Carbolite Gero EHC 12/600 with 3216 centre zone and 3216CC end zones Operating Manual

Add to My manuals
68 Pages

advertisement

Carbolite Gero EHC 12/600 with 3216 centre zone and 3216CC end zones Operating Manual | Manualzz

Installation, Operation and Maintenance Instructions

1200°C Tube Furnace (3-zone) EHC Model: 600mm

3216 Controller + 3216CC End Zone Controllers

EHC 12/600B + 3216 Controller + 3216CC

End Zone Controllers

MEN-EHC12600B-06_3216_3216CC ( 09-07-2019 )

2

Contents

This manual is for guidance on the use of the Carbolite Gero product specified on the front cover. This manual should be read thoroughly before unpacking and using the furnace or oven. The model details and serial number are shown on the back of this manual. Use the product for the purpose for which it is intended.

1.0 Symbols and Warnings

1.1

Switches and Lights

1.2

General Warnings

1.3

Warning Labels

2.0 Installation

2.1

Unpacking and Handling

2.2

Siting

2.3

Setting Up

2.4

Electrical Connections

3.0 3216 Controller

3.1

PID control

3.2

3216P1

3.3

3216P5

3.4

Operation

3.4.1

Controller Layout

3.4.2

Keys

3.5

Quick Start Guide

3.5.1

Operation as a simple controller

3.5.2

Changing the Setpoint

3.5.3

Using the Controller

3.5.4

Understanding User Levels

3.6

Setting up the Controller

3.6.1

Maximum Output Power

3.6.2

Customer ID

3.6.3

Units

3.6.4

Language

3.6.5

Scrolling Text

3.6.6

Customer Calibration

3.6.7

Holdback

3.7

Programming

3.7.1

Creating a Program

3.7.2

Program Number (3216P5 Only)

3.7.3

Ramp Units

3.7.4

Dwell Units

9

10

16

9

9

6

6

6

7

17

21

22

23

23

23

23

23

20

20

20

21

18

19

20

20

17

18

18

18

18

17

17

17

17

3.7.5

Holdback

3.7.6

Ramp Rate

3.7.7

Target Setpoint

3.7.8

Dwell Time

3.7.9

Running a Program

3.7.10

Program Status

3.7.11

Process Value

3.7.12

PSP, Segment Type and Number

3.8

Controller Options

3.8.1

Digital Communications - RS232

3.8.2

Digital Communications - RS485

3.8.3

Comms Address

3.8.4

Alarm Option

3.9

Temperature Controller Replacement

3.10

3216 Controller Navigation Diagram

4.0 3216CC Controller

4.1

3216CC

4.2

PID control

4.3

Operation

4.3.1

Controller Layout

4.3.2

Keys

4.4

Quick Start Guide

4.4.1

Operation as a simple controller

4.4.2

Changing the Setpoint

4.4.3

Using the Controller

4.4.4

Understanding User Levels

4.5

Setting up the Controller

4.5.1

Setpoint Ramp Rate

4.5.1.1

Setting Setpoint Ramp Rate

4.5.1.2

Running with Ramp Rate

4.5.2

Maximum Output Power

4.5.3

Customer ID

4.5.4

Units

4.5.5

Language

4.6

Timer

4.6.1

Setting the Timer

4.6.2

Dwell Timer

4.6.3

Delayed Switch On Timer

4.6.4

Soft Start Timer

30

31

31

31

32

30

30

30

30

31

31

33

33

33

33

34

34

34

34

34

34

35

35

36

27

27

27

27

28

28

28

24

24

24

24

23

23

23

23

3

4

4.7

Running a Timer

4.7.1

Dwell Timer

4.7.2

Power Failure While Using Dwell Timer

4.7.3

Running Dwell Timer with Ramp Rate

4.7.4

Running Dwell Timer with Ramp Rate & Threshold

4.7.5

Delayed Switch on Timer

4.7.6

Running Delay Timer with Ramp Rate

4.7.7

Delay timer with ramp rate functions

4.7.8

Power Failure While Using Delay Timer

4.7.9

Soft start Timer

4.7.10

Power Failure While Using Soft Start Timer

4.7.11

Ramp Rate with Soft Start Timer

4.7.12

Time Remaining

4.7.13

Alarms

4.8

Controller Options

4.8.1

Digital Communications - RS232

4.8.2

Digital Communications - RS485

4.8.3

Comms Address

4.8.4

Alarm Option

4.9

3216CC Navigation Diagram

5.0 2132 Over-Temperature Controller Description (if fitted)

5.1

Description

5.2

Operation

5.2.1

Controls

5.2.2

Operation

5.2.3

Over-Temperature Operation

5.2.4

Over-Temperature Alarm

5.2.5

Resetting the Over-Temperature Alarm

5.2.6

Sensor Break

5.3

Audible Alarm

5.4

Navigation Diagram

6.0 Operation

6.1

Operating Cycle

6.2

Control Method

6.3

Safe Operation of the Furnace

6.4

3-Zone Control Methods

A. Back-to-Back Thermocouples

B. Retransmission of Setpoint

44

45

45

45

45

44

44

44

45

46

46

40

40

41

41

39

40

40

40

41

42

42

42

43

36

37

37

38

38

38

39

47

47

47

47

48

49

49

C. Independent Control

6.5

General Operating Advice

6.6

Operator Safety

6.7

Tube Life

6.8

Pressure

6.9

Gas Tightness

7.0 Maintenance

7.1

General Maintenance

7.2

Maintenance Schedule

7.2.1

Cleaning

7.3

Calibration

7.4

After-Sales Service

7.5

Recommended Spare Parts and Spare Parts Kit

8.0 Repairs and Replacements

8.1

Safety Warning - Disconnection from Power Supply

8.2

Safety Warning - Refractory Fibre Insulation

8.3

Temperature Controller Replacement

8.4

Solid-state Relay Replacement

8.5

Thermocouple Replacement

8.6

Element Replacement

8.7

Fuse Replacement

9.0 Fault Analysis

A.

Furnace Does Not Heat Up

B.

Product Overheats

10.0 Wiring Diagrams

10.1

WC-13-30

10.2

WC-13-31

11.0 Fuses and Power Settings

11.1

Fuses

11.2 Power Settings

12.0 Specifications

12.1

Environment

Furnace drying out process

56

56

56

56

57

57

57

58

59

59

60

53

53

53

55

55

55

55

50

50

50

51

51

51

61

61

61

62

62

63

64

64

65

5

6

1.0   Symbols and Warnings

1.0

Symbols and Warnings

1.1

Switches and Lights

Instrument switch: when the instrument switch is operated the temperature control circuit is energised.

Heat light: the adjacent light glows or flashes to indicate that power is being supplied to the elements.

Heat switch: the switch disconnects power to the heating elements; unless this switch is OFF there is a danger of electric shock when inserting objects into the product.

1.2

General Warnings

DANGER – Electric shock. Read any warning printed next to this symbol.

WARNING: Risk of fatal injury.

DANGER – Hot surface. Read any warning printed next to this symbol.

WARNING: All surfaces of a product may be hot.

DANGER – Read any warning printed next to this symbol.

1.0   Symbols and Warnings

Caution – Double Pole/Neutral Fusing

1.3

Warning Labels

On the front control panel there are 2 warning labels as shown in figure 1.3.1; they are numbered 7 and 8. These warnings must be followed for the safe operation of this furnace.

7- Warning label - Do not operate without a work tube.

The furnace must not be operated without the correctly sized work tube and correspond work tube adaptors or it could be possible for an operator to access electrically live element coils that could cause serious injury or death.

8- Warning label - Switch off the furnace before loading and unloading.

The furnace heaters must be switched OFF using the heater switch, item

2 in figure 1.3.1, when the furnace is being loaded or unloaded. The work tube can become electrically conductive at high temperatures, presenting a possible hazard to the operator. If element failure is left undetected the element could collapse onto the work tube.

7

8

1.0   Symbols and Warnings

Figure 1.3.1 - Control Box layout and warning labels.

Figure 1.3.2- Back of control box showing mains lead socket

Index to numbered items in Figure 1.3.1 and 1.3.2

1. Electrical supply switch - switches electrical power ON and OFF to the furnace.

2. Heater switch - switches electrical power ON and OFF to the furnace heating elements.

3. Heater ON light - indicates that the furnace heating elements are energized.

4. Product rating label indicating the product serial number and electrical information.

5. Access holes to front panel fixing screws.

6. Warning label - Disconnect the mains supply before removing this cover.

7. Warning label - Do not operate without a work tube.

8. Warning label - Switch OFF the furnace before loading and unloading.

9. Electrical power lead socket.

10. Back panel fixing screws.

2.0   Installation

2.0

Installation

If the product has been transported or stored in humid conditions it must be dried out completely before operating the furnace. Contact

Carbolite Gero Service for instructions.

2.1

Unpacking and Handling

When unpacking or moving the product, always lift it by its base or both ends of the main body. Never lift it by the end insulation or by a work tube. It may take 2 or 3 people to lift the furnace, depending on the size and configuration.

NOTE: This product contains Refractory Ceramic Fibre (also known as

Alumino Silicate Wool - ASW). For precautions and advice on handling

this material see section 8.2.

2.2

Siting

Place the product on a level surface in a well ventilated area.

Site away from other sources of heat and on a non-flammable surface that is resistant to accidental spillage or hot materials.

The surface on which the equipment is mounted should be stable and not subject to movement or vibrations.

The height of the mounting surface is important to avoid operator strain when loading and unloading samples.

Unless otherwise stated elsewhere in this manual, ensure that there is at least 150 mm of free space around the back and sides of the product. Clear space is required above the product to dissipate heat.

Work tubes:

It is recommended that the work tube has either insulation plugs or radiation shields fitted to minimise heat loss from both ends of the work tube. If the work tube has open ends, a significant amount of energy could be radiated from the ends of the work tube. Adjacent surfaces should always be made from a non-flammable material.

Ensure that the ends of the work tube are positioned at least 500 mm away from any adjacent surface so that any energy radiated cannot heat an adjacent surface to a dangerous temperature.

9

2.0   Installation

If the product is to be used in a process which could liberate hazardous gases, then it should be installed together with a suitable fume extraction system.

Ensure that the product is placed in such a way that it can be quickly switched off or disconnected from the electrical supply.

2.3

Setting Up

The horizontal models must have work tubes fitted before being used. The diameter of the work tube is a customer order option and therefore varies between tube furnaces.

Note: If a metal work tube is being used in the furnace, ensure that it is

earthed. See 6.6.

Under no circumstances should any objects be placed on top of the product.

Always ensure that any vents on the top of the product are clear of any obstruction. Always ensure all cooling vents and cooling fans (if fitted) are clear of any obstruction.

Fitting the standard length work tube to furnace

Tools required: 4 mm Allen key

Fitting work tube is as follows with reference to Figure 2.3.2. Please note that standard length work tubes are also referred to as tubes suitable for working in air. They are 150

10

2.0   Installation mm longer than the heated length of the furnace (see the Specifications table at the

back of this manual). Read section 8.2 before fitting the work tube.

Figure 2.3.1 - Furnace model mounted on a control box

Figure 2.3.2 - Exploded view showing how to fit the work tube in the furnace

Index to numbered items in Figure 2.3.2

1. Tube furnace body

2. Work tube (diameter customer option)

3. Work tube adaptor (size dependent on work tube diameter)

4. Work tube adaptor fixing bracket

5. Work tube end stop (size dependent on work tube diameter)

6. Fixing screws M6 x 15

7. Washer M6

8. Tube furnace end guard l l l

Remove the work tube end guard (8) then remove the work tube adaptor fixing bracket (4) that holds in place the work tube end stop (5) and the end adaptor (3) from one side only. Note that if a different work tube with a different outer diameter is being fitted it will be necessary to fit new correctly sized work tube adaptors (3) in which case both end guards and work tube adaptor fixing brackets (4) will need removing.

Slide the work tube into the furnace through the work tube adaptor (3) until it reaches the opposite work tube end stop (5). Note that the work might be a tight fit when it is new and may need to be twisted backwards and forwards slightly as it slides in. For long work tubes it may be necessary to use a long wooden pole to support and line up the work tube as it pushed through. It may also take 2 people to perform this operation.

Reassemble the work tube end stop (5), work tube adaptor bracket (4) and tube end guard (8).

Fitting the extended work tube in the furnace

Tools required 4 mm Allen key.

Fitting of the work tube is as follows with reference to Figure 2.3.2 to 2.3.8.

11

12

2.0   Installation l l l l l l l l l

Before the extended work tube can be fitted, the work tube end stops for the standard length work tube (item 5 in figure 2.3.2 ) must be removed from both ends of the furnace. This is done by removing the furnace end guard (8) and the work tube adaptor brackets (4) to release the work tube end stop (5). The brackets should then be refitted.

Fit the tube support bracket, (5), figure 2.3.4. Use the M6 button head screws and washers supplied.

Fit the extended work tube guard, (4), figure 2.3.5. Use the M6 button head screws and washers supplied.

Re-fit furnace end guard, (3), figure 2.3.6. Use the M6 button head screws and washers supplied.

If supplied, fit the optional tube end seal assembly as shown in figures 2.3.9. and

2.3.10.

Refer to manual MEN-ENDSEALS-01 for detailed fitting instructions.

Fit the tube support bracket, (1), figure 2.3.7. Use the M6 button head screws and washers supplied.

Finally, fit tube support collar, (2) and secure figure tight using (6) until the tube is secure to be used in a vertical arrangement. The fitting arrangement is shown in figure 2.3.8.

Figure 2.3.3 - shows an exploded view of all the required parts.

Figure 2.3.8 - shows the assembled parts as they would be used.

Figure 2.3.3

2.0   Installation

Figure 2.3.4

Figure 2.3.5

Figure 2.3.6

Figure 2.3.7

Figure 2.3.8

13

2.0   Installation

Figure 2.3.9 - Tube support and end seal assembly

Figure 2.3.10 - Tube support and end seal assembly

Index to numbered items in figure 2.3.3 - 2.3.10

1. Tube support bracket

2. Tube support collar

14

2.0   Installation

3. End guards

4. Extended work tube guard

5. End adaptor

6. Fluted grip knob

Fitting the Optional Insulation Plugs and Radiation Shield

For optimum temperature uniformity, insulation plugs or radiation shields should be placed in the work tube ends as shown below. With a standard work tube, the insulation plug must be fitted as shown in figure A.

If a gas/vacuum end seal is fitted, either horizontally or vertically, the insulation plug hooks onto the end seal hook; see figure B.

Alignment of radiation shields is similar to that of insulation plugs, see figure C.

If a metal work tube is being used in the furnace, ensure that it is earthed. See the

safety warning in section 6.6.

Figure A- Cross-section view showing standard length work tube insulation plug fitted

Figure B- Cross-section view showing extended work tube insulation plug fitted

Figure C- Cross-section view showing an extended length work tube with a radiation shield fitted

15

2.0   Installation

2.4

Electrical Connections

Connection by a qualified electrician is recommended.

All furnaces in the range are single-phase and operate over the voltage ranges 100 to

110 volts or 200 - 240 volts. Check the rating label before connection, see "Warning

Labels" for location of rating label. To check that the OP.Hi setting is correct for the

appropriate voltage, or to change to another setting, follow the instructions in section

11.2.

The electrical supply should be fused at the next standard size equal to or higher than the design current. Where a supply cable is supplied there are internal supply fuses, in

which case customer fusing is preferred but not essential. See section 11.0 for furnace

rating power, current and fusing information.

The external connection should be either a permanent connection to a fused isolator supply or to a socket on a fused isolator supply; the isolating switch must operate on both conductors. Make sure that the isolator switch is within easy reach of the furnace operator.

Terminal Connection Details

Supply

1-phase

Terminal

L

N

PE

Label

UK/ Europe

Cable Colour

Brown

Blue

Green/ Yellow

USA/

Canada

Common

Cable

Colours

Red or

Black

Live -

Neutral

To live

White To neutral

Supply Type

Reversible or

Live - Live to either power conductor to the other power conductor

Green or

Green/

Yellow

To earth

(ground) to earth (ground)

16

3.0   3216 Controller

3.0

3216 Controller

3.1

PID control

This controller uses PID (Proportional Integral Derivative) temperature control. This type of control uses a complex mathematical control system to adjust the heating power and achieve the desired temperature.

3.2

3216P1

The 3216P1 is a digital temperature controller which uses PID algorithms to give excellent temperature control. This controller can store and operate a single program of

8 ramp/ dwell segments. The 3216P1 can also be used as a simple temperature controller.

3.3

3216P5

The 3216P5 is a digital temperature controller which uses PID algorithms to give excellent temperature control. This controller can store up to 5 programs of 8 ramp/ dwell segments. The 3216P5 can also be used as a simple temperature controller.

3.4

Operation

3.4.1

Controller Layout

Key

A Power Output Indicator

B Alarm Indicator

C

Remote Indicator

(when configured)

D Page

E Scroll

F Down

G Up

H Run Indicator

J

I Hold Indicator

Setpoint Temperature

(SP)

K

Measurement Temperature

17

3.0   3216 Controller

3.4.2

Keys

Page Key

Scroll Key

Ack

Page and

Scroll

Arrow Keys

+

+

The page key is used to access level 2 when held down for 3 seconds.

The scroll key is used to scroll through parameters.

When pressed simultaneously the ACK function is used to: l l l

Return to the Home Menu

Acknowledge an alarm if activated.

Reset a program after the program has ended.

The arrow keys are used individually to adjust the selected parameters and in combinations to operate a program.

Note: If a parameter is selected and no further action is taken, the display will time out and revert back to the home display in its working level after approximately 1 minute.

3.5

Quick Start Guide

3.5.1

Operation as a simple controller

When switched on, the controller goes through a short test routine and then shows the measured temperature (PV = Process Value) in the upper part of the display and below it, the desired temperature (Setpoint).

3.5.2

Changing the Setpoint

Press Up or Down to select the required SP. If the SP is higher than the measured temperature, the OP1 indicator will illuminate in the top left corner of the display, indicating that the controller is calling for power (giving an output).

The controller will immediately attempt to reach the setpoint and then maintain it.

This will cause the product to heat as quickly as possible which may not be appropriate where the product contains sensitive ceramic components. For products with ceramic components, e.g. a tube furnaces fitted with a long ceramic work tube, use the ramp rate feature set with a low heating rate such as 5°C per minute (300°C per hour), to prevent damage.

3.5.3

Using the Controller

The parameters in the controller are first shown by a short code (mnemonic). After 5

Seconds a description of the parameter will scroll once along the display and then revert back to the mnemonic. The scrolling text can be interrupted at any time by a single press of any of the buttons, but will not scroll again until the parameter is returned to.

18

3.0   3216 Controller

In this manual the mnemonic will be shown first, followed by the scrolling text in brackets; e.g. PROG <PROGRAM NUMBER>

3.5.4

Understanding User Levels

There are two user levels in the controller; Level 1 (Operator) and Level 2 (Supervisor).

Level 1 (Operator) is for the day to day operation of the controller. These parameters are not protected by a security code.

Level 2 (Supervisor) provides access to additional parameters. Access to this level protected by a security code

To Enter Level 2

1. Press and hold the page key for 3 seconds.

2. The display will show LEu 1 GOTO

3. Release the page Key

4. Press the up or down to choose LEu 2 (level 2)

5. Press the up or down to enter the code (Level 2 Code = 9).

If the correct code is entered, PASS should momentarily be displayed and then revert to the level 2 home display.

If an incorrect code is entered the display reverts back to Level 1 home display.

When level 2 operations have been completed, the supervisor must return to Level 1 either manually or by switching the instrument off and back on. There is no time out function.

To Return to Level 1

1. Press and hold the page Key

2. Press down to select LEu 1

It is not necessary to enter a code when going from a higher level to a lower level.

When level 1 is selected, the display reverts to the home display (See Controller Layout)

Table showing parameters accessible in level 1 and Level 2

Operator LEVEL 1 home display

Programming

Program Status

Supervisor LEVEL 2 home display

Programming

Program Status

Alarms (if configured)

Current Transformer Input (if configured)

Comms (if configured)

Controller Setup

Customer Calibration

TIP

19

3.0   3216 Controller

If while navigating the controller, a parameter has been passed or you need to access parameters which would be at the end of a scroll list, press and hold scroll and use up to return to a previous parameter.

3.6

Setting up the Controller

Before using the controller (or during its lifetime) certain parameters may have to be set, depending on specific requirements. To do this the controller must be set to supervisor level (Level 2).

3.6.1

Maximum Output Power

Press scroll until the display shows OP.HI <OUTPUT HIGH>. Use the up and down keys to select the output power required as a percentage. Once the setting is made, turn the instrument switch off and on to power cycle the temperature controller.

Depending on the furnace or oven model, the maximum output power setting OP.Hi

may be accessible or locked.

For silicon carbide heated furnaces, the parameter is accessible to allow compensation for element ageing.

In many models the maximum output power setting depends on the supply voltage, see

section 11.0.

3.6.2

Customer ID

A furnace or oven identification number can be entered if required. This maybe used to identify one of many units for production or quality control systems.

Press scroll until the display shows ID <CUSTOMER ID>. Use the up keys to enter your own identification number. This can range from 1-9999.

and down

3.6.3

Units or down Press scroll until the display shows UNITS <DISPLAY UNITS>. Use the up keys to select the required units.

Mnemonic

NONE

°C

°F

°K

PERC

Description

No units (Default °C)

Celsius

Fahrenheit

Kelvin

% (shows °C value)

3.6.4

Language

The scrolling text on the 3216 can be shown in different languages, this can only be set at the factory and therefore must be specified at the time of placing an order.

20

3.0   3216 Controller

3.6.5

Scrolling Text

If at any time the scrolling text is not required.

Press and hold the page for three seconds until “GOTO” is displayed.

Press scroll until the display shows. TEXT <ENABLE/ DISABLE SCROLLING TEXT>

Use the up and down keys to select ON or OFF.

3.6.6

Customer Calibration

The 3216 Controller series are calibrated for life at manufacture, there may however be sensor or other system errors, which affect the accuracy of the measured temperature.

Customer calibration can be used to compensate for these errors.

Dual Offset

Dual point calibration uses two offset values at two corresponding temperatures; this changes the calibration linearly as the temperature increases or decreases.

Press scroll until the display shows CAL.P (Enter Calibration Code) Use the up down keys to enter the password code. (Calibration Pass Code = 95). When the correct password has been entered the display will show PNT.LO. If the wrong pass code is entered the display will revert to zero pass code, until the correct pass code is entered.

When the correct pass code is entered and PNT.LO (Adjust Low Point) is displayed. Use the up and down keys to enter the Low Temperature Point, which you want to apply an Offset.

Press scroll until the display shows OFS.LO (Adjust Low OFFset). Use the up and down keys to enter the amount Offset you want to apply to the Low Temperature

Point.

Press scroll until the display shows PNT.HI (Adjust High Point). Use the up down and keys to enter the High Temperature Point, which you want to apply an Offset.

Press scroll until the display shows OFS.HI (Adjust High OFFset). Use the up down and keys to enter the amount Offset you want to apply the High Temperature

Point.

Once the calibration details have been entered, press scroll until the display shows the next required parameter or return to the home list. The calibration data will now be protected by the pass code. To edit the data the above procedure must be followed.

Single Offset

If a constant offset is required across the temperature range, set the required “High

Point” (PNT.HI) and “Low Point” (PNT.LO) to the required values (not the same), then set the “low Offset” (OFS.LO) and “High Offset” (OFS.HI) to the same value.

21

3.0   3216 Controller

Caution! - Do not make PNT.LO and PNT.HI the same value as the controller will not work correctly and could cause the product to overheat.

3.6.7

Holdback

If the temperature ramp rate of the program is quicker than the product can achieve, the program will wait until the temperature of the product catches up.

e.g. If a holdback value of 10 is set and the program is set to ramp to a setpoint of 600

°C, the program will reach 600 °C, then go into a hold state; the hold indicator will light until the product temperature reaches 590 °C, the program will then continue to control again.

The holdback will only apply once per segment, therefore when control has been reestablished, the holdback will not apply again to that segment, even if the product temperature goes outside the holdback band.

Holdback can only be accessed in supervisor level (level 2) by scrolling with the scroll until the display shows H.BACK <PROGRAM HOLDBACK>: Use the up keys to select the required Holdback value.

and down

If a multi programmer is used, each program can have its own holdback value assigned to it.

Note: When a holdback is set, each segment used must have a Ramp Rate assigned to it, in order for it to be recognised by the program.

22

3.0   3216 Controller

3.7

Programming

3.7.1

Creating a Program

Programs can be created in level 1 or level 2 of the 3216P1 and 3216P5. Each program contains 8 Ramp/ Dwell pairs.

Note: A currently active program cannot be altered. Go into 'Reset' mode before starting to create or modify a program

3.7.2

Program Number (3216P5 Only)

Press scroll until the display shows PROG <PROGRAM NUMBER.> Select the program number.

3.7.3

Ramp Units

Press scroll until the display shows RAMP.U <Ramp Units>: Use the up select the Ramp Units of Hour, Min or Seconds.

3.7.4

Dwell Units down to

Press scroll until the display shows DWEL.U <Dwell Units>: Use the up select the Dwell Units of Hour or Min.

3.7.5

Holdback down to

see section 3.6. Press scroll

until the display shows H.BACK <Program Holdback>: If a holdback value is required, use the up select “OFF” if no holdback is required.

down to enter the required value or

3.7.6

Ramp Rate

Press scroll until the display shows RMP.1 <Ramp Rate 1>: Using the up down enter the value for the first ramp rate depending on the Ramp Units selected. If the

Ramp segment is not required select “OFF”.

3.7.7

Target Setpoint

Press scroll until the display shows T.SP 1 <Target SP 1>: Enter the temperature that you want the product to ramp up to using “Ramp rate 1”.

If “Ramp Rate 1” has been set to “OFF”. The product will Heat/ Cool directly to the

Target SP.

3.7.8

Dwell Time

Press scroll until the display shows DWELL. 1 <DWELL TIME 1>: Enter the time to dwell at “Target SP 1”. If the dwell segment is not required, use the down to select

OFF, which is below the Zero value.

This Process is repeated for each of the 8 segments of the program.

23

3.0   3216 Controller

If not all the segments are used for a program, the Ramp & Dwell of each of the subsequent segments should be set to OFF.

A program will end in one of two ways, either revert to the control setpoint or dwell at the temperature set in the last segment used. When a program finishes on a dwell and the dwell time expires the temperature will revert to the control setpoint.

Note: Before operating a program ensure that the control setpoint is set to Zero to avoid unexpected heating at the end of the program.

3.7.9

Running a Program

If using the 3216P5 controller press scroll to display PROG <PROGRAM NUMBER>.

Select the required Program Number before operating a Program.

Table below shows the key presses to operate a program.

Operation Action

To RUN a program

Press and quickly release

+

Indication

Indicator – RUN = ON

Scrolling Display – Current

Program state

To HOLD a program

Press and quickly release

+

To RESET a program Press and hold

Program Ended

+ more than 1 second for

Indicator – RUN = Flashing

Scrolling Display – Program Hold

Indicator – RUN = OFF

Scrolling Display - None

Indicator – RUN = OFF

Scrolling Text – Program End

To RESET a program after it has completed

Press and hold + for more than 1 second or press and quickly release Ack

Indicator – RUN = OFF

Scrolling Display - None

3.7.10

Program Status

While the program is operating in level 1 or level 2, the home display shows two values at any one time:

3.7.11

Process Value

The upper display shows the current temperature of the product.

3.7.12

PSP, Segment Type and Number

The lower display continually alternates between the programs current set value

(Program SP = PSP) and scrolling text, indicating the current status of the program whether RAMP or DWELLING followed by the segment number.

Additional information can be obtained using the scroll key while the program is operating.

24

3.0   3216 Controller

Working Output Power

From the home display, press scroll until the display shows WRK.OP <WORKING

OUTPUT POWER>. This shows the power being used as a percentage.

Time Remaining

Press scroll until the display shows T.REMN <TIME REMAINING>. This shows the dwell time remaining for the current segment. There is no value for “Ramp Time

Remaining” therefore when the program is ramping the dwell time set will be shown and will only begin to count down when the ramp has finished.

Program Review

Further presses of scroll will reveal the settings of the current program operating.

These parameters are locked, while the program is operating.

Program Hold with Holdback

If a holdback value has been set (see section 3.6) and the program goes into a hold

state, the red “HLD” indicator will light, until the current temperature catches up.

If while in this condition the program itself is put into “Hold” by pressing the up , down together, the “HLD” indicator will turn off and the “Run” indicator will flash, indicating the program is on hold. When the program is started again by pressing the up , down together, the “Run“ indicator will stop flashing and show continually and the “HLD” indicator will light, if the current temperature has not caught up with the program.

Power Failure

If there is a power failure while the program is operating and the power is subsequently restored, the scrolling text will read <POWER FAIL - PROGRAM RESET>.

Press the “ACK” function to acknowledge this message, press the “ACK” function again to reset the program.

Alarms

Alarms are used to alert the operator when a pre-set level has been exceeded or a function error has occurred such as a sensor break. They are indicated by a scrolling message on the display and a flashing red ALM (Alarm) indicator. The alarm may also switch an output – usually a relay to allow external devices to be operated when an alarm occurs. Alarms only operate if they have been configured and are dependent on customer requirements.

How to acknowledge an alarm will depend on the type of latching which has been configured. A non-latched alarm will reset itself when the alarm condition is removed. A latched alarm requires acknowledgement with the “ACK” function before it is reset.

If an alarm has been activated the red “ALM” indicator will light and the scrolling text will indicate the type of alarm.

To acknowledge an alarm and cancel the “ALM” indicator, press “ACK” function.

Note: The alarm indicator may seem to be permanently on when viewed from above.

When an alarm is active the indicator should only be flashing, to confirm this, the controller must be viewed directly from the front.

25

26

3.0   3216 Controller

Program Example

The following sequence of entries creates and runs the program shown graphically below.

1. Press scroll until the display shows RAMP.U <SP RAMP UNITS>. Select MIN.

2. Press scroll until the display shows DWELL.U <DWELL UNITS>. Select MIN.

3. Press scroll until the display shows RMP.1 <RAMP RATE 1>. Select 5

4. Press scroll until the display shows T.SP1 <TARGET SP 1>. Select 600

5. Press scroll until the display shows DWEL.1 <DWELL TIME 1>. Select 30

6. Press scroll until the display shows RMP.2 <RAMP RATE 2>. Select 4

7. Press scroll until the display shows T.SP2 <TARGET SP 2>. Select 400

8. Press scroll until the display shows DWEL.2 <DWELL TIME 2>. Select 30

9. Press scroll until the display shows RMP.3 <RAMP RATE 3>. Select OFF

10. Press scroll until the display shows T.SP3 <TARGET SP 3>. Select 600

11. Press scroll until the display shows DWEL.3 <DWELL TIME 3>. Select 60

12. Press scroll until the display shows RMP.4 <RAMP RATE 4>. Select 3

13. Press scroll until the display shows T.SP4 <TARGET SP 4>. Select 800

14. Press scroll until the display shows DWEL.4 <DWELL TIME 4>. Select OFF

15. Press scroll until the display shows RMP.5 <RAMP RATE 5>. Select 5

16. Press scroll until the display shows T.SP5 <TARGET SP 5>. Select 400

17. Press scroll until the display shows DWEL.5 <DWELL TIME 5>. Select 480

18. Press the ACK function to return to the home display.

19. Press the up and down keys together, to operate the program.

Segment

3.0   3216 Controller

1

RMP.1= 5°C/Min

T.SP1= 600°C

Dwel.1= 30 Min

2

RMP.1= 4°C/Min

T.SP1= 400°C

Dwel.1= 30 Min

3

RMP.1= OFF

T.SP1= 600°C

Dwel.1= 60 Min

4

RMP.1= 3°C/Min

T.SP1= 800°C

Dwel.1= OFF

5

RMP.1=5°C

T.SP1= 400°C

Dwel.1= 480 Min

3.8

Controller Options

As options can be ordered in a variety of combinations and for a variety of purposes, exact instructions are not given here. The full Eurotherm manual may be required to determine customer parameter settings. To reveal or hide parameters in the controllers it is necessary to go into configuration mode, a security code is needed. Please consult

Carbolite Gero.

3.8.1

Digital Communications - RS232

If the RS232 option is supplied, the furnace is fitted with one sub-miniature Dsocket connected to the controller comms module. RS232 is suitable for direct connection to a personal computer (PC) using a “straight through” cable as follows

(the linked pins at the computer end are recommended but may not be necessary).

The cable is usually 9-pin at the furnace end and 9-pin at the computer, but other alternatives are shown in parentheses.

Product end of cable female (25-pin) 9-pin

RS232 Cable: product to PC

Computer end of cable

9-pin (25-pin) male

Rx

Tx

Com

(2)

(3)

(7)

3

2

5

_________________

_________________

_________________

3

2

(2)

(3)

Tx

Rx

5 (7) Com

7,8 (4,5) Link together

1,4,6 (6,8,20) Link together

3.8.2

Digital Communications - RS485

If an RS485 option is supplied, the furnace is fitted with two D-sockets. Connection between products is by “straight” cable as follows:

Product end of cable female (25-pin) 9-pin

-

+

Com

(2)

(3)

(7)

3

2

5

RS485 Cable: product to PC

_________________

Computer end of cable

9-pin (25-pin) female

3

2

5

(2)

(3)

(7)

Tx

Rx

Com

3.8.3

Comms Address

Typically the comms address is set to 1, but this can be changed. In the case of RS485 and multiple instruments it is necessary to set different addresses. To change the

27

3.0   3216 Controller address value, access the level 2 list. In level 2 press the page key until the COMMS parameter is displayed. Press up down to select the address value.

3.8.4

Alarm Option

When an alarm board is fitted, which consists of a relay with voltage free contacts, for operator use, the contacts are taken to a panel plug on the control panel, wired as indicated:

Key

C Temperature Controller

F Fuse (2A)

S Supply

L Load

*

Normally open relay contacts

RO

Relay Output 240V 2A

MAX

The purpose of the 2 amp fuse is to break the circuit to prevent overloading on the circuit due to high voltage.

The instrument configuration and parameters available to the operator depend on the customer requirements.

3.9

Temperature Controller Replacement

Before handling the controller: wear an anti-static wrist strap or otherwise avoid any possibility of damage to the unit by static electricity.

Refer to the detailed instructions supplied with the replacement controller.

Ease apart the two lugs at the side; grip the instrument and withdraw it from its sleeve; push in the replacement.

3.10

3216 Controller Navigation Diagram

The following diagram details how to navigate to the various menu options within the

3216 Controller. At each option, values can be set using the arrow keys.

28

3.0   3216 Controller

L1 Level 1 Press the Scroll Key

L2 Level 2

Press the Scroll Key multiple times

*

If configured A Access

**

Do not raise the power limit (if accessible) above the design level for the product

~

Multiple Program Only

Hold the Page key for 3 seconds

Locked - password required

Unlocked

Black = Progress

Dashed = Through multiple menus

White = Return

29

4.0   3216CC Controller

4.0

3216CC Controller

4.1

3216CC

This section should be disregarded unless the controller is used as an independent end zone controller.

The 3216CC Controller is a digital temperature controller which uses PID algorithms to give excellent temperature control when properly set. This controller can only be used as a simple temperature controller, it cannot be programmed.

4.2

PID control

This controller uses PID (Proportional Integral Derivative) temperature control. This type of control uses a complex mathematical control system to adjust the heating power and achieve the desired temperature.

4.3

Operation

4.3.1

Controller Layout

Key

A Power Output Indicator

B Alarm Indicator

C

Remote Indicator

(when configured)

D Page

E Scroll

F Down

G Up

H Run Indicator

I Hold Indicator

J

Setpoint Temperature

(SP)

K

Measurement Temperature

30

4.0   3216CC Controller

4.3.2

Keys

Page Key

Scroll Key

Ack

Page and

Scroll

Arrow Keys

+

+

The page key is used to access level 2 when held down for 3 seconds.

The scroll key is used to scroll through parameters.

When pressed simultaneously the ACK function is used to: l l l

Return to the Home Menu

Acknowledge an alarm if activated.

Reset a program after the program has ended.

The arrow keys are used individually to adjust the selected parameters and in combinations to operate a program.

Note: If a parameter is selected and no further action is taken, the display will time out and revert back to the home display in its working level after approximately 1 minute.

4.4

Quick Start Guide

4.4.1

Operation as a simple controller

When switched on, the controller goes through a short test routine and then shows the measured temperature (PV = Process Value) in the upper part of the display and below it, the desired temperature (Setpoint).

4.4.2

Changing the Setpoint

Press Up or Down to select the required SP. If the SP is higher than the measured temperature, the OP1 indicator will illuminate in the top left corner of the display, indicating that the controller is calling for power (giving an output).

The controller will immediately attempt to reach the setpoint and then maintain it.

This will cause the product to heat as quickly as possible which may not be appropriate where the product contains sensitive ceramic components. For products with ceramic components, e.g. a tube furnaces fitted with a long ceramic work tube, use the ramp rate feature set with a low heating rate such as 5°C per minute (300°C per hour), to prevent damage.

4.4.3

Using the Controller

The parameters in the controller are first shown by a short code (mnemonic). After 5

Seconds a description of the parameter will scroll once along the display and then revert back to the mnemonic. The scrolling text can be interrupted at any time by a single press of any of the buttons, but will not scroll again until the parameter is returned to.

In this manual the mnemonic will be shown first, followed by the scrolling text in brackets; e.g. PROG <PROGRAM NUMBER>

31

4.0   3216CC Controller

4.4.4

Understanding User Levels

There are two user levels in the controller; Level 1 (Operator) and Level 2 (Supervisor).

Level 1 (Operator) is for the day to day operation of the controller. These parameters are not protected by a security code.

Level 2 (Supervisor) provides access to additional parameters. Access to this level protected by a security code

To Enter Level 2

1. Press and hold the page key for 3 seconds.

2. The display will show LEu 1 GOTO

3. Release the page Key

4. Press the up or down to choose LEu 2 (level 2)

5. Press the up or down to enter the code (Level 2 Code = 9).

If the correct code is entered, PASS should momentarily be displayed and then revert to the level 2 home display.

If an incorrect code is entered the display reverts back to Level 1 home display.

When level 2 operations have been completed, the supervisor must return to Level 1 either manually or by switching the instrument off and back on. There is no time out function.

To Return to Level 1

1. Press and hold the page Key

2. Press down to select LEu 1

It is not necessary to enter a code when going from a higher level to a lower level.

When level 1 is selected, the display reverts to the home display (See Controller Layout)

Table showing parameters accessible in level 1 and Level 2

Operator LEVEL 1 home display

Supervisor LEVEL 2 home display

Programming

Program Status

Alarms (if configured)

Current Transformer Input (if configured)

Comms (if configured)

Controller set up (if configured)

Customer Calibration (if configured)

TIP

32

4.0   3216CC Controller

If while navigating the controller, a parameter has been passed or you need to access parameters which would be at the end of a scroll list, press and hold scroll and use up to return to a previous parameter.

4.5

Setting up the Controller

Before using the controller (or during its lifetime) certain parameters may have to be set, depending on specific requirements. To do this the controller must be set to supervisor level (Level 2).

4.5.1

Setpoint Ramp Rate

To control the rate at which the temperature rises to setpoint, the SP.RATE function is used.

Before setting the ramp rate, it is advisable to set the setpoint to a low value,

preferably 0 °C (see section 4.4). Once the ramp rate has been set, the required

setpoint can be entered from the home menu. Doing so will activate the ramp rate, which can be identified with the run indicator showing on the bottom of the display.

While the ramp rate is active the working setpoint will be shown on the lower temperature display (this is the setpoint, set by the ramp rate).

When the process temperature has reached the setpoint value at the given ramp rate, the run indicator will turn off and the instrument will control at the required setpoint temperature.

Any further modifications to setpoint will cause the ramp rate to be activated and the instrument to control as described above.

NOTE: Ensure timer configuration is set to ‘none’ (see section 4.6) to use the setpoint

ramp rate feature without any timer functions.

4.5.1.1

Setting Setpoint Ramp Rate

In supervisor level (level 2).

Press scroll until the display shows SP.Rate <setpoint rate limit>. Using up down select the ramp rate required, in °C/ Min.

4.5.1.2

Running with Ramp Rate and

Press the up and down keys at the same time to activate the ramp rate. The

"Run" indicator will illuminate and the scrolling text will read <RAMPING> to show the ramp rate is active. The ramp rate will then start from the current process temperature.

When the ramp reaches the setpoint temperature, the "Run" indicator will turn off and the instrument will maintain control at the setpoint.

To put the ramp rate into a hold condition, press the up and down keys and release. The "Run" indicator will flash and the scrolling text will read <HOLD> to show the ramp rate is on hold.

33

4.0   3216CC Controller

To cancel the ramp rate, press and hold the up indicator turns off.

4.5.2

Maximum Output Power and down keys until the "Run"

Press scroll until the display shows OP.HI <OUTPUT HIGH>. Use the up and down keys to select the output power required as a percentage. Once the setting is made, turn the instrument switch off and on to power cycle the temperature controller.

Depending on the furnace or oven model, the maximum output power setting OP.Hi

may be accessible or locked.

For silicon carbide heated furnaces, the parameter is accessible to allow compensation for element ageing.

In many models the maximum output power setting depends on the supply voltage, see

section 11.0.

4.5.3

Customer ID

A furnace or oven identification number can be entered if required. This maybe used to identify one of many units for production or quality control systems.

Press scroll until the display shows ID <CUSTOMER ID>. Use the up keys to enter your own identification number. This can range from 1-9999.

and down

4.5.4

Units or down Press scroll until the display shows UNITS <DISPLAY UNITS>. Use the up keys to select the required units.

Mnemonic

NONE

°C

°F

°K

PERC

Celsius

Kelvin

Description

No units (Default °C)

Fahrenheit

% (shows °C value)

4.5.5

Language

The scrolling text on the 3216 can be shown in different languages, this can only be set at the factory and therefore must be specified at the time of placing an order.

4.6

Timer

4.6.1

Setting the Timer

A timer can be configured to operate in four different modes. These can be selected in level 2 (supervisor level) using the TM.CFG parameter as:-

• None

• Dwell Timer

34

4.0   3216CC Controller

• Delayed switch on timer

• Soft start timer

None

The timer is turned off, no timer configurations are available, the instrument works as a simple setpoint controller.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select NONE.

4.6.2

Dwell Timer

A dwell timer is used to control a process at a fixed temperature for a defined period. At the end of the time period the controller will switch off the output power to the elements.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select Dwell.

When Dwell parameter is selected, the Timer resolution (TM.RES), Time duration

(DWELL) and Timer Threshold (THRES) functions become available.

Press scroll until the display shows TM.RES < Time resolution >. Use the up to select the timer units in Min or Hours.

down

Press scroll until the display shows DWELL < SET TIME DURATION >. Use the up down to enter the time duration required.

Press scroll until the display shows THres < TIMER THRESHOLD >. Use the up down to select the temperature threshold that you require the timer to start at.

The threshold value is ±n around the setpoint (n=threshold value).

Example: If the setpoint is set to 800 °C and the timer threshold is set to 2, after the timer is activated it will not start until the process value reaches 798 °C if ramping up or

802 °C if it is cooling.

Note: If the threshold is set to OFF, the timer will either; start to count down as soon

as it is activated with the mode keys or if a ramp rate has been set (see section 4.5.1

), the timer will start as soon as the ramp reaches the setpoint. (see section 4.7.1)

4.6.3

Delayed Switch On Timer

The delayed switch on timer is used to switch on the output power to the elements after a set time period.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select dELY.

When delay parameter is selected, the Timer Resolution (TM.RES) and Time Duration

(DWELL) functions become available.

Press scroll until the display shows TM.RES < Time Resolution >. Use the up to select the timer units in Min or Hours.

down

35

4.0   3216CC Controller

Press scroll until the display shows DWELL < SET TIME DURATION >. Use the up down to enter the time duration required before the output power switches on.

4.6.4

Soft Start Timer

The Soft Start Timer is used to start a process at a reduced setpoint and power. The

Soft Start Setpoint is used as a threshold only and is not a control point.

Example: Main Setpoint = 800 °C

Max power limit = 75 % (This may be set at the factory)

Soft Start Setpoint = 600 °C (Threshold)

Soft Start Power Limit = 50% (Cannot be set above max power Limit)

When the timer is running, the maximum power is controlled by the Soft Start Setpoint of 600 °C and the Soft Start Power limit of 50%. This will continue until the timer ends or the current temperature exceeds the Soft Start Setpoint.

When the timer ends or the current temperature exceeds the Soft Start Setpoint, the instrument will start to control using the main setpoint of 800 °C and the Max Power

Limit of 75%.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select SF.st.

When Soft Start parameter is selected, the Timer Resolution (TM.RES), Time Duration

(DWELL), Soft Start Setpoint (SS.SP) and Soft Start Power Limit (SS.PWR) functions become available.

Press scroll until the display shows TM.RES < Time resolution >. Use the up to select the timer units in minutes or hours.

down

Press scroll until the display shows DWELL < SET TIME DURATION >. Use the up down to enter the time duration required, before the instrument starts to control using the main setpoint and max power.

Press scroll until the display shows SS.SP < Soft Start Setpoint >. Use the up down to enter the Soft Start Setpoint.

Press scroll until the display shows SS.PWR < Soft Start Power Limit >. Use the up down to enter the Soft Start Power Limit.

4.7

Running a Timer

l l l l

Run . This starts the timer.

Hold . This stops the timer at the elapsed time. It will start again from the elapsed time when Run is selected again.

Reset . This sets the timer back to zero. It can be operated again from this state.

End cannot be set – it occurs automatically when the timer has counted down to zero.

36

4.0   3216CC Controller l

Acknowledge any timer after a timer has timed out using ACK function (see section

4.3.2) by pressing the

and simultaneously.

4.7.1

Dwell Timer

Operation

To RUN Timer

To HOLD timer

To switch off Timer / Cancel

Action

Press and quickly release

+

Press and quickly release

+

Press and hold + for more than 1 second

To return to home after reset Press and hold

+ for more than 1 second

Indication

Indicator – RUN = ON

Scrolling Display – Timer

Running

Indicator – RUN = Flashing

Scrolling Display – Timer

Hold

Indicator – RUN = OFF

Scrolling Display – None

Static Text - OFF

Indicator – RUN = OFF

Display – A-M <LOOP

MODE- AUTO MANUAL

OFF>

To re-RUN Timer

To RESET timer and return to home menu after timer end

Timer Ended

Press and quickly release

Ack

+

Press and quickly release

+

Press and hold + for more than 1 second

Use the up or down to select AUTO

Indicator – RUN = OFF

Scrolling Text – Timer End

Static Text - OFF

Indicator – RUN = ON

Scrolling Display – Timer

Running

Indicator – RUN = OFF

Scrolling Display - None

Indicator – RUN = OFF

Display – A-M <LOOP

MODE- AUTO MANUAL

OFF>

Use the up down to select

4.7.2

Power Failure While Using Dwell Timer

If there is a power failure while the timer is operating and the power is subsequently restored, the timer will reset and the static text will display “OFF“ until the are pressed to re-run the timer.

+ keys

37

4.0   3216CC Controller

4.7.3

Running Dwell Timer with Ramp Rate

Set the ramp rate as outlined in section 4.5.1

Set the dwell time as outlined in section 4.6.2.

When the timer is set to operate with a set ramp rate, the timer will not start to count down until the setpoint has been reached with the ramp, at which time the timer will begin time count down.

The scrolling display will indicate “timer running” and the run indicator will be illuminated while the ramp rate is active and during the timer count down, after which the display

will indicate the instrument has switched off power to the elements (see section 4.7.7),

and the run indicator will switch off.

4.7.4

Running Dwell Timer with Ramp Rate & Threshold

Set the ramp rate as outlined in section 4.5.1.

Set the dwell time as outlined in section 4.6.2.

Set the threshold as outlined in section 4.6.3.

When the timer is set to operate with a set ramp rate and threshold, the timer will not start to count down until the process temperature has reached the threshold value (see

example 4.6.3).

The scrolling display will indicate “timer running” and the run indicator will be illuminated while the ramp rate is active, while the process value is reaching the threshold value and during the timer count down, after which the display will indicate the instrument has

switched off power to the elements (see section 4.7.1).

4.7.5

Delayed Switch on Timer

Operation Action

To RUN Timer

To HOLD timer

Press and quickly release

Press and quickly release

+

+

Indication

Indicator – RUN = ON

Scrolling Display – Timer

Running

Static Text - OFF

Indicator – RUN = Flashing

Scrolling Display – Timer

Hold

Static Text - OFF

To switch off Timer /

Cancel

To return to home menu. After Resetting timer

Press and hold + for more than 1 second Indicator –

RUN = Off

Scrolling Display – None

Static Text - OFF

Press and hold + more than 1 second for

Indicator – RUN = Off

Display – A-M <LOOP MODE-

AUTO MANUAL OFF>

Use the up select or down to

38

4.0   3216CC Controller

To re-RUN Timer

Timer Ended

Press and quickly release +

Indicator – RUN = OFF

Scrolling Text – Timer End

Indicator – RUN = ON

Scrolling Display – Timer

Running

Static Text – OFF

4.7.6

Running Delay Timer with Ramp Rate

Set the ramp rate as outlined in section 4.5.1.

Set the delay time as outlined in section 4.6.3.

When ramp rate is active with a delay timer the run indicator serves two functions:

• Indicates timer is running

• Indicates ramp rate is active

This means that when the timer has timed out the run indicator will still be illuminated if the ramp rate is still active and will continue to be illuminated until the ramp reaches setpoint, at which time it will switch off.

A characteristic of these combinations of parameters is that the scrolling text will continue to indicate timer running when the timer has timed out. Checking whether the

timer has timed out or not can be done with the 'T.REMN' function. (see section 4.7.12)

The delay timer with ramp rate will function as outlined in the table above with the addition of the functions in the following table.

4.7.7

Delay timer with ramp rate functions

Timer Ended

When ramp rate active

Indicator – RUN = ON - if ramp rate active

Scrolling Text – Timer Running

To

HOLD timer

Press and quickly release +

Indicator – RUN = Flashing

Scrolling Display – Timer Hold

Static Text - OFF

To switch off

Timer /

Cancel

Press and hold

+ for more than 1 second

To re-

RUN

Timer Press and quickly release +

Indicator – RUN = ON - if ramp rate active

Scrolling Display – None

Static Text - OFF

Indicator – RUN = ON

Scrolling Display – Timer Running

Static Text – OFF

39

4.0   3216CC Controller

4.7.8

Power Failure While Using Delay Timer

If there is a power failure while the timer is operating and the power is subsequently restored, the timer will reset and will re-run from the power on time.

4.7.9

Soft start Timer

Operation

To RUN

Timer

To HOLD timer

To switch off

Timer/

Cancel

Action

Press and quickly release

Press and quickly release

Press and hold second

Timer Ended

+

+

+ for more than 1

Indication

Indicator – RUN = ON

Scrolling Display – Timer

Running

Static Text - OFF

Indicator – RUN = Flashing

Scrolling Display – Timer Hold

Static Text - OFF

Indicator – RUN = OFF

Scrolling Display – None

Static Text - OFF

Indicator – RUN = OFF

Scrolling Text – Timer End

Running Soft Start Timer

When the soft start timer is set to operate, the scrolling display will indicate “timer running” and the setpoint temperature, not the soft start setpoint.

4.7.10

Power Failure While Using Soft Start Timer

If there is a power failure while the timer is operating and the power is subsequently restored, the timer will reset and will re-run from the power on time.

4.7.11

Ramp Rate with Soft Start Timer

It is not recommended that the ramp rate function be used with a soft start timer.

Note: If the temperature is already above the threshold when the timer is set to operate, the timer will time out immediately.

4.7.12

Time Remaining

The time remaining of any 'Timer' mode can be checked at any time while a timer is active.

To view the time remaining, press scroll until the display shows T.REMN <TIME

REMAINING>.

Note: The time remaining can be modified at any time while the count down timer is operating by pressing the up active.

or down key while the time remaining function is

40

4.0   3216CC Controller

4.7.13

Alarms

Alarms are used to alert the operator when a pre-set level has been exceeded or a function error has occurred such as a sensor break. They are indicated by a scrolling message on the display and a flashing red ALM (Alarm) indicator. The alarm may also switch an output – usually a relay to allow external devices to be operated when an alarm occurs. Alarms only operate if they have been configured and are dependant on customer requirements.

How to acknowledge an alarm will depend on the type of latching which has been configured. A non-latched alarm will reset itself when the alarm condition is removed. A

latched alarm requires acknowledgement with the “ACK” Function (see section4.3.2)

before it is reset.

If an alarm has been activated the red “ALM” indicator will illuminate and the scrolling text will indicate the type of alarm.

To Acknowledge an alarm and cancel the “ALM” indicator, press ACK function.

Note: The alarm indicator may seem to be permanently on when viewed from above.

When an alarm is active the indicator should only be flashing, to confirm this, the controller must be viewed directly from the front.

4.8

Controller Options

As options can be ordered in a variety of combinations and for a variety of purposes, exact instructions are not given here. The full Eurotherm manual may be required to determine customer parameter settings. To reveal or hide parameters in the controllers it is necessary to go into configuration mode, a security code is needed. Please consult

Carbolite Gero.

4.8.1

Digital Communications - RS232

If the RS232 option is supplied, the furnace is fitted with one sub-miniature Dsocket connected to the controller comms module. RS232 is suitable for direct connection to a personal computer (PC) using a “straight through” cable as follows

(the linked pins at the computer end are recommended but may not be necessary).

The cable is usually 9-pin at the furnace end and 9-pin at the computer, but other alternatives are shown in parentheses.

Product end of cable female (25-pin) 9-pin

Computer end of cable

9-pin (25-pin) male

Rx

Tx

Com

(2)

(3)

(7)

3

2

5

RS232 Cable: product to PC

_________________

_________________

_________________

3 (2) Tx

2 (3) Rx

5 (7) Com

7,8 (4,5) Link together

1,4,6 (6,8,20) Link together

41

4.0   3216CC Controller

4.8.2

Digital Communications - RS485

If an RS485 option is supplied, the furnace is fitted with two D-sockets. Connection between products is by “straight” cable as follows:

Product end of cable female (25-pin) 9-pin

-

+

Com

(2)

(3)

(7)

3

2

5

RS485 Cable: product to PC

_________________

Computer end of cable

9-pin (25-pin) female

3

2

5

(2)

(3)

(7)

Tx

Rx

Com

4.8.3

Comms Address

Typically the comms address is set to 1, but this can be changed. In the case of RS485 and multiple instruments it is necessary to set different addresses. To change the address value, access the level 2 list. In level 2 press the page key until the COMMS parameter is displayed. Press up down to select the address value.

4.8.4

Alarm Option

When an alarm board is fitted, which consists of a relay with voltage free contacts, for operator use, the contacts are taken to a panel plug on the control panel, wired as indicated:

Key

C Temperature Controller

F Fuse (2A)

S Supply

L Load

*

Normally open relay contacts

RO

Relay Output 240V 2A

MAX

The purpose of the 2 amp fuse is to break the circuit to prevent overloading on the circuit due to high voltage.

The instrument configuration and parameters available to the operator depend on the customer requirements.

Before handling the controller: wear an anti-static wrist strap or otherwise avoid any possibility of damage to the unit by static electricity.

Refer to the detailed instructions supplied with the replacement controller.

42

4.0   3216CC Controller

Ease apart the two lugs at the side; grip the instrument and withdraw it from its sleeve; push in the replacement.

4.9

3216CC Navigation Diagram

43

5.0   2132 Over-Temperature

5.0

2132 Over-Temperature Controller Description (if fitted)

5.1

Description

Key

A Alarm Light

B Page

C Scroll

D Down

E Up

F Display

This over-temperature controller is fitted and supplied ready to use by Carbolite Gero.

It is a digital instrument with a latching alarm, requiring no additional panel controls.

The controller features easy setting of over-temperature setpoint and reading of current temperature by the over-temperature sensor.

5.2

Operation

5.2.1

Controls

Most Carbolite Gero products are fitted with an instrument switch which cuts off power to the controller and other parts of the control circuit.

To operate the controller, power must be supplied to the product and the instrument switch must be on. If a time switch is included in the product circuit, this must be in the

'ON' position.

When an over-temperature condition occurs, the controller cuts the power to a contactor, which in turn cuts power to the heating elements. Power is not restored until the controller is 'reset'.

Some components will operate after the over-temperature feature isolates the power supply e.g. cooling fans will continue to operate, provided that there is a power supply to the product. In some cases the product may not do so, if other options (such as a door switch) are fitted.

44

5.0   2132 Over-Temperature

5.2.2

Operation

When switched on, the controller lights up, goes through a short test routine and then displays the measured temperature or the over-temperature setpoint.

The page key allows access to parameter lists within the controller.

A single press of the page key displays the temperature units, normally set to °C; further presses reveal the lists indicated in the navigation diagram.

The scroll key allows access to the parameters within a list. Some parameters are display-only; others may be altered by the operator.

A single press of the scroll key in the 'Home' list displays the temperature units; further presses reveal the parameters in the current list indicated in the navigation diagram.

To return to the 'Home' list at any time, press page and scroll together, or wait for 45 seconds.

The down and up keys are used to alter the setpoint or other parameter values.

5.2.3

Over-Temperature Operation

Use down and up to alter the over-temperature setpoint. This should normally be set a little above the working temperature (for example 15 °C above). The product is supplied with the over-temperature set at 15 °C above the furnace or oven maximum working temperature.

Press scroll twice view the present temperature as measured by the overtemperature controller. Press it twice, the first press shows the temperature units (°C).

5.2.4

Over-Temperature Alarm

If an over-temperature condition occurs, the OP2 indicator flashes and an alarm message 2FSH also flashes, alternating with the setpoint. Power to the heating elements is disconnected.

5.2.5

Resetting the Over-Temperature Alarm

To acknowledge the alarm press scroll and page together.

If the alarm is acknowledged while there is still an over-temperature condition, the OP2 indicator stops flashing but continues to glow. The 2FSH alarm continues to flash until the over-temperature condition is cleared (by the temperature falling), when normal operation resumes.

If the alarm is acknowledged when the temperature has dropped (or after the overtemperature setpoint has been raised) so that the over-temperature condition no longer exists, then the furnace or oven immediately resumes normal operation.

5.2.6

Sensor Break

The over-temperature cut-out system also operates if the over-temperature control thermocouple breaks or becomes disconnected. The message S.br flashes where the measured temperature is normally displayed.

45

5.0   2132 Over-Temperature

5.3

Audible Alarm

If an audible alarm is supplied for use with the over-temperature controller, it is normally configured to sound on over-temperature condition and to stop sounding when

the alarm is acknowledged as given in section 5.2.

Note: the alarm may sound during controller start-up.

5.4

Navigation Diagram

HL Home List

OTSP

Over-Temperature

Setpoint

AL Access List

Page Key

Scroll Key

For factory access to list and parameters not available to the operator.

Black = Progress

Dashed = Through to other options

46

6.0   Operation

6.0

Operation

6.1

Operating Cycle

This product is fitted with an instrument switch which cuts off power to the control circuit.

Connect the product to the electrical supply.

Turn on the instrument switch to activate the temperature controllers. The controllers illuminate and go through a short test cycle.

Over-Temperature option only . If the digital over-temperature option has not yet been set as required, set and activate it according to the over-temperature controller instructions.

Switch on the heater switch, located on the instrument panel. Unless a time switch is fitted and is switched off, the product will start to heat up. The Heat light(s) glow steadily at first and then flash as the product approaches the desired temperature or a program setpoint.

Over-Temperature option only.

If the over-temperature circuit has tripped, an indicator on the over-temperature controller flashes and the heating elements are isolated. Find and correct the cause before resetting the over-temperature controller according to the instructions supplied.

To switch off power to the heating elements, use the heater switch. To switch the product off, use both the heater switch and the instrument switch. If the product is to be left switched off and unattended, isolate it from the electrical supply.

6.2

Control Method

Set the three temperature controllers to the desired setpoints. The setting and operation of the end zone controllers depends on the 3-zone control options selected when the product was ordered. These options are described in the 3-zone control methods section.

Note: Despite its vertical orientation, the heated zones of the KVZ model are labelled to correspond with the relevant control module on the CC-T1 touchscreen controller display (Left, Main, Right).

6.3

Safe Operation of the Furnace

For the safe operation of this furnace the following warnings must be followed:

47

6.0   Operation

Explosive Materials

The furnace must not be used to heat materials which could explode, or which could emit gases that could form explosive mixtures. If the safe heating of a material is dependent on its temperature, only heat these type of materials if the furnace has the optional over-temperature protection device fitted. Ensure that the over-temperature device is calibrated and set to an over-temperature safety limit that is sufficiently large as to avoid any hazards. If in doubt, seek expert advice before proceeding. Customers are responsible for carrying out their own risk assessments on the heating of materials.

Do not operate without a work tube . The furnace must not be operated without the correctly sized work tube and correspond work tube adaptor. Otherwise, an operator can access electrically live element coils that could cause serious injury of death.

Switch off the furnace before loading and unloading.

The furnace elements must be switched off using the heater switch, item 2 in

"Warning Labels", when the furnace is being loaded or unloaded. The

work tube can become electrically conductive at high temperatures. If an element has failed and collapsed onto the work tube, the work tube will become live causing serious injury or death.

6.4

3-Zone Control Methods

There are three different control options (A, B & C).

(A) Back to back thermocouples

(B) Retransmission of Setpoint

(C) Independent control

The models listed in this manual are designed to achieve an extended uniform temperature zone, through use of three control zones, rather than achieving different temperatures in each zone.

For A & B, the control zones are linked so that they all follow the centre zone controller in a master-slave approach

Note: l l

Option A is NOT applicable when using the CC-T1 controller

Option B is NOT applicable when using the Eurotherm 2132 End Zone Controller

48

6.0   Operation

A. Back-to-Back Thermocouples

This is the most commonly supplied option. The centre zone of the tube furnace is controlled directly by the centre zone temperature controller. The two end zone thermocouples are wired in opposition to the centre zone reference thermocouple. If the temperatures of the centre and end zones are the same then 0°C will be displayed on the end zone controllers. If the end zone temperatures are either higher or lower than the centre zone, the end zone controller will display the difference in temperature

(higher = positive value, lower = negative value).

It is best practice to set the setpoint of the two end zone controllers to zero.

Alternatively, a small temperature difference (offset) can be created by setting a nonzero value, for example to compensate for heat losses at the end or where using a gas flow. However, the sum of the centre zone controller setpoint and the end zone controller offset MUST NOT exceed the furnace maximum temperature.

To alter the setpoint with the display showing the Home screen, press Down or Up once to display the setpoint and then press again or hold down to adjust it. The display returns to the measured temperature when no key is pressed for a short period of time.

Sometimes a furnace using this type of control does not cool down because the end zones lose heat first and therefore the end zone controllers try to compensate for this by switching on the end zone elements, preventing the furnace from cooling.

B. Retransmission of Setpoint

Three independent thermocouples are connected to three controllers. The three controllers are linked together and the centre zone controller communicates the desired setpoint to the end zone controllers. If the centre zone controller is set to a setpoint or is running a program, the end zone controllers will automatically follow.

For products with the CC-T1 controller, please refer to the separate CC-T1 controller manual for details on enabling and disabling setpoint retransmission.

For other products, additional communication modules are fitted in the controllers. The communication between the controllers of the Eurotherm 3000 series is known as

Broadcast communications. It is possible to switch off the linked control and allow the controllers to work independently. In the level 2 menu of the end zone controllers (see controller operating instruction), scroll to L-r. Where the end zone controller is a 3216 use the up down buttons and select NO. Where the end zone controller is a 3508 use the up down buttons to select SP1, (SP1 = Local, and SP2 = Remote). There is no need to alter the centre zone controller.

It is possible to set an offset (local trim) between the centre and end zone controllers.

This can be either a positive or negative difference from the centre zone temperature.

Once entered, this offset will always be added to, or subtracted from, the retransmitted setpoint temperature.

49

6.0   Operation

For products with the CC-T1 controller, please refer to the separate CC-T1 controller manual for details on how to set an offset trim.

To make this adjustment on other controllers, enter thelevel 2 menu of the end zone controllers (see controller operating instruction), scroll to LOC.T (local trim) and use the up down buttons to enter the desired positive or negative value. This will then be added to, or subtract from, the end zone set temperature. There is no need to alter the centre zone controller.

C. Independent Control

The three controllers are completely independent. Note that it is not possible to maintain very different temperatures in the three zones because of heat transfer between the zones. The models listed in this manual are designed to achieve an extended uniform temperature zone by the use of three control zones rather than achieving different temperatures in each zone.

6.5

General Operating Advice

Heating element life is shortened by overheating. Do not leave the product at high temperature when it is not required. The maximum

temperature is shown on the product rating label and in section 12.0

towards the back of this manual.

Lightweight ceramic fibre insulation can easily be marked by accidental contact. Some fine cracks may develop in the surface of the insulation due to the progressive shrinkage of the insulation materials. Cracks are not usually detrimental to the functioning or the safety of the product.

Clean up any spillages in the insulation, as these can increase the rate of degradation of the insulation material.

6.6

Operator Safety

The ceramic materials used in the product manufacture become electrically conductive to some extent at high temperatures. DO NOT use any conductive tools within the product without isolating it. If a metal work tube is used, it must be earthed (grounded).

Switch off the heater switch whenever loading or unloading the product.

The elements are isolated when the heater switch is OFF. This switch cuts both sides of the circuit via a contactor.

50

6.0   Operation

6.7

Tube Life

A ceramic work tube may crack if work pieces are inserted too quickly or at temperatures below 900 °C (when the tube is more brittle). Large work pieces should also be heated slowly to ensure that large temperature differences do not arise.

Poor thermal contact should be encouraged between the work piece and the tube; crucibles or boats should be of low thermal mass and should have feet to reduce the contact with the tube (fig. 4).

Key

A Tube

B Crucible

Fig 4 - Avoidance of thermal contact

Do not set too high a heating or cooling rate. As tubes are susceptible to thermal shock and may break. Tubes which extend beyond the heated part of the furnace are more at risk. A general rule for maximum heating or cooling rate is 400 ÷ internal diameter in mm to give (°C/ min); for 75 mm i/ d tubes this comes to 5 °C per minute. The controller can be set to limit both the heating and cooling rate.

6.8

Pressure

Work tubes are not able to accept high internal pressure. When gas seals or similar fittings are in use, the gas pressure should be restricted to a maximum of 0.2 bar (3 psi). A pressure of approximately half of that should normally be sufficient to achieve the desired flow rate. The operator must ensure that the exhaust path from the tube is not blocked, so that excess pressure does not occur.

A suitably regulated gas supply should always be used.

It is recommended that a pressure relief system should be used to avoid an over pressurisation of the work tube.

Please note: A product should not be heated up if any valves that have been fitted are closed to create a sealed volume. A sealed work tube should not be heated from cold due to the pressure increase caused by the trapped air or gas expanding during the heating process.

6.9

Gas Tightness

Work tubes of IAP material are impervious. Sillimanite may look similar but is porous.

Ensure that the correct tube material is in use before connecting and using gases other

51

6.0   Operation than inert gases, such as nitrogen.

52

7.0   Maintenance

7.0

Maintenance

7.1

General Maintenance

Preventive rather than reactive maintenance is recommended. The type and frequency depends on the product use; the following are recommended.

7.2

Maintenance Schedule

CUSTOMER

QUALIFIED PERSONNEL

DANGER! ELECTRIC SHOCK . Risk of fatal injury. Only electrically qualified personnel should attempt these maintenance procedures.

Safety

Maintenance

Procedure

Over-Temperature Safety Circuit

(if fitted)

Method

Set an over-temperature setpoint lower than the displayed temperature and check for an over-temperature alarm as detailed in this manual

Over-Temperature Safety Circuit

(if fitted)

Safety Switch Function

(split models only)

Safety Switch Function

(split models only)

Electrical Safety (external)

Electrical Safety (internal)

Electrical measurement

Set a safe temperature above ambient, and open the furnace to see if the heater light goes out

Electrical measurement

Visual check of external cables and plugs

Physically check all connections and cleaning of the power plate area

Frequency

Daily Weekly Monthly

Bi-

Annually

Annually

Function

Temperature Calibration

Operational Check

Operational Check

Work Tube Position

End Plugs / Radiation Shields

Tested using certified equipment, frequency dependent on the standard required

Check that all functions are working normally

Thorough inspection and report incorporating a test of all functions

Visually check that the tube is central to the heated zone (horizontally / vertically)

Visual check for damage or wear, and correct positioning

53

7.0   Maintenance

Seals (if fitted)

Performance

Element Circuit

Power Consumption

Cooling Fans (if fitted)

Check all seals and O-rings and clamps

Electrical measurement

Measure the current drawn on each phase / circuit

Check whether the cooling fans are working

54

7.0   Maintenance

7.2.1

Cleaning

Soot deposits may form inside the furnace, depending on the process. At appropriate intervals remove these by heating as indicated in the General Operation Notes.

The product's outer surface may be cleaned with a damp cloth. Do not allow water to enter the interior of the case or chamber. Do not clean with organic solvents.

7.3

Calibration

After prolonged use, the controller and/or thermocouple may require recalibration. This is important for processes that require accurate temperature readings or for those that use the product close to its maximum temperature. A quick check using an independent thermocouple and temperature indicator should be made from time to time to determine whether full calibration is required. Carbolite Gero can supply these items.

Depending on the controller fitted, the controller instructions may contain calibration instructions.

7.4

After-Sales Service

Carbolite Gero Service has a team of Service Engineers who can offer repair, calibration and preventive maintenance of furnace and oven products both at the Carbolite Gero factory and at customers’ premises throughout the world. A telephone call or email often enables a fault to be diagnosed and the necessary parts to be despatched.

In all correspondence please quote the serial number and model type given on the rating label of the product. The serial number and model type are also given on the back of this manual when supplied with the product.

Carbolite Gero Service and Carbolite Gero contact information can be found on the back page of this manual.

7.5

Recommended Spare Parts and Spare Parts Kit

Carbolite Gero can supply individual spare parts or a kit of the items most likely to be required. Ordering a kit in advance can save time in the event of a breakdown.

Each kit consists of two thermocouples of different lengths, one solid state relay and one complete tube body element set. When ordering spare parts please quote the model details i.e. model type and serial number as stated on the rating label.

55

8.0   Repairs and Replacements

8.0

Repairs and Replacements

8.1

Safety Warning - Disconnection from Power Supply

Immediately switch the product off in the event of unforeseen circumstances (e.g. large amount of smoke). Allow the product to return to room temperature before inspection.

Always ensure that the product is disconnected from the electrical supply before repair work is carried out.

Caution : Double pole/neutral fusing may be used in this product.

8.2

Safety Warning - Refractory Fibre Insulation

Insulation made from High Temperature Insulation Wool

Refractory Ceramic Fibre, better known as (Alumina silicate wool - ASW).

This product contains alumino silicate wool products in its thermal insulation. These materials may be in the form of blanket or felt, formed board or shapes, slab or loose fill wool.

Typical use does not result in any significant level of airborne dust from these materials, but much higher levels may be encountered during maintenance or repair.

Whilst there is no evidence of any long term health hazards, it is strongly recommended that safety precautions are taken whenever the materials are handled.

Exposure to fibre dust may cause respiratory disease.

When handling the material, always use approved respiratory protection equipment (RPE-eg. FFP3), eye protection, gloves and long sleeved clothing.

Avoid breaking up waste material. Dispose of waste in sealed containers.

After handling, rinse exposed skin with water before washing gently with soap

(not detergent). Wash work clothing separately.

Before commencing any major repairs it is recommended to make reference to the

European Association representing the High Temperature Insulation Wool industry

(www.ecfia.eu).

Further information can be provided on request. Alternatively, Carbolite Gero Service can quote for any repairs to be carried out either on site or at the Carbolite Gero factory.

8.3

Temperature Controller Replacement

Refer to the controller instructions for more information on how to replace the temperature controller.

56

8.0   Repairs and Replacements

8.4

Solid-state Relay Replacement

Disconnect the product from the power supply and remove the appropriate cover as given above.

Make a note of the wire connections to the solid state relay and disconnect them.

Remove the solid state relay from the base panel or aluminium plate.

Replace and reconnect the solid state relay ensuring that the bottom of it has good thermal contact with the base panel or aluminium plate.

Replace the access panel.

8.5

Thermocouple Replacement

For vertical models it may be necessary to dismount the furnace from its stand and remove the terminal cover.

Disconnect the product from the power supply. Remove terminal cover to gain access to the thermocouple connections. Make a note of the thermocouple connections.

Thermocouple cable colour codings are: thermocouple leg colour positive (type N) negative pink white

Disconnect the thermocouple from its terminal block.

Carefully withdraw the thermocouple from the product and remove any broken bits of thermocouple.

Bend the new thermocouple carefully to match the shape of the original (working from the terminal end). Should the length differ from that of the original this is usually not important provided that the thermocouple tip is within a work tube diameter's distance from the furnace centre.

Insert the new thermocouple into position, restoring any removed porcelain spacers and ensuring correct polarity.

Re-assemble the furnace.

8.6

Element Replacement

Individual elements are not available for this model of product, if an element fails then a complete element assembly is required. For details and fitting instructions contact

Carbolite Gero Service, see the back page of this manual for contact information.

57

8.0   Repairs and Replacements

8.7

Fuse Replacement

Fuses are marked on the wiring diagram with type codes, e.g. F1, F2. For more

information on fuses refer to section 11.0.

Depending on model and voltage, the different fuse types may or may not be fitted.

If any fuse has failed, it is advisable for an electrician to check the internal circuits.

Replace any failed fuses with the correct type. For safety reasons do not fit larger capacity fuses without first consulting Carbolite Gero.

The fuses are located at the cable entry point. Remove the back panel or control box back panel to gain access to the fuses.

58

9.0   Fault Analysis

9.0

Fault Analysis

A.

Furnace Does Not Heat Up

1.

The HEAT light is ON

The heating element has failed

2.

The HEAT light is OFF

The controller shows a very high temperature or code such as S.br

The controller shows a low temperature

There are no lights glowing on the controller

Check also that the SSR is working correctly

The thermocouple has broken or has a wiring fault

The door switch(es) (if fitted) may be faulty or need adjustment

The contactor/relay (if fitted) may be faulty

The heater switch (if fitted) may be faulty or need adjustment

The SSR could be failing to switch on due to internal failure, faulty logic wiring from the controller, or faulty controller

Check the supply fuses and any fuses in the furnace control compartment

The controller may be faulty or not receiving a supply due to a faulty switch or a wiring fault.

59

9.0   Fault Analysis

B.

Product Overheats

1.

Product only heats up when the instrument switch is ON

2.

Product heats up when the instrument switch is OFF

The controller shows a very high temperature

The controller shows a low temperature

The SSR has failed

"ON"

The controller is faulty

The thermocouple may be faulty or may have been removed out of the heating chamber

The thermocouple may be connected the wrong way around

The controller may be faulty

Check for an accidental wiring fault that could have overloaded the SSR

60

10.0

Wiring Diagrams

10.1

WC-13-30

10.0   Wiring Diagrams

10.2

WC-13-31

Connections below show single phase with indirect safety switches and overtemperature control.

61

11.0   Fuses and Power Settings

11.0

Fuses and Power Settings

11.1

Fuses

F1 - F2: Refer to the circuit diagrams.

F1

Internal

Supply

Fuses

F2

Auxiliary

Circuit Fuses

Customer

Fuses

Fitted if supply cable fitted.

Fitted on board to some types of EMC filter.

GEC Safeclip of the type shown

(glass type F up to 16 A)

38 mm x 10 mm type F fitted on

EMC filter circuit board(s)

Fitted on board to some types of EMC filter.

May be omitted up to 25 Amp/ phase supply rating.

Required if no supply cable fitted.

Recommended if cable fitted.

2 Amps glass type F

On board: 20 mm x 5 mm

Other: 32 mm x 6 mm

See rating label for current;

See table below for fuse rating.

Model

EHC 12/600B

EHC 12/600B

Phases

1-phase

1-phase

Volts

200-208

220-240

Supply Fuse Rating (Amps)

F1

16 A

16 A

62

11.0   Fuses and Power Settings

11.2 Power Settings

The power limit settings (OP.Hi) for this model is as follows. The figures represent the maximum percentage of time that controlled power is supplied to the elements. Do not attempt to "improve performance" by setting a value higher than the one from the table. To adjust the parameter refer to the "Changing the Maximum Output Power" of the control section of the manual.

All standard models covered by this manual are fitted with elements designed for use over the range of voltages 100 V-120 V and 200 V-240 V; the power limit parameter is set according to the table below.

The power limit depends on the voltages follows:

Voltage

Percentage (%)

100 V 120 V 200 V 208 V 220 V 230 V 240 V

100 100 89 81 75

Please refer to the rating label for product specific information.

63

12.0   Specifications

12.0

Specifications

Carbolite Gero reserves the right to change the specification without notice.

All models have cylindrical elements with wire mounted in the surface of the insulation material.

All models can accept work tubes up to a maximum outside diameter of 60 mm.

All models have a maximum operation temperature of 1200°C (1100°C continuous).

Model

Max Temp

(°C)

Max Power

(kW)

Minimum

Work

Tube

Length

(mm)

Tube length for use with modified atmosphere

(mm)

Heated

Length

(mm)

Weight

(kg)

EHC 12/600B 1200

Horizontal 3-zone tube furnaces.

2.52

750 1050 600 25

Work tube adaptors, extended work tube supports, insulation plugs and gas/ vacuum end seals are available from Carbolite Gero for work tubes with outside diameters of 32 mm, 46 mm and 60 mm.

12.1

Environment

The furnaces contain electrical parts and should be stored and used in indoor conditions as follows:

Ambient temperature working range

Temperature: 5 °C to 40 °C

Note: when operating the furnace at temperatures close to the maximum and the ambient temperature is above 30 °C, the allowed external temperature defined in EN

61010-1:2010 may be exceeded.

Relative humidity

Maximum 80% up to 31 °C, decreasing linearly to 50% at 40 °C.

Important safety notice:

After transportation or storage in humid conditions, the furnace could fail to meet all the safety requirements of BSEN 61010-2-010 until it has completed the drying out process to restore its normal condition.

Warning:

It cannot be assumed that the furnace will meet all the safety requirements of BSEN

61010-2-010 during the drying out process.

64

12.0   Specifications

Furnace drying out process

Step 1. Before the furnace is connected to the electrical supply, remove the back panel and check for signs of moisture on the electrical circuits. If visible signs of moisture are present then allow it to dry out in ambient temperature for at least 24 hours. If the problem persists ensure that the furnace is isolated and contact Carbolite Gero Service for more information.

Step 2. Complete the Installation procedure (see section 2.1

Step 3. After reading the controller operation instructions, heat the furnace following the temperature profile given below. This will need to be done manually on furnaces with basic control option or programmed into the controller if an advanced control option is fitted: l l l l l

Ramp the setpoint temperature @ 2 °C/ minute to 100 °C and dwell for 2 hours.

Ramp the setpoint temperature @ 2 °C/ minute to 300 °C and dwell for 3 hours.

Ramp the setpoint temperature @ 3 °C/ minute to 1100 °C and dwell for 1 hour.

Cool naturally to ambient temperature.

Furnace drying out process is complete.

65

Notes

Engineer Name Date

Service Record

Record of Work

The products covered in this manual are only a small part of the wide range of ovens, chamber furnaces and tube furnaces manufactured by Carbolite Gero for laboratory and industrial use. For further details of our standard or custom built products please contact us at the address below, or ask your nearest stockist.

For preventive maintenance, repair and calibration of all furnace and oven products, please contact:

Carbolite Gero Service

Telephone: + 44 (0) 1433 624242

Fax: +44 (0) 1433 624243

Email: [email protected]

Carbolite Gero Ltd,

Parsons Lane, Hope, Hope Valley,

S33 6RB, England.

Telephone: + 44 (0) 1433 620011

Fax: + 44 (0) 1433 621198

Email: [email protected]

www.carbolite-gero.com

Copyright © 2019 Carbolite Gero Limited

advertisement

Related manuals

advertisement