Burkert 8746 is a versatile device serving as both a mass flow controller and a meter for gases. It excels in various applications, ranging from metal and glass manufacturing to test benches and filling systems. With its multiple interface options, it seamlessly integrates into existing systems, supporting CANopen, CAN-based büS, PROFIBUS-DP, and analog communication. The integrated configuration memory simplifies device exchange by storing relevant parameters, eliminating the need for software tools.
जाहिरात
जाहिरात
DATA SHEET
Type 8746
Mass flow controller (MFC) / Mass flow meter
(MFM) for gases
• Nominal flow ranges from 20 l
N
/min up to 2500 l
N
/min
• High measuring accuracy and repeatability with very fast response times
• Long-term stability of the flow calibration
• Simpler device exchange due to configuration memory
• Optional: ATEX II Cat. 3G/D or USP Class VI, FDA, EC 1935 con
-
formity
Product variants described in the data sheet may differ from the product presentation and description.
Can be combined with
Type 6013
Plunger valve 2/2 way direct-acting
Type 6027
Direct-acting 2/2 way plunger valve
Type 0330
Direct-acting 2/2 or
3/2-way pivoted arma ture valve
Type 0290
Servo-assisted 2/2-way diaphragm valve
Type ME43
Fieldbus gateway
Type ME63
Industrial Ethernet gateway, IP65/ IP67/ IP69k
Type description
The mass flow controller (MFC) / mass flow meter (MFM) Type 8746 for gases is suitable for a wide range of applications, e.g. metal and glass manufactur ing or processing, fermentation processes, test benches or filling systems and packaging machines. Type 8746 is available in two variants: A variant with several analogue or digital (communication) interfaces and a variant with a pure CANopen-based interface. The latter is suitable for integration in existing
CANopen networks or - in combination with a Bürkert fieldbus gateway - for integration in all common industry standards for Industrial Ethernet or field bus. This variant is tailor-made for applications with many control loops. Up to 32 MFCs / MFMs can be connected to one fieldbus gateway. The gateway transmits the internal CANopen-based communication to Industrial Ether net and fieldbus standards. The mass flow controller / mass flow meter can always be switched between büS and CANopen communication. Type 8746 can be configured as an MFM or an MFC according to demand. Optionally, up to four calibration curves can be stored in the device. The thermal inline sensor is located directly in the main flow and achieves fast response times and a high level of measuring accuracy with long-term stable calibration. As the actuator, a Bürkert direct-acting, electromagnetic proportional valve or motor valve guarantees high response sensitivity. The integrated PI controller ensures excellent control characteristics of the MFC. Type 8746 is character ised by low pressure drop, even at high flow rates, and is especially designed for use in harsh environments thanks to its high IP protection class and explo sion protection.
1000241027 | Standard | EU | en | 202108 | 16
© Christian Bürkert GmbH & Co. KG, Subject to alteration
Visit product website
Type 8746
Table of contents
5. Device/Process connections 17
6. Performance specifications 18
8. Product design and assembly 19
Visit product website
2 | 23
Type 8746
Visit product website
3 | 23
Type 8746
1. General Technical Data
1.1. General
Product properties
Materials
Body
Housing
Seal
Configuration memory (included in delivery)
Electrical data
Operating voltage
Voltage tolerance
Residual ripple
Stainless steel or aluminium
Aluminium die casting (coated)
FKM or EPDM (depending on gas) 1.)
EEPROM (μSIM card: stores all parameters (e.g. individual fieldbus or controller set tings) relevant for device replacement without software tool)
24 V DC
± 10 %
± 2 %
Electrical connection
Medium data
Operating medium
Calibration medium
Medium temperature
Neutral, non-contaminated gases, others on request
Operating gas or air with correction function
- 10 °C 2.) …+ 70 °C
(- 10 °C 2.) …+ 60 °C with oxygen)
Process/Port connection & communication
Port connection G or NPT ¼", ⅜", ½", ¾", 1"
Flange
Digital (communication) interfaces
Analogue interfaces
CANopen, CAN based büS or PROFIBUS-DP
4…20 mA, 0…20 mA, 0…10 V or 0…5 V
Input impedance > 20 kΩ (voltage) o.R. < 300 Ω (current)
Max. Current: 10 mA (voltage output); max. Load: 600 Ω (current output)
Environment and installation
Installation position
Ambient temperature
Accessories
Software-Tool
M12 plug, 5 pin
For analog and PROFIBUS-DP version additionally: M12 socket, 5 pin
Horizontal or vertical
- 10 °C…+ 50 °C 3.) (higher temperatures on request)
Bürkert Communicator
Detailed information can be found in chapter “9.1. Bürkert Communicator Software” on page 20
.
1.) When using the motor valve additionally:
- Type 3280 DN 4: valve seat seal from PEEK
- Type 3285: valve seat seal from Al2O3
2.) When using the motor valve, the minimum medium temperature is 0 °C
3.) Max. Ambient temperature for versions with cULus approval is 40 °C
1.2. Version with electromagnetic proportional valve
Type 8746 can be configured as MFC or MFM as required. The MFC version uses direct-acting proportional valves of the 287x series. These electromagnetic proportional valves are normally closed and stand for highest measuring accuracy and repeatability with response times of a few hundred milliseconds.
Product properties
Dimensions
Total weight
Proportional valve (electromagnetic)
Nominal valve sizes k
VS
value range
LED display
Detailed information can be found in chapter
.
approx. 1.8 kg (Al, 16 W valve) approx. 3.1 kg (VA, 16 W valve)
Normally closed
0.8…12 mm
0.02…2.5 m 3 /h
RGB-LED acc. to NAMUR NE107
Visit product website
4 | 23
Type 8746
Performance data
Nominal flow range (Q
Nom
) 20…1500 l
N
/min (N
2
MFM up to 2500 l
N
1:50 1.)
10 bar, for MFCs the max. pressure depends on the media and the orifice of the valve, optional up to 25 bar for MFM
± 1.5 % o.R ± 0.3 % F.S. (after 15 min warm up time)
± 0.1 % F.S.
< 500 ms
)
/min (N
2
)
Measuring range
Max. Operating pressure
(Overpressure to atmospheric pressure)
Measuring accuracy
Repeatability
Settling (MFC)/response (MFM) time (t
95 %
Electrical data
)
Power consumption 2.) Max. 2 W (as MFM)
Max. 10.5…29.5 W (as MFC, depending on the proportional valve type)
Environment and installation
Degree of protection IP65
1.) In vertical installation position with flow from top to bottom the measuring range is 1:10.
2.) Data refers to the typical power consumption (at 23 °C ambient temperature, nominal flow rate and 30 min control mode). The specifications according to UL 61010 - 1 can differ (see Operating Manual).
1.3. Version with electromotive proportional valve
Type 8746 with electromotive proportional valve is especially suitable for applications with high inlet pressures up to 22 bar or high flow rates (with low pressure loss). Thanks to their very low holding capacity, these valves can drastically reduce the less energy con sumption of a system. When de-energized, the motor valves remain in position. The maximum duty cycle of the motor depends on the ambient temperature. The duty cycle is not the duty cycle of the appliance but the duty cycle of the motor. This is only switched on when the valve is to move. The duty cycle of the motor increases drastically due to frequent changes in the setpoint value. More
.
Product properties
Dimensions
Total weight
LED display 1.)
Proportional valve (electromotive)
Nominal valve sizes k
VS
value
Performance data
Nominal flow range (Q
Nom
Measuring range
)
Max. Operating pressure
(Overpressure to atmospheric pressure)
Measuring accuracy
Repeatability
Settling (MFC)/response (MFM) time (t
95 %
Electrical data
)
Power consumption
Detailed information can be found in chapter
.
Ca. 1.67 kg (Al, Standard, valve Type 3280)
Ca. 2.94 kg (VA, Standard, valve Type 3280)
On MFM: RGB-LED acc. to NAMUR NE107
On valve: RGB-LED to indicate valve opening
Staying without current
2…20 mm
0.5…7.8 m
20…2500 l
N
1:50 2.)
3 /h
± 2 % o.R. ± 0.5 % F.S. (after 15 min warm up time)
± 0.5 % F.S.
< 5 s
/min (N
2
)
22 bar (for MFC the max. operating pressure depends on the nominal valve size)
Max. 2 W (as MFM)
Max. 10.5 W (as MFC) 3.)
Environment and installation
Degree of protection IP54 (with valve Type 3280) or IP50 (with valve Type 3285)
1.) Detailed description of the LED colours: see Operating Manual.
2.) In vertical installation position with flow from top to bottom the measuring range is 1:10.
3.) Data during the movement of the engine valve. The holding power of the valve is < 1 W.
Visit product website
5 | 23
Type 8746
2. Approvals
Note:
• The approvals and conformities listed below must be stated when making enquiries. This is the only way to ensure that the prod uct complies with all required specifications.
• Not all available types can be supplied with the approvals or conformities below.
Approvals Description
UL Listed according to DIN EN 61010-1 for USA and Canada
FDA
Conformity of all materials in contact with the medium
USP Class VI chapter “87 in vitro” and „88 in vivo, Implantation“
Conformity of all materials in contact with the medium
FDA – Code of Federal Regulations Title 21 Paragraph 177 (CFR 21 177.2600)
Conformity of all materials in contact with the medium
Regulation (EC) No. 1935/2004 on materials and objects intended to come into contact with food
ATEX
ATEX/ IECEx:
II 3G Ex nA IIC T* Gc X and
II 3D Ex tc IIIC T***°C Dc X acc. to DIN EN 60079 - 0 and DIN EN 60079 - 15, T3/4 and T160 °C/135 °C depending on device variant
3. Materials
3.1. Chemical Resistance Chart – Bürkert resistApp
Bürkert resistApp – Chemical Resistance Chart
You want to ensure the reliability and durability of the materials in your individual
application case? Verify your combination of media and materials on our website or in our resistApp.
Start Chemical Resistance Check
4. Dimensions
Note:
The following table applies to the following dimensions.
A
G ¼
NPT ¼
G ⅜
NPT ⅜
G ½
NPT ½
G ¾
NPT ¾
11
15
14
16
15
Thread depth [mm]
12
11
12
Visit product website
6 | 23
Type 8746
4.1. Devices with büS/CANopen interface
MFC with valve Type 2873 (9 W coil)
Note:
Dimensions in mm
4 x M4 10
48 40
194.15
MFC with valve Type 2875 (16 W coil)
Note:
Dimensions in mm
4 x M4 10
48 40 approx. 14.15
A
48
53
95.5
85.6
83
69.5
34
0
Visit product website
212.65
approx.
12.65
116
A
48
53
111.05
85.6
83
69.5
34
0
212.65
7 | 23
Type 8746
MFC with valve Type 2836 (24 W coil)
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
4 x M4 10
99
205 version with base block for large nominal flow rates
A
48
53
170.6
132.6
85.6
83
69.5
34
0
A
53
178.6
141.1
99.6
97
83.5
48
0
Visit product website
8 | 23
Type 8746
MFC with valve Type 3280
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
228
approx.
28
Ø A
48
53
58
155.9
85.6
83
69.3
34
0 version with base block for large nominal flow rates
228
approx.
28
Ø A
48
58
169.4
164.95
99.6
97
83.3
71
48
0
Visit product website
9 | 23
Type 8746
MFC with valve Type 3285
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
249
approx. 29
Ø A
48
58
77
161.95
157.85
99.6
97
83.3
71
48
0
DN20
251
approx. 22
Ø A
48
68
77
164.45
160.35
99.6
97
83.3
71
48
0
Visit product website
10 | 23
Type 8746
MFM
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
4 x M4 10
53
A
48
83
69.5
57
34
0 version with base block for large nominal flow rates
53
A
48
97
83.5
71
48
0
Visit product website
11 | 23
Type 8746
4.2. Devices with analog or PROFIBUS-DP interface
MFC with valve Type 2873 (9 W coil)
Note:
Dimensions in mm
4x M4 10
119.25
116
88
54
34
0
194
MFC with valve Type 2875 (16 W coil)
Note:
Dimensions in mm
4x M4 10
approx. 14
A
48
119.25
116
88
54
34
0
Visit product website
213
approx. 13
A
48
12 | 23
Type 8746
MFC with valve Type 2836 (24 W coil)
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
4x M4 10
170.6
119.25
116
88
54
34
0 version with base block for large nominal flow rates
4x M4 10
A
48
178.6
130
102
68
48
0
Visit product website
A
13 | 23
Type 8746
MFC with valve Type 3280
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
4x M4 10
155.9
119.25
116
88
54
34
0
227 version with base block for large nominal flow rates
4x M4 10
approx.
27
A
48
58
169.4
130
102
68
48
0
227
approx. 27
A
48
58
Visit product website
14 | 23
Type 8746
MFC with valve Type 3285
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
4x M4 10
161.95
157.85
130
102
68
48
0
DN20
4x M4 10
249
approx.
29
A
48
58
164.45
160.35
130
102
68
48
0
Visit product website
251
210.65 218.15
approx. 22
A
48
68
77
15 | 23
Type 8746
MFM
Note:
• From a nominal flow rate Q
Nom
> 1500 l
N
/min the overall length increases by 30 mm.
• Dimensions in mm
4x M4 10
40 48
116
88
54
34
0
A
48
130
102
68
48
0 version with base block for large nominal flow rates
4x M4 10
40 48
A
48
Visit product website
16 | 23
Type 8746
5. Device/Process connections
5.1. CANopen or CANopen-based büS
M12 plug, 5 pin (A-coded)
5
4
1
3
2
Coding
Pin Configuration
1 Shield
2 24 V
3 DGND
4 CAN_H
5 CAN_L
5.2. Analogue
M12 socket, 5 pin (A-coded)
5
4 1
Coding
3 2
M12 plug, 5 pin (A-coded)
3 2
4
Coding
1
5
Pin Configuration
1 Digital input GND
2 Digital input +
3 Relay, Reference contact
4 Relay, Opener (disconnect contact / normally closed (NC))
5 Relay, Closer (make contact / normally open (NO))
Pin Configuration
1 Set value input GND (not connected for MFM)
2 24 V
3 GND
4 Set value input (not connected for MFM)
5 Analogue output for the measured value
5.3. PROFIBUS-DP
M12 socket, 5 pin (B-coded)
5
3 4
Pin Configuration
1 5 V
2 RxD / TxD (Line A)
3 DGND
4 RxD / TxD (Line B)
5 Not connected
2 1
Coding
M12 plug, 5 pin (A-coded)
3 2
Coding
4 1
5
Pin Configuration
1 Shield
2 24 V
3 GND
4 Not connected
5 Not connected
Visit product website
17 | 23
Type 8746
6. Performance specifications
6.1. Pressure Loss Diagram of the MFM
The diagram shows an example of the pressure loss characteristics when air flows through. To determine the pressure loss of another gas, the corresponding air equivalent must first be calculated and the basic fluidics used for the other gas taken into account.
600
560
480
460
400
380
320
300
240
220
140
120
60
40
0
G1/4
G3/8
G1/2
G3/4
G1
250 500 750 1000 1250 1500 1750 2000 2250
Q [l
N
2500
/min]
6.2. Flow characteristic
Nominal flow range of typical gases
Note:
• All values refer to 1.013 bara and 0 °C (Index N)
• Other gases and gas mixtures on request
Gas
Acetylene
Ammonia
Argon
Carbon dioxide
Air, oxygen, nitrogen
Methane
Propane
20
20
20
20
Min. Q
Nom
[l
N
20
/min]
8
20
Max. Q
Nom
[l
N
/min]
320 (from 65 l
N
1000
/min with air calibration)
1600
1000
2500
750
200
6.3. Derating diagram
Electromotive versions
100
90
80
70
60
50
40
30
20
10
5 10 15 20 25 30 35 40 45 50 55 60 65
Max. ambient temperature [°C]
Visit product website
DN2...6 (< 6 bar)
DN8...10 and DN2...6 (> 6 bar)
DN12...20 (< 6 bar)
18 | 23
Type 8746
7. Product operation
7.1. Measuring principle
This sensor works as a hot-film anemometer in the so called CTA operational mode (Constant Temperature Anemometer). To do this, two resistors with precisely specified temperature coefficients located directly in the media flow and three resistors located outside the flow are connected together to form a bridge.
The first resistor in the gas flow (R
T
) measures the fluid temperature, while the second, low value resistor (R is a measure of the heat being removed by the flowing gas, and represents the primary measurement.
S
) is heated so that it is maintained at a fixed, predefined overtemperature with respect to the fluid temperature. The heating current required to maintain this
An adequate flow conditioning within the MFC and the calibration with high quality flow standards ensure that the mass of gas flow ing per time unit can be derived from the primary signal with high accuracy.
R
R
V
R
PI
I
S
R
T
R
S
8. Product design and assembly
8.1. Product features
Measures to comply with ATEX requirements
Note:
Devices with ATEX conformity meet protection class IP65.
5
1
4
2
3
No. Description
1 Standard requirements for cable glands are fulfilled for versions with external valve.
2 M12 plug achieves protection class IP65 with and without mounted counterpart.
3 Die-cast housing receives IP protection under high mechanical stress.
4 Screws prevent uncoupling of the M12 connection under tension.
5 Impact protection cap prevents damage of the M12 plug and all connected elements if mechanical stress is applied. No particular ATEX sockets are required.
Visit product website
19 | 23
Type 8746
9. Product accessories
9.1. Bürkert Communicator Software
Note:
To install the software, click here .
Part of Bürkert’s EDIP program (Efficient Device Integration Platform) is the Bürkert Communicator. This software can be run under
MS-Windows and it is available on Bürkert’s website for free. The Bürkert Communicator allows convenient system configuration and parametrisation of all connected field devices. An accessory part, the büS stick serves as the interface between computer and process instruments (see
“10.4. Ordering chart accessories” on page 21 ). It transfers “USB data” to “CAN data”. The Communi
cator allows:
• Diagnosis
• Parametrization
• Registration and storage of process data
• To watch graph of process
• To update firmware of the device connected
• Guided re-calibration
Type 8746 connection with Bürkert Communicator software
The interface to the “Bürkert Communicator” software tool is based on CANopen. The appropriate bus termination is mandatory.
Hence, please activate, for Type 8746 with analogue or PROFIBUS interface, the termination resistor switch on the büS-stick. For
Type 8746 büS / CANopen, this termination resistor should not be activated, in case the device is already integrated in a properly terminated bus network
To connect the MFC / MFM with the “Bürkert Communicator” software tool, you need a büS-stick. The büS-stick sets contain the necessary accessories.
• For Type 8746 büS / CANopen, the connection is made directly via the 5 pin M12 plug (büS-stick Set 1 contains the necessary accessories).
• For Type 8746, with analogue or PROFIBUS, the connection is made via the micro-USB socket on the device (büS-stick Set 2 contains the necessary accessories).
ATTENTION: No external power supply may be connected to the micro-USB socket! The power supply to the unit must be provided
as described in chapter “5. Device/Process connections” on page 17
.
Visit product website
20 | 23
Type 8746
10. Ordering information
10.1. Bürkert eShop – Easy ordering and quick delivery
Bürkert eShop – Easy ordering and fast delivery
You want to find your desired Bürkert product or spare part quickly and order directly?
Our online shop is available for you 24/7. Sign up and enjoy all the benefits.
Order online now
10.2. Recommendation regarding product selection
Note:
The product questionnaire form at the end of this document contains the relevant fluid specification. Using the experience of
Bürkert engineers already in the design phase provide us with a copy of the request containing the necessary data together with your inquiry or order.
For the proper choice of the actuator orifice within the MFC, not only the required maximum flow rate Q ues directly before and after the MFC (p
, but also the pressure val -
should be known. In general, these pressures are not the same as the overall inlet and outlet pressures of the whole plant, because usually there are additional flow resistors (tubing, additional shut-off valves, nozzles etc.) present both before and after the controller.
Please use the product questionnaire form at the end of this document to indicate the pressures directly before and after the MFC.
If these are unknown or not accessible to a measurement, estimates are to be made by taking into account the approximate pressure drops over the flow resistors before and after the MFC, respectively, at a flow rate of Q let pressure p
1
1
, p
2
) at this flow rate Q
Nom
Nom
Nom
. In addition, please quote the maximum in -
max. to be encountered. This data is needed to make sure the actuator is able to provide a close-tight function within all the specified modes of operation.
10.3. Bürkert product filter
Bürkert product filter – Get quickly to the right product
You want to select products comfortably based on your technical requirements?
Use the Bürkert product filter and find suitable articles for your application quickly and easily.
Try out our product filter
10.4. Ordering chart accessories
Note:
• A büS-Stick is required to connect the MFC / MFM with the “Bürkert Communicator” software tool. It is connected via the micro
USB-socket on the device (büS-Stick set 2 contains the necessary accessories).
• Please note: The interface to our software tool “Bürkert Communicator” is based on CANopen. A corresponding bus termination is mandatory. Therefore please activate the switchable terminating resistor on the büS-Stick.
Description
General accessories
Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 1.25 A, NEC Class 2 (UL 1310)
Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 1 A, NEC Class 2 (UL 1310)
Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 2 A, NEC Class 2 (UL 1310)
Power supply Type 1573 for rail mounting, 100…240 V AC / 24 V DC, 4 A
Article no.
772438
772361
772362
772363
Visit product website
21 | 23
Type 8746
Description büS-Stick Set 1 incl. cable (M12 and Micro-USB) Stick with integrated terminating resistor, power supply and software büS-Stick Set 2 incl. cable (M12 and Micro-USB) Stick with integrated terminating resistor
Configuration memory (Industrial µSim-Card)
Software Bürkert Communicator
Article no.
772426
772551
On request
Download from www.burkert.com
CANopen/büS büS cable extension M12, 0.1 m büS cable extension M12, 0.2 m büS cable extension M12, 0.5 m büS cable extension M12, 1 m büS cable extension M12, 3 m
Connector M12, socket, straight 1.)
Connector M12, plug, straight 1.)
Connector M12, socket, angled 1.)
Connector M12, plug, angled 1.)
CANopen/büS
Y-junction
Y-junction for connecting two separately powered segments of a büS network
Termination resistor 120 Ohm M12 plug
Termination resistor 120 Ohm M12 socket
LabVIEW device driver
EDS-File (CANopen)
772492
772402
772403
772404
772405
772416
772417
772418
772419
772420
772421
772424
772425
On request
Download from www.burkert.com
Analogue
Connection cable M12 plug (A-coded) on open leads, 5 m
Connection cable M12 plug (A-coded) on open leads, 10 m
Connection cable M12, socket (A-coded) on open leads, 5 m
Connection cable M12, socket (A-coded) on open leads, 10 m
PROFIBUS-DP
Connection cable M12, socket (A-coded) on open leads, 5 m
Connection cable M12, socket (A-coded) on open leads, 10 m
GSD-File (PROFIBUS-DP)
566923
571393
560365
563108
560365
563108
Download from www.burkert.com
1.) It is possible that the M12 connectors cannot be used together on the same side of a Y-junction. If that is the case, please use a prefabricated cable which uses typically a thinner connector.
Visit product website
22 | 23
Bürkert – Close to You
For up-to-date addresses please visit us at www.burkert.com
Austria
Belgium
Czech Republic
Denmark
Finland
France
Germany
Italy
Netherlands
Norway
Poland
Spain
Sweden
Switzerland
Turkey
United Kingdom
Russia
Canada
USA
Brazil
Uruguay
South Africa
United
Arab
Emirates
Australia
New Zealand
China
Hong Kong
India
Japan
Korea
Malaysia
Philippines
Singapore
Taiwan
Credits, © and concept: Christian Bürkert GmbH & Co. KG | Photographs: Marc Eggimann Fotografie - 4051 Basel | Scanner GmbH - Werbeagentur Künzelsau -
74653 Künzelsau
Product Enquiry Form
Mass Flow Controller for gases
Product Enquiry Form - Mass Flow Controller For Gases
Thank you for your interest in our products! In order to provide you with optimum advice, please fill out the following form and send it to your Bürkert representative or e-mail address: [email protected]
. All information submitted will of course be kept strictly confidential.
Please fill in the required fields ! *
*Note: The interactive functions of this PDF may be restricted depending on the PDF reader used.
Personal Information
Company
Customer no.
Street
Telephone no.
Delivery
MFC Application MFM Application
Contact person
Department
Postcode / Town
Quantity Required delivery date
Medium data
Type of gas or gas mixture
Medium temperature
Ambient temperature
ºC / ºF
ºC / ºF
Fluidic data
Flow range Q
Nom
Inlet pressure at Q
Nom
2.)
Outlet pressure at Q
Max. inlet pressure
Port connection
Nom
Min. Max. unit
Ref. N 1.) Ref. S 1.) p
1
= p
2
= p
1max
=
barg
barg
barg
3.)
3.)
3.)
Compression fitting Subbase Vacuum fitting
Thread: G (DIN ISO 228/1) NPT (ANSI B1.2)
¼" ⅜" ½" ¾" 1"
Installation
horizontal, valve upright vertical, upward flow
horizontal, valve horizontal vertical, downward flow 4.)
1.) Reference conditions: Ref. N: T=0°C, P=1,013 bar(a); Ref. S: T=20°C, P=1,013 bar(a)
2.) Corresponds to the calibration pressure
3.) Please indicate all pressure values as overpressure to atmospheric pressure [barg] (g = relative pressure)
4.) Possible reduction of the setting range to 1:10 for a vertical downwards flow
Material specifications
Body
Seals
Electrical data
IP protection
Control / Communication
Note:
Please choose one of the following op tions!
Aluminium Stainless steel
FKM EPDM
Industrial Ethernet
PROFINET
Ethernet IP
Modbus TCP
EtherCAT
(RJ45 always standard) Connection
Note:
Please choose one of the following op tions!
Yes (IP65) No (IP20 or better)
Normsignal CANopen/büS
0 … 5 V
0 … 10 V
0 … 20 mA
CANopen
büS
PROFIBUS DP
4 … 20 mA
D Sub socket
Terminal block
M12 socket
Terminal block
D Sub socket
M12 socket
Visit this product area on the website
© Christian Bürkert GmbH & Co. KG, subject to change
1 | 2
Product Enquiry Form
Mass Flow Controller for gases
Approvals / Conformities
UL
ATEX II Cat. 3 G/D, IECEx
USP Class VI conformity
FDA conformity
EG 1935/2004 conformity
Additional Requirements / Comment
Send form Delete form
Visit this product area on the website
© Christian Bürkert GmbH & Co. KG, subject to change