Lennox TSA*H4 Series Installation Instructions

Add to My manuals
20 Pages

advertisement

Lennox TSA*H4 Series Installation Instructions | Manualzz

2012 Lennox Industries Inc.

Dallas, Texas, USA

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.

Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.

IMPORTANT

The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.

Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.

IMPORTANT

This unit must be matched with an indoor coil as specified in Lennox Engineering Handbook. Coils previously charged with HCFC-22 must be flushed.

NOTICE TO INSTALLER

UNIT PLACEMENT

It is critical for proper unit operation to place outdoor unit on an elevated surface as described in Unit Placement

section on page 4.

BRAZING LINE SET TO SERVICE

VALVES

It is imperative to follow the brazing technique illustrated starting on

page 6 to avoid damaging the service valve's internal seals.

INSTALLATION

INSTRUCTIONS

Small Splits TSA*H4 Units

AIR CONDITIONER

506

646-01

4/2012

Supersedes 11/2010

TABLE OF CONTENTS

Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . .

1

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Model Number Identification . . . . . . . . . . . . . . . . . . . . . .

3

1

2

Operating Manifold Gauge Set and Service Valves . . .

New Unit Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

4

New or Replacement Line Set . . . . . . . . . . . . . . . . . . . . .

Brazing Connections . . . . . . . . . . . . . . . . . . . . . . . . . . .

Flushing Line Set and Indoor Coil . . . . . . . . . . . . . . . .

Installing Indoor Metering Device . . . . . . . . . . . . . . . .

9

10

5

6

Leak Test Line Set and Indoor Coil

Evacuating Line Set and Indoor Coil

. . . . . . . . . . . . . .

. . . . . . . . . . . . .

11

12

Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Unit Delivered Void of Charge . . . . . . . . . . .

13

15

Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

15

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Start-Up and Performance Checklist . . . . . . . . . . . . . .

18

20

Shipping and Packing List

Check the unit for shipping damage and listed times below are intact. If damaged, or if parts are missing, immediately contact the last shipping carrier.

1 — Assembled outdoor unit

1 — Liquid line filter drier

General

TSA*H4 Air Conditioners, which will also be referred to in this instruction as the outdoor unit, uses HFC-410A refrigerant. This outdoor unit must be installed with a matching indoor unit and line set as outlined in the Lennox

TSA*H4 Engineering Handbook .

This outdoor unit is designed for use in systems that use one of the following refrigerant metering devices:

Thermal expansion valve (TXV)

4/2012 506646-01

Page 1

Unit Dimensions - Inches (mm)

A

OUTDOOR COIL FAN

A

Discharge Air

COMPRESSOR

B

SUCTION AND LIQUID LINE

CONNECTIONS

OPTIONAL UNIT STAND‐OFF KIT

(4) (FIELD-INSTALLED)

SIDE VIEW SIDE VIEW

Model Numbers

TSA036H4N4

TSA042H4N4

TSA048H4N4

TSA060H4N4

A

28-1/4 (718)

28-1/4 (718)

28-1/4 (718)

32-1/4 (819)

B

37-1/4 (946)

29-1/4 (743)

37-1/4 (946)

33-1/4 (845)

Operating Manifold Gauge Set and

Service Valves

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.

CAUTION

Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.

IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.

When servicing or repairing HVAC components, ensure

the fasteners are appropriately tightened. Table 1 provides

torque values for fasteners.

Table 1. Torque Requirements

TORQUE REQUIREMENTS

When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are

appropriately tightened. Table 1 lists torque values for

fasteners.

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc -

Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.

Service valve stems are factory-torqued (from 9 ft-lbs for small valves, to 25 ft-lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an

Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.

See the Lennox Service and Application Notes #C-08-1 for further details and information.

Parts Recommended Torque

Service valve cap

Sheet metal screws

8 ft.- lb.

16 in.- lb.

Machine screws #10 28 in.- lb.

Compressor bolts 90 in.- lb.

Gauge port seal cap 8 ft.- lb.

11 NM

2 NM

3 NM

10 NM

11 NM

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low loss anti-blow back fittings.

Page 2

Manifold gauge set used with HFC-410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 - 800 psig on the high side and a low side of 30” vacuum to 250 psig with dampened speed to

500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.

506 11/2012

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.

Each valve is equipped with a service port which has a

factory-installed valve stem. Figure 1 provides information

on how to access and operating both angle and ball service valves.

Operating Angle Type Service Valve:

1. Remove stem cap with an appropriately sized wrench.

2. Use a service wrench with a hex-head extension (3/16” for liquid line valve sizes and 5/16” for vapor line valve sizes) to back the stem out counterclockwise as far as it will go.

SERVICE PORT CAP

SERVICE PORT CORE

TO INDOOR

UNIT (VALVE STEM SHOWN OPEN)

INSERT HEX WRENCH HERE

(VALVE STEM SHOWN

CLOSED) INSERT HEX

WRENCH HERE

SERVICE PORT

CORE

STEM CAP

TO OUTDOOR UNIT

ANGLE-TYPE SERVICE VALVE

(BACK-SEATED OPENED)

When service valve is OPEN , the service port is open to linE set, indoor and outdoor unit.

ANGLE-TYPE SERVICE VALVE

(FRONT-SEATED CLOSED)

WHEN SERVICE VALVE IS

CLOSED

, THE SERVICE PORT IS OPEN

TO THE LIN

E

SET AND INDOOR UNIT.

Operating Ball Type Service Valve:

1. Remove stem cap with an appropriately sized wrench.

2. Use an appropriately sized wrenched to open. To open valve, rotate stem counterclockwise 90°. To close rotate stem clockwise 90°.

TO OPEN ROTATE STEM

COUNTERCLOCKWISE 90°.

TO CLOSE ROTATE STEM

CLOCKWISE 90°.

SERVICE PORT

SERVICE PORT

CORE

SERVICE PORT

CAP

TO OUTDOOR

UNIT

TO INDOOR UNIT

BALL (SHOWN

CLOSED)

VALVE

STEM

STEM CAP

To Access Service Port:

A service port cap protects the service port core from contamination and serves as the primary leak seal.

1. Remove service port cap with an appropriately sized wrench.

2. Connect gauge set to service port.

3. When testing is completed, replace service port cap and tighten as follows:

1/6 TURN

With torque wrench: Finger tighten and

torque cap per table 1.

Without torque wrench: Finger tighten and use an appropriately sized wrench to turn an additional 1/6 turn clockwise.

Reinstall Stem Cap:

10

11 12

9

8

7

6

1

5

2

4

3

Stem cap protects the valve stem from damage and serves as the primary seal. Replace the stem cap and tighten as follows:

1/12 TURN

With Torque Wrench: Finger tighten and

then torque cap per table 1.

Without Torque Wrench: Finger tight­ en and use an appropriately sized wrench to turn an additional 1/12 turn clockwise.

9

10

8

11 12

7

6

1

5

2

4

3

NOTE — A label with specific torque requirements may be affixed to the stem cap. If the label is present, use the specified torque.

Figure 1. Angle and Ball Service Valves

Page 3

TSA*H4 SERIES

CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)

6 (152)

12 (305)

36 (914)

ACCESS PANEL

30 (762)

NOTES:

Clearance to one of the other three sides must be 36 inches (914mm).

Clearance to one of the remaining two sides may be 12 inches

(305mm) and the final side may be

6 inches (152mm).

LINE SET

CONNECTIONS

MINIMUM CLEARANCE BETWEEN

TWO UNITS

24 (610)

MINIMUM CLEARANCE

ABOVE UNIT

48 (1219)

DETAIL A

Install unit away from windows .

Figure 2. Installation Clearances

DETAIL B

Install unit level or, if on a slope, maintain slope tolerance of 2 degrees

(or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.

STRUCTURE

DISCHARGE AIR

Two 90° elbows installed in line set will reduce line set vibration.

GROUND LEVEL

MOUNTING SLAB MUST SLOPE

AWAY FROM BUILDING.

New Unit Placement

Figure 3. Placement, and Slab Mounting

See Unit Dimensions

on page 2 for sizing mounting slab,

platforms or supports. Refer to figure 2 for mandatory

installation clearance requirements.

CAUTION

In order to avoid injury, take proper precaution when lifting heavy objects.

POSITIONING CONSIDERATIONS

Consider the following when positioning the unit:

Some localities are adopting sound ordinances based on the unit's sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.

When possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation

to a window see the provided illustration in figure 3,

detail A.

Page 4

506 11/2012

PLACING UNIT ON SLAB

When installing unit at grade level, the top of the slab should be high enough above grade so that water from higher ground will not collect around the unit. The slab

should have a slope tolerance as described in figure 3,

detail B.

ROOF MOUNTING

Install the unit a minimum of 6 inches (152 mm) above the roof surface to avoid ice build-up around the unit. Locate the unit above a load bearing wall or area of the roof that can adequately support the unit. Consult local codes for rooftop applications.

If unit coil cannot be mounted away from prevailing winter winds, a wind barrier should be constructed. Size barrier at least the same height and width as outdoor unit. Mount barrier 24 inches (610 mm) from the sides of the unit in the direction of prevailing winds.

NOTICE

Roof Damage!

This system contains both refrigerant and oil. Some rubber roofing material may absorb oil and cause the rubber to swell when it comes into contact with oil. The rubber will then bubble and could cause leaks. Protect the roof surface to avoid exposure to refrigerant and oil during service and installation. Failure to follow this notice could result in damage to roof surface.

New or Replacement Line Set

This section provides information on new installation or replacement of existing line set. If a new or replacement line set is not required, then proceed to Brazing

Connections

on page 6.

Field refrigerant piping consists of liquid and suction lines from the outdoor unit (braze connections) to the indoor unit coil (flare or braze connections). Use Lennox L15 (braze, non-flare) series line set, or use field-fabricated refrigerant

lines as listed in table 2.

NOTE - When installing refrigerant lines longer than 50 feet, see the Lennox Refrigerant Piping Design and

Fabrication Guidelines, CORP. 9351-L9, or contact

Lennox Technical Support Product Applications for assistance.

NOTE - For new or replacement line set installation, refer to Service and Application Note - Corp. 9112-L4 (C-91-4).

To obtain the correct information from Lennox, be sure to communicate the following points:

Model (TSA*H4) and size of unit (e.g. -060).

Line set diameters for the unit being installed as listed

in table 2 and total length of installation.

Number of elbows and if there is a rise or drop of the piping.

If refrigerant lines are routed through a wall, seal and isolate the opening so vibration is not transmitted to the building. Pay close attention to line set isolation during installation of any HVAC system. When properly isolated from building structures (walls, ceilings. floors), the refrigerant lines will not create unnecessary vibration and subsequent sounds.

IMPORTANT

Mineral oils are not compatible with HFC-410A .

If oil must be added, it must be a Polyol ester oil.

The compressor is charged with sufficient Polyol ester oil for line set lengths up to 50 feet. Recommend adding oil to system based on the amount of refrigerant charge in the system. No need to add oil in system with 20 pounds of refrigerant or less. For systems over 20 pounds - add one ounce of every five pounds of refrigerant.

Recommended topping-off POE oils are Mobil EAL

ARCTIC 22 CC or ICI EMKARATE RL32CF.

MATCHING WITH NEW OR EXISTING INDOOR COIL

AND LINE SET

The RFC1-metering line consisted of a small bore copper line that ran from condenser to evaporator coil. Refrigerant was metered into the evaporator by utilizing temperature/pressure evaporation effects on refrigerant in the small RFC line. The length and bore of the RFC line corresponded to the size of cooling unit.

If the TSA*H4 is being used with either a new or existing indoor coil which is equipped with a liquid line which served as a metering device (RFCI), the liquid line must be replaced prior to the installation of the TSA*H4 unit.

Typically a liquid line used to meter flow is 1/4” in diameter and copper.

LIQUID LINE FILTER DRIER INSTALLATION

The filter drier (one is shipped with each TSA*H4 unit) must be field installed in the liquid line between the outdoor unit's liquid line service valve and the indoor coil's metering

device (fixed orifice or TXV) as illustrated in figure 4. This

filter drier must be installed to ensure a clean, moisture-free system. Failure to install the filter drier will void the warranty. A replacement filter drier is available from Lennox. See Brazing Connections

page 6 for

special procedures on brazing filter drier connections to the liquid line.

BRAZE CONNECTION POINTS

LIQUID LINE

SERVICE

VALVE

LINE

LIQUID LINE

FILTER DRIER

LIQUID

LINE

OUTDOOR

UNIT

Figure 4. Typical Liquid Line Filter Drier

Installation

Page 5

TSA*H4 SERIES

Models

Number

TSA036H4N4

TSA042H4N4

TSA048H4N4

Field Connections

Liquid Line

3/8 in. (10 mm)

TSA060H4N4 3/8 in. (10 mm)

Suction Line

7/8 in (22 mm)

Table 2. Refrigerant Line Set

Recommended Line Set

Liquid Line Suction Line

3/8 in. (10 mm)

1-1/8 in. (29 mm) 3/8 in. (10 mm)

7/8 in (22 mm)

L15 Line Set

L15-65 — 15 ft. - 50 ft. (4.6 m - 15 m)

1-1/8 in. (29 mm) Field Fabricated

IMPORTANT

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant.

Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

CAUTION

Brazing alloys and flux contain materials which are hazardous to your health.

Avoid breathing vapors or fumes from brazing operations. Perform operations only in well-ventilated areas.

Wear gloves and protective goggles or face shield to protect against burns.

Wash hands with soap and water after handling brazing alloys and flux.

Brazing Connections

Use the procedures outline in figures 5 and 6 for brazing

line set connections to service valves.

IMPORTANT

Connect gauge set low pressure side to vapor line service valve and repeat procedure starting at paragraph 4 for brazing the liquid line to service port valve.

IMPORTANT

Polyol ester (POE) oils used with HFC-410A refrigerant absorb moisture very quickly. It is very important that the refrigerant system be kept closed as much as possible. DO NOT remove line set caps or service valve stub caps until you are ready to make connections.

WARNING

Danger of fire. Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing. Application of a brazing torch to a pressurized system may result in ignition of the refrigerant and oil mixture - Check the high and low pressures before applying heat.

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

IMPORTANT

Allow braze joint to cool before removing the wet rag from the service valve. Temperatures above 250ºF can damage valve seals.

IMPORTANT

Use silver alloy brazing rods with 5% minimum silver alloy for copper-to-copper brazing. Use 45% minimum alloy for copper-to-brass and copper-to-steel brazing.

WARNING

Fire, Explosion and Personal Safety

Hazard.

Failure to follow this warning could result in damage, personal injury or death.

Never use oxygen to pressurize or purge refrigeration lines. Oxygen, when exposed to a spark or open flame, can cause fire and/or an ex­ plosion, that could result in property damage, personal injury or death.

Page 6

506 11/2012

1 CUT AND DEBUR

Cut ends of the refrigerant lines square (free from nicks or dents) and debur the ends. The pipe must remain round. Do not crimp end of the line.

CUT AND DEBUR

2 CAP AND CORE REMOVAL

Remove service cap and core from both the vapor and liquid line service ports.

SERVICE PORT

CAP

LINE SET SIZE MATCHES

SERVICE VALVE CONNECTION

COPPER TUBE

STUB

SERVICE VALVE

CONNECTION

REDUCER

SERVICE

PORT

CORE

LIQUID LINE SERVICE

VALVE

SERVICE

PORT

CORE

SERVICE

PORT CAP

SUCTION / VAPOR LINE

SERVICE VALVE

LINE SET SIZE IS SMALLER

THAN CONNECTION

REFRIGERANT LINE

DO NOT CRIMP SERVICE

VALVE CONNECTOR WHEN

PIPE IS SMALLER THAN

CONNECTION

3 ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE

VALVES

Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction / vapor line service port valve.

A Connect gauge set low pressure side to liquid line service valve (service port).

USE REGULATOR TO FLOW

NITROGEN AT 1 TO 2 PSIG.

B Connect gauge set center port to bottle of nitrogen with regulator.

LOW HIGH

C Remove Schrader valve in suction / vapor line service port to allow nitrogen to escape.

ATTACH

GAUGES

SUCTION / VAPOR SERVICE PORT MUST BE

OPEN TO ALLOW EXIT POINT FOR NITROGEN

C

VAPOR LINE

INDOOR

UNIT

LIQUID LINE

SUCTION /

VAPOR LINE

SERVICE

VALVE

B

OUTDOOR

UNIT

LIQUID LINE SERVICE

VALVE

A

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

NITROGEN

Figure 5. Brazing Procedures

Page 7

TSA*H4 SERIES

4 WRAP SERVICE VALVES

To help protect service valve seals during brazing, wrap a saturated cloth around service valve bodies and copper tube stub. Use another saturated cloth underneath the valve body to protect the base paint.

5 FLOW NITROGEN

Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections

6 BRAZE LINE SET

Wrap both service valves with a saturated cloth as illustrated here before brazing to line set.

LIQUID LINE SERVICE VALVE

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

IMPORTANT — Allow braze joint to cool. Apply additional saturated cloths to help cool brazed joint.

Do not remove wet rag until piping has cooled.

Temperatures above 250ºF will damage valve seals.

WARNING

1.

FIRE, PERSONAL INJURY, OR PROPERTY

DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper tube stub while brazing in the line set! The braze, when complete, must be quenched with water to absorb any residual heat.

2. Do not open service valves until refrigerant lines and indoor coil have been leak-tested and evacuated.

Refer to procedures provided in this supplement.

SATURATED CLOTH

LIQUID LINE

SUCTION / VAPOR LINE

SERVICE VALVE

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

SUCTION / VAPOR LINE

SATURATED CLOTH

7 PREPARATION FOR NEXT STEP

After all connections have been brazed, disconnect manifold gauge set from service ports. Apply saturated rags to both services valves to cool piping. Once piping is cool, remove all wet cloths. Refer to the unit installation instructions for the next step in preparing the unit.

Figure 6. Brazing Procedures (continued)

Page 8

506 11/2012

Flushing Line Set and Indoor Coil

Flushing is only required if existing indoor coil and line set are to be used. Otherwise proceed to Installing Indoor Metering

Device

on page 10.

1A TYPICAL EXISTING FIXED ORIFICE

REMOVAL PROCEDURE (UNCASED

COIL SHOWN)

OR

DISTRIBUTOR TUBES

LIQUID LINE ORIFICE HOUSING

1B TYPICAL EXISTING EXPANSION VALVE REMOVAL

PROCEDURE (UNCASED COIL SHOWN)

STUB END

TWO PIECE PATCH PLATE

LIQUID LINE CHECK

(UNCASED COIL ONLY)

ORIFICE EXPANSION

HOUSING

DISTRIBUTOR

VALVE

TEFLON

® TUBES

RING TEFLON

®

RING

FIXED ORIFICE

BRASS NUT

TEFLON®

RING

SENSING

LINE

DISTRIBUTOR

ASSEMBLY DISTRIBUTOR

ASSEMBLY

EQUALIZER

LINE REMOVE AND DISCARD

WHITE TEFLON

®

SEAL

(IF PRESENT) LIQUID LINE ASSEMBLY

(INCLUDES STRAINER) LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A On fully cased coils, remove the coil access and plumbing panels.

B Remove any shipping clamps holding the liquid line and distributor as­ sembly.

C Using two wrenches, disconnect liquid line from liquid line orifice hous­ ing. Take care not to twist or damage distributor tubes during this pro­ cess.

MALE EQUALIZER

LINE FITTING

SENSING BULB

VAPOR

LINE

LIQUID

LINE

D Remove and discard fixed orifice, valve stem assembly if present and

Teflon ® washer as illustrated above.

A On fully cased coils, remove the coil access and plumbing panels.

B Remove any shipping clamps holding the liquid line and distributor assembly.

E Use a field-provided fitting to temporary reconnect the liquid line to the indoor unit's liquid line orifice housing.

C Disconnect the equalizer line from the check expansion valve equalizer line fitting on the vapor line.

2

CONNECT GAUGES AND EQUIPMENT FOR

FLUSHING PROCEDURE

INVERTED HCFC-22

CYLINDER CONTAINS

CLEAN HCFC-22 TO BE

USED FOR FLUSHING.

GAUGE

MANIFOLD

A

VAPOR LINE

SERVICE VALVE

EXISTING

INDOOR

UNIT

LIQUID LINE SERVICE

VALVE

CYLINDER

1

B

NEW

OUTDOOR

UNIT

C

LOW

OPENED

TANK

RETURN

INLET

DISCHARGE

CLOSED

RECOVERY MACHINE

HIGH

A Inverted HCFC-22 cylinder with clean refrigerant to the vapor service valve.

B HCFC-22 gauge set (low side) to the liquid line valve.

C HCFC-22 gauge set center port to inlet on the recovery machine with an empty recovery tank to the gauge set.

D Connect recovery tank to recovery machines per machine instructions.

D Remove the vapor line sensing bulb.

E Disconnect the liquid line from the check expansion valve at the liquid line assembly.

F Disconnect the check expansion valve from the liquid line orifice housing. Take care not to twist or damage distributor tubes during this process.

G Remove and discard check expansion valve and the two Teflon ® rings.

H Use a field-provided fitting to temporary reconnect the liquid line to the

3 indoor unit's liquid line orifice housing.

FLUSHING LINE SET

The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system. Check the charge in the flushing cylinder before proceeding.

A Set the recovery machine for liquid recovery and start the recovery machine. Open the gauge set valves to allow the recovery machine to pull a vacuum on the existing system line

B

B Invert the cylinder of clean HCFC-22 and open its valve to allow liquid refrigerant to flow into the system through the vapor line valve. Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine.

C After all of the liquid refrigerant has been recovered, switch the recovery machine to vapor recovery so that all of the HCFC-22 vapor is recovered. Allow the recovery machine to pull down to 0 the system.

D Close the valve on the inverted HCFC-22 drum and the gauge set valves. Pump the remaining refrigerant out of the recovery machine and turn the machine off.

Figure 7. Removing Metering Device and Flushing

Page 9

TSA*H4 SERIES

Installing Indoor Metering Device

This outdoor unit is designed for use in systems that use either an fixed orifice (RFC) (included with outdoor unit), or expansion valve metering device (purchased separately) at the indoor coil.

See the Lennox TSA*H4 Engineering Handbook for approved expansion valve kit match ups. The expansion valve unit can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field-provided plenum, install the expansion valve in a manner that will provide access for field servicing of the expansion valve. Refer to below illustration for reference during installation of expansion valve unit. .

After installation of the indoor coil metering device, proceed to Leak Test Line Set and Indoor Coil

on page 11.

INDOOR EXPANSION VALVE INSTALLATION

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

(Uncased Coil Shown)

LIQUID LINE

ORIFICE

HOUSING

STUB

END

EXPANSION

VALVE

DISTRIBUTOR

TUBES

DISTRIBUTOR

ASSEMBLY

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR

FURTHER DETAILS)

TEFLON

®

RING

EQUALIZER

LINE bulb installation for bulb positioning.

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

VAPOR

LINE

Sensing bulb insulation is required if mounted external to the coil casing. sensing

EQUALIZER LINE INSTALLATION

SENSING

LINE

A Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.

B Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.

A Remove the field-provided fitting that temporary reconnected the liquid line to the indoor unit's distributor assembly.

B Install one of the provided Teflon ® rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ® ring with refrigerant oil.

C Attach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above, or 20 ft-lb.

D Place the remaining Teflon ® washer around the other end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon ® ring with refrigerant oil.

E Attach the liquid line assembly to the expansion valve.

Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft-lb.

1/2 Turn

9

8

10

11 12

7

6

1

2

3

4

5

SENSING BULB INSTALLATION

A Attach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided.

1/8 Turn

LIQUID LINE

NOTE — Confirm proper thermal contact between vapor line and expansion bulb before insulating the sensing bulb once installed.

B Connect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.

10

11 12

9

8

7

6

1

2

3

4

5

VAPOR LINE

BULB

12

BULB

ON LINES SMALLER THAN

7/8”, MOUNT SENSING

BULB AT EITHER THE 3 OR

9 O'CLOCK POSITION.

FLARE SEAL CAP FLARE NUT

VAPOR LINE

OR COPPER FLARE

SEAL BONNET

12

ON 7/8” AND LARGER LINES,

MOUNT SENSING BULB AT

EITHER THE 4 OR 8 O'CLOCK

POSITION. NEVER MOUNT ON

BOTTOM OF LINE.

MALE BRASS EQUALIZER

LINE FITTING

BULB

BULB

VAPOR LINE NOTE — NEVER MOUNT ON BOTTOM OF LINE.

Figure 8. Installing Indoor Expansion Valve

Page 10

506 11/2012

IMPORTANT

The Environmental Protection Agency (EPA) prohibits the intentional venting of HFC refrigerants during maintenance, service, repair and disposal of appliance.

Approved methods of recovery, recycling or reclaiming must be followed.

IMPORTANT

If this unit is being matched with an approved line set or indoor unit coil which was previously charged with mineral oil, or if it is being matched with a coil which was manufactured before January of 1999, the coil and line set must be flushed prior to installation. Take care to empty all existing traps. Polyol ester (POE) oils are used in Lennox units charged with HFC-410A refrigerant.

Residual mineral oil can act as an insulator, preventing proper heat transfer. It can also clog the expansion device, and reduce the system performance and capacity.

Failure to properly flush the system per the instructions below will void the warranty.

1 CONNECT GAUGE SET

A Connect an HFC-410A manifold gauge set high pressure hose to the vapor valve service port.

NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it to the vapor port better protects the manifold gauge set from high pressure damage.

B With both manifold valves closed, connect the cylinder of

HFC-410A refrigerant to the center port of the manifold gauge set.

NOTE — Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.

Leak Test Line Set and Indoor Coil

IMPORTANT

Leak detector must be capable of sensing HFC refrigerant.

After completing the leak testing the line set and indoor coil

as outlined in figure 9, proceed to

Evacuating Line Set and

Indoor Coil

on page 12.

WARNING

When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system, use a regulator that can control the pressure down to 1 or 2 psig (6.9 to 13.8 kPa).

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant must be used and recovered responsibly.

Failure to follow this warning may result in personal injury or death.

B

LOW HIGH

MANIFOLD GAUGE SET

A

OUTDOOR UNIT

TO VAPOR

SERVICE VALVE

2

NITROGEN

HFC-410A

TEST FOR LEAKS

After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use the following procedure to test for leaks:

A With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of the manifold gauge set. Open the valve on the HFC-410A cylinder (vapor only).

B Open the high pressure side of the manifold to allow HFC-410A into the line set and indoor unit. Weigh in a trace amount of HFC-410A.

[A trace amount is a maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure]. Close the valve on the HFC-410A cylinder and the valve on the high pressure side of the manifold gauge set. Disconnect the HFC-410A cylinder.

C Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

D Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit.

E After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector .

F After leak testing disconnect gauges from service ports.

Figure 9. Leak Test

Page 11

TSA*H4 SERIES

Evacuating Line Set and Indoor Coil

1 CONNECT GAUGE SET

NOTE — Remove cores from service valves (if not already done).

A Connect low side of manifold gauge set with 1/4 SAE in-line tee to vapor line service valve

B Connect high side of manifold gauge set to liquid line service valve

C Connect micron gauge available connector on the 1/4 SAE in-line tee.

D Connect the vacuum pump (with vacuum gauge) to the center port of the manifold gauge set. The center port line will be used later for both the

HFC-410A and nitrogen containers.

OUTDOOR

UNIT

A

NITROGEN

A34000 1/4 SAE TEE WITH

SWIVEL COUPLER

500

C

MICRON

GAUGE

TO VAPOR

SERVICE VALVE

LOW

MANIFOLD

GAUGE SET

HIGH

HFC-410A

B

VACUUM PUMP

TO LIQUID LINE

SERVICE VALVE

D

2 EVACUATE THE SYSTEM

A Open both manifold valves and start the vacuum pump.

B Evacuate the line set and indoor unit to an absolute pressure of 23,000 microns (29.01 inches of mercury).

RECOMMEND

MINIMUM 3/8” HOSE

NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a relatively large leak. If this occurs, repeat the leak testing procedure .

NOTE — The term absolute pressure means the total actual pressure within a given volume or system, above the absolute zero of pressure. Absolute pressure in a vacuum is equal to atmospheric pressure minus vacuum pressure.

C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury), perform the following:

Close manifold gauge valves

Close valve on vacuum pump

Turn off vacuum pump

Disconnect manifold gauge center port hose from vacuum pump

Attach manifold center port hose to a dry nitrogen cylinder with pressure regulator set to 150 psig (1034 kPa) and purge the hose.

Open manifold gauge valves to break the vacuum in the line set and indoor unit.

Close manifold gauge valves.

D Shut off the dry nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the dry nitrogen from the line set and indoor unit.

E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing the manifold gauge valves.

F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to an upright cylinder of HFC-410A refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit.

G Perform the following:

Close manifold gauge valves.

1/6 TURN

Shut off HFC-410A cylinder.

Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core tool while maintaining a positive system pressure.

Replace stem caps and secure finger tight, then tighten an additional one-sixth (1/6) of a turn as illustrated.

9

10

8

11 12

7

6

1

5

2

4

3

Figure 10. Evacuating System

Page 12

506 11/2012

WARNING

Danger of Equipment Damage. Avoid deep vacuum operation. Do not use compressors to evacuate a system. Extremely low vacuums can cause internal arcing and compressor failure. Damage caused by deep vacuum operation will void warranty.

CAUTION

Brazing alloys and flux contain materials which are hazardous to your health.

Avoid breathing vapors or fumes from brazing operations. Perform operations only in well ventilated areas.

Wear gloves and protective goggles or face shield to protect against burns.

Wash hands with soap and water after handling brazing alloys and flux.

Evacuating the system of non-condensables is critical for proper operation of the unit. Non-condensables are

SIZE CIRCUIT AND INSTALL SERVICE

DISCONNECT SWITCH

Refer to the unit nameplate for minimum circuit ampacity, and maximum fuse or circuit breaker (HACR per NEC). Install power wiring and properly sized disconnect switch.

SERVICE

DISCONNECT

SWITCH defined as any gas that will not condense under temperatures and pressures present during operation of an air conditioning system. Non-condensables and water suction combine with refrigerant to produce substances that corrode copper piping and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum gauge that is calibrated in microns. Use an instrument capable of accurately measuring down to 50 microns.

Electrical

In the U.S.A., wiring must conform with current local codes and the current National Electric Code (NEC). In Canada, wiring must conform with current local codes and the current Canadian Electrical Code (CEC).

Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size.

24VAC TRANSFORMER

Use the transformer provided with the furnace or air handler for low‐voltage control power (24VAC - 40 VA minimum)

INSTALL THERMOSTAT

Install room thermostat (ordered separately) on an inside wall approximately in the center of the conditioned area and 5 feet (1.5m) from the floor. It should not be installed on an outside wall or where it can be affected by sunlight or drafts.

THERMOSTAT

5 FEET

(1.5M)

NOTE — Units are approved for use only with copper conductors.

Ground unit at disconnect switch or to an earth ground.

NOTE — 24VAC, Class II circuit connections are made in the control panel.

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single‐pole contactors.

Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

Page 13

TSA*H4 SERIES

ROUTING HIGH VOLTAGE/ GROUND AND CONTROL WIRING

HIGH VOLTAGE / GROUND WIRES

Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control panel.

Connect conduit to the control panel using a proper conduit fitting.

CONTROL WIRING

HIGH VOLTAGE

FIELD WIRING

LOW VOLTAGE

FIELD WIRING

FACTORY

WIRING

GROUND

HIGH VOLTAGE

CONNECTIONS

(CONTACTOR)

NOTE — Wire tie provides low voltage control wire strain relief and to maintain separation of field installed low and high voltage circuits.

NOTE — For proper voltages, select thermostat wire (control wires) gauge per table above .

NOTE — Do not bundle any excess 24VAC control wires inside control panel.

GN

D

THREE PHASE

WIRE

NUTS

GROMMET

Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated.

A Run 24VAC control wires through hole with grommet and secure with provided wire tie.

THERMOSTAT

R

POWER

INDOOR UNIT

R

B Make 24VAC thermostat wire connections. Locate the two wires from the contactor and make connection using field provided wire nuts:

Yellow to Y1

Black to C (common)

W1

Y

HEA

T

COOLING

W

Y

HIGH VOLTAGE

FLEXIBLE CONDUIT

OUTDOOR

UNIT

Y1

G

INDOOR

BLOWER

G

B

CONTROL

WIRING

WIRE RUN LENGTH AWG# INSULATION TYPE

LESS THAN 100' (30 METERS) 18 TEMPERATURE RATING

MORE THAN 100' (30 METERS) 16 35ºC MINIMUM.

C

COMMON

C C

A

GROMMET

AND WIRE TIE

Typical Field Wiring Diagram (Y and G Voltages) Typical Field Wiring Diagram (J Voltage)

Figure 11. Typical Wiring Diagram

Page 14

506 11/2012

Servicing Units Delivered Void of Charge

If the outdoor unit is void of refrigerant, clean the system using the procedure described below.

1. Leak check system using procedure outlined on page

11.

2. Evacuate the system using procedure outlined on

page 12.

3. Use nitrogen to break the vacuum and install a new filter drier in the system.

4. Evacuate the system again using procedure outlined

on page 12.

5. Weigh in refrigerant using procedure outlined under

figure 15.

Unit Start-Up

IMPORTANT

If unit is equipped with a crankcase heater, it should be energized 24 hours before unit start-up to prevent compressor damage as a result of slugging.

1. Check that fan rotates freely.

2. Inspect all factory- and field-installed wiring for loose connections.

GAUGE SET

CONNECTIONS FOR TESTING AND CHARGING

B

SUCTION LINE

SERVICE PORT

CONNECTION

3. Open the liquid line and suction line service valve stems ( Operating Service Valves

on page 2) to

release the refrigerant charge (contained in outdoor unit) into the system.

4. Replace the valve stem caps and tighten as specified in Operating Service Valves

on page 2.

5. Check voltage supply at the disconnect switch. The voltage must be within the range listed on the unit's nameplate. If not, do not start the equipment until you have consulted with the power company and the voltage condition has been corrected.

6. Set the thermostat for a cooling demand. Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit.

7. Recheck voltage while the unit is running. Power must be within range shown on the unit nameplate.

8. Check system for sufficient refrigerate using the procedures outlined in under System Refrigerant .

System Refrigerant

This section outlines procedures for:

1. Checking and adjusting indoor airflow as

recommended in figure 14.

2. Determine the best method for adding or removing

refrigerant as outlined in figure 13.

MANIFOLD GAUGE SET

LOW HIGH

OUTDOOR UNIT

A Close manifold gauge set valves and connect the center hose to a cylinder of

HFC-410A. Set for liquid phase charging.

B Connect the manifold gauge set's low pressure side to the suction line service port.

C Connect the manifold gauge set's high pressure side to the liquid line service port.

D Position temperature sensor on liquid line near liquid line service port.

REFRIGERANT TANK

CHARGE IN

LIQUID PHASE

DIGITAL SCALE

A

C

TO LIQUID

LINE SERVICE

VALVE

TEMPERATURE SENSOR

(LIQUID LINE)

D

TEMPERATURE

SENSOR

Figure 12. Manifold Gauge Set Setup and Connections

Page 15

TSA*H4 SERIES

START: Determine how refrigerant is metered

WHEN TO CHARGE?

Warm weather best

Can charge in colder weather

CHARGE METHOD? Determine by:

Metering device type

Outdoor ambient temperature

REQUIREMENTS:

Sufficient heat load in structure

Indoor temperature between 70‐80ºF (21-26ºC)

Manifold gauge set connected to unit

Thermometers:

to measure outdoor ambient temperature

to measure liquid line temperature

to measure suction line temperature

65ºF (18.3ºC)

AND ABOVE

APPROACH OR

SUBCOOLING

TXV

OUTDOOR AMBIENT

TEMPERATURE

64ºF (17.7ºC)

AND BELOW

WEIGH‐IN

CHECKING AIR FLOW AT INDOOR COIL

Figure 13. Determining Charge Method

Temp.

of air entering indoor coil ºF

A

Delta −

T

80 24 24 24 23 23 22 22 22 20 19 18 17 16 15

78 23 23 23 22 22 21 21 20 19 18 17 16 15 14

76 22 22 22 21 21 20 19 19 18 17 16 15 14 13

74 21 21 21 20 19 19 18 17 16 16 15 14 13 12

72 20 20 19 18 17 17 16 15 15 14 13 12 11 10

70 19 19 18 18 17 17 16 15 15 14 13 12 11 10

Wet-bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70

B

C

53º

T

Drop

19º

A

72º

DRY

BULB air flow

All temperatures are expressed in ºF air flow

INDOOR

COIL

B

64º

WET

BULB

DRY

BULB

1. Determine the desired

D

T —Measure entering air temperature using dry bulb ( A ) and wet bulb ( B ). D T is the intersecting value of A and B in the table (see triangle).

2. Find temperature drop across coil —Measure the coil's dry bulb entering and leaving air temperatures ( A and C ). Temperature Drop

Formula: ( T

Drop

) = A minus C .

3. Determine if fan needs adjustment —If the difference between the measured T

Drop

and the desired

D

T (T

Drop

D

T) is within +3º, no ad­ justment is needed. See examples: Assume

D

T = 15 and A temp. =

72º, these C temperatures would necessitate stated actions:

Cº T

Drop

– D T = ºF ACTION

53º

58º

62º

19

14

10

15

=

4 Increase the airflow

15

=

-1 (within +3º range) no change

15 = -5 Decrease the airflow

4. Adjust the fan speed —See indoor unit instructions to increase/de­ crease fan speed.

Changing air flow affects all temperatures; recheck temperatures to confirm that the temperature drop and D T are within +3º.

Figure 14. Checking Indoor Airflow over Evaporator Coil using Delta-T Chart

START: Measure outdoor ambient temperature

USE SUBCOOLING

METHOD

65ºF

(18.3ºC) and

ABOVE

ABOVE or

BELOW

64ºF (17.7ºC) and BELOW

1. Check Liquid and suction line pressures

2. Compare unit pressures with table 3 or 6.

3. Conduct leak check; evacuate as previously outlined.

4. Weigh in the unit nameplate charge plus any charge required for line set differences over feet.

Refrigerant Charge per Line Set Length

Liquid Line

Set Diameter

Ounces per 5 feet (g per 1.5 m) adjust from 15 feet (4.6 m line set*

3/8” (9.5 mm) 3 ounces per 5' (85 g per 1.5 m)

NOTE - *If line length is greater than 15 feet (4.6 m), add this amount. If line length is less than 15 feet (4.6 m), subtract this amount.

Figure 15. HFC-410A Weigh In

Page 16

506 11/2012

This nameplate is for illustration purposes only. Go to actual nameplate on outdoor unit for charge information.

START: Measure outdoor ambient temperature

USE WEIGH‐IN METHOD

Weigh‐in or remove refriger­ ant based upon line length

If refrigerant is added or removed, verify charge using the

Subcooling Method .

If value is LESS than shown, add refrigerant.

64ºF and

BELOW

If value is MORE than shown, remove refrigerant.

MORE or

LESS

ABOVE or

BELOW

65ºF and

ABOVE

1. Confirm proper airflow across coil using figure 14.

2. Compare unit pressures with Table 3,

Normal Operating Pressures .

3. Set thermostat to call for heat (must have a cooling load between

70‐80ºF (21-26ºC).

4. Connect gauge set.

5. When heat demand is satisfied, set thermostat to call for cooling.

6. Allow temperatures and pressures to stabilize.

7. Record outdoor ambient temperature:

AMBº =_________

8. Record liquid line temperature:

LIQº = __________

9. Subtract to determine approach (APPº):

LIQº_____ - AMBº _____ = APPº_____

10. Compare results with table below.

APPº (Approach) Values(F:+/-1.0° [C: +/-0.6°])

ºF (ºC)* -036

Any 11 (6.1)

-042

9 (5.0)

-048

8 (4.4)

-060

9 (5.0)

*Temperature of air entering outdoor coil

Figure 16. HFC-410A Approach TXV Charge

START: Measure outdoor ambient temperature

ABOVE or

BELOW

65ºF and

ABOVE

64ºF and

BELOW

BLOCK OUTDOOR COIL: [sometimes necessary with lower temperatures] Use cardboard or plastic sheet to restrict the airflow through the outdoor coil to achieve pressures from 325-375 psig

(2240-2585 kPa).

Higher pressures are needed to check charge.

Block equal sections of air intake panels and move coverings sideways until the liquid pressure is in the above noted ranges.

If refrigerant is added or removed, verify charge using the

Approach Method .

If value is MORE than shown, remove refrigerant.

If value is LESS than shown, add refrigerant.

MORE or

LESS

1. Confirm proper airflow across coil using figure

14.

2. Compare unit pressures with Table 3,

Normal

Operating Pressures .

3. Set thermostat to call for heat (must have a cooling load between 70‐80ºF (21-26ºC)

4. Connect gauge set

5. Measure outdoor ambient temperature

6. When heat demand is satisfied, set thermostat to call for cooling

7. Allow temperatures and pressures to stabilize.

NOTE - If necessary, block outdoor coil to maintain 325 - 375 psig.

8. Record liquid line temperature:

LIQº = ______

9. Measure liquid line pressure and use the value to

determine saturation temperature (see table 4):

SATº = ______

10. Subtract to determine subcooling (SCº):

SATº_____ - LIQº _____ = SCº _____

11. Compare results with table below.

SCº (Subcooling) Values (F:+/-1.0° [C: +/-0.6°])

ºF (ºC)* -036

Any 12 (6.7)

-042

9 (5.0)

-048

9 (5.0)

-060

7 (3.9)

*Temperature of air entering outdoor coil

Figure 17. HFC-410A Subcooling TXV Charge

Page 17

TSA*H4 SERIES

Table 3. HFC-410A Normal Operating Pressures (Liquid +10 and Suction +5 psig)

IMPORTANT

Use this table to perform maintenance checks; it is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations.

Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.

TSA*H4 -036

5

F (

5

C)* Liquid / Suction

Expansion Valve (TXV)

65 (18)

70 (21)

263 / 135

281 / 138

75 (24)

80 (27)

85 (29)

90 (32)

95 (35)

100 (38)

105 (41)

110 (43)

115 (45)

302 / 140

325 / 142

349 / 142

375 / 143

404 / 144

433 / 145

462 / 147

494 / 149

527 / 150

-042

Liquid / Suction

238 /132

262 / 133

280 / 134

301 / 136

327 / 137

353 / 138

377 / 140

404 / 141

435 / 142

465 / 143

499 / 144

-048

Liquid / Suction

235 / 132

254 / 132

276 / 134

298 / 134

323 / 135

350 / 137

377 / 138

406 / 140

430 / 141

464 / 142

495 / 143

-060

Liquid / Suction

241 / 130

260 / 130

280 / 132

299 / 134

321 / 135

344 / 134

371 / 135

400 / 137

428 / 139

458 / 141

484 / 142

°F

10

15

20

-5

0

5

-40

-35

-30

-25

-20

-15

-10

25

30

35

40

45

50

55

Maintenance

°C

Table 4. HFC-410A Temperature (°F) - Pressure (Psig)

Psig °F °C

-20.6

-17.8

-15.0

-12.2

-9.4

-6.7

-40.0

-37.2

-34.4

-31.7

-28.9

-26.1

-23.3

-3.9

-1.1

1.7

4.4

7.2

10.0

12.8

42.5

48.6

55.2

62.3

70.0

78.3

11.6

14.9

18.5

22.5

26.9

31.7

36.8

87.3

96.8

107

118

130

142

155

95

100

105

110

115

120

60

65

70

75

80

85

90

125

130

135

140

145

150

35.0

37.8

40.6

43.3

46.1

48.9

15.6

18.3

21.1

23.9

26.7

29.4

32.2

51.7

54.4

57.2

60.0

62.8

65.6

Motor Nameplate :_________ Actual :__________.

Psig

295

317

340

365

391

418

170

185

201

217

235

254

274

446

476

507

539

573

608

6. Inspect drain holes in coil compartment base and clean if necessary.

NOTE ‐ If insufficient cooling occurs, the unit should be gauged and refrigerant charge should be checked.

DEALER

Maintenance and service must be performed by a qualified installer or service agency. At the beginning of each cooling season, the system should be checked as follows:

Outdoor Unit

1. Outdoor unit fan motor is pre-lubricated and sealed.

No further lubrication is needed.

2. Visually inspect all connecting lines, joints and coils for evidence of oil leaks.

3. Check all wiring for loose connections.

4. Check for correct voltage at unit (unit operating).

5. Check amp draw on outdoor fan motor.

Outdoor Coil

Clean and inspect outdoor coil (may be flushed with a water hose). Ensure power is off before cleaning.

NOTE — It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block airflow across the coil (e.g., pet urine, cottonwood seeds, fertilizers, fluids that may contain high levels of corrosive chemicals such as salts)

Page 18

506 11/2012

Sea Coast — Moist air in ocean locations can carry salt, which is corrosive to most metal. Units that are located near the ocean require frequent inspections and maintenance. These inspections will determine the necessary need to wash the unit including the outdoor coil.

Consult your installing contractor for proper intervals/procedures for your geographic area or service contract.

Indoor Unit

1. Clean or change filters.

2. Lennox blower motors are prelubricated and permanently sealed. No more lubrication is needed.

3. Adjust blower speed for cooling. Measure the pressure drop over the coil to determine the correct blower CFM. Refer to the unit information service manual for pressure drop tables and procedure.

4.

Belt Drive Blowers - Check belt for wear and proper tension.

5. Check all wiring for loose connections.

6. Check for correct voltage at unit. (blower operating)

7. Check amp draw on blower motor.

Motor Nameplate :_________ Actual :__________.

Indoor Coil

1. Clean coil if necessary.

2. Check connecting lines, joints and coil for evidence of oil leaks.

3. Check condensate line and clean if necessary.

HOMEOWNER

Cleaning of the outdoor unit's coil should be performed by a trained service technician. Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit. The following maintenance may be performed by the homeowner.

IMPORTANT

Sprinklers and soaker hoses should not be installed where they could cause prolonged exposure to the outdoor unit by treated water. Prolonged exposure of the unit to treated water (i.e., sprinkler systems, soakers, waste water, etc.) will corrode the surface of steel and aluminum parts and diminish performance and longevity of the unit.

Outdoor Coil

The outdoor unit must be properly maintained to ensure its proper operation.

Please contact your dealer to schedule proper inspection and maintenance for your equipment.

Make sure no obstructions restrict airflow to the outdoor unit.

Grass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy.

Page 19

Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit.

Routine Maintenance

In order to ensure peak performance, your system must be properly maintained. Clogged filters and blocked airflow prevent your unit from operating at its most efficient level.

1.

Air Filter — Ask your Lennox dealer to show you where your indoor unit's filter is located. It will be either at the indoor unit (installed internal or external to the cabinet) or behind a return air grille in the wall or ceiling. Check the filter monthly and clean or replace it as needed.

2.

Disposable Filter — Disposable filters should be replaced with a filter of the same type and size.

NOTE — If you are unsure about the filter required for your system, call your Lennox dealer for assistance.

3.

Reusable Filter — Many indoor units are equipped with reusable foam filters. Clean foam filters with a mild soap and water solution; rinse thoroughly; allow filter to dry completely before returning it to the unit or grille.

NOTE — The filter and all access panels must be in place any time the unit is in operation.

4.

Indoor Unit — The indoor unit's evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air. Have your dealer show you the location of the drain line and how to check for obstructions. (This would also apply to an auxiliary drain, if installed.)

Thermostat Operation

See the thermostat homeowner manual for instructions on how to operate your thermostat.

Preservice Check

If your system fails to operate, check the following before calling for service:

Verify room thermostat settings are correct.

Verify that all electrical disconnect switches are ON.

Check for any blown fuses or tripped circuit breakers.

Verify unit access panels are in place.

Verify air filter is clean.

If service is needed, locate and write down the unit model number and have it handy before calling.

Accessories

For update-to-date information, see any of the following publications:

Lennox TSA*H4 Engineering Handbook

Lennox Product Catalog

Lennox Price Book

Cleaning Outdoor Coil

1. Make sure power is off before cleaning. Clean and inspect outdoor coil. The coil may be flushed with a water hose.

2. The outdoor coil is protected by an inner mesh screen

and a wire cage (see figure 18). If debris has collected

between the mesh screen and the coil and cannot be dislodged by spraying un-pressurized water from

TSA*H4 SERIES

inside coil surface to the outside, the mesh may be removed by first removing the top of the unit which will allow for removal of the wire cage.

3. Then, using pliers to grip the head of the push pins, pull straight out to extract the push pins along one side of the coil. If necessary, remove the push pins along the back of the unit; it is usually unnecessary to fully remove the inner mesh screen.

4. Drape the mesh screen back and wash the coil. When all the debris has been removed from the coil, reinstall the mesh screen by positioning it in its original position and reinserting the push pin. No tool is required to push the pin back into the same slot in the fins.

5. If the push pin is loose and tends not to stay in place, brush the fins with a fin brush (22 fins/in). Line up the push pin a couple fins to the right or left of the original hole and re-insert the pin.

9 PINS USED ON -048

AND -060; 6 PINS ALL

OTHERS

ÂÂÂÂÂÂÂÂÂÂÂ

ÂÂÂÂÂÂÂÂÂÂÂ

ÂÂÂÂÂÂÂÂÂÂÂ

PUSH PIN

ÂÂÂÂÂÂÂÂÂÂÂ

MESH SCREEN

ÂÂÂÂÂÂÂÂÂÂÂ

ÂÂÂÂÂÂÂÂÂÂÂ

Figure 18. Cleaning Debris from Mesh

Start-Up and Performance Checklist

Job Name

Job Location

Installer

Unit Model No.

Job no.

City

City

Serial No.

Nameplate Voltage

Rated Load Ampacity Compressor

Maximum Fuse or Circuit Breaker

Electrical Connections Tight?

Indoor Blower RPM

Indoor Filter clean?

S.P. Drop Over Indoor (Dry)

Discharge Pressure Suction Pressure

Date

State

State

Service Technician

Outdoor Fan

Supply Voltage (Unit Off)

Outdoor Coil Entering Air Temp.

Refrigerant Charge Checked?

Refrigerant Lines: Leak Checked?

Service Valves: Fully Opened?

Voltage With Compressor Operating

Properly Insulated?

Caps Tight?

Outdoor Fan Checked?

Thermostat

Calibrated? Properly Set? Level?

Page 20

506 11/2012

advertisement

Related manuals

Download PDF

advertisement