7750 SR-a4 and 7750 SR-a8 Installation Guide
Alcatel-Lucent
Service Router | Release 13.0.R1
7750 SR-a4 and 7750 SR-a8 Installation Guide
Alcatel-Lucent Proprietary
This document contains proprietary information of Alcatel-Lucent and is not to be disclosed or used except in accordance with applicable agreements.
Copyright 2015 © Alcatel-Lucent. All rights reserved.
This document is protected by copyright. Except as specifically permitted herein, no portion of the provided information can be reproduced in any form, or by any means, without prior written permission from Alcatel-Lucent.
Alcatel, Lucent, Alcatel-Lucent and the Alcatel-Lucent logo are trademarks of Alcatel-Lucent. All other trademarks are the property of their respective owners.
The information presented is subject to change without notice.
Alcatel-Lucent assumes no responsibility for inaccuracies contained herein.
Copyright 2015 Alcatel-Lucent. All rights reserved.
Table of Contents
7750 SR-a4 and SR-a8 Installation Guide 3
Table of Contents
4 7750 SR-a4 and SR-a8 Installation Guide
Table of Contents
7750 SR-a4 and SR-a8 Installation Guide 5
Table of Contents
6 7750 SR-a4 and SR-a8 Installation Guide
Table of Contents
7750 SR-a4 and SR-a8 Installation Guide 7
Table of Contents
8 7750 SR-a4 and SR-a8 Installation Guide
List of Tables
7750 SR-a4 and SR-a8 Installation Guide 9
List of Tables
2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Specifications .............................152
2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Power
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP Features ...........................157
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP Specifications ...................158
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP Power
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP LEDs ................................159
10 7750 SR-a4 and SR-a8 Installation Guide
List of Tables
20-port 10/100/1000 TX RJ-45 MDA-a Power Consumption Values in Watts.............................164
7750 SR-a4 and SR-a8 Installation Guide 11
List of Tables
12 7750 SR-a4 and SR-a8 Installation Guide
List of Figures
7750 SR-a4 and SR-a8 Installation Guide 13
List of Figures
14 7750 SR-a4 and SR-a8 Installation Guide
List of Figures
7750 SR-a4 and SR-a8 Installation Guide 15
List of Figures
16 7750 SR-a4 and SR-a8 Installation Guide
Preface
About This Manual
This guide provides site preparation recommendations and step-by-step procedures to install the Alcatel-Lucent 7750 SR-a4 and 7750 SR-a8 routers horizontally in a standard EIA-310
19-inch wide rack or an ETSI 600 mm (width) x 300 mm (depth) rack with adapters. This guide includes instructions to install and provision the 7750 SR-a router components, including the Control and Processing Module (CPM-a), Input/Output Module (IOM-a),
Media Dependent Adapter (MDA-a) cards, Power Supply Units (PSUs), and fan trays.
Procedures to remove and replace field-replaceable parts are also described in this guide.
The 7750 SR-a4 and 7750 SR-a8 routers can be installed vertically in a 19-in. (482.6 mm)
EIA-310 rack or an ETSI 600 x 300 mm rack with adapter brackets. Vertical installations require the Vertical Rack Mount Kit (3HE09608AA), which is sold separately. The kit enables you to change the direction of the airflow through the rack from side to side, to front to back. Refer to the Vertical Rack Mount Kit Installation Guide (3HE10249AAAA TQZZA) for information about how to mount the 7750 SR-a4 and 7750 SR-a8 routers vertically.
Note: This manual generically covers Release 13.0 content and may contain some content that will be released in later maintenance loads. Please refer to the 7750 SR OS 13.0.Rx
Software Release Notice for information on features supported in each load of the Release
13.0 software.
After the hardware installation process is completed, refer to the following 7750 SR documents for information about the boot process, software configuration, and the command line interface (CLI) that is used to configure system and network parameters:
• 7750 SR Basic System Configuration Guide
This guide describes basic system configurations and operations.
• 7750 SR System Management Guide
This guide describes system security and access configurations as well as event logging and accounting logs.
• 7750 SR Interface Configuration Guide
This guide describes card, Media Dependent Adapter (MDA), and port provisioning.
7750 SR-a4 and SR-a8 Installation Guide 17
About This Manual
• 7750 SR Router Configuration Guide
This guide describes logical IP routing interfaces and associated attributes such as an
IP address, port, link aggregation group (LAG) as well as IP and MAC-based filtering, VRRP, and Cflowd.
• 7750 SR Routing Protocols Guide
This guide provides an overview of routing concepts and provides configuration examples for RIP, OSPF, IS-IS, multicast, BGP, and route policies.
• 7750 SR MPLS Guide
This guide describes how to configure Multiprotocol Label Switching (MPLS) and
Label Distribution Protocol (LDP).
• 7750 SR Services Overview Guide
This guide describes how to configure service parameters such as service distribution points (SDPs), customer information, and user services.
• 7750 SR Layer 2 Services and EVPN Guide: VLL, VPLS, PBB, and EVPN
This guide describes Virtual Leased Lines (VLL), Virtual Private LAN Service
(VPLS), Provider Backbone Bridging (PBB), and Ethernet VPN (EVPN).
• 7750 SR Layer 3 Services Guide: Internet Enhanced Services and Virtual Private
Routed Network Services
This guide describes Internet Enhanced Services (IES) and Virtual Private Routed
Network (VPRN) services.
• 7750 SR Versatile Service Module Guide
This guide describes how to configure service parameters for the Versatile Service
Module (VSM).
• 7750 SR OAM and Diagnostics Guide
This guide describes how to configure features such as service mirroring and
Operations, Administration and Management (OAM) tools.
• 7750 SR Triple Play Guide
This guide describes Triple Play services and support provided by the 7750 SR and presents examples to configure and implement various protocols and services.
• 7750 SR Quality of Service Guide
This guide describes how to configure Quality of Service (QoS) policy management.
• 7750 SR Multiservice Integrated Service Adapter Guide
This guide describes services provided by integrated service adapters such as
Application Assurance, IPSec, ad insertion (ADI) and Network Address Translation
(NAT).
18 7750 SR-a4 and SR-a8 Installation Guide
Preface
Warnings and Notes
Observe the dangers, warnings, and cautions in this guide to avoid injury or equipment damage during installation and maintenance. Follow the safety procedures and guidelines when working with and near electrical equipment.
Audience
This guide is intended for network installers and system administrators who are responsible for installing, configuring, or maintaining networks. This guide assumes you are familiar with electronic and networking technologies.
7750 SR-a4 and SR-a8 Installation Guide 19
Information Symbols
Information Symbols
Symbol Meaning
Danger
Caution
Note
describes information symbols contained in this guide.
Warning
Table 1: Information Symbols
Description
This symbol warns that incorrect handling and installation could result in bodily injury. An electric shock hazard could exist. Before you begin work on this equipment, be aware of hazards involving electrical circuitry, be familiar with networking environments, and implement accident prevention procedures.
This symbol warns that incorrect handling and installation could result in equipment damage or loss of data.
This symbol warns that incorrect handling may reduce your component or system performance.
This symbol provides additional operational information.
Class 1 laser products are identified in the adapter card installation guides.
Only approved Class 1 replaceable laser transceivers should be used with this product.
CLASS 1 LASER PRODUCT
Technical Support
If you purchased a service agreement for your 7750 SR-a chassis and related products from a distributor or authorized reseller, contact the technical support staff for that distributor or reseller for assistance.
20 7750 SR-a4 and SR-a8 Installation Guide
Preface
If you purchased an Alcatel-Lucent service agreement, contact technical assistance at: http://www.alcatel-lucent.com/wps/portal/support
Report documentation errors and comments to:
(include document name, version, part number and pages affected)
7750 SR-a4 and SR-a8 Installation Guide 21
Technical Support
22 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
In This Chapter
This chapter provides information about the Alcatel-Lucent 7750 SR-a4 and 7750 SR-a8 routers. Topics in this chapter include:
•
7750 SR-a Chassis Features on page 24
•
•
7750 SR-a Chassis Components on page 38
•
7750 SR-a System Installation Process on page 46
7750 SR-a4 and SR-a8 Installation Guide 23
7750 SR-a Chassis Features
7750 SR-a Chassis Features
The 7750 SR-a family of routers has two chassis models: the 7750 SR-a4 and 7750 SR-a8.
Both chassis are designed for a 19-in. (482.6 mm wide by 300 mm deep) EIA-310 rack with universal spacing. The chassis can also be installed in an ETSI 600 mm wide by 300 mm deep rack using the adapter brackets that are included with the chassis.
Each 7750 SR-a4 and 7750 SR-a8 router chassis is shipped with a backplane, card cage, and factory-installed air filter. Mounting brackets for the chassis are integrated so that the chassis can be mounted in a standard EIA-310 rack.
The AC or DC PSU, CPM-a, IOM-a, MDA-a, and fan tray components are packaged and shipped separately. Impedance panels, which are ordered separately, are required to cover empty slots to ensure cooling, for EMI containment during operation, and to prevent dust accumulation.
The chassis can be installed horizontally or vertically in the rack.
• In a horizontal installation, card slots are oriented horizontally; the fan tray and air filter are oriented vertically, and the airflow is side to side.
• In a vertical installation, card slots are oriented vertically; the fan tray and air filter are oriented horizontally, and the airflow is front to back. A vertical installation requires the Vertical Rack Mount Kit (3HE09608AA), which is sold separately.
Refer to the Vertical Rack Mount Kit Installation Guide (3HE10249AAAA TQZZA
Edition 01) for information about how to mount the 7750 SR-a4 and 7750 SR-a8 routers vertically.
Access to all 7750 SR-a components is from the front of the chassis.
See the following subsections for more information about each chassis.
•
7750 SR-a4 Chassis Features on page 24
•
7750 SR-a8 Chassis Features on page 27
7750 SR-a4 Chassis Features
The 7750 SR-a4 is a 100 Gb/s full-duplex system that is designed to be installed in a 19-in.
EIA-310 rack with universal spacing. The chassis occupies 5 RU when installed horizontally.
Figure 1 shows the front view of a fully populated 7750 SR-a4 chassis. Table 2
describes the features of the 7750 SR-a4 chassis. The chassis can also be installed in an ETSI 600 mm wide by 300 mm deep rack. Adapter brackets are required to accommodate the 535-mm mounting width aperture of the ETSI rack. The 7750 SR-a4 occupies 9 ETSI RU.
24 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
The CPM-a, IOM-a, and MDA-a cards, and the PSUs and fan tray must be installed after the chassis is mounted in the rack and grounded. All physical connections are made from the front of the chassis, including the chassis ground point. There are no connectors on the back of the chassis.
Figure 1: 7750 SR-a4 Chassis Front View
1
2
3
5
7750 S R-a4 Fan Tray
Pwr
Stat
Lnk Act
Lnk
1 2
Act Lnk
3 4
Act Lnk
5 6
Act Lnk
7 8
Act Lnk
9 10
Act Lnk
11 12
Act Lnk
13 14
Act Lnk
15 16
Act Lnk
17 18
Act Lnk
19 20
Act
Pwr
Stat
Pwr
S tat
S lot Layout
1/1 XP
1/3
1/2 XP
1/4
1
CPM A CPM B
Pwr
7750 SR-a Stat
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Critical Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
1 2 3 4 5
Pwr
Stat
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
6 7 8 9 10
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
Pwr
Stat
Lnk/Act
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
ACO
1PPS
Compact Flash
7750 SR-a4
Service Router
+
_
Pwr
S tat
+
_
Pwr
S tat
6
9
7
8
4
24537
7
8
9
5
6
3
4
Key
1
2
Table 2: 7750 SR-a4 Chassis Front View Features
Description
7750 SR-a4 fan tray in vertical slot
One IOM-a in chassis slot three
Chassis ground position on the chassis mounting flange
Up to four PSUs in the bottom chassis slot
ESD strap receptacle
Up to four MDA-a or MDA-aXP cards in the top two chassis slots
Up to two CPM-a cards in chassis slot four
Non-removable chassis filler plate
Air filter in vertical slot
1.
See 7750 SR-a4 Chassis Slot Allocation
for more information about MDA-a and MDA-aXP slots.
7750 SR-a4 and SR-a8 Installation Guide 25
7750 SR-a Chassis Features
7750 SR-a4 Chassis Slot Allocation
This section describes the slot allocations for each type of chassis component. Figure 2
identifies the slots and the components.
Figure 2: 7750 SR-a4 Chassis Slot Identification
F a n Tr a y Air Filter
Slot 1
Slot 2
Slot 3
Slot 4
MDA-XP 1/1
MDA 1/ 3
CPM A
IOM 1
MDA-XP 1/2
MDA 1/4
CPM B
Forw a rding
Complex
PSU 1 PSU 2 PSU 3 PSU 4
245 3 8
, slots 1 to 3 make up the 7750 SR-a4 forwarding complex. The forwarding complex has a single IOM-a and up to four MDA-a cards with a total forwarding capacity of 100 Gb/s.
MDA-a and MDA-aXP cards occupy a half of a chassis slot. Slot one (at the top of the chassis) supports up to two MDA-a cards. Slot two also supports up to two MDA-a cards. The adapter cards are numbered individually as MDA-a 1/1, MDA-a 1/2, MDA-a 1/3, and MDAa 1/4.
MDA-a slot 1/1 and 1/2 are XP-capable, meaning that they support 100 Gb/s MDA-aXPs.
These slots support up to 100 Gb/s full-duplex bandwidth. The remaining two MDA-a slots support 25 Gb/s full-duplex bandwidth. MDA-a cards must be ordered separately from the chassis. An impedance panel must be installed in any empty MDA-a slot. See
for more information.
Note:
• A 100 Gb/s MDA-aXP card can operate in a 25 Gb/s slots, but the slot will be oversubscribed. If you install a 100 Gb/s MDA-aXP card in a 25 Gb/s slot, the maximum line rate is 25 Gb/s.
• A 25 Gb/s MDA-a card can operate in 100 a Gb/s slot, but the slot will be undersubscribed. If you install a 25 Gb/s MDA-a card in a 100 Gb/s slot, the maximum line rate is 25 Gb/s.
26 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
Slot three supports one IOM-a. IOM-a cards occupy a full chassis slot. The IOM-a performs data forwarding from the ingress port to the egress port. There is no switch fabric for the
7750 SR-a4.
Slot four, the bottom slot, supports up to two CPM-a cards, designated as CPM A and CPM
B. In a redundant system, the CPM-a cards are installed in slots CPM A and CPM B. CPMa cards occupy a half of a chassis slot. In a simplex system, the CPM-a can be installed in slot
CPM A or CPM B; an impedance panel must be installed in the empty CPM-a slot.
Below slot four is a non-removable chassis filler plate.
Below the chassis filler plate, Power Supply Units are located at the bottom of the
7750 SR-a4 chassis, and are numbered PSU 1 to PSU 4, from left to right. Each PSU occupies one-quarter of a chassis slot. Two types of PSUs are available: one for universal AC power feeds and one for –48 VDC power feeds.
Chassis bundles for the 7750 SR-a4 include one PSU. PSUs are orderable items that are available for AC and DC power feeds. Alcatel-Lucent recommends that the PSUs be installed in an N+1 configuration. A PSU impedance panel must be installed in any empty PSU slot.
The right side of the chassis has one vertical slot for an air filter. The left side of the chassis has one vertical slot for the fan tray, which pulls air through the chassis from right to left.
7750 SR-a8 Chassis Features
The 7750 SR-a8 is a 200 Gb/s full-duplex system that is designed to be installed in an EIA
19-inch (482.6 mm) rack, where the chassis occupies 7 RU.
Figure 3 shows the front view of a populated 7750 SR-a8 chassis. Table 3
describes the features of the 7750 SR-a8 chassis.
The chassis can also be installed in an ETSI 600 mm wide by 300 mm deep rack. Adapter brackets are required to accommodate the 535-mm mounting width aperture of the ETSI rack.
The 7750 SR-a8 occupies 13 ETSI RU.
The CPM-a, IOM-a, and MDA-a cards, and the PSUs and fan tray must be installed after the chassis is mounted in the rack and grounded. All physical connections are made from the front of the chassis, including the chassis ground point. There are no connectors on the back of the chassis.
7750 SR-a4 and SR-a8 Installation Guide 27
7750 SR-a Chassis Features
1
2
2
3
5
Figure 3: 7750 SR-a8 Chassis Front View
R-a4 Fan Tray
Pwr
Stat
Pwr
Stat
Lnk Act
Lnk
1 2
Act Lnk
3 4
Act Lnk
5 6
Act Lnk
7 8
Act Lnk
9 10
Act Lnk
11 12
Act Lnk
13 14
Act Lnk
15 16
Act Lnk
17 18
Act Lnk
19 20
Act
Pwr
Stat
Lnk/Act
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
1 2 3 4 5 6
Pwr
Stat
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
7
Lnk Act
Pwr
S tat
Pwr
7750 SR-a Stat
Pwr
Stat
Lnk/Act
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
13 14
Pwr
Stat
Lnk/Act 1 2 3 4 5 6 7 8 9 10 11 12
Lnk Act Lnk Act
1 2 3 4 5 6 7 8 9 10
Pwr
Stat
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
Pwr
Stat
Lnk/Act
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
1/1 XP
1/3
1/2
1/4
1
2/1 XP
2/3
2/2 XP
2/4
CPM A
2
CPM B
Pwr
7750 SR-a Stat
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Critical Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Critical Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a8
Service Router
+ -
Pwr
S tat
6
6
8
7
4
24467
5
6
3
4
Key
1
2
7
8
Table 3: 7750 SR-a8 Chassis Front View Features
Description
7750 SR-a8 fan tray in vertical slot
IOM-a in chassis slots three and six
Chassis ground position on the chassis mounting flange
Up to four PSUs in the bottom chassis slot. Figure 3 shows impedance panels
in two of the four PSU positions.
ESD strap receptacle
Up to four MDA-a or MDA-aXP cards in the top two chassis slots and up to
four MDA-a or MDA-aXP cards in the chassis slots four and five
Up to two CPM-a cards in chassis slot seven
Air filter in vertical slot
1.
See 7750 SR-a8 Chassis Slot Allocation
for more information about MDA-a and MDA-aXP slots.
28 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
7750 SR-a8 Chassis Slot Allocation
This section describes the slot allocations for each type of chassis component. The
identifies the slots and the components.
Figure 4: 7750 SR-a8 Chassis Slot Identification
F a n Tr a y Air Filter
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
MDA-XP 1/1
MDA 1/ 3
MDA-XP 2/1
MDA 2/ 3
CPM A
IOM 1
IOM 2
MDA 1/2
MDA 1/4
MDA 2/2
MDA 2/4
CPM B
Forw a rding
Complex 1
Forw a rding
Complex 2
PSU 1 PSU 2 PSU 3 PSU 4
24468
, the 7750 SR-a8 chassis has two forwarding complexes. Each forwarding complex has a single IOM-a and up to four MDA-a cards with a forwarding capacity of 100 Gb/s.
MDA-a and MDA-aXP cards occupy a half of a chassis slot. MDA-a slot 1/1 and 2/1 are XPcapable, meaning that they support 100 Gb/s MDA-aXPs. These slots support up to
100 Gb/s full-duplex bandwidth.
The remaining six MDA-a slots support 25 Gb/s full-duplex bandwidth. MDA-a cards must be ordered separately from the chassis. An impedance panel must be installed in any empty
MDA-a slot. See
MDA-a Cards for more information.
7750 SR-a4 and SR-a8 Installation Guide 29
7750 SR-a Chassis Features
Note:
• A 100 Gb/s MDA-aXP card can operate in a 25 Gb/s slots, but the slot will be oversubscribed. If you install a 100 Gb/s MDA-aXP card in a 25 Gb/s slot, the maximum line rate is 25 Gb/s.
• A 25 Gb/s MDA-a card can operate in 100 a Gb/s slot, but the slot will be undersubscribed. If you install a 25 Gb/s MDA-a card in a 100 Gb/s slot, the maximum line rate is 25 Gb/s.
The 7750 SR-a8 supports up to two 7750 IOM-a cards. IOM-a 1 in slot three; IOM-a 2 in slot six. Each IOM-a performs data forwarding from the ingress port to the egress port. There is no switch fabric for the 7750 SR-a8.
The system can operate with one IOM-a and one forwarding complex. In this configuration impedance panels are required for the second complex IOM-a slot and MDA-a slots.
Each IOM-a can support up to four MDA-a cards:
• IOM-a 1 supports MDA-a cards in slot one at the top of the chassis and slot two. The adapter cards are numbered individually as MDA-a 1/1, MDA-a 1/2, MDA-a 1/3, and
MDA-a 1/4.
• IOM-a 2 supports MDA-a cards in slots four and five. The adapter cards are numbered individually as MDA-a 2/1, MDA-a 2/2, MDA-a 2/3, and MDA-a 2/4.
Each IOM-a with its MDA-a cards makes up a forwarding complex. Each complex has a forwarding capacity of 100 Gb/s.
Slot seven, the bottom slot, supports up to two CPM-a cards, designated as CPM A and CPM
B. In a redundant system, the CPM-a cards are installed in slots CPM A and CPM B. In a simplex system, the CPM-a can be installed in slot CPM A or CPM B; an impedance panel must be installed in the empty CPM-a slot.
Power Supply Units are located below slot 7 at the bottom of the 7750 SR-a8 chassis. The
PSUs are installed in an N+1 configuration, and numbered PSU 1 to PSU 4 from left to right.
PSUs are orderable items that are available for AC or DC power feeds.
Chassis bundles for the 7750 SR-a8 include two PSUs. PSUs are orderable items that are available for AC and/or DC power feeds. Alcatel-Lucent recommends that the PSUs be installed in an N+1 configuration. A PSU impedance panel must be installed in any empty
PSU slot.
When mounted horizontally, the right side of the 7750 SR-a8 chassis has one vertical slot for an air filter. The left side of the chassis has one vertical slot for the 7750 SR-a8 fan tray, which pulls air through the chassis from right to left.
30 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
7750 SR-a Modules
The 7750 SR-a modules are designed for use in the 7750 SR-a4 and 7750 SR-a8 chassis. This section describes the following modules:
•
•
•
CPM-a
The CPM-a, which is used in the 7750 SR-a4 and 7750 SR-a8, provides:
• control plane functions and determines the route tables
• management and console interfaces for system management
• system synchronization interfaces for external synchronization input and output signals
• alarm interface and notifications
The CPM-a does not provide a switch fabric. The IOM-a forwards traffic from the ingress to the egress ports.
At least one CPM-a must be installed in the 7750 SR-a chassis. The system cannot boot without a CPM-a installed in the chassis. Two CPM-a cards are required for system redundancy. The redundant standby (secondary) CPM-a operates in standby mode and takes over system operation if the active (primary) CPM-a fails. The 7750 SR-a CPM-a is intended only for the 7750 SR-a chassis and is not interchangeable with other 7750 SR products.
The CPM-a is field-replaceable and hot-swappable. Refer to the 7750 SR OS Basic System
Configuration Guide for information about CPM-a redundancy.
Each CPM-a supports two, Type-II capable compact flash (CF) memory devices:
• external CF slot—CF slot accessible from the front of the CPM-a card. The slot can support CF cards up to 32 Gbytes, and can be used to store accounting records, logs, and TiMOS images.
• internal CF slot—CF slot accessible on the circuit board when the CPM-a is removed from the chassis. This slot is used for the CF card that contains the system OS. See
CPM-a Internal CF Drive on page 34 for more information.
7750 SR-a4 and SR-a8 Installation Guide 31
7750 SR-a Modules
The internal and external CF cards are field-replaceable; see Replacing the Internal Compact
Flash Card on the CPM-a on page 195 .
Figure 5 shows the CPM-a faceplate. Table 4 describes the CPM-a features. See
LEDs and Connectors on page 142 for identification and description of the faceplate features.
Figure 5: 7750 SR-a CPM-a Features
1 3 5 7 9 11 13 1
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
2 4 6 8
Critical Major Minor
Alarms
10
ACO/LT
12
1PPS
Compact Flash
24539
2
3
Key Label/Part
1 Captive screws
Pwr / Stat
DTE
Subcategory
—
Table 4: 7750 SR-a CPM-a Features
Description
Secures the CPM-a in place.
4
5
DCE
Console
OES
LED
—
—
See
CPM-a LEDs and Connectors on page 142 for more information.
Set the switch to DTE when connecting to the serial port of a PC with a null modem cable. When the switch is set to DTE, the Console port acts as a data terminal equipment (DTE) serial port.
Set the switch to DCE when connecting to the serial port of a PC with a straight-through cable. When the switch is set to DCE, the Console port acts as a data communications equipment (DCE) serial port.
Connector The Console port uses an RJ-45 connector that enables a connection to a terminal for performing switch monitoring and configuration operations.
The terminal may be a PC or workstation that is running terminal emulation software (DCE), or a terminal configured as a Data Terminal Equipment
(DTE) connection. A null-modem wired serial cable is supplied with the router for connecting to this interface.
Connector RJ-45 Optical Extension Shelf (OES) Ethernet port. The OES Ethernet port is reserved for future use.
32 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
Key
6
7
8
9
10
11
12
Table 4: 7750 SR-a CPM-a Features (Continued)
Label/Part
Mgmt
BITS
Subcategory
Description
Connector The 10/100/1000Base-T Ethernet Management port has an RJ-45 copper
Ethernet connector used for the initial system startup as well as system configuration and monitoring. The management port provides a dedicated management interface that is segregated from data traffic crossing the other ports. Auto detection is supported. Refer to
for pinout assignments.
LEDs See
CPM-a LEDs and Connectors on page 142 for more information.
Connector The Building Integrated Timing Supply (BITS) port on the CPM-a front panel accesses a clock in a central office that supplies digital signal level 1
(DS1), 2.048 MHz (E1) timing references to all synchronous network elements in that office. This port is provisioned with an RJ-45 connector.
An appropriate T1 or E1 cable must be used to connect a device to this port.
See
CPM-a LEDs and Connectors on page 142 for more information.
Note: Ensure that you use shielded cable when connecting to the BITS port.
SyncE/1588 Connector The SyncE/1588 port is provisioned with an RJ-45 connector. The Sync-E/
1588 port is reserved for future use.
LEDs See
CPM-a LEDs and Connectors on page 142 for more information.
Critical
Major
Minor
Alarms Connector The alarm interface port is a D-type 15-pin connector that supports a critical alarm output, a major alarm output, and four alarm inputs. When the system has a critical or major alarm, the CPU causes the alarm relay to issue the alarm output and turn on the critical or major LED. If you push the alarm cut off (ACO) button, the relay will be released but the LED will stay on until the alarm is cleared. Minor alarm output to the DB-15 connector is not supported.
1PPS
ACO/LT
Connector 1PPS timing output. The 1PPS port is reserved for future use.
— The Alarm Cutoff/Lamp Test button verifies the operability of LEDs.
When you press this button, all LEDs on all chassis modules should temporarily illuminate and blink until the button is released. The ACO/LT button tests the functionality and operability of all LEDs on the chassis and components of the chassis. If any LED does not illuminate and blink, the
LED might not be functioning correctly.
This button also turns off all external alarm relay control bits until the next new alarm condition.
7750 SR-a4 and SR-a8 Installation Guide 33
7750 SR-a Modules
Key Label/Part
13 Compact
Flash
Table 4: 7750 SR-a CPM-a Features (Continued)
Subcategory
External memory card slot
Description
CF drive name: cf1:\
To eject a CF card, gently press the ejector button until the flash card releases.
Refer to the 7750 SR-a Release Notes for more information about the CF storage devices supported on the 7750 SR-a routers.
CPM-a Internal CF Drive
Figure 6 shows the location of the internal CF drive; Table 5
describes the features.
Figure 6: Internal CF drive
S tat
Con s ole
2
Alarm s
2
ACO
1PP
S
1PP Compact Fla s h
Compact Fla s h
1
1
24558
Key Label/Part
1 CF wire bail latch
Table 5: 7750 SR-a CPM-a Internal CF Drive Features
Subcategory
Description
Card slot CF drive name: cf3:\
To remove the CF card, lift the wire bail latch and pull the card from the slot.
34 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
Key Label/Part
2 CF card
Table 5: 7750 SR-a CPM-a Internal CF Drive Features (Continued)
Subcategory
Internal memory
Description
The primary copy of the 7750 SR-a TiMOS software is shipped with the
OS software license on a CF memory card. The card, which contains the boot software, must be inserted in the internal CF slot on the CPM-a before the CPM-a is installed in the chassis. The CF memory card can also be used to copy and store system boot software, OS software, and configuration files and logs.
Refer to the 7750 SR-a Release Notes for detailed information about the CF storage devices supported on the 7750 SR-a routers.
IOM-a
The IOM-a performs ingress and egress packet processing and queuing. All forwarding, service management, and traffic management functions are performed by the IOM-a.
One IOM-a is required by the 7750 SR-a4 in slot 3. Two IOM-a cards are supported by the
7750 SR-a8: one in slot 3 and one in slot 6. At least one IOM-a is required in the 7750 SR-a8.
The 7750 SR-a IOM-a is intended only for the 7750 SR-a chassis and is not interchangeable with other 7750 SR products.
Each IOM-a provides 100 Gb/s connectivity to MDA-a cards. Up to four MDA-a cards are supported by one IOM-a.
The IOM-a cards are optimized for deployment in a variety of Ethernet and IP-based
describes the IOM-a variants.
Table 6: IOM-a Variants
IOM-a Variant Description
IOM - 7750 SR-a - L2HQ 7750 SR-a 100Gb/s Input Output Module. This IOM-a includes a license for the Layer 2 with high queuing (L2HQ) features set.
IOM - 7750 SR-a - L3BQ 7750 SR-a 100Gb/s Input Output Module. This IOM-a includes a license for the Layer 3 with basic queuing (L3BQ) features set.
IOM - 7750 SR-a - L3HQ 7750 SR-a 100Gb/s Input Output Module. This IOM-a includes a license for the Layer 3 with high queuing (L3HQ) features set.
Part Number
3HE09202CA
3HE09202BA
3HE09202AA
7750 SR-a4 and SR-a8 Installation Guide 35
7750 SR-a Modules
Figure 7 shows the 7750 SR-a IOM-a, which is used in the 7750 SR-a4 and 7750 SR-a8. See
IOM-a LEDs on page 146 for a description of the LED.
Figure 7: 7750 SR-a IOM-a
Pwr
S tat
2445 3
MDA-a Cards
The 7750 SR-a MDA-a cards provide a wide variety of interfaces that support a full range of carrier Ethernet features.
The supported MDA-a locations are:
• 7750 SR-a4 supports MDA-a cards in slot one (at the top of the chassis) and slot two.
The MDA-a slots are numbered individually as MDA-a 1/1, MDA-a 1/2, MDA-a 1/
3, and MDA-a 1/4. See Figure 2 for MDA-a slot locations on the 7750 SR-a4.
• 7750 SR-a8 supports MDA-a cards in slot one (at the top of the chassis) and slot two.
Those MDA-a slots are numbered individually as MDA-a 1/1, MDA-a 1/2, MDA-a
1/3, and MDA-a 1/4.
The 7750 SR-a8 also supports MDA-a cards that are installed in slots four and five.
Those MDA-a slots are numbered individually as MDA-a 2/1, MDA-a 2/2, MDA-a
2/3, and MDA-a 2/4. See Figure 4 for MDA-a slot locations on the 7750 SR-a8.
• MDA-a cards operate only when their host IOM-a is installed.
• MDA-a and MDA-aXP cards can be installed in any MDA slot with the following limitation:
→ A 100 Gb/s MDA-aXP card can operate in a 25 Gb/s slots, but the slot will be oversubscribed. If you install a 100 Gb/s MDA-aXP card in a 25 Gb/s slot, the maximum line rate is 25 Gb/s.
→ A 25 Gb/s MDA-a card can operate in a 100 Gb/s slot, but the slot will be undersubscribed. If you install a 25 Gb/s MDA-a card in a 100 Gb/s slot, the maximum line rate is 25 Gb/s.
MDA-a cards can be installed in the chassis in any combination that does not exceed the maximum number. The adapter cards are hot-swappable and field-replaceable by qualified
personnel as described in the procedures in Appendix C: Field-Replaceable Units .
The following 25-Gb/s MDA-a cards are supported on the 7750 SR-a4 and 7750 SR-a8:
36 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
• 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a
• 4-port 10GigE SFP+ MDA-a
• 20-port 10/100/1000 TX RJ-45 MDA-a
• 44-port 1GigE CSFP/SFP MDA-a
MDA-aXP cards can achieve their maximum line rate only when installed in MDA-aXP slot
1/1 and 1/2 on the 7750 SR-a4 and in MDA-aXP slots 1/1 and 2/1 on the 7750 SR-a8. The following “XP” 100-Gb/s MDA-a cards are supported in the chassis.
• 1-port 100GigE CFP MDA-aXP
• 6-port 10GigE SFP+ and 1-port 40GigE QSFP+ Combo MDA-aXP
• 10-port 10GigE SFP+ MDA-aXP
Refer to Appendix B: MDA-a and MDA-aXP Card Descriptions on page 147 for more
information about each MDA-a. The 7750 SR-a MDA-as are intended only for the 7750 SR-a chassis and are not interchangeable with other 7750 SR products.
7750 SR-a4 and SR-a8 Installation Guide 37
7750 SR-a Chassis Components
7750 SR-a Chassis Components
The 7750 SR-a chassis are shipped empty and the components must be installed. See the following subsections:
•
•
•
•
•
Component Operating Requirements on page 44
PSUs
The 7750 SR-a4 and 7750 SR-a8 chassis are designed to accommodate swappable, load-sharing Power Supply Units (PSU).
Two types of PSUs are available, as listed in
: one for universal AC power feeds and one for –48 VDC power feeds.
Table 7: PSUs
Chassis Power Supply Unit
7750 SR-a4 and 7750 SR-a8 PSU - 7750 SR-a AC
PSU - 7750 SR-a –48V
Part Number
3HE09200AA
3HE09199AA
Each PSU is rated at 1600W when operating from DC power and high-line AC power feeds.
When operating from a low-line AC power feed, the AC PSU is rated at 1000W.
You must supply your own power cables. Verify that the cables are compliant with your local safety code. PSUs have no field-replaceable parts. You must replace the entire unit in the event of a failure.
7750 SR-a AC PSU
Figure 8 shows the 7750 SR-a AC PSU.
38 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
Figure 8: 7750 SR-a AC PSU
24450
Refer to
Installing, Wiring, and Connecting an AC PSU on page 94 and
LED and Connectors on page 138
for more information.
7750 SR-a –48 VDC PSU
Figure 9 shows the SR-a –48 VDC PSU.
Figure 9: 7750 SR-a –48 VDC PSU
Pwr
S tat
+
_
24451
Refer to
Installing, Wiring, and Connecting a –48 VDC PSU on page 98
and
VDC PSU LED and Connectors on page 139 for more information.
PSU Redundancy
Up to four PSUs can be installed in the front of each chassis. The chassis can support a mix of AC and DC power supplies.
For the 7750 SR-a4, one PSU can support the full system power requirements if you are operating without power redundancy. For redundancy, at least two PSUs must be installed and powered at all times.
7750 SR-a4 and SR-a8 Installation Guide 39
7750 SR-a Chassis Components
Note: For most applications, one PSU can power a 7750 SR-a4 system. However,
Alcatel-Lucent recommends that you calculate the maximum power consumption of all components in the chassis and install a second PSU, as required.
For the 7750 SR-a8, two PSUs are required to support the full system power requirements if you are operating without power redundancy. Three PSUs must be installed and powered at all times for (N + 1) redundancy.
All unused PSU slots must be filled with impedance panels to maintain EMI containment and proper air flow within the chassis.
Cooling System
The cooling system is designed to keep the internal components within the acceptable temperature range. The cooling system for the 7750 SR-a4 and 7750 SR-a8 has the following components:
• one fan tray
• one air filter with a reusable metal carrier and a field replaceable filter
• chassis right-side air intake and left-side exhaust
Fan Trays
The 7750 SR-a system is cooled by variable-speed fans housed in a fan tray. Air is pulled through the system from a right-side filtered-intake vent, through the chassis and across the line components, then exits through the fan tray in the left of the chassis.
The fan speed is reduced at normal temperatures and gradually increases up to its maximum speed as the ambient temperature increases. The fan trays are energy efficient and comply with NEBS3 acoustic requirements.
Fan trays are chassis-specific and described in Table 8
.
Chassis
7750 SR-a4
7750 SR-a8
Table 8: Fan Trays
Variant Part Number
FAN - 7750 SRa4 Fan Tray (four axial fans) 3HE09197AA
FAN - 7750 SRa8 Fan Tray (six axial fans) 3HE09198AA
40 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
shows the 7750 SR-a4 fan tray.
Figure 10: 7750 SR-a4 Fan Tray
shows the 7750 SR-a8 fan tray.
Figure 11: 7750 SR-a8 Fan Tray
24656
7750 SR-a4 and SR-a8 Installation Guide
24655
41
7750 SR-a Chassis Components
The fans are controlled by the system software, and their speed is set according to the environmental temperature surrounding the router. Allow at least 3 in. (7.6 cm) of clearance on each side of the rack to ensure adequate air intake and exhaust.
The fan LED located on the front panel of the fan tray indicates the tray status: normal online
for more information.
There are no field replaceable parts in the fan tray. The entire fan tray must be replaced if a component, such as a single fan, fails. See
Removing and Replacing a Fan Tray on page 185
for more information.
Fan trays must always be installed and fully operational while the 7750 SR-a chassis is powered.
Air Filters
Air filters are chassis specific:
• The 7750 SR-a4 chassis requires the 7750 SR-a4 filter.
• The 7750 SR-a8 chassis requires the 7750 SR-a8 filter.
Each chassis has one air filter slot that is located on the right side of the front panel.
The air filter has two parts: a reusable metal carrier, and a field replaceable filter. The reusable carrier and one air filter are shipped installed in the chassis.
shows an example of the air filter on the 7750 SR-a4.
42 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
Figure 12: Air Filter Carrier (7750 SR-a4)
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
Pwr
Stat
1
Pwr
Stat
2
3
4
5
6
Lnk Act
Lnk Act
7
8
Lnk Act
9
Lnk Act
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Air filter
24544
The air filter prevents large particles, debris, and dust from entering and circulating through the system. The air filter must always be in place while the chassis is powered.
Filters should be inspected monthly and replaced when accumulated dust is present. The
replaceable filters can be ordered separately, as described in Table 9
.
Chassis
7750 SR-a4
7750 SR-a8
Table 9: Air Filters
Variant
ACC - 7750 SR-a4 AIR FILTER (5 pack)
ACC - 7750 SR-a8 AIR FILTER (5 pack)
Part Number
3HE09420AA
3HE09421AA
See Removing and Replacing an Air Filter on page 189
for more information.
Impedance Panels
Impedance panels are required on all empty card and component slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference, and for safety reasons. Impedance panels do not have board components or connector pins.
7750 SR-a4 and SR-a8 Installation Guide 43
7750 SR-a Chassis Components
Part Number
3HE09417AA
3HE09418AA
3HE09419AA
The 7750 SR-a chassis support three types of impedance panels. The 7750 SR-a4 and
7750 SR-a8 chassis use the same three types of impedance panels. Impedance panels are
ordered separately, as described in Table 10
.
Table 10: Impedance Panels
Product
ACC - 7750 SR-a CPM/MDA
Impedance Panel
Description
One panel covers a one-half chassis slot.
Intended only for an individual MDA-a or CPMa slot.
ACC - 7750 SR-a IOM Impedance Panel One panel covers one chassis slot. Intended only for an individual IOM-a slot.
ACC - 7750 SR-a PSU Impedance Panel One panel covers a one-quarter chassis slot.
Intended only for an individual PSU slot.
shows the impedance panels that are used in the 7750 SR-a chassis.
Figure 13: 7750 SR-a Impedance Panels
CPM a nd MDA
PSU
IOM
24545
Component Operating Requirements
Table 11 lists the 7750 SR-a4 hardware component operating requirements.
Table 11: 7750 SR-a4 Hardware Component Operating Requirements Summary
Component
Backplane (factory installed)
AC or DC PSU
Minimum
1
1
Maximum
1
4
Field Replaceable
N
Y
44 7750 SR-a4 and SR-a8 Installation Guide
7750 SR-a4 and 7750 SR-a8 Overview
Table 11: (Continued)7750 SR-a4 Hardware Component Operating Requirements Summary
Component
Fan tray
Air filter
CPM-a
IOM-a
MDA-a
Minimum
1
1
1
1
1
Maximum
1
1
2
1
4
Field Replaceable
Y
Y
Y
Y
Y
Table 12 lists the 7750 SR-a8 hardware component operating requirements.
Table 12: 7750 SR-a8 Hardware Component Operating Requirements Summary
Component
Backplane (factory installed)
AC or DC PSU
Fan tray
Air filter
CPM-a
IOM-a
MDA-a
Minimum
1
2
1
1
1
1
1
Maximum
1
4
1
1
2
2
8
Field Replaceable
N
Y
Y
Y
Y
Y
Y
7750 SR-a4 and SR-a8 Installation Guide 45
7750 SR-a System Installation Process
7750 SR-a System Installation Process
To install the 7750 SR-a system, perform the installation procedures in the following order:
Step 1.
Prepare the site.
Step 2.
Unpack the chassis and components.
Step 3.
Mount the chassis.
Step 4.
Prepare the chassis ground cables and make the grounding connections.
Step 5.
Install at least one PSU.
Step 6.
Prepare and connect the DC input power cables to a direct DC circuit, or connect an AC power source.
Step 7.
Install at least one CPM-a.
Step 8.
Install at least one IOM-a.
Step 9.
Install at least one MDA-a.
Step 10.
Connect the network cables.
Step 11.
Power up the system.
Step 12.
Configure card slot, IOM, MDA, and port information.
46 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
In This Chapter
This chapter describes how to prepare your site to install a 7750 SR-a4 or 7750 SR-a8. Topics in this chapter include:
•
•
•
•
•
•
•
Safety Standards/Compliance Agency Certifications
7750 SR-a4 and SR-a8 Installation Guide 47
Warnings and Notes
Warnings and Notes
Danger:
• 7750 SR-a systems equipped with DC-input power supplies should be installed in restricted access areas, such as a dedicated equipment room or an equipment closet, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electric Code
ANSI/ NFPA 70.
• This product complies with, and has been CE marked in accordance with, the European
Directives 89/336/EEC (EMC as amended by directive 93/68)
• The 7750 SR-a4 and 7750 SR-a8 routers are Class 1 laser products that use fiber-optic communications. Only trained service personnel familiar with laser radiation hazards should install or remove fiber-optic cables and cards in this system.
Warning:
•
Ensure that you comply with the location requirements outlined in Chassis Location
Requirements on page 59 . Failure to comply with these requirements may impede
proper airflow and may result in the system overheating.
48
Note:
General:
• Prepare the equipment rack and site before installing the router. Plan the router placement near the power sources and network interface connections.
• Maintain a clearance of at least 20 in. (50.8 cm) at the front of the router.
• Maintain a clearance of at least 3 in. (7.6 cm) on each side of the rack to ensure adequate air intake and exhaust.
• The 7750 SR-a chassis includes integrated rack mounting flanges to mount in a 19-in.
(482.6 mm) equipment rack.
7750 SR-a4-specific:
• An empty 7750 SR-a4 chassis weighs 22.71 lb (10.30 kg).
• A fully loaded 7750 SR-a4 chassis with the heaviest components and cards weighs approximately 58 lb (26.31 kg).
7750 SR-a8-specific:
• An empty 7750 SR-a8 chassis weighs 30 lb (13.61 kg).
• A fully loaded 7750 SR-a8 chassis with the heaviest components and cards weighs approximately 84 lb (38.10 kg).
7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
System Specifications
Chassis Specifications
Parameter
Dimensions (H
x W
)
Chassis weight (unpopulated)
Chassis weight (full)
CPM-a slots
IOM-a slots
MDA-a slots
PSU slots
Fan tray slot
Air filter slot
Mounting
Table 13: 7750 SR-a4 Chassis Specifications
Description
8.75 x 19.00 x 9.56 in. (22.23 x 48.26 x 24.28 cm)
22.71 lb (10.30 kg)
58 lb (26.31 kg)
2
1
4
4
1
1
Mount in a recommended 19-in. (482.6 mm) equipment rack
Chassis has integrated mounting flanges for mounting in a 19-in. (482.6 mm) rack.
1.
Height equals 5 RU.
2.
Width includes the integrated flanges for rack mounting.
3.
Depth does not include panel protrusions, such as panel screws, connectors, and ground studs.
Parameter
Dimensions (H
x W
)
Chassis weight (unpopulated)
Chassis weight (full)
CPM-a slots
Table 14: 7750 SR-a8 Chassis Specifications
Description
12.25 x 19.00 x 9.56 in. (31.11 x 48.26 x 24.28 cm)
30.0 lb (13.61 kg)
84.0 lb (38.10 kg)
2
7750 SR-a4 and SR-a8 Installation Guide 49
System Specifications
Parameter
IOM-a slots
MDA-a slots
PSU slot
Fan tray slot
Air filter slot
Mounting
Table 14: 7750 SR-a8 Chassis Specifications (Continued)
Description
2
1
1
8
4
Mount in a recommended 19-in. (482.6 mm) equipment rack
Chassis has integrated mounting flanges for mounting in a 19-in.
(482.6 mm) rack.
1.
Height equals 7 RU.
2.
Width includes the integrated flanges for rack mounting.
3.
Depth does not include panel protrusions, such as panel screws, connectors, and ground studs.
Environmental Specifications
Parameter
Table 15: 7750 SR-a4 Environmental Specifications
Normal operating temperature
Short-term operating temperature 1
Maximum altitude
Normal operating relative humidity
Short-term operating relative humidity
Acoustic noise level
Shock and vibration
Description
23 to 113ºF (–5 to 45ºC)
23 to 131ºF (–5 to 55ºC)
13 000 ft (3962.4 m)
5 to 90% (non-condensing)
5 to 93% (non-condensing)
78 dBA at 27ºC (80.6ºF). Fan speed is adaptive.
Very low levels for continuous duration disturbance (similar to modern office building, for example)
Shock: 3 g half sine 11 ms
Vibration: 0.1 g from 5 to 100 Hz
50 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Parameter
Earthquake
Table 15: 7750 SR-a4 Environmental Specifications (Continued)
Description
Suitable for high-risk areas (Zone 4/California, for short-duration disturbance)
2
Rated voltage (DC)
Operating voltage range (DC)
Rated voltage (AC)
Operating voltage range (AC)
–48 VDC
–40 to –72 VDC
120 or 240 VAC
90 to 264 VAC
Notes:
1.
Short-term refers to no more than 96 consecutive hours per occurrence and no more than 15 occurrences in a one-year period.
2.
Pollution degree is as defined in IEC 60950. Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation.
Parameter
Table 16: 7750 SR-a8 Environmental Specifications
Normal operating temperature
Short-term operating temperature
Maximum altitude
Normal operating relative humidity
Short-term operating relative humidity
Acoustic noise level
Shock and vibration
Description
23 to 113ºF (–5 to 45ºC)
23 to 131ºF (–5 to 55ºC)
13 000 ft (3962.4 m)
5 to 90% (non-condensing)
5 to 93% (non-condensing)
Earthquake
78 dBA at 27ºC (80.6ºF). Fan speed is adaptive.
Very low levels for continuous duration disturbance (similar to modern office Building, for example)
Shock: 3 g half sine 11 ms
Vibration: 0.1 g from 5 to 100 Hz
Suitable for high-risk areas (Zone 4/California, for short-duration disturbance)
2
7750 SR-a4 and SR-a8 Installation Guide 51
System Specifications
Table 16: 7750 SR-a8 Environmental Specifications (Continued)
Parameter
Rated voltage (DC)
Operating voltage range (DC)
Rated voltage (AC)
Operating voltage range (AC)
Description
–48 VDC
–40 to –72 VDC
120 or 240 VAC
90 to 264 VAC
Notes:
1.
Short-term refers to no more than 96 consecutive hours per occurrence and no more than 15 occurrences in a one-year period.
2.
Pollution degree is as defined in IEC 60950. Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation.
Power Supply Unit Module Specifications
Parameter
Dimensions (H x W x D)
Weight
Voltage range
Maximum current
Efficiency
Table 17: AC PSU Specifications
Description
3.4 x 7.78 x 1.59 in. (8.64 x 19.77 x 4.05 cm)
2.33 lb (1.06 kg)
90 to 264 VAC
12 A
93%
Parameter
Dimensions (H x W x D)
Weight
Voltage range
Maximum current
Efficiency
Table 18: –48 VDC PSU Specifications
Description
3.4 x 7.78 x 1.57 in. (8.6 x 19.77 x 3.99 cm)
2.44 lb (1.108 kg)
–40 to –72 VDC
40 A
93%
52 7750 SR-a4 and SR-a8 Installation Guide
CPM-a Specifications
Parameter
Dimensions (H x W x D)
Weight
Table 19: CPM-a Specifications
Description
1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
2.35 lb (1.06 kg)
IOM-a Specifications
Parameter
Dimensions (H x W x D)
Weight
Table 20: IOM-a Specifications
Description
1.4 x 15.3 x 9.0 in. (3.56 x 38.86 x 22.86 cm)
6.25 lb (2.84 kg)
MDA-a Specifications
MDA-a or MDA-aXP
All
Table 21: MDA-a Dimensions Specifications
Dimensions (H x W x D)
1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
MDA-a or MDA-aXP
1-port 100GigE CFP MDA-aXP
Table 22: MDA-a Weight Specifications
6-Port 10GigE SFP+ and 1-Port 40GigE
QSFP+ Combo MDA-aXP
10-port 10GigE SFP+ MDA-aXP
2-port 10GigE SFP+ and 12-port 1GigE
SFP Combo MDA-a
Weight
2.76 lb (1.25 kg)
2.11 lb (0.96 kg)
2.13 lb (0.96 kg)
2.03 lb (0.92 kg)
Site Preparation
7750 SR-a4 and SR-a8 Installation Guide 53
System Specifications
Table 22: MDA-a Weight Specifications (Continued)
MDA-a or MDA-aXP
4-port 10GigE SFP+ MDA-a
Weight
1.90 lb (0.86 kg)
20-port 10/100/1000 TX RJ-45 MDA-a 2.46 lb (1.12 kg)
44-port 1GigE CSFP/SFP MDA-a 2.45 lb (1.11 kg)
Fan Tray Specifications
Parameter
Dimensions (H x W x D)
Weight
Table 23: 7750 SR-a4 Fan Tray Specifications
Description
7.4 x 1.6 x 9.0 in. (18.80 x 4.06 x 22.86 cm)
3.28 lb (1.49 kg)
Parameter
Dimensions (H x W x D)
Weight
Table 24: 7750 SR-a8 Fan Tray Specifications
Description
10.8 x 1.6 x 9.0 in. (27.43 x 4.06 x 22.86 cm)
4.8 lb (2.18 kg)
54 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Power Consumption
Description
Table 25: System Component Power Consumption Values in Watts
Idle
Zero
Traffic
Maximum
Power (W)
Chassis components
7750 SR-a4 Fan tray
7750 SR-a8 Fan tray
CPM-a
IOM-a
MDA-a and MDA-aXP cards
1-port 100GigE CFP MDA-aXP
6-Port 10GigE SFP+ and 1-Port 40GigE
QSFP+ Combo MDA-aXP
10-port 10GigE SFP+ MDA-aXP
2-port 10GigE SFP+ and 12-port 1GigE
SFP Combo MDA-a
4-port 10GigE SFP+ MDA-a 0
20-port 10/100/1000 TX RJ-45 MDA-a 0
44-port 1GigE CSFP/SFP MDA-a 0
0
0
0
0
30
30
28
70
30
30
30
175
52
40
40
38
32
28
45
30
30
30
190
56
52
48
41
32
30
48
240
240
35
250
75
72
55
42
35
35
52
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration NEBS requirement
(65ºC).
5.
The chassis consumes no power because it has no power dissipating components when the fans and cards are removed.
7750 SR-a4 and SR-a8 Installation Guide 55
Operating Requirements
Operating Requirements
Table 26: 7750 SR-a Hardware for AC or DC Operational Requirements
Description Minimum
CPM-a
Maximum Field-Replaceable
1 2 Yes
IOM-a 7750 SR-a4: 1
7750 SR-a8: 1
7750 SR-a4: 1
7750 SR-a8: 2
Yes
MDA-a Yes
Fan tray
Air filter
Universal AC PSU (if connecting to an AC power source) or –48 VDC PSU (if connecting to a DC circuit)
7750 SR-a4: 1
7750 SR-a8: 1
1
1
7750 SR-a4: 1
7750 SR-a8: 2
1
4
7750 SR-a4: 4
7750 SR-a8: 8
1 Yes
Yes
Yes
1 per PSU 1 per PSU Yes
Note:
1.
AC power cables are only shipped with the 7750 SR-a chassis if ordered. 10A and 13A cords can be ordered from Alcatel-Lucent
If AC power cables are not ordered, you must supply them. You must use a 12A rated cord or better for low line voltage (100-120V), and a 10A cord for high-line voltage.
DC power cables are not supplied. All power cables used on the 7750 SR-a chassis must meet your local safety code.
56 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Equipment Rack
Warning:
• Ensure that you follow the equipment rack manufacturer’s instructions for correct rack installation.
•
Ensure that you comply with the location requirements outlined in Chassis Location
Requirements on page 59 . Failure to comply with these requirements may impede
correct airflow and may result in the system overheating.
The router must be installed in an equipment rack. The router cannot operate from a tabletop or floor.
The 7750 SR-a chassis are designed to be front mounted and installed in an EIA-310 standard
19-in. (482.6 mm) equipment rack.
The chassis have integrated mounting flanges for front-mount installation in a 19-in.
(482.6 mm) rack. The rail mounting holes in the equipment rack must align with the mounting holes on the chassis mounting flanges.
Figure 14 shows the dimensions of the rack.
7750 SR-a4 and SR-a8 Installation Guide 57
Equipment Rack
Figure 14: EIA-310 19-in. (482.6 mm) Equipment Rack Dimensions
1 RU
1.75 in.
(44.45 mm)
0.625 in.
(15.9 mm)
0.625 in.
(15.9 mm)
0.5 in.
(12.7 mm)
7750 S R-a4 Fan Tray
Pwr
Stat
Lnk Act
Lnk
1 2
Act Lnk
3 4
Act Lnk
5 6
Act Lnk
7 8
Act Lnk
9 10
Act Lnk
11 12
Act Lnk
13 14
Act Lnk
15 16
Act Lnk
17 18
Act Lnk
19 20
Act
Pwr
Stat
Pwr
S tat
S lot Layout
1/1 XP
1/3
1/2 XP
1/4
1
CPM A CPM B
Pwr
7750 SR-a Stat
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Critical Major Minor
Alarms
ACO/LT
1PPS
Compact Flash
1 2 3 4 5 6 7 8 9 10
Pwr
Stat
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
Pwr
Stat
Lnk/Act
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
ACO
1PPS
Compact Flash
7750 SR-a4
Service Router
+
_
Pwr
S tat
+
_
Pwr
S tat
Chassis width
10RU
17.72 in.
(445 mm)
Chassis Flange width
19 in.
(4 8 2.6 mm)
5 RU
8 .
8 6 in.
(222.25 mm)
24700
ETSI Rack Adapter Brackets
For a front mount in an ETSI rack, you must first install mounting bracket extenders, which are shipped in the accessory box with the chassis. The accessory box includes adapter brackets for a 535-mm ETSI rack and eight 12-24 screws to mount the brackets. See
Attaching the Adapter Brackets to the Chassis on page 80 for more information.
58 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Torque Specifications for Rack Mounting
Racks and rack-mounting screws are not supplied by Alcatel-Lucent. EIA-310 defines four screw sizes: 10-32, 12-24, M5, and M6. Each screw size has a different typical torque value, which can vary depending on the material used in the manufacture of the rack and screws.
Table 27 lists some typical torque values.
Warning: Always follow the rack manufacturer’s instructions regarding screws and torque.
Table 27: Typical Torque Values for Rack Mounting the Chassis
Screw Size
10-32
12-24
M5
M6
Typical Torque
18-20 lbf-in (2.03 to 2.25 N .
m)
24-28 lbf-in (2.71 to 3.16 N
.
m)
20-22 lbf-in (2.25 to 2.48 N
.
m)
34-38 lbf-in (3.84 to 4.29 N
.
m)
Chassis Location Requirements
Observe the following requirements when installing the system horizontally in the 19-in.
(482.6 mm) rack.
• Maintain clearance around the chassis as shown in the shaded areas in
and as described in
• Ensure that the inlet and exhaust of the chassis is free of obstructions from cabling, mounting hardware, or other electronic equipment in the area.
7750 SR-a4 and SR-a8 Installation Guide 59
Equipment Rack
Figure 15: Chassis Clearance Requirements for Horizontal Mount (View from Top)
2 Rear
3 3
4
1
24546
2
3
Key
1
Table 28: Chassis Clearance Specifications for Horizontal Mount
Description
Front: 20 in. (50.8 cm) required for service access
Rear: No clearance required
Side: 3 in. (7.6 cm) minimum required on each side of the rack for air intake
(right) and for exhaust (left)
60 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Safety Considerations
This section contains safety information about the following:
•
•
•
•
•
•
•
Placement
Danger:
• Verify that the rack is correctly bolted, braced, and grounded to a grounding electrode.
Warning:
• Install the 7750 SR-a chassis in a clean, dry, ventilated, and temperature-controlled room.
• Install the chassis in the equipment rack before installing the components.
7750 SR-a4 and SR-a8 Installation Guide 61
Safety Considerations
Grounding
Danger: AC powered units
• Chassis ground cables are not included. Use only power cords that have a grounding
(earthing) path. Main grounding (earthing) connection points are through the IEC60320 appliance inlets. Grounding (earthing) points on the sides of the equipment are for equipotential bonding only and are safety grounding (earthing) points for the equipment.
Lack of correct grounding (earthing) of the equipment may result in a safety hazard and excessive electromagnetic emissions.
The ground conductor must be #8 AWG minimum or the same AWG as the power conductors if they are larger.
• The router and equipment rack must be correctly grounded. If you ground the equipment by a method other than those provided in this manual, that method should be in compliance with all local wiring regulations and practices.
Warning:
• Electrostatic discharge (ESD) damage can occur if components are mishandled.
Always wear an ESD-preventive wrist or ankle strap in contact with bare skin. Always connect the ESD strap (with banana plug) to the ESD connection socket (grounding jack) on the front of the chassis. An ESD strap is included in the accessory box that is shipped with the chassis.
Danger: DC powered units
• The 7750 SR-a includes a terminal for chassis ground on the front of the chassis. For both AC- and DC-powered deployments, the ground terminal must be connected.
Ensure that all power is OFF from the DC circuit. Locate the circuit breaker on the panel board that serves the DC circuit. Switch the circuit breaker to the OFF position. For extra safety, you can tape the handle of the circuit breaker to the OFF position.
• When wiring the unit, the ground connection must always be made first and disconnected last.
• The correct wiring sequence is -V BAT/negative to -V BAT/negative and 0V
RTN/positive to 0V RTN/positive.
The router is suitable for installation as part of the Common Bonding Network (CBN) or an
Isolated Bonding Network (IBN).
The router is suitable for installation in Network Telecommunication Facilities or locations where the NEC applies.
62 7750 SR-a4 and SR-a8 Installation Guide
Cabling
Site Preparation
For information about grounding the chassis and connecting the AC or DC supply, see
Chassis Ground Wiring on page 85
; Installing, Wiring, and Connecting an AC PSU on page
Installing, Wiring, and Connecting a –48 VDC PSU on page 98 .
Warning:
• To comply with the GR-1089-CORE, Issue 06, requirement R4-9 [31] standard for electromagnetic compatibility and safety, all intra-building ports are specified for use with shielded and grounded cables at both ends.
• Intrabuilding ports of the equipment or subassembly are suitable for connection to intrabuilding or unexposed wiring or cabling only. Intrabuilding ports of the equipment or subassembly must not be metallically connected to interfaces that connect to the
Outside Plant (OSP) or its wiring or to equipment in an Isolated Bonding Network (IBN) unless the wiring passes through an SPCW as defined in GR-295. These interfaces are designed for use as intrabuilding interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 06) and require isolation from the exposed OSP cabling. The addition of primary protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring. For equipment installed in an IBN, use Mesh-BN,
Mesh-IBN, or Chain-IBN. Equipment rearrangements shall maintain the existing bonding topology.
• Bare conductors must be coated with an appropriate antioxidant compound before crimp connections are made. All unplated connectors, braided strap, and bus bars must be brought to a bright finish, then coated with an antioxidant before they are connected.
• The 7750 SR-a is suitable for use in DC-I, DC-C, or AC powered installations. There are no connections between the battery returns and the chassis ground within the
7750 SR-a.
7750 SR-a4 and SR-a8 Installation Guide 63
Safety Considerations
Power
Danger:
• Only trained and qualified electrical service personnel should perform wiring and cabling to the system.
• All power to the equipment rack or cabinet should be disconnected before the installation.
• The power cables must be copper and meet your local electric code requirements.
• The circuit breaker is not intended to be used as the chassis ON/OFF switch.
Disconnect the power from the power source to remove power.
• The 7750 SR-a routers with DC PSU modules should be installed only in restricted access areas (such as dedicated equipment rooms and electrical closets).
• An external circuit breaker no greater than 60 A must be located within a readily accessible distance of the equipment. This is intended as the disconnect device.
DC Power Requirements
• A disconnect device must be provided within 9.84 ft (3 m) of the 7750 SR-a chassis.
• A #8 AWG (maximum) power conductor must be provided for each of the DC input connections.
AC Power Cord Requirements by Country
The following AC power cord requirements are applicable to all countries:
• The length of the power cord must be at least 6 ft (1.8 m) and a maximum of
9.75 ft (3.0 m).
• All power cords must be approved by an acceptable accredited agency responsible for evaluation in the country where the power cord set is used.
• The power cord must have a minimum current capacity of 10 A and a nominal voltage rating of 220 or 240 VAC, as required by each country’s power system. The power cord must have a minimum current capacity of 12 A for 100V-120 VAC.
• The appliance coupler must meet the mechanical configuration of an EN 60 320/IEC
320 Standard Sheet C13 connector for mating with appliance inlet on the unit.
• The power cord set used with this 7750 SR-a must meet the local safety code and requirements.
64 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
lists the power cord requirements for individual countries; Table 30
describes the common grounding requirements for AC power cords for specific regions.
Table 29: Power Cord Set Requirements – By Country
Country
Belgium
France
Italy
Norway
Sweden
Switzerland
United Kingdom
Accredited Agency
EANSW
OVE
CEBC
CSA
DEMKO
SETI
UTE
VDE
IMQ
JIS
NEMKO
SEMKO
SEV
BSMI
BSI
UL
1. The flexible cord must be a harmonized (HAR) Type HO5VV-F, 3-conductor cord with a minimum 0.75 mm
2
conductor size. The power cord fittings (the appliance coupler and wall plug) must bear the certification mark of the agency responsible for evaluation in the country where it is used.
2. Canada, Japan, Taiwan, and USA can use 100-120 V systems. In which case a minimum 12 A cord must be used.
7750 SR-a4 and SR-a8 Installation Guide 65
Safety Considerations
3. The flexible cord must be a minimum Type SVT or equivalent, #18 AWG,
3-conductor. The wall plug must be a two-pole (3-pin) grounding type with a NEMA
6-15P (15 A, 250 V) configuration. For 100-120 VAC systems, the flexible cord must be Type SVT or equivalent, #16 AWG, 3-conductor.
4. The appliance coupler, flexible cord, and wall plug must bear a “T” mark and registration number in accordance with the Japanese Dentori Law. The flexible cord must be Type VCT or VCTF, 3-conductor, 0.75 mm2 conductor size. The wall plug must be a two-pole grounding type with a Japanese Industrial Standard C8303 (15 A,
125 V) configuration. For 100-120 VAC systems, the flexible cord must be Type
VCT or VCTF, 3-conductor, 1.25 mm 2 conductor size.
Table 30: Common Grounding-Type (Earthing) Power Cord Descriptions
Country/Plug Description
Continental Europe:
• CEE7 standard VII male plug
• Harmonized cord (HAR marking on the outside of the cord jacket to comply with the CENELEC
Harmonized Document HD-21)
USA/Canada:
• NEMA 6-15P male plug
• UL recognized (UL stamped on cord jacket)
• CSA certified (CSA label secured to the cord)
Japan:
• JIS 8303 male plug
• Carry Japan T-mark approval
United Kingdom:
• BS1363 male plug with fuse
• Harmonized cord
Specifications
220 or 230 VAC
50 Hz
Single phase
100-120, 220 or 240 VAC
50 to 60 Hz
Single phase
100-120, 220 or 240 VAC
50 to 60 Hz
Single phase
240 VAC
50 Hz
Single phase
Fan Tray
For a horizontally mounted 7750 SR-a chassis, the cooling system must have at least
3 in. (7.6 cm) of clearance on each side of the rack to ensure adequate air intake and exhaust and at least 20 in. (50.8 cm) in the front for installation and maintenance access.
The fan tray must be in place before the chassis is powered up.
66 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Air Filter
The air filter is factory-installed and is field-replaceable. The air filter must be in place before the chassis is powered up.
The air filter should be inspected monthly. Replace the filter media when accumulated dust is present.
Allow at least 20 in. (50.8 cm) in the front for installation and maintenance access.
Storage
Impedance panels are required in all empty card and component slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference.
To store an uninstalled 7750 SR-a4 or 7750 SR-a8 or extra field-replaceable parts (if applicable), repackage the components in the original packaging or an appropriately sized container and keep them in a dry, dust-free, and temperature-controlled environment.
Table 31 describes the storage specifications.
Table 31: Storage Specifications
Parameter Description
Storage and shipping temperature From –40° to 158°F (–40° to 70°C)
Non-condensing relative humidity Within 5 to 95%
7750 SR-a4 and SR-a8 Installation Guide 67
Safety Standards/Compliance Agency Certifications
Safety Standards/Compliance Agency
Certifications
Type
Safety
EMC
Immunity
Table 32: Compliance Certifications
Standard
CAN/CSA–C22.2 No 60950-1
ANSI/UL 60950-1
EN 60950-1
IEC 60950-1CB Scheme
FDA CDRH 21-CFR 1040
EN 60825-1
IEC 60825-2
CB certificate
FCC Part 15 Class A
ICES-003 Class A
VCCI Class A
EN 300 386
IEC CISPR22
AS/NZS CISPR22
CNS 13438
KCC Korea-Emissions & Immunity (in accordance CISPR/KN22)
EN55022 Class A
ETSI EN 300 132-2
ETSI EN 300 132-3
EN 55024
BT GS-7
ES 201 468
68 7750 SR-a4 and SR-a8 Installation Guide
Site Preparation
Type
Table 32: Compliance Certifications (Continued)
Standard
NEBS Level 3 GR-1089-CORE
GR-63-CORE
GR-295-CORE
ATIS-0600020
ATIS-0600019
ATIS-0600010.03
ATIS-0600015
RBOC
ATIS-0600015.03
ATT-TP-76200
VZ-TPR-9205
VZ-TPR-9307
VZ-TPR-9305
Environmental ETSI EN 300 019-2-1; Storage Tests, Class 1.2
ETSI EN 300 019-2-2; Transportation Tests, Class 2.3
ETSI EN 300 019-2-3; Operational Tests, Class 3.2
ETSI EN 300 753 Acoustic Noise
7750 SR-a4 and SR-a8 Installation Guide 69
Safety Standards/Compliance Agency Certifications
70 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
In This Chapter
This chapter describes how to unpack and install the 7750 SR-a4 and 7750 SR-a8 chassis.
Topics in this chapter include:
•
Unpacking the Chassis on page 72
•
Installation Preparation and Precautions on page 75
•
Installing a 7750 SR-a Chassis Horizontally in a Rack on page 77
•
Chassis Ground Wiring on page 85
•
Installing the Wire-Form Cable Guides on page 89
Note: You must comply with the general safety precautions and product requirements described in
Site Preparation on page 47 before you perform the procedures contained in
this chapter.
7750 SR-a4 and SR-a8 Installation Guide 71
Unpacking the Chassis
Unpacking the Chassis
Unpack and install the 7750 SR-a4 or 7750 SR-a8 chassis before you install the components.
The CPM-a, IOM-a, MDA-a cards, and cables are field-installable and field-replaceable components. Refer to
Installing Components on page 107
Field-Replaceable Units on page 171 for more details.
Unpacking Precautions
Review the following list to avoid injury and to prevent damage to the 7750 SR-a chassis.
Danger:
• To prevent injury or damage to the router, it is recommended that two people remove the router from the shipping box and mount it into a rack.
• When unpacking the chassis, lift the chassis by its rack mounting brackets; do not put your hands inside a card slot to lift the chassis.
• Do not load components into the chassis until the chassis is mounted in the rack.
Warning:
• The shipping weight of each SR-a chassis is:
→ 7750 SR-a4 chassis: 31 lb (14.06 kg)
→ 7750 SR-a8 chassis: 38 lb (17.24 kg)
• The 7750 SR-a4 and 7750 SR-a8 chassis are shipped in a heavy corrugated cardboard container protected by a foam cap and base. Do not discard the packaging container and materials used in shipping. The packing materials should be reused if it is necessary to relocate the router.
• Keep the arrows on the shipping container pointed up.
• Keep the chassis wrapped in the antistatic packaging until you are ready to install the chassis.
Note:
• The unpackaged weight of each SR-a chassis is:
→ empty 7750 SR-a4 chassis: 22.71 lb (10.30 kg)
→ empty 7750 SR-a8 chassis: 30 lb (13.61 kg)
shows the 7750 SR-a chassis packaging.
Table 33 describes the contents.
72 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Figure 16: Unpacking the 7750 SR-a Chassis
5
2
4
3
2
1
24547
4
5
2
3
Key
1
Table 33: Contents of Shipping Package
Description
Shipping container
Foam caps
7750 SR-a chassis
Antistatic bag
Accessory kit. See
To unpack the chassis:
Step 1.
Open the shipping container
Step 2.
Remove accessory kit.
Step 3.
Remove the foam cap.
Step 4.
With two people, carefully remove the chassis from the box. The chassis is wrapped in an antistatic bag.
7750 SR-a4 and SR-a8 Installation Guide 73
Unpacking the Chassis
Caution: There are no handles or hand grips on the 7750 SR-a chassis. Lift the chassis by its rack mounting brackets. Do not put your hands inside the chassis.
Step 5.
Remove the protective antistatic wrapping when you are ready to install the chassis.
Accessories
Table 34 lists the contents of the accessories kit.
Quantity
1
2
1
2
2
8
1
Table 34: Accessories List
Accessory
Console cable
10-32 KEP nuts for ground lug
45-degree ground lug
Wire-form cable guide specific to the chassis size
ETSI bracket specific to the chassis size, to accommodate the 535-mm mounting width aperture of the ETSI 600 mm wide by 300 mm deep rack
12-24 Phillips screws for adapter brackets for ETSI rack
ESD wrist strap
74 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Installation Preparation and Precautions
Before you begin, observe the following:
Danger:
• Only trained and qualified personnel should install or replace this equipment.
• Verify the following:
→ The power to the rack is OFF .
→ The equipment rack must be correctly grounded.
• Do not assume that power has been disconnected from a circuit. Be sure to disconnect power from the equipment rack and external cables before installing or removing the
7750 SR-a4 or 7750 SR-a8.
• Ensure that nearby equipment, including breaker panel bus bars and power connectors, is made safe. Either shut off the power, if possible, or install safety guards or mats over exposed power points and cables.
• Verify that the equipment rack is securely installed, anchored, and grounded. Refer to the rack manufacturer’s documentation for instructions.
• For personal safety, use at least two people to install the router. Use a equipment lift, if necessary.
• Always install the heaviest equipment in the bottom of the rack to keep the center of gravity of the equipment rack as low as possible.
Warning:
• Prepare the equipment rack and site before installing the 7750 SR-a chassis and ensure that you comply with all the requirements described in
. Plan the chassis placement near the power sources and network interface connections.
Caution:
• There are no handles or hand grips on the 7750 SR-a chassis. Lift the router from underneath. Do not lift the router by the internal chassis frame.
• When rack-mounting a chassis in an equipment rack, do not stack one 7750 SR-a chassis or any other equipment directly on top of another 7750 SR-a chassis, such that the bottom chassis is supporting other devices. Each unit must be secured in the rack with the appropriate mounting apparatus.
7750 SR-a4 and SR-a8 Installation Guide 75
Installation Preparation and Precautions
Note:
• Installation of the 7750 SR-a4 or the 7750 SR-a8 chassis in the rack requires two people, one person to hold the chassis and one person to secure it to the rack.
76 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Installing a 7750 SR-a Chassis Horizontally in a
Rack
Two rack sizes are supported. See the following sections:
•
Standard 19-in. (482.6 mm) EIA-310 Rack on page 77
•
ETSI 600-mm x 300mm Rack on page 79
Standard 19-in. (482.6 mm) EIA-310 Rack
The 7750 SR-a chassis are designed for front-mount installation in a 19-in. (482.6 mm)
EIA-310 rack with universal spacing. Figure 17 shows the 7750 SR-a4 chassis,
Figure 18 shows the 7750 SR-a8 chassis, and Table 35
describes the features of both chassis.
Figure 17: Installing the 7750 SR-a4 Chassis in a 19-in. (482.6 mm) EIA-310 Rack
7750 SR-a4
S ervice Router
7750 SR-a4 and SR-a8 Installation Guide
1
4 3 2
2454 8
77
Installing a 7750 SR-a Chassis Horizontally in a Rack
Figure 18: Installing the 7750 SR-a8 Chassis in a 19-in. (482.6 mm) EIA-310 Rack
78
1
7750 SR-a8
S ervice Router
3 2
4
24549
3
4
Key
1
2
Table 35: Rack Mounting Parts: 19-in. (482.6 mm) EIA-310 Rack
Description
19-in. (482.6 mm) equipment rack rail
Screws used temporarily to support the bottom edge of the rack-mounting flange during chassis installation. Screws are partially installed in the equipment rack rail in the lowest allocated U-space on both sides of the rack unit.
Integrated rack-mounting flange on the chassis. Flanges cannot be removed.
Eight rack-mounting screws (screws not included)
Required tools:
7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
• a torque driver for the rack screws. Refer to the rack manufacturer’s documentation for instructions.
To install the chassis horizontally in the 19-in. (482.6 mm) EIA-310 rack:
Step 1.
Install screws in the rack rail in the bottom-most hole of the allocated U space to support the chassis temporarily during installation. Make sure that the screws are installed at least half way into the hole. Do not tighten the screw. (Key 2 in
Step 2.
With at least two people and, if necessary, using an equipment lift, position the chassis in front of the rack.
Step 3.
Lift the chassis from the bottom and position it in the rack, resting the bottom of the
rack-mounting flange (Key 3 in Figure 17 and
Figure 18 ) on the temporary screws
(Key 2 in
Step 4.
Align the mounting holes on each bracket with the mounting holes on the rack rail.
Step 5.
Insert a screw into each mounting hole. Do not skip any holes. Do not tighten the screws fully.
Note: The oval-shaped holes in the mounting flanges enable you to adjust the alignment of the chassis during installation before you tighten the screws.
Step 6.
Align the chassis in the rack, if required.
Step 7.
Tighten all screws. Refer to the rack manufacturer’s documentation for
instructions. See Torque Specifications for Rack Mounting on page 59
for more information.
Step 8.
Ground the chassis to the building ground. See Chassis Ground Wiring on page 85 .
ETSI 600-mm x 300mm Rack
The accessory box that is shipped with the chassis contains rack mounting brackets that adapt the 535-mm wide mounting aperture of the ETSI rack to the width of the mounting flanges of the 7750 SR-a chassis. The inner part of the ETSI rack adapter bracket emulates the universal spacing of the EIA-310 rack. The outer part of the ETSI rack adapter bracket attaches to the ETSI rack rail.
The horizontally mounted 7750 SR-a4 occupies 9 ETSI RUs. The horizontally mounted
7750 SR-a8 occupies 13 ETSI RUs.
7750 SR-a4 and SR-a8 Installation Guide 79
Installing a 7750 SR-a Chassis Horizontally in a Rack
Attaching the Adapter Brackets to the Chassis
shows the 7750 SR-a4 chassis,
Figure 20 shows 7750 SR-a8 chassis, and Table 36
describes the keys to both figures.
Figure 19: Attaching the 9-RU ETSI Adapter Brackets to the 7750 SR-a4 Chassis
7750 SR-a4
S ervice Router
3 2 1
24660
80 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Figure 20: Attaching the 13-RU ETSI Adapter Brackets to the 7750 SR-a8 Chassis
7750 SR-a8
S ervice Router
3 2 1
2465 8
2
3
Key
1
Table 36: Attaching ETSI Adapter Brackets
Description
ETSI adapter bracket (two supplied in the accessory kit). The round threaded holes are used to attach the adapter to the chassis mounting flange.
Integrated rack-mounting flange on the chassis. Flanges cannot be removed.
Eight 12-24 Phillips screws to mount ETSI adapter brackets to the chassis
(supplied in the accessory kit)
Required tools:
• a #3 Phillips torque driver for the supplied Phillips screws
7750 SR-a4 and SR-a8 Installation Guide 81
Installing a 7750 SR-a Chassis Horizontally in a Rack
To attach the ETSI adapter brackets to the chassis:
Step 1.
Position an adapter bracket so that the narrower portion of the bracket with the round threaded holes is behind the mounting flange of the chassis. The portion of the adapter with the oval mounting holes must face outwards.
Step 2.
Attach the adapter brackets to the chassis using the eight supplied 12-24 screws.
Step 3.
Use a #3 Phillips torque driver to tighten the screws. Do not over-tighten. Torque to 24 to 28 lbf-in (2.71 to 3.15 N.m).
Step 4.
Repeat Step 1 to Step 3 to attach the bracket to the other side of the chassis. You
are now ready to install the chassis in the rack.
Installing the Chassis in the ETSI 600-mm x 300mm Rack
shows the 7750 SR-a4 chassis, Figure 22 shows the 7750 SR-a8 chassis, and
Table 37 describes the keys to both figures.
Figure 21: Installing the 7750 SR-a4 Chassis in the ETSI Rack
82
7750 SR-a4
S ervice Router
4 3 2
1
24659
7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Figure 22: Installing the 7750 SR-a8 Chassis in the ETSI Rack
1
7750 SR-a8
S ervice Router
4 3 2
24657
Key
1
2
3
4
Table 37: Rack Mounting Parts: ETSI Rack with Adapters
Description
ETSI equipment rack rail
Screws used temporarily to support the bottom edge of the ETSI brackets during chassis installation. Screws are partially installed in the rack rail in the lowest allocated U-space on both sides of the rack unit.
ETSI brackets (installed on chassis, as described in
Brackets to the Chassis on page 80
). The oval (unthreaded) mounting holes are used to attach the adapter bracket to the rack.
Eight screws to attach the ETSI adapter bracket to the equipment rack (screws not included)
Required tools:
7750 SR-a4 and SR-a8 Installation Guide 83
Installing a 7750 SR-a Chassis Horizontally in a Rack
• a torque driver for the ETSI rack screws. Refer to the rack manufacturer’s documentation for instructions.
• a #2 or #3 Phillips torque driver, depending on the screw size that you use
To install the chassis horizontally in the ETSI rack:
Step 1.
Install screws in the rack rail in the bottom-most hole of the allocated U space to support the chassis temporarily during installation. Make sure that the screws are installed at least half way into the hole. Do not tighten the screw. (Key 2 in
Step 2.
With at least two people and, if necessary, using an equipment lift, position the chassis in front of the rack.
Step 3.
Lift the chassis from the bottom and position it in the rack, resting the bottom of the
ETSI brackets (Key 3 in
) on the temporary screws (Key 2
Step 4.
Insert a screw into each mounting hole. Do not skip any holes. Do not tighten the screws fully.
Note: The oval-shaped holes in the mounting flanges enable you to adjust the alignment of the chassis during installation before you tighten the screws.
Step 5.
Align the chassis in the rack, if required.
Step 6.
Tighten all screws. Refer to the rack manufacturer’s documentation for
instructions. See Torque Specifications for Rack Mounting on page 59
for more information.
Step 7.
Ground the chassis to the building ground. See Chassis Ground Wiring on page 85 .
84 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Chassis Ground Wiring
Danger:
• Only trained and qualified personnel should install or replace this equipment.
• The 7750 SR-a chassis ground studs located on the left-hand side mounting bracket must be a permanent connection to the earth (building) ground point. The connection requires the use of the supplied lug and nuts.
• When wiring the 7750 SR-a router, the ground connection must always be made first and disconnected last.
Preparing the Ground Wire
The 7750 SR-a chassis must be correctly connected to earth ground.
Grounding cables are not provided with the 7750 SR-a chassis. The length of the grounding wire that you need depends on the location of the 7750 SR-a router and its proximity to the correct grounding facilities. You must use a minimum of #8 AWG wire for the ground connection.
Alcatel-Lucent supplies the chassis ground lug (Burndy YAZ8C2TC1045, Alcatel-Lucent
PN 52-1178-01). Because of the compact design of the 7750 SR-a chassis, the lug is angled at 45 degrees. The lug and two 10-32 nuts are included in the accessory kit that is shipped with the chassis. The lug is designed for #8 AWG ground wire.
Note: If you require a gauge larger than #8 AWG, the lug must be a two-hole, 45-degree lug for #10 studs. The spacing between the two holes in the lug must be 5/8 in. (1.59 cm).
shows how to prepare the ground wire for installation.
ground wiring features.
Figure 24 shows attaching the ground wire connection. Table 39
describes the ground wire connection features.
7750 SR-a4 and SR-a8 Installation Guide 85
Chassis Ground Wiring
3
Figure 23: Preparing the Ground Wire
2
1
24650
2
3
Key
1
Table 38: Ground Wiring Parts
Description
Copper ground wire with green or green/yellow colored insulation jacket, minimum #8 AWG (not supplied)
Insulation stripped 7/8 in. (22.23 mm) according to Burndy specification.
Two-hole ring lug, Burndy YAZ8C2TC1045, Alcatel-Lucent PN 52-1178-01
(supplied in the accessory kit)
Making the Ground Connection
Figure 24 shows how to attach the ground wire to the chassis. Table 39
describes the parts.
86 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
2 3 1
Figure 24: Attaching the Chassis Ground Connector
1
7750 S
R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act Lnk
3 4
Act
Lnk
5 6
Act
Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act
Lnk
19
20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/2
1/3
1/4
CPM A
1
CPM B
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat 7750 SR-a4
S ervice Router
1
Pwr
Stat
2
3
4
5
6
Lnk Act 7
Lnk Act 8
Lnk
Act
9
Lnk
Act
10
Lnk Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Table 39: Ground Wire Connection Parts
Description
Chassis ground studs on the chassis mounting flange
Two 10-32 KEP nuts for the ground lug (supplied in the accessory kit)
Two-hole ground lug and copper wire cable
24551
Key
1
2
3
Required tools and hardware:
• wire stripping tool
• wire cutter
• crimping tool, Burndy Die Index #49
• 3/8 in. hex torque driver for #10 hex nut
• copper ground wire cable (minimum #8 AWG)
To make the chassis ground connection:
Step 1.
Run a single length of minimum #8 AWG wire from the ground point (building ground or equipment ground bus) to the chassis ground studs. When routing the cable, ensure that there is enough extra wire to form a service loop at the chassis end in order to facilitate maintenance.
7750 SR-a4 and SR-a8 Installation Guide 87
Chassis Ground Wiring
Step 2.
Using a wire-stripping tool, strip the insulation from the wire according to the local
safety code and crimp the ring lug to the wire, as shown in Figure 23 .
Step 3.
Place the two-hole lug on the ground studs such that the wire runs down the rack upright.
Step 4.
Secure the lug with the two supplied KEP nuts. Orient the KEP nuts so that the KEP washer is in contact with the lug. Tighten the nuts to a torque of 18 to 20 lbf-in
(0.9 to 1.13 N
.
m) maximum. Do not over-tighten.
Step 5.
Form a service loop with the extra wire and secure it to a convenient place (for example, a rack upright).
Step 6.
Connect the opposite end of the ground wire to the appropriate ground point at the installation site. Ensure that the chassis ground connection is made according to the local safety code.
Step 7.
Install an optional cable management system. Otherwise, go to Installing PSUs on page 91
for information about how to connect the router to the power source.
88 7750 SR-a4 and SR-a8 Installation Guide
Installing the 7750 SR-a Chassis
Installing the Wire-Form Cable Guides
Two wire-form cable guides are supplied with each 7750 SR-a4 and 7750 SR-a8 chassis. The guides are shipped in the accessory box with the chassis. Each guide has a series of hooks to route and retain the chassis cables.
The wire-form cable guides are optional. Wire-form cable guides are designed for horizontally deployed systems but can also be used for vertically mounted systems.
If you choose to use the wire-form cable guide, you can install one on one side or one on each side. The guides are installed on the chassis on the rack flanges on the left and right side using
two screws, which are not included with the guides. Figure 25 shows the guides.
Figure 25: Wire-Form Cable Guides
Left br a cket, hole s 1 a nd 3
7750 SRa 4 F a n Tr a y
Pwr a t
Pwr
S tat
1
2
3
4
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Pwr
S tat
5
6
7
Lnk Act
Lnk
Act
Lnk Act
1
2
3
4
5
6
Lnk Act
Lnk Act
Lnk
Act
Lnk Act
Lnk Act
Lnk Act
7
Lnk Act
8
9
10
Lnk Act
Lnk Act
Lnk Act
Pwr
S tat
Lnk
Pwr
S tat
1
2
Lnk
Act
Lnk Act
3
4
Lnk Act
Lnk
Act
Slot L a yo u
1/1 XP t
1/2
1/ 3
1/4
1
2/1 XP
2/2 XP
2/ 3
2/4
2
CPM A
CPM B
Pwr
S tat
Lnk/Act
1 2 3
4 5 6 7
8 9 10 11 12 1
3 14 15 16
17 1
8 19 20 21 22
24
25 26 27 2
8 29 3
0 3 2
33 3 4
3 5 3 6 3
7 38 3 9 40
41 42 4
3 44
Pwr
S tat
Lnk/Act
1
2 3
1 3
14
4 5
6
7
8
9
10 11
12
Lnk
Act
Lnk
Act
Pwr
S tat
Pwr
S tat
DTE
DCE
Lnk
Act Lnk
Act
Con s ole
Critical
Major
Alarm s
Minor
ACO
LT
1PP S
Compact Fla s h
Pwr
S tat
Lnk
1 2
Act
Lnk
3 4
Act
Lnk
5
6
Act Lnk
7 8
Act
Lnk
9 10
Act
Lnk
11
12
Act
Lnk
1 3 14
Act
Lnk
15 16
Act
Lnk
17
1 8
Act Lnk
19 20
Act
Pwr
S tat
1
2
3
4
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Pwr
S tat
DTE
DCE
Lnk
Act Lnk
Act
Con s ole
Critical
Major
Minor
ACO
LT
1PP
S
Compact Fla s h
7750
S R-a
Service Ro ter
8
Right br a cket, hole s 2 a nd 4
2466 3
7750 SR-a4 and SR-a8 Installation Guide 89
Installing the Wire-Form Cable Guides
Note: When routing cables to the sides of the chassis, the egress cables may impede the removal and replacement of the fan on the left or the air filter on the right. For this reason, left mounting the cable guide may be the preferred option, because the air filter must be removed frequently for inspection.
Guides are normally installed after the chassis is mounted in a rack. For EIA racks, you must remove two of the four rack-mount screws completely, then re-use the screws to mount the guides to the chassis and the chassis to the rack. If ETSI brackets are used, you can install the guides with the adapter brackets before you mount the chassis in the rack.
Required tools:
• a torque driver for the cable guide screws. Refer to the rack manufacturer’s documentation for instructions.
• EIA rack screws (not supplied), or 12-24 screws supplied with the ETSI adapter brackets
To install the wire-form cable guides:
Step 1.
Remove the screws in holes 1 and 3 on the left side of the chassis flange.
Step 2.
Orient the cable guide so the mounting eyelets are pointing toward the chassis, as indicated in
.
Step 3.
Replace and tighten the two screws. Refer to the rack manufacturer’s documentation for instructions. See
Torque Specifications for Rack Mounting on page 59
for more information.
Step 4.
Remove the screws in holes 2 and 4 on the right side of the chassis flange.
Step 5.
Orient the cable guide so the mounting eyelets are pointing toward the chassis, as indicated in
.
Step 6.
Replace and tighten the two screws. Refer to the rack manufacturer’s documentation for instructions. See
Torque Specifications for Rack Mounting on page 59
for more information.
90 7750 SR-a4 and SR-a8 Installation Guide
Installing PSUs
In This Chapter
This chapter describes how to install, wire, and connect the AC and DC Power Supply Units
(PSUs) in the 7750 SR-a4 and 7750 SR-a8 chassis. Topics in this chapter include:
•
•
Installing, Wiring, and Connecting an AC PSU on page 94
•
Installing, Wiring, and Connecting a –48 VDC PSU on page 98
7750 SR-a4 and SR-a8 Installation Guide 91
Warnings and Notes
Warnings and Notes
Danger:
• Only trained and qualified personnel should install or replace this equipment and connect the power cables.
• Confirm that the DC power source is OFF during installation. The power source should be a safety extra-low voltage (SELV) source.
• Turn off power at the power source before you install or remove power cords.
• Before working on equipment that is connected to power, remove jewelry, such as rings, necklaces, and watches. When metal objects are in contact with power and ground, serious burns can occur or the objects can be welded to the terminals.
• Make all ground connections first.
• The router and equipment rack must be correctly grounded.
• You must use power cables that meet the local electrical code requirements.
• This product relies on the building’s installation for short-circuit (overcurrent) protection.
For AC powered systems, ensure that a circuit breaker, or other equivalent means, rated 20 A, is used in the building’s AC branch circuit for the current carrying conductors.
• For DC powered systems, the unit should be connected to a DC branch circuit with a maximum 60 A circuit breaker that meets the requirements for branch circuit protection.
A suitable disconnect device must be provided in the DC branch, either a circuit breaker or switch that can disconnect power from the system during servicing.
Warning:
• Impedance panels are required in all empty slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference. Impedance panels do not have board components or connector pins.
• Electrostatic discharge (ESD) damage can occur if components are mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
• Do not install equipment that appears to be damaged.
92 7750 SR-a4 and SR-a8 Installation Guide
Installing PSUs
Note:
• The 7750 SR-a4 chassis requires a minimum of one PSU to operate, but two are recommended for redundancy. The 7750 SR-a8 chassis requires a minimum of two
PSUs to operate, but four are recommended for redundancy.
• For full redundancy, each PSU module should be attached to an independent power source with a dedicated circuit breaker. A fully redundant system must be connected to both DC PSU modules, or both AC PSU modules, or one DC and one AC PSU module.
• In the event of a PSU module failure, the entire AC or DC PSU must be replaced. There are no field-serviceable parts inside the PSU.
• Empty PSU slots in the chassis must be covered by impedance panels. Panels must be ordered separately. See
Impedance Panels on page 43 for more information.
7750 SR-a4 and SR-a8 Installation Guide 93
Installing, Wiring, and Connecting an AC PSU
Installing, Wiring, and Connecting an AC PSU
This section describes the following:
•
Installing an AC PSU in the 7750 SR-a chassis on page 94
•
AC-Input Power Supply Guidelines on page 96
•
Connecting the AC Power Cord to the PSU on page 96
Installing an AC PSU in the 7750 SR-a chassis
and Figure 27 shows how to install an AC PSU in the chassis. Table 40
describes the parts and actions.
Figure 26: Installing an AC PSU (7750 SR-a4)
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
2
4 3
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk Act
Lnk
Act
8
9
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
1
24553
94 7750 SR-a4 and SR-a8 Installation Guide
Figure 27: Installing a AC PSU (7750 SR-a8)
Installing PSUs
7750 S
R-a4 Fan Tray
Pwr
S tat
Pwr
Stat
Pwr
Stat
Lnk Act
Lnk
1
1
Act
2
Lnk Act
2
Lnk Act
3
Lnk Act
4
5
6
Lnk Act
Lnk Act
Lnk Act
7
8
9
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
Lnk Act
Pwr
Stat
Lnk
Pwr
Stat
1
2
3
4
Lnk Act
Lnk Act
Lnk Act
Lnk Act
S lot Layout
1/1 XP
1/2
1/3
1/4
1
2/1 XP
2/2 XP
2/3
2/4
CPM A
2
CPM B
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2
3
4 5
6
7
8
9
10 11
13
14
12 Lnk
Act
Lnk
Act
Pwr
Stat
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat 7750 SR-a8
S ervice Router
Pwr
Stat
Lnk
1
2
Act Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act
Lnk
19
20
Act
Pwr
Stat
1
2
Lnk Act
Lnk Act
3
4
Lnk Act
Lnk Act
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
1
4 3
24590
2
3
Key
1
4
Table 40: Installing an AC PSU
Description
Chassis guides in the power slot
AC PSU handle
Spring-loaded latch lock
Direction of movement
To install an AC PSU in a 7750 SR-a chassis:
Step 1.
Align the PSU module with the chassis guides in power slot (Key 1 in Figure 26
Step 2.
Grip and hold the handle (Key 2 in
) on the PSU with your hand.
Step 3.
Slide the unit into the slot. Firmly press the PSU module all the way into the slot.
The latch clicks into place to secure the PSU when the unit is fully inserted.
7750 SR-a4 and SR-a8 Installation Guide 95
Installing, Wiring, and Connecting an AC PSU
AC-Input Power Supply Guidelines
Danger:
• The AC power cord is not supplied and must be ordered to comply with local country codes and the intended voltage. When applying power to the chassis, be sure to use an approved AC power cord set, and ensure that you do not use any other product's AC power cord set.
• AC units are rated 100-120 V or 200-240 V. For 100-120 V, you must use a cord rated for a minimum of 12 A. For 200-240 V, you must use a cord rated for a minimum of 10 A.
• For AC powered units, use only power cords that have a grounding (earthing) path.
Main grounding (earthing) connection points are through the IEC60320 appliance inlets.
Grounding (earthing) points on the front of the equipment are for equipotential bonding only and are not the safety grounding (earthing) points for the equipment. Lack of correct grounding (earthing) of the equipment may result in a safety hazard and excessive electromagnetic emissions.
Warning:
• If you ground the equipment by a method other than those provided in this manual, that method should be in compliance with all local wiring regulations and practices.
• In order to comply with the GR-1089 Lightning Criteria for Equipment Interfacing With
AC Power Ports, an external Surge Protective Device is intended to be used at the AC input of the router.
Note: To facilitate power redundancy, you must connect all PSU modules to an appropriate
source (see DC-Input Power Supply Guidelines on page 100 .)
Connecting the AC Power Cord to the PSU
There is one input AC power cord receptacle for each AC PSU. The AC PSU has an AC plug inlet to accept an AC power cord. The other end of the AC power cord must have a plug that
can fit into the power source receptacle that is standard for your geographic region. Figure 28
shows how to connect the AC power cord.
Table 41 describes the connections.
96 7750 SR-a4 and SR-a8 Installation Guide
Installing PSUs
Warning: Do not apply power to the chassis. The chassis does not have an ON/OFF switch.
The unit will be powered on if you plug the power cord into an AC power source receptacle.
is shown as an example: do not plug the far end of the power cord into an AC power source until all components are installed.
Figure 28: AC Power Cord Connection
S lot Layout
1/1 XP
1/3
1/2 XP
1/4
1
CPM A CPM B
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Critical Major Minor
Alarms
ACO
LT
1
1PPS
Compact Flash
2
7750 SR-a4
Service Router
24554
Key
1
2
Table 41: AC Power Cord Connection Descriptions
Description
Power cord inserted in AC PSU inlet
Example of a remote AC power source receptacle
To connect the AC power cable to the PSU:
Step 1.
Verify that the AC cord meets your regional requirements. Do not use power cords that do not meet these standards.The AC cord must be rated at 12A minimum for use at 100-120V and 10A minimum for use at 220/240V.
Step 2.
On the AC PSU, plug the AC power cord into the inlet on the front of each AC PSU,
as shown in key 1 of Figure 28 .
Step 3.
Engage the power cord retainer on the PSU inlet by lowering the retainer until it fully secures the cord.
Step 4.
Install the other components in the chassis, as described in Installing Components on page 107
before you power up the system. Power up is described in Powering
Up, Initializing, and Configuring on page 123
.
7750 SR-a4 and SR-a8 Installation Guide 97
Installing, Wiring, and Connecting a –48 VDC PSU
Installing, Wiring, and Connecting a –48 VDC PSU
This section describes the following:
•
Installing a –48 VDC PSU in the 7750 SR-a Chassis on page 98
•
DC-Input Power Supply Guidelines on page 100
•
Preparing the PSU Ground and Power Cables on page 101
•
Connecting –48 VDC Power on page 104
Installing a –48 VDC PSU in the 7750 SR-a Chassis
and Figure 30 shows how to install an DC PSU in the chassis. Table 42
describes the parts and actions.
Figure 29: Installing a –48 VDC PSU (7750 SR-a4)
2
4
7750
S R-a4 Fan Tray
Pwr
Stat
Pwr
Stat
Lnk
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
Pwr
Stat
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
1
3
24555
98 7750 SR-a4 and SR-a8 Installation Guide
Figure 30: Installing a –48 VDC PSU (7750 SR-a8)
Installing PSUs
4
2
7750
S R-a4 Fan Tray
Pwr
S tat
Pwr
Stat
1
2
Lnk Act
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
8
9
10
Lnk
Act
Lnk Act
Lnk Act
Lnk Act
Pwr
Stat
1
2
3
4
5
Lnk
Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
6
Lnk Act
7
Lnk Act
Pwr
Stat
Lnk
Pwr
Stat
1
Lnk
Act
2
3
4
Lnk Act
Lnk Act
Lnk Act
S lot Layout
1/1 XP
1/3
1/2
1/4
1
2/1 XP
2/3
2/2 XP
2/4
CPM A
2
CPM B
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2 3
4
5
6 7
13
14
8 9
10
11
12 Lnk
Act
Lnk Act
Pwr
Stat
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a8
S ervice Router
Pwr
Stat
Pwr
Stat
Lnk
1 2
Act
Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
Stat
1
2
Lnk Act
Lnk Act
3
4
Lnk Act
Lnk Act
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
3
1
245 8 4
2
3
Key
1
4
Table 42: Installing a DC PSU
Description
Chassis guide in the power slot
DC PSU handle
Spring-loaded latch lock
Direction of movement
To install a –48 VDC PSU in a 7750 SR-a chassis:
Step 1.
Align the PSU module with the chassis guides in power slot (Key 1 in Figure 29
Step 2.
Grip and hold the handle (Key 2 in
) on the PSU with your hand.
Step 3.
Slide the unit into the slot. Firmly press the PSU module all the way into the slot.
The latch (Key 3) clicks into place to secure the PSU when the unit is fully inserted.
7750 SR-a4 and SR-a8 Installation Guide 99
Installing, Wiring, and Connecting a –48 VDC PSU
DC-Input Power Supply Guidelines
Danger:
• Ensure that all power is OFF from the DC circuit. Locate the circuit breaker on the panel board that serves the DC circuit. Set the circuit breaker to the OFF (O) position.
• When wiring the unit, the ground connection must always be made first and disconnected last.
• The correct wiring sequence is positive PSU terminal to the power source return terminal, and negative PSU terminal to the –48V terminal.
• 7750 SR-a systems equipped with DC-input power supplies should be installed in restricted access areas, such as a dedicated equipment room or an equipment closet, in accordance with Articles 110-16, 110-17, and 110-18 of the National Electric Code
ANSI/ NFPA 70.
Warning:
• Use a minimum of #8 AWG wire for the –48 VDC and RTN connections.
• Use a minimum of #8 AWG wire for the ground connections.
• A ring lug (approved by an accredited safety agency) and associated approved crimp tool must be used.
• Consult your local electrical code for more information.
If you intend to use DC-input power in the 7750 SR-a chassis, observe the following:
• The 7750 SR-a4 chassis requires a minimum of one PSU to operate, but two are recommended for redundancy. The 7750 SR-a8 chassis requires a minimum of two
PSUs to operate, but four are recommended for redundancy.
• A fully redundant system operates with two power systems. AC and DC power types are available in the 7750 SR-a chassis. Ideally, the power sources should be connected to separate breakers.
• DC-input power connections require copper wire cables.
• DC power cables are not shipped with the 7750 SR-a chassis.
• For DC power connections, a ground connection on the chassis is required.
Grounding cables are not provided.
Wiring the DC Inputs
The –48 VDC PSU has one ground screw and a terminal block with positive and negative
terminals. Figure 31 shows the –48 VDC PSU. Table 43 describes the components.
100 7750 SR-a4 and SR-a8 Installation Guide
Installing PSUs
Figure 31: –48 VDC Ground and Power Connection
1
Pwr
S tat
4
+ -
2 3
24556
3
4
Key
1
2
Table 43: –48 VDC Ground and Power Connection Descriptions
Description
DC power grounding terminal with M4 screw
Positive (+) terminal with M4 screw
Negative (–) terminal with M4 screw
Clear plastic sliding safety cover for the terminal block. The cover rests on three raised guides to provide clearance for the cable connectors. During installation, the cover can be removed temporarily to access the terminal screws.
Preparing the PSU Ground and Power Cables
Alcatel-Lucent does not supply the ground cable. You must use a minimum #8 AWG wire, fitted with terminal rings suitable for #8 AWG wire.
Alcatel-Lucent does not supply the DC cable. The PSU compliance rating requires that you use #8 AWG wire, fitted with terminal rings. To ensure that the terminal rings fit the terminal block, Alcatel-Lucent recommends the following #8 AWG terminal rings:
• Insulated: Molex 19071-0178
• Non-insulated: Molex 19130-0200
• Sealing: Molex 19164-0889
Required tools and hardware
7750 SR-a4 and SR-a8 Installation Guide 101
Installing, Wiring, and Connecting a –48 VDC PSU
• three lengths of #8 AWG wire, insulated and color-coded according to local safety code, or #8 AWG jacketed three-conductor cord:
→ one ground wire, measured to extend from the PSU to the building ground point or equipment bus ground point
→ one positive battery cable, measured to extend from the PSU to the positive battery terminal
→ one negative battery cable, measured to extend from the PSU to the negative battery terminal or disconnect device, if used
• three single-hole terminal lugs for the three lengths of #8 AWG wire for connection to the PSU
• wire stripping tool
• wire crimper
• Phillips torque screwdriver
To prepare the PSU end of the ground cable:
Step 1.
Using a wire-stripping tool, strip the wire insulation to the length according to the recommendation of the terminal manufacturer or local safety code (Keys 1and 2 in
Step 2.
Attach the wire to the terminal ring and crimp the ring lug according to the
instructions of the terminal ring manufacturer (Key 3 in Figure 32
).
Figure 32: Attaching the Ring Lug to a Ground Cable
2
3
1
19641
Key
1
2
3
Table 44: Ring Lug to Ground Cable Descriptions
Description
#8 AWG copper wire (see Required tools and hardware)
Insulation stripped according to the recommendation of the manufacturer or local safety code
Ring lug (see Required tools and hardware)
102 7750 SR-a4 and SR-a8 Installation Guide
Installing PSUs
To prepare the PSU end of the DC power cables:
Step 1.
For the DC positive and DC negative wires, use a wire-stripping tool to strip the wire insulation to the length according to the recommendation of the manufacturer
or local safety code (Keys 1 and 2 in Figure 33 ).
Step 2.
Attach each wire to the terminal ring and crimp the ring lug according to the
instructions of the terminal ring manufacturer (Key 3 in Figure 33
).
Figure 33: Attaching the Ring Lug to a Power Cable
2
3
1
19641
Key
1
2
3
Table 45: Ring Lug to Power Cable Descriptions
Description
#8 AWG copper wire (see Required tools and hardware)
Insulation stripped according to the recommendation of the manufacturer or local safety code
Ring lug (see Required tools and hardware)
Remote Cable Connections
Cables that connect to the building ground point, equipment bus ground point, DC power sources, and disconnect devices must be prepared and attached according to the local safety code.
shows an example of how redundant connections can be terminated. A circuit breaker is used in each power feed as a disconnect device. See
DC Power Requirements on page 64
for information about the recommended ratings for circuit breakers.
7750 SR-a4 and SR-a8 Installation Guide 103
Installing, Wiring, and Connecting a –48 VDC PSU
Figure 34: Example of Redundant DC Power Feeds
1
2
+B a tt A
-B a tt A
+B a tt B
-B a tt B
3
6 7
3
+
_
+
_
4
5
24670
6
7
4
5
2
3
Key
1
Table 46: Redundant DC Power Feeds Description
Description
DC PSU ground
Terminal block
Disconnect device
DC source A
DC source B
Battery wire (negative)
Battery return wire (positive)
Connecting –48 VDC Power
Note:
• For a fully redundant power system, you must connect at least two DC PSU modules or one DC and one AC PSU module.
• Wires can be routed to either side of the chassis.
104 7750 SR-a4 and SR-a8 Installation Guide
Installing PSUs
Required tools and hardware
• three lengths of #8 AWG wire: one length for the ground and two lengths for the
battery cables, prepared as described in Preparing the PSU Ground and Power Cables on page 101
• Phillips torque screwdriver
To connect the –48 VDC power feeds:
Step 1.
Ensure that all power to the router at the remote DC power source is OFF.
Step 2.
Attach the ground wire, if required by the local electrical code.
i.
Run a length of ground wire from the appropriate grounding point to the router.
ii. Prepare the end of the wire at the ground point according to local safety practices and attach it to the grounding terminal.
iii. Prepare the end of the wire at the router by attaching a ring lug, as described in
Preparing the PSU Ground and Power Cables on page 101
.
iv. Attach the ring lug on the ground wire to the DC PSU ground (Key 1 in
v. Tighten the M4 screw. Do not over-tighten. Torque to 8-10 lbf-in.
Step 3.
Remove the safety cover from the three raised guides on the terminal block (Key4
Step 4.
Remove the positive and negative terminal screws (Keys 2 and 3 in
).
Step 5.
Make the battery return connections.
i.
Run the length of wire from the power source positive terminal to the terminal block on the router.
ii. Prepare the end of the wire at the power source according to local safety practices and attach it to the power source positive terminal.
iii. Prepare the end of the wire at the router by attaching a ring lug, as described in
Preparing the PSU Ground and Power Cables on page 101
.
iv. Attach the wire at the router end to the positive (+) battery return terminal on the PSU.
v. Replace and tighten the terminal screw using a Phillips torque screwdriver. Do not over-tighten. The recommended torque is 3 lbf-in (0.339 N
.
m).
Step 6.
Make the battery connections to the disconnect device.
i.
Run a length of wire from the disconnect device to the router.
ii. Prepare the end of the wire at the router by attaching a ring lug, as described in
Preparing the PSU Ground and Power Cables on page 101
.
iii. Attach the battery wire at the router end to the negative (–) battery terminal on the PSU.
7750 SR-a4 and SR-a8 Installation Guide 105
Installing, Wiring, and Connecting a –48 VDC PSU iv. Replace and tighten the terminal screw using a Phillips torque screwdriver. Do not over-tighten. The recommended torque is 3 lbf-in (0.339 N .
m).
v. Replace the safety cover that you removed from the terminal block in Step
.
vi. Prepare the wire at the disconnect device according to local safety practices.
vii. Attach the wire to the disconnect device.
Step 7.
Check that the DC supply wiring is correct.
Step 8.
For redundant supply configurations, repeat Step 2 to
Step 9.
Install the other components in the chassis (as described in Installing PSUs on page
), before you power up the system (as described in Powering Up, Initializing, and
106 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
In This Chapter
This chapter describes how to perform the initial installation of the 7750 SR-a4 and
7750 SR-a8 chassis components. Topics in this chapter include:
•
Warnings and Notes on page 108
•
Installing a Fan Tray on page 109
•
Installing the Internal CF Card on the CPM-a on page 111
•
Installing the CPM-a on page 112
•
Installing the IOM-a on page 114
•
Installing MDA-a and MDA-aXP Cards on page 116
•
Installing an SFP, SFP+, CSFP, CFP, or QSFP on an MDA-a or MDA-aXP Card on page 119
•
Managing Cable Connections to MDA-a and MDA-aXP Cards on page 120
7750 SR-a4 and SR-a8 Installation Guide 107
Warnings and Notes
Warnings and Notes
Danger:
• Only trained and qualified personnel should install or replace this equipment.
• Invisible laser radiation can be emitted from the aperture ports when no cable is connected. Avoid exposure and do not stare into open apertures.
• Install the components after the 7750 SR-a chassis has been installed in the rack.
• Do not power up a 7750 SR-a router until all components are installed and verified.
• Before you perform any procedures in this chapter, ensure that you comply with the general safety precautions and product requirements described in
.
Warning:
• Electrostatic discharge (ESD) damage can occur if MDA-a cards are mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
• Place the 7750 SR-a components on an antistatic surface during installation.
• Do not over-tighten the captive screws when securing modules.
Note:
• Alcatel-Lucent recommends that you read the following sections in the Overview chapter for detailed information and specific requirements that apply to the 7750 SR-a components:
→
→
→
→
→
• If you need to remove or replace an installed component, refer to
Field-Replaceable Units on page 171
.
• Empty slots in the chassis must be covered by impedance panels. Panels must be ordered separately. See
Impedance Panels on page 43 for more information.
108 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Installing a Fan Tray
The fan tray is chassis specific. The 7750 SR-a4 has four axial fans. The 7750 SR-a8 chassis requires a larger fan tray, which has six axial fans. The fan tray is mandatory, and must be installed in the vertical slot on the left side of the chassis.
Figure 35 shows how to install the SR-a4 fan tray in the 7750 SR-a4 chassis. Table 47
describes the features. The same installation method applies to the SR-a8 fan tray in the
7750 SR-a8 chassis.
Figure 35: Installing the Fan Tray (7750 SR-a4)
2
1
7750
S R-a4 Fan Tray
Pwr
Stat
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
Pwr
Stat
1
Pwr
Stat
2
3
4
5
6
Lnk Act
Lnk Act
7
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
Key
1
2
Table 47: Fan Tray Installation Features
Description
Chassis slot guide for fan tray
Captive screws
Required tools:
• #2 Phillips or flat blade torque driver
To install the fan tray:
Step 1.
Align the fan tray with the guides in fan tray slot (Key 1 in Figure 35 ).
245 8 6
7750 SR-a4 and SR-a8 Installation Guide 109
Installing a Fan Tray
Step 2.
Grip the replacement fan tray from the top and bottom of the faceplate and slide the connector end halfway into the slot.
Step 3.
Push on the faceplate of the fan tray until the connectors are fully seated.
Step 4.
With a torque driver, secure the fan tray into place by tightening the captive screws.
Torque to 4 to 5 lbf-in (0.45 to 0.56 N
.
m). Do not over torque.
110 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Installing the Internal CF Card on the CPM-a
The CPM-a supports an internal CF card that contains the boot file that is required to boot the
7750 SR-a at startup.
The CF card is shipped separately from the chassis and the CPM-a. The card must be installed on the CPM-a before you insert the CPM-a in the 7750 SR-a chassis.
Figure 36 shows the location of the CF card on the CPM-a.
describes the installation features.
Figure 36: Location of Internal CF Card on CPM-a
S tat
Con s ole
2
Alarm s
2
ACO
1PP
S
1PP Compact Fla s h
Compact Fla s h
1
1
24558
Key
1
2
Table 48: CF Installation Features
Description
Card retainer bail
CF card (shown installed in the slot)
To install the CF card on the CPM-a:
Step 1.
Remove the CF card from the packaging and place it on a flat antistatic work surface.
Step 2.
Remove the CPM-a from the packaging and place it on a flat antistatic work surface. Hold the CPM-a by the edges. Do not touch the printed circuit board or connector pins.
Step 3.
Lift the card retainer bail (Key 1 on Figure 36 ) which covers the CF slot.
Step 4.
Insert the CF card (Key 2 on Figure 36 ) into the slot until it is fully seated.
Step 5.
Close the card retainer bail to hold the CF card in the slot.
7750 SR-a4 and SR-a8 Installation Guide 111
Installing the CPM-a
Installing the CPM-a
The 7750 SR-a chassis requires a minimum of one CPM-a to operate, but two are
recommended for redundancy. CPM-a cards occupy half of a slot, as listed in Table 49 .
Table 49: CPM-a positions in the SR-a chassis
Chassis Type
7750 SR-a4
7750 SR-a8
Slot Numbers
4
7
CPM-a Position
A (left)
B (right)
A (left)
B (right)
shows the installation of the CPM-a in slot 4, position B of a 7750 SR-a4.
describes the installation features.
Figure 37: Installing a CPM-a (7750 SR-a4)
R-a4 Fan Tray
7750 SR-a4
S ervice Router
2
Pwr
S tat
Pwr
Stat
Pwr
Stat
Pwr
Stat
Lnk
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACOLT
1PPS
Compact Flash
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
1
3
24559
112 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Key
1
2
3
Table 50: CPM-a Installation Features
Description
Slot guide
Captive screw
Threaded receptacle
Required tools:
• #2 Phillips or flat blade torque driver
To install a CPM-a:
Note: The following procedure assumes that you have performed the steps described in
Installing the Internal CF Card on the CPM-a on page 111
.
Step 1.
Locate the appropriate CPM-a slot on the chassis.
Step 2.
Insert the CPM-a into the CPM-a slot. Align the card with the slot guides and the captive screw with the threaded receptacle.
Step 3.
Press the CPM-a firmly into the slot. Make sure that the connectors are fully seated in the chassis. The faceplate of the CPM-a should be flush with the chassis.
Step 4.
Use a torque driver to tighten the captive screws. The recommended torque is 4 to
5 lbf-in (0.45 to 0.56 N .
m). Do not over-tighten.
Step 5.
If applicable, insert a compact flash card into the external CF card slot on the front of the card (cf1).
Step 6.
(Optional) Install the redundant CPM-a in the other CPM-a slot on the chassis.
Step 7.
Attach cables to the CPM-a ports.
7750 SR-a4 and SR-a8 Installation Guide 113
Installing the IOM-a
Installing the IOM-a
The 7750 SR-a4 has one IOM-a in slot 3, as shown in
Figure 38 . The 7750 SR-a8 has up to
two IOM-a cards, one in slot 3, the other in slot 6.
Table 51 describes the installation features;
the features apply to both chassis.
Figure 38: Installing an IOM-a
3
4
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
Stat
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO
LT
1PPS
Compact Flash
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk
Act
Lnk
Act
8
9
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO
LT
1PPS
Compact Flash
3
4
1
2
2
3
Key
1
4
Table 51: Installing an IOM-a Features
Description
IOM-a positioned in the chassis slot guides
Threaded receptacle on the chassis
IOM-a captive screws, one on each side of the IOM-a
Ejector lever, one on each side of the IOM-a (in open position)
Required tools:
• #2 Phillips or flat blade torque driver
To install an IOM-a:
24560
114 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Step 1.
Remove the IOM-a from the packaging and place it on a flat antistatic work surface.
Do not touch the printed circuit board or connector pins. Hold the IOM-a by the edges.
Step 2.
Move the ejector levers to the open position (Key 4 in Figure 38
).
Step 3.
Locate the IOM-a slot (Slot 3) on the chassis, and align the card with the slot guide
(Key 1 in
).
Step 4.
Slide the card inward until the captive screws align with the threaded receptacle in the chassis (Key 2 in
), and the connectors are seated in the backplane.
Step 5.
Push the ejector levers simultaneously inward to complete the seating and to lock the connectors and IOM-a in place.
The faceplate must be flush with the front of the chassis. If an ejector lever does not shift to the locked position, the IOM-a is not seated correctly. Pull the card out, reinsert it, then shift the levers to the locked position.
Step 6.
Use a torque driver to tighten the captive screws (Key 3 in Figure 38 ). The
recommended torque is 4 to 5 lbf-in (0.45 to 0.56 N
.
m). Do not over-tighten. The ejector levers must remain in the locked position while the card is installed in the chassis.
Step 7.
For the 7750 SR-a8, repeat these steps to install the second IOM-a in slot 6 on the chassis.
7750 SR-a4 and SR-a8 Installation Guide 115
Installing MDA-a and MDA-aXP Cards
Installing MDA-a and MDA-aXP Cards
The term MDA-a is used generically in this section to refer to MDA-a and MDA-aXP cards.
For information about the MDA-a cards that are supported in the 7750 SR-a4 and 7750 SR-a8
chassis and the slots in which the cards are supported, see MDA-a Cards on page 36
.
and Figure 40 show the installation of an MDA-a. Table 52 describes the
installation features.
Figure 39: Installing an MDA-a (7750 SR-a4)
R-a4 Fan Tray
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
7750 SR-a4
S ervice Router
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Pwr
Stat
2
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
1
Pwr
Stat
2
Lnk Act
Lnk Act
3
Lnk Act
4
Lnk Act
Stat
Lnk/Act
Lnk
Act
6
1 2 3 4
Lnk
Act
7
8
9
10
5 6 7 8
Lnk
Act
9 10 11 12
Lnk
13 14 15 16
Act
Lnk
17 18 19 20
Act
21 22 23 24
Lnk
Act
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor 2
ACO/LT
1PPS
Compact Flash Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat
1
3
24561
116 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Figure 40: Installing an MDA-a (7750 SR-a8)
7750
S R-a4 Fan Tray
Pwr
S tat
S lot Layout
1/1 XP
1/3
1/2
1/4
1
2/1 XP
2/3
2/2 XP
2/4
CPM A
2
CPM B
Pwr
Stat
Pwr
Stat
1
2
3
4
5
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
1
Act
2
Lnk Act
6
7
8
Lnk Act
Lnk Act
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
1
Stat
Act
Lnk Act
2
2
9
10
Lnk Act
Lnk Act
3
4
Lnk
Act
Lnk
Act
5
Pwr
Stat
Lnk Act
6
7
Lnk Act
Lnk Act
8
Lnk
Act
9
10
Lnk Act
Lnk Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2
3
4
5
6 7
8
9
10
11
12 Lnk
13
Act
Lnk
14
Act
Pwr
Stat
Pwr
Stat
1
2
3
4
Lnk Act
Lnk Act
Lnk
Act
Lnk Act
2
Pwr
Stat
Lnk
1
2
Act Lnk
3 4
Act
Lnk
5 6
Act
Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16 Act Lnk
17 18
Act
Lnk
19 20
Act
1
2
Lnk Act
Lnk Act
3
4
Lnk Act
Lnk Act
ACO
1PPS
Compact Flash
7750 SR-a8
S ervice Router
ACO
1PPS
Compact Flash
1
3
24550
Key
1
2
3
Table 52: MDA-a Installation Features
Description
Slot guide
Captive screw
Threaded receptacle
Required tools:
• #2 Phillips or flat blade torque driver
To install an MDA-a card:
Step 1.
Remove the MDA-a from the packaging and place it on a flat antistatic work surface. Do not touch the printed circuit board or connector pins. Hold the card by the edges.
Step 2.
Locate the appropriate chassis slot and MDA-a or MDA-aXP slot.
7750 SR-a4 and SR-a8 Installation Guide 117
Installing MDA-a and MDA-aXP Cards
Step 3.
Insert the MDA-a into the MDA-a or MDA-aXP slot. Align the card with the slot guides and the captive screw with the threaded receptacle.
Step 4.
Press the MDA-a firmly into the slot. Make sure that the connectors are fully seated in the chassis. The faceplate of the MDA-a should be flush with the chassis.
Step 5.
Use a torque driver to tighten the captive screws. The recommended torque is 4 to
5 lbf-in (0.45 to 0.56 N .
m). Do not over-tighten.
Step 6.
Repeat these steps for the other MDA-a cards, as required.
Step 7.
Attach cables to the MDA-a ports.
118 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Installing an SFP, SFP+, CSFP, CFP, or QSFP on an
MDA-a or MDA-aXP Card
A variety of types of transceivers are supported on the 7750 SR-a, depending on the MDA-a or MDA-aXP card. The following optical transceivers are supported:
• Small Form Factor Pluggable (SFP and SFP+)
• Compact Small Form Factor Pluggable (CSFP)
• C Form Factor Pluggable (CFP)
• Quad Small Form Factor Pluggable Plus (QSFP+)
See Appendix E: Pluggable Transceivers on page 221
for information about how to install and replace optical transceivers.
7750 SR-a4 and SR-a8 Installation Guide 119
Managing Cable Connections to MDA-a and MDA-aXP Cards
Managing Cable Connections to MDA-a and MDAaXP Cards
All cable connections to MDA-a cards are made from the front of the 7750 SR-a chassis. The
MDA-a cards can be connected using Ethernet, copper, or fiber-optic cables. The 7750 SR-a chassis are designed to enable cable routing and management from the front of the chassis.
Ethernet and Copper Wire Cables
For a horizontally mounted chassis, Ethernet and copper wire cables can be routed to the left or right of the chassis using the (optional) wire-form cable management brackets, described
in Installing the Wire-Form Cable Guides on page 89
.
To maintain EMC compliance, cables that are shielded and grounded at both ends must be used with the adapter card interfaces. Use CAT5e shielded cables with Gigabit Ethernet interfaces (electrical).
Warning: To prevent damage to the components during installation, such as damage to the faceplate connectors, avoid excessive bending, twisting, and pulling of Ethernet and copper wire cables. When bundling the cables, leave enough slack to allow room to move the cables aside during servicing and to prevent stress at the termination to the module.
To attach Ethernet and copper wire cables:
Step 1.
Attach the cable to the port connector or SFP connector on the adapter card.
Step 2.
Route the cables to the left or right of the chassis.
Step 3.
Attach the cable to a distribution panel or appropriate connector.
120 7750 SR-a4 and SR-a8 Installation Guide
Installing Components
Fiber Cables
Warning:
• Fiber cables are sensitive to bending, twisting and pulling. Extreme caution is recommended when handling fiber cable.
• To ensure that the minimum fiber bend radius is maintained in the allowable space
AT&T TP-76450 specifies a minimum of 1.0 in (25.4 mm) inside radius for single fibers.
• Use fiber cable with a pre-installed open-angled 90º boot.
• Observe correct fiber connector handling regarding the use of dust covers and cleaning.
Fiber-optic cables are routed in a similar fashion to Ethernet and copper wire cables. Cables are routed to the left or right of the chassis.
Hardware required:
• Velcro straps (optional)
To attach fiber cables:
Step 1.
Attach the cable to the port connector or SFP connector on the adapter card.
Step 2.
Route the cables to the left or right of the chassis. If needed, use a Velcro strap to bundle the cables from each card.
Step 3.
Attach the fiber cable to a distribution panel or appropriate connector.
Alarm Port Connections
The Alarm port on the CPM-a has a 15-pin DB connector. Use a shielded cable to connect the Alarm port to a suitable alarm panel, such as a punch-down or wire-wrap panel. See
Alarms Interface Port Pinouts on page 218 for the required pinout information.
To connect the Alarm port:
Step 1.
Connect the cable assembly to the External Alarm port.
Step 2.
Route the cable to the left or the right of the chassis.
Step 3.
Connect the far end of the cable to the alarm panel.
7750 SR-a4 and SR-a8 Installation Guide 121
Managing Cable Connections to MDA-a and MDA-aXP Cards
122 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and
Configuring
In This Chapter
This chapter describes how to install compact flash cards, power up the 7750 SR-a4 or
7750 SR-a8 chassis, establish the initial router connections, and get started with basic card and port configuration commands. The topics in this chapter include:
•
Compact Flash Card on page 124
•
Powering Up the 7750 SR-a on page 126
•
Establishing Router Management Connections on page 128
•
Configuring Parameters on page 131
•
Configuring Parameters on page 131
7750 SR-a4 and SR-a8 Installation Guide 123
Compact Flash Card
Compact Flash Card
The primary copy of the 7750 SR-a OS software is located on a compact flash card, which is shipped with each software license agreement.
Note:
• The CPM has two slots for removable compact flash cards:
→ Compact Flash Slot 1 (cf1) is on the front of the CPM
→ Compact Flash Slot 3 (cf3) is internal
Configurations and executable images can be stored on flash cards or an FTP file location.
• The flash card containing the bootstrap and boot option files must be installed in the internal Compact Flash Slot 3 (cf3), as described in
Installing the Internal CF Card on the CPM-a on page 111
.
• You must have a console connection. See
Console Connection on page 128 .
shows the compact flash directory structure and filenames.
Figure 41: Files on the Compact Flash
Root bof.cfg
boot.idr
config.cfg TiMOS-m.n.Yz
cpm.tim
iom.tim
Files on the compact flash are:
• bof.cfg — boot option file (bof)
• boot.ldr — bootstrap software
• config.cfg — default configuration file
• TiMOS-m.n.Yz:
→ m — major release number
→ n — minor release number
2456 3
124 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and Configuring
→ Y — A (alpha release), B (beta release), M (maintenance release), or R (released software)
→ z — version number
• cpm.tim — application software file
• iom.tim — application software file
7750 SR-a4 and SR-a8 Installation Guide 125
Powering Up the 7750 SR-a
Powering Up the 7750 SR-a
The 7750 SR-a4 and 7750 SR-a8 do not have a power switch or internal circuit breaker to turn the power ON or OFF:
• For AC power, power is supplied from an AC power outlet.
• For –48 VDC power, the 7750 SR-a system DC power is supplied by a DC branch circuit.
Danger:
• You must comply with the general safety precautions and product requirements described in
Site Preparation on page 47 and the requirements described in
PSUs on page 91 before performing the procedures contained in this chapter.
• Do not power up a 7750 SR-a before verifying that all common equipment (chassis, power, cooling, and grounding) is connected correctly.
• Always keep your fingers away from rotating fan blades. Do not put your fingers or any tool in the fan tray if the fans are still spinning.
Warning: For correct thermal operation, ensure that Impedance panels are installed in all empty slots before powering up the 7750 SR-a.
Note:
• You must complete the procedure
Installing, Wiring, and Connecting an AC PSU on page 94
in
Installing Components on page 107
initialization procedure.
before proceeding with the power-up and
• The primary copy of the 7750 SR-a TiMOS software is located on the compact flash
memory card that must be installed on the CPM, as described in Installing the Internal
CF Card on the CPM-a on page 111
.
• At power up, the fans initially run at full speed. Thereafter, the control system reduces the fan speed based on temperature. During normal operation, fans never turn off completely.
Power-Up
To power-up an AC powered system:
126 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and Configuring
Step 1.
To initiate the boot process, plug the male end of the power cord into a 3-terminal, single-phase power source that provides power within the acceptable range, as described in
Step 2.
Check that the LED on each PSU is green. A green LED indicates that the AC standby and main power supply outputs are operating within specification. If the
LED is off, there is no power input. Refer to
for more information.
To power-up a DC powered system:
Step 1.
Turn on the power at the remote power sources to initiate the boot process.
Step 2.
Check that the LED on each PSU is green. A green LED indicates that the DC standby and main power supply outputs are operating within specification. If the
LED is off, there is no power input. Refer to
for more information.
Component LED Verification
To verify that the components power up correctly:
Step 1.
Verify that the system is initializing.
The system searches the CF card on the CPM for the boot.ldr
file (also known as the bootstrap or boot loader file).
The Status LED on the CPM-a slowly blinks green during initialization.
After initialization (approximately 30 s), the Status LED on the active CPM turns solid green to indicate that the CPM boot/load process is complete and that the
CPM-a is operational as the primary CPM.
The Status LED on the inactive secondary CPM-a rapidly blinks green to indicate that the CPM-a boot/load process is complete and that the CPM-a is operational as the secondary CPM-a.
If the LEDs do not operate as described above, or if they blink and turn off, refer to
Troubleshooting Initial Startup on page 134
.
Step 2.
Verify the operational status of the router components by checking all the LEDs on the CPM-a, IOM-a, fan tray and MDA-a components.
Refer to
Appendix A: Connectors and LEDs on page 137 and
Appendix B: MDAa and MDA-aXP Card Descriptions on page 147
for more information.
7750 SR-a4 and SR-a8 Installation Guide 127
Establishing Router Management Connections
Establishing Router Management Connections
There are two ways to access the management interface for the 7750 SR-a:
•
Console Connection on page 128
•
Console Connection
The Console port on the CPM has an RJ-45 serial port connector. To establish a console connection, you need the following:
• an ASCII terminal or a PC running terminal emulation software set to the parameters shown in
•
a standard RJ-45 serial cable, as described in Table 54
For pinout information, see Console Port Pinouts RS-232 DCE Mode on page 213 .
Parameter
Baud Rate
Data Bits
Parity
Stop Bits
Flow Control
Table 53: Console Configuration Parameter Values
Value
115 200
8
None
1
None
Cable Type
Null modem
Straight-through
Table 54: Console Configuration Parameter Values
DTE/DCE Switch
DTE
DCE
128 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and Configuring
Figure 42: CPM Console Port Connection
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Console Port
Critical Major Minor
Alarms
ACO/LT
1PPS
Compact Flash
24564
To establish a console connection:
Step 1.
Power on the terminal and set the emulation software to the parameters shown in
.
Step 2.
Connect the terminal to the Console port on the front panel ( Figure 42 ) using the
serial cable. Note:
→ If you use a null modem cable, make sure that the switch beside the Console port is set to DTE when connecting to the serial port of a PC.
→ If you use a straight-through cable, make sure that the switch beside the
Console port is set to DCE when connecting to the serial port of a PC.
Step 3.
Establish the connection by pressing the <Enter> key a few times on your terminal keyboard.
Step 4.
At the router prompt, enter the login and password.
The default login is admin
.
The default password is admin
.
Telnet Connection
After a successful initialization, you can access the router with a Telnet connection from a PC
or workstation connected to the network, after the management port (see Figure 43
) has been configured using the bof>address
command. Telnet access provides the same options for user and administrator access as those available through the Console port.
To configure the 7750 SR-a for Telnet access, you need to have a device with Telnet software located on the same network. The 7750 SR-a must have a management IP address. The IP address is manually configured. Each 7750 SR router is limited to a total of seven inbound/ outbound Telnet or SSH sessions to guarantee that either inbound or outbound sessions will be available. For information about configuring router parameters, refer to the appropriate
Router Configuration Guide. For pinout information, refer to Appendix D: CPM-a Pinout
.
7750 SR-a4 and SR-a8 Installation Guide 129
Establishing Router Management Connections
MAC addresses are listed on the small labels on the chassis, IOM-a, and MDA-a. The MAC address also appears in the show router arp
command output.
Figure 43: CPM Management Port Connection
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
Management Port
Critical Major Minor
Alarms
ACO/LT
1PPS
Compact Flash
24565
CLI Syntax: bof address ip-address/mask [active | standby]
For pinout information, see Management Port Pinouts on page 215 .
Running Telnet
After the IP parameters are configured, the CLI can be accessed with a Telnet connection. To establish a Telnet connection, run a Telnet program and issue the Telnet command, followed by the IP address.
The following is an example of a Telnet login:
C:\>telnet 192.168.1.xx1
Login: admin
Password: #####
ALU-1#
The default login is admin
.
The default password is admin
.
130 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and Configuring
Configuring Parameters
After the CPM is installed, chassis slots, IOM-a and MDA-a cards can be configured before or after the components are installed.
Each specific slot must specify an IOM-a, MDA-a slot, and MDA-a type. You cannot configure ports until the MDA-a is configured.
Note:
• IOM-a cards are configured using the card
and card-type
commands (items 1 and
2 in the following list).
• MDA-a cards are configured using the mda
and mda-type
commands (items 3 and 4 in the following list).
Configure components in the following order:
1. Card slot number (use the card
command)
2. Card type (use the card-type
command)
3. MDA-a slot number (use the mda
command)
4. MDA-a type (use the mda-type
command)
5. Ports
Configuring Chassis Slot and IOM-a Parameters
In the config
context, use the following CLI commands and syntax examples to provision the chassis slot and IOM-a:
Command Syntax
Step 1.
card slot-number
Step 2.
card-type card-type
Example card 1 card-type iom-a
Configuring MDA-a Parameters
MDA-a cards must be configured before their ports can be configured.
7750 SR-a4 and SR-a8 Installation Guide 131
Configuring Parameters
MDA-a slots with odd numbers are on the left side of the router; MDA-a slots with even
numbers are on the right side. See Figure 2 and
, which identify the slots in the
7750 SR-a4 and 7750 SR-a chassis.
After the IOM-a is activated, continue in the config
context with the following CLI commands to provision the MDA-a cards.
Command Syntax
Step 1.
mda mda-slot
Step 2.
mda-type mda-type
Step 3.
exit
Example mda 1 mda-type maxp10-10gb-sfp+ exit
To provision additional MDA-a cards, continue the configuration process with Step 4:
Step 4.
mda mda-slot
Step 5.
mda-type mda-type
Step 6.
exit mda 2 mda-type ma4-10gb-sfp+ exit
132 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and Configuring
Example
The following example shows the card
, card-type
, mda,
and mda-type
commands:
ALU-1>config# card 1
ALU-1>config>card# card-type iom-a
ALU-1>config>card# mda 1
ALU-1>config>card>mda# mda-type maxp10-10gb-sfp+
ALU-1>config>card>mda# exit
ALU-1>config>card# mda 3
ALU-1>config>card>mda# mda-type ma4-10gb-sfp+
ALU-1>config>card>mda# exit
The CLI display for the preceding configuration example looks similar to the following:
ALU-1>config# info
. . .
---------------------------------------------echo "Card Configuration"
#--------------------------------------------card 1 card-type iom-a mda 1 mda-type maxp10-10gb-sfp+ exit mda 3 mda-type ma4-10gb-sfp+ exit exit
----------------------------------------------
ALU-1>config#
7750 SR-a4 and SR-a8 Installation Guide 133
Troubleshooting Initial Startup
Troubleshooting Initial Startup
If the Status LED does not light after 30 s, as described in
Component LED Verification on page 127
, the compact flash card is most likely faulty.
If the system cannot load or cannot find the boot.ldr
file on the cf3: slot, the Status LED on the CPM turns off and the system checks for a manual boot sequence interruption. Perform a manual boot sequence interruption by connecting a terminal to a Console port and pressing any key when prompted by the display. Unless an unsuccessful system initialization is manually interrupted, the system will continuously reboot in an attempt to successfully find and load the boot.ldr
file. Insert a compact flash card with the appropriate boot.ldr
file into the cf3: slot, as described in
Replacing the Internal Compact Flash Card on the CPMa on page 195
.
When the system finds the boot.ldr
file, the system processes the initialization parameters from the BOF. The BOF must be on the same drive as the boot loader file. If the BOF cannot be found or loaded, the system prompts for a different image and configuration location.
When the image is successfully loaded, control is passed from the boot loader file to the image. The runtime image attempts to locate the configuration file as configured in the BOF.
The configuration file include chassis, IOM-a, MDA-a, and port configurations, as well as system, routing, and service configurations.
The following example shows the output when either no flash is present or the boot.ldr file cannot be found.
Example: Rebooting display
Rebooting...
Alcatel 7xxx Boot ROM. Copyright 2000-2014 Alcatel-Lucent.
All rights reserved. All use is subject to applicable license agreements.
Build: X-0.0.x-x on Sat Aug 30 19:55:06 PDT 2014 by builder
Version: 0x29
Processor core is CN66xx
COLD boot on processor #1
?Preparing for jump to RAM...
Starting bootrom RAM code...
CPU #1 booted from working sector
Boot rom version is v41
CPU Control FPGA version is 0x07
>>>Testing SDRAM from 0x0000000002200000 to 0x0000000080000000
>>>Testing SDRAM from 0xffffffffe0000000 to 0xfffffffffe000000
>>>Testing SDRAM from 0x0000000080000000 to 0x00000000e4000000
>>>Testing Compact Flash 1... Slot Empty
>>>Testing Compact Flash 3... Slot Empty
Board Serial Number is '0123456789'
Chassis Serial Number is '1234567890'
Searching for boot.ldr on local drives:
No disk in cf3
No disk in cf3
134 7750 SR-a4 and SR-a8 Installation Guide
Powering Up, Initializing, and Configuring
No disk in cf3
Error - file boot.ldr not found on any drive
Please insert CF containing boot.ldr. Rebooting in 5 seconds.
Rebooting...
When the system finds the boot.ldr
file, the system processes the initialization parameters from the BOF (boot option file). The BOF should be on the same drive as the boot.ldr
file. If the BOF cannot be found or loaded, then the system prompts the user for alternate software and configuration file locations.
When the system software is successfully loaded, control is passed from the boot loader file to the system software. The system software attempts to locate the configuration file as configured in the BOF. The configuration file includes chassis, CPM-a, IOM-a, MDA-a, and port configurations, as well as system, routing, and service configurations.
It is important that cables connected to the Console port on the 7750 SR-a chassis are correctly terminated and terminal servers should be correctly configured so as to not negatively affect the functioning of the node.
Noisy lines can be interpreted by the node as keystrokes and could interrupt the boot sequence resulting in an outage. After reboot, the CPM can go into a continuous reboot cycle if the boot process is interrupted by random characters received on the Console port.
To prevent random characters received on the Console port, terminate all console connections. If a terminal server is connected to the 7750 SR-a CPM-a ensure that it is configured to not send unwanted characters to the CPM-a that could interrupt the boot cycle.
For example, configure a no exec
or equivalent CLI command on the terminal server.
7750 SR-a4 and SR-a8 Installation Guide 135
Troubleshooting Initial Startup
136 7750 SR-a4 and SR-a8 Installation Guide
Appendix A: Connectors and LEDs
In This Chapter
This chapter describes the connectors and LEDs for the components and modules used in the
7750 SR-a4 and 7750 SR-a8 routers. All connectors or LEDs are visible from the front of the router; there are no connectors or LEDs on the back of the units. This chapter includes the following topics:
•
7750 SR-a Chassis Indicators on page 138
•
PSU LEDs and Connectors on page 138
•
•
7750 SR-a Module LEDs and Connectors on page 142
7750 SR-a4 and SR-a8 Installation Guide 137
7750 SR-a Chassis Indicators
7750 SR-a Chassis Indicators
The product name is back lit on the chassis as long as at least one PSU is installed and running.
PSU LEDs and Connectors
The following sections describe the LEDs and connectors for the two types of PSUs:
•
7750 SR-a AC PSU LED and Connectors on page 138
•
7750 SR-a –48 VDC PSU LED and Connectors on page 139
7750 SR-a AC PSU LED and Connectors
Figure 44 shows the 7750 SR-a AC PSU. Table 55 describes the connectors and LEDs.
Figure 44: 7750 SR-a AC PSU
3 5
Key
1
2
Part
Handle
Fan
6
1 2 4
24566
Table 55: 7750 SR-a AC PSU Description
Description
Used to remove power supply after the latch (Key 6) is unlocked
Cooling fan for the PSU
138 7750 SR-a4 and SR-a8 Installation Guide
Appendix A: Connectors and LEDs
5
6
Key
3
4
Part
LED
Table 55: 7750 SR-a AC PSU Description (Continued)
Description
Unlit : The AC power input is below the specified minimum to turn on the
PSU.
Green (slow blink) : The PSU is in standby mode. Standby output is operating within normal parameters. The main output is disabled.
Green (solid) : The standby and main outputs are operating within normal parameters and delivering power.
Yellow (slow blink) : A warning condition has been detected on the PSU.
Yellow (solid) : A fault condition has been detected on the PSU.
Red (solid) : An incorrect PSU has been inserted in the shelf.
AC power/ground connector retainer
Secures the AC power cable in place.
AC inlet (IEC 60320-C14) Connector for AC power cable
Latch lock Secures the PSU in place. Press the latch lock to the left to unlock the
PSU.
Refer to Installing, Wiring, and Connecting an AC PSU on page 94 for requirements and
information regarding AC power cables and AC power converters.
7750 SR-a –48 VDC PSU LED and Connectors
shows the SR-a –48 VDC PSU. Table 56
describes the connectors and LEDs.
Figure 45: 7750 SR-a –48 VDC PSU
3
Pwr
S tat
6
7
1 2
+
4
_
5
24567
7750 SR-a4 and SR-a8 Installation Guide 139
Fan Tray LEDs
5
6
3
4
Key
1
2
7
Table 56: 7750 SR-a –48 VDC PSU Description
Part
Handle
Fan
Description
Used to remove power supply after the latch (Key 7) is unlocked
Cooling fan for the PSU
Ground terminal M4 screw
Power connector screw Left terminal stud (Batt terminal) for connection to –48 VDC battery cable
Power connector screw Right terminal stud (RTN terminal) for connection to 0 VDC return cable
LED Unlit
PSU.
: The DC power input is below the specified minimum to turn on the
Green (slow blink) : The PSU is in standby mode. Standby output is operating within normal parameters. The main output is disabled.
Green (solid) : The standby and main outputs are operating within normal parameters.
Yellow (slow blink) : A warning condition has been detected on the PSU.
Yellow (solid) : A fault condition has been detected on the PSU.
Latch lock
Red (solid) : An incorrect PSU has been inserted in the shelf.
Secures the PSU in place. Press the latch lock to the left to unlock the PSU.
You must supply your own DC power cables. Verify that they are compliant with your local safety code. PSUs have no field-replaceable parts. You must replace the entire unit in the event of a failure.
Refer to Installing, Wiring, and Connecting a –48 VDC PSU on page 98
for requirements and information regarding preparing DC power cables.
Fan Tray LEDs
Fan trays are chassis-specific.
• The 7750 SR-a4 5-RU chassis requires the SR-a4 fan tray, which houses four axial fans.
• The 7750 SR-a8 7-RU rack requires the SR-a8 fan tray, which houses six axial fans.
140 7750 SR-a4 and SR-a8 Installation Guide
Appendix A: Connectors and LEDs
shows the 7750 SR-a fan tray LEDs.
Figure 46: 7750 SR-a Fan Tray LEDs
7750 SRa 4 F a n Tr a y
Pwr
St a t
LED
7750 SRa 4 F a a y
Slot L a yo u t
1/1 XP
1/ 3
1/2
1/4
1
2/1 XP
2/ 3
2/2 XP
2/4
2
CPM A CPM B
LED Pwr
St a t
1/1 XP
1/ 3
Slot L a yo u t
1/2 XP
1/4
1
CPM A CPM B
7750 SRa 8 7750 SRa 4
24568
Label/Part
Pwr / Stat
Subcategory
Power
LED
Status
LED
Table 57: 7750 SR-a Fan Tray LED Descriptions
Description
Blue (solid) : During initial power up of the chassis, blue indicates that power to the fan tray is on.
Unlit : There is no power to the fan tray or the power is faulty.
Green (solid) : The fan tray is operational and communicating with the
CPM-a.
Amber (solid) : A fault condition exists for the fan tray. An alarm is generated.
7750 SR-a4 and SR-a8 Installation Guide 141
7750 SR-a Module LEDs and Connectors
7750 SR-a Module LEDs and Connectors
The following SR-a modules are designed for use in the 7750 SR-a4 and 7750 SR-a8 chassis:
•
CPM-a LEDs and Connectors on page 142
•
See Appendix B: MDA-a and MDA-aXP Card Descriptions on page 147
for information about individual MDA-a cards.
CPM-a LEDs and Connectors
shows the CPM-a, which is used in the 7750 SR-a4 and 7750 SR-a8.
describes the connectors and LEDs.
Figure 47: 7750 SR-a CPM-a Features
1 3 5 7 9 11 13 1
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
2 4 6 8
Critical Major Minor
Alarms
10
ACO/LT
12
1PPS
Compact Flash
24539
Key
1
Label/Part
Captive screws
Table 58: 7750 SR-a CPM-a Connector and LED Descriptions
Subcategory
—
Description
Secures the CPM-a in place
142 7750 SR-a4 and SR-a8 Installation Guide
Appendix A: Connectors and LEDs
Key
2
3
4
5
Table 58: 7750 SR-a CPM-a Connector and LED Descriptions (Continued)
Label/Part
Pwr / Stat
Subcategory
Power
Description
DTE
DCE
Console
OES
Status
—
—
Port
Port
Blue (solid) : Power to the CPM-a is on
Unlit : There is no power to the CPM-a or the power is faulty.
Green (slow blink) : The CPM-a is loading firmware and running CPU diagnostics.
Green (solid) : The CPM-a boot/load process is complete and is operational as the primary CPM-a.
Green (slow blink) : The CPM-a boot/load process is complete and is operational as the secondary CPM-a.
Unlit : The CPM-a is operationally down and administratively down.
Set the switch to DTE when connecting to the serial port of a PC with a null modem cable. When the switch is set to DTE, the Console port acts as a data terminal equipment (DTE) serial port.
Set the switch to DCE when connecting to the serial port of a PC with a straight-through cable. When the switch is set to DCE, the Console port is acting as a data communications equipment (DCE) serial port.
The Console port uses an RJ-45 connector that enables a connection to a terminal for performing router monitoring and configuration operations.
Refer to Console Port Pinouts RS-232 DCE Mode on page 213
for pinout assignments.
RJ-45 Optical Extension Shelf port. The OES port is reserved for future use.
7750 SR-a4 and SR-a8 Installation Guide 143
7750 SR-a Module LEDs and Connectors
Key
6
7
8
Mgmt
Table 58: 7750 SR-a CPM-a Connector and LED Descriptions (Continued)
Label/Part Subcategory
Port
Description
BITS
SyncE/
1588
Lnk
Act
Port
Lnk
Port
The 10/100/1000Base-T Ethernet Management port has an RJ-45 copper
Ethernet connector used for system configuration and monitoring.
Autonegotiation is supported. Refer to
Management Port Pinouts on page
for pinout assignments.
The Lnk (link) LED is located in the bottom left corner of the port.
Green : Port speed is 100 Mb/s
Amber : Port speed 10 Mb/s
Blinking : Duplex operation enabled
Solid : Simplex operation enabled
Unlit : The Ethernet link has no activity, or is down or disabled.
The Act (activity) LED is located in the bottom right corner of the port.
Green : There is Rx/Tx activity
Amber : An error condition exists
Unlit : There is no communications link, or the link is operationally down or disabled or shut down.
The BITS port is provisioned with an RJ-45 jack and used for the network clock source. Refer to
BITS Port on page 216 for pinout
assignments.
Green (solid) : Sync-if-timing is configured and a clock signal is received.
Amber (solid) : Sync-if-timing is configured and no clock signal is received.
Notes: Make sure to use shielded cable when connecting to the BITS port.
The SyncE/1588 port is provisioned with an RJ-45 connector. The
Sync-E/1588 port is reserved for future use.
144 7750 SR-a4 and SR-a8 Installation Guide
Appendix A: Connectors and LEDs
Key
9
10
11
12
13
Alarms
Table 58: 7750 SR-a CPM-a Connector and LED Descriptions (Continued)
Label/Part Subcategory
Critical
Description
Alarms port
ACO/LT
1PPS
Compact
Flash
Memory
Card Slot
Major
Minor
Port
—
Port
Slot
Red : Indicates that a critical condition exists, such as a fan failure, a power feed failure, or a critical external alarm input detected
Unlit : No critical alarm conditions
Red : Indicates that a serious condition exists, such as an over-temperature condition or a major external alarm input detected
Unlit : No major alarm conditions
Amber : Minor condition exists, or a minor external alarm input detected
Unlit : No minor alarm conditions
The alarms interface port is a D-type 15-pin receptacle. Refer to
Interface Port on page 217 for pinout assignments.
The Alarm Cutoff/Lamp Test button verifies the operability of LEDs.
When you press and hold this button for three seconds, all LEDs on all chassis modules (see exceptions below) should temporarily illuminate and blink until the button is released. The ACO/LT button tests the functionality and operability of all LEDs on the chassis and components of the chassis. If any LED does not illuminate and blink, the LED may not be functioning correctly.
This button also turns off all external alarm relay control bits until the next new alarm condition.
Exceptions:
The LT has no affect on:
• the back-lit product name, which is always on when a PSU is installed and running
• Pwr/Stat LED on the CPM
Timing output with subminiature version B (SMB) connector. The 1PPS port is reserved for future use.
The CF card slot accepts Type I and Type II CF cards. It can be used to store accounting records, logs, and TiMOS images. It can also be used to boot the system. Refer to the 7750 SR-a Release Notes for detailed information about the supported Compact Flash storage devices supported on the 7750 SR-a.
7750 SR-a4 and SR-a8 Installation Guide 145
7750 SR-a Module LEDs and Connectors
IOM-a LEDs
shows the IOM-a, which is used in the 7750 SR-a4 and 7750 SR-a8.
describes the parts and LEDs.
Figure 48: IOM-a LEDs
1 1
Pwr
S tat
2 3 3
24570
Key Label/Part
1
Subcategory
—
Table 59: 7750 SR-a IOM LED Descriptions
Description
Secures the IOM-a in place.
2
Captive screws
Pwr / Stat
3 Ejector levers
Power
LED
Status
LED
—
Blue (solid) : Power to the IOM-a is on.
Unlit : There is no power to the IOM-a or the power is faulty.
Green (slow blink) : The IOM-a is loading firmware and running CPU diagnostics.
Green (solid) : The IOM-a boot/load process is complete and the IOM-a is operational.
Unlit : The IOM-a is operationally down and administratively down.
One on each side of the IOM-a. The levers are used to remove or install the
IOM-a.
146 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card
Descriptions
In This Chapter
This chapter describes the MDA-a and MDA-aXP cards that are supported on the 7750 SR-a4 and 7750 SR-a8 chassis. Topics in this chapter include:
•
1-port 100GigE CFP MDA-aXP Overview on page 148
•
2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Overview on page 151
•
4-port 10GigE SFP+ MDA-a Overview on page 154
•
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP on page 157
•
10-port 10GigE SFP+ MDA-aXP Overview on page 160
•
20-port 10/100/1000 TX RJ-45 MDA-a Overview on page 163
•
44-port 1GigE CSFP/SFP MDA-a Overview on page 166
7750 SR-a4 and SR-a8 Installation Guide 147
1-port 100GigE CFP MDA-aXP Overview
1-port 100GigE CFP MDA-aXP Overview
The 1-port 100GigE CFP MDA-aXP supports one 100 Gigabit Ethernet CFP port for a maximum rate of 100 Gb/s. The card can operate in the 100 Gigabit Ethernet slot at or near the line rate.
shows the 1-port 100GigE CFP MDA-aXP.
describes the features.
Figure 49: 1-port 100GigE CFP MDA-aXP
1 5 1
Pwr
S tat
2 3
Lnk Act
4 6
24571
3
4
5
6
Key
1
2
Table 60: 1-port 100GigE CFP MDA-aXP Features
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -aXP suffix : The card can operate in a 100 Gigabit Ethernet slot at or near the line rate.
Pwr / Stat Power and Status LED. See
1-port 100GigE CFP MDA-aXP LEDs
.
Lnk/Act
Port
MDA-a model
1-100GB-CFP
1-port 100GigE CFP MDA-aXP LEDs
One 100 Gigabit Ethernet CFP+ port, numbered 1
Technical Specifications
Table 61: 1-port 100GigE CFP MDA-a Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
148 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
Table 61: 1-port 100GigE CFP MDA-a Specifications (Continued)
Parameter
Weight
Description
2.76 lb (1.25 kg)
Power Consumption
Table 62 lists the power consumption values for the 1-port 100GigE CFP MDA-a.
Table 62: 1-port 100GigE CFP MDA-a Power Consumption Values in Watts
Zero Traffic
Typical
Maximum Power
0 52 56 75
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at high temperature
(65ºC)
1-port 100GigE CFP MDA-aXP LEDs
shows the 1-port 100GigE CFP MDA-aXP.
describes the LEDs.
Table 63: 1-port 100GigE CFP MDA-aXP LEDs
Label
Pwr / Stat Power and Status
LED
Green (slow blink) : The MDA-a is loading the firmware and running diagnostics.
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA-a is operationally down and administratively down.
7750 SR-a4 and SR-a8 Installation Guide 149
1-port 100GigE CFP MDA-aXP Overview
Label
Lnk/Act
Table 63: 1-port 100GigE CFP MDA-aXP LEDs (Continued)
Link and Activity
LED
Green (solid) : Valid communications link established
Green (blink) : Port active and receiving or transmitting data
Amber (fast blink) : Loopback
Amber (slow blink) : Administratively up, but no optic module installed
Amber (solid) : Optics installed, but no link present or LOS
Unlit : Laser disabled or port shut down
150 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
2-port 10GigE SFP+ and 12-port 1GigE SFP Combo
MDA-a Overview
Figure 50 shows the 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a. Table 64
describes the features.
Figure 50: 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Features
1 5 7 1
Pwr
S tat
Lnk/Act 1 2 3 4 5 6 7 8 9 10 11 12
2 3 4 6
1 3 14
Lnk Act Lnk Act
8
24460
7
8
5
6
3
4
Key
1
2
Table 64: 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Features
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -a suffix : The card can operate in any MDA-a slot at or near the line rate. See
Port Line Rate on page 152 for more information.
Pwr / Stat
Port number and row indicators
Power and Status LED
A triangle above each port number indicates the position of the port. Upward pointing triangles represent ports in the top row. Downward pointing triangles represent ports in the bottom row.
The Gigabit Ethernet SFP ports are numbered as follows:
• Top row—ports 1, 3, 5, 7, 9, 11
• Bottom row—ports 2, 4, 6, 8, 10, 12
Ports
Lnk/Act
Ports
MDA-a model
Twelve 1Gigabit Ethernet SFP ports, numbered 1 to 12
Link and Activity LED
Two 10 Gigabit Ethernet SFP+ ports, numbered 13 and 14
2-10GB-SFP+ 12-1GB-SFP
7750 SR-a4 and SR-a8 Installation Guide 151
2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Overview
Port Line Rate
The 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a car is an oversubscribed 25
Gb/s MDA-a. The card’s connection to the IOM is only 25 Gb/s.
If you install both 10GE ports and more that five 1GE ports, the card will be oversubscribed.
If all twelve 1 GE ports and one 10GE port are installed, only 22 Gb/s are used. In this scenario, the other 10GE port could be used as a standby link, and the card would not be oversubscribed.
The card is limited to 25 Gb/s, installing the card in a 100 Gb/s slot does not increase the throughput.
Technical Specifications
Table 65: 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
Weight 2.03 lb (0.92 kg)
Power Consumption
Table 66 lists the power consumption values for the 2-port 10GigE SFP+ and 12-port 1GigE
SFP Combo MDA-a.
0
Table 66: 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a Power
Consumption Values in Watts
Zero Traffic
38
Typical
41
Maximum Power
42
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
152 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at a high temperature
(65ºC)
2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a
LEDs
shows the 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a. Table 67
describes the LEDs.
Label/Part
Pwr / Stat
Lnk/Act
Table 67: 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a LEDs
Description
(Power and
Status LED)
Link and Activity
LED
LED Display
Green (slow blink) : The MDA-a is loading the firmware and running diagnostics.
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA-a is operationally down and administratively down.
Green (solid) : Valid communications link established
Green (blink) : Port active and receiving or transmitting data
Amber (fast blink) : Loopback
Amber (slow blink) : Administratively up, but no optic module installed
Amber (solid) : Optics installed, but no link present or LOS
Unlit : Laser disabled or port shut down
7750 SR-a4 and SR-a8 Installation Guide 153
4-port 10GigE SFP+ MDA-a Overview
4-port 10GigE SFP+ MDA-a Overview
Figure 51 shows the 4-port 10GigE SFP+ MDA-a. Table 68
describes the features.
Figure 51: 4-port 10GigE SFP+ MDA-a Features
1 4 1
Pwr
S tat
2 3
1 2 3 4
Lnk Act Lnk Act Lnk Act Lnk Act
5
2457 3
3
4
5
Key
1
2
Table 68: 4-port 10GigE SFP+ MDA-a Features
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -a suffix : The card can operate in any MDA-a slot at or near the line rate. See
Port Line Rate on page 154 for more information.
Pwr / Stat Power and Status LED. See
.
Ports
MDA-a model
Four 10 Gigabit Ethernet SFP+ ports, numbered 1 to 4.
4-10GB-SFP+
Port Line Rate
The 4-port 10GigE SFP+ MDA-a card is an oversubscribed 25 Gb/s MDA-a. The card’s connection to the IOM is only 25 Gb/s. The card supports 10 Gb/s line rate out of each port only if 2 or fewer ports are in use.
If more than 2 ports are in use, the per-port maximum simultaneous line rate diminishes as a ratio of 25 Gb/s divided by the number of ports in use. For example, if all 4 ports are installed and are run at full speed, the line rate is approximately 25 Gb/s divided by 4 ports, which is
6.25 Gb/s per port.
154 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
The card is limited to 25 Gb/s; installing the card in a 100 Gb/s slot does not increase the throughput.
Technical Specifications
Table 69: 4-port 10GigE SFP+ MDA-a Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
Weight 1.90 lb (0.86 kg)
Power Consumption
Table 70 lists the power consumption values for the 4-port 10GigE SFP+ MDA-a.
Table 70: 4-port 10GigE SFP+ MDA-a Power Consumption Values in Watts
0
Zero Traffic
32
Typical
Maximum Power
32 35
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at a high temperature
(65ºC)
4-port 10GigE SFP+ MDA-a LEDs
shows the 4-port 10GigE SFP+ MDA-a. Table 71
describes the LEDs.
7750 SR-a4 and SR-a8 Installation Guide 155
4-port 10GigE SFP+ MDA-a Overview
Label/Part
Pwr / Stat
Lnk/Act
Table 71: 4-port 10GigE SFP+ MDA-a LEDs
Power and Status
LED
Link and Activity
LED
Green (slow blink) : The MDA-a is loading the firmware and running diagnostics.
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA is operationally down and administratively down.
Green (solid) : Valid communications link established
Green (blink) : Port active and receiving or transmitting data
Amber (fast blink) : Loopback
Amber (slow blink) : Administratively up, but no optic module installed
Amber (solid) : Optics installed, but no link present or LOS
Unlit : Laser disabled or port shut down
156 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+
Combo MDA-aXP
shows the 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP.
Table 72 describes the connectors and LEDs.
Figure 52: 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP Features
1 4 1
1 2 3 4 5 6
Pwr
S tat
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
2 3 5
7
Lnk Act
6 7
24576
5
6
3
4
7
Key
1
2
Table 72: 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP Features
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -aXP suffix : The card can operate in the 100 Gigabit Ethernet slot at or near the line rate.
Pwr / Stat
Ports
Lnk/Act
Port
MDA-a-a model
Power and Status LED
Six 10 Gigabit Ethernet SFP+ ports, numbered 1 to 6
Link and Activity LED
One 40 Gigabit Ethernet QSFP+ port, numbered port 7
6-10GB-SFP+ 1 40GE-QSFP+
7750 SR-a4 and SR-a8 Installation Guide 157
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP
Technical Specifications
Table 73: 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP
Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
Weight 2.11 lb (0.96 kg)
Power Consumption
Table 74 lists the power consumption values for the 6-Port 10GigE SFP+ and 1-Port 40GigE
QSFP+ Combo MDA-aXP.
0
Table 74: 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP Power
Consumption Values in Watts
Zero Traffic
40
Typical
52
Maximum Power
72
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at a high temperature
(65ºC)
6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo
MDA-aXP LEDs
shows the 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP.
158 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
Label/Part
Pwr / Stat
Lnk/Act
Table 75: 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP LEDs
Power and Status
LED
Link and Activity
LED
Green (slow blink) diagnostics.
: The MDA-a is loading the firmware and running
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA-a is operationally down and administratively down.
Green (solid) : Valid communications link established
Green (blink) : Port active and receiving or transmitting data
Amber (fast blink) : Loopback
Amber (slow blink) : Administratively up, but no optic module installed
Amber (solid) : Optics installed, but no link present or LOS
Unlit : Laser disabled or port shut down
7750 SR-a4 and SR-a8 Installation Guide 159
10-port 10GigE SFP+ MDA-aXP Overview
10-port 10GigE SFP+ MDA-aXP Overview
Figure 53 shows the 10-port 10GigE SFP+ MDA-aXP. Table 76
describes the features.
Figure 53: 10-port 10GigE SFP+ MDA-aXP Features
1 4 1
1 2 3 4 5 6 7 8 9 10
Pwr
Stat
Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act Lnk Act
2 3 5 6
24572
3
4
5
6
Key
1
2
Table 76: 10-port 10GigE SFP+ MDA-aXP Features
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -aXP suffix : The card can operate in a 100 Gigabit Ethernet slot at or near the line rate.
Pwr / Stat Power and Status LED
Port
Lnk/Act
MDA-a model
Ten 10 Gigabit Ethernet SFP+ ports, numbered 1 to 10.
Link and Activity LED
10-10GB-SFP+
Technical Specifications
Table 77: 10-port 10GigE SFP+ MDA-aXP Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
Weight 2.13 lb (0.96 kg)
160 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
Power Consumption
Table 78 lists the power consumption values for the 10-port 10GigE SFP+ MDA-aXP.
0
Table 78: 10-port 10GigE SFP+ MDA-aXP Power Consumption Values in Watts
Zero Traffic
40
Typical
48
Maximum Power
55
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at a high temperature
(65ºC)
10-port 10GigE SFP+ MDA-aXP LEDs
shows the 10-port 10GigE SFP+ MDA-aXP. Table 79
describes the LEDs.
Label
Pwr / Stat
Table 79: 10-port 10GigE SFP+ MDA-aXP LEDs
Description
Power and Status
LED
LED Display
Green (slow blink) : The MDA-a is loading the firmware and running diagnostics.
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA-a is operationally down and administratively down.
7750 SR-a4 and SR-a8 Installation Guide 161
10-port 10GigE SFP+ MDA-aXP Overview
Label
Lnk/Act
Table 79: 10-port 10GigE SFP+ MDA-aXP LEDs (Continued)
Description
Link and Activity
LED
LED Display
Green (solid) : Valid communications link established
Green (blink) : Port active and receiving or transmitting data
Amber (fast blink) : Loopback
Amber (slow blink) : Administratively up, but no optic module installed
Amber (solid) : Optics installed, but no link present or LOS
Unlit : Laser disabled or port shut down
162 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
20-port 10/100/1000 TX RJ-45 MDA-a Overview
shows the 20-port 10/100/1000 TX RJ-45 MDA-a
Table 80 describes the features.
Figure 54: 20-port 10/100/1000 TX RJ-45 MDA-a Features
1 1 5 7
Lnk
1 2
Act Lnk
3 4
Act Lnk
5 6
Act Lnk
7 8
Act Lnk
9 10
Act Lnk
11 12
Act Lnk
13 14
Act Lnk
15 16
Act Lnk
17 18
Act Lnk
19 20
Act
Pwr
Stat
2 3 4 6 8
24575
6
7
8
3
4
5
Key
1
2
Table 80: 20-port 10/100/1000 TX RJ-45 MDA-a Features
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -a suffix : The card can operate in any MDA-a slot at or near the line rate.
Pwr / Stat
Ports
Port number and row indicators
Ports
Lnk/Act
MDA-a model
Power and Status LED
Twelve 1 Gigabit Ethernet RJ-45 ports, numbered 1 to 12
A triangle above each port number indicates the position of the port. Upward pointing triangles represent ports in the top row. Downward pointing triangles represent ports in the bottom row.
Ports are numbered as follows:
• Top row—ports 1, 3, 5, 7, 9, 11, 13, 15, 17, 19
• Bottom row—ports 2, 4, 6, 8, 10, 12, 14, 16, 18, 20
Eight 1 Gigabit Ethernet RJ-45 ports, numbered 13 to 20
Link and Activity LEDs
20-1GB-TX
7750 SR-a4 and SR-a8 Installation Guide 163
20-port 10/100/1000 TX RJ-45 MDA-a Overview
Technical Specifications
Table 81: 20-port 10/100/1000 TX RJ-45 MDA-a Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
Weight 2.46 lb (1.12 kg)
Power Consumption
Table 82 lists the power consumption values for the 20-port 10/100/1000 TX RJ-45 MDA-a.
Table 82: 20-port 10/100/1000 TX RJ-45 MDA-a Power Consumption Values in Watts
0
Zero Traffic
28
Typical
30
Maximum Power
35
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at a high temperature
(65ºC)
20-port 10/100/1000 TX RJ-45 MDA-a LEDs
shows the 20-port 10/100/1000 TX RJ-45 MDA-a.
describes the LEDs.
164 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
Label
Pwr / Stat
Lnk/Act Activity LED
(right side)
Link LED
(left side)
Table 83: 20-port 10/100/1000 TX RJ-45 MDA-a LEDs
Description
Power and
Status LED
LED Display
Green (slow blink) : The MDA-a is loading the firmware and running diagnostics.
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA-a is operationally down and administratively down.
Green (solid) : No errored packets have been detected since the last poll.
Amber (blink) : Errored packets have been detected since the last poll.
Unlit : The port is down, or the port is operational but not carrying traffic.
Green (solid) : Valid communications link established. Port speed is running at 1000BASE-T.
Green (fast blink) : Valid communications link established. Port speed is running at 100BASE-T.
Green (slow blink) : Valid communications link established. Port speed is running at 10BASE-T.
Amber (fast blink) : Port loopback
Amber (solid) : The link is down or signal is lost.
Unlit : The port is shut down.
7750 SR-a4 and SR-a8 Installation Guide 165
44-port 1GigE CSFP/SFP MDA-a Overview
44-port 1GigE CSFP/SFP MDA-a Overview
shows the 44-port 1GigE CSFP/SFP MDA-a.
Table 84 describes the features.
The 44-port 1GigE CSFP/SFP MDA-a card has 22 CSFP slots. CSFP slots have the same form factor as slots used by SFPs, which enables the card to support dual-port CSFPs and
Single-port SFPs, copper SFPs, and bidirectional SFPs.
Figure 55: 44-port 1GigE CSFP/SFP MDA-a Features
1 5 7 8 1
Pwr
S tat
Lnk/Act
1 2 3 4 5 6 7 8 9 10 11 12 1 3 14 15 16 17 1 8 19 20 21 22 2 3 24 25 26 27 2 8 29 3 0 3 1 3 2 33 3 4 3 5 3 6 3 7 38 3 9 40 41 42 4 3 44
2 3 4 6 9
24574
3
4
5
Key
1
2
6
Table 84: 44-port 1GigE CSFP/SFP MDA-a Description
Label/Part
Captive screws
Description
Secures the MDA-a in place.
7750 MDA-a type -a suffix : The card can operate in any MDA-a slot at or near the line rate. See
.
Pwr / Stat Power and Status LED
Lnk/Act
Ports
Port number and row indicators
Link and Activity LED
24 1 Gigabit Ethernet SFP ports, numbered 1 to 24.
The ports are aligned in two rows as follows:
• Top row—ports 1-2, 5-6, 9-10, 13-14, 17-18, 21-22
• Bottom row—ports 3-4, 7-8, 11-12, 15-16, 19-20, 23-24
A triangle above each port number indicates the position of the port. Upward pointing triangles represent ports in the top row. Downward pointing triangles represent ports in the bottom row.
166 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
Key
7
8
9
Label/Part
Ports
Ports
Table 84: 44-port 1GigE CSFP/SFP MDA-a Description (Continued)
MDA-a model
Description
Sixteen 1 Gigabit Ethernet SFP ports, numbered 25 to 40
The ports are aligned in two rows as follows:
• Top row—ports 25-26, 29-30, 33-34, 37-38
• Bottom row—ports 27-28, 31-32, 35-36, 39-40
Four 1 Gigabit Ethernet SFP ports, numbered 41 to 44
The ports are aligned in two rows as follows:
• Top row—ports 41-42
• Bottom row—ports 43-44
44-1GB-CSFP-SFP
Port Allocation
The type of modules that you install affects the numbering of the allocated ports.
One dual-port-CSFP occupies one slot and two ports. If all 22 slots have dual-port CSFPs installed, 44-ports are allocated. The card requires 22 CSFPs for full 44-port operation.
One single-port SFP occupies one slot and one port. Single-port SFPs use one odd-numbered port when plugged into a CSPF slot. If all 22 slots have single-port SFPs installed, 22 ports are allocated as 1, 3, 5...41, 43.
The card also supports a mixed configuration of CFSPs and SFPs. If you install a mix of single-port and dual-port (CSFP) modules, the allocated port numbers will be non-consecutive. For example, if the first and fourth modules are dual-port CSPFs and the second and third modules are SFPs, the following ports are used 1, 2, 3, 5, 7, 8.
Port Line Rate
The 1GigE CSFP/SFP MDA-a card is an oversubscribed 25 Gb/s MDA-a. The card’s connection to the IOM is only 25 Gb/s. The card supports 1 Gb/s line rate out of each port only if 25 or fewer ports are in use.
7750 SR-a4 and SR-a8 Installation Guide 167
44-port 1GigE CSFP/SFP MDA-a Overview
If more than 25 ports are in use, the per-port maximum simultaneous line rates diminishes as a ratio of 25 Gb/s divided by the number of ports in use. For example, if all 44 ports are installed and are run at full speed, the line rate is approximately 25 Gb/s divided by 44 ports, which is 560 Mb/s per port.
The card is limited to 25 Gb/s; installing the card in a 100 Gb/s slot does not increase the throughput.
Technical Specifications
Table 85: 44-port 1GigE CSFP/SFP MDA-a Specifications
Parameter Description
Dimensions (H x W x D) 1.4 x 7.6 x 9.0 in. (3.56 x 19.30 x 22.86 cm)
Weight 2.45 lb (1.11 kg)
Power Consumption
Table 86 lists the power consumption values for the 44-port 1GigE CSFP/SFP MDA-a.
0
Table 86: 44-port 1GigE CSFP/SFP MDA-a Power Consumption Values in Watts
Zero Traffic
45
Typical
48
Maximum Power
52
Note:
1.
Idle: Slots not configured or provisioned
2.
Zero Traffic: Traffic load: 0% line rate at 25ºC (reset case)
3.
Typical: Traffic load: 50% line rate with Internet mix (IMIX) at 25ºC
4.
Worst Case: Traffic Load: 100% line rate with IMIX at the maximum short duration and at a high temperature
(65ºC)
44-port 1GigE CSFP/SFP MDA-a LEDs
shows the 44-port 1GigE CSFP/SFP MDA-a.
168 7750 SR-a4 and SR-a8 Installation Guide
Appendix B: MDA-a and MDA-aXP Card Descriptions
Label/Part
Pwr / Stat
Lnk/Act
Table 87: 44-port 1GigE CSFP/SFP MDA-a LEDs
Power and
Status LED
Link and
Activity LED
Green (slow blink) : The MDA-a is loading the firmware and running diagnostics.
Green (solid) : The MDA-a has successfully completed loading the firmware and running diagnostics, and is operationally up and administratively up.
Amber (solid) : The MDA-a is operationally down but administratively up.
Unlit : The MDA-a is operationally down and administratively down.
Green (solid) : Valid communications link established
Green (blink) : Port active and receiving or transmitting data
Amber (fast blink) : Loopback
Amber (slow blink) : Administratively up, but no optic module installed
Amber (solid) : Optics installed, but no link present or LOS
Unlit : Laser disabled or port shut down
7750 SR-a4 and SR-a8 Installation Guide 169
44-port 1GigE CSFP/SFP MDA-a Overview
170 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
In This Chapter
This chapter describes how to remove and replace field-replaceable units (FRUs) in the
7750 SR-a4 and 7750 SR-a8 chassis. Topics in this chapter include:
•
Removing and Replacing a PSU on page 172
•
Removing and Replacing a Fan Tray on page 185
•
Removing and Replacing an Air Filter on page 189
•
Removing and Replacing a CPM-a on page 192
•
Removing and Replacing an IOM-a on page 198
•
Removing and Replacing an MDA-a or MDA-aXP Card on page 204
•
Removing and Replacing an Impedance Panel on page 209
Note:
• Alcatel-Lucent recommends that you read the following sections in the Overview chapter for detailed information and specific requirements that apply to the 7750 SR-a component being replaced:
→
→
→
→
→
7750 SR-a4 and SR-a8 Installation Guide 171
Removing and Replacing a PSU
Removing and Replacing a PSU
This section includes information about:
•
Warnings and Notes on page 172
•
Removing an AC PSU on page 173
•
Replacing an AC PSU on page 175
•
Removing a –48 VDC PSU on page 178
•
Replacing a –48 VDC PSU on page 181
Warnings and Notes
Danger:
• Make the ground connections first.
• Only trained and qualified personnel should install or replace this equipment and connect the power cables.
• External power must be disconnected at the power source. Disconnect and unplug the power cables before you remove and replace a PSU module.
• You must use power cables that meet local electrical code requirements.
Warning:
• Do not install equipment that appears to be damaged.
• Impedance panels are required in all empty slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference. Impedance panels do not have board components or connector pins.
• Electrostatic discharge (ESD) damage can occur if components are mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
172 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Note:
• The 7750 SR-a4 chassis requires a minimum of one PSU to operate, but two are recommended for redundancy. The 7750 SR-a8 chassis requires a minimum of two
PSUs to operate, but four are recommended for redundancy.
• For full redundancy, each PSU module should be attached to an independent power source with a dedicated circuit breaker. A fully redundant system must be connected to both DC PSU modules, or both AC PSU modules, or one DC and one AC PSU module.
• In the event of a PSU module failure, the entire module must be replaced. There are no field-serviceable parts inside the PSUs.
7750 SR-a AC PSU
If you are operating your 7750 SR-a with redundant PSU modules, you can install, remove, or replace a PSU module without affecting system operation.
Danger: Unplug the power cable from the remote power source during the PSU module removal and replacement procedures.
Note: Refer to
7750 SR-a –48 VDC PSU LED and Connectors on page 139
for a description of the PSU.
Removing an AC PSU
Figure 56 and Figure 57 show how to remove an AC PSU from the 7750 SR-a chassis.
Table 88 describes the features.
7750 SR-a4 and SR-a8 Installation Guide 173
Removing and Replacing a PSU
Figure 56: Removing an AC PSU (7750 SR-a4)
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
2
4 1 3
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Figure 57: Removing an AC PSU (7750 SR-a8)
24579
174
7750
S R-a4 Fan Tray
Pwr
S tat
Pwr
Stat
Pwr
Stat
1
Lnk
Act
2
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk
Act
Lnk Act
1
2
Lnk Act
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
8
9
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
Lnk Act
Pwr
Stat
Lnk
Pwr
Stat
1
2
3
Lnk Act
Lnk Act
Lnk Act
4
Lnk
Act
S lot Layout
1/1 XP
1/3
1/2
1/4
1
2/1 XP
2/3
2/2 XP
2/4
CPM A
2
CPM B
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2
3
4
5
6 7
8
9
10
11
12 Lnk
13
Act
Lnk
14
Act
Pwr
Stat
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
7750 SR-a8
S ervice Router
Pwr
Stat
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
Stat
1
2
Lnk
Act
Lnk Act
3
4
Lnk Act
Lnk Act
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
4 1 3
245 8 0
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
3
4
Key
1
2
Table 88: AC PSU Removal Features
Description
LED
Handle
Spring-loaded latch lock
Direction of movement
To remove an AC PSU module:
Step 1.
Disconnect power from the external branch circuit.
Step 2.
Disengage the power cord retainer by lifting the retainer away from the power cord.
Step 3.
Remove the AC power cord from the inlet on the front of the PSU.
Step 4.
Ensure that the LED is unlit (Key 1 in Figure 56 and Figure 57 ).
Step 5.
Press and hold the latch lock to the left to unlock the PSU (Key 3 in
and
Step 6.
Grip and hold the handle on the PSU with your hand (Key 2 in
and
Step 7.
Pull the PSU module out of the slot (Key 4 in
).
Step 8.
Do one of the following: a. If you are installing a replacement PSU module, go to
Replacing an AC PSU on page 175 .
b. If you are not installing a replacement PSU module, insert an impedance panel in the empty slot.
Replacing an AC PSU
The following procedure assumes that you have removed the AC PSU, as described in
.
and
show how to replace an AC PSU in the 7750 SR-a chassis. Table 89
describes the features.
7750 SR-a4 and SR-a8 Installation Guide 175
Removing and Replacing a PSU
176
Figure 58: Replacing an AC PSU (7750 SR-a4)
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat
7750 SR-a4
S ervice Router
2
4 3
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
Lnk Act
8
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
1
Figure 59: Replacing an AC PSU (7750 SR-a8)
24553
7750
S R-a4 Fan Tray
Pwr
S tat
Pwr
Stat
Pwr
Stat
1
Lnk
1
Act
2
2
Lnk Act
Lnk Act
3
Lnk Act
Lnk Act
4
5
Lnk Act
Lnk Act
6
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
8
9
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
Lnk Act
Pwr
Stat
Lnk
Pwr
Stat
1
2
3
4
Lnk Act
Lnk Act
Lnk Act
Lnk Act
S lot Layout
1/1 XP
1/2
1/3
1/4
1
2/1 XP
2/2 XP
2/3
2/4
2
CPM A
CPM B
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2 3
13
14
4 5
6
7
8
9
10 11
12
Lnk
Act
Lnk
Act
Pwr
Stat
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat 7750 SR-a8
S ervice Router
Pwr
Stat
Lnk
1 2
Act
Lnk
3 4
Act
Lnk
5
6
Act Lnk
7 8
Act
Lnk
9 10
Act
Lnk
11
12
Act
Lnk
13 14 Act Lnk
15 16
Act
Lnk
17
18
Act Lnk
19
20
Act
Pwr
Stat
1
2
Lnk Act
Lnk Act
3
4
Lnk Act
Lnk Act
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
1
4 3
24590
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
3
4
Key
1
2
Table 89: AC PSU Replacement Features
Description
Chassis guide
PSU handle
Spring-loaded latch lock
Direction of movement
To replace an AC PSU module:
Step 1.
Align the PSU module with the chassis guides in power slot (Key 1 in Figure 58 and Figure 59 ).
Step 2.
Grip and hold the handle (Key 2 in
) on the PSU with your hand.
Step 3.
Slide the unit into the slot. Firmly press the PSU module all the way into the slot
(Key 4 in
Figure 58 and Figure 59 ). The latch clicks into place to secure the PSU
when the unit is fully inserted.
Step 4.
Locate the AC power cord. Verify that the AC power cord meets your regional requirements. Do not use power cords that do not meet these standards.
Step 5.
Reconnect the AC power cord into the inlet on the PSU module.
Step 6.
Lower the cord retainer until it fully secures the cord.
Step 7.
Reconnect the other end of the power cord to the AC power source receptacle.
Step 8.
After the replacement PSU module is installed and energized, check the LED status on the front of the AC PSU.
7750 SR-a –48 VDC PSU
If you are operating the 7750 SR-a with redundant PSU modules, you can install, remove, or replace a PSU module without affecting system operation.
7750 SR-a4 and SR-a8 Installation Guide 177
Removing and Replacing a PSU
Danger:
• Ensure that all power from the DC circuit is OFF. Locate the circuit breaker on the panel board that serves the DC circuit. Switch the circuit breaker to the OFF position. For extra safety, lock out the circuit breaker by taping the handle of the circuit breaker in the OFF position.
• When wiring the unit, the ground connection must always be made first and disconnected last.
• The correct wiring sequence is ground/negative to ground/negative and positive/return to positive/return.
Note:
Refer to 7750 SR-a –48 VDC PSU LED and Connectors on page 139
for a description of the PSU.
Removing a –48 VDC PSU
and
Figure 61 show how to remove a –48 VDC PSU from the 7750 SR-a chassis.
Table 90 describes the features.
Figure 60: Removing a –48 VDC PSU (7750 SR-a4)
2
4
7750
S R-a4 Fan Tray
Pwr
Stat
Pwr
Stat
Lnk
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
Pwr
Stat
3
1
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
Lnk Act
8
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
245 8 2
178 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Figure 61: Removing a –48 VDC PSU (7750 SR-a8)
4
2
7750
S R-a4 Fan Tray
Pwr
S tat
Pwr
Stat
Pwr
Stat
1
Lnk Act
1
Lnk Act
2
Lnk Act
2
Lnk Act
3
Lnk Act
4
5
6
Lnk Act
Lnk Act
Lnk Act
7
8
9
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
Lnk Act
Pwr
Stat
Lnk
Pwr
Stat
1
2
3
4
Lnk Act
Lnk Act
Lnk Act
Lnk Act
S lot Layout
1/1 XP
1/3
1/2
1/4
1
2/1 XP
2/3
2/2 XP
2/4
CPM A
2
CPM B
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2 3
4
5
6 7
13
14
8 9
10
11
12 Lnk
Act
Lnk Act
Pwr
Stat
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a8
S ervice Router
Pwr
Stat
Pwr
Stat
Lnk
1 2
Act
Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
Stat
1
2
3
4
Lnk Act
Lnk Act
Lnk Act
Lnk Act
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
3
1
245 8 3
2
3
Key
1
4
Table 90: –48 VDC PSU Removal Features
Description
LED
PSU handle
Spring-loaded latch lock
Direction of movement
To remove a –48 VDC PSU module:
Step 1.
Ensure external power has been disconnected or turned off at the branch circuit device. The status LED on the faceplate (Key 1 in
) of the
–48 VDC PSU module must be unlit.
See 7750 SR-a –48 VDC PSU LED and Connectors for more information.
Step 2.
Remove the protective cover from the terminal block (Key 4 in
7750 SR-a4 and SR-a8 Installation Guide 179
Removing and Replacing a PSU
Figure 62: –48 VDC Ground and Power Connectors
1
Pwr
S tat
4
+ -
2 3
24556
2
3
Key
1
4
Table 91: –48 VDC Ground and Power Connection Descriptions
Description
DC power grounding terminal with M4 screw
Positive (+) terminal with M4 screw
Negative (–) terminal with M4 screw
Clear plastic sliding safety cover for the terminal block. The cover rests on three raised guides to provide clearance for the cable connectors. When removing the DC PSU, remove the cover to access the terminal screws.
Step 3.
Remove the screws holding the terminal lugs in place and remove the power cables
Step 4.
Remove the screw holding the terminal lug to the grounding point and remove the
ground cable (Key 1 in Figure 62 ).
Step 5.
Press and hold the latch lock (Key 3 in Figure 60 or
) to the left to unlock the PSU.
Step 6.
Grip and hold the handle (Key 2 in
or Figure 61 ) on the PSU with your
hand.
Step 7.
Pull the PSU module out of the slot (Key 4 in
Step 8.
Do one of the following: a. If you are installing a replacement PSU module, go to
Replacing an AC PSU on page 175 .
b. If you are not installing a replacement PSU module, insert an impedance panel in the empty slot.
180 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Replacing a –48 VDC PSU
The following steps assume that you have removed the DC PSU from the slot, as described
and Figure 64 show how to replace a –48 VDC PSU in the 7750 SR-a chassis.
Table 92 describes the features.
Figure 63: Replacing a –48 VDC PSU (7750 SR-a4)
2
4
7750
S R-a4 Fan Tray
Pwr
Stat
Pwr
Stat
Lnk
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk
Act
Lnk
Act
8
9
Lnk
Act
Lnk
Act
Lnk
Act
Lnk Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
3
1
24555
7750 SR-a4 and SR-a8 Installation Guide 181
Removing and Replacing a PSU
Figure 64: Replacing a –48 VDC PSU (7750 SR-a8)
182
4
2
7750
S R-a4 Fan Tray
Pwr
S tat
Pwr
Stat
1
2
Lnk Act
Lnk Act
3
4
5
6
Lnk Act
Lnk Act
Lnk Act
Lnk Act
7
8
9
10
Lnk
Act
Lnk Act
Lnk Act
Lnk Act
Pwr
Stat
1
2
3
4
5
Lnk
Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
6
Lnk Act
7
Lnk Act
Pwr
Stat
Lnk
Pwr
Stat
1
Lnk
Act
2
3
4
Lnk Act
Lnk Act
Lnk Act
S lot Layout
1/1 XP
1/3
1/2
1/4
1
2/1 XP
2/3
2/2 XP
2/4
CPM A
2
CPM B
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
Lnk/Act
1
2 3
4
5
6 7
13
14
8 9
10
11
12 Lnk
Act
Lnk Act
Pwr
Stat
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a8
S ervice Router
Pwr
Stat
Pwr
Stat
Lnk
1 2
Act
Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
Stat
1
2
Lnk Act
Lnk Act
3
4
Lnk Act
Lnk Act
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
3
1
245 8 4
2
3
Key
1
4
Table 92: –48 VDC PSU Replacement Features
Description
Chassis guide
PSU handle
Spring-loaded latch lock
Direction of movement
To replace a –48 VDC PSU module:
Step 1.
Ensure external power has been disconnected or turned off at the branch circuit device.
See 7750 SR-a –48 VDC PSU LED and Connectors for more information.
Step 2.
Align the PSU module with the chassis guides in power slot (Key 1 in Figure 63 ).
Step 3.
Grip and hold the handle (Key 2 in
) on the PSU with your hand.
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Step 4.
Slide the unit into the slot. Firmly press the PSU module all the way into the slot.
The latch (Key 3) clicks into place to secure the PSU when the unit is fully inserted.
Step 5.
Attach the ground wire to the DC PSU ground if required by the local electrical
code. Do not over-tighten. Torque to 8-10 lbf-in (Key 1 in Figure 65 ).
Figure 65: –48 VDC Ground and Power Connection
1
Pwr
S tat
4
+ -
2 3
24556
3
4
Key
1
2
Table 93: –48 VDC Ground and Power Connection Descriptions
Description
DC power grounding terminal with M4 screw
Positive (+) terminal with M4 screw
Negative (–) terminal with M4 screw
Clear plastic sliding safety cover for the terminal block. The cover rests on three raised guides to provide clearance for the cable connectors. During installation, the cover can be removed temporarily to access the terminal screws.
Step 6.
Remove the safety cover from the three raised guides on the terminal block (Key 4
Step 7.
Remove the positive and negative terminal screws.
Step 8.
Make the battery return ground connections.
i.
Attach the wire at the router end to the positive (+) battery return terminal on
the PSU (Key 2 in Figure 65 ).
ii. Tighten the screw with a Phillips torque screwdriver. Do not over-tighten. The recommended torque is 3 lbf-in (0.339 N
.
m).
Step 9.
Make the connections to the disconnect device.
i.
Attach the battery wire at the router end to the negative (–) battery terminal on
the PSU (Key 3 in Figure 65 ).
7750 SR-a4 and SR-a8 Installation Guide 183
Removing and Replacing a PSU ii. Tighten the screw with a Phillips torque screwdriver. Do not over-tighten. The recommended torque is 3 lbf-in (0.339 N .
m).
iii. Replace the safety cover that you removed from the terminal block in
.
Step 10.
Check that the DC supply wiring is correct.
Step 11.
Restore the external power that was disconnected or turned off at the branch circuit device. See
7750 SR-a –48 VDC PSU LED and Connectors for more information.
184 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Removing and Replacing a Fan Tray
The procedures in this section apply to the following fan trays:
• SR-a4 fan tray for the 7750 SR-a4 5-RU chassis
• SR-a8 fan tray for the 7750 SR-a8 7-RU chassis
Where figures in this section only show the fan tray that is used in the 7750 SR-a4 chassis, the figures also apply to the 7750 SR-a8 chassis.
This section includes information about:
•
Warnings and Notes on page 185
•
Removing a Fan Tray on page 186
•
Replacing a Fan Tray on page 187
Warnings and Notes
Danger: Always keep your fingers away from rotating fan blades. Do not put your fingers or any tool in the fan tray if the fans are still spinning. Wait until the fans stop spinning (about
2 s) before completely removing the fan tray from its slot.
Warning:
• The fan tray is hot-swappable. The 7750 SR-a chassis operates safely for up to one minute while you replace the fan tray. If a longer maintenance time is required, power off the system to prevent over-heating.
• In the event of a single fan failure, the remaining fans switch to their highest speeds.
The remaining fans continue to provide adequate cooling for the system, but the fan tray must be replaced as soon as possible. Individual fans are not field replaceable.
Note: When a fan tray is replaced, the fans initially run at full speed. Thereafter, the control system reduces the fan speed based on temperature. During normal operation, fans never turn off completely.
7750 SR-a4 and SR-a8 Installation Guide 185
Removing and Replacing a Fan Tray
Removing a Fan Tray
Figure 66 shows how to remove the fan tray from the 7750 SR-a4 chassis. Table 94
describes the features. The same method applies to the fan tray in the 7750 SR-a8 chassis.
Figure 66: Removing the Fan Tray (7750 SR-a4)
1
1
7750
S R-a4 Fan Tray
Pwr
Stat
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
Pwr
Stat
1
Pwr
Stat
2
3
4
5
6
Lnk Act
Lnk Act
7
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
245 8 5
Key
1
Table 94: Fan Tray Removal Features
Description
Captive screws
Required tools:
• #2 Phillips or flat blade screwdriver
To remove the fan tray:
Step 1.
Unpack the replacement fan tray from the protective packaging. Place the fan tray on an antistatic surface.
Step 2.
To remove the fan tray from the chassis, use a screwdriver to loosen the captive screws on the fan tray faceplate.
Step 3.
Grip the two captive screws (Key 1 in
), and pull the fan tray halfway out of the chassis and allow the fans to stop spinning.
186 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Danger: Do not put your fingers or any tool in the fan tray if the fans are still spinning. Wait until the fans stop spinning (about 2 s) before completely removing the fan tray from its slot.
Step 4.
When the fans stop spinning, pull the fan tray completely out of the slot.
Replacing a Fan Tray
The following procedure assumes that you have removed the fan tray, as described in
Figure 67 shows how to replace the fan tray in the 7750 SR-a4 chassis. Table 95 describes
the features. The same method applies to the fan tray in the 7750 SR-a8 chassis.
Figure 67: Replacing the Fan Tray (7750 SR-a4)
2
1
7750
S R-a4 Fan Tray
Pwr
Stat
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
Pwr
Stat
1
Pwr
Stat
2
3
4
5
6
Lnk Act
Lnk Act
7
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
245 8 6
Required tools:
Key
1
2
Table 95: Fan Tray Replacement Features
Description
Chassis slot guide for fan tray
Captive screws
7750 SR-a4 and SR-a8 Installation Guide 187
Removing and Replacing a Fan Tray
• #2 Phillips or flat blade torque driver
To replace the fan tray:
Step 1.
Align the fan tray with the guides in fan tray slot (Key 1 in Figure 67 ).
Step 2.
Grip the replacement fan tray from the top and bottom of the faceplate and slide the connector end halfway into the slot.
Step 3.
Push on the faceplate of the fan tray until the connectors are fully seated.
Step 4.
With a screwdriver, secure the fan tray into place by tightening the captive screws.
Torque to 4 to 5 lbf-in (0.45 to 0.56 N .
m). Do not over torque.
Step 5.
Verify the LED on the fan tray. The LED is lit green if functioning correctly or amber if there is a fault. If there is no power to the fan tray, the LED is unlit.
188 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Removing and Replacing an Air Filter
The procedures in this section apply to the following air filters:
• SR-a4 air filter for the 7750 SR-a4 5-RU chassis
• SR-a8 air filter for the 7750 SR-a8 7-RU chassis
Where figures in this section only show the air filter that is used in the 7750 SR-a4 chassis, the figures also apply to the 7750 SR-a8 chassis.
This section includes information about:
•
Air Filter Routine Maintenance on page 189
•
Removing the Air Filter on page 189
•
Replacing the Air Filter on page 190
Air Filter Routine Maintenance
The air filter has two parts: a reusable metal carrier, and a replaceable filter. The filter is designed to snap into the carrier, and has a polarity tab. Replacement filter units can be ordered separately from Alcatel-Lucent. Filter replacements are individually bagged, five to a box.
Note: Each replacement filter is packaged in an oversized plastic bag to allow the dirty filter to be placed in the bag for disposal without releasing the dust.
Alcatel-Lucent recommends that you inspect the air filter monthly. If dirt and dust accumulation are found, replace the air filter.
Removing the Air Filter
shows how to remove the air filter from the 7750 SR-a4 chassis.
the features. The same method applies to the air filter in the 7750 SR-a8 chassis.
7750 SR-a4 and SR-a8 Installation Guide 189
Removing and Replacing an Air Filter
Figure 68: Removing the Air Filter Carrier (showing 7750 SR-a4)
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
1
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
1
245 8 7
Key
1
Table 96: Air Filter Removal Features
Description
Grips, used to pull out the metal filter carrier. The metal carrier is held in place in the chassis by magnets.
To remove the air filter:
Step 1.
Grasp the grips on the filter carrier (Key 1 in
).
Step 2.
Gently pull the filter carrier out of the chassis and place it on an antistatic surface.
Step 3.
Remove the filter pad from the filter carrier.
Step 4.
Clean or dispose of the filter, as required. Go to Replacing the Air Filter on page
.
Replacing the Air Filter
The following procedure assumes that you have removed the filter carrier and filter media, as described in
shows how to replace the air filter in the
7750 SR-a4 chassis.
describes the features. The same method applies to the air filter in the 7750 SR-a8 chassis.
190 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Figure 69: Replacing the Air Filter Carrier (showing 7750 SR-a4)
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
2 1
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
2
245 88
Key
1
2
Table 97: Air Filter Replacement Features
Description
Chassis slot guide for air filter
Grips for the metal filter carrier
To replace the air filter:
Step 1.
Unpack the new replacement air filter from the protective packaging, and place it on an antistatic surface.
Step 2.
Install the filter in the filter carrier.
Step 3.
Locate the vertical air filter slot on the right side of the chassis (Key 1 in
).
Step 4.
Orient the air filter carrier so that the label “Air Filter Access” is on top.
Step 5.
Hold the filter carrier by the grips, then slide the carrier into the filter slot until the carrier is fully seated. (Key 2 in
).
7750 SR-a4 and SR-a8 Installation Guide 191
Removing and Replacing a CPM-a
Removing and Replacing a CPM-a
The procedures in this section describe how to remove and replace a CPM-a in a 7750 SR-a4 or 7750 SR-a8 chassis.
This section includes information about:
•
Warnings and Notes on page 192
•
•
•
Replacing the Internal Compact Flash Card on the CPM-a on page 195
Warnings and Notes
Warning:
• Electrostatic discharge (ESD) damage can occur if components are mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
• Impedance panels are required in all empty slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference. Impedance panels do not have board components or connector pins.
Note:
General:
• When replacing CPM-a cards, configuration modifications are not required.
• The 7750 SR-a chassis requires a minimum of one CPM-a to operate, but two are recommended for redundancy.
• CPM-a cards occupy half of a slot:
→ The 7750 SR-a4 supports up to two CPM-a cards in slot 4. CPM-a slots are designated CPM A and CPM B.
→ The 7750 SR-a8 supports up to two CPM-a cards in slot 7. CPM-a slots are designated CPM A and CPM B.
192 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Removing a CPM-a
shows how to remove a CPM-a from the 7750 SR-a4 chassis.
the features. The same method applies to the CPM-a cards in the 7750 SR-a8 chassis.
Figure 70: Removing a CPM-a
R-a4 Fan Tray
7750 SR-a4 ervice Router
2
Pwr
S tat
Pwr
Stat
Pwr
Stat
Pwr
Stat
Lnk
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACOLT
1PPS
Compact Flash
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
2
1
3
24559
2
3
Key
1
Table 98: Removing a CPM-a Features
Description
Slot guide
Captive screws
Threaded receptacle
Required tools:
• #2 Phillips or flat blade screw driver
To remove a CPM-a:
Step 1.
Disconnect all cables connected to the CPM-a ports.
Step 2.
Use a screwdriver to loosen the captive screws.
Step 3.
Grip the CPM-a captive fasteners and slide the CPM-a out of the slot.
7750 SR-a4 and SR-a8 Installation Guide 193
Removing and Replacing a CPM-a
Step 4.
Place the CPM-a on an antistatic surface or in an antistatic bag.
Step 5.
Do one of the following:
a. If you are installing a replacement CPM-a, go to Replacing a CPM-a on page
. b. If you are not installing a replacement CPM-a module, insert an impedance panel in the empty slot.
Replacing a CPM-a
The following procedure assumes that you have removed the CPM-a, as described in
.
Figure 71 shows how to replace a CPM-a in the 7750 SR-a4 chassis. Table 99
describes the features. The same method applies to the CPM-a in slot 7 of the 7750 SR-a8 chassis.
Figure 71: Replacing a CPM-a
194
R-a4 Fan Tray
Pwr
Stat
Pwr
Stat
Lnk
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACOLT
1PPS
Compact Flash
7750 SR-a4 ervice Router
2
Pwr
Stat
Pwr
Stat
1
2
3
4
5
6
Lnk
Act
7
Lnk
Act
Lnk
Act
8
9
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
2
1
3
24559
Key
1
2
Table 99: Replacing a CPM-a Features
Description
Chassis slot guide
Captive screws
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Key
3
Table 99: Replacing a CPM-a Features (Continued)
Description
Threaded receptacle
Required tools:
• #2 Phillips or flat blade torque driver
To replace a CPM-a:
Step 1.
Remove the new CPM-a from the packaging. Do not touch the printed circuit board or connector pins. Hold the CPM-a by the edges.
Step 2.
Locate the appropriate CPM-a chassis slot.
Step 3.
Step 4.
Insert the CPM-a into the CPM-a slot. Press the CPM-a firmly into the slot. Make sure that the connectors are fully seated in the chassis. The faceplate of the CPM-a should be flush with the chassis.
Step 5.
Tighten the captive screws (Key 2 on
) to secure the CPM-a. The recommended torque is 4 to 5 lbf-in (0.45 to 0.56 N .
m). Do not over-tighten.
Step 6.
If the system is powered, check the Power LED on the CPM-a faceplate.
Step 7.
Attach cables to the CPM-a ports.
Replacing the Internal Compact Flash Card on the CPM-a
Note:
•
The internal compact flash (CF) card is on the CPM-a; see Figure 72 . To replace the
compact flash card, you must first remove the CPM-a from the chassis.
The CF card is user-replaceable. It must be replaced by a supported CF card that has the following files:
• bof.cfg – boot option file
• boot.ldr – bootstrap software
• config.cfg – default configuration file
• TiMOS-m.n.Yz
7750 SR-a4 and SR-a8 Installation Guide 195
Removing and Replacing a CPM-a
→ m – major release number
→ n – minor release number
→ Y – A (alpha release), B (beta release), M (maintenance release), or R (released software)
→ z – version number
• iom.tim
• cpm.tim
These files can be transferred to the new compact flash as follows:
• copy the files from another compact flash to a PC, then transfer the files to the new compact flash card
• access a 7750 SR-a node using FTP, then transfer the files from the node to the new
CF card
shows the location of the internal CF card on the CPM-a.
describes the features.
Figure 72: Location of Internal CF Card on CPM-a
196
S tat
Con s ole
2
Alarm s
2
ACO
1PP
S
1PP Compact Fla s h
Compact Fla s h
1
1
Key
1
2
Table 100: Replacing a CPM-a Internal CF Card Features
Description
CF card retainer bail
CF card (shown installed in the slot)
Required tools:
• small set of pliers or tweezers
To replace a compact flash card:
24558
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Step 1.
If the system has a single CPM-a and you have a spare CPM-a with the appropriate
CF card, install the spare CPM-a in the empty CPM-a slot; see Replacing a CPM-a on page 194 .
Step 2.
Remove the CPM-a that has the compact flash that you need to replace and place it on a flat antistatic work surface; see
.
Step 3.
Remove the new CF card from the packaging and place it on a flat anti-static work surface.
Step 4.
Remove the CF card that is being replaced by doing the following; see Figure 72
for its location on the CPM-a.
i.
Lift the card retainer bail that covers the CF card slot (Key 1 on Figure 72 ).
ii. Use a pair of pliers or tweezers to pull the CF card out of the slot (Key 2 on
Figure 72 ). (The card is intentionally difficult to remove.)
iii. Place the extracted CF card on a flat antistatic work surface.
Step 5.
Insert the new CF card into the slot until it is fully seated.
Step 6.
Close the card retainer bail to hold the CF card in the slot.
Step 7.
If you installed a spare CPM-a in Step 1 , remove it; see
.
Step 8.
Reinstall the CPM-a that has the new CF card; see Replacing a CPM-a on page 194 .
7750 SR-a4 and SR-a8 Installation Guide 197
Removing and Replacing an IOM-a
Removing and Replacing an IOM-a
The 7750 SR-a4 has one IOM-a module in slot 3. The 7750 SR-a8 has two IOM-a modules, one in slot 3, the other in slot 6.
This section includes information about:
•
Warnings and Notes on page 198
•
Shutting Down and Modifying an IOM-a Configuration on page 199
•
•
Replacing an IOM-a on page 202
Warnings and Notes
Warning:
• Do not install equipment that appears to be damaged.
• Impedance panels are required in all empty slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference. Impedance panels do not have board components or connector pins.
• Electrostatic discharge (ESD) damage can occur if components are mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
Note:
• When replacing an IOM-a, ports, MDA-a, and card parameters must be shut down.
• All 7750 SR-a routers require at least one IOM-a.
• When removing an IOM-a, always use the ejector levers to make sure that the connector pins disconnect from the backplane.
• Removing an IOM-a module will not cause the system to shut down. If you are not immediately installing a replacement IOM-a module, insert an impedance panel in the empty slot.
198 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Shutting Down and Modifying an IOM-a Configuration
Caution: IOM-a and MDA-a cards are hot-swappable but you cannot replace an IOM-a without affecting MDA-a connectivity.
You can shut down ports, cards, and MDAs with the following commands in the config context:
Example Command Syntax
Shut down ports:
Step 1.
port port-id
Step 2.
shutdown
Step 3.
port port-id
Step 4.
shutdown port 1/1 shutdown port 1/2 (and so on) shutdown
Shut down the card:
Step 5.
card slot-number
Step 6.
shutdown
Shut down the MDAs:
Step 7.
Step 8
Step 9.
slot-number shutdown
Step 10.
mda mda slot-number shutdown card 1 shutdown mda 1 shutdown mda 2 (and so on) shutdown
Remove the MDAs and card from the configuration:
Step 11.
no mda slot-number no mda 1
Step 12.
no mda slot-number
Step 13.
no card slot-number
Step 14.
exit no mda 2 (and so on) no card 1 exit
After replacing the IOM-a, use the following command syntax to reconfigure the card, MDAa, and port configurations.
Command Syntax
Shut down ports:
Example
7750 SR-a4 and SR-a8 Installation Guide 199
Removing and Replacing an IOM-a
Command Syntax
Step 1.
card slot-number
Step 2.
card-type card-type
Step 3.
no shutdown
Configure the MDA slot and type:
Step 4.
mda slot-number
Step 5.
mda mda-type
Step 6.
no shutdown
Step 7.
mda slot-number
Step 8.
mda mda-type
Step 9.
no shutdown
Configure port:
Step 10.
port port-id
Step 11.
no shutdown
Step 12.
exit
Continue port configurations as required.
Example card 1 card-type iom-a no shutdown mda 1 mda maxp1-100gb-cfp no shutdown mda 2 mda ma4-10gb-sfp+ no shutdown port 1/1 no shutdown exit
Removing an IOM-a
shows how to remove an IOM-a from slot 3 in the 7750 SR-a4 chassis.
describes the features. The same method applies to the IOM-a in slots 3 and 6 in the
7750 SR-a8 chassis.
200 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Figure 73: Removing an IOM-a
3
4
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
Stat
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Minor
Alarms
ACO
LT
1PPS
Compact Flash
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk
Act
Lnk
Act
8
9
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO
LT
1PPS
Compact Flash
4
3
1
2
24592
2
3
Key
1
4
Table 101: Removing an IOM-a Features
Description
IOM-a positioned in the chassis slot guides
Threaded receptacle
IOM-a captive screws (one on each side of the IOM-a)
Ejector lever (one on each side of the IOM-a) in open position
Required tools:
• #2 Phillips or flat blade screwdriver
To remove an IOM-a:
Step 1.
Use a screwdriver to loosen the IOM-a captive screws (Key 3 in
).
Step 2.
Grip both ejector levers and simultaneously pull the ejector levers outward to unlock the IOM-a and to disengage the backplane connections (Key 4 in
Step 3.
Slide the IOM-a out of the slot and place it on a flat antistatic work surface. Do not touch the printed circuit board or connector pins.
7750 SR-a4 and SR-a8 Installation Guide 201
Removing and Replacing an IOM-a
Replacing an IOM-a
The following procedure assumes that you have removed the IOM-a, as described in
shows how to replace an IOM-a in slot 3 of the 7750 SR-a4 chassis. Table 102
describes the features. The same method applies to the IOM-a in slots 3 and 6 in the
7750 SR-a8 chassis.
Figure 74: Replacing an IOM-a
202
3
4
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
Stat
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO
LT
1PPS
Compact Flash
7750 SR-a4
S ervice Router
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk
Act
Lnk
Act
8
9
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO
LT
1PPS
Compact Flash
3
4
1
2
24560
2
3
Key
1
4
Table 102: Replacing an IOM-a Features
Description
IOM-a positioned in the chassis slot guides
Threaded receptacle on the chassis
IOM-a captive screws, one on each side of the IOM-a
Ejector lever, one on each side of the IOM-a (in open position)
Required tools:
• #2 Phillips or flat blade torque driver
To replace an IOM-a:
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Step 1.
Remove the new IOM-a from the packaging and place it on a flat antistatic work surface. Do not touch the printed circuit board or connector pins. Hold the IOM-a by the edges.
Step 2.
Move the ejector levers to the open position (Key 4 in Figure 74
).
Step 3.
Locate the IOM-a slot (Slot 3) on the chassis, and align the card with the slot guide
(Key 1 in
).
Step 4.
Slide the card inward until the captive screws align with the threaded receptacle in the chassis (Key 2 in
), and the connectors are seated in the backplane.
Step 5.
Push the ejector levers simultaneously inward to complete the seating and to lock the connectors and IOM-a in place.
The faceplate must be flush with the front of the chassis. If an ejector lever does not shift to the locked position, the IOM-a is not seated correctly. Pull the card out, reinsert it, then shift the levers to the locked position.
Step 6.
Use a torque driver to tighten the captive screws (Key 3 in
). Torque to 4 to 5 lbf-in (0.45 to 0.56 N
.
m). Do not over-tighten. The ejector levers must remain in the locked position while the card is installed in the chassis.
7750 SR-a4 and SR-a8 Installation Guide 203
Removing and Replacing an MDA-a or MDA-aXP Card
Removing and Replacing an MDA-a or MDA-aXP
Card
The procedures in this section apply to the MDA-a and MDA-aXP cards which are supported
on the 7750 SR-a4 and 7750 SR-a8 and described in MDA-a Cards on page 36
. The term
MDA-a is used generically in this chapter to refer to MDA-a and MDA-aXP cards.
The illustrations in this section show the 7750 SR-a4 chassis, but also pertain to the 7750
SR-a8 chassis.
This section includes information about:
•
Warnings and Notes on page 204
•
Changing the MDA-a Configuration on page 205
•
•
Replacing an MDA-a on page 207
Warnings and Notes
Danger: Invisible laser radiation can be emitted from the aperture ports of an optical module when no cable is connected. Avoid exposure and do not stare into open apertures.
Warning:
• Do not install equipment that appears to be damaged.
• Impedance panels are required in all empty slots to prevent excess dust accumulation and to help control airflow and electromagnetic interference. Impedance panels do not have board components or connector pins.
• Electrostatic discharge (ESD) damage can occur if components are mishandled.
Always wear an ESD-preventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
• Always place components on an antistatic surface.
204 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Note:
• MDA-a cards cannot be provisioned if the CPM-a is not preprovisioned.
• Ports cannot be provisioned if the MDA-a is not preprovisioned.
• Services cannot be provisioned if ports are not provisioned.
Changing the MDA-a Configuration
If you replace an MDA-a with a different type of MDA-a, you must change the configuration to reflect the new MDA-a type before the installation. All services and each active port must be unconfigured and shutdown to remove an MDA-a. Refer to the 7750 SR-OS Interface
Configuration Guide for information about configuring MDA-a cards and ports.
Use the following commands in the config
context to shut down ports and remove the
MDA-a from the configuration:
Command Syntax
Shut down ports:
Step 1.
Step 2.
port port-id shutdown
Example port 1/1 (etc.) shutdown
Note: The port> shutdown command must be entered for all enabled ports on the MDA.
Step 3.
exit exit
Shut down the card and MDA slot:
Step 4.
card slot-number
Step 5.
mda mda-slot
Step 6.
shutdown card 1 mda 1 shutdown exit Step 7.
exit
Remove the MDA from the configuration:
Step 8.
no mda mda-slot
Configure the MDA slot and type: no mda 1
Step 9.
mda slot-number
Step 10.
mda mda-type
Step 11.
no shutdown
Step 12.
exit mda 1 mda maxp1-100gb-cfp no shutdown exit
7750 SR-a4 and SR-a8 Installation Guide 205
Removing and Replacing an MDA-a or MDA-aXP Card
Removing an MDA-a
Figure 75 shows how to remove an MDA-a from the 7750 SR-a4 chassis. Table 103
describes the features. The same method applies to the MDA-a cards in the 7750 SR-a8 chassis.
Figure 75: Removing an MDA-a
206
R-a4 Fan Tray
Pwr
S tat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
7750 SR-a4
S ervice Router
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Pwr
Stat
2
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
1
Pwr
Stat
2
Lnk Act
Lnk Act
3
Lnk Act
4
Lnk Act
Stat
Lnk/Act
Lnk
Act
6
1 2 3 4
Lnk
Act
7
8
9
10
5 6 7 8
Lnk
Act
9 10 11 12
Lnk
13 14 15 16
Act
Lnk
17 18 19 20
Act
21 22 23 24
Lnk
Act
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor 2
ACO/LT
1PPS
Compact Flash Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat
1
3
24594
Key
1
2
3
Table 103: Removing an MDA-a Features
Description
MDA-a positioned in the chassis slot guides
MDA-a captive screws (one on each side of the MDA-a)
Threaded receptacle
Required tools:
• #2 Phillips or flat blade screwdriver
To remove an MDA-a:
Step 1.
Disconnect all cables connected to the MDA-a ports.
Step 2.
Use a Phillips screwdriver to loosen the MDA-a captive screws (Key 2 in
7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Step 3.
Grip the MDA-a captive fasteners and slide the MDA-a out of the slot.
Step 4.
Place the MDA-a on a flat antistatic work surface.
Step 5.
Do one of the following: a. If you are installing a replacement MDA-a, go to
. b. If you are not installing a replacement PSU module, insert an impedance panel in the empty slot.
Replacing an MDA-a
The following procedure assumes that you have removed an MDA-a from a slot, as described
.
Figure 76 shows how to replace an MDA-a from the 7750 SR-a4 chassis. Table 104 describes
the features. The same method applies to the MDA-a cards in the 7750 SR-a8 chassis.
Figure 76: Installing an MDA-a
R-a4 Fan Tray
Pwr
S tat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
7750 SR-a4
S ervice Router
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Pwr
Stat
2
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
1
2
Pwr
Stat
Lnk
Act
3
Lnk
Act
Lnk
Act
4
Lnk Act
Stat
Lnk/Act
Lnk
Act
6
1 2 3 4
Lnk
Act
7
8
9
10
5 6 7 8
Lnk
Act
9 10 11 12
Lnk
13 14 15 16
Act
Lnk
17 18 19 20
Act
21 22 23 24
Lnk
Act
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
Pwr
Stat
Console
DCE
Lnk
Act Lnk
Act
Critical
Major
Alarms
Minor
2
ACO/LT
1PPS
Compact Flash Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat
1
3
24561
Key
1
Table 104: Replacing an MDA-a Features
Description
MDA-a positioned in the chassis slot guides
7750 SR-a4 and SR-a8 Installation Guide 207
Removing and Replacing an MDA-a or MDA-aXP Card
Key
2
3
Table 104: Replacing an MDA-a Features (Continued)
Description
MDA-a captive screws (one on each side of the MDA-a)
Threaded receptacle
Required tools:
• #2 Phillips or flat blade torque driver
To replace an MDA-a:
Step 1.
Remove the new MDA-a from the packaging and place it on a flat antistatic work surface. Do not touch the printed circuit board or connector pins.
Step 2.
Locate the appropriate chassis slot and MDA-a slot.
Step 3.
Align the MDA-a with the slot guides and the captive screw with the threaded
receptacle (Key 1 and Key 2 in Figure 76
).
Step 4.
Press the MDA-a firmly into the slot. Make sure that the connectors are fully seated in the chassis. The faceplate of the MDA-a should be flush with the chassis.
Step 5.
Tighten the captive screws to secure the MDA-a (Key 2 in
). The recommended torque is 4 to 5 lbf-in (0.45 to 0.56 N .
m). Do not over-tighten.
Step 6.
If the system is powered, check the Pwr/Stat LED on the MDA-a faceplate.
Step 7.
Attach cables to the MDA-a ports.
208 7750 SR-a4 and SR-a8 Installation Guide
Appendix C: Field-Replaceable Units
Removing and Replacing an Impedance Panel
Empty slots in the chassis must be covered by impedance panels. Panels must be ordered
separately. See Impedance Panels on page 43
for more information.
If you need to install a component in a slot which has an impedance panel, remove the panel only when you are ready to install a component in its place.
An impedance panel slides into a slot using the chassis slot guides in the same way as the corresponding component. MDA and IOM impedance panels have captive screws to secure the panel. PSU impedance panels have a latch lock that operates like the latch lock on the PSU components.
7750 SR-a4 and SR-a8 Installation Guide 209
Removing and Replacing an Impedance Panel
210 7750 SR-a4 and SR-a8 Installation Guide
Appendix D: CPM-a Pinout
Assignments
In This Chapter
This chapter describes the pinout assignments for the port connectors on the CPM-a that is supported on the 7750 SR-a4 and 7750 SR-a8 chassis. Topics in this chapter include:
•
→
→
→
→
→
→
Alarms Interface Port on page 217
→
7750 SR-a4 and SR-a8 Installation Guide 211
CPM-a Port Types
CPM-a Port Types
identifies the ports on the CPM-a and
Table 105 describes the features.
Figure 77: CPM-a Ports
3 5 7
DTE DCE
Lnk Act Lnk Act
Pwr
Stat
Console
1 2 4
Critical Major Minor
Alarms
6
ACO/LT
1PPS
Compact Flash
24596
Table 105: 7750 SR-a CPM-a Connector and LED Features
6
7
4
5
2
3
Key
1
Port
Console Port
The RS-232 serial port on the front panel of the CPM uses an RJ-45 connector to connect to the router for out-of-band console configuration.
A null cable is included in the accessory box (3HE08703AA). The null cable has an RJ-45 connector on one end for use with the serial port on the CPM, and a DB9 female connector on the other end for use with the craft terminal.
212 7750 SR-a4 and SR-a8 Installation Guide
Appendix D: CPM-a Pinout Assignments
The on-board configuration program can be accessed from a terminal or a PC running a terminal emulation program.
for information about the Console Port pin numbers.
Figure 78: Console Port Pin Numbers
Pin 8 Pin 1
1959 3
6
7
8
4
5
2
3
RJ-45
Pin
1
Console Port Pinouts RS-232 DTE Mode
Table 106 describes the Console port pin assignments when the CPM is in DTE mode.
Table 106: Console Port Pinouts— RS-232 DTE Mode: RJ-45 to DB9 Cable
Signal
RTS
DTR
TXD
GND
GND
RXD
DSR
CTS
Direction Description
Output Request to send
Output
Output
—
—
Input
Input
Input
Data terminal ready
Transmit data
Signal ground
Signal ground
Receive data
Data set ready
Clear to send
3
4
7
1
5
6
2
DB9
Pin
8
Signal
CTS
DSR
RXD
GND
GND
TXD
DTR
RTS
Description
Clear to send
Data set ready
Receive data
Signal ground
Signal ground
Transmit data
Data terminal ready
Request to send
Console Port Pinouts RS-232 DCE Mode
Table 107 describes the Console port pin assignments when the CPM is in DCE mode.
7750 SR-a4 and SR-a8 Installation Guide 213
CPM-a Port Types
6
7
8
4
5
2
3
RJ-45
Pin
1
Table 107: Console Port Pinouts— RS-232 DCE Mode: RJ-45 to DB9 Cable
Signal
CTS
DSR
RXD
GND
GND
TXD
DTR
RTS
Direction
Output
Output
Output
—
—
Input
Input
Input
Description
Clear to send
Data set ready
Receive data
Signal ground
Signal ground
Transmit data
Data terminal ready
Request to send
3
4
7
1
5
6
2
DB9
Pin
8
Signal
RTS
DTR
TXD
GND
GND
RXD
DSR
CTS
Description
Request to send
Data terminal ready
Transmit data
Signal ground
Signal ground
Receive data
Data set ready
Clear to send
Management Port
Use a shielded twisted-pair (STP) cable for RJ-45 connections and 100-ohm Category 3, 4, or 5 cable for 10 Mb/s connections or 100-ohm Category 5 cable for 100 Mb/s connections.
Make sure that the length of any shielded twisted-pair cable does not exceed 328 ft (100 m).
The RJ-45 ports on the router support automatic MDI/MDI-X operation, so you can use straight-through cables for all network connections to PCs or servers, or to other switches or hubs. In straight-through cable, pins 1, 2, 3, and 6, at one end of the cable, are connected straight through to pins 1, 2, 3, and 6 at the other end of the cable. When using any RJ-45 port on these switches, you can use either straight-through or crossover cable.
shows the Management port pin numbers.
Figure 79: Management Port Pin Numbers
Pin 1 Pin 8
24689
214 7750 SR-a4 and SR-a8 Installation Guide
Appendix D: CPM-a Pinout Assignments
Management Port Pinouts
Table 108 describes the 10/100 Mb/s Management port pin assignments. Table 109 describes
the 1000 Mb/s Management port pin assignments.
5
6
3
4
7
8
Pin
1
2
Table 108: 10/100Mbs Ethernet Management Port Pinouts—RJ-45 Female
Signal
TX+
TX–
RX+
NC
NC
RX–
NC
NC
Direction
Output
Output
Input
—
—
Input
—
—
Description
Differential transmit data – positive
Differential transmit data – negative
Differential receive data – positive
Not connected
Not connected
Differential receive data – negative
Not connected
Not connected
5
6
3
4
7
8
Pin
1
2
Table 109: 1000Mbs Ethernet Management Port Pinouts—RJ-45 Female
Signal
TRD0+
TRD0–
Direction
Bidirectional
Bidirectional
TRD1+ Bidirectional
TRD2+ Bidirectional
TRD2–
TRD1–
Bidirectional
Bidirectional
TRD3+
TRD3–
Bidirectional
Bidirectional
Description
Differential Bidirectional Data Positive
Differential Bidirectional Data Negative
Differential Bidirectional Data Positive
Differential Bidirectional Data Positive
Differential Bidirectional Data Negative
Differential Bidirectional Data Negative
Differential Bidirectional Data Positive
Differential Bidirectional Data Negative
7750 SR-a4 and SR-a8 Installation Guide 215
CPM-a Port Types
OES Port
Sync-E/1588v2
The CPM-a supports one Sync-E/1588v2 timing port, which uses an RJ-45 connector. The
Sync-E/1588v2 port is reserved for future use.
BITS Port
The CPM-a supports one Open Enterprise Server (OES) 10/100 Mb/s Ethernet RJ-45 port.
The OES port is reserved for future use.
The BITS port is provisioned with an RJ-45 jack and used for the network clock source. Use shielded cable when connecting to the BITS port.
shows the BITS port pin numbers.
Figure 80: BITS Port Pin Numbers
216
Pin 8 Pin 1
4
5
2
3
Pin
1
Table 110 specifies the BITS port connector pinouts.
Table 110: BITS Port Pinouts—RJ-45 Female
Signal
RXRING
RXTIP
NC
TXRING
TXTIP
Direction
Input
Input
—
Output
Output
Description
Receive Ring Signal
Receive Tip Signal
Not connected
Transmit Ring Signal
Transmit Tip Signal
1959 3
7750 SR-a4 and SR-a8 Installation Guide
Appendix D: CPM-a Pinout Assignments
7
8
Pin
6
Table 110: BITS Port Pinouts—RJ-45 Female (Continued)
Signal
NC
NC
NC
Direction
—
—
—
Description
Not connected
Not connected
Not connected
Alarms Interface Port
The alarms interface port is a D-type 15-pin connector that supports a critical alarm output, a major alarm output, and four alarm inputs. When your system has a critical or major alarm, the CPU causes the alarm relay to issue the alarm output and turn on the critical or major
LED. If you push the alarm cut off (ACO) button, the relay will be released but the LED will stay on until the alarm is cleared.
shows the DB-15 Alarm Connector. Pinouts are numbered as follows:
• top row: right to left, pins 1 to 8
• bottom row: right to left, pins 9 to 15
Figure 81: DB-15 Receptacle Alarm Connector
1
15
24597
The system signals the appropriate alarm output for the following events:
• Fan failure - Critical alarm is raised.
• One Power Supply Failure - Critical alarm is raised.
The critical alarm is cleared and a major alarm is raised if the failed power supply is removed.
• Chassis temperature threshold exceeded - Major alarm is raised.
The system also supports four alarm inputs. The input voltage range is from 24 VDC to 48
VDC. If an alarm input is active, the CPU will process it, output it to the CLI, and issue an
SNMP trap. An alarm input can also be configured to activate the appropriate alarm output pin.
7750 SR-a4 and SR-a8 Installation Guide 217
CPM-a Port Types
Refer to the 7750 SR OS Basic System Configuration Guide for more details about configuring the alarm inputs.
7
8
5
6
9
Alarms Interface Port Pinouts
Table 111 describes the alarms interface port pinouts.
12
13
14
Pin
1
2
3
4
10
11
15
MJR_ALARM_NC
Table 111: Alarms Interface Port Pinouts
Name
CRIT_ALARM_COM
CRIT_ALARM_NO
Description
Common contact for Critical alarm relay.
Normally open contact will be connected to the common contact during a Critical alarm state.
Normally closed contact will be disconnected from the common contact during a Major alarm state.
Available as a source voltage for use with Alarm In 1-4.
+24 VDC source 100 mA referenced to chassis ground
ALARM_IN4_EXT_+
ALARM_IN3_EXT_+
ALARM_IN2_EXT_+
ALARM_IN1_EXT_+
CRIT_ALARM_NC
MJR_ALARM_COM
MJR_ALARM_NO
ALARM_IN4_EXT_RTN
ALARM_IN3_EXT_RTN
ALARM_IN2_EXT_RTN
ALARM_IN1_EXT_RTN
External alarm input 4 (external relay dry contact closure to pin 12).
External alarm input 3 (external relay dry contact closure to pin 13).
External alarm input 2 (external relay dry contact closure to pin 14).
External alarm input 1 (external relay dry contact closure to pin 15).
Normally closed contact will be disconnected from the common contact during a Critical alarm state.
Common contact for Major alarm relay.
Normally open contact will be connected to the common contact during a Major alarm state.
External alarm input 4 (external relay dry contact closure from pin 5).
External alarm input 3 (external relay dry contact closure from pin 6).
External alarm input 2 (external relay dry contact closure from pin 7).
External alarm input 1 (external relay dry contact closure from pin 8).
218 7750 SR-a4 and SR-a8 Installation Guide
Appendix D: CPM-a Pinout Assignments
RTN refers to the negative side of the Alarm-In connections when a floating power supply is used. If an external power supply is used as the voltage source for Alarm-In 1-4, its negative rail must not be connected to chassis ground and it should be 18 to 50 VDC at 100 mA.
When using the internal isolated 24 VDC power supply on pin 4 of the DB15 connector, the
Alarm RTN pins must be connected to chassis ground. The metal shell of the alarm plug may be used as a chassis ground connection for the internal +24 VDC supply providing that the plug mounting (hold down) screws are firmly attached to the alarm connector.
Major and Critical alarm dry relay contact outputs are provided on pins 3, 10, 11, and 1, 2, 9.
These reflect the Major and Critical alarms output by the chassis and can be manually cleared by pressing the ACO button.
The four alarm inputs are customer configurable to monitor alarms provided by additional
equipment. See Figure 82 . These inputs must use one of the following:
• the voltage source provided on pin 4 of the DB15 connector
• a separate isolated DC power supply, rated between 18 to 50 VDC at 100 mA
If an external power source is used, its outputs must be isolated from chassis ground, as shown in
. Do not connect the alarm power supply return to the chassis or rack ground in this scenario.
Figure 82: Alarm Inputs using DB 15 Alarm Connector
7750 SRa
+24VDC
Pin 4+
- Ch ass i s Gro u nd
Extern a l Al a rm Rel a y s
On Other Eq u ipment
Al a rm 1 off a ctive
Al a rm DB15
Pin 8+
Pin 15Al a rm in 1
Pin 7+
Pin 14-
Al a rm in 2 off
Al a rm 2 a ctive off
Al a rm 3 a ctive off
Al a rm 4 a ctive
Pin 6+
Pin 1 3 -
Al a rm in 3
Pin 5+
Pin 12Al a rm in 4
24598
7750 SR-a4 and SR-a8 Installation Guide 219
CPM-a Port Types
Figure 83: Alarm Inputs Using External Power Source
Power S u pply M us t be
Flo a ting or I s ol a ted from
Ch ass i s Gro u nd
DC Power S u pply
18-50 VDC @ 100 mA
+
-
Extern a l Al a rm Rel a y s
On Other Eq u ipment
Al a rm 1 off a ctive off
Al a rm 2 a ctive off
Al a rm 3 a ctive off
Al a rm 4 a ctive
Al a rm DB15
Pin 8+
Pin 15Al a rm in 1
Pin 7+
Pin 14-
Al a rm in 2
Pin 6+
Pin 1 3 -
Al a rm in 3
Pin 5+
Pin 12-
Al a rm in 4
24599
1PPS Port
The CPM-a supports one 1PPS port, which uses an SMB coaxial connector. The 1PPS port is reserved for future use.
220 7750 SR-a4 and SR-a8 Installation Guide
Appendix E: Pluggable Transceivers
In This Chapter
This chapter describes how to install and replace the following pluggable transceivers in
MDA-a or MDA-aXP cards.
• Small Form Factor Pluggable (SFP and SFP+)
• Compact Small Form Factor Pluggable (CSFP)
• C Form Factor Pluggable (CFP)
• Quad Small Form Factor Pluggable Plus (QSFP+)
Topics in this chapter include:
•
Warnings and Notes on page 222
•
•
Installation and Replacement of Pluggable Transceivers on page 224
7750 SR-a4 and SR-a8 Installation Guide 221
Warnings and Notes
Warnings and Notes
Danger:
• Fiber-optic equipment can emit laser or infrared light that can injure your eyes. Never look into an optical fiber or connector port. Always assume that fiber-optic cables are connected to a light source.
• CFP and QSFP+ pluggable optic modules are very hot while in use. Touch only the captive screws when removing the module. Allow the module to cool before further handling.
Warning:
• Make sure that the safety cap on the transceiver is inserted while you install or remove the SFP, SFP+, CSFP, CFP, or QSFP+ transceivers. Only remove the safety cap when you are ready to attach network cables.
• Always replace the dust cover when the SFP, SFP+, CSFP, CFP, or QSFP is removed.
• Use only approved small form factor pluggable (SFP) and compact form factor pluggable (CFP) fiber-optic devices in MDA-a ports.
• Before using the optics, verify that the optical path is in compliance with the parameters of the optical components. In particular, verify any minimum attenuation requirements for the optics. If minimum attenuation requirements are not met, the optical receiver components may be permanently damaged.
• Electrostatic discharge (ESD) damage can occur if router components, including SFP,
SFP+, CSFP, CFP, and QSFP+ transceivers are mishandled. Always wear an ESDpreventive wrist or ankle strap and always connect an ESD strap to the grounding plug on the front of the chassis.
Caution:
• Always place router components on an antistatic surface.
• Avoid bending fiber-optic cable beyond its minimum bend radius.
• Do not exceed the recommended minimum bend radius for fiber-optic cables. AT&T TP-
76450 specifies 1.0 in. (25.4 mm) inside radius for single fibers.
Note:
• Discard SFP, SFP+, CSFP, CFP, and QSFP+ transceivers according to all local laws and regulations.
• SFP, SFP+, CSFP, CFP, and QSFP+ transceivers can be installed and replaced without disabling the interfaces.
• SFP, SFP+, CSFP, CFP, and QSFP+ transceivers are keyed to prevent incorrect insertion.
222 7750 SR-a4 and SR-a8 Installation Guide
Appendix E: Pluggable Transceivers
Preparation
Clean the connector on the fiber cable before inserting it into the transceiver to prevent the transfer of small particles and contaminants to the transceiver. If you switch an SFP, SFP+,
CSFP, CFP, or QSFP+ from one port to another ensure that you clean the fiber connectors before reinserting them.
Apply high standards when inspecting and cleaning fiber connectors. Use a “dry” cleaning method to clean fiber connectors.To clean the connector, you can either:
• Wipe the side and end of the ferrule with a lint-free alcohol-dampened cloth.
• Blow dry the ferrule with compressed air and inspect for lint. Do not insert the compressed air nozzle into the receptacle.
Locking Mechanisms
SFP, SFP+, CSFP, CFP, and QSFP+ transceivers use different lock and release methods.
Possible lock and release mechanisms include:
• Bail— A bar or wire in the front of the transceiver that you use to release the module.
SFP, SFP+, and CSFP transceivers use bail-actuated bottom latching. QSFP+ use bail-actuated side latching.
• Captive screws—Fixed screws on both sides of the transceivers. Screws are used on
CFP transceivers.
7750 SR-a4 and SR-a8 Installation Guide 223
Installation and Replacement of Pluggable Transceivers
Installation and Replacement of Pluggable
Transceivers
The following sections describe how to install and replace the pluggable transceivers supported on MDA-a cards.
An SFP module can be installed on the following MDA-a cards:
• 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a
• 44-port 1GigE CSFP/SFP MDA-a
An CSFP module can be installed on the following MDA-a card:
• 44-port 1GigE CSFP/SFP MDA-a
An SFP+ module can be installed on the following MDA-a and MDA-aXP cards:
• 2-port 10GigE SFP+ and 12-port 1GigE SFP Combo MDA-a
• 4-port 10GigE SFP+ MDA-a
• 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP
• 10-port 10GigE SFP+ MDA-aXP
A QSFP+ module can be installed on the following MDA-a XP card:
• 6-Port 10GigE SFP+ and 1-Port 40GigE QSFP+ Combo MDA-aXP
A CFP module can be installed on the following MDA-aXP card:
• 1-port 100GigE CFP MDA-aXP
Installing an SFP, SFP+, CSFP, or QSFP+
To install an SFP, SFP+, CSFP, or QSFP+ transceiver:
Step 1.
Locate the transceiver receptacle on the MDA-a card.
Step 2.
Remove the transceiver from its antistatic packaging.
Step 3.
While holding the transceiver by its sides, slide the unit into the port at the correct angle. If other transceivers are present, you may need to push on the face to fully seat the transceiver. The transceiver is seated when it clicks into place. See
Figure 84 . Table 112 describes the SFP installation features. The same features
apply to SFP+s and CSFPs.
224 7750 SR-a4 and SR-a8 Installation Guide
Appendix E: Pluggable Transceivers
Figure 84: Installing an SFP, SFP+, CSFP, or QSFP+
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1 2
Act Lnk
3
4
Act Lnk
5 6
Act
Lnk
7 8
Act
Lnk
9
10
Act Lnk
11 12
Act
Lnk
13 14
Act
Lnk
15
16
Act Lnk
17 18
Act
Lnk
19 20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/3
1/2
1/4
CPM A
1
CPM B
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
7750 SR-a
S ervice Router
4
Pwr
Stat
1
Pwr
Stat
2
3
4
5
6
Lnk Act
7
Lnk Act
8
Lnk Act
9
Lnk Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
Link
Act
5
6
Link
Act
Link
Act
7
Act
Link
Act
Link
2
1
24600
Key
1
2
Table 112: SFP, SFP+, CSFP, or QSFP+ Installation Features
Description
SFP, SFP+, CSFP, or QSFP+. The wire bail is in the upright rest position during installation.
SFP insertion
Step 4.
Remove the safety cap from the transceiver optical bore when you are ready to attach the network cable.
Replacing an SFP, SFP+, CSFP, or QSFP+
The following equipment is required:
• a replacement transceiver or slot plug
• an antistatic mat
• a safety cap for the transceiver
To replace an SFP, SFP+, CSFP, or QSFP+ transceiver:
Step 1.
Locate the transceiver on the MDA-a card.
7750 SR-a4 and SR-a8 Installation Guide 225
Installation and Replacement of Pluggable Transceivers
Step 2.
Disconnect the network cable from the optical connector.
Step 3.
Locate the bail in the front of the transceiver.
Step 4.
Grasp the bail with your thumb and forefinger, and pull it downwards to disengage the transceiver.
Step 5.
Slide the transceiver out of the port, as shown in
Figure 85: Removing an SFP, SFP+, CSFP, or QSFP+
7750
S R-a4 Fan Tray
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
3 4
Act
Lnk
5 6
Act Lnk
7
8
Act Lnk
9 10
Act
Lnk
11 12
Act
Lnk
13
14
Act Lnk
15 16
Act
Lnk
17 18
Act Lnk
19
20
Act
Pwr
S tat
Pwr
Stat
S lot Layout
1/1 XP
1/2
1/3
1/4
1
CPM A
CPM B
DTE
DCE
Lnk
Act Lnk
Act
Pwr
Stat
Console
Critical
Major
Alarms
Minor
ACO/LT
1PPS
Compact Flash
Pwr
Stat 7750 SR-a4
S r
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk Act
Lnk Act
8
9
Lnk Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
10
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12 13
14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Pwr
Stat
DTE
DCE
Lnk
Act Lnk
Act
Console
Critical
Major
Minor
Alarms
ACO/LT
1PPS
Compact Flash
Link
Act
5
6
Link
Act
Link
Act
7
Act
Link
Act
Link
2
1
24601
Key
1
2
Table 113: SFP, SFP+, CSFP, or QSFP+ Removal Features
Description
SFP, SFP+, CSFP, or QSFP+ wire bail
SFP, SFP+, CSFP, or QSFP+ removal
Step 6.
Place the transceiver on an antistatic mat or in an electrostatic bag.
Step 7.
Remove the new transceiver from its antistatic packaging.
Note: If you are not replacing the transceiver with a new transceiver, you must reinsert a plug into the transceiver receptacle.
226 7750 SR-a4 and SR-a8 Installation Guide
Appendix E: Pluggable Transceivers
Step 8.
While holding the transceiver by its sides, slide the unit into the port at the correct angle. If other transceivers are present, you may need to push on the face to fully seat the transceiver. The transceiver is seated when it clicks into place. See
Figure 84 . Table 112 describes the installation features.
Step 9.
Remove the safety cap from the optical transceiver.
Step 10.
Connect the network cable to the optical transceiver.
Installing a CFP
To install a CFP transceiver:
Step 1.
Locate the CFP receptacle on the MDA-a card.
Step 2.
Remove the CFP from its antistatic packaging.
Step 3.
While holding the CFP by its sides, slide the unit into the port at the correct angle
until it clicks into place, as shown in Figure 86 .
Figure 86: CFP Installation
S
R-a4 Fan Tray
Pwr
S tat
S lot Layout
1/1 XP
1/2
Pwr
Stat
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
Tx 3
4
Act
Lnk
5 6
Act Lnk
Rx 7
8
Act
Lnk
9 10
Act
Lnk
11
12
Act
Lnk
13
14
Act Lnk
15
16
Act
Lnk
17 18
Act Lnk
19
20
Act
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk
Act
8
Lnk
Act
9
Lnk
Act
10
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Lnk
Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
Step 4.
Tighten the captive screw on each side of the CFP.
Step 5.
Remove the safety cap from the optical transceiver.
Step 6.
Connect the network cable to the optical transceiver connector.
24541
7750 SR-a4 and SR-a8 Installation Guide 227
Installation and Replacement of Pluggable Transceivers
Replacing a CFP
The following equipment is required:
• a replacement transceiver or slot plug
• an antistatic mat
• a safety cap for the transceiver
Danger: CFP pluggable optic modules are very hot while in use. Touch only the captive screws when removing the module. Allow the CFP to cool before further handling.
To replace a CFP transceiver:
Step 1.
Remove the new CFP from its antistatic packaging and place it on an antistatic mat.
Step 2.
Locate the CFP on the MDA-a card.
Step 3.
Disconnect the network cable from the optical connector.
Step 4.
Loosen the captive screw on each side of the CFP.
Caution: Be careful not to loosen the captive screw too far. It is possible to entirely remove the captive screw from the CFP.
Step 5.
Grip both captive screws, and gently pull to remove the CFP from the port, as
.
228 7750 SR-a4 and SR-a8 Installation Guide
Appendix E: Pluggable Transceivers
Figure 87: Removing a CFP
S
R-a4 Fan Tray
Pwr
S tat
S lot Layout
1/1 XP
1/2
Pwr
Stat
Pwr
Stat
Lnk
Pwr
Stat
Lnk
1
2
Act
Lnk
Tx 3
4
Act
Lnk
5 6
Act Lnk
Rx 7
8
Act
Lnk
9 10
Act
Lnk
11
12
Act
Lnk
13
14
Act Lnk
15
16
Act
Lnk
17 18
Act Lnk
19
20
Act
1
Pwr
Stat
2
3
4
5
6
Lnk
Act
7
Lnk Act
Lnk
Act
8
9
Lnk
Act
10
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Lnk Act
Pwr
Stat
Lnk/Act
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
17 18 19 20
21 22 23 24
25 26 27 28
29 30 31 32
33 34 35 36
37 38 39 40
41 42 43 44
24602
Step 6.
Place the CFP on an antistatic mat, then wait about 5 minutes for the CFP to cool.
Step 7.
Install a CFP replacement or re-insert the plug.
Note: If you are not replacing the CFP with a new transceiver, you must reinsert a plug into the receptacle.
Step 8.
Connect the network cable or place a safety cap over the optical transceiver.
7750 SR-a4 and SR-a8 Installation Guide 229
Installation and Replacement of Pluggable Transceivers
230 7750 SR-a4 and SR-a8 Installation Guide
Customer documentation and product support
Customer documentation
http://www.alcatel-lucent.com/myaccess
Product manuals and documentation updates are available at alcatel-lucent.com. If you are a new user and require access to this service, please contact your Alcatel-Lucent sales representative.
Technical support
http://support.alcatel-lucent.com
Documentation feedback
© 2015 Alcatel-Lucent. All rights reserved.
3HE 10231 AAAA TQZZA Edition 01
Download
Advertisement
Key features
Delivers high-density 10/25/40/100GbE interfaces.
Supports MPLS, VPNs, and IPv6.
Provides comprehensive security features, including firewall, intrusion detection, and DoS protection.
Offers flexible service deployment options, including VPLS, VLL, and QinQ.
Delivers scalable performance with up to 16Tbps of switching capacity.
Features redundant power supplies and cooling fans for high availability.
Frequently asked questions
16Tbps
Yes
Firewall, intrusion detection, and DoS protection