Panduit P24G05M Monitored & Switched per Outlet PDU Specification Sheets

Add to My manuals
6 Pages

advertisement

Panduit P24G05M Monitored & Switched per Outlet PDU Specification Sheets | Manualzz

SmartZone

G5 Basic & Intelligent

Power Distribution Units (iPDUs) for Japan

S P E C I F I C A T I O N S H E E T o v e r v i e w

The Panduit ™ SmartZone ™ G5 Basic & Intelligent Power Distribution Units are more than a power distribution unit and energy meter. These iPDUs monitor the data center power and environment (at the rack or cabinet level), by continuously scanning for electrical circuit overloads, and physical environmental conditions that place critical IT equipment at risk. Panduit’s iPDUs provide comprehensive, accurate, energy measurement data to efficiently use power resources, make informed capacity planning decisions, improve uptime, measure PUE (power usage effectiveness), and drive green data center initiatives to save energy and money.

Making the right choice in IT equipment is essential for a safe, efficient data center operation. Our full range of iPDUs, environmental sensors, and dual locking power cords are the key to fulfilling mission‐critical data center needs.

t e c h n i c a l i n f o r m a t i o n

Dimensions:

Mounting:

1U:

1U:

1U:

2U:

0U FULL:

Height Inch (mm)

1.6 (40.6)

1.7 (43.2)

1.7 (43.2)

3.4 (86.4)

68.9 (1750.1)

Width Inch (mm)

17.5 (444.5)

17.5 (444.5)

17.5 (444.5)

17.5 (444.5)

2.0 (50.8)

Depth Inch (mm)

2.0 (50.8)

7.8 (198.1)

10.6 (269.2)

7.8 (198.1)

2.1 (53.3)

0U Full Wide:

0U Full Wide +:

68.9 (1750.1)

74.0 (1880)

3.3 (83.8)

3.3 (83.8)

2.1 (53.3)

2.1 (53.3)

Vertical units provide up to 54 outlets and without encroaching on the EIA space.

Horizontal units provide up to 16 outlets and mount in standard.

(1U or 2U) TIA/EIA rack space.

k e y f e a t u r e s a n d b e n e f i t s ( i P D U s )

HotSwappable

Controller

Redundant Network

Access

Hardened Security

1GB Ethernet

Plug & Play Sensors

Multi-Color PDUs

Mobile & Desktop

Friendly Web GUI

Replace the controller and display module without having to power down the rack

Specifically designed for Landlord/Tenant (Co-Lo’s) allowing for remote access of real-time, vital statistics and operating information on two separate, secure networks

Not only Physical but hardened Digital Security; layers within the firmware LDAP,

SNMP v3, TLS, Encrypted Security; allows for Panduit PDUs to pass standard certified security scans

The 1G controller is compatible with the new Data Center Network switches being deployed - reducing special network configurations/resources required to support the iPDU

Digital sensors not only allow for multiple sensors on the same bus; but also identify themselves to the controller to simplify setup and commissioning.

Different color PDUs simplify power feed identification and management.

The new Panduit Intelligent PDUs are available in Black, White, Red, Blue,

Yellow, or Green.

The intelligent PDUs feature an enhanced designed web interface which detects the type of device that you are on; and automatically adjusts the screen for an optimal experience

Meets demands of densely packed IT equipment in rack or cabinet space Outlet Density

Form Factor Optimal form factor enables efficient rack space utilization

Operating Temperature 60°C ambient at full load for operational reliability in high temperature areas

(continued pg. 2) www.panduit.com

SmartZone ™ G5 Basic & Intelligent Power Distribution Units (iPDUs) for Japan k e y f e a t u r e s a n d b e n e f i t s ( i P D U s )

(continued)

Cable Retention

Circuit Breakers

Innovative cable tie accepting outlets allow for secure cord retention (C13 & C19 only) using a cable tie for added safety and security. (Panduit part number: PLT2I-C0)

Protects data center equipment for increased reliability by interrupting potentially hazardous circuit over-current conditions*

Color Coded Circuits* Easily identify phase to outlet banks to aid in fault isolation or load balancing

External Chassis

Ground

Meets NEC requirements and installation guidelines for IT equipment

Load Balancing

Multiple Input Plug

Options

Monitored through visual display on oLED (for 3 phase units only)

A full breadth offering to seamlessly interoperate with existing building power wiring schemes

Multiple Mounting

Options

Mounting Buttons

Supported Metering

Enables simple out of the box commissioning and flexibility with Panduit cabinets and industry standard mounting features enabling installation into third party cabinets

Allows tool-less mounting of rack PDUs for faster installations on vertical 0U units

Frequency, VA, PF, plus aggregate and per phase Amperage, Voltage, Wattage, and Kilowatts per hour

*Applies to products outfitted with circuit breakers

P D U p r o d u c t f a m i l i e s

Basic Series:

MI Series:

MS Series:

MPO Series:

MSPO Series:

Non Networked Rack PDUs provide reliable and cost effective power distribution in a variety of inputs (Single or Three Phase) and outlet configurations (IEC C13, C19, or 5-20R).

Rack PDUs that have the ability for aggregate power monitoring to quickly identify potential power issues, and reclaim available or under-utilized power capacity.

Rack PDUs that have the ability for aggregate power monitoring and outlet level switching capabilities for individual outlets or a group of outlets. Enabling power sequencing, rebooting equipment or restrict unauthorized use of individual outlets.

Rack PDUs that have the ability for outlet level (and aggregate) power monitoring to quickly identify potential power issues, and reclaim available or under-utilized power capacity at the outlet level enabling the redeployment or decommissioning of individual servers to reclaim available or under-utilized power capacity.

Rack PDUs that have the ability for outlet level (and aggregate) power monitoring and outlet level switching capabilities for individual outlets or a group of outlets. Power monitoring at the individual outlet level provides actionable management data on the power consumption of each connected IT device enabling the redeployment or decommissioning of individual servers to reclaim available or under-utilized power capacity. Ideal for remote power reset, and cabinet power on sequencing and restrict unauthorized use of individual outlets.

e l e c t r i c a l s p e c i f i c a t i o n s

Input Voltage:

Input Current:

(per phase)

Input Power:

Input Frequency:

Output Voltage:

Maximum output: current (outlet)

Overload protection:

(where applicable)

JAPAN

• Single-Phase 100V

• Single-Phase 200V

• Three-Phase 200V

• Three-Phase 415V

JAPAN

• 16A, 20A, 30A, 32A, 60A

JAPAN

• 1.9 – 22.0 (kVA)

50/60 Hz

100VAC, 200VAC, 240VAC

IEC C13: 10A

IEC C19: 16A

NEMA 5-20R: 16A

Circuit Breakers, hydraulic magnetic

Input Cord Length: 10 ft. (3m) unless otherwise specified www.panduit.com

SmartZone ™ G5 Basic & Intelligent Power Distribution Units (iPDUs) for Japan g e n e r a l s p e c i f i c a t i o n s

Temperature:

Operating

10°C to 60°C (50°F to 140°F)

-20°C to 60°C (-4°F to 140°F) Temperature:

Storage

Relative Humidity:

Operating

Relative Humidity:

Non-Operating

Relative Humidity:

Storage

10% to 90% non-condensing

5% to 95% RH

5% to 95%

Elevation:

Operating

Elevation:

Storage

Conformance

Standards:

Environmental

Compliances:

0 to 10,000 ft. (0 to 3000m)

0 to 30,000 ft. (0 to 9144m)

PSE Compliant: PDUs ≤ 50A or ≤ 300V

UL File number: E218078

PSE Exempt: PDUs > 50A or > 300V

RoHS & REACH c a b i n e t c o m p a t i b i l i t y

Panduit iPDUs can be easily installed into Panduit (or third party cabinets) by utilizing the installed mounting buttons

(18.4 mm diameter). Where necessary, a Small Diameter (14.5 mm) mounting button is available (sold separately,

P/N: MA018). Panduit PDUs feature threaded inserts on the back and both sides for the ultimate in mounting flexibility.

They safely and efficiently manage and distribute power to multiple devices through a single input power connector, per PDU, to enhance scalability of network build outs.

www.panduit.com

SmartZone ™ G5 Basic & Intelligent Power Distribution Units (iPDUs) for Japan

Basic Series

Region

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

Form Factor

1U

1U

1U

0U HALF

2U

0U HALF

0U HALF

0U HALF

0U HALF

0U HALF

0U MID

0U MID

0U MID

1U

Input Plug Type

NEMA L5-20P

NEMA L6-20P

NEMA L6-30P

NEMA L5-20P

NEMA L5-30P

NEMA L6-30P

NEMA L5-20P

NEMA L5-30P

NEMA L6-20P

NEMA L5-30P

NEMA L6-30P

NEMA L6-30P

NEMA L6-30P

IEC 60309 3P+E 9h 60A (IP44)

Input

Voltage

Range

Input

Current per phase

100VAC 20

100-200VAC 20

200VAC

100VAC

30

20

Circuit

Breakers

0

0

2

0

100VAC

200VAC

100VAC

100VAC

30

30

20

30

100-200VAC 20

100VAC

200VAC

200VAC

200VAC

200VAC

30

30

30

30

60

2

2

2

2

6

0

2

2

2

0

Apparent

Power

(kVA)

1.9 kVA

3.3 kVA

5.0 kVA

1.9 kVA

2.9 kVA

5.0 kVA

1.9 kVA

2.9 kVA

3.3 kVA

2.9 kVA

5.0 kVA

5.0 kVA

5.0 kVA

17.3 kVA

22

24

42

42

6

16

20

22

22

22

Outlet

Count

12

12

12

16

(12)5-20R

(12)C13

(12)C13

(16)5-20R

Outlet

Type

(16)5-20R

(20)C13

(20)C13, (2)C19

(22)5-20R

(20)C13, (2)C19

(22)5-20R

(20)C13, (4)C19

(36)C13, (6)C19

(36)C13, (6)C19

(6)C19

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

0U FULL

1U

0U HALF

0U MID

0U FULL

0U FULL

1U

0U FULL

0U MID

0U FULL

IEC 60309 3P+E 9h 60A (IP44)

NEMA L15-30P

NEMA L15-30P

NEMA L15-30P

NEMA L15-30P

200VAC

200VAC

200VAC

200VAC

200VAC

IEC 60309 3P+N+E 6h 16A (IP44) 200VAC

IEC 60309 3P+N+E 6h 32A (IP44) 200VAC

IEC 60309 3P+N+E 6h 32A (IP44) 200VAC

IEC 60309 3P+N+E 6h 16A (IP44) 200VAC

IEC 60309 3P+N+E 6h 32A (IP44) 200VAC

60

30

30

30

30

60

30

30

30

30

3

3

6

3

3

3

3

6

3

3

8.6 kVA

8.6 kVA

8.6 kVA

8.6 kVA

11.0 kVA

8.6 kVA

8.6 kVA

8.6 kVA

8.6 kVA

11.0 kVA

24

30

6

6

42

24

6

18

36

42

(12)C13, (12)C19

(6)C19

(18)C13

(30)C13, (6)C19

(36)C13, (6)C19

(6)C19

(6)C19

(12)C13, (12)C19

(24)13, (6)C19

(30)C13, (12)C19

JPN

JPN

JPN

JPN

0U MID

1U

0U FULL

0U FULL

JPN 0U FULL - Wide

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

415VAC

415VAC

30

50

60

30

30

0

6

6

0

6

22.0 kVA

11.0 kVA

22.0 kVA

11.0 kVA

17.3 kVA

42

6

24

36

48

(36)C13, (6)C19

(6)C19

(12)C13, (12)C19

(24)C13, (12)C19

(48)C13

JPN 0U FULL - Wide NEMA L22-30P 415VAC 30 0 17.3 kVA 54 (48)C13, (6)C19

Note: Minimum Order Quantity: 30 Pieces Per Part Number, Lead Time: 45 Business Days, Terms: Non-Cancellable / Non-Returnable

Monitored Input (MI Series)

Region

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

Form Factor

1U

1U

2U

2U

0U HALF

0U MID

0U MID

0U MID

0U MID

0U FULL

0U FULL

1U

0U FULL

1U

0U MID

0U FULL

1U

1U

0U FULL

0U MID

0U FULL

Input Plug Type

NEMA L5-20P

NEMA L6-20P

NEMA L5-30P

NEMA L6-30P

NEMA L5-20P

NEMA L6-30P

NEMA L5-30P

NEMA L6-20P

NEMA L5-30P

NEMA L6-30P

NEMA L6-30P

Input

Voltage

Range

100VAC

IEC 60309 3P+E 9h 60A (IP44)

IEC 60309 3P+E 9h 60A (IP44)

NEMA L15-30P

NEMA L15-30P

NEMA L15-30P

200VAC

200VAC

200VAC

200VAC

200VAC

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

Input

Current per phase

20

100-200VAC 20

100VAC 30

200VAC

100VAC

200VAC

30

20

30

100VAC 30

100-200VAC 20

100VAC

200VAC

200VAC

30

30

30

16

32

32

16

32

60

60

30

30

30

Circuit

Breakers

0

2

2

2

0

2

2

0

0

2

2

6

0

0

6

6

3

3

6

6

3

Apparent

Power

(kVA)

1.9 kVA

3.3 kVA

2.9 kVA

5.0 kVA

1.9 kVA

5.0 kVA

2.9 kVA

3.3 kVA

2.9 kVA

5.0 kVA

5.0 kVA

17.3 kVA

17.3 kVA

8.6 kVA

8.6 kVA

8.6 kVA

11.0 kVA

22.0 kVA

22.0 kVA

11.0 kVA

22.0 kVA

Outlet

Count

8

12

16

16

16

24

24

24

24

38

38

24

30

6

6

42

6

24

6

24

36

(8)5-20R

(12)C13

(16)5-20R

Outlet

Type

(12)C13, (4)C19

(16)5-20R

(20)C13, (4)C19

(24)5-20R

(20)C13, (4)C19

(24)5-20R

(32)C13, (6)C19

(32)C13, (6)C19

(6)C19

(12)C13, (12)C19

(6)C19

(18)C13, (6)C19

(30)C13, (6)C19

(6)C19

(6)C19

(12)C13, (12)C19

(24)C13, (6)C19

(30)C13, (12)C19

JPN

JPN

JPN

JPN

0U FULL

1U

0U FULL

0U FULL

JPN 0U FULL - Wide

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

415VAC

415VAC

16

30

30

30

30

0

6

6

6

6

11.0 kVA

17.3 kVA

17.3 kVA

17.3 kVA

17.3 kVA

42

6

24

36

48

(36)C13, (6)C19

(6)C19

(12)C13, (12)C19

(24)C13, (12)C19

(48)C13

JPN 0U FULL + NEMA L22-30P 415VAC 30 6 17.3 kVA 42 (36)C13, (6)C19

Note: Minimum Order Quantity: 30 Pieces Per Part Number, Lead Time: 45 Business Days, Terms: Non-Cancellable / Non-Returnable

Output

Voltage

Panduit

Part Number

100 P12BF6M-BL6C

200 P12BF7M-BL6C

200 P12BF8M-BL6C

100 P16BF9M-BL1C

100 P16BG0M-BL6C

200 P20BG2M-BL1C

100 P22BG3M-BL1C

100 P22BG4M-BL1C

200 P22BG5M-BL1C

100 P22BH9M-BL1R

200 P24BG7M-BL1C

200 P42BH0M-BL1C

200 P42BJ0M-BL1R

200 P06B03M

240

240

240

240

240

240

200

200

200

200

200

200 P24B14M

200 P06BF5M-BL6C

200 P18BG1M-BL1C

200 P36BG8M-BL1C

200 P42BH1M-BL1C

P06B37M

P06B38M

P24B12M

P30B13M

P42B11M

P42B44M

P06B04M

P24B02M

P36B02M

P48B03M

P54B03M

Output

Voltage

Panduit

Part Number

100 P08DE8M-BL6C

200 P12DE9M-BL6C

100 P16DF0M-BL6C

200 P16DF1M-BL6C

100 P16DF2M-BL1C

200 P24DF3M-BL1C

100 P24DF4M-BL1C

200 P24DF5M-BL1C

100 P24DG9M-BL1R

200 P38DF9M-BL1C

200 P38DH0M-BL1R

240

240

240

240

240

240

240

240

240

240

240

200

200

P06D19M

P24D34M

200 P06DE6M-BL6C

200 P24DF6M-BL1C

200 P36DF8M-BL1C

P06D38M

P06D39M

P24D43M

P30D05M

P42D04M

P42D42M

P06D02M

P24D04M

P36D02M

P48D03M

P42D07M

SmartZone ™ G5 Basic & Intelligent Power Distribution Units (iPDUs) for Japan

Monitored Per Outlet (MPO)

Region

JPN

Form Factor

0U FULL

Input Plug Type

NEMA L6-30P

Input

Voltage

Range

Input

Current per phase

Circuit

Breakers

Apparent

Power

(kVA)

Outlet

Count

200VAC 30 2 5.0 kVA 24

Outlet

Type

(20)C13, (4)C19

JPN 0U FULL NEMA L6-30P 200VAC 30 2 5.0 kVA 36 (30)C13, (6)C19

JPN

JPN

JPN

JPN

JPN

JPN

JPN

JPN

0U FULL

0U FULL

0U FULL

0U FULL

0U FULL

0U FULL

0U FULL

0U FULL

IEC 60309 3P+E 9h 60A (IP44)

NEMA L15-30P

NEMA L15-30P

NEMA L15-30P

200VAC

200VAC

200VAC

200VAC

NEMA L15-30P 200VAC

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

32

16

30

16

30

30

60

30

6

0

3

0

3

3

6

3

17.3 kVA

8.6 kVA

8.6 kVA

8.6 kVA

8.6 kVA

11.0 kVA

22.0 kVA

11.0 kVA

24

36

36

24

36

36

24

24

(12)C13, (12)C19

(18)C13, (6)C19

(30)C13, (6)C19

(30)C13, (6)C19

(30)C13, (6)C19

(18)C13, (6)C19

(12)C13, (12)C19

(30)C13, (6)C19

JPN 0U FULL - Wide IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

JPN 0U FULL NEMA L22-30P 415VAC

JPN

JPN

0U FULL

0U FULL

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

32

30

30

30

6

6

6

6

22.0 kVA

17.3 kVA

17.3 kVA

17.3 kVA

36

24

24

24

(24)C13, (12)C19

(12)C13, (12)C19

(18)C13, (6)C19

(24)C13

JPN 0U FULL - Wide NEMA L22-30P 415VAC 30 6 17.3 kVA 36 (24)C13, (12)C19

JPN 0U FULL - Wide NEMA L22-30P 415VAC 30 6 17.3 kVA 36 (30)C13, (6)C19

JPN

JPN

0U FULL -

Wide+

0U FULL -

Wide +

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

30

30

6

6

17.3 kVA

17.3 kVA

48

48

(48)C13

(42)C13, (6)C19

Note: Minimum Order Quantity: 30 Pieces Per Part Number, Lead Time: 45 Business Days, Terms: Non-Cancellable / Non-Returnable

Monitored Switched (MS Series)

Region Form Factor Input Plug Type

Input

Voltage

Range

Input

Current per phase

Circuit

Breakers

Apparent

Power

(kVA)

Outlet

Count

Outlet

Type

Output

Voltage

Panduit

Part Number

Output

Voltage

Panduit

Part Number

200 P24FC0M-BL1C

200 P36FC3M-BL1C

240

240

240

240

240

240

240

240

200 P24F05M

200 P24FC1M-BL1C

200 P36FC5M-BL1C

200 P36FC9M-BL1B

200 P36FC9M-YL1B

240 P24F07M

240

240

P24F08M

P36F12M

P36F13M

P24F10M

P24F16M

P24F17M

P36F02M

P36F06M

P48F04M

P48F06M

JPN 0U FULL IEC 60309 3P+E 9h 60A (IP44) 200VAC 60 6 17.3 kVA 24 (12)C13, (12)C19 200 P24E32M

JPN

JPN

0U FULL

0U FULL

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

JPN 0U FULL IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

JPN 0U FULL - Wide IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

16

32

16

32

0

6

0

6

11.0 kVA

22.0 kVA

11.0 kVA

22.0 kVA

36

36

24

24

(18)C13, (6)C19

(12)C13, (12)C19

(30)C13, (6)C19

(24)C13, (12)C19

JPN

JPN

0U FULL

0U FULL

JPN 0U FULL

JPN 0U FULL - Wide

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

415VAC

415VAC

30

30

30

30

6

6

6

6

17.3 kVA

17.3 kVA

17.3 kVA

17.3 kVA

24

24

24

36

(12)C13, (12)C19

(18)C13, (6)C19

(24)C13

(24)C13, (12)C19

JPN 0U FULL - Wide NEMA L22-30P 415VAC 30 6 17.3 kVA 36 (30)C13, (6)C19

JPN

JPN

0U FULL -

Wide +

0U FULL -

Wide +

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

30

30

6

6

17.3 kVA

17.3 kVA

48

48

(48)C13

(42)C13, (6)C19

Note: Minimum Order Quantity: 30 Pieces Per Part Number, Lead Time: 45 Business Days, Terms: Non-Cancellable / Non-Returnable

240

240

240

240

240

240

240

240

240

240

240

P24E02M

P24E03M

P36E08M

P36E09M

P24E06M

P24E12M

P24E13M

P36E02M

P36E06M

P48E04M

P48E06M

SmartZone ™ G5 Basic & Intelligent Power Distribution Units (iPDUs) for Japan

Monitored & Switched Per Outlet (MSPO)

Region Form Factor Input Plug Type

Input

Voltage

Range

Input

Current per phase

Circuit

Breakers

Apparent

Power

(kVA)

Outlet

Count

Outlet

Type

Output

Voltage

Panduit

Part Number

JPN 0U FULL IEC 60309 3P+E 9h 60A (IP44) 200VAC 60 6 17.3 kVA 24 (12)C13, (12)C19 200 P24G05M

JPN

JPN

0U FULL

0U FULL

IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

JPN 0U FULL IEC 60309 3P+N+E 6h 16A (IP44) 415VAC

JPN 0U FULL - Wide IEC 60309 3P+N+E 6h 32A (IP44) 415VAC

JPN

JPN

0U FULL

0U FULL

JPN 0U FULL

JPN 0U FULL - Wide

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

415VAC

415VAC

16

32

16

32

30

30

30

30

0

6

0

6

6

6

6

6

11.0 kVA

22.0 kVA

11.0 kVA

22.0 kVA

17.3 kVA

17.3 kVA

17.3 kVA

17.3 kVA

24

24

36

36

24

24

24

36

(18)C13, (6)C19

(12)C13, (12)C19

(30)C13, (6)C19

(24)C13, (12)C19

(12)C13, (12)C19

(18)C13, (6)C19

(24)C13

(24)C13, (12)C19

JPN 0U FULL - Wide

JPN

NEMA L22-30P

NEMA L22-30P

415VAC

415VAC

30

30

6

6

17.3 kVA

17.3 kVA

36

48

(30)C13, (6)C19

(48)C13

JPN NEMA L22-30P 415VAC 30 6 17.3 kVA 48 (42)C13, (6)C19

Note: Minimum Order Quantity: 30 Pieces Per Part Number, Lead Time: 45 Business Days, Terms: Non-Cancellable / Non-Returnable

240

240

240

240

240

240

240

240

240

240

240

P24G07M

P24G08M

P36G15M

P36G16M

P24G10M

P24G18M

P24G19M

P36G02M

P36G06M

P48G04M

P48G06M

PANDUIT US/CANADA

Phone: 800.777.3300

PANDUIT EUROPE LTD.

London, UK

Phone: 44.20.8601.7200

WORLDWIDE SUBSIDIARIES AND SALES OFFICES

PANDUIT SINGAPORE PTE. LTD.

Republic of Singapore

Phone: 65.6305.7575

PANDUIT JPN

Tokyo, JPN

Phone: 81.3.6863.6000

PANDUIT LATIN AMERICA

Guadalajara, Mexico

Phone: 52.33.3777.6000

PANDUIT AUSTRALIA PTY. LTD.

Victoria, Australia

Phone: 61.3.9794.9020

For a copy of Panduit product warranties, log on to www.panduit.com/warranty

For more information

Visit us at www.panduit.com

Contact Customer Service by email: [email protected] or by phone: 800.777.3300

©2021 Panduit Corp.

ALL RIGHTS RESERVED.

PUSP83--WW-ENG

2/2021