American Dynamics 2032 Installation And Operating Instructions Manual
American Dynamics 2032 Alarm Responder is a device designed to provide relay closures when a monitor goes into an alarm condition. It can be used with American Dynamics Matrix Switching Systems to follow and respond to alarm conditions. The 2032 can follow up to 128 system monitors, in groups of 16. It features screw terminal wire connectors, LED indicators for valid code and power, DIP switch selection for monitor groups, and compatibility with either data line or control code.
Reklamë
Reklamë
2032
Alarm Responder
Installation and Operating Instructions
This manual describes the installation and operating procedures for the American Dynamics model 2032 Alarm Responder.
The 2032 Alarm Responder can be used with all American Dynamics Matrix Switching Systems to follow and respond to alarm conditions. The 2032 Alarm Responder provides a relay closure when a monitor goes into an alarm condition. The relay closures may be used to start a VCR or other such device. Other uses include the operation of panel displays showing alarmed monitors.
The software/firmware furnished with this equipment is confidential to and is copyrighted by SENSORMATIC
ELECTRONICS CORPORATION. It is not to be copied or disclosed in any manner without the express written consent of
SENSORMATIC. The software/firmware is furnished to the purchaser under a license for use on a single system.
Information furnished by SENSORMATIC is believed to be accurate and reliable. However, no responsibility is assumed by
SENSORMATIC for its use; nor for any infringements of other rights of third parties which may result from its use. No license is granted by implications or otherwise under any patent or patent rights of SENSORMATIC.
Copyright 2000 by Sensormatic. All rights reserved.
AMERICAN
DYNAMICS
The installation of this product should be made by qualified service personnel and should conform to all local codes.
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
!
CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK,
DO NOT REMOVE COVERS (OR BACK) .
NO USER-SERVICEABLE PARTS INSIDE.
REFER SERVICING TO QUALIFIED SERVICE PERSONNEL
!
The lightning flash with arrowhead symbol, within an equilateral triangle, is intended to alert the user to the presence of uninsulated
"dangerous voltage" within the product's enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance
(servicing) instructions in the literature accompanying the product.
W ARRRRNN N G
To reduce the risk of fire or shock hazard, do not expose this product to rain or moisture.
This equipment has been tested and found to comply with Part 15 of the
FCC Rules.
Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.
UUU N N G A N O N
Unpack carefully. This is an electronic product and should be handled as such. Compare the items received with the packing list with your order.
Be sure to save:
1. The shipping cartons and insert pieces. They are the )
safest material in which to make future shipments of
the product.
2. The IMPORTANT SAFEGUARDS sheet.
3. These Installation and Operating Instructions.
M AIIIINN N A
User maintenance of this unit is limited to external cleaning and inspection. For specific recommendations refer to the
IMPORTANT SAFEGUARDS sheet packaged with this product.
A N
If you require information during installation of this product or if service seems necessary, contact the
Sensormatic Repair and Service Department at (800)
442-2225. You must obtain a Return Authorization Number and shipping instructions before returning any product for service.
Do not attempt to service this product yourself. Opening or removing covers may expose you to dangerous voltages or other hazards. Refer all servicing to qualified personnel.
QA301D
Table of Contents
Description ............................................................ 1
Features ................................................................. 1
Installation............................................................ 2
Setup ..................................................................... 2
Monitor Select............................................ 2
Connections
Relay Connections ..................................... 3
Data Line Connections............................... 3
Control Code Line Connections................. 4
Operation.............................................................. 5
Power Sources ...................................................... 5
Powering Up......................................................... 5
Typical System Connections ....................Appendix
Specifications ...........................................back page
DESCRIPTION
GROUP 1
PWR
DATA
GROUP 2
ON
OFF
SELECT
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
1
A B
17
2
A B
18
3
A B
19
4
A B
20
A B A B A B A B
B W S
5 6 7 8
A B
21
A B
22
A B
23
A B
24
A B A B A B A B
9 10 11 12
A B
25
A B
26
A B
27
A B
28
A B A B A B A B
13 14 15 16
A B
29
A B
30
A B
31
A B
32
A B A B A B A B
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
DATA LINE
IN
1
OUT
120V
60Hz
Figure 1 - 2032 Alarm Responder Rear Panel
DESCRIPTION FEATURES
The 2032 Alarm Responder provides relay contact closures which correspond to Matrix Switching System monitors that are in an alarm condition. The Alarm Responder reads the switching system's LAN/Data Line or Control Code interface to determine which monitor is in alarm, then provides a contact closure that corresponds to the monitor in alarm.
The 2032 Alarm Responder has the following features:
☛
☛
SCREW TERMINAL WIRE CONNECTORS
LED INDICATOR FOR “VALID" CODE
☛
LED POWER INDICATOR
The 2032 receives data from either the LAN output of a 1995, the DATA LINE output of a 1996, or the Control Code output of other Matrix Switching Systems.
☛
DIP SWITCH SELECTION FOR MONITOR GROUP
☛
COMPATIBLE WITH EITHER DATA LINE OR
CONTROL CODE
The 2032 filters the incoming codes for monitor commands to identify alarm messages. When a monitor alarm is detected, the corresponding 2032 relay contact is closed. After all alarms have been cleared from a followed monitor, the corresponding relay closure opens.
☛
UNIVERSAL MOUNT CABINET
The Alarm Responder can follow a maximum of 128 system monitors, in groups of 16. Note: Monitors 65-128 can be followed only from 1995/1996 systems, on Data Line 2. The
2032 contains 32 addressable, normally open relays. The 32 relays can be grouped in series or in two groups of 16. Each of the two groups can control 16 relays.
IF YOU ENCOUNTER ANY PROBLEMS
OPERATING THIS UNIT, OR NEED
TECHNICAL ASSISTANCE, CALL OUR
SERVICE CENTER AT: within the United States: 1-800-442-2225 outside the United States: (845) 624-7600
1
INSTALLATION and SETUP
INSTALLATION SETUP
This installation should be made by qualified service personnel and should conform to all local codes. Safeguards must be taken to avoid unintentional operation by employees and maintenance personnel working about the premises, by falling objects, by customers, by building vibration, and by similar causes.
Monitor Group Select
The relay closures on the 2032 are activated in response to a
Matrix Switching System monitor going into alarm. Two 8position DIP switches located on the rear panel of the 2032 are used to identify the monitors that the 2032 will respond to. The DIP switches and associated relay group connectors are shown in Figure 2.
For optimum performance, the 2032 Alarm Responder should be located near the Switching System Controller or near the
Data Line or Control Code Line of the Matrix Switching
System.
The cabinet of a 2032 may be surface or rack mounted in any convenient location with adequate ventilation. Avoid heat sources or poorly ventilated racks.
The first DIP switch (1) sets the monitor group for the
GROUP 1 relays (relays 1 through 16). The third DIP switch
(3) sets the monitor group for the GROUP 2 relays (relays 17 through 32). The second and fourth DIP switches are not used in the 2032. Switches 1 and 3 can be set either to the same or to two different monitor groups.
Rack Mounting
The 2032 is shipped with mounting ears flush with the front panel, and can be mounted to the front of a standard 19-inch rack. The mounting ears of the 2032 can also be placed such that they are flush with the rear panel. This allows the 2032 to be mounted to the rear of a rack equipped with mounting channels. For proper ventilation allow at least three feet (1m) from the rear of the racks to any wall and one EIA rack height
(1 3/4 inches) between units in a rack.
For Control Code use, each control line contains information for a maximum of eight monitors, thus the DIP switches are not used and must be set to OFF.
For 1995/1996 systems, each Data Line contains information for up to 64 switching system monitors. Data Line 1 is for monitors 1-64 and Data Line 2 is for monitors 65-128. The
DIP switches must be set to identify the group of monitors that the 2032 will respond to, for the Data Line connected to the 2032. Table 1 below shows the DIP switch settings applicable to both Data Lines.
Surface Mounting
The unit can also be surface mounted. Reinstall the mounting ears such that they are perpendicular to the side of the unit.
The mounting ears may be positioned either flush with the top or bottom covers of the unit or offset from the covers.
Table 1 - DIP Switches 1 or 3, Monitor Group Select
0 = OFF, 1=ON
Monitor Group
Data Line 1 Data Line 2
1-16
17-32
65-80
81-96
33-48
49-64
97-112
113-128
A B C D E F
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0 0 0 0
0 0
0 0
0 1
0 1
0
1
0
1
GROUP 1
PWR
DATA
GROUP 2
DIP Switch 1 - Monitor Group Setting for Group 1 Relays (1 - 16)
DIP Switch 2 - Not Used
DIP Switch 3 - Monitor Group Setting for Group 2 Relays (17 - 32)
DIP Switch 4 - Not Used
ON
OFF
SELECT
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
1
A B
17
A B
18
A B
19
A B
20
A B
B W S
2
A B
3
A B
4
A B
5
A B
6
A B
7
A B
8
A B
21
A B
22
A B
23
A B
24
A B
9
A B
25
A B
10 11
A B
26
A B
27
A B A B
12
A B
28
A B
13
A B
29
A B
A B
30
A B
31
A B
32
G1 IN G1 OUT G2 IN G2 OUT
A B
14
A B
A B
15
A B
A B
16
A B
A B
IN
OUT
120V
60Hz
Group 1 Relays
DATA LINE
1
Group 2 Relays
Figure 2 - Monitor Group Relays and Switches
2
A
1
B A
2
B
3
A B A
G1 IN
B
CONNECTIONS
A
G1 OUT
B
Figure 3 - 2032 Relay Contacts (Group 1)
CONNECTIONS
Relay Connections
The 2032 Alarm Responder provides relay closures only; they are not intended to supply power. Two groups (GROUP
1 and GROUP 2) of four 12-pin relay connectors are provided on the rear panel (see Figure 2, page 2). Each group provides connections for double pole relays. The two groups provide 32 pairs of relay closures. Figure 3 illustrates the internal 2032 relay interconnections for Group 1 relays.
For ease of attaching to external equipment, each connector is supplied with a mating screw terminal connector, shown in
Figure 4. Insert the signal and shield wires into the slots of the mating connector and tighten the hold-down screws.
When all lines have been connected, insert the 12-pin connectors into the rear panel mating terminals.
The relay contact ratings are 0.6 Amps at 24 VAC, or 2 Amps at 30 VDC, resistive load. Power through the relays is not supplied by the 2032.
One 12-pin connector on the lower right of the 2032 rear panel contains the common connections for each relay group.
Each set of pins is labeled with the group number G1 IN, G1
OUT, G2 IN, and G2 OUT, and each pin is labeled with an A,
B, and ground. The A and B pins are common contacts for the other side of the double pole relays; G1 IN and OUT are connected to relays 1-16 (see Figure 3), and G2 IN and OUT are connected to relays 17-32. The Group IN connections are used for determining the function of the associated relays, such as providing a user-supplied voltage, a short to ground, or a unique signal on relay activation. The Group IN pins can also be used as inputs from cascading 2032 units. The Group
OUT connections are used to connect the associated relays to a single responding device, such as a speaker or an indicator light, or for cascading to additional 2032’s.
Data Line Connections (1995 or 1996)
The relay connections to the unit must be made with shielded,
2-wire twisted pair (22 AWG or heavier gauge wire or equivalent). The shield wire is to be connected to the grounding terminal.
Each set of three pin connections is labeled with a relay number, from 1 through 32, corresponding to one of the monitors of the monitor group(s) selected. Each pin within one of the numbered sets is also labeled, under the connector, with an A, a B, and a ground symbol. The A and B pins on each connection are the contacts for one side of each double pole relay. The contacts for the other side of each relay are connected to the common Group connectors (next paragraph).
The ground pin is provided for shielding.
A DATA LINE is connected from the DATA LINE OUT
BNC on a Matrix Bay to the DATA LINE IN BNC on the rear panel of the Alarm Responder. (Older 1995 systems used the term LAN IN/OUT). Use a good grade RG-59 video cable (Belden 8241 or equivalent). The DATA LINE OUT
BNC on the Alarm Responder must be fitted with a 75-ohm
BNC terminator, or if used to loop to other DATA LINE controlled equipment, it must be terminated at the end of the run.
The 2032 must be connected to the Data Line which is used for the group of monitors to be followed. For 1995 and 1996 systems, Data Line 1 is for monitors 1-64 and Data Line 2 is for monitors 65-128.
The LED labeled DATA, on the rear panel, will illuminate when valid code is received on the Data Line.
A
B
A
B
HOLD DOWN SCREWS
A
B
A
B
INSERT CONNECTOR
THIS DIRECTION
Figure 4 - Typical 12-Pin Connector
3
CONNECTIONS
Control Code Line Connections
The 12-pin terminal connector located at the lower left side of the rear panel is used for Control Code connections. The connector is labeled B, W, and S. The B is for the BLACK code wire, the W is for the WHITE code wire, and the S is for the SHIELD wire.
The Control Code line connections to the 2032 Alarm
Responder must be shielded, 2-wire twisted pair (Belden
8760; for plenum use Belden 88760 or equivalent).
Multiple 2032s may be connected in a "Star" configuration to a Control Code distribution unit (1691 or 2091). See Figure
5. For this connection, each 2032 must have a 120-ohm termination.
2 0 3 2
B W S
T
2 0 3 2
B W S
T
2 0 3 2
B W S
T
Code Lines are NEC Class 2, low voltage circuits. Where local codes permit, installation in conduit is not required.
Avoid installation near high voltage or other potential interference sources.
OTHER CODE
LINES
CODE
DISTRIBUTOR
T = 120 OHM TERMINATION
Figure 5 - Code "Star" Configuration"
CAUTION - Due to the presence of noninsulated components with hazardous voltages, the following internal adjustments should be performed by qualified service personnel only.
If the 2032 Alarm Responder is used with Control Code, remove the top cover of the unit and locate the DIP switch on the printed circuit board (see Figure 4, below). Set the eighth switch position of this DIP switch to the ON position. This setting enables the use of Control Code in the 2032.
A maximum of three 2032s, or other Control Control devices, may be “Daisy-chained” on a single code line. When devices are “Daisy Chained”, intermediate devices must not contain a
120-ohm termination on the Control Code line. Only the last unit in a "Daisy Chain" has a 120-ohm terminator. See
Figure 6 for “Daisy Chain” connections.
2 0 3 2
B W S
2 0 3 2
B W S
2 0 3 2
B W S
Note: As shipped, the 2032 is set to operate in the Data Line mode; this switch is set to the OFF position.
T
Control Code lines must be terminated in 120 ohms. Check the last unit on each line to ensure that 120-ohm termination is present. Intermediate units on a Control Code line must not have 120-ohm termination. To remove the termination of the 2032 code line, jumper J32 must be removed from the main PCB. See Figure 4 for the location of this jumper.
Note: As shipped, the 2032 is set for 120-ohm termination; this jumper is inserted.
OTHER CODE
LINES
CODE
DISTRIBUTOR
T = 120 OHM TERMINATION
Figure 6 - Code "Daisy Chain" Configuration
J32
ON
12345678
OFF
120 ohm Termination Jumper
Dip Switch
Power Cord
Figure 4 - DIP Switch Location on PCB
4
In switching systems using Control Code, the 2032 Alarm
Responder must be connected to the code line which contains the monitors to be followed.
For 1650A operation, four separate control lines could be in use. The first control line is for monitors 1-8 and cameras 1-
64. The second control line is for monitors 1-8 and cameras
65-128. The third control line is for monitors 9-16 and cameras 1-64. The fourth control line is for monitors 9-16 and cameras 65-128. Separate 2032 Alarm Responders may be required for following monitors on separate control lines.
See the Appendix for illustration of a typical connection to multiple 1650A control lines.
OPERATION
OPERATION Power Sources
After completing the Data Line (or Code) connections, power up the unit (see Powering Up, next section). When the 2032 receives valid code through the Data Line or Control Code inputs, the green DATA LED on the front panel illuminates.
If the green DATA LED is flickering, the code lines may be backwards. Try reversing the black and white code lines.
If the DATA LED does not illuminate, check for proper operation of the System. Check all connections. If all the connections are as they should be and the 2032 still does not operate properly, unplug the 2032, remove the top cover, and check the DIP switch settings. Refer to the DIP switch illustration on page 4.
The 2032 Alarm Responder does not contain an On/Off
Switch. The socket outlet shall be located near the equipment and shall be readily accessible. The 120V units are supplied with a pendant 3-wire cord and plug for mating to the primary source outlet. The 230V units are supplied with a
Euro style IEC 320 type inlet. A suitable detachable cord should be connected between the IEC 320 inlet and the power source. The cord should conform to all national and local use code requirements.7 There is a green PWR LED power indicator, located on the rear panel, that illuminates when power is applied.
If connected to a 1995 or 1996 System Data Line, all the DIP switches should be in the OFF position. If connected to a
1650/1650A System Control Code line, the position for the eighth DIP switch should be in the ON position.
2032 models are configured for 120V, 50/60 Hz or 230V,
50/60Hz primary power source as follows:
AD2032: 120V, 50/60Hz
AD2032-1: 230V, 50/60Hz
Powering Up
DO NOT CONNECT THE EQUIPMENT TO THE POWER
SOURCE UNTIL ALL CONNECTIONS HAVE BEEN
PROPERLY MADE.
Make all connections to the 2032, (Data Lines, Control Code lines, and Relay connections) and set the DIP switches before applying power.
If a valid code is being received, the green DATA LED will illuminate and glow steadily. If it flickers there may be a problem with the Control Input line.
5
APPENDIX
2032 ALARM RESPONDER
Monitor #1 Relay
Connections
1234
A B A B A B A B
DATALINE/LAN
FROM CPU
(1995,1996)
Selects Monitor
Group to Follow
GROUP 1
PWR
DATA
GROUP 2
ON
OFF
SELECT
ABCDEF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
A B A B A B A B
17181920
A B A B A B A B
B W S
5678
A B A B A B A B
21222324
A B A B A B A B
9101112
A B A B A B A B
25262728
A B A B A B A B
13141516
A B A B A B A B
29303132
DATA LINE
IN
1
OUT
A B A B A B A B
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
CONTROL CODE INPUT
(1600, 1650A)
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
Relay Group 1
Input Connections
Relay Group 1
Output Connections or
Cascading to other 2032's
DATA LINE/LAN OUT to
Additional 2032's, Bays, or 75-ohm Terminator
TYPICAL SYSTEM CONNECTIONS
2032 ALARM RESPONDER with 1691
GROUP 1
PWR
DATA
GROUP 2
ON
OFF
SELECT
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
1 2 3 4
A B
17
A B
18
A B
19
A B
20
A B A B A B A B
B W S
5 6
A B
21
A B
22
7 8
A B
23
A B
24
A B A B A B A B
9 10 11 12
A B
25
A B
26
A B
27
A B
28
A B A B A B A B
B S
13 14 15 16
A B
29
A B
30
A B
31
A B
32
A B A B A B A B
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
DATA LINE
IN
1
OUT
120V
60Hz
2032
C O D E L E
1
1691
O U
R S 2 3
18 AWG SHIELDED
TWISTED PAIR BELDEN
8760 OR EQUIVALENT
S W B A C A C
5604-0109-01
12 VOLTS AC
10 VA
M O T O M ON T O M O T O M O T O C A M E R A C A M E R A
1 0
1 1
1 2
1 3
1 4
1 5
1 6
1650/1650A
B
W
S
TYPICAL SYSTEM CONNECTIONS
2032 ALARM RESPONDER with 1650
ALARM CONTACTS
SELECT
1 2 3 4 5 6
ABCDEFGH
A A A A A A
POWER 25 26 27 28 29 30
ALARM
ABCDEFGH
A A A A A A
C
O
M
49 50 51 52 53 54
INPUT OUTPUT
A A A A A A
7 8 9 10 11 12
A A A A A A
31 32 33 34 35 36
A A A A A A
55 56 57 58 59 60
A A A A A A
13 14 15 16 17 18
A A A A A A
37 38 39 40 41 42
A A A A A A
61 62 63 64
A A A A
19 20 21 22 23 24
A A A A A A
43 44 45 4647 48
A A A A A A
PRGM
120V
60Hz
N N C
O C M
2096 ALARM
INTERFACE UNIT
1
RS-232
2
3
J1
OUT
4
SYNC MONITOR
8 7
A
A
B
B
O
U
T
O
U
T
MONITOR
6 5
A
A
B
B
MONITOR
4 3
B
B
A
A
O
U
T
O
U
T
O
U
T
O
U
T
MONITOR
2 1
A
A
B
B
CAMERA
O
U
T
O
U
T
12
13
14
9
10
11
15
16
CAMERA
7
8
5
6
3
4
1
2
1650: MONITORS 1 - 8
J1
OUT
4
MONITOR
16 15
B
B
A
A
MONITOR
14 13
B
B
A
A
MONITOR
12 11
B
B
A
A
MONITOR
10 9
B
B
A
A
CAMERA
O
U
T
O
U
T
O
U
T
O
U
T
O
U
T
O
U
T
O
U
T
O
U
T
14
15
16
9
10
11
12
13
CAMERA
7
8
5
6
3
4
1
2
1650: MONITORS 9 - 16
B
W
S
GROUP 1
PWR
DATA
GROUP 2
B W S
ON
SELECT
ABCDEF
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
1234
A B A B A B A B
ON
OFF
A B A B A B A B
17181920
B W S
5678 9101112
A B A B A B A B
21222324
A B A B A B A B
25262728
A B A B A B A B
13141516
A B A B A B A B A B A B A B A B
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
DATA LINE
IN
A B A B A B A B
29303132 OUT
1
2032: MONITORS 9 - 16
GROUP 1
PWR
DATA
GROUP 2
B W S
ON
SELECT
ABCDEF
OFF
ON
OFF
ABCDEF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
1234
A B A B A B A B
17181920
A B A B A B A B
B W S
5678 9101112
A B A B A B A B
21222324
A B A B A B A B
25262728
13141516
A B A B A B A B
29303132
DATA LINE
IN
1
OUT
A B A B A B A B A B A B A B A B A B A B A B A B
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
2032: MONITORS 1 - 8
TYPICAL SYSTEM CONNECTIONS
2032 ALARM RESPONDER with
1024
ALARM CONTACTS
POWER
SELEC
T
ABCDEFGH
1 2 3 4 5 6
A A A A A A
25 26 27 28 29 30
ALARM
ABCDEFGH
A A A A A A
49 50 51 52 53 54
C
O
M
INPUT OUTPUT
A A A A A A
7 8 9 10 11 12
A A A A A A
31 32 33 34 35 36
A A A A A A
55 56 57 58 59 60
A A A A A A
13 14 15 16 17 18
A A A A A A
37 38 39 40 41 42
A A A A A A
61 62 63 64
A A A A
19 20 21 22 23 24
A A A A A A
43 44 45 46 47 48
PRGM
A A A A A A
120V
60Hz
N N C
O C M
2096 ALARM
INTERFACE UNIT
DATA LINE
1 2
PORTS
PROG MON
120V
60Hz
1024 CPU
1 2
3 4 5 6 7 8 9 10
T o 1024 Bays and 2032 for MONITORS 65-128
1
S
I
O
N
X
P
A
N
E
/
T
E
S
T
DATA LINE
IN
OUT
SYNC
120 VAC
50/60 Hz
1024 Bay
3
4
1
2
5
6
7
8
9
10
11
12
13
14
15
16
Additional 1024 Bays
GROUP
1
PWR
DATA
GROUP
2
SELECT
ON
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
ON
OFF
ABCDEF
1
A B A B A B A B
17
2
18
3
19
4
20
A B A B A B A B
B W S
5 6 7 8
A B A B A B A B
21 22 23 24
A B A B A B A B
9 10 11 12
A B A B A B A B
25 26 27 28
A B A B A B A B
13 14 15 16
A B A B A B A B
29 30 31 32
A B A B A B A B
G1 IN G1 OUT G2 IN G2 OUT
A B A B A B A B
DATA LINE
IN
1
OUT
120 VAC
50/60 Hz
TERMINATION
2032:
MONITORS 1 - 64
DECLARATION OF CONFORMITY
According to ISO/IEC Guide 22 and EN45014
Manufacturer’s Name: Sensormatic Electronics Corporation
Manufacturer’s Address: 1 Blue Hill Plaza
2 nd
Floor
Pearl River, New York, 10965 USA
Declares, that the product listed below:
Name/Type:
Model Number:
Alarm Responder
AD2032-1 complies with all applicable directives as demonstrated by conformance to the following Product Specifications:
Safety:
EMC:
EN 60950: 1992
EN 50130-4: 1995
EN 55022: 1994 , Class B
EN 61000-3-2: 1995
EN 61000-3-3: 1995
EN 61000-4-2: 1995
EN 61000-4-3: 1996
EN 61000-4-4: 1995
EN 61000-4-5: 1995
EN 61000-4-6: 1996
EN 61000-4-11: 1994
Supplementary Information:
The products herewith comply with the requirements of the Low Voltage Directive, 73/23/EEC as amended by
93/68/EEC, and the EMC Directive, 89/339/EEC as amended by 93/68/EEC.
Pearl River, NY, USA 15 December, 2000
Harold D. Johnson, Ph.D.
Director of Engineering
European Contact: Sensormatic France S.A.
7, rue Alexis de Tocqueville, Parc de Haute Technologie, 92183 ANTONY CEDEX
SPECIFICATIONS
Electrical Ratings: AD2032 120 VAC, 50/60 Hz, 15 W
AD2032-1 230 VAC, 50/60 Hz, 125 mA
Relay Contact Ratings: 0.6 A, 24 VAC; 2 A, 30 VDC
Mounting: Surface Mount or Rack Mount
Weight:
Finish:
Dimensions:
7 lbs (1.4 Kg)
Shadow Gray
17" W x 3.5" H x 8" D (432 x 89 x 203 mm)
Sensormatic Video Systems Divsion
One Blue Hill Plaza
Pearl River, New York 10965
(845) 624-7600
Technical Support Center: 800-442-2225
FAX: (845) 624-7685
8000-1816-01, Revision_A
December,_2000_________________________________________________________________________Printed_in_USA