Evco EV3 CHIL is a controller for single-circuit chillers that offers a range of capabilities to help you manage your cooling system efficiently. With its ability to monitor and control various parameters such as temperature, pressure, and flow, this device provides comprehensive protection for your chiller system. You can set alarms to notify you of any irregularities, ensuring that potential issues are addressed promptly. Additionally, the EV3 CHIL allows for flexible configuration of analog and digital inputs and outputs, enabling you to customize it to your specific requirements.
Advertisement
Advertisement
EVCO S.p.A. | EV3 CHIL | Instruction sheet ver. 1.0 | Code 1043CHILI104 | Page 1 of 2 | PT 21/15
EV3 CHIL Controller for single-circuit chillers
I ENGLISH 1
1.1
MEASUREMENTS AND INSTALLATION
Measurements
Measurements are expressed in mm (inches).
IMPORTANT
Read this document carefully before installation and before using the device and take all the prescribed precautions. Keep this document with the device for future consultation.
Only use the device in the ways described in this document.
Do not use the device as safety device.
For more information see the installer manual.
The device must be disposed of according to local regulations governing the collection of electrical and electronic waste.
1.2 Installation
To be installed on a panel with snap-in brackets.
2.2 Description of connectors
INSTALLATION PRECAUTIONS
- The thickness of the panel on which the device is to be installed must be between 0.8 and 2.0mm (0.031 and 0.078 in).
- Ensure that the working conditions for the device
(operating temperatures, humidity, etc.) are within the set limits. See the section TECHNICAL
SPECIFICATIONS.
-
-
Do not install the device close to heat sources
(heating elements, hot air ducts, etc.), equipment with a strong magnetic field (large diffusers, etc.), in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or shocks.
In compliance with safety regulations, the device must be installed properly to ensure adequate protection from contact with electrical parts. All protective parts must be fixed in such a way as to need the aid of a tool to remove them.
2
2.1
ELECTRICAL CONNECTION
I/O configuration
ANALOGUE INPUTS
IN1 Condensation temperature/pressure (NTC/4-20 mA)
IN2 System return temperature (NTC)
IN3 System delivery temperature (NTC)
IN4 Compressor discharge temperature (NTC)
DIGITAL INPUTS
IN5 System flow switch
IN10 On/Off
IN9 Fan thermal protection
IN8 Compressor 1 thermal protection
IN7 Maximum pressure switch
IN6 Minimum pressure switch
ANALOGUE OUTPUTS
AO1 Compressor 1 (0-10 V/phase cutting/PWM)
AO2 Fan (0-10V/phase cutting/PWM)
DIGITAL OUTPUTS
DO1 Alarm
DO2 Enable fan
DO3 Circulation pump
DO4 Enable compressor 1
TK1 Compressor 2 (if installed)
TK2 Fan (if installed)
Connector 1
PART DESCRIPTION
1
2
3
4
5
Electro-mechanical relay digital outputs DO1... DO4
(max. 6A): common
Electro-mechanical relay digital output DO4 (2A
SPST): normally open
Electro-mechanical relay digital output DO3 (2A
SPST): normally open
Electro-mechanical relay digital output DO2 (2A
SPST): normally open
Electro-mechanical relay digital output DO1 (2A
SPST): normally open
Connector 2
PART DESCRIPTION
1
2
Dry contact digital input IN6
Analogue input IN1 (NTC/4-20 mA)
3
4
5
6
7
8
9
10
11
Dry contact digital input IN7
Analogue input IN2 (NTC)
Dry contact digital input IN8
Analogue input IN3 (NTC)
Dry contact digital input IN9
Analogue input IN4 (NTC)
Dry contact digital input IN10
Digital input IN5
Analogue output AO1 (0-10V/phase cutting/PWM)
12
13
14
15
Analogue input GND, digital input GND, analogue output GND and GND for powered INTRABUS port
Analogue output AO2 (0-10V/phase cutting/PWM)
INTRABUS port powered up signal
Power supply to transducer analogue inputs 4-20 mA (12 VDC, max. 40 mA)
16
17
18
Analogue input GND, digital input GND, analogue output GND and GND for powered INTRABUS port
EV3 CHIL power supply (12VAC not insulated)
EV3 CHIL power supply (12VAC not insulated)
Connector 3 (if installed)
PART DESCRIPTION
1
2
3
RS-485 MODBUS slave port: +
RS-485 MODBUS slave port: --
RS-485 MODBUS slave port: shield
Connector 4 (if installed)
PART DESCRIPTION
1
2
Triac TK1 output: GND
Triac TK1 output (200 mA): OUT
Connector 5 (if installed)
PART DESCRIPTION
1
2
Triac TK2 output: GND
Triac TK2 output (2 A): OUT
2.3 Example of electrical connection
See next page.
PRECAUTIONS FOR ELECTRICAL CONNECTION
- Do not use electric or pneumatic screwdrivers on the
- terminal blocks of the device.
If the device has been moved from a cold to a warm
- place, the humidity may cause condensation to form inside. Wait about an hour before switching on the power.
Make sure that the supply voltage, electrical
-
-
- frequency and power are within the set limits. See the section TECHNICAL SPECIFICATIONS.
Disconnect the device from the power supply before doing any type of maintenance.
The devices must be fed by power of the same phase as that feeding any module with a phasecutting command signal.
If using triac digital outputs, we recommend
-
- connecting a noise filter; do not touch the heat dissipator because it could be very hot
Connect the device to an RS-485 network using a screened twisted pair. We recommend using a
BELDEN 3106A cable.
Connect the power cables as far away as possible from those for the signal.
- For repairs and for further information on the device, contact the EVCO sales network.
3
3.1
SIGNALS AND ALARMS
Signals
LED DESCRIPTION
Function mode LED
Compressor 1 LED
Compressor 2 LED
Circulation pump LED
Fan LED
Temperature LED
Pressure LED
Alarm LED
Set-up LED
On/stand-by LED
3.2 Alarms
CODE DESCRIPTION
EA01
Condensation temperature condensation pressure probe alarm probe
EA02 System return temperature probe alarm
EA03 System delivery temperature probe alarm alarm/
EA04 Compressor discharge temperature probe alarm
AFLo Flow switch alarm
AHtr Maximum temperature alarm
AFr1 Antifreeze alarm
AHP1 Maximum pressure switch alarm
ALP1 Minimum pressure switch alarm
AtC1 Compressor 1 thermal protection alarm
AtF1 Fan thermal protection alarm
EVCO S.p.A. | EV3 CHIL | Foglio istruzioni ver. 1.0 | Codice 1043CHILI104 | Pag. 2 di 2 | PT 21/15
4 TECHNICAL SPECIFICATIONS
Operating temperature
Purpose of the control device
Function controller.
Storage temperature
Construction of the control device
Container
Built-in electronic device.
Black, self-extinguishing.
Operating humidity
Category of heat and fire resistance
D.
Measurements
Mounting methods for the control device
Degree protection of front
75.0 x 33.0 x 59.0mm (2.952 x
1.299 x 5.898in; L x H x D).
To be fitted to a panel, snap-in brackets provided.
IP65.
From -10 to 55°C (from 14 to
131°F).
From -25 to 70 °C (from -13 to 158
°F).
Relative humidity condensate from 10 to 90%.
Pollution status of the control device
2.
Operating altitude From 0 to 2,000m (from 0 to 6,591
Transport altitude From 0 to 3,048m (from 0 to
- RoHS 2011/65/EC
Environmental compliance
-
-
WEEE 2012/19/EU
REACH
1907/2006.
(EC) without
Regulation
Connections
The maximum length of the connection cables are as follows:
-
-
-
-
Micro-Fit connector (power supply, analogue inputs, digital inputs, analogue outputs and powered communications port)
Edge outputs)
Plug-in screw terminal block
(RS-485 connectors
INTRABUS
MODBUS communications port).
(digital slave
EMC compliance
-
-
EN 60730-1
IEC 60730-1.
Power supply:
12VAC (+10 -15%), 50/60 Hz
(±3 Hz), max. 7VA not insulated.
Protect the power supply with a 1 A-T 250V fuse.
Rated impulsewithstand voltage
4 KV.
Over-voltage category III.
Software class and structure
Clock
A.
On request (with secondary lithium battery).
-
- power supply: 10m (32.8 ft)
Analogue inputs: 10m (32.8 ft)
Power supply for transducer analogue inputs 4-20mA:
-
-
-
10m (32.8 ft)
Digital inputs: 10m (32.8 ft)
Battery autonomy in the absence of a power supply:
> 6 months at 25°C (77°F).
Battery charging time: 24h (the battery is charged by the power supply of the device).
Drift: ≤ 60s/month at 25°C (77°F).
4 inputs:
-
Analogue outputs 0-10V: 10m (32.8 ft)
Phase cutting analogue outputs: 10m (32.8 ft)
PWM analogue outputs: 1m (3.28 ft)
- 3 for NTC probes
-
-
Electro-mechanical relay digital outputs: 10m (32.8 ft)
Triac digital outputs: 10m (32.8 ft)
Analogue inputs
- 1 can be set up using the configuration parameter for
- INTRABUS powered ports: 10m (32.8 ft)
- RS-485 MODBUS master/slave ports: 1,000m (3,280 ft); see also the MODBUS manual, specifications and implementation guides available on
Digital inputs
NTC probes or 4-20mA
6 dry contact inputs.
2 outputs that can be set up using
www.modbus.org/specs.php.
Analogue outputs
Use cables of an adequate section for the current running the configuration parameter for 0-
10V, phase cutting or PWM.
through them.
We recommend using the CJAV37 connection kit (to be ordered separately).
2
2.3
ELECTRICAL CONNECTION
Example of electrical connection
Digital outputs
Up to 6 outputs:
- 4 with SPST electro-mechanical
- relay, 2A res. @ 250VAC
1 with triac, 200 mA res. @
250 VAC at 25 °C (77 °F)
- 1 with triac, 2A res. @
250 VAC at 25 °C (77 °F).
Type 1 or Type 2
Actions
Type 1.
Additional features of
Type 1 or Type 2 actions
Displays
C.
Communications ports
Alarm buzzer
Custom 4+4 digit display.
Up to 2 ports:
-
-
1 powered INTRABUS port
1 RS-485 MODBUS slave port
Built-in.
EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
Tel. 0437/8422 | Fax 0437/83648
email [email protected] | web www.evco.it
This document and the solutions contained therein are the intellectual property of EVCO and thus protected by the Italian Intellectual
Property Rights Code (CPI). EVCO imposes an absolute ban on the full or partial reproduction and disclosure of the content other than with the express approval of EVCO. The customer (builder, installer or end-user) assumes all responsibility for the configuration of the device. EVCO accepts no liability for any possible errors in this document and reserves the right to make any changes, at any time without prejudice to the essential functional and safety features of the equipment.
Download
Advertisement