INSTALLATION MANUAL
Z-FLOWCOMPUTER
/
Z-FLOWCOMPUTER-B
Computer for the calculation of flow and energy of liquids, gases and steam
CONTENTS:
PRELIMINARY WARNINGS .............. 2
PRELIMINARY USE
INSTRUCTIONS ................................. 2
GENERAL FEATURES ....................... 2
TECHNICAL SPECIFICTIONS ........... 2
INSTALLATION RULES ..................... 4
ELECTRICAL CONNECTIONS .......... 5
SIGNALS VIA LED ON FRONT
PANEL Errore. Il segnalibro non è definito.
ACCESSORIES .................................. 7
FRONT PANEL / MODULE LAYOUT . 8
DECOMMISSIONING AND
DISPOSAL .......................................... 8
Manufacturer
Seneca srl
Registered office: Via Austria 26
35127 – Z.I. - Padua – I
Tel. +39.049.8705355 - 8705355
Fax +39 049.8706287
Website
Mail Technical support: www.seneca.it
Product information: [email protected]
This document is the property of SENECA srl. Unauthorized duplication and reproduction is strictly forbidden. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.
MI003722E ENGLISH 1/8
PRELIMINARY WARNINGS
The full content of this manual must be read before performing any operation. The module must only be used by qualified electricians. Specific documentation is available from: www.seneca.it/products/z-flowcomputer
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during all operations.
The warranty is null and void in the event the module or devices supplied by the
Manufacturer, necessary for its correct operation, are improperly used or tampered with and, in any case, if the instructions contained in this manual were not followed.
PRELIMINARY USE INSTRUCTIONS
Obstructing ventilation slots with any object is prohibited.
Installing the module next to devices that generate heat is prohibited.
GENERAL FEATURES
Computer for the calculation of flow and energy of liquids, gases and steam
Calculation rules: IAPWS IF-97, AGA8 GROSS METHOD, AGA8-92DC (ISO 12213-2),
SGERG88 (ISO 12213-3), Redlich-Kwong (RK) and Redlich-Kwong-Soave (RKS) equations .
CPU ARM 32 bit
Ethernet 10-100Mbps port
Side micro USB port, No. 1 RS485 terminal port
Slot for micro SD card, 32 Gb max.
1500 V power insulation compared with the remaining low voltage circuits.
Module dockable to IEC EN 60715 omega-shaped guide. Pull-out terminals, section 2.5mm
2
Rechargeable backup batteries for internal UPS.
Insulation
1500 V
TECHNICAL SPECIFICTIONS
Standards
The instrument complies with the following standards:
EN61000-6-4 (electromagnetic emission, industrial environment)
EN61000-6-2 (electromagnetic immunity, industrial environment)
EN61010-1 (safety).
SUPPLEMENTARY NOTES ON USE:
A 1 A, delayed fuse must be installed in series on the power connection, near the module.
MI003722E ENGLISH 2/8
RS485 terminal: 10, 11, 12
Ethernet
Communication ports
Baud rate 115200 baud max
Fast Ethernet 10/100 Mbps
Communication port: front with RJ45 connector
Connection maximum distance 100m
Plug-in: Micro USB Side USB
Digital input (pulsed Q flow measurement)
Input type: PNP / Absorbed current: 3mA
Voltage and internal power supply: 12V / 20mA / Maximum frequency: 250 Hz.
Analogue inputs 1 and 2 Voltage/Current
(A1 Q flow measurement, A2 Pressure P measurement / Temperature T)
Number of channels: 2 / Input type: configurable mA or V / Resolution: 16 bit
Voltage input: 0 – 30 V / precision 0.1% of Full Scale
Current input: 0 – 20 mA / precision 0.1% of Full Scale / Input protection: 30 V / 25 mA / Max voltage drop: 1.2 V
Universal analogue input 3
(Temperature measurement T)
Type: V / mA 2 wires passive / mA 4 wires active / RTD 2 wires / RTD 3 wires / RTD 4 wires
Resolution: 15 bit / Sampling: 20ms (50Hz rejection)
INPUT TYPE: voltage 0 – 10 V / Input impedance: 120kΩ current: 0 – 20 mA / Input protection: 30 V / 25 mA / Max voltage drop: 1.2 V resistance thermometer (RTD): PT100 / 500 / 1000 / NI100 connection with 2 / 3 / 4 wires with burnout detection.
Analogue output
Type: configurable V – mA / Resolution: 14 bit / Width-limited signal.
Voltage output: 0 – 10 V (minimum load resistance = 1kΩ),
Current output (active / passive):0 – 20 mA (maximum load resistance 600Ω),
Precision: 0.1% / Thermal stability: 0.01%/°K / Linearity error: 0.01% / EMI < 1%.
Digital outputs
Number of channels: 2 / Type: SPDT free contact relay / Voltage: 30 V / 30 V / Current: 2 A.
Voltage
Absorption
Internal batteries
Power supply
10 – 40 V ; 19 – 28 V 50 – 60 Hz
Max.: 5 W @ 24V
2xAAA NiMH
Temperature
Humidity
Altitude
Storage temperature
Environmental conditions
-10 – +40°C (limit with UPS recharge battery)
-10 – +50°C (limit without UPS recharge battery)
30 – 90% to 40°C non condensing up to 2000 m above sea level
-20 – +45°C (< 6 months)
Protection rating IP20
Connections
3-way removable screw terminals, pitch 5 mm
RJ45 and micro USB
Micro SD card slot
Dimensions/Weight
Case
Overall dimensions / Case
L: 100 mm; H: 112 mm; W: 52.5 mm / 315 gr.
PA6, black
MI003722E ENGLISH 3/8
INSTALLATION RULES
The module has been designed for vertical installation on an IEC EN 60715 omega guide. For optimal operation and long working life, adequate ventilation must be provided. Avoid positioning cable ducts or other objects so that they obstruct the ventilation slots. Avoid mounting modules over equipment generating heat. Installation in the bottom part of the distribution board is recommended.
OMEGA IEC EN 60715 guide installation and removal.
Insertion onto the IEC EN 60715 guide:
1) Move the four hooks on the back of the module outwards as illustrated in fig. 1b.
2) Rest the module on the OMEGA guide.
3) To secure the module to the OMEGA guide, tighten the four hooks on the side of the IDC10 rear connector as shown in fig. 1a.
Removal from the IEC EN 60715 guide:
As shown in figure 1b:
1) Move outwards the four hooks on the side of the module, with the help of a screwdriver.
2) Extract the module from the guide.
Installation of the display panel (not present in the Z-FLOWCOMPUTER-B version)
Make a rectangular hole with the following dimensions:
W=119 mm x H=93 mm.
Insert the panel into the hole.
Secure the panel as shown in the figure using all the screws and fixing brackets supplied.
Be careful not to drop the panel while fixing it, so as not to damage it.
MI003722E ENGLISH 4/8
ELECTRICAL CONNECTIONS
Z-FLOWCOMPUTER module power supply
The power supply must be connected to terminals 2 and 3. The supply voltage must be between 10 and 40V (any polarity), or between 19 and 28 V .
The upper limits must not be exceeded in order to avoid serious damage to the module.
The power supply source must be protected from any malfunctions of the module through appropriately sized safety fuse.
Important: On first start-up, the module must be supplied without any interruptions for at least 72 hours to charge the internal batteries.
Z-FLOWCOMPUTER Digital input 1 (pulsed flow measurement)
Digital input 1 can be connected to a Q flow,
V Volume or digital mass/weight sensor with pulse output.
Voltage
Z-FLOWCOMPUTER analog outputs 1 and 2
The Z-FLOWCOMPUTER module has two voltage or current configurables analog inputs.
Input 1 is used for Q flow measurements.
Input 2 is used for P pressure or T1 temperature measurements.
The figures show some sensor connection examples.
Pressure sensor Temperature1 sensor Flow sensor
Current
4 – 20 mA 0 – 10 V 0 – 20 mA
Z-FLOWCOMPUTER universal analog input 3
The Z-FLOWCOMPUTER module has a universal analogue input to be used for temperature measurements T2. The figures show the connection modes and sensor types that can be connected to this input.
Active input means that Z-FLOWCOMPUTER supplies the current loop.
Passive input means that the sensor supplies the current loop.
Transducer Transducer Transducer 4 wires RTC
0 – 10 V 0 – 20 mA passive (2 wires) 4 – 20 mA active (4 wires)
MI003722E ENGLISH 5/8
Input V Input mA active 4 wires
Input mA passive 2 wires
RTD input
2 wires
RTD input
3 wires
RTD input
4 wires
Analog output (V)
Digital output 1
Analog output (mA)
Digital output 2
Configurable output
The Z-FLOWCOMPUTER has an analog output that can be configured for either voltage or current.
The figures show the connections.
Outputs with free contacts
The Z-FLOWCOMPUTER has two digital outputs with free contacts.
The figures show the internal relay contacts available.
Connection of the RS485 port
The RS485 port of the Z-FLOWCOMPUTER can be connected as shown in the figure.
Connection RJ45 ETHERNET - HMI display
(not present in the Z-FLOWCOMPUTER-B version)
The RJ45 ETHERNET cable for the connection of the HMI display panel supplied with the
Z-FLOWCOMPUTER module must be connected as shown in the figure. For further information, refer to the MI003740-I installation manual of the Visual3 display.
MI003722E ENGLISH 6/8
Micro SD card slot
The Z-FLOWCOMPUTER has a micro SD card slot on the side of the case.
Before insert the SD card in the matching slot, make sure the metal contacts are facing right (with reference to the side figure).
NOTA
BENE:
For the Z-FLOWCOMPUTER to working properly the micro SD card must be inserted .
RJ45 Ethernet port (on front)
Z-FLOWCOMPUTER has an Ethernet port with RJ45 connector on the front of the module, for display connection and/or for TCP-IP communications.
For further information, refer to the USER MANUAL.
USB micro port (side)
Z-FLOWCOMPUTER has a serial USB micro port.
This port allows module connection to a computer in order to configure it.
For further information, refer to the USER MANUAL.
LED INDICATIONS ON THE FRONTAL PANEL
LED
PWR/STS Green
SD/STS Red
ETH ACT Yellow
ETH LNK Green
DI1 Red
DI1 Red
DI2 Red
DI2 Red
DI3 Red
DI3 Red
DI4 Red
DI4 Red
DO1 Red
DO1 Red
DO2 Red
DO2 Red
485 ACT Green
STATUS
ON
Flashing
Flashing
Flashing
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Flashing
LED meaning
The device is supplied correctly
Access to micro SD card
Packet transit on Ethernet port
Connection on RJ45 activated
Digital input 1 PNP closed at + 12V
Digital input 1 PNP open
Digital input 1 PNP closed at + 12V
Digital input 2 PNP open
Digital input 3 PNP closed at + 12V
Digital input 3 PNP open
Digital input 4 PNP closed at + 12V
Digital input 4 PNP open
Digital output 1, relay energised
Digital output 1, relay deenergised
Digital output 2, relay energised
Digital output 2, relay deenergised
Reading on internal I/O card
ACCESSORIES
CODE
CS-DB9F-TIP_V
CE-RJ45-RJ45-R
DESCRIPTION
RS485 connection cable
ETHERNET connection cable
MI003722E ENGLISH 7/8
FRONT PANEL / MODULE LAYOUT
MONITOR
SIZE
(not present in the Z-FLOWCOMPUTER-B version)
For the configuration, use the EASY FLOWCOMPUTER software available for download, at: www.seneca.it/products/z-flowcomputer
For further information on the product, refer to the USER MANUAL available for download, at: www.seneca.it/products/z-flowcomputer
DECOMMISSIONING AND DISPOSAL
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or packaging indicates that the product cannot be discarded as domestic waste. It should be taken to an authorised recycling centre for electrical and electronic waste. Ensuring that the product is suitably discarded will avoid potential negative impacts on the environment and human health, that could be caused by non compliant product disposal. Material recycling will contribute to the preservation of natural resources. To receive further information, please contact your local waste disposal service centre or product dealer.
MI003722E ENGLISH 8/8