Masport LE 3000/W Owner's Manual & Installation Manual

Add to My manuals
20 Pages

advertisement

Masport LE 3000/W Owner's Manual & Installation Manual | Manualzz

THE INSTALLATION AND OPERATING INSTRUCTIONS IN THIS

MANUAL APPLY TO THE FOLLOWING WOODFIRES:-

Free standing models:-

MASPORT HORIZON, HORIZON/S

MASPORT LE 2000, 2000/S, 2000/W

MASPORT LE 3000, 3000/S, 3000/W (Series 2 and 3)

MASPORT LE 5000, 5000/S, 5000/W (Series 2 and 3)

MASPORT SIENA, SIENA/S

MASPORT VERONA

MASPORT GRANDVIEW

MASPORT TORONTO

Fireplace Insert models:-

MASPORT LE 3000 PROVINCIAL (Series 2)

MASPORT LE 3000/S PROVINCIAL (Series 2)

MASPORT LE 3000/W PROVINCIAL (Series 2)

MASPORT LE 3000 PROVINCIAL (Clean Air Zone)

MASPORT LE 7000 PROVINCIAL (Series 3)

MASPORT GRANDE PROVINCIAL

Note: Models without a suffix have been emission tested using hardwood fuel.

Models /S have been emission tested for N.Z. without water boosters, using softwood fuel.

Models /W have been emission tested for N.Z. with water boosters, using softwood fuel.

CONTENTS OF LOOSE PARTS BAG (Freestanding models)

(Note: You may not need all these parts for your installation)

Part No.

Quantity

501682 10

Description

M6 Hexagon Nut

501703

501815

501959

503005

503259

503388

503459

595381

986413

4

4

1

2

2

2

4

4

6

M6 Flat Washer

M6 x 35mm Hex. Set Screw

M6 x 12mm Hex. Set Screw

Self Threading Screw —

12mm long, zinc plated finish

Self Threading Screw —

12mm long, black finish

‘C’ Nut (Spire # SNU 0537)

Self Threading Screw —

25mm long

Installing & Operating Manual

‘L’ Bracket

Where Used

4 — Pedestal front to pedestal sides

4 — Firebox to pedestal

2 — ‘L’ Brackets to pedestal

4 — Firebox to pedestal

4 — Firebox to pedestal

4 — Pedestal front to pedestal sides

2 — ‘L’ Brackets to pedestal

4 — Heat shield to top of pedestal

4 — Pedestal rear panel to pedestal

2 — Seismic restraint bar to pedestal

2 — Seismic restraint bar to pedestal

2 — Sides or rear of pedestal

6mm 12mm 25mm 35mm

CONTENTS

INTRODUCTION............................................................................2

FREE-STANDING MODELS — INSTALLATION

UNPACKING ..................................................................................3

ASSEMBLY ....................................................................................3

PEDESTAL .....................................................................................3

FAN .................................................................................................3

BOTTOM HEAT SHIELD ..............................................................3

POSITIONING ............................................................................4, 5

FLOOR PROTECTOR (HEARTH) REQUIREMENTS...............5, 6

CORNER FLOOR PROTECTORS (HEARTHS).............................6

FLOOR PROTECTOR (HEARTH) CONSTRUCTION...................7

INSTALLING THE FLUE...............................................................7

RECOMMENDED FLUE OPTIONS...........................................7, 8

FIXING IN POSITION ....................................................................8

FINAL ASSEMBLY ........................................................................8

INSTALLING A WATER HEATING BOOSTER ...........................9

WATER PIPE CONNECTION POSITIONS ...................................9

FIREPLACE INSERT MODELS — INSTALLATION

UNPACKING ................................................................................10

INSTALLATION REQUIREMENTS ............................................10

FIREPLACE ..................................................................................10

FLOOR PROTECTOR AND MANTEL-SHELF REQTS. .............11

MANTEL-SHELF SHIELDING ....................................................11

FLOOR PROTECTOR CONSTRUCTION ................................... 12

INSTALLING THE FIREBOX AND FLUE ..................................12

INTERNAL PARTS.......................................................................12

FASCIA .........................................................................................12

DOOR............................................................................................12

ASH SHELF OR LOWER GRILLE...............................................12

UPPER GRILLE ............................................................................12

INSTALLING A WATER HEATING BOOSTER .........................12

OPERATING INSTRUCTIONS — ALL MODELS

BASIC INFORMATION................................................................13

LIGHTING UP ........................................................................ 13, 14

OPERATING HINTS ....................................................................14

SAFETY ........................................................................................15

MAINTENANCE............................................................... 15, 16, 17

BEFORE EACH HEATING SEASON...........................................17

FAN WIRING DIAGRAMS...........................................................17

DIMENSIONS...............................................................................18

THIS BOOK CONTAINS IMPORTANT INFORMATION.

PLEASE KEEP IT IN A SAFE PLACE FOR FUTURE REFERENCE.

1

INTRODUCTION

In the interests of your safety, most building regulatory Authorities in Australia and New

Zealand require any woodfire installation to comply with Installation Standard AS/NZS 2918.

They may also have local requirements in addition to those in the Standard so you should approach your local Building Authority before commencing installation to establish whether you will require a Permit and whether you will need to meet extra requirements. All MASPORT

Woodfires have been tested to ensure that they will meet the appropriate safety Standard requirements if the instructions in this book are followed.

Woodfire models covered by this manual have been tested to demonstrate compliance with current emission requirements in Australia and New Zealand.

WE RECOMMEND THAT THE INSTALLATION OF YOUR MASPORT

WOODFIRE BE CARRIED OUT BY A QUALIFIED SPECIALIST INSTALLER.

IF ANY ELECTRICAL WORK IS REQUIRED, IT MUST BE CARRIED OUT BY A

LICENSED ELECTRICIAN.

ONLY THE MANUFACTURER, THE MANUFACTURER’S SERVICE AGENTS OR

SIMILARLY QUALIFIED PERSONS SHOULD REMOVE THE BOTTOM GRILLE

OF THE GRANDE PROVINCIAL OR THE ASH SHELF OF THE LE 7000

PROVINCIAL.

PLEASE ENSURE THAT ONLY COMPONENTS APPROVED BY MASPORT ARE USED

FOR THE INSTALLATION, as substitutes may adversely affect performance and might nullify compliance with the requirements of AS/NZS 2918.

WARNING: THE APPLIANCE AND FLUE SYSTEM MUST BE INSTALLED IN ACCORDANCE

WITH AS/NZS 2918 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING

CODE OR CODES.

WARNING: APPLIANCES INSTALLED IN ACCORDANCE WITH THIS STANDARD SHALL

COMPLY WITH THE REQUIREMENTS OF AS/NZS 4013 WHERE REQUIRED BY THE

REGULATORY AUTHORITY, I.E. THE APPLIANCE SHALL BE IDENTIFIABLE BY A

COMPLIANCE PLATE WITH THE MARKING ‘TESTED TO AS/NZS 4013’. ANY MODIFICATION

OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITNG BY THE TESTING

AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR

COMPLIANCE WITH AS/NZS 4013.

CAUTION: MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT SOURCES

OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN

HAZARDOUS CONDITIONS. WHERE SUCH ACTION IS CONSIDERED, THE MANUFACTURER

SHOULD BE CONSULTED IN THE FIRST INSTANCE.

CAUTION: CRACKED AND BROKEN COMPONENTS, e.g. GLASS PANELS, MAY RENDER THE

INSTALLATION UNSAFE.

Additionally, for woodfires using water heating devices:-

WARNING: DO NOT CONNECT TO AN UNVENTED HOT WATER SYSTEM. INSTALL IN

ACCORDANCE WITH AS 3500.4.1 OR NZS 4603 AND THE APPROPRIATE REQUIREMENTS OF

THE RELEVANT BUILDING CODE OR CODES.

Some areas in New Zealand and Australia have special emission regulations and MASPORT woodfires are approved for use in those areas. Approval has been given provided that no modifications are made to the appliance.

In New Zealand areas covered by emission regulations:-

(I) If a water heating device is permitted, it must be factory fitted or be a Masport accessory retro-fitted strictly in accordance with the instructions supplied by Masport.

(II)

(III)

Coal must not be used as a fuel.

Wood fuel must have a moisture content of less than 25%.

2

FREE-STANDING MODELS

(See page 11 for in-built models)

UNPACKING

After removal of the shipping carton, open the door and lift it from its hinges. Do not remove the polystyrene packers above the top baffle at this stage. Do NOT discard the top baffle. Remove the pedestal components from the firebox in the case of fires requiring pedestal assembly.

Remove and discard the four bolts holding the woodfire to the shipping pallet.

Remove the woodfire from the pallet, lifting only from the lower edge of each side.

DO NOT LIFT BY THE LOWER FRONT PANEL OR THE REAR PANEL.

ASSEMBLY OF FREE-STANDING MODELS

The table inside the front cover of this guide will help you identify the various fastenings.

PEDESTAL.

Some models are shipped with the pedestal dis-assembled

.

For these ones, the first step is to assemble the pedestal. Secure the two pedestal sides to the front, using four M6x12 set screws and taking care that the bottom flanges of the side panels align with the bottom flange of the front panel. The side with the square hole for the fan switch goes on the right (as viewed when looking at the front of the front panel). The top flange of the front panel will be above the top flanges of the side panels. Fit the slotted pedestal rear panel using the four black 12mm long self threading screws (sharp points).

FAN. If you intend installing a fan (available as an accessory), assemble the pedestal completely to the heater (if not already assembled). The fan is best fitted after the fire has been moved close to its final position. Then remove the rear pedestal panel and install the fan instead of the rear panel.

BOTTOM HEAT SHIELD. Using the four zinc plated 12mm long self threading screws (blunt points), screw the heat shield to the top of the pedestal assembly with the turned up ends of the heat shield facing upwards. Check that the pedestal foot and trim (if any) will fit snugly around the assembled pedestal before tightening all assembly screws fully.

Roll the woodfire carefully onto its back, using the flattened carton to protect the floor.

Taking care that the slotted pedestal rear panel will be at the rear, attach the pedestal and heat shield assembly to the firebox using the four M6x 35 set screws, four M6 flat washers and four M6

Hexagon nuts. Place the washers on the set screws and pass the screws from inside the firebox through the holes in the pedestal. In the case of the Horizon, Siena and LE 2000, two of the screws pass through holes in the heat shield. The nuts will be inside the pedestal. Check the alignment of the pedestal before tightening the nuts firmly.

Roll your woodfire carefully back into the upright position.

3

POSITIONING YOUR FREE-STANDING WOODFIRE

Free-standing woodfires must not be installed in a fireplace or alcove, or under a ceiling of less than

2.3m height. No wall or other fixed object may be closer to the front of the woodfire than one metre.

When fitting a water heating tube, the woodfire should be close to the water cylinder (See page 9).

Determine the installation position for your woodfire only after considering the necessary clearances

(See Tables below) and checking the practicability of installing the flue system. Regard heat resistant walls with heat sensitive surface treatments (e.g. wallpaper or heat sensitive paints) as heat sensitive walls. The flue shielding and the 25mm outer clearance gap above the ceiling will occupy a diameter of 300mm (Grandview and Toronto 325mm), and this space must be available without the removal of structural beams. Flue installations other than strictly vertical ones are possible. See AS/NZS 2918 for information on non-vertical flues and flues passing through walls and eaves.

NEW ZEALAND — MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm) ‡

Model Flue Heat Shield A B C D E F R§

Horizon &

LE 2000

Siena

LE 3000 &

LE 5000

Verona

Toronto

Grandview

YES - 1200mm ¶ 50

NO 300

YES - 1200mm ¶ 100

NO 360

YES - 1200mm ¶ 75

NO

YES - 1200mm ¶ 125

NO

YES - 900mm ¶

NO

YES - 900mm ¶

NO

125

475

200

450

300

300

250

250

300

300

400

400

350

350

220

470

270

530

578

578

528

528

300 630

Not Tested

345 630

Not Tested

320 730

670 730

395

645

730

730

50

150

50

230

50

125

50

300

50

250

355

455

355

535

405

480

425

675

458

658

500

645

500

760

575

680

600

955

650

930

¶ All Flue Heat Shields polished stainless steel with top heat dispersal cap.

See note under minimum New Zealand floor protector dimension table (page 5).

AUSTRALIA

MINIMUM DISTANCES TO HEAT SENSITIVE WALLS (mm) ‡

WITH THE APPROPRIATE FLUE HEAT SHIELD

Model A B C D E

Horizon

LE 2000

Siena (with flue shield)

Siena (without flue shield)

LE 3000 and LE5000

Verona

Toronto

Grandview

150*

125

150

360

150*

250†

125

150

350

325

250

250

325

300

350

350

320*

295

320

530

375*

470†

320

345

628

603

528

528

655

630

680

730

100

100

100

230

125

125

100

100

‡, §, *, ,

— See next page.

F

405

405

405

535

480

480

475

508

R §

575

575

575

760

680

680

675

720

4

* May be reduced by 25mm if a polished stainless steel flue shield is fitted instead of an enamelled one.

May be reduced by 50mm if a polished stainless steel flue shield is fitted instead of an enamelled one.

† May be reduced by 125mm if a polished stainless steel flue shield is fitted instead of an enamelled one.

§ Valid only when the room walls are at 90° to each other.

Note: Clearances are for fire hazard only. For durability of finishes or surfaces you should contact the relevant manufacturer for their specification. Masport accepts no responsibility for the deterioration of surfaces or finishes.

See INSTALLING THE FLUE for recommended Australian flue systems.

FLOOR PROTECTOR (Hearth) REQUIREMENTS — Free - standing models

Unless your woodfire will be standing on an un-covered fireproof floor (containing no combustible material) extending at least 500mm from the appliance, it will be necessary to provide a floor protector (hearth). See page 7 for construction details. Where the minimum size requirements bring the side of the floor protector nearly to a wall, it is advisable to extend the protector to meet the wall.

W

Heat sensitive wall K J

Minimum allowable

'A' dimensions are shown on page 4.

A

G

H

C

#

S

#

L

Gl ass

\

Minimum Floor

Protector Dimensions

540 min.

(565 min. for

Grandview & Toronto)

# Dimensions in the table are valid only when the fire is exactly at

its minimum allowable wall clearance.

NEW

ZEALAND

A # C # G H J K L W S #

Ash

Floor

Prot.

Insul

Floo r

Prot.

Flue Shield Flue Shield Flue Shield

YES NO YES NO YES NO Ø Ø

Horizon, LE 2000 50 300 220 470 170 435 555 160 300 875 785 1035 Yes Yes

Siena 100 360 270 530 170 490 555 160 300 875 890 1150 Yes Yes

LE 3000 75

LE 3000 with ash shelf 75

300

300

225 490 660 138 420¥ 935 985¥ –

225 490 660 138 300 935 865 –

No Yes

Yes Yes

LE 5000

Verona

Toronto

75

125

300

345

225 490 660 138 300 935 865

220 560 660 140 300 940 985

Yes Yes

Yes Yes

125 475 320 670 195 540 660 153 300 965 965 1315 Yes Yes

Grandview 200 450 395 645 195 610 760 103 520¥ 965

1330

¥

1580

¥

No Yes

¥ Increase by 80 mm if the floor protector top is not at least 50 mm above the floor.

ø See page 7 for minimum constructional requirements.

# Valid only when the fire is exactly at its minimum allowable wall clearance.

NOTE: Where a fan is being fitted, you may prefer to increase the ‘A’ dimension to 100 mm to provide easier access for servicing. If so, the amount you add to ‘A’ to bring it to 100 mm must also be added to the ‘C’ and ‘S’ dimensions.

5

AUSTRALIA

A # C# G H J K L W S #

Horizon (with flue shield)

LE 2000 (with flue shield)

Siena (with flue shield)

150* 320* 170 435 555 160 300 875 885*

125 295 170 435 555 160 300 875 860

150 320 170 490 555 160 300 875 940

Siena (without flue shield) 360 530 170 490 555 160 300 875 1150

LE 3000 & LE 5000 (with fl. shld) 150* 375* 225 490 660 138 350 935 990*

Verona (with flue shield) 250† 470† 220 560 660 140 300 940 1110†

Toronto (with flue shield) 125 320 195 540 660 153 300 965 965

Grandview (with flue shield) 150 345 195 610 760 103 300 965 1060

* Reduce by 25mm for a polished stainless steel heat shield instead of an enamelled one.

Reduce by 50mm for a polished stainless steel heat shield instead of an enamelled one.

† Reduce by 125mm for a polished stainless steel heat shield instead of an enamelled one.

CORNER FLOOR PROTECTORS (Hearths)

While the information in the previous section details the MINIMUM size of floor protector necessary to comply with the Safety Standards, it may often be desirable to use a somewhat larger size for aesthetic reasons. A particular example is when the woodfire is installed diagonally in a corner. It will be more practical to carry the protector right into the corner and shape it as shown. The chart facilitates calculation of the MINIMUM dimensions required for floor protectors of this shape.

Minimum allowable values for dimension ‘E’ are given in the tables on page 4.

E

Y

X

E

Y

X

Corner Floor

Pr ote ct or

Ar ran gem en t

MINIMUM DIMENSIONS — mm

See pages 6, 8 for construction.

Horizon,

LE 2000

Siena

LE3000

With Shelf

Without Shelf

LE 5000

With Shelf

Without Shelf

With Shelf

Without Shelf

Verona

Toronto With Shelf

Without Shelf

Grandview

AUSTRALIA

X

980

980

970

1025

1100

880

880

880

980

980

Y

605

605

655

625

725

560

560

600

605

605

NEW

ZEALAND

X Y

880

880

950

1035

950

970

1015

1250

565

600

570

650†

570

655

640

890†

Your measurement ‘ E’ must be added to ‘ X’ and ‘ Y’ to find the appropriate minimum overall floor protector dimensions.

See page 4 for minimum values of ‘ E’.

Increase ‘ Y’ by 120mm if the floor protector top is not at least 50mm above the floor.

6

FLOOR PROTECTOR (Hearth) CONSTRUCTION

In Australia the minimum floor protection requirement is a sheet of 6mm fibre cement board. It is usually fastened directly to the floor.

In New Zealand, some woodfires must have an insulating floor protector. (See page 5). All other current models may be installed on an ash type floor protector. Of course, all models may be installed on insulating floor protectors if desired. The necessary minimum construction details for ash and insulating floor protectors are shown below, and such constructions are suitable for use on solid timber or particle board floors. Bricks or concrete in contact with the flooring material do NOT provide the required insulation. If the floor within 500mm of the appliance is concrete and has no combustible material in contact with it, a floor protector is not required. In this case, if tiles or pieces of slate etc. are required for decorative purposes, they may be fixed directly to the concrete floor.

In both countries, the protector must extend right under the woodfire and a durable top surface will be needed to resist damage from heat or dropped embers. Obvious surface materials are slate, bricks and ceramic tiles. Any gaps in the top surfacing material must be grouted to prevent the penetration of embers. A trim moulding will provide a neat edge finish.

Australia — One sheet 6mm fibre cement board.

New Zealand — Insulating Floor Protectors:- Two sheets of MICORE160 or one sheet of WOODTEX (35 thick).

Ash Floor protectors:- One sheet 6mm fibre cement board,

(e.g. Hardies TILE & SLATE UNDERLAY)

Timber or Particle

Board Floor

Ceramic tiles, slate etc.

Trim moulding

Minimum Floor

Protector (Hearth)

Construction

Requirements

INSTALLING THE FLUE

You MUST use a flue system which complies with the current installation Standard AS/NZS 2918.

Full instructions are supplied with the flue kit, and these must be followed closely, including the minimum flue exit height from the top of the floor protector and the minimum exit height above the roof line or roof ridge as illustrated in the instructions. Always seal the flue to the flue socket of the firebox using firebox cement or fibreglass rope.

Only flue systems tested with your particular model are approved for use at the tabled clearances.

TESTED AUSTRALIAN 150mm FLUE OPTIONS: (For all models except Toronto and Grandview)

Acorn Metal - Special Insulated Flue Kit with 900mm 120Ëš polished reflector.

Benja Pty Ltd - Benja Mk II with 900mm decorative heat shield with 120Ëš solid back. (Not tested on Verona)

Floate Metal - Flomet Super Single with full length decorative heat shield with 120Ëš solid back.

Shamic Sheetmetal - Model 1A with full length decorative heat shield with 180Ëš solid back.

(Not tested on Verona)

Statewide Heating - Model M1 with 900mm half-round enamelled flue shield.

Woodland Fireplaces - Woodland Double Flue System with flat ceiling plate and 900mm

180Ëš stainless steel heat shield. For LE3000 Series 2, LE 5000 Series 2, and Verona only.

TESTED AUSTRALIAN 178mm (7”) FLUE OPTIONS:- (For Toronto and Grandview models)

Acorn Metal - Special Insulated Flue Kit with 900mm long half-round enamelled mild steel or polished stainless steel flue shield.

Floate Metal - Flomet 7” Super Single flue system with full length perforated decorative heat shield with 120Ëš solid back. The ceiling plate has a 200mm diameter collar extending down

100mm surrounding the decorative shield.

Statewide Heating - Standard 7” Flue Kit with 900mm long half round polished stainless steel flue shield. (Not tested with Toronto)

7

TESTED NEW ZEALAND FLUES: In New Zealand we recommend the use of genuine Masport flue kits or kits approved by Masport. The flue MUST be installed in accordance with the detailed instructions accompanying it. Grandview & Toronto ceiling plates must be at least 450mm square. A flue heat shield (including a top dispersal cap), as detailed on page 4, must be fitted at the back of the flue

(directly above the stove) to achieve the reduced wall clearances shown in the table. The Masport flue heat shield kit for 150mm flues is Part No 551481, while the kit for 178mm flues is Part No 551793.

Kits include mounting brackets and heat dispersal caps.

OTHER FLUE SYSTEMS

Flues and flue heat shields other than those listed above may be used, but if they have not been tested with these heaters, their installation clearances will be those specified in AS/NZS 2918:2001 for untested flue installations. Unless otherwise specified on page 4, all heat sensitive wall material must be kept at least 600mm away from any flue which is not fitted with a flue heat shield.

FIXING THE WOODFIRE IN POSITION

Once the flue shielding system has been installed through the ceiling and roof, the woodfire can be placed in its approximate position on the floor protector, and the flue pipes installed. Finally adjust the stove position making sure the flue is vertical and that the necessary minimum woodfire-to-wall distances are being achieved. In New Zealand and some parts of Australia, Standards require that the woodfire and floor protector be secured to prevent shifting in the event of an earthquake. This is best done by fastening the woodfire right through the protector to the floor, using two screws not less than 12 gauge, or the equivalent size of coach bolts or toggle fasteners. Anchor the appliance through the holes in the seismic restraint bracket at the rear of the pedestal or in the two angle brackets supplied. The angle brackets attach at each side of the pedestal (except for some of the smaller models, where they attach at the rear). The pedestal can be fastened to the seismic restraint bracket either before or after fitting the anchor screws. The small centreline hole in the bracket will help in pre-positioning it.

FINAL ASSEMBLY

Before using the woodfire, confirm that the internal firebox components are in their correct positions.

(See ‘FIREBOX LINERS” in the Maintenance section).

Reach down through the flue spigot and carefully remove the polystyrene packing above the firebox top baffle, remembering that the baffle can be broken by rough handling. Make sure that the baffle is correctly placed on top of the supporting shelves at each side of the firebox, and that it is back far enough for the two front corners to drop behind the retaining ribs on top of the shelves. On some models, a metal reinforcing channel is provided for the baffle. Fit this along the edge of the baffle nearest the door.

If you need to remove the top baffle, first withdraw the secondary air tube following the instructions in the Maintenance section.

In cases where a pedestal foot is to be fitted, simply fit the trim into the foot and slide the assembly onto the pedestal, keeping the foot in contact with the Floor protector all the time to avoid marking the finish on the sides of the pedestal.

Finally, spread the sand provided evenly over the bottom of the firebox and refit the door, if necessary, before lighting the first fire.

8

INSTALLING A WATER HEATING BOOSTER

Water heating booster tubes can be fitted to some woodfires installed in New Zealand in areas other than the Christchurch and Canterbury clean air zones. Booster tubes are not available in Australia.

Fitting a water booster tube converts an /S model into a /W type. If a tube is retro-fitted, in some cases the air metering plate must be changed to ensure that emission requirements are still met. Only the models listed in the table below may be installed in the ‘clean air’ zones, and in some cases other components will be required in addition to the water tube. (See the table below). The air metering plate is fitted directly behind the sliding plate that controls the stove heat output, and it can be reached by removing the air control knob (remove the screw underneath), and lifting off the air grille.

Water booster tube holes are provided and plugged in the back wall of the free-standing firebox and the side walls of the in-built model. All plumbing work must meet the requirements of NZS 4603 unless local building regulations dictate otherwise. Pipe connections are 1” BSP and the pipe positions are illustrated below. Special piping methods must be followed to ensure effective circulation, and the hot water cylinder will need to have an internal riser pipe to two thirds of the cylinder height to discourage unwanted water circulation when the woodfire is not burning. This internal riser pipe must be connected to the return pipe from the woodfire.

THE SYSTEM MUST BE VENTED. See the warning on page 2.

For effective circulation, the pipes from the woodfire should rise at the rate of one in five toward the storage cylinder, and ideally the cylinder should be within three metres of the woodfire. Detailed piping instructions are included in the conversion kit, but two safety requirements deserve special emphasis.

THERE MUST BE NO NON-RETURN OR SHUT-OFF VALVES IN THE PIPES BETWEEN

THE WOODFIRE AND THE STORAGE CYLINDER.

A WOODFIRE FITTED WITH A WATER HEATING BOOSTER MUST NOT BE FIRED

UNLESS IT IS CONNECTED TO A VENTED STORAGE CYLINDER FILLED WITH WATER

FREE TO CIRCULATE.

Return

170

340

Inlet

20

Return

Inlet

50

300

630 Toronto

590 Grandview

520 Verona

520 LE 3/5000

#

475 Siena

450 LE 2000 / Horizon

55

334

Free-standing Models

Viewed from Rear

Water Pipe Connection Positions

In-built LE 3000 Models

#

#

CAUTION: This dimension has recent ly been increased. Always check all t he pipe posit ions on your heat er bef ore inst alling t he pipew ork.

Front

9

FIREPLACE INSERT MODELS

(See page 3 for free-standing models)

NOTE.

The following instructions cover the installation of any Provincial heater into a sound masonry fireplace with an integral masonry chimney. Where such a chimney is not available, the heater can be installed into a timber framed structure provided that it is mounted in a special ‘built in’

(or ‘zero clearance’) metal shielding box. Built-in (zero clearance) installation kits and the special flue components necessary are available from your Masport Dealer. Full assembly instructions are included in the kit.

All Provincial models (Australian and New Zealand), can be fitted with air circulating fans. These are mounted inside the ash shelf (below the firebox door) in the case of LE 3000 and LE 7000 models.

The Grande Provincial fan is mounted below the firebox at the rear of the steel shielding box. (Fans are not permitted in Provincial fires installed in the Clean Air Zones of Christchurch and Canterbury).

Fascia extending kits are available for the LE 3000 Provincial models to extend the fascia size from

660 high by 810 wide to 700 high by 900 wide to suit larger than normal fireplace openings. [Part No

986580 (black)].

UNPACKING

After removal of the shipping carton from the assembled heater, remove any shipping restraints, remove the retaining screw under the control knob and pull it off. Lift the top grille clear. To avoid the risk of electric shock or contact with moving parts, only the manufacturer, the manufacturer’s service agents or similarly qualified persons should remove the bottom grille of the Grande Provincial or the ash shelf of the LE 7000 Provincial.

To release the bottom grille or ash shelf, it will be necessary on some models to turn the retaining screw(s) underneath it anticlockwise one quarter of a turn. Swing the bottom away from the heater and lift clear. Remove six screws holding the fascia and lift it clear, paying particular attention to the exact positioning of any electrical wiring connections so that they can be re-assembled correctly later.

Keeping the fire upright, release it from the shipping pallet by unscrewing the shipping bolts.

INSTALLATION REQUIREMENTS

Please read the INTRODUCTION on page 2, as this applies also to in-built models.

FIREPLACE

For a safe installation the following matters must be attended to.

• The masonry fireplace and chimney must be thoroughly cleaned and checked for soundness.

• The chimney must not connect to a second fireplace.

• The joint between the chimney face and the fireplace surround must be checked and sealed to prevent leakage if necessary.

• Heat sensitive materials on the wall each side of the fireplace recess must not be closer to the recess centreline than 595 mm for the LE 3000 Provincial, 615 mm for the LE 7000 Provincial and 660 mm for the Grande Provincial. Above the recess, such materials must not be closer to the recess base than

1235 mm (all models), but this figure may be reduced to the ‘D’ dimension (see the Table on page 11) corresponding to the intended mantelshelf width or to the ‘D’ dimension for the smallest shelf width if no shelf is to be fitted.

• In New Zealand, the LE 3000 Provincial can be installed in a masonry fireplace even though the fireplace has not been constructed to meet the timber-to-masonry separation requirements specified in the Building Code and even though timber is in contact with the outside of the masonry. Where New

Zealand fireplaces can be shown to comply with those separation requirements, the LE 7000 and

Grande Provincial models can be installed. As noted above, all models can be installed in a timber framed enclosure fitted with a specially designed metal shielding box. In Australia, all models may be installed in any sound masonry fireplace equipped with a sound masonry chimney. Further, they may be installed in a masonry enclosure by following the requirements detailed in AS/NZS 2918. Again, they may also be installed in a timber framed enclosure fitted with a shielding box as mentioned above.

• A flue pipe must be fitted right up the chimney, and the space between the flue pipe and chimney must be ventilated at the top. The area of this vent must be not less than 10,000mm

2

. The vent must be fitted with means to prevent significant ingress of water and debris. The flue must be free to move up and down at the top as it expands and contracts with temperature changes. This movement can be

25mm or more.

10

FLOOR PROTECTOR AND MANTEL-SHELF REQUIREMENTS

«

NOTE: Where a floor protector is shown as having zero height, its dimensions define the limits to which a heat sensitive floor covering may extend toward the heater. Since the floor within these boundaries will have no protective insulation, it will need to be heat resistant (e.g.concrete with no timber in contact).

MINIMUM FLOOR PROTECTOR SIZES (mm)

NZ LE 3000 Provincial

Australia LE 3000 Provincial

NZ and Aust LE 7000 Provincial

H

X to surround

X to glass

W

H

X to surround

X to glass

W

H

X to surround

X to glass

W

47 or more

330

300

60 or more

300

330

50

325

355

935

Any height

375

405

935

44

336

306

37.5

349

319

935

25

400

430

25

373

343

Zero «

450

480

Zero «

430

400

NZ and Aust. Grande Provincial H

X to surround

X to glass

W

94 or more

335

300

75

373

338

50

418

383

965

44

429

394

25

466

431

Zero «

500

465

MANTEL-SHELF DIMENSIONS and SIDE WALL CLEARANCES (mm)

NZ LE 3000 Provincial

Australia LE 3000 Provincial

NZ and Aust. LE 7000 Provincial

NZ and Aust. Grande Provincial

A minimum

225

225

180

185

B

810

810

1000

1095

C minimum

295

565

565

260

590

290

590

D minimum

955

1225

1225

980

1310

1080

1380

E maximum

75

250

250

150

250

150

250

MANTEL-SHELF SHIELDING

Mantel-shelves wider or lower than those specified above can be used provided that they are fitted with metal heat shields below them. We recommend a sheet metal shield fixed 20mm below the undersurface of the shelf on non-combustible spacers. The shield must abut the wall beneath the mantelshelf and protect the entire depth of the under-surface of the shelf. It must extend outwards at least 200mm from each side of the appliance or to the ends of the shelf if this is a shorter distance.

The 20mm air space under the shelf must be open at the ends and front to allow free circulation.

11

FLOOR PROTECTOR CONSTRUCTION

Where the original masonry floor protector in front of the fireplace is not large enough, the extension must be securely fixed to the floor, and the joint between the extension and the original masonry must be sealed to prevent entry of ash or embers. The extension should consist of a 6mm layer of fibre cement such as Hardies Tile and Slate Underlay, topped with decorative tiles or slate. Additionally, in

New Zealand there should be one layer of Micore 160 beneath the fibre cement sheet. A decorative trim can be fitted around the edges to tidy up the construction.

INSTALLING THE FIREBOX AND FLUE

The flue recommended for use in Australia is a stainless steel chimney kit such as the Shamic #4. In

New Zealand, we recommend the use of the Masport Provincial flue kit.

Measure the fireplace recess and remove bricks as necessary to accept the firebox outer case which is

560mm high, 590mm wide and 460mm deep for the LE 3000 models. The LE 7000 case is 595mm high, 630mm wide and 485 deep, while the Grande Provincial is 670mm high, 720mm wide and

485mm deep. Clear away any rubble and inspect and seal the chimney and fireplace as detailed under

INSTALLATION REQUIREMENTS.

Remove the polystyrene packing from above the baffle taking care not to damage the baffle.

Check the distance back from the face of the surround to the centre of chimney to determine whether the flue will mate with the flue socket in the stove without requiring an offset. If an offset is needed, fix it to the lower end of the assembled flue sections in the chimney and lift the flue assembly up while the firebox case is pushed back into the recess. Verify that the case will be fully supported in a level position when installed. Slide the case in and adjust its position so that its flange is in line with the face of the surround. (If a fascia extending kit is being used on the LE 3000, the flange should be

10mm forward from the surround face).

Where seismic restraint is necessary, screw the case to the base of the fireplace recess with at least two 12 gauge screws through the holes in the bottom panel of the firebox outer case.

If space above the case for positioning and fixing the flue is limited, access can be provided by sliding out the top front section of the case. Alternatively, the top baffle inside the firebox may be removed for access purposes. Removal is described in the MAINTENANCE section under FIREBOX TOP

BAFFLE. The flue can then be lowered into position.

Seal the flue at the firebox spigot using fire cement or fibreglass rope. Secure the flue to the spigot .

Re-fit the sliding panel with the insulating blanket on top of the LE 3000 in New Zealand. Do not forget to replace the baffle and secondary air tube if they have been removed.

Instructions for fixing and weather-proofing the top end of the flue are supplied with the flue kit.

INTERNAL PARTS

Check for correct positioning. See ‘FIREBOX LINERS’ in the Maintenance section.

FASCIA

Re-assemble the fascia to the firebox case, fitting the wiring exactly as shown on page 17.

DOOR

Hook the bottom pivot over the lower end of the hinge pin and lift the door up until the top pivot drops over the top end of the hinge pin.

ASH SHELF OR LOWER GRILLE

To avoid the risk of electric shock or contact with moving parts, only the manufacturer, the manufacturer’s service agents or similarly qualified persons should remove the bottom grille of

the Grande Provincial or the ash shelf of the LE 7000 Provincial. To fit the grille or shelf, hang it on the posts at the bottom of the fascia, taking care to feed the mains flex for the fan through the fascia side panel as the shelf is lowered into position. Hook the top on first, then swing the bottom into position. If a retaining screw (or screws) is fitted underneath, align the screw with the socket and press inward gently on the screw head until it ‘clicks’ into engagement.

UPPER GRILLE (or fascia)

The primary air control knob must be removed before the upper grille can be fitted or removed. It is retained by a Phillips-head screw from underneath. To avoid damaging the knob, check that the screw hole and the hole in the plate are in line before replacing the screw.

INSTALLING A WATER HEATING BOOSTER (LE 3000 Provincial in New Zealand only).

The necessary piping arrangements must be made for this before the case is fitted into the recess. The tube may be fitted on either side of the firebox, and the plumbing requirements are the same as those for the free-standing models. See page 9 for details.

12

OPERATING INSTRUCTIONS — ALL MODELS

BASIC INFORMATION

DOOR HANDLE

Front mounted handles. Swing the door open and shut with the handle in the 1 o’clock position.

Latch the door shut by pushing in on the handle and turning it to the 4 or 5 o’clock position.

Side mounted handles. The door is opened by pulling forward on the lower part of the handle. Hold the handle in this forward position when shutting the door, finally pushing it back to vertical to lock the door.

HEAT OUTPUT CONTROL

This control has a sliding action. It is clearly marked with a wedge shaped symbol. Slide the control in the direction of the wide end of the wedge (to the right) to increase the heat output and toward the narrow end (to the left) to decrease it. A high fire can be shut down rapidly only by starving it of air, and this will result in undesirable emissions. For this reason, Masport woodfires are designed to settle down to lower heat outputs comparatively slowly.

OVERNIGHT BURNING

Old fashioned stove designs attempted to achieve long burn times by starving the fuel of air, thus creating over-rich fuel/air mixtures and emitting pollutants. Modern designs avoid pollution by eliminating air starvation. This might seem to rule out overnight burning, but this is not so provided that a suitable fuel is used. Hardwood fuels give longer low-burn times than softwoods, while thicker pieces of fuel burn longer than thin ones.

FAN OPERATION

The LE 7000 and Grande Provincial models should not be operated on maximum heat with very dry softwood unless the fan is operating. Using the fan, except when the fire is set on LOW, will improve the heating efficiency and distribution of warm air in the room.

ESSENTIAL ADVICE

• Correct installation, the use of only DRY wood and adherence to the following instructions will ensure satisfactory performance.

WARNING: MAKE SURE THE MINIMUM HEATER-TO-WALL DISTANCES SHOWN ON

PAGES 4 AND 5 ARE ALWAYS MAINTAINED BETWEEN THE HEATER AND ANY HEAT

SENSITIVE ITEMS. ( FURNITURE, DRAPES, ETC.)

WARNING: DO NOT STORE FUEL WITHIN THE HEATER INSTALLATION CLEARANCES.

WARNING: DO NOT USE FLAMMABLE LIQUIDS OR AEROSOLS OR PLACE THESE IN THE

VICINITY OF THIS APPLIANCE WHEN IT IS OPERATING.

WARNING: THIS APPLIANCE MUST NOT BE USED AS AN OPEN FIRE.

WARNING: WHEN FITTED WITH A WATER HEATING BOOSTER, THIS APPLIANCE MUST

NOT BE CONNECTED TO AN UNVENTED HOT WATER SYSTEM. THIS APPLIANCE MUST

BE INSTALLED WITH AN OPEN VENT. THERE MUST BE NO SHUT-OFF OR NON-RETURN

VALVES IN THE PIPING SYSTEM. REFER TO WATER PIPE INSTALLATION

INSTRUCTIONS.

LIGHTING UP

CAUTION: THIS APPLIANCE SHOULD BE MAINTAINED AND OPERATED AT ALL TIMES

IN ACCORDANCE WITH THESE INSTRUCTIONS

Before lighting the first fire, spread the sand provided evenly over the floor of the firebox.

Subsequently, always leave sand or ash to the level of the tops of the floor ribs.

Slide the heat output control fully to the hot position.

Crumple up several double sheets of newspaper and place them in the centre of the firebox. Build a pyramid of thin, dry kindling wood on the paper with some heavier pieces on top. Light the paper at the bottom and leave the door slightly ajar until the kindling has ‘caught’, then latch the door shut firmly.

WARNING: DO NOT USE FLAMMABLE LIQUIDS OR AEROSOLS TO START OR REKINDLE

THE FIRE.

WARNING: ALWAYS MOVE THE AIR CONTROL TO THE OPEN POSITION (TO THE RIGHT)

BEFORE OPENING THE FIRING DOOR.

13

When the kindling is well alight, open the door slowly and add some larger pieces of wood.

Do not throw fuel pieces into the firebox as this could damage the top baffle and the insulating boards or firebricks.

Close and latch the door firmly.

Move the heat output control away from the maximum position only after the fire is well established.

A new woodfire should not be run at higher than half setting beyond the first 30 minutes until it has been used for a total of 8 hours. Once fully ‘run in’, we recommend running at full heat for up to one hour after lighting as this will minimise creosote build-up in the flue. The control can then be set wherever desired.

The special high temperature paint on the firebox will emit some smoke as it cures during the first few minutes of running. This is quite normal.

CAUTION: THIS APPLIANCE SHOULD NOT BE OPERATED WITH A CRACKED GLASS

OPERATING HINTS FOR CLEAN BURNING AND BEST EFFICIENCY

FUEL: USE ONLY WOOD THAT HAS BEEN AIR DRIED IN A SHELTERED WELL

VENTILATED STACK, PREFERABLY FOR AT LEAST 12 MONTHS. If moist fuel must be used, add it only to a really hot fire, mixing it with a large proportion of dry fuel. In Clean Air Zones, only wood may be used as fuel, and it must have a moisture content not greater than 25% (measured on a wet weight basis).

• Do not burn driftwood, as salt will corrode the woodfire.

CAUTION: THE USE OF SOME TYPES OF PRESERVATIVE TREATED WOOD AS FUEL

CAN BE HAZARDOUS.

• Add fuel reasonably often. A large fuel load placed on a dying fire can drop combustion temperatures undesirably.

• Avoid large smouldering fires. A small intense fire is more efficient.

• Move the heat control to maximum for a minute or so and turn off the air circulating fan (if fitted) before opening the door on a low burning fire. This will clear away any fumes in the firebox.

• Always open the door SLOWLY, and close and latch it shut securely again as soon as possible after re-loading.

• When loading fuel, place the pieces of wood in a front-to-back direction to ensure good air access and the cleanest possible burning. In the Christchurch Clean Air Zone, load the fuel from side to side in the LE 3000 model. Wood pieces for the Provincial Clean Air Zone (Christchurch) model should be generally about 250mm long, and should not exceed 300mm in length.

Load fuel carefully to avoid damage to the insulating boards, firebricks or top baffle.

• If smoke wafts into the room while the door is open, first check that make-up air can flow freely into the room to replace the air passing up the flue. (See box below). Then check that the flue is not obstructed in any way, particularly by the rain cap being too close to the end of the flue. If these checks do not uncover the fault, add an extra length of flue (bracing it, if necessary) to counteract the down draught effects caused by roof shape, nearby buildings, hills or trees.

• Switch off the circulating fan (if fitted) when the fire is burning at low heat outputs. Use only the slow fan speed at medium heat output, moving to the higher speed(s) only when full heat output has been reached.

• Adjust the door to eliminate any minor leakage. (See MAINTENANCE - page 15). Serious leakage will require a new door seal.

REMEMBER, FOR THE FIRE TO DRAW PROPERLY, AIR MUST BE ABLE

TO ENTER THE ROOM WHERE YOUR WOODFIRE IS INSTALLED. YOU

MAY HAVE TO LEAVE A DOOR SLIGHTLY OPEN AND PERHAPS A

WINDOW ELSEWHERE IN THE HOUSE IF YOUR HOME IS OF MODERN

AIRTIGHT CONSTRUCTION. LEAVING THE ROOM DOOR OPEN WILL

HELP SPREAD WARMTH THROUGH THE REST OF YOUR HOME.

14

SAFETY

• Always keep children well away from the woodfire when it is alight.

• The appliance is not intended for use by young children or infirm persons without supervision.

• Supervise young children to ensure they do not play with the appliance.

• If the supply cord is damaged it must be replaced by the manufacturer, its service agent or a suitably qualified person in order to avoid electrical hazard.

• Ensure that the electrical plug is accessible after installation. The heater must not be located immediately below an electrical socket.

• Do not put furniture, clothing, firewood or other combustibles near the woodfire. The minimum safe distance is 420mm from the sides and 1 metre from the front.

• Do not leave the fire unattended with the door open.

• Accidental fires can be caused by wrapping seemingly cold ashes in paper. It is much safer to place ashes outside in a metal container with a close fitting lid.

• If a fire is burning up inside the flue, slide the heat output control to the low heat position ( to the left) and call the Fire Service. DO NOT OPEN THE WOODFIRE DOOR.

• If you have had a flue fire, inspect your flue for damage before lighting another fire.

• Do not modify your woodfire in any way without obtaining written permission from the

Manufacturers.

CAUTION. THIS APPLIANCE MUST NOT BE USED IF THE GLASS IS CRACKED OR

BROKEN. THE GLASS SHOULD BE REPLACED ONLY WITH A GENUINE CERAMIC

GLASS REPLACEMENT PART AVAILABLE FROM YOUR MASPORT DEALER.

MAINTENANCE

ASH REMOVAL

This should be necessary only very occasionally. Simply shovel out any excess, always leaving a bed of sand or ash to the tops of the ribs on the bottom of the firebox. Place the removed ashes in a noncombustible container with a tightly fitting lid, and move the container outdoors immediately to a place clear of combustible materials.

CLEANING THE GLASS

A good hot fire will burn away any deposits left from a long slow burn. If desired, a NON-CAUSTIC oven cleaner can be used.

CLEANING THE CABINET OR FASCIA

A damp rag with a touch of household detergent is sufficient to maintain the finish.

ADJUSTING THE DOOR LATCH

If the handle is front mounted, the latch can be adjusted to overcome settling of the door gasket by transferring a washer to the outside of the door catch spindle. If the handle is side mounted, the latch is adjusted by rotating the door catch peg. First undo the lock-nut on the inside of the peg, then rotate the peg to the position where the cam portion gives the right locking pressure. Holding the peg in this position, re-tighten the lock nut. The hinge on all models can also be adjusted inward if necessary.

Move it in about a millimetre at top and bottom to maintain an even gasket pressure.

CLEANING INSIDE

If you wish to clean the flue or clear away creosote debris, the internal components can be removed easily (See below). We recommend that you check the condition of all internal components at least once a season to make sure they are still serviceable.

15

SECONDARY AIR TUBE REMOVAL

The tube will have either one or two removable angle pins to prevent it from moving endways and falling out. If there is one removable pin, one end of the tube will have a welded-on locating pin. To remove the tube, simply withdraw the angle pin(s) from the tube, move it sideways until one end can be swung down from its locating hole in the firebox side casting and then move it sideways in the other direction to disengage it completely from the firebox.

When re-fitting the tube, ensure that the small air holes will discharge generally toward the lower front of the firebox, rotating the tube until the welded-on locating pin (or the angle pin) will engage in the slot in the cast iron firebox side casting to maintain the correct angular position of the tube.

Replace the angle pin at the other end of the tube.

FIREBOX TOP BAFFLE

The special top baffle material operates at very high temperature to ensure clean burning. Take care not to knock and damage it. For flue cleaning or baffle replacement the secondary air tube must first be removed as described above. When replacing the baffle, ensure that it is sitting on top of the supporting shelf at each end and that it is pushed right to the back until the front corners drop behind the small retainer ribs on the shelves. Re-fit the secondary air tube.

FIREBOX LINERS

While the insulating boards or firebricks are durable, they will eventually require replacement. A cracked liner does not require replacing unless it will no longer stay in position in the firebox.

All Masport models have either fire-bricks or insulating board to line the firebox. (Some models have insulating boards already fixed in position at the factory). In the other models, two of the bricks or boards fit across the back of the firebox wall, and the others fit against the end walls. No force should be required to fit them, and they can be removed, if desired, for flue cleaning. However, they MUST be in place, and in good condition, before lighting the fire. Each brick or board is fitted in the same way. Angle it into position with its top corner behind the upper retaining lug, then swing it until it is parallel to the wall with its bottom corner behind the lower retaining lug. Lower the brick or board into position. In some models there are two boards at the rear and at each end. In that case, fit the metal retaining channel over the top edges of these pairs of bricks or boards to hold them in line. The wider leg of the channel goes next to the firebox wall.

16

FAN MAINTENANCE

Only the manufacturer, its service agent or a similarly qualified person should remove the bottom grille of the Grande Provincial or the ash shelf of the LE 7000 Provincial to carry out

fan installation, servicing and maintenance. The fan should need little attention other than occasionally removing it to clean dust and lint from the impeller. First unplug the mains lead from the power point. Fans on in-built fires can be accessed by lifting off the ash shelf. Fans on free-standing fires are reached by removing the rear of the pedestal. On free-standing models with internally switched fans, first gently ease off the speed control knob, taking care to pull it off squarely. Remove the four screws (two on the Grandview) which hold the fan box in position.

If the fan on the free-stander is internally switched, move it slightly away from the switch end and withdraw it completely. Some fans simply stand on rubber bushes fitted over fixed posts. These simply lift away vertically from the post (remove any shipping nuts first, but do not replace it). Clean the impeller blades carefully by blowing or vacuuming, and reassemble in the reverse order.

CLEANING THE FLUE

This may be needed about once a year or more frequently under adverse conditions. Signs of creosote and soot build-up are inadequate draught, smoking when the door is opened and a dull thud when the outside of the flue is tapped. A blocked flue can be cleaned only by sweeping. DO NOT USE

CHEMICAL CHIMNEY CLEANERS.

FLUE INSPECTION

Check regularly that the flue is sound, particularly the metal base of enamelled flues.

BEFORE EACH HEATING SEASON.

To ensure continued safety, check the condition of the following items; the flue system (particularly the flue sections nearest the firebox), the firebox top baffle, the firebox liners (bricks and boards) and the door gasket. Replace parts only with genuine MASPORT spares.

________________________________________________

FAN WIRING DIAGRAMS

SWITCH

CONNECTORS

BROW N

BLUE

GN/YEL

BRN

BLUE

GN/YEL

ORANGE

RED

SIX PIN PLUG AND SOCKET

BROW N

BLACK

BLUE

GN/YEL

FAN

EARTH POST

MAINS LEAD

588068

SW ITCH LOOM

590226

LE 7000 PROVINCIAL FAN WIRING DIAGRAM — TWO SPEED

FAN

595652

595199

SWITCH

CONNECTORS

BROW N BRN

BLUE

GN/YEL

BLUE

GN/YEL

ORANGE

RED

SIX PIN PLUG AND SOCKET

ORANGE

RED

BLUE

GN/YEL

BROW N

BLACK

BLUE

GN/YEL

FAN

EARTH POST

MAINS LEAD

588068

SW ITCH LOOM

590226

EXTENSION

LOOM

595197

FAN

595652

GRANDE PROVINCIAL FAN WIRING DIAGRAM — TWO SPEED 595198

If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid electrical hazard.

17

MODEL

HORIZON / LE 2000

SIENA

LE 3000 / 5000 S2, S3

VERONA

TORONTO

GRANDVIEW

LE 3000 PROVINCIAL S2

LE 7000 PROVINCIAL S3

GRANDE PROVINCIAL

SHELF

NO

YES

NO

NO

YES

NO

NO

YES

NO

D

DIMENSIONS

D H

440 615

525 615

490 640

490 680

585 680

570 705

545 825

660 825

620 790

460 570

485 595

485 670

660

660

760

590

630

720

W

555

555

555

660

660

660

D

195

195

195

125

175

175

F

165

165

165

220

220

220

W

FH FW

— —

660 810 335

720 1000 310

790 1095 310

FF

W

F

H

FH

H

F

FF

FW

FREESTANDING INBUILT

MASPORT WOODFIRES ARE MANUFACTURED IN NEW ZEALAND BY

MASPORT LTD. 1/37 MT WELLINGTON HIGHWAY.

P.O. BOX 14-349 PANMURE, AUCKLAND NEW ZEALAND.

MASPORT WOODFIRES ARE DISTRIBUTED IN AUSTRALIA BY

MASPORT PTY LTD.

P.O. BOX 533, MORDIALLOC, VICTORIA.

18

31.08.2004

advertisement

Key Features

  • Tested to meet the current emission requirements in New Zealand
  • Water heating booster
  • Large viewing window
  • High-quality construction
  • Efficient and environmentally friendly

Related manuals

Frequently Answers and Questions

What is the water heating booster used for?
The water heating booster can be used to heat water for your home or for a spa pool.
How big is the viewing window?
The viewing window is large, providing a great view of the fire.
Is the LE 3000/W difficult to install?
We recommend that the installation of your Masport woodfire be carried out by a qualified specialist installer.