Burkert 8695 Control head Operating Instructions
Advertentie
Advertentie
Type 8695 REV.2
Control Head
Operating Instructions
We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous réserve de modifications techniques.
© Bürkert Werke GmbH & Co. KG, 2019 - 2020
Operating Instructions 2007/01_EU-EN_00815306 / Original DE
Type 8695 REV.2
Control head Type 8695 REV.2
T able of
C onTenTs
5.1.2 Model for control of process valves belonging to the 20xx series (CLASSIC) ...........12
3 english
4
Type 8695 REV.2
Inhaltsverzeichnis
Installation of the control head Type 8695 on process valves of series 21xx (ELEMENT) .....17
Installation of the control head Type 8695 on process valves of series 20xx (CLASSIC) ......22
Rotating the actuator module on process valves of series 2100, 2101, 2000 and 2012 ........26
Teach function: Determine end positions and save these, REV.2
...........................................34
english
Type 8695 REV.2
5 english
6 english
Type 8695 REV.2
Type 8695 REV.2
About these instructions
1 About these instructions
The operating instructions describe the entire life cycle of the device.
→ Keep these instructions ready to hand at the operation site.
Important safety information.
▶ Carefully read these instructions.
▶ Observe in particular the safety instructions, intended use and operating conditions.
▶ Persons, who work on the device, must read and understand these instructions.
1.1 symbols
Danger
Warns of an immediate danger.
▶ Failure to observe the warning will result in a fatal or serious injury.
Warning
Warns of a potentially dangerous situation.
▶ Failure to observe the warning may result a fatal or serious injury.
Caution
Warns of a possible danger.
▶ Failure to observe the warning may result in moderate or minor injuries. attention
Warns of damage to property.
▶ Failure to observe the warning may result in damage to device or system.
Indicates important additional information, tips and recommendations.
Refers to information in these operating instructions or in other documentation.
▶ Indicates an instruction for risk prevention.
→ Indicates a procedure which you must carry out.
Indicates a result.
menu Indicates a interface text.
1.2
Definition of terms
In these instructions the term “device” denotes the following device types:
Control head Type 8695.
The term “büS” (Bürkert system bus) used in this instruction stands for the communication bus developed by Bürkert and based on the CANopen protocol.
In these instructions, the abbreviation “Ex” always refers to “potentially explosive area”.
7 english
Type 8695 REV.2
Intended use
2 intended use
The control head Type 8695 REV.2 is designed to be mounted on pneumatic actuators of process valves for the control of media. The permitted fluid media are listed in the technical data.
▶ Use the device for its intended purpose only. Non-intended use of the device may be dangerous to peo ple, nearby equipment and the environment.
-
▶ Correct transportation, correct storage as well as correct installation, commissioning, operation and maintenance are essential for reliable and problem-free operation.
▶ When using the device, observe the permitted data, operating conditions and application conditions.
This information can be found in the contractual documents, the operating instructions and on the type label.
▶ Use the device only in conjunction with third-party devices and components recommended and autho rized by Bürkert.
-
▶ Do not use the device outdoors without protection from the weather.
▶ In areas at risk of explosion, only use devices approved for use in those areas. These devices are labeled with a separate Ex type label. For such use, note the information provided on the separate Ex type label and the additional explosion-related information or separate explosion-related operating instructions.
8 english
Type 8695 REV.2
Basic safety instructions
3 bAsic sAfety instructions
These safety instructions do not consider any contingencies or incidents which occur during installation, operation and maintenance.
The operator is responsible for observing the location-specific safety regulations, also with reference to the personnel.
Danger
Risk of injury from high pressure and discharge of medium.
▶ Before working on the device or system, switch off the pressure. Vent or drain lines.
Danger
Risk of injury from electric shock.
▶ Before working on the device or system, switch off the power supply. Secure against reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
To prevent injury, ensure the following:
▶ Secure device or system to prevent unintentional activation.
▶ Only trained technicians may perform installation and maintenance work.
▶ Perform installation and maintenance with suitable tools only.
▶ Do not make any changes to the device and do not subject it to mechanical stress.
▶ Operate the device only in perfect state and in consideration of the operating instructions.
▶ Observe the general rules of technology.
▶ Install the device according to the regulations applicable in the respective country.
▶ Do not feed corrosive or flammable media into the device connections.
▶ Do not feed any fluids into the connections of the device.
▶ After the process is interrupted, restart in a controlled manner. Observe sequence:
1. Connect electrical or pneumatic power supply.
2. Charge the device with medium.
▶ Observe intended use.
▶ When unscrewing and screwing in the body casing or the transparent cap, do not hold the actuator of the process valve but the basic housing of the device.
english
9
Type 8695 REV.2
General information
4 GenerAl informAtion
4.1 germany
Contact address
Bürkert Fluid Control System
Sales Center
Chr.-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: [email protected]
international
Contact addresses can be found on the final pages of the printed operating instructions.
And also on the Internet at: www.burkert.com
4.2
Warranty
The warranty is only valid if the control head Type 8695 is used as intended in accordance with the specified application conditions.
4.3
Trademarks
Brands and trademarks listed below are trademarks of the corresponding companies / associations / organizations
Loctite Henkel Loctite Deutschland GmbH
4.4
Information on the internet
The operating instructions and data sheets for Type 8695 can be found on the Internet at: www.burkert.com
10 english
Type 8695 REV.2
System description
5 system description
5.1
Structure and function
The control head Type 8695 can control single or double-acting process valves.
The control head Type 8695 has been optimized for the integrated modular fitting of series 21xx process valves
(ELEMENT) with actuator size ∅ 50. Various expansion stages are possible thanks to the modular design.
.
The valve position is recorded via a contactless, analog sensor element which automatically detects and saves the valve end positions by means of the teach function during start-up.
Option: Communication possible via IO-Link and büS.
5.1.1
Control head for integrated installation on 21xx series
(element)
View without transparent cap:
Pressure limiting valve
(for protection against too high internal pressure in case of error)
Electrical connection
Circular plug-in connector
M12 x 1
Basic housing
Figure 1: Structure and function
Pilot air port
(label: 1)
Fastening screws (2 x)
Air exhaust port
(label: 3)
11 english
Type 8695 REV.2
System description
5.1.2
Model for control of process valves belonging to the 20xx series (CLASSIC)
A special model enables the control head Type 8695 to be attached to process valves belonging to the
20xx series.
This model has a different pneumatic connection module so that the pilot air ports can be connected to the
outside of the actuator (see “Figure 2”
).
Figure 2: Model for control of process valves, 20xx series
Pilot air outlet 2
1
Pilot air outlet 2
2
12 english
Type 8695 REV.2
Technical data
6 technicAl dAtA
6.1
Conformity
In accordance with the EU Declaration of conformity, the control head Type 8695 is compliant with the
EU Directives.
6.2
Standards
The applied standards on the basis of which compliance with the EU Directives is confirmed are listed in the
EU-Type-Examination Certificate and/or the EU Declaration of Conformity.
6.3
Licenses
The product is approved for use in zone 2 and 22 in accordance with ATEX directive 2014/34/EU category
3GD.
Observe instructions on operation in an explosion-risk (Ex) area.
Observe the ATEX additional instructions.
6.4
Operating conditions
Warning!
Solar radiation and temperature fluctuations may cause malfunctions or leaks.
▶ If the device is used outdoors, do not expose it unprotected to the weather conditions.
▶ Ensure that the permitted ambient temperature does not exceed the maximum value or drop below the minimum value.
Ambient temperature see type label
Degree of protection
Evaluated by the manufacturer: Evaluated by UL:
IP65 / IP67 according to EN 60529 1) UL Type 4x Rating 1)
Operating altitude up to 2000 m above sea level
1)
Only if cables, plugs and sockets have been connected correctly and in compliance with the exhaust air concept see
chapter “8 Pneumatic installation”.
13 english
Type 8695 REV.2
Technical data
14
6.5
Mechanical data
Dimensions See data sheet
Body material exterior PPS, PC, VA interior PA6; ABS
Sealing material exterior EPDM / FKM
Stroke range of valve spindle
21xx series (ELEMENT) and 20xx series (CLASSIC)
Third-party devices
(modified guide element required)
2 – 35 mm
2 – 44 mm
6.6
Type labels
6.6.1
Type label standard
Supply voltage or fieldbaus control
Type
8695 24 V/DC single act Pilot 0,6
Pmax 7 bar
Tamb 0°C - +55°C REV.2
S/N 001000
00185114 W14UN
Order number
Figure 3: Type label (example)
Control function, pilot valve
Max. operating pressure
Ambient temperature, version
Serial number, CE marking
Barcode
6.6.2
UL type label
Type, Features of the type code applicable to UL and ATEX
Control function, pilot valve, supply voltage pilot valve
8695 -E1-...-0 PU02
Single act Pilot 0.6 24V
Pmax 7 bar
Tamb -10 - +55 °C REV.2
S/N 1001
00123456
W15MA
Max. operating pressure
Ambient temperature, version
Serial number, CE marking
Barcode
Order number, manufacture code
Figure 4: UL type label (example) english
Type 8695 REV.2
Technical data
6.6.3
UL additional label
Figure 5:
Degree of protection
Circuit with limited power
Communication, supply voltage
Power consumption
UL additional label (example)
Type 4X enclosure
NEC Class 2 only
E238179
Power Supply: büS
24V ±25% max. 3,5 W
6.7
Pneumatic data
Control medium neutral gases, air
Quality classes in accordance with ISO 8573-1
Dust content Class 7 max. particle size 40 µm, max. particle density 10 mg/m³
Water content Class 3 max. pressure dew point
- 20 °C or min. 10 °C below the lowest operating temperature
Oil content Class X max. 25 mg/m³
Temperature range -10 – +50 °C
Pressure range 3 – 7 bar
Air output of pilot valve 7 l
N
(Q
Nn
/ min (for aeration and deaeration)
- value according to definition for pressure drop from 7 to 6 bar absolute)
Connections 21xx (ELEMENT) Plug-in hose connector ∅ 6 mm (1/4“)
Socket connection G 1/8
20xx (CLASSIC) Socket connection G 1/8 with M5 connection for connecting to the actuator english
15
Type 8695 REV.2
Technical data
6.8
Electrical data
Warning!
Only circuits with limited power may be used for UL approved components according to “NEC Class 2”.
6.8.1
Electrical data without field bus communication
Protection class III as per DIN EN 61140 (VDE 0140-1)
Connections Circular plug-in connector (M12 x 1, 8-pole)
Operating voltage 24 V DC ± 25 %, max. residual ripple 10 %
Current consumption max. 150 mA
Power consumption max. 3.5 W
Output max. 100 mA per output
Display max. 20 mA per illustrated illuminated display (LED)
Communications interface Connection to PC via USB bus interface set
Communication software Bürkert Communicator
6.8.2
Electrical data, IO-Link
Protection class III as per DIN EN 61140 (VDE 0140-1)
Connection Circular plug-in connector M12 x 1, 5-pin, A-coded
Operating voltage
System supply (Pin 1+3) 24 V DC ±25 % (according to specification)
Actuator supply (Pin 2+5) 2) 24 V DC ±25 % (according to specification)
Current consumption
System supply (Pin 1+3) max. 50 mA
Actuator supply (Pin 2+5) max. 100 mA, only with installed pilot valves
Total power consumption max. 3.5 W
2)
Actuator supply is galvanically isolated from system supply in accordance with IEC 60664 and for electrical safety in accordance with SELV from IEC 61010-2-201
16
6.8.3
Electrical data, büS
Protection class III as per DIN EN 61140 (VDE 0140-1)
Connection Circular plug-in connector M12 x 1, 5-pin, A coded
Operating voltage 24 V DC ±25 %
Current consumption max. 150 mA
Total power consumption max. 3.5 W english
Type 8695 REV.2
Installation
7 instAllAtion
7.1
Safety instructions
Danger!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
Warning!
Risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following assembly, ensure a controlled restart.
7.2
Installation of the control head Type 8695 on process valves of series 21xx (ELEMENT)
attention!
When mounting on process valves with a welded connection, follow the installation instructions in the operating instructions for the process valve.
Procedure:
1. install switch spindle
Transparent cap
Pilot air ports
(plug-in hose connectors with collets or threaded bushings)
Actuator
Figure 6: Installation of switch spindle (1), series 21xx
→ Unscrew the transparent cap on the actuator and unscrew the position display (yellow cap) on the spindle extension (if present).
17 english
Type 8695 REV.2
Installation
→ For version with plug-in hose connector, remove the collets (white nozzles) from both pilot air ports (if present).
Puck
Switch spindle
Guide element
Groove ring max. 1 Nm max. 5 Nm
Actuator cover
O-ring
Spindle extension
18
Figure 7: Installation of the switch spindle (2), series 21xx attention!
Improper installation may damage the groove ring in the guide element.
The groove ring is already be pre-assembled in the guide element and must be “locked into position” in the undercut.
▶ When installing the switch spindle, do not damage the groove ring.
→ Push the switch spindle through the guide element.
attention!
Screw locking paint may contaminate the groove ring.
▶ Do not apply any screw locking paint to the switch spindle.
→ To secure the switch spindle, apply some screw locking paint (Loctite 290) in the tapped bore of the spindle extension in the actuator.
→ Check that the O-ring is correctly positioned.
→ Screw the guide element to the actuator cover (maximum torque: 5 Nm).
→ Screw switch spindle onto the spindle extension. To do this, there is a slot on the upper side
(maximum torque: 1 Nm).
→ Push puck onto the switch spindle and lock into position.
english
Type 8695 REV.2
Installation
2. install sealing rings
→ Pull the form seal onto the actuator cover (smaller diameter points upwards).
→ Check that the O-rings are correctly positioned in the pilot air ports.
When the control head is being installed, the collets of the pilot air ports must not be fitted to the actuator.
Pilot air ports
Caution:
Collets must not be fitted !
Form seal
Installation of the form seal
Figure 8: Installation of the sealing rings english
19
Type 8695 REV.2
Installation
3. install control head attention!
Damaged printed circuit board or malfunction.
▶ Ensure that the puck is situated flat on the guide rail.
→ Align the puck and the control head until
1. the puck can be inserted into the guide rail of the control head and
2. the connection pieces of the control head can be inserted into the pilot air ports of the actuator.
Connection pieces
Guide rail
Puck
Guide rail
Puck
20
Figure 9: Aligning the puck and the connection pieces english
Connection pieces
Pilot air ports
(actuator)
Type 8695 REV.2
Installation
→ Push the control head, without turning it, onto the actuator until no gap is visible on the form seal.
attention!
Too high torque when screwing in the fastening screw does not ensure degree of protection IP65 / ip67.
▶ The fastening screws may be tightened to a maximum torque of 1.5 Nm only.
→ Attach the control head to the actuator using the two side fastening screws. In doing so, tighten the screws only hand-tight (maximum torque: 1.5 Nm).
Connection pieces
Pilot air ports
(actuator)
Figure 10: Installation of control head
Fastening screws max. 1.5 Nm english
21
Type 8695 REV.2
Installation
7.3
Installation of the control head Type 8695 on process valves of series 20xx (CLASSIC)
Procedure:
1. install switch spindle
Transparent cap
Position indicator
Actuator
Figure 11: Installation of the switch spindle (1), series 20xx
→ Unscrew the transparent cap on the actuator.
→ Using a hexagon socket key, unscrew the orange/yellow position indicator from the inside of the actuator.
Puck
Switch spindle
Guide element
O-ring
Plastic part
(of the switch spindle)
Spindle (actuator)
Figure 12: Installation of the switch spindle (2), series 20xx
→ Press the O-ring downwards into the cover of the actuator.
→ Manually screw the switch spindle (and the plugged-on guide element) together with the plastic part onto the spindle of the actuator, but do not tighten spindle yet.
→ Tighten the guide element with a face wrench 3) into the actuator cover (maximum torque: 8.0 Nm).
→ Tighten the switch spindle on the spindle of the actuator. To do this, there is a slot on the upper side
(maximum torque: 1.0 Nm).
→ Push the puck onto the switch spindle until it engages.
22 3) journal Ø: 3 mm; journal gap: 23.5 mm english
Type 8695 REV.2
Installation
2. install control head
Guide rail
Puck
Guide rail
Puck
Figure 13: Aligning the puck, series 20xx attention!
Damaged printed circuit board or malfunction.
▶ Ensure that the puck is situated flat on the guide rail.
→ Push the control head onto the actuator. The puck must be aligned in such a way that it is inserted into the guide rail of the control head.
→ Press the control head all the way down as far as the actuator and turn it into the required position.
Ensure that the pneumatic connections of the control head and those of the valve actuator are
If they are positioned differently, longer hoses may be required other than those supplied in the accessory kit.
23 english
Type 8695 REV.2
Installation
Fastening screws maximum 1.5 Nm
Figure 14: Installing the control head, series 20xx attention!
Too high torque when screwing in the fastening screw does not ensure degree of protection IP65 / ip67.
▶ The fastening screws may be tightened to a maximum torque of 1.5 Nm only.
→ Attach the control head to the actuator using the two side fastening screws. In doing so, tighten the fastening screws hand-tight only (maximum torque: 1.5 Nm).
24 english
Type 8695 REV.2
Installation
3. install pneumatic connection between control head and actuator
Pilot air outlet 2
1
Pilot air outlet 2
2
Upper pilot air port
Lower pilot air port
Figure 15: Installing the pneumatic connection between control head and actuator, series 20xx
→ Screw the plug-in hose connectors onto the control head and the actuator.
→ Using the hoses supplied in the accessory kit, make the pneumatic connection between the control head and actuator with the following
“Table 1: Pneumatic connection to actuator CFA and CFB” or
Pneumatic connection to actuator CFI”
.
attention!
Damage or malfunction due to ingress of dirt and moisture.
▶ To comply with degree of protection IP65 / IP67, connect the pilot air outlet is not required to the free pilot air port of the actuator or seal with a plug.
(only for CFA or CFB) which
“In rest position” means that the pilot valves of the control head Type 8695 are isolated or not actuated.
Control function a (CFa)
Process valve closed in rest position (by spring force)
Control head Pilot air outlet
2
2
2
1
Actuator
Upper pilot air port
Lower pilot air port
Control function B (CFB)
Process valve open in rest position (by spring force)
Control head Pilot air outlet
2
2
2
1
Actuator
Table 1:
Upper pilot air port
Lower pilot air port
Pneumatic connection to actuator CFA and CFB or or
2
2
2
1
2
2
2
1
25 english
26
Type 8695 REV.2
Installation
Control function i (CFi)
Process valve closed in rest position
Control head Pilot air outlet
2
2
2
1
Actuator
Upper pilot air port
Lower pilot air port
Process valve open in rest position
Control head Pilot air outlet
2
2
2
1
Actuator
Table 2:
Upper pilot air port
Lower pilot air port
Pneumatic connection to actuator CFI
If the ambient air is humid, a hose can be connected between pilot air outlet 2
2
of the control head and the unconnected pilot air port of the actuator for control function A or control function
B. As a result, the spring chamber of the actuator is supplied with dry air from the vent duct of the control head.
7.4
Rotating the actuator module on process valves of series 2100, 2101, 2000 and 2012
The actuator module (control head and actuator) can be rotated for globe valves and angle-seat valves belonging to series 2100, 2101, 2000 and 2012 only.
The process valve must be in the open position for alignment of the actuator module.
The position of the ports can be aligned steplessly by rotating the actuator module (control head and actuator) through 360°.
Series 2100 and 2101:
Only the entire actuator module can be rotated. The control head cannot be rotated contrary to the actuator.
english
Type 8695 REV.2
Installation
Danger!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Procedure:
→ Clamp valve body in a holding device (only required if the process valve has not yet been installed).
→ Control function A: Open process valve.
Actuator module
Hexagon
Nipple
Hexagon
Nipple
Series 2100 and 2101 Series 2000 and 2012
Figure 16: Rotating the actuator module
→ Using a suitable open-end wrench, counter the wrench flat on the pipe.
→ Place suitable open-end wrench on the hexagon of the actuator.
Warning!
Risk of injury from discharge of medium and pressure.
If the direction of rotation is wrong, the body interface may become detached.
▶ Rotate the actuator module counter-clockwise only (see
).
→ Rotate counter-clockwise (as seen from below) to bring the actuator module into the required position.
Open-end wrench
Figure 17: Rotating with open-end wrench
27 english
28
Type 8695 REV.2
Installation
7.5
Rotating the control head for process valves belonging to series 20xx
If the connecting cables or hoses cannot be fitted properly following installation of the process valve, the control head can be rotated contrary to the actuator.
Fastening screw (2x)
Pneumatic connection
Control head
Actuator
Figure 18: Rotating the control head, series 20xx
Procedure
→ Loosen the pneumatic connection between the control head and the actuator.
→ Loosen the fastening screws countersunk in the side of the body (hexagon socket wrench size 2.5).
→ Rotate the control head into the required position.
attention!
Too high torque when screwing in the fastening screw does not ensure degree of protection IP65 / ip67.
▶ The fastening screws may be tightened to a maximum torque of 1.5 Nm only.
→ Tighten the fastening screws hand-tight only (maximum torque: 1.5 Nm).
→ Re-attach the pneumatic connections between the control head and the actuator. If required, use longer hoses.
english
Type 8695 REV.2
Pneumatic installation
8 pneumAtic instAllAtion
Danger!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
Warning!
Risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
Procedure:
→ Connect the control medium to the pilot air port (1)
(3 – 7 bar; instrument air, free of oil, water and dust).
→ Attach the exhaust airline or a silencer to the exhaust air port (3).
Important information for the problem-free functioning of the device:
▶ The installation must not cause back pressure to build up.
▶ Select a hose for the connection with an adequate cross-section.
▶ The exhaust air line must be designed in such a way that no water or other liquid can get into the device through the exhaust air port.
▶ Keep the adjacent supply pressure always at least 0.5 – 1 bar above the pressure which is required to move the actuator to its end position.
english
29
Type 8695 REV.2
Pneumatic installation
Pilot air port
(label: 1)
Exhaust air port
(label: 3)
Figure 19: Pneumatic connection air exhaust concept:
▶ In compliance with degree of protection IP67, an air exhaust line must be installed in the dry area.
30 english
Type 8695 REV.2
Electrical installation
9
9.1
electricAl instAllAtion
Safety instructions
Danger!
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
Warning!
Risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
english
31
Type 8695 REV.2
Electrical installation
9.2 Electrical installation, without fieldbus communication
Configuration circular plug (M12 x 1, 8-pin):
5
7
8
6
1
4
2
3
Figure 20: Circular plug M12 x 1, 8-pin
Pin
1
2
5
6
3
4
7
8
Table 3:
Wire color 4) Designation white Digital output top position brown green
Digital output bottom position
Operating voltage
Configuration
DO 1 (=Top)
DO 2 (=Bot)
GND yellow grey pink
Operating voltage +
Valve control +
Valve control -
-
-
Connection with circular plug-in connector
24 V DC
Valve +
Valve not used not used
→ Connect the control head according to the table.
External circuit / signal level
5
6
3
4
GND
24 V
24 V
GND
32
4)
The indicated colors refer to the connecting cable available as an accessory (919061).
english
Type 8695 REV.2
Electrical installation
9.3 Electrical installation, IO-Link Port Class B and Port
Class A
5 port Class b
1
Table 4:
4
Pin
3
2
1
2
3
4
5
Pin assignment, Port Class B
L +
P24
L –
C/Q
M24
Designation Configuration
24 V DC
24 V DC
0 V (GND)
IO-Link
0 V (GND)
System supply
Actuator supply
System supply
Actuator supply
5 port Class A
1
Table 5:
4
Pin Designation
3
2
1
2
3
4
5
Pin assignment, Port Class A
L +
Do not connect
L –
C/Q
Do not connect
Configuration
24 V DC
0 V (GND)
IO-Link
9.4 Electrical installation, büS
System supply
System supply
5
1
4 3
2
Figure 21: Pin assignment
Pin
Table 6:
3
4
5
1
2
Wire color
CAN plate/shielding red black white blue
Pin assignment
Configuration
CAN plate/shielding
+24 V DC ±25%, max. residual ripple 10%
GND / CAN_GND
CAN_H
CAN_L
For electrical installation with büS network, note:
Use a 5-pin round plug and shielded 5-core cable.
The shielding in the device is not connected to the functional earth.
33 english
Type 8695 REV.2
Start-up
10 START-UP
10.1 Safety instructions
Warning!
Risk of injury from improper operation.
Improper operation may result in injuries as well as damage to the device and the area around it.
▶ Before start-up, ensure that the operating personnel are familiar with and completely understand the con tents of the operating instructions.
-
▶ Observe the safety instructions and intended use.
▶ Only adequately trained personnel may operate the equipment/the device.
10.2 Teach function: Determine end positions and save these, REV.2
• automatic teach function: For devices with pilot valve
The teach function automatically identifies and saves the end positions of the valve.
• Manual teach function: For devices without pilot valve
The end positions are captured and saved automatically.
10.2.1 Automatic teach function
For devices with pilot valve:
The teach function automatically identifies and saves the end positions of the valve.
With the IO-Link variant, the teach function can also be started with an acyclic IO-Link parameter (see parameter list) or with the Bürkert Communicator.
With the büS variant, the teach function can also be started with the Bürkert Communicator.
34 essential requirements:
• The device is mounted on the actuator.
• The supply voltage is connected.
• The compressed air supply is connected.
• So that the correct reference conditions are identified, the pilot pressure must correspond to the operating conditions.
Transparent cap
Body casing
Basic housing
Actuator
Figure 22: Open device english
Type 8695 REV.2
Start-up attention
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When opening or closing the device, do not press against the actuator, but against the basic housing.
→ Open the device: turning the transparent cap anti-clockwise.
Button 1
Figure 23: Teach function
→ Hold down the button 1 to start the teach function for approx. 5 s until the teach LED flashes.
→ When the teach LED starts flashing, release the button within 5 seconds.
When the teach LED stops flashing, the teach function is terminated.
The end positions of the valve have been identified and saved.
attention
Damage or malfunction due to ingress of dirt or moisture.
To observe the degree of protection IP65 or IP67:
▶ Screw in transparent cap to the stop.
→ Close the device (wrench 5) : 674078 ).
Description of workflow for teach function:
The teach LED flashes red when the teach function is running.
• The end position is scanned in.
• The pilot valve switches.
• The actuator moves automatically to the upper position.
• The upper end position is scanned in.
• The pilot valve is switched off.
• The actuator moves to the lower position.
• In order to determine the opening time and the closing time, the actuator moves again into the upper and lower end position.
5)
The wrench (674078) is available from your Bürkert sales office..
35 english
Type 8695 REV.2
Start-up
10.2.2 Manual teach function
For devices without pilot valve:
The end positions are captured and saved manually by the user.
With the IO-Link variant, the teach function can also be started with an acyclic IO-Link parameter (see parameter list) or with the Bürkert Communicator.
With the büS variant, the teach function can also be started with the Bürkert Communicator.
essential requirements:
• The device is mounted on the actuator.
• The supply voltage is connected.
• The compressed air supply is connected.
• So that the correct reference conditions are identified, the pilot pressure must correspond to the operating conditions.
• Provide the possibility for the user to switch the pneumatic actuator (open and closed).
Transparent cap
Body casing
Basic housing
Actuator
Figure 24: Opening or closing the device attention
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When opening or closing the device, do not press against the actuator, but against the basic housing.
→ Screw off the transparent cap by turning counterclockwise.
Button 1
36
Figure 25: Starting teach function
→ Air bleed the pneumatic actuator: move to the unactuated end position.
→ Hold down the button 1 to start the teach function for at least 10 s.
After 5 s, the red teach LED will start flashing. Keep the button pressed down. After a further 5 s, the red teach LED flashes very quickly. Only then release the button.
english
Type 8695 REV.2
Start-up
Teach LED red flashes once every second: The manual teach function is active.
→ Check whether the pneumatic actuator is in the deaerated, unactuated end position.
→ This end position is confirmed by briefly pressing the button 1.
Yellow valve LED is lit.
→ Move the pneumatic actuator into the aerated, switched end position.
→ This end position is confirmed by briefly pressing the button 1.
Yellow valve LED is not lit.
→ Air bleed the pneumatic actuator: move to the unactuated end position.
Yellow valve LED is lit.
to determine the opening times and closing times, aerate and deaerate the pneumatic actuator:
Measurement of opening time (Opening_Time):
→ Move the pneumatic actuator into the aerated, switched end position.
Yellow valve LED is not lit.
Measurement of closing time (Closing_Time):
→ Air bleed the pneumatic actuator: move to the unactuated end position.
When the red teach LED stops lighting, the teach function is terminated.
The end positions of the valve have been identified and saved.
Note: If the red teach LED is lit, the manual teach function is defective and must be repeated.
attention
Damage or malfunction due to ingress of dirt or moisture.
To observe the degree of protection IP65 or IP67:
▶ Screw in transparent cap to the stop.
→ Close the device (wrench 6) : 674078).
6)
The wrench (674078) is available from your Bürkert sales office.
37 english
Type 8695 REV.2
Start-up
10.3 Setting with Bürkert Communicator
The Bürkert Communicator can be used to make all settings on the device.
The settings in the Bürkert Communicator can be found in the operating manual.
10.3.1 Connecting IO-Link device with Bürkert Communicator
To ensure clear communication, the IO-Link devices should not be parameterised simultaneously by the higherlevel controller (PLC) via the IO-Link master and with the Bürkert Communicator (via the service).
required components:
• Communications software: Bürkert Communicator for PC
• USB-büS interface set (see accessories)
• büS adapter for communication interface (see accessories)
• If necessary, a büS cable extension (see accessories)
Transparent cap
Body casing
Basic housing
Actuator
Figure 26: Opening or closing the device attention
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When opening or closing the device, do not press against the actuator, but against the basic housing.
→ Screw off the transparent cap by turning counterclockwise.
38 english
Type 8695 REV.2
Start-up
Key 1
Valve LED
Com LED
Communication interface
Teach LED
Key 2
Status LED
Figure 27: Communication interface
→ Insert micro USB plug in communication interface.
→ Establish connection to PC with USB-büS interface set.
→ Starting Bürkert Communicator.
→ Implementing settings.
10.3.2 Connecting büS device with Bürkert Communicator
required components:
• Communications software: Bürkert Communicator for PC
• USB-büS interface set (see accessories)
→ Establish connection to PC with USB-büS interface set.
→ Starting Bürkert Communicator.
→ Implementing settings.
english
39
40
Type 8695 REV.2
IO-Link
11 IO-LINk
11.1
Information, IO-Link
IO-Link is an internationally standardized IO technology (IEC 61131-9) to enable sensors and actuators to communicate.
IO-Link is a point-to-point communication with 3-wire connection technology for sensors and actuators and unshielded standard sensor cables.
To ensure clear communication, the IO-Link devices should not be parameterised simultaneously by the higher-level controller (PLC) via the IO-Link master and with the Bürkert Communicator (via the communication interface).
11.2
Technical specifications, IO-Link
Port Class
IO-Link Specification
Supply
SIO mode
IODD file
VendorID
DeviceID
ProductID
Transmission speed
PD Input Bits
PD Output Bits
M-sequence Cap.
Min. cycle time
Data Storage
Max. cable length
A B
V1.1.2
via IO-Link (M12 x 1, 5-pin, A-coded)
No see Internet
0x0078, 120 see IODD file
8695 Class A
COM3 (230,4 kbit/s)
8695 Class B
48
8
0x0D
5 ms
Yes
20 m
11.3
Configuration of the fieldbus
The required start-up files and the description of the process data and acyclic parameters are available on the Internet.
Download from: www.burkert.com
/ Type 8695 / Software english
Type 8695 REV.2
büS
12 büs
12.1
Information, büS
büS is a system bus developed by Bürkert with a communication protocol based on CANopen.
12.2
Configuration of the fieldbus
The required start-up files and the description of objects are available on the Internet.
Download from: www.burkert.com
/ Type 8695 / Software english
41
Type 8695 REV.2
Control and display elements
13 control And displAy elements
The following chapter describes the operating states as well as the control and display elements of the control head.
For further information on the operation of the control, refer to chapter “10 Start-up”
13.1
Operating state
To operate the buttons, make sure that the local control lock is deactivated/unlocked (factory setting): with communication software or fieldbus communication.
AUTOMATIC (AUTO)
Normal controller mode is implemented and monitored in AUTOMATIC operating state.
MANUAL (MANU)
In MANUAL operating state the valve can be opened and closed manually via the button 2.
The status LED flashes orange (function check, see “13.4.2.3 NAMUR mode”
).
The buttons can be used to switch between the two operating states AUTOMATIC and MANUAL:
→ Press both buttons simultaneously between 2 s and 10 s (com LED flashes 0 – 2 s at 5 Hz).
42 english
Type 8695 REV.2
Control and display elements
13.2
Control and display elements
Button 1
Valve LED
Com LED
Communication interface
Teach LED
Button 2
Status LED
Figure 28: Description control and display elements attention!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the basic housing.
Transparent cap
Body casing
Basic housing
Actuator
Figure 29: Open device
→ Screw off the transparent cap of the device to operate the buttons.
attention!
Damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way.
→ Close the device (assembly tool: 674078 7) ).
7)
The assembly tool (674078) is available from your Bürkert sales office.
43 english
Type 8695 REV.2
Control and display elements
44
13.3
Configuration of the buttons
To operate the buttons, make sure that the local control lock is deactivated/unlocked (factory setting): with communication software or fieldbus communication.
The configuration of the 2 buttons varies depending on the operating state (AUTOMATIC / MANUAL).
Button 1
Valve LED
Com LED
Communication interface
Teach LED
Button 2
Status LED
Figure 30: Description buttons attention!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the basic housing.
→ To operate the buttons unscrew the transparent cap.
Transparent cap
Body casing
Basic housing
Actuator
Figure 31: Open device attention!
Damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way.
→ Close the device (assembly tool: 674078 8) ).
8)
The assembly tool (674078) is available from your Bürkert sales office.
english
Type 8695 REV.2
Control and display elements
MANUAL operating state (status LED flashes orange, function check):
Button
1 -
Function
-
2 Press briefly Valve switches
LeD
Valve LED is lit yellow
1 and 2 simultane ously
Table 7:
Press longer than 2 s
(< 10 s)
Press longer than 10 s
(< 30 s)
Switching to AUTOMATIC operating state
Device restart
Press longer than 30 s Reset device to factory setting
Com LED flashes at 5 Hz
(0 – 2 s)
Valve LED, Com LED and
Teach LED flash at 5 Hz
(10 – 30 s)
Valve LED, Com LED and
Teach LED flash at 10 Hz
(> 30 s)
Configuration of the buttons for MANUAL operating state
AUTOMATIC operating state:
Button
1
2
Press longer than 5 s
(< 10 s)
Press longer than 10 s
(< 30 s)
-
Function
Starting the automatic teach function
Starting the manual teach function
-
LeD
Teach LED flashes at 5 Hz
(5 –10 s)
Teach LED flashes at 10 Hz
(>10 s)
1 and 2 simultane ously
Table 8:
Press longer than 2 s
(< 10 s)
Press longer than 10 s
(< 30 s)
Press longer than 30 s
Switching to AUTOMATIC operating state
Device restart
Reset device to factory setting
Com LED flashes at 5 Hz
(0 – 2 s)
Status LED flashes orange
Valve LED, Com LED and
Teach LED flash at 5 Hz
(10 – 30 s)
Valve LED, Com LED and
Teach LED flash at 10 Hz
(> 30 s)
Configuration of the buttons for AUTOMATIC operating state
45 english
46
Type 8695 REV.2
Control and display elements
13.4
Display of the LEDs
The following status are displayed with LEDs:
• Valve LED yellow: Activation of the pilot valve
• Status LED RGB: status indicator (errors, warnings) and valve position
• Com LED green: fieldbus communication (IO-Link)
• Teach LED red: teach function, error
Button 1
Valve LED
Com LED
Communication interface
Teach LED
Button 2
Status LED
Figure 32: Description LEDs attention!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the basic housing.
Transparent cap
Body casing
Basic housing
Actuator
Figure 33: Open control head attention!
Damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way. english
Type 8695 REV.2
Control and display elements
13.4.1
Valve LED, activation of the pilot valve
Color yellow yellow
Table 9:
Status is lit is not lit
Valve LED
Description
Pilot valve is activated
Pilot valve is not activated
13.4.2
Status indicator
The status LED (RGB) show the device status.
The user can set the following LED modes for the display of device status and valve position.
• NAMUR mode
• Valve mode
• Valve mode with warnings (factory setting)
• Fixed color
• LED off
The LED mode and the colors of the valve position can be set with the Bürkert Communicator.
IO-Link:
The LED mode and the colors of the valve position can be also set with an acyclic parameter (see para meter list).
13.4.2.1 Valve mode
Displays in valve mode:
• Valve position: open, half-way, closed
• Device status: failure
Valve position
Open
Half-way
Closed
Table 10:
Valve position status, color is lit yellow*
LED off* is lit green*
Valve mode
Device status: error status, color flashes red flashes red flashes red alternately with yellow* alternately with LED off* alternately with green*
* Factory setting, selectable colors for the valve position: Off, white, green, blue, yellow, orange, red
47 english
Type 8695 REV.2
Control and display elements
13.4.2.2 Valve mode + warnings
Displays in valve mode + warnings:
• Valve position: open, half-way, closed
• Device status: failure, function check, out of specification, maintenance required (according to NAMUR)
Valve position
Open
Half-way
Closed
Table 11:
Status, color is lit yellow*
LED off* is lit green*
Device status normal operation
--
--
--
Valve mode + warnings, normal operation
If several device statuses exist simultaneously, the device status with the highest priority is displayed.
Valve position Device status
Failure
Status, color
Function check out of specification
Maintenance required
Status, color Status, color Status, color
Open flashes red flashes orange flashes yellow flashes blue
Half-way
Closed flashes red flashes orange flashes yellow flashes red flashes orange flashes yellow flashes blue flashes blue
Table 12: Valve mode + warnings, device status alternately with yellow* alternately with LED off* alternately with green*
For warning messages, the LEDs are briefly switched off between the change of the colors.
For localizations, the colors are only shown momentarily.
48
* Factory setting, selectable colors for the valve position: Off, white, green, blue, yellow, orange, red english
Type 8695 REV.2
Control and display elements
13.4.2.3 NAMUR mode
The device status LED show the device status.
The display elements change color in accordance with NAMUR NE 107.
If several device statuses exist simultaneously, the device status with the highest priority is displayed. The priority is determined by the severity of the deviation from controlled operation (red LED = failure = highest priority).
Status display in accordance with NE 107, edition 2006-06-12
Color Color code Status Description
Red 5
Orange
Yellow
4
3
Outage, error or malfunction
Function check
Normal operation is not possible due to a mal function in the device or on its peripheral equipment.
Work is being carried out on the device; normal ope ration is therefore temporarily not possible
Out of specification Ambient conditions or process conditions for the device are outside the specified area.
Blue 2 Maintenance required The device is in normal operation, although a function is briefly restricted.
Green 1 Diagnostics active
→ Service device.
Device is operating perfectly. Status changes are indicated in different colors.
Messages are transmitted via a fieldbus if connected.
Table 13: Description of the colors
13.4.3
Com LED, filedbus communication (IO-Link)
Color green green
Table 14:
Status is not lit flashes
Com LED, green
Description
IO-Link communication inactive
IO-Link communication active
13.4.4
Teach LED, teach function
Color red red red
Table 15:
Status is lit is not lit flashes
Teach LED, red
Description
Teach function error
After restart or successful teach function
Teach function active
49 english
Type 8695 REV.2
Control and display elements
13.5
Manual actuation of the actuator with pilot valve
The actuator can be moved without a supply voltage from the rest position to its end position and back again when pilot air is connected .
To do this, the pilot valves must be actuated with a screwdriver. opening the device:
Transparent cap
Body casing
Basic housing
Actuator
Figure 34: Opening the device attention!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the body casing or transparent cap, do not hold the actuator of the process valve but the basic housing.
→ To activate the device manually, unscrew the body casing (wrench 9) : 674078).
Manual activation: attention!
The hand lever may be damaged if it is simultaneously pressed and turned.
▶ Do not press the hand lever when turning it.
Pilot valve non activated
(normal position)
Hand lever to the left
Hand lever
Pilot valve activated
Hand lever to the right
50
Figure 35: Pilot valves for aerate and deaerate the actuator
9)
The wrench (674078) is available from your Bürkert sales office.
english
Type 8695 REV.2
Control and display elements
Move actuator to end position
→ Turn the hand levers to the right using a screwdriver.
Note: do not press the hand levers when turning them
Move actuator back to the rest position
→ Turn the hand levers to the left using a screwdriver.
Note: do not press the hand levers when turning them
Caution:
If the pilot valves are actuated, electrical control is not possible.
▶ Move hand levers to normal position before starting up the device.
Closing the device:
Transparent cap
Body casing
Basic housing
Actuator
Figure 36: Closing the device attention
Damage or malfunction due to ingress of dirt or moisture.
To observe the degree of protection IP65 or IP67:
▶ Screw in body casing to the stop.
→ Close the device (wrench 10) : 674078 ).
10)
The wrench (674078) is available from your Bürkert sales office..
english
51
Type 8695 REV.2
Control and display elements
13.6
Setting the LED mode, status indicator
User level: installer
Factory setting: valve mode + warnings
Values or description Menu or function
Device
> general settings
> parameter
> status lEd mode nAmuR mode
Valve mode
Valve mode + Warnings
Fixed color
LED off
Setting the LeD mode, status indicator:
→ Status LED
→ Mode
Possible selection:
nAmuR mode
Valve mode
Valve mode + Warnings
Fixed color
LED off
→ Select mode.
The mode is set.
52 english
Type 8695 REV.2
Safety end positions
14 sAfety end positions
Safety end positions after failure of the electrical or pneumatic auxiliary power:
Actuator system Designation
Safety end positions after failure of the auxiliary power electrical pneumatic up down single-acting
Control function A down down up down single-acting
Control function B up up up down
Table 16: Safety end positions double-acting
Control function B down not defined
15 mAintenAnce
The control head Type 8695 is maintenance-free when operated according to the instructions in this manual.
english
53
Type 8695 REV.2
Disassembly
16 disAssembly
16.1
Safety instructions
Danger!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
Warning!
Risk of injury from improper disassembly.
▶ Disassembly may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following disassembly, ensure a controlled restart.
16.2
Disassembly the control head
Procedure:
1. Pneumatic connection
Danger!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
→ Loosen the pneumatic connection.
→ 20xx series:
Loosen the pneumatic connection to the actuator.
54 english
Type 8695 REV.2
Disassembly
2. Electrical connection
Danger!
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
→ Loosen the circular plug-in connector.
3. Mechanical connection
→ Loosen the fastening screws.
→ Remove the control head upwards.
Control head
Electrical connection circular plug-in connector
Pneumatic connections
Fastening screws (2x)
Pneumatic connection to the actuator
Actuator
Series 20xx
(Classic)
Series 21xx
(Element)
Figure 37: Disassembly the control head
55 english
Type 8695 REV.2
Accessories
17 Accessories
Designation
Connection cable M12 x 1, 8-pin
Wrench for opening/closing the transparent cap
Communication software Bürkert Communicator order no.
919061
674078
Information at www.burkert.com
USB-büS interface set:
USB-büS interface set (büS stick + 0.7 m cable with M12 plug) büS adapter for communication interface
(M12 on büS service interface Micro-USB)
2
3
5
4
L
1
4 5
3
2 büS cable extension (M12 pin to M12 socket), length 1 m büS cable extension (M12 pin to M12 socket), length 3 m büS cable extension (M12 pin to M12 socket), length 5 m büS cable extension (M12 pin to M12 socket), length 10 m
Table 17: Accessories
772551
773254
772404
772405
772406
772407
17.1
Communications software
The PC operating program Bürkert Communicator is designed for communication with the devices Type 8695.
If you have any questions regarding compatibility, please contact the Bürkert Sales Center.
A detailed description and precise schedule of the procedure for the installation and operation of the software can be found in the associated documentation.
Download the software at: www.burkert.com
56 english
Type 8695 REV.2
Packaging and transport
18 PACkAgINg AND TRANSPORT
attention!
Transport damages.
Inadequately protected equipment may be damaged during transport.
▶ During transportation protect the device against wet and dirt in shock-resistant packaging.
▶ Avoid the effects of heat and cold which could result in temperatures above or below the permitted stor age temperature.
-
19 storAGe
attention!
Incorrect storage may damage the device.
▶ Store the device in a dry and dust-free location.
▶ Storage temperature -20 – +65°C.
20 disposAl
→ Dispose of the device and packaging in an environmentally friendly manner.
attention!
Damage to the environment caused by device components contaminated with media.
▶ Observe the relevant disposal and environmental protection regulations.
Note:
Observe national waste disposal regulations.
english
57
58 english