1
Wine Cellar Cooling Systems
Cabinet Cooling Systems
Installation, Operation and Maintenance Guide
60Hz Models CAB018
50Hz Models CAB25
Manufactured by:
Syracuse, NY wineguardian.com
airinnovations.com
Wine Guardian reserves the right, without notice, to make changes to this document at its sole discretion.
Please visit our web site for the most current version of the Wine Guardian manual and other literature.
Wine Guardian is a registered trademark (US 2,972,262, EU #005108675) of Air Innovations, Inc.
Wine Guardian Through-the-Wall U.S. Pat. No. D634,760S,
Edition 011-2020
© Air Innovations, 2020
Part No.
15H0307-00
TABLE OF CONTENTS
Receiving, Inspecting and Unpacking the Wine Guardian System .............. 6
The Wine Guardian Cabinet System Contains ....................................................... 10
Extended Compressor Warranty---U.S. and Canada only ..................................... 11
Overview ................................................................................................................... 13
2
Starting-up and Operating the Wine Guardian .......................................... 26
Standard Controller Functions .................................................................. 27
Installing the Optional Remote Interface Controller and Communication
Mounting the Optional Remote Interface Controller (Wired) ...................... 38
Mounting the Optional Remote Interface Controller (Wireless) ................. 39
Installation of the Optional Wine Guardian Remote Sensor ...................... 40
Remote Sensor Pairing Instructions – Multiple Sensors (Wireless) ........... 43
High Pressure Switch Has Shut the System Down ............................... 46
3
Problems Controlling Cellar Humidity ........................................................................ 50
Manufacturer’s Warranty – U.S. and Canada only .................................... 51
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
RSS GEN (English)
This device contains licence-exempt transmitter(s)/receiver(s) that comply with Innovation, Science and Economic
Development Canada’s licence-exempt RSS(s). Operation is subject to the following two conditions:
1.
2.
This device may not cause interference.
This device must accept any interference, including interference that may cause undesired operation of the device.
RSS GEN (French)
L’émetteur/récepteur exempt de licence contenu dans le présent appareil est conforme aux CNR d’Innovation,
Sciences et Développement économique Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes :
1.
2.
L’appareil ne doit pas produire de brouillage;
L’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
4
Directory of Terms
Ambient Air – The surrounding area outside the cellar such as a room, basement, garage or outdoors.
CFM – Cubic feet per minute. A unit of measurement for the amount of air handled by the fan.
Condensate / Condensation – The water formed out of the air when it is cooled below a certain temperature (called dew point). Often referred to as “sweating” on pipes and cold surfaces. This water collects at the bottom of the evaporator or cooling coil and drains out of the unit through the drain line.
Condenser (Heat Rejection) Section / Coil – The Condenser Section uses the compressor, condenser coil and fan to remove heat from the refrigerant to the ambient air outside the wine cellar. The word condenser refers to the condensation of the refrigerant from gas to liquid phase.
CSA/ETL – Canadian Standard Association/Electric Testing Laboratory
CE – Certificate of European conformity
Exhaust Air – The air leaving the evaporator or condenser section of the Wine Guardian unit.
Evaporator (Cooling) Section / Coil – The Evaporator Section uses the cooling coil and the fan to remove heat from the air inside the wine cellar to the refrigerant, cooling the air and condensing moisture out of the air. The word evaporator refers to the evaporation of the refrigerant from liquid to gas phase in the coil. The Evaporator Section is connected to or inside the wine cellar.
Flexible Duct – Round ducts with steel reinforced plastic liners, a layer of insulation and an outer plastic layer used to convey the air from the unit to the cellar or ambient space.
Grille or Diffuser – Inlet or outlet plates to direct the airflow or protect the inside of the unit.
Heat Gain / Loss – The amount of cooling or heating expressed in watts transferred between the wine cellar and the ambient space. The Wine Guardian must offset this load.
Inlet Air – The air entering the evaporator and condenser sections of the Wine
Guardian unit.
NEC – National Electrical Code
Recovery – The amount of cooling the unit does to return the cellar to its set point temperature after some new load is introduced, such as people or new cases of warm wine entering the cellar.
Return Air - The air leaving the cellar and returning to the inlet of the evaporator coil.
SP – Static pressure. Unit of measurement (inches of water column) of the pressure of the air handled by the fan.
Set Point – The desired temperature or humidity set on the thermostat or humidistat.
Supply Air - The air entering the cellar from the discharge of the evaporator coil.
5
Receiving, Inspecting and Unpacking the Wine
Guardian System
NOTE: Wine Guardian systems are factory assembled and tested prior to shipment.
Wine Guardian systems are shipped individually in corrugated boxes specially designed to protect the equipment during shipment.
Before opening the container, inspect the packing crates or boxes for obvious signs of damage or mishandling.
Write any discrepancy or visual damage on the bill of lading before signing.
Inspect all equipment for any sign of damage caused during transit.
Report all visual or concealed damage to the carrier and file a claim immediately.
IMPORTANT
If this procedure is not followed, the shipping company may reject the
claim and the consignee may suffer the loss. Do not return the shipment
to the factory .
WARNING
**THE UNIT SHOULD BE LIFTED FROM UNDERNEATH ITS BASE AT
BOTH ENDS OF THE SYSTEM.
Review the Packing Slip to Verify:
Model number
Factory-installed options
System accessories
If any items listed on the packing slip do not match your order information, contact the place of purchase immediately.
Check the unit for
:
An electrical power cord
Foam gasket for seal between Wine Guardian unit and cabinent
Accessories such as condenser air duct collar or duct collar kit, and optional controls, if ordered.
6
General Description
The Wine Guardian Cabinet cooling system is a professional grade, self-contained climate control system designed specifically for the storage of wine at cellar temperatures. It is designed for easy installation and operation. Wine Guardian uses digital electronic controls and environmentally friendly R-134a refrigerant. The entire system is run-tested at the factory and shipped as a single package. All components are of a high quality standard commercial grade. The entire system is approved by ETL (Equipment Testing Lab) according to UL (Underwriters Laboratory) 484 and
CSA (Canadian Standard Association) safety standards. All wiring complies with NEC (National
Electrical Code). All 50Hz Wine Guardian equipment is CE certified. Each system is factory installed with a sealed, UL-approved power cord and plug. Wine Guardian products are made in the USA.
The Wine Guardian Cabinet system is completely self-contained and includes an integral air cooled condenser. The system is functionally divided into two sections, the evaporator or cooling section, and the condenser or heat rejection section. Each section contains a coil to add or remove heat and a fan to move the air through the coil and into our or out of the cellar or adjacent space.
Air from the cabinet first enters the cooling coil. Air passes through the cooling coil and is cooled by the refrigerant inside the coil. This causes any excess humidity in the air to condense and be captured in the drain pan and internally evaporates as it comes in contact with the integral condensate removal coil. Air then enters the fan where it is pressurized and discharged out of the system. The thermostat (remote interface controller) turns the cooling on and off as needed to maintain its set point.
The compressor and condenser section are activated whenever the system is cooling. The condenser fan draws air from the surrounding or ambient space. The airflows through the condenser coil where it absorbs heat from the refrigerant in the coil. The air is finally discharged out of the system by the condenser fan, and can be ducted outside or to an unused space through optional duct collars.
CAUTI ON
THE AIR EXHAUST FORM THE CONDENSER FAN IS WARM AND CAN BE 20 DEGREES F
ABOVE THE ENTERING AIR TEMPERATURE.
7
Wine Guardian Controls
Wine Guardian’s digital electronic control system offers a versatile solution for controlling and monitoring your cabinet temperature and humidity. This system consists of three controls; a main control board; a remote user interface; and a remote temperature and humidity sensor. The system only requires the use of the main control board and the remote user interface to function. However, users have the following options to customize the control capabilities for their application: (See pg. 8 for description of control boards and optional sensors).
The Wine Guardian’s digital electronic controls are designed to control the operation of the compressor, condenser fan, evaporator fan, and optional humidifier. There also is pressure switch monitoring with a dry contact alarm output that will energize in the event of a pressure switch fault or a high/low temperature or humidity alarm. The remote user interface controls employ userfriendly, menu-driven programming features that can easily be accessed by holding the mode button on the control for five seconds. Once in the program menu, the user can scroll through the settings by pressing the mode button and can adjust each setting by using the up and down arrows.
The programming mode allows the user to customize features such as °F or °C temperature scale, high/low temperature and humidity alarm set points, an adjustable 0-10 minute compressor antishort cycle delay, sensor averaging options, enable or disable the defrost feature, differential and dead band adjustments, room temperature calibration, enable or disable the humidifier, and automatic or continuous fan option. To exit the programming mode the user may either hold the mode button for 5 seconds or the control will automatically store the settings and exit the programming mode after 10 seconds of inactivity. Each remote user interface control will also employ an ON/OFF button that turns the system on or off respectively.
8
Wine Guardian Controls
One-way communication: remote temp/humidity sensor reports temp and humidity readings to main control.
Temperature/Humidity Sensor: Can be used in conjunction with the Main
Control to report temp/humidity from inside the wine cellar without requiring a user interface to be located inside the wine cellar.
Main Control: Performs all switching functions and interfaces with inputs and outputs. It can connect to local or remote user interface, as well as remote temperature/humidity sensor.
Two way communications: remote user interface reports settings back to main control, main control energizes outputs and reports alarms and temp/humidity readings to remote user interface.
Default to 13 Deg C for 50Hz models
Remote User Interface: Can be used with Main Control for adjusting settings, reading temp/humidity, and reading fault codes in a remote location away from the unit.
9
Standard Specifications
IMPORTANT
Design and specifications are subject to change without notice
The Wine Guardian Cabinet System Contains
A capillary tube expansion to control the flow of refrigeration into the evaporator coil
A filter dryer to keep the refrigerant clean and free of contaminants
A manually reset, high-pressure switch on the condenser discharge to protect the compressor from high pressures
Environmentally friendly-134a refrigerant
An internally/externally mounted digital electronic control with many user-controlled settings
Multi-panel evaporator/condenser return/intake connections
All exterior framing of the Wine Guardian is 0.063" gauge aluminum to prevent rust and corrosion. All coils are aluminum tubes with aluminum fins. The system uses an internal drain system to remove excess moisture and does not reintroduce it back into the cabinet.
Each system is provided with a pre-wired and tested remote user interface as standard, an optional temperature and humidity sensor (up to three) are available as options. The thermostat has multiple control functions for the fan, operation, cooling, and maintaining humidity (if equipped).
Compressors are self-lubricating, permanently sealed, hermetic reciprocating type compressors, with internal overload protection and capacity start with a minimum of one-year manufacturer’s warranty and an optional five-year warranty. Compressors are mounted on rubber-in-shear isolators to reduce noise and vibration.
Electric power is supplied by a single, factory-furnished cord and plug.
Serving Temperature Option
The factory configured serving-temperature option allows a Wine Guardian unit to control to an extended temperature range from 42° F to 64° F (5 ° C - 18 ° C). Perfect for single to multiple cabinet applications and small wine rooms in which consumption-temperature cooling is preferred. It also allows the user to rotate wine stock and change the set point from season to season, making it ideal for restaurants, wine bars, clubs, etc.
10
Accessories and Optional Equipment
Extended Compressor Warranty---U.S. and Canada only
The Wine Guardian uses only the best commercially available compressors on the market.
However, since the compressor is the single most expensive component in the system, it is recommended that you purchase the extended, five-year warranty option.
Duct Collar Adapter
Optional duct collar adapters are available for ease in directing the warm condenser air away from the cabinet or for directing cold conditioned air to the cabinet from the cooling unit.
Remote Temperature/Humidity Controller
The remote temperature/humidity controller (Remote Interface Controller) is intended to provide a means for user interface at a remote location. The controller can be used as a remote sensor/controller mounted within the cabinet. The controller can also be used as a remote indicator
(without sensor) mounted directly outside of the cabinet. The Remote Interface Controller includes a backlit face for temperature and humidity indication along with controller set-up and operational functions. Up to two (2) remote interface controllers can be used on one Wine Guardian Cabinet unit.
Remote Temperature/Humidity Sensor
The remote temperature/humidity sensor is intended to provide a means of sensing one or more locations within the wine cellar and designed to work in conjunction with the Remote Interface
Controller or Local Interface Controller integral to the Wine Guardian Cabinet system. Multiple sensor readings are averaged and controlled to a single point. The sensors do not have any temperature or humidity indication and must be mounted within the cabinet.
Heater Option
The electric heat option includes an integral electric heating element, thermal overload protection device and controls. The Wine Guardian will either cool or heat the air, but it is not designed to do both at the same time. The Wine Guardian electric heat option must be specified at time of order and installed at our factory.
11
Humidity Option
NOT AVAILABLE
Overview of the Wine Guardian Unit
Refer to illustrations on page 14
Cabinet – The cabinet is constructed of aluminum for corrosion protection and maintenance-free appearance. Areas in contact with cold temperatures are lined with insulation to prevent condensation.
Condensing Section - Ambient air is circulated through the condenser section by a direct drive, permanently lubricated, motorized impeller blower. This section also contains the compressor and the electrical controls.
Evaporator Section – Cabinet air is circulated through the evaporator section by a direct drive, permanently lubricated motorized impeller blower. The large evaporator coil face area eliminates condensate carry-over, reduces air pressure drop and optimizes heat transfer. A drain pan is located directly below the coil to capture condensate and is fabricated from aluminum to prevent rust and corrosion.
Electrical Controls –All solid state electronic controls are connected internally and/or externally through an RJ9 phone cord-type connection. There is no need to open the chassis to access the factory mounted and wired control. All internal wiring is in accordance with the National Electrical
Code. Wires are numbered and color coded to match the wiring diagrams.
Factory Tested – All Wine Guardian units are factory run-tested and checked for operational performance.
Internal Drain – Condensate from the evaporator coil is directed to the condensate removal system at the condenser end of the unit. This allows the drain pan to drain freely.
Refrigerant Circuit – The factory-charged circuit includes a capillary tube expansion device, a filter dryer, and a manual reset high pressure switch.
12
13
CAB018
14
Cabinet Unit
CAB018 and CAB25
15
Safety
The following is suggested before installing or maintaining the Wine Guardian System:
1) Read these instructions
2) Keep these instructions
3) Heed all warnings
4) Follow all instructions
Safety Message Conventions
Safety messages contained in this manual, DANGER, WARNING, and CAUTION are bold and highlighted in red for quick identification.
Danger
A DANGER message indicates an imminently hazardous situation which, if not avoided, results in death or serious injury. Messages identified by the word DANGER are used sparingly and only for those situations presenting the most serious hazards.
DANGER
HIGH VOLTAGE - RISK OF SERIOUS INJURY OR DEATH
High voltages are present in the cabinets
TURN OFF ALL POWER BEFORE OPENING PANELS
USE THE LOCKOUT/TAGOUT PROCEDURE
Warning
A WARNING message indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Following is a typical example of a WARNING message as it could appear in the manual:
WARNING
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT Modification to the equipment may cause injury.
Caution
A CAUTION message indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices.
Following is a typical example of a CAUTION message as it could appear in the manual:
CAUTION
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Improper installation may result in the equipment malfunctioning and a safety hazard. Read all of the installation instructions before installing the Wine Guardian.
16
Lockout/Tagout Procedure
1) Turn the system to off at the remote interface controller (the display will
indicate the system is off).
2) Unplug the unit from the electrical outlet and cover the outlet to prevent
accidently plugging in the system.
Safety Considerations
The equipment covered by this manual is designed for safe and reliable operation when installed and operated within its designed specifications. To avoid personal injury or damage to equipment or property when installing or operating this equipment, it is essential that qualified, experienced personnel perform these functions using good judgment and safe practices. See the following cautionary statements.
Installation and maintenance of this equipment is to be performed only by qualified personnel who are familiar with local codes and regulations, and are experienced with this type of equipment.
Safety Hazards
Exposure to safety hazards is limited to maintenance personnel working in and around the system. When performing maintenance, always use the Lockout/Tagout procedure, which is described in this chapter. Observe the maintenance safety guidelines in the Wine Guardian manual.
IMPORTANT
The equipment described in this manual uses electricity. When using this equipment, be sure to follow the safety procedures outlined in the
Wine Guardian manual.
Electrical Hazards
Working on the equipment may involve exposure to dangerously high voltage. Make sure you are aware of the level of electrical hazard when working on the system. Observe all electrical warning labels on the system.
Electrical Shock Hazards
All power must be disconnected prior to installation and servicing this equipment. More than one source of power may be present. Disconnect all power sources to avoid electrocution or shock injuries.
Hot Parts Hazards
Electric Resistance heating elements (if equipped) must be disconnected prior to servicing. Electric heaters may start automatically, disconnect all power and control circuits prior to servicing the system to avoid burns.
17
Moving Parts Hazards
The Motor and Blower must be disconnected prior to opening access panels. The motor can start automatically. Disconnect all power and control circuits prior to servicing to avoid serious injuries or possible dismemberment.
The fans are free-wheeling after the power is disconnected. Allow the fans to stop completely before servicing the system to avoid cuts or dismemberment.
Rotating Fan Blades are present in the Wine Guardian system. Sticking a hand into an exposed fan while under power could result in serious injury. Be sure to use the Lockout/Tagout procedure when working in this area or remove the power cord.
Equipment Safety Interlocks
There are no electrical safety lockouts installed within the system. The power cord attached to the control box must be disconnected from the power sources prior to working on any part of the electrical system.
On/Off Switch
To shut down all high volt power internally, the power cord must be removed from power outlet.
Energy Type Voltage
Hazard ....................................................................... Electrocution, electrical burns and shock
60Hz Magnitude ..................................................... 120 Vac and 230 Vac, 1 phase, 60 cycles
50Hz Magnitude ..................................................................... 220/240 Vac, 1 phase, 50 cycles
Control Method ....................................................... Disconnect power cord and On/Off Switch
DANGER
• Never reach into the system while the fan is running.
• Avoid risk of fire or electric shock.
Do not expose the system to rain or moisture .
WARNING
• All supports for the system must be capable of safely supporting the equipment’s weight and any additional live or dead loads encountered.
• All supports for the system nances.
must be designed to meet applicable local codes and ordi-
• Do no t remove access panels until fan impellers have completely stopped. Pressure developed by moving impellers can cause excessive force against the access panels.
• Fan impellers continue to turn (free-wheel) after the power is shut off.
CAUTION
• Do not block any supply or return air opening. Install in accordance with the instructions in the Wine Guardian manual.
18
• Protect the power cord from being walked on or pinched, particularly at the outlet plug, convenience receptacles, and the point where it exits the system.
• Only use attachments/accessories specified by the manufacturer.
• Always operate this equipment from a 120Vac, 1 phase 60Hz power sources only . For
50Hz equipment 220/240Vac, 1 phase 50Hz power sources only.
• Always ground the outlet to provide adequate protections against voltage surges and built-up static charges (see Section 810 of the National Electric Code).
• Refer all servicing to qualified service personnel.
Servicing is required when the system has been damaged in any way, such as:
Power supply cord or plug is damaged
Liquid has been spilled or objects have fallen into the system
The system has been exposed to rain or moisture
The system does not operate normally
The system has been dropped
19
Installation
CAUTION
SHARP EDGES
RISK OF SERIOUS INJURY
Sharp edges are present inside the Wine Guardian system.
Pre-installation Test
Test the system before installing it to check for non-visible shipping damage.
To test the system:
Set the system on the floor or a sturdy level surface
Plug in the system
Plug the control cable into either COM1 or COM2 at the unit
Press the on/off button at the remote user interface
The built in timer prevents short cycling and keeps the system from turning on right away. The system comes on and runs as long as the temperature of the space is above the thermostat set point. After several minutes, cold air comes out of the system from the evaporator section side and hot air comes from the condenser section. Listen for any unusual noise or vibration.
Air Flow Illustration
20
WARNING
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Modification to the equipment may cause injury or damage
to the equipment
.
DANGER
This equipment is heavy. Place the unit on the floor or on a level and stable surface that can support the full weight of the unit.
Do not modify the equipment, it may cause damage to the equipment and voids the warranty.
Never place anything on top of the unit.
Never block or cover any of the openings or outlets to the unit.
Never allow anything to rest on or roll over the power cord.
Never place the unit where the power cord is subject to wear or abuse.
Do not use extension cords.
Never overload wall outlets.
Do not remove or open any cover unless the unit is turned off and the power cord is plugged in.
Use only dedicated power outlet boxes of the correct capacity and configuration for the unit model.
CAUTION
RISK OF PERSONAL INJURY OR DAMAGE TO EQUIPMENT
Improper installation may result in the equipment malfunctioning and a safety hazard. Read all of the installation instructions before installing the Wine Guardian unit
Planning the Installation
Tools required
Drill/Phillips head Level Stud finder Tape measure Square Drywall screws
21
Urethane caulk Hand saw Drywall saw Heavy duty
s nap knife
Where to locate the unit? Above the cabinet or below the cabinet.
How to mount above or below the unit? Where the supply/return opening are located.
Locate the electrical power outlet close to the unit, above cabinet or below. Do not use an extension cord!
Does the condenser heat exhaust need to be ducted away? An optional duct collar is available.
Where to locate the remote interface control? Remote interface controls should be located midpoint on a wall within the wine cabinet and provide sufficient access and exposure to airflow.
Are all the parts here to complete the installation? G asket, duct collars, fasteners
Performing a Pre-installation Check
Check for the properly sized breaker as dictated by the system rating plate data.
Is the cabinet built with adequate insulation and vapor barriers?
Locating the system
The Wine Guardian cabinet system can be mounted either above or below the cabinet. Coordinate supply and return air openings on the Wine Guardian System with that of the cabinet so that air is directed as needed in and out of the system without obstruction. Multiple condenser intake and exhaust locations provides flexibility in directing warm air in and out of the unit from ambient spaces. Gasket material is provided with the unit to assist in sealing the system to the cabinet enclosure.
Power cord location
The power cord is located at the side of the unit adjacent to the com port area. The Wine Guardian system ships complete with six (6) feet of 120 volt, 1phase, 6hz. removable power cord.
Evaporator Connections
Step 1 – locate supply and return opening penetrations at the cabinet ceiling (or floor if mounting unit below) and ensure the Wine Guardian system will fit location and match to the openings provided. If locations do not match to the openings at the Wine Guardian system then you may be required to install optional duct collars and ductwork to connect to the appropriate supply/return locations.
Step 2 - Top mount – place the foam gasket pad above the cabinet (on top of the ceiling) and position the openings in the gasket so that they coincide with the supply and return openings of the cabinet.
22
Bottom mount – re-locate the solid panels that cover the supply and return air openings on the top of the unit to the bottom of the unit. Next place the foam gasket on top of the Wine Guardian unit and align the two openings in the gasket with the supply and return openings on the unit.
Step 3 – Top mount – place the Wine Guardian system on top of the gasket and position the supply and return openings over the corresponding openings in the gasket so the penetrations line up with the cabinet.
Please note that you may need to adjust the position of the gasket and Wine Guardian system so that openings line up with each other and the cabinet structure.
Bottom mount – place the unit beneath the cabinet and adjust the position of the unit and gasket so that it lines up with the openings in the wine cabinet. Add shims or wooden supports under the unit so that the top of the Wine Guardian system is tight to the bottom of the cabinet and the gasket is compressed for a tight seal.
You may need to duct tape the inside of the opening between the wine cabinet, gasket and Wine Guardian unit so that the air way is sealed. This can be accomplished by applying the tape from inside of the cabinet.
Step 4 – Determine the ideal location to mount the Wine Guardian Remote Interface Controller within the wine cabinet and mark its mounting hole locations for future reference.
Step 5 - Route the RJ9 control cable provided with the Wine Guardian system from the cooling unit into the cabinet and to the location determined in step 4. Depending upon the construction of the cabinet you may need to drill a hole within the top or bottom of the cabinet to route the control wire to its controller location. Minimum hole diameter is 7/6” ( 2 cm) and the hole should be sealed once the wire has been installed. You may wish to hide the wire behind trim or in areas that are covered with lighting or racking.
Step 6 – install two screws at the mounting location of the Remote Interface Controller. Connect the RJ9 control wire to the back of the Remote Interface Controller and attach the controller to the cabinet at the screw locations by inserting them into the back of the controller and sliding the controller down so that it is seated.
Condenser Connections
Step 1 – Determine locations within the cabinet (front, side(s), top or back) where condenser air intake and exhaust will be connected. Optional duct collars and ductwork may be required for proper venting.
Step 2 – Condenser air intake can be connected at the top, front or back of the Wine Guardian cabinet system. Connect optional duct collar to one (1) of these three locations.
Step 3 – Connect 6” (15.24 cm) round ductwork to the duct collar and position the ductwork to the desired air intake location on the cabinet.
Step 4 – Condenser air exhaust can be connected at the top, front or back of the Wine Guardian cabinet system. Connect optional duct collar to one (1) of these three locations.
23
Step 5 - Connect 6” (15.24 cm) round ductwork to the duct collar and position the ductwork to the desired air exhaust location on the cabinet.
Turning on system
Step 1 - Plug the female end of the power cord into the connection at the Wine Guardian unit and the receptacle end into a 120 volt, 1 ph, 60 hz, (220 volt, 1 ph, 50 hz. for WGCAB25) dedicated circuit.
Step 2 – Turn the system on at the Remote Interface Controller by touching the on/off button once. You should hear the system turn-on and start to deliver cold air to the cabinet.
Step 3 – Visually inspect the installation for any air leaks at the supply and return locations.
Step 4 – Check system set point at Remote Interface controller by touching the any button on the touch screen to wake the system up. Once the display is bright touch the up arrow button to display the temperature set point. Adjust as needed to your preference.
Step 5 – The Wine Guardian cabinet system is now installed and should cool the cabinet to your desired set point. Please note that initial run time may vary depending upon the loading of wine and its initial temperature. Once the cabinet and wine is brought to set point normal run time should be 15 to 20 minutes per hour.
Wiring the System for Power
WARNING
ELECTRICAL SHOCK HAZARD
The electrical outlet and wiring installation must meet the national and local building codes.
DO:
Match the electrical outlet to the plug provided on the Wine Guardian.
Provide dedicated circuit and wiring for the system.
Match the wiring and breaker size to the rated load as shown on the serial plate and in this guide. See sample serial plate illustration below.
DO NOT:
1.
DO NOT MODIFY THE PLUGS IN ANY WAY!
2.
Do not use extension cords.
24
IMPORTANT
The electrical power supply must be 115-volt AC 1 phase 60 cycle (240-volt AC 1 phase 50 cycle), depending on the model of the system, and cannot vary more than +/- 4% or damage may occur to the unit.
Plug the system into the wall outlet. Gently pull on the plug to make sure it is tight.
Electrical Plug Configuration 60Hz Models Only
Detachable UL/CSA 120 volt/1ph/60 hz. power cord rated for 15 amp service with NEMA 5-15P type plug and IEC 60320 C-13 Connector type at Wine Guardian unit. Power cord is 80” long and includes an SJT 3 wire
14-gauge cable. Color: Black. RoHS compliant.
Electrical Plug Configuration 50Hz Models Only
Detachable 250 volt/1ph/50 hz. power cord rated for 10 amp service with CEE
7 Sheet VII type plug and IEC 60320 C-13 Connector type at Wine Guardian unit. Power cord is 80” long and includes an H05VV-F 3 wire 1.00 sq.mm cable. Color: Black. RoHS compliant.
25
Starting-up and Operating the Wine Guardian
Control Settings
The control has been wired and set up in the factory for testing with default settings. It is an electronic digital thermostat for one-stage cooling. No additional adjustments should be necessary except adjusting the cellar temperature to your preference. If additional adjustments or changes are necessary, please refer to the configuration settings section in this manual.
Controller Functions
ON/OFF – The ON/OFF button will be used to turn the system on or off. When set to the off mode the control will not allow any of the outputs to energize effectively locking the system out. It will not allow any outputs to energize until the system is turned on with the ON/OFF button. It should be noted that high voltage will still be present at the main control board when the system is set to off even though the control will not allow it to switch to the outputs.
UP Arrow – The UP arrow will allow the user to increase settings.
DOWN Arrow – The DOWN arrow will allow the user to decrease settings.
SETTINGS – The setting button will be used to select between HEAT, COOL and AUTO MODE, as well as entering the configuration settings. Holding the SETTINGS button for 5 seconds will enter configuration mode. Once in configuration mode the user can adjust settings by pressing the
UP or DOWN arrows. Pressing the SETTINGS button once will advance to the next configuration settings. Holding the SETTINGS button for 5 seconds while in configuration mode will store all changes and exit configuration mode.
For cooling operation only: Cooling for 60Hz models is set at 55°F from the factory and 13°C for
50Hz models . This can be changed by hitting the UP or DOWN arrow, but please refer to configuration settings # 2 and # 3 for limitations in comparison to the High and Low temperature alarm settings.
For units with optional humidifier controlled by TTW WG: The RH% is factory set at 55%.
This can be changed by referring to configurations setting # 6. If no humidifier is attached, the control will read RH%, but will not be controlling it.
Changing fan operation: The default setting from the factory is “AUTO” fan. If desired it can be changed to fan “ON” by accessing configuration setting # 7.
26
Standard Controller Functions
“Cool” Symbol
“Heat” Symbol
Settings and
Defrost Area
Temperature
How to:
Turn system on/off
On/Off Button
Change temperature
Up Button
Change humidity
27
Change Settings
Cooling/
Heating / Auto
Alarms
Battery Life
Humidity
Down Button Settings Button
Press the “On/Off” button once.
Note: There is a five (5) minute time delay before the system turns on or turns off.
Press the “Up” arrow once. The display will show the existing temperature setpoint.
Press the up or down arrow buttons to adjust the temperature to the desired set point.
Press the “Up” arrow once. This display will show the existing temperature setpoint.
Press the “Settings” button once to display the “Humidity” setpoint.
Press the “Up” or “Down” arrows to adjust the humidity to the desired set point.
Note: A Wine Guardian humidifier must be installed and Setting 6 set to “1” or “2” before the controller will let you change percent humidity.
Press the Setting button once to display the setting function at the bottom of the screen.
Press the Settings button again to scroll through settings for cool only, heat only or heat/cool only – auto mode.
Settings – Press and hold the “Settings” button for five (5) seconds to access the following settings .
Degrees F or
Degrees C Press the “Up” arrow to change temperature from °F to °C.
Press the “Down” arrow to change temperature from °C to °F.
Low temperature alarm setpoint
Setting 2
Press “Settings” button to advance to
Setting 2.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. Factory default is 50°F (10°C).
Setting 3
Press “Settings” button to advance to
Setting 3.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. Factory default is 65°F (18°C).
High temperature alarm setpoint
Low humidity alarm set point
High humidity alarm setpoint
Add or remove humidifier
Setting 4
Press “Settings” button to advance to
Setting 4.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. Factory default is 5%.
Setting 5
Press “Settings” button to advance to
Setting 5.
Press the up or down arrow buttons to
adjust to the desired setpoint. Factory default is 95%.
Setting 6
Press “Settings” button to advance to
Setting 6.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. Factory default is zero (0).
Zero (0) = No humidifier
One (1) = Integral Wine Guardian mounted humidifier
Two (2) = Stand-alone remote mounted humidifier
28
Setting 7
Press “Settings” button to advance to
Setting 7.
Press the “Up” or “Down” arrow buttons to adjust number to the desired set point.
Factory default is zero (0).
Zero (0) = Auto–fan only turns on when there is a call for cooling or heating
One (1) = Fan On–fan remains on continuously
Setting 8
Press “Settings” button to advance to
Setting 8.
Press the “Up” or “Down” arrow buttons to adjust to the desired time in one-minute increments. Maximum is 10 minutes, minimum is 3 minutes. Factory default is 5 minutes.
Compressor anti-short cycling time is the amount of allowable time between compressor stop and restart. Rapid start/stop of compressors can cause premature failure.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER
THAN FACTORY DEFAULT.
Setting 9
Press “Settings” button to advance to
Setting 9.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint.
1 will equal enabled and a 0 (zero) will equal disabled.
Setting 10
Press "Settings" button to advance to
Setting 10.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. This setting is adjustable from 25°F to 40°F.
Factory default is 39°F.
There must be at least a 1°F difference between defrost cut-in and cut-out set points.
29
RH offset
30
Setting 11
Press "Settings" button to advance to
Setting 11.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. This setting is adjustable from 35°F to 50°F.
Factory default is 40°F.
Note: This setpoint must be 1°F/°C higher than setting 10.
Note: If °C is selected and then switched back to °F the default cut-out will change to 41°F.
Setting 12
Press "Settings" button to advance to
Setting 12.
Press the “Up” or “Down” arrow buttons to adjust to the desired setpoint. This setting is adjustable from 30 min at 0
(zero), 1 hour at 1, and then in 1 hour increments up to a maximum of 12 hours at 12.
Setting 13
Press “Settings” button to advance to
Setting 13.
Press the “Up” or “Down” buttons to adjust to the desired set point. Maximum setting is +5°F, minimum setting is -5°F.
Factory default is zero (0).
Room temperature offset changes the actual display reading (temperature only) by the value of this setting.
Example: Sensor reading = 55°F (13°C)
Setting 15 set to +4
Display reading = 59°F (15°C)
Setting 14
Press “Settings” button to advance to
Setting 14
Press the “Up” or “Down” buttons to adjust to the desired setpoint. This setting allows the adjustment of %RH reading by
+/-10%. Factory default is 0%RH.
31
Reserved
Reserved
Setting 15
Press “Settings” button to advance to
Setting 15
Press the “Up” or “Down” buttons to adjust to the desired setpoint. This setting changes the system/compressor turn-on temperature above setpoint. Factory default is 1°F.
Example: Sensor reading = 55°F (13°C)
Setting 17 set to +3°F
System/compressor turns on at 58°F
(14°C)
Setting 16
Press “Settings” button to advance to
Setting 16.
Press the “Up” or “Down” buttons to adjust to the desired setpoint. This setting is the minimal allowable temperature difference between heating and cooling setpoints. Maximum is 5°F (3°C), minimum is 1°F (1°C). Factory default is
2°F (1°C).
Setting 17
Press “Settings” button to advance to
Setting 17.
Press the “Up” or “Down” buttons to adjust to the desired setpoint. This setting disables or enables the Condensate switch.
0 (zero) is disabled, 1 is enabled. Factory default is 0.
Settings 18 & 19
Reserved for additional fields.
Setting 20
System setting. DO NOT CHANGE.
Settings 21-29
Reserved for additional fields.
Define remote user interface
RF channel select
Reserved
Thermistor 1
N/A
32
Thermistor 2
N/A
Thermistor 3
N/A
Setting 30
Press “Settings” button to advance to
Setting 30
Press the “Up” or “Down” buttons to adjust to the desired setpoint.
1 = Remote User interface #1 mounted within the wine room space and enabled
2 = Remote User interface #2 mounted within the wine room space and enabled
3 = Remote User Interface #1 disabled - will display only and can be mounted outside of wine room
4 = Remote User Interface #2 disabled - will display only and can be mounted outside of wine room
Setting 31
Press “Settings” button to advance to
Setting 31.
Press the “Up” or “Down” buttons to adjust to the desired setpoint.
Each system needs all devices to be on the same RF channel.
0 = RF disabled - system must be hardwired
1 through 12 = RF enabled and 12 channels available
Settings 32-39
Reserved for additional fields.
Setting 40
NOT AVAILABLE
Reserved for thermistor
Setting 41
NOT AVAILABLE
Reserved for thermistor
Setting 42
NOT AVAILABLE
Reserved for thermistor
33
Thermistor 4
Reserved
Output test
Reserved
Default temperature
Default %RH
Default mode
Setting 43
Press “Settings” button to advance to
Setting 43.
No setting adjustment.
Displays the defrost sensor temperature.
Setting 44-49
Reserved for additional fields.
Setting 50
Press “Settings” button to advance to
Setting 50.
Press the “Up” or “Down” buttons to adjust to the desired setpoint.
Steps through relays as output test.
0 = Disabled
1 = Enabled
Setting 51-69
Reserved for additional fields.
Setting 70
Press “Settings” button to advance to
Setting 70.
No setting adjustment.
Initial temperature set point. Will revert to this setting upon loss of power.
Setting 71
Press “Settings” button to advance to
Setting 71.
No setting adjustment.
Initial relative humidity set point. Will revert to this setting upon loss of power.
Setting 72
Press “Settings” button to advance to
Setting 72.
Press the “Up” or “Down” buttons to adjust to the desired setpoint.
Initial mode set point. Will revert to this setting upon loss of power.
1 = Auto
2 = Cool
3 = Heat
Alarm Codes
High temperature alarm
Flashing temperature number
Low temperature alarm
Flashing temperature number
High humidity alarm
Flashing humidity number
Low humidity alarm
Flashing humidity number
!1 = High Pressure
Switch Fault
!2 = CS (Condensate
Switch Fault)
34
Flashing temperature number along with
(!) symbol will remain on screen until temperature falls below the High
Temperature Alarm set point (Setting 3).
Flashing temperature number along with
(!) symbol will remain on screen until temperature rises above the Low
Temperature Alarm set point (Setting 2).
Flashing humidity number along with
(!) symbol will remain on screen until humidity falls below the High Humidity
Alarm setpoint (Setting 5).
Flashing humidity number along with
(!) symbol will remain on screen until humidity rises above the Low Humidity
Alarm set point (Setting 4).
THIS ALARM FORCES THE
SYSTEM TO SHUT DOWN
(!1) will remain on screen until the High
Pressure reset switch has been reset.
See the trouble shooting guide page 57 for “Instructions to Reset High Pressure
Switch”.
THIS ALARM FORCES THE
SYSTEM TO SHUT DOWN
(!2) will remain on screen until the CS
(condensate switch) fault is resolved and reset.
!3 = Defrost Sensor
Fault
THE SYSTEM REMAINS
OPERATIONAL DURING THIS
ALARM
Defrost sensor has been shorted, disconnected or open.
(!3) will remain on screen until the defrost sensor issue has been resolved.
!4 = Communication loss
THE SYSTEM REMAINS
OPERATIONAL DURING THIS
ALARM
Bad or no data transfer between sensing device and main control board.
“!4” will remain on screen until communication is re-established.
!WARNING!
Only one Unit can be set up at a time. Ensure other units are unplugged while pairing a unit to ensure there are no communication issues between Wine Guardian Units
35
Installing the Optional Remote Interface Controller and
Communication Cable
The Wine Guardian Wireless-to-base Remote Interface
Controller is a combination temperature and humidity controller with single stage cooling, heating and humidity control. It’s capacitive touch screen incorporates an on/off switch, adjustment arrows and settings buttons for ease of use and programming. The controller can be installed one of two ways:
Wired (recommended)
– wired directly to the Wine Guardian unit through an RJ-9 communication cable. 50’ (15.25 meters) of control cable is included with each controller with longer lengths available as an option.
IMPORTANT
Whenever possible we strongly suggest wiring the Remote Interface Controller directly to the Wine Guardian unit to avoid periodic battery changes and uninterrupted service.
Wirelessly -
connects wirelessly to the Wine Guardian unit by Radio Frequency connectivity through one of twelve selectable channels.
IMPORTANT
Wireless installation may result in limited communication range and connectivity issues depending upon building construction and distance between Wine Guardian unit and Remote Interface Controller and/or
Remote Sensors.
The Wine Guardian Wireless-to-base Remote Interface Controller is a configurable device that can be fine-tuned through a series of individual settings. The controller incorporates eight (8) key temperature, humidity and system alarm points. Remote alarm indication is possible through terminal point connections at our main control board.
In most applications, the remote interface controller will be mounted within the wine cellar. The remote interface controller can also be mounted directly outside of the wine cellar or in any other room of the home or building. When mounted outside of the wine cellar, a remote sensor kit or a second wireless remote interface must be purchased and installed within the wine cellar.
Additional Remote Interface:
IMPORTANT
36
Regardless of wired or wireless each, Wine guardian System can have a maximum of two (2) Remote Interface
Controllers and three (3) Remote Sensors.
37
Additional Remote Interface:
If adding more than one remote interface to the system, you will have to change setting 30 at each remote user interface controller to define its use. Refer back to page 27 for instructions on how to access the interface Settings, and get to Setting 30 (shown on page 32).
Controller Specification
Application WG only, single stage cooling or heating
Humidification
No Programmable
Change over
Color
User interface
Auto defrost control
Connection
Wireless-to-base communication range
Wireless-to-base channels
Remote sensors
Temperature adjustment
Temperature tolerance
Humidity adjustment
Humidity tolerance
System temperature diagnostics
Alarms
Auto or manual, Fan ON or AUTO
Black (only)
Touch screen
Yes, with Serving temp option
Communicating – RJ-9 cable
40’ line of site
12
Yes, wired or wireless
34 to 97 Deg F (1 to 36 Deg C)
+/- 2 Deg F (+/- 1.1 Deg C)
2% to 93% RH
+/- 10% RH
Not available
High temp, low temp.
High humidity, low humidity.
High pressure fault.
Condensate, Defrost and Communication error
Mounting the Optional Remote Interface Controller (Wired)
Fig. 1
1. Disconnect the communication cable from the Wine Guardian unit and the remote interface controller. (Fig. 1) a. Route the communication cable within the wall and/or ceiling structure of the wine cellar to the desired controller mounting location. b. Plan on mounting the remote interface controller on a solid surface away from doors, corners, air outlets, drafts or heat generating equipment. Do not mount the remote interface controller directly on an outside wall, a wall adjacent to a boiler room, or other hot area. Use a piece of foam insulation behind the sensor to insulate it from a hot or cold surface. The recommended height is four to five feet above the finished floor.
Fig. 2
Fig. 3
Fig. 4
2. Remove the back plate of the controller (Fig. 2) by removing two (2) screws that hold it in place on the remote interface. Place the back plate against the wall and mark the location of the two mounting points (Fig. 3).
Also mark the location of the penetration for the communication cable as this area will require sufficient clearance for the cable to exit the wall and attach to the back of the controller.
3. Drill two one-eighth inch holes and insert anchors at the marked locations. Anchors may not be required if securing to a wall stud or racking system. Insert the screws into the holes and test fit the backing plate to ensure it mounts easily onto the two screws and slides down onto the slotted opening freely (Fig. 4).
4. Re-install plastic face plate on to backing plate.
38
Fig. 5
5. Plug in the communication cable to the back of the remote interface controller backing plate. (Fig. 5) a. If using multiple Remote Interfaces either connect each Sensor to each other in series using RJ-9 cable or purchase a RJ-9 Splitter to be used on the unit.
6. Attach the Controller to the wall
7. Re-attach the communication cable to the back of the
Wine Guardian cooling unit.
Mounting the Optional Remote Interface Controller (Wireless)
Fig. 1
1. Disconnect the controller wire from the side of Wine
Guardian unit and save for future use.
2. Plan on mounting the remote interface controller on a solid surface away from doors, corners, air outlets, drafts or heat generating equipment. Do not mount the remote interface controller directly on an outside wall, a wall adjacent to a boiler room, or other hot area. Use a piece of foam insulation behind the sensor to insulate it from a hot or cold surface. The recommended height is four to five feet above the finished floor.
Fig. 2
3. Unscrew and remove the back plate from the
Remote Interface Controller (Fig. 1)
4. Place the back plate against the wall and mark the mounting points at the desired location. (Fig. 2)
5. Drill two one-eighth inch holes and insert anchors within the mounting surface. Anchors may not be required if securing to a wall stud or racking system.
Insert the screws into the holes and test fit the backing plate for mounting to ensure it mounts easily onto the two screws and slides down onto the slotted openings freely (Fig. 3)
Fig. 3
6. Reattached the back plate to the Remote Interface
Controller. (Fig. 4)
Fig. 4
7. Insert the three AA batteries.
(only applicable with wireless installations)
8. The system will automatically acknowledge a wireless device (Remote Interface or Remote
Sensor). Go to Setting “30” to define the Remote
User Interface use.
9. Attach controller to the wall.
39
Fig. 2
40
Installation of the Optional Wine Guardian Remote Sensor
The wireless remote sensor is a combination temperature and humidity sensor only. It is designed to be mounted within the wine cellar and can be used in combination with the remote interface controller or up to two additional remote sensors to read and control multiple areas within the wine cellar.
For a wired application you will require a RJ-9 communication cable.
Mounting the Wired Remote Sensor (Wired)
Fig. 1
1.
Disconnect the communication cable from the back of the Wine Guardian unit and the remote sensor. Route the communication cable within the wall and/or ceiling structure of the wine cellar to the desired controller mounting location.
2.
Plan on mounting the remote sensor on a solid surface away from doors, corners, air outlets, drafts or heat generating equipment. Do not mount the remote sensor directly on an outside wall, a wall adjacent to a boiler room, or other hot area. Use a piece of foam insulation behind the sensor to insulate it from a hot or cold surface. The recommended height is four to five feet above the finished floor.
3.
Remove the remote sensor’s face plate (Fig. 1) and mark the mounting points at the desired location within the wine cellar (Fig. 2). Also, mark the location of the communication cable connection as this area will require sufficient clearance, for the cable to exit the wall and attach to the back of the sensor.
Fig. 3
Fig. 4
Fig. 5
41
6.
7.
5.
4. Drill two one-eighth inch holes and insert anchors within the mounting surface. Anchors may not be required if securing to a wall stud or racking system. Insert the screws into the holes and test fit the backing plate for mounting to ensure it mounts easily onto the two screws and slides down onto the slotted openings freely. (Fig. 3)
Plug in the communication cable to the remote sensor and mount the Remote Sensor to the wall. (Fig. 3)
Reattach the sensor’s faceplate (Fig. 4)
If multiple sensors are being used either connect each Sensor to each other in series using RJ-9 cable or purchase a RJ-9 Splitter
(Fig. 5) to be connected to the unit.
NOTE: Remote Sensor’s will always be treated as “enabled” when hardwired. Their temperature and humidity readings will always be calculated towards the average by the system .
Mounting the Remote Sensor (Wireless)
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5
1.
Disconnect the controller wire from the side of Wine
Guardian unit and save for future use.
2.
Plan on mounting the remote sensor on a solid surface away from doors, corners, air outlets, drafts or heat generating equipment. Do not mount the remote sensor directly on an outside wall, wall adjacent to a boiler room, or other hot area as this runs the risk of influencing its temperature readings. The recommended height is four to five feet above the finished floor.
3.
Remove the sensor face plate (Fig. 1). Mark the mounting points at the desired location within the wine cellar (Fig. 2).
4.
5.
6.
Drill two one-eighth inch holes and insert anchors within the mounting surface. Anchors may not be required if securing to a wall stud or racking system.
Insert screws to secure the sensor to the wall to ensure it mounts easily onto the two screws and slides down onto the slotted openings freely.
Input the three AA batteries. (Fig. 3)
(only applicable with wireless installations)
Pair the sensor with the unit
(See Page 46 for Pairing Instructions)
NOTE: Once Paired the Remote Interface’s readings will be included into the system’s temperature and humidity averages.
7.
Mount the Remote Sensor on the wall (Fig. 4)
8.
Reattach the sensor’s faceplate (Fig. 5)
42
Fig. 2
Remote Sensor Pairing Instructions – Multiple Sensors (Wireless)
Fig. 1
If using multiple remote temperature/humidity sensors in your application, refer to the figures and the procedure below to change each remote sensor’s device number (Three Remote Sensors maximum). Each Remote Sensor must have its own device number and must also be on the same RF channel (Setting 31) as the system they are being paired with.
1.
To change the remote sensor’s device number, see the following instructions: a.
Use a pin to press the button for about half a second and release (Fig. 1).
b.
Observe the LED on the side of the remote sensor (Fig. 2).
The LED will flash once for a Device #1, twice for a #2, three times for a #3. At any time, while in this mode press the button once to change the device number. Once each remote sensor has its own unique device number simply wait for the LED to stop flashing and the setting will be saved.
2.
To change the remote sensor’s RF channel, see the following instructions:
NOTE: Check what RF Channel the System is set to using Setting 31 to more easily connect your Remote
Sensors.
a.
Use a pin to press the red button at the back of the Remote
Sensor for 5 seconds until the LED blinks rapidly then release the button. b.
The LED will flash a number of times to portray which RF channel it is set to and repeat a total of 3 times. c.
To change the RF channel, press the button once to increment the RF channel. There are 12 possible RF channels. All Remote Sensors will need to be on the same channel for the system to detect them. To save the RF channel setting simply wait for the mode to time out by not pressing the button.
43
Regulating the Cabinet Temperature
To keep the entire cabinet at the same temperature, set the thermostat to run the supply fan continuously, and not just when there is a call for cooling. Set Fan switch to ON instead of
AUTO, by accessing configuration setting # 7.
Maintenance
WARNING
BEFORE PERFORMING MAINTENANCE ON THE SYSTEM, READ AND UNDERSTAND THE SAFETY
INFORMATION CONTAINED WITHIN THE SAFETY CHAPTER OF THE WINE GUARDIAN MANUAL.
DANGER
HIGH VOLTAGE - RISK OF SERIOUS INJURY OR DEATH
High voltages are present in the cabinets. Turn off all power. Use the Lockout/Tagout procedure before removing end panels or cover.
CAUTION
SHARP EDGES
RISK OF SEROUS INJURY
SHARP EDGES ARE PRESENT ON THE FAN WHEELS, HOUSEING, INS AND COILS.
Maintenance on Wine Guardian system requires working with high voltage and sheet metal with possible sharp edges. Only qualified personnel should perform maintenance. Some tasks require knowledge of mechanical and electrical methods. Make sure you are familiar with all hazards, general safety related procedures, and safety labels on the system
CAUTION
EXPOSURE TO MICROBIAL GROWTH (MOLD) CAN CAUSE SERIOUS HEALTH PROBLEMS
Standing water in drain pans promote microbial growth (mold) that cause unpleasant odors and serious health-related indoor air quality problems. If mold is found, remove it immediately and sanitize that portion of the system.
The Wine Guardian is designed for minimum maintenance. The refrigerant system is hermetically sealed and requires no maintenance. The fans are permanently lubricated and require no maintenance. Some maintenance to the system may be required due to dust or dirt in the air stream.
44
Maintenance Schedule
Monthly
(Or quarterly depending on experience with individual cellar)
Check for noise or vibration.
Check for short-cycling of the system – a turning on and off of the compressor unit more than eight (8) times/hour.
Yearly
(In addition to monthly)
Check evaporator and condenser coils for dirt – use a vacuum with a brush attachment to clean the coils.
Clean condensate pan under the evaporator coil by flushing. Be careful to keep the drain pans clear of any and all debris.
Inspect cabinet for corrosion or rusting – clean and paint.
Inspect for dirt buildup on or inside the unit. Clean system by vacuuming or wiping it down.
Check for loose insulation, fasteners, gaskets or connections.
Check the wiring connections and integrity or cords.
Examine condenser duct (if option is used) for any cracks or breach.
45
High Pressure Switch Has Shut the System Down
Every Wine Guardian system has a manual reset high pressure switch in the refrigeration system.
This switch shuts the compressor and condenser down if the head pressure in the system is too high. It is intended to protect the compressor. Restricted airflow through the condenser is the most common reason for the pressure to become too high. This can be caused by dust covering the coil or an obstruction blocking the airflow in the duct or grille.
Possible Cause
Head pressure in unit is too high because an obstruction is restricting air flow through the unit.
Solution
Remove the obstruction in the duct or grille or clean the coil. Then restart the system after resetting the high-pressure switch.
Instructions to Reset High Pressure Switch
Turn the Wine Guardian system off at the remote interface controller.
Locate the high pressure reset switch behind the circular black plastic cove at the condenser side of the system. The switch has a red push button and is accessible by removing the plastic cover.
Locate red push and push in the button until it locks into position.
Replace circular black plastic cover.
Restart the unit at the control panel remote interface controller.
Alarm Annunciation
When an alarm condition occurs, the control will flash the backlight on the display in addition to annunciating the actual fault on the screen. The user can make the backlight flashing stop by pressing a button on the local user interface. However, the alarm annunciation will not actually clear on the display until the fault is corrected.
46
Troubleshooting
WARNING
BEFORE PROCEEDING, READ AND UNDERSTAND THE SAFETY INFORMATION CONTAINED
IN THE SAFETY SECTION OF THE WINE GUARDIAN MANUAL.
IMPORTANT
This section is intended as a diagnostic aid only. For detailed repair or parts replacement procedures, contact a qualified service company. Check the following table for some solutions before calling a service technician.
Typical Start-up Problems
Possible Cause
Incorrect thermostat or humidistat
Changed settings on the thermostat
Solution
Check the thermostat and humidistat setup for the application. Read the thermostat troubleshoot guidelines in the
Thermostat Installation and Operating
Instructions.
A common problem is not waiting long enough for the internal timers to complete their timed delay. Allow 5 minutes for compressor to start.
Unit Does Not Start-up
Thermostat light is off
Possible Cause
No power to outlet
Unit not plugged in
Thermostat light is on
Possible Cause
Remote interface controller is not set up properly
Solution
Check circuit breaker and wiring
Plug in the unit
Solution
Check remote interface controller set up in the guide
47
Unit is Operating and Blows Evaporator Air, but the Supply Air is not Colder than the Return Air from the Cellar
Possible Cause
Remote interface controller not set up properly
Compressor not operating
Condenser airflow is blocked
Head Pressure (HP) switch is open
Solution
Check remote interface controller setup in the manufacture’s remote interface controller guide
High pressure switch open (button up) (see below)
Remove blockage
Clean coil (if needed)
Reset HP switch – see reset instructions on page 45
Problems Controlling Cellar Temperature
**Problems are occurring even though the unit seems to be fully operational – evaporator fan blows air into the cellar and compressor and condenser fans run
Cellar temperature is low (below 51° when unit is running Solution
Possible Cause
Remote interface controller set too low on cooling
Remote interface controller not controlling temperature
Cellar temperature is too cold (below 51°) when unit is not running
Possible Cause
Reset remote interface controller to higher cooling temperature
Wiring integrity compromised (shorted), replace wiring
Solution
Too much heat loss to adjacent spaces Increase insulation around the ductwork and doorways - Add heater
Cellar temperature is too high, but supply air is cold
Possible Cause
Not enough evaporator airflow
Cellar heat loads are too high
Solution
Remove blockage in supply or return
Check and clean coil
Coil frozen – shut off unit for two hours
Install additional insulation Replace with larger sized unit
48
49
Problems Controlling Cellar Humidity
Humidity too low or supply air is too cold, without optional Standalone humidifier
Possible Cause Solution
Not enough evaporator airflow
Defective or incorrect expansion device or coils
Humidity too low, without optional humidifier
Possible Cause
Remove blockage in supply or return ductwork
Check and clean coil
Coil frozen – shut off system for two hours
Call factory for service
Solution
No moisture being added to cellar
Humidity too low with optional humidifier –
Possible Cause
Humidifier not operating
Humidifier operating
Humidity too high when unit is running, but not cooling
Possible Cause
Compressor not operating
Ambient temperature is too high
Add Wine Guardian humidifier or room humidifier
Solution
Check wiring for loose, broke or frayed connections
Check humidistat set up
Check for water flow & solenoid valve operation
Check for water being hot
Check drop pad – replace if scaled
No vapor barrier installed around cellar
Solution
Check and reset high limit switch
Clear blockage of condenser airflow
Reduce temperature or draw condenser air from another space
Problems Controlling Cellar Humidity
Humidity too high when unit is not running
Possible Cause
Solution
System needs to run to dehumidify Lower room temperature setpoint. Seal openings around doors (gasket and sweep)
50
Humidity too high when unit is running and cooling
Possible Cause Solution
Too much moisture in cellar Poor vapor barrier installation
Humidifier malfunction refer to the humidifier instructions
Add dehumidifier to surrounding space
Other Miscellaneous Problems
System is leaking water
Possible Cause Solution
Condensate pan plugged Remove blockage and clean
Unit not level Level with shims
System is running properly, but the sounds of unit is objectionable
Possible Cause
Solution
Noise is from airflow Duct airflow from condenser to outdoors
Manufacturer’s Warranty – U.S. and Canada only
Warranty outside of the U.S. is determined by the country. Refer to your distributor for your Wine Guardian warranty.
GENERAL
Wine Guardian warrants, to the original buyer, its goods and all parts thereof to be free from defects in material and workmanship for a period of two (2) years from the date of invoicing assuming NORMAL USE AND SERVICE.
LIABILITY
Wine Guardian liability shall be limited to the repair or replacement (at its option) of any part, which, at our sole discretion, is determined to be defective. Wine Guardian shall pay transportation costs to and from original “ship to” address for the replacement and/or return of defective equipment.
LIMITATIONS OF LIABILITY
THESE WARRANTIES ARE MADE IN LIEU OFF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING ANY
IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AND IN LIEU OF ANY OTHER
OBLIGATION OR LIABILITY, INCLUDING LIABILITY FOR ANY INCIDENTAL OR CONSQUENTIAL DAMAGES. Wine Guardian will not be responsible for any costs or liabilities whatsoever resulting from improper installation or service of its equipment. In the event that Wine Guardian or its distributors are found liable for damage based on any defect or nonconformity in the products, their total liability for each defective product shall not exceed the purchase price of such defective products. Wine Guardian will not be responsible for the removal of defective equipment or the installation of its replacement system. No person or representative is authorized to change these warranties or assume any other obligations or liabilities for Wine Guardian in connection with the sale of its systems.
INDEMNIFICATION
Purchaser agrees to indemnify, hold harmless and defend seller and its officers, directors, agents and employees from and against any and all claims, liabilities, costs and expenses arising out of or related to Purchaser’s use of the goods, or in any way involving injury to person or property or accident occasioned by the goods sold by Wine Guardian to Purchaser.
FOREIGN GOVERNMENT AND INDIAN NATIONS
If Purchaser is a foreign government or an Indian nation, Purchaser hereby expressly waives its defense of sovereign immunity in the event of a dispute between Purchaser and Wine Guardian regarding this invoice and Purchaser expressly acquiesces to the jurisdiction of the federal and state courts of the United States.
SEVERABILITY
If one or more of the provisions contained in this contract shall for any reason be held to be invalid, illegal or unenforceable in any respect, such invalidity, illegality or unenforceability shall not affect any provision of this contract, but this contract shall be construed as if such invalid, illegal or unenforceable provision had never been contained.
ADDITONAL REQUIREMENTS
If a defect covered by the Warranty occurs, contact Wine Guardian for authorization to proceed with corrective action. Do not return any parts or incur any charges for which you expect to be reimbursed under this Warranty without receiving this authorization. If parts are replaced under this Warranty, the defective parts must be returned prepaid within 30 days. This warranty shall be null and void in its entirety if the Serial Number on the air conditioner or compressor is altered, removed or defaced.
51
Cabinet Unit Return Policy for U.S. and Canada only
Cabinet Unit Warranty term
Wine Guardian warrants, to the original buyer, its goods and all parts thereof to be free from defects in material and workmanship for a period of two (2) years from the date of invoicing assuming NORMAL USE AND SERVICE.
Please see “Wine Guardian Warranty” document for complete warranty coverage
Installation Instructions
Included with each Wine Guardian unit is a Quick Start Installation Guide. Each guide should be read, understood and followed prior to installation of the Wine Guardian system. Failure to do so can cause system damage, premature failure and/or improper operation of the system.
Under Warranty
If a problem develops with the Wine Guardian unit during the warranty period, the user must:
1.
Contact the Selling Dealer - for initial trouble shooting and performance verification. Should the system be deemed defective the Selling Dealer will contact Wine Guardian’s Service Department for repair or replacement procedure. Wine Guardian reserves the right to repair the original unit or replace the unit with either a refurbished or new unit at its discretion. a.
Unit replacement – Wine Guardian shall send a replacement unit as a means to satisfy the warranty claim. A credit card number will be required as a means to secure the return of the defective unit. Failure to return defective unit within 30 days of shipment of replacement may result in charges to credit card. The replacement unit packaging material MUST be retained and used to package the defective unit for preparation of return back to Wine Guardian factory.
OR b.
Unit repair - Wine Guardian shall repair, at its N. Syracuse, New York factory, the defective unit as a means to satisfy the warranty claim. If the original packaging has been discarded, Air
Innovations will send (for a fee) a replacement box and packaging materials for proper freight protection back to Wine Guardian factory. Alternatively, the unit can be packaged in a U-Haul specific “27 TV/Micro. Box” with dimensions of 24-1/2” x 24-1/2” x 27-1/2” which meets UPS and/or FedEx shipping requirements. Please note: when using U-Haul specific box the Wine
Guardian end covers must be removed to avoid damage.
2.
Acquire Returned Goods Authorization (RGA) number – Prior to return of any Wine Guardian unit,
Wine Guardian’s Service Department will issue an RGA number which must be clearly marked on all return packaging. The RGA # provides a method for tracking the unit through Air Innovations and provides disposition upon its return.
3.
Freight – Air Innovations shall cover the cost of freight for pick up and return of the Wine Guardian unit from the original “ship to” address. Any special handling, pick up, or drop off charges are not covered under warranty and shall be assessed and quoted prior to pick up of unit. Special handling charges shall be paid in full prior to return of system. Air Innovations shall schedule a freight carrier upon notification from the user that the system has been packaged and is ready for pickup.
4.
Removal and installation - removal of defective units and installation of repaired or replacement systems is NOT covered under the Through-the-Wall warranty and it is the responsibility of the user to remove and re-install the system once the warranty issues have been addressed.
Out of Warranty
Should a problem develop with the Wine Guardian unit out of warranty you can contact Air Innovations Service
Department for a quotation to diagnose and/or repair the defective system. All freight and packaging costs shall be the responsibility of the owner and shall be prepaid via check or credit card prior to any work being performed.
52
Contact Information
Wine Guardian
7000 Performance Drive
North Syracuse, NY 13212
Toll free: (800) 825-3268 or
Help.wineguardian.com
Normal business hours are 8 a.m. to 5 p.m. Eastern, Monday-Friday.
Web site: airinnovations.com
Email: [email protected]
53
advertisement
Related manuals
advertisement
Table of contents
- 5 Directory of Terms
- 6 Receiving, Inspecting and Unpacking the Wine Guardian System
- 6 Review the Packing Slip to Verify:
- 6 Check the unit for:
- 7 General Description
- 8 Wine Guardian Controls
- 9 Wine Guardian Controls
- 10 Standard Specifications
- 10 The Wine Guardian Cabinet System Contains
- 10 Serving Temperature Option
- 11 Accessories and Optional Equipment
- 11 Extended Compressor Warranty---U.S. and Canada only
- 11 Duct Collar Adapter
- 11 Remote Temperature/Humidity Controller
- 11 Remote Temperature/Humidity Sensor
- 11 Heater Option
- 12 Humidity Option
- 12 Overview of the Wine Guardian Unit
- 13 Overview
- 16 Safety
- 16 Safety Message Conventions
- 16 Danger
- 16 Warning
- 16 Caution
- 17 Lockout/Tagout Procedure
- 17 Safety Considerations
- 17 Safety Hazards
- 17 Electrical Hazards
- 17 Electrical Shock Hazards
- 17 Hot Parts Hazards
- 18 Moving Parts Hazards
- 18 Equipment Safety Interlocks
- 20 Installation
- 20 Pre-installation Test
- 20 Air Flow Illustration
- 22 Performing a Pre-installation Check
- 22 Locating the system
- 22 Power cord location
- 22 Evaporator Connections
- 23 Condenser Connections
- 24 Turning on system
- 24 Wiring the System for Power
- 25 Electrical Plug Configuration 60Hz Models Only
- 26 Starting-up and Operating the Wine Guardian
- 26 Control Settings
- 26 Controller Functions
- 27 Standard Controller Functions
- 34 Alarm Codes
- 36 Installing the Optional Remote Interface Controller and Communication Cable
- 37 Controller Specification
- 38 Mounting the Optional Remote Interface Controller (Wired)
- 39 Mounting the Optional Remote Interface Controller (Wireless)
- 40 Installation of the Optional Wine Guardian Remote Sensor
- 40 Mounting the Wired Remote Sensor (Wired)
- 42 Mounting the Remote Sensor (Wireless)
- 43 Remote Sensor Pairing Instructions – Multiple Sensors (Wireless)
- 44 Regulating the Cabinet Temperature
- 44 Maintenance
- 45 Maintenance Schedule
- 45 Monthly
- 45 Yearly
- 46 High Pressure Switch Has Shut the System Down
- 46 Instructions to Reset High Pressure Switch
- 46 Alarm Annunciation
- 47 Troubleshooting
- 47 Typical Start-up Problems
- 47 Unit Does Not Start-up
- 48 Unit is Operating and Blows Evaporator Air, but the Supply Air is not Colder than the Return Air from the Cellar
- 48 Problems Controlling Cellar Temperature
- 49 Problems Controlling Cellar Humidity
- 50 Other Miscellaneous Problems
- 47 Thermostat light is offPossible Cause
- 47 Solution
- 47 Check circuit breaker and wiring
- 47 No power to outlet
- 47 Plug in the unit
- 47 Unit not plugged in
- 47 Thermostat light is onPossible Cause
- 47 Solution
- 47 Check remote interface controller set up in the guide
- 47 Remote interface controller is not set up properly
- 50 Problems Controlling Cellar Humidity
- 50 System is leaking water
- 50 Possible Cause
- 50 Solution
- 50 Remove blockage and clean
- 50 Condensate pan plugged
- 50 Level with shims
- 50 Unit not level
- 50 System is running properly, but the sounds of unit is objectionable
- 50 Solution
- 50 Possible Cause
- 50 Duct airflow from condenser to outdoors
- 50 Noise is from airflow
- 51 Manufacturer’s Warranty – U.S. and Canada only
- 52 Cabinet Unit Return Policy for U.S. and Canada only
- 53 Contact Information