
From the Advanced Diagnostics page, select Backplane Statistics to see values similar to that shown.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 99
Appendix B Adapter Web Dialogs
3.
From the Advanced Diagnostics page, select Module Statistics to see values similar to that shown.
Work with the
Configuration Pages
To work with the Configuration pages, follow these procedures.
IMPORTANT The values on these pages are in non-volatile memory. Changes to these parameters do not take effect until you reset or cycle power through the I/O adapters.
IMPORTANT If you set the value of the I/O adapters switch to 888 and then power cycle the module, the following occurs:
·
The DHCP Enabled function is enabled (set to True).
·
The Ethernet link is negotiated automatically. The Auto Negotiate function is set to True.
·
The web server is enabled. The Disabled Web Server function is disabled.
·
The Ethernet port are disabled. Both ports are re-enabled once the switches are returned to their previous value and power is cycled.
·
The password for this page resets to the factory default which is
“password”.
Note the value of the switches before you enter the 888 value because you must return the adapter to those values once this process is complete.
100 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Adapter Web Dialogs Appendix B
1.
From the Home page, click Configuration or Expand to see the
Configuration options, if needed.
2.
From the Configuration page, click one of the following:
• Identity
• Network
• Services
A login dialog opens as shown. The dialog may vary in appearance depending on your operating system and browser.
3.
From the user name and password dialog, enter values, noting the following:
• The values for user name and password are case sensitive.
• The default user name is admin.
• The default password is “password”.
4.
Click OK to log in. After you log in, you can go to any of the
Configuration pages without having to log in again.
5.
Refer to the section of this manual that corresponds to the section you clicked:
• Identity
• Network Configuration
• Services
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 101
Appendix B Adapter Web Dialogs
Use the Identity Page
To use the Identity page to make entries for the host name, module description, module location, and chassis size, use this procedure.
1.
Click Identity from the tab at the top of the page or panel on the left.
The Identity page opens
102
2.
From the Identity page, complete entries for the following, noting that the description and location help you identify where modules are in the facility:
• Host Name – the name a Domain Name Server uses to resolve this adapter’s IP address
• Module Description
• Module Location
• Chassis Size - the value that shows the number of I/O modules plus the adapter. This value must match the number of I/O modules plus 1 for the adapter before any I/O connections are allowed.
3.
Click Apply Changes to save the modified values.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Adapter Web Dialogs Appendix B
Use the Network Configuration Page
To use the Network Configuration page to make entries for enabling or disabling
DHCP and setting TCP/IP parameters and Ethernet link operation, follow this procedure.
1.
Click Network from the tab at the top of the page or panel on the left. The
Network Configuration page opens.
2.
From the Network Configuration page, complete these entries, noting that values for Network Interface are disabled when DHCP is
Dynamic DHCP and port speed and duplex mode are disabled when
Autonegotiate Speed and Duplex is selected.
• For Initial Network Configuration:
– Ethernet Interface Configuration
- Static
- Dynamic DHCP
• For Network Interface, select from these choices:
– IP Address
– Subnet Mask
– Gateway Address
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 103
Appendix B Adapter Web Dialogs
– Primary Name Server
– Secondary Name Server
– Domain Name
• For Ethernet Link, select from these choices:
– Autonegotiate Status
- Autonegotiate Speed and Duplex
- Force Speed and Duplex
– Select Port Speed - 10 megabits, 100 megabits
– Select Duplex Mode - Half Duplex, Full Duplex
3.
From the Network Configuration page, click Apply Changes to save the modified values.
IMPORTANT If there is a mismatch in duplex between the adapter and the connected equipment you may experience 'intermittent connectivity.' For complete details and information on how to resolve this, refer to publication ENET-A003 .
Use the Services Page
To use the Services page to change the password for the Configuration web page or disable the web server, complete these procedures.
1.
Click Services from the tab at the top of the page or panel on the left.
The Services page opens.
104
2.
From the Services page, make these entries.
• Click in the Enable box to change whether the web server runs after the module is reset.
• Click in the Enable box to change whether QoS is enabled or disabled after the module is reset.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Work with the Browse
Chassis Page
Adapter Web Dialogs Appendix B
• Change the password by typing the new value for New Password and
Confirm Password, noting the following:
– The entry is case sensitive.
– The default value is the word password.
3.
Click Apply Changes.
Use the Browse Chassis page for the following:
• See what modules are present on the system.
• Run a query from slot 1 to slot 63.
• Display the modules found based on the query.
• Provide an easy way to see which modules the adapter recognizes on your system.
To work with the Browse Chassis page, follow these procedures.
1.
From the Home page, click Browse Chassis
.
The following page displays.
2.
Click START to run a query. A Browser Chassis page opens.
Note that module hyperlinks are inactive before the query completes or is cancelled.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 105
Appendix B Adapter Web Dialogs
After completing a query, here is how a typical Browse Chassis page looks.
If there is no response to the query, the Module not found message appears.
3.
To view information about a particular module, click the corresponding
Module Description hyperlink. In the following example, the first Module has been selected:
106
The 1734 Module Information page opens showing this information about the module:
• Product Name
• Vendor
• Product Type
• Product Code
• Module Revision
• Serial Number
• Status
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Appendix
C
Configure the RSLinx Ethernet
Communication Driver
Overview
To communicate with your adapter over your network, you must configure the
RSLinx Ethernet Communication Driver (AB_ETH) or the EtherNet/IP driver
(AB-ETHIP). You can configure the AB_ETH driver with the IP addresses of all the Ethernet devices on your system. You need one of these drivers to download the example application programs in this manual.
See the table for a list of the contents of this appendix.
For Information About
Page
ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
Install the RSLinx Software
Use this procedure to install the RSLinx software on your computer.
1.
Insert the CD in the CD-ROM drive.
Note that the CD-ROM supports Windows Autorun. Once inserted into the CD-ROM drive, if you have Autorun configured, the installation automatically starts at the first setup screen.
If Autorun is not configured for your CD-ROM drive, go to step 2.
2.
From the Start menu, choose Run. The Run dialog opens.
3.
Type D:/setup (if it doesn’t appear automatically), where D: is your CD-
ROM drive letter.
4.
Click OK.
The progress bar, followed by the welcome screen opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 107
Appendix C Configure the RSLinx Ethernet Communication Driver
Configure the AB_ETH
Driver
To configure the AB-ETH Ethernet communication driver perform the following steps:
1.
Start the RSLinx software.
2.
From the Communications menu, select Configure Drivers.
3.
Select Ethernet Devices from the list and click Add/New...
108
4.
Select the default driver name (for example, AB_ETH-1) or type in a name and click OK.
The Configure driver dialog opens.
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the RSLinx Ethernet Communication Driver Appendix C
5.
Click Add New and enter the IP address or Host Name of your Ethernet device (for example, 10.88.70.4, Pump1).
6.
Repeat step 6 for each additional Ethernet device you need to access.
7.
After entering the IP addresses, click Apply.
8.
Click OK to close the Configure driver dialog.
The new driver appears in the list of configured drivers. Your list displays the drivers you configured on your workstation.
9.
Close the RSLinx software .
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 109
Appendix C Configure the RSLinx Ethernet Communication Driver
Configure the AB_ETHIP
Driver
To configure the AB-ETHIP Ethernet communication driver, perform the following steps.
1.
Start the RSLinx software.
2.
From the Communications menu, select Configure Drivers.
3.
Select EtherNet/IP Devices from the list and click Add/New...
110 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Configure the RSLinx Ethernet Communication Driver Appendix C
The Configure Driver dialog box opens.
Make sure the Browse Local Subnet button is selected.
The RSLinx software browses your local subnet and automatically reads the IP address.
4.
Click OK.
The AB-ETHIP driver is now configured and appears in the configured drivers window.
5.
Close the RSLinx software .
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 111
Appendix C Configure the RSLinx Ethernet Communication Driver
Notes:
112 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Index
Numerics
1734-AENT specifications
A
adapter
AENT
diagnostics
features
I/O
mounted
address fixed IP
Gateway
IP
network
switches
auto negotiate
autobaud
Autonegotiate Status
B
bandwidth insufficient
limit
used
BootP software
BootP/DHCP utility
C
chassis
ControlLogix
size
chassis size
CIP
set
Common Industrial Protocol
common techniques used in this manual
compatibility hardware and software
conducted RF immunity
configuration
network
option
page
configure adapter
driver dialog
for direct connection
connection direct
controller
ControlLogix
L63
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 tags
conventions
D
data messaging
Default Gateway
device consuming
producing
DHCP
(Dynamic Host Configuration Protocol)
enabled
server
software
DHCP enabled function
Diagnostic messaging
diagnostic general information
messaging
overview
diagnostics
additional
page
web page
web pages
Dimensions
DIN rail
direct connection
,
disabled web server function
download program
driver
AB_ETH
AB-ETHIP
configured
EtherNet/IP
RSLinx Ethernet communication
Duplex
E
EFT/B immunity
empty terminal bases
Enclosure type rating
enhanced rack-optimization
ESD immunity
EtherNet adapter
Ethernet device
link
statistics
113
Index
Ethernet cable
Ethernet communication rate
Ethernet connectors
Ethernet Interface Configuration
Ethernet network topologies supported
Ethernet ports
Ethernet wire connections
EtherNet/IP bridge
driver
Ethernet Industrial Protocol
example applications
F
Field power output
Field power supply
Field side power
firmware revisions
G
Gateway default
Gateway address
H
Home page
Host ID
Host Name
host name
I
I/O adapter
connection
direct connection
connection format
direct connection rack-optimization connection
enhanced rack-optimization connection
module
modules
I/O adapter
primary tasks
I/O configuration folder
I/O Connection
I/O connection direct
enhanced rack-optimization
rack-optimization
114
I/O Connections
I/O connections
I/O data real-time
I/O Hardware set up
I/O module
bridge
Identify page
Identity
page
information configuration
programming
Input overvoltage protection
Input voltage rating
Input voltage, range
Inrush current
Interface State
Interruption
IP address
fixed address
network
IP Address
IP address
fixed
IP network
splitting
subgroup
subnet
Isolation voltage
L
ladder logic program
ladder program example
Link Status
M
manuals related
Media Counters
Media Speed
messaging explicit
implicit
mix enhanced rack-optimization
rack-optimization
model master/slave
producer consumer
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Index producer/consumer
Module
module
location description
Module Description
Module input
modules overview
N
Network settings
network configuration
Network Address
thumbwheel
network address
network address switches
Network Configuration
Network Settings
O
Overview
1734 POINT I/O Installation
P
pen-push thumbwheel
POINTBus output current
power consumption
Power dissipation
power up system for the first time
primary tasks
protocol message-based
publications related
purpose of this manual
Q
QoS Quality of Service
R
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 rack optimized connection
rack-optimization
radiated RF immunity
rate of change
recover from an overloaded adapter
Refresh Rate
reinsertion of modules
Related Documentation
related publications
Relation List
relative humidity
relative path
removal of modules
replacement of adapter
requested packet interval (RPI)
RJ-45 connectors
Rockwell BootP utility
RPI
RPI requested packet interval
RSLinx
Ethernet communication driver
RSLinx software
install
S
select
Ethernet Devices
Services
page
shock nonoperating
operating
software releases
specification emissions
ESD immunity
specifications general
statistics
Ethernet
status indicators
subgroup
subnet
Subnet Mask
subnet mask
surge transient immunity
T
TCP/IP network
temperature ambient
nonoperating
operating
115
Index
Terminal base screw torque
Thermal dissipation
thumbwheel chassis size
network address
settings
U
upgrades firmware
software
Uptime
V
vibration
W
web dialogs
server
web dialogs
Advanced Diagnostics
Browse Chassis
Diagnostic Overview
Ethernet Address
Ethernet Link
Ethernet Statistics
web page diagnostics
web server disable
Weight, approx.
wiring
116 Rockwell Automation Publication 1734-UM018D-EN-E - September 2017
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/ , you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/ .
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States or Canada
Outside United States or
Canada
1.440.646.3434
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html
, or contact your local Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
United States
Outside United States
Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.
Please contact your local Rockwell Automation representative for the return procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002 , available at http://www.rockwellautomation.com/literature/ .
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Publication 1734-UM018D-EN-E - September 2017 118
Supersedes Publication 1734-UM018C-EN-P - March 2015 Copyright © 2017 Rockwell Automation, Inc. All rights reserved.
Download
Advertisement
Key features
Connects POINT I/O modules to EtherNet/IP networks.
Supports real-time I/O data control (implicit messaging).
Supports messaging data for configuration and programming (explicit messaging).
Offers configuration via RSLogix 5000 or Logix Designer software.
Supports multiple controller connections simultaneously.
Supports Rack-optimization, Enhanced Rack-optimization, and Direct Connections
Frequently asked questions
It provides connectivity to EtherNet/IP networks for POINT I/O modules.
It supports direct, rack-optimization and enhanced rack-optimization connections.
RSLogix 5000 or Logix Designer software.