Lennox SSB*H4 Series Installation Instructions

Add to My manuals
28 Pages

advertisement

Lennox SSB*H4 Series Installation Instructions | Manualzz

201

9

Lennox Industries Inc.

Dallas, Texas, USA

INSTALLATION

INSTRUCTIONS

Elite

®

SSB*H4 Units

AIR CONDITIONER UNITS

50

8039

-01

11

/201

9

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.

Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.

IMPORTANT

The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.

Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.

TABLE OF CONTENTS

Shipping and Packing List

General

. . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Model Number Identification

Unit Parts Arrangement

. . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . .

Operating Gauge Set and Service Valves . . . . . . . . .

Recovering Refrigerant from Existing System

New Unit Placement

. . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Removing and Installing Panels . . . . . . . . . . . . . . . . .

New or Replacement Line Set . . . . . . . . . . . . . . . . . . .

Brazing Connections . . . . . . . . . . . . . . . . . . . . . . . . . . .

Flushing Line Set and Indoor Coil . . . . . . . . . . . . . . . .

Installing Indoor Metering Device . . . . . . . . . . . . . . . .

Leak Test Line Set and Indoor Coil . . . . . . . . . . . . . . .

Evacuating Line Set and Indoor Coil . . . . . . . . . . . . .

Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Units Delivered Void of Charge

Unit Start-Up

. . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Shipping and Packing List

25

26

27

19

21

21

22

16

17

18

9

10

12

15

4

6

7

2

2

3

1

1

IMPORTANT

This unit must be matched with an indoor coil as speci­ fied in Lennox SSB*H4 Product Specification bulletin .

Coils previously charged with HCFC-22 must be flushed.

NOTICE TO INSTALLER

UNIT PLACEMENT

It is critical for proper unit operation to place outdoor unit on an elevated surface as described in Unit Placement

section on page 7.

BRAZING LINE SET TO SERVICE VALVES

It is imperative to follow the brazing technique illustrated starting on

page 12 to avoid damaging the service valve's internal seals.

Page 1

Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.

1 - Assembled outdoor unit.

General

Two-stage

Elite ®

SSB*H4 outdoor units use

HFC-410A refrigerant. This unit must be installed with a matching indoor coil and line set as outlined in the

Product Specification bulletin

(EHB)

.

Elite ®

SSB*H4 outdoor units are designed for use in expansion valve systems (TXV) only. They are not designed to be used with other refrigerant f l ow control devices. The

Product Specification bulletin lists a TXV kit that must be ordered separately.

Unit Dimensions - Inches (mm)

UNIT SUPPORT

FEET

D

K

E

J

F G H

BASE WITH ELONGATED LEGS

C

DISCHARGE AIR

B

LIQUID LINE

CONNECTION

ELECTRICAL

INLETS

SUCTION LINE

CONNECTION

A

2 (51)

4-1/4(1

08)

4-3/4

(121)

SIDE VIEW 1 (25) SIDE VIEW

Model

Number

A B C D E F G H

SSB036H4S4 31 (787) 30-1/2 (775)

SSB048H4S4 39 (991) 30-1/2 (775)

35 (889)

13-7/8 (352) 7-3/4 (197) 3-1/4 (83) 27-1/8 (689) 3-5/8 (92)

35 (889)

SSB060H4S4 45 (1143) 35-1/2 (902) 39-3/8 (1001) 16-7/8 (429) 8-3/4 (222) 3-1/8 (79) 30-3/4 (781) 4-5/8 (117)

J

4-1/2 (114)

3-3/4 (95)

K

20-5/8 (524)

26-7/8 (683)

Model Number Identification

S =

Brand/Family

Elite ®

Product Line

Unit Type

S = Air Conditioner Outdoor Unit

S S B 036 H 4 S 4 1 Y

Voltage

Y = 208/230V‐3 phase‐60hz

G = 460V‐3 phase‐60hz

Minor Design Sequence

1 = 1st Revision

2 = 2nd Revision

3 = 3rd Revision

Coil type

4 = Four-sided

Major Design Sequence

A = 1st Generation

B = 2nd Generation

Nominal Cooling Capacity -

Tons

036 = 3 Tons

048 = 4 Tons

060 = 5 Tons

Cooling Efficiency

H = High Efficiency

Part Load Capability

S = Part load capabilities with multi-stage operation.

Refrigerant Type

4 = HFC-410A

Page 2

Typical Unit Parts Arrangement

CONTROL PANEL

CRANKCASE HEATER RELAY

(K-191) (G-VOLTAGE UNITS

ONLY)

DUAL RUN CAPACITOR

(C12)

THREE POLE CONTACTOR (K1)

GROUND)

PLUMBING, SWITCHES AND ELECTRICAL COMPONENTS

COMPRESSOR

COMPRESSOR

HARNESS

CRANKCASE

THERMOSTAT

(S40)

LIQUID LINE FILTER

DRIER (SINGLE FLOW)

LIQUID LINE SERVICE

VALVE

FIELD CONNECTION

FOR LIQUID LINE SET

Figure 1. Typical Parts Arrangements

Page 3

CRANKCASE HEATER

(HR1)

HIGH PRESSURE SWITCH

(MANUAL RESET) (S4)

LOW PRESSURE

SWITCH (S87)

SUCTION LINE

SERVICE VALVE

FIELD CONNECTION

FOR SUCTION LINE

SSB*H4 SERIES

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single‐pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

CAUTION

Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.

Operating Gauge Set and Service Valves

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.

TORQUE REQUIREMENTS

When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are

appropriately tightened. Table 1 lists torque values for

fasteners.

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc -

Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.

Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an

Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.

See the Lennox Service and Application Notes #C-08-1 for further details and information.

IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.

Table 1. Torque Requirements

Parts

Service valve cap

Recommended Torque

8 ft.- lb.

11 NM

Sheet metal screws 16 in.- lb.

Machine screws #10 28 in.- lb.

2 NM

3 NM

Compressor bolts 90 in.- lb.

Gauge port seal cap 8 ft.- lb.

10 NM

11 NM

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings.

Manifold gauge set used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 psig on the high side and a low side of 30” vacuum to 250 psig with dampened speed to

500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.

Each valve is equipped with a service port which has a

factory-installed valve stem. Figure 2 provides information

on how to access and operating both angle and ball service valves.

Page 4

Operating Angle-Type Service Valve:

1. Remove stem cap with an appropriately sized wrench.

2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.

SERVICE PORT CAP

SERVICE PORT CORE

TO INDOOR

UNIT (VALVE STEM SHOWN OPEN)

INSERT HEX WRENCH HERE

(VALVE STEM SHOWN

CLOSED) INSERT HEX

WRENCH HERE

SERVICE PORT

CORE

STEM CAP

TO OUTDOOR UNIT

ANGLE-TYPE SERVICE VALVE

(BACK-SEATED / OPENED)

When service valve is OPEN , the service port is open to line set, indoor and outdoor unit.

ANGLE-TYPE SERVICE VALVE

(FRONT-SEATED / CLOSED)

WHEN SERVICE VALVE IS

CLOSED

, THE SERVICE PORT IS OPEN

TO THE LINE SET AND INDOOR UNIT.

Operating Ball-Type Service Valve:

1. Remove stem cap with an appropriately sized wrench.

2. To open valve, use a wrench to rotate stem counterclockwise

90°. To close, rotate stem clockwise 90°.

TO OPEN ROTATE STEM

COUNTERCLOCKWISE 90°.

TO CLOSE ROTATE STEM

CLOCKWISE 90°.

SERVICE PORT

SERVICE PORT

CORE

SERVICE PORT

CAP

TO OUTDOOR

UNIT

TO INDOOR UNIT

BALL (SHOWN

CLOSED)

VALVE

STEM

STEM CAP

To Access Service Port:

A service port cap protects the service port core from contamination and serves as the primary leak seal.

1. Remove service port cap with an appropriately sized wrench.

2. Connect gauge set to service port.

3. When testing is completed, replace service port cap and tighten as follows:

1/6 TURN

With torque wrench: Finger tighten and

torque cap per table 1.

Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.

Reinstall Stem Cap:

10

11 12

9

8

7

6

1

5

2

4

3

Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:

1/12 TURN

With torque wrench: Finger tighten and

then torque cap per table 1.

Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.

9

10

8

11 12

7

6

1

5

2

4

3

NOTE - A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.

Figure 2. Angle and Ball-Type Service Valves

Page 5

SSB*H4 SERIES

Recovering Refrigerant from Existing System

1 DISCONNECT POWER

Disconnect all power to the existing outdoor unit at the disconnect switch or main fuse box/breaker panel.

2 CONNECT MANIFOLD GAUGE SET

Connect a gauge set, clean recovery cylinder and a recovery machine to the service ports of the existing unit. Use the instructions provided with the recovery machine to make the connections.

MAIN FUSE BOX/BREAKER PANEL

MAIN FUSE

BOX/BREAKER

PANEL

DISCONNECT

SWITCH

RECOVERY MACHINE

MANIFOLD GAUGES

LOW HIGH

OUTDOOR UNIT CLEAN RECOVERY

CYLINDER

RECOVER REFRIGERANT 3

Remove existing HCFC-22 refrigerant using one of the following procedures:

IMPORTANT - Some system configurations may contain higher than normal refrigerant charge due to either large internal coil volumes, and/or long line sets.

METHOD 1:

Us this method if the existing outdoor unit is not equipped with shut-off valves, or if the unit is not operational and you plan to use the existing

HCFC-22 to flush the system.

Remove all HCFC-22 refrigerant from the existing system. Check gauges after shutdown to confirm that the system is completely void of refriger­ ant.

METHOD 2:

Use this method if the existing outdoor unit is equipped with manual shut-off valves, and you plan to use new HCFC-22 refrigerant to flush the system.

The following devices could prevent full system charge recovery into the outdoor unit:

Outdoor unit's high or low-pressure switches (if applicable), when tripped, can cycle the compressor OFF .

Compressor can stop pumping due to tripped internal pressure relief valve.

Compressor has internal vacuum protection that is designed to unload the scrolls (compressor stops pumping) when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig. (Compressor suction pressures should never be allowed to go into a vacuum.

Prolonged operation at low suction pressures will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seals.)

Once the compressor cannot pump down to a lower pressure due to one of the above system conditions, shut off the vapor valve. Turn OFF the main power to unit and use a recovery machine to recover any refrigerant left in the indoor coil and line set.

Perform the following task:

A Start the existing HCFC-22 system in the cooling mode and close the liquid line valve.

B Use the compressor to pump as much of the existing HCFC-22 refrigerant into the outdoor unit until the outdoor system is full. Turn the outdoor unit main power OFF and use a recovery machine to remove the remaining refrigerant from the system.

Note - It may be necessary to bypass the low pressure switches (if equipped) to ensure complete refrigerant evacuation.

C When the low side system pressures reach 0 psig, close the vapor line valve.

D Check gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system.

Figure 3. Recovering Refrigerant

Page 6

CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)

6 (152)

12 (305)

36 (914)

ACCESS PANEL

CONTROL PANEL

ACCESS

LOCATION

30 (762)

NOTES:

Clearance to one of the other three sides must be 36 inches (914mm).

Clearance to one of the remaining two sides may be 12 inches

(305mm) and the final side may be

6 inches (152mm).

LINE SET

CONNECTIONS

MINIMUM CLEARANCE

ABOVE UNIT

48 (1219)

MINIMUM CLEARANCE BETWEEN

TWO UNITS

24 (610)

New Unit Placement

Figure 4. Installation Clearances

NOTE - If necessary for stability, anchor unit to slab as illustrated in

figure 5, detail D.

CAUTION

In order to avoid injury, take proper precaution when lifting heavy objects.

See Unit Dimensions on page 3 for sizing mounting slab,

platforms or supports. Refer to figure 4 for mandatory

installation clearance requirements.

POSITIONING CONSIDERATIONS

Consider the following when positioning the unit:

Some localities are adopting sound ordinances based on the unit's sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.

When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation

to a window see the provided illustration in figure 5,

detail A.

PLACING UNIT ON SLAB

When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab

should have a slope tolerance as described in figure 5,

detail B.

IMPORTANT

To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.

ELEVATING THE UNIT

Units are outfitted with elongated support feet as illustrated

in figure 5, detail C.

If additional elevation is necessary, raise the unit by extending the height of the unit support feet. This may be achieved by using a 2 inch (50.8mm) Schedule 40 female threaded adapter.

The specified coupling will fit snuggly into the recessed portion of the feet. Use additional 2 inch (50.8mm)

Schedule 40 male threaded adaptors which can be threaded into the female threaded adaptors to make additional adjustments to the level of the unit.

NOTE - Keep the height of extenders short enough to ensure a sturdy installation. If it is necessary to extend further, consider a different type of field-fabricated framework that is sturdy enough for greater heights.

Page 7

SSB*H4 SERIES

DETAIL A

— Outside Unit Placement

Install unit away from windows.

DETAIL B

— Slab Mounting at Ground Level

Install unit level or, if on a slope, maintain slope tolerance of two (2) degrees (or two inches per five feet [50 mm per 1.5 m]) away from building structure.

BUILDING

STRUCTURE

MOUNTING

SLAB

GROUND LEVEL TWO 90° ELBOWS INSTALLED IN LINE SET WILL

REDUCE LINE SET VIBRATION.

DETAIL C

— Elevated Slab Mounting using Feet Extenders

STABILIZING UNIT ON UNEVEN SURFACES

DETAIL D

— Slab Side Mounting

#10 1/2” LONG SELF-DRILLING

SHEET METAL SCREWS

STABILIZING BRACKET (18 GAUGE

METAL — 2” WIDTH; HEIGHT AS

REQUIRED)

COIL

BASE PAN

BASE

#10 1-1/4” LONG HEX HD SCREW

AND FLAT WASHER

CORNER POST

Concrete slab — use two plastic anchors (hole drill 1/4”)

Wood or plastic slab — no plastic an­ chor (hole drill 1/8”)

DETAIL E

— Deck Top Mounting

Stabilizing bracket (18 gauge metal — 2” (50.8mm) width; height as required); bend to form right angle as exampled below.

MINIMUM ONE

PER SIDE

LEG DETAIL

2” (50.8MM) SCH 40

FEMALE THREADED

ADAPTER

2” (50.8MM) SCH 40

MALE THREADED

ADAPTER SAME FASTENERS AS

SLAB SIDE MOUNTING.

FOR EXTRA

STABILITY

Use additional 2” SCH 40 male threaded adapters which can be threaded into the female threaded adapters to make additional adjustments to the level of the unit.

One bracket per side (minimum). For extra stability, two brackets per side, two inches

(51mm) from each corner.

IMPORTANT - To help stabilize an outdoor unit, some installations may require strapping the unit to the pad using brackets and anchors commonly available in the marketplace.

Figure 5. Placement, Slab Mounting and Stabilizing Unit

Page 8

ROOF MOUNTING

Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.

NOTICE

Roof Damage!

This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.

Removing and Installing Panels

IMPORTANT

Do not allow panels to hang on unit by top tab. Tab is for alignment and not designed to support weight of panel.

WARNING

To prevent personal injury, or damage to panels, unit or structure, be sure to observe the following:

While installing or servicing this unit, carefully stow all removed panels out of the way, so that the panels will not cause injury to personnel, nor cause damage to objects or structures nearby, nor will the panels be subjected to damage (e.g., being bent or scratched).

While handling or stowing the panels, consider any weather conditions, especially windy conditions, that may cause panels to be blown around and battered.

LOUVERED PANEL REMOVAL

Remove the louvered panels as follows:

1.

Remove two screws, allowing the panel to swing open slightly.

2.

Hold the panel firmly throughout this procedure. Rotate bottom corner of panel away from hinged corner post until lower three tabs clear the slots as illustrated in detail B.

3.

Move panel down until lip of upper tab clears the top slot in corner post as illustrated in detail A .

IMPORTANT! DO NOT ALLOW PANELS TO HANG ON UNIT BY TOP TAB. TAB IS FOR

ALIGNMENT AND NOT DESIGNED TO SUPPORT WEIGHT OF PANEL.

PANEL SHOWN SLIGHTLY ROTATED TO ALLOW TOP TAB TO EXIT (OR

ENTER) TOP SLOT FOR REMOVING (OR INSTALLING) PANEL.

LIP

SCREW

HOLES

LOUVERED PANEL INSTALLATION

Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible. Then, in a continuous motion:

1. Slightly rotate and guide the lip of top tab inward as illustrated in detail A and

C ; then upward into the top slot of the hinge corner post.

2. Rotate panel to vertical to fully engage all tabs.

3. Holding the panel's hinged side firmly in place, close the right-hand side of the panel, aligning the screw holes.

4. When panel is correctly positioned and aligned, insert the screws and tighten .

DETAIL A

DETAIL B

Detail C

MAINTAIN MINIMUM PANEL ANGLE (AS CLOSE TO PARALLEL

WITH THE UNIT AS POSSIBLE) WHILE INSTALLING PANEL.

ANGLE MAY BE TOO

EXTREME

PREFERRED ANGLE

FOR INSTALLATION

HOLD DOOR FIRMLY TO THE HINGED

SIDE TO MAINTAIN

FULLY-ENGAGED TABS

ROTATE IN THIS DIRECTION;

THEN DOWN TO REMOVE

PANEL

Figure 6. Removing and Installing Panels

Page 9

SSB*H4 SERIES

New or Replacement Line Set

REFRIGERANT LINE SET

This section provides information on installation or replacement of existing line set. If new or replacement line set is not being installed then proceed to Brazing

Connections

on page 12.

NOTE - When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and

Fabrication Guidelines, CORP. 9351-L9, or contact

Lennox Technical Support Product Applications for assistance.

IMPORTANT

Lennox highly recommends changing line set when converting the existing system from HCFC-22 to

HFC-410A .

If that is not possible and the line set is the proper size as reference in table 2, use the procedure outlined under Flushing the System on page 13.

If refrigerant lines are routed through a wall, then seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and

subsequent sounds. See figure 7 for recommended

installation practices. Also, consider the following when placing and installing a high-efficiency outdoor unit.

To obtain the correct information from Lennox, be sure to communicate the following information:

Model SSB*H4 and size of unit (e.g. -036).

Line set diameters for the unit being installed as listed

in table 2 and total length of piping.

Number of elbows vertical rise or drop in the piping.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds - add one ounce of oil for every five pounds of refrigerant.

Recommended topping-off POE oils are Mobil EAL

ARCTIC 22 CC or ICI EMKARATE RL32CF.

Liquid lines that meter the refrigerant, such as RFC1 liquid lines, must not be used in this application. Existing line set

of proper size as listed in table 2 may be reused. If system

was previously charged with HCFC-22 refrigerant, then existing line set must be flushed (see Flushing Line Set and Indoor Coil

on page15).

WARNING

Polyol Ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.

Field refrigerant piping consists of liquid and vapor lines from the outdoor unit to the indoor unit coil (braze connections). Use Lennox L15 (sweat, non-flare) series line set or field-fabricated refrigerant line sizes as listed in

table 2.

IMPORTANT

Mineral oils are not compatible with HFC-410A .

If oil must be added, it must be a Polyol Ester oil.

Table 2. Refrigerant Line Set — Inches (mm)

Model Number

Field Connections

Liquid Line Vapor Line

Recommended Line Set

Vapor Line L15 Line Sets Liquid Line

SSB036H4S4

3/8 in. (10 mm) 7/8 in. (22 mm) 3/8 in. (10 mm) 7/8 in (22 mm) L15-65 — 15 ft. - 50 ft. (4.6 m - 15 m)

SSB048H4S4

1-1/8 in. (29 mm) Field Fabricated SSB060H4S4 3/8 in. (10 mm) 1-1/8 in. (29 mm) 3/8 in. (10 mm)

NOTE - Some applications may required a field provided 7/8” to 1-1/8” adapter

Page 10

Line Set Isolation — The following illustrations are examples of proper refrigerant line set isolation:

REFRIGERANT LINE SET — TRANSITION

FROM VERTICAL TO HORIZONTAL

ANCHORED HEAVY NYLON

WIRE TIE OR AUTOMOTIVE

MUFFLER‐TYPE HANGER

AUTOMOTIVE

MUFFLER‐TYPE HANGER

REFRIGERANT LINE SET — INSTALLING

VERTICAL RUNS (NEW CONSTRUCTION SHOWN)

NOTE - Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig .

OUTSIDE WALL

LIQUID LINE

VAPOR LINE

WALL

STUD

STRAP LIQUID LINE TO

VAPOR LINE

LIQUID LINE

NON-CORROSIVE

METAL SLEEVE

VAPOR LINE - WRAPPED

IN ARMAFLEX

WOOD BLOCK

BETWEEN STUDS

WIRE TIE

INSIDE WALL

STRAP

NON-CORROSIVE

METAL SLEEVE

WIRE TIE

WOOD BLOCK

WIRE TIE

STRAP

REFRIGERANT LINE SET — INSTALLING

HORIZONTAL RUNS

To hang line set from joist or rafter, use either metal strapping material or anchored heavy nylon wire ties.

WIRE TIE (AROUND

VAPOR LINE ONLY)

8 FEET (2.43 METERS)

STRAPPING

MATERIAL (AROUND

VAPOR LINE ONLY)

FLOOR JOIST OR

ROOF RAFTER

TAPE OR

WIRE TIE

8 FEET (2.43 METERS)

TAPE OR

WIRE TIE

NON-CORROSIVE

METAL SLEEVE

STRAP THE VAPOR LINE TO THE JOIST

OR RAFTER AT 8 FEET (2.43 METERS)

INTERVALS THEN STRAP THE LIQUID

LINE TO THE VAPOR LINE.

FLOOR JOIST OR

ROOF RAFTER

SLEEVE

VAPOR LINE WRAPPED

WITH ARMAFLEX

OUTSIDE

WALL

LIQUID

LINE

PVC

PIPE

FIBERGLASS

INSULATION

CAULK

NOTE Similar installation practices should be used if line set is to be installed on exterior of outside wall.

Figure 7. Line Set Installation

Page 11

SSB*H4 SERIES

Brazing Connections

Use the procedures outline in figures 8 and 9 for brazing

line set connections to service valves.

WARNING

Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture - Check the high and low pressures before applying heat.

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

CAUTION

Brazing alloys and flux contain materials which are hazardous to your health.

Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.

Wear gloves and protective goggles or face shield to protect against burns.

Wash hands with soap and water after handling brazing alloys and flux.

IMPORTANT

Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.

IMPORTANT

Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.

IMPORTANT

Use silver alloy brazing rods with 5% minimum silver alloy for copper-to-copper brazing. Use 45% minimum alloy for copper-to-brass and copper-to-steel brazing.

WARNING

Fire, Explosion and Personal Safety Haz­ ard.

Failure to follow this warning could result in damage, personal injury or death.

Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when ex­ posed to a spark or open flame, can cause fire and/or an explosion, that could result in property damage, personal inju­ ry or death.

Page 12

1 CUT AND DEBUR

Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.

2 CAP AND CORE REMOVAL

Remove service cap and core from both the vapor and liquid line service ports.

CUT AND DEBUR

SERVICE PORT

CAP

LINE SET SIZE MATCHES

SERVICE VALVE CONNECTION

COPPER TUBE

STUB

SERVICE VALVE

CONNECTION

REDUCER

SERVICE

PORT

CORE

LIQUID LINE SERVICE

VALVE

SERVICE

PORT

CORE

SERVICE

PORT CAP

SUCTION / VAPOR LINE

SERVICE VALVE

LINE SET SIZE IS SMALLER

THAN CONNECTION

REFRIGERANT LINE

DO NOT CRIMP SERVICE VALVE

CONNECTOR WHEN PIPE IS

SMALLER THAN CONNECTION

3 ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE

VALVES

Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.

A Connect gauge set low pressure side to liquid line service valve (service port).

USE REGULATOR TO FLOW

NITROGEN AT 1 TO 2 PSIG.

B Connect gauge set center port to bottle of nitrogen with regulator.

LOW HIGH

C Remove Schrader valve in suction / vapor line service port to allow nitrogen to escape.

ATTACH

GAUGES

SUCTION / VAPOR SERVICE PORT MUST BE

OPEN TO ALLOW EXIT POINT FOR NITROGEN

C

INDOOR

UNIT

VAPOR LINE

LIQUID LINE

B

SUCTION /

VAPOR LINE

SERVICE

VALVE

OUTDOOR

UNIT

LIQUID LINE SERVICE

VALVE

A

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

NITROGEN

Figure 8. Brazing Procedures

Page 13

SSB*H4 SERIES

4 WRAP SERVICE VALVES

To help protect service valve seals during brazing, wrap a saturated cloth around service valve bodies and copper tube stub. Use another saturated cloth underneath the valve body to protect the base paint.

5 FLOW NITROGEN

Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections

6 BRAZE LINE SET

Wrap both service valves with a saturated cloth as illustrated here before brazing to line set.

LIQUID LINE SERVICE VALVE

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

IMPORTANT - Allow braze joint to cool. Apply additional saturated cloths to help cool brazed joint. Do not remove wet rag until piping has cooled. Temperatures above 250ºF will damage valve seals.

WARNING

1.

FIRE, PERSONAL INJURY, OR PROPERTY

DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.

2. Do not open service valves until refrigerant lines and indoor coil have been leak-tested and evacuated.

Refer to procedures provided in this supplement.

SATURATED CLOTH

LIQUID LINE

SUCTION / VAPOR LINE

SERVICE VALVE

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

SUCTION / VAPOR LINE

SATURATED CLOTH

7 PREPARATION FOR NEXT STEP

After all connections have been brazed, disconnect manifold gauge set from service ports. Apply saturated rags to both services valves to cool piping. Once piping is cool, remove all wet cloths. Refer to the unit installation instructions for the next step in preparing the unit.

Figure 9. Brazing Procedures (continued)

Page 14

Flushing Line Set and Indoor Coil

1A TYPICAL EXISTING FIXED ORIFICE

REMOVAL PROCEDURE (UNCASED

COIL SHOWN)

DISTRIBUTOR TUBES

LIQUID LINE ORIFICE HOUSING

OR

1B TYPICAL EXISTING EXPANSION VALVE REMOVAL

PROCEDURE (UNCASED COIL SHOWN)

STUB END

TWO PIECE PATCH PLATE

LIQUID LINE EXPANSION

(UNCASED COIL ONLY)

ORIFICE

VALVE

HOUSING

DISTRIBUTOR

TUBES

TEFLON

®

RING TEFLON

®

RING

FIXED ORIFICE

BRASS NUT

TEFLON®

RING

SENSING

LINE

DISTRIBUTOR

ASSEMBLY DISTRIBUTOR

ASSEMBLY

EQUALIZER

LINE REMOVE AND DISCARD

WHITE TEFLON

®

SEAL

(IF PRESENT) LIQUID LINE ASSEMBLY

(INCLUDES STRAINER) LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A On fully cased coils, remove the coil access and plumbing panels.

B Remove any shipping clamps holding the liquid line and distributor as­ sembly.

C Using two wrenches, disconnect liquid line from liquid line orifice hous­ ing. Take care not to twist or damage distributor tubes during this pro­ cess.

D Remove and discard fixed orifice, valve stem assembly if present and

Teflon ® washer as illustrated above.

E Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing.

2

CONNECT GAUGES AND EQUIPMENT FOR

FLUSHING PROCEDURE

A

INVERTED HCFC-22

CYLINDER CONTAINS

CLEAN HCFC-22 TO BE

USED FOR FLUSHING.

1

LOW

GAUGE

MANIFOLD

HIGH

MALE EQUALIZER

LINE FITTING

SENSING BULB

VAPOR

LINE

LIQUID

LINE

A On fully cased coils, remove the coil access and plumbing panels.

B Remove any shipping clamps holding the liquid line and distributor assembly.

C Disconnect the equalizer line from the expansion valve equalizer line fitting on the vapor line.

D Remove the vapor line sensing bulb.

E Disconnect the liquid line from the expansion valve at the liquid line assembly.

F Disconnect the expansion valve from the liquid line orifice housing.

Take care not to twist or damage distributor tubes during this process.

G Remove and discard expansion valve and the two Teflon ® rings.

H Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing.

VAPOR LINE

SERVICE VALVE

EXISTING

INDOOR

UNIT

LIQUID LINE SERVICE

VALVE

RECOVERY

CYLINDER

D

B

NEW

OUTDOOR

UNIT

C

OPENED

TANK

RETURN

INLET

DISCHARGE

CLOSED

RECOVERY MACHINE

A Inverted HCFC-22 cylinder with clean refrigerant to the vapor service valve.

B HCFC-22 gauge set (low side) to the liquid line valve.

C HCFC-22 gauge set center port to inlet on the recovery machine with an empty recovery tank to the gauge set.

D Connect recovery tank to recovery machines per machine instructions.

3 FLUSHING LINE SET

The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.

A Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the

B set and indoor unit coil.

B Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.

C After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.

D Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.

Figure 10. Installing Indoor Expansion Valve

Page 15

SSB*H4 SERIES

Installing Indoor Metering Device

This outdoor unit is designed for use in systems that use a expansion valve metering device at the indoor coil.

See the Lennox SSB*H4 Product Specification bulletin for approved expansion valve kit match-ups. The expansion valve unit can be installed either internal or external to the

INDOOR EXPANSION VALVE INSTALLATION

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

DISTRIBUTOR

TUBES

(Uncased Coil Shown)

LIQUID LINE

ORIFICE

HOUSING

STUB

END

EXPANSION

VALVE

TEFLON

®

RING

DISTRIBUTOR

ASSEMBLY

TEFLON

®

RING

EQUALIZER

LINE

SENSING

LINE indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit.

1/2 Turn

C Install one of the provided Teflon ® rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ® ring with refrigerant oil.

D Attach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or tighten to

20 ft-lb.

E Place the remaining Teflon ® washer around the other end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ® ring with refrigerant oil.

F Attach the liquid line assembly to the expansion valve.

Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft-lb.

9

8

10

11 12

7

6

1

2

3

4

5

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

SENSING BULB INSTALLATION

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR

FURTHER DETAILS)

VAPOR

LINE

Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.

LIQUID LINE

A Attach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided.

NOTE Confirm proper thermal contact between vapor line and expansion valve sensing bulb before insulating the sensing bulb once installed.

B Connect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.

1/8 Turn

10

11 12

9

8

7

6

1

2

4

3

5

9 O'CLOCK TO

3 O'CLOCK

EQUALIZER LINE INSTALLATION

A Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.

B Remove the field-provided fitting that temporarily recon­ nected the liquid line to the indoor unit's distributor assem­ bly

BULB

12

BULB

ON LINES SMALLER THAN

7/8”, MOUNT SENSING

BULB BETWEEN THE 9 AND

3 O'CLOCK POSITIONS.

FLARE SEAL CAP FLARE NUT

VAPOR LINE

VAPOR LINE

OR COPPER FLARE

SEAL BONNET

12

ON 7/8” AND LARGER LINES,

MOUNT SENSING BULB AT

EITHER THE 4 OR 8 O'CLOCK

POSITION. NEVER MOUNT

THE SENSING BULB ON

BOTTOM OF LINE.

MALE BRASS EQUALIZER

LINE FITTING

BULB

BULB

VAPOR LINE NOTE - NEVER MOUNT THE SENSING BULB ON

BOTTOM OF LINE.

Figure 11. Installing Indoor Expansion Valve

Page 16

IMPORTANT

The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance.

Approved methods of recovery, recycling or reclaiming must be followed.

IMPORTANT

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant. Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

1 CONNECT GAUGE SET

A Connect an HFC-410A manifold gauge set high pressure hose to the vapor valve service port.

NOTE Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.

B With both manifold valves closed, connect the cylinder of

HFC-410A refrigerant to the center port of the manifold gauge set.

NOTE - Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.

Leak Test Line Set and Indoor Coil

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

IMPORTANT

Leak detector must be capable of sensing HFC refrigerant.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.

Failure to follow this warning may result in personal injury or death.

B

LOW HIGH

MANIFOLD GAUGE SET

A

OUTDOOR UNIT

TO VAPOR

SERVICE VALVE

2

NITROGEN

HFC-410A

TEST FOR LEAKS

After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:

A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).

B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A.

[A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.

C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.

E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector .

F After leak testing disconnect gauges from service ports.

Figure 12. Leak Test

Page 17

SSB*H4 SERIES

Evacuating Line Set and Indoor Coil

1 CONNECT GAUGE SET

NOTE Remove cores from service valves (if not already done).

A Connect low side of manifold gauge set with 1/4 SAE in-line tee to vapor line service valve

B Connect high side of manifold gauge set to liquid line service valve

C Connect micron gauge available connector on the 1/4 SAE in-line tee.

D Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the

HFC-410A and nitrogen containers.

OUTDOOR

UNIT

A

NITROGEN

A34000 1/4 SAE TEE WITH

SWIVEL COUPLER

500

C

MICRON

GAUGE

MANIFOLD

GAUGE SET

TO VAPOR

SERVICE VALVE

LOW HIGH

HFC-410A

B

VACUUM PUMP

TO LIQUID LINE

SERVICE VALVE

D

2 EVACUATE THE SYSTEM

A Open both manifold valves and start the vacuum pump.

B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).

RECOMMEND

MINIMUM 3/8” HOSE

NOTE During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure .

NOTE The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:

Close manifold gauge valves

Close valve on vacuum pump

Turn off vacuum pump

Disconnect manifold gauge center port hose from vacuum pump

Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.

Open manifold gauge valves to break the vacuum in the line set and indoor unit.

Close manifold gauge valves.

D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.

E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.

F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.

G Perform the following:

Close manifold gauge valves.

1/6 TURN

Shut off HFC-410A cylinder.

Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure.

Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.

9

10

8

11 12

7

6

1

5

2

4

3

Figure 13. Evacuating System

Page 18

IMPORTANT

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.

WARNING

Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.

Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are defined as any gas that will not condense under temperatures and pressures present during operation of

1 SIZE CIRCUIT AND INSTALL DISCONNECT

SWITCH

Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.

MAIN FUSE

BOX/BREAKER

PANEL

DISCONNECT

SWITCH an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.

Electrical

In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current

Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.

24VAC TRANSFORMER

Use the transformer provided with the furnace or air handler for low‐voltage control power (24VAC - 40 VA minimum)

INSTALL THERMOSTAT 2

Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet

(1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.

THERMOSTAT

5 FEET

(1.5M)

NOTE - Units are approved for use only with copper conductors.

Ground unit at disconnect switch or to an earth ground.

3

UNIT LOW VOLTAGE CONNECTIONS

C

WIRE NUTS

A

CUTOUT WITH

GROMMET

24V CONTROL WIRES

B

NOTE - 24VAC, Class II circuit connections are made in the control panel.

HIGH VOLTAGE FIELD WIRING

FACTORY WIRING

LOW VOLTAGE (24V) FIELD WIRING

WIRE RUN LENGTH

LESS THAN 100' (30 METERS)

MORE THAN 100' (30 METERS)

AWG# INSULATION TYPE

18 TEMPERATURE RATING

16 35ºC MINIMUM.

A Run 24VAC control wires through cutout with grommet.

B Run 24VAC control wires through wire tie.

C Make 24VAC control wire connections using field provided wire nuts.

D Tighten wire tie to security 24V control wiring.

NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES)

GAUGE PER TABLE ABOVE.

NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND TO MAINTAIN

SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.

NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL

BOX.

D

TIGHTEN WIRE TIE

Page 19

SSB*H4 SERIES

Figure 14. Typical Wiring Diagram (Y-Voltage)

Figure 15. SSB*H4 Typical Factory Diagram (Y-Voltage)

Page 20

Figure 16. SSB*H4 Typical Wiring Diagram (G-Voltage)

Servicing Units Delivered Void of Charge

If the outdoor unit is void of refrigerant, clean the system using the procedure described below.

1. Leak check system using procedure outlined on page

17.

Figure 17. SSB*H4 Typical Factory Diagram (G-Voltage)

2. Evacuate the system using procedure outlined on

page 18.

3. Use nitrogen to break the vacuum and install a new filter drier in the system.

4. Evacuate the system again using procedure outlined

on page 18.

Page 21

SSB*H4 SERIES

5. Weigh in refrigerant using procedure outlined in figure

21.

6. Monitor the system to determine the amount of moisture remaining in the oil. It may be necessary to replace the filter drier several times to achieve the required dryness level.

If system dryness is not verified, the compressor will fail in the future.

Unit Start-Up

IMPORTANT

If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

4. Replace the stem caps and tighten to the value listed

in table 1.

5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.

6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.

7. Recheck voltage while the unit is running. Power must be within range shown on the nameplate.

8. Check system for sufficient refrigerant by using the procedures listed under System Charge.

1. Rotate fan to check for binding.

System Refrigerant

2. Inspect all factory- and field-installed wiring for loose connections.

3. After evacuation is complete, open both the liquid and vapor line service valves to release the refrigerant charge contained in outdoor unit into the system.

This section outlines procedures for:

1. Connecting gauge set for testing and charging;

2. Checking and adjusting indoor airflow;

3. Adding or removing refrigerant.

GAUGE SET

CONNECTIONS FOR TESTING AND CHARGING

B

A Close manifold gauge set valves and connect the center hose to a cylinder of

SUCTION LINE

SERVICE PORT

CONNECTION

HFC-410A. Set for liquid phase charging.

REFRIGERANT TANK

B Connect the manifold gauge set's low pressure side to the suction line service port.

CHARGE IN

LIQUID PHASE

A

C Connect the manifold gauge set's high pressure side to the liquid line service port.

DIGITAL SCALE

D Position temperature sensor on liquid line near liquid line service port.

MANIFOLD GAUGE SET

LOW HIGH

OUTDOOR UNIT

VAPOR LINE

SERVICE VALVE

D

TEMPERATURE

SENSOR

C

TO LIQUID

LINE SERVICE

VALVE

TEMPERATURE SENSOR

(LIQUID LINE)

LIQUID LINE

SERVICE VALVE

Figure 18. Gauge Set Setup and Connections

Page 22

CHECKING AIR FLOW AT INDOOR COIL

Temp.

of air entering indoor coil ºF

A

D

T

80 24 24 24 23 23 22 22 22 20 19 18 17 16 15

78 23 23 23 22 22 21 21 20 19 18 17 16 15 14

76 22 22 22 21 21 20 19 19 18 17 16 15 14 13

74 21 21 21 20 19 19 18 17 16 16 15 14 13 12

72 20 20 19 18 17 17 16 15 15 14 13 12 11 10

70 19 19 18 18 17 17 16 15 15 14 13 12 11 10

Wet-bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70

C

53º

DRY

BULB

T

Drop

19º air flow

All temperatures are expressed in ºF

INDOOR

COIL

B air flow B

64º

WET

BULB

A

72º

DRY

BULB

1. Determine the desired

D

T —Measure entering air temperature using dry bulb ( A ) and wet bulb ( B ).

D

T is the intersecting value of

A and B in the table (see triangle).

2. Find temperature drop across coil —Measure the coil's dry bulb entering and leaving air temperatures ( A and C ). Temperature Drop

Formula: ( T

Drop

) = A minus C .

3. Determine if fan needs adjustment —If the difference between the measured T

Drop

and the desired

D

T (T

Drop

D

T) is within +3º, no adjustment is needed. See examples: Assume

D

T = 15 and A temp. = 72º, these C temperatures would necessitate stated ac­ tions:

Cº T

Drop

D

T

=

ºF ACTION

53º 19 – 15

=

4 Increase the airflow

58º

62º

14 – 15

=

-1 (within +3º range) no change

10 – 15

=

-5 Decrease the airflow

4. Adjust the fan speed —See indoor unit instructions to increase/de­ crease fan speed.

Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and

D

T are within +3º.

Figure 19. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart

START: Determine how refrigerant is metered

WHEN TO CHARGE?

Warm weather best

Can charge in colder weather

CHARGE METHOD?

Determine by:

Metering device type

Outdoor ambient temperature

REQUIREMENTS:

Sufficient heat load in structure

Indoor temperature between 70‐80ºF (21-26ºC)

Manifold gauge set connected to unit

Thermometers:

to measure outdoor ambient temperature

to measure liquid line temperature

to measure suction line temperature

64ºF (17.7ºC) and Below

WEIGH‐IN

TXV

65ºF (18.3ºC) and Above

APPROACH OR

SUBCOOLING

Figure 20. Determining Charge Method

WEIGH-IN

CHARGING METHOD FOR LONG LINE SETS

64ºF (17.7ºC) and Below

Amount specified on nameplate

Adjust amount for variation in line set length and liquid line diameter using table below.

+ =

Total charge

Liquid Line

Set Diameter

5/16”

3/8”

1/2”

HFC-410A

(ounces per foot)

0.40

0.60

1.00

NOTE - Insulate liquid line when it is routed through areas where the surrounding ambient temperature could become higher than the temperature of the liquid line or when pressure drop is equal to or greater than 20 psig.

NOTE - The above nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.

Charging Formula for Liquid Line Charge Adjustments

[(Line set oz./ft. x total length) ­ (factory charge for line set)] = charge adjustment

Example : Units are factory­charged for 15 feet (4.6 meters) of 3/8" line set.

Factory charge for 3/8" is 0.60 oz/ft x 15 = 9.0 ounces.

Figure 21. Using HFC-410A Weigh-In Method

Page 23

SSB*H4 SERIES

START: Measure outdoor ambient temperature 65ºF

(18.3ºC) and

Above

64ºF

(17.7ºC) and

APPROACH TXV

Below

ABOVE or

BELOW

Once refrigerant charge is correct, disconnect gauge set and replace service port caps.

1. Connect gauge set as illustrated in figure 18.

2. Confirm proper airflow across coil using figure

19.

3. Compare unit pressures with table 4,

Normal

Operating Pressures .

4. Set thermostat to call for heat (must have a cooling load between 70‐80ºF (21-26ºC).

5. When heat demand is satisfied, set thermostat to call for cooling.

6. Allow temperatures and pressures to stabilize.

7. Record outdoor ambient temperature:

AMBº =_________

8. Record liquid line temperature:

LIQº = __________

9. Subtract to determine approach (APPº):

LIQº_____ - AMBº _____ = APPº_____

10. Compare results with table below.

If refrigerant is added or removed, verify charge using the

Subcooling Method .

If value is MORE than shown, remove refrigerant.

If value is LESS than shown, add refrigerant.

MORE or

LESS

APPº (Approach) Values(F:+/-1.0° [C: +/-0.6°])

-036 -048 -060

TEMP* 6 (3.3) 8 (4.4) 4 (2.2)

*Temperature of air entering outdoor coil is 65ºF (18ºC) or above.

Figure 22. Using HFC-410A Approach (TXV) Charge Method

START: Measure outdoor ambient temperature

65ºF

(18.3ºC) and

Above

C

64ºF

(17.7ºC) and

Below

SUBCOOLING TXV

ABOVE or

BELOW

BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325-375 psig

(2240-2585 kPa).

Higher pressures are needed to check charge. Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.

Once refrigerant charge is correct, disconnect gauge set and replace service port caps.

CARDBOARD OR

PLASTIC SHEETS

If refrigerant is added or removed, verify charge using the Approach

Method .

If value is LESS than shown, add refrigerant.

If value is MORE than shown, remove refrigerant.

MORE or

LESS

1. Connect gauge set as illustrated in figure 18.

2. Confirm proper airflow across coil using figure 19.

3. Compare unit pressures with table 4,

Normal

Operating Pressures .

4. Set thermostat to call for heat (must have a cooling load between 70‐80ºF (21-26ºC)

5. Measure outdoor ambient temperature

6. When heat demand is satisfied, set thermostat to call for cooling

7. Allow temperatures and pressures to stabilize.

NOTE - If necessary, block outdoor coil to maintain

325 - 375 psig.

8. Record liquid line temperature:

LIQº = ______

9. Measure liquid line pressure and use the value to

determine saturation temperature (see table 3):

SATº = ______

10. Subtract to determine subcooling (SCº):

SATº_____ - LIQº _____ = SCº _____

11. Compare results with table below.

SCº (Subcooling) Values (F:+/-1.0° [C: +/-0.6°])

-036 -048 -060

TEMP* 6 (3.3) 6 (3.3) 9 (5.0)

*Temperature of air entering outdoor coil is 65ºF (18ºC) or above.

Figure 23. Using HFC-410A Subcooling (TXV) Charge Method

Page 24

Table 3. HFC-410A Temperature (°F) - Pressure (Psig)

°F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig °F Psig

42

43

44

45

46

39

40

41

32

33

34

35

36

37

38

47

58

59

60

61

62

55

56

57

48

49

50

51

52

53

54

115.8

118.0

120.3

122.6

125.0

127.3

129.7

132.2

100.8

102.9

105.0

107.1

109.2

111.4

113.6

134.6

155.5

158.2

161.0

163.9

166.7

169.6

172.6

175.4

137.1

139.6

142.2

144.8

147.4

150.1

152.8

73

74

75

76

77

70

71

72

63

64

65

66

67

68

69

78

89

90

91

92

93

86

87

88

79

80

81

82

83

84

85

200.6

203.9

207.2

210.6

214.0

217.4

220.9

224.4

178.5

181.6

184.3

187.7

190.9

194.1

197.3

228.0

258.0

262.0

266.0

270.0

274.1

278.2

282.3

286.5

231.6

235.3

239.0

242.7

246.5

250.3

254.1

101

102

103

104

105

106

107

108

94

95

96

97

98

99

100

109

321.8

326.4

331.0

335.7

340.5

345.3

350.1

355.0

290.8

295.1

299.4

303.8

308.2

312.7

317.2

360.0

117

118

119

120

121

122

123

124

110

111

112

113

114

115

116

401.3

406.7

412.2

417.7

423.2

428.8

434.5

440.2

365.0

370.0

375.1

380.2

385.4

390.7

396.0

132

133

134

135

136

137

138

139

125

126

127

128

129

130

131

140

487.8

494.0

500.2

506.5

512.9

519.3

525.8

532.4

445.9

451.8

457.6

463.5

469.5

475.6

481.6

539.0

148

149

150

151

152

153

154

155

141

142

143

144

145

146

147

593.8

601.0

608.1

615.4

622.7

630.1

637.5

645.0

545.6

552.3

559.1

565.9

572.8

579.8

586.8

Table 4. Normal Operating Pressures (Liquid +10 and Suction +5 psig)

IMPORTANT

Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.

Model

5 F ( 5 C)*

SSB036H4S4

Liquid Suction Liquid

SSB048H4S4

Suction Liquid

SSB060H4S4

Suction

65 (18)

75 (24)

85 (29)

95 (35)

105 (41)

115 (46)

217

251

292

337

387

440

141

143

146

147

150

154

First Stage (Low Capacity)

229

263

304

350

400

453

140

143

146

148

150

155

Second Stage (High Capacity)

229

264

305

349

402

455

65 (18)

75 (24)

85 (29)

95 (35)

230

265

307

354

137

140

141

144

234

269

312

359

135

137

140

141

244

282

324

371

129

131

133

136

105 (41)

115 (46)

405

460

146

149

409

465

143

146

422

474

*Temperature of air entering outdoor coil.

**(Liquid +10 psig; Vapor +5 psig) Typical pressures; indoor unit match up, indoor air quality equipment, and indoor load will cause the pressures to vary.

139

143

134

138

140

142

147

149

System Operation

SECOND-STAGE OPERATION

If the demand defrost control (A108) receives a call for second-stage compressor operation Y2 in heating or cooling mode and the first‐stage compressor output is active, the second‐stage compressor solenoid output will be energized.

If first‐stage compressor output is active in heating mode and the outdoor ambient temperature is below the selected compressor lock-in temperature, the second‐stage compressor solenoid output will be energized without the

Y2 input. If the jumper is not connected to one of the temperature selection pins on P3 (40, 45, 50, 55°F), the default lock-in temperature of 40°F (4.5°C) will be used.

IMPORTANT

Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig. A hissing sound will be heard when the compressor is running unloaded. Protector will reset when low pressure in system is raised above 40 psig. DO

NOT REPLACE COMPRESSOR.

Page 25

SSB*H4 SERIES

UNIT COMPONENTS

High Pressure Switch (S4)

This unit now employs a automatic pressure switch located on the liquid line of the compressor. The pressure switch (SPST, auto-reset, normally closed) removes power form the compressor when liquid pressure rises above factory setting (opens at 590 + 15 psig and closes at

418 + 15 psig).

Low Pressure Switch (S87)

SSB*H4 units are also equipped with a low pressure switch that is located in the vapor line of the compressor. The switch (SPST, auto-reset, normally closed) removes power from the compressor when vapor line pressure drops below factory setting at 40 + 5 psi.

Crankcase Heater Relay (K191)

(G Voltage Units Only)

All 460 volt SSB units require the S40 thermostat to be wired in series with the 24 volt coil of the K191 relay. The contacts of the K191 control operation of crankcase heater

HR1. When ambient temperature drops below 50° F, K191 contacts close energizing HR1. When the ambient temperature rises to 70° F the contacts open de-energizing HR1.

Crankcase Heater (HR1) and Crankcase Thermostat

(S40)

The reference models are equipped with a 70 watt, belly band type crankcase heater. HR1 prevents liquid from accumulating in the compressor. HR1 is controlled by a thermostat located on the liquid line. When liquid line temperature drops below 50° F the thermostat closes energizing HR1. The thermostat will open, de-energizing

HR1 once liquid line temperature reaches 70° F .

Internal Solenoid (L34)

The internal unloader solenoid controls the two-stage operation of the compressor by shifting a slide ring mechanism to open two by-pass ports in the first compression pocket of the scrolls in the compressor. The internal solenoid is activated by a 24 volt direct current solenoid coil. The coil power requires 20VAC. The internal wires from the solenoid in the compressor are routed to a 2 pin fusite connection on the side of the compressor shell.

The external electrical connection is made to the compressor with a molded plug assembly. This plug contains a full wave rectifier that converts 24 volt AC into

24 volt DC power to power the unloader solenoid. Refer to unit diagram for internal circuitry view of plug).

Liquid Line Bi-Flow Filter Drier

The unit is equipped with a large-capacity biflow filter drier which keeps the system clean and dry. If replacement is necessary, order another of like design and capacity. The replacement filter drier must be suitable for use with

HFC-410A refrigerant.

Maintenance

DEALER

Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:

Page 26

Outdoor Unit

1. Clean and inspect the outdoor coil. The coil may be flushed with a water hose. Ensure the power is turned off before you clean the coil.

2. Outdoor fan motor is prelubricated and sealed. No further lubrication is needed.

3. Visually inspect connecting lines and coils for evidence of oil leaks.

4. Check wiring for loose connections.

5. Check for correct voltage at the unit (with the unit operating).

6. Check amp-draw outdoor fan motor.

UNIT NAMEPLATE: _________ ACTUAL: __________

NOTE - If owner reports insufficient cooling, the unit should be gauged and refrigerant charge checked.

Outdoor Coil

It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)

Outdoor Coil — The outdoor coil may be flushed with a water hose.

Outdoor Coil (Sea Coast) — Moist air in ocean locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil. Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.

INDOOR UNIT

1. Clean or change filters.

2. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM.

Refer to the unit information service manual for pressure drop tables and procedure.

3. Check blower drive belt for wear and proper tension.

4. Check all wiring for loose connections

5. Check for correct voltage at unit (blower operating).

6. Check amp-draw on blower motor.

UNIT NAMEPLATE: _________ ACTUAL: __________

INDOOR COIL

1. Clean coil, if necessary.

2. Check connecting lines and coils for signs of oil leaks.

3. Check condensate line and clean, if necessary.

OWNER

Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.

IMPORTANT

Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.

Outdoor Coil

The outdoor unit must be properly maintained to ensure its proper operation.

Please contact your dealer to schedule proper inspection and maintenance for your equipment.

Make sure no obstructions restrict airflow to the outdoor unit.

Grass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy.

Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.

Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit.

Routine Maintenance

In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.

1.

Air Filter — Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.

Checklists

Use the following checklist to verify part‐load and full‐load capacity operation of two‐stage modulation compressors.

TOOLS REQUIRED

Refrigeration gauge set

Digital volt/amp meter

Electronic temperature thermometer

On‐off toggle switch

2.

Disposable Filter — Disposable filters should be replaced with a filter of the same type and size.

NOTE - If you are unsure about the filter required for your system, call your Lennox dealer for assistance.

3.

Reusable Filter — Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.

NOTE - The filter and all access panels must be in place any time the unit is in operation.

4.

Indoor Unit — The indoor unit's evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)

Thermostat Operation

See the thermostat homeowner manual for instructions on how to operate your thermostat.

Preservice Check

If your system fails to operate, check the following before calling for service:

Verify room thermostat settings are correct.

Verify that all electrical disconnect switches are ON.

Check for any blown fuses or tripped circuit breakers.

Verify unit access panels are in place.

Verify air filter is clean.

If service is needed, locate and write down the unit model number and have it handy before calling.

Accessories

For update-to-date information, see any of the following publications:

Lennox SSB*H4 Product Specification bulletin

Lennox Product Catalog

Lennox Price Book

IMPORTANT

This performance check is ONLY valid on systems that have clean indoor and outdoor coils, proper airflow over coils, and correct system refrigerant charge. All components in the system must be functioning properly to correctly perform compressor operational check.

(Accurate measurements are critical to this test as indoor system loading and outdoor ambient can affect variations between low and high capacity readings).

Page 27

SSB*H4 SERIES

Two-Stage Modulation Compressors Field Operational Checklist

Y1 - First‐Stage

Expected results during Y2 demand

(Toggle switch On) Unit Readings

COMPRESSOR

Voltage

Amperage

OUTDOOR UNIT FAN MOTOR

Amperage

TEMPERATURE

Ambient

Outdoor Coil Discharge Air

Compressor Discharge Line

Indoor Return Air

Indoor Coil Discharge Air

PRESSURES

Suction (Vapor)

Same

Higher

Same or Higher

Same

Higher

Higher

Same

Lower

Lower

Liquid Higher

Y2 - Second‐Stage

Start-Up and Performance Checklist

Job Name

Job Location

Installer

Unit Model No. Serial No.

Nameplate Voltage

Rated Load Ampacity Compressor

Maximum Fuse or Circuit Breaker

Electrical Connections Tight?

Indoor Blower RPM

Indoor Filter clean?

S.P. Drop Over Indoor (Dry)

Discharge Pressure Suction Pressure

Job no.

City

City

Date

State

State

Service Technician

Outdoor Fan

Supply Voltage (Unit Off)

Outdoor Coil Entering Air Temp.

Refrigerant Charge Checked?

Refrigerant Lines: Leak Checked?

Service Valves: Fully Opened?

Voltage With Compressor Operating

Properly Insulated?

Caps Tight?

Outdoor Fan Checked?

Thermostat

Calibrated? Properly Set? Level?

Page 28

advertisement

Related manuals

Download PDF

advertisement