ICP DAS USA CAN-2054D User Manual
Add to My manuals21 Pages
ICP DAS USA CAN-2054D is a DeviceNet general I/O slave device with 8-channel isolated sink/source input and 8-channel isolated sink output, allowing for a wide range of industrial applications. It features DeviceNet communication, a compact design, and easy configuration via EDS files. With its digital input and output capabilities, it can be utilized in various scenarios such as industrial automation, data acquisition, and remote monitoring systems.
advertisement
DeviceNet Slave Device
CAN-2054D
User ’s Manual
Warranty
Without contrived damage, all products manufactured by ICP DAS are warranted in one year from the date of delivery to customers.
Warning
ICP DAS revises the manual at any time without notice. However, no responsibility is taken by ICP DAS unless infringement act imperils to patents of the third parties.
Copyright
Copyright © 2015 is reserved by ICP DAS.
Trademark
The brand name ICP DAS as a trademark is registered, and can be used by other authorized companies.
CAN-2054D
User’s Manual (v1.10, April/2015) 1
Contents
Overview ......................................................................................... 3
Hardware Specifications ............................................................... 4
Application ..................................................................................... 5
Node ID & Baud Rate Rotary Switch ............................................ 7
LED Description ............................................................................. 8
PIN Assignment ........................................................................... 10
Wire Connection .......................................................................... 11
DeviceNet Statement of Compliance .......................................... 12
Identity Object (Class ID: 0x01) .................................................. 13
Connection Object (Class ID:0x05) ............................................ 14
Assembly Object (Class ID: 0x04) .............................................. 15
Application Object1 (Class ID: 0x64).......................................... 17
CAN-2054D
User’s Manual (v1.10, April/2015) 2
1 Introduction
1.1 Overview
DeviceNet is one kind of the network protocols based on the CAN bus and mainly used for the embedded network of the machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc.
The CAN-2054D follows DeviceNet specification Volume I/II, Release 2.0.
User can access the digital I/O status and set the configuration via DeviceNet
EDS file. This module has 8-channel isolated sink/source input and 8-channel isolated sink output. It can be applied to various applications, such as PNP,
NPN, TTL, relay contact and so forth. By owing to the DeviceNet masters of
ICP DAS, you can quickly build a DeviceNet network to approach your requirements.
CAN-2054D
User’s Manual (v1.10, April/2015) 3
1.2 Hardware Specifications
Digital Output:
Output Channels: 8 (Sink)
DO Load Voltage: +5 ~ +30 V
DC
Output Max Load Current: 700 mA per channel.
Output Type: Open Collector.
Intra-module Isolation: 3750 Vrms
ESD Protection: 4 kV Contact for each channel
Digital Input:
Input Channels: 8 (Sink/Source).
DI On Level: +3.5 ~ +30 V
DC
.
DI Off Level: +1V
DC
Max.
Input Impedance: 3 kΩ, 0.3 W.
Intra-module Isolation: 3750 Vrms
ESD Protection: 4 kV Contact for each channel
Others:
DeviceNet Status: 3 LEDs for PWR / NET / MOD.
Terminator Resister: 1 LED as terminator resister indicators
DI LED: 8 LEDs as digital input indicators.
DO LED: 8 LEDs as digital output indicators.
Power Supply: Unregulated +10 ~ +30 V
DC
.
Power Consumption: 1.5 W.
Operating Temperature: -25 ~ 75 ℃.
Storage Temperature: -30 ~ 80 ℃.
Humidity: 10 to 90% RH, Non-condensing.
Dimensions: 32.3 mm x 99 mm x 77.5 mm (W x L x H) Detail .
CAN-2054D
User’s Manual (v1.10, April/2015) 4
1.3 Features
DeviceNet general I/O slave devices.
Comply with DeviceNet specification Volume I, Release 2.0 &
Volume II, Release 2.0, Errata 5
Group 2 Only Server (non UCMM-capable)
Support Predefined Master/Slave Connection Set
Connection supported:
1 connection for Explicit Messaging
1 connection for Polled I/O
1 connection for Bit-Strobe I/O connection
Support DeviceNet heartbeat and shutdown messages
Provide EDS file for standard DeviceNet master interface.
NET, MOD and PWR Led indictors
1.4 Application
CAN-2054D
User’s Manual (v1.10, April/2015) 5
2 Hardware
2.1 Structure
(Top View) (Bottom View)
CAN-2054D
User’s Manual (v1.10, April/2015) 6
2.2 Node ID & Baud Rate Rotary Switch
The rotary switches of node ID configure the node ID of CAN-2054D module. These two switches are for the tens digit and the units digit of the node ID. The node ID value of this demo picture is 32.
Node ID rotary switch
The rotary switch for baud rate handles the CAN baud rate of CAN-2054D module. The relationship between the rotary switch value and the practical baud rate is presented in the following table.
Baud rate rotary switch
Rotary Switch Value Baud rate (kbps)
0 125
250
500
1
2
CAN-2054D
User’s Manual (v1.10, April/2015) 7
2.3 LED Description
PWR LED
The CAN-2054D needs the power of 10 ~ 30 V
DC
. Under a normal connection, a good power supply and a correct voltage selection, as the unit is turned on, the LED will light up in red.
NET LED
The NET LED indicates the current status of the DeviceNet communication link. condition
Init Off Off line status indicates
Device is not online
Off
Flashing
Init solid
Solid
Connection timeout
On line
Link failed
I/O connection timeout
Device is on line, but not communicating
(Critical) Device has detected an error that has rendered it incapable of communicating on the link; for example, detected a duplicate node address or network configuration error
On line, communicating Device is online and communicating
MOD LED
This LED provides the devices status. It indicates whether or not the device is operating properly. condition status indicates
Off
Solid
Normal
Critical fault
Flashing Non_critical fault
Device has unrecoverable fault.
Device has recoverable fault to recover. If users want to fix the problem, reconfiguring device’s
MAC ID or resetting device may work.
CAN-2054D
User’s Manual (v1.10, April/2015) 8
Terminal Resistor LED
When enable the 120Ω terminator resistor, the LED will be turned on.
DO LED
If the DO LED is turned on, it means that the corresponding DO channel is active.
DI LED
If the DI LED is turned on, it means that the channel of DI is receiving an ON-Voltage-Level digital signal.
CAN-2054D
User’s Manual (v1.10, April/2015) 9
2.4 PIN Assignment
CAN-2054D
User’s Manual (v1.10, April/2015) 10
2.5 Wire Connection
CAN-2054D
User’s Manual (v1.10, April/2015) 11
3 DeviceNet Profile Area
This section describes the detailed functions for each object class that is implemented in the CAN-2054D DeviceNet network.
3.1 DeviceNet Statement of Compliance
General Device Data
Device Information Description
Version Description of DeviceNet Volume I, Release 2.0 &
Specification
Vendor Name
Volume II, Release 2.0
ICP DAS
Device Profile Name
Production Revision
CAN-2054D
1.1
DeviceNet Physical Conformance Data
Item Description
LED Support
MAC ID Setting
Yes
Switch (0 ~ 63)
Default MAC ID 1
Communication Baud Rate Setting Switch (125, 250, 500 kbps)
Default Baud Rate 125 kbps
Predefined Master/Slave Connection Group 2 Only Server
Set
CAN-2054D
User’s Manual (v1.10, April/2015) 12
3.2 Identity Object (Class ID: 0x01)
This object provides the identification of and general information about the device.
Class Attribute (Instance ID=0)
Attribute ID Attribute name
0x01
0x02
Revision
Max Instance
Class Service
Data Type
UINT
UINT
Method
Get
Get
Value
0001
1
Service Code
0x0E
Service name
Get_Attribute_Single
Instance Attribute (Instance ID=1)
Attribute
Description
ID
1 Vendor
Method
Get
Support
Yes
DeviceNet Data
Type
UINT
Value
803
2
3
4
Product type
Product code
Major. Minor of firmware version
Get
Get
Get
UINT
UINT
Struct of
USINT
USINT
0x00
0x700
1.1
5
6
7
10
Instance Service
Status
Serial number
Product name
Heartbeat Interval
Get
Get
Get
Get/Set
WORD
UDINT
-
1
Short_String CAN-2054D
USINT 0(default)
Service Code
0x0E
0x10
0x05
Service name
Get_Attribute_Single
Set_Attribute_Single
Reset
Note: Use the Instance Service 0x05 will reboot the device.
Support
Yes
Yes
Yes
CAN-2054D
User’s Manual (v1.10, April/2015) 13
3.3 Connection Object (Class ID:0x05)
This section presents the externally visible characteristics of the
Connection Objects associated with the Predefined Master/Slave Connection
Set within slave devices.
The default IO connection path is as follow.
Connection Path
Poll Produced
Poll Consumed
Class ID
0x04
0x04
Bit Strobe Produced 0x04
Bit Strobe Consumed 0x04
Instance ID
0x64
0x65
0x64
0x65
Attribute ID
0x03
0x03
0x03
0x03
Connection
Instance ID
1
2
3
Description
References the Explicit Messaging Connection into the Server
References the Poll I/O Connection
References the Bit
–Strobe I/O Connection
CAN-2054D
User’s Manual (v1.10, April/2015) 14
3.4 Assembly Object (Class ID: 0x04)
The Assembly Object binds attributes of multiple objects, which allows data to or from each object to be sent or received over a single connection.
Assembly objects can be used to bind input data or output data. The terms of ”input” and ”output” are defined from the network’s point of view. An input will produce data on the network and an output will consume data from the network.
Class attribute (Instance ID=0)
Attribute ID
0x01
0x02
Class service
Attribute name
Revision
Max Instance
Data Type
UINT
UINT
Method
Get
Get
Value
1
0x02
Service Code
0x0E
Instance ID
Instance ID
Service name
Get_Attribute_Single
OUTPUT
0x64
0x65 Set DO value
Contents of Each Assembly Object Instance
Instance
Description
ID
Type
Support
Get DI value
Get DO value
Yes
INPUT
Method
0x64
0x65
Channel 0 ~ 7 DI value
Channel 0 ~ 7 DO value
USINT
USINT
Get
Default
Value
0x00
Get/Set 0x00
CAN-2054D
User’s Manual (v1.10, April/2015) 15
Parameter description of Assembly Object Instance
Instance
ID
Data Range Parameter Description
0x64
0x65
0x00 ~ 0xFF
0x00 ~ 0xFF
Bit 0 => channel 0 DI value
Bit 1 => channel 1 DI value
…
Bit 7 => channel 7 DI value
Bit 0 => channel 0 DO value
Bit 1 => channel 1 DO value
…
Bit 7 => channel 7 DO value
Note: x is channel number of module
Instance attribute (Instance ID=0x64~0x65)
Attribute ID
0x03
Description
Data
Method
Get/Set
DeviceNet
Data Type
OUTPUT/
INPUT
Value
Dependent on instance ID
Instance service
Service Code
0x0E
0x10
Service name
Get_Attribute_Single
Set_Attribute_Single
Support
Yes
Yes
CAN-2054D
User’s Manual (v1.10, April/2015) 16
3.5 Application Object1 (Class ID: 0x64)
Application objects are the interfaces between an application and the
DeviceNet Layer. The attributes of application Objects contain the data for the application, which are accessed and exchanged via DeviceNet. DeviceNet accesses application data by invoking read and write functions. These functions need to be provided by an Application Object. DeviceNet provides
Get_Attribute_Single and Set_ Attribute_Single to read and write CAN-2054D module.
Application Object1 defines pulse output channels and digital input channels configuration.
Class attribute (Instance ID=0)
Attribute ID
0x01
0x02
Class service
Attribute name
Revision
Max Instance
Data Type
UINT
UINT
Method
Get
Get
Value
1
0x06
Service Code
0x0E
Service name
Get_Attribute_Single
Instance attribute (Instance ID=0x01)
Attribute
Description
ID
0x01 DI value
Method
Get
Support
Data Type
USINT
Yes
Default
Value
0x00
0x02 DO value
0x03 DO power on value
0x04 DO safe value mask
0x05 DO safe value
0x06
Save all Configuration to
EEPROM
Get/Set
Get/Set
Get/Set
Get/Set
Set
USINT
USINT
UDINT
USINT
USINT
0x00
0x00
0x00
0x00
-
CAN-2054D
User’s Manual (v1.10, April/2015) 17
18
Parameter description of Application Object1 attributes
Attribute
ID
Data Range Parameter Description
0x01
0x02
0x03
0x00 ~ 0xFF
0x00 ~ 0xFF
0x00 ~ 0xFF
Bit 0 => channel 0 DI value
Bit 1 => channel 1 DI value
…
Bit 7 => channel 7 DI value
Bit 0 => channel 0 DO value
Bit 1 => channel 1 DO value
…
Bit 7 => channel 7 DO value
Bit 0 => channel 0 DO power on value
Bit 1 => channel 1 DO power on value
…
Bit 7 => channel 7 DO power on value
0x04
0x05
0x06
0x00 ~ 0xFF
0x00 ~ 0xFF
0x01: Use default configuration
0x02: Save all Configuration to
EEPROM
Bit 0 => channel 0 DO safe value mask
Bit 1 => channel 1 DO safe value mask
…
Bit 7 => channel 7 DO safe value mask
Bit value=1 => apply safe value setting
Bit value=0 => apply DO output value
Bit 0 => channel 0 DO safe value
Bit 1 => channel 1 DO safe value
…
Bit 7 => channel 7 DO safe value
0x01: After restarting the device, configuration will become factory setting.
0x02: Save all channels configuration into EEPROM
Instance service
Service Code
0x0E
0x10
Service name
Get_Attribute_Single
Set_Attribute_Single
Support
Yes
Yes
CAN-2054D
User’s Manual (v1.10, April/2015)
4 Application
Application Object1 (Class ID:0x64) lists all the parameters of the module.
Each Instance ID is corresponding to the different cahnnels. By using “Set/Get
Attribute Single” service, user can read/write the parameters of each channel.
Example1:
Set DO output value.
(Class ID: 0x64, Instance ID: 0x01, Attribute ID 0x02).
If the node ID of the CAN-2054D is 1, and the master (ID: 0x0A) has completed “Explicit” connection with the device. By setting the value of
Attribute ID 0x02 to 0xF0, you can set the DO4, DO5, DO6, and DO7 to turn
ON and others to turn OFF.
IDENTIFIER BITS 8-byte Data (byte)
Data
Destination MAC ID RTR (HEX)
Length
10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7
1 0 0 0 0 0 0 1 1 0 0 0 6
Master
IDENTIFIER BITS
Source MAC ID
10 9 8 7 6 5 4 3 2 1 0
RTR
Data
Length
0A 10 64 01 02 FF -- --
Slave
(CAN-2054D)
8-byte Data (byte)
(HEX)
0 1 2 3 4 5 6 7
1 0 0 0 0 0 0 1 0 1 1 0 2 0A 90 -- -- -- -- -- --
Master
Slave
(CAN-2054D)
Set the value 0xFF to the Application Object1 with Instance ID 0x01 and Attribute
ID 0x02. After sending the
“Set Attribute Single”, the slave device will response
0x90 to mean that the setting is OK. Then the DO4, DO5, DO6, and DO7 will be turned ON and others are turned OFF.
Via changing the Attribute ID of the Application Object, user can set other parameters of this device.
CAN-2054D
User’s Manual (v1.10, April/2015) 19
Example2:
Get DI data (Class ID: 0x64, Instance ID: 0x01, Attribute ID 0x01).
If the node ID of the CAN-2054D is 1, and the master (id: 0x0A) has completed
“Explicit” connection with the device. By getting the value of the object with attribute ID 0x01, you can get the channel 0 ~ 7 of the DI data.
IDENTIFIER BITS 8-byte Data (byte)
Data
Destination MAC ID RTR (HEX)
Length
10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7
1 0 0 0 0 0 0 1 1 0 0 0 5
Master
IDENTIFIER BITS
Source MAC ID
10 9 8 7 6 5 4 3 2 1 0
RTR
Data
Length
0A 0E 64 01 01 -- -- --
Slave
(CAN-2054D)
8-byte Data (byte)
(HEX)
0 1 2 3 4 5 6 7
1 0 0 0 0 0 0 1 0 1 1 0 3 0A 8E 0F -- -- -- -- --
Master
Slave
(CAN-2054D)
Get the value of Application Object1 with Instance ID 0x01 and Attribute ID 0x01.
After sending the
“Get Attribute Single”, the slave device response the DI data
(0x0F) at byte 2. The value 0x0F means that the status of DI3, DI2, DI1 and DI0 are turned on and others are turned off.
By changing the Instance ID and Attribute ID of the Application Object, you can get other parameters of this device.
The Attribute 0x03 of Application Object1 can control the DO power on value of each channel. After setting this attribute, the DO channels will output
DO power on value when booting up.
Attribute 0x04 and 0x05 of Application Object1 are used for safe value configuration when
“Explicit Message Timeout” error occurs. When setting the channel selection value of the Attribute ID 0x04 to
“0x1”, the safe value of
Channel 0 will be active. If the value is set to 0x4, it means that the safe value of the channel 2 is active. Afterwards, you can configure the output safe value of this channel by setting the value of Attribute ID 0x05. When setting the
Attribute ID 0x04 to
“0x1” and Attribute ID 0x05 to “0x1”, the channel 0 will turn
ON while the error occurs.
CAN-2054D
User’s Manual (v1.10, April/2015) 20
Appendix A: Dimension
CAN-2054D
User’s Manual (v1.10, April/2015) 21
advertisement
Related manuals
advertisement
Table of contents
- 3 Introduction
- 3 Overview
- 4 Hardware Specifications
- 5 Features
- 5 Application
- 6 Hardware
- 6 Structure
- 7 Node ID & Baud Rate Rotary Switch
- 8 LED Description
- 10 PIN Assignment
- 11 Wire Connection
- 12 DeviceNet Profile Area
- 12 DeviceNet Statement of Compliance
- 13 Identity Object (Class ID: 0x01)
- 14 Connection Object (Class ID:0x05)
- 15 Assembly Object (Class ID: 0x04)
- 17 Application Object1 (Class ID: 0x64)
- 19 Application
- 21 Appendix A: Dimension