Carbolite Gero TZF 12/38/400 with 3508 centre zone and 3216CC end zones Installation, Operation And Maintenance Instructions

Add to My manuals
80 Pages

advertisement

Carbolite Gero TZF 12/38/400 with 3508 centre zone and 3216CC end zones Installation, Operation And Maintenance Instructions | Manualzz

Installation, Operation and Maintenance Instructions

1200 °C Tube Furnace (3-zone) - TZF Model: 400mm

3508 Controller + 3216CC End Zone Controllers

TZF 12/38/400 + 3508 Controller + 3216CC

End Zone Controllers

MEN-TZF12038-400-09_3508_3216CC ( 19-06-

2019 )

2

Contents

This manual is for guidance on the use of the Carbolite Gero product specified on the front cover. This manual should be read thoroughly before unpacking and using the furnace or oven. The model details and serial number are shown on the back of this manual. Use the product for the purpose for which it is intended.

1.0 Symbols and Warnings

1.1

Switches and Lights

1.2

General Warnings

2.0 Installation

2.1

Unpacking and Handling

2.2

Siting and Setting Up

2.3

Electrical Connections

3.0 3508 Controller

3.1

PID control

3.2

3508P1

3.3

3508P10

3.4

3508P25

3.5

Basic Operation

3.5.1

Controller Layout

3.5.2

Keys

3.6

Quick Start Guide

3.6.1

Operation as a simple controller

3.6.2

Changing the Setpoint

3.6.3

Resetting the programmer

3.6.4

Understanding User Levels

3.7

Setting Up Controller

3.7.1

Maximum output power setting

3.7.2

Customer ID.

3.7.3

Units

3.7.4

Language

3.8

Programming

3.8.1

Programming Notes

3.8.2

Holdback

3.8.3

Wait Segments

3.8.4

Program Cycling

3.8.5

Creating a Program

3.8.6

Running a Program

3.8.7

To pause (hold) a program

3.8.8

To stop and reset a program

9

9

9

12

7

7

7

15

21

21

22

22

20

20

20

20

23

24

24

18

19

19

19

17

17

17

18

15

15

15

15

16

17

17

3.8.9

To run a different program (P10 and P25)

3.8.10

Program Status

3.8.11

Program Hold with Holdback

3.8.12

Power Failure Recovery

3.8.13

Alarms

3.8.14

Program Example 1

3.8.15

Program Example 2

3.9

Controller Options

3.9.1

Digital Communications - RS232

3.9.2

Digital Communications - RS485

3.9.3

Comms Address

3.9.4

Alarm Option

3.9.5

Remote Input and Output (Analogue Communications)

3.9.6

Program segment output

3.10

Temperature Controller Replacement

3.11

Controller Navigation Diagrams

3.11.1

Operator Level 1 - No Program Running

3.11.2

Operator Level 1 - Program Running

3.11.3

Supervisor Level 2

4.0 3508 Dual Loop Cascade Control (if fitted)

4.1

Principle of Cascade Control

4.2

Operation of Cascade Control

4.3

Bypassing Cascade Control

4.4

3508P1 Element Loop (Loop 2)

4.5

Caution

4.6

Over-Temperature Control

5.0 3216CC Controller

5.1

3216CC

5.2

PID control

5.3

Operation

5.3.1

Controller Layout

5.3.2

Keys

5.4

Quick Start Guide

5.4.1

Operation as a simple controller

5.4.2

Changing the Setpoint

5.4.3

Using the Controller

5.4.4

Understanding User Levels

5.5

Setting up the Controller

37

37

37

41

41

41

41

32

32

33

33

31

31

31

31

25

26

28

30

24

24

25

25

34

35

36

42

43

43

43

43

43

44

45

42

42

42

42

3

4

5.5.1

Setpoint Ramp Rate

5.5.1.1

Setting Setpoint Ramp Rate

5.5.1.2

Running with Ramp Rate

5.5.2

Maximum Output Power

5.5.3

Customer ID

5.5.4

Units

5.5.5

Language

5.6

Timer

5.6.1

Setting the Timer

5.6.2

Dwell Timer

5.6.3

Delayed Switch On Timer

5.6.4

Soft Start Timer

5.7

Running a Timer

5.7.1

Dwell Timer

5.7.2

Power Failure While Using Dwell Timer

5.7.3

Running Dwell Timer with Ramp Rate

5.7.4

Running Dwell Timer with Ramp Rate & Threshold

5.7.5

Delayed Switch on Timer

5.7.6

Running Delay Timer with Ramp Rate

5.7.7

Delay timer with ramp rate functions

5.7.8

Power Failure While Using Delay Timer

5.7.9

Soft start Timer

5.7.10

Power Failure While Using Soft Start Timer

5.7.11

Ramp Rate with Soft Start Timer

5.7.12

Time Remaining

5.7.13

Alarms

5.8

Controller Options

5.8.1

Digital Communications - RS232

5.8.2

Digital Communications - RS485

5.8.3

Comms Address

5.8.4

Alarm Option

5.9

3216CC Navigation Diagram

6.0 2132 Over-Temperature Controller Description (if fitted)

6.1

Description

6.2

Operation

6.2.1

Controls

6.2.2

Operation

6.2.3

Over-Temperature Operation

45

45

45

54

54

54

55

52

53

53

53

52

52

52

52

50

50

51

51

48

49

49

50

46

47

47

48

46

46

46

46

46

56

56

56

56

57

57

6.2.4

Over-Temperature Alarm

6.2.5

Resetting the Over-Temperature Alarm

6.2.6

Sensor Break

6.3

Audible Alarm

6.4

Navigation Diagram

7.0 Operation

7.1

Operating Cycle

7.2

Control Method

7.3

3-Zone Control Methods

A. Back-to-Back Thermocouples

B. Retransmission of Setpoint

C. Independent Control

7.4

General Operating Advice

7.5

Operator Safety

7.6

Tube Life

7.7

Pressure

7.8

Power Adjustment

7.9 Running at Low Temperatures

8.0 Maintenance

8.1

General Maintenance

8.2

Maintenance Schedule

8.2.1

Cleaning

8.3

Calibration

8.4

After-Sales Service

8.5

Recommended Spare Parts and Spare Parts Kit

9.0 Repairs and Replacements

9.1

Safety Warning - Disconnection from Power Supply

9.2

Safety Warning - Refractory Fibre Insulation

9.3

Temperature Controller Replacement

9.4

Solid-state Relay Replacement

9.5

Thermocouple Replacement

9.6

Element Replacement

9.7

Fuse Replacement

10.0 Fault Analysis

A.

Furnace Does Not Heat Up

B.

Product Overheats

11.0 Wiring Diagrams

67

67

67

67

68

68

69

70

64

64

64

66

66

66

66

71

71

72

73

59

60

61

61

61

59

59

59

60

62

62

63

63

57

57

57

58

58

5

6

11.1

WC-13-01

11.2

WC-13-31

11.3

2- and 3-phase With Neutral

11.4

Independent Zones (control method C)

11.5

Control by Broadcast Comms (control method B)

12.0 Fuses and Power Settings

12.1

Fuses

12.2

Power Settings

User Power Setting Adjustments

13.0 Specifications

13.1

Environment

76

76

76

77

73

74

75

75

75

78

78

1.0   Symbols and Warnings

1.0

Symbols and Warnings

1.1

Switches and Lights

Instrument switch: when the instrument switch is operated the temperature control circuit is energised.

Heat light: the adjacent light glows or flashes to indicate that power is being supplied to the elements.

Heat switch: the switch disconnects power to the heating elements; unless this switch is OFF there is a danger of electric shock when inserting objects into the product.

1.2

General Warnings

DANGER – Electric shock. Read any warning printed next to this symbol.

WARNING: Risk of fatal injury.

DANGER – Hot surface. Read any warning printed next to this symbol.

WARNING: All surfaces of a product may be hot.

DANGER – Read any warning printed next to this symbol.

7

8

1.0   Symbols and Warnings

Caution – Double Pole/Neutral Fusing

2.0   Installation

2.0

Installation

2.1

Unpacking and Handling

When unpacking or moving the product always lift it by its base or by both ends of the main body. Never lift it by its work tube or the surrounding insulation. Use two or more people to carry the product and control box. Remove any packing material from inside the product before use.

If an optional or special stand is separately supplied, assemble the product on to it.

Some models may be supplied for customer mounting and may require customer preparation of mounting components before installation.

NOTE: This product contains Refractory Ceramic Fibre (also known as

Alumino Silicate Wool - ASW). For precautions and advice on handling

this material see section 9.2.

2.2

Siting and Setting Up

Place the product on a level surface in a well ventilated area.

Site away from other sources of heat and on a non-flammable surface that is resistant to accidental spillage or hot materials.

The surface on which the equipment is mounted should be stable and not subject to movement or vibrations.

The height of the mounting surface is important to avoid operator strain when loading and unloading samples.

Unless otherwise stated elsewhere in this manual, ensure that there is at least 150 mm of free space around the back and sides of the product. Clear space is required above the product to dissipate heat.

Work tubes:

It is recommended that the work tube has either insulation plugs or radiation shields fitted to minimise heat loss from both ends of the work tube. If the work tube has open ends, a significant amount of energy could be radiated from the ends of the work tube. Adjacent surfaces should always be made from a non-flammable material.

Ensure that the ends of the work tube are positioned at least 500 mm away from any adjacent surface so that any energy radiated cannot heat an adjacent surface to a dangerous temperature.

9

2.0   Installation

Ensure that the product is placed in such a way that it can be quickly switched off or disconnected from the electrical supply.

If the product is supplied with a work tube or any accessories fit these into position.

For optimum temperature uniformity, insulating plugs should be placed in the tube ends as shown in fig.1. With a long work tube, the stem of the plug assembly should line up with the end of the tube as in fig.2. Alignment of radiation shields is similar to that of plugs.

If stainless steel seals with gas inlets are supplied, they are to be fitted as shown in fig.3; the stem of any insulating plug should touch the seal.

For vertical models with stainless steel seals, a hook and eye arrangement holds the upper insulating plug assembly.

Horizontal models: if heavy fittings are to be clamped to the end of an extended work tube they can increase the bending stress at the centre of the tube. Support such fittings in such a way that expansion of the tube is allowed.

If a metal work tube is being used in the product, ensure that it is earthed for operator safety.

10

2.0   Installation

Fig 1 - Insulating Plug

(standard length tube)

Key

A Tube

B Insulating Plug

C Stem

Fig 2 - Insulating Plug

(long work tube)

11

2.0   Installation

Key

A Clamp

B Seal plate

C 'O' Ring seal

D Seal sleeve

E Clamp seal

F End plate

Key

A Clamp

B End plate

C

Clamp seal (between Seal sleeve and Clamp

D Seal sleeve

E

Seal plate & 'O' Ring seal

(underneath clamp)

F Tube

Fig 3 'Twin Clamp' End Seal

For assembly details refer to the separate work tube end seal manual.

Under no circumstances should any objects be placed on top of the product.

Always ensure that any vents on the top of the product are clear of any obstruction. Always ensure all cooling vents and cooling fans (if fitted) are clear of any obstruction.

2.3

Electrical Connections

Connection by a qualified electrician is recommended.

12

2.0   Installation

The product covered by this manual normally requires a single phase A.C. supply, which may be Live to Neutral non-reversible, Live to Neutral reversible or Live to Live. Some models may be ordered for 3-phase use, which may be star or delta.

Check the product rating label before connection. The supply voltage should agree with the voltage on the label and the supply capacity should be sufficient for the current on the label.

The supply should be fused at the next size equal to, or higher than the current on the label. A table of the most common fuse ratings is also given towards the back of this manual. When the mains cable is factory fitted, internal fuses are also fitted. It is essential that the operator ensures that the product is correctly fused.

Products with a factory fitted supply cable are designed to be wired directly to an isolator or fitted with a line plug.

Products without a factory fitted supply cable require a permanent connection to a fused and isolated supply. The product's electrical access panel should be temporarily removed, and connections made to the internal terminals.

If the product is to be connected by line plug. The plug should be within reach of the operator and should be easy to remove.

When connecting the product to an isolating switch ensure that both conductors (single phase) or on all live conductors (three phase), and should be within reach of the operator.

The supply MUST incorporate an earth (ground).

Electrical Connection Details:

Supply Types

Supply Terminal Label Cable Colour

Live - Neutral

Reversible or Live-

Live

1-phase L

N

Brown

Blue to live to neutral to either power conductor

(For USA 200-240V, connect L1) to the other power conductor

(For USA 200-240V, connect L2)

PE Green/ Yellow to earth

(ground) to earth (ground)

13

2.0   Installation

3-phase L1

L2

L3

N

PE

Black to phase 1

Black to phase 2

Black

Light Blue to phase 3 to neutral ( except delta

Green/ Yellow to earth ( ground )

)

DO NOT connect a product ordered for three phase use to a single phase supply or to the wrong type of three phase supply.

14

3.0   3508 Controller

3.0

3508 Controller

3.1

PID control

This controller uses PID (Proportional Integral Derivative) temperature control. This type of control uses a complex mathematical control system to adjust the heating power and achieve the desired temperature.

3.2

3508P1

The 3508P1 is a digital temperature controller which uses PID algorithm to give excellent temperature control when properly set. This controller can store and operate a single program of up to 20 segments. The 3508P1 can also be used as a simple temperature controller.

3.3

3508P10

The 3508P10 is a digital controller which uses PID algorithms to give excellent temperature control when properly set. This controller can store 10 programs of up to

50 segments each. Programs can be operated individually or linked by a Call parameter as sub-programs or to form single long programs. The 3508P10 can also be used as a simple temperature controller.

3.4

3508P25

The 3508P25 is a digital temperature controller which uses PID algorithms to give excellent temperature control when properly set. This controller has a maximum of 500 segments or 25 programs; each program has a maximum of 50 segments. For example 3508P25 could store 10 programs with 50 segments or 25 programs with 20 segments. Programs can be operated individually or linked by a Call parameter as subprograms or to form single long programs. The 3508P25 can also be used as a simple temperature controller.

15

3.0   3508 Controller

3.5

Basic Operation

Key

A Alarm Indicator

B Power Output Indicator

C Not Used

D Runs, Holds, Resets the current program

E Page

F Scroll

G Down

H Up

J

I Power Output Percentage

Program Setpoint Temperature (PSP) when a program is running

K Setpoint Temperature (SP) when basic controlling

16

3.0   3508 Controller

L Measurement Temperature

M Measurement Units

3.5.1

Controller Layout

3.5.2

Keys

A/ Man -

RUN/ HOLD

Page Key

Scroll Key

-

Disabled

Runs, Holds or Resets the current program. Hold down for 3 seconds to Reset.

Scrolls through the page headings. Hold down for 3 seconds to access further levels, pass codes are required.

Scrolls through parameters listed on pages.

Arrow Keys

+

Adjust parameter values.

Page and

Scroll together

Page and Up together

+

+

Press together to return to the home display or to acknowledge an alarm.

Press together quickly to scroll back up the page headings.

Scroll and Up together

+

Press together quickly to scroll back up a parameter list.

Pressing any other combination of keys together has no effect.

Note: If no keys are pressed for 1 minute, the display returns to Home.

3.6

Quick Start Guide

3.6.1

Operation as a simple controller

When switched on the controller goes through a short test routine and then shows the measured temperature. Below it, the setpoint temperature (SP) and percentage of power output.

The controller will immediately attempt to reach the set temperature and maintain it.

This will cause the product to heat as quickly as possible which may not be appropriate where the product contains sensitive ceramic components. For products with ceramic components, e.g. a tube furnaces fitted with a long ceramic work tube, use the ramp rate feature set with a low heating rate such as 5°C per minute (300°C per hour), to prevent damage.

3.6.2

Changing the Setpoint

Press up or down to select the required SP. If the SP is higher than the measured temperature, the OP1 indicator will illuminate at the top of the display, indicating that the product is heating.

17

3.0   3508 Controller

The controller will immediately attempt to reach the set temperature and maintain it.

This will cause the product to heat as quickly as possible which may not be appropriate where the product contains sensitive ceramic components. For products with ceramic components, e.g. a tube furnaces fitted with a long ceramic work tube, use the ramp rate feature set with a low heating rate such as 5°C per minute (300°C per hour), to prevent damage.

3.6.3

Resetting the programmer

To reset the programmer to simple controller mode, press RUN/HOLD for 2 seconds.

Operating the current program

• To avoid unwanted heating at the end of a program, set the SP temperature to zero before operating a program.

• Ensure the programmer is reset to simple controller mode before starting a program by pressing RUN/HOLD for 2 seconds.

• To start the program, press RUN/HOLD twice, RUN will light up on the display.

The displayed Program Setpoint (PSP) follows ramps, dwells and steps as the program runs. The SP temperature of the controller does not apply when a program is operating.

• To pause the program, press RUN/HOLD.

• To stop the program and return to simple controlling (reset), press RUN/HOLD for 2 seconds.

When the program ends, the programmer will either:

• Automatically reset to operation as a simple controller.

• Dwell at the last temperature of the program (with the RUN indicator flashing), until the operator presses RUN/HOLD for 2 seconds to manually reset, or presses RUN/HOLD once to restart the program.

• Turn power to the elements down to zero.

3.6.4

Understanding User Levels

There are two levels in the controller; Level 1(Operator) and Level 2 (Supervisor).

Level 1 (Operator) is for the day-to-day operation of the controller is not protected by a security code. There are 3 pages at this level. Page 1, Customer Identity, can only be altered in level 2. Page 2 shows the current program status. Page 3 is for writing and viewing programs.

Level 2 (Supervisor) requires a security code to enter, but once enable, provides access to additional parameters. A further 4 pages are accessible in this level as follows; Home

, Customer identity, Control Output Hi percentage, Units.

18

3.0   3508 Controller

To Enter Level 2:

1. Press and hold page

1” for 3 seconds. The display will show “Access Goto Level

2. Press up to select level 2. After a short pause the display will show “Access

Pass code”.

3. Press up or down to enter the pass code. Pass is momentarily displayed.

After a short pause the display will return to home, the controller is now in level 2.

When Level 2 operations have been completed the supervisor must return to Level

1 manually. It is not necessary to enter a code when going from a higher level to a lower level.

To Return to Level 1:

1. Press and hold page for 3 seconds. The display will show “Access Goto Level 2.

2. Press down to go to level 1. After a short pause the display will revert to home, the controller is now in level 1.

3.7

Setting Up Controller

Before using the controller (or during its lifetime) certain parameters may have to be set, depending on specific requirements. To do this the controller must be set to

Supervisor Level 2, see "Controller Navigation Diagrams".

3.7.1

Maximum output power setting

Press page the value.

until "Control Output Hi" is displayed. Press up or down to adjust

Depending on the product model, the maximum power output setting may be accessible or locked.

For silicon carbide heated products the parameter is accessible to allow compensation for element ageing.

In many models the maximum power output setting depends on the electrical supply

voltage, refer to section 12.0.

3.7.2

Customer ID.

A product identity number can be entered if required. This may be used to identify one of many units, for production or quality control systems.

Press page number.

until "Customer Identity" is displayed. Press up or down to select a

19

3.0   3508 Controller

3.7.3

Units

Press page

C Celsius

F Fahrenheit

K Kelvin until "Units" is displayed. Press up or down to select:

3.7.4

Language

The text on the 3508 Controller can be shown in different languages, this can only be set at the factory and therefore must be specified at the time of placing an order.

3.8

Programming

3.8.1

Programming Notes

Programs can be created in Level 1 or Level 2 of the 3508 Controller.

For the P10 and P25, new programs can be created while the current program is operating.

To avoid unwanted heating at the end of a program, set the controller setpoint temperature to zero before operating a program.

All new unused programs show only 1 segment of type 'End'.

The minimum number of segments for a program is 2. The second being an 'End' type.

Ramp-to-setpoint control. To achieve this, create a two segment program. Set the first segment type as 'Rate' or 'Time'. Set the second segment type 'End' type' Dwell'.

For the P10 and P25, programs can be linked together using a 'Call' segment. However, a lower number program can not be called and a program can not be ended with a call segment.

A program can be ended in four ways:

1. With 'End' segment set to S.OP the power to the elements is turned down to 0%, no matter what the 'Setpoint' temperature is.

2. With 'End' segment set to 'Reset' and the 'Setpoint' temperature turned down to zero, power to the elements will be 0%. To do this set the 'Setpoint' temperature to the minimum possible. For type B thermocouples this will be below zero.

3. With the 'End' segment set to 'Reset'. The controller will try to reach and maintain the 'Setpoint' temperature in place before the program started.

4. With the 'End' segment set to 'Dwell'. The controller will dwell at the 'PSP' of the last segment ("RUN" indicator flashes), until it is reset.

To reduce the number of segments in a program, change the last required segment to an 'End' type.

You will be asked to press to cancel or for OK.

To cancel all segments in a program, change the first segment to an 'End' type.

20

3.0   3508 Controller

To alter parameters or segments of an operating program, this program must be held or reset. Press RUN/ HOLD to pause the program, or press RUN/ HOLD for 2 seconds to reset.

3.8.2

Holdback

Holdback can be used to prevent the program from operating ahead of the actual heating or cooling.

The holdback value is the amount, in degrees, by which the program setpoint can run ahead of the measured temperature before holdback operates. The value applies to a whole program.

To set the value press page twice, press scroll until 'Holdback Value' appears and press up or down to set.

Holdback can be used in 'Rate', 'Time' and 'Step' segments.

• For 'Rate' and 'Time' segments holdback will operate during the segment.

• For a 'Step' segment holdback delays continuation to the next segment until the step target is reached.

The 'Holdback Type' can be set as follows:

• Low Applies to heating only

• High Applies to cooling only

• Band Applies to both heating and cooling

• Off Holdback is switched off

To set the holdback type, press page shows 'Holdback Type' for each segment and press up

The default setting for holdback is 'OFF'.

twice, then press scroll until the display or down to set.

3.8.3

Wait Segments

Wait prevents the program proceeding to the next segment, in a similar way to holdback, until the selected ‘Wait-For’ parameter has been met. There are 5 ‘Wait For’ parameters. The first 4 only work if there are configured inputs to the controller.

1. PrgIn1 Wait until Input 1 is true

2. PrgIn2 Wait until Input 2 is true

3. PrgIn 1&2 Wait until Inputs 1 AND 2 are true

4. PrgIn 1or2 Wait until Inputs 1 OR 2 is true

5. PVWaitIP Wait until the measured temperature reaches a threshold value before continuing. It can operate in one of 4 ways:

1. 'Abs Hi' Wait until the measured temperature is greater than or equal to a value 'WaitVal' set for that segment.

2. 'Abs Lo' Wait until the measured temperature is less than or equal to a value

'WaitVal' set for that segment.

3. 'Dev Hi’ Wait until the measured temperature exceeds a fixed* threshold by an amount ‘WaitVal’ set for that segment.

21

3.0   3508 Controller

4. ‘Dev Lo’ Wait until the measured temperature drops below a fixed* threshold by an amount ‘WaitVal’ set for that segment.

* The fixed threshold used by deviation parameters is set in the configuration level of the programmer and if required should be requested when purchasing a product from

Carbolite Gero.

3.8.4

Program Cycling

The 'Cycles' parameter sets the number of times the program will operate.

The default setting is 1 cycle.

To change the number of cycles, press page twice, then press scroll until the display shows 'Prog Cycles', then press up to set a finite number of cycles up to 999.

Or press down to set cycling to continuous.

3.8.5

Creating a Program

From the home display, press page three times to get to the programming page, the display will show “ProgEdit 1”.

Program number

On P10 or P25 models press up or down to select a new program number. The display will show that new programs have only one segment.

Holdback Value

Press scroll until the display shows 'Holdback Value". If required: Press up or down to set a value. This value will be used in any segment where a 'Holdback Type' is set.

Ramp Units

These apply to Rate segments only. Press scroll until the display shows 'Ramp Units'.

Press up or down to select the ramp units of degrees per Hour, Min or Sec.

Number of program cycles

Press scroll until the display shows 'Cycles'. Press up than one cycle.

or down to select more

Now create all the segments for your program, finishing with an 'End' segment. When parameters for each segment have been entered the display goes to the next segment number.

Segment Type

Press scroll until the display shows 'Segment Type'. Press up

'Rate', 'Time', 'Dwell', 'Step', 'Wait', 'GoBack', 'Call' or 'End'.

or down to select

22

3.0   3508 Controller

Holdback Type

Press scroll until the display shows 'Holdback Type'. If required, press up to select 'Off', 'Low', 'High' or 'Band'.

Target Setpoint (Visible only for Rate, Time and Step segments) or down

Press scroll until the display shows 'Target SP'. Press up value.

Ramp Rate (Visible only for Rate segments)

Press scroll until the display shows 'Ramp Rate'. Press up number of degrees per 'Ramp Unit' as set above.

Duration (Visible only for Time and Dwell segments) or down to set a or down to set the

Press scroll until the display shows 'Duration". Press up

Wait For (Visible only for Wait segments) or down to set a value.

Press scroll until the display shows 'Wait For'. Press up

PrgIn1, PrgIn2, PrgIn1In2, PrgIn1orIn2, PVWaitIP.

or down

GoBack to segment number (visible only for GoBack segments) to select:

Press scroll until the display shows 'GoBack Seg'. Press down to select a segment number to go back to.

GoBack Cycles (visible only for GoBack segments)

Press scroll until the display shows 'GoBack Cycles'. Press up value.

Call Cycles (Visible only for call segments) or down to set a

Press scroll until the display shows 'Call Cycles'. Press up value.

End Type (Visible only for End segments) or down to set a

Press scroll until the display shows 'End Type'. Press up

'Reset', 'Dwell' or 'SafeOp'.

or down to select:

3.8.6

Running a Program

The current program can be started from the home display by pressing RUN/HOLD or by pressing page once, then scroll once (twice for P10 and P25), then press up or down to change the status to 'Run'.

23

3.0   3508 Controller

3.8.7

To pause (hold) a program

Press RUN/HOLD or

Press page until 'Program Status Reset' appears

Press scroll until the cursor moves to 'Reset'

Press up or down to select 'Hold'

RUN/HLD will be displayed

3.8.8

To stop and reset a program

Press and hold RUN/HOLD or

Press page until 'Program Status Reset' appears

Press scroll until the cursor moves to 'Reset'

Press up or down to select 'Reset'

3.8.9

To run a different program (P10 and P25)

To select a program

Press page until 'Program Status Reset' appears

Press scroll then up or down to select a program number

To operate the program

Press RUN/HOLD or

Press scroll until the cursor moves to 'Reset'

Press up or down to select 'Run'

Run will be displayed

3.8.10

Program Status

While a program is operating the home display shows 3 values: l l l

Top: Measured temperature

Centre: Program Setpoint (PSP)

Bottom: Power output percentage

To see more detail:

Press page once to go to the program status page. The top and centre values from the home page remain on the display. The lower half of the screen now shows:

24

3.0   3508 Controller l l l

Current program number (P10 and P25 only)

Current segment number

Time remaining for that segment

Further presses of the scroll key while a program is operating will reveal additional information:

Status. This can be changed to 'Hold', 'Reset' or 'Run' by pressing up or down

Program Setpoint (PSP)

Current Segment Type. 'Step' and 'Call' segments are instant, so are only flashed on the screen, unless holdback is operating on that segment.

Target Setpoint

Segment Rate For 'Rate', 'Time' and 'Step' segments only

Cycles left

Program Time Left

3.8.11

Program Hold with Holdback

If a holdback value has been set and the program goes into a hold state, the green HLD indicator will flash until the measured temperature catches up.

While in this condition, the program itself is put into hold by pressing the RUN/HLD button, the 'HLD' indicator will stop flashing and remain on with the 'RUN' indicator.

When the program is started again by pressing the RUN/HLD button, the 'HLD' indicator will flash again if the measured temperature has not caught up with the program.

Programming note: For P10 and P25 models, other programs can be created or changed whilst the current program is operating.

3.8.12

Power Failure Recovery

If there is a power interruption to the controller during a program, when power is restored the controller pauses the program, then ramps the temperature back up to the current program setpoint (PSP) before continuing the program.

• Power failure during ramp segments: The ramp rate will be that of the current ramp segment.

• Power failure during dwell segments: The ramp rate will be that of the previous ramp segment. If a previous ramp segment does not exist, then the dwell will continue at the current measured temperature.

• Power failure during time-to-target segments: The ramp rate will be that of the current segment. The ramp rate is maintained, but the time remaining is recalculated.

If there is a power interruption while controlling to setpoint, when power is restored the controller automatically calls for maximum power.

3.8.13

Alarms

Alarms are used to alert the operator when a pre-set level has been exceeded or a function error has occurred such as a sensor break. They are indicated by a flashing red

25

3.0   3508 Controller

ALM (Alarm) indicator. The alarm may also switch an output – usually a relay to allow external devices to operate when an alarm occurs. Alarms only operate if they have been configured and are dependent on customer requirements.

How to acknowledge an alarm will depend on the type of latching which has been configured. A non-latched alarm will reset itself when the alarm condition is removed. A latched alarm requires acknowledgement with the 'ACK' function before it is reset.

If an alarm has been activated, the red 'ALM' indicator will flash and the text will indicate the type of alarm.

To acknowledge an alarm and cancel the 'ALM' indicator, press and together.

3.8.14

Program Example 1

The following sequence of entries creates and runs the program shown graphically below.

1. Turn the controller SP down to '0' by pressing down .

2. Press page until 'Prog Segments Used' is displayed. On P10 or P25 models press up or down to select a new program number, (a program with only 1 segment).

3. Press scroll until 'Holdback Value' is displayed. Default ‘0’ degrees.

4. Press scroll until 'Ramp Units' is displayed. Press up

5. Press scroll until 'Cycles' is displayed. Default ‘1’

6. Press scroll until 'Segment 1' is displayed or down to set to ‘Min’

7. Press scroll until 'Segment Type' is displayed. Press up

'Rate"

8. Press scroll until 'Holdback Type' is displayed. Default ‘Off’ or down to select

9. Press scroll until 'Target SP' is displayed. Press up degrees.

or down to set to ‘400’

10. Press scroll until 'Ramp Rate' is displayed. Press up degrees per minute.

or down to set to ‘5.0’

Repeat steps 6 to 10 for 4 more segments. Set 'Holdback' to the default ‘Off’. Enter the following parameters and values:

Segment Type Dwell Duration ‘30:00.0’ minutes

Segment Type Step Target SP ‘600’ degrees

Segment Type Dwell Duration ‘30:00.0’ minutes

Segment Type Time Target SP ‘200’ degrees, Duration ‘2:00:0’ hours

Finish the program with an 'End' segment:

11. Press scroll until 'Segment Type' is displayed. Press up

'End' or down to select

26

3.0   3508 Controller

12. Press scroll until 'End Type' is displayed. Press up or down to select 'Reset'

13. Press page and scroll together to return to the home display.

To run the program either press RUN/HOLD or:

14. Press page until 'Program Status' is displayed

15. Press scroll until the cursor moves to the program status of 'Reset'

16. Press to select 'Run'.

27

3.0   3508 Controller

Time Display Examples

10:05:3 Min/Sec/10th Sec

21:10:05 Hour/Min/Sec

196:10 Hour/Min

Segment

1

Type 'Rate'

2

Type 'Dwell'

3

Type 'Step'

4

Type 'Dwell'

5

Type 'Time'

6

Type 'End'

Target 400°C Duration 30 min Target 600° Duration 30 min Target 200° End Type 'Reset'

Rate 5.0°/Min Time 120 min

3.8.15

Program Example 2

The following sequence of entries creates and runs the program shown graphically below.

1. Turn the 'Setpoint' to ‘0’ by pressing down

2. Press page until 'Prog Segments Used' is displayed. On P10 and P25 models press up or down to select a new program number, (a program with only 1 segment).

3. Press scroll until 'Holdback Value' is displayed. Press up degrees or down to set to ‘5’

4. Press scroll until 'Ramp Units' is displayed. Press up or down to set to ‘Min’

28

3.0   3508 Controller

5. Press scroll until 'Cycles' is displayed. Default ‘1’

6. Press scroll until 'Segment 1' is displayed

7. Press scroll until 'Segment Type' is displayed. Press up

‘Time’

8. Press scroll until 'Holdback Type' is displayed. Default ‘Off’ or down to select

9. Press scroll until 'Target SP' is displayed. Press up or down to set to ‘600’ degrees

10. Press scroll until 'Duration" is displayed. Press up

’30:00.0’ minutes or down to set to

Repeat steps 6 to 10 for 4 more segments. Enter the following parameters and values:

Note: Call segments are not available on single program models.

Segment Type Rate

Target SP ‘400’ degrees. Ramp Rate ‘2.0’ degrees per minute

Segment Type Step Target SP ‘200’ degrees

Segment Type Dwell Holdback ‘High’. Duration ’30:00.0’ minutes

Segment Type Call Call Prog ‘next number’. Call Cycles ‘2’

Finish the program with an End segment:

11. Press scroll until 'Segment Type' is displayed. Press up

'End' or down to select

12. Press scroll until 'End Type' is displayed. Press up or down to select 'Dwell'

Repeat the sequence to create a short program ‘3’ as suggested in the diagram.

13. Press page and scroll together to return to the home display

To operate the program either press RUN/HOLD or

14. Press page until 'Program Status' is displayed

15. Press scroll until the cursor moves to the program status of 'Reset'

16. Press to select 'Run'

29

3.0   3508 Controller

1

Type 'Time'

2

Type 'Rate'

3

Type 'Step'

Target 600°C Target 400°C Target 200°C

Duration 30min Rate 2°C/min

Segment

4

Type 'Dwell'

5

Type 'Call'

Duration 30 min

H back type 'High'

Call prog 3

Call cycles 2n

* Segment 4 'Holdback Value' 5°C ** P10 and P25 only

*** Program 3 Example

6

Type 'End'

End Type 'Dwell'

3.9

Controller Options

As options can be ordered in a variety of combinations and for a variety of purposes, exact instructions are not given here. The full Eurotherm manual may be required to determine customer parameter settings. To reveal or hide parameters in the controllers it is necessary to go into configuration mode, a security code is needed. Please consult

Carbolite Gero.

30

3.0   3508 Controller

3.9.1

Digital Communications - RS232

If the RS232 option is supplied, the furnace is fitted with one sub-miniature Dsocket connected to the controller comms module. RS232 is suitable for direct connection to a personal computer (PC) using a “straight through” cable as follows

(the linked pins at the computer end are recommended but may not be necessary).

The cable is usually 9-pin at the furnace end and 9-pin at the computer, but other alternatives are shown in parentheses.

Product end of cable female (25-pin) 9-pin

RS232 Cable: product to PC

Computer end of cable

9-pin (25-pin) male

Rx

Tx

Com

(2)

(3)

(7)

3

2

5

_________________

_________________

_________________

3

2

(2)

(3)

Tx

Rx

5 (7) Com

7,8 (4,5) Link together

1,4,6 (6,8,20) Link together

3.9.2

Digital Communications - RS485

If an RS485 option is supplied, the furnace is fitted with two D-sockets. Connection between products is by “straight” cable as follows:

Product end of cable female (25-pin) 9-pin

-

+

Com

(2)

(3)

(7)

3

2

5

RS485 Cable: product to PC

_________________

Computer end of cable

9-pin (25-pin) female

3

2

5

(2)

(3)

(7)

Tx

Rx

Com

3.9.3

Comms Address

Typically the comms address is set to 1, but this can be changed. In the case of RS485 and multiple instruments it is necessary to set different addresses. To change the address value, access the level 2 list. In level 2 press the page key until the COMMS parameter is displayed. Press up down to select the address value.

3.9.4

Alarm Option

When an alarm board is fitted, which consists of a relay with voltage free contacts, for operator use, the contacts are taken to a panel plug on the control panel, wired as indicated:

31

3.0   3508 Controller

Key

C Temperature Controller

F Fuse (2A)

S Supply

L Load

*

Normally open relay contacts

RO

Relay Output 240V 2A

MAX

The purpose of the 2 amp fuse is to break the circuit to prevent overloading on the circuit due to high voltage.

The instrument configuration and parameters available to the operator depend on the customer requirements.

3.9.5

Remote Input and Output (Analogue Communications)

When analogue communications are fitted, the contacts are taken to insulated terminal sockets on the control panel.

Key

C Controller

Controller configuration depends on customer requirements.

Remote input (when specified) may be switched on and off using the remote setpoint enable parameter in the controller level 2, if this was made available for a particular application. In level 2 press page until ‘REM SP Enable’ is displayed, press up or down to select SP1 (the normal controller setpoint) or SP2 (the remote input setpoint), ‘SPX’ will appear in the top left corner of the display.

Remote output does not require switching on and off.

3.9.6

Program segment output

When the customer requirement is for program segment output, an extra parameter is revealed in the PROG list. For each program segment, after the segment type and settings, the parameter EVENT OUTS appears. This has values on and off. If the value is

32

3.0   3508 Controller set to on, then the relay closes during the segment and a small 1 appears in the top left of the screen.

If more than one program segment output is fitted, then there are extra boxes depending on how many event outputs there are.

3.10

Temperature Controller Replacement

Before handling the controller: wear an anti-static wrist strap or otherwise avoid any possibility of damage to the unit by static electricity.

Refer to the detailed instructions supplied with the replacement controller.

Ease apart the two lugs at the side; grip the instrument and withdraw it from its sleeve; push in the replacement.

3.11

Controller Navigation Diagrams

The following diagrams detail how to navigate to the various menu options within the

3508 Controller. At each option, values can be set using the arrow keys.

33

3.0   3508 Controller

3.11.1

Operator Level 1 - No Program Running

34

HD Home Display

R/O Read Only

Page Key

Scroll Key

Controller identity when using more than one controller

Black = Progress

White = Return

*

Visible Parameters depend on the Segment Type

3.11.2

Operator Level 1 - Program Running

3.0   3508 Controller

HD Home Display

R/O Read Only

Page Key

Scroll Key

Controller identity when using more than one controller

Black = Progress

White = Return

*

See previous diagram: Operator Level 1- No Program Running

35

3.0   3508 Controller

3.11.3

Supervisor Level 2

36

A To enter Level 2

B Level 2

L1 Level 1 Home Display

L2 Level 2 Home Display

Page Key

Hold Page Key for 3 seconds

Arrow Key

Scroll Key

Locked before Pass Code entered

Unlocked

*

Black = Progress

See previous diagram:

Operator Level 1- No Program Running

**

If configured

4.0   3508 Dual Loop Cascade

4.0

3508 Dual Loop Cascade Control (if fitted)

4.1

Principle of Cascade Control

When cascade control is fitted, the Load Loop 3508 senses the temperature of the workload, and the Element Loop 3508 senses the element temperature. Depending on the oven or furnace model, the Load Thermocouple may be in a fixed position, or may be movable. The Element Thermocouple is fixed in a predetermined position near the heating elements. The Load Thermocouple should be placed as near as possible to the work to be heated.

The Load Loop communicates with the Element Loop, calling for heat according to the load temperature and the current program or set point. The Element Loop regulates the heat according to element temperature and the requests from the Load Loop.

The element temperature could, in principle, vary between the furnace or oven maximum and minimum, regardless of the working temperature of the load. In practice, the cascade control system is configured to limit the element temperature to a band around the load temperature, typically of ±10% of the set-point temperature.

The set point of the load loop, shown at the top of the display, can be adjusted by the operator. The Element Loop, shown at the bottom of the display, should not be adjusted by the operator & will automatically regulate the element temperature to achieve the Load set temperature.

In a three-zone furnace for which the “three zone cascade” option has been ordered the centre zone is a 3508 Dual Loop & separate end zone controls are fitted. The operator sets the Load loop set point on the 3508 centre zone. The end zone controllers work automatically & need no adjustment by the operator.

4.2

Operation of Cascade Control

The operator may ignore all the complications of the system, and program the Load

Loop according to the standard instructions for that controller. The home display shows the load loop at the top of the display and the Element loop at the bottom. By pressing the page key, separate views of load and element loops will be shown.

37

4.0   3508 Dual Loop Cascade

Key

A Home Display View

B Load Loop View

C Element Loop View

The Element Loop should never be adjusted. Note that the elements usually run at a higher temperature than the load.

38

4.0   3508 Dual Loop Cascade

Because the details of the customer’s cascade application (in particular the nature of the load) are generally not known, the feed forward parameter (FF Trim) is made easily accessible in level 2 (Refer to instrument operating instructions). Its default setting is 2%. If overshoot of the load temperature occurs – often a problem at low temperatures – then FF Trim can be reduced in order to limit the amount of overshoot. However, if FF trim is reduced too much, the load may not reach the desired temperature. If the load does not reach the desired temperature or is slow in the final stages, FF Trim can be increased: a maximum of 10% is suggested.

Feed Forward View

When attempting to control at very low temperatures it can become a problem to achieve stable control because of excessive power being supplied during heating.

The available power can be limited using the power limit parameter OP.Hi, make a note of the original settings before adjusting. For power settings please refer to the fuse and power section at the back of the manual. If the parameter is normally set to 100%, try initially setting it to 50% to improve stability. Avoid settings below 40% where possible (though some furnaces require low settings for reasons unconnected with cascade control).

39

40

4.0   3508 Dual Loop Cascade

Power Limit View

4.0   3508 Dual Loop Cascade

4.3

Bypassing Cascade Control

This applies where the Control Thermocouple is a removal probe (e.g. in a tube furnace), or where for other reasons it may be required to operate the furnace or oven directly from the Element Loop.

To operate without Cascade Control the load thermocouple has to remain connected at all time; or a link has to be made across the thermocouple input connections.

4.4

3508P1 Element Loop (Loop 2)

In these circumstances the Element Controller is configured with the local/remote parameter, accessible in level 2 (Refer to instrument operating instructions).

To switch cascade control on or off. In Level 2, press Scroll until the display shows .

Using the up down set:

= cascade control on

= cascade control off

The top left hand side of the screen will show X when operates as an independent Programmer/Controller when cascade control, change the is enabled. The instrument is set to . To return to parameter to . Also note that cooling at low temperatures takes longer per degree than it does at high temperatures.

4.5

Caution

If the Load Thermocouple is removable, leave it in the furnace or oven chamber whenever possible. Operating with the Cascade Control active and with the Load Thermocouple in an unheated position (such as lying on the work bench) may cause the furnace or oven to heat up to its maximum temperature, wasting power and possibly shortening element life.

4.6

Over-Temperature Control

Where over-temperature control is fitted, it normally protects against failure of the control system or of a component such as a power control relay. The over-temperature controller must be set at a level higher than the greatest element temperature, typically

15 °C above maximum.

If the working temperature is less than the maximum temperature, then it may be possible to set the over-temperature limit as follows: working temperature + (maximum temperature x FF/100) + 15 °C where FF is the Feed Forward percent parameter value (e.g. 10)

Example: for working at 800 °C in a 1200 °C product, the over-temperature limit could be set to 800+120+15=935.

41

5.0   3216CC Controller

5.0

3216CC Controller

5.1

3216CC

This section should be disregarded unless the controller is used as an independent end zone controller.

The 3216CC Controller is a digital temperature controller which uses PID algorithms to give excellent temperature control when properly set. This controller can only be used as a simple temperature controller, it cannot be programmed.

5.2

PID control

This controller uses PID (Proportional Integral Derivative) temperature control. This type of control uses a complex mathematical control system to adjust the heating power and achieve the desired temperature.

5.3

Operation

5.3.1

Controller Layout

Key

A Power Output Indicator

B Alarm Indicator

C

Remote Indicator

(when configured)

D Page

E Scroll

F Down

G Up

H Run Indicator

I Hold Indicator

J

Setpoint Temperature

(SP)

K

Measurement Temperature

42

5.0   3216CC Controller

5.3.2

Keys

Page Key

Scroll Key

Ack

Page and

Scroll

Arrow Keys

+

+

The page key is used to access level 2 when held down for 3 seconds.

The scroll key is used to scroll through parameters.

When pressed simultaneously the ACK function is used to: l l l

Return to the Home Menu

Acknowledge an alarm if activated.

Reset a program after the program has ended.

The arrow keys are used individually to adjust the selected parameters and in combinations to operate a program.

Note: If a parameter is selected and no further action is taken, the display will time out and revert back to the home display in its working level after approximately 1 minute.

5.4

Quick Start Guide

5.4.1

Operation as a simple controller

When switched on, the controller goes through a short test routine and then shows the measured temperature (PV = Process Value) in the upper part of the display and below it, the desired temperature (Setpoint).

5.4.2

Changing the Setpoint

Press Up or Down to select the required SP. If the SP is higher than the measured temperature, the OP1 indicator will illuminate in the top left corner of the display, indicating that the controller is calling for power (giving an output).

The controller will immediately attempt to reach the setpoint and then maintain it.

This will cause the product to heat as quickly as possible which may not be appropriate where the product contains sensitive ceramic components. For products with ceramic components, e.g. a tube furnaces fitted with a long ceramic work tube, use the ramp rate feature set with a low heating rate such as 5°C per minute (300°C per hour), to prevent damage.

5.4.3

Using the Controller

The parameters in the controller are first shown by a short code (mnemonic). After 5

Seconds a description of the parameter will scroll once along the display and then revert back to the mnemonic. The scrolling text can be interrupted at any time by a single press of any of the buttons, but will not scroll again until the parameter is returned to.

In this manual the mnemonic will be shown first, followed by the scrolling text in brackets; e.g. PROG <PROGRAM NUMBER>

43

5.0   3216CC Controller

5.4.4

Understanding User Levels

There are two user levels in the controller; Level 1 (Operator) and Level 2 (Supervisor).

Level 1 (Operator) is for the day to day operation of the controller. These parameters are not protected by a security code.

Level 2 (Supervisor) provides access to additional parameters. Access to this level protected by a security code

To Enter Level 2

1. Press and hold the page key for 3 seconds.

2. The display will show LEu 1 GOTO

3. Release the page Key

4. Press the up or down to choose LEu 2 (level 2)

5. Press the up or down to enter the code (Level 2 Code = 9).

If the correct code is entered, PASS should momentarily be displayed and then revert to the level 2 home display.

If an incorrect code is entered the display reverts back to Level 1 home display.

When level 2 operations have been completed, the supervisor must return to Level 1 either manually or by switching the instrument off and back on. There is no time out function.

To Return to Level 1

1. Press and hold the page Key

2. Press down to select LEu 1

It is not necessary to enter a code when going from a higher level to a lower level.

When level 1 is selected, the display reverts to the home display (See Controller Layout)

Table showing parameters accessible in level 1 and Level 2

Operator LEVEL 1 home display

Supervisor LEVEL 2 home display

Programming

Program Status

Alarms (if configured)

Current Transformer Input (if configured)

Comms (if configured)

Controller set up (if configured)

Customer Calibration (if configured)

TIP

44

5.0   3216CC Controller

If while navigating the controller, a parameter has been passed or you need to access parameters which would be at the end of a scroll list, press and hold scroll and use up to return to a previous parameter.

5.5

Setting up the Controller

Before using the controller (or during its lifetime) certain parameters may have to be set, depending on specific requirements. To do this the controller must be set to supervisor level (Level 2).

5.5.1

Setpoint Ramp Rate

To control the rate at which the temperature rises to setpoint, the SP.RATE function is used.

Before setting the ramp rate, it is advisable to set the setpoint to a low value,

preferably 0 °C (see section 5.4). Once the ramp rate has been set, the required

setpoint can be entered from the home menu. Doing so will activate the ramp rate, which can be identified with the run indicator showing on the bottom of the display.

While the ramp rate is active the working setpoint will be shown on the lower temperature display (this is the setpoint, set by the ramp rate).

When the process temperature has reached the setpoint value at the given ramp rate, the run indicator will turn off and the instrument will control at the required setpoint temperature.

Any further modifications to setpoint will cause the ramp rate to be activated and the instrument to control as described above.

NOTE: Ensure timer configuration is set to ‘none’ (see section 5.6) to use the setpoint

ramp rate feature without any timer functions.

5.5.1.1

Setting Setpoint Ramp Rate

In supervisor level (level 2).

Press scroll until the display shows SP.Rate <setpoint rate limit>. Using up down select the ramp rate required, in °C/ Min.

5.5.1.2

Running with Ramp Rate and

Press the up and down keys at the same time to activate the ramp rate. The

"Run" indicator will illuminate and the scrolling text will read <RAMPING> to show the ramp rate is active. The ramp rate will then start from the current process temperature.

When the ramp reaches the setpoint temperature, the "Run" indicator will turn off and the instrument will maintain control at the setpoint.

To put the ramp rate into a hold condition, press the up and down keys and release. The "Run" indicator will flash and the scrolling text will read <HOLD> to show the ramp rate is on hold.

45

5.0   3216CC Controller

To cancel the ramp rate, press and hold the up indicator turns off.

5.5.2

Maximum Output Power and down keys until the "Run"

Press scroll until the display shows OP.HI <OUTPUT HIGH>. Use the up and down keys to select the output power required as a percentage. Once the setting is made, turn the instrument switch off and on to power cycle the temperature controller.

Depending on the furnace or oven model, the maximum output power setting OP.Hi

may be accessible or locked.

For silicon carbide heated furnaces, the parameter is accessible to allow compensation for element ageing.

In many models the maximum output power setting depends on the supply voltage, see

section 12.0.

5.5.3

Customer ID

A furnace or oven identification number can be entered if required. This maybe used to identify one of many units for production or quality control systems.

Press scroll until the display shows ID <CUSTOMER ID>. Use the up keys to enter your own identification number. This can range from 1-9999.

and down

5.5.4

Units or down Press scroll until the display shows UNITS <DISPLAY UNITS>. Use the up keys to select the required units.

Mnemonic

NONE

°C

°F

°K

PERC

Celsius

Kelvin

Description

No units (Default °C)

Fahrenheit

% (shows °C value)

5.5.5

Language

The scrolling text on the 3216 can be shown in different languages, this can only be set at the factory and therefore must be specified at the time of placing an order.

5.6

Timer

5.6.1

Setting the Timer

A timer can be configured to operate in four different modes. These can be selected in level 2 (supervisor level) using the TM.CFG parameter as:-

• None

• Dwell Timer

46

5.0   3216CC Controller

• Delayed switch on timer

• Soft start timer

None

The timer is turned off, no timer configurations are available, the instrument works as a simple setpoint controller.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select NONE.

5.6.2

Dwell Timer

A dwell timer is used to control a process at a fixed temperature for a defined period. At the end of the time period the controller will switch off the output power to the elements.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select Dwell.

When Dwell parameter is selected, the Timer resolution (TM.RES), Time duration

(DWELL) and Timer Threshold (THRES) functions become available.

Press scroll until the display shows TM.RES < Time resolution >. Use the up to select the timer units in Min or Hours.

down

Press scroll until the display shows DWELL < SET TIME DURATION >. Use the up down to enter the time duration required.

Press scroll until the display shows THres < TIMER THRESHOLD >. Use the up down to select the temperature threshold that you require the timer to start at.

The threshold value is ±n around the setpoint (n=threshold value).

Example: If the setpoint is set to 800 °C and the timer threshold is set to 2, after the timer is activated it will not start until the process value reaches 798 °C if ramping up or

802 °C if it is cooling.

Note: If the threshold is set to OFF, the timer will either; start to count down as soon

as it is activated with the mode keys or if a ramp rate has been set (see section 5.5.1

), the timer will start as soon as the ramp reaches the setpoint. (see section 5.7.1)

5.6.3

Delayed Switch On Timer

The delayed switch on timer is used to switch on the output power to the elements after a set time period.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select dELY.

When delay parameter is selected, the Timer Resolution (TM.RES) and Time Duration

(DWELL) functions become available.

Press scroll until the display shows TM.RES < Time Resolution >. Use the up to select the timer units in Min or Hours.

down

47

5.0   3216CC Controller

Press scroll until the display shows DWELL < SET TIME DURATION >. Use the up down to enter the time duration required before the output power switches on.

5.6.4

Soft Start Timer

The Soft Start Timer is used to start a process at a reduced setpoint and power. The

Soft Start Setpoint is used as a threshold only and is not a control point.

Example: Main Setpoint = 800 °C

Max power limit = 75 % (This may be set at the factory)

Soft Start Setpoint = 600 °C (Threshold)

Soft Start Power Limit = 50% (Cannot be set above max power Limit)

When the timer is running, the maximum power is controlled by the Soft Start Setpoint of 600 °C and the Soft Start Power limit of 50%. This will continue until the timer ends or the current temperature exceeds the Soft Start Setpoint.

When the timer ends or the current temperature exceeds the Soft Start Setpoint, the instrument will start to control using the main setpoint of 800 °C and the Max Power

Limit of 75%.

Press scroll until the display shows TM.CFG <TIMER CONFIGURATION>. Using the up down select SF.st.

When Soft Start parameter is selected, the Timer Resolution (TM.RES), Time Duration

(DWELL), Soft Start Setpoint (SS.SP) and Soft Start Power Limit (SS.PWR) functions become available.

Press scroll until the display shows TM.RES < Time resolution >. Use the up to select the timer units in minutes or hours.

down

Press scroll until the display shows DWELL < SET TIME DURATION >. Use the up down to enter the time duration required, before the instrument starts to control using the main setpoint and max power.

Press scroll until the display shows SS.SP < Soft Start Setpoint >. Use the up down to enter the Soft Start Setpoint.

Press scroll until the display shows SS.PWR < Soft Start Power Limit >. Use the up down to enter the Soft Start Power Limit.

5.7

Running a Timer

l l l l

Run . This starts the timer.

Hold . This stops the timer at the elapsed time. It will start again from the elapsed time when Run is selected again.

Reset . This sets the timer back to zero. It can be operated again from this state.

End cannot be set – it occurs automatically when the timer has counted down to zero.

48

5.0   3216CC Controller l

Acknowledge any timer after a timer has timed out using ACK function (see section

5.3.2) by pressing the

and simultaneously.

5.7.1

Dwell Timer

Operation

To RUN Timer

To HOLD timer

To switch off Timer / Cancel

Action

Press and quickly release

+

Press and quickly release

+

Press and hold + for more than 1 second

To return to home after reset Press and hold

+ for more than 1 second

Indication

Indicator – RUN = ON

Scrolling Display – Timer

Running

Indicator – RUN = Flashing

Scrolling Display – Timer

Hold

Indicator – RUN = OFF

Scrolling Display – None

Static Text - OFF

Indicator – RUN = OFF

Display – A-M <LOOP

MODE- AUTO MANUAL

OFF>

To re-RUN Timer

To RESET timer and return to home menu after timer end

Timer Ended

Press and quickly release

Ack

+

Press and quickly release

+

Press and hold + for more than 1 second

Use the up or down to select AUTO

Indicator – RUN = OFF

Scrolling Text – Timer End

Static Text - OFF

Indicator – RUN = ON

Scrolling Display – Timer

Running

Indicator – RUN = OFF

Scrolling Display - None

Indicator – RUN = OFF

Display – A-M <LOOP

MODE- AUTO MANUAL

OFF>

Use the up down to select

5.7.2

Power Failure While Using Dwell Timer

If there is a power failure while the timer is operating and the power is subsequently restored, the timer will reset and the static text will display “OFF“ until the are pressed to re-run the timer.

+ keys

49

5.0   3216CC Controller

5.7.3

Running Dwell Timer with Ramp Rate

Set the ramp rate as outlined in section 5.5.1

Set the dwell time as outlined in section 5.6.2.

When the timer is set to operate with a set ramp rate, the timer will not start to count down until the setpoint has been reached with the ramp, at which time the timer will begin time count down.

The scrolling display will indicate “timer running” and the run indicator will be illuminated while the ramp rate is active and during the timer count down, after which the display

will indicate the instrument has switched off power to the elements (see section 5.7.7),

and the run indicator will switch off.

5.7.4

Running Dwell Timer with Ramp Rate & Threshold

Set the ramp rate as outlined in section 5.5.1.

Set the dwell time as outlined in section 5.6.2.

Set the threshold as outlined in section 5.6.3.

When the timer is set to operate with a set ramp rate and threshold, the timer will not start to count down until the process temperature has reached the threshold value (see

example 5.6.3).

The scrolling display will indicate “timer running” and the run indicator will be illuminated while the ramp rate is active, while the process value is reaching the threshold value and during the timer count down, after which the display will indicate the instrument has

switched off power to the elements (see section 5.7.1).

5.7.5

Delayed Switch on Timer

Operation Action

To RUN Timer

To HOLD timer

Press and quickly release

Press and quickly release

+

+

Indication

Indicator – RUN = ON

Scrolling Display – Timer

Running

Static Text - OFF

Indicator – RUN = Flashing

Scrolling Display – Timer

Hold

Static Text - OFF

To switch off Timer /

Cancel

To return to home menu. After Resetting timer

Press and hold + for more than 1 second Indicator –

RUN = Off

Scrolling Display – None

Static Text - OFF

Press and hold + more than 1 second for

Indicator – RUN = Off

Display – A-M <LOOP MODE-

AUTO MANUAL OFF>

Use the up select or down to

50

5.0   3216CC Controller

To re-RUN Timer

Timer Ended

Press and quickly release +

Indicator – RUN = OFF

Scrolling Text – Timer End

Indicator – RUN = ON

Scrolling Display – Timer

Running

Static Text – OFF

5.7.6

Running Delay Timer with Ramp Rate

Set the ramp rate as outlined in section 5.5.1.

Set the delay time as outlined in section 5.6.3.

When ramp rate is active with a delay timer the run indicator serves two functions:

• Indicates timer is running

• Indicates ramp rate is active

This means that when the timer has timed out the run indicator will still be illuminated if the ramp rate is still active and will continue to be illuminated until the ramp reaches setpoint, at which time it will switch off.

A characteristic of these combinations of parameters is that the scrolling text will continue to indicate timer running when the timer has timed out. Checking whether the

timer has timed out or not can be done with the 'T.REMN' function. (see section 5.7.12)

The delay timer with ramp rate will function as outlined in the table above with the addition of the functions in the following table.

5.7.7

Delay timer with ramp rate functions

Timer Ended

When ramp rate active

Indicator – RUN = ON - if ramp rate active

Scrolling Text – Timer Running

To

HOLD timer

Press and quickly release +

Indicator – RUN = Flashing

Scrolling Display – Timer Hold

Static Text - OFF

To switch off

Timer /

Cancel

Press and hold

+ for more than 1 second

To re-

RUN

Timer Press and quickly release +

Indicator – RUN = ON - if ramp rate active

Scrolling Display – None

Static Text - OFF

Indicator – RUN = ON

Scrolling Display – Timer Running

Static Text – OFF

51

5.0   3216CC Controller

5.7.8

Power Failure While Using Delay Timer

If there is a power failure while the timer is operating and the power is subsequently restored, the timer will reset and will re-run from the power on time.

5.7.9

Soft start Timer

Operation

To RUN

Timer

To HOLD timer

To switch off

Timer/

Cancel

Action

Press and quickly release

Press and quickly release

Press and hold second

Timer Ended

+

+

+ for more than 1

Indication

Indicator – RUN = ON

Scrolling Display – Timer

Running

Static Text - OFF

Indicator – RUN = Flashing

Scrolling Display – Timer Hold

Static Text - OFF

Indicator – RUN = OFF

Scrolling Display – None

Static Text - OFF

Indicator – RUN = OFF

Scrolling Text – Timer End

Running Soft Start Timer

When the soft start timer is set to operate, the scrolling display will indicate “timer running” and the setpoint temperature, not the soft start setpoint.

5.7.10

Power Failure While Using Soft Start Timer

If there is a power failure while the timer is operating and the power is subsequently restored, the timer will reset and will re-run from the power on time.

5.7.11

Ramp Rate with Soft Start Timer

It is not recommended that the ramp rate function be used with a soft start timer.

Note: If the temperature is already above the threshold when the timer is set to operate, the timer will time out immediately.

5.7.12

Time Remaining

The time remaining of any 'Timer' mode can be checked at any time while a timer is active.

To view the time remaining, press scroll until the display shows T.REMN <TIME

REMAINING>.

Note: The time remaining can be modified at any time while the count down timer is operating by pressing the up active.

or down key while the time remaining function is

52

5.0   3216CC Controller

5.7.13

Alarms

Alarms are used to alert the operator when a pre-set level has been exceeded or a function error has occurred such as a sensor break. They are indicated by a scrolling message on the display and a flashing red ALM (Alarm) indicator. The alarm may also switch an output – usually a relay to allow external devices to be operated when an alarm occurs. Alarms only operate if they have been configured and are dependant on customer requirements.

How to acknowledge an alarm will depend on the type of latching which has been configured. A non-latched alarm will reset itself when the alarm condition is removed. A

latched alarm requires acknowledgement with the “ACK” Function (see section5.3.2)

before it is reset.

If an alarm has been activated the red “ALM” indicator will illuminate and the scrolling text will indicate the type of alarm.

To Acknowledge an alarm and cancel the “ALM” indicator, press ACK function.

Note: The alarm indicator may seem to be permanently on when viewed from above.

When an alarm is active the indicator should only be flashing, to confirm this, the controller must be viewed directly from the front.

5.8

Controller Options

As options can be ordered in a variety of combinations and for a variety of purposes, exact instructions are not given here. The full Eurotherm manual may be required to determine customer parameter settings. To reveal or hide parameters in the controllers it is necessary to go into configuration mode, a security code is needed. Please consult

Carbolite Gero.

5.8.1

Digital Communications - RS232

If the RS232 option is supplied, the furnace is fitted with one sub-miniature Dsocket connected to the controller comms module. RS232 is suitable for direct connection to a personal computer (PC) using a “straight through” cable as follows

(the linked pins at the computer end are recommended but may not be necessary).

The cable is usually 9-pin at the furnace end and 9-pin at the computer, but other alternatives are shown in parentheses.

Product end of cable female (25-pin) 9-pin

Computer end of cable

9-pin (25-pin) male

Rx

Tx

Com

(2)

(3)

(7)

3

2

5

RS232 Cable: product to PC

_________________

_________________

_________________

3 (2) Tx

2 (3) Rx

5 (7) Com

7,8 (4,5) Link together

1,4,6 (6,8,20) Link together

53

5.0   3216CC Controller

5.8.2

Digital Communications - RS485

If an RS485 option is supplied, the furnace is fitted with two D-sockets. Connection between products is by “straight” cable as follows:

Product end of cable female (25-pin) 9-pin

-

+

Com

(2)

(3)

(7)

3

2

5

RS485 Cable: product to PC

_________________

Computer end of cable

9-pin (25-pin) female

3

2

5

(2)

(3)

(7)

Tx

Rx

Com

5.8.3

Comms Address

Typically the comms address is set to 1, but this can be changed. In the case of RS485 and multiple instruments it is necessary to set different addresses. To change the address value, access the level 2 list. In level 2 press the page key until the COMMS parameter is displayed. Press up down to select the address value.

5.8.4

Alarm Option

When an alarm board is fitted, which consists of a relay with voltage free contacts, for operator use, the contacts are taken to a panel plug on the control panel, wired as indicated:

Key

C Temperature Controller

F Fuse (2A)

S Supply

L Load

*

Normally open relay contacts

RO

Relay Output 240V 2A

MAX

The purpose of the 2 amp fuse is to break the circuit to prevent overloading on the circuit due to high voltage.

The instrument configuration and parameters available to the operator depend on the customer requirements.

Before handling the controller: wear an anti-static wrist strap or otherwise avoid any possibility of damage to the unit by static electricity.

Refer to the detailed instructions supplied with the replacement controller.

54

5.0   3216CC Controller

Ease apart the two lugs at the side; grip the instrument and withdraw it from its sleeve; push in the replacement.

5.9

3216CC Navigation Diagram

55

6.0   2132 Over-Temperature

6.0

2132 Over-Temperature Controller Description (if fitted)

6.1

Description

Key

A Alarm Light

B Page

C Scroll

D Down

E Up

F Display

This over-temperature controller is fitted and supplied ready to use by Carbolite Gero.

It is a digital instrument with a latching alarm, requiring no additional panel controls.

The controller features easy setting of over-temperature setpoint and reading of current temperature by the over-temperature sensor.

6.2

Operation

6.2.1

Controls

Most Carbolite Gero products are fitted with an instrument switch which cuts off power to the controller and other parts of the control circuit.

To operate the controller, power must be supplied to the product and the instrument switch must be on. If a time switch is included in the product circuit, this must be in the

'ON' position.

When an over-temperature condition occurs, the controller cuts the power to a contactor, which in turn cuts power to the heating elements. Power is not restored until the controller is 'reset'.

Some components will operate after the over-temperature feature isolates the power supply e.g. cooling fans will continue to operate, provided that there is a power supply to the product. In some cases the product may not do so, if other options (such as a door switch) are fitted.

56

6.0   2132 Over-Temperature

6.2.2

Operation

When switched on, the controller lights up, goes through a short test routine and then displays the measured temperature or the over-temperature setpoint.

The page key allows access to parameter lists within the controller.

A single press of the page key displays the temperature units, normally set to °C; further presses reveal the lists indicated in the navigation diagram.

The scroll key allows access to the parameters within a list. Some parameters are display-only; others may be altered by the operator.

A single press of the scroll key in the 'Home' list displays the temperature units; further presses reveal the parameters in the current list indicated in the navigation diagram.

To return to the 'Home' list at any time, press page and scroll together, or wait for 45 seconds.

The down and up keys are used to alter the setpoint or other parameter values.

6.2.3

Over-Temperature Operation

Use down and up to alter the over-temperature setpoint. This should normally be set a little above the working temperature (for example 15 °C above). The product is supplied with the over-temperature set at 15 °C above the furnace or oven maximum working temperature.

Press scroll twice view the present temperature as measured by the overtemperature controller. Press it twice, the first press shows the temperature units (°C).

6.2.4

Over-Temperature Alarm

If an over-temperature condition occurs, the OP2 indicator flashes and an alarm message 2FSH also flashes, alternating with the setpoint. Power to the heating elements is disconnected.

6.2.5

Resetting the Over-Temperature Alarm

To acknowledge the alarm press scroll and page together.

If the alarm is acknowledged while there is still an over-temperature condition, the OP2 indicator stops flashing but continues to glow. The 2FSH alarm continues to flash until the over-temperature condition is cleared (by the temperature falling), when normal operation resumes.

If the alarm is acknowledged when the temperature has dropped (or after the overtemperature setpoint has been raised) so that the over-temperature condition no longer exists, then the furnace or oven immediately resumes normal operation.

6.2.6

Sensor Break

The over-temperature cut-out system also operates if the over-temperature control thermocouple breaks or becomes disconnected. The message S.br flashes where the measured temperature is normally displayed.

57

6.0   2132 Over-Temperature

6.3

Audible Alarm

If an audible alarm is supplied for use with the over-temperature controller, it is normally configured to sound on over-temperature condition and to stop sounding when

the alarm is acknowledged as given in section 6.2.

Note: the alarm may sound during controller start-up.

6.4

Navigation Diagram

HL Home List

OTSP

Over-Temperature

Setpoint

AL Access List

Page Key

Scroll Key

For factory access to list and parameters not available to the operator.

Black = Progress

Dashed = Through to other options

58

7.0   Operation

7.0

Operation

7.1

Operating Cycle

This product is fitted with an instrument switch which cuts off power to the control circuit.

Connect the product to the electrical supply.

Turn on the instrument switch to activate the temperature controllers. The controllers illuminate and go through a short test cycle.

Over-Temperature option only . If the digital over-temperature option has not yet been set as required, set and activate it according to the over-temperature controller instructions.

Switch on the heater switch, located on the instrument panel. Unless a time switch is fitted and is switched off, the product will start to heat up. The Heat light(s) glow steadily at first and then flash as the product approaches the desired temperature or a program setpoint.

Over-Temperature option only.

If the over-temperature circuit has tripped, an indicator on the over-temperature controller flashes and the heating elements are isolated. Find and correct the cause before resetting the over-temperature controller according to the instructions supplied.

To switch off power to the heating elements, use the heater switch. To switch the product off, use both the heater switch and the instrument switch. If the product is to be left switched off and unattended, isolate it from the electrical supply.

7.2

Control Method

Set the three temperature controllers to the desired setpoints. The setting and operation of the end zone controllers depends on the 3-zone control options selected when the product was ordered. These options are described in the 3-zone control methods section.

7.3

3-Zone Control Methods

There are three different control options (A, B & C).

(A) Back to back thermocouples

(B) Retransmission of Setpoint

(C) Independent control

The models listed in this manual are designed to achieve an extended uniform temperature zone, through use of three control zones, rather than achieving different temperatures in each zone.

For A & B, the control zones are linked so that they all follow the centre zone controller in a master-slave approach

59

7.0   Operation

Note: l l

Option A is NOT applicable when using the CC-T1 controller

Option B is NOT applicable when using the Eurotherm 2132 End Zone Controller

A. Back-to-Back Thermocouples

This is the most commonly supplied option. The centre zone of the tube furnace is controlled directly by the centre zone temperature controller. The two end zone thermocouples are wired in opposition to the centre zone reference thermocouple. If the temperatures of the centre and end zones are the same then 0°C will be displayed on the end zone controllers. If the end zone temperatures are either higher or lower than the centre zone, the end zone controller will display the difference in temperature

(higher = positive value, lower = negative value).

It is best practice to set the setpoint of the two end zone controllers to zero.

Alternatively, a small temperature difference (offset) can be created by setting a nonzero value, for example to compensate for heat losses at the end or where using a gas flow. However, the sum of the centre zone controller setpoint and the end zone controller offset MUST NOT exceed the furnace maximum temperature.

To alter the setpoint with the display showing the Home screen, press Down or Up once to display the setpoint and then press again or hold down to adjust it. The display returns to the measured temperature when no key is pressed for a short period of time.

Sometimes a furnace using this type of control does not cool down because the end zones lose heat first and therefore the end zone controllers try to compensate for this by switching on the end zone elements, preventing the furnace from cooling.

B. Retransmission of Setpoint

Three independent thermocouples are connected to three controllers. The three controllers are linked together and the centre zone controller communicates the desired setpoint to the end zone controllers. If the centre zone controller is set to a setpoint or is running a program, the end zone controllers will automatically follow.

For products with the CC-T1 controller, please refer to the separate CC-T1 controller manual for details on enabling and disabling setpoint retransmission.

For other products, additional communication modules are fitted in the controllers. The communication between the controllers of the Eurotherm 3000 series is known as

Broadcast communications. It is possible to switch off the linked control and allow the controllers to work independently. In the level 2 menu of the end zone controllers (see controller operating instruction), scroll to L-r. Where the end zone controller is a 3216 use the up down buttons and select NO. Where the end zone controller is a 3508 use the up down buttons to select SP1, (SP1 = Local, and SP2 = Remote). There is no need to alter the centre zone controller.

60

7.0   Operation

It is possible to set an offset (local trim) between the centre and end zone controllers.

This can be either a positive or negative difference from the centre zone temperature.

Once entered, this offset will always be added to, or subtracted from, the retransmitted setpoint temperature.

For products with the CC-T1 controller, please refer to the separate CC-T1 controller manual for details on how to set an offset trim.

To make this adjustment on other controllers, enter thelevel 2 menu of the end zone controllers (see controller operating instruction), scroll to LOC.T (local trim) and use the up down buttons to enter the desired positive or negative value. This will then be added to, or subtract from, the end zone set temperature. There is no need to alter the centre zone controller.

C. Independent Control

The three controllers are completely independent. Note that it is not possible to maintain very different temperatures in the three zones because of heat transfer between the zones. The models listed in this manual are designed to achieve an extended uniform temperature zone by the use of three control zones rather than achieving different temperatures in each zone.

7.4

General Operating Advice

Heating element life is shortened by overheating. Do not leave the product at high temperature when it is not required. The maximum

temperature is shown on the product rating label and in section 13.0

towards the back of this manual.

Lightweight ceramic fibre insulation can easily be marked by accidental contact. Some fine cracks may develop in the surface of the insulation due to the progressive shrinkage of the insulation materials. Cracks are not usually detrimental to the functioning or the safety of the product.

Clean up any spillages in the insulation, as these can increase the rate of degradation of the insulation material.

7.5

Operator Safety

The ceramic materials used in the product manufacture become electrically conductive to some extent at high temperatures. DO NOT use any conductive tools within the product without isolating it. If a metal work tube is used, it must be earthed (grounded).

61

7.0   Operation

Switch off the heater switch whenever loading or unloading the product.

The elements are isolated when the heater switch is OFF. This switch cuts both sides of the circuit via a contactor.

7.6

Tube Life

A ceramic work tube may crack if work pieces are inserted too quickly or at temperatures below 900 °C (when the tube is more brittle). Large work pieces should also be heated slowly to ensure that large temperature differences do not arise.

Poor thermal contact should be encouraged between the work piece and the tube; crucibles or boats should be of low thermal mass and should have feet to reduce the contact with the tube (fig. 4).

Key

A Tube

B Crucible

Fig 4 - Avoidance of thermal contact

Do not set too high a heating or cooling rate. As tubes are susceptible to thermal shock and may break. Tubes which extend beyond the heated part of the furnace are more at risk. A general rule for maximum heating or cooling rate is 400 ÷ internal diameter in mm to give (°C/ min); for 75 mm i/ d tubes this comes to 5 °C per minute. The controller can be set to limit both the heating and cooling rate.

7.7

Pressure

Work tubes are not able to accept high internal pressure. When gas seals or similar fittings are in use, the gas pressure should be restricted to a maximum of 0.2 bar (3 psi). A pressure of approximately half of that should normally be sufficient to achieve the desired flow rate. The operator must ensure that the exhaust path from the tube is not blocked, so that excess pressure does not occur.

A suitably regulated gas supply should always be used.

It is recommended that a pressure relief system should be used to avoid an over pressurisation of the work tube.

Please note: A product should not be heated up if any valves that have been fitted are closed to create a sealed volume. A sealed work tube should not be heated from cold due to the pressure increase caused by the trapped air or gas expanding during the heating process.

62

7.0   Operation

7.8

Power Adjustment

The product control system incorporates electronic power limiting. The power limit parameter OP.Hi is accessible to the operator and can be used to adjust the product to the actual supply voltage.

Some models covered by this manual are fitted with 208 V elements and are designed for use over the range of voltages 200 V- 250 V; the power limit parameter is set accordingly. These models may be relocated to a different voltage within the range: the power limit should be reset to match the voltage.

To check whether the furnace is a 208 V model: l l l l look at the OP.Hi parameter

make a note of the value and compare with the 12.0;

observe the rating label; if a range of voltages is stated, it is not a 208 V multi voltage model; if in doubt, check with Carbolite Gero – each product has its own record card.

Refer to the controller instructions for how to change the power limit.

7.9 Running at Low Temperatures

The power limit may be adjusted to a low level in order to achieve better control when operating the product at a low temperature. Before changing the power limit, record the default settings for possible future use. Refer to the Power Settings section of this manual for default power limits. If the product fails to reach the desired temperature, refer to the Temperature Controller and Fault Analysis sections.

63

8.0   Maintenance

8.0

Maintenance

8.1

General Maintenance

Preventive rather than reactive maintenance is recommended. The type and frequency depends on the product use; the following are recommended.

8.2

Maintenance Schedule

CUSTOMER

QUALIFIED PERSONNEL

DANGER! ELECTRIC SHOCK . Risk of fatal injury. Only electrically qualified personnel should attempt these maintenance procedures.

Safety

Maintenance

Procedure

Over-Temperature Safety Circuit

(if fitted)

Method

Set an over-temperature setpoint lower than the displayed temperature and check for an over-temperature alarm as detailed in this manual

Over-Temperature Safety Circuit

(if fitted)

Safety Switch Function

(split models only)

Safety Switch Function

(split models only)

Electrical Safety (external)

Electrical Safety (internal)

Electrical measurement

Set a safe temperature above ambient, and open the furnace to see if the heater light goes out

Electrical measurement

Visual check of external cables and plugs

Physically check all connections and cleaning of the power plate area

Frequency

Daily Weekly Monthly

Bi-

Annually

Annually

Function

Temperature Calibration

Operational Check

Operational Check

Work Tube Position

End Plugs / Radiation Shields

Tested using certified equipment, frequency dependent on the standard required

Check that all functions are working normally

Thorough inspection and report incorporating a test of all functions

Visually check that the tube is central to the heated zone (horizontally / vertically)

Visual check for damage or wear, and cor-

64

Seals (if fitted)

Performance

Element Circuit

Power Consumption

Cooling Fans (if fitted) rect positioning

Check all seals and O-rings and clamps

Electrical measurement

Measure the current drawn on each phase / circuit

Check whether the cooling fans are working

8.0   Maintenance

65

8.0   Maintenance

8.2.1

Cleaning

The product's outer surface may be cleaned with a damp cloth. Do not allow water to enter the interior of the case or chamber. Do not clean with organic solvents.

Under no circumstances should any objects be placed on top of the product.

Always ensure that any vents on the top of the product are clear of any obstruction. Always ensure all cooling vents and cooling fans (if fitted) are clear of any obstruction.

8.3

Calibration

After prolonged use, the controller and/or thermocouple may require recalibration. This is important for processes that require accurate temperature readings or for those that use the product close to its maximum temperature. A quick check using an independent thermocouple and temperature indicator should be made from time to time to determine whether full calibration is required. Carbolite Gero can supply these items.

Depending on the controller fitted, the controller instructions may contain calibration instructions.

8.4

After-Sales Service

Carbolite Gero Service has a team of Service Engineers who can offer repair, calibration and preventive maintenance of furnace and oven products both at the Carbolite Gero factory and at customers’ premises throughout the world. A telephone call or email often enables a fault to be diagnosed and the necessary parts to be despatched.

In all correspondence please quote the serial number and model type given on the rating label of the product. The serial number and model type are also given on the back of this manual when supplied with the product.

Carbolite Gero Service and Carbolite Gero contact information can be found on the back page of this manual.

8.5

Recommended Spare Parts and Spare Parts Kit

Carbolite Gero can supply individual spare parts or a kit of the items most likely to be required. Ordering a kit in advance can save time in the event of a breakdown.

Each kit consists of one of each type of thermocouple, one solid state relay and one heating element

When ordering spare parts please quote the model details as requested above.

66

9.0   Repairs and Replacements

9.0

Repairs and Replacements

9.1

Safety Warning - Disconnection from Power Supply

Immediately switch the product off in the event of unforeseen circumstances (e.g. large amount of smoke). Allow the product to return to room temperature before inspection.

Always ensure that the product is disconnected from the electrical supply before repair work is carried out.

Caution : Double pole/neutral fusing may be used in this product.

9.2

Safety Warning - Refractory Fibre Insulation

Insulation made from High Temperature Insulation Wool

Refractory Ceramic Fibre, better known as (Alumina silicate wool - ASW).

This product contains alumino silicate wool products in its thermal insulation. These materials may be in the form of blanket or felt, formed board or shapes, slab or loose fill wool.

Typical use does not result in any significant level of airborne dust from these materials, but much higher levels may be encountered during maintenance or repair.

Whilst there is no evidence of any long term health hazards, it is strongly recommended that safety precautions are taken whenever the materials are handled.

Exposure to fibre dust may cause respiratory disease.

When handling the material, always use approved respiratory protection equipment (RPE-eg. FFP3), eye protection, gloves and long sleeved clothing.

Avoid breaking up waste material. Dispose of waste in sealed containers.

After handling, rinse exposed skin with water before washing gently with soap (not detergent). Wash work clothing separately.

Before commencing any major repairs it is recommended to make reference to the

European Association representing the High Temperature Insulation Wool industry

(www.ecfia.eu).

Further information can be provided on request. Alternatively, Carbolite Gero Service can quote for any repairs to be carried out either on site or at the Carbolite Gero factory.

9.3

Temperature Controller Replacement

Refer to the controller instructions for more information on how to replace the temperature controller.

67

9.0   Repairs and Replacements

9.4

Solid-state Relay Replacement

Disconnect the product from the power supply and remove the appropriate cover as given above.

Make a note of the wire connections to the solid state relay and disconnect them.

Remove the solid state relay from the base panel or aluminium plate.

Replace and reconnect the solid state relay ensuring that the bottom of it has good thermal contact with the base panel or aluminium plate.

Replace the access panel.

9.5

Thermocouple Replacement

The coverings and guards which must be removed to gain access to the thermocouple depend on the model, its orientation (horizontal or vertical), and possibly other options and fittings.

It will usually be necessary to separate the product from its base or stand. On horizontal models one outer end-cap will need to be removed and on vertical models the terminal cover. Within some models the thermocouple lies inside the product body; the body must be removed from the control base and the end-cap and insulation ring removed from one end.

Disconnect the product from the power supply. Remove terminal cover to gain access to the thermocouple connections. Make a note of the thermocouple connections.

Thermocouple cable colour codings are: thermocouple leg colour positive (type K) green negative white

Disconnect the thermocouple from its terminal block. Withdraw the thermocouple from its sheath and remove any broken bits of thermocouple.

Bend the new thermocouple carefully to match the shape of the original (working from the terminal end). Should the length differ from that of the original this will usually not be important provided that the thermocouple tip is within a tube diameter's distance from the product centre.

Insert the new thermocouple into position, restoring any removed porcelain spacers and ensuring correct polarity. Re-assemble the product.

68

9.0   Repairs and Replacements

9.6

Element Replacement

See section 9.2 - wearing a face mask is required.

The coverings and guards which must be removed to enable replacement of the wound tube element depend on the furnace model, its orientation (horizontal or vertical), and other options and fittings. The general procedure is:

Disconnect the product from the electrical supply.

Remove all outer guards, meshes and terminal covers from the product's body. For a horizontally mounted product remove the product body from its base; to reach the bolts or screws which fix the body to the base, remove the back panel from the base.

Disconnect all electrical leads from the terminal blocks on the product case. Note the colours and positions of the connecting leads to enable correct reassembly. Take care not to crack porcelain terminal blocks - use two spanners where appropriate.

Remove the thermocouples.

Lay the furnace body horizontally with the split in the cylindrical case uppermost.

Remove the two metal end-caps from the body. Except TZF 12/38, undo the selftapping screws which hold the terminal strip to the case join. The case should spring open slightly. Remove the ceramic board disc from one end.

Use a sharp knife to cut right through the insulation down to the wire-wound tube element along the whole length of the body, but do not cut either of the ceramic board end discs. The knife cut must be in line with the element lead wires. Slide the element gently out through the end of the product body.

Check the cylindrical case and clean out as appropriate.

Remove any insulation sleeving from the tails of the old element and fit to the replacement element.

Slide in the new element(s). Close up the product again, refitting the terminal strip

(where applicable) and the end-caps. Any cut made in the insulation should close up completely: if the insulation appears loose or damaged in any way, please contact the

Carbolite Gero service division.

Reverse the rest of the disassembly process. Take care to make all connections to the correct terminals. Do not over tighten the connectors in porcelain terminal blocks.

Let the product heat up at its maximum rate to 900 °C without interruption and then soak for 1 hour. Fumes may be emitted: this should be done in conditions of good ventilation.

Check that the product is controlling properly to rule out the possibility that the element failed because of a fault in the control system.

If you have any problems with this procedure, please contact the Carbolite Gero service division.

69

9.0   Repairs and Replacements

9.7

Fuse Replacement

Fuses are marked on the wiring diagram with type codes, e.g. F1, F2. For more

information on fuses refer to section 12.0.

Depending on model and voltage, the different fuse types may or may not be fitted.

If any fuse has failed, it is advisable for an electrician to check the internal circuits.

Replace any failed fuses with the correct type. For safety reasons do not fit larger capacity fuses without first consulting Carbolite Gero.

The fuses are located at the cable entry point. Remove the back panel or control box back panel to gain access to the fuses.

70

10.0   Fault Analysis

10.0

Fault Analysis

A.

Furnace Does Not Heat Up

1.

The HEAT light is ON

The heating element has failed

2.

The HEAT light is OFF

The controller shows a very high temperature or code such as S.br

The controller shows a low temperature

There are no lights glowing on the controller

Check also that the SSR is working correctly

The thermocouple has broken or has a wiring fault

The door switch(es) (if fitted) may be faulty or need adjustment

The contactor/relay (if fitted) may be faulty

The heater switch (if fitted) may be faulty or need adjustment

The SSR could be failing to switch on due to internal failure, faulty logic wiring from the controller, or faulty controller

Check the supply fuses and any fuses in the furnace control compartment

The controller may be faulty or not receiving a supply due to a faulty switch or a wiring fault.

71

10.0   Fault Analysis

B.

Product Overheats

1.

Product only heats up when the instrument switch is ON

2.

Product heats up when the instrument switch is OFF

The controller shows a very high temperature

The controller shows a low temperature

The SSR has failed

"ON"

The controller is faulty

The thermocouple may be faulty or may have been removed out of the heating chamber

The thermocouple may be connected the wrong way around

The controller may be faulty

Check for an accidental wiring fault that could have overloaded the SSR

72

11.0   Wiring Diagrams

11.0

Wiring Diagrams

11.1

WC-13-01

Connections below show single phase with indirect safety switches and overtemperature control.

73

11.0   Wiring Diagrams

11.2

WC-13-31

Connections below show single phase with indirect safety switches and overtemperature control.

74

11.0   Wiring Diagrams

11.3

2- and 3-phase With Neutral

Each SSR is connected to a different phase. The control circuit is taken between L1 and

N.

Safety switch A applies for 2-phase. Safety switch B applies for 3-phase.

If type F1 fuse is present, one per phase if fitted.

If type F2 fuse is present, one is fitted; if type F3 fuse is present, one per phase is fitted.

Note that on 2- or 3-phase models there may be three separate neutrals taken to a common supply terminal, depending on EMC filter requirements.

11.4

Independent Zones (control method C)

When this is ordered there are three independent thermocouples (instead of the four shown) connected to the three controllers; the words “master” and “slave” may be replaced by “centre” and “end”.

11.5

Control by Broadcast Comms (control method B)

When this is ordered there are three independent thermocouples connected to the three controllers; the controllers are linked together (not shown), and remain “master” and “slave”.

The communication between the controllers of the Eurotherm 3000 series is known as

Broadcast comms. The wiring connections between the controllers are as follows:

75

12.0   Fuses and Power Settings

12.0

Fuses and Power Settings

12.1

Fuses

F1-F3: Refer to the circuit diagrams.

F1

Internal

Supply

Fuses

F2

Auxiliary

Circuit Fuses

F3

Heat Light

Fuses

Customer

Fuses

Model

TZF 12/38/400

TZF 12/38/400

TZF 12/38/400

Fitted if supply cable fitted.

Fitted on board to some types of EMC filter.

GEC Safeclip of the type shown

(glass type F up to 16 A)

38 mm x 10 mm type F fitted on

EMC filter circuit board(s)

Fitted on board to some types of EMC filter.

May be omitted up to 25 Amp/ phase supply rating.

2 Amps glass type F

On board: 20 mm x 5 mm

Other: 32 mm x 6 mm

May be omitted up to 25 Amp/ phase supply rating.

2 Amps glass type F

32 mm x 6 mm

Required if no supply cable fitted.

Recommended if cable fitted.

Phases

1-phase

1-phase

2-or 3- phase

Volts

110-120

200-240

See rating label for current;

See table below for fuse rating.

380/220-415/240

Supply Rating

20 A

10 A

6 A

12.2

Power Settings

The power limit settings (parameter OP.Hi) for this model are voltage dependant. The figures represent the maximum percentage of time that controlled power is supplied to the elements. Do not attempt to “improve performance” by setting a value higher than the recommended values. To adjust the parameter refer to the "Changing the

Maximum Output Power" of the control section of the manual.

110 V 120 V 208 V 200 V 220 V 230 V 240 V

Volts:

TZF

12/38

1-phase

100|100|100 83|84|83 100|100|100 100|100|100 100|100|100 100|100|100 100|100|100

76

User Power Setting Adjustments

Date % Power Comments

12.0   Fuses and Power Settings

Note: If a new set of elements are fitted then return the power settings to the original value.

Please refer to the rating label for product specific information.

77

13.0   Specifications

13.0

Specifications

Carbolite Gero reserves the right to change the specification without notice.

Model

Max

Temp

(°C)

Max

Power

(kW)

Work Tube

Bore (mm)

Work Tube

Length (mm)

Heated

Length

(mm)

Tube furnaces with a ceramic work tube wound with resistance wire.

TZF 12/38/400 1200 1.3

38 450 400

Net

Weight

(kg)

20

Note: Weights are approximate for horizontal models and do not include fittings or vertical stands.

13.1

Environment

The models listed in this manual contains electrical parts and should be stored and used in indoor conditions as follows:

Temperature: 5 °C - 40 °C

Relative humidity:

Maximum 80 % up to 31 °C decreasing linearly to 50 % at 40

°C

78

Notes

Engineer Name Date

Service Record

Record of Work

The products covered in this manual are only a small part of the wide range of ovens, chamber furnaces and tube furnaces manufactured by Carbolite Gero for laboratory and industrial use. For further details of our standard or custom built products please contact us at the address below, or ask your nearest stockist.

For preventive maintenance, repair and calibration of all furnace and oven products, please contact:

Carbolite Gero Service

Telephone: + 44 (0) 1433 624242

Fax: +44 (0) 1433 624243

Email: [email protected]

Carbolite Gero Ltd,

Parsons Lane, Hope, Hope Valley,

S33 6RB, England.

Telephone: + 44 (0) 1433 620011

Fax: + 44 (0) 1433 621198

Email: [email protected]

www.carbolite-gero.com

Copyright © 2019 Carbolite Gero Limited

advertisement

Related manuals

advertisement