Det-Tronics Gas Inspector Software Instructions

Add to My manuals
12 Pages

advertisement

Det-Tronics Gas Inspector Software Instructions | Manualzz

INSTRUCTIONS

Gas Inspector Monitor Software for use with Det-Tronics

FlexVu

®

Universal Display

Model UD10

IMPORTANT

All firmware versions of the FlexVu® UD10 are compatible with the latest Gas Inspector Monitor

(1.6.xx). To take full advantage of the latest Gas

Inspector Monitor features, the FlexVu UD10 firmware must be 2.80 or higher. The firmware version is located in the Systems Setup window

(see Figure 11).

DESCRIPTION

The FlexVu ® Universal Display Model UD10 is designed and approved as a ‘stand alone’ device, while also performing all the functions of a gas controller. When the

FlexVu UD10 is used in combination with a compatible

Detector Electronics Corporation (Det-Tronics) gas sensor/detector, it is able to record important information

(alarms, faults, and calibrations) from the sensor/detector.

The information is date and time stamped, and stored in the electronics module of the FlexVu UD10. Gas

Inspector Monitor allows the user to later upload the stored information to a Personal Computer (PC), where it can be displayed, saved, or printed.

FEATURES

HARDWARE REQUIREMENTS

Gas Inspector Monitor software can operate on most

Intel ® based computers running Microsoft ® Windows

XP or Windows 7. When installing Gas Inspector Monitor in Windows 7, ensure that the PC is a 32-bit version.

Currently, 64-bit computers running Windows 7 are incompatible with Gas Inspector Monitor.

A minimum of 16 megabytes of RAM is required, however,

32 or more megabytes are recommended for optimum performance. The software also requires a color monitor with a minimum resolution of 640 by 480, and a hard drive with at least 10 megabytes of free space.

• Data logs available for Det-Tronics sensors/detectors

(see Table 1)

• Displays real time fault/alarm indicators

• Stored data can be uploaded to a PC

• Logs can be viewed, stored to a file, or printed.

INSTALLATION

SOFTWARE

CAUTION

The PC must always be located in a non-hazardous controlled location.

Table 1—Data Logging Capabilities

GT3000

PIR9400

PIRECL

OPECL

NTMOS

C706X

CGS

Calibration Log Storage

UD10

X

X

X

X

X

X

X

SENSOR/DETECTOR

X

X

X

NOTE: All event logs are stored in the UD10.

NOTE

It is recommended that the installation of the USB and RS-485 drivers be completed before installing the Gas Inspector Monitor software.

NOTE

The following procedures are for Windows XP. If using Windows 7, note that the dialog windows may appear different from the examples shown.

2.2 © 2020 Detector Electronics Corporation Rev: 1/13 95-8645

WARNING

Do not open the FlexVu UD10 assembly in a hazardous area when power is applied.

Driver Software

The first installation setup is for the USB driver followed automatically by the installation of the RS-485 driver.

Follow these steps to install the driver software:

1. Apply power to the FlexVu UD10. Allow it to warm up and reach a normal operating mode.

2. Insert the driver installation CD.

3. Connect the RS-485 to the FlexVu UD10’s Modbus terminal, then connect the converter to a USB port on the PC (Figure 1).

CONNECT THIS END TO

THE PC USB PORT

5. On the following window, select “Install the software automatically (Recommended),” then click Next

(Figure 3).

Figure 3—Recommended Driver Installation

A2497

CONNECT THIS END TO

THE FLEXVU UD10

RS485 PORT (J2)

Figure 1—Gas Inspector Connector with RS-485 to USB Converter

NOTE

The Gas Inspector Connector includes a universal power supply that can plug into any standard

120/240 Vac outlet.

4. The Found New Hardware Wizard will appear. Select

“No, not this time,” then click Next (Figure 2).

6. Installation will begin when the Hardware Installation window appears. Click Continue Anyway to proceed with the installation (Figure 4).

Figure 4—Hardware Installation Window

2.2

Figure 2—Found New Hardware Wizard

2 95-8645

7. When installation is complete, a confirmation window will appear (Figure 5). Click Finish to complete this stage of the installation.

3. Choose a destination (Figure  7) for installing Gas

Inspector Monitor, then click Next to continue.

Figure 7—Install Destination

4. A confirmation window will appear to verify that the installation should begin. Click Next to confirm

(Figure 8).

Figure 5—Completed Driver Installation

8. The installation process for the RS-485 driver will begin automatically. Follow the instructions from

Step 4 to complete the installation for the RS-485.

Gas Inspector Monitor Software

NOTE

It is strongly recommended that all running programs in Windows be closed before installing the Gas Inspector Monitor software.

NOTE

Uninstall all previous versions of Gas Inspector

Monitor and restart the computer before proceeding to Step 1.

1. Insert the Gas Inspector Monitor software CD

(p/n 010268-001).

2. Click Next on the Welcome window (Figure 6).

Figure 8—Conirm Installation

5. When the installation is complete, a confirmation window will appear (Figure  9). Click Close to end the installation process.

2.2

Figure 6—Welcome Window

3

Figure 9—Installation Complete Window

95-8645

Active X Software

At the initial startup of Gas Inspector Monitor, some users may be alerted to install Active X (Figure 10). This installation is performed only once and is required for

Gas Inspector Monitor to function correctly. If the alert for Active X does not appear, proceed to the “Startup” section.

4. Click the large button to continue (Figure 10C).

Figure 10C—Installation Location Window

Figure 10—Install Active X Alert

Use the following procedure to install Active X:

1. Click on the “setuppad” installer, located on the Gas

Inspector Monitor software CD.

2. Click Yes to accept the End User Agreement

(Figure 10A).

5. Click Continue on the Program Group window to continue the installation (Figure 10D).

Figure 10A—End User Agreement Window

3. Click Continue on the Welcome window (Figure 10B).

Figure 10D—Program Group Window

6. Click OK on the next window to exit the installer (Figure 10E).

Figure 10E—Exit Installer Window

Figure 10B—Welcome Window

2.2

4 95-8645

STARTUP

NOTE

Communication between the FlexVu UD10 module and the PC uses the Modbus RTU protocol, with the FlexVu UD10 module configured as a Modbus slave.

WARNING

Do not open the FlexVu UD10 assembly in a hazardous area when power is applied.

1. With the FlexVu UD10 in a normal operating mode, open Gas Inspector Monitor. The System Setup window will open with the recommended Modbus

Settings of 9600 baud rate, no parity, and a polling address of 1 (Figure 11).

Figure 12—Computer Management Window

3. Click Find Device to create a connection between the FlexVu UD10 and the PC. A dialog box will appear above the System Setup window to confirm the connection (Figure  13). Click OK , then click

Proceed to continue.

Figure 11—System Setup with Default Settings

2. Verify that the appropriate PC Comm port is selected by looking in the Windows Device Manager for the correct setting. This is accomplished by right-clicking on My Computer (from the Start Menu), then select

“Manage.” When the Computer Management window appears, select Device Manager (Figure  12) and expand the menu tree for Ports (COM & LPT). Make sure the RS-485 Port is using the same Comm Port shown in the System Setup window (Figure 11).

Figure 13—Device Connected Dialog Box

NOTE

In cases where the FlexVu UD10 cannot be found (Figure 14) after selecting “Find Device,” the settings entered in the System Setup are incorrect or the USB converter is faulty. Uninstall and reinstall the drivers to resolve this problem.

2.2

5

Figure 14—Device Not Connected Dialog Box

95-8645

UNINSTALLING DRIVERS

1. To uninstall drivers, right-click on My Computer and select “Manage” to open the Computer Management window. Select “Device Manager ” (Figure 12).

2. Expand the “Universal Serial Bus controllers” tree, and the USB converter will be listed by model number. Right-click on the appropriate model and choose “Uninstall.”

3. Click OK to confirm removal of the drive. The same steps can be used to uninstall the RS-485 driver.

TOOLS MENU

After the user completes all the required installations, Gas

Inspector Monitor is ready to monitor information stored in the FlexVu UD10. The monitoring tools accessible to the user are Logs, Status, and System Setup.

Event Logs

Event logs are listed by Event (number), Date, Time,

Description, and Event ID. Each Event ID number is related to a specific Description (e.g. POWER UP, LOW

ALARM ON, etc.). Normal status is highlighted in green, faults in yellow, and alarm events are red (Figure 20).

Calibration Logs

Calibration logs are listed by Event (number), Date, Time,

Description, Event ID, Cal Zero, and Cal Span. Each

Event ID number is related to a specific Description (e.g.

ZERO CAL, SPAN CAL, etc.). The values under the Cal

Zero and Cal Span columns represent the “Raw Sensor

A-to-D (Analog-to-Digital) Counts.” Normal calibration status is highlighted in green, calibration faults in yellow, and failed calibrations are red (Figure 21).

SORT ORDER

By default, logs are sorted by most recent date and time.

Logs can also be sorted by description (alphabetically), by double-clicking on the Description column header.

LOGS

This option opens the Logs window, where the user can select between Event Logs or Calibration Logs. Choose the log type to be retrieved by selecting from the dropdown menu, labeled “Log Type” (Figure  15). Storing and retrieving of event logs are performed by the FlexVu

UD10, for all sensor/detector types. Depending on the sensor/detector logging capabilities, calibration logs are stored in the sensor/detector or in the FlexVu UD10,

(Table 1). All Event and Calibration Logs are dated and time stamped.

SAVING FILES

To save a file for use in a spreadsheet, such as Excel, click the Export to File button (Figure 17).

Figure 17—Export to File

ADDITIONAL BUTTONS

The Stop button (Figure  18) will immediately suspend the retrieval of an event log or calibration log. Click the

Retrieve Logs button to begin a new retrieval.

Figure 15—Log Type Selection

To begin retrieving logs, click the Retrieve Logs button

(Figure 16).

Figure 18—Stop

Figure 16—Retrieve Logs

All data is stored in non-volatile memory, which can accommodate approximately 1000 events. When the maximum is exceeded, the oldest events are automatically overwritten to make room for the newest events.

The Close button (Figure  19) exits the Logs window, allowing other user accessible tools to be selected.

Figure 19—Close

2.2

6 95-8645

Figure 20—Example of Event Logs

2.2

Figure 21—Example of Calibration Logs

7 95-8645

STATUS

Click the Status button to view the current status of the

FlexVu UD10 and the connected device. By default, the status window displays the FlexVu UD10 information only. Select the Device tab to view information about the connected device.

The Fault/Status window displays various status and fault information about the FlexVu UD10 and the device connected to it. Note that all information in this window is read only. The FlexVu UD10 and the connected device each have their own distinct Fault/Status windows

(Figures 22-25).

GAS LEVEL= THE CURRENT GAS LEVEL READ BY THE UD10.

TEMPERATURE= CURRENT OPERATING TEMPERATURE OF THE UD10.

mA= THE CURRENT MILLIAMP LEVEL OF THE DEVICE

CONNECTED TO THE UD10.

EXIT= RETURN TO PREVIOUS SCREEN (TOOLS MENU).

UD10 and CONNECTED DEVICE TABS

STATUS

ANY FAULT

WARM UP

LOW RELAY ACTIVE

HIGH RELAY ACTIVE

AUXILIARY ACTIVE

OUTPUT CURRENT FIXED

MODBUS WRITE ENABLED

HART SELF TEST

RESPONSE TEST

MANUAL SELF TEST

INPUT HART

DESCRIPTION

GENERAL FAULT INDICATION.

UD10 IS IN THE POWER-UP MODE.

LOW ALARM IS ACTIVE.

HIGH ALARM IS ACTIVE.

AUXILIARY ALARM IS ACTIVE.

CURRENT IS FIXED FOR TESTING THE 4-20 LOOP.

THERE IS ACCESS TO THE FACTORY CONFIGURATION VARIABLES

IN THE UD10.

HART INITIATED SELF TEST IS IN PROCESS.

4-20 IS LOCKED AT 4.0 mA FOR TESTING THE DISPLAY

MANUAL SELF TEST IS IN PROCESS.

THERE IS NO COMMUNICATION BETWEEN THE UD10 AND THE

CONNECTED HART BASED DETECTOR.

NOTE 1 : ALL INFORMATION DISPLAYED

ON THIS SCREEN IS READ ONLY.

NOTE 2 : INDICATORS THAT ARE LABELED

“RSVD,” ARE NOT USED.

Figure 22—FlexVu UD10 Status Indicators Defined

2.2

8 95-8645

2.2

FAULT CONDITION

EE FAULT

ADC FAULT

24 VOLT FAULT

FLASH FAULT

RAM FAULT

WDT FAULT

12 VOLT FAULT

5 VOLT FAULT

3 VOLT FAULT

OUTPUT LOOP FAULT

INPUT LOOP FAULT

DESCRIPTION

FAULT IN NON-VOLATILE CONFIGURATION MEMORY.

ADC REFERENCE VOLTAGE TOO HIGH OR LOW.

PROBLEM IN THE 24 VOLT POWER SUPPLY OR POWER WIRING.

FAULT IN VOLATILE MEMORY.

FAULT IN VOLATILE MEMORY.

WATCHDOG TIMER IS NON-FUNCTIONAL.

12 VOLT INTERNAL POWER SUPPLY OUT OF TOLERANCE.

5 VOLT INTERNAL POWER SUPPLY OUT OF TOLERANCE.

3 VOLT INTERNAL POWER SUPPLY OUT OF TOLERANCE.

FAULT IN 4-20 mA OUTPUT LOOP.

FAULT IN SENSOR OR SENSOR LOOP.

RECOMMENDED ACTION

RETURN TO FACTORY.

RETURN TO FACTORY.

CHECK POWER SOURCE.

RETURN TO FACTORY.

RETURN TO FACTORY.

RETURN TO FACTORY.

RETURN TO FACTORY.

RETURN TO FACTORY.

RETURN TO FACTORY.

RETURN TO FACTORY.

CHECK 4-20 mA LOOP WIRING FOR SHORTS OR OPENS.

CHECK SENSOR WIRING.

CALIBRATE SENSOR.

ENSURE THAT SENSOR TYPE MATCHES CONFIGURATION.

NOTE

1

: ALL INFORMATION DISPLAYED

ON THIS SCREEN IS READ ONLY.

NOTE

2

: INDICATORS THAT ARE LABELED

“RSVD,” ARE NOT USED.

Figure 23—FlexVu UD10 Fault Indicators Defined

9 95-8645

STATUS

WRITE PROTECT

RESPONSE TEST

4-20 FIXED

SENSOR REMOVED

SENSOR END OF LIFE (CGS ONLY)

LOOP TEST ACTIVE

TDSA ALARM

QUICK ALARM

DESCRIPTION

THE DEVICE IS IN THE WRITE PROTECT MODE.

4-20 IS LOCKED AT 4.0 mA FOR TESTING THE DEVICE.

OUTPUT CURRENT IS FIXED FOR TESTING 4-20 LOOP.

SENSOR MODULE IS MISSING OR DEFECTIVE.

SENSOR NEEDS REPLACEMENT.

4-20 LOOP IS IN PROCESS.

NOT USED.

NOT USED.

2.2

STATUS

CALIBRATION ACTIVE

WARM UP MODE

LOW ALARM

AUXILIARY ALARM

HIGH ALARM

HART SELF TEST

CONFIGURATION CHANGE

ALIGNMENT MODE

DESCRIPTION

CALIBRATION IS IN PROCESS.

DEVICE IS IN POWER-UP MODE.

A LOW ALARM CONDITION HAS BEEN DETECTED.

AN AUXILIARY ALARM CONDITION HAS BEEN DETECTED.

A HIGH ALARM CONDITION HAS BEEN DETECTED.

HART INITIATED SELF TEST IS IN PROCESS.

A CHANGE HAS BEEN MADE TO A CRITICAL DEVICE

PARAMETER.

DEVICE IS IN A SPECIAL ALIGNMENT MODE (FOR OPECL).

NOTE 1 : ALL INFORMATION DISPLAYED

ON THIS SCREEN IS READ ONLY.

NOTE 2 : EACH DETECTOR TYPE UTILIZES A SET OF DEVICE

SPECIFIC STATUS BITS THAT DETERMINE WHICH

INDICATORS BECOME ACTIVE DURING AN ALARM OR FAULT.

Figure 24—Device Status IndIcators Defined (GT3000 Shown)

10 95-8645

STATUS

LOOP FAULT

SUPPLY VOLTAGE FAULT

CALIBRATION FAULT

MEMO RY FAULT

ADC FAULT

INTERNAL VOLTAGE FAULT

ZERO DRIFT

TEMP. SENSOR FAULT

WRONG SENSOR TYPE

LAMP FAULT

ALIGNMENT FAULT

BLOCKED OPTIC FAULT

CAL LINE ACTIVE

SENSOR FAULT

NOISE FAULT

ALIGN ADC SAT

24

DESCRIPTION

CURRENT LOOP BELOW FAULT THRESHOLD.

VOLT POWER SUPPLY VOLTAGE TOO LOW OR

TOO HIGH.

UNSUCCESSUL CALIBRATION

SELF-DETECTED MEMORY FAULT.

SELF-DETECTED ADC FAULT.

SELF-DETECTED VOLTAGE FAULT.

SENSOR SIGNAL HAS DRIFTED NEGATIVE.

TEMPERATURE SENSOR IS OUT OF RANGE.

NEW OR DIFFERENT SENSOR TYPE IS INSTALLED.

OPEN OR SHORTED LAMP.

ALIGNMENT PROBLEM.

OPTICAL PATH IS BLOCKED.

CAL LINE IS ACTIVE AT START-UP.

SELF-DETECTED FAULT WITH THE SENSOR.

EXCESSIVE NOISE ON SIGNAL.

ALIGNMENT ADC SATURATED.

RECOMMENDED ACTION

CHECK 4-20 mA LOOP WIRING FOR SHORTS OR OPENS.

VERIFY PROPER WIRING TO THE DEVICE AND CORRECT VOLTAGE LEVEL AT THE DISPLAY AND DETECTOR.

THIS FAULT CAN BE CAUSED IF THE CALIBRATION IS ALLOWED TO TIME OUT. IF SO, RE-CALIBRATE.

ENSURE THAT THERE IS ENOUGH GAS IN THE CALIBRATION BOTTLE TO COMPLETE THE CALIBRATION.

ENSURE THAT THE GAS BEING USED FOR CALIBRATION IS THE CORRECT TYPE AND CONCENTRATION.

IT MUST MATCH THE CONFIGURED SETTING.

RETURN TO FACTORY.

RETURN TO FACTORY.

CHECK SUPPLY VOLTAGE. RETURN TO FACTORY.

THIS DEVICE MAY HAVE BEEN CALIBRATED WITH BACKGROUND

GAS PRESENT. PURGE WITH CLEAN AIR AND RE-CALIBRATE.

RETURN TO FACTORY.

CALIBRATING THE SENSOR WILL CLEAR THE FAULT.

THE “CHANGE SENSOR TYPE” COMMAND CAN BE SENT FROM THE UD10 IF THE SENSOR IS

PRE-CALIBRATED

REPLACE LAMP IF POSSIBLE. RETURN TO FACTORY.

CHECK ALIGNMENT.

LOCATE AND REMOVE OBSTRUCTION FROM THE OPTICAL PATH.

ENSURE THAT THE CAL LINE WIRING IS NOT SHORTED AND THE SWITCH IS OPEN.

CHECK SENSOR WIRING. CALIBRATE SENSOR.

ENSURE THAT SENSOR TYPE MATCHES CONFIGURATION.

CHECK ALIGNMENT OF THE DETECTOR.

CHECK ALIGNMENT OF THE DETECTOR.

2.2

STATUS

ALIGN FAULT

ALIGN WARNING

DAC FAULT

HIGH FAULT

LOW FAULT

WARM UP FAULT

REF. CHANNEL FAULT

ACTIV E CHANNEL FAULT

INCOMPATIBLE VERSION

DETECTION DISABLED

Oi FAULT

DIMINISHED DETECTION

FAULT

COMMUNICATION FAULT

GENERAL FAULT

DESCRIPTION

ALIG NMENT FAULT.

ALIGNMENT WARNING.

DAC FAULT DETECTED

DETECTOR OUTPUT IS HIGHER THAN SPECIFIED

LIMIT.

DETECTOR OUTPUT IS LOWER THAN SPECIFIED

LIMIT.

DEVICE IS WARMING UP.

ERROR IN THE REFERENCE CHANNEL.

ERROR IN THE ACTIVE CHANNEL

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

A FAULT OF ANY TYPE HAS OCCURED

RECOMMENDED ACTION

CHECK ALIGNMENT.

CHECK ALIGNMENT.

RETURN TO FACTORY.

CHECK SENSOR WIRING FOR SHORTS AND VERIFY CORRECT SENSOR TYPE AND CALIBRATION.

CHECK SENSOR WIRING FOR OPENS AND CORRECT SENSORY TYPE AND CALIBRATION.

WAIT FOR WARM UP TO COMPLETE.

RETURN TO FACTORY.

AN ACTIVE CHANNEL FAULT WOULD INDICATE AN ERROR IN THE ACTIVE CHANNEL.

MOST LIKELY WILL REQURE FACTORY SERVICE.

N/A

N/A

N/A

N/A

N/A

REFERENCE THE SPECIFIC FAULT FOR RECOMMENDED ACTION

NOTE

1

: ALL INFORMATION DISPLAYED

ON THIS SCREEN IS READ ONLY.

NOTE

2

: EACH DETECTOR TYPE UTILIZES A SET OF DEVICE

SPECIFIC STATUS BITS THAT DETERMINE WHICH

INDICATORS BECOME ACTIVE DURING AN ALARM OR FAULT.

NOTE 3 : INDICATORS THAT ARE LABELED

“RSVD,” ARE NOT USED.

Figure 25—Device Fault Indcators Defined (GT3000 Shown)

11 95-8645

SYSTEM SETUP

NOTE

Det-Tronics reserves the right to apply a service charge for repairing returned product damaged as a result of improper packaging.

Clicking the System Setup button will open the System

Setup window (shown below) where current settings can be viewed. It is also useful for troubleshooting the cause of any communication problem that might occur between the FlexVu UD10 and the PC.

Return all equipment transportation prepaid to the factory in Minneapolis.

NOTE

This System Setup window also appears each time Gas Inspector Monitor is opened (see

Figure 11 in the “Startup” section).

ORDERING INFORMATION

When ordering, please specify:

Part Number Description

010204-001 W6300G1003, Gas Inspector

Connector (includes Gas Inspector

Monitor Software CD)

System Setup Window

010268-001 Gas Inspector Monitor Software CD

For assistance in ordering a system to fit your application, please contact:

Detector Electronics Corporation

6901 West 110th Street

Minneapolis, Minnesota 55438 USA

Operator: (952) 941-5665 or (800) 765-FIRE

Customer Service: (952) 946-6491

Fax: (952) 829-8750

Web site: www.det-tronics.com

E-mail: [email protected]

REPLACEMENT PARTS

The Inspector Connector is not designed to be repaired in the field. If it is determined that the problem is caused by an electronic defect, the device must be returned to the factory for repair.

Prior to returning devices, contact the nearest local

Detector Electronics office so that a Return Material

Identification (RMI) number can be assigned. A written statement describing the malfunction must accompany the returned device or component to assist and expedite finding the root cause of the failure.

Pack the unit properly. Always use sufficient packing material in addition to an antistatic bag as protection from electrostatic discharge.

Environmental Protection

Waste electrical products should not be disposed of with industrial and commercial waste. Please recycle where facilities exist. Check with your Local Authority or the local Detector Electronics office for recycling advice.

Specifications subject to change without notice.

All trademarks are the property of their respective owners.

© 2020 Detector Electronics Corporation. All rights reserved.

Det-Tronics manufacturing system is certified to ISO 9001— the world’s most recognized quality management standard.

Corporate Office

6901 West 110 th

Street

Minneapolis, MN 55438 USA www.det-tronics.com

Phone: +1 952.941.6665

Toll-free: +1 800.765.3473

Fax: 952.829.8750

[email protected]

95-8645

advertisement

Related manuals

advertisement