Cyber Power PDU15M10AT, PDU20M10AT, PDU30MT17AT User Manual

Add to My manuals
34 Pages

advertisement

Cyber Power PDU15M10AT, PDU20M10AT, PDU30MT17AT User Manual | Manualzz

Automatic Transfer Switch

USER'S MANUAL

Copyright © 2018 Cyber Power Systems, Inc. All rights reserved.

Table of Contents

Overview ................................................................................. 1

Model List ............................................................................... 1

Product Contents ..................................................................2

For 1U Models .............................................................................................2

For 2U Models ............................................................................................3

Product Features .................................................................. 4

Front/Rear Panel Description (1U 15A Models) ............................ 4

Technical Specifications ........................................................................ 4

Front/Rear Panel Description (1U 20A Models) ...........................5

Technical Specifications .........................................................................5

Front/Rear Panel Description (2U 30A Models) ..........................6

Technical Specifications .........................................................................6

Front/Rear Panel Description (2U 32A Models) ...........................7

Technical Specifications .........................................................................7

Installation Guide ..................................................................8

ATS PDU Configuration ..........................................................................8

Front Mounting ..........................................................................................9

For 1U Models .......................................................................................9

For 2U Models ....................................................................................10

Rear Mounting .......................................................................................... 1 1

For 1U Models ..................................................................................... 1 1

For 2U Models .................................................................................... 13

Replacing LCD Panel ............................................................................. 15

Electrical Installation ............................................................................. 15

Power Cord Locking - For IEC Type ATS PDU ............................ 16

Input Power Cord .............................................................................. 16

Output Power Cord .......................................................................... 16

Network Installation ............................................................................... 17

Operation .............................................................................. 18

Remote Management ............................................................................ 18

Web ........................................................................................................ 18

Telnet and SSH ................................................................................... 18

SNMP ..................................................................................................... 18

Local Management ................................................................................. 18

LCD Operation ................................................................................... 18

LED Indicators .................................................................................... 19

Environmental Monitoring (optional) ........................................ 19

Device Reset ....................................................................................... 19

Unattended/Automatic Shutdown ............................................. 19

Firmware Upgrade.............................................................. 20

ATS PDU ..............................................................................................20

LCD ...................................................................................................... 2 1

RMCARD .............................................................................................. 23

Troubleshooting ................................................................. 25

Conformance Approvals .................................................... 26

Customer Service & Warranty .......................................... 27

Appendix A-Hyper Terminal ............................................. 28

Appendix B-Power Device Network Utility .................... 29

Overview

CyberPower Automatic Transfer Switches PDUs with dual input for power provide redundant and increased reliability for critical devices with a single power plug. Users can define the preferred input power source. When a selected source is unstable or unavailable, the ATS PDU will switch to the second power source to constantly provide power to connected devices. The entire ATS PDU series are designed with LED and LCD interfaces for users to easily observe power status and device load. On-site power management is accomplished as users can configure power settings, via LCD interface, according to local power condition. Available in both switched and metered/ monitored configurations, users have a broad base of options to select the

ATS PDU that best fits their needs.

WARNING: This automatic transfer switch has dual power cords (A & B) to provide redundant power sources to devices with single power supplies and can be plugged into separate compatible sources* to ensure continuous access. Users select the preferred source as the primary input. CyberPower

Smart App Online and Sinewave series UPS are highly recommended for use as the power source.

* Note: Only sine wave AC power sources are compatible with this ATS PDU.

Simulated sine wave AC power sources are NOT compatible.

Model List

Switched Series

1U

PDU15SW10ATNET

PDU20SW10ATNET

PDU20SWT10ATNET

PDU20SWHVT10ATNET

PDU15SWHVIEC12ATNET

PDU20SWHVIEC10ATNET

PDU20SWHVCEE10ATNET*

2U

PDU30SWT17ATNET

PDU30SWHVT19ATNET

PDU32SWHVCEE18ATNET*

Metered/Monitored Series

1U

PDU15M10AT

PDU20M10AT

PDU20MT10AT

PDU20MHVT10AT

PDU15MHVIEC12AT

PDU20MHVIEC10AT

PDU20MHVCEE10AT*

2U

PDU30MT17AT

PDU30MHVT19AT

PDU32MHVCEE18AT*

*Selected models may not be available in certain regions. Please contact your

CyberPower sales team for more information.

Safety Precautions

Read the following before installing or operating the Automatic Transfer

Switches (ATS) PDU:

• Use only the supplied hardware to attach the mounting brackets.

• The ATS PDU must be plugged into a single phase three-wire, grounded outlet on a circuit that is protected by a fuse or circuit breaker. For

PDU15xxxxx series, please use a 15A circuit protector. For PDU20xxxxx series, please use a 20A circuit protector. For PDU30xxxxx series, please use a 30A circuit protector. Connection to any other type of power outlet may result in a electrocution hazard.

• Do not use extension cords or adapters with these ATS PDUs.

• Never install an ATS PDU or associated wiring or equipment during a lightning storm.

• Ensure that the power cord, plug, and socket are in good condition.

Check

To prevent the risk of fire or electrocution, this ATS PDU should be installed in a temperature and humidity controlled indoor area free of conductive contaminants. Do not install this ATS PDU where excessive moisture or heat is present.

Before using, please check to ensure the package contains all the items shown below. If there are missing parts, please contact your local CyberPower sales team for technical support.

1

Product Contents

For 1U Models

ATS PDU

Mounting Bracket x 2 24 (M4x8) Bracket Mounting Screws

(Includes eight spares)

Cord Retention Tray 4 (M3x4) Cord Retention Tray

Mounting Screws

6 (M5x12) Rack Mounting Screws/

6 Washers (Includes two spares for each)

Cable Ties

Qty.: 18 (NEMA Outlet)

Qty.: 30 (IEC Outlet)

RJ45/DB9 Serial Port

Connection Cable

Jumper (Switched type only)

Users Manua l

Registration

Card

PowerPanel

Management Software

User's Manual, Registration & Software Download Cards

Below items only provided with IEC type ATS PDU

Power Cord 10 feet

IEC-320 C13/C14 x 2

(PDU15SWHVIEC12ATNET/

PDU15MHVIEC12AT Model Only)

Power Cord 10 feet

IEC-320 C19/C20 x 2

(PDU20SWHVIEC10ATNET/

PDU20MHVIEC10AT Model Only)

2

Product Contents

For 2U Models

ATS PDU

Mounting Bracket x 2 24 (M4x8) Bracket Mounting Screws

(Includes eight spares)

Cord Retention Tray X 2 8 (M3x4) Cord Retention Tray

Mounting Screws

6 (M5x12) Rack Mounting Screws/

6 Washers (Includes two spares for each)

Cable Ties

Qty.: 30 (NEMA Outlet)

Qty.: 50 (IEC Outlet)

RJ45/DB9 Serial Port

Connection Cable

Jumper (Switched type only)

Users Manua l

Registration

Card

PowerPanel

Management Software

User's Manual, Registration & Software Download Cards

3

A B

Expansion Port

Provides SNMP Card Communication

Serial Port

C D E F G

Source Output

A

- Normal

- Overload

B

QCN-0000002-00

PDU20SWT10ATNET

Select

Enter

J

SOURCE A SOURCE B

H I

1 2 3 4 5

K

6 7 8 9 10

J

10

H I

1 2 3 4 5 6

K

7 8 9

A B C D E F G

H

H

SOURCE A

SOURCE B

SOURCE A

SOURCE B

Expansion Port

Provides SNMP Card Communication

Serial Port

Source Output

A B1

B

B2

B3

QCN-0000005-00

- Warning

- Overload

PDU30SWT17ATNET

Select

Enter

I

1 2 3 4 5 6 7

9 10 11 12 13

J

I

14 15

BANK 1 (20A)

BANK 3 (24A)

8

16

K

BANK 2 (20A)

L

L5-30R

17

BANK 1 (20A)

BANK 3 (24A)

1 2 3 4 5 6 7 8 9

BANK 2 (20A)

L6-30R

19

10 11 12 13 14 15 16

J

17 18

K L

Product Features

Front/Rear Panel Description (1U 15A Models)

A B C D E F G

Expansion Port

Provides SNMP Card Communication

Serial Port

Source Output

A

- Normal

- Overload

B

QCN-0000003-00

PDU20SWHVIEC10ATNET

Select

Enter

NEMA Type

SOURCE A SOURCE B

J

3 4 8 9

H

IEC Type

I

J

K

6 10

1 2 3 4 9 10 11 12

H I

5 6

K

7 8

H

A. SNMP/HTTP Network Slot

Allows users to remotely control and monitor the ATS PDU when installed with CyberPower’s Remote Management Card.

B. Serial Port (RJ45 modular port)

Use serial port to connect with PC and execute local control of the ATS PDU.

C. Source Indicator

Indicates Source A or B is in use. When both sources are normal, selected source shows constant green LED while another source shows blinking green LED.

D. Output Indicator

Indicates load condition of the ATS PDU.

E. Multifunction LCD Readout

C D E F G

Displays various ATS PDU information such as power and load conditions.

F. Select Button

Source Output

A B1

Select

Use to control the LCD screen and toggle through the available

Provides SNMP Card Communication informational options.

B B2

Enter

QCN-0000021-00

PDU32SWHVCEE18ATNET

Serial Port

G. Enter Button

Use to choose selected items, enter to next level menu or return to

I previous menu.

H. AC Inlet/AC Power Cord

Use to connect ATS PDU to utility power or UPS.

I. Ground Stud

BANK 1 (20A)

Use to ground the ATS PDU.

J. AC Output Receptacles

5 6 7 8 9

BANK 2

(20A)

Provides power distribution for connected equipment.

K. Outlet Indicator (switched series only)

17 18

When the LED is on, the outlet is providing power to connected equipment.

J K L

Technical Specifications

Model Name

Input

Nominal Voltage

Frequency

Derated Input Current

Plug Type

100-120V

12A

Switched Series

(2) NEMA 5-15P

Metered Series

PDU15SW10ATNET PDU15SWHVIEC12ATNET PDU15M10AT

200-240V

50/60Hz

100-120V

12A(UL)/10A(CE)

(2) IEC-320 C14

12A

(2) NEMA

5-15P

Socket

10 ft/3.05 m

SR (14 AWG)

PDU15MHVIEC12AT

200-240V

12A(UL)/10A(CE)

(2) IEC-320 C14

Power Cord Type

Power Cord Length

Output

Nominal Voltage

Derated Output Current

Outlet Type

Outlet Number

Transfer Time

SR (14 AWG)

100-120V

12A

NEMA 5-15R

10

200-240V

12A(UL)/10A(CE)

IEC-320 C13

100-120V

12A

NEMA 5-15R

12 10

Typical: 8-12ms

16ms max @ 60Hz/ 18ms max @ 50Hz

Socket

200-240V

12A(UL)/10A(CE)

IEC-320 C13

12

Management and Communications

Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information

Software

Networking

Serial Port

PowerPanel® Business Edition

Yes, with installed RMCARD

RJ45

Optional

Yes, with optional RMCARD

Sensor Capable

Physical

Dimension (W x H x D) 17.05" x 1.75" x 9.3"/433mm x 44mm x 236mm

Environmental

Humidity

Altitude

Temperature

Safety Approvals

0 to 95% Non-condensing

13100 ft/4000 m

32 o F to 113 o F/0 o C to 45 o C

Certifications

UL 60950-1

FCC Class A

UL 60950-1

CE, FCC Class A

UL 60950-1

FCC Class A

UL 60950-1

CE, FCC Class A

* All specifications are subject to change without notice.

4

Product Features

Front/Rear Panel Description (1U 20A Models)

A B C D E F G

Expansion Port

Provides SNMP Card Communication

Serial Port

Source Output

A

- Normal

- Overload

B

QCN-0000002-00

PDU20SWT10ATNET

Select

Enter

NEMA Type

SOURCE A SOURCE B

J

H

IEC Type

I

1 2 3 4 5

K

6 7 8 9

J

10

A B

Expansion Port

Provides SNMP Card Communication

Serial Port

SOURCE A SOURCE B

H I

3 4

J

J

K

6

C D E F G

Source Output

A

- Normal

- Overload

B

QCN-0000003-00

PDU20SWHVIEC10ATNET

Select

Enter

8 9 10

1 2 3 4 5 6 7 8

C D E

9 10 11 12

1 2 3 4 9 10

H I

5 6

K

7 8

A. SNMP/HTTP Network Slot

Allows users to remotely control and monitor the ATS PDU when installed with CyberPower’s Remote Management Card.

B. Serial Port (RJ45 modular port)

Use serial port to connect with PC and execute local control of the ATS PDU.

C. Souce Indicator

Indicates Source A or B is in use. When both sources are normal, selected source shows constant green LED while another source shows blinking

A B C D E F G green LED.

D. Output Indicator

Indicates load condition of the ATS PDU.

E. Multifunction LCD Readout

Displays various ATS PDU information such as power and load conditions.

F. Select Button

Provides SNMP Card Communication

A B1

B2

Select

B

QCN-0000005-00

B3

- Warning

- Overload

PDU30SWT17ATNET

Enter Use to control the LCD screen and toggle through the available informational options.

G. Enter Button

Use to choose selected items, enter to next level menu or return to previous menu.

H. AC Inlet/AC Power Cord

BANK 1 (20A)

BANK 3 (24A)

Use to connect ATS PDU to utility power or UPS.

1 2

I. Ground Stud

3 4 5 6 7 8

BANK 2 (20A)

Use to ground the ATS PDU.

J. AC Output Receptacles

L5-30R

17

12 13 14 15 16

H

Provides power distribution for connected equipment.

K. Outlet Indicator (switched series only)

K L

When the LED is on, the outlet is providing power to connected equipment.

I

BANK 1 (20A)

SOURCE A

Technical Specifications

BANK 3 (24A)

SOURCE B

Model Name

1

10

Nominal Voltage

Frequency

Derated Input Current

2

11

3 4

PDU20SW10ATNET

14

5 Switched Series 8

15

9

PDU20SWHVT10ATNET

PDU20SWHVCEE10ATNET

BANK 2 (20A)

Metered Series

PDU20M10AT

PDU20MT10AT

K L

PDU20MHVT10AT

L6-30R

PDU20MHVCEE10AT

19

PDU20MHVIEC10AT

100-120V

J

200-240V

50/60Hz

16A

(2) NEMA L6-20P

100-120V 200-240V

Plug Type

(2) NEMA 5-20P

(2) IEC 309 16A

(2) IEC-320 C20

( 2) NEMA 5-20P

(2) NEMA L6-20P

(2) IEC 309 16A

Power Cord Type

(2) NEMA L5-20P

SR (12AWG)

SR (12AWG)

Socket

10 ft/3.05 m

(2) NEMA L5-20P

SR (12 AWG)

(2) IEC-320 C20

SR (12AWG)

Socket

Power Cord Length

Output

Nominal Voltage

Derated Output Current

Outlet Type

100-120V

16A

NEMA 5-20R

200-240V

C13: 12A (UL)

10A (CE)

C19: 16A

(8) IEC C13

(2) IEC C19

8+2

100-120V

16A

NEMA 5-20R

200-240V

C13: 12A (UL)

10A (CE)

C19: 16A

(8) IEC C13

(2) IEC C19

8+2 Outlet Number 10 10

Transfer Time

Typical: 8-12ms

16ms max @ 60Hz/ 18ms max @ 50Hz

Management and Communications

Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information

Software

Networking

Serial Port

Sensor Capable

Physical

Dimension (W x H x D)

Environmental

Humidity

Altitude

Temperature

Safety Approvals

PowerPanel® Business Edition

Yes, with installed RMCARD

RJ45

Optional

13100 ft/4000 m

Certifications

UL 60950-1

FCC Class A

UL 60950-1

FCC Class A

UL 60950-1

CE, FCC Class A

* All specifications are subject to change without notice.

Yes, with optional RMCARD

17.05" x 1.75" x 9.3"/433mm x 44mm x 236mm

0 to 95% Non-condensing

32 o F to 113 o F/0 o C to 45 o C

UL 60950-1

FCC Class A

UL 60950-1

FCC Class A

UL 60950-1

CE, FCC Class A

H

A

H I

B

Expansion Port

Provides SNMP Card Communication

Serial Port

1 2 3 4

I

5 6

K

7 8

10 11 12 13

J

14 15 16 17

K

BANK 1 (20A)

BANK 2

(20A)

L

F G

Source Output

A B1

B

QCN-0000021-00

B2

- Normal

- Warning

- Overload

PDU32SWHVCEE18ATNET

Select

Enter

9

18

5

A B

Expansion Port

Provides SNMP Card Communication

Serial Port

C D E F G

Source Output

A

- Normal

- Warning

- Overload

B

QCN-0000002-00

PDU20SWT10ATNET

Select

Enter

J

SOURCE A SOURCE B

H I

1 2 3 4 5

K

6 7 8 9 10

J

10

H I

1 2 3 4 5 6

K

7 8 9

A

SOURCE A SOURCE B

H I

B

Expansion Port

Provides SNMP Card Communication

Serial Port

3 4

J

J

K

6

C D E F G

Source Output

A

- Normal

- Warning

- Overload

B

QCN-0000003-00

PDU20SWHVIEC10ATNET

Select

Enter

8 9 10

H I

1 2 3 4 5 6

K

7 8 9 10 11 12

Product Features

Front/Rear Panel Description (2U 30A Models)

A B C D E F G

A B C D E

Expansion Port

Provides SNMP Card Communication

Source Output

A B1

B

B2

B3

QCN-0000005-00

- Warning

- Overload

PDU30SWT17ATNET

Select

Enter

Serial Port

NEMA Type

SOURCE A

I

BANK 1 (20A)

BANK 3 (24A)

1 2 3 4 5 6 7 8

SOURCE B

BANK 2 (20A)

L5-30R

17

9 10 11 12 13 14 15 16

J

I

K L

H

IEC Type

SOURCE A

BANK 1 (20A)

BANK 3 (24A)

1 2 3 4 5 6 7 8 9

BANK 2

(20A)

SOURCE B

L6-30R

19

10 11 12 13 14 15 16 17 18

K L

H J

A. SNMP/HTTP Network Slot

Allows users to remotely control and monitor the ATS PDU when installed with CyberPower’s Remote Management Card.

B. Serial Port (RJ45 modular port)

Use serial port to connect with PC and execute local control of the ATS PDU.

C. Source Indicator

Indicates Source A or B is in use. When both sources are normal, selected source shows constant green LED while another source shows blinking green LED.

D. Output Indicator

Indicates load condition of the ATS PDU.

E. Multifunction LCD Readout

Displays various ATS PDU information such as power and load conditions.

F. Select Button

Use to control the LCD screen and toggle through the available informational options.

G. Enter Button

Use to choose selected items, enter to next level menu or return to previous menu.

H. AC Inlet/AC Power Cord

Use to connect ATS PDU to utility power or UPS.

I. AC Output Receptacles

Provides power distribution for connected equipment.

J. Outlet Indicator (switched series only)

When the LED is on, the outlet is providing power to connected equipment.

K. Circuit Breaker

Provides output overload protection.

L. Ground Stud

Use to ground the ATS PDU.

Technical Specifications

Model Name

Input

Nominal Voltage

Frequency

Derated Input Current

Plug Type

Power Cord Type

Power Cord Length

Output

Nominal Voltage

PDU30SWT17ATNET PDU30SWHVT19ATNET

100-120V

Switched Series

(2) NEMA L5-30P

200-240V

50/60Hz

24A

Metered Series

PDU30MT17AT

100-120V

PDU30MHVT19AT

200-240V

(2) NEMA L6-30P (2) NEMA L5-30P (2) NEMA L6-30P

SR (10 AWG)

10 ft/3.05 m

Derated Output Current

100-120V

5-20R: 16A

L5-30R: 24A

200-240V

C13: 12A

C19: 16A

L6-30R: 24A

100-120V

5-20R: 16A

L5-30R: 24A

200-240V

C13: 12A

C19: 16A

L6-30R: 24A

Derated Output Current

(each bank)

20A

Bank Number

Outlet Type

Outlet Number

Circuit Breaker

Sensor Capable

Physical

Dimension (W x H x D)

(16) NEMA 5-20R

(1) NEMA L5-30R

17

2

(16) IEC C13

(2) IEC C19

(1) NEMA L6-30R

19

Yes

RJ45

Optional

(16) NEMA 5-20R

(1) NEMA L5-30R

17

17.05" x 3.5" x 9.3"/433mm x 88mm x 236mm

(16) IEC C13

(2) IEC C19

(1) NEMA L6-30R

19

Transfer Time

Typical: 8-12ms

16ms max @ 60Hz/ 18ms max @ 50Hz

Management and Communications

Multifunction LCD

Readout

Voltage, Frequency, Load, Current, HW/FW Version, Network Information

Software

Networking

PowerPanel® Business Edition

Yes, with installed RMCARD Yes, with optional RMCARD

Serial Port

Environmental

Humidity

Altitude

Temperature

Safety Approvals

Certifications

0 to 95% Non-condensing

13100 ft/4000 m

32 o F to 113 o F/0 o C to 45 o C

UL 60950-1, FCC Class A

* All specifications are subject to change without notice.

6

H

Expansion Port

Provides SNMP Card Communication

Serial Port

I

1 2 3 4 5 6 7 8

10 11 12 13

J

14 15 16 17

Source Output

A B1

B

QCN-0000021-00

B2

- Normal

- Warning

- Overload

PDU32SWHVCEE18ATNET

Select

Enter

9

18

K

BANK 1 (20A)

BANK 2 (20A)

L

F G

A B

Expansion Port

Provides SNMP Card Communication

Serial Port

C D E

Source Output

A

B

QCN-0000002-00

F G

PDU20SWT10ATNET

Select

Enter

J

SOURCE A SOURCE B

H I

1 2 3

J

4 5

K

6 7 8 9 10

10

H I

1 2 3 4 5 6

K

7 8 9

A

SOURCE A SOURCE B

H I

B

Expansion Port

Provides SNMP Card Communication

Serial Port

3 4

J

J

K

6

C D E F G

Source Output

A

B

QCN-0000003-00

Select

PDU20SWHVIEC10ATNET

Enter

8 9 10

H I

1 2 3 4 5 6

K

7 8 9 10 11 12

A B C D E F G

H

H

SOURCE A

SOURCE B

SOURCE A

SOURCE B

Expansion Port

Provides SNMP Card Communication

Serial Port

Source Output

A B1

B

QCN-0000005-00

B2

B3

- Normal

- Overload

PDU30SWT17ATNET

Select

Enter

1 2 3

1 2 3 4

4

9 10 11 12

I

BANK 1 (20A)

BANK 3 (24A)

5 6 7 8

BANK 2 (20A)

13

J

I

14 15 16

K

BANK 1 (20A)

L

L5-30R

17

BANK 3 (24A)

5 6 7 8 9

BANK 2 (20A)

L6-30R

19

10 11 12 13 14 15 16

J

17 18

K L

Product Features

Front/Rear Panel Description (2U 32A Models)

A B C D E F G

H

Expansion Port

Provides SNMP Card Communication

Serial Port

Source Output

A B1

B

QCN-0000021-00

B2

- Warning

- Overload

PDU32SWHVCEE18ATNET

Select

Enter

I

1 2 3 4 5 6 7 8

10 11 12 13

J

14 15 16 17

9

18

K

BANK 1 (20A)

BANK 2

(20A)

L

A. SNMP/HTTP Network Slot

Allows users to remotely control and monitor the ATS PDU when installed with CyberPower’s Remote Management Card.

B. Serial Port (RJ45 modular port)

Use serial port to connect with PC and execute local control of the

ATS PDU.

C. Source Indicator

Indicates Source A or B is in use. When both sources are normal, selected source shows constant green LED while another source shows blinking green LED.

D. Output Indicator

Indicates load condition of the ATS PDU.

E. Multifunction LCD Readout

Displays various ATS PDU information such as power and load conditions.

F. Select Button

Use to control the LCD screen and toggle through the available informational options.

G. Enter Button

Use to choose selected items, enter to next level menu or return to previous menu.

H. AC Inlet/AC Power Cord

Use to connect ATS PDU to utility power or UPS.

I. AC Output Receptacles

Provides power distribution for connected equipment.

J. Outlet Indicator (switched series only)

When the LED is on, the outlet is providing power to connected equipment.

K. Circuit Breaker

Provides output overload protection.

L. Ground Stud

Use to ground the ATS PDU.

Technical Specifications

Model Name

Input

Nominal Voltage

Frequency

Max. Input Current

Plug Type

Power Cord Type

Power Cord Length

Output

Nominal Voltage

Switched Series

PDU32SWHVCEE18ATNET

200-240V

50/60Hz

32A

(2) IEC 309 32A

SR (10 AWG)

10 ft/3.05 m

Metered Series

PDU32MHVCEE18AT

200-240V

C13: 10A

Derated Output Current

C19: 16A

Derated Output Current

(each bank)

Bank Number

20A

Outlet Type

2

(16) IEC C13

(2) IEC C19

Outlet Number

Circuit Breaker

18

Yes

Transfer Time

Typical: 8-12ms

16ms max @ 60Hz/ 18ms max @ 50Hz

Management and Communications

Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information

Software

Networking

Serial Port

Sensor Capable

PowerPanel® Business Edition

Yes, with installed RMCARD

RJ45

Optional

Yes, with optional RMCARD

Physical

Dimension (W x H x D)

Environmental

Humidity

Altitude

Temperature

Safety Approvals

Certifications

17.05" x 3.5" x 9.3"/433mm x 88mm x 236mm

0 to 95% Non-condensing

13100 ft/4000 m

32 o F to 113 o F/0 o C to 45 o C

CE

* All specifications are subject to change without notice.

7

Installation Guide

ATS PDU Configuration

WARNING: This automatic transfer switch has dual power cords (A & B) to provide redundant power sources to devices with single power supplies and can be plugged into separate compatible sources* to ensure continuous access. Users select the preferred source as the primary input. CyberPower

Smart App Online and Sinewave series UPS are highly recommended for use as the power source.

* Note: Only sine wave AC power sources are compatible with this ATS PDU.

Simulated sine wave AC power sources are NOT compatible.

Best Configuration

SOURCE A

SOURCE B

Minimum Acceptable Configuration

ON/OFF

ON/OFF

SELE CT

SELE CT

SOURCE A

(Preferred Source)

SOURCE B

8

Installation Guide

Please only use the provided screws for the entire installation process.

Front Mounting

For 1U Models

Step 1. Mounting Bracket Installation

Use the provided Mounting Bracket Screws (16) to attach the

Mounting Brackets (2) to the ATS PDU.

Step 2. Cord Retention Tray Installation (optional)

Adjust the length of the Cord Retention Tray till the screw hole on the

Tray and ATS PDU are aligned. Attach the Cord Retention Tray to the

ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws.

Tighten the Cord Retention Tray with the screw on it.

Step 3. ATS PDU Mounting

Use the provided Washers (4) and Screws (4) to secure the ATS PDU to your existing rack system.

Note: You may also use the screw sets provided by the rack to secure the ATS PDU.

9

Installation Guide

Front Mounting

Step 4. Cable Ties (Optional)

Use the provided Cable Ties to fasten each cord to the Cord

Retention Tray.

For 2U Models

Step 1. Mounting Bracket Installation

Use the provided Mounting Bracket Screws (16) to attach the

Mounting Brackets (2) to the ATS PDU.

Step 2. Cord Retention Tray Installation (optional)

Adjust the length of the Cord Retention Trays till the screw hole on the Trays and ATS PDU are aligned. Attach the Cord Retention Trays to the ATS PDU with the 8 supplied Cord Retention Tray Mounting

Screws. Tighten the Cord Retention Trays with the screw on it.

10

Installation Guide

Front Mounting

Step 3. ATS PDU Mounting

Use the provided Washers (4) and Screws (4) to secure the ATS PDU to your existing rack system.

Note: You may also use the screw sets provided by the rack to secure the ATS PDU.

Step 4. Cable Ties (Optional)

Use the provided Cable Ties to fasten each cord to the Cord

Retention Tray.

Rear Mounting

For 1U Models

Step 1. Mounting Bracket Installation

Use the provided Mounting Bracket Screws (16) to attach the

Mounting Brackets (2) to the ATS PDU.

11

Installation Guide

Rear Mounting

If you plan on attaching the Cord Retention Tray to the ATS PDU, use the provided Mounting Bracket Screws (8) to attach the Mounting

Brackets (2) to the ATS PDU.

Step 2. Cord Retention Tray Installation (optional)

Adjust the length of the Cord Retention Tray till the screw hole on the

Tray and ATS PDU are aligned. Attach the Cord Retention Tray to the

ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws.

Tighten the Cord Retention Tray with the screw on it.

Step 3. ATS PDU Mounting

Use the provided Washers (4) and Screws (4) to secure the ATS PDU to your existing rack system.

Note: You may also use the screw sets provided by the rack to secure the ATS PDU.

12

Installation Guide

Rear Mounting

Step 4. Cable Ties (Optional)

Use the provided Cable Ties to fasten each cord to the Cord

Retention Tray.

For 2U Models

Step 1. Mounting Bracket Installation

Use the provided Mounting Bracket Screws (16) to attach the

Mounting Brackets (2) to the ATS PDU.

If you plan on attaching the Cord Retention Tray to the ATS PDU, use the provided Mounting Bracket Screws (8) to attach the Mounting

Brackets (2) to the ATS PDU.

13

Installation Guide

Rear Mounting

Step 2. Cord Retention Tray Installation (optional)

Adjust the length of the Cord Retention Trays till the screw hole on the Trays and ATS PDU are aligned. Attach the Cord Retention Trays to the ATS PDU with the 8 supplied Cord Retention Tray Mounting

Screws. Tighten the Cord Retention Trays with the screw on it.

Step 3. ATS PDU Mounting

Use the provided Washers (4) and Screws (4) to secure the ATS PDU to your existing rack system.

Note: You may also use the screw sets provided by the rack to secure the ATS PDU.

Step 4. Cable Ties (Optional)

Use the provided Cable Ties to fasten each cord to the Cord

Retention Tray.

14

Installation Guide

Replacing the LCD Panel

Step 1. Use a slotted screwdriver to gently lift out the LCD panel.

Step 2. Disconnect the cable connector.

Electrical Installation

Step 1. Receptacle evaluation

Ensure that the plug type of your ATS PDU unit matches the receptacles that you are using.

The ATS PDU must be plugged into a three-wire, grounded utility receptacle or a UPS that is connected to a grounded utility receptacle. The utility receptacle must also be connected to an appropriate branch circuit/main with fuse or circuit breaker protection. Connection to any other type of receptacle may result in an electrocution hazard.

Step 2. Plug the ATS PDU into the utility receptacle and/or UPS.

For configuration details, refer to ATS PDU Configuration on page 8.

Step 3. Attach equipment

It is extremely important not to exceed the ATS PDU's maximum current load (as outlined in the Specifications section). In order to determine total load, use the LCD screen on the front of the ATS

PDU to monitor the load being attached.

15

Installation Guide

Power Cord Locking - For IEC Type ATS PDU

Input Power Cord

Step 1. Align and insert the Cable Tie from the upper side of the Fixed Stand and fasten it as shown below.

Step 2. Align and insert the Cable Tie from the bottom side of the Fixed

Stand and fasten it as shown below.

Output Power Cord

Step 1. Align and insert the Cable Tie from the upper side of the Fixed Stand and fasten it as shown below.

16

Installation Guide

Network Installation

(Performed when a Remote Management Card is installed)

Step 1. Attach the LAN Cable

Using a CAT5 RJ45 cable, attach one end to the Ethernet port on the

RMCARD, and the other end to a network port.

Step 2. Establish the ATS PDU IP address

Assigning an IP address to the CyberPower ATS PDU requires the user to have an available IP address that is valid on the respective network. If an available IP address is unknown, contact the network administrator to obtain one. The default IP is 192.168.20.177 and the default for the DHCP function is on.

There are multiple methods for setting up the IP address of the ATS PDU

Please follow the instructions below for the method that is appropriate for your application.

Please make sure the ATS PDU is powered on during this process.

Option 1 (recommended): Power Device Network Utility

1. Download the Power Device Network Utility software available at www.cyberpower.com.

2. Highlight the ATS PDU device from the list and select Edit and Setup device =>

Assisted Setup from the menu.

3. Configure the IP Address, Subnet Mask, and Gateway Address to match your network settings.

4. Enter the user name and password of the ATS PDU device at the Authentication menu.

Note: The default username is “ cyber ” and the default password is “ cyber ”. For further information and installation instructions, see Appendix B.

Option 2: DHCP Server

1. Ask your administrator if there is DHCP server on the LAN.

2. Make sure the DHCP is Enabled.

3. Make sure the network connection is ready and power on the ATS PDU.

4. The ATS PDU will obtain an IP address from the DHCP server automatically.

Option 3: Address Resolution Protocol (ARP) Command

1. Obtain the MAC address from the sticker on the ATS PDU.

2. Open a command prompt as an administrator and type the following:

“arp -s [available IP address] [MAC address of ATS PDU]”.

Example: arp -s 192.168.20.240 00-0C-15-00-00-01

IP Address MAC Address

3. Use the Ping command to assign a size of 123 bytes to the IP.

* Type in “ ping 192.168.20.240 -l 123 ” then press Enter .

* If the replies are received, your computer can communicate with the IP address.

Option 4: Hyper Terminal or Terminal Emulator

1. Use the included RJ45/DB9 serial port connection cable, attach one end to the serial port on the front of the ATS PDU, and the other end to the PC/server.

2. Open the Hyper Terminal software on your PC and select a name and icon for the connection.

3. Setup the COM port settings using the values indicated in Appendix A.

4. Press Enter to enter the Authentication menu.

5. Enter the user name and password of the ATS PDU device at the Authentication menu.

6. Press 4 and Enter to access Network Settings to view the IP address.

Note: The default username is “ cyber ” and the default password is “ cyber ”.

For further information and configuration via Hyper Terminal, see

Appendix A-Hyper Terminal.

17

Operation

Remote Management

The remote management function via the RMCARD205 provides for monitoring of the ATS PDU operational information, controlling outlets and utilizing SNMP functionality.

Web

Remote management can be performed via web interface. To access the web interface, please follow the instructions below:

1. Enter the IP address of the ATS PDU into a web browser.

2. Enter the user name and password of the ATS PDU device at the authentication screen.

Note: The default username is “ cyber ” and the default password is “ cyber ”.

Telnet and SSH

The CyberPower ATS PDU provides Telnet and Secure Shell (SSH) as Remote

Management methods. Telnet uses user name and password as basic security while SSH has a higher security level with encryption of the transmitted packets including user name, password, and data. Configure the Setting of

Telnet and SSH on the Web Interface. The default user name and password is cyber / cyber .

Note: When user logs in with the admin username and admin password through Telnet or SSH, there are two types of interfaces available. One is the command line interface (CLI) and the other is a menu interface.

The default is CLI. If the user wants to change to the menu interface, type in the [ menumode ] command. To switch back to CLI, it is necessary to logout and login to the RMCARD.

SNMP

The CyberPower ATS PDU supports SNMPv1 and SNMPv3 protocols.

Download the CyberPower MIB file and add it to a SNMP-supported management software. Default read/write community is public/private for

SNMPv1. SNMPv3 provides a higher security level than SNMPv1 by encrypting the transmitted packet. Configure the settings of the SNMPv1/SNMPv3 on

Web Interface. For more details, please see the RMCARD205 User Manual.

Local Management

LCD Operation

The LCD screen provides instant information, such as source condition, voltage and current, for the ATS PDU. In addition, users can use the interface to configure each PDU parameters and control each outlet on the switched ATS PDU.

A. Scroll Mode: The ATS PDU information will display in following order automatically when “Scroll Mode On” is configured.

Source A information

Source B information

Device Load

Bank 1 Current (2U series)

Bank 2 Current (2U series)

Bank 3 Current (2U series)

Environment Status (Displays when the ENVIROSENSOR is connected)

B. Main Menu Map

About

Hardware Version

Firmware Version

Network Information

Serial Number

Settings

Preferred Source

Source

Configuration

A/B/None

Nominal Voltage

Voltage Range

Freq. Deviation

Sensitivity

Load

Configuration

Outlet Control

Device

Bank/1/2/3

Device

Bank/1/2/3

Overload

Threshold

Near Overload

Threshold

Low Load

Threshold

All/Outlet 1-N

Immediate On

Delay On

Immediate Off

Delay Off

Reboot

Delay Reboot

LCD Settings

Brightness

Scroll Mode

Screen Off

18

Operation

Local Management

Reset/Reboot

Reset All (ATS PDU, RMCARD and LCD)

Reset Except TCP/IP

Reset Account (User Name and Password)

Reboot

LED Indicators

Indicator

Source

Load

Tx/Rx

LINK

Outlet

Status Description

Solid Green Selected source and power condition is normal.

Flashing Green Backup source and power condition is normal.

Orange Power condition is abnormal.

Green

Orange

Red

The aggregate current of each bank is normal.

Near overload.

Overload.

Off The ATS PDU power is off.

On (Green) The ATS PDU power is on.

Flashing

On

Off

On

Off

Receiving/transmitting data packet.

Reset finished.

Indicates the ATS PDU is connected to the LAN.

Indicates the ATS PDU is not connected to the LAN.

The outlet is on and providing power.

The outlet is off.

Environmental Monitoring (optional)

The CyberPower ATS PDU with an environmental sensor (ENVIROSENSOR) installed, provides remote temperature and humidity monitoring in a server closet and/or datacenter. To connect ATS PDU with ENVIROSENSOR, use

RJ45 Ethernet Cable included with the ENVIROSENSOR. Plug one end into the Universal port on the RMCARD205 and the other end into the RJ45 port on the ENVIROSENSOR (as shown in figures below). When the ATS PDU connected correctly to the ENVIROSENSOR, users can see the temperature and humidity data via the Web Interface.

Device Reset

● To reset all the settings to default locally, use Reset function in the LCD screen.

● To reset all the settings to default remotely, log in Web interface, enter the

Reset page and apply the function.

Unattended/Automatic Shutdown

PowerPanel Business Edition software automatically initiates a graceful shutdown on the connected computer's operating system in an orderly fashion.

PowerPanel must be installed on every computer or server for which the shutdown is to take place. The computer will receive a device status message from the RMCARD205 and will perform the shutdown according to the instructions provided, including shutdowns at exact times and dates.

Follow the directions below for setting up Unattended/Automatic Shutdown.

Step 1. Computer Configuration

1. Install PowerPanel Business Edition Client on every computer/server that will be part of the shutdown process (Follow the instructions in the

PowerPanel Business Edition Client User Manual).

2. Configure the settings in PowerPanel Business Edition Client. See the

PowerPanel Business Edition Client User Manual for detailed instructions.

Step 2. ATS PDU Network Configuration

Verify that the IP address of all computers, that will be part of the shutdown process, are included in the Client List of the web interface (Follow the instructions in the PowerPanel Business Edition User Manual).

Step 3. Notification

Notifying the computers of potential outlet shutdowns can be accomplished using the following functions:

● Outlets Control Menu: Performing the task of turning off or rebooting outlets

● Scheduling Menu: Setting the application to perform the task of turning off or rebooting outlets. The notification will occur prior to the scheduled date/time.

● Outlet Overload: In the event of ATS PDU overload, notification will be sent prior to the ATS PDU shutting down.

19

Firmware Upgrade

By upgrading the Firmware, you can obtain new features, updates and improvements to existing functionality. To ensure the firmware is kept up to date, please regularly visit our website to see if there is any updated firmware version available.

Note: Please do not turn the ATS PDU off when processing the firmware upgrade. ATS PDU outlets will remain powered on while the firmware update takes place. Only the ATS PDU LCD screen will reboot.

ATS PDU

Update the following file to upgrade the firmware.

- cpsatsmafw_xxx.bin

Note that the XXX is not part of the file name but is where the version number in the filename is given.

Use the following steps to upgrade the firmware.

1. Download the latest firmware from www.cyberpower.com.

2. Extract the file to “C:\”.

3. Open Hyper Terminal to connect the ATS PDU and use the command “ @NEW ”.

Note: In order for Hyper Terminal to interact with the ATS PDU, the PC/ server must be connected directly to the ATS PDU via the serial port.

(1). Use the included RJ45/DB9 serial port connection cable. Attach one end to the serial port on the front of the ATS PDU, and the other end to the PC/server.

(2). Open the Hyper Terminal software on your PC and select a name and icon for the connection.

(3). Setup the COM port settings using the following values.

* Bits per second: 38400

* Data bits: 8

* Parity: None

* Stop bits: 1

* Flow control: None

4. The ATS PDU will reboot and show main menu on Hyper Terminal.

5.

Press “1” to select ATS PDU upgrade.

20

Firmware Upgrade

6.

Select Transfer > Send File.

7.

Note that the Ymodem protocol and file “C:\cpsatsmafw_xxx.bin” are selected in Hyper Terminal.

8.

The download progress window will open after you click the Send button.

9.

After uploading the binary file Hyper Terminal will show as below.

LCD

Update the following file to upgrade the firmware.

- cpsatslafw_xxx.bin

Note that the XXX is not part of the file name but is where the version number in the filename is given.

Use the following steps to upgrade the firmware.

1. Download the latest firmware from www.cyberpower.com.

2. Extract the file to “C:\”.

3. Open Hyper Terminal to connect the ATS PDU and use the command “ @NEW ”.

Note: In order for Hyper Terminal to interact with the ATS PDU, the PC/ server must be connected directly to the ATS PDU via the serial port.

(1). Use the included RJ45/DB9 serial port connection cable. Attach one end to the serial port on the front of the ATS PDU, and the other end to the PC/server.

(2). Open the Hyper Terminal software on your PC and select a name and icon for the connection.

(3). Setup the COM port settings using the following values.

* Bits per second: 38400

* Data bits: 8

* Parity: None

* Stop bits: 1

* Flow control: None

21

Firmware Upgrade

4.

The ATS PDU will reboot and show main menu on Hyper Terminal.

5.

Press “2” to select LCD upgrade.

6.

Press “1”.

7.

Select Transfer > Send File.

8.

Note that the Ymodem protocol and file “C:\cpsatslafw_xxx.bin” are selected in Hyper Terminal.

22

Firmware Upgrade

9 The download progress window will open after you click the Send button.

10.

After uploading the binary file, Hyper Terminal will be shown as below.

You can see if the firmware upgrade is successful by checking the

“CyberPower System Firmware Version” after login.

Note : 1.

Please do not turn the ATS PDU off and ensure the quality of selected source power when processing firmware upgrade. The

ATS PDU will not perform the ATS function when upgrading firmware.

2. Press “3” to exit the main menu of firmware upgrade.

RMCARD

There are two files to update in order to upgrade the firmware:

- cpsrm2scfw_XXX.bin

- cpsrm2scdata_XXX.bin

Note that the XXX is not part of the file name but is where the version number in the filename is given.

Option 1: Using FTP Command

Use the following steps to upgrade the firmware.

1.

Download the latest firmware.

2.

Extract the downloaded files to “C:\”.

3.

Open a command prompt window.

4.

Login to the CyberPower Remote Management Card with FTP command, in the command prompt type:

23

Firmware Upgrade

(1) ftp

(2) ftp > open

(3) To [current IP address of RMCARD] [port] ; e.g., To 192.168.22.126 21

(4) Input USER NAME and PASSWORD (same as the administrator account in web user interface)

5.

Upload the cpsrm2scfw_XXX.bin, type: ftp > bin ftp > put cpsrm2scfw _XXX.bin

6 . Upgrade is now complete, type: ftp > quit

7.

The system will reboot after you type “ quit ”.

8.

Login to the FTP again as step 4.

9.

Upload cpsrm2scdata _XXX.bin, type: ftp > bin ftp > put cpsrm2scdata _XXX.bin

10.

Upgrade complete, type ftp > quit

11. The system will reboot after you type “ quit ”.

Option 2: Using Upgrade and Configuration Utility Tool

(Bulk Firmware Upgrade Tool)

Use the following steps to upgrade the firmware.

1. Install the CyberPower Upgrade and Configuration Utility tool available for download at www.cyberpower.com.

2. After installation completes, run the “Upgrade and Configuration Utility”.

3. The main window of the Upgrade and Configuration Utility tool program is shown in below figure. The configuration tool will display all CyberPower

Remote Management devices present on the local network subnet. The

"Discover" button is used to search the local network subnet again.

Note: You can click “View” to select the items you want to view.

The main window of the “Upgrade and Configuration Utility” program

4. Check the boxes to select the devices you wish to upgrade, and select

“Update” on the right to update the device user account and password.

Once the update is confirmed, the status icon next to the IP Address will change from orange to green.

Note: You must update the device user account and password credentials before firmware upgrade.

5. Select the devices you wish to upgrade by checking their respective checkbox and select “Upgrade Firmware”.

Note: You can upgrade the firmware of multiple devices that use the same firmware files (Bulk firmware upgrade).

6. Select the Firmware and Data files and click “OK”, as shown in below figure.

The File Locations of Firmware & Data window

7. Click “Yes” to start firmware upgrade on selected devices, as shown in below figure.

24

Firmware Upgrade

Confirm Upgrade Firmware message window

8. If the firmware upgrade is implemented, you will see the Result in the main window, as shown in below figure.

Firmware upgrade success in the main window

Troubleshooting

Problem

ATS PDU outlets do not provide power to connected equipment

Possible Cause

1. Breaker tripped

2. Power cord is not properly plugged in

Amperage displayed on LCD screen exceeds the units capability

Circuit breakers have tripped

Overload

1. Sustained overload

2. Excessive ambient or internal temperatures

3. Faulty breaker

Solution

Reset Breaker, check the plug to insure its connected correctly. If the problem remains, contact technical support.

The load indicator shows red when overload. Reduce the load on the ATS PDU until the overload is gone. If the problem remains, contact technical support.

Reset Breaker.

If the problem remains, contact technical support.

25

Conformance Approvals

FCC Warning

WARNING!! This equipment has been tested and found to comply with the limits for a Class A Digital Device, pursuant to Part 15 of the FCC Rules.

These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense.

Any special accessories needed for compliance must be specified in the instruction.

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Notice: (1) An unshielded-type power cord is required in order to meet FCC emission limits and also to prevent interference to the nearby radio and television reception. It is essential that only the supplied power cord is used.

(2) Use only shielded cables to connect I/O devices to this equipment.

Note: THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY RADIO OR TV

INTERFERENCE CAUSED BY UNAUTHORIZED MODIFICATIONS TO THIS

EQUIPMENT. SUCH MODIFICATIONS COULD VOID THE USER’S AUTHORITY

TO OPERATE THE EQUIPMENT.

The Class A digital apparatus meets all requirements of the Canadian

Interference-Causing Equipment Regulation.

Cet appareil numerique de la class A respecte toutes les exigencies du

Reglement sur le materiel brouilleur du Canada.

European Union

This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

Customer Service & Warranty

Product Registration

Thank you for purchasing a CyberPower product. Prompt product registration entitles coverage under the Limited Warranty and also allows the opportunity to be notified of product enhancements, upgrades, and other announcements.

Registration is quick and easy at www.cyberpower.com/registration.

CyberPower International

Feel free to contact our Tech Support department with installation, troubleshooting, or general product questions.

Cyber Power Systems, Inc.

www.cyberpower.com

For USA and Canada:

4241 12th Ave East, Suite 400

Shakopee, MN 55379

Toll-free: (877) 297-6937

For all other regions:

Please visit our website for local contact information.

26

Customer Service & Warranty

Limited Warranty

Read the following terms and conditions carefully before using the

CyberPower ATS PDU series. By using the Product, you consent to be bound by and become a party to the terms and conditions of this Limited Warranty.

If you do not agree to the terms and conditions of this Warranty, you should return the Product for a full refund prior to using it.

Who Is Providing This Warranty?

Cyber Power Systems, Inc. provides this Limited Warranty.

What Does This Warranty Cover?

This warranty covers defects in materials and workmanship in the Product under normal use and conditions.

What Is The Period of Coverage?

For USA and Canada, CyberPower provides a 3-Year limited warranty to the original purchaser who owns the Product. For other regions, please contact your local CyberPower sales team for more information.

Who Is Covered?

This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.

How Do You Get Service?

1. You can use the contact information mentioned above for instructions.

2. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment.

3. You must provide a purchase receipt (or other proof of the original purchase) and provide a description of the defect.

What Will We Do To Correct Problems?

CyberPower will inspect and examine the Product.

If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you paid for the

Product (purchase receipt showing price paid is required).

Who Pays for Shipping?

We pay when we send items to you; you pay when you send items to us.

What Are Some Things This Warranty Does Not Cover?

1. This Warranty does not cover any software that is damaged or needs to be replaced due to the failure of the Product or any data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.

2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums, medical or life support devices, etc.

What Are The Limitations?

1. This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use of any adapters or other connectors.

2. The Product must have been plugged directly into the power source and the equipment connected to the Product must be directly connected to the Product and not "daisy-chained" together in serial fashion with any extension cords, another Product or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.

3. The Product and equipment connected to it must have been used properly in a suitable and proper environment and in conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.

4. The Product must have been used at all times within the limitations on the

Product's VA capacity.

5. The sole and exclusive remedies of the Initial Customer are those provided by this Warranty

27

Appendix A-Hyper Terminal

Hyper Terminal software can be used for basic ATS PDU configuration. In order for Hyper Terminal to interact with the ATS PDU, the PC/server must be connected directly to the ATS PDU via the serial port with the included

RJ45/DB9 serial port connection cable. It utilizes a text-based interface and menu system. Navigation through the interface is done by typing the number of the menu option and pressing the Enter key. Setup the COM port settings using the following values.

* Bits per second: 38400

* Data bits: 8

* Parity: None

* Stop bits: 1

* Flow control: None

Note: The session will timeout and logout after 3 minutes of inactivity. Menu options are shown below:

[Main Menu]

1. Utility Configuration

2. Outlet Manager (Switched Series Only)

3. Load Configuration

4. Network Settings

5. System Configuration

6. Account Settings

7. Configure System to Default

8. Logout

[Utility Configuration]

1. Preferred Source: A

2. Sensitivity: High

3. Voltage Range: Medium

4. Frequency Deviation: 1 Hz

5. Nominal Voltage: 230 V

6. Wide Voltage Range: 30 V

7. Medium Voltage Range: 23 V

8. Narrow Voltage Range: 16 V

9. Set Load Restriction (Switched Series Only)

[Outlet Manager]

1. Outlet Control

2. Outlet Configuration

[Load Configuration]

1. Device Threshold Configuration

2. Bank 1 Threshold Configuration

3. Bank 2 Threshold Configuration

4. Bank 3 Threshold Configuration

[Network Setting]

Physical MAC Address: 00-0C-15-00-00-01

1. System IP: 192.168.20.240

2. Subnet Mask: 255.255.255.0

3. Default Gateway: 192.168.20.254

4. DHCP: Enabled

5. Http Port: 80

6. Http Access: Enabled

[System Configuration]

1. Name: PDU15SW10ATNET

2. Location: Server Room

3. Contact: Administrator

[Account Setting]

1. Administrator

[Configure System to Default]

Sure to Configure System to Default

1. Reset ATS PDU

2. Reset ATS PDU (TCP/IP Settings Reserved)

28

Appendix B-Power Device Network Utility

Overview

The CyberPower Power Device Network Utility is an easy-to-use interface which is used for establishing IP addresses on CyberPower ATS PDUs.

Installation

Step 1. Download the Power Device Network Utility software available at www.cyberpower.com.

Step 2. Select Next in the software wizard (Shown in Figure 1).

Figure 1

Step 3. Choose an installation directory. Select Next (Shown in Figure 2).

Figure 2

Step 4. Select Install to confirm the settings and install (Shown in Figure 3).

Figure 3

29

Appendix B-Power Device Network Utility

Step 5. Select Finish to finalize the installation (Shown in Figure 4).

Figure 4

Launch Program

To launch the Power Device Network Utility and get started, select Programs from the Start menu in Windows and locate the new folder and icons for

Power Device Network Utility. Select Power Device Network Utility from the program folder (Shown in Figure 5).

Figure 5. Power Device Network Utility

Getting Started

The Power Device Network Utility scans the network for devices with MAC addresses that match CyberPower network hardware. Once found, the device(s) can then be figured with a specific IP address, subnet mask, and gateway address. This allows the device(s) to function properly on the network and interface with CyberPower Management Console.

Step 1. Select the appropriate ATS PDU from the Equipment List (Shown in

Figure 6).

Figure 6. Equipment List

Note: If the ATS PDU does not appear on the list, click the Refresh button to rescan the network. If it still does not appear, ensure that the ATS PDU is turned on and is installed correctly.

Pressing Stop will cancel the scan/refresh process.

Note: If your computer has a software firewall installed, you may see a

Windows Security Alert message (Shown in Figure 7).

In Windows XP SP2, the default firewall alert message is shown as

Figure 7. You need to allow the Power Device Network Utility access through the firewall.

30

Appendix B-Power Device Network Utility

Figure 7. Windows Security Alert

Step 2. Assign a valid IP Address to the ATS PDU.

With the appropriate device selected from the Equipment List, open the Network Settings menu (shown in Figure 8) [Tools=>Device

Setup]. In the Device Network Setting Menu, enter a valid IP address, subnet mask, and gateway address to setup the ATS PDU device.

Figure 8. Network Setting Menu (Device Setup)

Step 3. Authentication

Enter the user name and password of the ATS PDU at the

Authentication menu (shown in Figure 9).

Note: The default username is “ cyber ” and the default password is “ cyber ”.

Figure 9. Authentication screen

Advanced Settings

Timeout Settings

The Timeout Setting (Shown in Figure 10). [Edit=>Timeout Settings] is used to specify the wait time when scanning for network ATS PDUs. When there are many devices on the local network, it may take extended periods of time to locate all the devices. The timeout function is used to limit the search time.

The default setting is 3 seconds. Valid values are 3 to 60 seconds.

Figure 10. Timeout Setting

31

Cyber Power Systems, Inc.

www.cyberpower.com

K01-0000322-03