Wiremold electrical systems conform to and should be properly grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Wiremold electrical products may bear the mark as UL Listed and/or Classified and should be installed in conformance with current local and/or the
National Electrical Code.
Convia
®
Enabled
Walkerflex
®
System
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 008 478 – August 2009
IMPORTANT: Please read all instructions before beginning.
Products Covered: NVHUB, LVHUB, NRD1, NRD2, LRD1, LRD2, NPM12, NPM22, NPM24, NPM44, NPM24PF,
NPM44PF, CNDU, CLDU, CNWC, CLWC, CNPA, CLPA, CNCS, CLCS, CNCBS, CLCBS, CNCW,
CLCW, CAP3456 & CAP810
NOTE: Label on product indicates which products are suitable for use in air handing spaces in accordance with Sec. 300-22(C) of the National Electric Code.
GENERAL INFORMATION
1. Each Convia ® Enabled Walkerflex ® System connector contains a color coded key that indicates rating, conductor location and orientation. Only like colored keys can be mated. See Key Configuration and Color Chart on page 11 for available options. Each key is comprised of one or more configurations.
2. Disconnect power from source prior to wiring any Walkerflex component into the building’s electrical power system.
3. Installer to determine the maximum power cable length based on wire gauge and circuit load.
4. Installer to ensure adequate overload protection based on the system key, rating and circuit load.
5. Refer to appropriate Wiring Diagram and System Key
Configuration Conductor Location Chart for field connections of Cat. Nos. CNWC/CLWC (Wire Connector) and
CNCW/CLCW (Cable Whips). Refer to wiring diagram supplied with CNDU/CLDU (Distribution Unit) for field termination.
6. Securing and Supporting of Cables and Components: Refer to NEC Article 604, Manufacturing Wiring Systems and any local codes.
7. Cap all unused connector openings with Cat. No. CAP3456
(for 3 through 6 wire system) or Cat. No. CAP810 (for 8 and
10 wire system).
8. All Convia Enabled accessories are available in a 3-6 wire and 8-10 wire system and are rated 20A, 120V.
9. 277V Convia Enabled Walkerflex components are only available in 3-6 wire configurations.
10. The Convia Enabled Walkerflex system is compatible with the standard Walkerflex system of the same configuration and key.
CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION
CNDU and CLDU Module & Flex Cables:
The CNDU and CLDU (CLDU is available for 3-6 wire configurations only) module is the main power source and interface to the Convia Enabled Walkerflex System. It is to be fed from a distribution panel outfitted with appropriate circuit breakers to protect wiring.
CNDU & CLDU Distribution Unit:
NOTE: Cap Unused Connectors
On All Power Out Modules.
Power
Out
Power
In
Po wer
In
Cat. No. CAP3456 End Cap
(for 3-6 wire configurations)
Cat. No. CAP810 End Cap
(for 8-10 wire configurations)
Power
Out
Current Flow
Direction
Secure Box in Place
Feed Power
Ou t
Cat. No. CNWC & CLWC
(Wire Connector)
Cat. No. CNPA & CLPA
(Power Adapter)
Connected to
Protected Circuit(s)
Cat. No. CNCS & CLCS
(Cable Set)
Cat. No. CNCBS & CLCBS
(Splitter) Current Flow
Direction
Current Flow
Direction
CAUTION: Do not make or break connections while circuits are energized.
Current Flow
Direction
Cat. No. CNCW & CLCW
(Cable Whip)
Cat. No. CNCS &CLCS
(Cable Set)
Mate only identical Keys and Configurations.
2
CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION (continued)
Network Hubs
The Network Hub module makes up the backbone or Main Bus of the network. Multiple
Network Hubs can be configured to increase the size of the network or to increase the number of available ports in an installation location. Up to 50
Network Hubs can be connected on a single network with a patch cable length of up to 2000 feet. Refer to the ConviaNet Design Guide for more information.
Step 1: Mount Network Hub securely using appropriate screws and anchors.
Table A – NETWORK HUB POWER CONFIGURATIONS
120V SYSTEM
Part Walkerflex
Number Phase Configurations
NVHUBA
NVHUBB
NVHUBC
NVHUBD
NVHUBF
A
B
C
111, 211, 311
211, 311
311
222
Field Wired
277V SYSTEM
Part Walkerflex
Number Phase Configurations
LVHUBA
LVHUBB
LVHUBC
LVHUBF
LVHUBF
A
B
C
111, 211, 311
211, 311
311
Field Wired
Field Wired
Mounting Holes
RJ11 Jack for Main
Bus Connections
RJ45 Jacks for Node
Bus Connections
RJ11 Jack for Main
Bus Connections
Step 2: Connect Power to Network Hub.
For Modular Connection: Connect Convia
Enable Walkerflex Modular Cable to modular input.
Prewired 5-Port Network Hub
For Field Wired Units: Connect conduit to appropriate conduit opening and wire per the National Electric
Code. (See Wiring Schematic below or on product label for connections.
Power input coming from Distribution Box or main panel
Field Wired 5-Port Network Hub
Current Flow
Direction
3/4" Trade Size
Knockout
Hub Wiring Schematic
1/2" Trade Size
Knockout
Step 3: Connect Wiremold Convia Enabled pre-terminated
RJ11 cables between the Network Hubs. Install
Communication Loop Closures into RJ11 ports at the beginning and end of the network run (Main Bus).
Communications Loop
Closure – 2 required for each network
Step 4: Install Wiremold Convia Enabled pre-terminated
RJ45 cables between the Network Hubs and the
Relay Dimmers, Power Modules, Sims, Switches, and Scene Controllers.
Wiremold Convia
Enabled Pre-terminated
RJ11 Cable to next
Network Hub in network
NOTE: To ensure proper network functioning, Communication
Loop Closures need to be installed into the beginning and end of the Main Bus of the network. If there is only one Network Hub in the installation, then
Communication Loop Closures must be installed in both RJ11 ports on the Network Hub.
3
Wiremold Convia Enabled Preterminated RJ45 Cables going to Relay Dimmers, Power
Modules, Sims, Switches and
Scene Controllers
Step 5: Move on to the installation of Relay Dimmers and Power Modules.
CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION (continued)
Relay Dimmer
The Relay Dimmer Modules are used to control lighting and other devices, (maximum
20A load) via the Convia Enabled Walkerflex
System. They connect to the Network Hub to create the Node Bus of the network. Up to 25 nodes can be connected on a single
Node Bus with a maximum patch cable length of 1000 feet. Refer to the ConviaNet
Design Guide for more information.
Table B – RELAY DIMMER POWER CONFIGURATIONS
120V SYSTEM
Part Walkerflex
Number Phase Configurations
NRD1A, NRD2A
NRD1B, NRD2B
A
B
111, 211, 311
211, 311
NRD1C, NRD2C
NRD1F, NRD2F
C 311
Field Wired
277V SYSTEM
Part Walkerflex
Number Phase Configurations
LRD1A, LRD2A A 111, 211, 311
LRD1B, LRD2B
LRD1C, LRD2C
LRD1F, LRD2F
B
C
211, 311
311
Field Wired
NRD1/LRD1 has one (1) controlled Walkerflex 111 output.
NRD2/LRD2 has two (2) controlled Walkerflex 111 outputs.
NOTE: For proper dimming function, use only approved dimming ballasts.
Additional ballasts are being added as they become available. For updated ballast information, visit www.wiremold.com. If a qualified
0-10 VDC dimming ballast is not on the list, please contact your sales representative for verification.
APPROVED DIMMING BALLASTS
Manufacturer Name
Advanced Transformer
Osram Sylvania
Universal Technologies
General Electric
Mark
Quiktronic
SuperDim
UltraMax
Step 1: Mount Relay Dimmer securely using appropriate screws and anchors.
Mounting Holes
Convia Net
(RJ45) Jack for
Accessory Bus
Connections
Convia Net
(RJ45) for
Node Bus
Connections
Step 2: Connect Power to Relay Dimmers.
For Modular Connection: Connect Convia
Enabled Walkerflex Modular Cable to modular input and output.
Power input coming from Distribution Box or main panel
Power Output going to light fixture ballasts
Current Flow
Direction
ConviaIR (RJ11)
Jack for IR
Connections
For Field Wired Units: Connect conduit to appropriate conduit opening and wire per the National
Electric Code. (See Wiring Schematic below or on product label for connections.
1/2" Trade Size
Knockout
Current Flow
Direction
3/4" Trade Size
Knockout
NRD2 Wiring Schematic
NRD1 Wiring Schematic
4
CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION (continued)
Step 3: Connect Wiremold Convia Enabled Pre-terminated
RJ45 cables between the Network Hub and the
Relay Dimmers to create the Node Bus. The top
ConviaNet RJ45 jack is IN, the bottom ConviaNet
RJ45 jack is OUT.
In from Network
Hub or upstream
Relay Dimmer or
Power Module
Step 4: Connect Wiremold Convia Enabled Pre-terminated
RJ45 cables between the Relay Dimmers and the
Sims, Sensors, Switches, and Scene Controllers to create the Accessory Bus. An Accessory Bus can contain up to 50 devices with a maximum patch cable length of 500 feet.
Out to Sim, Switch or Scene Controller
Out to downstream
Relay Dimmer or
Power Module
Step 5: Install End Terminators in all ConviaNet RJ45
Node Bus Terminals not being used.
Step 6: Install IR Sensors into ConviaIR RJ11 Port.
IR Sensor
NOTE: To ensure proper network functioning, End
Terminators need to be installed in all unused
Node ports, and Inline Terminators need to be installed at the end of all Accessory Bus Runs.
Step 7: Connect Class 2 cable to Dimming Terminal Block.
See Product Label for dimming connections.
NOTE: IR Sensor can be installed using a RJ11 In-Line
Connector (PNRJ11LC) and a Wiremold Convia
Enabled pre-terminated RJ11 Cable when necessary. IR Sensors are needed in all boxes for commissioning and are recommended to aid in reconfiguring or troubleshooting network setups.
Step 8: Connect system to light fixtures per the National
Electric Code.
0-10VDC Dimmer
Terminal Block
NOTE: Connect appropriate Class 2 cable (Plenum rated if installed in an Air Handling Space) to terminals on the Relay Dimmer Modules in accordance with
Article 725 of the National Electric Code.
5
CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION (continued)
Power Modules
The Power Modules are used to control general purpose loads, (maximum 20A load) via the Convia Enabled Walkerflex System.
They connect to the Network Hub to create the Node Bus of the network. Up to 25 nodes can be connected on a single Node
Bus with a maximum patch cable length of
1000 feet. Refer to the ConviaNet Design
Guide for more information.
Part
Number
NPM12
NPM22
NPM12F
NPM22F
NPM24
NPM44
NPM24F
NPM44F
NPM24PF
NPM44PF
Table C – POWER MODULE CONFIGURATIONS
Number of
Controlled Circuits
1
2
1
2
Number of
Total Circuits
2
2
2
2
Walkerflex
Input(s)
222
222
Walkerflex
Output(s)
Field Wired
Field Wired
222
222
2
4
2
4
2
4
4
4
4
4
4
4
422
422
422
422
Field Wired
Field Wired
(2) 222
(2) 222
422
422
Step 1: Mount Power Modules securely using appropriate screws and anchors.
ConviaNet
(RJ45) Jack for
Accessory Bus
Connections
ConviaNet (RJ45)
Jack for Node
Bus Connections
Mounting Holes
ConviaIR (RJ11)
Jack for IR
Connections
Step 2: Connect Power to Power Modules.
For Modular Connection: Connect Convia Enabled Walkerflex Modular
Cable to modular input and output(s).
Power input coming from Distribution Box or main panel
Two Circuit Power Modules
Power Output going to
Floor Boxes, Poke-Thru
Devices, etc.
Four Circuit Power Modules
Power input coming from Distribution Box or main panel
Power Output going to
Floor Boxes, Poke-Thru
Devices, etc.
Current Flow
Direction
Current Flow
Direction
Current Flow
Direction
Current Flow
Direction
Power input coming from Distribution Box or main panel
Four Circuit Partition Feed Modules
Power Output going to
Floor Boxes, Poke-Thru
Devices, etc.
Current Flow
Direction
Current Flow
Direction
6
CONVIA ENABLE WALKERFLEX SYSTEM INSTALLATION (continued)
Step 2 (continued):
For Field Wired Units: Connect conduit to appropriate conduit opening and wire per the National
Electric Code. (See Wiring Schematic below or on product label for connections).
Two Circuit Power Modules – Field Wired Four Circuit Power Modules – Field Wired
3/4" Trade Size
Knockout
NPM12 Wiring Schematic
1/2" Trade Size
Knockout
3/4" Trade Size
Knockout
NPM24 Wiring Schematic
1/2" Trade Size
Knockout
NPM22 Wiring Schematic NPM44 Wiring Schematic
Step 3: Connect Wiremold Convia Enabled pre-terminated
RJ45 cables between the Network Hubs and the
Power Modules to create the Node Bus. The top
ConviaNet RJ45 jack is IN, the bottom ConviaNet
RJ45 jack is OUT.
In from Network
Hub or upstream
Relay Dimmer or
Power Module
Step 4: Connect Wiremold Convia Enabled pre-terminated
RJ45 cables between the Power Modules and the
Sims, Switches, and Scene Controllers to create the Accessory Bus. An Accessory Bus can contain up to 50 devices with a maximum patch cable length of 500 feet.
Out to Sim, Switch or Scene Controller
Out to downstream
Relay Dimmer or
Power Module
Step 5: Install End Terminators in all ConviaNet RJ45
Node Bus terminals not being used.
Step 6: Install IR Sensors into ConviaIR RJ11 Port.
IR Sensor
NOTE: To ensure proper network functioning, End Terminators need to be installed in all unused Node ports, and End
Terminators or Inline Terminators need to be installed at the end of all Accessory Bus Runs.
7
NOTE: IR Sensor can be installed using a RJ11 In-Line
Connector (PNRJ11LC) and a Wiremold Convia Enabled pre-terminated RJ11 Cable when necessary. IR Sensors are needed in all boxes for commissioning and are recommended to aid in reconfiguring or troubleshooting network setups.
WALKERFLEX SYSTEM ACCESSORIES
TYPICAL PREWIRED ACCESS FLOOR BOX INSTALLATIONS
Access
Floor Box
Cat. No. CNCS
(Cable Set)
Cat. No. CNPA
(Power Adapter)
Cat. No. CNCS
(Cable Set)
Cat. No. CNCW
(Cable Whip)
CE4ATCAL222PA
CE6STCP222PA CE3ATCAL111PA CE4FFATCAL422CW
8
WALKERFLEX SYSTEM WIRING DIAGRAMS
120V 20A SYSTEM FOR 1, 2, 3 OR 4 LINE CONDUCTORS
CONNECTED TO A GROUNDED THREE-PHASE WYE
120V 20A SYSTEM FOR 1 OR 2 LINE CONDUCTORS
CONNECTED TO A DUAL NEUTRAL GROUNDED
THREE-PHASE WYE AND ISOLATED GROUND
120V 20A SYSTEM FOR 1 OR 2 LINE CONDUCTORS
CONNECTED TO A DUAL NEUTRAL GROUNDED
THREE-PHASE WYE
120V 20A SYSTEM FOR 1 OR 2 LINE CONDUCTORS
CONNECTED TO A GROUNDED THREE-PHASE WYE
AND ISOLATED GROUND
277V 20A SYSTEM FOR 1, 2, OR 3 LINE CONDUCTORS
CONNECTED TO A GROUNDED THREE-PHASE WYE
277V 20A SYSTEM FOR 1 OR 2 LINE CONDUCTORS
CONNECTED TO A DUAL NEUTRAL GROUNDED
THREE-PHASE WYE AND ISOLATED GROUND
277V 20A SYSTEM FOR 1 OR 2 LINE CONDUCTORS
CONNECTED TO A DUAL NEUTRAL GROUNDED
THREE-PHASE WYE
277V 20A SYSTEM FOR 1 OR 2 LINE CONDUCTORS
CONNECTED TO A GROUNDED THREE-PHASE WYE
AND ISOLATED GROUND
L1 Black
9
WALKERFLEX SYSTEM WIRING DIAGRAMS (continued)
120V 20A SYSTEM FOR 4 LINE CONDUCTORS & 2
NEUTRALS CONNECTED TO AN ISOLATED GROUND
THREE-PHASE WYE
120V 20A SYSTEM FOR 6 LINE CONDUCTORS & 2
NEUTRALS CONNECTED TO AN ISOLATED GROUND
THREE-PHASE WYE
120V 20A SYSTEM FOR 3 LINE CONDUCTORS & 3
NEUTRALS CONNECTED TO AN ISOLATED GROUND
THREE-PHASE WYE
120V 20A SYSTEM FOR 4 LINE CONDUCTORS & 4
NEUTRALS CONNECTED TO AN ISOLATED GROUND
THREE-PHASE WYE
120V 20A SYSTEM FOR 6 LINE CONDUCTORS & 3
NEUTRALS CONNECTED TO A THREE-PHASE WYE
10
WALKERFLEX SYSTEM WIRING CONFIGURATIONS
WALKERFLEX 3-6 KEY CONFIGURATIONS
SYSTEM
20A, 120V
20A, 120V,
IG
20A, 120V,
2N
20A, 277V
TERMINAL
BLOCK
COLOR KEY POWER OUT
Black A
G 5 6
1 2 3
Orange B
G 5 6
1 2 3
Clear C
G 5 6
1 2 3
Yellow D
POWER IN
6
3
5
2
G
1
6
3
5
2
G
1
6
3
5
2
G
1
20A, 277V,
IG
Green E
20A, 277V,
2N
Blue F
WALKERFLEX 8-10 KEY CONFIGURATIONS
TERMINAL
BLOCK
SYSTEM COLOR
20A, Black
120V,
4H/2N/IG
KEY
422
POWER OUT
6
5
7
4
8
3
9 10
2 G
20A, Orange 442
120V,
4H/4N/IG
6
5
7
4
8
3
9 10
2 G
20A, Natural 332
120V,
3H/3N/IG
6
5
7
4
8
3
9 10
2 G
20A, Blue
120V,
6H/3N/G
631
6
5
7
4
8
3
9 10
2 G
20A, Ivory
120V,
6H/2N/IG
622
6
5
7
4
8
3
9 10
2 G
POWER IN
10 9
G 2
8
3
7
4
6
5
10
G
9
2
8
3
7
4
6
5
10 9
G 2
8
3
7
4
6
5
10
G
9
2
8
3
7
4
6
5
10 9
G 2
8
7
3
4
6
5
SYSTEM
120V
4H/2N/IG
120V
4H/4N/IG
120V
3H/3N/IG
120V
6H/3N/G
120V
6H/2N/IG
8-10 SYSTEM KEYING CONFIGURATIONS & COLORS
H N
TERMINAL
BLOCK
COLOR
Black
Orange
Natural
Blue
Ivory
KEY CONFIG
422
442
332
631
622
422
442
332
631
622
WIRE
COLOR
WIRE
COLOR
G
WIRE
COLOR
7 Line 1: Black
8 Line 2: Red
9 Line 3: Blue
10 Line 4: Blk/Wht
2
3
Neutral 1: White
Neutral 2: Wht/Red
1
6
Equip Gnd: Green
ISO Gnd: Grn/Yel
7 Line 1: Black
8 Line 2: Red
2 Neutral 1: White 1 Equip Gnd: Green
3 Neutral 2: Wht/Red 6 ISO Gnd: Grn/Yel
9 Line 3: Blue 4 Neutral 3: Wht/Blu
10 Line 4: Blk/Wht 5 Neutral 4: Wht/Blk
7
8
9
Line 1: Black
Line 2: Red
Line 3: Blue
5 Line 1: Black
6 Line 2: Red
7 Line 3: Blue
8 Line 4: Blk/Wht
9 Line 5: Red/Wht
10 Line 6: Blu/Wht
2 Neutral 1: White 1 Equip Gnd: Green
3 Neutral 2: Wht/Red 6 ISO Gnd: Grn/Yel
4 Neutral 3: Wht/Blu
2 Neutral 1: White
3 Neutral 2: Wht/Red
4 Neutral 3: Wht/Blu
1 Equip Gnd: Green
4 Line 1: Black
5 Line 2: Red
7 Line 3: Blue
8 Line 4: Blk/Wht
9 Line 5: Red/Wht
10 Line 6: Blu/Wht
2 Neutral 1: White 1 Equip Gnd: Green
3 Neutral 2: Wht/Red 6 ISO Gnd: Grn/Yel
11
WALKERFLEX SYSTEM WIRING CONFIGURATIONS (continued)
TERMINAL
BLOCK
COLOR KEY CONFIG
Black A 111
211
Orange B
3-6 SYSTEM KEYING CONFIGURATIONS & COLORS
H N
311
411
112
WIRE
COLOR
1 Line 1: Black
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
2 Line 2: Red
3 Line 3: Blue
1 Line 1: Black
2 Line 2: Red
3 Line 3: Blue
5 Line 4: Blk/Wh
1 Line 1: Black
WIRE
COLOR
6 Neutral 1: White
6 Neutral 1: White
6 Neutral 1: White
6 Neutral 1: White
G
WIRE
COLOR
4 Equip Gnd: Green
4 Equip Gnd: Green
4 Equip Gnd: Green
4 Equip Gnd: Green
Clear
Yellow
Green
C
D
E
212
222
221
111
211
311
411
112
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
2 Line 2: Red
3 Line 3: Blue
1 Line 1: Black
2 Line 2: Red
3 Line 3: Blue
5 Line 4: Blk/Wh
1 Line 1: Black
6
6
Neutral 1: White
Neutral 1: White
4 Equip Gnd: Green
5 ISO Gnd: Grn/Yel
4 Equip Gnd: Green
5 ISO Gnd: Grn/Yel
6 Neutral 1: White 4 Equip Gnd: Green
3 Neutral 2: Wht/Red 5 ISO Gnd: Grn/Yel
6 Neutral 1: White
5 Neutral 2: Wht/Red
4 Equip Gnd: Green
6 Neutral 1: White 4 Equip Gnd: Green
6 Neutral 1: White 4 Equip Gnd: Green
6 Neutral 1: White
6 Neutral 1: White
4 Equip Gnd: Green
4 Equip Gnd: Green
Blue F
212
222
221
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
2 Line 2: Red
1 Line 1: Black
2 Line 2: Red
6
6
Neutral 1: White
Neutral 1: White
4 Equip Gnd: Green
5 ISO Gnd: Grn/Yel
4 Equip Gnd: Green
5 ISO Gnd: Grn/Yel
6 Neutral 1: White 4 Equip Gnd: Green
3 Neutral 2: Wht/Red 5 ISO Gnd: Grn/Yel
6 Neutral 1: White 4 Equip Gnd: Green
3 Neutral 2: Wht/Red 5
© Copyright 2009 Legrand All Rights Reserved
WIREMOLD
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251
Canada:
570 Applewood Crescent • Vaughan, Ontario L4K 4B4
1-800-723-5175 • FAX 905-738-9721
1 008 478 0809