York V* Series Technical Manual

Add to My manuals
32 Pages

advertisement

York V* Series Technical Manual | Manualzz

246681-YTG-B-0607

TECHNICAL GUIDE

MAXA-MI$ER

V* Series

Unitized Energy Recovery

Ventilators

®

ERV Unit with a Champion® Series Packaged Unit

ERV Unit with Predator® Packaged Unit

®

DESCRIPTION

• Reduces cooling load at design temperatures up to 4 tons per

1000 cfm of outside air.

• Reduces heating load up to 2.5 Tons Btuh per 1000 CFM of outside air.

• Dry energy transfer. Moisture in supply (intake) air stream is transferred to exhaust air stream in a vapor state, eliminating condensate plumbing from the UERV.

• Attaches directly to the York rooftop units. All mounting equipment is provided.

• Separate fused power supply.

• Filters / mist eliminators are provided on the entering air openings.

• Adjustable support legs are provided.

• Two modes of operation (Pivoting Wheel Models only)

• Recovery mode during normal energy recovery operation.

• True economizer mode when outside sensor calls for economizer operation (3 - 12.5 ton packaged units equipped with economizers). U. S. Patent 5,548,970.

• Pivoting wheel models used with packaged unit with economizer. Sequence of operation controlled by economizer. (select models only)

• Balancing dampers provided on VR, VH and VU Modules.

(Except Millennium or VR74 and VR122)

• Centrifugal blowers (both intake and exhaust for high static capability and low sound levels).

• Heavy gauge galvanized steel cabinets corrosion protected with powder paint process that match York units.

• Fully insulated cabinet.

• ARI certified internal enthalpy wheel is provided.

• Internal enthalpy wheel made of polymeric material with silica gel impregnated into the material. The enthalpy wheel has a five year limited warranty.

• Internal enthalpy wheels are easily cleanable. Large wheels (25 inch diameter and above) are split into easily removable pie segments. Smaller wheels can be removed from the ERV.

• Continuous operation down to 10 ºF (-12 ºC) without defrost at indoor relative humidity up to 40%. For temperatures below 10

ºF (-12 ºC), Optional Low Ambient Control Kit is required. Kit includes temperature sensor to control the ERV before frost build up can occur on recovery wheel.

Note: MAXA-MI $ ER

®

UERV’s are designed for use with rooftops using 14” high or greater roof curbs.

ERV Unit with Sunline® Packaged Unit

Energy recovery COMPONENT rated in accordance with ARI Standard 1060-2000 and certified to ARI. Actual performance in packaged equipment may vary.

ETL Certified per UL 1995 and CSA 22.2

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

246681-YTG-B-0607

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

YORK UERV MODEL NOMENCLATURE . . . . . . . . . . . 3

APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

PRINCIPLE OF OPERATION . . . . . . . . . . . . . . . . . . . . . 4

ARI STANDARD 1060-2000 FOR AIR-TO-AIR ENERGY

RECOVERY VENTILATION EQUIPMENT . . . . . . . . . . . 4

ENERGY RECOVERY WHEEL . . . . . . . . . . . . . . . . . . . . 4

CROSS LEAKAGE IN UERV’S (PURGE SECTORS) . . . 5

OPTIONAL ACCESSORIES - FIELD INSTALLED . . . . 5

OPTIONAL ACCESSORIES - FACTORY INSTALLED 6

HOW TO SELECT THE PROPER AIR CONDITIONING

UNIT AND UNITARY ENERGY RECOVERY

VENTILATOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . 26

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

APPROVALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

SEQUENCE OF OPERATION: . . . . . . . . . . . . . . . . . . 27

UERV TROUBLESHOOTING GUIDE . . . . . . . . . . . . . 28

UERV BELOW 600 CFM WITH STATIONARY WHEEL

(NO ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

UERV ABOVE 600 CFM WITH STATIONARY WHEEL

(NO ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

UERV ABOVE 600 CFM WITH PIVOTING WHEEL (USED

WITH ECONOMIZER) . . . . . . . . . . . . . . . . . . . . . . . . . . 29

LIST OF FIGURES

Fig. # Pg. #

1 UNITIZED ENERGY RECOVERY VENTILATOR . . . . 4

2 ENERGY RECOVERY WHEEL . . . . . . . . . . . . . . . . . . 4

3 “P” SERIES PIVOTING WHEEL FOR UNITS

W/ECONOMIZERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4 UERV DIMENSIONAL DATA - 018 THROUGH 060 . . 17

5 UERV DIMENSIONAL DATA - 036 THROUGH 072 . . 17

6 UERV DIMENSIONAL DATA - 078 THROUGH 150 . . 18

7 UERV DIMENSIONAL DATA - 180 THROUGH 300 . . 18

8 MILLENNIUM UNIT VR074 AND VR122 . . . . . . . . . . 19

9 STAND ALONE UERV’S FOR SIDE BY SIDE DUCT

ARRANGEMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

10 STAND ALONE UERV’S FOR OVER AND UNDER

DUCT ARRANGEMENTS . . . . . . . . . . . . . . . . . . . . . . 22

11 HORIZONTAL SPLIT SYSTEM UERV’S FOR VH006

AND VH011 SERIES . . . . . . . . . . . . . . . . . . . . . . . . . 23

12 UPFLOW SPLIT SYSTEM UERV’S . . . . . . . . . . . . . . 24

LIST OF TABLES

Tbl. # Pg. #

1 UERV OUTSIDE AIR CFM SELECTION BY CFM . . . . 5

2 PERFORMANCE - 1 1/2 THROUGH 12 1/2 TON

UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3 PERFORMANCE - 15 THROUGH 25 TON UNITS . . . 8

4 PERFORMANCE - PIVOTING WHEEL MODELS . . . . 9

5 SPECIFICATIONS AND ELECTRICAL DATA - 300

THROUGH 550 CFM ERV’S . . . . . . . . . . . . . . . . . . . 10

6 SPECIFICATIONS AND ELECTRICAL DATA - 600

THROUGH 1700 CFM ERV’S . . . . . . . . . . . . . . . . . . 11

7 SPECIFICATIONS AND ELECTRICAL DATA - 1500

THROUGH 2800 CFM ERV’S . . . . . . . . . . . . . . . . . . 12

8 SPECIFICATIONS AND ELECTRICAL DATA - 2800

THROUGH 3600 CFM ERV’S . . . . . . . . . . . . . . . . . . 13

9 SPECIFICATIONS AND ELECTRICAL DATA - 3400

THROUGH 5600 CFM ERV’S . . . . . . . . . . . . . . . . . . 14

10 SPECIFICATIONS AND ELECTRICAL DATA - 5500

THROUGH 6200 CFM ERV’S . . . . . . . . . . . . . . . . . . 15

11 SPECIFICATIONS AND ELECTRICAL DATA - 6000

THROUGH 13000 CFM UERV’S . . . . . . . . . . . . . . . . 16

12 BLOWER PERFORMANCE CHART - VR074 . . . . . . 20

13 BLOWER PERFORMANCE CHART - VR122 . . . . . . 20

14 YORK HORIZONTAL AND UPFLOW SPLIT SYSTEM

UERV MODELS 300 - 500 CFM . . . . . . . . . . . . . . . . . 25

15 YORK HORIZONTAL AND UPFLOW SPLIT SYSTEM

UERV MODELS 600 - 1,000 CFM . . . . . . . . . . . . . . . 25

2 Unitary Products Group

246681-YTG-B-0607

YORK UERV MODEL NOMENCLATURE

Unitary Products Group 3

246681-YTG-B-0607

APPLICATIONS

Unitized Energy Recovery Ventilators (UERV) are used with the York rooftop packaged units. The internal wheel provides sensible and latent energy exchange between the entering and exhaust air streams of a building. This allows a substantial amount of the energy, which is normally lost in the exhaust air stream to be returned into the entering air. Ideal applications are areas that have cold or hot temperatures, or areas that have high humidity or very low humidity (recover exhaust air from buildings that have humidifiers to add humidity). Application software is available to provide the energy and dollar savings for all areas of the United States and Canada.

PRINCIPLE OF OPERATION

The UERV enthalpy wheel contains parallel layers of a polymeric material that are impregnated with silica gel (desiccant). The wheel is located in the entering (intake) air and exhaust air streams of the ventilation equipment. As the wheel rotates through each air stream, the wheel surface adsorbs sensible and latent energy. In the heating mode, the wheel rotates to provide a constant transfer of heat from the exhaust air stream to the colder intake air stream. During the cooling season, the process is reversed. On units equipped with an economizer (3 - 12.5 tons), the wheel pivots out of the air stream to allow economizer to operate normally for "free cooling" when outdoor temperature and humidity is acceptable. During economizer operation, the UERV exhaust blower continues to run, providing power exhaust for the system. The intake blower is de-energized during economizer operation.

ARI STANDARD 1060-2000 FOR AIR-TO-AIR

ENERGY RECOVERY VENTILATION EQUIPMENT

The Air-Conditioning and Refrigeration Institute (ARI) issued

Standard 1060-2000 to certify air-to-air energy recovery ventilators. This standard deals specifically with the ratings of the

Energy Recovery Wheel that is incorporated into the Energy

Recovery Ventilator (ERV). All of the York ERV's have an ARI certified energy recovery wheel. The data shown in the specification charts is the ARI certified ratings for the wheel.

Actual performance in the ERV may vary.

Critical Terms for Standard 1060 are as follows:

1.

Effectiveness . The measured energy recovery effectiveness not adjusted to account for that portion of the psychrometric change in the leaving supply air (Station

2) that is the result of leakage of entering exhaust air

(Station 3) rather than exchange of heat or moisture between the air streams.

2.

Net Effectiveness . The measured recovery effectiveness adjusted to account for that portion of the psychometric change in the leaving supply air (Station 2) that is the result of leakage of the entering exhaust air (Station

3) rather than exchange of heat or moisture between the air streams.

3.

Exhaust Air Transfer Ratio (EATR) . The tracer gas concentration difference between the leaving supply air

(Station 2) and entering supply (outdoor) air stream (Station 1) divided by the tracer gas concentration in the entering exhaust (return) air (Station 3) at the 100% rated air-flow, expressed as a percentage.

4.

Outdoor Air Correction Factor (OACF) . The entering supply (outdoor) airflow (Station 1) divided by the measured (gross) leaving supply airflow (Station 2).

ENERGY RECOVERY WHEEL

The heart of the Energy Recovery Ventilator is the Energy

Recovery Wheel (defined by ARI as a rotary heat exchanger).

The wheel has a patented design of parallel layers of wrapped polymeric material that is impregnated with a silica gel (desiccant). This unique design makes it the only truly cleanable wheel on the market today. The small wheels (30 inch diameter and smaller) are slide out cassettes, and the larger wheels have pie segments that are removable for cleaning.

FIGURE 1 - UNITIZED ENERGY RECOVERY

VENTILATOR

4

FIGURE 2 - ENERGY RECOVERY WHEEL

Unitary Products Group

246681-YTG-B-0607

CROSS LEAKAGE IN UERV’S (PURGE SECTORS)

The issue of cross leakage in rotary wheel based UERV's used in space conditioning applications is often misunderstood. As a result, many systems are installed with purge sectors and the additional fan capacity required to allow these sectors to function when in fact they are unnecessary.

A better understanding of the rational for the purge sector, and its history, allows us to dispense with the purge sector, its added first cost and continuing cost of operation.

A purge sector minimizes the carry over cross leakage from the exhaust into the supply (outside air) air stream by shunting a portion of the supply air back into the exhaust air stream across the seal separating the exhaust and supply. This is required in industrial applications where the exhaust carries contaminants. This typically results in air volume being 15%

TABLE 1: UERV OUTSIDE AIR CFM SELECTION BY CFM

to 20% higher to get the desired air intake, and the cost associated with it.

In space conditioning applications, where the ventilation is operating to maintain acceptable indoor air quality, there are no contaminants in concentrations large enough to cause concern. Cross leakage in the UERV system results in a small amount of the exhaust air, typically less than 5% in balanced airflow, returning to the space. This is not contaminated air, as some would suggest. It is however air that effectively never left the space. The operation cost of moving this air is far less than that required for a purge sector. Do not use the York UERV's in applications that have concentrations of contaminants.

Unit-Tons 300-550 600-1000 1100-1700 1500-2800 2800-3600 3400-4600 4800-5600 5500-6200 6000-8000 8000-13000

Rooftop

1.5 - 6 1.5 - 6 Stand Alone type ERV’s are available for all tonnage sizes.

7.5 - 12.5

7.5 - 12.5

7.5 - 12.5

15 - 25 15 - 25 15 - 25 15 - 25 15 - 25

30 - 50 30 - 50

Upflow 1.5 - 5

Horizontal 1.5 - 5

1.5 - 5

1.5 - 5 Stand Alone ERV’s are available for equipment room applications.

OPTIONAL ACCESSORIES - FIELD

INSTALLED

UERV Equipment Support - 8 inch (203 mm) high base for support of the exhaust and intake end of the UERV. Must be ordered separately from the UERV.

Equipment Support

VR006

VR/P011

VR/P020

VR/P028

1ES0401

1ES0402

1ES0402

1ES0402

Equipment Support

VR036

VR046

VR062

VR074

VR122

1ES0403

1ES0403

1ES0404

Roof Curb - A 14 or 24 inch (355 or 610 mm) roof curb is required to match supply and exhaust openings of the UERV with the rooftop units. York provides a full line of roof curbs to match the specified unit. See specification pages for required curb. Must be ordered separately from UERV.

Stand Alone Balancing Damper - Balancing dampers are used with VO and VS models when ERV is connected to the rooftop unit, not to ductwork on the roof.

Unitary Products Group 5

246681-YTG-B-0607

RSI Model

80-950-23

80-950-24

80-950-13

80-950-29

80-950-19

80-950-18

York

Model

1DB0402

1DB0401

1DB0403

1DB0404

1DB0405

1DB0406

Description

* Balancing Damper, “VO and VS”

* Balancing Damper, “VO and VS”

* Balancing Damper, “VO and VS”

* Balancing Damper, “VO and VS”

** Balancing Damper, “VO and VS”

** Balancing Damper, “VO and VS”

* These balancing dampers work best with”VO” stand alones.

** These balancing dampers work best with”VS” stand alones.

OPTIONAL ACCESSORIES - FACTORY

INSTALLED

Low Ambient Control Kit - Prevents frost formation on energy wheel heat transfer surfaces by terminating the intake blower operation when discharge air temperature falls below a field selectable temperature setting. Intake blower operation resumes operation after temperature rises above the adjustable temperature differential.

Pressure Sensor - Measurement device on the UERV to determine airflow across the Wheel.

Motorized Intake Air Damper - Damper mounts in the outdoor air intake hood. It opens when the UERV is energized and closes when de-energized.

Stop-Start-Jog - Function that rotates the Enthalpy Wheel

(non-pivoting models) on a preset timer to prevent contamination of the wheel during economizer operation.

ERV Option Codes (ex.: VR028A12H4AL3 would be an R28 series high speed 460 volt UERV with a Low Ambient kit,

Motorized Outside Air, and Stop-Start-Jog kit.)

L1 - Low Ambient Kit (LAK) *

L2 - LAK & Motorized. Outside Air (MOA) *

L3 - LAK, MOA, & Stop-Start-Jog (SSJ) *

L4 - LAK, MOA, SSJ, & Pressure Sensor (PS)

L5 - LAK and SSJ *

L6 - LAK, SSJ, and PS

L7 - LAK and PS

L8 - LAK, MOA, and PS

M1 - Motorized Outside Air (MOA) *

M2 - MOA and Stop-Start-Jog (SSJ) *

M3 - MOA, SSJ, and Pressure Sensor (PS)

Used With

D*NA/NH/N; 018-060

D*EB/EH/EM/B*HA/HH 018-060

DM/DF/DH 036-072 & BQ 036-060

DM/DF/DH 078-150 & BP 078-150

DM/DH 180 & BP 180

DM/DH 240-300, DJ/DR 180-300 & BQ 240

M4 - MOA and PS

S1 - Stop-Start-Jog (SSJ) *

S2 - SSJ and Pressure Sensor (PS)

P1 - Pressure Sensor (PS)

NOTE: * denotes only options available for VR074 & VR122.

HOW TO SELECT THE PROPER AIR

CONDITIONING UNIT AND UNITARY ENERGY

RECOVERY VENTILATOR

1.

Determine the air conditioning load requirements with the required amount of outside air without an UERV.

2.

Select the proper UERV for the outside air CFM requirements and calculate the tonnage reduction through the

York UERV software program.

3.

Select the air conditioning unit required by reducing the load determined in step 1 by the reduction in step 2.

(Example: If the load in Step 1 was 10 tons, and the reduction in Step 2 was 2.5 tons, select a 7.5 ton unit.)

4.

Select the proper UERV based on the select unit. The

York part numbering scheme is as follows:

V R 028 A12 H 4 A L3 1

Voltage

Generation

Option Code (see list above)

Duct Type (A, D or W)

Blower Speed (H for High, M for Medium)

York Unit Cabinet Size

CFM = 2800

Wheel Type

Ventilator

6 Unitary Products Group

246681-YTG-B-0607

TABLE 2: PERFORMANCE - 1 1/2 THROUGH 12 1/2 TON UNITS

York

Packaged Unit

Model No.

D*EB 018-060

D*EH 018-060

D*EM 036-060

B*HA 018-060

B*HH 018-060

B*HP 024-048

Unit

Size

(Tons)

1.5 - 5

“R” Series Stationary Wheel for Units without Economizers

ERV CFM

Range

Matching ERV

Model

Voltage &

Phase

Voltage

Code

Nominal ARI Data (Total

Net Effectiveness

CFM

Heating Cooling

300-550 VR006B05H

110v-1ph

208/230v-1ph

208/240v-3ph

1

9

2 500 65% 64%

460v-3ph 4

D*NH 018-060

D*NA 018-060

D*NP 024-048

D*NZ 024-060

DM 036-072

DF 036-072

DH 036-060

BQ 036-060

DM 090-102

DF 090-102

DH 078-102

BP 090

DM 078

DM 120-150

DF 078

DF120

DH 120-150

DJ 150

DR 090-150

BP 078

BP 120-150

1.5 - 5

3 - 6

7.5 - 8.5

7.5 -

12.5

300-550

300-550

VR006A05H

VR006A06H

600-1000 VR011A06H

600-1000 VR011B12H

1100-1700 VR020B12H

600-1000 VR011A12H

1100-1700 VR020A12H

1500-2200 VR028A12M

2200-2800 VR028A12H

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

110v-1ph

208/230v-1ph

208/240v-3ph

460v-3ph

110v-1ph

208/230v-1ph

208/240v-3ph

460v-3ph

208/230v-1ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

5

2

2

4

4

5

4

5

5

2

2

4

4

5

5

2

2

4

4

5

9

2

2

4

1

9

2

4

1

9

500

500

900

900

1600

900

1600

1950

2600

65%

65%

73%

73%

65%

73%

65%

71%

65%

64%

64%

72%

72%

64%

72%

64%

70%

63%

Note 1: Complete York ERV model number includes the electrical information. Example DM 060 needing 500 CFM outside of air at 230 volts/3 phase. Model would be a VR006A06H2AAA1.

Unitary Products Group 7

246681-YTG-B-0607

TABLE 3: PERFORMANCE - 15 THROUGH 25 TON UNITS

Use this table to determine ventilation and size requirements. Table shows York packaged units and matching ERV model,

Air Flow Range, and ARI rated Net Effectiveness at 100% of rated CFM.

“R” Series Stationary Wheel for Units without Economizers

York

Packaged Unit

Model No.

Unit

Size

(Tons)

ERV CFM

Range

Matching ERV

Model

Voltage &

Phase

Voltage

Code

Nominal ARI Data (Total

Net Effectiveness

CFM

Heating Cooling

1500-2200 VR028A15M

208/230v-3ph

460v-3ph

575v-3ph

2

4

5

1950 71% 70%

DM 180

DH 180

BP 180

15

2200-2800

2800-3600

3400-4600

VR028A15H

VR036A15H

VR046A15H

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

2

4

5

2

4

5

2

4

2600

3100

3900

65%

65%

65%

63%

63%

63%

DM 240

DM 300

DH 240

BP 240

BQ 240

DJ 180

DJ 210

DJ 240

DJ 300

DR 180

DR 240

DR 300

15 - 25

4800-5600

5500-6200

2200-2800

2800-3600

3400-4600

4800-5600

VR062A15M

VR062A15H

VR028A25H

VR036A25H

VR046A25H

VR062A25M

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

5

2

4

5

2

4

5

2

4

5

2

4

5

2

4

5

4125

5500

2600

3100

3900

4125

71%

65%

65%

65%

65%

71%

70%

63%

63%

63%

63%

70%

(See note 2)

(See note 2)

5500-6200

6000-8000

8000-13000

VR062A25H

VR074A40*

VR122A40*

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

2

4

5

2

5

4

2

4

4

5

5

2

5500

6600

10800

65%

65%

65%

63%

63%

63%

Note 1: Complete York ERV model number includes the electrical information. Example: DM180 needing 2800 CFM outside of air at 230 volts/3 phase. Model would be a VR028A15H2AAA1.

Note 2: For VR074 and VR122 units used with an economizer must have the Start-Stop-Jog (SSJ) option.

8 Unitary Products Group

246681-YTG-B-0607

TABLE 4: PERFORMANCE - PIVOTING WHEEL MODELS

York

Packaged Unit

Model No.

DM 036-072

DF 036-072

DH 036-060

BQ 036-060

DM 090-102

DF 090-102

DH 078-102

BP 090

(See note 2)

DM 078

DM 120-150

DF 078

DF120

DH 120-150

DJ 150

DR 090-150

BP 078

BP 120-150

(See note 2)

Unit

Size

(Tons)

3 - 6

7.5 - 8.5

7.5 -

12.5

“P” Series Pivoting Wheel for Units with Economizers

ERV

CFM

Range

Max.

CFM

Power

Exhaust

Matching

ERV

Model

Voltage &

Phase

Voltage

Code

600-

1000

600-

1000

1100-

1700

600-

1000

1100-

1700

1500-

2200

2200-

2800

1900

1900

3000

1900

3000

3450

4200

VP011A06H

VP011B12H

VP020B12H

VP011A12H

VP020A12H

VP028A12M

VP028A12H

208/230v-1ph

208/240v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

208/230v-3ph

460v-3ph

575v-3ph

4

5

5

2

2

4

4

5

5

2

2

4

4

5

9

2

5

2

2

4

4

5

Nominal ARI Data (Total

Net Effectiveness

CFM

Heating Cooling

900

900

1600

900

1600

1950

2600

73%

73%

65%

73%

65%

71%

65%

72%

72%

64%

72%

64%

70%

63%

Note 1: Complete York ERV model number includes the electrical information. Example DM 060 needing 800 CFM outside of air at 230 volts/3 phase. Model would be a VP011A06H2AAA1.

2: Predator models D/B*078-150, with ERV must use “slab” type economizers and downflow position.

Outside

Air Blower

(energized)

Enthalpy Wheel

Pivoted out of Intake and

Discharge Air Stream

Fresh Air Damper

(opens during economizer operation)

Exhaust

Air Blower

(energized)

Enthalpy Wheel

(with removable pie segments)

Exhaust

Air Blower

Unit & UERV Disconnect

(provided correct wire size used for both units and local code approval

)

FIGURE 3 - “P” SERIES PIVOTING WHEEL FOR UNITS W/ECONOMIZERS

Unitary Products Group 9

246681-YTG-B-0607

TABLE 5: SPECIFICATIONS AND ELECTRICAL DATA - 300 THROUGH 550 CFM ERV’S

Specifications and Electrical Data - 300 through 550 CFM ERV's

Model Numbers

VS006 - S/S Stand Alone Stationary

VR006 - Rooftop Stationary

VH006 - Horizontal Split System

VU006 - Upflow Split System

VO006 - O/U Stand Alone Stationary

Line Voltage - 60hz 115v-1ph 208/230v/460-1ph 208/230v/460-3ph

Fresh Air Blower

Motor - hp

Wheel Size (dia x width) -in

Motor Speed -rpm

Motor Speed(s)

Bearing Type

Full Load Amps

Service Factor

Motor - hp

Wheel Size (dia x width) -in

Motor Speed -rpm

Motor Speed(s)

Exhaust Air Blower

Bearing Type

Full Load Amps-Stationary

Full Load Amps-Pivoting

Service Factor

Wheel Electrical

Data

Total Electrical

Potential Volts

Motor Speed -rpm

Full Load Amps

MCA

OCPD

0.2 / PSC

5.5 x 6.3

1780

2

Sleeve

3.8

1.1

0.25 / PSC

5.5 x 6.3

1780

2

Sleeve

3.8

NA

1.1

115

1050

0.6

8.7

10

Wheel Data

Total

Effectiveness

Net

Effectiveness

Wheel Depth

Wheel Diameter -in

Construction

Enthalpy Wheel

ARI Airflow Data

Nominal Airflow CFM

EATR - -0.50 H

2

O

EATR - 0.00 H

2

O

EATR - +0.50 H

2

O

OACF - -0.50 H

2

O

OACF - 0.00 H

2

O

OACF - +0.50 H

2

O

Thermal Ratings @ 0" Pressure Diff.

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

2

19.3

One Piece / Polymeric

500 @ .6

Δ

9.90%

0.20%

0.00%

1.02%

1.33%

1.59%

Latent

60%

65%

60%

65%

60%

65%

60%

65%

Total

65%

70%

64%

69%

65%

70%

64%

69%

Curb A/C Unit Curb Height - in 14

Weights

Shipping Weight - lbs.

Net Weight - lbs.

198

155

Note 1: A stepdown transformer is provided to stepdown high voltage primary to 115 volt secondary.

2: On Horizontal and upflow UERVs, the transformer is provided for field installation.

10 Unitary Products Group

246681-YTG-B-0607

TABLE 6: SPECIFICATIONS AND ELECTRICAL DATA - 600 THROUGH 1700 CFM ERV’S

Model Numbers

VR011 - Rooftop Stationary

VP011 - Rooftop Pivoting

VH011 - Horizontal Split System

VU011 - Upflow Split System

VO011 - O/U Stand Alone

VS011 - S/S Stand Alone

Line Voltage - 60hz

Fresh Air

Blower

Motor - hp

Wheel Size (dia x width) -in

Motor Speed -rpm

Motor Speed(s)

Bearing Type

Full Load Amps

Service Factor

Motor - hp Stationary

Motor - hp Pivoting

Wheel Size (dia x width) -in

Exhaust Air

Blower

Motor Speed -rpm

Motor Speed(s)

Bearing Type

Full Load Amps-Stationary

Full Load Amps-Pivoting

Service Factor

Wheel

Electrical

Data

Potential Volts

Motor Speed -rpm

Full Load Amps

MCA - Stationary

OCPD - Stationary Total

Electrical

MCA - Pivoting

OCPD - Pivoting

Wheel Data

Wheel Depth - in

Wheel Diameter - in

Construction / Media

Nominal Airflow CFM

EATR - -1.00 H

2

O

Enthalpy

Wheel ARI

Rating Data

EATR - 0.00 H

2

EATR - +1.00 H

O

2

O

OACF - -1.00 H

2

O

OACF - 0.00 H

2

O

OACF - +1.00 H

2

O

Thermal Ratings @ 0" Pressure Diff.

Total

Effectiveness

Net

Effectiveness

Curb

Weights

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

A/C Unit Curb Hgt - in

Shipping Weight - lbs.

Net Weight - lbs.

208/ 230v-

1ph

3.4

3.4

208/ 230v-

3ph

.5 / PSC

10 x 6 AT

460v-

1ph

1120 / 960 / 850

3

Sleeve

3.4

1

.5 / PSC

.5 / PSC

10 x 6 AT

1120 / 960 / 850

3

Sleeve

3.4

3.4

1

1.5

1.5

208 / 230

1050

0.6

460v-

3ph

1.5

1.5

8.25

10

8.25

10

Sensible

76%

81%

76%

81%

76%

81%

76%

81%

8.25

10

8.25

10

4.4

6

4.4

6

3

25.3

One Piece / Polymeric

900 @ 1.0

Δ

9.30%

0.70%

0.00%

0.97%

1.19%

1.34%

Latent

68%

73%

68%

73%

68%

73%

68%

73%

14 on A06

318

245

Total

73%

78%

72%

76%

73%

78%

72%

76%

4.4

6

4.4

6

Note 1: On Horizontal and upflow UERVs, the transformer is field installed.

Note 2: Pivoting electrical data applies to VP models only.

VR020 - Rooftop Stationary

VP020 - Rooftop Pivoting

VO020 - O/U Stand Alone

VS020 - S/S Stand Alone

208/ 230v-

3ph

3.8

460v-3ph 575v-3ph

1.0 / Belt

9 x 9

1725

Adjustable Sheave

Ball

1.9

1.15

1.4

3.8

5.6

1.0 / Belt

1.5 / Belt

9 x 9

1725

Adjustable Sheave

Ball

1.9

2.8

1.15

208 / 230

1050

0.6

1.4

2.0

9.15

12

11.4

15

4.9

6

6

8

3

30.346

One Piece / Polymeric

1600 @ .95

Δ

7.80%

0.40%

0.00%

0.97%

1.16%

1.29%

3.8

5

4.5

6

Sensible

68%

72%

68%

72%

68%

72%

68%

72%

Latent

61%

67%

61%

67%

61%

67%

61%

67%

24

425

345

Total

65%

71%

64%

70%

65%

71%

64%

70%

Unitary Products Group 11

246681-YTG-B-0607

TABLE 7: SPECIFICATIONS AND ELECTRICAL DATA - 1500 THROUGH 2800 CFM ERV’S

Model Numbers

Line Voltage - 60hz

Motor - hp / type

Wheel Size (dia x width) - in

Motor Speed - rpm

Fresh Air

Blower

Motor Speed(s)

Bearing Type

Full Load Amps

Service Factor

Motor - hp Stationary

Motor - hp Pivoting

Exhaust Air

Blower

Wheel Size (dia x width) - in

Motor Speed - rpm

Motor Speed(s)

Bearing Type

Full Load Amps-Stationary

Full Load Amps-Pivoting

Service Factor

Motor - hp (1 phase)

Wheel

Electrical

Data

Potential Volts

Motor Speed - rpm

Full Load Amps

MCA - Stationary

Total

Electrical

OCPD - Stationary

MCA - Pivoting

OCPD - Pivoting

Wheel Depth x Diameter - in

Wheel

Data Construction / Media Type

Nominal Airflow CFM

Enthalpy

Wheel ARI

Rating Data

EATR - -1.00 H

2

O

EATR - 0.00 H

2

O

EATR - +1.00 H

2

O

OACF - -1.00 H

2

O

OACF - 0.00 H

2

O

OACF - +1.00 H

2

O

Thermal Ratings @ 0” Pressure Diff.

Total

Effectiveness

Net

Effectiveness

Curb

Weights

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

A/C Unit Curb Height - in

Shipping Weight - lbs.

Net Weight - lbs.

* Electric data is for (A12) DM/DF/DH/DJ 078-150 and BP 078-150 only.

** Electric data is for (A15 and A25) DM/DH/DJ/DR 180-300 and BQ 240 only.

Note: Pivoting electrical data applies to VP models only.

* VR028 - Rooftop Stationary

* VP028 - Rooftop Pivoting

VO028 - O/U Stand Alone

208/230v-3ph

5.6

460v-3ph

1.5 / Belt

10 x 10

1725

Adjustable Sheave

Ball

2.8

1.15

5.6

9

1.5 / Belt

3 / Belt

10 x 10

1725

Adjustable Sheave

Ball

2.8

4.4

575v-3ph

2

2

3.6

1.15

0.17

200-208 / 230

1725

13.7

20

18

25

1.1

7.4

10

9.4

12

3 x 37.759

Segmented Pies / Polymeric

2600 @ .95

Δ

6.10%

5.6

7

7.6

10

0.40%

0.00%

0.99%

1.13%

Sensible

68%

74%

68%

74%

68%

74%

68%

74%

1.23%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24 on A12, 14 on A15 & A25

Total

65%

71%

63%

70%

65%

71%

63%

70%

470

395

** VR028 - Rooftop Stationary

VS028 - S/S Stand Alone

208/230v-3ph

6.6

460v-3ph

2 / Belt

10 x 10

1725

Adjustable Sheave

Ball

3.3

1.15

6.6

-

2 / Belt

-

10 x 10

1725

Adjustable Sheave

Ball

3.3

-

575v-3ph

2.4

2.4

-

1.15

0.17

200-208 / 230

1725

16

20

-

-

1.1

8.6

10

-

-

3 x 37.759

Segmented Pies / Polymeric

2600 @ .95

Δ

6.10%

6.6

7

-

-

0.40%

0.00%

0.99%

1.13%

Sensible

68%

74%

68%

74%

68%

74%

68%

74%

1.23%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24 on A12, 14 on A15 & A25

Total

65%

71%

63%

70%

65%

71%

63%

70%

470

395

12 Unitary Products Group

246681-YTG-B-0607

TABLE 8: SPECIFICATIONS AND ELECTRICAL DATA - 2800 THROUGH 3600 CFM ERV’S

Model Numbers

Line Voltage - 60hz

Motor - hp / type

Wheel Size (dia x width) - in

Motor Speed - rpm

Fresh Air

Blower

Motor Speed(s)

Bearing Type

Full Load Amps

Service Factor

Motor - hp Stationary

Wheel Size (dia x width) - in

Exhaust Air

Blower

Motor Speed - rpm

Motor Speed(s)

Bearing Type

Full Load Amps-Stationary

Wheel

Electrical

Data

Service Factor

Motor - hp (1 phase)

Potential Volts

Motor Speed - rpm

Total

Electrical

Full Load Amps

MCA - Stationary

OCPD - Stationary

Wheel Depth x Diameter - in Wheel

Data Construction / Media Type

Nominal Airflow CFM

Enthalpy

Wheel ARI

Rating Data

EATR - -1.00 H

2

O

EATR - 0.00 H

2

O

EATR - +1.00 H

2

O

OACF - -1.00 H

2

O

OACF - 0.00 H

2

O

OACF - +1.00 H

2

O

Thermal Ratings @ 0” Pressure Diff.

Total

Effectiveness

Net

Effectiveness

Curb

Weights

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

A/C Unit Curb Height - in

Shipping Weight - lbs.

Net Weight - lbs.

VR036 - Rooftop Stationary

VS036 - S/S Stand Alone

208/230v-3ph

9.4

460v-3ph

3 / Belt

12 x 9

1725

Adjustable Sheave

Ball

4.3

1.15

9.4

3 / Belt

12 x 9

1725

Adjustable Sheave

Ball

4.3

1.15

0.50

575v-3ph

3.2

3.2

Sensible

68%

74%

68%

74%

68%

74%

68%

74%

200-208 / 230

1725

2.7

10.9

22.4

30 15

3 x 41.825

Segmented Pies / Polymeric

3100 @ .9

Δ

8.4

9

4.90%

1.30%

0.30%

0.99%

1.07%

1.12%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24

571

475

Total

65%

71%

63%

70%

65%

71%

63%

70%

VO036 - O/U Stand Alone

208/230v-3ph

6.6

460v-3ph

2 / Belt

12 x 9

1725

Adjustable Sheave

Ball

3.3

1.15

6.6

2 / Belt

12 x 9

1725

Adjustable Sheave

Ball

3.3

1.15

0.50

575v-3ph

2.4

2.4

Sensible

68%

74%

68%

74%

68%

74%

68%

74%

200-208 / 230

1725

2.7

18.6

16.1

20 12

3 x 41.825

Segmented Pies / Polymeric

3100 @ .9

Δ

6.6

9

4.90%

1.30%

0.30%

0.99%

1.07%

1.12%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24

571

475

Total

65%

71%

63%

70%

65%

71%

63%

70%

Unitary Products Group 13

246681-YTG-B-0607

TABLE 9: SPECIFICATIONS AND ELECTRICAL DATA - 3400 THROUGH 5600 CFM ERV’S

Model Numbers

Line Voltage - 60hz

Motor - hp / type

Wheel Size (dia x width) - in

Motor Speed - rpm

Fresh Air

Blower

Motor Speed(s)

Bearing Type

Full Load Amps

Service Factor

Motor - hp Stationary

Wheel Size (dia x width) - in

Exhaust Air

Blower

Motor Speed - rpm

Motor Speed(s)

Bearing Type

Full Load Amps-Stationary

Wheel

Electrical

Data

Service Factor

Motor - hp (1 phase)

Potential Volts

Motor Speed - rpm

Total

Electrical

Full Load Amps

MCA - Stationary

OCPD - Stationary

Wheel Depth x Diameter - in

Wheel

Data Construction / Media Type

Nominal Airflow CFM

Enthalpy

Wheel ARI

Rating Data

EATR - -1.00 H

2

O

EATR - 0.00 H

2

O

EATR - +1.00 H

2

O

OACF - -1.00 H

2

O

OACF - 0.00 H

2

O

OACF - +1.00 H

2

O

Thermal Ratings @ 0” Pressure Diff.

Total

Effectiveness

Net

Effectiveness

Curb

Weights

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

A/C Unit Curb Height - in

Shipping Weight - lbs.

Net Weight - lbs.

VR046 - Rooftop Stationary

VS046 - S/S Stand Alone

208/230v-3ph

14.8

460v-3ph

5 / Belt

12 x 12

1725

Adjustable Sheave

Ball

7

1.15

14.8

5 / Belt

12 x 12

1725

Adjustable Sheave

Ball

7

1.15

0.5

575v-3ph

5.1

5.1

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

200-208 / 230

1150

1.2

17 34.5

40 25

3 x 46.776

Segmented Pies / Polymeric

3900 @ .95

Δ

4.40%

12

15

1.10%

0.20%

0.99%

1.06%

1.11%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24

920

805

Total

65%

71%

63%

70%

65%

71%

63%

70%

VO046 - O/U Stand Alone

208/230v-3ph

9

460v-3ph

3 / Belt

12 x 12

1725

Adjustable Sheave

Ball

4.4

1.15

9

3 / Belt

12 x 12

1725

Adjustable Sheave

Ball

4.4

1.15

0.5

575v-3ph

3.4

3.4

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

22

30

200-208 / 230

1150

1.2

11

15

3 x 46.776

Segmented Pies / Polymeric

3900 @ .95

Δ

4.40%

8.7

12

1.10%

0.20%

0.99%

1.06%

1.11%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24

920

805

Total

65%

71%

63%

70%

65%

71%

63%

70%

14 Unitary Products Group

246681-YTG-B-0607

TABLE 10: SPECIFICATIONS AND ELECTRICAL DATA - 5500 THROUGH 6200 CFM ERV’S

Model Numbers VO062 - O/U Stand Alone

Line Voltage - 60hz

Motor - hp / type

Wheel Size (dia x width) - in

Motor Speed - rpm

Fresh Air

Blower

Motor Speed(s)

Bearing Type

Full Load Amps

Service Factor

Motor - hp Stationary

Wheel Size (dia x width) - in

Exhaust Air

Blower

Motor Speed - rpm

Motor Speed(s)

Bearing Type

Full Load Amps-Stationary

Wheel

Electrical

Data

Service Factor

Motor - hp (1 phase)

Potential Volts

Motor Speed - rpm

Total

Electrical

Full Load Amps

MCA - Stationary

OCPD - Stationary

Wheel Depth x Diameter - in

Wheel

Data Construction / Media Type

Nominal Airflow CFM

Enthalpy

Wheel ARI

Rating Data

EATR - -1.00 H

2

O

EATR - 0.00 H

2

O

EATR - +1.00 H

2

O

OACF - -1.00 H

2

O

OACF - 0.00 H

2

O

OACF - +1.00 H

2

O

Thermal Ratings @ 0” Pressure Diff.

Total

Effectiveness

Net

Effectiveness

Curb

Weights

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

A/C Unit Curb Height - in

Shipping Weight - lbs.

Net Weight - lbs.

208/230v-3ph

15

460v-3ph

5 / Belt

12 x 12

1725

Adjustable Sheave

Ball

7.4

1.15

14.8

5 / Belt

12 x 12

1725

Adjustable Sheave

Ball

7

1.15

0.5

575v-3ph

5.9

5.1

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

200-208 / 230

1075

1.2

17.5

36.8

50 25

3 x 52.026

Segmented Pies / Polymeric

5500 @ .95

Δ

4.00%

13.6

20

1.00%

0.20%

0.99%

1.06%

1.10%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24

1250

1075

Total

65%

71%

63%

70%

65%

71%

63%

70%

VR062 - Rooftop Stationary

VS062 - S/S Stand Alone

208/230v-3ph

15

460v-3ph

5 / Belt

12 x 12

1725

Adjustable Sheave

Ball

7

1.15

14.8

5 / Belt

12 x 12

1725

Adjustable Sheave

Ball

7

1.15

0.5

575v-3ph

5.8

5.1

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

200-208 / 230

1075

2.7

17 34.5

40 25

3 x 52.026

Segmented Pies / Polymeric

5500 @ .95

Δ

4.00%

12.7

15

1.00%

0.20%

0.99%

1.06%

1.10%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

24

1250

1075

Total

65%

71%

63%

70%

65%

71%

63%

70%

Unitary Products Group 15

246681-YTG-B-0607

TABLE 11: SPECIFICATIONS AND ELECTRICAL DATA - 6000 THROUGH 13000 CFM UERV’S

UERV Series

Line Voltage - 60hz

Motor - hp

Wheel Size (dia x width) - in

Motor Speed - rpm

Exhaust Air

Blower

Motor Speed(s)

Bearing Type

Full Load Amps

OCPD

Wheel

Electrical

Data

Service Factor

Motor - hp (3 phase)

Motor Speed - rpm

Full Load Amps

Total

Electrical

OCPD

MCA

OCPD

Wheel Depth x Diameter - in

Wheel

Data Construction / Media Type

Nominal Airflow CFM

Enthalpy

Wheel

Airflow Data

EATR - -1.00 H

2

O

EATR - 0.00 H

2

O

EATR - +1.00 H

2

O

OACF - -1.00 H

2

O

OACF - 0.00 H

2

O

OACF - +1.00 H

2

O

Thermal Ratings @ 0” Pressure Diff.

Total

Effectiveness

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

Net

Effectiveness

Curb

Weights

100% Airflow Heating

75% Airflow Heating

100% Airflow Cooling

75% Airflow Cooling

A/C Unit Curb Height - in

Shipping Weight - lbs.

Net Weight - lbs.

VR074

208/230v-3ph

14.8

20

460v-3ph

(2) 5 / Belt

(2) 12 x 12

1725

Adjustable Sheave

Ball

7

9

575v-3ph

5

7

0.25

1.15

0.25

1725

0.8

0.33

1.6

3

34.9

50

2

16.6

20

3 x 58

Segmented Pies / Polymeric

6600 @ .95

Δ

4.60%

1.4

2

12.7

15

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

1.90%

0.90%

0.99%

1.05%

1.09%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

14

2800

2600

Total

65%

71%

63%

70%

65%

71%

63%

70%

VR122

208/230v-3ph

22.4

30

460v-3ph

(2) 7.5 / Belt

(2) 15 x 15

1725

Adjustable Sheave

Ball

9.7

15

575v-3ph

7.8

10

0.25

1.15

0.25

1725

0.8

0.33

1.6

3

52

70

2

22.6

30

3 x 74

Segmented Pies / Polymeric

10800 @ .95

Δ

3.40%

1.4

2

19

25

Sensible

68%

73%

68%

73%

68%

73%

68%

73%

1.20%

0.40%

0.99%

1.04%

1.07%

Latent

60%

67%

60%

67%

60%

67%

60%

67%

14

3000

2800

Total

65%

71%

63%

70%

65%

71%

63%

70%

16 Unitary Products Group

246681-YTG-B-0607

D*NA/NH/NP/NZ 018-060

D*EB/EH/EM 018-060

B*HA/HH/HP 018-060

A

C

Exhaust Blower

D

Optional Eqpt

Support

14" High Curbs Required on VR006-1RC0463

ERV Model York Model

VR006B05H

D*EB/EH/EM, B*HA/HH/HP

018-060

VR006A05H

D*NA/NH/NP/NZ

018-060

A

24.75

(629)

24.75

(629)

B

24.63

(624)

24.63

(624)

C

34.83

(885)

34.83

(885)

D

8

(203)

8

(203)

CFM

300-550

300-550

FIGURE 4 - UERV DIMENSIONAL DATA - 018 THROUGH 060

DM/DF/DH 036-072

BQ 036-060

A C

B

Outdoor Air

Intake Blower

Enthalpy

Wheel

D

B

14" High Curbs Required -1RC0434

ERV Model

VR006A06H

VR011A06H

VP011A06H

York Size

036-072

036-072

036-072

A

24.75

(629)

32.13

(816)

32.13

(816)

B

24.63

(624)

33.5

(851)

33.5

(851)

C

37.96

(964)

48.75

(1238)

48.75

(1238)

Intake Air Blower

Enthalpy Wheel

D

8

(203)

8

(203)

8

(203)

CFM

300-550

600-1100

600-1100

FIGURE 5 - UERV DIMENSIONAL DATA - 036 THROUGH 072

Exhaust Blower

Unitary Products Group 17

246681-YTG-B-0607

DM/DF/DH/DJ 078-150

BP 078-150

C

A

D

B

14" High Curbs Required on "VR011" & "VP011" - 1RC0471

24" High Curbs Required on "VR020" & "VP020" - 1RC0476

24" High Curbs Required on "VR028" & "VP028" - 1RC0476

Model Number

VR011B12H

VP011B12H

VR020B12H

VP020B12H

VR011A12H

VP011A12H

VR020A12H

VP020A12H

VR028A12M

VP028A12M

VR028A12H

VP028A12H

York Size

078-102

078-102

090-150

090-150

090-150

090-150

A

32.13

(816)

37.25

(946)

32.13

(816)

37.25

(946)

42.63

(1083)

42.63

(1083)

B

33.5

(851)

37.5

(953)

33.5

(851)

37.5

(953)

43.56

(1106)

43.56

(1106)

C

44.75

(1137)

60.38

(1533)

44.75

(1137)

60.38

(1533)

64.25

(1631)

64 25

(1631)

Exhaust Blower

D

11

(279)

20.32

(516)

11

(279)

20.32

(516)

18.32

(466)

18.32

(466)

CFM

600-1000

1100-1700

600-1000

1100-1700

1500-2200

2200-2800

FIGURE 6 - UERV DIMENSIONAL DATA - 078 THROUGH 150

Outdoor Air

Intake Blower

Enthalpy Wheel

Optional Eqpt

Support

Enthalpy

Wheel

DM 180-300

DH 180-240

DJ 180-300

DR 180-300

BP 180

BP 240

BQ 240

B

14" Roofcurbs Required on "VR028" - 1RC0436 - 437

24" High Curbs Required on "VR036" - 1RC0477 or 1RC0478

24" High Curbs Required on "VR046" - 1RC0477 or 1RC0478

24" High Curbs Required on "VR062" - 1RC0477 or 1RC0478

Model Number

VR028A15M

VR028A15H

VR028A25M

VR036A15H

VR036A25H

VR046A15H

VR046A25H

VR062A15M

VR062A25M

VR062A15H

VR062A25H

Unit Size

180

180-300

180

180-300

180

180-300

180

180-300

180

180-300

A

42.63

(1083)

46.68

(1186)

52.68

(1338)

58.88

(1496)

58.88

(1496)

B

43.56

(1106)

57.38

(1457)

57.38

(1457)

57.38

(1457)

57.38

(1457)

C

52.13

(1327)

60.00

(1524)

60.00

(1524)

60.00

(1524)

60.00

(1524)

D

22.50

(572)

30.50

(775)

30.50

(775)

30.50

(775)

30.50

(775)

CFM

1500-2200

2200-2800

NOTE: Refer to Unit Price Pages for exact unit, ERV and curb matchup.

2800-3600

3400-4600

4800-5600

5500-6200

Exhaust

Blower

FIGURE 7 - UERV DIMENSIONAL DATA - 180 THROUGH 300

Outdoor Air Intake

Blower

A

C

D

18 Unitary Products Group

246681-YTG-B-0607

24.59

74.75

82.13

20.92

61.23

- Designed to meet Millennium unit specifications

- 14’ High Curbs Required

- Rooftop unit blower exceeds the capacity of the ERV Exhaust Blowers

Model Number

VR074A40L

VR074A40V

VR122A40L

VR122A40V

CFM

6000 - 8000

6000 - 8000

8000 - 13000

8000 - 13000

Description

Constant volume

Variable Air Vaolume

Constant Volume

Variable Air Volume

- See blower performance charts for airflow at various external static pressures.

FIGURE 8 - MILLENNIUM UNIT VR074 AND VR122

Unitary Products Group 19

246681-YTG-B-0607

TABLE 12: BLOWER PERFORMANCE CHART - VR074

CFM

6000

6500

7000

7500

Exhaust

Blower RPM for VR074, (2) 5HP, Barometric Hood

0

External Static Pressure (in water)

0.5

1 1.5

910

955

1000

1040

8000 1080

Notes:

1. Drive losses included in the above table

2. Performance can vary depending on ambient conditions

3. Blower RPMs are for reference only

1060

1095

1130

1170

1200

1200

1225

1260

1290

1315

RPM Range

1300

1360

1380

1400

1425

2

1400

1430

1475

1500

1530

Low 910-1320 Standard Unit

High 1325-1565 Optional Kit (01-KIT-RH58)

TABLE 13: BLOWER PERFORMANCE CHART - VR122

CFM

8000

9000

10000

11000

Exhaust

Blower RPM for VR122, 7.5HP, Barometric Hood

0

External Static Pressure (in water)

0.5

1 1.5

775

825

875

925

12000

13000

970

1015

Notes:

1. Drive losses included in the above table

2. Performance can vary depending on ambient conditions

3. Blower RPMs are for reference only

900

945

985

1030

1070

1110

1030

1055

1090

1125

1165

1200

RPM Range

1125

1150

1190

1215

1250

1280

2

1200

1240

1280

1310

1355

1360

Low 775-1000 Standard Unit

Med 1000-1200 Optional Kit (0-KIT-RM74)

High 1175-1375 Optional Kit (01-KIT-RH74)

20 Unitary Products Group

246681-YTG-B-0607

Balancing Damper

(field supplied)

Ductwork Field

Supplied

UERV with Rooftop for Maximum Outside Air

(optional balancing damper can be provided with UERV)

UERV with Horizontal Ductwork

(balancing damper field supplied)

Features and Notes

1. Stand Alone design allows higher levels of out-

door air to be introduced into the a/c unit.

2. Static test ports provided to verify intake and

exhaust CFM.

3. Balancing damper is field provided when UERV

is connected to ductwork.

System will not operate properly without balancing damper.

4. Roof curbs are available for the UERV's.

5. CFM at 0.0 external static pressure.

C

E

A

D

D

G

UERV

Series

VS006

VS011

VS020

VS028

VS036

VS046

VS062

UERV Roof Curbs

Series Model Number

VS006

VS011

VS020

VS028

VS036

VS046

VS062

1RC0480

1RC0481

1RC0482

1RC0483

1RC0484

1RC0485

1RC0486

UERV Data

CFM Range Curb Size

300-550

600-1000

1100-1700

1500-2800

2800-3600

3400-4600

4800-6200

23.25 x 32.5

30.25 x 43

35.5 x 52.75

41 x 49.5

41.81 x 55.75

47.81 x 55.75

54 x 55.75

A

34.69

44.25

54.38

52.25

60

B

24.75

32.13

37.25

42.62

46.69

52.69

58.88

C

24.63

33.50

37.50

43.56

57.37

F

H

Dimensional Data

D E F

8.00

12.00

12.00

14.00

20.00

27.00

30.00

32.00

2.32

3.25

1.63

1.63

16.5

39.5

6.03

G

2.00

5.00

4.00

4.00

9.00

10.32

13.41

B

H

0.75

1.56

4.06

4.75

6.00

6.66

8.21

I

I

8.00

17.00

20.32

22.50

30.50

FIGURE 9 - STAND ALONE UERV’S FOR SIDE BY SIDE DUCT ARRANGEMENTS

Unitary Products Group 21

246681-YTG-B-0607

Features and Notes

1. Stand Alone design allows higher levels of outdoor air to be intr oduced into the a/c unit.

2. Static test ports provided to verify intake and exhaust CFM.

3. Balancing damper field supplied.

4. Roof curbs are available for the UERV's.

5. CFM is based on 0 external static pressure.

A

UERV Roof Curbs

Series

VO006

VO011

VO020

VO028

VO036

VO046

VO062

M odel No

1RC0480

1RC0481

1RC0482

1RC0483

1RC0484

1RC0485

1RC0486

B

A

Ductwork Field

Supplied

UERV with Horizontal Ductwork

C

C G

D

D

F

14

E

B

J

K

H

UERV

Series

VO006

VO011

VO020

VO028

VO036

VO046

VO062

UERV Data

CFM Range

Curb Size

(J x K)

A

23.25 x 32.5

34.83

300-550

600-1000

1100-1700

30.25 x 43

35.5 x 52.75

1500-2800 41 x 49.5

2800-3600 41.81 x 55.75

3400-4600 47.81 x 55.75

4800-6200 54 x 55.75

44.75

52.38

52.25

60.00

60.00

60.00

B

24.75

32.13

37.25

42.63

46.69

52.69

58.88

C

24.63

33.50

37.50

43.56

57.37

57.37

57.37

Dimensional Data

D

8.00

12.00

12.00

14.00

16.50

16.50

16.50

E

20.00

27.00

30.00

32.00

39.50

39.50

39.50

F

2.00

2.60

4.50

4.75

8.19

8.19

8.19

G

2.25

5.00

4.00

4.00

8.00

8.00

8.00

FIGURE 10 - STAND ALONE UERV’S FOR OVER AND UNDER DUCT ARRANGEMENTS

H

2.32

2.56

3.63

5.31

3.59

6.59

9.68

I

8.00

11.00

20.32

18.32

18.32

18.32

18.32

22 Unitary Products Group

246681-YTG-B-0607

UERV

H06 and H11 Series

Air Handler

Balancing Damper

UERV

Intake Air

(field selected)

Air Handler End

A

B

C

E

D

Model

CFM Range

A

B

C

D

E

Exhaust Air

(Transition

Provided)

Features

Intake Duct

Exhaust Duct

Return Duct

(bottom of UERV)

1. Fresh air intake can be field located on top or end of unit.

2. Electrical control box can be located to either side for access.

3. Access panels located on both sides of ERV for servicing.

4. Static test ports are provided for verification of CFM.

5. Filter rack accepts 1" or 2" filters and comes with flex connector to air handler.

6. On Horizontal and upflow UERVs, the transformer is supplied for field installation.

Dimensions

VH006 VH011

300-550 600-1,000

34.70

40.25

24.75

24.62

30.25

32.50

5.63

40.33

9 rd

9 rd

16 or 18 oval

10.00

50.25

10 rd

10 rd

16 or 18 oval

Note: Applications with extensive duct on intake and exhaust may require booster fans for airflow.

FIGURE 11 - HORIZONTAL SPLIT SYSTEM UERV’S FOR VH006 AND VH011 SERIES

Unitary Products Group

Control Box

(moveable to either side)

Filter Rack

(1 or 2 inch )

23

246681-YTG-B-0607

VU006-D- Series for 300 - 450 CFM

UERV for Ducted Applications

Features include service access from either end with control box moveable to either side.

Note: Booster fans may be required with long duct runs.

Air Handler

Control Box

VU006-W- Series for 300 - 450 CFM

UERV for Thru-the-Wall Applications

Features include service access from either end with control box moveable to either side.

Duct Box

(D1-Option)

Exploded View

29.00

22.13

37.25

12.75

Return Duct

(16" or 18" dia)

Filter Rack

15.13

10.00

40.13

24.50

23.63

Exhaust Air

(9" Dia)

Intake Air

(9" Dia)

VU011 Series for 600 - 1,000 CFM

UERV for Ducted Applications

Air Handler

Outline

The U11 ducted series is designed for installations that require higher airflow. The air handler is installed on top of one end of the UERV. Return, intake, and exhaust air is ducted to the

UERV.

Applications with long duct runs may require booster fans .

31.88

24.75

FIGURE 12 - UPFLOW SPLIT SYSTEM UERV’S

40.13

37.25

29.00

Perfect method of adding UERV to existing school classroom.

24.50

14.00

Adapter plate provided to fit air handler bottom.

29.50

Filter Rack

30.13

23.88

67.88

30.88

Wall Sleeve

(W1-Option)

Return Air (16" or 18" dia)

32.5

Exhaust Air (10" rd dia)

(Transition Provided)

Intake Air (10" rd dia on end of UERV)

Static Test

Ports

24 Unitary Products Group

246681-YTG-B-0607

TABLE 14: YORK HORIZONTAL AND UPFLOW SPLIT SYSTEM UERV MODELS 300 - 500 CFM

York Models

P*DH / P*XD-V

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*DH / P*XD-V

N*AH / N*VS B--G2FD

G*C

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*UR / P*XU / P*XU-V

N*AH / N*VS C--G2FD

G*C

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*UR / P*XU / P*XU-V

P*UR / P*XU / P*XU-V

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*DH / P*XD-V

P*DH / P*XD-V

P*DH / P*XD-V

N*AH / N*VS D--G2FD

G*C

CFM in

100’s

10

12

12

10

12

16

16

8

12

08/12

12

16

20

20

16

20

20

20

16

16

14

20

14/20

20

Capacity

037

032,048,060

037

055,075

024S,030S,036S

050,075

064,080

080

055

075

036S,042S,048S

075,100

064,080,092

092

075

095

095

104

112,130

075

075

112

048S,060S,061H

100,125,150

300-550 CFM

Horizontal Upflow

VH-006-Z02H

VH-006-Z03H

Horz Only

Upflow Only

VH-006-Y03H

VH-006-X03H

VH-006-W03H

VH-006-Z04H

Upflow Only

VH-006-Y04H

VH-006-X04H

VH-006-Z05H

Upflow Only

VH-006-Y05H

Upflow Only

VH-006-X05H

VH-006-W05H

VH-006-V05H

YH-006-U05H

Note: To designate whether the upflow UERV is ducted or thru-the-wall select “D” or “W” for digit #11.

Example: A UERV for wall sleeve application for a P3DHD20N112 would be a VH006W05H9WAA1.

VU-006-Z03H

Horz Only

VU-006-X03H

VU-006-W03H

VU-006-Z04H

VU-006-Y04H

VU-006-X04H

VU-006-Z05H

VU-006-Y05H

Horz Only

Horz Only

Horz Only

VU-006-V05H

YU-006-U05H

TABLE 15: YORK HORIZONTAL AND UPFLOW SPLIT SYSTEM UERV MODELS 600 - 1,000 CFM

York Models

P*DH / P*XD-V

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*DH / P*XD-V

N*AH / N*VS B--G2FD

G*C

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*UR / P*XU / P*XU-V

N*AH / N*VS C--G2FD

G*C

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*UR / P*XU / P*XU-V

P*UR / P*XU / P*XU-V

P*HU / P*DU / P*DU-V / P*HU-L / P*DU-L

P*UR / P*XU / P*XU-V

P*DH / P*XD-V

P*DH / P*XD-V

P*DH / P*XD-V

N*AH / N*VS D--G2FD

G*C

20

20

16

20

16

16

14

20

20

14/20

20

12

16

16

20

12

16

12

10

CFM in

100’s

10

12

8

12

08/12

Capacity

037

032,048,060

037

055,075

024S,030S,036S

050,075

064,080

080

055

075

036S,042S,048S

075,100

064,080,092

092

075

095

095

104

112,130

075

075

112

048S,060S,061H

100,125,150

600-1,000 CFM

Horizontal

VH-011-Z02H

Upflow

Horz Only

VH-011-Z03H

Upflow Only

VU-011-Z03H

VH-011-Y03H

VH-011-X03H

VH-011-W03H

Horz Only

VU-011-X03H

VU-011-W03H

VH-011-Z04H

Upflow Only

VH-011-Y04H

VH-011-X04H

VH-011-Z05H

Upflow Only

VH-011-Y05H

Upflow Only

VH-011-X05H

VH-011-W05H

VH-011-V05H

YH-011-U05H

VU-011-Z04H

VU-011-Y04H

VU-011-X04H

VU-011-Z05H

VU-011-Y05H

Horz Only

Horz Only

Horz Only

VU-011-V05H

YU-011-U05H

Note: Voltages are either single or three phase on 600 to 1,000 CFM UERV’s.

Unitary Products Group 25

246681-YTG-B-0607

Prepared for the guidance of architects, consulting engineers, and mechanical contractors.

GENERAL

GUIDE SPECIFICATIONS

Furnish and install _____________ mechanical cooling system, complete with a Unitized Energy Recovery Ventilator

(UERV).

APPROVALS

The Unitized Energy Recovery Ventilator will contain an energy recovery component rated in accordance with ARI

Standard 1060-2000 with ratings certified by ARI.

Cabinet

UERV shall be designed to attach directly to the a/c (rooftop, upflow, horizontal) unit. It shall be G90 galvanized material with a powdered enamel paint finish electrostatically bonded to the metal. Cabinet panels where conditioned air is handled shall be fully insulated to prevent sweating and minimize sound. Openings shall be provided for power connections.

Lifting devices will be provided for rigging. Test ports shall be provided so airflow can be measured across the energy recovery wheel.

Intake Air Blower (direct drive)

UERV shall contain a centrifugal blower. All UERV's will be equipped with direct drive PSC blower motors. The motor will be multiple speed and will be individually controlled. Airflow will also be adjustable by means of a damper on the intake air opening. Blowers and motors will be removable through means of a connecting plug for ease of servicing.

Intake Air Blower (belt drive)

UERV shall contain a centrifugal blower. It shall have ball bearings and adjustable belt drive. Motor mount base shall permit ease of motor changeover and belt tension adjustment. On pivoting wheel models, supply blower will be deenergized during economizer operation. (Except for VR074 and VR122.)

Exhaust Air Blower (direct drive)

UERV shall contain a centrifugal blower. All UERV's will be equipped with direct drive PSC blower motors. The motor will be multiple speed and shall be individually controlled. Blowers and motors will be removable through means of a connecting plug for ease of servicing. On pivoting wheel models, blower shall be sized to provide power exhaust during economizer operation.

Exhaust Air Blower (belt drive)

UERV shall contain a centrifugal blower. It shall have ball bearings and adjustable belt drive. Motor mount base shall permit ease of motor changeover and belt tension adjustment. On pivoting wheel models, exhaust blowers shall be sized to provide power exhaust during economizer operation.

Where single blowers cannot provide adequate exhaust, two blowers will be utilized. One blower is energized during energy recovery mode, and both blowers are energized during economizer mode.

Energy Recovery Wheel

The energy recovery device shall be a rotary heat exchanger per ARI Standard 1060 description. The device will be an enthalpy wheel coated with a silica gel desiccant by a patented process without the use of binders or adhesives which may plug the desiccant aperture. The substrate shall be a lightweight polymer. Desiccant shall not dissolve or deliquesce in the presence of water or high humidity. The wheel shall be easily cleanable with standard coil cleaning solution.

On UERV's Series 20 and less, the wheel will easily be removable from the cabinet for cleaning. On UERV's Series

28 and above, the wheel will be provided with removable segments for cleaning and maintenance. All diameter and perimeter seals shall be provided. The energy recovery cassette shall be Underwriters Laboratories Recognized Component for electrical and fire safety.

Balancing Dampers

Balancing dampers will be provided for all VR UERV’s. These dampers will be mounted inside the rooftop air conditioning unit to adjust for the amount of exhaust air on packaged units.

On pivoting wheel models, the unit economizer becomes the balancing damper. Upflow and horizontal ERVs' will have the balancing damper provided in the ERV. Optional on VO and

VS UERV’s when connected to rooftop units. (Except for

VR074 and VR122.)

Barometric Relief Dampers

Barometric relief dampers will be provided in the exhaust air hood to prevent air infiltration when the UERV is de-energized.

ERV Support

All UERV's will be provided with support legs attached to the cabinet to support the intake and exhaust end of the ERV unit. Horizontal ERV's will be provided with support brackets for hanging.

Filters

All units shall be provided with mist eliminator type filters in the intake air hood.

Power Connection

The UERV shall be provided with a single point power connection for high voltage.

26 Unitary Products Group

246681-YTG-B-0607

OPTIONS

Optional UERV Equipment Support

Furnish and install the optional equipment support for the intake and exhaust end of the unit.

Optional Roof Curb

Furnish and install the optional roof mounting frame to maintain proper height above the roof.

Optional Low Ambient Kit

Furnish and install the optional low ambient kit to prevent frost formation on the energy recovery wheel.

Optional Motorized Intake Air Damper

Furnish and install the optional motorized intake air damper.

Optional Stop-Start-Jog

On units without economizers furnish and install the optional stop-start-jog controls.

SEQUENCE OF OPERATION:

Fixed Models - Normal Operation

1.

The space thermostat sends a signal to the RTU for cooling, heating or fan only operation.

2.

The ERV is activated simultaneously with the supply blower of the RTU. The intake blower, the exhaust blower, and the wheel rotation motor of the ERV are activated. These motors will remain energized as long as the supply blower on the RTU is energized. The RTU is in standard (non-economizer) mode.

3.

If the optional motorized fresh air damper in the outside air intake of the ERV is present, it opens and the ERV is energized.

4.

If the optional low ambient kit is present, and the temperature leaving the exhaust side of the wheel drops below the field adjusted set point on the temperature sensor of the low ambient kit, the optional motorized fresh air damper will close and the intake blower will de-energize.

The exhaust air blower and wheel rotation motor will continue to operate. When the temperature sensor has a sixteen-degree rise, the wheel is defrosted and the optional motorized damper will open and the fresh air blower will reactivate.

Pivoting Models - Normal Operation

1.

The space thermostat sends a signal to the RTU for cooling, heating or fan only operation.

2.

The ERV is activated with the supply blower of the RTU.

The intake blower, the exhaust blower, and the wheel rotation motor of the ERV are activated. These motors will remain energized as long as the supply blower on the RTU is energized and the RTU is in standard (noneconomizer) mode.

3.

If the optional motorized fresh air damper in the outside air intake of the ERV is present, it opens and the ERV is energized.

4.

If the optional low ambient kit is present, and the temperature leaving the exhaust side of the wheel drops below the field adjusted set point on the temperature sensor of the low ambient kit, the optional motorized fresh air damper will close and the intake blower will de-energize.

The exhaust air blower and wheel rotation motor will continue to operate. When the temperature sensor has a sixteen-degree rise, the wheel is defrosted and the optional motorized damper will open and the fresh air blower will reactivate.

Pivoting Models - Economizer Operation

1.

The space thermostat sends a signal to the RTU for cooling operation.

2.

The outdoor air sensor for the RTU senses the outdoor air and determines it is appropriate for economizer operation.

3.

As the economizer outside air dampers open, the ERV economizer end switch is activated sending a signal to the ERV that the system is in the economizer mode.

4.

The intake blower, the exhaust blower and the wheel rotation motor all deactivate for up to two minutes. The optional motorized fresh air damper (if present) also closes.

5.

The ERV enthalpy wheel pivots out of the air stream and the bypass dampers along each side of the intake blower open.

6.

After a time delay to allow the wheel to pivot out of the airstream and the bypass dampers to open, the optional motorized fresh air damper opens to allow for full economizer operation, and the exhaust blower is reactivated to provide power exhaust for the system.

Unitary Products Group 27

246681-YTG-B-0607

UERV BELOW 600 CFM WITH STATIONARY WHEEL

(NO ECONOMIZER)

UERV will not operate.

1.

Quick check items.

a.

Verify S51 door switch is closed. The switch must be in the closed position to power the A130 circuit board.

b.

Verify the A130 circuit board switch SW1 Power is in the “on” position.

c.

Verify 24 volts to A130 circuit board terminals TB1

“G” and “C” if in the cooling mode, or “W” and “C” if in the heating mode. The terminals must be powered to allow any blower relays / contactors to operate.

2.

Verify high voltage power to UERV.

a.

Verify 110 volts for UERV to L1 and L2 on TB2 on the A130 board.

b.

Verify the F1 fuse is good. Replace any bad fuses.

c.

Verify that the T28 step down transformer on 208,

230, and 460 volt units have the voltage correctly applied to the correct transformer terminals.

UERV has power, but the enthalpy wheel does not spin.

1.

Check wheel belt is in place and tight.

2.

Verify the A130 circuit board switch SW1 Power is in the

"on" position.

3.

Verify the A130 circuit board terminals Wheel "1" and "2" are outputting 110 volts to B28 wheel motor through J/

P150 plug assembly.

4.

Verify B28 wheel motor C23 capacitor is good. Replace the capacitor if it is bad.

5.

If the optional Stop, Start, Jog (SSJ) feature is installed, verify that the temperature setpoint on the SSJ does not have the wheel stopped.

6.

If all of the above are operational, the wheel motor is bad. Replace it with new motor.

UERV has power, but the exhaust blower does not operate.

1.

Verify the A130 circuit board switch SW1 Power is in the

"on" position.

2.

Verify the A130 circuit board terminals Exhaust "1” and

"3” if in high speed operation, or "1” and "2" if in low speed operation are outputting 110 volts to B26 exhaust blower motor though J/P151 plug assembly.

UERV TROUBLESHOOTING GUIDE

3.

Verify B26 wheel motor C25 capacitor is good. Replace the capacitor if it is bad.

4.

If all of the above are operational, the exhaust motor is bad. Replace it with new motor.

UERV has power, but the fresh air blower does not operate.

1.

Verify the A130 circuit board switch SW1 Power is in the

"on" position.

2.

Verify the A130 circuit board terminals Fresh "1” and "3" if in high speed operation, or "1” and "2" if in low speed operation are outputting 110 volts to B27 fresh air blower motor though J/P148 plug assembly.

3.

On units equipped with the optional low ambient control, verify that the A130 circuit board TB3 terminals marked

"low ambient" are closed. The low ambient control will stop the fresh air motor operation and close the optional outside air damper if it senses conditions for frost on the

UERV wheel. The "low ambient" terminals can be jumped together to verify if the low ambient control has the fresh air blower stopped.

4.

Verify B27 wheel motor C26 capacitor is good. Replace the capacitor if it is bad.

5.

If all of the above are operational, the fresh air motor is bad. Replace it with new motor.

UERV has power, but the optional motorized fresh air damper does not open.

1.

Verify 24 volts to A130 circuit board terminals TB1 "G" and "C" if in the cooling mode, or "W" and "C" if in the heating mode.

2.

Verify the A130 circuit board switch SW1 Power is in the

"on" position.

3.

Verify 24 volts to B30 motorized outdoor air motor through J/P160 plug assembly.

4.

If all of the above are operational, replace the outdoor air damper motor.

UERV ABOVE 600 CFM WITH STATIONARY WHEEL

(NO ECONOMIZER)

UERV will not operate.

1.

Quick check items.

a.

Verify S51 door switch is closed. The switch must be in the closed position to power the A130 circuit board.

28 Unitary Products Group

246681-YTG-B-0607 b.

Verify 24 volts to A130 circuit board terminals

XFORMER "+" and "-". The terminals must be powered to allow blower contactors to operate. c.

Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the hot and "3" is the common side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit.

2.

Verify high voltage power to UERV.

a.

Check for correct voltage for UERV to L1 and L2 on

1-phase units. b.

Check for correct voltage for UERV to L1, L2, and

L3 on 3-phase units.

c.

Verify the F29 fuses are good. Replace any bad fuses.

d.

Verify that the T27 transformer has the UERV voltage correctly applied to the correct transformer terminals.

UERV has power, but the enthalpy wheel does not spin.

1.

Check wheel belt is in place and tight.

2.

Verify the A130 circuit board terminals Exhaust "A" (hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B" and that the contacts are closed.

3.

Verify power to B28 wheel motor.

4.

Verify B28 wheel motor C23 capacitor is good. Replace the capacitor if it is bad. (Except VR074 to VR122)

5.

If the optional Stop, Start, Jog (SSJ) feature is installed, verify that the timer on the SSJ does not have the wheel stopped.

6.

If all of the above are operational, the wheel motor is bad. Replace it with new motor.

UERV has power, but the exhaust blower does not operate.

1.

Check that the blower belt is in place and tight on belt drive models. If it is loose, tighten it. If it is broken replace it.

2.

Verify the A130 circuit board terminals Exhaust "A" (hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B", and that the contacts are closed.

3.

Verify power to B26 exhaust blower motor.

4.

On direct drive models, verify B26 wheel motor C25 capacitor is good. Replace if necessary.

5.

If all of the above are operational, the exhaust motor is bad. Replace it with new motor.

UERV has power, but the fresh air blower does not operate.

1.

Check that the blower belt is in place and tight on belt drive models. Tighten it if it is loose. Replace it if it is broken.

2.

Verify the A130 circuit board terminals Fresh "A" (hot) and "B" (common) are outputting 24 volts to K164 contactor terminal "A" and "B", and that the contacts are closed.

3.

Verify power to B27 fresh air blower motor though J/

P148 plug assembly.

4.

On direct drive models, verify B27 wheel motor C26 capacitor is good. Replace if necessary.

5.

On units equipped with the optional low ambient control, verify that the circuit on the A130 circuit board terminal

"5" and "6" is closed. The low ambient control will stop the fresh air motor operation and close the optional outside air damper if it senses frost on the UERV wheel.

Terminal "5" and "6" can be jumped together to verify if the low ambient control has the fresh air blower stopped.

6.

If all of the above are operational, the fresh air motor is bad. Replace it with new motor.

UERV has power, but the optional motorized fresh air damper does not open.

1.

Verify 24 volts to the A130 circuit board terminals

XFORMER "+" and "-".

2.

Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the hot and "3" is the common side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit.

3.

Verify 24 volts to B30 motorized outdoor air motor through J/P160 plug assembly.

4.

If all of the above are operational, replace the outdoor air damper motor.

UERV ABOVE 600 CFM WITH PIVOTING WHEEL

(USED WITH ECONOMIZER)

UERV will not operate.

1.

Quick check items.

a.

Verify S51 door switch is closed. The switch must be in the closed position to power the A130 circuit board.

Unitary Products Group 29

246681-YTG-B-0607 b.

Verify 24 volts to A130 circuit board terminals

XFORMER "+" and "-". The terminals must be powered to allow any blower relays / contactors to operate. c.

Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the hot and "3" is the common side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit.

2.

Verify high voltage power to UERV.

a.

Check correct voltage for UERV to L1 and, L2 on 1phase units. b.

Check for correct voltage to L1, L2, and L3 on 3phase units.

c.

Verify the F29 fuses are good. Replace any bad fuses.

d.

Verify that the T27 transformer has the UERV voltage correctly applied to the correct transformer terminals.

UERV has power, but the enthalpy wheel does not spin.

1.

Check wheel belt is in place and tight.

2.

Verify the A130 circuit board terminals Exhaust 1 "A"

(hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B" and that the contacts are closed.

3.

Verify power to B28 wheel motor through J/P150 plug assembly.

a.

If there is no power on the T1 leg of the motor (pivoting models only) verify that the S110 switch located inside the B29 damper motor is in the closed position.

4.

Verify B28 wheel motor C23 capacitor is good. Replace the capacitor if it is bad.

5.

If all of the above are operational, the wheel motor is bad. Replace it with new motor.

UERV has power, but the exhaust blower does not operate.

1.

Check that the blower belt is in place and tight. If it is loose, tighten it. If it is broken replace it.

2.

Verify the A130 circuit board terminals Exhaust 1 "A"

(hot) and "B" (common) are outputting 24 volts to K163 contactor terminal "A" and "B", and that the contacts are closed.

3.

Verify power to B26 exhaust blower motor though J/P151 plug assembly.

4.

On direct drive models, verify B26 wheel motor C25 capacitor is good. Replace if necessary.

5.

If all of the above are operational, the exhaust motor is bad. Replace it with new motor.

UERV has power, but the fresh air blower does not operate.

1.

Energy Recovery Mode of operation.

a.

Check that the blower belt is in place and tight on belt drive models. Tighten it if it is loose. Replace it if it is broken.

b.

Verify the A130 circuit board terminals Fresh "A"

(hot) and "B" (common) are outputting 24 volts to

K164 contactor terminal "A" and "B", and that the contacts are closed. c.

Verify power to B27 fresh air blower motor though J/

P148 plug assembly.

d.

On units equipped with the optional low ambient control, verify that the circuit on the A130 circuit board terminal "5" and "6" is made. The low ambient control will stop the fresh air motor operation and close the optional outside air damper if it senses frost on the UERV wheel. Terminal "5" and "6" can be jumped together to verify if the low ambient control has the fresh air blower stopped. e.

On direct drive models, verify B27 wheel motor C26 capacitor is good. Replace if necessary.

f.

If all of the above are operational, the fresh air motor is bad. Replace it with new motor.

2.

Economizer Mode of operation.

a.

The fresh air blower is not operational in the economizer mode.

UERV has power, but the wheel does not rotate out of airstream during economizer operation.

1.

Check the linkage from the B29 damper motor to the

UERV wheel.

2.

Verify shipping retainers are removed.

3.

Verify the S122 economizer end switch is closed. The switch is located on the damper and closes when the damper moves from minimum position to the economizer position (field adjustable).

4.

Verify the B29 damper motor has 24 volts to terminals

"B" and "T1" through J/P160 plug assembly

5.

If all of the above are operational, replace the damper motor.

30 Unitary Products Group

246681-YTG-B-0607

UERV has power, but the optional motorized fresh air damper does not open.

1.

Verify 24 volts to the A130 circuit board terminals

XFORMER "+" and "-".

2.

Verify 24 volts to A130 circuit board terminals TB 37 numbers "1" and "3". Terminal "1" is the "hot" and "3" is the "common" side of the power source from activation power source (a/c unit, energy management control, etc.). Typically, "1" would be from the blower contactor on an a/c unit.

3.

Verify 24 volts to B30 motorized outdoor air motor through J/P160 plug assembly.

4.

If all of the above are operational, replace the outdoor air damper motor.

Unitary Products Group 31

Subject to change without notice. Printed in U.S.A.

Copyright © by Unitary Products Group 2007. All rights reserved.

Unitary

Products

Group

5005

York

Drive

246681-YTG-B-0607

Supersedes: 246681/036-21360-004-A-0105

Norman

OK

73069

advertisement

Related manuals

advertisement