ICP DAS USA CAN-2054D User Manual

Add to My manuals
21 Pages

advertisement

ICP DAS USA CAN-2054D User Manual | Manualzz

DeviceNet Slave Device

CAN-2054D

User ’s Manual

Warranty

Without contrived damage, all products manufactured by ICP DAS are warranted in one year from the date of delivery to customers.

Warning

ICP DAS revises the manual at any time without notice. However, no responsibility is taken by ICP DAS unless infringement act imperils to patents of the third parties.

Copyright

Copyright © 2015 is reserved by ICP DAS.

Trademark

The brand name ICP DAS as a trademark is registered, and can be used by other authorized companies.

CAN-2054D

User’s Manual (v1.10, April/2015) 1

Contents

1 Introduction ............................................................................................. 3

1.1

Overview ......................................................................................... 3

1.2

Hardware Specifications ............................................................... 4

1.3

Features .......................................................................................... 5

1.4

Application ..................................................................................... 5

2 Hardware ................................................................................................. 6

2.1

Structure ......................................................................................... 6

2.2

Node ID & Baud Rate Rotary Switch ............................................ 7

2.3

LED Description ............................................................................. 8

2.4

PIN Assignment ........................................................................... 10

2.5

Wire Connection .......................................................................... 11

3 DeviceNet Profile Area ......................................................................... 12

3.1

DeviceNet Statement of Compliance .......................................... 12

3.2

Identity Object (Class ID: 0x01) .................................................. 13

3.3

Connection Object (Class ID:0x05) ............................................ 14

3.4

Assembly Object (Class ID: 0x04) .............................................. 15

3.5

Application Object1 (Class ID: 0x64).......................................... 17

4 Application ............................................................................................ 19

Appendix A: Dimension ............................................................................... 21

CAN-2054D

User’s Manual (v1.10, April/2015) 2

1 Introduction

1.1 Overview

DeviceNet is one kind of the network protocols based on the CAN bus and mainly used for the embedded network of the machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc.

The CAN-2054D follows DeviceNet specification Volume I/II, Release 2.0.

User can access the digital I/O status and set the configuration via DeviceNet

EDS file. This module has 8-channel isolated sink/source input and 8-channel isolated sink output. It can be applied to various applications, such as PNP,

NPN, TTL, relay contact and so forth. By owing to the DeviceNet masters of

ICP DAS, you can quickly build a DeviceNet network to approach your requirements.

CAN-2054D

User’s Manual (v1.10, April/2015) 3

1.2 Hardware Specifications

Digital Output:

 Output Channels: 8 (Sink)

 DO Load Voltage: +5 ~ +30 V

DC

 Output Max Load Current: 700 mA per channel.

 Output Type: Open Collector.

 Intra-module Isolation: 3750 Vrms

 ESD Protection: 4 kV Contact for each channel

Digital Input:

 Input Channels: 8 (Sink/Source).

 DI On Level: +3.5 ~ +30 V

DC

.

 DI Off Level: +1V

DC

Max.

 Input Impedance: 3 kΩ, 0.3 W.

 Intra-module Isolation: 3750 Vrms

 ESD Protection: 4 kV Contact for each channel

Others:

 DeviceNet Status: 3 LEDs for PWR / NET / MOD.

 Terminator Resister: 1 LED as terminator resister indicators

 DI LED: 8 LEDs as digital input indicators.

 DO LED: 8 LEDs as digital output indicators.

 Power Supply: Unregulated +10 ~ +30 V

DC

.

 Power Consumption: 1.5 W.

 Operating Temperature: -25 ~ 75 ℃.

 Storage Temperature: -30 ~ 80 ℃.

 Humidity: 10 to 90% RH, Non-condensing.

Dimensions: 32.3 mm x 99 mm x 77.5 mm (W x L x H) Detail .

CAN-2054D

User’s Manual (v1.10, April/2015) 4

1.3 Features

 DeviceNet general I/O slave devices.

 Comply with DeviceNet specification Volume I, Release 2.0 &

Volume II, Release 2.0, Errata 5

 Group 2 Only Server (non UCMM-capable)

 Support Predefined Master/Slave Connection Set

 Connection supported:

1 connection for Explicit Messaging

1 connection for Polled I/O

1 connection for Bit-Strobe I/O connection

 Support DeviceNet heartbeat and shutdown messages

 Provide EDS file for standard DeviceNet master interface.

 NET, MOD and PWR Led indictors

1.4 Application

CAN-2054D

User’s Manual (v1.10, April/2015) 5

2 Hardware

2.1 Structure

(Top View) (Bottom View)

CAN-2054D

User’s Manual (v1.10, April/2015) 6

2.2 Node ID & Baud Rate Rotary Switch

The rotary switches of node ID configure the node ID of CAN-2054D module. These two switches are for the tens digit and the units digit of the node ID. The node ID value of this demo picture is 32.

Node ID rotary switch

The rotary switch for baud rate handles the CAN baud rate of CAN-2054D module. The relationship between the rotary switch value and the practical baud rate is presented in the following table.

Baud rate rotary switch

Rotary Switch Value Baud rate (kbps)

0 125

250

500

1

2

CAN-2054D

User’s Manual (v1.10, April/2015) 7

2.3 LED Description

PWR LED

The CAN-2054D needs the power of 10 ~ 30 V

DC

. Under a normal connection, a good power supply and a correct voltage selection, as the unit is turned on, the LED will light up in red.

NET LED

The NET LED indicates the current status of the DeviceNet communication link. condition

Init Off Off line status indicates

Device is not online

Off

Flashing

Init solid

Solid

Connection timeout

On line

Link failed

I/O connection timeout

Device is on line, but not communicating

(Critical) Device has detected an error that has rendered it incapable of communicating on the link; for example, detected a duplicate node address or network configuration error

On line, communicating Device is online and communicating

MOD LED

This LED provides the devices status. It indicates whether or not the device is operating properly. condition status indicates

Off

Solid

Normal

Critical fault

Flashing Non_critical fault

Device has unrecoverable fault.

Device has recoverable fault to recover. If users want to fix the problem, reconfiguring device’s

MAC ID or resetting device may work.

CAN-2054D

User’s Manual (v1.10, April/2015) 8

Terminal Resistor LED

When enable the 120Ω terminator resistor, the LED will be turned on.

DO LED

If the DO LED is turned on, it means that the corresponding DO channel is active.

DI LED

If the DI LED is turned on, it means that the channel of DI is receiving an ON-Voltage-Level digital signal.

CAN-2054D

User’s Manual (v1.10, April/2015) 9

2.4 PIN Assignment

CAN-2054D

User’s Manual (v1.10, April/2015) 10

2.5 Wire Connection

CAN-2054D

User’s Manual (v1.10, April/2015) 11

3 DeviceNet Profile Area

This section describes the detailed functions for each object class that is implemented in the CAN-2054D DeviceNet network.

3.1 DeviceNet Statement of Compliance

General Device Data

Device Information Description

Version Description of DeviceNet Volume I, Release 2.0 &

Specification

Vendor Name

Volume II, Release 2.0

ICP DAS

Device Profile Name

Production Revision

CAN-2054D

1.1

DeviceNet Physical Conformance Data

Item Description

LED Support

MAC ID Setting

Yes

Switch (0 ~ 63)

Default MAC ID 1

Communication Baud Rate Setting Switch (125, 250, 500 kbps)

Default Baud Rate 125 kbps

Predefined Master/Slave Connection Group 2 Only Server

Set

CAN-2054D

User’s Manual (v1.10, April/2015) 12

3.2 Identity Object (Class ID: 0x01)

This object provides the identification of and general information about the device.

Class Attribute (Instance ID=0)

Attribute ID Attribute name

0x01

0x02

Revision

Max Instance

Class Service

Data Type

UINT

UINT

Method

Get

Get

Value

0001

1

Service Code

0x0E

Service name

Get_Attribute_Single

Instance Attribute (Instance ID=1)

Attribute

Description

ID

1 Vendor

Method

Get

Support

Yes

DeviceNet Data

Type

UINT

Value

803

2

3

4

Product type

Product code

Major. Minor of firmware version

Get

Get

Get

UINT

UINT

Struct of

USINT

USINT

0x00

0x700

1.1

5

6

7

10

Instance Service

Status

Serial number

Product name

Heartbeat Interval

Get

Get

Get

Get/Set

WORD

UDINT

-

1

Short_String CAN-2054D

USINT 0(default)

Service Code

0x0E

0x10

0x05

Service name

Get_Attribute_Single

Set_Attribute_Single

Reset

Note: Use the Instance Service 0x05 will reboot the device.

Support

Yes

Yes

Yes

CAN-2054D

User’s Manual (v1.10, April/2015) 13

3.3 Connection Object (Class ID:0x05)

This section presents the externally visible characteristics of the

Connection Objects associated with the Predefined Master/Slave Connection

Set within slave devices.

The default IO connection path is as follow.

Connection Path

Poll Produced

Poll Consumed

Class ID

0x04

0x04

Bit Strobe Produced 0x04

Bit Strobe Consumed 0x04

Instance ID

0x64

0x65

0x64

0x65

Attribute ID

0x03

0x03

0x03

0x03

Connection

Instance ID

1

2

3

Description

References the Explicit Messaging Connection into the Server

References the Poll I/O Connection

References the Bit

–Strobe I/O Connection

CAN-2054D

User’s Manual (v1.10, April/2015) 14

3.4 Assembly Object (Class ID: 0x04)

The Assembly Object binds attributes of multiple objects, which allows data to or from each object to be sent or received over a single connection.

Assembly objects can be used to bind input data or output data. The terms of ”input” and ”output” are defined from the network’s point of view. An input will produce data on the network and an output will consume data from the network.

Class attribute (Instance ID=0)

Attribute ID

0x01

0x02

Class service

Attribute name

Revision

Max Instance

Data Type

UINT

UINT

Method

Get

Get

Value

1

0x02

Service Code

0x0E

Instance ID

Instance ID

Service name

Get_Attribute_Single

OUTPUT

0x64

0x65 Set DO value

Contents of Each Assembly Object Instance

Instance

Description

ID

Type

Support

Get DI value

Get DO value

Yes

INPUT

Method

0x64

0x65

Channel 0 ~ 7 DI value

Channel 0 ~ 7 DO value

USINT

USINT

Get

Default

Value

0x00

Get/Set 0x00

CAN-2054D

User’s Manual (v1.10, April/2015) 15

Parameter description of Assembly Object Instance

Instance

ID

Data Range Parameter Description

0x64

0x65

0x00 ~ 0xFF

0x00 ~ 0xFF

Bit 0 => channel 0 DI value

Bit 1 => channel 1 DI value

Bit 7 => channel 7 DI value

Bit 0 => channel 0 DO value

Bit 1 => channel 1 DO value

Bit 7 => channel 7 DO value

Note: x is channel number of module

Instance attribute (Instance ID=0x64~0x65)

Attribute ID

0x03

Description

Data

Method

Get/Set

DeviceNet

Data Type

OUTPUT/

INPUT

Value

Dependent on instance ID

Instance service

Service Code

0x0E

0x10

Service name

Get_Attribute_Single

Set_Attribute_Single

Support

Yes

Yes

CAN-2054D

User’s Manual (v1.10, April/2015) 16

3.5 Application Object1 (Class ID: 0x64)

Application objects are the interfaces between an application and the

DeviceNet Layer. The attributes of application Objects contain the data for the application, which are accessed and exchanged via DeviceNet. DeviceNet accesses application data by invoking read and write functions. These functions need to be provided by an Application Object. DeviceNet provides

Get_Attribute_Single and Set_ Attribute_Single to read and write CAN-2054D module.

Application Object1 defines pulse output channels and digital input channels configuration.

Class attribute (Instance ID=0)

Attribute ID

0x01

0x02

Class service

Attribute name

Revision

Max Instance

Data Type

UINT

UINT

Method

Get

Get

Value

1

0x06

Service Code

0x0E

Service name

Get_Attribute_Single

Instance attribute (Instance ID=0x01)

Attribute

Description

ID

0x01 DI value

Method

Get

Support

Data Type

USINT

Yes

Default

Value

0x00

0x02 DO value

0x03 DO power on value

0x04 DO safe value mask

0x05 DO safe value

0x06

Save all Configuration to

EEPROM

Get/Set

Get/Set

Get/Set

Get/Set

Set

USINT

USINT

UDINT

USINT

USINT

0x00

0x00

0x00

0x00

-

CAN-2054D

User’s Manual (v1.10, April/2015) 17

18

Parameter description of Application Object1 attributes

Attribute

ID

Data Range Parameter Description

0x01

0x02

0x03

0x00 ~ 0xFF

0x00 ~ 0xFF

0x00 ~ 0xFF

Bit 0 => channel 0 DI value

Bit 1 => channel 1 DI value

Bit 7 => channel 7 DI value

Bit 0 => channel 0 DO value

Bit 1 => channel 1 DO value

Bit 7 => channel 7 DO value

Bit 0 => channel 0 DO power on value

Bit 1 => channel 1 DO power on value

Bit 7 => channel 7 DO power on value

0x04

0x05

0x06

0x00 ~ 0xFF

0x00 ~ 0xFF

0x01: Use default configuration

0x02: Save all Configuration to

EEPROM

Bit 0 => channel 0 DO safe value mask

Bit 1 => channel 1 DO safe value mask

Bit 7 => channel 7 DO safe value mask

Bit value=1 => apply safe value setting

Bit value=0 => apply DO output value

Bit 0 => channel 0 DO safe value

Bit 1 => channel 1 DO safe value

Bit 7 => channel 7 DO safe value

0x01: After restarting the device, configuration will become factory setting.

0x02: Save all channels configuration into EEPROM

Instance service

Service Code

0x0E

0x10

Service name

Get_Attribute_Single

Set_Attribute_Single

Support

Yes

Yes

CAN-2054D

User’s Manual (v1.10, April/2015)

4 Application

Application Object1 (Class ID:0x64) lists all the parameters of the module.

Each Instance ID is corresponding to the different cahnnels. By using “Set/Get

Attribute Single” service, user can read/write the parameters of each channel.

Example1:

Set DO output value.

(Class ID: 0x64, Instance ID: 0x01, Attribute ID 0x02).

If the node ID of the CAN-2054D is 1, and the master (ID: 0x0A) has completed “Explicit” connection with the device. By setting the value of

Attribute ID 0x02 to 0xF0, you can set the DO4, DO5, DO6, and DO7 to turn

ON and others to turn OFF.

IDENTIFIER BITS 8-byte Data (byte)

Data

Destination MAC ID RTR (HEX)

Length

10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7

1 0 0 0 0 0 0 1 1 0 0 0 6

Master

IDENTIFIER BITS

Source MAC ID

10 9 8 7 6 5 4 3 2 1 0

RTR

Data

Length

0A 10 64 01 02 FF -- --

Slave

(CAN-2054D)

8-byte Data (byte)

(HEX)

0 1 2 3 4 5 6 7

1 0 0 0 0 0 0 1 0 1 1 0 2 0A 90 -- -- -- -- -- --

Master

Slave

(CAN-2054D)

Set the value 0xFF to the Application Object1 with Instance ID 0x01 and Attribute

ID 0x02. After sending the

“Set Attribute Single”, the slave device will response

0x90 to mean that the setting is OK. Then the DO4, DO5, DO6, and DO7 will be turned ON and others are turned OFF.

Via changing the Attribute ID of the Application Object, user can set other parameters of this device.

CAN-2054D

User’s Manual (v1.10, April/2015) 19

Example2:

Get DI data (Class ID: 0x64, Instance ID: 0x01, Attribute ID 0x01).

If the node ID of the CAN-2054D is 1, and the master (id: 0x0A) has completed

“Explicit” connection with the device. By getting the value of the object with attribute ID 0x01, you can get the channel 0 ~ 7 of the DI data.

IDENTIFIER BITS 8-byte Data (byte)

Data

Destination MAC ID RTR (HEX)

Length

10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7

1 0 0 0 0 0 0 1 1 0 0 0 5

Master

IDENTIFIER BITS

Source MAC ID

10 9 8 7 6 5 4 3 2 1 0

RTR

Data

Length

0A 0E 64 01 01 -- -- --

Slave

(CAN-2054D)

8-byte Data (byte)

(HEX)

0 1 2 3 4 5 6 7

1 0 0 0 0 0 0 1 0 1 1 0 3 0A 8E 0F -- -- -- -- --

Master

Slave

(CAN-2054D)

Get the value of Application Object1 with Instance ID 0x01 and Attribute ID 0x01.

After sending the

“Get Attribute Single”, the slave device response the DI data

(0x0F) at byte 2. The value 0x0F means that the status of DI3, DI2, DI1 and DI0 are turned on and others are turned off.

By changing the Instance ID and Attribute ID of the Application Object, you can get other parameters of this device.

The Attribute 0x03 of Application Object1 can control the DO power on value of each channel. After setting this attribute, the DO channels will output

DO power on value when booting up.

Attribute 0x04 and 0x05 of Application Object1 are used for safe value configuration when

“Explicit Message Timeout” error occurs. When setting the channel selection value of the Attribute ID 0x04 to

“0x1”, the safe value of

Channel 0 will be active. If the value is set to 0x4, it means that the safe value of the channel 2 is active. Afterwards, you can configure the output safe value of this channel by setting the value of Attribute ID 0x05. When setting the

Attribute ID 0x04 to

“0x1” and Attribute ID 0x05 to “0x1”, the channel 0 will turn

ON while the error occurs.

CAN-2054D

User’s Manual (v1.10, April/2015) 20

Appendix A: Dimension

CAN-2054D

User’s Manual (v1.10, April/2015) 21