ACT ACTLAN - INTERFACE Configuration
ACT ACTLAN - INTERFACE
The ACT ACTLAN - INTERFACE is a versatile device that allows you to connect your ACT controllers to a LAN/WAN network. This enables you to remotely monitor and control your access control system from anywhere with an internet connection.
The ACTLAN - INTERFACE supports both direct connect and TCP/IP connections. For direct connect, you can use a standard alarm cable or a twin twisted-pair cable. For TCP/IP connections, you will need to configure the ACTLAN - INTERFACE with a permanent IP network address.
Once the ACTLAN - INTERFACE is configured, you can use the ACTWin Pro software to manage your access control system. ACTWin Pro allows you to view the status of your controllers, doors, and inputs/outputs. You can also use ACTWin Pro to grant and revoke access to users, and to generate reports.
Reklama
Reklama
ACTLAN Interface Configuration
LAN/WAN
3 2 7
DB25 Male
(Rear View)
22 21 15 14
DB25 Male
(Rear View)
ACTWin Pro Software
Connections for Network
Max cable length is 5m using standard alarm cable or 30m using twin twisted-pair
(use 0V in each pair)
NETWORK
A B 0V
A
B
0V
Connections for Direct Connect
1. Connect cable directly to
ACT1000/2000 and LAN device
2. In Communications Menu Set:
Address = 1
Direct Conn = Y
NETWORK
A B 0V
1. Connect LAN RS-485 cable to
NETWORK terminals on the controller and LAN Interface
2. In ACT1000/2000 Communications
Menu set the controller Address and set Direct Conn = N
DTR
RX
TX
0V
RX = Pin 3
TX = Pin 2
0V = Pin 7
ACT 2000
A
B
0V
A = Pin 14
B = Pin 15
0V = Pin 7
Pin 14 = Pin 21
Pin 15 = Pin 22
ACT 2000
TCP/IP Configuration
1. Ask the network administrator to supply you with a permanent IP network address.
2. Connect a PC directly to the ACTLAN and run HyperTerminal at 9600 baud, no parity, 1 stop.
3. Power up the ACTLAN and immediately hit 3 lowercase "x" (xxx).
4. Hit the Enter key to go inte Setup Mode.
5. Select 0 and follow the prompts until you get to IP address.
6. Enter the new IP address.
7. If the ACT controllers are on a different LAN segment to the ACTWin Pro PC, then a Gateway
Address is required. Check with the network administrator for the IP address of the router.
8. A Netmask may also be required. Check with the network administrator.
9. Follow the prompts to come back to the Setup Menu.
10. Select 1 to configure the RS232 channel.
11. Set up the following parameters as follows:
Baud Rate 9600 I/F Mode 4C for Direct Connect,4F for Network
Flow 00 Port 10001
Connect Mode C0 Disconnect Mode 00
Flush Mode 80 Pack Control 00
Remote IP Address none
12. Return to the Setup Menu and select 9 to save the settings.
13. Finally test the setup by connecting to the IP address using a Web browser or 'Pinging'.
14. From ACTWin Pro, enter the new IP address into the location manager for the site.
18-00026 Issue 4
ACT, Unit C1, South City Business Centre, Tallaght, Dublin 24, Ireland. www.accesscontrol.ie
Telephone: 353 1 466 2570 UK Lo-Call 0845-300 5204 Fax: 353 1 452 0427 E-mail: [email protected]
ACT LAN Manufacturing Instructions
Issue 3 - 8 March 2004
Instructions
1. Insert ACTLAN Interface Configuration Sheet (18-00026) inside Box
2. Insert Modem Direct Connect Cable and LAN RS-485 Cable (see below) inside Box
3. Insert 9-way to 25-way serial cable (ACT Part num 44-0005)
3. Seal Box and place ACT LAN Sticker outside
ACT 2000
NETWORK
A B 0V
A
B
0V
DTR
RX
TX
0V
Modem Direct Connect Cable
3m Cable length
Connections for 25 Way male Connector
RX = Pin 3
TX = Pin 2
0V = Pin 7
7 3 2
DB25 Male
(Rear View)
ACT Nework Interface Card
RS485 232 Interface
Converter
LAN RS-485 Cable
RS232
PORT
~AC~ +BAT-
LED2
Line 1 Line 2
LED3
Line 3
Line 4
3m Cable length
DO = Pin 2
DI = Pin 3
C = NC
SCN = Pin 7
7 3 2
DB25 Male
(Rear View)
Connections for 25 Way male Connector
Unit C1 South City Business Centre, Tallaght, Dublin 24, Ireland.
Telephone: 353 1 466 2570. Telefax: 353 1 452 0427. E-mail: [email protected] Web: www.accesscontrol.ie
Atsisiųsti
Reklama