Protec 6100 Installation And Commissioning Manual
Advertentie
Advertentie
6100 SINGLE LOOP DIGITAL
ADDRESSABLE FIRE ALARM
CONTROL PANEL
INSTALLATION AND COMMISSIONING
MANUAL
Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND
+44 (0) 1282 717171 www.protec.co.uk [email protected]
Document Revision Details
Issue Modification Detail
0
1
2
3
Document Creation.
Refer to ECN3252.
Compatible software versions updated.
RVAV operation amended. ECN3283.
Addition of EN54 BSI approval table.
4
5
6
Refer to ECN3380 .
Refer to ECN3414.
Addition of Output Group T1/T2 option.
Addition of Device Disablement.
Refer to ECN3477.
7
Addition of VAD details on section 3.
Standards section expanded.
Section 7.16 added regarding VADs.
Appendix 3 expanded with new device types.
8
9
10
11
12
PropointPLUS product added to Appendix 3.
Refer to ECN3729.
Addition of Invisible Switch, Disable Control Group,
Disable Output Group 31 and disable Output Group 32 class details.
Update to section 7.20.
Refer to ECN3890.
Update to BS5839 references
Change to BSI NB Number
Refer to ECN4363
Change to operating temperature range in section 10.0
Change to copyright year
Refer to ECN4463
Author
NH
NH
NH
NH
AH
NH
NH
NH
NH
NH
NH
NH
NH
Date
22/01/2012
27/03/2012
25/06/2012
28/09/2012
28/06/2013
10/10/2013
17/03/2014
22/06/2014
05/08/2014
14/07/2015
26/04/2017
16/05/2019
10/02/2020
N93-572-88 Issue 12 NH Page 2 of 52 © Protec Fire Detection plc 2020
Table of Contents
IMPORTANT NOTES – PLEASE READ CAREFULLY ................................................................................... 5
STANDARDS, DIRECTIVES AND REGULATIONS INFORMATION ............................................................. 6
1.0
ITEMS SUPPLIED WITH THE 6100 ...................................................................................................... 7
2.0
ITEMS AND INFORMATION REQUIRED PRIOR TO COMMISSIONING ............................................ 7
2.1
Site information required to commission the 6100 .......................................................................... 7
2.2
Items required to commission the 6100 using the windows software .............................................. 7
3.0
INTRODUCTION AND KEY FEATURES ............................................................................................... 8
4.0
6100 CABLING REQUIREMENTS ........................................................................................................ 9
4.1
General ............................................................................................................................................ 9
4.2
Mains Input Rating Label ................................................................................................................. 9
4.3
Mains Wiring .................................................................................................................................... 9
4.4
Alarm Circuit Wiring ......................................................................................................................... 9
4.5
Fire Link Wiring .............................................................................................................................. 10
4.6
Addressable Loop Wiring and Devices .......................................................................................... 10
5.0
INSULATION TESTING OF CABLING PRIOR TO CONNECTION .................................................... 12
6.0
INSTALLING THE 6100 ....................................................................................................................... 13
6.1
Unpacking ...................................................................................................................................... 13
6.2
Removal of the Door ...................................................................................................................... 13
6.3
Disconnection of the Fire Brigade Panel (FBP) Connections ........................................................ 14
6.4
Removal of the Control PCB Housing ........................................................................................... 15
6.5
Preparing the Mounting Position and Cable Entries ...................................................................... 16
6.6
Installing the Standby Batteries ..................................................................................................... 16
6.7
Connecting the Standby Batteries ................................................................................................. 17
6.8
Refitting the Control PCB Housing ................................................................................................ 18
6.9
Connecting the Addressable Loop Wiring ..................................................................................... 18
6.10
Connecting the Conventional Alarm Circuit Wiring .................................................................... 18
6.11
Connecting the Fire Link Wiring ................................................................................................. 19
6.12
Connecting the Auxiliary Wiring ................................................................................................. 19
6.13
Connecting the Mains Cabling ................................................................................................... 20
6.14
Connecting the Fire Brigade Panel Controller ........................................................................... 21
6.15
Re-fitting the Door ...................................................................................................................... 21
6.16
Switching the Mains Power On .................................................................................................. 21
7.0
COMMISSIONING THE 6100 ............................................................................................................... 22
7.1
Terminology ................................................................................................................................... 22
7.2
Loop Device Input Group, Output Group and Zone Programming ................................................ 22
7.3
Non latching Loop Devices ............................................................................................................ 22
7.4
Loop Device Class Programming .................................................................................................. 23
7.5
Loop Device Sensitivity Programming ........................................................................................... 24
7.6
Loop Sounder Volume Programming ............................................................................................ 24
7.7
Talking Sounder Programming Considerations ............................................................................. 25
7.8
Fire Link Operation ........................................................................................................................ 26
7.9
Global Fire Contact Operation ....................................................................................................... 27
7.10
Global Fault Contact Operation ................................................................................................. 27
7.11
Remote Alarm Input Operation .................................................................................................. 27
7.12
Class Change Input Operation ................................................................................................... 27
7.13
Conventional Alarm Output Operation ....................................................................................... 28
7.14
Output Group Type .................................................................................................................... 28
7.15
Output Group Delays (T1 and T2) ............................................................................................. 28
7.16
Programming the coverage volume of Visual Alarm Devices (VADs) ....................................... 30
7.17
Logging and Mapping Loop Devices .......................................................................................... 30
7.18
Programming Loop Device Address Data .................................................................................. 32
7.19
Exchanging Loop Devices ......................................................................................................... 34
7.20
Disabling / Enabling a Loop Device ........................................................................................... 35
7.21
Loop Device Remote Visual Address Verification ( RVAV ) ...................................................... 36
N93-572-88 Issue 12 NH Page 3 of 52 © Protec Fire Detection plc 2020
7.22
Editing Device Location Text ..................................................................................................... 37
7.23
Editing Zone Text ....................................................................................................................... 37
7.24
Clearing the Historic Fire Event Log .......................................................................................... 38
7.25
Clearing the Historic General Event Log .................................................................................... 38
7.26
Displaying Loop Device Data ..................................................................................................... 39
7.27
Displaying Panel Diagnostic Data .............................................................................................. 41
7.28
Displaying Panel Manufacturing Details .................................................................................... 42
7.29
Connecting the 6100 to a PC ..................................................................................................... 43
7.30
Restarting the 6100 .................................................................................................................... 43
8.0
PROGRAMMING THE SYSTEM USING THE WINDOWS SOFTWARE SUITE ................................. 44
9.0
GENERAL SYSTEM OPERATION ...................................................................................................... 44
9.1
Panel Initialisation .......................................................................................................................... 44
9.2
Loop Initialisation ........................................................................................................................... 44
9.3
Added Loop Devices ..................................................................................................................... 44
10.0
6100 TECHNICAL SPECIFICATION ................................................................................................ 45
APPENDIX 1 LIST OF 6100 SPARES AND ACCESSORIES ................................................................. 46
APPENDIX 2 6100 CONTROL PCB HOUSING ....................................................................................... 47
APPENDIX 3 LOOP DEVICES SUPPORTED BY THE 6100 .................................................................. 48
APPENDIX 4 6100 EVENT DESCRIPTIONS ........................................................................................... 49
N93-572-88 Issue 12 NH Page 4 of 52 © Protec Fire Detection plc 2020
Important Notes – PLEASE READ CAREFULLY
•
Both the 6100 user manual and this manual should be thoroughly read and understood before installation and commissioning is undertaken.
•
The 6100 and its associated connections must be installed, commissioned and maintained by a suitably trained, skilled and competent person.
•
It is assumed that the person commissioning the system is aware of Protec Fire
Detection equipment terminology and terms of reference.
•
This equipment must be earthed and earth continuity must be preserved on broken segments of screened cable used anywhere in the system installation.
•
This equipment is not guaranteed unless installed and commissioned in accordance with current national standards.
•
This equipment WILL NOT operate as a fire alarm panel when the USB port is connected and is in commissioning mode.
•
This equipment is not suitable as part of an I.T type power distribution system as defined in IEC 60364-3.
•
It is perfectly normal for sealed lead acid batteries to vent small amounts of hydrogen when being charged. The 6100 is vented to dissipate any build-up of hydrogen. The 6100 enclosure must not be not sealed in any way.
•
A competent person trained to undertake such work MUST carry out any internal maintenance. There are no user serviceable parts inside the 6100. Opening the
PCB housing will immediately invalidate the warranty.
N93-572-88 Issue 12 NH Page 5 of 52 © Protec Fire Detection plc 2020
Standards, Directives and Regulations Information
2797
Protec Fire Detection plc, Nelson, Lancashire, England BB9 6RT
12
PFD-CPR-0055
BS EN 54-2:1997+A1:2006
BS EN 54-4:1997 + A1 + A2:2006
Control / Indicating and Power Supply equipment for fire detection and fire alarm systems for buildings
6100 Fire Alarm Control Panel
Control & Indicating:
Performance under fire conditions: Pass
Response delay (response time to fire): Pass
Operational reliability: Pass
Durability of operational reliability, Temperature resistance: Pass
Durability of operational reliability, Vibration resistance: Pass
Durability of operational reliability, Electrical stability: Pass
Durability of operational reliability, Humidity resistance: Pass
Power supply:
Performance of power supply: Pass
Durability of operational reliability, Temperature resistance: Pass
Durability of operational reliability, Vibration resistance: Pass
Durability of operational reliability, Electrical stability: Pass
Durability of operational reliability, Humidity resistance: Pass
This equipment has been manufactured in conformance with the requirements of all
applicable EU council directives and regulations.
Electrical or electronic devices that are no longer serviceable must be collected separately and sent for environmentally compatible recycling (in accordance with the European Waste Electrical and Electronic Equipment Directive). To dispose of old electrical or electronic devices, you should use the return and collection systems put in place in the country concerned.
The policy of Protec Fire Detection plc is one of continuous improvement. As such we reserve the right to make changes to product specifications at any time and without prior notice. Errors and omissions excepted.
N93-572-88 Issue 12 NH Page 6 of 52 © Protec Fire Detection plc 2020
1.0 Items Supplied with the 6100
• User manual
• Installation and Commissioning Manual (this manual)
• Loop Commissioning Booklet (used to affix loop device barcode labels at the relevant addresses)
• 6100 Spares kit
2.0 Items and Information Required Prior to Commissioning
2.1 Site information required to commission the 6100
To ensure rapid and trouble-free commissioning the following information should be supplied to the commissioning engineer in advance of the proposed commissioning date.
• Loop device text (20 characters maximum per device)
• Zone text (20 characters maximum per zone)
• Panel text (2 lines of 20 characters maximum)
• Cause and effect programming, including;
Zone information
Matrix information
Delays to outputs
Fire Link Delay
Coincidence operation
2.2 Items required to commission the 6100 using the windows software
• Suitable PC with a USB port ( please consult the 6100 programming manual for details of the recommended PC specification )
• 6100 commissioning software Windows program ( and associated dongle if the system is managed )
• 6100 Programming Manual ( available upon request, or from the Protec website )
• USB 2.0 Lead ( Type A male to Type B male 2 metre maximum length ), as illustrated below
.
TYPE A TYPE B
N93-572-88 Issue 12 NH Page 7 of 52 © Protec Fire Detection plc 2020
3.0 Introduction and Key Features
The 6100 is a single loop fire alarm control panel incorporating an integrated power supply and high power loop driver circuit that communicates to a maximum of 192 Protec 6000Plus series detectors / sounders.and
6000 series interfaces.
The 6100 has been designed and manufactured in the United Kingdom and complies fully with current standards dictating fire alarm system design practice (EN54 parts 2 and 4).
Sophisticated tracking algorithms Protec Algo-Tec™) are employed in the 6100 to discriminate between genuine and unwanted alarms, reducing the incidence of false alarms.
The integrity and reliability of a fire alarm system is paramount and consequently the 6100 continually monitors all critical paths for faults. The fire detection loop devices and wiring are constantly monitored to check for faults. The integrated power supply regularly performs self-checks to ensure it is fully working and that the stand-by batteries are in a good state.
Any alarms or faults detected are reported clearly on the front panel display and entered into a 300 event historic event log.
The key features include.
• High capacity single loop driver supporting a maximum of 192 Protec loop devices ( detectors, sounders and interfaces )
• Clear controls and indications
• Intuitive menu system
• Uses Protec Algo-Tec™ detection algorithms to minimise unwanted alarms
• Two operating sensitivity levels may be set up per automatic detection device
• Sensitivity levels on detectors can be programmed to switch at preset times ( Day / Night mode )
• Devices may be programmed into any one of 32 zones
• Monitored Fire Link output ( including fire link delay, search time and disablement )
• Two monitored conventional alarm circuits ( always driven as a pair )
• Global volt free fault and fire changeover contacts
• Monitored Auxiliary 24V output
• Programmable Remote Alarm input
• Programmable Class Change input
• Programmable Sound Alarms button operation
• Programmable conventional alarm output group
• Global walk test feature
• Alarm, zone, buzzer and Fire Link disablement
• Programmable T1 and T2 output group delays ( output group specific )
• Programmable pulsing alarm timeout ( global )
• Programmable coverage volume for EN54-23 compliant VAD devices
• Coincidence operation ( to EN54 part 2 type C dependency )
• Global fire relay can operate on automatic, manual or all types of alarm
• Alarm counter ( maximum of 9999 alarms )
• 300 event fire and non-fire historic logs
• Output groups may be programmed to be alarm or control type
• Loop devices may be individually programmed to be non-latching
• Programmable volume on loop sounders note1
Note 1: The loop sounder must have programmable volume capability
N93-572-88 Issue 12 NH Page 8 of 52 © Protec Fire Detection plc 2020
4.0 6100 Cabling Requirements
4.1 General
All wiring associated with the system must conform to the current I.E.E Regulations, and cabling must conform to the relevant BS specifications. ECA recommended cable separation for electromagnetic compatibility in buildings must be followed.
Where screened cables are used it is important to ensure that screen continuity is maintained between cable segments. Any screen wiring in the panel enclosure must be sleeved and securely bonded to the earth points provided.
For further information on cables, wiring and other interconnections please consult clause 26 of
BS 5839 Part 1 : 2017 ( or any document superseding it ).
4.2 Mains Input Rating Label
The mains rating label is located on the inner door of the 6100 and should be consulted before starting installation. The label details the working voltage, frequency and maximum current of the
6100.
4.3 Mains Wiring
The 6100 requires a mains supply exclusive to the panel that uses fixed three-core wiring
( between 0.75mm
2 and 2.5mm
2 ) which is fed from a double pole isolating fused spur, fused at 3A.
Unauthorised operation of the mains supply must not be allowed and the fused spur should be labelled
“ FIRE ALARM PANEL: DO NOT SWITCH OFF ” .
Mains wiring must be segregated from all other system wiring. The wiring clamp must be used to secure the incoming cables.
4.4 Alarm Circuit Wiring
Two alarm circuits are provided which are always driven simultaneously. Each alarm output can provide 100mA of current and must be terminated with the correct value end of line resistor, even if the alarm output is not used.
The gauge of the alarm circuit wiring must be chosen such that the volt drop along the wiring does not exceed specified limits. The maximum wiring resistance may be calculated using the following formula.
R
wiring_max
= ( 20.5 – V
device min
) / ( I
device max
)
Where R wiring_max
is the maximum resistance of the alarm circuit wiring ( both conductors )
V device min
is the minimum Voltage the alarm circuit devices are specified to work down to
I device max
is the maximum total current that will be drawn on the alarm circuit
For example if alarm devices are specified to work to a minimum of 16V and the maximum alarm circuit current is 80mA, the maximum alarm cable resistance is 56.25Ω ( 28.13Ω per conductor ).
To achieve an enhanced drive capability of 200mA it is permitted to connect both alarm circuits in parallel, in which case the end of line resistor must be reduced. Please see section 10.0 for end of line values.
Devices connected to the alarm circuits must be polarised and suppressed.
Alarm devices must not be connected on spurs from the main alarm circuit wiring as a spur will not be monitored for open circuit faults.
N93-572-88 Issue 12 NH Page 9 of 52 © Protec Fire Detection plc 2020
4.5 Fire Link Wiring
The fire link output may be used to signal an alarm condition to a remote monitoring station.
The fire link output is monitored for open and short circuit cable faults and, when used, must only connect to the Protec 6100 fire link end of line module. If the fire link output is not used it must be terminated locally in the panel ( consult section 10.0 for details ).
Suitably fire rated, screened cable must be used to connect the 6100 to the remote end of line module. The resistance of the cabling must be no more than 25Ω in total ( 12.5Ω per conductor ).
4.6 Addressable Loop Wiring and Devices
The 6100 loop wiring carries both power and data to the loop devices. In order for the system to operate correctly under all conditions the voltage drop along the loop must be kept within specified limits.
The voltage drop on the loop is a function of both the resistance of the loop cabling
( determined by the gauge of cable and the length of the loop ) and the current that the loop must carry
( determined by the number and type of loop devices connected ).
The loop wiring must be wired from the panel terminals marked ‘LA+ and LA-’ round all the loop devices and reconnected at the panel terminal marked ‘LB+ and LB-’ ( see figure 4.0 ).
Most Protec loop devices incorporate an integrated short circuit loop isolator. No more than 20 loop devices must be connected between isolators, and a loop isolating device must always be used on a zone boundary ( a Manual Call Point is usually used for this purpose ).
To comply with EN54-2 a Manual Call Point must be located next to the 6100, so that any system delays ( if programmed ) will be overridden by activation of the Manual Call
Point at access level 1.
In the case of screened cables always ensure that individual segments have earth continuity ( cable screen and / or drain wire is classed as earth ), and that the earth wiring does not touch any other connections, or any other earthed points.
Figure 4.0 Typical 6100 loop configuration
LA+
LA-
LB+
LB-
N93-572-88 Issue 12 NH Page 10 of 52 © Protec Fire Detection plc 2020
Table 4.0 shows the general characteristics required for the loop cabling.
Table 4.0 General loop cable requirements
Recommended Cable Type
Twin core twisted pair or twin core screened ( screen must be connected to earth ). Four core cable must not be used.
Recommended Cable Size 1.0mm
2 to 2.5mm
2
Maximum Cable Resistance
16Ω per conductor ( dependent on loop volt drop calculations )
Maximum Cable Capacitance 0.22µF ( 220nF ) per km between conductors
Maximum Cable Distance 1.5km ( dependent on loop volt drop calculations )
Table 4.1
Total loop load in alarm
(mA)
50
100
150
200
250
300
350
400
450
500
550
600
Total loop load in alarm
(mA)
50
100
150
200
250
300
350
400
450
500
550
600
Guide to required cable size vs average loop current
1.0
1.0
1.0
1.0
1.0
500
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
550
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
600
1.0
1.0
1.0
1.0
1.0
1.0
650
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.5
Loop Length ( meters )
700
1.0
1.0
750
1.0
1.0
800
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.5
1.5
1.0
1.0
1.5
1.5
1.5
1.0
1.0
1.5
1.5
1.5
850
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
900
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
950
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
1.0 1.0 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
Loop Length ( meters )
1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
N/A
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
N/A
2.5
2.5
2.5
2.5
2.5
2.5
N/A
N/A
N/A
1000
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
N93-572-88 Issue 12 NH Page 11 of 52 © Protec Fire Detection plc 2020
5.0 Insulation Testing of Cabling Prior to Connection
Before connecting any external cables to any field device or the 6100, tests should be carried out using a 500V
DC insulation tester ( ‘ Megger ® ‘ ). If tests are performed the insulation readings between each cable core, and each cable core and earth must be greater than 10M W .
The 6100 or associated devices must not be connected to any cables when high voltage insulation tests are being performed on the cabling. The cabling must be completely discharged prior to connection to the 6100. Equipment connected to the cabling during insulation tests will be damaged by the high voltages used, invalidating any warranty.
N93-572-88 Issue 12 NH Page 12 of 52 © Protec Fire Detection plc 2020
6.0 Installing the 6100
The 6100 may be surface or flush mounted ( no extra bezel is required when flush mounting ).
The 6100 circuit board is fully enclosed within a sealed control PCB housing. The control PCB housing must never be opened. If the 6100 requires repair it must be sent back to the Protec factory.
The batteries are fully accessible with the control PCB housing removed from the back-box.
The 6100 must be located internally in an area that is not subject to dampness, direct sunlight, extremes of temperature or physical abuse. The environmental limits are given in section 10.0.
6.1 Unpacking
Carefully open the cardboard carton ( do not use a sharp object ) and remove the packing fitments, manuals and spares pack.
6.2 Removal of the Door
Remove the 6100 from the packaging then, using a T15 Torx® type security tool, unscrew but do not withdraw the fixing screw from the bottom of the panel housing front as shown in figure 6.0 stage 1.
( stage 1 ).
Slide the door upward from the bottom and pull away as shown in figure 6.0 ( stages 2 and 3 ).
Put all removed parts in a safe, dry place.
Figure 6.0 Removing the 6100 door
3
2
N93-572-88 Issue 12 NH
1
Page 13 of 52 © Protec Fire Detection plc 2020
6.3 Disconnection of the Fire Brigade Panel (FBP) Connections
If the 6100 is equipped with the optional Fire Brigade Panel control interface ensure that the ribbon cable and earthing cable are disconnected from the rear of the controller as shown in figure 6.1.
Figure 6.1 Removing the FBP control interface connections
N93-572-88 Issue 12 NH Page 14 of 52 © Protec Fire Detection plc 2020
6.4 Removal of the Control PCB Housing
Before handling the 6100 panel control PCB housing it is important that any operatives discharge themselves of any static charge that may have built up. This can be done by momentarily touching a solid earth point ( a non-painted part of a radiator, for example
).
The Control PCB housing is a sealed unit and must not be opened. Tampering with this unit will invalidate the warranty. If the unit becomes faulty it must be returned for repair.
Unscrew and remove the four mounting screws on the control PCB housing. Carefully lift away the control PCB housing from the plastic enclosure. See figure 6.2.
The 6100 control PCB housing and all screws should be stored in the cardboard carton away from the place of work where they will not get damaged.
Figure 6.2 Removal of the 6100 Control PCB Housing
N93-572-88 Issue 12 NH Page 15 of 52 © Protec Fire Detection plc 2020
6.5 Preparing the Mounting Position and Cable Entries
Use the dimensions shown on the interior rear face of the 6100 back-box in conjunction with a spirit level to mark out the fixing locations for the panel. Drill and plug the mounting holes just marked.
Using a suitable tool carefully remove the rear panel knockouts at the required cable entry positions and mount the enclosure in position whilst feeding the cables into the enclosure via suitable glands.
The mains cable entry position must be segregated from all other system cabling, a reserved knock-out is provided specifically for this purpose.
A four way brass earth block is supplied with the 6100. Three locations are provided for this in the
6100 back box. This allows the best location to be selected depending on wiring entry requirements.
Choose the location then clip the earth block into the back box, ensuring it is securely fitted.
6.6 Installing the Standby Batteries
The 6100 is designed to house two 12V 3.3Ah Valve Regulated Lead Acid ( VRLA ) batteries. These fit into the back-box and must be secured with the two plastic tie-wraps provided ( as shown in figure
6.3 ).
Only use batteries supplied or recommended by Protec. The internal charger has been specifically designed to maintain the charge voltage at an optimum level for these batteries over the entire operating temperature range in order to maximise the life of the batteries.
Figure 6.3 Installation of 6100 standby batteries ( shown with the lid and control PCB housing removed )
Tie-Wraps must be used to secure the batteries
N93-572-88 Issue 12 NH Page 16 of 52 © Protec Fire Detection plc 2020
6.7 Connecting the Standby Batteries
The two standby batteries must be connected in series with the battery link provided. Then, observing correct polarity ( red lead to the positive of one battery and black lead to the negative of the other battery ), carefully push the spade connectors of the 6100 battery leads onto the relevant battery terminals ( illustrated in figure 6.4 ).
Please note that at this point the 6100 will not power up until the mains supply is connected.
Figure 6.4 Standby battery connections
RED battery lead
Observe polarity when connecting the battery leads
BLACK battery lead
N93-572-88 Issue 12 NH Page 17 of 52 © Protec Fire Detection plc 2020
6.8 Refitting the Control PCB Housing
Ensure that all cable earth connections are sleeved to insulate them and then securely connect them to the brass earth terminals in the back-box.
Carefully route the battery leads ( from the rear of the control PCB housing ) down between the two batteries.
If the 6100 is equipped with a fire brigade panel controller, ensure the ribbon cable connected to the back of the control PCB housing is located over the top of the control PCB housing when refitting into the back-box.
Replace the control PCB housing ( a reversal of removal ), ensuring it is pushed flush to the back box and that the battery leads do not get trapped. Secure with the four screws removed previously, taking care not to over tighten the screws.
6.9 Connecting the Addressable Loop Wiring
The 6100 loop wiring must always be connected as a complete loop ( LA + and LA - connections ) to each device, then back to the panel again ( LB + and LB - connections ). Please see figure 6.5 and refer to figure 4.0.
Figure 6.5 Loop Connection Details
Outgoing loop connections
Return loop connections
6.10 Connecting the Conventional Alarm Circuit Wiring
The 6100 can drive two conventional alarm outputs. These must be connected as shown in figure
6.6. Unused outputs must still be terminated with an end of line resistor locally in the panel.
Figure 6.6 Conventional Alarm Output Connection Details
N93-572-88 Issue 12 NH Page 18 of 52 © Protec Fire Detection plc 2020
6.11 Connecting the Fire Link Wiring
The 6100 is equipped with an output to signal to a remote monitoring station. This output is monitored for cable faults and must only be connected to the Protec Fire Link End of Line Module
( see appendix 1 for stock code ). The End of Line Module must be fitted in the remote equipment, and not in the 6100. If the fire link end of line module is not required, the fire link output must still be terminated with an end of line resistor.
Figure 6.7 Fire Link Connection Details
6.12 Connecting the Auxiliary Wiring
The auxiliary wiring must now be connected if required. The auxiliary wiring comprises the class change input, remote alarm input, auxiliary 24V supply output, global fire contacts and global fault contacts. Note that these connections are optional and if not used do not require any termination.
Figure 6.8 Auxiliary 24V Output Details
Figure 6.9 Remote Alarm Input Wiring
Figure 6.10 Class Change Input Wiring
N93-572-88 Issue 12 NH Page 19 of 52 © Protec Fire Detection plc 2020
6.13 Connecting the Mains Cabling
Isolate the incoming mains supply by ensuring the fused double pole isolator is in the
‘OFF’ position.
Pay particular attention that the incoming mains cable is segregated from all other cables within the 6100 enclosure.
Ensure the incoming earth cable is firmly connected to the Main PCB ( see figure
6.11 ), and that the earth cable from the Main PCB is securely connected to the brass earth terminals within the back-box.
The mains wiring must now be restrained using the clamp provided to secure the mains cables to the control PCB housing ( see figure 6.12 ). The restraining clamp must be supported at the rear when the two screws are being tightened.
Figure 6.11 Power Supply Terminal Details
Figure 6.12 Mains wiring connections
Main PCB to earth block cable
Mains wiring clamp
N93-572-88 Issue 12 NH Page 20 of 52 © Protec Fire Detection plc 2020
6.14 Connecting the Fire Brigade Panel Controller
If the 6100 is equipped with the optional Fire Brigade Panel control interface ensure that the ribbon cable and key-switch earthing cable are re-connected to the rear of the controller as shown in figure
6.13.
Figure 6.13 Reconnecting the Fire Brigade Panel Connections
6.15 Re-fitting the Door
Before replacing the door ensure all mains, loop, alarm and auxiliary wiring has been completed and will not foul the door when it is refitted.
Replace the plastic door by raising the door and placing flush to the back-box of the panel ( figure 6.14 step 1 ). Slide the door down and ensure it pushes fully home into the back box ( figure 6.14 step 2 ).
Finally screw in the fixing screw, taking care not to over tighten it ( figure 6.14 step 3 )
Figure 6.14 Refitting the 6100 door
1
2
3
6.16 Switching the Mains Power On
Switch the fused isolator to the ‘ON’ position. The green ‘Power’ indicator will illuminate and, assuming all other connections are correct, the 6100 should show one fault on the display ( a ‘panel reset ‘ fault
). The 6100 is now ready to be programmed and commissioned.
N93-572-88 Issue 12 NH Page 21 of 52 © Protec Fire Detection plc 2020
7.0 Commissioning the 6100
The 6100 can be commissioned in a basic manner by using the menus, or more extensively using the Windows programming software. It is recommended that the Windows software is used ( for a list of compatible PC hardware and operating systems please consult the 6100 programming manual ).
It has been assumed that the time and date have been set ( consult the user manual for details of how to do this ).
7.1 Terminology
Loop input devices ( Detectors, Manual Call Points, MIP’s etc ) are programmed into input groups and zones .
Loop output devices ( Sounders, CCO’s etc ) are programmed into output groups .
How an activation from a device in a particular input group triggers output groups is determined by how the panel is programmed to execute it’s cause and effects sequences ( in the matrix ).
Output groups are set to either Continuous ( C ), Warble ( W ), Pulsed ( P ) or Off ( O ), operation and activation is strictly by precedence ( continuous, warble, pulsed and off. In that order ).
7.2 Loop Device Input Group, Output Group and Zone Programming
Loop input devices must be programmed with an input group and zone appropriate to the cause and effects sequences required.
31 input groups are available for loop devices ( please note that, if enabled, the ‘Remote Alarm ‘ and
‘ Class Change ‘ inputs occupy inputs groups 31 and 30 respectively which cannot then be used by other input devices ). Input group 32 is reserved for the Sound Alarms button.
Zone numbers range from 1 to 32 ( inclusive ).
Loop output devices must be programmed with an Output Group ( 1 to 32 inclusive ) appropriate to the cause and effects sequence required.
7.3 Non latching Loop Devices
Loop devices may be individually programmed as non-latching. This means that when that device returns to normal after having been in alarm the 6100 will automatically reset ( assuming no other devices have entered the alarm condition ).
An activation from a non-latching device does not activate the global fire contacts.
Devices programmed to be non-latching usually need to be set as non latching on the device itself
( please consult the relevant loop device datasheet for details ).
N93-572-88 Issue 12 NH Page 22 of 52 © Protec Fire Detection plc 2020
7.4 Loop Device Class Programming
Loop devices may be programmed to belong to a certain class. The currently available class options are:
Automatic Class
Standard detection devices (for example, optical smoke detectors or heat detectors).
Manual Class
Manual Call Points are programmed as manual class. When activated, devices programmed as manual class will override any programmed system delays.
Silence, Reset, IReset, Sound Alarms and Accept Class
Loop devices programmed into any of these classes will mimic the relevant 6100 button press when activated. The loop device itself must be set to non-latching, but not programmed as non-latching on the 6100.
Invisible Switch Class
Loop input devices may be programmed to be ‘Invisible Switch’ class. The loop device itself must be set to non-latching, but not programmed as non-latching on the 6100.
Invisible switch class devices can trigger input groups and activate output groups via the cause and effect matrix but, unlike Automatic and Manual class devices, do not activate any panel indications, internal buzzer, fire link outputs or global fire contacts.
Disable Control Output Groups Class
Loop input devices may be programmed to be ‘Disable Control Groups’ class. The loop device itself must be set to non-latching, but not programmed as non-latching on the 6100.
Disable Control Output Groups class devices, when active, disable output activations to loop devices assigned to control type output groups. Devices in alarm type output groups still operate.
Disable Output Group 31 and 32 Class
Loop input devices may be programmed to be ‘Disable Output Group 31’ (or 32) class. The loop device itself must be set to non-latching, but not programmed as non-latching on the 6100.
Devices programmed to class ‘Disable Output Group 31’ (or 32) disable activations to output group
31 (or 32) when activated. This may be found to be an advantageous feature in certain installations where output devices must be temporarily disabled under certain conditions.
N93-572-88 Issue 12 NH Page 23 of 52 © Protec Fire Detection plc 2020
7.5 Loop Device Sensitivity Programming
This setting is only applicable to automatic detectors and allows two detection sensitivities to be programmed. The 6100 offers a range of sensitivities that can be used to tailor the response of the detector to suit individual site conditions. The 6100 supports the following sensitivities.
Table 7.0
Programmed
Sensitivity
Automatic Detector Sensitivity Setting Options
Typical Applications
NONE Used for non-detector types ( interfaces, MCP’s etc )
OFFICE
BEDROOM
ENHANCED
NO OP
PRISON
For use in general environments ( offices, for example )
Incorporates an anti-steam algorithm for use in bedrooms
Enhanced sensitivity for use in clean room environments
Turns optical-heat devices into heat only devices
Note: The spacing distance for heat detectors must be adopted for the loop device if this sensitivity is used
Prison Cells
7.6 Loop Sounder Volume Programming
Individual loop sounder devices can have their volume level programmed. Volume settings of high, medium and low are supported ( please consult the datasheet for the individual loop sounder product to ensure it can support programmable volume ).
N93-572-88 Issue 12 NH Page 24 of 52 © Protec Fire Detection plc 2020
Off
Off
Off
Off
Off
Off
Ö
Ö
7.7 Talking Sounder Programming Considerations
The 6100 supports Protec talking sounders and special consideration must be given to them when programming. Talking sounders contain several pre-set messages that the control panel activates when required.
Talking sounders and non-talking output devices must not be mixed in the same output groups .
Talking sounders have a message synchronisation rate that is determined by programming at commissioning time. The typical synchronisation time is 20 seconds, which is sufficient to allow the longest standard audio message to be reproduced.
When the pulsing electronic bell sound is specified from a talking sounder ( using setup features available in the Windows programming software ) the standard system pulse rate is adopted.
Table 7.1 details how talking sounders operate with various panel activations.
Table 7.1 Talking Sounder Programming table
Fire Activation Walk Test Activation Class Change
Ö
X
X
Ö
X
X
Ö
X
X
Off
Ö
Off
Ö
Off
Ö
Off
Ö
C
M1
M5
M15
M13
P
M2
M6
M14
M12
As above
W
M3
M9
M1
M5
M11
C P W C
Same as Fire Activation M15
M4
M7
P
M14
As above
W
M3
M5
M3
M5
M3
M5
M1
M2
M3
M4
M5
M6
M7
M8
M9
M10
M11
M12
M13
M14
M15
Female Evac 1
Female Alert
Female Evac 2
Female Test
Male Evac
Male Alert
Male Test
Bell
No message
(used to mute the sounder)
Unused
(defaults to M1)
Electronic Warble
Electronic Alert
Electronic Continuous
Intermittent Bell
Continuous Bell
Key
Ö
Off
X
Option selected
Option not selected
Option selection does not matter
Ö
Notes
1. The Class Change messages do not function in a Fire Alarm condition.
2. The pulsing rate for message 14 is determined by the Pulse Times programmed.
Table 7.2 details how talking sounders operate with various panel activations with Dutch software.
Table 7.2 Talking Sounder Programming table ( For Dutch panels only )
Sound Alarms
C
(User code entered)
P W
Fire Activation
C P W C
Walk Test
Activation
P W C
Class Change
P W
Ö
Key
Ö
Off M1 M2 M3
Option selected
M1 M2 M3 M4 M15 M14 M3
M10
M11
M12
M13
Off Option not selected
M14
M15
Notes
1. The Class Change messages do not function in a fire alarm condition.
2. The pulsing rate for message 14 is determined by the pulse times programmed.
3. Pressing Sound Alarms while in engineer or advanced engineer code produces message M4. If ‘Sound Alarms’ is pressed during a fire condition then test message M4 will replace the fire message.
4. Pressing Sound Alarms while in user exchange code produces message M7 however if a fire event occurs then
‘Sound alarms’ is cancelled and the appropriate fire message M1, M2 or M3 is output. If ‘Sound Alarms’ is pressed during a fire condition then, to avoid replacing the fire message with message M7, the output message will be determined by the cause and effect programming of the fire event and the sound alarms input group.
M1
M2
M3
M4
M5
M6
M7
M8
M9
Fire Message
M1
M1
Test Message
M1
M1
Health and Safety Message
Bell
No message
(used to mute the sounder)
M1
Electronic Warble
Electronic Alert
Electronic Continuous
Intermittent Bell
Continuous Bell
N93-572-88 Issue 12 NH Page 25 of 52 © Protec Fire Detection plc 2020
7.8 Fire Link Operation
Normal Operation
The fire link output activates within one second of the panel entering the alarm state ( if a Fire Link delay has not been programmed ).
The following 6100 activation’s will not activate the Fire Link:
• Activation from a device programmed as Silence, Reset, IReset, Sound Alarms, Accept or
Invisible Switch class
• Activation from a device in a zone that is programmed in walk test mode
• Activation from the Remote Alarm or Class Change inputs
Delayed Operation and Search Time
Using the Windows commissioning software the fire link activation can be programmed to be delayed by a fixed time. Upon a device activation the fire link delay timeout will begin, the fire link output then activates upon expiration of the delay. The maximum fire link delay time is 10 minutes.
A ‘search time’ of 0 to 10 minutes may also be programmed which is instigated by pressing the Mute
Buzzer button at access levels 2 or 3 during the fire link delay. This gives an extra timeout before activation of the Fire Link occurs ( search time can only be performed once until reset ).
Note that the total Fire Link delay timeout is limited to 10 minutes, even if the Fire Link delay plus the search time exceeds 10 minutes.
An activation of a device programmed as manual class will override any Fire Link delay currently running.
Table 7.3 Effects of Panel Programming on Fire Link Operation
Fire Link
Disabled
Fire Link
Delayed
Activation from a Non latching
Device
Activation from a device in walk test zone
1 st
knock coincidence
2 nd knock coincidence and Manual
Class
Fire Link
Disabled
Does not activate
Does not activate
Does not activate
Does not activate
Does not activate
Does not activate
Fire Link Delayed
Does not activate
Activates after delay time
Activates after delay timeout
Does not activate
See Note 1 See Note 2
Activation from a
Non latching
Device
Activation from a device in walk test zone
1 st
knock coincidence
2 nd knock coincidence and
Manual class
Does not activate
Does not activate
Does not activate
Does not activate
Activates after delay time
Does not activate
See Note 1
See Note 2
Activates immediately
Does not activate
See Note 1
See Note 2
Does not activate
Does not activate
Does not activate
Does not activate
See Note 1
Does not activate
See Note 1
See Note 2
See Note 2
Does not activate
See Note 2
See Note 2
Note 1:
The first activation to trigger the Fire Link takes precedence. For example, if an non-coincidence activation begins a Fire Link delay of 5 minutes, a first knock coincidence activation with a delay of 3 minutes will not override the original timeout.
Note 2:
The Fire Link will activate immediately if this feature has been enabled during commissioning. If the feature has not been enabled, then the current Fire Link delay time will apply.
N93-572-88 Issue 12 NH Page 26 of 52 © Protec Fire Detection plc 2020
7.9 Global Fire Contact Operation
The 6100 controls a set of volt free changeover contacts that can be programmed to operate under various panel activation conditions. The fire contact connections are shown on the terminal label in the non fire state.
The contacts can be programmed to activate upon receipt of an activation from automatic class devices only, manual class devices only or both.
Devices set as anything other than automatic or manual class, programmed as non-latching, or in a walk test zone will not activate the contacts.
7.10 Global Fault Contact Operation
The 6100 will operate the global fault contacts under any fault condition ( including when the panel is un-powered ). The fault contacts connections are shown on the terminal label in the non fault state.
7.11 Remote Alarm Input Operation
The Remote Alarm input can be enabled and disabled by using the 6100 commissioning software.
When enabled a remote alarm activation input triggers programming associated with input group 31.
When the remote alarm input is enabled, input group 31 is not available for use by any other input device.
When the Remote Alarm input is disabled input group 31 becomes available for use as normal.
A remote alarm activation does not activate the Fire Link, or Global Fire contacts and can be configured to activate control output groups, or not.
The Remote Alarm input can also be configured ( using the Windows commissioning software ) to function as a Day / Night timer input. In this configuration the system switches the sensitivities of all automatic detectors to night mode when the remote alarm input is short circuited.
7.12 Class Change Input Operation
The Class Change input can be enabled and disabled by using the 6100 commissioning software.
When enabled a class change input activation triggers programming associated with input group 30.
When the class change input is enabled, input group 30 is not available for use by any other input device.
When the Class Change input is disabled input group 30 becomes available for use as normal.
Outputs will activate as programmed for input group 30 in the matrix, with the exception of talking devices which activate as shown below:
Activations from loop devices or the Remote Alarm input always override a Class Change activation.
Table 7.4 Class Change Input Operation of Talking Sounders
Matrix / panel programming Output from talking sounder when class change active
Continuous Continuous electronic bell sound will be reproduced
Pulse
Warble and ‘Male Voice’ option disabled
Warble and ‘Male Voice’ option enabled
Off
Pulsing electronic bell sound will be reproduced
The female evacuation message will be reproduced
The male evacuation message will be reproduced
Does not activate
N93-572-88 Issue 12 NH Page 27 of 52 © Protec Fire Detection plc 2020
7.13 Conventional Alarm Output Operation
The 6100 provides two conventional alarm outputs designed to drive 24V dc alarm devices. The alarm outputs are always driven as a pair and cannot be controlled separately.
The conventional alarm output can be programmed to follow any one of the 32 output groups, the operation is shown in table 7.5.
The conventional alarm outputs cannot be mapped to output groups containing talking devices.
Table 7.5 Conventional Alarm Output Operation
Output Group Activation Conventional Alarm Activation
Continuous
Pulse
Warble
Off
Activates
Pulses in accordance with system pulse times
Activates
Does not activate
7.14 Output Group Type
Each output group can be individually set to be of type 'alarm', or 'control'. The operational differences between the two types are detailed in table 7.6.
Table 7.6
6100 Trigger Source Alarm Output Group Control Output Group
Manual or Automatic class Loop device
Sound Alarms
Activates as programmed
Activates as programmed
Remote Alarm
Class Change
6100 Silenced
6100 Reset
Activates as programmed
Activates as programmed
Turns off current activation
Turns off current activations and resets panel state
Activates as programmed
Does not activate
Setup to activate control groups
Activates as programmed
Setup not to activate control groups
Does not activate
Activates as programmed
No change to current activation
Turns off current activations and resets panel state
7.15 Output Group Delays (T1 and T2)
Each output group can have two delays introduced by appropriate programming in the Windows PC software. Delay 1 is termed 'T1' and delay 2 is termed 'T2'.
When an output group is activated by the cause and effects programmed into the 6100, the activation of the relevant output group can be delayed by up to 10 minutes for T1, and up to 20 minutes for T2. The T1 delay is introduced automatically, and T1 is replaced by T2 delay (if T2 is larger than T1) if the 'Mute Buzzer' button is pressed at access level 2 or 3 during an alarm condition.
The usual reason for using T1/T2 programming is to delay activation of sounders until the premises management reach the 6100 (T1 delay) and instigate a search time (T2 delay). The source of the alarm can then be investigated, and the panel reset if required.
T1/T2 delays will be cancelled by activation of a manual class device, or if the 6100 is in night mode and the 'Cancel Delays in Night Mode' option has been selected in the
Windows software. Delays are not used when in 'Walk Test' mode.
N93-572-88 Issue 12 NH Page 28 of 52 © Protec Fire Detection plc 2020
Figure 7.0 – 6100 Engineer (Access level 3) Menu Structure
View Faults
Refer to User Manual
View Disablements
Refer to User Manual
Clear System Faults
Refer to User Manual
Test Indications
Refer to User Manual
Program Zone Options
Refer to User Manual
Disable Options
Refer to User Manual
Set Date and Time
Refer to User Manual
View Alarm Count
Refer to User Manual
View Fire Event Log
Refer to User Manual
View General Event Log
Refer to User Manual
Log Loop Devices
See Section 7.17
Program Address Data
See Section 7.18
Exchange Devices
See Section 7.19
Disable a device
See Section 7.20
Device RVAV
See Section 7.21
Edit Device Text
See Section 7.22
Edit Zone Text
See Section 7.23
Clear Fire Event Log
See Section 7.24
Clear General Event Log
See Section 7.25
Display Loop Device Data
See Section 7.26
Display Diagnostic Data
See Section 7.27
Display Panel Details
See Section 7.28
Connect to PC Using USB
See Section 7.29
Restart System
See Section 7.30
Exit Menu
Refer to User Manual
N93-572-88 Issue 12 NH Page 29 of 52 © Protec Fire Detection plc 2020
7.16 Programming the coverage volume of Visual Alarm Devices (VADs)
The coverage volume of EN54-23 compliant VADs may be set up on a device specific basis by appropriate programming in the Windows PC software.
This feature allows the individual coverage requirements of loop VADs to be tailored for the specific installation environment, which results in optimised system operating currents.
7.17 Logging and Mapping Loop Devices
Logging and mapping loop devices is the process the 6100 uses to work out how many, and what type of devices are connected to the loop, and where they are in relation to each other.
Before logging always ensure there are no loop faults on the panel
Logging and mapping could take up to 6 minutes, depending on the loop configuration
The 6100 WILL NOT detect fires during the logging and mapping phase
Logging
During the logging phase the 6100 drives the loop from sides A and B, all relevant devices connected to the loop are logged and stored in memory ( devices will not be logged if the 6100 does not support the device type, or the software version of the device is not supported by the 6100 ).
When the 6100 has logged a loop device it searches the existing panel loop device data to see if the loop device is already logged and allocated on the system, if it is, the software version of the loop device is updated in memory. By doing this site files that have been created using a device serial number barcode scanner ( which does not contain the device software version ) and downloaded using the PC commissioning software are completed. The resulting ‘complete’ site file must always be uploaded from the panel to the PC and stored for backup.
Mapping
During the mapping phase the loop drives from side A only. Loop isolators on devices are sequentially closed and each group of devices between isolators are allocated an ‘isolator node number’. As devices are sequentially mapped, data stored during the logging phase is checked, if the mapped device was not logged originally the mapping process will fail. Device loop isolators are closed sequentially until all logged devices have had their isolators closed, after which the panel has complete information of how the system is configured.
Please note, even if the mapping process fails, the logging data stored in memory may still be used to allocate loop devices onto the 6100, even though the isolator node data may not be present.
At the LOG LOOP DEVICES menu press the ¿ key to begin the loop logging sequence ( as shown in figure 7.1 and 7.2 )
Line 1 of the display indicates the logging and mapping progress, and has the following sections.
RESETTING LOOP
Displayed when the 6100 is resetting the loop to make sure all loop devices are ready to be logged.
LOGGING LOOP
Displayed when the 6100 is logging the loop devices.
LOGGING COMPLETE
Displayed when the 6100 has finished logging the loop devices and is preparing to map the loop devices. Logged device data is now in temporary memory.
MAPPING LOOP
Displayed when the 6100 is mapping the sections of the loop separated by loop isolators.
N93-572-88 Issue 12 NH Page 30 of 52 © Protec Fire Detection plc 2020
MAPPING SUCCESS
Displayed when the 6100 has successfully logged and mapped the loop. Mapping data is now in memory ready for loop devices to be allocated.
MAPPING FAILED
Displayed if the 6100 could not successfully log or map the loop. This could be because there are more than 192 devices on the loop.
Figure 7.1 6100 loop logging display
This field indicates the number of loop devices logged
Row 1 displays the logging process
LOGGING LOOP
Logging
=
001
(
000
)
MAPPING
=
000
ISOL 000 CLOSED 000
These fields are not used during logging
Figure 7.2 6100 loop mapping display
MAPPING LOOP
Logging
=
029
(
000
)
MAPPING
=
001
ISOL 001 CLOSED 001
This field indicates the number of loop devices seen during the mapping phase
This field indicates the number of loop Isolators detected
This field indicates the number of loop isolators closed during the mapping phase
This field indicates the change in the number of logged devices compared to those stored in the panel
N93-572-88 Issue 12 NH Page 31 of 52 © Protec Fire Detection plc 2020
7.18 Programming Loop Device Address Data
If new loop devices are to be allocated the loop must be logged and mapped before entering this menu.
The loop devices temporarily stored during logging and mapping must be allocated certain operational parameters before the 6100 can process data from them. The PROGRAM ADDRESS
DATA menu is used to achieve this.
At the PROGRAM ADDRESS DATA menu option press the ¿ key. A flashing cursor indicates which parameter is currently being edited. Note that choices are spread over multiple screens.
Also note that not all parameters apply to all device types ( for example sensitivity setting is meaningless for a loop sounder, and volume is meaningless for a heat detector ) non applicable device parameters can be still be set up but are not processed by the 6100.
With reference to figure 7.3
Selecting a loop address to edit its parameters
Using the ◄ or ► keys choose the loop ADDRESS to be edited.
To allocate a loop device serial number to the address
Use the ▲ and ▼ keys to select SNUM field.
Using the ◄ or ► keys link a currently unallocated loop devices to this address.
To de-allocate a device from this address select a SNUM of 000000, this then makes the loop device free to swap to another address or it can be left de-allocated ( the 6100 will not process a de-allocated device ).
To set the zone number for the address
Use the ▲ and ▼ keys to select ZONE field.
Use the ◄ or ► keys to set the zone number for the address, valid zone numbers are 1 to 32 inclusive.
To set address to be latching or non-latching
Use the ▲ and ▼ keys to select STATE field.
Use the ◄ or ► keys to toggle the state between LATCHING and NON LATCHING as required.
Figure 7.3 Program address screen 1
The loop address being programmed
The zone number of the loop address
Address 001 Opt Ht
Snum
Zone e00461
01
+
State Latching
Set-up latching or non-latching here
The loop device serial number currently allocated the address.
• Nothing here means the device is already stored in the memory
• A + means the device is not currently stored in the memory
• A – means the device is stored in the 6100 memory but has not been logged
N93-572-88 Issue 12 NH Page 32 of 52 © Protec Fire Detection plc 2020
With reference to figure 7.4
To set the input group for the address
Use the ▲ and ▼ keys to select INPUT GROUP field.
Use the ◄ or ► keys to set the input group number for the address. Refer to section 7.2 for input group ranges.
To set the output group for the address
Use the ▲ and ▼ keys to select OUTPUT GROUP field.
Use the ◄ or ► keys to set the output group number for the address, valid output group numbers are
1 to 32 inclusive.
To set the volume level for the address
Use the ▲ and ▼ keys to select VOLUME field.
Use the ◄ or ► keys to set the required volume level for the loop sounder. Valid levels are LOW, MED and HIGH.
Figure 7.4 Program address screen 2
Address 001 Opt Ht
Input group
Output group
Volume
01
01
High
With reference to figure 7.5
To set the DAY and NIGHT sensitivities for the address
Use the ▲ and ▼ keys to select the DAY SENSE, or NIGHT SENSE field as required.
Use the ◄ or ► keys to set the required sensitivity level for the address. Refer to section 7.6 for input group ranges.
To set the CLASS data for the address
Use the ▲ and ▼ keys to select CLASS field.
Use the ◄ or ► keys to set the class for the address.
Figure 7.5 Program address screen 3
Address 001 Opt Ht
Day sense bedroom
Night sense office class automatic
Press the ¿ key at any time to store any changes, the 6100 will warn that changes are to be made to the site data and the panel will reset and reboot as shown in figure 7.6.
Figure 7.6 Program address warning display
Warning
Panel will reset and update site data continue
?
Press the ¿ key to accept, or the ◄, ►, ▲ or ▼ keys to decline and remain in the menu. Then, if possible, upload and save the site file on a PC.
N93-572-88 Issue 12 NH Page 33 of 52 © Protec Fire Detection plc 2020
7.19 Exchanging Loop Devices
Exchanging loop devices incorrectly can result in undefined system operation. If in doubt contact your service agent. Loop devices can only be exchanged with other loop devices of the same type. Any exchanged devices MUST be fully tested in all required modes to ensure they are fully operational.
1. Enter the user code supplied with the system and press the ¿ key to access the menus.
2. Scroll to the EXCHANGE DEVICES menu and press the ¿ key. The 6100 is now in exchange devices mode ( figure 7.7 ). Up to 8 loop devices may be exchanged at a time.
3. Remove the device(s) that are to be exchanged and wait for the 6100 to declare them as missing.
4. Add the new device(s) in place of the old ones, ensuring the replacement device is of exactly the same type as the original. Wait for the 6100 to recognise them as added.
5. Press the ¿ key to access the final exchange menu ( figure 7.8 ).
6. Take a note of the serial numbers, loop addresses and device text of the old and new devices.
7. Using the ◄ , ▲, ► and ▼ keys locate old device(s) and swap with corresponding new device(s).
The 6100 will only offer matching types to be exchanged. Update all devices to be exchanged as necessary.
8. Press the ¿ key to proceed to the exchange devices save confirmation as shown in figure 7.9.
9. Press the ¿ key to save the exchanged devices to the panel memory and reset the panel.
Alternatively press the ◄ , ▲, ► and▼ keys to exit this screen and return to the exchange devices display.
F igure 7.7 Exchange Devices Initialisation display
Figure 7.8
Replace existing devices with new
Devices of the
Same type
Exchange Devices display
Figure 7.9
Exchange devices
Old 1A2345 optical new AA5410 optical
Exchange Devices Save confirmation display
Warning
Panel will reset and
Update site date
Continue
?
N93-572-88 Issue 12 NH Page 34 of 52 © Protec Fire Detection plc 2020
7.20 Disabling / Enabling a Loop Device
1. Enter the engineer code supplied with the system and press the ¿ key to access the menus.
2. Scroll to the DISABLE A DEVICE menu and press the ¿ key. See Figure 7.10.
3. Using the ◄ and ► keys select the device address to be disabled / enabled.
The current disablement state of the address is displayed next to the address number, and any programmed address text is displayed on row 3 of the LCD.
4. Press the '▲' key to disable the address, or the '▼' key to enable the address.
Zone disablements take precedence over device disablements. A device that is in a disabled zone cannot be individually enabled. The whole zone must be enabled.
If a device is being taken out of disablement, but is in the alarm state, then the 6100 will display a warning screen and then automatically perform a system reset. This is done to avoid the 6100 immediately entering the alarm state when the device is normalised.
Figure 7.10 Device Disablement Screens
Loop address number
Indicates if the device is currently Enabled or
Disabled
ADDRESS 001 DISABLED
DEVICE TEXT HERE XXX
Device text
N93-572-88 Issue 12 NH Page 35 of 52 © Protec Fire Detection plc 2020
7.21 Loop Device Remote Visual Address Verification ( RVAV )
The DEVICE RVAV menu allows loop devices to be programmed to indicate their address by flashing the indication LED to aid locating the device during commissioning.
Devices set to RVAV operation cannot detect a fire
At the DEVICE RVAV menu press the ¿ key the 6100 will warn that devices programmed to RVAV will not detect fires. The user may then accept this condition by pressing the ¿ key, or decline by pressing the ▲, ▼, ◄ or ► keys.
Figure 7.11 RVAV warning display
Warning
Devices set to rvav
Cannot detect a fire
Continue
?
Figure 7.12 RVAV Range selection display
Device rvav
Start address 000
End address 000
Using the ▲ or ▼ keys toggle the flashing cursor between the start and end address’s to be set to RVAV.
Using the ◄ or ► keys set the address range as required.
Press the ¿ key to accept the range and set all relevant devices into RVAV mode. As shown in Figure
7.13.
Pressing any key while in this screen will cancel RVAV mode and return any devices previously in
RVAV to normal operation.
Figure 7.13 RVAV accepted display
Device rvav
ADDRESS 123
CANNOT DETECT A FIRE
After 10 minutes in this screen any devices set to RVAV mode will automatically time out and return to normal operation.
N93-572-88 Issue 12 NH Page 36 of 52 © Protec Fire Detection plc 2020
7.22 Editing Device Location Text
The Edit Device Text menu allows the user to enter 20 characters of text for any loop device on the
6100.
1. Enter the user code supplied with the system and press the ¿ key to access the menus.
2. Using the ◄ and ► keys navigate to the EDIT DEVICE TEXT menu and press ¿ .
3. Using the ◄ and ► keys navigate to the device address that you wish to edit the text on and press the ▲ or ▼ to enter editing mode ( Figure 7.14 ).
4. Using the ◄ and ► keys navigate through the text characters then ( the character being edited has a ^ positioned underneath it ), then using the ▲ and ▼ keys, edit the character as required.
5. Press the ¿ key to accept the changes and return to the main menu.
Figure 7.14 – Edit Device Text display
Address 001 optical
Device text addRESS 1
^ . . . . . . . . . . . . . . . . . .
7.23 Editing Zone Text
The Edit Zone Text menu allows the user to enter 20 characters of text for each of the 32 zones available on the 6100.
1. Enter the user code supplied with the system and press the ¿ key to access the menus.
2. Using the ◄ and ► keys navigate to the EDIT ZONE TEXT menu and press ¿ .
3. Using the ◄ and ► keys navigate to the zone that you wish to edit the text on and press the ▲ or ▼ to enter editing mode ( Figure 7.15 ).
4. Using the ◄ and ► keys navigate through the text characters then ( the character being edited has a ^ positioned underneath it ), then using the ▲ and ▼ keys, edit the character as required
5. Press the ¿ key to accept the changes and return to the main menu.
Figure 7.15 – Editing Zone Text display
ZONE 28
ZONE TEXT FOR ZONE 28
^ . . . . . . . . . . . . . . . . . .
N93-572-88 Issue 12 NH Page 37 of 52 © Protec Fire Detection plc 2020
7.24 Clearing the Historic Fire Event Log
The CLEAR FIRE EVENT LOG menu function allows the engineer to erase all logged fire events from the 6100 memory.
At the CLEAR FIRE EVENT LOG menu screen press the ¿ key to accept the option.
A warning screen ( illustrated in figure 7.16 ) will be displayed to verify if events should be cleared.
Press the ¿ key to clear the fire event log and return to the main menu.
Press the ▲, ▼, ◄ or ► keys to return to the main menu without clearing the log.
Figure 7.16 Clear Fire Event Log warning display
All fire log data will be permanently deleted
Continue
?
7.25 Clearing the Historic General Event Log
The CLEAR GENERAL EVENT LOG menu function allows the user to delete all logged general events from the 6100 memory.
At the CLEAR GENERAL EVENT LOG menu screen press the ¿ key to accept the option.
A warning screen ( illustrated in figure 7.17 ) will be displayed to verify if events should be cleared.
Press the ¿ key to clear the general event log and return to the main menu.
Press the ▲, ▼, ◄ or ► keys to return to the main menu without clearing the log.
Figure 7.17 Clear General Event Log warning display
All general log data will be permanently deleted
Continue
?
N93-572-88 Issue 12 NH Page 38 of 52 © Protec Fire Detection plc 2020
7.26 Displaying Loop Device Data
The DISPLAY LOOP DEVICE DATA menu allows the engineer to view data relating to any loop device logged onto the 6100. During the commissioning phase this feature may be useful to determine the state of each loop device, the reply values for each channel and any missed replies.
Press the ¿ key at the DISPLAY LOOP DEVICE DATA menu option. The first screen is then displayed.
Using the ◄ or ► keys locate the address of the device to be viewed.
Press the ▲ key to scroll through the data screens for the device.
Press the ¿ key at any time to return to the main menu.
Figure 7.18 Display loop device data screen 1
DEVICE STATE
NORMAL the device has no faults
FAULT the device is in fault
FAILED SETUP the device has failed initialisation
Address 001 opt ht
Snum E00461
(
sht
)
Zone 01
State normal
ADDRESSING MODE
SHT means short addressed
MED means medium addressed
LNG means long addressed
Screen 2 displays the current and the time averaged analogue values for the device.
Rows 2, 3 and 4 of the screen display return values for channel 1, 2 and 3 of the device. If the device does not use all channels the unused channels appear as 000.
Figure 7.19 Display loop device data screen 2
Time Averaged Values
Current Value
CH1
CH2
CH3
T0 T1 T2 T3 Th
058 058 058 058 058
122 122 122 122 122
000 000 000 000 000
Figure 7.20 Display loop device data screen 3
If the device has a Carbon Monoxide detection channel this value is used to determine the operational state of the cell.
Missed scans 01
Co cell ok 060
Eeprom prog passed
Displays how many reply scans have been missed since the counter was last reset. Pressing the ▼ key will reset the counter.
PASSED – the device received and stored its output data successfully
FAILED – the device failed to store its output data
N93-572-88 Issue 12 NH Page 39 of 52 © Protec Fire Detection plc 2020
The two remaining screens show the programming data.
Figure 7.21 Display loop device data screen 4
Input group
Output group volume sw ver
Figure 7.22 Display loop device data screen 5
01
01 high
014
Day sense office
*
Night sense office class automatic
An * indicates which is currently running Day or
Night sensitivity
N93-572-88 Issue 12 NH Page 40 of 52 © Protec Fire Detection plc 2020
7.27 Displaying Panel Diagnostic Data
The DISPLAY DIAGNOSTIC DATA menu allows the engineer to view various values used within the panel, and can be used as an aid when diagnosing problems.
Press the ¿ key to enter the DISPLAY DIAGNOSTICS DATA menu.
Press the ▲ or ▼ keys to move through the data screens.
Press the ¿ key in any screen to return to the main menu.
Screen 1 displays various levels associated with the 6100 power supplies.
Figure 7.23 Typically Panel Diagnostic data screen 1
Indicates the standby battery Voltage
Psu data
Chg volts
=
27
.
4v
Batt volts
=
27
.
0v
Indicates the battery charger Voltage
Screen 2 displays the levels read from the Auxiliary 24V, Firelink End of Line Monitoring and conventional alarm circuits. The numbers in brackets are internal data.
Figure 7.24 Panel Diagnostic data screen 1 ( showing typical values )
Indicates the state of the Auxiliary
24V output.
Indicates the state of the Firelink output.
OK is normal
SC indicates short circuit fault
OC indicates open circuit fault
Auxiliary data
Aux 24v
=
OK
(
861
)
Firelink
Alarm
=
=
OK
OK
(
(
237
266
)
)
OK is normal
SC means short circuit fault
Indicates the state of the
Conventional Alarm outputs.
Screen 3 displays levels associated with the loop driver circuits.
OK is normal
SC indicates short circuit fault
OC indicates open circuit fault
The ‘missed scans’ and ‘seen scans’ numbers may be used to determine the integrity of the loop communications by comparing how many ‘good’ scans versus how many ‘bad’ scans have been detected since the counters were reset ( 20 minutes of detection time is given until the counters reach the end value ).
Figure 7.25 Panel Diagnostic data screen 1
Loop data
Lp ol val
=
415
Displays the number of seen replies when scanning devices
Pressing ◄ or ► clears the count
Missed SCANS
=
00000
SEEN SCANS
=
00100
Displays the number of missed replies to devices when scanned
Pressing ◄ or ► clears the count
N93-572-88 Issue 12 NH Page 41 of 52 © Protec Fire Detection plc 2020
7.28 Displaying Panel Manufacturing Details
The DISPLAY PANEL DETAILS menu function allows the engineer to view the manufacturing details of the panel, which include software versions, panel serial number and the revision of the site file.
Press the ¿ key to enter the DISPLAY PANEL DETAILS menu as shown in figure 7.26.
Press the ¿ key to return to the main menu
Figure 7.26 Display Panel Data display
Sw ver
Sp ver snum sf rev
1
.
25
0
.
00
61000100
0001
N93-572-88 Issue 12 NH Page 42 of 52 © Protec Fire Detection plc 2020
7.29 Connecting the 6100 to a PC
The CONNECT TO PC USING USB menu allows the engineer to connect the 6100 to a PC in order download panel firmware or update and backup the site specific settings. Consult the 6100
Programming Manual for further details.
Before entering this menu ensure that suitable software and drivers are loaded on the
PC and that the USB cable is connected from the 6100 panel to the PC.
When the 6100 is connected to the PC it WILL NOT operate as a fire alarm panel and the power to the loop circuits is removed.
When the USB cable is unplugged the 6100 will automatically reset.
Connect a PC to the 6100 using the USB connection.
Press the ¿ key at the CONNECT TO PC USING USB menu, the 6100 will display a warning screen
( illustrated in figure 7.27 ).
Press the ¿ key to connect to the connected PC.
Press the ▲, ▼, ◄ or ► keys to return to the main menu without connecting to the PC.
Figure 7.27 Connect to PC using USB warning display
Warning
System cannot detect
Fires in this mode
Continue
?
Figure 7.28 Display shown when the 6100 is connected to the PC
Connected to pc warning system can not detect fires
7.30 Restarting the 6100
The RESTART SYSTEM menu function allows the engineer to fully reset the 6100. All loop devices will be re-programmed and re-initialised and any faults will be regenerated.
Figure 7.29 Restart System menu option
Main menu
Restart system
N93-572-88 Issue 12 NH Page 43 of 52 © Protec Fire Detection plc 2020
8.0 Programming the system using the Windows software suite
The 6100 Windows software suite allows all the programming aspects of the 6100 to be accessed.
Please consult the accompanying 6100 Programming Manual for details on how to commission the
6100 using a PC.
9.0 General System Operation
9.1 Panel Initialisation
When the 6100 is powered up, rebooted, or when the RESTART SYSTEM menu option is accepted the 6100 performs a full initialisation.
The initialisation consists of the following tasks and, depending on loop device types, can take up to one minute to complete.
1. Any current faults are cancelled, and any faults are re-generated.
2. All loop device running data used by the panel is reset.
3. Loop devices are reset, then reprogrammed with any relevant site specific data.
4. Automatic class loop devices are initialised as required.
5. The 6100 will log and display a Panel Reset event ( which must be cleared manually ).
9.2 Loop Initialisation
Automatic class loop devices require initialisation in order to calculate various running values used by the Algo-Tec™ algorithms.
Loop devices are initialised whenever the 6100 is initialised, or when a missing loop device is re-connected.
The initialisation process consists of several stabilisation scans ( the exact number depends on the type of loop device ) followed by four scans of each reply channel from the device.
The scan values are checked for stability; each scan value must be within 4 reply counts of any other for that channel. If a ‘noisy‘ device is detected the 6100 issues a ‘Device Failed Setup‘ event for that loop address and the device is not permitted to generate a fire. It will remain in fault until:
1. The 6100 is restarted.
2. The device is removed, seen as missing, then re-connected.
( In this case the indicator on the loop device is illuminated for about three seconds to signal that the device is being initialised )
9.3 Added Loop Devices
The 6100 will process any devices that are stored in its memory. Periodically the 6100 checks for extra loop devices that may have been added. Up to 8 added devices can be detected.
Added loop devices generate a single ‘Added Loop Device‘ event ( only one event irrespective of how many devices are added ). The indicator LED on the added loop device will flash at a rate of approximately 3 seconds on and 3 seconds off to signify it has been recognised by the 6100, but not fully programmed.
To enable them to operate correctly added devices must be logged on to the 6100 in the normal manner, then given a loop address and all relevant programming data as required .
N93-572-88 Issue 12 NH Page 44 of 52 © Protec Fire Detection plc 2020
10.0 6100 Technical Specification
General System Specification
Ambient Temperature Range -5 to 40 degrees Celsius
Humidity Limit 95% RH (no condensation, or icing)
Environment
Meets IP30 if mounted in a dry position that does not exceed the temperature and humidity limits given. DO NOT position in areas subject to direct sunlight.
Mounting
Standby Time ( typical )
3 points surface mount or flush ( no bezel required when flush mounting )
24 Hours, assuming 100mA quiescent current then 700mA in-alarm current for
30 minutes. ( Note that currents are additions of panel, alarm, loop, auxiliary
24V and fire link ). The exact standby time must be calculated and then verified by measurement
Power Supply Specification
Rated Voltage
Rated Frequency
Rated Current
Maximum Inrush Current
Maximum Quiescent Load, Imax_a
Maximum Alarm Load, Imax_b
Minimum Load, Imin, panel only
100 to 240V ac rms
50 to 60 Hz
600mA rms
20A at 240V from cold
647mA ( 22mA panel, 200mA loop, 150mA aux. 24V, 275mA battery charge )
372mA ( 22mA panel, 200mA loop, 150mA aux. 24V )
1026mA ( 56mA panel, 600mA loop, 200mA alarm, 150mA aux. 24V, 20mA fire-link ). Batteries are not charged during an alarm condition
22mA ( panel normal, 30 seconds after a mains failure )
56mA ( panel in alarm, 30 seconds after a mains failure )
Current Consumption from Batteries
( low battery cut-off condition)
Mains Input Fuse
Less than 150μA ( 6100 is turned off )
Battery Type
Output Voltage
Output Ripple Voltage
Battery Charge Voltage
1.6A time delay ( not user or engineer replaceable )
2 x 12V 3.3Ah Sealed Lead Acid ( connected in series )
Only use batteries recommended by Protec ( see appendix 1 )
24 – 29V dc with mains present , 17 – 29V dc on batteries
400mV maximum ( peak to peak ) at full output load
27.3V at 20 degrees C. Temperature compensated at
– 40mV / deg C. Protected by 1.6A self resetting thermal fuse
Battery Charge Current
Battery Test Load
Battery Over Voltage Fault Level
Battery Under Voltage Fault Level
Battery Low Voltage Cut-off Level
Battery Monitoring
Maximum Battery Resistance ( Ri )
250mA ( ± 25mA )
47Ω ( internal to the 6100 )
28.5V dc
22V dc
18.5V dc Battery Voltage ( 6100 turns off )
Charger dip, battery load and internal impedance
2Ω ( battery internal resistance + lead and connection resistances )
N93-572-88 Issue 12 NH Page 45 of 52 © Protec Fire Detection plc 2020
Control Panel Specification
Loop Driver Output Capability
Auxiliary 24V Output
Auxiliary 24V Fault Thresholds
Conventional Alarm Outputs
Conventional Alarm Output End of
Line Fault thresholds
Remote Alarm and Class Change
Inputs
Fire and Fault Outputs
600mA average, 1.2A peak
150mA maximum ( limited by monitored, self resetting thermal fuse ). Any overload must be completely removed to clear a fault condition
An ‘Aux Supply Fault’ is generated when the voltage on the
Aux. 24V output drops to 75% of the panel running voltage
100mA maximum current per output, monitored for open and short circuit faults. A 10kΩ ¼W ( ± 5% ) end of line resistor is required on each alarm output
The alarm outputs can be connected in parallel to achieve a single alarm output with 200mA drive capability, in which case the end of line resistor must change to a 4.7kΩ ¼W ( ± 5% )
All devices connected to the alarm outputs must be polarised and suppressed.
The alarm outputs are monitored as a pair. An alarm fault is generated if the measured resistance ( both alarm circuits in parallel ) is above 7.5kΩ or below
2.5kΩ
50Ω or less to activate
Volt free changeover contacts rated at a maximum of 1A 24V dc
Fire Link Output
Monitored for open and short circuit faults. Requires Protec end of line module
( see appendix 1 ) if used to signal to a remote station, otherwise a 4.7kΩ ¼W
( ± 5% ) termination resistor must be connected locally in the 6100
Fire link Output Current When
Operated
20mA
Fire Link Output End of Line Fault thresholds
A ‘ Fire Link Fault ’ is generated if the measured resistance is above 7.5kΩ or below 2.5kΩ
Appendix 1
Description
List of 6100 Spares and Accessories
Protec Stock Code
Standby battery inter connection lead
12V 3.3Ah VRLA battery ( Online OL3.3-12 )
6100 spares kit
6100 user manual
N 41-796-44
N 13-120-24
N 62-587-76
N 93-571-87
6100 Installation & commissioning manual ( this manual ) N 93-572-88
6100 programming manual N 93-573-89
6100 loop commissioning booklet N 93-574-89
6100 fire link end of line module SF 41-657-59
N93-572-88 Issue 12 NH Page 46 of 52 © Protec Fire Detection plc 2020
Appendix 2
The diagram below shows the 6100 Control PCB housing and highlights the main connections and controls.
Global fault contacts
6100 Control PCB Housing
Remote Alarm input
Global fire contacts
Class Change input
Monitored conventional alarm outputs
Monitored
Auxiliary 24V output
Mains cable restraint ac mains input supply connections
Monitored Fire Link output
Addressable loop connections
Multifunction display
- +
FIRE
LINK FAULT FIRE
+ +
REMOTE
ALARM
CLASS
CHANGE LOOP ALARM
N L
USB connection for PC upload and download
Firemans access level 2 keyswitch input
( specific models only )
N93-572-88 Issue 12 NH Page 47 of 52 © Protec Fire Detection plc 2020
Appendix 3 Loop Devices Supported by the 6100
Detection / Sounder Device Support
Description
All 6000Plus devices
Sounder / Beacon Device Support
Description
All 6000Plus devices
6000/ASB2*
6000/ASB4*
6000/ASBEA2*
6000/ASBEA4*
6000/LED/RED
6000/SSR2 (UK and Dutch)
6000/SSR/LED (UK and Dutch)
Input / Output Device Support
Description
6000/MCP
6000/FRI
Compatible from device software version
15
4
8
1
31
2
Compatible from device software version
15
28
8
Compatible from device software version
11
5
6000/MIP
6000/CCO
6000/MICCO
6000/RESET MICCO
6000/ZAI
6000/16ZAI, 6000/16ZCI, 6000/16ZOI
6000/16WAY I/O Interfaces ( PAI and FRI )
6000/DIU (Damper Interface)
6000/LCM
6000/EVAC
6000/EVAC MIMIC
6000/LCD
6000/PROPOINT
6000/PROPOINTPLUS
6000/TSR2
6000/LPZA
6
1
1
10
1
8
9
25
9
26
7
2
10
7
15
2
6000/APZA
6000/2APZA
6000/2LPZA
6000/2IO
10
2
2
2
6000/4IO
6000/VAD/C/x (x = RED or WHITE)
2
20
6000/VAD/W/x (x = RED or WHITE) 20
6000/TSx/VAD (x = R or W depending on colour) 20
* Any non 6000 PLUS series detection device attached to this device is not supported by the 6100.
N93-572-88 Issue 12 NH Page 48 of 52 © Protec Fire Detection plc 2020
Appendix 4 6100 Event Descriptions
DEVICE IN ALARM
The loop device at the address shown has entered the alarm state.
DEVICE FAULT
The loop device at the address shown has entered the fault state. It may no longer be operating correctly and must be investigated immediately.
DEVICE FAILED SETUP
The loop device at the address shown has failed to setup correctly when the system initialised. The device will not detect fires. The system must be restarted, or the device must be removed for 30 seconds, then replaced to attempt to rectify the fault.
DEVICE PREALARM
The loop device at the address shown has detected a level of smoke, heat or carbon monoxide that is indicative of a fire but not quite at the fire threshold. To view devices in pre-alarm, use the 'View Faults' menu.
DEVICE DISABLED
The device at the address shown has been disabled. Activations from this device will not generate an alarm.
If the device develops a fault, the fault will not be registered on the 6100. Disabled output devices will still activate.
DEVICE INVISIBLE SW
A device, at the address shown, programmed as class ‘Invisible Switch’ has activated.
CONT OPGRPS DISABLED
A loop device programmed to disable control output groups has operated, and output devices programmed into control type output groups will not have been able to activate.
OPGROUP 31 DISABLED
A loop device programmed to disable output group 31 has operated, and output devices programmed into output group 31 will not have been able to activate.
OPGROUP 32 DISABLED
A loop device programmed to disable output group 32 has operated, and output devices programmed into output group 32 will not have been able to activate.
ZONE IN TEST
The zone shown has been programmed into walk test mode.
ZONE DISABLEMENT
The zone shown has been disabled. Activations from devices in this zone will not generate an alarm. If devices in this zone develop a fault, the fault will not be registered on the 6100. Disabled output devices will still activate.
ZONE FAULT
One, or more, loop devices in this zone have developed a fault.
ALARM FAULT
A fault has been detected with an alarm output device on the loop, or a fault has been detected on one or both of the conventional alarm outputs.
ALARMS DISABLED
The alarm outputs have been disabled. Alarm outputs from loop devices, or connected to the conventional alarm outputs will not activate.
FIRE LINK FAULT
A fault has been detected on the fire link output. The fire link may not operate when the 6100 detects a fire.
N93-572-88 Issue 12 NH Page 49 of 52 © Protec Fire Detection plc 2020
FIRE LINK DISABLED
The fire link output has been disabled. Fire link faults and activations will not occur.
BATTERY FAULT
The 6100 has detected a fault with the internal standby battery. This may be due to a fault with the batteries, or the connections to the batteries. The 6100 may not operate correctly in the event of a mains failure.
REPEAT FAULT
A fault has been detected with one, or more loop powered LCD repeat units.
FBP COMMS FAULT
A communications fault has been reported between the 6100 main board, and the internal Fire Brigade
Panel interface module. Only applicable to Australian 6100 models.
AUX SUPPLY FAULT
A fault has been detected with the Auxiliary 24V output. This may be a wiring fault, or the output may have been overloaded. The connection to the auxiliary 24V output must be disconnected for 10 seconds to allow the internal thermal ‘fuse’ to reset.
CLASS CHANGE
The Class Change input ( if enabled ) has been operated.
REMOTE ALARM
The Remote Alarm input ( if enabled ) has been operated.
USER CODE ENTERED
ENG CODE ENTERED
ADV ENG CODE ENTERED
The relevant code entry sequence has been entered into the 6100.
PANEL RESET
The 6100 has been reset either via the menu system, or the 6100 has been powered up from cold.
LOOP FAULT
A fault, or overload has been detected on the loop driver outputs. This may be due to an open circuit loop wiring fault, a short circuit loop wiring fault or a fault on a loop device. This event can take up to 5 minutes to clear once the fault condition has been rectified.
PC CONNECTED
The 6100 has been connected to a PC to upgrade its operating system or site specific data.
SITE DATA CORRUPT
An error has been detected in the site specific data memory.
ADDED DEVICE FAULT
One, or more new loop devices have been detected on the 6100 loop. Added devices must be logged onto the system in order for them to function correctly.
LOOP ALARM FAULT
A fault has been detected with one, or more loop alarm output devices. One or more loop alarm output devices may no longer operate correctly.
LOOP LOGGED
The loop devices on the 6100 have been logged.
SITE DATA CHANGED
The site specific data memory has been altered. This may be due to logging, allocating and saving new loop devices or editing device or zone text.
NIGHT SENS ON
The 6100 has switched from day sensitivity operation to night sensitivity operation.
N93-572-88 Issue 12 NH Page 50 of 52 © Protec Fire Detection plc 2020
EVAC PNL ACTIVE
A 6000 series loop evacuation panel has activated the 6100.
OP GROUP DISABLED
The output group shown has been disabled. Devices programmed into this output group will no longer activate.
SITEFILE ERROR
The revision of ‘site file’ in the 6100 is incompatible with the version of 6100 operating system.
The correct ‘site file’ revision must be programmed into the 6100, or the operating system must be updated as required.
N93-572-88 Issue 12 NH Page 51 of 52 © Protec Fire Detection plc 2020
N93-572-88 Issue 12 NH
Designed and manufactured in the United Kingdom
Page 52 of 52 © Protec Fire Detection plc 2020
Downloaden
Advertentie