King Electric PYROBOX FPC is a smart and easy-to-use control device for heat tracing systems. It offers various operating and programming options to ensure efficient and reliable temperature control for pipes, valves, and gutters. With its backlit LCD screen, you can easily monitor the system status and make adjustments as needed. Choose between Automatic and Manual modes, set the desired temperature, and adjust the heater hold-on and off delay to optimize energy consumption.
advertisement
![King Electric PYROBOX FPC Installation Instructions | Manualzz King Electric PYROBOX FPC Installation Instructions | Manualzz](http://s3.manualzz.com/store/data/059456354_1-c83c617d05ddc69b372d41aa02fab8ff-360x466.png)
FPC-02 Series
Installation and Operating manual
Index
Introduction…………………………………………………………………...……. 3
FPC-02 Installation notes ……...…………...…………………………………... 4
Wiring the FPC-02-120V, FPC-02-120V-MDB ………………………………. 5
Wiring the FPC-02-240V, FPC-02-240V-MDB ………………………………. 6
Operating instructions…………………………………………………………….7
Turning the system ON and OFF………………………………………………. 7
Selecting temperature scale…………………………………………………….. 7
Selecting Automatic or Manual mode …………………………………………. 7
Heater indication…………..……………………………………………………... 7
Snow flake icon and digital time indication……………………………………. 7
Technician settings……………………………………………………………….. 8
Enter technician settings mode…………………………………………...……. 8
P01 - Temperature set point……………………………………………………. 8
P02 - Lower limit temperature for heating …………………………………….. 9
P03 -Time delay before stopping the heater……..…………………………….9
P04 - Manual mode ON time……………………………………………………. 10
P05 – Not in use……………………………….…………………………………. 10
P06 - Enable/Disable 2 nd temperature sensor (Aquastat)…………………… 10
P07 – Not in use……………………………….…………………………………. 11
P08 – MODBUS MAC Address for building automation (option)…….…...… 11
P09 - Test conditions mode…………………………………………………….. 12
Save changes and return to normal display…………………………...…..…. 12
Restore default values……………………………………………………………. 12
DIP Switch settings……………………………………………………………….. 13
DIP switch S2 - Short measuring times (test only) …………………………... 13
DIP switches S3 and S4 – not in use………………...………………………... 13
Temperature reading errors……………………………………………………... 14
MODBUS communication error……………………..………………………….. 14
Temperature sensor not connected or short circuit ……...………………….. 14
Calibrating and testing the internal GFCI …………………………………….. 14
MODBUS object list……………………………...……………………………….. 15
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 2 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Introduction
The FPC-02 Series power boxes offer smart and easy control for HEAT TRACING SYSTEMS.
It can operate one heating zones.
Typical applications include pipes, valves and gutters.
The backlit LCD screen provides full interface and information to the system status.
The FPC-02 offers various operating and programming options such as:
- Switchable temperature scales (°F or °C) - Adjustable Lower ambient temperature limit to stop
- Both Automatic and Manual modes
- Energy saving temperature limit
- Adjustable heater hold on off delay
heater (lockout)
- Commissioning/Test environment
FPC-02 General system layout
Operating panel
ON
Aquastat sensor (option)
Temperature sensor
FPC-02
Zone 1 Pipe
Sensor
Heater
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 3 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
FPC-02 Series Installation
PLEASE READ THIS MANUAL AND THE SAFETY WARNINGS CAREFULLY BEFORE INSTALLING
AND USING THE CONTROLLER AND SAVE IT FOR FUTURE USE
Installation notes
Familiarize yourself with the markings, warnings, components and terminology.
The FPC-02 power boxes and its accessories must be installed by a qualified electrician in accordance with local regulations and the requirements of the NEC (NFPA 72 ) and the CEC part 1.
WARNING: Ensure the power is disconnect from all circuits before mounting the power box and making any connections. Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death.
Installer must ensure the installation of approved disconnect means, for all power supply circuits feeding this unit.
The power boxes are suitable for indoor wall mount installation only.
Ensure wiring according to the provided schematics using copper conductors only.
Make sure the wire gauge (AWG) is suitable for the circuit amperage draw, as specified in the
NEC/CEC table 1.
Ensure that the main breakers (fuses) are suitable for the heating systems rating (80% load).
Grounding means must comply with local regulations and CEC/NEC.
Ensure that the heating system/de-icing system connected to this unit complies with the UL 499 or
UL 515 & CSA 22.2 # 130.3 standard and is certified / listed by an NRTL.
Ensure that all wiring is rated for the application at 60°C (140°F as per UL 515 CSA 22.2 #130 clause 12 table 12.1.
Beware that any holes punched for conduit are to compromise the integrity of the enclosure ratings.
Ground fault equipment protection (GFEP)
The ground fault interrupter/residual current detector installed in this system is a Non class A GFCI, intended for equipment protection.
Familiar yourself with its operation and required setting.
The GFEP should be tested monthly. Please refer to the GFEP testing instructions on page 14 of this manual.
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 4 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Wiring the FPC-02
Heater load connection
Provide terminals L, N with up to 120 VAC, 30 AMP.
Make sure the wire Gauge (AWG) is suitable for the circuit Amperage draw, as specified in the NEC/
CEC table 1.
Caution: Incorrect voltage may cause fire or seriously damage the unit.
N N L L
FPC-02-120V
NO NC HE C C 1 2
Main
Supply
120 VAC
Branch circuit protection and disconnect provided by installer. Max. 30A
Heater
Load connection
120 VAC, 30A
GFEP
Indication
Dry Contact
(NO/NC)
*See table
Heat
Indication
(24VAC)
PYROULS
(By Meitav-tec)
Aquastat
(option)
Main
Supply
120 VAC
Branch circuit protection and disconnect provided by installer. Max. 30A
N N L L
FPC-02-120V-MDB
NO NC HE C C 1 2
Heater
Load connection
120 VAC, 30A
GFEP
Indication
Dry Contact
(NO/NC)
*See table
Heat
Indication
(24VAC)
A B
RS485
MODBUS
Communication cable
2x22AWG
Twisted, Shielded
PYROULS
(By Meitav-tec)
Aquastat
(option)
*GFEP Indication - Dry Contact
GFEP Tripped
GFEP NOT Tripped
NO - COM
SHORT
OPEN
NC - COM
OPEN
SHORT
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 5 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Wiring the FPC-02
Heater load connection
Provide terminals L, N with up to 240 VAC, 30 AMP.
Make sure the wire Gauge (AWG) is suitable for the circuit Amperage draw, as specified in the NEC/
CEC table 1.
Caution: Incorrect voltage may cause fire or seriously damage the unit.
L1 L1 L2 L2
FPC-02-240V
NO NC HE C C 1 2
Main
Supply
240 VAC
Branch circuit protection and disconnect provided by installer. Max. 30A
Heater
Load connection
240 VAC, 30A
GFEP
Indication
Dry Contact
(NO/NC)
*See table
Heat
Indication
(24VAC)
PYROULS
(By Meitav-tec)
Aquastat
(option)
Main
Supply
240 VAC
Branch circuit protection and disconnect provided by installer. Max. 30A
*GFEP Indication - Dry Contact
GFEP Tripped
GFEP NOT Tripped
NO - COM
SHORT
OPEN
L1 L1 L2 L2
FPC-02-240V-MDB
NO NC HE C C 1 2
Heater
Load connection
240 VAC, 30A
GFEP
Indication
Dry Contact
(NO/NC)
*See table
Heat
Indication
(24VAC)
A B
RS485
MODBUS
Communication cable
2x22AWG
Twisted, Shielded
PYROULS
(By Meitav-tec)
Aquastat
(option)
NC - COM
OPEN
SHORT
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 6 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Operating instructions
Turning the system ON and OFF
Press and hold the [ON] button for 0.5 seconds to turn the system ON or OFF.
The words “ON” or “OFF” will appear on display.
When ON, the green LED on the front panel will also turn ON .
Selecting temperature scale
Press the [+] button for Celsius.
Press the [-] button for Fahrenheit.
Selecting Automatic or Manual mode
Press the [SELECT] button to switch between modes:
“Automatic” Heating will start and stop automatically depending on the set point and ambient temperatures.
“Manual ON” Heating will start regardless of the set point and ambient temperatures and will stop after a preset time (pls. refer to the
“Manual ON” section in the tech. settings).
Note: Mode will always return to “Automatic” after switching the unit OFF and ON.
Heater indication
Black icon – Heater ON
White icon – Heater OFF
Heater ON Heater OFF
When ON, the red LED on the front panel indicating heater operation will also turn ON .
Snow flake icon and digital time indication
A solid snow flake icon will appear on display during normal heater operation.
A blinking snow flake icon will appear on display during heater off delay or when manual mode is activated. The digital clock will count down the remaining time until the heater is turned off.
The snow flake icon will disappear from display as long as the heater is turned off.
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 7 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Technician settings
Use the technician settings mode to view and adjust the following parameters:
P01 Temperature set point
P02 Lower ambient temperature limit to stop the heater
P03 Time delay before stopping the heater
P04 ON time for manual mode
P05 Not in use
P06 Enable/Disable 2 nd temperature sensor logic (Aquastat)
P07 Not in use
P08 MODBUS MAC Address for home automation system (option)
P09 Commissioning / Test mode
Restore defaults
Enter technician settings mode
Disconnect power and open the internal door by releasing the two screws.
Move DIP switch S1 located on the side of thermostat to ON position.
Press the [SELECT] and [+] buttons simultaneously to move forward to the next technician parameter.
Press the [SELECT] and [-] buttons simultaneously to return to the previous technician parameter.
Save changes and exit technician settings mode
Move DIP switch S1 located on the side of thermostat to OFF position.
Important: Changes made to technician parameters will not take effect as long as DIP switch S1 is in ON position.
Enter technician settings mode
Save changes and exit technician settings mode
Parameters:
P01 - Temperature set point
Move DIP switch S1 located on the side of thermostat to ON position.
“P01” and the temperature set point will appear on display.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: 5…60°F / -15…+15°C, Default: 37°F / 3°C
As long as the ambient temperature is lower than the temperature set point P01, the FPC-02 will turn ON.
Temperature set point
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 8 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Technician settings (Cont’)
P02 - Lower limit temperature for heating
Press the [SELECT] and [+] buttons simultaneously.
“P02” and the low limit temperature will appear on display.
When the temperature on the temperature sensor drops below the low temperature limit, the heating system will stop.
Use the [+] and [-] buttons to adjust the temperature set point.
Range: -40…+23°F / -40…-5°C Default: -40°F / -40°C
Press the [SELECT] and [+] buttons simultaneously again.
The word “ON” or “OFF” will appear on display.
Use the [+] and [-] buttons enable (ON) or disable (OFF) the P02 parameter.
If disabled, the heating system will operate without low temperature limitations.
P03 -Time delay before stopping the heater
Press the [SELECT] and [+] buttons simultaneously.
“P03”, “dL” and the time delay before stopping the heater (Hold ON) will appear on display. The hours will blink.
Use the [+] and [-] buttons to adjust the hours of the time delay.
Range: 0000...9999 minutes Default: 120 minutes
Note 1. The time delay countdown will start when the ambient temperatures rises above the set point temperature.
Note 2. The staggering sequence will continue during the time delay period.
P02 enabled
Low limit
Temperature
P02 disabled
Time delay
(minutes)
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 9 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Cont’
Technician settings (Cont’)
P04 - Manual mode ON time
Press the [SELECT] and [+] buttons simultaneously.
“P04”, “On” and the time “Manual ON” mode time period will appear on display. The hours will blink.
The delay time parameter defines a time frame in which the heater remains
ON after receiving an “Manual ON” command.
Use the [+] and [-] buttons to adjust the hours of the working time.
Range: 00...99 hours Default: 03 hours
Press the [SELECT] and [+] buttons simultaneously again.
The minutes will blink.
Use the [+] and [-] buttons to adjust the minutes of the working time.
Range: 00...59 minutes Default: 00 minutes
P05 – Not in use
Press the [SELECT] and [+] buttons simultaneously.
“P05” will appear on display.
Proceed to P06.
Manual ON
(minutes)
P06 – Enable/Disable Temperature sensor / Aquastat logic
Press the [SELECT] and [+] buttons simultaneously.
“P06” and the number “0” or “1” will appear on display.
Use the [+] and [-] buttons to select between:
“0” - Logic set by both TEMPERATURE SENSOR and AQUASTAT (default).
“1” - Logic set by TEMPERATURE sensor only.
“2” - Logic set by AQUASTAT sensor only
Logic by temperature sensor and aquastat
Logic by temperature sensor only
Logic by aquastat sensor only
Cont’
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 10 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Technician settings (Cont’)
P07 – Not in use
Press the [SELECT] and [+] buttons simultaneously.
“P07” will appear on display.
Proceed to P08.
P08 – MODBUS MAC Address (for MDB models only)
Press the [SELECT] and [+] buttons simultaneously.
“P08” and the MODBUS MAC Address will appear on display.
Use the [+] and [-] buttons to set the MAC Address of the unit.
Setting the MAC address for the unit will make it available through the home automation system.
Range: 0 – 60.
Select “0” for NO COMMUNICATION system (default).
MODBUS
MAC Address
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 11 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Cont’
Technician settings (Cont’)
P09 - Test conditions mode / Technician commissioning mode
Turn ON test conditions to check the functionality of the system regardless of temperature sensors parameters (i.e. during the summer).
In test conditions, the Ambient temperature is always -7°C/19°F.
Press the [SELECT] and [+] buttons simultaneously.
“P09” will appear on display. The hours will blink.
Use the [+] button to enter test/commissioning mode – the word “Test” will appear on display.
Use the [-] button to manually exit test/commissioning mode – the word
“Test” will disappear from display.
Note: If the technician did not manually exit test/commissioning mode, the unit will automatically return to normal mode after 5 hours.
Save changes and return to normal display
In order to save changes and return to normal display, move DIP switch S1 back to
OFF position.
Important: Changes made to technician parameters will not take effect as long as DIP switch S1 is in ON position.
Restore default values
Move DIP switch S1 to ON position.
Press and hold the [ON] button for 10 seconds. The controller will beep.
Move DIP switch S1 back to OFF position.
Test conditions mode
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 12 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Technician settings (Cont’)
DIP switch S2 - Short measuring times (test only)
Use DIP switch S2 to short the
- “ON” - Short measuring times – for test/commissioning only (measuring times will be divided by 60).
- “OFF” - Normal operation.
Short measuring times: A real 1 hour will take 1 minute and a real 1 minute will take 1 second.
DIP switches S3 and S4 – Not in use (must be in OFF position)
S3 OFF, S4 OFF
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 13 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
System Errors
Error 1 – MODBUS Communication error
“Aux1” Will appear on display.
Communication error
Error 2 – Temperature sensor is not connected or short circuit
“SensErr 1” Will appear on display.
Temperature
Sensor error
GFEP
The GFEP is designed to provide protection for electrical equipment.
GFEP TEST
The GFEP should be tested monthly. Press the blue “T” test button to trip the outlet and break the circuit. The YELLOW LED on the front panel should lit. Lift the RESET GFEP button to return to normal operation and reestablish power and protection.
Test button
Reset button
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 14 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Object list (for MDB models only)
OBJECT LIST FOR FPC-02-MDB Series rev. 1.0
MODBUS RTU Mode, Address Slave 1-60, Baud Rate 9600, n, 8, 1
All Registers Signed Integer 16 bit,
R - Register Read Only, R/W - Register Read/Write
Dec,[Hex] Value Description Read/Write
0, [0000] -13°F .. 54°F/ -40..+16°C Measured Temperature
1, [0001] 5°F... 59°F /-15°C...+15°C P01 – Temperature set point
2, [0002] -40°F... +23°F/-40°C...-5°C P02 – Lower temperature limit for heating
3, [0003] min (0-9999) P03 – Time delay before stopping the heater
4, [0004] min (0-9999) P04 – Manual mode ON time
5, [0005] 60
6, [0006] 0,1,2
7, [0007]
8, [0008] 0/1
9, [0009] 0/1/2
10, [000A] 0/1/2
11, [000B] 0/1/2
12, [000C] 0/1/2
P05 – Not in use
P06 – Enable/Disable temp. sensor/Aquastat logic
P07 – Not in use
P09 – Test conditions mode
Heater 1 (0-OFF, 1-ON, 2-Not in use)
Not in use
Not in use
Not in use
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R/W
R/W
R/W
R/W
13, [000D] 0/1/2
14, [000E] 0/1
15, [000F] 0/1
16, [0010] 0/1
17, [0011] 0/1
18, [0012] 0/1
19, [0013] 0/1
20, [0014] 0/1
Not in use
Aquastat Signal (0-OFF, 1-ON)
SW1
SW2
SW3 – Not in use
SW4 – Not in use
ON/OFF (0-OFF, 1-ON)
Celsius/Fahrenheit (0-F, 1-C)
R
R
R
R/W
R
R
R/W
R/W
FPC-02 Series
Owner’s manual & Technician Settings
Pg. 14 Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com
Tel: (856) 2882882
Tel: +972-3-9626462
Fax: +972-3-9626620 support@meitavtec .
com www.meitavtec.com
advertisement
Related manuals
advertisement
Table of contents
- 3 Introduction
- 4 FPC-02 Installation notes
- 5 Wiring the FPC-02-120V, FPC-02-120V-MDB
- 6 Wiring the FPC-02-240V, FPC-02-240V-MDB
- 7 Operating instructions
- 7 Turning the system ON and OFF
- 7 Selecting temperature scale
- 7 Selecting Automatic or Manual mode
- 7 Heater indication
- 7 Snow flake icon and digital time indication
- 8 Technician settings
- 8 Enter technician settings mode
- 8 P01 - Temperature set point
- 9 P02 - Lower limit temperature for heating
- 9 P03 -Time delay before stopping the heater
- 10 P04 - Manual mode ON time
- 10 P05 – Not in use
- 10 temperature sensor (Aquastat)
- 11 P07 – Not in use
- 11 P08 – MODBUS MAC Address for building automation (option)
- 12 P09 - Test conditions mode
- 12 Save changes and return to normal display
- 12 Restore default values
- 13 DIP Switch settings
- 13 DIP switch S2 - Short measuring times (test only)
- 13 DIP switches S3 and S4 – not in use
- 14 Temperature reading errors
- 14 MODBUS communication error
- 14 Temperature sensor not connected or short circuit
- 14 Calibrating and testing the internal GFCI
- 15 MODBUS object list