- Home
- Home security & automation
- Carbon monoxide (CO) detectors
- Det-Tronics
- Gas Inspector Software
- Instructions
advertisement
INSTRUCTIONS
Gas Inspector Monitor Software for use with Det-Tronics
FlexVu
®
Universal Display
Model UD10
IMPORTANT
All firmware versions of the FlexVu® UD10 are compatible with the latest Gas Inspector Monitor
(1.6.xx). To take full advantage of the latest Gas
Inspector Monitor features, the FlexVu UD10 firmware must be 2.80 or higher. The firmware version is located in the Systems Setup window
(see Figure 11).
DESCRIPTION
The FlexVu ® Universal Display Model UD10 is designed and approved as a ‘stand alone’ device, while also performing all the functions of a gas controller. When the
FlexVu UD10 is used in combination with a compatible
Detector Electronics Corporation (Det-Tronics) gas sensor/detector, it is able to record important information
(alarms, faults, and calibrations) from the sensor/detector.
The information is date and time stamped, and stored in the electronics module of the FlexVu UD10. Gas
Inspector Monitor allows the user to later upload the stored information to a Personal Computer (PC), where it can be displayed, saved, or printed.
FEATURES
HARDWARE REQUIREMENTS
Gas Inspector Monitor software can operate on most
Intel ® based computers running Microsoft ® Windows
XP or Windows 7. When installing Gas Inspector Monitor in Windows 7, ensure that the PC is a 32-bit version.
Currently, 64-bit computers running Windows 7 are incompatible with Gas Inspector Monitor.
A minimum of 16 megabytes of RAM is required, however,
32 or more megabytes are recommended for optimum performance. The software also requires a color monitor with a minimum resolution of 640 by 480, and a hard drive with at least 10 megabytes of free space.
• Data logs available for Det-Tronics sensors/detectors
(see Table 1)
• Displays real time fault/alarm indicators
• Stored data can be uploaded to a PC
• Logs can be viewed, stored to a file, or printed.
INSTALLATION
SOFTWARE
CAUTION
The PC must always be located in a non-hazardous controlled location.
Table 1—Data Logging Capabilities
GT3000
PIR9400
PIRECL
OPECL
NTMOS
C706X
CGS
Calibration Log Storage
UD10
X
X
X
X
X
X
X
SENSOR/DETECTOR
X
X
X
NOTE: All event logs are stored in the UD10.
NOTE
It is recommended that the installation of the USB and RS-485 drivers be completed before installing the Gas Inspector Monitor software.
NOTE
The following procedures are for Windows XP. If using Windows 7, note that the dialog windows may appear different from the examples shown.
2.2 © 2020 Detector Electronics Corporation Rev: 1/13 95-8645
WARNING
Do not open the FlexVu UD10 assembly in a hazardous area when power is applied.
Driver Software
The first installation setup is for the USB driver followed automatically by the installation of the RS-485 driver.
Follow these steps to install the driver software:
1. Apply power to the FlexVu UD10. Allow it to warm up and reach a normal operating mode.
2. Insert the driver installation CD.
3. Connect the RS-485 to the FlexVu UD10’s Modbus terminal, then connect the converter to a USB port on the PC (Figure 1).
CONNECT THIS END TO
THE PC USB PORT
5. On the following window, select “Install the software automatically (Recommended),” then click Next
(Figure 3).
Figure 3—Recommended Driver Installation
A2497
CONNECT THIS END TO
THE FLEXVU UD10
RS485 PORT (J2)
Figure 1—Gas Inspector Connector with RS-485 to USB Converter
NOTE
The Gas Inspector Connector includes a universal power supply that can plug into any standard
120/240 Vac outlet.
4. The Found New Hardware Wizard will appear. Select
“No, not this time,” then click Next (Figure 2).
6. Installation will begin when the Hardware Installation window appears. Click Continue Anyway to proceed with the installation (Figure 4).
Figure 4—Hardware Installation Window
2.2
Figure 2—Found New Hardware Wizard
2 95-8645
7. When installation is complete, a confirmation window will appear (Figure 5). Click Finish to complete this stage of the installation.
3. Choose a destination (Figure 7) for installing Gas
Inspector Monitor, then click Next to continue.
Figure 7—Install Destination
4. A confirmation window will appear to verify that the installation should begin. Click Next to confirm
(Figure 8).
Figure 5—Completed Driver Installation
8. The installation process for the RS-485 driver will begin automatically. Follow the instructions from
Step 4 to complete the installation for the RS-485.
Gas Inspector Monitor Software
NOTE
It is strongly recommended that all running programs in Windows be closed before installing the Gas Inspector Monitor software.
NOTE
Uninstall all previous versions of Gas Inspector
Monitor and restart the computer before proceeding to Step 1.
1. Insert the Gas Inspector Monitor software CD
(p/n 010268-001).
2. Click Next on the Welcome window (Figure 6).
Figure 8—Conirm Installation
5. When the installation is complete, a confirmation window will appear (Figure 9). Click Close to end the installation process.
2.2
Figure 6—Welcome Window
3
Figure 9—Installation Complete Window
95-8645
Active X Software
At the initial startup of Gas Inspector Monitor, some users may be alerted to install Active X (Figure 10). This installation is performed only once and is required for
Gas Inspector Monitor to function correctly. If the alert for Active X does not appear, proceed to the “Startup” section.
4. Click the large button to continue (Figure 10C).
Figure 10C—Installation Location Window
Figure 10—Install Active X Alert
Use the following procedure to install Active X:
1. Click on the “setuppad” installer, located on the Gas
Inspector Monitor software CD.
2. Click Yes to accept the End User Agreement
(Figure 10A).
5. Click Continue on the Program Group window to continue the installation (Figure 10D).
Figure 10A—End User Agreement Window
3. Click Continue on the Welcome window (Figure 10B).
Figure 10D—Program Group Window
6. Click OK on the next window to exit the installer (Figure 10E).
Figure 10E—Exit Installer Window
Figure 10B—Welcome Window
2.2
4 95-8645
STARTUP
NOTE
Communication between the FlexVu UD10 module and the PC uses the Modbus RTU protocol, with the FlexVu UD10 module configured as a Modbus slave.
WARNING
Do not open the FlexVu UD10 assembly in a hazardous area when power is applied.
1. With the FlexVu UD10 in a normal operating mode, open Gas Inspector Monitor. The System Setup window will open with the recommended Modbus
Settings of 9600 baud rate, no parity, and a polling address of 1 (Figure 11).
Figure 12—Computer Management Window
3. Click Find Device to create a connection between the FlexVu UD10 and the PC. A dialog box will appear above the System Setup window to confirm the connection (Figure 13). Click OK , then click
Proceed to continue.
Figure 11—System Setup with Default Settings
2. Verify that the appropriate PC Comm port is selected by looking in the Windows Device Manager for the correct setting. This is accomplished by right-clicking on My Computer (from the Start Menu), then select
“Manage.” When the Computer Management window appears, select Device Manager (Figure 12) and expand the menu tree for Ports (COM & LPT). Make sure the RS-485 Port is using the same Comm Port shown in the System Setup window (Figure 11).
Figure 13—Device Connected Dialog Box
NOTE
In cases where the FlexVu UD10 cannot be found (Figure 14) after selecting “Find Device,” the settings entered in the System Setup are incorrect or the USB converter is faulty. Uninstall and reinstall the drivers to resolve this problem.
2.2
5
Figure 14—Device Not Connected Dialog Box
95-8645
UNINSTALLING DRIVERS
1. To uninstall drivers, right-click on My Computer and select “Manage” to open the Computer Management window. Select “Device Manager ” (Figure 12).
2. Expand the “Universal Serial Bus controllers” tree, and the USB converter will be listed by model number. Right-click on the appropriate model and choose “Uninstall.”
3. Click OK to confirm removal of the drive. The same steps can be used to uninstall the RS-485 driver.
TOOLS MENU
After the user completes all the required installations, Gas
Inspector Monitor is ready to monitor information stored in the FlexVu UD10. The monitoring tools accessible to the user are Logs, Status, and System Setup.
Event Logs
Event logs are listed by Event (number), Date, Time,
Description, and Event ID. Each Event ID number is related to a specific Description (e.g. POWER UP, LOW
ALARM ON, etc.). Normal status is highlighted in green, faults in yellow, and alarm events are red (Figure 20).
Calibration Logs
Calibration logs are listed by Event (number), Date, Time,
Description, Event ID, Cal Zero, and Cal Span. Each
Event ID number is related to a specific Description (e.g.
ZERO CAL, SPAN CAL, etc.). The values under the Cal
Zero and Cal Span columns represent the “Raw Sensor
A-to-D (Analog-to-Digital) Counts.” Normal calibration status is highlighted in green, calibration faults in yellow, and failed calibrations are red (Figure 21).
SORT ORDER
By default, logs are sorted by most recent date and time.
Logs can also be sorted by description (alphabetically), by double-clicking on the Description column header.
LOGS
This option opens the Logs window, where the user can select between Event Logs or Calibration Logs. Choose the log type to be retrieved by selecting from the dropdown menu, labeled “Log Type” (Figure 15). Storing and retrieving of event logs are performed by the FlexVu
UD10, for all sensor/detector types. Depending on the sensor/detector logging capabilities, calibration logs are stored in the sensor/detector or in the FlexVu UD10,
(Table 1). All Event and Calibration Logs are dated and time stamped.
SAVING FILES
To save a file for use in a spreadsheet, such as Excel, click the Export to File button (Figure 17).
Figure 17—Export to File
ADDITIONAL BUTTONS
The Stop button (Figure 18) will immediately suspend the retrieval of an event log or calibration log. Click the
Retrieve Logs button to begin a new retrieval.
Figure 15—Log Type Selection
To begin retrieving logs, click the Retrieve Logs button
(Figure 16).
Figure 18—Stop
Figure 16—Retrieve Logs
All data is stored in non-volatile memory, which can accommodate approximately 1000 events. When the maximum is exceeded, the oldest events are automatically overwritten to make room for the newest events.
The Close button (Figure 19) exits the Logs window, allowing other user accessible tools to be selected.
Figure 19—Close
2.2
6 95-8645
Figure 20—Example of Event Logs
2.2
Figure 21—Example of Calibration Logs
7 95-8645
STATUS
Click the Status button to view the current status of the
FlexVu UD10 and the connected device. By default, the status window displays the FlexVu UD10 information only. Select the Device tab to view information about the connected device.
The Fault/Status window displays various status and fault information about the FlexVu UD10 and the device connected to it. Note that all information in this window is read only. The FlexVu UD10 and the connected device each have their own distinct Fault/Status windows
(Figures 22-25).
GAS LEVEL= THE CURRENT GAS LEVEL READ BY THE UD10.
TEMPERATURE= CURRENT OPERATING TEMPERATURE OF THE UD10.
mA= THE CURRENT MILLIAMP LEVEL OF THE DEVICE
CONNECTED TO THE UD10.
EXIT= RETURN TO PREVIOUS SCREEN (TOOLS MENU).
UD10 and CONNECTED DEVICE TABS
STATUS
ANY FAULT
WARM UP
LOW RELAY ACTIVE
HIGH RELAY ACTIVE
AUXILIARY ACTIVE
OUTPUT CURRENT FIXED
MODBUS WRITE ENABLED
HART SELF TEST
RESPONSE TEST
MANUAL SELF TEST
INPUT HART
DESCRIPTION
GENERAL FAULT INDICATION.
UD10 IS IN THE POWER-UP MODE.
LOW ALARM IS ACTIVE.
HIGH ALARM IS ACTIVE.
AUXILIARY ALARM IS ACTIVE.
CURRENT IS FIXED FOR TESTING THE 4-20 LOOP.
THERE IS ACCESS TO THE FACTORY CONFIGURATION VARIABLES
IN THE UD10.
HART INITIATED SELF TEST IS IN PROCESS.
4-20 IS LOCKED AT 4.0 mA FOR TESTING THE DISPLAY
MANUAL SELF TEST IS IN PROCESS.
THERE IS NO COMMUNICATION BETWEEN THE UD10 AND THE
CONNECTED HART BASED DETECTOR.
NOTE 1 : ALL INFORMATION DISPLAYED
ON THIS SCREEN IS READ ONLY.
NOTE 2 : INDICATORS THAT ARE LABELED
“RSVD,” ARE NOT USED.
Figure 22—FlexVu UD10 Status Indicators Defined
2.2
8 95-8645
2.2
FAULT CONDITION
EE FAULT
ADC FAULT
24 VOLT FAULT
FLASH FAULT
RAM FAULT
WDT FAULT
12 VOLT FAULT
5 VOLT FAULT
3 VOLT FAULT
OUTPUT LOOP FAULT
INPUT LOOP FAULT
DESCRIPTION
FAULT IN NON-VOLATILE CONFIGURATION MEMORY.
ADC REFERENCE VOLTAGE TOO HIGH OR LOW.
PROBLEM IN THE 24 VOLT POWER SUPPLY OR POWER WIRING.
FAULT IN VOLATILE MEMORY.
FAULT IN VOLATILE MEMORY.
WATCHDOG TIMER IS NON-FUNCTIONAL.
12 VOLT INTERNAL POWER SUPPLY OUT OF TOLERANCE.
5 VOLT INTERNAL POWER SUPPLY OUT OF TOLERANCE.
3 VOLT INTERNAL POWER SUPPLY OUT OF TOLERANCE.
FAULT IN 4-20 mA OUTPUT LOOP.
FAULT IN SENSOR OR SENSOR LOOP.
RECOMMENDED ACTION
RETURN TO FACTORY.
RETURN TO FACTORY.
CHECK POWER SOURCE.
RETURN TO FACTORY.
RETURN TO FACTORY.
RETURN TO FACTORY.
RETURN TO FACTORY.
RETURN TO FACTORY.
RETURN TO FACTORY.
RETURN TO FACTORY.
CHECK 4-20 mA LOOP WIRING FOR SHORTS OR OPENS.
CHECK SENSOR WIRING.
CALIBRATE SENSOR.
ENSURE THAT SENSOR TYPE MATCHES CONFIGURATION.
NOTE
1
: ALL INFORMATION DISPLAYED
ON THIS SCREEN IS READ ONLY.
NOTE
2
: INDICATORS THAT ARE LABELED
“RSVD,” ARE NOT USED.
Figure 23—FlexVu UD10 Fault Indicators Defined
9 95-8645
STATUS
WRITE PROTECT
RESPONSE TEST
4-20 FIXED
SENSOR REMOVED
SENSOR END OF LIFE (CGS ONLY)
LOOP TEST ACTIVE
TDSA ALARM
QUICK ALARM
DESCRIPTION
THE DEVICE IS IN THE WRITE PROTECT MODE.
4-20 IS LOCKED AT 4.0 mA FOR TESTING THE DEVICE.
OUTPUT CURRENT IS FIXED FOR TESTING 4-20 LOOP.
SENSOR MODULE IS MISSING OR DEFECTIVE.
SENSOR NEEDS REPLACEMENT.
4-20 LOOP IS IN PROCESS.
NOT USED.
NOT USED.
2.2
STATUS
CALIBRATION ACTIVE
WARM UP MODE
LOW ALARM
AUXILIARY ALARM
HIGH ALARM
HART SELF TEST
CONFIGURATION CHANGE
ALIGNMENT MODE
DESCRIPTION
CALIBRATION IS IN PROCESS.
DEVICE IS IN POWER-UP MODE.
A LOW ALARM CONDITION HAS BEEN DETECTED.
AN AUXILIARY ALARM CONDITION HAS BEEN DETECTED.
A HIGH ALARM CONDITION HAS BEEN DETECTED.
HART INITIATED SELF TEST IS IN PROCESS.
A CHANGE HAS BEEN MADE TO A CRITICAL DEVICE
PARAMETER.
DEVICE IS IN A SPECIAL ALIGNMENT MODE (FOR OPECL).
NOTE 1 : ALL INFORMATION DISPLAYED
ON THIS SCREEN IS READ ONLY.
NOTE 2 : EACH DETECTOR TYPE UTILIZES A SET OF DEVICE
SPECIFIC STATUS BITS THAT DETERMINE WHICH
INDICATORS BECOME ACTIVE DURING AN ALARM OR FAULT.
Figure 24—Device Status IndIcators Defined (GT3000 Shown)
10 95-8645
STATUS
LOOP FAULT
SUPPLY VOLTAGE FAULT
CALIBRATION FAULT
MEMO RY FAULT
ADC FAULT
INTERNAL VOLTAGE FAULT
ZERO DRIFT
TEMP. SENSOR FAULT
WRONG SENSOR TYPE
LAMP FAULT
ALIGNMENT FAULT
BLOCKED OPTIC FAULT
CAL LINE ACTIVE
SENSOR FAULT
NOISE FAULT
ALIGN ADC SAT
24
DESCRIPTION
CURRENT LOOP BELOW FAULT THRESHOLD.
VOLT POWER SUPPLY VOLTAGE TOO LOW OR
TOO HIGH.
UNSUCCESSUL CALIBRATION
SELF-DETECTED MEMORY FAULT.
SELF-DETECTED ADC FAULT.
SELF-DETECTED VOLTAGE FAULT.
SENSOR SIGNAL HAS DRIFTED NEGATIVE.
TEMPERATURE SENSOR IS OUT OF RANGE.
NEW OR DIFFERENT SENSOR TYPE IS INSTALLED.
OPEN OR SHORTED LAMP.
ALIGNMENT PROBLEM.
OPTICAL PATH IS BLOCKED.
CAL LINE IS ACTIVE AT START-UP.
SELF-DETECTED FAULT WITH THE SENSOR.
EXCESSIVE NOISE ON SIGNAL.
ALIGNMENT ADC SATURATED.
RECOMMENDED ACTION
CHECK 4-20 mA LOOP WIRING FOR SHORTS OR OPENS.
VERIFY PROPER WIRING TO THE DEVICE AND CORRECT VOLTAGE LEVEL AT THE DISPLAY AND DETECTOR.
THIS FAULT CAN BE CAUSED IF THE CALIBRATION IS ALLOWED TO TIME OUT. IF SO, RE-CALIBRATE.
ENSURE THAT THERE IS ENOUGH GAS IN THE CALIBRATION BOTTLE TO COMPLETE THE CALIBRATION.
ENSURE THAT THE GAS BEING USED FOR CALIBRATION IS THE CORRECT TYPE AND CONCENTRATION.
IT MUST MATCH THE CONFIGURED SETTING.
RETURN TO FACTORY.
RETURN TO FACTORY.
CHECK SUPPLY VOLTAGE. RETURN TO FACTORY.
THIS DEVICE MAY HAVE BEEN CALIBRATED WITH BACKGROUND
GAS PRESENT. PURGE WITH CLEAN AIR AND RE-CALIBRATE.
RETURN TO FACTORY.
CALIBRATING THE SENSOR WILL CLEAR THE FAULT.
THE “CHANGE SENSOR TYPE” COMMAND CAN BE SENT FROM THE UD10 IF THE SENSOR IS
PRE-CALIBRATED
REPLACE LAMP IF POSSIBLE. RETURN TO FACTORY.
CHECK ALIGNMENT.
LOCATE AND REMOVE OBSTRUCTION FROM THE OPTICAL PATH.
ENSURE THAT THE CAL LINE WIRING IS NOT SHORTED AND THE SWITCH IS OPEN.
CHECK SENSOR WIRING. CALIBRATE SENSOR.
ENSURE THAT SENSOR TYPE MATCHES CONFIGURATION.
CHECK ALIGNMENT OF THE DETECTOR.
CHECK ALIGNMENT OF THE DETECTOR.
2.2
STATUS
ALIGN FAULT
ALIGN WARNING
DAC FAULT
HIGH FAULT
LOW FAULT
WARM UP FAULT
REF. CHANNEL FAULT
ACTIV E CHANNEL FAULT
INCOMPATIBLE VERSION
DETECTION DISABLED
Oi FAULT
DIMINISHED DETECTION
FAULT
COMMUNICATION FAULT
GENERAL FAULT
DESCRIPTION
ALIG NMENT FAULT.
ALIGNMENT WARNING.
DAC FAULT DETECTED
DETECTOR OUTPUT IS HIGHER THAN SPECIFIED
LIMIT.
DETECTOR OUTPUT IS LOWER THAN SPECIFIED
LIMIT.
DEVICE IS WARMING UP.
ERROR IN THE REFERENCE CHANNEL.
ERROR IN THE ACTIVE CHANNEL
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
A FAULT OF ANY TYPE HAS OCCURED
RECOMMENDED ACTION
CHECK ALIGNMENT.
CHECK ALIGNMENT.
RETURN TO FACTORY.
CHECK SENSOR WIRING FOR SHORTS AND VERIFY CORRECT SENSOR TYPE AND CALIBRATION.
CHECK SENSOR WIRING FOR OPENS AND CORRECT SENSORY TYPE AND CALIBRATION.
WAIT FOR WARM UP TO COMPLETE.
RETURN TO FACTORY.
AN ACTIVE CHANNEL FAULT WOULD INDICATE AN ERROR IN THE ACTIVE CHANNEL.
MOST LIKELY WILL REQURE FACTORY SERVICE.
N/A
N/A
N/A
N/A
N/A
REFERENCE THE SPECIFIC FAULT FOR RECOMMENDED ACTION
NOTE
1
: ALL INFORMATION DISPLAYED
ON THIS SCREEN IS READ ONLY.
NOTE
2
: EACH DETECTOR TYPE UTILIZES A SET OF DEVICE
SPECIFIC STATUS BITS THAT DETERMINE WHICH
INDICATORS BECOME ACTIVE DURING AN ALARM OR FAULT.
NOTE 3 : INDICATORS THAT ARE LABELED
“RSVD,” ARE NOT USED.
Figure 25—Device Fault Indcators Defined (GT3000 Shown)
11 95-8645
SYSTEM SETUP
NOTE
Det-Tronics reserves the right to apply a service charge for repairing returned product damaged as a result of improper packaging.
Clicking the System Setup button will open the System
Setup window (shown below) where current settings can be viewed. It is also useful for troubleshooting the cause of any communication problem that might occur between the FlexVu UD10 and the PC.
Return all equipment transportation prepaid to the factory in Minneapolis.
NOTE
This System Setup window also appears each time Gas Inspector Monitor is opened (see
Figure 11 in the “Startup” section).
ORDERING INFORMATION
When ordering, please specify:
Part Number Description
010204-001 W6300G1003, Gas Inspector
Connector (includes Gas Inspector
Monitor Software CD)
System Setup Window
010268-001 Gas Inspector Monitor Software CD
For assistance in ordering a system to fit your application, please contact:
Detector Electronics Corporation
6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.det-tronics.com
E-mail: [email protected]
REPLACEMENT PARTS
The Inspector Connector is not designed to be repaired in the field. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair.
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure.
Pack the unit properly. Always use sufficient packing material in addition to an antistatic bag as protection from electrostatic discharge.
Environmental Protection
Waste electrical products should not be disposed of with industrial and commercial waste. Please recycle where facilities exist. Check with your Local Authority or the local Detector Electronics office for recycling advice.
Specifications subject to change without notice.
All trademarks are the property of their respective owners.
© 2020 Detector Electronics Corporation. All rights reserved.
Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.
Corporate Office
6901 West 110 th
Street
Minneapolis, MN 55438 USA www.det-tronics.com
Phone: +1 952.941.6665
Toll-free: +1 800.765.3473
Fax: 952.829.8750
95-8645
advertisement
Related manuals
advertisement