Grossenbacher Systeme SP-240-05R-000 Device Description
Grossenbacher Systeme SP-240-05R-000 is an embedded industrial automation and building automation device that combines high performance and reliability with a long operating life. With its powerful 400MHz ARM processor, seamless resistive touch-screen, optional WindowsCE or Linux operating system, and extensive connectivity options (including Ethernet, USB, and CAN), the device is suitable for a wide range of applications, including HMI (Human Machine Interface), HMI-Open (user-programmable HMI), and HMI-Control (with integrated Codesys Soft-PLC, TargetVisu, and WebVisu).
Advertisement
Advertisement
DEVICE DESCRIPTION
S mart P anel
Hardware
SP-240
Grossenbacher Systeme AG
Spinnereistrasse 10, CH-9008 St. Gallen
Phone +41 (0)71 243 29 29 / Fax +41 (0)71 243 29 28 [email protected] / www.gesys.ch
DVS 63067-V3.0
Grossenbacher Systeme GmbH
Ruhrstrasse 15, DE-63452 Hanau
Phone +49 (0)6181 6751 999/ Fax +49 (0)6181 6751 998 [email protected]
S mart P anel
Hardware
Copyright
Keep documentation for future use!
This documentation is the intellectual property of
Grossenbacher Systeme AG
, which also has the exclusive copyright. Any modification of the content, duplication or reprinting of this documentation, as well as any distribution to third parties can only be made with the express permission of
Grossenbacher Systeme AG
.
Grossenbacher Systeme AG
does not accept any liability for damages arising from the use of any incorrect or incomplete information contained in this documentation or any information missing therefrom.
Grossenbacher Systeme AG
reserves the right to make complete or partial modifications to this document.
All brand and product names are trademarks or registered trademarks of the owner concerned
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
Proper use
The device must only be used for the applications specified in the device description and only in conjunction with the components recommended by Moeller GmbH.
Warning
Trouble-free and safe operation of the product can only be ensured if the measures relating to proper transport, storage, assembly, installation and careful operation are strictly observed.
The device must not be switched on when it is covered with condensation. When changing its location from cold to warm allow the device to acclimatize to the new conditions before commissioning.
No warranty claims will be recognized for faults arising from the improper handling of the device.
The device should not be used for the implementation of any safety functions relating to the protection of personnel and machinery.
No liability is accepted for claims for damages arising from a failure or functional defect in the device.
All data specified in this document does not represent guaranteed specifications in the legal sense.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
3
S mart P anel
Hardware
Safety instructions for the user
This device description contains the information required for the proper use of the products described therein. Sections 1 to 10 address technically qualified personnel and Section onwards addresses personnel not requiring any technical knowledge.
Qualified personnel in the sense of the safety instructions given in this device description or on the product itself are persons who: as engineering personnel are either familiar with the safety concepts of automation, or as operating personnel, are instructed in the use of automation components and are familiar with the contents of this device description relating to the operation of the device, or as commissioning or service personnel are suitably trained for the repair of automation devices and are authorized to commission circuits and devices/systems in accordance with standard safety engineering principles.
4
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
Contents
1 Explanation of symbols................................................. 7
2 Introduction.................................................................... 9
3 Device Versions ........................................................... 11
3.1
Specification ......................................................................... 11
3.2
Accessories ..........................................................................12
4 Features........................................................................ 13
5 Commissioning............................................................ 15
5.1
Overview of connections ......................................................15
5.2
Connecting the power supply ...............................................15
5.3
Power Fail and UPS .............................................................16
5.4
Fuse .....................................................................................16
5.5
Setup of RTC
.......................................................................16
5.6
Preparing the shield connections .........................................17
5.7
Connecting the Ethernet.......................................................18
5.8
Connecting the USB-Interface..............................................18
5.9
Connection for COM1 serial interface ..................................19
5.10
CAN interface...................................................................19
5.11
Inserting / Removing the Micro-SDCARD™.....................22
5.12
Temperature sensor connector ........................................22
6 Operation...................................................................... 23
6.1
Startup / Shutdown behaviour ..............................................23
7 Mounting instructions ................................................. 23
7.1
General mounting instructions..............................................23
7.2
Mounting in the front panel - General...................................23
7.3
Front panel cutout 3,5“ to 7“ ................................................24
7.4
Mechanical dimensions - Frontside 3,5“ to 7“......................25
8 Notes on the touch-screen.......................................... 29
8.1
Basic touch-screen function .................................................29
9 Backlight, contrast....................................................... 31
9.1
Contrast................................................................................31
9.2
Backlight...............................................................................31
9.3
Diagnostics...........................................................................31
10 Maintenance and repair............................................... 33
11 Technical data.............................................................. 35
12 Disposal........................................................................ 37
13 EU Conformity and Standards.................................... 39
14 Revision history........................................................... 41
15 Alphabetical index ....................................................... 43
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
5
S mart P anel
Hardware
6
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
1 Explanation of symbols
Danger warnings
The following information is for your personal safety and the prevention of damage to the device described or connected devices.
Safety instructions and warnings for the prevention of danger to the life and health of users or service personnel, and for the prevention of damage are highlighted in this document by the following pictograms. “Warning” and
“Information” pictograms are shown in this document.
Warnings indicate the following:
Death, serious injury or substantial material damage may occur if the related safety measures are not implemented.
The individual “Warning” pictograms have the following meaning:
Caution! General!
An instruction to be observed in order to ensure protection against hazards and the safe operation of the device. The specified procedure should be observed.
Caution! Electric shock!
Persons may be exposed to dangerous voltages that occur in electrical systems. There is a danger of electric shock if a live part is touched.
Caution! Observe ESD measures!
Electrostatic discharge may destroy electronic components.
Information pictograms indicate the following:
Important information about the product or the relevant section of the document, requiring the particular attention of the reader.
The “Information” pictogram has the following meaning:
Indicates important and instructional information.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
7
S mart P anel
Hardware
8
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
2 Introduction
The new SmartPanels enhances the openAutomation concept of
Grossenbacher System AG in the range of small and medium applications.
So price and performance can be optimized to the requirements of the application.
Based on a powerful 400MHz ARM processor with WindowsCE or Linux,
3,5“, 4,3“, 5,7“ or 7“ TFT display with LED backlight and touch screen,
Ethernet, USB-Host and CAN on-board, the devices perfectly fits together with the openAutomation software solutions of Grossenbacher Systeme
AG.
In the basic configuration the device can be used as „HMI“ or as a user programmable „HMI-Open“ with Ethernet, USB and CAN onboard.
With CoDeSys IEC-61131 Soft-PLC the device can be used as "HMI-
Control" with Codesys including integrated TargetVisu and WebVisu.
Without moving parts the devices are “at home” in rugged environment!
The seamless resistive touch-screen provides a fast, intuitive and ergonomic operation.
Unique is the mechanical concept with one equal mounting cutout for all devices! So it is possible to change the display size at any time very easy without mechanical changes!
Features:
• 3,5”, 4,3”, 5,7” or 7” TFT
• One mounting cutout for all sizes
• Resistive Touch-screen
• Powerful 400MHz ARM CPU
• WindowsCE or Linux
• Fanless
• Ethernet
• Exchangeable micro SD-Card
• CANopen
• CoDeSys Soft-PLC (Option)
The devices can be installed in control panels or control desks without any problem. The devices are not designed for mobile use.
This device description is a reference for the technical data, installation, terminals, commissioning, operation, and maintenance of all SmartPanel versions.
Additional documentation :
System description WindowsCE
System description CoDeSys Soft-PLC
DVS 49631
DVS 49634
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
9
S mart P anel
Hardware
10
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
3 Device Versions
In this chapter all device versions of the SmartPanels and available accessories are specified.
3.1 S PECIFICATION
General features of all device versions:
Processor:
Memory:
SP-240-03R-000
400MHz
64MB
Mass storage:
Interfaces:
128MB onboard NAND-Flash, MicroSD-Slot
1 x Ethernet
2 x USB Master
RS232/485/422
1 x CAN
Stromversorgung: 24VDC
ARM CPU
Ord.No.: 50 81 862
SmartPanel 3,5” TFT 320x240 64k colours
Resistive-Touchscreen
SP-240-04R-000
SP-240-05R-000
SP-240-07R-000
Ord.No.: 50 81 863
SmartPanel 4,3” TFT 480x272 64k colours
Resistive-Touchscreen
Ord.No.: 50 81 864
SmartPanel 5,7” TFT 640x480 64k colours
Resistive-Touchscreen
Ord.No.: 50 81 865
SmartPanel 7” TFT 800x480 64k colours
Resistive-Touchscreen
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
11
S mart P anel
Hardware
3.2 A CCESSORIES
Runtime-System
Micro-SDCARD
Stecker für
Stromversorgung
Ord.No
: 5055014
RTS HMI CEARM SPi25
WindowsCE6 Professional and EPAM-RTS preinstalled on Onboard Flash
Ord.No
: 5055015
RTS HMI-Control CEARM SPi25 3S
WindowsCE6 Professional, EPAM-RTS and
Codesys-RTS V2.3 preinstalled on Onboard Flash
Ord.No
: 5055030
RTS HMI ThinClient SPi25
WindowsCE6 Professional ThinClient preinstalled on Onboard Flash
Ord.No
: 5055033
RTS HMI-open .NET SPi25
WindowsCE6 Professional, .NET Framework preinstalled on Onboard Flash
Ord.No
: 32 01 381
Micro-SDCARD 1GB, INDUSTRIAL
Ord.No
: 32 01 382
Micro-SDCARD 2GB, INDUSTRIAL
Ord.No
: 12 17 013
3pol Phoenix Contact, MSTB2.5/3-STF-5.08
12
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
Feature
Display
Touch-screen
Realtime clock
Processor
Mass storage
Memory
Retain memory
Exchangeable memory
Interfaces
Power supply
S mart P anel
Hardware
4 Features
Comment
Display Size
Resistive touchscreen
Resolution 12 Bit (0-4096)
Yes Capacitor-backed (ca. 1 week)
ARM9 iMX25
400MHz
Onboard Flash Type 128MB NAND Flash
64MB
256kB
1
kB
Micro-SDCARD
Memorystick
Type Micro SD-Card-Slot or Memorystick (optional via
USB)
COM1
Ethernet 1
USB 1-2 (2.0)
Type
Type
Type
RS232/485/422, max. 115 kBit/s
10 / 100 MBit/s
1.5 / 12 / 480 MBit/s
CAN Type CiA V2.0 Part B; max. 1MBaud; not isolated
Type , NOT isolated
1 Retain data will be saved on power fail to Flash
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
13
S mart P anel
Hardware
14
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
5 Commissioning
5.1 O
VERVIEW OF CONNECTIONS
7
2 6 4 3
8 5
62528-V1.0
1
No . Element
1 Function
2 24VDC power supply
3 COM1
4 CAN
Description
Î Chap. 5.2
Î Chap. 5.9
Î Chap. 5.10
5 2xUSB
6 1xEthernet
Î Chap. 5.8
Î Chap. 5.7
7 Micro-SDCARD-Slot Î Chap. 5.11
8 Temp.sensor connector Î Chap.
5.12
5.2 C
ONNECTING THE POWER SUPPLY
The SmartPanel devices belongs to protection class 3. The system power supply must be provided with a 24VDC SELV voltage ( Î Section 11).
The power supply is NOT isolated. The GND connection is directly connected to the housing potential. The device is protected with a fuse (note disconnection capacity Î Section 11).
A reverse polarity protective device is used to protect the device in the event of reversed poles. Operation, however, is only possible if the connection was made correctly.
Connections for the SmartPanel must comply with specific, local regulations.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
15
S mart P anel
Hardware
The connection must be made as follows:
1. The cross-section of the power supply cable must be at least 0.75 mm² and a maximum of 2.5 mm².
2. A flexible lead or wire can be used for the connection.
3. The current consumption ( Î Section 11) must be taken into account when implementing the power supply.
4. The functional earth is not compulsory for operation. But it can help to avoid disturbance caused by potential differences.
5. The GND connection is directly connected to the housing potential
6. For safety reasons the wires should be fixed together near by the connector
The plug connector (socket connector with screw terminals) is supplied with the device for connection.
Connector assignment
Designation Function
24VDC 0VDC
+24 VDC +24VDC power supply
reserved
0 V 0V power supply
(plug connector: 3pol Phoenix MSTB2.5/3-ST-
5.08, RM 5.08mm, Phönix Ord.Nr 1757022) reserved !
In the event of reverse connection and simultaneous connection of a further 0V connection, e.g. GND connection of the COM1 interface, the fault current flows via this 0V connection. If the housing is not lying well set on the 0V potential, the result can be destruction of the device or of the external components!
For safety reasons the wires should be fixed together near by the connector.
5.3 P
OWER
F
AIL AND
UPS
The device includes a power fail functionality. The power fail mechanism prevents the loss of retain data if a Soft-PLC is used. The retain data are stored on Flash when the PLC is shutting down and are read out again when the PLC starts up. (for details s.a. System description Soft-PLC)
The standard integrated UPS-solution can bridge brownouts up to 5s.
5.4 F USE
The device is protected with a fuse internally. The fuse can not be changed by the user.
5.5 S
ETUP OF
RTC
If the device is powerless for a long time (more than 1 week), it may be necessary to setup the Time and Date again.
16
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
5.6 P REPARING THE SHIELD CONNECTIONS
The preparation of the data and signal cables is an important factor for the electromagnetic compatibility (EMC) of the SmartPanel, both in terms of interference immunity and emission.
The RS232 and CAN interface are connected via D-Subminiature plug connectors in accordance with DIN 41652. Only use metal or metallised connector casings with a cable clamp for strain relief fastened or clamped on the connector. The clamping of the cable shield ensures an optimum contact area and a low impedance connection with the connector casing of the SmartPanel.
The following procedure is recommended for making the low-impedance connection for the cable shield:
1. Strip the cable.
2. Shorten the exposed shield braid by approx. 3 cm.
3. Turn back the braid over the cable sheath.
4. Use a heat shrinkable tubing or rubber grommet to cover the exposed cable sheath with the folded back shield braid so that 5 to 8 mm of exposed cable shield is left at the sheath end and is cleanly covered at the back.
5. Fit the connector
6. The cable is then fastened at the exposed shield braid and the cable sheath below it directly underneath the cable clamp strap of the connector casing.
Metal or metallised connector casing
Shield braid pulled back over the cable sheath
Fastening screws
Metallic connector shroud
Heat shrinkable tubing for covering the shield braid
Strap for cable clamp and contacting of the cable shield with the connector casing
D-subminiature connector
Connection work should be carried out with special care in order to ensure trouble-free operation.
The EMC values stated in the technical data can only be guaranteed if the cables are prepared according to the following specifications.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
17
S mart P anel
Hardware
5.7 C ONNECTING THE E THERNET
The Ethernet-Interface is compatible with standard IEEE 802.3
(10/100BASE-T).
The network connection is implemented via a Cat 5e cable with shield and
RJ45 connectors. The maximum cable length and transfer speed is limited by the cable quality in EIA/TIA 568 TSB-36. Cable lengths up to 100m are possible.
Two diagnosis LEDs are available:
Orange:
Green:
LINK (connection to HUB or to another device)
ACT (sending or receiving)
Cables connected to the Ethernet must be laid separately from the lowvoltage cables.
To ensure disturbance-free operation, it is strongly recommended to use network cables with shield.
Connector assignment
RJ45
Pin No. Signal
connector
1
2
5
6
3
4
Description
LINK
Socket, 8pole
RJ45
7 -
8 -
5.8 C
ONNECTING THE
USB-I
NTERFACE
The USB Interface is compatible to USB-standard Version 2.0
The use of the USB-Interface requires support by the operating system.
Cables connected to the USB must be laid separately from the low-voltage cables.
3
ACT
18
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
1 2 3 4 5
6 7 8 9
5
S mart P anel
Hardware
5.9 C ONNECTION FOR COM1 SERIAL INTERFACE
The serial Interface COM1 is PC-compatible. This interface is not isolated.
The GND connection is implemented directly on the housing potential ( Î
Section 11).
Connector
Pin No. Signal Description
1
6
2
7
RS232/ 485/ 422
8
3
4
TXD/TXB(+)/485-
B(+)
9
5 direct on housing potential
6 -
Connector
9pole
SubD
Cables connected to the serial COM interface must be laid separately from the low-voltage cables.
To ensure disturbance-free operation, it is strongly recommended to use cables with shield.
The COM1 interface can be configured as RS232/485 or 422. In case of
RS485 the configuration for send or receive is done automatically.
Dip-Switch:
5.10 CAN INTERFACE
The communication interface is defined in accordance with the CiA CAN
Specification V2.0 part B. The fully-integrated CAN unit supports the sending and receiving of frames with an 11-bit identifier. The type of configuration selected depends on the software protocol. The baud rate can be selected in a wide range, and only the standard CiA baud rates are implemented.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
19
S mart P anel
Hardware
1 2 3 4 5
Connect or
CAN connector
Pin No.
Sub-D 9 Pole male
Assignme nt
Function
6 7 8 9
6
6
7
8
9
1
2
3
4
5
The CAN interface is NOT isolated.
The max. baud rate is 1MBit/s.
2 CAN
LOW
Negative data signal
3 GND Signal Ground (ground potential)
4 -
5 -
6 GND Signal Ground (ground potential)
7 CAN
HIGH
Positive data signal
8 -
9 CAN_V+ Internally connected with +24VDC; optional power supply via CAN-cable
Case shield
The terminating resistor must be implemented externally, e.g. in the connector, and is not part of the device.
Pin 9 (CAN-V+) is connected with +24VDC internally to provide optional power supply of the device via the CANcable.
A detailed description of the wiring is provided in the
“Codesys Soft-PLC” system description
Wiring instructions
The stations on the bus system are connected via fieldbus lines complying with ISO 11898. The cables must accordingly have the following electrical characteristics:
Parameter Abbreviation Unit Value Value Value Note min.
Impedance Z
Specific resistance
Ω 108 120 132 Measured between two signal lines m Ω receiver module, the differential voltage on the bus cable depends on cable resistance between it and the sender
Cable delay ns/m 5 The mininum delay between to points on the bus is 0. The maximum delay is determined by the bit timing and the delays of the sender and receiver circuits
The figure shows the minimum wiring with shielding between two bus stations with the Sub-D connector as an example. A bus terminating
20
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware resistor (120 Ohm between Pin 2 and Pin 7 of the Sub-D connector) must be connected at the beginning and the end of each CAN bus. Do not swap around the two signal wires!
Interface 1
Shield
Protective ground
Protective ground
Shield Inside: twisted pair cable
Station n bus terminating resistor
Station 1
Pin 3 and 6 (CAN_GND) are both connected internally with the CAN
Ground. Pins 4, 5 and 8 must not be connected! The CAN bus driver is fed internally.
Baud rate and cable lengths
Baud rate Max. length
20kBit/sec 2500m
25kBit/sec 2000m
50kBit/sec 1000m
100kBit/sec 650m
125kBit/sec 500m
250kBit/sec 250m
500kBit/sec 100m
1Mbit/sec 6m
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
21
S mart P anel
Hardware
5.11 I NSERTING / R EMOVING THE M ICRO -SDCARD™
The SmartPanel series devices use a Micor-SDCARD slot for removable mass storage devices.(s.a. accessories)
Micro-SDCARDs may be removed during operation. To avoid data loss it is recommended to use the operating system functionality to replace the removeable devices. (s.a. system description WindowsCE)
5.12 T
EMPERATURE SENSOR CONNECTOR
The Temperature sensor connector can be used to connect a KTY10-6 (= KTY81-210) sensor to measure e.g. the room temperature.
22
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
6 Operation
6.1 S
TARTUP
/ S
HUTDOWN BEHAVIOUR
After power on the SmartPanel boots the installed operating system from the Onboard-Flash.
7 Mounting instructions
7.1 G ENERAL MOUNTING INSTRUCTIONS
All SmartPanel series devices are mounted from the front, i.e. in a control panel. They are fastened from the rear with the supplied 4 securing nuts.
All SmartPanel series devices can be operated up to a maximum ambient temperature of 60°C ( Î Section 11). The ambient temperature stated applies to the area 5cm above the device, if it is mounted vertically with unimpeded air convection and a maximum operating height of 2000m above sea level.
The device can be mounted in an enclosure if the ambient temperature is taken into consideration. Provide a wall clearance of at least 50 mm on all sides of the housing, so that sufficient air circulation is ensured. A minimum clearance of 75 mm from active elements such as load current supply, transformers etc. must be ensured.
Avoid the exposure of the flat screen to direct sunlight. The radiation from the sun (UV component) reduces the lifespan of the LCD display.
The following must be ensured in order to prevent the device from overheating during operation:
- The cooling slots must always be free in order to ensure the proper cooling of the system.
- Avoid the exposure of the flat screen to direct sunlight.
- The mounting angle must not exceed ± 35° from the vertical
If these conditions cannot be met, the mounting of an external fan is recommended.
7.2 M
OUNTING IN THE FRONT PANEL
- G
ENERAL
1. The front seal must be inlayed from the back side. The seal is selfadhesive on one side.
2. Push the SmartPanel from the front into the cutout of the front panel.
3. Secure the device from the rear with the supplied 4 securing nuts which should be tightened evenly from the rear until the front frame is flush with the front panel all round.
Ensure that the seal is fitted correctly on the front panel.
Avoid tightening torques of greater than 0.5 Nm as this could otherwise damage the device.
The thickness of the front panel must not exceed 2.5 mm.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
23
S mart P anel
Hardware
7.3 F RONT PANEL CUTOUT 3,5“ TO 7“
Tolerance for panel cutout +0/-0.5 mm
The thickness of the front panel must not exceed 2.5 mm.
24
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
7.4 M ECHANICAL DIMENSIONS - F RONTSIDE 3,5“ TO 7“
S mart P anel
Hardware
Dimensions – 3,5"
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
25
S mart P anel
Hardware
Dimensions – 4,3" IR
26
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
Dimensions – 5,7“
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
27
S mart P anel
Hardware
Dimensions - 7"
28
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
8 Notes on the touch-screen
8.1 B
ASIC TOUCH
-
SCREEN FUNCTION
Devices with resistive touch-screen
The resistive touch-screen operates on an analog principle. Pressing the touch-screen at any point results in an electrical resistance which is measured and will be calculated into a position by the touch controller. This initiates an operation if a touch activated screen element was touched (e.g. a button).
Because of this function principle the resistive touch-screen has to be calibrated. The first calibration is already done when delivered. A recalibration of the touch-screen is necessary when the touch position is different to the screen, e.g. because of ageing, temperature, etc.
For an optimal operation of the resistive touch-screen it is recommended to use a touch-pen for the calibration.
(s.a. manual system description WindowsCE)
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
29
S mart P anel
Hardware
30
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
9 Backlight, contrast
9.1 C
ONTRAST
The SmartPanel series are delivered with TFT displays. This displays require no contrast settings (only necessary for passive LCD displays).
9.2 B
ACKLIGHT
The backlight can be selected in the application program.
9.3 D IAGNOSTICS
The following optical and acoustic diagnostic options are available:
Symptom Possible cause and solution
Device does not start, screen dark or error
- Check power supply/fuse faulty messages during startup
Date/time incorrect
Touch-screen not functioning
- device was not powered for at least 1 week Æ setup RTC
- Hardware faulty or touch not calibrated
Æ recalibrate touchscreen
Ethernet connection faulty - Incorrect Ethernet cable fitted
(crosslink/direct).
Î The LINK LED is lit when the connection is correct
Î The ACT LED is lit (flashing during transfer) with a correct data transfer
- Incorrect/invalid IP address set
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
31
S mart P anel
Hardware
32
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
10 Maintenance and repair
Cleaning of resistive touch-screen
Do not expose the front of the device to solvents which may corrode and loosen the plastic membrane (material: Polyester). Ensure that the surface is not scratched or scoured, especially when removing hard deposits and abrasive dust.
Cleaning should only be carried out with the device switched off!
This will ensure that any touching of the screen will not accidentally initiate functions.
Please use a soft cloth to ensure that the surface is not scratched or scoured. Do not use solvents.
Repairs
Repairs to the SmartPanels should only be carried out by the manufacturer.
(manufacturer address Î Section 13)
No liability is accepted for any modifications made to the device that are not described in this document.
Transport
Only the original packaging must be used for transporting the device. The climatic conditions ( Î Section 11) has to be observed.
Storage
The device has to be stored under the conditions specified in Section 11.
It is recommended to store the device at room temperature.
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
33
S mart P anel
Hardware
34
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
Display
Operation
Ambient conditions
EMC
Degree of protection
S mart P anel
Hardware
11 Technical data
Technology 3,5“, 4,3“, 5,7“, 7“ TFT LCD
Resolution 3,5“
4,3“
5,7“
7”
Display area 3,5“
4,3“
5,7“
7 “
Backlight
3,5“
4,3“
5,7“
7”
Front plate
QVGA 320 x 240
WQVGA 480 x 272
VGA 640 x 480
WVGA 800 x 480
70 x 53 mm
95 x 53 mm
115 x 86 mm
152 x 91 mm
LED, dimmable via software
40000h, contrast 450:1, brightness 350cd/m2
40000h, contrast 300:1, brightness 350cd/m2
40000h, contrast 350:1, brightness 400cd/m2
40000h, contrast 350:1, brightness: 350cd/m2
Resistive touch-screen: Polyester/glass laminate
Resolution
Resistive touch-screen
Keyboard
Mouse
Operating climate
Storage climate
Transport climate
Vibration
Shock
EMC interference immunity
Emission
Front
Rear
12 Bit analog (0-4096) for all display sizes
Via USB
Class 3K3 EN50178 (advanced/reduced)
0..60°C vertical installation
10...90% rel. air humidity, non-condensing
Class 1K4 EN50178 (reduced)
-20...70°C, 10...90% rel. air humidity, non-condensing
Class 2K3 EN50178 (reduced)
-20...70°C, 10...90% rel. air humidity, non-condensing
<60Hz: 3.5mm EN60068-2-6
>60Hz : 1g EN60068-2-6
15g / 11ms EN60068-2-27
Industrial EN 61000-6-2
4kV / 8 kV EN 61000-4-2
10V/m EN 61000-4-3
2kV EN 61000-4-4
0.5kV / 0.5kV EN 61000-4-5
10Vrms EN 61000-4-6
Residential EN 61000-6-3
IP 65 (NEMA 12), after EN 60068-2-68
Æ note section 7.1
IP20
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
35
S mart P anel
Hardware
Technical data (continue)
Weight
Dimensions
System supply
3,5“
4,3“
5,7“
7”
B x H x T
Rated voltage
3,5/4,3“
5,7/7”
Cutout approx. 0,45kg approx. 0,5kg approx. 0,65kg approx. 0.7kg
142 x 107 x 36(25)mm
200 x 142 x 38(27)mm
125 x 90 mm
(mounting holes: 129x94 Ø4mm) Æ see mounting instructions!
24 VDC SELV, safety extra low voltage, protection class
III
Voltage range
Voltage dips
Protection against reverse polarity
Fuse
24 VDC to DIN 19240
10...28.8 VDC effective, absolute value with ripple 8.5...30.2 VDC
35.0 VDC for a duration of < 100ms
EN61000-6-2, up to 5s
Yes ( Î isolation
Current consumption 3,5“
(Idle, without USB-load) 4,3“
5,7“
7”
4W
4W
5W
6W
5.2)
( Î 5.3)
CPU
Memory
Realtime clock
Fuse protection
Communication-
Interfaces
Type
Type
Counters
Leap year change
DST change
Backup device internal
Breaking
ARM9 iMX25 400MHz
64MB soldered
Seconds, minutes, hour, day, month, year
Automatic
Manual via the software
Capacitor backup for approx. 1 week
1 A Fast tbd
Ethernet 1x ( Î 5.7)
Micro-SDCARD
Slot
USB 1-2
COM1
CAN
Temp.connector
Micro-SDCARD
2 x 2.0
RS232/485/422
USB-connector
D-Sub 9 Pol male
( Î Kap.5.8)
( Î Kap. 5.9)
CAN, not isolated CiA, D-Sub 9 Pol male ( Î Kap. 5.10)
Connector for KTY10-6 (= KTY81-210) sensor
( Î Kap.
Fehler! Verweisquelle konnte nicht gefunden werden.
)
Exchangeable storage device
36
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
12 Disposal
SmartPanel devices that are no longer used must be disposed of properly or returned to the manufacturer for disposal. (manufacturer's address Î
Section 13)
Materials:
Housing:
Front frame:
Galvanized sheet steel
Plastic
Printed-circuit board: 1. quality
Polyester/glass laminate
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
37
S mart P anel
Hardware
38
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
13 EU Conformity and Standards
The SmartPanel meets the requirements specified by the EU Council
Directives for harmonizing the regulations of EU member states relating to electromagnetic compatibility ( 89/336/EEC ).
The generic standards below were used to assess the electromagnetic compatibility of the SmartPanel:
EN 61000-6-3
(Emission)
EN 61000-6-2
(Immunity)
The following standard was used to assess the functionality of the
SmartPanel:
The following standard was used to assess the electrical safety of the
SmartPanel:
EN 60950 und EN 50178
Manufacturer: Grossenbacher
Manufacturer address: Spinnereistrasse 10
AG
St.Gallen
Switzerland
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
39
S mart P anel
Hardware
40
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
14 Revision history
Revision Date / Signed Modifications
1.0
2.0
04-11 / Fis
05-11 / Fis
First version
P.19 RS485 Signal A/B changed
3.0 10-11 / Fis
Manufacturer address:
P.19 COM1 discription changed
Grossenbacher Systeme AG
Spinnereistrasse 10
CH-9008 St.Gallen
Switzerland
Tel
Fax
: +41 (0)71 243 29 29
: +41 (0)71 243 29 28 [email protected] www.gesys.ch
Branch Germany:
Grossenbacher Systeme GmbH
Ruhrstrasse 15
D-63452 Hanau
Germany
Tel : +49 (0)6181 6751 999
Fax : +49 (0)6181 6751 998 [email protected] www.gesys.ch
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
41
S mart P anel
Hardware
42
DVS 63067-V3.0
DVS 63067 V2.0 © 2011 by Grossenbacher Systeme AG
S mart P anel
Hardware
15 Alphabetical index
A
Accessories .................................................................. 12
Additional documentation.............................................. 9
Ambient conditions...................................................... 37
B
Backlight...................................................................... 33
Backlight, contrast ....................................................... 33
Basic touch-screen function......................................... 31
C
CAN ............................................................................. 15
CAN connector ............................................................ 20
CAN interface .............................................................. 19
COM1 .................................................................... 13, 15
Commissioning ............................................................ 15 communication-interfaces............................................ 13
Connecting the power supply....................................... 15
Contents ......................................................................... 5
Contrast........................................................................ 33
Copyright ....................................................................... 2
D
Danger warnings ............................................................ 7
Degree of protection .................................................... 37
Device Versions........................................................... 11
Diagnostics................................................................... 33
Dimensions ................................................................... 38
Display................................................................... 13, 37
Disposal ....................................................................... 39
E
Ethernet.............................................................13, 15, 18
EU Conformity and Standards ..................................... 41
Exchangeable memory................................................. 13
Explanation of symbols................................................. 7
F
Features........................................................................ 13
Front panel cutout ........................................................ 25
Fuse.............................................................................. 16
Fuse protection............................................................. 38
I
Inserting /Removing the Micro-SDCARD................... 22
Introduction.................................................................... 9
K
Keyboard...................................................................... 13
M
Maintenance and repair................................................ 35
Manufacturer................................................................ 41
Manufacturer address................................................... 43 mass storage................................................................. 13
Mechanical dimensions - Frontside ............................. 26
Micro-SDCARD ......................................................... 15
Minimum clearance...................................................... 23
Mounting in the front panel - General.......................... 23
Mouse........................................................................... 13
N
Notes on the touch-screen ............................................ 31
O
Operation...................................................................... 23
Overview of connections ............................................. 15
P
Power Fail and UPS ..................................................... 16
Preparing the shield connections.................................. 17
Proper use....................................................................... 3
R
Realtime clock ....................................................... 13, 38
Repairs ......................................................................... 35
Revision history ........................................................... 43
S
Safety instructions for the user....................................... 4
Scope of delivery ......................................................... 11
Setup of RTC ............................................................ 16
Startup / Shutdown behaviour...................................... 23
Storage ......................................................................... 35
System description CoDeSys Soft-PLC......................... 9
System description WindowsCE.................................... 9
System supply................................................................ 38
T
Technical data .............................................................. 37
Temp.sensor connector ................................................ 22
Transport...................................................................... 35
U
USB.................................................................. 13, 15, 18
W
Warnings........................................................................ 7
Weight.......................................................................... 38
© 2011 by Grossenbacher Systeme AG DVS 63067 V2.0
DVS 63067-V3.0
43
DVS 63067-V3.0
Download