advertisement
Compact performance
Manual
Electronics
CPV valve terminal with direct connection
Type CPV..-DI01
Field bus protocols:
- PROFIBUS-DP
- Festo field bus
- ABB CS31
- SUCOnet K
Manual
165 817 en 0007a
Contents and general instructions
Authors . . . . . . . . . . . . . . . . . . . . . .
U. Reimann, H. Hohner
Editors . . . . . . . . . . . . . . . . . . . . . . . .
H.-J. Drung, M. Holder
Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
de
Translation . . . . . . . . . . . . . . . . . . . . .
transline Deutschland
Layout . . . . . . . . . . . . . . . . . . .
Festo AG & Co., Dept. KG-GD
Type setting . . . . . . . . . . . . . . . . . . . .
transline Deutschland
Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
en 0007a
Title . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MANUAL-EN
Designation . . . . . . . . . . . . . . . . . . . . . . . .
P.BE-CP-DI01-EN
Order-no.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
165 817
E (Festo AG & Co., D-73726 Esslingen, Federal Republic of
Germany, 2000)
Internet: http://www.festo.com
e-mail: [email protected]
The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved, in particular the right to carry out patent, utility model or ornamental design registrations.
Festo P.BE-CP-DI01-EN en 0007a
I
Contents and general instructions
II
Festo P.BE-CP-DI01-EN en 0007a
Contents and general instructions
Contents
Designated use
Target group
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on the use of this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII
VIII
VIII
VIII
IX
1.
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.1
1.2
General instructions on installation
Configuring the CPV Direct
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1
Fitting and removing the switch module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2
Setting the CPV Direct
1.3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the field bus baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4
Connecting the field bus
1.4.1
Field bus cable
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2
Field bus baud rate and field bus length for PROFIBUS-DP
1.4.3
Connecting the field bus
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5
Bus termination with terminating resistors . . . . . . . . . . . . . . . . . . . . . . . . . .
1.6
1.7
Optical-fibre waveguide connection for PROFIBUS-DP
Power supply
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.1
Cable for power supply
1.7.2
Selecting the power unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.3
Connecting the power supply
1.8
Extending the CPV Direct
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3
1-5
1-5
1-7
1-18
1-19
1-19
1-20
1-22
1-25
1-27
1-28
1-28
1-30
1-32
1-37
2.
Commissioning PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
2.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
2.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2
Address assignment of the CPV valve terminal . . . . . . . . . . . . . . . . . . . . . . .
2.1.3
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2
Configuration with a Siemens master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1
Preparations for COM PROFIBUS 3.x and 5.0
. . . . . . . . . . . . . . . . . . . . . . . .
2.2.2
COM PROFIBUS 3.x
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3
2-3
2-4
2-6
2-9
2-9
2-11
Festo P.BE-CP-DI01-EN en 0007a
III
Contents and general instructions
2.2.3
COM PROFIBUS 5.0
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.4
Configuration examples for COM PROFIBUS 3.x and 5.0
. . . . . . . . . . . . . . . .
2.2.5
Input and output addresses with COM PROFIBUS 3.x and 5.0
. . . . . . . . . . .
2.2.6
STEP 7 V4.x / 5.1 - Hardware configurator . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.7
Example of addressing: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.8
Commissioning the CP system on the PROFIBUS-DP . . . . . . . . . . . . . . . . . . .
2.3
Operation with general DP Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1
Bus run-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2
Sending a parametrizing telegram
2.3.3
Sending configuration data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.4
Requesting diagnostic information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.5
Starting cyclic data transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.6
Summary of implemented functions and service access points (SAP) . . . . .
2.3.7
Bus parameter/reaction times
2.3.8
Transmission times on the PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4
Device data base (GSD)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-26
2-28
2-28
2-29
2-31
2-32
2-32
2-34
2-35
2-35
2-36
2-15
2-18
2-19
2-20
2-25
3.
Diagnosis PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
3.2
3.3
Locating faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnosis with PROFIBUS-DP
3.3.1
Diagnostic words
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2
Diagnostic information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1
General DP Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2
Siemens SIMATIC S5/S7
3.5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Online diagnosis mit COM PROFIBUS 5.0
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6
Online diagnosis with STEP 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6.1
Diagnostic buffer STEP 7 (version 4.x, 5.1) . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6.2
Device-specific diagnosis with STEP 7 (version 5.1) . . . . . . . . . . . . . . . . . . .
3.7
Short circuit/overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-7
3-8
3-8
3-12
3-17
3-18
3-3
3-3
3-4
3-6
3-18
3-21
3-22
3-22
3-24
3-26
IV
Festo P.BE-CP-DI01-EN en 0007a
Contents and general instructions
3.7.1
Output module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.2
Sensor supply to an input module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-26
3-27
4.
Commissioning the Festo field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
4.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2
Address assignment of the CPV valve terminal . . . . . . . . . . . . . . . . . . . . . . .
4.2
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1
Configuration with the field bus configurator . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4-3
4-3
4-4
4-6
4-7
5.
Diagnosis Festo field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
5.2
Diagnosis with the field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1
Reaction of the CPV valve terminal to faults . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2
Short circuit/overload at output module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3
Short circuit in the sensor supply on an input module . . . . . . . . . . . . . . . . .
5-3
5-3
5-4
5-6
5-7
5-8
5-8
5-9
5-10
6.
Commissioning the ABB CS31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
6.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2
Address assignment of the CPV valve terminal
6.1.3
General information
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.1
CS31 central unit as bus master
6.2.2
T200 / 07CS61 as bus master
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6-3
6-3
6-4
6-5
6-6
6-7
6-9
7.
Diagnosis with the ABB CS31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1
7-3
7-3
Festo P.BE-CP-DI01-EN en 0007a
V
Contents and general instructions
A.
A.1
A.2
B.
7.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
7.2
7.3
7.4
Diagnosis with the field bus
Setting the diagnostic mode
Error treatment
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.1
Reaction of the CPV valve terminal to faults . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.2
Short circuit/overload at output module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.3
Short circuit in the sensor supply on an input module . . . . . . . . . . . . . . . . .
7-4
7-6
7-7
7-11
7-12
7-12
7-13
7-14
8.
Commissioning the Moeller SUCOnet K . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
8.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1.2
Address assignment of the CPV valve terminal
8.2
. . . . . . . . . . . . . . . . . . . . . . .
CP system extension and number of inputs/outputs . . . . . . . . . . . . . . . . . .
8.3
8.4
Configuration für SUCOnet K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addressing inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1
8-3
8-3
8-4
8-6
8-8
8-9
9.
Diagnosis with the Moeller SUCOnet K . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1
9.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
9.2
9.3
Diagnosis with the field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3.1
Reaction of the CPV valve terminal to faults . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3.2
Short circuit/overload at output module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3.3
Short circuit in the sensor supply on an input module . . . . . . . . . . . . . . . . .
9-7
9-9
9-9
9-10
9-11
9-3
9-3
9-4
9-6
Technical data and accessories
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
A-3
A-5
B-1
VI
Festo P.BE-CP-DI01-EN en 0007a
Contents and general instructions
Designated use
The CPV valve terminal type CPV-DI01 with field bus direct connection (CPV direct) described in this documentation is designed exclusively for use as a slave on the following field buses:
– PROFIBUS-DP
– Festo field bus
– ABB CS31
– Moeller SUCOnet K
The valve terminal may only be used as follows:
– in accordance with designated use
– in its original state
– without any modifications by the user
– in faultless technical condition.
– The maximum values specified for pressures, temperatures, electrical data, torques etc. must be observed.
Please comply with national and local safety laws and regulations.
If implementing an emergency stop function, please observe the measures listed in chapter 1.7.3.
Warning
If the CP valve terminal is used as an explosion-proof operating medium, do not disconnect the electrical connections under tension.
Festo P.BE-CP-DI01-EN en 0007a
VII
Contents and general instructions
Target group
This manual is intended exclusively for technicians trained in control and automation technology, who have experience in installing, commissioning, programming and diagnosing slaves on the field buses named above.
Service
Please consult your local Festo repair service if you have any technical problems.
Notes on the use of this manual
Please note
This manual describes the functionality of the software version as from 1.x and the hardware version as from
04/98 of the CPV valve terminal with direct connection for PROFIBUS-DP, Festo field bus, ABB CS31, Moeller
SUCOnet K.
This manual contains specific information on installing, commissioning, programming and diagnosing CPV valve terminals with direct connection for the field buses named.
Information on pneumatics can be found in the “Pneumatics manual, P.BE-CPV-...”.
VIII
Festo P.BE-CP-DI01-EN en 0007a
Contents and general instructions
Important user instructions
Danger categories
This manual contains instructions on the possible dangers which may occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc), printed on a shaded background and marked additionally with a pictogram. A distinction is made between the following danger warnings:
Warning
This means that failure to observe this instruction may result in serious personal injury or damage to property.
Caution
This means that failure to observe this instruction may result in personal injury or damage to property.
Please note
This means that failure to observe this instruction may result in damage to property.
The following pictogram marks passages in the text which describe activities with electrostatically sensitive components.
Electrostatically sensitive components may be damaged if they are not handled correctly.
Festo P.BE-CP-DI01-EN en 0007a
IX
Contents and general instructions
Marking special information
The following pictograms mark passages in the text containing special information.
Pictograms
Information:
Recommendations, tips and references to other sources of information.
Accessories:
Information on necessary or sensible accessories for the
Festo product.
Environment:
Information on environment-friendly use of Festo products.
Text markings
S The bullet indicates activities which may be carried out in any order.
1. Figures denote activities which must be carried out in the numerical order specified.
– Hyphens indicate general activities.
X
Festo P.BE-CP-DI01-EN en 0007a
Contents and general instructions
Term/abbreviation
AB
CP
CP connection
CP modules
CP system
CPV Direct
I
CP cable
I/O modules
I/Os
O
Octet
PLC/IPC
The following product-specific terms and abbreviations are used in this manual:
Meaning
Output byte
Compact performance
Plug or socket on the CP modules which enables the modules to be connected with the CP cable
Common term for various modules which can be incorporated in a
CP system
Complete system consisting of CPV Direct and CP modules
CPV valve terminal with field bus direct connection
Special cable for coupling the various CP modules
Digital input
Common term for the CP modules which provide digital inputs and outputs (CP input modules and CP output modules)
Digital inputs and outputs
Digital output
Number of address bytes assigned by the CP system
Programmable logic controller/industrial PC
Festo P.BE-CP-DI01-EN en 0007a
XI
Contents and general instructions
XII
Festo P.BE-CP-DI01-EN en 0007a
Installation
Chapter 1
Festo P.BE-CP-DI01-EN en 0007a
1-1
1. Installation
Contents
1.
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1.1
General instructions on installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2
Configuring the CPV Direct . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1
Fitting and removing the switch module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2
Setting the CPV Direct
1.3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the field bus baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4
Connecting the field bus
1.4.1
Field bus cable
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.2
Field bus baud rate and field bus length for PROFIBUS-DP
1.4.3
Connecting the field bus
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5
1.6
1.7
Bus termination with terminating resistors
Optical-fibre waveguide connection for PROFIBUS-DP
Power supply
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.1
Cable for power supply
1.7.2
Selecting the power unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.7.3
Connecting the power supply
1.8
Extending the CPV Direct
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-20
1-22
1-25
1-27
1-28
1-28
1-30
1-32
1-37
1-3
1-5
1-5
1-7
1-18
1-19
1-19
1-2
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.1
General instructions on installation
Warning
Before carrying out installation and maintenance work, switch off the following:
– the compressed air supply
– the operating voltage for the internal logics
– the load voltage for the valves.
You can thereby avoid:
– uncontrolled movements of loose tubing
– unexpected movements of the connected actuators
– non-defined switching states of the electronic components.
Caution
The CPV valve terminal with field bus direct connection
(CPV Direct) contains electrostatically sensitive components.
– Do not therefore touch any contacts.
– Observe the regulations for handling electrostatically sensitive components.
You will then prevent the electronics in the node from being damaged.
Festo P.BE-CP-DI01-EN en 0007a
1-3
1. Installation
1
2
3
4
Electrical connecting and display elements
The following connecting and display elements can be found on the CPV valve terminal with field bus direct connection
(CPV Direct):
5
6
1
Field bus connection
(9-pin sub-D socket)
2
Switch module (can be removed)
3
Operating voltage connection for electronics/load voltage connection for CP valves (4-pin M12 plug)
4
Bus status and power LEDs
(red resp. green)
5
CP extension connection
6
Switching status displays for the CP valve coils (yellow LEDs)
Fig. 1/1: Connecting and display elements for CPV Direct
1-4
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.2
Configuring the CPV Direct
1.2.1 Fitting and removing the switch module
Caution
The switch module contains electrostatically sensitive components.
– Do not therefore touch any contacts.
– Observe the regulations for handling electrostatically sensitive components.
The switch module must be removed before the CPV Direct can be set.
Festo P.BE-CP-DI01-EN en 0007a
Fig. 1/2: Fitting/removing the switch module
1-5
1. Installation
Removing
1. Switch off the operating voltage.
2. Unscrew the two fastening screws of the switch module.
3. Lift up and remove the switch module.
Fitting
1. Place the switch module carefully in the groove.
2. Tighten the two fastening screws alternately to the same extent.
Please note
– Do not tilt the switch module when fitting it. The fitting position is clearly marked by a groove in the housing.
– Make sure that the seal is seated correctly.
1-6
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.2.2 Setting the CPV Direct
When the switch module has been removed, you will see two
DIL switches in it (Fig. 1/3).
You can set the following parameters with the DIL switches:
– the field bus protocol
– the extension to the CP system
– the station number
– the diagnostic mode
Proceed as follows:
1. Switch off the operating voltage.
2. Remove the switch module (chapter 1.2.1).
3. Set the field bus protocol (4-position DIL switch, elements
1...2).
4. Set the extension to the CP system (4-position DIL switch, elements 3...4).
5. Assign an unused station number to the CPV Direct. Set the desired station number (8-position DIL switch, elements 1...7).
6. Set the diagnostic mode (8-position DIL switch, element 8).
7. Fit the switch module (chapter 1.2.1).
Festo P.BE-CP-DI01-EN en 0007a
1-7
1. Installation
1 3
PROFIBUS-DP
2
4-position DIL switch:
1
Setting the field bus protocol
2
Setting the extension to the CP system
8-position DIL switch:
3
Address selector switch for station number
4
Setting the diagnostic mode
Fig. 1/3: DIL switch in the switch module (further information on 1 ...
4 see following pages)
Setting the field bus protocol
1
The CPV Direct can be operated with one of four field bus protocols. The desired protocol can be seleced with switch elements 1 and 2 of the 4-position DIL switch.
Set the field bus protocol you wish to use as follows:
Festo field bus ABB CS31 SUCOnet K
4
Fig. 1/4: Setting the field bus protocol with the 4-position DIL switch
1-8
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Extension to the CP system
Setting the extension to the CP system
2
Further CP modules can be connected to the CPV Direct. You can set the extension to the CP system with switch elements 3 and 4 of the 4-position DIL switch as shown in the diagram below.
Number of inputs/outputs Setting the DIL switches
CPV Direct without extension
16 outputs
CPV valve terminal with extension with:
– a CP input module
CPV valve terminal with extension with:
– a CP valve terminal or
– a CP output module
CPV valve terminal with extension with:
– a CP valve terminal/CP output module and
– a CP input module
16 outputs
16 outputs
+
16 outputs
16 outputs
+
16 outputs
+
16 inputs
+
16 inputs
Fig. 1/5: Setting: extension of the CP system with 4-position DIL switch
Please note
Depending on the extension set, the CP system occupies a different number of inputs and outputs or station numbers. Further information can be found in chapter 1.8.
Festo P.BE-CP-DI01-EN en 0007a
1-9
1. Installation
Setting the station number
3
You can set the field bus station number with the 8-position
DIL switch.
Please note
Station numbers may only be assigned once per field bus line.
The following station numbers are permitted:
Protocol
PROFIBUS-DP
Festo field bus
ABB CS31
Moeller SUCOnet K
Address designation
PROFIBUS address field bus address
CS31 module address
–
Permitted station numbers
0; ...; 125
1; ...; 63
0; ...; 60
2; ...; 98
Recommendation:
Assign the field bus addresses in ascending order. Assign the field bus addresses to suit the machine structure of your system.
1-10
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1
Setting the station number for
- PROFIBUS-DP
- ABB CS31
- SUCOnet K
(8-position DIL switch, elements
1...7)
2
Setting the station number for
- Festo field bus
(8-position DIL switch, elements
1...6)
1
2
Fig. 1/6: Setting the station number (8-position DIL switch)
The station number is entered coded with the 8-position DIL switch.
Set station number: 05
(= 1 + 4)
Set station number: 38
(= 2 + 4 + 32)
Fig. 1/7: Examples of set station numbers
Festo P.BE-CP-DI01-EN en 0007a
1-11
1. Installation
The following pages contain a summary of the settings for the station numbers. You can use the tables for all protocols with which the valve terminal can be used.
Please note
With protocols ABB CS31 and Festo field bus, the DIL switch elements 1...6 suffice for setting the station number.
With protocol ABB CS31, switch element 7 must be set to
OFF.
With the Festo field bus, switch elements 7 and 8 are used for setting the baud rate.
1-12
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Station no.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1 2 3 4 5 6 7 8 Station no.
16
OFF OFF OFF OFF OFF OFF OFF
ON
OFF OFF OFF OFF OFF OFF
ON
OFF
ON ON
OFF OFF OFF OFF OFF
OFF OFF OFF OFF OFF
ON
OFF OFF OFF OFF OFF OFF
ON
OFF
ON
OFF OFF OFF OFF
ON ON
OFF
ON ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON ON
OFF
ON
ON
OFF
ON ON
OFF OFF OFF OFF
ON
OFF OFF OFF
ON
OFF OFF OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
OFF OFF OFF
OFF
OFF
OFF
OFF
OFF
ON ON ON
OFF
ON ON ON ON
OFF OFF OFF
OFF OFF OFF
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
1 2 3 4 5 6
ON
OFF OFF OFF OFF
ON
OFF OFF OFF
ON
OFF
ON ON
OFF OFF
OFF OFF
ON
OFF OFF OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
ON ON
ON ON ON
ON
OFF
ON
OFF
ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON ON
OFF
ON
ON
ON
ON
ON ON
OFF
ON ON ON
OFF OFF
ON
OFF
ON ON ON
ON ON ON ON
OFF
ON ON ON ON ON
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
OFF OFF
Fig. 1/8: Setting the station numbers 0...31: Position of the DIL switch elements
7 8
Festo P.BE-CP-DI01-EN en 0007a
1-13
1. Installation
Station no.
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
1 2 3 4 5 6 7 8 Station no.
ON 48
OFF OFF OFF OFF OFF
ON
OFF OFF OFF OFF
ON
OFF
ON ON
OFF OFF OFF
OFF OFF OFF
ON
OFF OFF OFF OFF
ON
OFF
ON
OFF OFF
ON ON
OFF
ON ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON ON
OFF
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
ON
OFF
OFF
OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
ON ON ON
OFF
ON ON ON ON
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
1 2 3 4 5 6 7 8
OFF OFF OFF OFF
ON
OFF OFF OFF
ON
OFF
ON ON
OFF OFF
OFF OFF
ON
OFF OFF OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
OFF OFF
ON
OFF
ON
ON
ON ON
OFF
ON ON
OFF
ON ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON ON
OFF
ON
ON
ON
ON
ON
ON
ON ON ON
OFF
ON ON ON ON
ON ON ON ON
ON ON ON ON ON
OFF
ON ON ON ON
ON ON
ON ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Fig. 1/9: Setting station numbers 32...63: Position of the DIL switch elements
1-14
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Station no.
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
1 2 3 4 5 6 7 8 Station no.
ON 80
OFF OFF OFF OFF OFF OFF
ON
OFF OFF OFF OFF OFF
ON
OFF
ON ON
OFF OFF OFF OFF
OFF OFF OFF OFF
ON
OFF OFF OFF OFF OFF
ON
OFF
ON
OFF OFF OFF
ON ON
OFF
ON ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON ON
OFF
ON
ON
OFF
ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF OFF
OFF
OFF
OFF
OFF
OFF OFF
ON
OFF
ON
OFF
ON
OFF
OFF OFF
OFF
OFF
OFF
ON ON ON
OFF
ON ON ON ON
OFF OFF
OFF OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
1 2 3 4 5 6
ON
OFF OFF OFF OFF
ON
OFF OFF OFF
ON
OFF
ON ON
OFF OFF
OFF OFF
ON
OFF OFF OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
OFF
ON ON
ON ON ON
ON
OFF
ON
OFF
ON ON
OFF OFF OFF
ON
OFF OFF
ON
OFF
ON ON
OFF
ON
ON
ON
ON
ON ON
OFF
ON ON ON
OFF OFF
ON
OFF
ON ON ON
ON ON ON ON
OFF
ON ON ON ON ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Fig. 1/10: Setting station numbers 64...95: Position of the DIL switch elements
7 8
Festo P.BE-CP-DI01-EN en 0007a
1-15
1. Installation
Station no.
1 2 3 4 5 6 7 8 Station no.
ON ON 96
97
98
99
100
101
102
OFF OFF OFF OFF OFF
ON
OFF OFF OFF OFF
ON
OFF
ON ON
OFF OFF OFF
OFF OFF
OFF OFF OFF
ON
OFF OFF
ON ON
OFF
ON ON
OFF OFF
OFF OFF OFF
103 ON ON ON
104
105
106
107
108
OFF
ON
OFF
ON
OFF
ON
OFF
OFF OFF
ON
OFF
ON
ON
OFF
ON ON
OFF OFF
ON
OFF
ON
OFF
OFF
OFF
OFF OFF OFF
109 ON
110
ON ON
OFF
ON ON ON
OFF
OFF OFF
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
ON ON
1 2 3 4 5 6 7
111 ON ON ON ON ON ON
OFF
ON ON ON 112
OFF OFF OFF OFF
113 ON
114
OFF
OFF OFF OFF
ON
OFF OFF
ON ON ON
ON ON ON
115 ON ON
116
117
118
OFF OFF
ON ON
OFF
ON ON
OFF OFF
ON
OFF
OFF
OFF OFF
119 ON ON ON
ON ON ON
ON ON ON
ON ON ON
ON ON ON
ON ON ON
OFF
ON ON ON ON 120
OFF OFF OFF
121 ON
122
OFF
OFF OFF
ON
OFF
ON ON ON ON
ON ON ON ON
123 ON ON ON
124
ON ON ON
OFF
ON ON ON ON ON
OFF OFF
125 ON ON ON ON ON ON
OFF
8
Fig. 1/11: Setting station numbers 96...125: Position of the DIL switch elements
1-16
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1
Diagnosis ON
2
Diagnosis OFF
1
2
Setting the diagnostic mode
5
(only for PROFIBUS-DP and ABB CS31)
The following diagnosis can be activated/deactivated with switch element 8 of the 8-position DIL switch:
– PROFIBUS-DP Device-related diagnosis active/inactive
– ABB CS31: load voltage monitoring active/inactive
Fig. 1/12: Setting the diagnostic mode
For PROFIBUS-DP:
If the device-related diagnosis is masked out with switch element 8, no device-related diagnostic information will be sent from the valve terminal to the master system, e.g. short circuit at the outputs or undervoltage of the valves (see chapter
3.3).
Festo P.BE-CP-DI01-EN en 0007a
1-17
1. Installation
1.3
Setting the field bus baud rate
Please note
It is only necessary to set the desired baud rate with the
Festo field bus protocol.
The CPV Direct automatically recognizes the baud rate for the
PROFIBUS-DP (9.2 kBd...12 MBd) and SUCOnet K
(187.5 kBd...375 kBd) protocols.
The baud rate 187.5 kBd is always used for the ABB CS31 protocol.
With the Festo field bus protocol, DIL switch elements 7 and 8 of the 8-position DIL switch are used for setting the baud rate.
Setting the baud rate with the Festo field bus protocol
31.25 kBd 62.5 kBd 187.5 kBd 375 kBd
Fig. 1/13: Setting the baud rate for the Festo field bus
1-18
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.4
Connecting the field bus
1.4.1 Field bus cable
Bus length
Please note
Faults in data transmission can occur due to signal reflections and attenuation, if installation is not carried out correctly and if the baud rates are too high.
The causes of transmission faults may be:
– a missing or incorrect terminating resistor
– incorrect screening/shield connection
– branches
– transmission over long distances
– unsuitable cables
Please observe the cable specifications. Please refer to the manual for your controller for information on the cable type to be used.
If you use the Festo IP65 plug, the cable must have a diameter of 5...8 or 7...10 mm.
PROFIBUS-DP
Use a twisted screened 2-core cable for the field bus.
Detailed specifications on the bus length can be found in chapter 1.4.2 and in the manuals for your control system.
Festo field bus/ABB CS31/Moeller SUCOnet K
Please refer to the PLC manual for your controller for information on the cable type to be used. Take into account the distance and the field bus baud rate set.
Festo P.BE-CP-DI01-EN en 0007a
1-19
1. Installation
1.4.2 Field bus baud rate and field bus length for PROFIBUS-DP
Please note
The CP system sets itself automatically to one of the baud rates listed in Fig. 1/14.
The maximum permitted field bus length depends on the baud rate used. Fig. 1/14 shows the baud rates which can be used.
Length of branch lines
Please note
S Please note the maximum permitted length of the field bus cable if you connect the CPV Direct via a branch line.
S When calculating the maximum permitted length of the field bus cable, also take into consideration the sum of the branch line lengths.
The maximum permitted length of a branch line depends on the cable type and on the baud rate.
1-20
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Recommendation:
Use a cable with a capacitance per unit length of < 30 nF/km as specified below.
Otherwise the permitted cable length will be reduced.
Baud rate
(in kBaud)
9.6
19.2
93.75
187.5
500
1500
3000...12000
1200 m
1200 m
1200 m
1.000 m
400 m
200 m
100 m
Field bus length
(max.)
Maximum permitted branch line length
500 m
500 m
100 m
33.3 m
20 m
6.6 m
—
Fig. 1/14: Maximum permitted field bus and branch line lengths for PROFIBUS-DP depending on the baud rate
Cable specification as per EN 50170 (cable type A):
Characteristic impedance: 135...165 Ohm (3...20 MHz)
Capacitance per unit length: < 30 nF/km
Loop impedance: < 110 Ohm/km
Core diameter:
Core cross sectional area
> 0.64 mm
> 0.34 mm
2
Festo P.BE-CP-DI01-EN en 0007a
1-21
1. Installation
1.4.3 Connecting the field bus
Please note
Please note that only the Festo plug complies with protection class IP65.
Before connecting sub-D plugs of other manufacturers:
S replace the two flat screws by bolts (part no. 340960).
There is a 9-pin sub-D socket on the CPV Direct for connecting the CPV valve terminal to the field bus.
This connection is for the supply line and continuing field bus cable. You can connect the CPV valve terminal with the sub-D plug from Festo (part no. 18529).
Connecting the PROFIBUS-DP
Pin Festo sub-D plug
(IP65)
PROFIBUS-DP
5
6
3
4
1
2
7
8
9
Housing
B
A
Cable clip
Designation n.c.
n.c.
RxD/TxD-P
CNTR-P 1)
DGND
VP n.c.
RxD/TxD-N n.c.
Screening/shield not connected not connected
Receive/send data P
Repeater control signal
Data reference potential (M5V)
Supply voltage positive (P5V) not connected
Receive/send data N not connected
Connection to housing
(view of socket)
1) The repeater control signal CNTR-P is in the form of a TTL signal.
Fig. 1/15: Connecting the field bus interface to the CPV Direct with PROFIBUS-DP
1-22
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Manufacturer-specific connection
Pin Festo sub-D plug (IP65)
Festo field bus
5
6
3
4
7
1
2
8
9
Housing
B
A
Cable clip
S+
S-
Screening/ shield
ABB (CS31) SucoNet K sub D9-pin
Bus 1 3 (T
A
/R
A
) 2)
Bus 2
Screening/ shield
7 (T
B
/R
B
) 2)
4 (screening/ shield) 2)
SucoNet K
(round) 5-pin
4 (T
A
/R
A
) 2)
1 (T
B
/R
B
) 2)
Housing
(view of socket)
2) Pin numbers of the SUCOnet K interface
Fig. 1/16: Connecting the field bus interface to the CPV Direct with the Festo field bus,
ABB CS13 and SUCOnet K
Please note
If a valve terminal is fitted in a machine which moves, the field bus cable on the moving part of the machine must be supplied with strain relief. Please observe the relevant regulations of standard EN 60204 part 1.60204 part 1.
Festo P.BE-CP-DI01-EN en 0007a
1-23
1. Installation
1
Screening connection, cable clip
2
Only connected capacitively
3
CPV Direct
(shown reduced)
4
Pin assignment in the plug
1
2
Festo sub-D plug
Fig. 1/17 shows the pin assignment in the Festo sub-D plug.
A floating screening connection is intended with the Festo sub-D plug.
S Clamp the screening of the field bus cable under the cable clip of the Festo sub-D plug (Fig. 1/17).
ON
4
3
Fig. 1/17: Festo sub-D plug, pin assignment and screening connection (see also Fig. 1/15 or Fig. 1/16)
Please note
The cable clip in the Festo sub-D plug is connected internally only capacitively with the metallic housing of the sub-D plug. This is to prevent equalizing currents from flowing through the screening of the field bus cable
(Fig. 1/17).
1-24
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.5
Bus termination with terminating resistors
Please note
Use a bus termination at both ends of a bus segment. This also applies when the bus module or bus interface is at the beginning of the bus cable.
If the CPV valve terminal is at the end of the field bus system, a bus termination is necessary.
Recommendation:
Use here the sub-D plug from Festo (part no. 18529). A suitable resistor network is provided in the housing of the sub-D plug. The bus termination must be switched manually with slide switches.
1
Plug
2
Slide switch
1
2
A B
A B not
Bus termination switched on switched on
ON ON
Fig. 1/18: Switch for bus termination in the Festo sub-D plug
Festo P.BE-CP-DI01-EN en 0007a
1-25
1. Installation
1
Switch in the
Festo plug
2
Pin 6 power supply
3
Pin 5 data reference potential
1 2
Pin 6
390 Ω
Data signal
Pin 3
220 Ω
Data signal
Pin 8
390 Ω
3
Pin5
1
Fig. 1/19: Circuit diagram for bus termination network for cable type A as per EN 50170
1-26
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.6
Optical-fibre waveguide connection for PROFIBUS-DP
We recommend optical-fibre waveguide technology for transmission in areas which are subjected to heavy interference, as well as for extending the range of transmission with high baud rates.
This offers the following extra advantages:
– high degree of EMC compatibility, ESD protection due to the optical transmission of the signals
– protection against lightning
– potential isolation of the individual DP slaves.
The PROFIBUS-DP interface of the CPV Direct has been designed in accordance with specification EN 50170 volume 2 and therefore supports the control of network components for optical-fibre waveguides.
Examples of optical-fibre waveguide network components:
– Siemens optical link module (OLM) for PROFIBUS plus
– Siemens optical link plug (OLP) for PROFIBUS
Festo P.BE-CP-DI01-EN en 0007a
1-27
1. Installation
1.7
Power supply
1.7.1 Cable for power supply
S Use a supply voltage cable with sufficient cross-sectional area.
S Avoid long distances between the power unit and the CPV valve terminal. Long operating voltage cables reduce the voltage supplied by the power unit.
S If necessary, ascertain the most suitable cross-sectional area and the maximum permitted cable length.
The connection for the power supply is in the form of a plug.
Please see the following chapters for the pin assignment of the plug.
Use plugs from the Festo sales range for connecting the power supply. The plugs must suit the outer diameter of the cables used (see Appendix A.2).
1-28
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1
Cables
2
Strain relief
3
Housing
4
Connecting part
1
4
Fig. 1/20: Individual socket parts and cable routing
Preparing the cables When you have selected suitable cables, connect them as follows (Fig. 1/20):
1. In order to open the sockets, loosen the centre knurled nut.
2. Open the strain relief on the rear of the housing. Then pass the cable through.
3. Remove 5 mm of the insulation and fit end sleeves onto the wires.
4. Connect the conductors.
5. Insert the connecting part into the housing of the plug again. Pull the cable back so that there are no loops inside the housing.
6. Tighten the strain relief.
2
3
Festo P.BE-CP-DI01-EN en 0007a
1-29
1. Installation
1.7.2 Selecting the power unit
Warning
Use only power units which guarantee reliable electrical isolation of the voltage supplies in accordance with
IEC 742/EN 60742/VDE 0551 with at least 4 kV isolation resistance (Protected Extra-Low Voltage, PELV). Switch power packs are permitted providing they guarantee reliable isolation in accordance with EN 60950/VDE 0805.
Remark:
By using PELV power units with Festo valve terminals, you can ensure protection against electric shock (protection against direct and indirect contact) in accordance with EN 60204-1 /
IEC 204. For supplying power to PELV networks, you should use safety transformers with the symbol shown here. The valve terminal must be earthed in order to guarantee the operation of certain functions (e.g. EMC).
The current requirements of a CP system depends on the number of CP modules and valve coils. Recommendation:
S Use closed-circuit power units.
S When selecting a power unit, make sure that it has sufficient power output. To do this, calculate the total current requirements as shown in the following table:
1-30
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Total current consumption The following table shows you how to calculate the total current consumption of a CP system. The values specified have been rounded up.
Current consumption for the CP electronics (pin 1)
Sums
CPV Direct
CPV valve terminal
CPA valve terminal
CP input module
Sensors max. 100 mA max. 40 mA
20 mA max. 40 mA
See manufacturer specifications max. 40 mA CP output module
Carried forward = ______ mA
Current consumption of the valve supply (pin 2)
Current consumption of all simultaneously energized valve coils 1) __ x ____ mA = ______ mA
1) Current consumption depends on valve type (see Technical specifications of the valves)
Festo P.BE-CP-DI01-EN en 0007a
1-31
1. Installation
1.7.3 Connecting the power supply
Warning
If the valve terminal is supplied with load voltage via the output of a “fail-safe I/O module”, make-contact test pulses of the “fail-safe I/O module” can cause the valve terminal to react unexpectedly.
S Make sure that make-contact test pulses are reliably suppressed or switched off.
Power is supplied via the 4-pin M12 plug (see Fig. 1/1).
Current consumption depends on the type of valve terminal.
For the values, please refer to the “Pneumatics manual,
P.BE-CPV-..” and the previous chapter.
Please note the following when connecting the 24 V load voltage (pin 2):
S Observe the tolerance (20.4 V...26.4 V DC). Check the
24 V load voltage of the valves while the system is in operation.
1-32
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Please note
Check within the framework of your EMERGENCY STOP circuit to ascertain the measures which are required for putting your machine/system in a safe state in the event of an EMERGENCY STOP, e.g.
– switching off the load voltage for the valves and output modules in the secondary circuit of the power unit
– switching off the compressed air supply to the valve terminal.
When the load voltage is switched off, there may be a delay before the valves are also switched off. This is due to energy being stored in the input circuitry of valve terminals.
Take this into consideration, e.g. as follows:
– by registering the switch-off moment of the load voltage by means of an input signal in the controller.
– by blocking the control signal for the valves by locking the output signal with the “Load voltage” input signal.
Festo P.BE-CP-DI01-EN en 0007a
1-33
1. Installation
Pin assignment of the power supply connection for the CPV valve terminal
1
1
Pin assignment
1: 24 V DC operating voltage for the electronics (and inputs, in the case of modules connected to the extension connection)
2: 24 V DC load voltage for the valves
3: 0 V
4: Earth/ground connection
Fig. 1/21: Pin assignment of power supply connection
Potential equalization
The CPV valve terminal has two earth connections for potential equalization:
– on the power supply connection
– on the end plate.
1-34
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Please note
S Always connect the earth potential to pin 4 of the power supply connection.
S Connect the earth connection of the end plate to the earth potential with low impedance (short cable with large cross-sectional area).
S Use low-impedance connections to ensure that the housing of the valve terminal and the earth connection at pin 4 have the same potential and that there are no equalizing currents.
You thereby avoid faults caused by electromagnetic influences.
Festo P.BE-CP-DI01-EN en 0007a
1-35
1. Installation
1-36
0 V
24 V
1 2 3 2 4
1
PE
2
Potential equalization
3
Load voltage can be switched off separately
4
Earth connection pin 4 designed for 3 A
Fig. 1/22: Example of connection with PELV power unit and potential equalization
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
1.8
Extending the CPV Direct
You can connect further modules of the CP system to the CPV
Direct by means of the CP extension connection.
5 4 3 2 1
9 8 7 6 1
BUS
POWER
1
CP extension connection
Fig. 1/23: CP extension connection
Caution
Set the exact extension to your CP system on the 4-position DIL switch of the switch module. In this way you will prevent the system from functioning incorrectly.
Modules, which you connect to the CP extension connection, will only be recognized if the DIL switches are set correctly.
Information on setting the DIL switches can be found in chapter 1.2.2.
Festo P.BE-CP-DI01-EN en 0007a
1-37
1. Installation
You can connect the following CP modules to the CP extension connection:
– CP input module with 16 inputs, either with 8 M12 plugs
(sockets assigned twice) or 16 M8 plugs (sockets assigned once).
– CP output module with 8 outputs each with 0.5A. The module is also supplied with power via the CP extension connection. The load voltage must be supplied separately via an M18 plug.
– CPV valve terminals in sizes 10, 14 and 18 mm. These are available with 4, 6 or 8 CP valve plates.
– CPA valve terminals in sizes 10 and 14 mm. These are available for a field bus connection with max. 8 doublesolenoid or 16 single-solenoid valve plates.
Please note
The CPV Direct can be extended by maximum:
– one CP input module
– one CP valve terminal or one CP output module
1-38
Festo P.BE-CP-DI01-EN en 0007a
1. Installation
Caution
The maximum length of line between the CPV Direct and the last CP module must not exceed 10 m.
The CP connecting cables must have special electrical characteristics. Therefore, always use Festo CP connecting cables.
You can obtain ready-to-use cables from Festo. These are available in various lengths and designs. A summary can be found in Appendix A.
Seal the unused CP connections on your CP system with the appropriate seal provided. In this way, you will comply with protection class IP65.
The following diagram shows some possible extensions.
Festo P.BE-CP-DI01-EN en 0007a
1-39
1. Installation
Extension to the CP system
CPV Direct Output module or CP valve terminal
Input module
Settings of the switch elements on the iti DIL it h
1
2 3
1
1
2
4
1
2
1
2
5
4
2
15 13
3
5
2 3
1
2
Total cable length of the CP system maximum 10 m
1
CPV Direct
2
CP connecting cable 0.5 m, 2 m, 5 m, 8 m
3
CP input module with 16 inputs (8 M12, 16 M8 plugs)
4
CP output module with 8 outputs (8 M12 plugs)
5
CPV or CPA valve terminal
Fig. 1/24: Extension possibilities of the CPV Direct
1-40
Festo P.BE-CP-DI01-EN en 0007a
Commissioning PROFIBUS-DP
Chapter 2
Festo P.BE-CP-DI01-EN en 0007a
2-1
2. Commissioning PROFIBUS-DP
Contents
2.
Commissioning PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1
2.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
2.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.2
Address assignment of the CPV valve terminal . . . . . . . . . . . . . . . . . . . . . . .
2.1.3
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2
Configuration with a Siemens master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1
Preparations for COM PROFIBUS 3.x and 5.0
2.2.2
COM PROFIBUS 3.x
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.3
COM PROFIBUS 5.0
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.4
Configuration examples for COM PROFIBUS 3.x and 5.0
. . . . . . . . . . . . . . . .
2.2.5
Input and output addresses with COM PROFIBUS 3.x and 5.0
. . . . . . . . . . .
2.2.6
STEP 7 V4.x / 5.1 - Hardware configurator . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.7
Example of addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.8
Commissioning the CP system on the PROFIBUS-DP . . . . . . . . . . . . . . . . . . .
2.3
Operation with general DP Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.1
Bus run-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.2
Sending a parametrizing telegram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.3
Sending configuration data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.4
Requesting diagnostic information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.5
Starting cyclic data transmission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.6
Summary of implemented functions and service access points (SAP) . . . . .
2.3.7
Bus parameter/reaction times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3.8
Transmission times on the PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4
Device data base (GSD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-26
2-28
2-28
2-29
2-31
2-32
2-32
2-34
2-35
2-35
2-36
2-3
2-3
2-4
2-6
2-9
2-9
2-11
2-15
2-18
2-19
2-20
2-25
2-2
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.1
Preparing the CPV valve terminal for commissioning
2.1.1 Switching on the operating voltages
Common supply
Separate supply
Please note
Please observe also the switching-on instructions in the manual for your PLC controller.
When the controller is switched on, it automatically carries out a comparison between the NOMINAL and the ACTUAL configurations. For this configuration run it is important that:
– the specifications for the field bus configuration are complete and correct.
– the power supplies for the PLC and the field bus slaves are switched on either simultaneously or in the sequence specified below.
Please note the following when switching on the power supply:
If there is a common power supply for the control system and all the field bus slaves, the power should be switched on via a central power unit or switch.
If the control system and the field bus slaves have separate power supplies, the power should be switched on in the following sequence:
1. the power supply for all the field bus slaves
2. the power supply for the controller.
Festo P.BE-CP-DI01-EN en 0007a
2-3
2. Commissioning PROFIBUS-DP
2.1.2 Address assignment of the CPV valve terminal
The CPV valve terminal with field bus direct connection always occupies 16 output addresses, irrespective of the number of valve coils fitted on it. This enables the CPV valve terminal to be extended at a later stage without the need to shift the addresses.
The diagram below shows the addressing sequence of the individual CPV valve plates.
2-4
0-1
2-3
4-5
6-7
8-9 12-13
10-11 14-15
Fig. 2/1: Address assignment of a CPV valve terminal
– A valve location on the CPV valve terminal always occupies 2 addresses, even if it is fitted with a reserve plate or pressure isolation plate. If a valve location is fitted with a double-solenoid valve, the following allocation applies:
– pilot solenoid 14 occupies the lower-value address,
– pilot solenoid 12 occupies the higher-value address.
The higher-value address remains unused with singlesolenoid valves.
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
– Addresses are assigned on the CPV valve terminal from left to right and on the individual valve locations from the front to the rear.
5 4 3 2 1
9 8 7 6
BUS
POWER
1 3 5 7 1 3 5 7
0 2
AB x
4 6 0 2
AB x+1
4 6
AB: output byte
Fig. 2/2: Address assignment of the CPV valve terminal (outputs) with example for AB20 and AB21
Festo P.BE-CP-DI01-EN en 0007a
2-5
2. Commissioning PROFIBUS-DP
2.1.3 General information
FREEZE and SYNC
The operating modes FREEZE and SYNC are supported by the
CP system in accordance with EN 50170 (DIN 19245).
The use of the FREEZE or SYNC command depends on your controller. Please refer to the documentation for your field bus module for further information.
Caution
In the following cases, the FREEZE or SYNC mode will be automatically reset:
– when the CP system is switched on/off
– when the field bus module has stopped.
The FREEZE mode will also be automatically reset in the following case:
– when the bus connection to the CP system is interrupted
(response monitoring active).
FREEZE
With this function all the inputs of the CP system can be
“frozen”. The CP system then sends a constant input image of all the inputs to the master. The following FREEZE command causes the input image to be updated. The updated input image is then sent constantly to the master.
Return to normal operation with the UNFREEZE command.
2-6
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Module consistency
DIL switch
SYNC
With this function all the outputs of the CP system can be
“frozen”. As a consequence, the CP system no longer reacts to modifications of the output image in the master. The following SYNC command causes the output image of the master to be updated.
Return to normal operation with the UNSYNC command.
Module consistency
The CP system supports the following variant of module consistency:
– via the selected format (word)
Configuration
The settings of the DIL switches for the extension to the CP system are relevant for the required DP identifiers (see chapter 1.2.2 and 1.8).
Please note
Make sure that the DIL switches are set corresponding to the extension of your CP system.
Festo P.BE-CP-DI01-EN en 0007a
2-7
2. Commissioning PROFIBUS-DP
The following table provides a summary of the possible DP identifiers for the CP system:
Extension of the CPV Direct
Only CPV Direct (no extension)
Extension with one input module
Extension with a CP valve terminal or one CP output module
Extension with a CP valve terminal/ one CP output module and one input module
ID1: 16DO
ID1: 16DO
ID2: 16DI
ID1: 16DO
ID2: 16DO
ID1: 16DO
ID2: 16DO
ID3: 16DI
DP identifier
Siemens EN50170
ID1: 033
D
ID1: 033
D
ID2: 017
D
ID1: 033
D
ID2: 033
D
ID1: 033
D
ID2: 033
D
ID3: 017
D
Comment
16 digital outputs
16 digital outputs
16 digital inputs
16 digital outputs
16 digital outputs
16 digital outputs
16 digital outputs
16 digital inputs
Fig. 2/3: Summary – DP identifiers for different extensions to the CPV Direct
1
2
Please note
Enter the identifiers, corresponding to the physical sequence of the modules, from the CPV Direct.
Example:
CPV Direct and extension with one input module.
DP identifier
16DO
16DI
Comment
16 digital outputs
16 digital inputs
2-8
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.2
Configuration with a Siemens master
Please note
Various configuration programs are available in conjunction with a Siemens master.
Note the relevant procedure with your configuration program.
The following chapters describe as an example the most important steps for configuring the Festo valve terminal with the
COM PROFIBUS or STEP 7 software. It is assumed here that the user is already familiar with the information in the manual for the COM PROFIBUS or STEP 7 software.
2.2.1 Preparations for COM PROFIBUS 3.x and 5.0
GSD
CD-ROM Utilities
1. Copy the Device data base of the valve terminal into the following directory on your PC or programmer.
– COM PROFIBUS 3.x: \COMPB3x\GSD
– COM PROFIBUS 5.0: \SIEMENS\CPBV50\GSD
The GSD file can be found on the accompanying CD-ROM or in
Internet under www.profibus.com in the “GSD Library” file: VI1000C9.GSD
Please note
Update the slave catalog when you copy the Device data base while working with COM PROFIBUS menu: “File” - “Load GSD file”
Festo P.BE-CP-DI01-EN en 0007a
2-9
2. Commissioning PROFIBUS-DP
Icons 2. There are icon files for Festo valve terminals on the CD
ROM to facilitate configuration. Copy the relevant files into the following directory on your PC or programmer:
– COM PROFIBUS 3.x: ...\COMPB3x\BITMAPS file: PB_DICP*.BMP
– COM PROFIBUS 5.0: ...\SIEMENS\CPBV50\BITMAPS file: PB_DICP*.DIB
3. Edit the following fields in the menu “Configure” in the mask “Bus parameter”:
– Bus profile
– Baud rate
Further information (directories, etc.) can be found in the file
“Readme” in the main directory of the CD ROM.
2-10
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.2.2 COM PROFIBUS 3.x
Selecting the station
1 2 3
4
Fig. 2/4: Station selection with COM PROFIBUS 3.x (explanations see text. The masks shown cannot all be seen simultaneously)
1. Use the left-hand mouse key to mark the slave type
“VALVES” in the slave catalog.
The slave type “VALVES” will appear if you have copied the Device data base correctly (see step 1 of the preparations).
Festo P.BE-CP-DI01-EN en 0007a
2-11
2. Commissioning PROFIBUS-DP
Configuring
2. Position the mouse under the icon of the master and click once 2 .
The mask “PROFIBUS Address” will appear 3 .
3. Select the address identical to the selected setting of the
DIL switch in the switch module (see chapter 1.2.2) and confirm.
The mask “Slave Parameters” will appear 4 .
4. Select the station type “Festo CPV DI01” and confirm. The icon of the Festo valve terminal will appear under the graphic of the master. (Prerequirements: You have copied the icon file as described in step 2 of the preparations).
Station selection is then completed.
Configuration with COM PROFIBUS 3.x
Prerequirements:
– The Device data base must be in the directory of your
PC/programmer.
– The mask “Bus parameter” must be edited (bus profile, baud rate)
– The PROFIBUS address must be assigned (see above)
– The station type “FESTO CPV DI01” must be selected (see above)
Access the mask “Configure”.
1. Double-click with the left-hand mouse key or once with the right-hand key on the icon of the Festo valve terminal.
2. Select “Configure” in the menu which appears. The mask
“Configure” appears (Fig. 2/5).
2-12
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Fig. 2/5: Configuration with COM PROFIBUS 3.x (example with extension with one CP input module)
The program has already automatically entered the DP identifier for the 16 inputs and outputs of the CPV valve terminal in this mask (line 1).
3. Enter the DP identifiers for the extensions to your CP system in lines 2 and 3 in the column “Identifier” (summary see Fig. 2/3).
Alternative entry of the system extension in the mask
“Order Number”
You can also enter the identifiers in a mask.
1. Mark the next unused field in the column “Order number” and click on the button “Order No. ...”.
The mask “Select by Order Number” will appear
(Fig. 2/6).
2. Mark the entry which corresponds to your system extension and confirm with “Accept”.
Festo P.BE-CP-DI01-EN en 0007a
2-13
2. Commissioning PROFIBUS-DP
Fig. 2/6: Entering the system extension in a mask with COM
PROFIBUS 3.x
3. Repeat step 2 if you wish to include further modules in the system extension.
Read further in chapter 2.2.4.
2-14
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.2.3 COM PROFIBUS 5.0
1 2
Selecting the station
3 4
5
Fig. 2/7: Station selection with COM PROFIBUS 5.0 (explanations see text)
1. Open the directory \DP-Slave\Valves\... in the Hardware
Catalog 1 .
The Festo valve terminals will be listed. (Prerequirements:
You have copied the Device data base as described in step
1 of the preparations).
Festo P.BE-CP-DI01-EN en 0007a
2-15
2. Commissioning PROFIBUS-DP
Configuring
2-16
2. Click with the left-hand mouse key on the icon of the CPV
Direct in the Hardware Catalog 2 . With the mouse key pressed down pull the icon onto the PROFIBUS line on the
DP Master 3 .
The icon of the valve terminal will appear 4 .
(Prerequirements: You have copied the icon file as described in step 2 of the preparations).
3. Double-click on the icon of the valve terminal 4 .
The mask “Slave properties” will appear 5 .
4. Set the PROFIBUS address identical to the setting on the
DIL switch in the switch module of the CPV Direct (see chapter 1.2.1) and confirm.
Station selection is then completed.
Configuration with COM PROFIBUS 5.0
Prerequirements:
– The Device data base must be in the directory of your
PC/programmer.
– The mask “Bus parameter” must be edited (bus profile, baud rate)
– The PROFIBUS address must be assigned (see above)
– The station type “FESTO CPV DI01” must be selected (see above)
Access the mask “Configure” as follows:
1. Double-click with the left-hand mouse key or once with the right-hand key on the icon of the Festo valve terminal.
Now click “Configure” in the menu which appears.
The mask “Configure” will appear (Fig. 2/8).
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Fig. 2/8: Configuration with COM PROFIBUS 5.0
The program has already automatically entered the DP identifier for the 16 outputs of the CPV valve terminal in this mask.
2. Enter the extensions to your CP system in lines 2 and 3 in the column “Identifier” (summary see Fig. 2/3).
Alternative entry of the system extension in the mask
“Module selection”
1. Mark the next unused field in the column “Module” and click on the button “Module...”.
The mask “Module selection” will appear (Fig. 2/9).
2. Mark the entry which corresponds to your system extension and confirm with “Apply”.
3. Repeat step 2 if you wish to include further modules in the system extension.
Festo P.BE-CP-DI01-EN en 0007a
2-17
2. Commissioning PROFIBUS-DP
Fig. 2/9: Alternative entry of the system extension in the mask “Module selection”
2.2.4 Configuration examples for COM PROFIBUS 3.x and 5.0
Example 1:
CPV Direct extended with one input module with 16 digital inputs.
DP identifier
1 16DO
2 16DI
Order number or module
Comment
Entered automatically
Input module, 16 digital inputs
DP identifier
1 16DO
2 16DO
3 16DI
Example 2:
CPV Direct extended with one CPV valve terminal and an input module with 16 digital inputs.
Order number or module
Comment
Entered automatically
CPV valve terminal with 8 valve plates
(double-solenoid), 16 outputs
Input module, 16 digital inputs
2-18
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.2.5 Input and output addresses with COM PROFIBUS 3.x and 5.0
Addressing Enter the starting addresses of the inputs and outputs under
I Address or O Address (see Fig. 2/5 or Fig. 2/8).
Example 3:
Extension as in example 1, addresses as from input/output word 42 used.
DP identifier Order number or module
1 16DO
2 16DI CP-E16: 16DI
Example 3 – input and output addresses
Comment Input address
Output address
P042
P042
Please note
The function “Auto address.” carries out an automatic assignment of the unused addresses of the system with a marked I/O address range, depending on the system limits.
Configuration and address assignment are then completed.
Festo P.BE-CP-DI01-EN en 0007a
2-19
2. Commissioning PROFIBUS-DP
2.2.6 STEP 7 V4.x / 5.1 - Hardware configurator
GSD
CD ROM utilities
Preparations
1. Copy the Device data base of the valve terminal into directory \STEP7\S7DATA\GSD of your PC or programmer. You will find the Device data base on the accompanying CD ROM or in Internet under www.profibus.com in the “GSD Library” file: VI1000C9.GSD
The Device data base can either be:
S copied manually into the above-mentioned directory
(e.g. with Windows Explorer) or
S loaded via menu item “Extras” – “Install new GSD” in the mask “HW Config”
Please note
Update the hardware catalogue when you copy the Device data base while working with STEP 7.
Menu in Hardware config: “Extras” – “Update catalog”
Please note
As from STEP 7 V4.02, Device data base are saved within the STEP 7 project (station Device data bases). This can cause the updating/loading of new Device data bases to be carried out supposedly incorrectly. Please inform yourself about handling the station Device data bases in the
STEP 7 help.
2-20
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Icons 2. There are Bitmap files with icons for Festo valve terminals on the CD ROM to facilitate configuration.
Copy the files PB_DICP*.BMP into directory
\STEP7\S7DATA\NSBMP on your PC/programmer.
The Bitmaps can either be:
S copied into the above-mentioned directory or
S loaded via menu item “Extras” – “Install new GSD” data type “Bitmap” in HW Config
3. Edit the mask “Properties of the DP Master”.
– - Bus profile
– - Baud rate
4. Activate the DP Master in the rack.
Further information (directories, etc.) can be found in the file
“Readme” in the main directory of the CD ROM.
Festo P.BE-CP-DI01-EN en 0007a
2-21
2. Commissioning PROFIBUS-DP
Station selection and configuration with STEP 7
1 2
3 4
Fig. 2/10: Station selection with STEP 7 V4.x/5.1 – HW Config (the masks shown are not all visible simultaneously, see text)
1. Click on the catalogue icon. The Hardware Catalog opens
1 .
2. Use the left-hand mouse key to mark station type “FESTO
CPV DI01” 2 (\PROFIBUS-DP\Further Field Devices\
VALVES) in the Hardware Catalog.
The slave type “VALVES” will appear under folder “Further
Field Devices”, if you have copied the Device data basecorrectly (see step 1 of the preparations).
2-22
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
3. Hold the left-hand mouse key pressed down and pull the cursor onto the graphic PROFIBUS lineon the DP Master
(drag and drop) 3 .
The mask “Properties - PROFIBUS Node” will appear.
4. Select the address identical to the selected setting of the
DIL switch in the switch module (see chapter 1.2.2) 4 and confirm.
The icon of the valve terminal appears in the PROFIBUS line (see 5 in Fig. 2/11).
7 5 6
Fig. 2/11: Configuration with STEP 7 V4.x / 5.1 – Hardware Catalog (example for extension with one CP input module)
Festo P.BE-CP-DI01-EN en 0007a
2-23
2. Commissioning PROFIBUS-DP
Adressing (see Fig. 2/11)
5. Mark the icon of the valve terminal to be configured in the HW Config 5 . The configuration data with the columns “Module DP ID”, “Order Number”, “I Address”,
“O Address”, “Comment” appear in the table in the lower half of the monitor screen.
6. Open the directory “Festo CPV DI01” in the Hardware
Catalog and mark a module corresponding to the extension to your CP system 6 .
7. With the mouse key pressed down, pull the marked module out of the Hardware Catalog and onto the next unused line of the configuration table 7 .
The address assignment is carried out automatically.
If necessary, repeat steps 6 and 7 for further modules.
Please note
Pull the modules into the configuration table according to the physical sequence of the extensions to your CP system.
Modifying the address
The input addresses and output addresses are assigned automatically by STEP 7. Proceed as follows, if you wish to modify this address assignment:
Open the mask “Properties - DP Slave” by double-clicking the appropriate line in the configuration table of the DP slave and modify the starting address of the inputs/outputs.
2-24
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Please note
In S7-400 controllers, 4 bytes of addresses are always reserved per DP identifier.
Station selection and configuration are then completed.
2.2.7 Example of addressing:
Extension to the CP system
1 CPV Direct (without extension)
2 CPV valve terminal with 8 double-solenoid valves
3 CP input module, 16 inputs
DP identifier
16DO
16DO
16DI
Example: Input and output address (see Fig. 2/12)
1
CPV Direct
2
CPV valve terminal with
8 valve plates
3
CP input module with 16 inputs
1 2
I/O address (IN/OUT)
O20.0...21.7
O22.0...23.7
I20.0...21.7
3
O20.0...21.7
O22.0...23.7
I20.0...21.7
Fig. 2/12: Example – Addressing the inputs and outputs of a CP system with CPV Direct and maximum extension
Festo P.BE-CP-DI01-EN en 0007a
2-25
2. Commissioning PROFIBUS-DP
2.2.8 Commissioning the CP system on the PROFIBUS-DP
Configuration run
Please note
Please observe also the switching-on instructions in the manual for your PLC controller.
Proceed as follows:
1. Connect the field bus cable to the CPV Direct.
2. Switch on the power supplies:
– for all field bus slaves
– for the CP system
3. Switch on the power supply for the master module.
Some master systems automatically carry out a comparison between the NOMINAL and the ACTUAL configurations (= DIL switch setting), when you switch on the system. For this configuration run it is important that:
– the specifications for the NOMINAL configuration are complete and correct (see also chapter 2.1.2).
– the power supplies for the PLC and the field bus slaves are switched on either simultaneously or in the sequence specified below.
2-26
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Recommendation:
Providing the safety concept of your machine/system permits, commission the CP system with both operating voltages
(pins 1 and 2), but without compressed air. You therefore have a suitable test function which does not trigger undesired reactions.
Please note
A CP valve location occupies two addresses.
The following applies:
– lower-value address: pilot solenoid 14
– higher-value address: pilot solenoid 12
Festo P.BE-CP-DI01-EN en 0007a
2-27
2. Commissioning PROFIBUS-DP
2.3
Operation with general DP Master
The Festo CP system can be controlled from any PLC, PC or industrial PC with a PROFIBUS-DP module in accordance with
EN 50170 (DIN 19245).
Information on the functions FREEZE, SYNC and the DP identifiers can be found in chapter 2.1.3.
2.3.1 Bus run-up
Before the CP system can be commissioned properly, the DP
Master must perform the following functions in the sequence specified.
1. send a parametrizing telegram
2. send a configuration telegram
3. request diagnostic information
4. start cyclic data transmission
The structure and contents of the individual telegrams are described in the following chapters.
2-28
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.3.2 Sending a parametrizing telegram
The parametrizing data are transmitted from the DP Master to the CP system with the function Set_Prm .
2
3
0
1
Octet 1 Station status
Bit Meaning Explanation
Reserved —
—
—
WD_On
4
5
6
7
Freeze_Req
Sync_Req
Unlock_Req
Lock_Req
Response monitoring of the CP system on/off: logical “0”: Off logical ”1”: On logical “0”: logical ”1”: logical “0”: logical ”1”:
Freeze mode not requested by master
Freeze mode set by master
Sync mode not requested by master
Sync mode set by master
Bit 7 Bit 6 Explanation
0 0
0 1 min T
SDR
+ slave parameters may be overwritten
Release CP system for other masters
1
1
0
1
CP system blocked for other masters
Release CP system for other masters
Festo P.BE-CP-DI01-EN en 0007a
2-29
2. Commissioning PROFIBUS-DP
Octet
2 and 3
4
5 and 6
7
8...32
Designation
WD_Fact_1
WD_Fact_2
Group_Ident
User_Prm_Data
Further octets
Minimum Station Delay
Responder (min T
SDR
)
Ident_Number
Explanation
Range 1...255: The response monitoring time of the
CP system is transferred with these two octets:
TWD [s] = 10 ms x WD_Fact_1 x WD_Fact_2
The minimum time the CP system must wait before the reply telegram may be sent to the DP Master.
Transfer of Ident number (= 009C) of the CP system; parametrizing telegrams to the CP system will only be accepted if the transferred and the programmed
Ident numbers are the same.
Not supported by the CP system
Not supported by the CP system
2-30
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.3.3 Sending configuration data
The configuration data are transmitted from the DP master to the CP system with the function Chk_Cfg .
Summary of parameters (Chk_Cfg)
Octet 1-n: DP identifier
Permitted identifiers for Festo CPV Direct
(see also Fig. 2/3):
Extension to the CP system
CPV Direct (without extension)
Extension with one input module
Extension with a CP valve terminal or one CP output module
Extension with a CP valve terminal or one CP output module and one input module
DP identifier decimal hex
Octet 1 033
Octet 1: 033
Octet 2: 017
Octet 1: 033
Octet 2: 033
Octet 1: 033
Octet 2: 033
Octet 3: 017
Octet 1 021
Octet 1: 021
Octet 2: 011
Octet 1: 021
Octet 2: 021
Octet 1: 021
Octet 2: 021
Octet 3: 011
Comment
16 digital outputs
16 digital outputs
16 digital inputs
16 digital outputs
16 digital outputs
16 digital outputs
16 digital outputs
16 digital inputs
Example:
Configuring a CPV Direct extended with one input module.
Comment
1
2
Octet DP identifier decimal hex
033
017
021
011
16DO of the CPV Direct
16DI of the input module
Festo P.BE-CP-DI01-EN en 0007a
2-31
2. Commissioning PROFIBUS-DP
2.3.4 Requesting diagnostic information
The diagnostic data are requested by the CP system with the function Slave_Diag . A description of this function can be found in chapter 3.3.2, Diagnosis with PROFIBUS-DP.
2.3.5 Starting cyclic data transmission
The cyclic exchange of data is carried out with function
Data_Exchange .
With this function, the output data for the CP system are transferred as an octet string of length x. The length of the octet string depends on the number of identifier bytes.
Please note
With the function Data_Exchange, the CP system expects the output information for the valves and electric outputs.
The input information is sent as a reply telegram to the master.
Parameter summary (Data_Exchange) for maximum equipment fitted:
Octet 1: O data byte_1
Bit 0: outputs x
*)
Bit 1: output x+1
Bit 2: output x+2
Bit 3: output x+3
Bit 4: output x+4
Bit 5: output x+5
Bit 6: output x+6
Bit 7: output x+7
2-32
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
Octet 2: O data byte_2
Bit 0: output x+8
Bit 1: output x+9
...
Bit 7: output x+15
Octet 3: I/O data byte_3
Bit 0: Input/output y
*)
Bit 1: input/output y+1
...
Bit 7: input/output y+7
Octet 4: I/O data byte_4
Bit 0: input/output y+8
Bit 1: input/output y+9
...
Bit 7: input/output y+15
Octet 5: I/O data byte_5
Bit 0: Input/output z
*)
Bit 1: input/output z+1
...
Bit 7: input/output z+7
Octet 6: I/O data byte_6
Bit 0: input/output z+8
Bit 1: input/output y+9
...
Bit 7: input/output z+15
*) x, y, z = Address offset of master module
Festo P.BE-CP-DI01-EN en 0007a
2-33
2. Commissioning PROFIBUS-DP
2.3.6 Summary of implemented functions and service access points (SAP)
Function Available
Data_Exchange
RD_Inp
RD_Outp
Slave_Diag
Set_Prm
Chk_Cfg
Get_Cfg
Global_Control
Set_Slave_Add
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Destination SAP
(DSAP)
NIL
56
57
60
61
62
59
58
55
2-34
Festo P.BE-CP-DI01-EN en 0007a
2. Commissioning PROFIBUS-DP
2.3.7 Bus parameter/reaction times
Baud rate
(kBaud)
.. 187.5
500
1500
3000
6000
12000 max. T
SDR
(T
Bit
) max. T
SDR
(T
Bit
)
60
100
150
250
450
800
2.3.8 Transmission times on the PROFIBUS-DP
Please note
Note here the cycle time of your PLC and the update time of the PROFIBUS-DP.
The delay time within the CP system depends on the amount of data and, therefore, on the extension of the CP system. It amounts to: < 2 ms.
Please refer to the manual for your controller for calculating the total transmission time.
Festo P.BE-CP-DI01-EN en 0007a
2-35
2. Commissioning PROFIBUS-DP
2.4
Device data base (GSD)
CD ROM utilities
Internet
The accompanying CD ROM contains the Device data base
(GSD) with the specific standardized Device data bases for the CP system. Further information can be found in the file
“Readme” on the CD ROM.
Current GSD files can also be found in the Internet under www.profibus.com in the “GSD Library”.
The Device data base contains a selection of identifiers in addition to the slave-typical entries (Ident number, revision, etc.).
Enter the identifiers for the CP system in the physical sequence of the modules.
2-36
Festo P.BE-CP-DI01-EN en 0007a
Diagnosis PROFIBUS-DP
Chapter 3
Festo P.BE-CP-DI01-EN en 0007a
3-1
3. Diagnosis PROFIBUS-DP
Contents
3.
Diagnosis PROFIBUS-DP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1
3.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
3.2
Locating faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3
Diagnosis with PROFIBUS-DP
3.3.1
Diagnostic words
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2
Diagnostic information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1
General DP Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.2
Siemens SIMATIC S5/S7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5
Online diagnosis mit COM PROFIBUS 5.0
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6
Online diagnosis with STEP 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6.1
Diagnostic buffer STEP 7 (version 4.x, 5.1) . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6.2
Device-specific diagnosis with STEP 7 (version 5.1)
3.7
Short circuit/overload
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.1
Output module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.2
Sensor supply to an input module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-12
3-17
3-18
3-18
3-21
3-22
3-22
3-24
3-26
3-26
3-27
3-3
3-3
3-4
3-6
3-7
3-8
3-8
3-2
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
3.1
Diagnosis with LEDs
The LEDs on the cover indicate the operating status of the
CPV valve terminal.
1
Red LED: bus status/error
(BUS)
2
Green LED: operating voltage display (POWER)
3
Yellow LED row for pilot solenoid
12
4
Yellow LED row for pilot solenoid
14
1
2
Fig. 3/1: LEDs on the CPV Direct
BUS
POWER
3 4
5 4 3 2 1
9 8 7 6
3.1.1 Normal operating status
In normal operating status the green power LED lights up.
lights up; flashes; out
LED
BUS
Colour out
Operating status normal
Error treatment none
POWER green lights up normal none
Fig. 3/2: Normal operating status
Festo P.BE-CP-DI01-EN en 0007a
3-3
3. Diagnosis PROFIBUS-DP
3.1.2 Error displays of the BUS/POWER LEDs
LED Colour
POWER out
Error diagnosis with the green LED (POWER)
Operating status
Operating voltage for the electronics is not switched on
Error treatment
S Check the operating voltage connection (pin 1)
Load voltage for CP valves
<
20.4 V
S
Check the load voltage supply
(pin 2)
POWER green flashes fast
POWER green flashes slowly
Load voltage for CP valves < 10 V S Check the load voltage supply
(pin 2)
Fig. 3/3: Error diagnosis with the green POWER LED
Load voltage faults are always shown with the green LED,
(irrespective of the diagnostic mode set).
If the device-related diagnosis is activated, the faults will also be communicated to the master PLC via the field bus direct connection.
3-4
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
LED
BUS
Colour red lights up
BUS red flashes fast
Error diagnosis with the red LED (BUS):
Operating status
Hardware fault
Error treatment
S Servicing required
PROFIBUS address not permitted S Correct address setting
(0,...,125)
BUS red flashes slowly
(1 second intervals)
BUS flashes red out briefly
Field bus connection not correct.
Possible causes:
– Station number not correct (e.g.
address assigned twice)
– Switched-off or defective field bus module
– Interrupted, short-circuited or faulty field bus connection
– Configuration incorrect, master configuration setting in switch module
Check the ...
S address setting
S field bus module
S field bus connection
S configuration of the master and the setting in the switch module
Switch module missing
Switch module defective
S
Insert switch module
S
Replace switch module
Fig. 3/4: Error diagnosis with the red BUS LED
Festo P.BE-CP-DI01-EN en 0007a
3-5
3. Diagnosis PROFIBUS-DP
3.1.3 LEDs for the status display of the valve solenoid coils
There is a yellow LED for each valve solenoid coil (see
Fig. 3/1). This LED indicates the switching status of the valve solenoid coil.
LED Colour out yellow lights up
Switch position of valve solenoid coil
Basic position
– switch position or
– basic position
Meaning logical 0 (no signal) logical 1 (signal present) logical 1 but:
– load voltage of the valves lies below the permitted tolerance range ( < 20.4V DC) or
– compressed air supply not correct or
– pilot exhaust blocked or
– servicing required
Fig. 3/5: LEDs for the status display of the valve solenoid coils
Please note
If there is no valve coil, the assigned LED will not indicate control of the output.
3-6
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
3.2
Locating faults
A deviation in the actual extension of your CP system from the extension set in the switch module can lead to problems when the system is started. Read further in chapter 1.8. The following table shows the reaction.
Extension to the CP system (examples)
>
Deviation
Extension greater than setting of DIL switches
<
Extension smaller than setting of DIL switches
Fig. 3/6: Reaction when system extension differs from DIL switch setting
Reaction
System starts.
Superfluous, nonconfigured module is ignored
System starts.
Carry out device-specific diagnosis (see chapter 3.3)
3-7
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
3.3
Diagnosis with PROFIBUS-DP
The CP system supports diagnostic possibilities via the PRO-
FIBUS in accordance with EN 50170 (DIN 19245). The devicespecific diagnosis is supported.
Please note
The identifier-related or channel-related diagnosis listed in
EN 50170 (DIN 19245) is not supported.
3.3.1 Diagnostic words
The following error states of the CP system are grouped into diagnostic words and passed on to the DP master:
– Failure of the load voltage for the valves (pin 2)
– Short circuit in power supply to the sensors
– Failure of the load voltage supply at the output modules
– Short circuit/overload at the output modules
– Interruption in CP connection on various CP modules
– Drop below tolerance in voltage for CP valves ( < 20.4 V)
3-8
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
Diagnostic possibilities
As a slave on the PROFIBUS-DP the CP system offers extensive diagnostic possibilities via the PROFIBUS-DP.
Please note
The diagnostic information is only sent to the master system when device-related diagnosis is activated in the switch module. To do this, set switch element 8 of the
8-element DIL switch to “ON”.
The diagram below shows the steps which are important for diagnosing the CP system.
7 6 5 4 3 2
1
1 0
1
Bit
Station status 1
CPV Direct is without voltage or the bus plug is not inserted
Fig. 3/7: First diagnostic step
Planned extension of the CP system is not the same as the extension set with the DIL switch (see chapters 3.2 and
1.8)
Festo P.BE-CP-DI01-EN en 0007a
3-9
3. Diagnosis PROFIBUS-DP
Below are the diagnostic bits which require further diagnostic steps.
7 6 5 4 3
1
2 1 0 Bit
Station status 1
Device-related diagnosis 1 exists
7 6 5 4
1
3 2 1 0
1
Bit
Device-related diagnosis 1
(see Fig. 3/14)
Error on CP string/
CP valve terminal
There is at least one error
7 6 5 4 3 see Fig. 3/15
2 1 0 Bit
Device-related diagnosis 2
Fig. 3/8: Further diagnostic steps
When you are commissioning your system, it can in some cases be useful if you switch off the device-related diagnosis.
If your controller does not start, try the setting “Device-related diagnosis inactive” on the 8-element DIL switch (see chapter 1.2.2).
3-10
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
Diagnostic words
Summary of diagnostic bytes
Several diagnostic words are provided for each bus slave. The diagnostic words and their meanings in conjunction with the
Festo CP system are as follows:
Byte
*
Octet
**
Diagnostic address Diagnostic address + 1 Octet
**
Byte
*
0
2
4
1
3
5
Station status 1
Station status 3
Station status 2
Master address
(Diag. master_Add)
Manufacturer identification Manufacturer identification 6
2
4
6 7
(Ident_number high byte 00
H
Header
)
(Ident_number low byte C9
H
)
Device related diagnosis 1
(summary of errors)
8 9 Device related diagnosis 2
(error byte CPV Direct)
Always logical “0”
Heavy print = Content will be modified by the CP system
* = Siemens
** = EN50170
8
10
1
3
5
7
9
Fig. 3/9: Diagnostic words
Festo P.BE-CP-DI01-EN en 0007a
3-11
3. Diagnosis PROFIBUS-DP
3.3.2 Diagnostic information
The following diagnostic information can be requested by the
DP master from the CP system with the function Slave_Diag.
The CP system replies with an octet string of length 10. The procedure for reading out this diagnostic information with a
SIMATIC S5/S7 system is described in chapter 3.4.2.
Structure of station status 1
Octet 1: station status_1
Bit Meaning Explanation
0
1
2
3
4
Diag.Station_Non_Existent
Diag.Station_Not_Ready
Diag.Cfg_Fault
Diag.Ext_Diag
Diag.Not_Supported
CP system is no longer/not yet addressable.
Possible causes:
– operating voltage not applied
– data cable interrupted
– fault in data cable
CP system for data exchange not yet ready
The configuration data received from the master do not correspond to those ascertained by the CP system.
Device-related diagnosis exists. Possible causes:
– cable fracture on input/output module
– short circuit/overload at electric outputs
– V
– V
– V valves outputs sensor
20.4 V
10 V
10 V
Logical“1”: CP system does not support the function requested
5
6
Diag.Invalid_Slave_Response
Diag.Prm_Fault
Always logical “0” (set by CP system)
Last parametrizing telegram faulty
7 Diag.Master_Lock
Heavy print = Valve terminal related bits
Always logical “0” (set by CP system)
Fig. 3/10: Diagnostic bits of station status_1
3-12
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
Structure of station status 2
Octet 2: station status_2
Bit Meaning Explanation
0
1
Diag.Prm_Req
Diag.Stat_Diag
Logical “1”: master must configure the CP system again
Logical “1”: master must request diagnostic data until this bit is set to logical ”0”
4
5
2
3
–
Diag.WD_On
Diag.Freeze_Mode
Diag.Sync_Mode
Always logical “1” (set by CP system)
Logical “1”: Watchdog activated
Logical “1”: Freeze activated
Logical “1”: Sync activated
6
7
–
Diag.Deactivated
Heavy print = Valve terminal related bits
Reserved
Always logical “0” (set by CP system)
Fig. 3/11: Diagnostic bits of station status_2
Structure of station status 3
Octet 3: station status_3
Bit Meaning
0...6
–
7 Diag.Ext_Diag_Overflow
Fig. 3/12: Diagnostic bits of station status_3
Explanation
Reserved
Always logical “0” (set by CP system)
Festo P.BE-CP-DI01-EN en 0007a
3-13
3. Diagnosis PROFIBUS-DP
Octets 4...7: summary
Octet Designation
4 Diag.Master_Add
Further octets
5...6
Ident_Number
7 Ext_Diag_Data
(Device-related diagnosis)
Explanation
Master address:
The address of the master, which parametrized the
CP system, is entered in this octet.
Manufacturer identification:
These octets contain the manufacturer identifier.
009C h for the CPV Direct.
Header device-related diagnosis:
This octet represents the header for the device diagnosis. The CP system enters the value 4 in this octet, i.e. 4 octets “Device-related diagnosis” incl. header octet are provided/transmitted, irrespective of the equipment fitted on the CP system. 3 of the 4 octets are used.
Fig. 3/13: Summary of the octets 4 ...7
3-14
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
Structure of device-related diagnosis 1
Octet 8: Device-related diagnosis 1
1)
Bit Meaning Explanation
0
3
4
1
2
Common error
CP system
–
–
–
Common error
Logical “1”:
There is at least one error.
not used not used not used
Logical “1”: error CP string/CP valve terminal
5
6
–
– not used not used
7 – not used
1) Is only sent to the master PLC when the device-related diagnosis in the switch module is activated.
Heavy print = Valve terminal related bits
Fig. 3/14: Diagnostic bits of device-related diagnosis 1
Festo P.BE-CP-DI01-EN en 0007a
3-15
3. Diagnosis PROFIBUS-DP
Structure of device-related diagnosis 2
Octet 8: Device-related diagnosis 2
Bit Meaning
0
1
2
3
4
5
6
I out
I on
Short circuit/overload
V out
V sen
V val
V load
Explanation
Logical “1”:
CP connection interrupted on output module
Logical “1”:
CP connection interrupted on input module
Logical “1”:
Short circuit/overload at output module
Logical “1”: load voltage failure on output module
Logical “1”:
Short circuit/overload in sensor supply voltage < 10 V
Logical “1”: power supply for valve coils
<
20.4 V
Logical “1”: power supply for valve coils < 10 V not used 7 Ex
Heavy print = Valve terminal related bits
Fig. 3/15: Diagnostic bits of device-related diagnosis 2
3-16
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
3.4
Error treatment
With the following faults, the reaction of the CP system depends on the configured reaction of the master module:
– telegram failure
– master has stopped
– interruption in bus cable.
If the setting or configuration is successful, all the outputs
(valves and electric outputs) will be switched off or maintain their status.
Warning
S Make sure that valves and outputs are reset when the faults mentioned occur.
A dangerous situation can arise if the valves and outputs are not reset.
Please note
If the outputs are reset after PLC stop, field bus interruption or fault, please observe the following:
– single-solenoid valves move to the basic position
– double-solenoid valves remain in the current position
– mid-position valves move to the mid-position (depending on valve type): pressurized, exhausted or blocked).
Festo P.BE-CP-DI01-EN en 0007a
3-17
3. Diagnosis PROFIBUS-DP
3.4.1 General DP Master
With the function Set_Prm you have the possibility of determining the watchdog time (WD_Fact_1, Octet 2, WD_Fact_2,
Octet 3). In the event of a fault, e.g. a bus failure, the CP system will switch off all the valves and electric outputs after the parametrized time.
3.4.2 Siemens SIMATIC S5/S7
With these controllers you can determine the reaction of the
CP system to the faults mentioned (details see controller manual).
Almost all configuration programs contain the function “Response monitoring.” For the operating modes mentioned, the time specified corresponds to the drop-off time of the valves and electric outputs.
Further details on response monitoring can be found in the appropriate manuals.
3-18
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
You can set two types of error reactions of the control system:
S When a fault occurs the controller switches to the operating mode “STOP” (hard error reaction) or
S when a fault occurs the controller remains in the operating mode “RUN” (soft error reaction).
Control system
SIMATIC S5 with IM 308C
SIMATIC S7/M7
QVZ:
OB:
PEU:
Function module
OB23
OB24
OB35
OB82
OB86
Meaning STOP
Reaction to QVZ with direct periphery access
Reaction to QVZ with periphery access via process image
Reaction to PEU
Reaction to a devicerelated diagnosis
Reaction to failure of a DP slave default default default default default
Delay in quitting
Organisation module
Periphery not clear
Fig. 3/16: Error reactions of the control system
RUN
OB is programmed
OB is programmed
OB is programmed
OB is programmed
OB is programmed
Further details can be found in the appropriate manuals for the control systems.
Festo P.BE-CP-DI01-EN en 0007a
3-19
3. Diagnosis PROFIBUS-DP
Possibility of reading diagnosis for S5/S7
The diagnosis for the PROFIBUS-DP is supported by function modules in the various control systems. These function modules read out the slave diagnoses and write them in a data range in the user program.
Control system
SIMATIC S5 with
IM 308C
SIMATIC S5 with
S5-95U/DP Master
SIMATIC S5 with
SF 50/DP Master
SIMATIC S7/M7
Function module
FB 192 “IM 308C”
FB 230 “S_DIAG”
FB 230 “S_DIAG”
SFC 13 “DP NRM_DG”
See...
Manufacturer
Manual “ET 200 decentral periphery system”
Manual “ET 200 decentral periphery system”
Manual “Programmable valve terminal with SB/SF 50”
Reference manual “System and standard functions”
Siemens
Siemens
Festo
Siemens
Fig. 3/17: Possibility of reading diagnosis for S5/S7
Example of a STEP 7 user program:
STL
CALL SFC 13
REQ:=TRUE
LADDR:=W#16#03FE
Explanation
Request to read
Pointer to diagnostic address, e.g. 1022 d
= 03FE h
(see mask “Features of DP slave” in HW Config)
RET_VAL:=MW100
When faults occur, output error code
RECORD:=P#M110.0 WORD 5
Pointer to start of data range for diagnosis and length of diagnostic data
BUSY:=M10.0
Reading finished
Fig. 3/18: Example
3-20
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
3.5
Online diagnosis mit COM PROFIBUS 5.0
You can display error messages of the device-related diagnosis with COM PROFIBUS 5.0.
1. Click with the right-hand mouse key on the slave.
A menu will appear.
2. Click on“Diagnosis...”
The mask “Bus parameter DP card” will appear.
3. Select the bus parameters which correspond to your system. Confirm with OK.
A window with diagnostic information will appear.
4. Read the diagnostic information (see Fig. 3/19).
Festo P.BE-CP-DI01-EN en 0007a
Fig. 3/19: Online diagnostic information with COM
PROFIBUS 5.0
3-21
3. Diagnosis PROFIBUS-DP
3.6
Online diagnosis with STEP 7
Direct diagnostic events in conjunction with the CP valve terminal can be:
– decentral periphery: station failure
– communication between slave and master interrupted
– Faulty module
– see device-related diagnosis
– Transition from operating status START to RUN (nominal/ actual difference)
– configuration data of the CP valve terminal do not correspond to the periphery
– CP valve terminal has incorrect DIL setting
3.6.1 Diagnostic buffer STEP 7 (version 4.x, 5.1)
The diagnostic buffer of STEP 7 offers the possibility of displaying diagnostic events of the S7 system in the order in which they occur.
Prerequirements:
– HW Config has been accessed
Proceed as follows (Fig. 3/20):
1. Switch from Offline to Online 1
2. Use the right-hand mouse key to mark the CPU in the rack. Now click “Module Information” in the menu which appears.
2
3. The window “Module Information” will appear.
3
4. Select the rider “Diagnostic Buffer” 4
3-22
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
1 2
5. Mark the event and read the details on the event. These will give you more detailed information on how to proceed further and depend on the S7 controller used 5 .
3 4
6 5
Fig. 3/20: Online diagnosis via diagnostic buffer (explanation see text)
Festo P.BE-CP-DI01-EN en 0007a
3-23
3. Diagnosis PROFIBUS-DP
Module information of the CP valve terminal
6. Mark the CP valve terminal instead of the CPU (see
Fig. 3/20, 6 ). You can read further information on the status of the CP system in the window “Module Information”.
3.6.2 Device-specific diagnosis with STEP 7 (version 5.1)
You can display error messages of the device-related diagnosis with STEP 7 HW Config V5.0.
Proceed as follows (Fig. 3/21).
Prerequirements:
– HW Config. has been accessed
1. Switch from Offline to Online.
2. Click with the right-hand mouse key on the icon of the valve terminal 1 . A menu will appear.
3. Click on “Module Information”.
The window “Module Information” will appear.
4. Read the diagnostic information 2 .
3-24
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
1 2
Fig. 3/21: Device-specific diagnosis with STEP 7 V5.0
Festo P.BE-CP-DI01-EN en 0007a
3-25
3. Diagnosis PROFIBUS-DP
3.7
Short circuit/overload
Detailed information on input and output modules can be found in the manual “CP modules - electronics”.
3.7.1 Output module
If there is a short circuit or overload:
– all the digital outputs of an output module will be switched off
– the green LED “Diag” on the output module will flash fast
– the bit short circuit/overload in octet 9 “Device-related diagnosis 2” will be set to logical “1”.
Please note
The outputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error
You can delete the error by resetting all eight outputs. You can do this in one of the following ways:
3-26
Festo P.BE-CP-DI01-EN en 0007a
3. Diagnosis PROFIBUS-DP
Possibilities
S Reset all the outputs of the output module to logical “0” (RESET) or
S
Briefly interrupt the CP connection on the CP output module
S Briefly interrupt the power supply to the CP system
Explanation
– Manually or automatically in the program
– Outputs on the output module will be reset automatically
– All the outputs of the CP system will be reset automatically
The outputs can then be used again. If the short circuit/overload still exists, the outputs will be switched off again.
3.7.2 Sensor supply to an input module
If there is a short circuit, overload or voltage fault in the sensor supply:
– the sensor supply for all inputs of the module will be switched off
– the green LED “Diag” on the input module will flash fast
– the error bit V sen in octet 9 “Device-related diagnosis 2” will be set to logical “1”.
Please note
The inputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Festo P.BE-CP-DI01-EN en 0007a
3-27
3. Diagnosis PROFIBUS-DP
Deleting the error/short circuit/overload
You can delete the error in one of the following ways:
S Briefly interrupt the CP connection on the CP input module or
S Briefly interrupt the operating voltage for the CP system on the CPV Direct.
The inputs can then be interrogated again. If the short circuit/ overload still exists, the error will be shown again.
Module CP-E16-M8-Z:
The short circuit/overload will be reset automatically and the voltage will be switched on again.
3-28
Festo P.BE-CP-DI01-EN en 0007a
Commissioning the Festo field bus
Chapter 4
Festo P.BE-CP-DI01-EN en 0007a
4-1
4. Commissioning the Festo field bus
Contents
4.
Commissioning the Festo field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
4.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2
Address assignment of the CPV valve terminal . . . . . . . . . . . . . . . . . . . . . . .
4.2
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.1
Configuration with the field bus configurator . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4-3
4-3
4-4
4-6
4-7
4-2
Festo P.BE-CP-DI01-EN en 0007a
4. Commissioning the Festo field bus
4.1
Preparing the CPV valve terminal for commissioning
4.1.1 Switching on the operating voltages
Common supply
Separate supply
Please note
Please observe also the switching-on instructions in the manual for your PLC controller.
When the controller is switched on, it automatically carries out a comparison between the NOMINAL and ACTUAL configurations. For this configuration run it is important that:
– the specifications for the field bus configuration are complete and correct.
– the power supplies for the PLC and the field bus slaves are switched on either simultaneously or in the sequence specified below.
Please note the following when switching on the power supply:
If there is a common power supply for the control system and all the field bus slaves, the power should be switched on via a central power unit or switch.
If the control system and the field bus slaves have separate power supplies, the power should be switched on in the following sequence:
1. the power supply for all the field bus slaves
2. the power supply for the controller.
Festo P.BE-CP-DI01-EN en 0007a
4-3
4. Commissioning the Festo field bus
4.1.2 Address assignment of the CPV valve terminal
The CPV Direct always occupies 16 output addresses, irrespective of the number of valve coils fitted on it. This enables the CPV valve terminal to be extended at a later stage without the need to shift the addresses.
The diagram below shows the addressing sequence of the individual CPV valve plates.
4-4
0-1
2-3
4-5
6-7
8-9 12-13
10-11 14-15
Fig. 4/1: Address assignment of a CPV valve terminal
– A valve location on the CPV valve terminal always occupies 2 addresses, even if it is fitted with a reserve plate or pressure isolation plate. If a valve location is fitted with a double-solenoid valve, the following allocation applies:
– pilot solenoid 14 occupies the lower-value address,
– pilot solenoid 12 occupies the higher-value address.
The higher-value address remains unused with singlesolenoid valves.
Festo P.BE-CP-DI01-EN en 0007a
4. Commissioning the Festo field bus
– Addresses are assigned on the CPV valve terminal from left to right and on the individual valve locations from the front to the rear.
5 4 3 2 1
9 8 7 6
BUS
POWER
1 3 5 7 1 3 5 7
0 2 4
AWn.x
6 0 2 4
AWn.x+1
6
AW: output word n: slave number x: word (8 bits)
Fig. 4/2: Address assignment of the CPV valve terminal (outputs) with example for slave no. 1
Festo P.BE-CP-DI01-EN en 0007a
4-5
4. Commissioning the Festo field bus
4.2
Configuration
Please note
The CP modules occupy constantly 16 outputs or 16 inputs, irrespective of the system extension and the type of module (inputs, outputs, valves).
The settings of the DIL switches for the extension to the CP system are relevant for the number of assigned I/O addresses and station numbers (see chapter 1.2.2 and 1.8).
Please note
Make sure that the DIL switches in the switch module are set corresponding to the extension of your CP system.
If the set extension is greater than the actual extension, an error message (ACP) will be displayed.
4-6
Festo P.BE-CP-DI01-EN en 0007a
4. Commissioning the Festo field bus
4.2.1 Configuration with the field bus configurator
The field bus configurator in the FST software will help you in creating the NOMINAL configuration. The menu control and operation of the FST software is described in the appropriate
FST manual for your controller.
Proceed as follows: 1. Enter the field bus address of the field bus slave
(CP system).
2. Select the type of field bus slave (“Valve terminal 10” for
CP system).
3. Enter the number of assigned inputs/outputs byte-bybyte under IW and OW.
Please note
The entry mask of the field bus configurator shows the IWs and OWs on the screen. This stands for input words and output words, therefore 8 bits each.
Enter 2 EW or 2 AW per module (16 inputs or 16 outputs).
Please note
With a Festo field bus master you can also configure the CP system with an ACTUAL-NOMINAL comparison. An existing field bus configuration is then loaded into the master.
Festo P.BE-CP-DI01-EN en 0007a
4-7
4. Commissioning the Festo field bus
Fig. 4/3: Example – Configuring with FST 200; select CP system from slave list
Fig. 4/4: Example – Configuring with FST 200; enter number of IW or OW
4-8
Festo P.BE-CP-DI01-EN en 0007a
4. Commissioning the Festo field bus
Addressing
Please note
The addressing of the CP system via the Festo field bus is made byte-by-byte.
Note the differences from the word-by-word addressing of other field bus slaves.
Addressing the inputs/ outputs
Example
The following example shows the addressing of the inputs/ outputs with the CPV valve terminal extended with a CP valve terminal and an output module.
Master: Festo SF3
Configuration with FST 200: 2 IW and 4 OW
Field bus address of CP system: 3
1 2 3
1
CPV Direct
2
CPV valve terminal with
8 valve plates
3
CP input module with 16 inputs
O3.0.0...O3.0.7
O3.1.0...O3.1.7
Fig. 4/5: Example – Addressing with Festo field bus
O3.2.0...O3.2.7
O3.3.0...O3.3.7
I3.0.0...I3.0.7
I3.1.0...I3.1.7
Festo P.BE-CP-DI01-EN en 0007a
4-9
4. Commissioning the Festo field bus
4-10
Festo P.BE-CP-DI01-EN en 0007a
Diagnosis with the Festo field bus
Chapter 5
Festo P.BE-CP-DI01-EN en 0007a
5-1
5. Diagnosis with the Festo field bus
Contents
5.
Diagnosis with the Festo field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1
5.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
5.2
Diagnosis with the field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1
Reaction of the CPV valve terminal to faults . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2
Short circuit/overload at output module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3
Short circuit in the sensor supply on an input module . . . . . . . . . . . . . . . . .
5-3
5-3
5-4
5-6
5-7
5-8
5-8
5-9
5-10
5-2
Festo P.BE-CP-DI01-EN en 0007a
5. Diagnosis with the Festo field bus
5.1
Diagnosis with LEDs
The LEDs on the cover of the CPV valve terminal indicate the operating status of the CPV valve terminal.
1
Red LED: bus status/error
(BUS)
2
Green LED: operating voltage display (POWER)
3
Yellow LED row for pilot solenoid
12
4
Yellow LED row for pilot solenoid
14
1
2
Fig. 5/1: LEDs on the CPV Direct
BUS
POWER
3 4
5 4 3 2 1
9 8 7 6
5.1.1 Normal operating status
In normal operating status the green power LED lights up.
lights up; flashes; out
LED
BUS
Colour out
Operating status normal
Error treatment none
POWER green lights up normal none
Fig. 5/2: Normal operating status
Festo P.BE-CP-DI01-EN en 0007a
5-3
5. Diagnosis with the Festo field bus
5.1.2 Error displays of the BUS/POWER LEDs
LED Colour
POWER out
Error diagnosis with the green LED (POWER):
Operating status
Operating voltage for the electronics is not switched on
Error treatment
S Check the operating voltage connection (pin 1)
Load voltage for CP valves
<
20.4 V
S
Check the load voltage supply
(pin 2)
POWER green flashes fast
POWER green flashes slowly
Load voltage for CP valves
<
10 V
S
Check the load voltage supply
(pin 2)
Fig. 5/3: Error diagnosis with the green POWER-LED
Load voltage errors are always shown with the green LED.
5-4
Festo P.BE-CP-DI01-EN en 0007a
5. Diagnosis with the Festo field bus
LED
BUS
Colour red lights up
Error diagnosis with the red LED (BUS):
Operating status
Hardware fault
Error treatment
S Servicing required
BUS red flashes fast
Field bus address not permitted
S
Correct address setting (0...63)
BUS red flashes slowly
(1 second intervals)
BUS flashes red out briefly
Field bus connection not correct.
Possible causes:
– station number not correct (e.g.
address assigned twice)
– switched-off or defective field bus module
– interrupted, short-circuited or faulty field bus connection
– configuration faulty.
Master configuration ≠ setting in the switch module
Switch module missing
Switch module defective
Check the ...
S
S
S field bus connection
S address setting field bus module configuration of the master and the setting in the switch module
S Insert switch module
S Replace switch module
Fig. 5/4: Error diagnosis with the red BUS-LED
Festo P.BE-CP-DI01-EN en 0007a
5-5
5. Diagnosis with the Festo field bus
5.1.3 LEDs for the status display of the valve solenoid coils
There is a yellow LED for each valve solenoid coil (see
Fig. 5/1). This LED indicates the switching status of the valve solenoid coil.
LED Colour out yellow lights up switch position valve solenoid coil
Basic position
– switch position or
– basic position
Error treatment logical 0 (no signal) logical 1 (signal present) logical 1 but:
– load voltage of the valves lies below the permitted tolerance range ( < 20.4 V DC) or
– compressed air supply not correct.
or
– pilot exhaust blocked or
– servicing required
Fig. 5/5: LEDs for the status display of the valve solenoid coils
Please note
If there is no valve coil, the assigned LED will not indicate control of the output.
5-6
Festo P.BE-CP-DI01-EN en 0007a
5. Diagnosis with the Festo field bus
5.2
Diagnosis with the field bus
All diagnostic information can be evaluated directly with a
Festo PLC. For this purpose an error list is compiled in the master. All diagnostic bytes are included and continually updated in this error list.
The following errors are recognized by the CP system:
Diagnostic bit
Meaning
KCP
V
V val tol
V sen
V out
Short circuit/ overload
ACP
CP system not yet ready (during the starting phase)
Configuration error in field bus master
Load voltage failure of CP valves < 10.4 V
– CPV Direct
– CP valve terminal in the extension
Undervoltage of CP valves
<
20.4 V
– CPV Direct
– CP valve terminal in the extension
Short circuit in sensor supply to CP input module
Load voltage failure on CP output module
Short circuit/overload on CP output module
Connection to a CP module in the extension interrupted
– CP input module
– CP output module
– CP valve terminal
Fig. 5/6: Summary of diagnostic bits
The diagnostic byte is interrogated with function module 44 or in the command interpreter (CI).
Further information can be found in the PLC manual for your controller.
Festo P.BE-CP-DI01-EN en 0007a
5-7
5. Diagnosis with the Festo field bus
5.3
Error treatment
5.3.1 Reaction of the CPV valve terminal to faults
Reaction to faults in the control system
The CP valves and any existing electric outputs are switched off in the event of a fault after the following times:
Baud rate (kBaud)
31.25
62.5
187.5
375
Switch-off time
2 s
1 s
500 ms
250 ms
Fig. 5/7: Switch-off times of CP valve terminals and outputs during faults (depending on baud rate)
Please note
If the outputs are reset after PLC stop, field bus interruption or fault, please observe the following:
– single-solenoid valves move to the basic position
– double-solenoid valves remain in the current position
– mid-position valves move to the mid-position (depending on valve type: pressurized, exhausted or blocked).
5-8
Festo P.BE-CP-DI01-EN en 0007a
5. Diagnosis with the Festo field bus
5.3.2 Short circuit/overload at output module
If there is a short circuit or overload:
– all the digital outputs of the module will be switched off
– the green LED “Diag” on the output module will flash fast
– the bit short circuit/overload of the diagnostic byte will be set to “logical 1”.
Please note
The outputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error
You can delete the error by resetting all eight outputs. You can do this in one of the following ways:
Possibilities
S
Reset all the outputs of the output module to logical “0” (RESET) or
S
Briefly interrupt the CP connection on the CP output module or
S
Briefly interrupt the power supply to the CPV
Direct
Explanation
– Manually or automatically in the program
– Outputs on the output module will be reset automatically
– All the outputs of the CP system will be reset automatically
The outputs can then be reset to “logical 1”.
If the short circuit still exists, the outputs will be switched off again.
Festo P.BE-CP-DI01-EN en 0007a
5-9
5. Diagnosis with the Festo field bus
5.3.3 Short circuit in the sensor supply on an input module
If there is a short circuit, overload or voltage fault in the sensor supply:
– the sensor supply for all inputs of the module will be switched off
– the green LED “Diag” on the input module will flash fast
– the error bit in the diagnostic byte will be set to “logical
1”.
Please note
The inputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error/short circuit/overload
You can delete the error in one of the following ways:
S Briefly interrupt the CP connection on the CP input module or
S Briefly interrupt the power supply to the CPV Direct
The inputs can then be interrogated again.
If the short circuit/overload still exists, the error will be shown again.
5-10
Festo P.BE-CP-DI01-EN en 0007a
Commissioning the ABB CS31
Chapter 6
Festo P.BE-CP-DI01-EN en 0007a
6-1
6. Commissioning the ABB CS31
Contents
6.
Commissioning the ABB CS31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
6.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1.2
Address assignment of the CPV valve terminal . . . . . . . . . . . . . . . . . . . . . . .
6.1.3
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2.1
CS31 central unit as bus master
6.2.2
T200 / 07CS61 as bus master
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6-3
6-3
6-4
6-5
6-6
6-7
6-9
6-2
Festo P.BE-CP-DI01-EN en 0007a
6. Commissioning the ABB CS31
6.1
Preparing the CPV valve terminal for commissioning
6.1.1 Switching on the operating voltages
Common supply
Separate supply
Please note
Please observe also the switching-on instructions in the manual for your PLC controller.
When the controller is switched on, it automatically carries out a comparison between the NOMINAL and ACTUAL configurations. For this configuration run it is important that:
– the specifications for the field bus configuration are complete and correct.
– the power supplies for the PLC and the field bus slaves are switched on either simultaneously or in the sequence specified below.
Please note the following when switching on the power supply:
If there is a common power supply for the control system and all the field bus slaves, the power should be switched on via a central power unit or switch.
If the control system and the field bus slaves have separate power supplies, the power should be switched on in the following sequence:
1. the power supply for all the field bus slaves
2. the power supply for the controller.
Festo P.BE-CP-DI01-EN en 0007a
6-3
6. Commissioning the ABB CS31
6.1.2 Address assignment of the CPV valve terminal
The CPV Direct always occupies 16 output addresses, irrespective of the number of valve coils fitted on it. This enables the CPV valve terminal to be extended at a later stage without the need to shift the addresses.
The diagram below shows the addressing sequence of the individual CPV valve plates.
6-4
0-1
2-3
4-5
6-7
8-9 12-13
10-11 14-15
Fig. 6/1: Address assignment of a CPV valve terminal
– A valve location on the CPV valve terminal always occupies 2 addresses, even if it is fitted with a reserve plate or pressure isolation plate. If a valve location is fitted with a double-solenoid valve, the following allocation applies:
– pilot solenoid 14 occupies the lower-value address,
– pilot solenoid 12 occupies the higher-value address.
The higher-value address remains unused with singlesolenoid valves.
Festo P.BE-CP-DI01-EN en 0007a
6. Commissioning the ABB CS31
– Addresses are assigned on the CPV valve terminal from left to right and on the individual valve locations from the front to the rear.
5 4 3 2 1
9 8 7 6
BUS
POWER
1 3 5 7 1 3 5 7
0 2 4 6 0 2 4 6 n: Station number
Fig. 6/2: Address assignment of the CPV valve terminal
(outputs)
6.1.3 General information
A CP system can be fitted with different numbers of inputs and outputs. The addressing of the CPV valve terminal with
ABB CS31 direct connection is based on the regulations for the CS31 system bus.
The following applies for the CP system: 16 inputs or 16 outputs each occupy a CS31 bus address. A 16-group which has been started also requires a full CS31 bus address.
Festo P.BE-CP-DI01-EN en 0007a
6-5
6. Commissioning the ABB CS31
The following applies if the CP system is connected to an ABB
Procontic T200:
– The address designation of the inputs/outputs is different from that of a CS31 central unit.
– The appropriate module identifiers must be entered in the configuration table of the T200.
Please note
Select the range n = 0...60 for the address to be set in the CPV valve terminal. A CP valve terminal or CP output module connected to the extension can then also be addressed.
Please note
Note that the CP system occupies one or two station numbers depending on the extension.
6.2
Configuration
Please note
The CP modules occupy constantly 16 outputs or 16 inputs, irrespective of the system extension and the type of module (inputs, outputs, valves).
The settings of the DIL switches for the extension to the CP system are relevant for the number of assigned I/O addresses and station numbers (see chapter 1.2.2 and 1.8)
6-6
Festo P.BE-CP-DI01-EN en 0007a
6. Commissioning the ABB CS31
Please note
Make sure that the DIL switches in the switch module are set corresponding to the extension of your CP system.
If the set extension is greater than the actual extension, the error message “BE” will be displayed.
6.2.1 CS31 central unit as bus master
The CPV Direct offers the following on the ABB CS31
– max. 32 outputs (valves or digital outputs) and
– max. 16 inputs
The diagram below shows a summary of the addresses.
CP system
Extension
CPV Direct (without extension)
CP extension modules:
CP valve terminal or
CP output module
CP input module n: Set station number
Inputs/outputs
16O
32O
16I
Signal designation if a CS31
CPU is used
Outputs Inputs
O n,00 ... O n,15
O n+1,00 ... O n+1,15
—
—
—
I n,00...I n,15
Fig. 6/3: Configuration possibilities and addresses for a CS31 central unit
The CS31 central unit ascertains the configuration of the
CS31 system bus when it is switched on and does not require any settings.
Festo P.BE-CP-DI01-EN en 0007a
6-7
6. Commissioning the ABB CS31
Please note
With system flag KW 00,09, program processing can be blocked until the specified number of I/O modules (incl.
CP system) exists on the CS31 system bus.
1
CPV Direct
2
CPV valve terminal with
8 valve plates
3
CP input module with 16 inputs
Example: addressing with a CS31 central unit
Station number 20 is set in the CPV Direct. The CPV valve terminal has been extended with a CPV valve terminal and a
CP input module and occupies two CS31 bus addresses (station numbers).
1 2 3
O20.0.0 ... O20.15
O21.0.0 ... O21.15
I20.00 ... I20.15
Fig. 6/4: Example - Addressing with a CS31 central unit
6-8
Festo P.BE-CP-DI01-EN en 0007a
6. Commissioning the ABB CS31
6.2.2 T200 / 07CS61 as bus master
You can connect four CS31 system buses to the T200 station.
The coupler 07CS61 plugged in nearest to the T200 central unit has line no. 1, the next following have line numbers 2, 3 and 4.
Example:
Signal designation A 1.20,05 means: line 1, CS31 bus address 20, output 05.
When the program is created, the central unit must be informed how the lines are configured. With the programming system (e.g. 07 PC 332), enter here the appropriate module identifiers in the configuration table. The table below gives a summary.
Extension to the CP Module identifier
07CS61
O16 CPV Direct
(without extension)
CPV Direct +
CP input module
CPV Direct +
CP valve terminal or
CP output module
CPV Direct +
CP input module +
CP valve terminal or
CP output module l: Line number n: Set station number
IO16
O16
O16
IO16
IO16
Fig. 6/5: Summary of module identifiers
Signal designation
Outputs
O l.n,00 ... O l.n,15
O l.n,16 ... O l.n,3
O l.n,00 ... O l.n,15
O l.n+1,00 ... O l.n+1,15
O l.n,16 ... O l.n,31
O l.n+1,00 ... O l.n+1,15
Inputs
I l.n,00 ... I l.n,15
I l.n,00 ... I l.n,15
Festo P.BE-CP-DI01-EN en 0007a
6-9
6. Commissioning the ABB CS31
1
CPV Direct
2
CPV valve terminal with
8 valve plates
3
CP input module with 16 inputs
Example: Addressing with a T200 central unit with coupler
07CS61 (line 1):
Station number 12 is set in the CPV Direct. The CPV valve terminal has been extended with a CPV valve terminal and a
CP input module and occupies two CS31 bus addresses (station numbers).
1 2 3
O1.12,16 ... O1.12,31 O1.13,00 ... O1.13,15 I1.12,00 ... I1.12,15
Fig. 6/6: Example - Addressing with a T200 central unit
6-10
Festo P.BE-CP-DI01-EN en 0007a
Diagnosis with the ABB CS31
Chapter 7
Festo P.BE-CP-DI01-EN en 0007a
7-1
7. Diagnosis with the ABB CS31
Contents
7.
Diagnosis with the ABB CS31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1
7.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
7.2
Diagnosis with the field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3
7.4
Setting the diagnostic mode
Error treatment
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.1
Reaction of the CPV valve terminal to faults . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.2
Short circuit/overload at output module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4.3
Short circuit in the sensor supply on an input module . . . . . . . . . . . . . . . . .
7-3
7-3
7-4
7-6
7-7
7-11
7-12
7-12
7-13
7-14
7-2
Festo P.BE-CP-DI01-EN en 0007a
7. Diagnosis with the ABB CS31
7.1
Diagnosis with LEDs
The LEDs on the cover of the CPV valve terminal indicate the operating status of the CPV valve terminal.
1
Red LED: bus status/error
(BUS)
2
Green LED: operating voltage display (POWER)
3
Yellow LED row for pilot solenoid
12
4
Yellow LED row for pilot solenoid
14
1
2
Fig. 7/1: LEDs on the CPV Direct
BUS
POWER
3 4
5 4 3 2 1
9 8 7 6
7.1.1 Normal operating status
In normal operating status the green power LED lights up.
lights up; flashes; out
LED
BUS
Colour out
Operating status normal
Error treatment none
POWER green lights up normal none
Fig. 7/2: Normal operating status
Festo P.BE-CP-DI01-EN en 0007a
7-3
7. Diagnosis with the ABB CS31
7.1.2 Error displays of the BUS/POWER LEDs
LED Colour
POWER out
Error diagnosis with the green LED (POWER):
Operating status
Operating voltage for the electronics is not switched on
Error treatment
S Check the operating voltage connection (pin 1)
Load voltage for CP valves
<
20.4 V
S
Check the load voltage supply
(pin 2)
POWER green flashes fast
BUS red lights up
POWER green flashes slowly
Load voltage for CP valves < 10 V S Check the load voltage supply
(pin 2)
BUS red lights up
Fig. 7/3: Error diagnosis with the green POWER-LED
Load voltage faults are always shown with the green and red
LEDs (irrespective of the diagnostic mode set).
If the device-related diagnosis is activated, the faults will also be communicated to the master PLC via the field bus direct connection.
7-4
Festo P.BE-CP-DI01-EN en 0007a
7. Diagnosis with the ABB CS31
LED
BUS
Colour red flashes fast
Error diagnosis with the red LED (BUS):
Operating status
– Station number set ( > 60) incorrectly
Error treatment
S Correct station number (0,...,60)
BUS
BUS red flashes slowly
(1 second intervals) red lights up
– Address setting is not correct, e.g. assigned twice
– CPV valve terminal not yet initialized
S
S
Correct station number
Start bus
– Load voltage failure on the CPV
Direct 1)
– Load voltage failure on the
CP valve terminal in the extension 1)
– Load voltage failure on the CP output module 1)
S
S
Check power supply
Check power supply
S
Check power supply
– Undervoltage on valves of the
CPV Direct 1)
– Undervoltage on CP valves
< 20.4 V (in the extension) interrupted
– CP input module
– CP output module
– CP valve terminal
1)
– Short circuit/overload on CP output module
– Short circuit in sensor supply to CP input module
– Connection to a CP module
S
Check power supply
S Check power supply
S
Eliminate short circuit/overload
S Eliminate short circuit/overload
S Restore connection
1) These error displays can be switched off by means of the diagnostic mode setting.
They will then no longer be sent to the CS31 master (see chapter 1.2.2).
Fig. 7/4: Error diagnosis with the red BUS LED
Festo P.BE-CP-DI01-EN en 0007a
7-5
7. Diagnosis with the ABB CS31
7.1.3 LEDs for the status display of the valve solenoid coils
There is a yellow LED for each valve solenoid coil (see
Fig. 7/1). This LED indicates the switching status of the valve solenoid coil.
LED Colour out yellow lights up
Switch position valve solenoid coil
Basic position
– switch position or
– basic position
Error treatment logical 0 (no signal) logical 1 (signal present) logical 1 but:
– load voltage of the valves lies below the permitted tolerance range ( < 20.4V DC) or
– compressed air supply not correct.
or
– pilot exhaust blocked or
– servicing required
Fig. 7/5: LEDs for the status display of the valve solenoid coils
Please note
If there is no valve coil, the assigned LED will not indicate control of the output.
7-6
Festo P.BE-CP-DI01-EN en 0007a
7. Diagnosis with the ABB CS31
7.2
Diagnosis with the field bus
The valve terminal reacts on the ABB CS31 system bus like a binary input/output module. All central units and couplers perform the general monitoring of the CS31 system bus, e.g.
total failure of the local modules.
The central units and couplers interrogate the diagnostic messages provided by the CPV valve terminal.
The relevant ABB manuals apply to all the central units and couplers.
The following diagrams show as an example the diagnostic possibility in conjunction with
– central unit 07KR91
– T200 with coupler 07CS61.
Please note
With the ABB CS31 protocol, several CP diagnostic messages are grouped together as common messages.
Festo P.BE-CP-DI01-EN en 0007a
7-7
7. Diagnosis with the ABB CS31
Example 1: Central unit 07KR91
The entries of the CPV valve terminal in the error flag words have the following meanings:
FK3 = simple fault FK4 = warning
Flag 255,10
1
2
3
Flag 255,13
Flag word 255,00
Flag word 255,01
Flag word 255,02
Flag word 255,03
Flag word 255,04
Flag word 255,05
Flag word 255,06
Flag 255,14
Flag word 255,08
Flag word 255,09
Flag word 255,10
Flag word 255,11
Flag word 255,12
Flag word 255,13
Flag word 255,14
Flag word 255,07 Flag word 255,15
Error recognition/meaning with Festo CP systems
1 15
D
= CPV valve terminal not connected
2 Device type:
2
D
= Binary outputs (CPV Direct without extension or extended with one CP valve terminal/
CP output module)
4
D
= Binary inputs/outputs (CPV Direct extended with one input module)
3 Group no. (= set station number, decimal)
4
1
D
= Internal module error /in the CP system)
– undervoltage in valves 20.4 V
– load voltage failure (CP output module, CP valve terminal)
– short circuit in sensor supply
2
D
= Wire fracture, connection to following interrupted:
– CP output module / CP input module / CP valve terminal
4
D
= Overload/short circuit at an electric output
5
Channel no.: Always 0 in conjunction with CPV valve terminals.
4
2
3
5
Fig. 7/6: Example 07KR91 – Meaning of the ABB error flags on Festo CP systems
7-8
Festo P.BE-CP-DI01-EN en 0007a
7. Diagnosis with the ABB CS31
Example 2: Coupler 07CS61
The diagnostic information of the CPV valve terminal is entered in the following error flags:
– Line 1: Flag word 4104,04
– Line 2: Flag word 4105,12
– Line 3: Flag word 4107,04
– Line 4: Flag word 4108,12
They have the following meanings:
Festo P.BE-CP-DI01-EN en 0007a
7-9
7. Diagnosis with the ABB CS31
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Error code
0000 No fault
1111 Module (CPV valve terminal) disconnected from the bus
0100 Overload (at least one electric output of the CP output module short-circuited/ overloaded
0010 Wire fracture (connection to
CP output module/CP valve terminal or CP input module interrupted)
0001 Internal error in the CP system
– Undervoltage in valves of the CPV Direct < 20.4 V
– Load voltage failure in CP valve terminal in the extension
– Load voltage failure in the
CP output module < 10 V
– Sensor supply for CP input module short-circuited
Channel no. always 0
1 = input/output module
Always 1 in conjunction with CPV valve terminals
Set station address
0 = binary module
Fig. 7/7: Example 07CS61 – Meaning of the ABB error flags with Festo CP systems
(see also Fig. 7/6)
7-10
Festo P.BE-CP-DI01-EN en 0007a
7. Diagnosis with the ABB CS31
7.3
Setting the diagnostic mode
The following error messages can be switched off with switch element 8 of the 8-element DIL switch in the switch module
(see chapter 1.2.2):
– Load voltage failure
– of the CPV Direct
– of the CP valve terminal in the extension
– of the CP output module in the extension
The following table shows the reaction of the diagnostic LEDs or of the error flags with active/inactive load voltage monitoring:
Monitoring active Monitoring inactive
BUS LED lights up flashes 1) out flashes 1) POWER LED
Error flag set reset
1) Only with load voltage error on the CPV Direct
Fig. 7/8: Diagnostic mode setting – reaction of LEDs and error flags
Festo P.BE-CP-DI01-EN en 0007a
7-11
7. Diagnosis with the ABB CS31
7.4
Error treatment
7.4.1 Reaction of the CPV valve terminal to faults
Reaction to faults in the control system
The CP valves and any existing electric outputs are switched off in the event of a fault after 250 ms.
Please note
If the outputs are reset after PLC stop, field bus interruption or fault, please observe the following:
– single-solenoid valves move to the basic position
– double-solenoid valves remain in the current position
– mid-position valves move to the mid-position (depending on valve type: pressurized, exhausted or blocked).
7-12
Festo P.BE-CP-DI01-EN en 0007a
7. Diagnosis with the ABB CS31
7.4.2 Short circuit/overload at output module
If there is a short circuit or overload:
– all the digital outputs of the module will be switched off
– the green LED “Diag” on the output module will flash fast
– the appropriate diagnostic bit will be set.
Please note
The outputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error
You can delete the error by resetting all eight outputs. You can do this in one of the following ways:
Possibilities
S
Reset all the outputs of the output module to logical “0” (RESET) or
S
Briefly interrupt the CP connection on the CP output module or
S Briefly interrupt the power supply to the CPV
Direct
Explanation
– Manually or automatically in the program
– Outputs on the output module will be reset automatically
– All the outputs of the CP system will be reset automatically
The outputs can then be reset to “logical 1”.
If the short circuit still exists, the outputs will be switched off again.
Festo P.BE-CP-DI01-EN en 0007a
7-13
7. Diagnosis with the ABB CS31
7.4.3 Short circuit in the sensor supply on an input module
If there is a short circuit, overload or voltage fault in the sensor supply:
– the sensor supply for all inputs of the module will be switched off
– the green LED “Diag” on the input module will flash fast
– the error bit in the diagnostic byte will be set to “logical 1”.
Please note
The inputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error/short circuit/overload
You can delete the error in one of the following ways:
S Briefly interrupt the CP connection on the CP input module or
S Briefly interrupt the power supply to the CPV Direct
The inputs can then be interrogated again.
If the short circuit/overload still exists, the error will be shown again.
7-14
Festo P.BE-CP-DI01-EN en 0007a
Commissioning the Moeller SUCOnet K
Chapter 8
Festo P.BE-CP-DI01-EN en 0007a
8-1
8. Commissioning the Moeller SUCOnet K
Contents
8.
Commissioning the Moeller SUCOnet K . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1
Preparing the CPV valve terminal for commissioning . . . . . . . . . . . . . . . . . .
8.1.1
Switching on the operating voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.1.2
Address assignment of the CPV valve terminal . . . . . . . . . . . . . . . . . . . . . . .
8.2
8.3
8.4
CP system extension and number of inputs/outputs
Configuration für SUCOnet K
Addressing inputs/outputs
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-1
8-3
8-3
8-4
8-6
8-8
8-9
8-2
Festo P.BE-CP-DI01-EN en 0007a
8. Commissioning the Moeller SUCOnet K
8.1
Preparing the CPV valve terminal for commissioning
8.1.1 Switching on the operating voltages
Common supply
Separate supply
Please note
Please observe also the switching-on instructions in the manual for your PLC controller.
When the controller is switched on, it automatically carries out a comparison between the NOMINAL and ACTUAL configurations. For this configuration run it is important that:
– the specifications for the field bus configuration are complete and correct.
– the power supplies for the PLC and the field bus slaves are switched on either simultaneously or in the sequence specified below.
Please note the following when switching on the power supply:
If there is a common power supply for the control system and all the field bus slaves, the power should be switched on via a central power unit or switch.
If the control system and the field bus slaves have separate power supplies, the power should be switched on in the following sequence:
1. the power supply for all the field bus slaves
2. the power supply for the controller.
Festo P.BE-CP-DI01-EN en 0007a
8-3
8. Commissioning the Moeller SUCOnet K
8.1.2 Address assignment of the CPV valve terminal
The CPV valve terminal with field bus direct connection always occupies 16 output addresses, irrespective of the number of valve coils fitted on it. This enables the CPV valve terminal to be extended at a later stage without the need to shift the addresses.
The diagram below shows the addressing sequence of the individual CPV valve plates.
8-4
0-1
2-3
4-5
6-7
8-9 12-13
10-11 14-15
Fig. 8/1: Address assignment of a CPV valve terminal
– A valve location on the CPV valve terminal always occupies 2 addresses, even if it is fitted with a reserve plate or pressure isolation plate. If a valve location is fitted with a double-solenoid valve, the following allocation applies:
– pilot solenoid 14 occupies the lower-value address,
– pilot solenoid 12 occupies the higher-value address.
The higher-value address remains unused with singlesolenoid valves.
Festo P.BE-CP-DI01-EN en 0007a
8. Commissioning the Moeller SUCOnet K
Addresses are assigned on the CPV valve terminal from left to right and on the individual valve locations from the front to the rear.
5 4 3 2 1
9 8 7 6
BUS
POWER
1 3 5 7 1 3 5 7
0 2 4 6 0 2 4 6
Fig. 8/2: Address assignment of the CPV valve terminal (outputs), example: station number 2, unit 1
Festo P.BE-CP-DI01-EN en 0007a
8-5
8. Commissioning the Moeller SUCOnet K
8.2
CP system extension and number of inputs/outputs
Please note
The CP system constantly occupies 32 inputs and 32 outputs within the PLC, irrespective of the system extension and the type of module (inputs, outputs, valves) and irrespective of the setting of the DIL switches for the extension to the CP system.
With the SUCOnet K protocol, the setting of the CP system extension refers only to the checking of the connected extension modules. The position of the DIL switches for the extension to the CP system is relevant here (see chapter 1.2.2 and
1.8). The CP system itself always occupies 32 I/Os.
Please note
Make sure that the DIL switches in the switch module are set corresponding to the extension of your CP system.
8-6
Festo P.BE-CP-DI01-EN en 0007a
8. Commissioning the Moeller SUCOnet K
The following shows the different variants.
Extension to the CP system Number of outputs
16O inputs
— CPV Direct
(without extension)
CPV Direct +
CP input module
CPV Direct +
CP valve terminal or
CP output module
CPV Direct +
CP input module +
CP valve terminal or
CP output module
16O
16O
16O
16O
16I
—
16I
16O
Fig. 8/3: Number of inputs/outputs for extension possibilities of the CPV Direct
Festo P.BE-CP-DI01-EN en 0007a
8-7
8. Commissioning the Moeller SUCOnet K
8.3
Configuration für SUCOnet K
The following type of module is required for the CPV Direct and any extensions
– SIS-K-06/07
(SUCOnet K slave with max. 32 inputs and 32 outputs).
The topology configurator from Moeller is available for configuring bus slaves. The diagram below shows the configuration entry for a CP system with SUCOnet K direct connection in conjunction with a PS4-201 as master.
8-8
Fig. 8/4: Example - Configuration PS4
Festo P.BE-CP-DI01-EN en 0007a
8. Commissioning the Moeller SUCOnet K
8.4
Addressing inputs/outputs
Please note the following when addressing the inputs/outputs of a CP system with CPV Direct on the SUCOnet K.
The slave number or the number of the unit differs from the set station number by -1.
Example:
Set station number of the
CP system
4
...
2
3
Number of the unit or slave number
3
...
1
2
Fig. 8/5: Difference between station number and slave number (-1)
Festo P.BE-CP-DI01-EN en 0007a
8-9
8. Commissioning the Moeller SUCOnet K
Addressing the inputs and outputs with master PS 4
Example of configuration CPV Direct
– connected to the PS4 string 1
– set station number: 2 (= unit 1)
– extension with a CP valve terminal or one CP output module
1
CPV Direct
2
CPV valve terminal with
8 valve plates
3
CP input module with 16 inputs
1 2 3
%SD 1.1.0.0.0
.
.
%SD 1.1.0.1.7
%SD 1.1.0.2.0
.
.
%SD 1.1.0.3.7
%RD 1.1.0.0.0
.
.
%RD 1.1.0.1.7
Fig. 8/6: Example – Addressing with a PS4 master
8-10
Festo P.BE-CP-DI01-EN en 0007a
Diagnosis with the Moeller SUCOnet K
Chapter 9
Festo P.BE-CP-DI01-EN en 0007a
9-1
9. Diagnosis with the Moeller SUCOnet K
Contents
9.
Diagnosis with the Moeller SUCOnet K . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-1
9.1
Diagnosis with LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.1
Normal operating status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.2
Error displays of the BUS/POWER LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1.3
LEDs for the status display of the valve solenoid coils . . . . . . . . . . . . . . . . . .
9.2
Diagnosis with the field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3.1
Reaction of the CPV valve terminal to faults . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3.2
Short circuit/overload at output module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3.3
Short circuit in the sensor supply on an input module . . . . . . . . . . . . . . . . .
9-3
9-3
9-4
9-6
9-7
9-9
9-9
9-10
9-11
9-2
Festo P.BE-CP-DI01-EN en 0007a
9. Diagnosis with the Moeller SUCOnet K
9.1
Diagnosis with LEDs
The LEDs on the cover of the CPV valve terminal indicate the operating status of the CPV valve terminal.
1
Red LED: bus status/error
(BUS)
2
Green LED: operating voltage display (POWER)
3
Yellow LED row for pilot solenoid
12
4
Yellow LED row for pilot solenoid
14
1
2
Fig. 9/1: LEDs on the CPV Direct
BUS
POWER
3 4
5 4 3 2 1
9 8 7 6
9.1.1 Normal operating status
In normal operating status the green power LED lights up.
lights up; flashes; out
LED
BUS
Colour out
Operating status normal
Error treatment none
POWER green lights up normal none
Fig. 9/2: Normal operating status
Festo P.BE-CP-DI01-EN en 0007a
9-3
9. Diagnosis with the Moeller SUCOnet K
9.1.2 Error displays of the BUS/POWER LEDs
LED Colour
POWER out
Error diagnosis with the green LED (POWER):
Operating status
Operating voltage for the electronics is not switched on
Error treatment
S Check the operating voltage connection (pin 1)
Load voltage for CP valves
<
20.4 V
S
Check the load voltage supply
(pin 2)
POWER green flashes fast
POWER green flashes slowly
Load voltage for CP valves < 10 V S Check the load voltage supply
(pin 2)
Fig. 9/3: Error diagnosis with the green POWER-LED
Load voltage errors are always shown with the green LED.
9-4
Festo P.BE-CP-DI01-EN en 0007a
9. Diagnosis with the Moeller SUCOnet K
LED
BUS
Colour red lights up
Error diagnosis with the red LED (BUS):
Operating status
Hardware fault
Error treatment
S Servicing required
BUS red flashes fast
Station number set incorrectly
S
Correct station number
(0,...,98)
BUS red flashes slowly
(1 second intervals)
BUS flashes red out briefly
Field bus connection not correct.
Possible causes:
– station number not correct (e.g.
address assigned twice)
– switched-off or defective field bus module
– interrupted, short-circuited or faulty field bus connection
– configuration incorrect, master configuration setting in switch module
Check the ...
S
S
S address setting field bus module field bus connection
S configuration of the master and the setting in the switch module
Switch module missing
Switch module defective
S
Insert switch module
S
Replace switch module
Fig. 9/4: Error diagnosis with the red BUS LED
Festo P.BE-CP-DI01-EN en 0007a
9-5
9. Diagnosis with the Moeller SUCOnet K
9.1.3 LEDs for the status display of the valve solenoid coils
There is a yellow LED for each valve solenoid coil (see
Fig. 9/1). This LED indicates the switching status of the valve solenoid coil.
LED Colour out yellow lights up
Switch position of valve solenoid coil
Basic position
– switch position or
– basic position
Error treatment logical 0 (no signal) logical 1 (signal present) logical 1 but:
– load voltage of the valves lies below the permitted tolerance range ( < 20.4 V DC) or
– compressed air supply not correct or
– pilot exhaust blocked or
– servicing required
Fig. 9/5: LEDs for the status display of the valve solenoid coils
Please note
If there is no valve coil, the assigned LED will not indicate control of the output.
9-6
Festo P.BE-CP-DI01-EN en 0007a
9. Diagnosis with the Moeller SUCOnet K
9.2
Diagnosis with the field bus
The following errors are recognized by the CP system:
Diagnostic bit
V val
Meaning
V tol
V sen
V out
Short circuit/ overload
ACP
Load voltage failure of CP valves
<
10.4 V
– CPV Direct
– CP valve terminal in the extension
Undervoltage of CP valves
<
20.4 V
– CPV Direct
– CP valve terminal in the extension
Short circuit in sensor supply to CP input module
Load voltage failure on CP output module
Short circuit/overload on CP output module
Connection to a CP module in the extension interrupted
– CP input module
– CP output module
– CP valve terminal
Fig. 9/6: Summary of diagnostic bits
The master receives the diagnostic byte from the SUCOnet K via the 5th. input byte.
Festo P.BE-CP-DI01-EN en 0007a
9-7
9. Diagnosis with the Moeller SUCOnet K
The diagram below shows the structure of the diagnostic byte of the CP system.
Bit no.
7 6 5 4 3 2
Diagnostic information
— V val
V tol
V sen
V out
Signal status 0 0/1 0/1 0/1 0/1
Meaning Signal status “0”: no error
Signal status “1”: error
*) As from software version 1.1 always 0, up to software version 1.1 always 1
Short circuit/ overload
0/1
Fig. 9/7: Structure of diagnostic byte SUCOnet K
Example:
Load diagnostic byte
Master: PS4
Station number: 2 (= unit 1)
Program extract:
1
ACP
0
—
0/1 0*
%RDB1.1.0.4
Fig. 9/8: Program example with SUCOnet K
Please refer to the PLC manual for your controller for further information.
9-8
Festo P.BE-CP-DI01-EN en 0007a
9. Diagnosis with the Moeller SUCOnet K
9.3
Error treatment
9.3.1 Reaction of the CPV valve terminal to faults
Reaction to faults in the control system
The CP valves and any existing electric outputs are switched off in the event of a fault after 250 ms.
Please note
If the outputs are reset after PLC stop, field bus interruption or fault, please observe the following:
– single-solenoid valves move to the basic position
– double-solenoid valves remain in the current position
– mid-position valves move to the mid-position (depending on valve type: pressurized, exhausted or blocked).
Festo P.BE-CP-DI01-EN en 0007a
9-9
9. Diagnosis with the Moeller SUCOnet K
9.3.2 Short circuit/overload at output module
If there is a short circuit or overload:
– all the digital outputs of the module will be switched off
– the green LED “Diag” on the output module will flash fast
– the short circuit/overload bit of the diagnostic byte will be set to “logical 1”.
Please note
The outputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error
You can delete the error by resetting all eight outputs. You can do this in one of the following ways:
Possibilities
S
Reset all the outputs of the output module to logical “0” (RESET) or
S
Briefly interrupt the CP connection on the CP output module or
S
Briefly interrupt the power supply to the CPV
Direct
Explanation
– Manually or automatically in the program
– Outputs on the output module will be reset automatically
– All the outputs of the CP system will be reset automatically
The outputs can then be reset to “logical 1”.
If the short circuit still exists, the outputs will be switched off again.
9-10
Festo P.BE-CP-DI01-EN en 0007a
9. Diagnosis with the Moeller SUCOnet K
9.3.3 Short circuit in the sensor supply on an input module
If there is a short circuit, overload or voltage fault in the sensor supply:
– the sensor supply for all inputs of the module will be switched off
– the green LED “Diag” on the input module will flash fast
– the error bit in the diagnostic byte will be set to “logical 1”.
Please note
The inputs cannot be used again until the short circuit or the overload is eliminated and the error is deleted.
Deleting the error/short circuit/overload
You can delete the error in one of the following ways:
S Briefly interrupt the CP connection on the CP input module or
S Briefly interrupt the power supply to the CPV Direct
The inputs can then be interrogated again.
If the short circuit/overload still exists, the error will be shown again.
Festo P.BE-CP-DI01-EN en 0007a
9-11
9. Diagnosis with the Moeller SUCOnet K
9-12
Festo P.BE-CP-DI01-EN en 0007a
Technical data and accessories
Appendix A
Festo P.BE-CP-DI01-EN en 0007a
A-1
A. Technical data and accessories
Contents
A.
A.1
A.2
Technical data and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
A-3
A-5
A-2
Festo P.BE-CP-DI01-EN en 0007a
A. Technical data and accessories
A.1
Technical specifications
General
Temperature range:
– Operation
– Storage/transport
Relative humidity
Protection class as per EN 60529 plug connector inserted or fitted with protective cap
Protection against electric shock
Protection against electric shock (protection against direct and indirect contact as per
EN 60204-1/IEC 204)
Protection against explosion
(as per EU guideline 94/9/EG, EN 50021 and
EN 50281-1-1) Do not disconnect when under tension.
Valves
- 5 °C ... + 50 °C
- 20 °C ... + 70 °C
95 % non condensing
IP65
By PELV power unit
(Protected Extra-Low Voltage)
II 3 G/D EEx nA II T5 -5 °C ≤ Ta ≤ +50 °C
T 80 °C (year of manufacture see Ex-marking on the product)
See Pneumatics manual P.BE-CPV-...
Operating voltage for bus interface and logic
Pin 1
Power supply connection fused internally
– Rated value
– Tolerance 24 V DC (protected against incorrect polarity)
20.4...26.4 V
Current consumption
– Rated value
Residual ripple
Eletrical isolation max. 100 mA
4 Vpp (within tolerance)
Bus interface optically isolated
Festo P.BE-CP-DI01-EN en 0007a
A-3
A. Technical data and accessories
Load voltage for solenoid coils of CP valve terminal
Pin 2
Power supply connection
– Rated value
– Tolerance
Current consumption
– Rated value
– Tolerance
Residual ripple
24 V DC (protected against incorrect polarity)
20.4...26.4 V
Sum of all switched on CP solenoid valves; see manual “CP pneumatics”
4 Vpp (within tolerance)
Electromagnetic compatibility
– Interference emission
– Immunity to interference
Tested as per EN 55011 limit value class A *)
Tested as per EN 50082-2
*) The CP valve terminal can also be used with special authorization in residential areas
(living, business and commercial areas, small firms).
Technical specifications for the pneumatic components can be found in the “Pneumatics manual, P.BE-CPV-...”.
A-4
Festo P.BE-CP-DI01-EN en 0007a
A. Technical data and accessories
A.2
Accessories
This chapter provides a summary of necessary and useful acesssories.
CP valve supply
The power supply for the CP valves is provided via a 4 pin
M12 socket with PG 7 or 9 screw connector. You can order these from Festo.
Plug
PG7 straight
PG9 straight
PG7 angled
PG9 angled
Type
FB-SD-GD7
FB-SD-GD9
FB-SD-WD7
FB-SD-WD9
Part no.
18 497
18 495
18 524
18 525
Bus connection
Bus connection is provided by a 9-pin sub-D plug. You can order these from Festo.
Type FBS-SUB-9-GS-9 (part no. 18529)
If you wish to use 9-pin sub-D plugs from other manufacturers, you must replace the two flat screws on the plug with threaded bushings (part no. 340 960).
Festo P.BE-CP-DI01-EN en 0007a
A-5
A. Technical data and accessories
Summary of CP connecting cables
The following CP connecting cables are available for extending the CPV Direct:
Valve terminal connection
Angled plug – angled socket 0.5 m
Angled plug – angled socket 2 m
Angled plug – angled socket 5 m
Straight plug – angled socket 5 m
Straight plug – angled socket 8 m
Straight plug – straight socket 2 m, suitable as drag chain
Straight plug – straight socket 5 m, suitable as drag chain
Straight plug – straight socket 8 m, suitable as drag chain
Type
KVI-CP-1-WS-WD-0.5
KVI-CP-1-WS-WD-2
KVI-CP-1-WS-WD-5
KVI-CP-1-GS-WD-5
KVI-CP-1-GS-WD-8
KVI-CP-2-GS-GD-2
KVI-CP-5-GS-GD-5
KVI-CP-8-GS-GD-8
Part no.
178 564
163 139
161 138
163 137
163 136
170 234
170 235
165 616
Summary of CP plugs for output module
Plug
Mains power connector plug straight, PG9
Mains power connector plug straight, PG13.5
Mains power connector plug angled, PG9
Sensor plug straight, M12, PG7
Type
NTSD-GD-9
NTSD-GD-13.5
NTSD-WD-9
SEA-GS-7
Part no.
18 493
18 526
18 527
18 666
A-6
Festo P.BE-CP-DI01-EN en 0007a
A. Technical data and accessories
Summary of CP plugs for input module
Plug
Sensor plug straight, M12, PG7
Sensor plug straight, M12, 5-pin, PG7
DUO plug M12 (2 cable openings)
DUO plug M12 (2 cable openings), 5-pin
Sensor plug straight, M8, 3-pin (can be soldered)
Sensor plug straight, M8, 3-pin (can be screwed)
Type
SEA-GS-7
SEA-M12-5GS-7
SEA-GS-11-DUO
SEA-5GS-11-DUO
SEA-GS-M8
SEA-3GS-M8-S
Part no.
18 666
175 487
18 779
192 010
18 696
192 009
Festo P.BE-CP-DI01-EN en 0007a
A-7
A. Technical data and accessories
A-8
Festo P.BE-CP-DI01-EN en 0007a
Index
Appendix B
Festo P.BE-CP-DI01-EN en 0007a
B-1
B. Index
Contents
B.
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B-1
B-2
Festo P.BE-CP-DI01-EN en 0007a
B. Index
Festo P.BE-CP-DI01-EN en 0007a
A
ABB CS31
Address assignment
Addressing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4
6-5, 6-8
BUS LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4
6-7, 6-9
Bus termination
Configuration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-25
6-6
Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic mode . . . . . . . . . . . . . . . . . . . . . . . . . .
7-7
1-17, 7-11
Error treatment
LEDs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-12
7-3
Operating voltage, switching on
POWER-LED
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3
7-4
Preparing for commissioning
Short circuit/overload
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
6-3
7-13
Abbreviations
Product-specific . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
XI
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-5
B
Baud rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-18, 1-20
C
Cables
Accessories
Field bus
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-6
1-19
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-28
CD ROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-9, 2-20, 2-36
Connecting
Field bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply
1-19, 1-22
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-28
CP extension connection . . . . . . . . . . . . . . . . . . . . . . . . . .
1-37
B-3
B. Index
B-4
D
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VII
DIL switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
E
Earth connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-35
Electrical connecting and display elements . . . . . . . . . . . .
1-4
EMERGENCY STOP circuit . . . . . . . . . . . . . . . . . . . . . . . . .
1-33
Extending the CPV Direct . . . . . . . . . . . . . . . . . . . . . . . . . .
1-37
F
Festo field bus
Address assignment
Addressing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4
4-9
BUS LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus termination
5-5, 7-5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-25
Configuration
Diagnosis
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field bus configurator . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6
5-7
5-8
4-7
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating voltage, switching on
POWER-LED
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preparing for commissioning
Short circuit/overload
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
4-3
5-4
4-3
5-9
Field bus address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-10
Field bus baud rate . . . . . . . . . . . . . . . . . . . . . . . . .
1-18, 1-20
Field bus cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-19
Field bus length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-20
I
Important user instructions . . . . . . . . . . . . . . . . . . . . . . . . . .
IX
Festo P.BE-CP-DI01-EN en 0007a
B. Index
Festo P.BE-CP-DI01-EN en 0007a
M
Moeller SUCOnet K
Address assignment
Addressing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-4
8-9
Bus termination
Configuration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-25
8-8
Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Error treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-7
9-9
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Number of inputs/outputs . . . . . . . . . . . . . . . . . . . . . . . .
Operating voltage, switching on
POWER LED
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3
8-6
8-3
9-4
Preparing for commissioning
Short circuit/overload
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
8-3
9-10
N
Notes on the use of this manual . . . . . . . . . . . . . . . . . . . . .
VIII
O
Operating voltage
Switching on . . . . . . . . . . . . . . . . . . . . . . . .
2-3, 4-3, 6-3, 8-3
Operating voltage cable . . . . . . . . . . . . . . . . . . . . . . . . . .
1-28
P
Pictograms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X
Pin assignment
Field bus interface . . . . . . . . . . . . . . . . . . . . . . . .
Power supply connection
1-22, 1-23
. . . . . . . . . . . . . . . . . . . . . . . .
1-34
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-34
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-28
Power unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-30
B-5
B. Index
B-6
PROFIBUS-DP
Address assignment
Addressing
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4
2-19, 2-24
Branch line lengths
BUS LED
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-21
3-5
Bus termination
CD ROM
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-25
2-9, 2-20, 2-36
COM PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cyclic data transmisssion . . . . . . . . . . . . . . . . . . . . . . . .
2-9
COM PROFIBUS Online diagnosis
Configuration
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
3-21
2-7, 2-9, 2-12
2-32
Device data base (GSD) . . . . . . . . . . . . . . . . .
2-9, 2-20, 2-36
Device-related diagnosis 1
Device-related diagnosis 2
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
3-15
3-16
Diagnostic bytes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic information . . . . . . . . . . . . . . . . . . . . . . . . . .
3-11
3-12
Diagnostic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic possibilities . . . . . . . . . . . . . . . . . . . . . . . . . .
1-17
3-9
Diagnostic words
DP identifier
. . . . . . . . . . . . . . . . . . . . . . . . . .
3-8, 3-11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-8
Error treatment
FREEZE
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-17
2-6
General DP master . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Implemented functions . . . . . . . . . . . . . . . . . . . . . . . . .
2-28
2-34
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4, 5-4
Octets 4...7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating voltage, switching on . . . . . . . . . . . . . . . . . . .
3-14
2-3
Optical-fibre waveguide
POWER LED
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-27
3-4
Preparing for commissioning . . . . . . . . . . . . . . . . . . . . . .
Reaction times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sending a parametrizing telegram . . . . . . . . . . . . . . . .
2-3
2-35
2-29
Sending configuration data
Service access points (SAP)
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
Short circuit/overload
Station status 1
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-31
2-34
3-26
3-12
Station status 2
Station status 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-13
3-13
STEP 7 Hardware configurator
STEP 7 Online diagnosis
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
SYNC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-20
3-22
2-7
Festo P.BE-CP-DI01-EN en 0007a
B. Index
Festo P.BE-CP-DI01-EN en 0007a
S
Screening connection . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-24
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII
Setting
Diagnostic mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-17
Extension to the CP system
Field bus baud rate
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9
1-18
Field bus protocol
Station number
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8
1-10
Station numbers
Permitted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-10
1-12
Strain relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-23
SucoNet K.
Siehe Moeller SUCOnet K
Switch module
Fitting and removing
Setting
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5
1-7
T
Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIII
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-3
Text markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
X
Total current consumption . . . . . . . . . . . . . . . . . . . . . . . .
1-31
V
Valve solenoid coils
Status display . . . . . . . . . . . . . . . . . . . . . . .
3-6, 5-6, 7-6, 9-6
B-7
B. Index
B-8
Festo P.BE-CP-DI01-EN en 0007a
advertisement
Related manuals
advertisement