advertisement
Installation and Operation Instructions Document 1318G
Installation and Operation
Instructions for
THE FT
SERIES
Wall-Mounted, Modulating
Gas, Condensing, Combination Boiler
Model FTCW
140,000 BTU/hr
199,000 BTU/hr
• Natural Gas (NG) - Factory Configuration
• Propane Gas (LP) - Field-Convertible
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables dans le à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE
GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dans le bâtiment où vous vous trovez.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
TABLE OF CONTENTS
SECTION 1 Product Accessories
1.1 Introduction ..........................................................
3
1.2 Included with the Unit .........................................
3
SECTION 2 Product Characteristics
2.1 Model Nomenclature (model number) .................
5
2.2 Specifications ......................................................
6
2.3 Dimensions .........................................................
8
2.4 Names of Components ......................................
10
2.5 Product Flow Paths and Characteristics ............
12
2.5.1 Central Heating flow.. .......................................
12
2.6 Product Flow Paths and Characteristics ............
13
2.6.1 Domestic Hot Water flow. . ................................
13
SECTION 3 Safety Regulations
3.1 Safety Symbols ..................................................
14
3.2 Safety Precautions and Proper Use ..................
16
4.15.5 Zoning with circulation pumps ...........................
43
4.16 Pressure Relief Valve ........................................
44
4.17 Disposal of Condensate ....................................
45
4.18 DHW Flow Restrictors ......................................
46
4.19 Electrical Wiring Connections ............................
47
4.20 DIP Switches .....................................................
48
4.21 Control Board, Electrical Diagram ....................
49
4.22 Ladder Diagram .................................................
50
4.23 Electrical Connections .......................................
51
SECTION 5 Control Display and Operation
5.1 Control Dial and Buttons ....................................
53
5.2 LCD Overview ..................................................
54
5.3 Operating Mode .................................................
55
5.4 Status Display Mode ..........................................
56
5.5 DHW Set Point Change Mode ..........................
57
5.6 CH Set Point Change Mode ..............................
58
5.7 Storage Mode ....................................................
58
5.8 Installer Parameters ..........................................
59
5.9 Outdoor Reset Adjustment ................................
61
5.10 External Set Point Temperature Control ............
61
5.11 Error Mode .........................................................
62
SECTION 4 Installation
4.1 Location and Clearances ...................................
18
4.2 Wall Mount Bracket ............................................
19
4.3 Combustion Air ..................................................
20
4.3.1 Combustion Air from Room ...............................
20
4.3.2 Ducted Combustion Air ......................................
20
4.4 Venting (Exhaust) ..............................................
22
4.5 General Location Guideline ...............................
23
4.6 Locations for Vent Pipe Terminator ....................
24
4.6.1 Direct Venting Clearances ................................
24
4.6.2 Venting Requirements in the
Commonwealth of Massachusetts .....................
25
4.7 Common Vent Test ............................................
26
4.8 Air Supply and Vent Connections ......................
27
4.8.1 Vent / Air Pipe Lengths ......................................
27
4.8.2 Indoor Combustion Air .......................................
28
4.9 Vent / Air Pipe Termination.................................
28
4.10 Gas Supply and Piping ......................................
31
4.11 Gas Supply Pressure .........................................
34
4.12 Adjusting Combustion ........................................
35
4.13 High Altitude Installations. .................................
36
4.14 Natural Gas to Propane Conversion ..................
37
4.15 Plumbing Guidelines
.......................................41
4.15.1 External Plumbing and
Water Connection Guidelines
............................
41
4.15.2 Applicable Backflow Preventer ..........................
41
4.15.3 Diaphragm type Expansion tank ........................
41
4.15.4 Zoning with zone valves ....................................
42
SECTION 6 Error Codes
6.1 Error Code Tables .............................................
63
6.2 Fault Tree Analysis ...........................................
66
SECTION 7 Trouble Shooting
7.1 Diagnostics ........................................................
68
7.2 Suggested Corrective Actions ...........................
69
SECTION 8 Maintenance
8.1 Annual startup & general maintenance .............
71
8.2 Flushing the Combination Boiler ........................
73
8.3 Draining and Cleaning ......................................
74
8.4 Freeze Protection ..............................................
74
SECTION 9 Installation Check
9.1 Quick View .........................................................
75
9.2 Final Check Lists ...............................................
76
SECTION 10 Parts List and Illustrations
10.1 FT 140 ...............................................................
79
10.2 FT 199 ...............................................................
85
The FT Series Wall Mounted, Combination Boiler
Page 3
SECTION 1 Product Accessories
1.1 Introduction
This manual provides information necessary for the installation, operation, and maintenance of the FT Series
Wall Mounted, Combination Boiler . All application and installation procedures must be read and reviewed completely before proceeding with the installation. Consult the factory, or your local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest Edition
“National Fuel Gas Code” or
2) CSA B149.1 “Natural Gas and Propane Installation Code” and with the requirement of the local utility or other authorities having jurisdiction. Such applicable requirements take precedence over the general instructions contained herein.
All electrical wiring is to be done in accordance with the local codes, or in the absence of local codes, with: 1) The
National Electrical Code ANSI/NFPA No. 70-latest Edition, or
2) CSA STD. C22.1 “Canadian Electrical Code - Part 1”. This appliance must be electrically grounded in accordance with these codes.
1.2 Included with the Unit
Item Description
Qty
Wall Mounted,
Combination Boiler
FTCW140 / 199
1
Installation Instructions and
User’s Manual
THE FT THE
FT
1
Page 4
1.2 Included with the Unit
(continued)
Items Descriptions
Condensate Hose
Wall Mount Bracket
2 types of Wall Anchors
Pressure Relief Valve
(CH LINE 3/4˝
30psi)
Model: CASH ACME F-82
3” Mesh Screens
O-Ring and Gasket Kit
4
Outdoor Sensor with screws and anchors
4.5 GPM Flow Restrictor
(dark blue)
Propane Conversion Orifice
FTCW
140
*
FTCW
199
N/A
*
A 3.2 GPM Flow Restrictor (white) has been factory installed. See Section 4.17
Auto Fill Valve and Backflow Preventer Valves are NOT included (Field Supplied).
FT1894
1
Qty
1
4
1
2
1
1
1
1
The FT Series Wall Mounted, Combination Boiler
Page 5
SECTION 2 Product Characteristics
2.1
Model Nomenclature (model number)
The Model Nomenclature is shown on your Rating Plate and consists of a series of letters and numbers
( Nomenclature
) that further identifies the characteristics of your FT.
1
M
2 3 4
F T C
SERIES
FT C Combination
5 6 7 8
W
CONFIG
W - Wall Hung
SIZE
MBTU/h
1 4 0
1 9 9
9
FUEL
N - Natural
P - Propane
10
A
11
1
ALTITUDE
A 0 -10,000 Feet
REVISION
1 First
12
X
OPTIONS
X -
Standard
13
N
PUMP
N - with Pump
MODEL NUMBER
Page 6
2.2
Specifications
Model Name
Gas Input Rate
Hot Water Capacity
Installation
Flue System
Vent Run
Gas Supply Pressure
MAX
MIN
35°F
Rise
45°F
Rise
77°F
Rise
NG
LP
FTCW
140
140,000 Btu/h
28,000 Btu/h
7.1 GPM
5.5 GPM
3.2 GPM
Indoor / Wall hung type
Sealed Combustion Direct / Single Vent / Concentric Vent
2˝(50ft) , 3˝(100ft) Schedule 40 CPVC, PP, PVC
3.5˝ WC to 10.5˝ WC
8.0˝ WC to 13˝ WC
Manifold Pressure
Gas type
Vent size
Max Fire
Min Fire
NG
2˝ or 3˝ VENT
-0.216
” WC
0.002
” WC
120V 60Hz / 4A
LP
2˝ or 3˝ VENT
-0.216
” WC
0.079
” WC
Power Supply
Main Supply
Maximum Power
Consumption
Ignition System
Burner System
Gas Valve System
Minimum Flow Rate
Dimensions
Shipping Weight
Sub Heat Exchanger Water Capacity(DHW)
160W
Direct Electronic Ignition / Automatic Flame Sensing
Single Orifice Premixed Fuel Modulation
Combination modulating (Current proportional)
0.5 GPM
W17.25˝ - H29.0˝ - D15.5˝
111 lbs (50 kg)
Under 1 Gallon
Main Controller / Control Panel
Gas Inlet
NGTX-900CP / P-920C
Domestic Hot Water Pressure, DHW
Central Heat Water Pressure, CH
Connection Sizes
Cold Water Inlet / Hot Water
Outlet
(CH) Space Heating Supply/Re
turn
Min 15 ~ Max 150 PSI
Min 15 ~ Max 30 PSI
3/4˝ NPT
1˝ NPT
3/4˝ NPT
Materials
Safety Devices
Casing
Heat Exchanger
Cold Rolled Carbon Steel
Primary Heat Exchanger : Stainless Steel
Sub Heat Exchanger : Stainless Steel
Flame Rod, Overheat Cut Off Device, Gas Valve Opera
tion Detector, Exhaust Temperature High Limit Switch,
Water Temperature High Limit Switch
The FT Series Wall Mounted, Combination Boiler
Page 7
2.2 Specifications (continued)
Model Name
Gas Input Rate
Hot Water Capacity
Installation
Flue System
Vent Run
Gas Supply Pressure
Manifold Pressure
MAX
MIN
35°F
Rise
45°F
Rise
77°F
Rise
NG
LP
Gas type
Vent size
Max Fire
FTCW
199
199,000 Btu/h
19,900 Btu/h
9.88 GPM
7.7 GPM
4.8 GPM
Indoor / Wall hung type
Sealed Combustion Direct / Single Vent / Concentric Vent
2˝(50ft) , 3˝(100ft) Schedule 40 CPVC, PP, PVC
3.5˝ WC to 10.5˝ WC
8.0˝ WC to 13˝ WC
NG LP
2˝ VENT 3˝ VENT
-0.314
”WC
-0.015
”WC
120V 60Hz / 4A
-0.173
”WC
-0.015
”WC
Power Supply
Min Fire
Main Supply
Maximum Power
Consumption
Ignition System
Burner System
Gas Valve System
Minimum Flow Rate
Dimensions
Shipping Weight
Sub Heat Exchanger Water Capacity(DHW)
160W
Direct Electronic Ignition / Automatic Flame Sensing
Single Orifice Premixed Fuel Modulation
Combination modulating (Current proportional)
0.5 GPM
W19.6” - H32.0” - D16.3”
130 lbs (59 kg)
Under 1 Gallon
Main Controller / Control Panel
Domestic Hot Water Pressure, DHW
NGTX-900CP / P-920C
Min 15 ~ Max 150 PSI
Min 15 ~ Max 30 PSI
Central Heat Water Pressure, CH
Connection Sizes
Cold Water Inlet / Hot Water
Outlet
(CH) Space Heating Supply/Re
turn
3/4˝ NPT
1˝ NPT
Gas Inlet
3/4˝ NPT
Materials
Safety Devices
Casing
Heat Exchanger
Cold Rolled Carbon Steel
Primary Heat Exchanger : Stainless Steel
Sub Heat Exchanger : Stainless Steel
Flame Rod, Overheat Cut Off Device, Gas Valve Opera
tion Detector, Exhaust Temperature High Limit Switch,
Water Temperature High Limit Switch
Page 8
2.3
Dimensions FTCW
140
Air Intake
Vent
Description
D
E
F
G
H
A
B
C
‘DHW’ Outlet
Air Intake collar
Vent Pipe Collar
‘CH’ Supply
‘CH’ Return
‘DHW’ Inlet
Gas Inlet
Condensate Line
Diameter
3"
3"
1" NPT
1” NPT
3/4” NPT
3/4” NPT
3/4” NPT
1/2" NPT
The FT Series Wall Mounted, Combination Boiler
2.3 Dimensions
FTCW
199
Air Intake
Vent
Page 9
Description
D
E
F
G
H
A
B
C
‘DHW’ Outlet
Air Intake collar
Vent Pipe Collar
‘CH’ Supply
‘CH’ Return
‘DHW’ Inlet
Gas Inlet
Condensate Line
Diameter
3"
3"
1" NPT
1” NPT
3/4” NPT
3/4” NPT
3/4” NPT
1/2" NPT
Page 10
2.4
Names of Components
FTCW140
30
2
3
#
1
4
5
6
Name of Component
Air Vent (air eliminator)
Pressure Relief Valve
Air Intake Collar
Air Gas Mixing Pipe
Gas Valve
DHW Water Tank
7 Main PCB
8
9
Manual Power Switch (ON / OFF)
Recirculation Pump DHW / CH Primary Pump
10
'CH' Supply Connection
11
'CH' Return Connection
12 CH Pressure Gauge
13 DHW Outlet Connection
14 Gas Inlet Connection
15
DHW Inlet Connection (filter and flow restrictor)
# Name of Component
16 Condensate Connection
17 Condensate Trap
18
Air Pressure Switch (condensate)
19
Mixing Valve
20
Terminal Block
21 Control Panel and Display
22
Heat Exchanger
23 Ignition Trans
24
Flame Detecting Sensor
25 Burner Case
26
BLDC Fan (Blower)
27
Vent Pipe
28
Air Pressure Switch
29
Vent Pipe Collar
30
Sight Glass
The FT Series Wall Mounted, Combination Boiler
FTCW199
Page 11
#
1
2
3
4
5
6
Name of Component
Air Vent (air eliminator)
Pressure Relief Valve
Air Intake Collar
Gas Valve
Air Gas Mixing Pipe
DHW Water Tank
7 Main PCB
8
9
Manual Power Switch (ON / OFF)
Recirculation Pump DHW / CH Primary Pump
10
'CH' Supply Connection
11
'CH' Return Connection
12 CH Pressure Gauge
13 DHW Outlet Connection
14
Gas Inlet Adapter
15 DHW Inlet Connection (filter and flow restrictor)
# Name of Component
16 Condensate Connection
17 Condensate Trap
18
Air Pressure Switch (condensate)
19
Mixing Valve
20
Terminal Block
21 Control Panel and Display
22
Heat Exchanger
23 Ignition Trans
24
Flame Detecting Sensor
25 Burner Case
26
BLDC Fan (Blower)
27
Vent Pipe
28
Air Pressure Sensor
29
Vent Pipe Collar
30
Sight Glass
Page 12
2.5 Product Flow Paths and Characteristics
2.5.1
Central Heating flow. Combination Boiler Heating Mode.
Water in the heating pipe is used for space heating.
FTCW140
Combustion
Air
Vent
FTCW199
Combustion
Air
Combustion
Air
Vent
CH Supply
CH Return
DHW Supply DHW Return
The FT Series Wall Mounted, Combination Boiler
2.6 Product Flow Paths and Characteristics
2.6.1
Domestic Hot Water flow. Combination Boiler Domestic Hot Water Mode.
Cold water passes through the exchanger and is heated via a mini indirect tank.
The domestic hot water (DHW) is provided on demand.
FTCW140
Air
Vent
Vent
FTCW199
Combustion
Air
Page 13
Hydronic Supply
Water Inlet
Page 14
SECTION 3 Safety Regulations
3.1
Safety Symbols
WARNING
To avoid product damage, personal injury, or even possible death, carefully read, understand, and follow all the instructions in the Installation and
Operation manual before installation, operation and service the Boiler.
Manufacturer cannot anticipate every circumstance that might involve a potential hazard. Therefore, all possible incidents are not included in our warnings. Proper installation, operation, and service are your responsibility.
You must make sure that the operation and settings of the Boiler are safe for you and for others.
This manual provides Safety Symbols. When the user fails to adhere to the following requirement, it may cause death, serious injury, and substantial property damage.
For safety symbols, ‘DANGER’, ‘WARNING’,
CAUTION’ are indicated and the definitions for these terms are as follow:
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
This signal word is limited to the most extreme situations.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
WARNING
WARNING
Cancer and Reproductive Harm. www.P65WARNINGS.CA.GOV.
as required by the state of California Proposition 65.
WARNING
FOR YOUR SAFETY READ BEFORE
OPERATING
If you do not follow these instructions exactly, a fire or explosion could result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
It is also used to alert against unsafe practices and hazards involving only property damage.
This appliance must be installed in accordance with local codes if any; if not, follow ANSI Z224.1/NFPA
54 or CAN/CSA B149.1, Natural Gas and Propane
Installation Code, as applicable.
This appliance is certified for use at altitudes up to 4,500ft(1,370m) in accordance to the latest CSA/
CGA 2.17-M91 Gas-Fired Appliances for Use at
High Altitudes.
The FT Series Wall Mounted, Combination Boiler
Page 15
DANGER
Vapors from flammable liquids will explode and catch on fire. These will cause death or severe burns.
Do not use or store flammable products such as gasoline, solvents or adhesives in the same room or area near the appliance.
Keep flammable products
Far away from boiler
In approved containers
Tightly closed
Out of children’s reach
Vapors
Cannot be seen
are heavier than air
spread on the floor
Can spread from other rooms to the main burner by air currents
Do not install the appliance where flammable products will be stored.
Read and follow boiler warnings and instructions thoroughly. If owner’s manual is missing, contact the retailer or manufacturer.
This combination boiler must be installed by a qualified plumber, a licensed gas fitter, and/or a professional service technician.
Improper installation and/or operation will cause a potentially hazardous situation, such as serious injury or death. Also, it will void the warranty.
• The National Fuel Gas Code NFPA 54 / ANSI Z224.1
• National Electric Code ANSI/NEPA 70
• All applicable local, state, national and provincial codes, regulations and laws.
Proper care is your responsibility. Carefully read and understand the Operating Information in this manual before operating the Boiler.
Be aware of the location of the gas shut-off valve and operation method. Close the gas shut-off valve immediately if the appliance is subjected to fire, overheating, flood, physical damage, or any other damaging condition that might affect the operation of the unit. Boiler must be checked by a qualified technician before resuming operation.
DO NOT use this Boiler if any part has been under water. Immediately call a qualified technician for inspecting the Boiler and replacing any part of the control system and gas control which have been under water.
Do not power up the unit until the gas and water supply valves are fully opened. Make sure that the fresh air intake port and exhaust gas port are opened and functional.
DO NOT attempt to install, repair, or service this
Boiler by yourself.
Do not change any part of the Boiler.
Contact a qualified technician if the Boiler needs repair or maintenance.
Ask your gas supplier for a list of qualified service
providers.
DO NOT use spray paint, hair spray, or any other flammable spray near Boiler or near the exterior fresh air inlet port. DO NOT place any items in or around the exterior exhaust gas outlet port and/or fresh air inlet port. These could restrict or block the flow in or out of the vent system.
“Caution: While repairing control, all wires are labeled. You must connect the wires in accordance with the instruction.
Wiring errors can cause improper and dangerous
operation.
“Verify proper operation after servicing operation”
This consists of the gas ignition system components which are protected from water (dripping, spraying, rain, etc.) during operation and service (circulator replacement, condensate trap, control replacement, etc.).
After installing the heater, safety devices must be tested.
This boiler is equipped with a blocked vent shutoff system.
If the error code ‘41’ occurs, follow the instructions
below.
- First, turn off the manual gas valve.
- Make sure that there is no foreign object in the vent passage or rodent screen.
- If you do not find any problem, do the following.
- Turn off the error state by pressing the power button of control panel.
- If the error occurs repeatedly, call your service technician or gas supplier.
Page 16
3.2
Safety Precautions and Proper Use
Before Operation
1. Check the Gas Type (NG/LP)
When using or moving the unit for the first time, check if gas type matches with the gas type of the Boiler.
Check whether the gas type which is supplied is NG
(Natural Gas) or LP (Propane) and also check the
Boiler gas type.
The gas type is indicated on the rating plate on side of the Boiler.
2. Check the Power (120V 60Hz)
Check that the appliance is connected properly.
3. Check the Cold Water Inlet valve
Please keep the appliance water inlet valve open at all times.
The appliance will not ignite when insufficient water or no water is in the heating pipes.
(valve: always open position)
open
4. Check the Gas Valve
Check that the manual gas shut-off valve that supplies the FT is opened.
5. Check the area around the appliance and remove any combustible or flammable materials. Remove laundry or any other items that are on or near the boiler or vent pipe.
When in Operation CAUTION
1. Caution for Gas leak
Frequently check for a gas leak at the gas connection portion with soapy water.
Steps to take if you have a Gas leak.
1. Shut down the boiler as soon as gas fumes are detected.
2. Close the intermediate gas valve.
3. Open windows for ventilation.
4. Call a qualified service technician for immediate repair.
2. Caution for Ventilation
Make sure that there is sufficient inflow and outflow of air ventilation while using the unit.
If the ventilation is improper, combustion quality may deteriorate inside the appliance and cause shortened life of the appliance.
3. Burn Warning
Be careful not to burn yourself on the flue or pipes. They become extremely hot during operation.
The FT Series Wall Mounted, Combination Boiler
WARNING
Do not use the appliance for any other purpose than for heating and hot water.
Do not store combustibles or flammable material such as gasoline near the appliance.
Do not store other items on or near this boiler.
Do not store combustible (flammable) materials such as papers.
Do not hang clothes on the vent pipe. This may start a fire.
CAUTION
Scalding Risk: Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet (boiler location) to reduce potential for scalding.
Contact Manufacturer for recommended models.
Check with local codes.
__________________________________________
After repair of gas pipeline or gas regulator replacement, call A qualified contractor for inspection before starting it up.
Carbon monoxide poisoning
If vent pipe fumes enter the room, it could cause poisoning by carbon monoxide gas. Check that the vent pipes are properly connected. Open windows for ventilation. Call a qualified service technician for immediate repair.
Gas leakage test.
Gas supply line must be inspected regularly.
Do not shut off the Boiler.
When you leave home for a long time, do not shut off
Boiler. The Boiler has a freeze protection function. The ceramic heater is installed inside of the heater’s internal pipe to protect the heater from freezing.
Do not wipe the appliance or control panel with wet cloth. Electric shock may occur, or internal parts may fail due to the exposure to moisture.
Do not disassemble the Boiler.
If repair is required, call your local qualified technician.
Page 17
Page 18
SECTION 4 Installation
4.1 Location and Clearances
The FT must be mounted to a suitable wall by a qualified heating contractor under the guidelines of a boiler. The wall may be of concrete or wood. Suitable fasteners for concrete or wood must be used. Failure to wall mount this boiler using correct fasteners will affect the performance and life expectancy of the boiler and will void the warranty.
3
8
18
46
12
30
3
8
24
61
Minimum clearances to Combustibles.
WARNING
Installations must comply with
• All the local, state, provincial, and national codes, laws, regulations and ordinances.
• National Fuel Gas Code, ANSI Z223.1 – The latest version.
• National Electrical Code.
• A National Standard of Canada CAN/CSA-B149.1
Check before placing the Combination boiler
• Always check the connected components which are near to the heater. The components are below.
Water piping position / Venting adapter / Gas supply piping / Electrical power / Condensate drain hose.
• Inspect area around Combination boiler. Remove any combustible materials, gasoline and other flammable liquids. Failure to keep Combination boiler area clear and free of combustible materials, gasoline and other flammable liquids and vapors can result in severe personal injury, death or substantial property damage.
• The Combination boiler which has gas control system components must be protected from any possible danger during operation and service.
• If new Combination boiler replaces an existing appliance, check and correct system problems, for example:
- Do not install if: System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits.
Provide clearances
• If the heater was installed in a narrow space or corner, please ensure that there is sufficient space for service and maintenance access. For regular maintenance, gas and water lines must be accessible.
The boiler must be installed on a wall that can bear its weight.
For Installation from
Non-Combustibles and
Combustibles
TOP of appliance
BACK
FRONT
of appliance
SIDE
of appliance of appliance
18 in
(46 cm)
5 /
8
in
(1.5 cm)
24 in
(61 cm)
3 in
(7 cm)
Suggested
Service
Clearance
18 in
(46 cm)
5 /
8
in
(1.5 cm)
40 in
(101 cm)
8 in
(20 cm)
BOTTOM of appliance
12 in
(30 cm)
24 in
(61 cm)
Table 1.
Minimum Clearances to Combustibles and for Service.
WARNING
CLEARANCES FOR SERVICE ACCESS
• If you do not provide the minimum clearances shown, it might not be possible to service the boiler without removing it from the space.
• Space must be provided with combustion / ventilation air openings correctly sized for all other appliances located in the same space as the boiler. The boiler cover must be securely fastened to prevent it from drawing air from the boiler room. This is particularly important if the boiler is in a room with other appliances. Failure to comply with the above warnings could result in substantial property damage, severe personal injury, or death.
The FT Series Wall Mounted, Combination Boiler
4.2 Wall Mount Bracket
• The installation height and location for your
FT depends on your installation scenario. With all clearances considered, and given adequate positioning for air supply and venting, you will need to determine the best position to mount the Wall Mount Bracket. The wall must be concrete, wood, or plywood over studs, and must be strong enough to hold the boiler!
• Start by familiarizing yourself to how the included Wall Mount Bracket hooks underneath the two Hangers that are attached to the back of the boiler. The ‘hooks’ of the Wall Mount Bracket will be 3”
from the Top of the boiler once the boiler is hung.
Bolts (4)
Anchors
(4)
Wall Mount
Bracket
*
• Position the Wall Mount Bracket at the location that it will go, being sure that it is level, and then drill 4 holes (0.47”dia) with a 1/2” drill bit, into the wall through the Bracket.
• If mounting to a concrete wall, then use the concrete anchors.
If onto wood or 5/8” (16 mm) plywood, then use the wood screws. Do not hang the FT onto sheetrock unless it is possible to fasten directly into the structural studs. If the included anchors do not suit your installation, you must use
‘Field Supplied’ anchors that are appropriate for the wall’s construction.
Hangers (2)
(fastened to the back of unit)
Page 19
3" to Top
of Unit
Concrete,
Wood, or 5/8" Plywood
Wall Mount
Bracket
Hang the Boiler
• Lift the boiler up, align the Hangers on the back of the boiler with the hooks on the Wall Mount
Bracket, and hang the boiler onto the Wall Mount
Bracket. Do a visual inspection to make sure that the boiler is hanging properly onto the hooks of the Wall Mount Bracket.
• Fasten the bottom of the boiler to the wall using
2 suitable wall anchors (field supplied).
Page 20
4.3
Combustion Air
FT boilers must have provisions for combustion and ventilation air in accordance with the applicable requirements for Combustion Air Supply and Ventilation in the National Fuel Gas Code, ANSI Z223 1; or in
Canada, the Natural Gas and Propane Installation Code,
CSA B149.1. All applicable provisions of local building codes must also be adhered to.
A FT unit can take combustion air from the space in which it is installed, or the combustion air can be ducted directly to the unit. Ventilation air must be provided in either case.
4.3.1
Combustion Air from Room
In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow.
Where ducts are used, they shall be of the same crosssectional area as the free area of the openings to which they connect.
Method 1
:
Two permanent openings, one commencing within 12” (300mm) of the top and one commencing within 12” (300mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors, or when communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.
Method 2
:
One permanent opening, commencing within 12” (300mm) of the top of the enclosure, shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000
Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.1
4.3.2
Ducted Combustion Air
The combustion air can be taken through the wall, or through the roof. When taken from the wall, it must be taken from out-of-doors by means of the horizontal wall terminal. When taken from the roof, a field-supplied rain cap or an elbow arrangement must be used to prevent entry of rain water.
Use ABS, PVC, CPVC, polypropylene, or galvanized pipe for the combustion air intake. Route the intake to the boiler as directly as possible. Seal all joints.
Provide adequate hangers. The unit must not support the weight of the combustion air intake pipe. Maximum linear pipe length allowed is shown in
Table 5
. Subtract
5 allowable linear ft. (1.5m) for every elbow used.
The connection for the intake air pipe is at the top of the unit.
In addition to air needed for combustion, air shall also be supplied for ventilation, including air required for comfort and proper working conditions for personnel.
COMBUSTION AIR INSTALLATION STANDARDS
MATERIAL
ABS
PVC, sch 40
CPVC, sch 40
Polypropylene
Single wall galv. steel
UNITED STATES
ANSI/ASTM D1527
ANSI/ASTM D1785 or D2665
ANSI/ASTM F441
UL1738, ULC S636.
26 gauge
CANADA
Air pipe material must be chosen
CPVC, sch 40, ANSI/ASTM, Polypropylene based upon the intended application of the boiler.
Table 2. Required Combustion Air Pipe Material.
The FT Series Wall Mounted, Combination Boiler
Page 21
NOTICE
The instructions for the installation of the venting system shall specify that the horizontal portions of the venting system shall be supported to prevent sagging; the methods of and intervals for support shall be specified. These instructions shall also specify that the venting system:
Category I, II and IV boilers must be installed so that horizontal sections have a slope of at least ¼ inch per foot (21 mm/m) to prevent accumulation of condensate; and
For Category II and IV boilers, where necessary, have means provided for drainage of condensate.
CAUTION
The FT is standard as a Natural Gas Boiler and must be converted if propane is the desired gas, unless specifically manufactured for propane.
Adequate drainage
• The appliance should be installed not to damage the adjacent area. If such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not block combustion air flow.
Connecting the Water Supply
• To conserve water and energy, insulate all water piping—especially the hot and recirculation water lines. Never cover the drain or pressure relief valve.
Having a backflow preventer in the cold water supply line will prevent thermal expansion backflow. Contact the water supplier or local plumbing inspector for information about how to control this situation.
If overheating occurs or the gas supply fails to shut off, turn off the manual gas valve.
This installation must conform with below section
• “Air for Combustion and Ventilation” of the
National Fuel Gas Code, ANSI Z224.1/NFPA 54, or Sections 8.2, 8.3 or 8.4 of Natural Gas and
Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
AVIS
Les instructions d'installation du système d'évacuation doivent préciser que les sections horizontales doivent être supportées pour prévenir le fléchissement. Les méthodes et les intervalles de support doivent être spécifiés. Les instructions doivent aussi indiquer les renseignements suivants: les chaudières de catégories I, II et IV doivent présenter des tronçons horizontaux dont la pente montante est d'au moins ¼ po par pied (21 mm/m) entre la chaudière et l'évent; les chaudières de catégories II et IV doivent être installées de façon à empêcher l'accumulation de condensat; et si nécessaire, les chaudières de catégories II et IV doivent être pourvues de dispositifs d'évacuation du condensat.
Page 22
4.4
Venting (Exhaust)
NOTICE
DO NOT COMMON VENT FT UNITS. FT units are never permitted to share a vent with
Category I appliances.
WARNING
All venting must be installed according to this manual and any other applicable local codes, including but not limited to, ANSI Z224.1/NFPA 54, CAN/CSA
B149.1 and ULC-S636. Failure to follow this manual and applicable codes may lead to property damage, severe injury, or death.
AVIS
NE PAS ÉVENT COMMUNE FT UNITÉS. FT unités ne sont jamais autorisés à partager un
évent Catégorie I avec les appareils.
The flue temperature of the FT changes dramatically with changes in operating water temperature. Therefore, it is necessary to assess the application of the boiler to determine the required certified vent class. If the FT is installed in an application where the ambient temperature is elevated, and/or installed in a closet/alcove,
CPVC, polypropylene, or stainless steel material is required. If the system temperatures are unknown at the time of installation, stainless, polypropylene or CPVC material is recommended.
The FT is a Category IV appliance and may be installed with PVC, CPVC or polypropylene that complies with
ULC
-S636, ANSI/ASTM D1785 F441
(see Table 3) or a stainless steel venting system that complies with UL 1738 Standard and ULC S636.
WARNING
Failure to use the appropriate vent material, installation techniques, glues/sealants could lead to vent failure causing property damage, personal injury or death.
WARNING
Use of cellular core PVC (ASTM F891), cellular core
CPVC, or Radel® (polyphenolsulfone) in non-metallic venting systems is prohibited and covering nonmetallic vent pipe and fittings with thermal insulation is prohibited.
INSTALLATIONS IN CANADA
require the use of venting material certified to ULCS636. All Gas vents connected to the FT, plastic, stainless steel or otherwise must be certified to this ULC stand
ard. Appropriate selection of vent material is very important for proper performance and safe opera
tion of the FT.
The flue temperature of the FT changes dramati
cally with changes in operating water temperature.
Therefore, it is necessary to assess the application of the boiler to determine the required certified vent class. If the FT is installed in an application where the outlet water temperature exceeds 145°F, and/or installed in a closet, class IIB or higher vent mate
rial is required. If the system temperatures are un
known at the time of installation, class IIB or higher venting material is recommended.
IN CANADA
all venting used must meet the following requirements:
1. ULC-S636 certified and marked
2. The first 3 feet of venting must be accessible for visual inspection.
3. All components used in the vent system must be from a certified manufacturer.
MATERIAL
Stainless Steel
PVC, sch 40
CPVC, sch 40
Polypropylene
UNITED STATES
UL 1738
ANSI/ASTM D1785
ANSI/ASTM F441
Table 3. Required Exhaust Vent Material.
UL1738 or ULC-S636
CANADA
Venting must be ULC-S636 certified for use as venting material. The venting material must be chosen based upon the intended application of the boiler.
The FT Series Wall Mounted, Combination Boiler
Page 23
4 . Vent system components must not be mixed with alternate manufacturers certified components and/or unlisted components.
5 . The venting must be installed according to the vent manufacturers installation instructions.
The unit’s vent can terminate through the roof, or through an outside wall.
Vent pipe must pitch upward, toward the vent terminal, not less than 1/4” per foot, so that condensate will run back to the FT to drain. Route vent pipe to the heater as directly as possible. Seal all joints and provide adequate hangers as required in the venting system manufacturer’s Installation
Instructions. Horizontal portions of the venting system must be supported to prevent sagging and may not have any low sections that could trap condensate. The unit must not support the weight of the vent pipe.
WARNING
Failure to vent this Boiler in accordance with these instructions could cause a fire, resulting in severe property damage, personal injury or death.
Do not interchange vent systems or materials unless it is specified.
The use of thermal insulation covering pipe and fittings is prohibited.
Do not apply an electric damper, draft hood or vent damper with this Boiler.
Do not locate vent termination where exposed to prevailing winds. Moisture and ice may fall on surface around vent termination. To prevent deterioration, surface must be in good repair
(sealed, painted, etc.).
4.5 General Location Guideline
1. Vent system installation must be in accordance with Local codes or, in the absence of local codes, the National Fuel Gas Code, ANSI Z224.1 /NFPA
54 and/or CSA B149.1, Natural Gas and Propane
Installation Code.
2. The Boiler is designed to be installed as a Direct
Vent (sealed combustion) type. The air for combustion must be supplied directly from the outside to the burner. Also, the flue gases must be vented directly to the outdoors (through wall or roof).
3. Do not install venting system components on the exterior of building except as specifically required by these instructions
- Vent terminals must be at least 1 foot from any door, window, or gravity inlet into the building.
- Maintain the correct clearance and orientation between the vent and air intake terminals.
The vent and air intake terminals must be at the same height and their center lines must be spaced apart 12˝ minimum.
- The bottom of the vent and air intake terminal must be at least 12˝ above the normal snow line. In no case should they be less than 12˝ above grade level.
- Do not install the vent terminal directly over windows or doors.
- Air intake terminal must not terminate in areas that might contain combustion air contaminates, such as near swimming pools.
- For sidewall venting, the minimum horizontal distance between any adjacent individual Module
(Boiler) vent terminations is twelve (12) inches. It is better to be far more than 12 inches for avoiding frost damage to building surfaces where vent terminations are placed.
- The minimum horizontal distance between any adjacent individual module (boiler) roof vent endpiece is one (1) foot.
Page 24
4.6
Locations for Vent Pipe Terminator
4.6.1 Direct Venting Clearances
U.S. Installations (see note 1) Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch, 12 inches (30 cm) deck, or balcony See note 6
B=
Clearance to window or door that may be Direct vent only: 12 inches (30cm); opened Other than Direct vent: 4 ft (1.2m) below or to side of opening; 1 ft (30cm) above opening
C=
Clearance to permanently closed window See note 4
D=
Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center
See note 4 line of the terminal
12 inches (30 cm)
See note 6
36 inches (91 cm)
NT 80 only - 12 inches (30 cm)
See note 5
See note 5
E=
F=
G=
H=
I=
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
Clearance to each side of center line
See note 4
See note 4
See note 4 extended above meter/regulator assembly See note 4
Clearance to service regulator vent outlet See note 4
See note 5
See note 5
See note 5
3 feet (91 cm) within a height 15 feet above the meter/regulator assembly
3 feet (91 cm)
J=
Clearance to nonmechanical air supply Direct vent only: 12” (30cm) 80-285; 36” (91cm) inlet to building or the combustion air inlet 399-850. Other than Direct vent: 4 ft (1.2m) below 36 inches (91 cm) to any other appliance or to side of opening; 1 ft (30cm) above opening NT 80 only - 12 inches (30 cm)
6 feet (1.83 m)
K=
Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) horizontally
L=
Clearance above paved sidewalk or paved Vent termination not allowed in this location driveway located on public property for category IV appliances.
M=
Clearance under veranda, porch, deck, or balcony
See note 4
7 ft (2.1 m)
See note 5
12 inches (30 cm) (see note 3)
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CSA-B149.1 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the gas supplier.
5. For clearances not specified in CAN/CSA-B149, clearance is in accordance with local installation codes and the requirements of the gas supplier.
6. IMPORTANT: Terminal must be placed such that it remains a minimum 12” above expected snow line. Local codes may have more
specific requirements, and must be consulted.
Table 4.
Direct Vent Clearances
The FT Series Wall Mounted, Combination Boiler
Page 25
4.6.2
Venting Requirements in the
Commonwealth of Massachusetts
In Massachusetts the following items are required if the side-wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches. From Massachusetts Rules and regulations 248 CMR 5.08
1. Installation of Carbon Monoxide Detectors
At the time of installation of the side wall vented gas fueled appliance, the installing plumber or gasfitter shall observe that a hard-wired carbon monoxide detector with an alarm battery back-up is installed on the floor level where the gas appliance is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard-wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side-wall horizontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for installation of hard-wired carbon monoxide detectors.
a. In the event that the side-wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of the subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty
(30) days to comply with the above requirements, provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm be installed.
2. Approved Carbon Monoxide Detectors
Each carbon monoxide detector shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. Signage. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print no less than one-half (1/2) inch in size: “GAS
VENT DIRECTLY BELOW, KEEP CLEAR OF ALL
OBSTRUCTIONS”.
4. Inspection The state or local gas inspector of the side-wall horizontally vented gas fueled appliance shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1-4.
Page 26
4.7 Common Vent Test
NOTE: This section does not describe a method for common venting FT units. It describes what must be done when an existing unit is removed
from a common vent system.
NOTICE
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
1. Seal any Not Used openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so the appliance will operate continuously.
5. Operate the main burner for 5 minutes then, determine if the cut-draw overflows to the discharge opening. Use the flame of a match or a candle or the smoke of a cigarette, a cigar or a pipe
6. Once it has been determined, according to the method indicated above, that each device connected to the drainage system is placed in the open air in an adequate manner.
Install the doors and windows, fans, the registers of chimneys and gas appliances to their original position
7. Any malfunction of the venting system should be corrected so that the installation conforms to the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and (or) the installation codes CAN/
CSA-B149.1. If the size of a section of the evacuation system must be changed, the system should be modified to comply with the minimum values of the relevant tables of appendix F of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and
(or) the installation codes CAN/CSA-B149.1
AVIS
Au moment du retrait d'une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d'évacuation commun et qui fonctionne alors que d'autres appareils toujours raccordés au système d'évacuation ne fonctionnent pas:
1. Sceller toutes les ouvertures non utilisées du système d'évacuation.
2. Inspecter de façon visuelle le système d'évacuation pour déterminer la grosseur et l'inclinaison horizontale qui conviennent et s'assurer que le système est exempt d'obstruction, d'étranglement, de fuite, de corrosion et autres défaillances qui pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre l'espace où les appareils toujours raccordés au système d'évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d'évacuation commun et tous les ventilateurs d'extraction comme les hottes de cuisinière et les ventilateurs des salles de bain.
S'assurer que ces ventilateurs fonctionnent à la vitesse maximale.
Ne pas faire fonctionner les ventilateurs d'été. Fermer les registres des cheminées.
4. Mettre l'appareil inspecté en marche. Suivre les instructions d'allumage. Régler le thermostat de façon que l'appareil fonctionne de façon continue.
5. Faire fonctionner le brûleur principal pendant 5 min ensuite, déterminer si le coupe-tirage déborde à l'ouverture de décharge.
Utiliser la flamme d'une allumette ou d'une chandelle ou la fumée d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode indiquée cidessus, que chaque appareil raccordé au système d'évacuation est mis à l'air libre de façon adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
7. Tout mauvais fonctionnement du système d'évacuation commun devrait être corrigé de façon que l'installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'installation CAN/CSA-B149.1. Si la grosseur d'une section du système d'évacuation doit être modifiée, le système devrait
être modifié pour respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI
Z223.1/NFPA 54 et (ou) les codes d'installation CAN/CSA-B149.1
NOTICE
DO NOT COMMON VENT FT UNITS. FT units are never permitted to share a vent with
Category I appliances.
AVIS
NE PAS ÉVENT COMMUNE FT UNITÉS. FT unités ne sont jamais autorisés à partager un évent
Catégorie I avec les appareils.
The FT Series Wall Mounted, Combination Boiler
Page 27
4.8
Air Supply and Vent Connections
4.8.1
Vent / Air Pipe Lengths
Combination Boiler Model
3˝ Combustion Air / Vent Pipe
Max
2˝ Combustion Air / Vent Pipe
Max
FTCW140/199
100´ (30M)
50´
*
(15M
*
)
Table 5. Maximum Vent / Air Pipe Lengths for either 3” or 2 “ Pipes
* Propane models are limited to 25 equivalent feet of 2” vent
NOTE : For each elbow, reduce maximum allowable length
• 5 feet (1.5M) for each 3-inch 90-degree elbow
• 2.5 feet (0.75M) for each 3-inch 45-degree elbow
• 8 feet (2.4M) for each 2-inch 90-degree elbow
• 4 feet (1.2M) for each 2-inch 45-degree elbow
• Maximum of 6 elbows for 3” vent. Max of 4 elbows for 2” vent.
NOTE: When using a 2” vent pipe, DIP Switch 4 must be in the OFF position.
For 3” Pipe vent, the default setting for DIP 4 is ON.
Refer to Section 4.19
3” pipe
4.7.2 Direct Venting
The boiler uses 3˝ or 2˝ diameter exhaust and 3˝ or 2˝diameter intake air ducts. To ensure the draw of air directly from and exhaust of air directly to the outside of the building, create an airtight seal from the boiler collar to the vent termination.
(For installations in Canada) field-supplied plastic vent piping must comply with CAN/CSA B149.1
(latest edition) and be certified by the Standard
For Type BH Gas Venting Systems, ULC-S636.
Components of this listed system must not be interchanged with other vent systems or unlisted pipes or fittings. All plastic components and specified primers and glues of the certified vent system must be from a single system manufacturer and must not be intermixed with another system manufacturer’s parts.
Tightening — Boiler Collar (Socket) to Vent
Pipe & Inlet Pipe
- Clean and dry your selected PVC, CPVC vent pipe and boiler collar (socket).
- You can select to the size of vent pipe(2˝ & 3˝), according to the installation conditions.
- Push the pipe into the collar (socket) until it touches the bottom of the socket fitting.
- For 2” installations, install a field supplied 3” to
2” adaptor. Adaptor must be installed in vertical section of piping only.
2” pipe connected, using an adapter
3” to 2” adapter is NOT included.
Page 28
4.8.2
Indoor Combustion Air
Read and Follow Sections 4.3 Guidelines First.
1. Insert the termination end cap into the intake air duct.
2. Provide two openings to allow for circulation of combustion air as specified by ANSI Z224.1/NFPA 54.
In Canada refer to CAN/CSA B-149.1
NOTE: The FT needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
Model
Maximum Input (BTU/H)
Indoor make up air is provided, a mini
mum free area of 1 in 2 per 1,000 BTU/H
FTCW140
140,000
140 in2 13 1/4"
(W) x 13 1/4" (H)
4.9
Vent / Air Pipe Termination
Vent Air Terminations:
After connecting terminals install vent screens on both the vent and air inlet.
Two 3” vent screens are included with each unit.
Additional replacement screens are available for purchase.
2” Vent Screen P/N - FT1508
3” Vent Screen P/N - FT1730
FTCW199
199,000
199 in2 13 1/4"
(W) x 13 1/4" (H)
Vertical Vent Termination
• Direct Vent - Vertical Terminations with Sloped Roof
Vent Screens are required
The FT Series Wall Mounted, Combination Boiler
Horizontal Vent Termination
• Direct Vent - Sidewall Termination
Page 29
4.8 Vent / Air Pipe Termination (continued)
Exhaust
12” MIN
Apart
NOTE: The Exhaust must be equal to or above the
Combustion Intake while at a Minimum of 12” apart.
FRONT VIEW
Vent Screens are required
1” MIN
12” MIN
Exhaust
Exhaust Screen
Exterior Wall
90 o
Elbow
NOTE: Must be 12”
Minimum distance above highest anticipated snow level or grade, whichever is greater (TYP).
Air Intake Screen
Combustion
Intake
SIDE VIEW
A
Exterior Wall
Exhaust Exhaust
Exhaust Screen
B
12” MIN
12”
MIN
Combustion
Intake
FRONT VIEW
Vent Screens are required
12” MIN
90 o
Elbow
NOTE: Must be 12”
Minimum distance above highest anticipated snow level or grade, whichever is greater (TYP).
Air Intake Screen
Combustion
Intake
SIDE VIEW
Exhaust Exhaust
Screen
1” MIN
Sill
Exterior Wall
C
Exhaust
12” MIN
12”
MIN
Combustion
Intake
FRONT VIEW
Combustion
Intake
12” MIN
NOTE: Must be 12”
Minimum distance above highest anticipated snow level or grade, whichever is greater (TYP).
SIDE VIEW
Vent
Screens are required
1” MIN
Sill
• Direct Vent - Optional Side wall Terminations
• Direct Vent - Optional Side wall Terminations
Page 30
• Direct Vent - Optional Side wall Terminations
Exterior Wall
Concentric Vent Termination
• Direct Vent - Optional Horizontal and Vertical Concentric Vent
(2” or 3”)
Side Wall Kit
(2” or 3”)
12” Minimum clearance above highest anticipated
4. Concentric Vent Termination
• Direct Vent - Optional Horizontal and Vertical Concentric Vent
12” Minimum clearance above highest anticipated
Exhaust snow level or grade,
Exterior Wall
Exhaust
Exhaust
4. Concentric Vent Termination
• Direct Vent - Optional Horizontal and Vertical Concentric Vent
4" (100mm)
12” Minimum clearance above highest anticipated snow level or grade, whichever is greater.
12” (30cm) Minimum clearance above highest anticipate
snow level.
4. Concentric Vent Termination
• Direct Vent - Optional Horizontal and Vertical Concentric Vent
above highest anticipated snow level or grade, whichever is greater.
Strap
Vent
Combustion Air
12” Minimum clearance above highest anticipated snow level or grade, whichever is greater.
Vent
12” Minimum clearance above highest anticipated snow level or grade, whichever is greater. clearance above highest anticipate
snow level.
12” (30cm) Minimum clearance above highest anticipate
snow level.
Vent
Combustion Air
Vent
Combustion Air
Vent
Combustion Air
The FT Series Wall Mounted, Combination Boiler
Page 31
4.10
Gas Supply and Piping
Gas piping should be supported by suitable hangers or floor stands, not the appliance.
Review the following instructions before proceeding with the installation.
1. Verify that the appliance is fitted for the proper type of gas by checking the rating plate. FT will function properly at elevations up to 10,000 feet
(3050 m). Refer to Section 4.12 for High Altitude
Settings.
2. For minimum and maximum supply pressures, see
Table 9 on page 34
3. Refer to
Table 6, Table 7, and Table 8
to size piping.
4. Run gas supply line in accordance with all applicable codes.
5. Locate and install manual shutoff valves in accordance with state and local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to action of liquefied petroleum gas.
8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.45kPa).
9. The unit must be isolated from the gas supply system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2
PSIG (3.45kPa).
10. The appliance and its gas connection must be leak tested before placing it in operation.
11. Purge all air from gas lines.
CAUTION
PRV (included) must be installed immediately at the top of boiler outlet to PRV, with no valves between.
Refer to Section 4.15
__________________________________________
WARNING:
Open flame can cause gas to ignite and result in property damage, severe injury, or loss of life.
NOTE
: The FT appliance and all other gas appliances sharing the gas supply line must be firing at maximum ca
pacity to properly measure the inlet supply pressure. The pressure can be measured at the supply pressure port on the gas valve. Low gas pressure could be an indication of an undersized gas meter, undersized gas supply lines and/or an obstructed gas supply line.
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY
UNDILUTED PROPANE
NOMINAL PIPE SIZE
@
11" W.C. INLET AND 0.5" W.C. PRESSURE DROP
SIZE 1/2" 3/4" 1"
LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER
HOUR
20 200 418 787
40
60
80
137
-
-
287
231
197
541
434
372
100 - 175 330
NOTES:
1. Follow all local and national propane gas codes for line sizing and equipment requirements. 2. Verify that inlet gas pressure remains between
4 and 13 inches of water column before and during operation.
Source: ANSI Z223.1-80 National Fuel Gas Code.
Table 6. Nominal Pipe Size, Propane
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS
NOMINAL PIPE SIZE
@
0.30" W.C. PRESSURE DROP
LENGTH 3/4" 1"
FT CUBIC FEET OF GAS PER HOUR
20 190 350
40
60
80
130 245
105 195
90 170
100
Table 7. Nominal Pipe Size, Natural Gas
ATTENTION
PRV (inclus) doit être installé immédiatement en haut de la chaudière sortie de PRV, sans les vannes entre.
Se reporter à la Section 4.15
__________________________________________
EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS
NOMINAL PIPE SIZE
FITTING
1/2" 3/4"
LINEAR FEET
1"
90° ELBOW 3.6 4.4 5.2
TEE 4.2 5.3 6.6
Table 8. Equivalent Pipe Lengths
Page 32
The gas connection fitting is,
3/4” male NPT
on FTCW140 models
3/4” male NPT
on FTCW199 models
The supply line must be sized for the maximum output of the combination boiler model being installed. If there are additional gas appliances from the main supply line, you must measure sizes of the supply line according to the
COMBINED total maximum BTUH draw for the appliances as if they were all operating at the same time.
Measure the length of the gas supply line from the gas meter to the Combination boiler.
Use the tables in this manual or refer to the gas line manufacturers sizing information to determine the correct supply pipe size.
The gas shut-off valve in the gas supply line should be installed close to the unit.
To facilitate any future maintenance, it is also recommended that an approved gas union fitting be installed in the supply line between the shut-off valve and the 3/4˝ male NPT connection on the
Combination boiler.
1) Install an approved gas line pipe to gas line connection under the Combination boiler.
Include manual shut off valve and gas union connection, as shown.
2) Test gas pressure to make sure it meets the minimum standards and does not exceed the maximum standards for the combination boiler.
3) Leak test the gas line pipe before placing the unit in operation. Use approved leak detector liquid solutions only to check for leaks.
Do Not Operate the combination boiler until all connections have been completed, checked for leaks, and the heat exchanger is filled with water.
CLOSED POSTION
UNION
FITTING
MANUAL SHUT OFF VALVE
GAS PIPE
Gas Line Valve Detail
The FT Series Wall Mounted, Combination Boiler
4.10 Gas Supply and Piping (cont)
Suggested Natural Gas (NG) Layout
NOTE: Total gas supply capacity must not be less than the total demand capacity of the connected appliances.
Page 33
Suggested Propane Gas (LP) Layout
NOTE: Total gas supply capacity must not be less than the total demand capacity of the connected appliances.
The combination boiler must be installed downstream of the gas meter for adequate gas supply.
The gas piping must not be less than
1/2”
for FTCW140 models and
3/4” female NPT on FTCW199 models.
Page 34
4.11
Gas Supply Pressure
Refer to the illustration.
Offset Adjustment.
Do Not Adjust without using a combustion analyzer to verify adjustment. Adjust ONLY when in MIN Fire and when using a combustion analyzer.
See Section 4.12 for step by step details.
Gas Outlet / Manifold Pressure Port
Inlet Gas Pressure Port
FTCW
140
FTCW
199
Gas Outlet / Manifold Pressure Port
Inlet Gas Pressure Port
Offset Adjustment.
Do Not Adjust without using a combustion analyzer to verify adjustment. Adjust
ONLY when in MIN Fire and when using a combustion analyzer.
See Section 4.12 for step by step details.
LP Gas Natural Gas
The Maximum and Minimum gas line pressures must be at
Max Fire operation.
Maximum Pressure
13.0" WC
Maximum Pressure
10.5" WC
Minimum Pressure
8.0" WC
Minimum Pressure
3.5" WC
CAUTION
Table 9.
Gas Pressures
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
Loosen the pressure port screws before you check the gas inlet pressure.
The FT Series Wall Mounted, Combination Boiler
4.12
Adjusting Combustion
1. Using a Phillips screwdriver, remove the 4 screws on the front cover and remove cover.
2. Turn ON the GAS and WATER supply to the FT.
3. Turn ON the FT.
4. Ensure your mascot FT is set for the correct altitude. The default setting is for altitudes of
0~1,999 ft above sea level. If your Mascot FT is installed at an altitude of 2,000 ft,or greater the correct altitude setting should be set according to Section 4.13 of the Mascot FT Install and
Operating Manual (document #1318) before you continuing tuning this unit.
5. Connect a manometer to the manifold pressure port. For dual port manometers, use the positive pressure side. Check for proper manifold gas pressure. Refer to table below.
6. Establish a call for heat. You may need to disconnect the outdoor reset if you are making this gas conversion during warm weather.
7. Setup your combustion analyzer and place the sensor into the combustion test port
Page 35
8. Per Table B for Max Fire, change dip switch 6 to
ON and 7 to OFF. The unit will cycle up to MAX fire.
9. WAIT for your combustion analyzer to stabilize.
This may take up to 3 minutes depending on your combustion analyzer. Then check the CO2 measurement for MAX fi re. Refer to Table 10 for acceptable MAX fire combustion readings Do
NOT attempt to adjust CO2 at MAX Fire.
ONLY adjust CO2 in MIN Fire operation .
10. Per Table B for MIN Fire, change dip switch 6 to
OFF and 7 to ON. The unit will cycle down to MIN
Fire.
11. WAIT for your combustion analyzer to stabilize.
Then check the CO2 measurement for MIN fi re. Refer to Table 10 for acceptable MIN fire combustion readings
12. Open the Gas Valve Adjustment Port by removing the cap screw with a 4mm Allen wrench.
13. Then use the 4 mm Allen wrench to make a minor adjustment (1/8 turn) to either increase or decrease CO2. See 4.11 on page 34
WARNING
Document 4288D
NOTE: Installer is required to verify combustion settings as part of the installation process. CO should not exceed 200 ppm.
Standard Factory Setting is for
MAX Fire. 9.0% CO2 @ 0-2,000 ft altitude (Natural Gas).
CO
2
value
FTCW (ALL Sizes)
( and all altitudes)
CO2 Values
MAX FIRE
MIN FIRE
Natural Gas (NG)
2˝ VENT 3˝ VENT
8.5 - 10.5%
8 - 10%
Propane Gas (LP)
2˝ VENT 3˝ VENT
9.5 - 11%
9 - 10.5 %
Manifold pressure
FTCW140
FTCW199
MAX FIRE
MIN FIRE
MAX FIRE
MIN FIRE
Table D
Manifold Pressures
‘NG’ type combustibility
2"/3" VENT
-0.216
" WC
0.002
" WC
-0.314
"WC
-0.015
"WC
‘LP’ type combustibility
2"/3" VENT
-0.216
" WC
0.079
" WC
-0.173
"WC
-0.015
"WC
21.
It may be necessary to go back and forth between HI Fire and LOW Fire several times (and making adjustments only at LOW Fire), before
CO2
at both are within acceptable levels. Be sure to put the adjustment port cap screw back onto the valve when done.
22.
Once the CO2
and manifold pressure measurements for both MIN and MAX Fire are acceptable per
Table C, set DIP switches 6 and 7 to the OFF position for Nominal Fire (normal operation).
23.
Write in the correct Conversion Date and the Technicians Name to the included gas conversion sticker. See Figure F. Then apply that sticker adjacent to the rating plate.
24. Remove your combustion analyser from the Test Port and be sure to thread the Test Port plug back into position.
25. Re-connect outdoor reset if it was disconnected, put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
This unit was converted on ____/____/___to _____gas with kit #____________by______________________
(name and company __________________________ accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz en utilisant le kit numéro _____ par______________
(nom et société_________________________________ responsable)___________________________________
_____________________________________________
Figure F (Conversion label)
800.900.9276
•
Fax 800.559.1583 (Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355 (Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
• pg 4 of 4 www.Laars.com
Page 36
14. It may be necessary to go back and forth between HI Fire and LOW Fire several times (and adjusting only at LOW Fire), before CO2 at both are within acceptable levels. Be sure to put the adjustment port cap screw back onto the valve when done.
15 Once the CO2 and manifold pressure measurements for both MIN and MAX Fire are acceptable per Table C, set DIP switches 6 and
7 to the OFF position for Nominal Fire (normal operation).
16. Remove your combustion analyzer from the Test
Port and be sure to thread the Test Port plug back into position.
17. Re-connect outdoor reset if it was disconnected, put the boiler cover back on and assemble/tighten the 4 screws that hold the cover in place.
4.13
High Altitude Installations. 2,000’ to 10,000’
The FT is shipped with a default factory setting for installation at an altitude of 0 to 2000’ (approx). For maximum efficiencies at higher altitudes (2,000’ to 10,000’), the FT does have an adjustment in the
Installer Parameters Mode.
Follow these instructions if your installation is at 2,000’ - 10,000’.
1. With the Power
turned OFF, press the 'Modes button' for 5 seconds to get into the Installer
Parameters Mode.
2. Turn the dial (E) until ‘ 28:HA ’ appears.
3. Press the dial (E).
4. Set the high altitude value by turning the dial.
#
2
4
0
1
Altitude of Installation
0~1999 ft (0~609 m)
2,000~4,499 ft (610~1,645 m)
4,500~7,699 ft (1,646~2,346 m)
7,700~10,000 ft (2,347~3,048 m)
Refer to table.
5. Press the dial again (E) to save the setting.
6. Press the ‘Modes button’
for one second, to
Save the number and to go back to initial status.
The FT Series Wall Mounted, Combination Boiler
Page 37
The FT Series, Wall Combi, Gas Conversion Kit
4.14
Natural Gas to Propane Conversion
Kit # R20770
The FT Series, wall combi, condensing boiler is confi gured for Natural Gas (NG) from the factory.
A Natural Gas to Propane Conversion Kit is included with every FT. The gas conversion kit will show you how to convert your FT boiler to propane gas. If your
FT does not have the bag containing the conversion kit, a replacement kit can be obtained. Contact the manufacturer and request a replacement conversion kit.
NOTICE
If your installation altitude is greater than 2000 ft, check that the ‘High Altitude’ Installer Setting has been adjusted to suit your installation altitude. Refer to Section 4.12 of the
Installation and Operation Instructions (Document 1318).
WARNING
This gas conversion kit shall be installed by a qualifi ed service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. The information in these instructions must be followed to minimize the risk of fi re or explosion or to prevent property damage, personal injury or death. The qualifi ed service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specifi ed in the manufacturer’s instructions supplied with the kit.Installation must conform to local codes and the latest edition of the National Fuel
Gas Code, ANSI Z223.1 and CAN-B149.1. Failure to follow instructions could result in serious injury or property damage. The qualifi ed agency performing this work assumes responsibility for gas conversion.
CAUTION
This combination boiler has already been set to burn natural gas, but can be converted to burn LP gas. Before placing the combination boiler into operation, verify that the type of gas supplied to your combination boiler.
ON / OFF
Document 4288D
Steps 1 thru 17
1. Turn OFF the FT. The ON / OFF button is located at the bottom left of the Control Display
.
2. Turn OFF the GAS and WATER supply to the FT
(valves are located on the plumbing pipes.)
3. Using a Phillips screwdriver, remove the 4 screws on the front cover. See Figure A.
4. Locate the Gas Inlet Pipe at the top left of the unit as shown in Figure A, and loosen the Brass Fittings at both ends of the Gas Inlet Pipe.
5. Completely unthread the brass fi tting on the blower end of the Gas Inlet Pipe and then carefully swing the Gas
Inlet Pipe to the left or right, just enough so that it is out of the way. See Figure B.
6. Remove the existing natural gas nozzle or orifi ce. If your unit is a 199, note that the fl at side of the orifi ce is towards the blower. Save the packing for re-use. See
Figure C.
Model
FTCW140
Natural Gas (NG) part #
FT1412N
FTCW199
Table A. Gas Conversion Parts
FT1780
Propane Gas (LP) part #
FT1412P
FT1802
Nozzle
Orifi ce
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
• pg 1 of 4 www.Laars.com
Page 38
The FT Series, Wall Combi, Gas Conversion Kit
Figure A
Gas Valve
Combustion
Test Port
Figure B
Document 4288D
Figure C
Gas Valve
FTCW
140
FTCW
199
Figure B
Gas Valve
Figure C
ORIFICE
PACKING
WARNING
AVERTISSEMENT
This conversion shall be installed by a qualifi ed service agency in accordance with the manufacturer's
Ce conversion doit être installé par un organisme de service conformément aux instructions du fabricant instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a fi re, et tous les codes et les exigences de l’autorité compétente. Si les informations contenues dans ces instructions n’est pas suivi à la lettre, un incendie, an explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualifi ed service agency is une explosion ou de la production de monoxyde de carbone mais résultat causant des dommages matériels, des blessures ou des pertes de vie. Le responsible for the proper and complete installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specifi ed in the manufacturer's instruction supplied with the kit.
• service est responsable pour la bonne et complète l’installation de ce kit. L’installation n’est pas correcte et complète jusqu’à ce que le fonctionnement de l’appareil converti est vérifi ée comme spécifi é dans le manuel d’instruction fourni avec le kit.
•
(Applications Engineering)
905.238.0100
• pg 2 of 4 www.Laars.com
The FT Series Wall Mounted, Combination Boiler
Page 39
Document 4288D
ON
MIN Fire
MAX Fire
NG Natural
3” Vent Size
ON OFF
ON
OFF
OFF
ON
OFF
Normal Operation
Normal Operation
LP Propane
2” Vent Size
ON ON
OFF
ON
ON
ON
MBH 120 140 175 199
Table B DIP Switch Settings
7. Install the new LP (propane) nozzle or orifi ce. Reuse the packing from previous.
8. Return the Gas Inlet Pipe to its original position and tighten both brass fi ttings.
9. Per Table B, set DIP Switch 5 to OFF for LP
Propane.
10. Turn ON the GAS and WATER supply to the FT
11. Now start the unit and adjust combustion as described in Section 4.12
12. Upon completion of set up, write in the correct
Conversion Date and the Technicians Name to the included gas conversion sticker. See Figure F.
Then apply that sticker adjacent to the rating plate.
Shown is a
Model 140 with 3" Venting and using
Natural Gas
Figure D
Gas Valve
Adjustment Port
FTCW
140
Figures E
Gas Valve
Adjustment Port
-
-
+
800.900.9276
•
Fax 800.559.1583
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
FTCW
Fax 603.335.3355
199
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
• pg 3 of 4 www.Laars.com
Page 40
The FT Series, Wall Combi, Gas Conversion Kit
Document 4288D
NOTE: Installer is required to verify combustion settings as part of the installation process.
CO should not exceed 200 ppm.
FTCW (ALL Sizes)
( and all altitudes)
Table C
CO
2
value
MAX FIRE
MIN FIRE
Natural Gas (NG)
2˝ VENT 3˝ VENT
8.5 - 10.5%
8 - 10%
Propane Gas (LP)
2˝ VENT 3˝ VENT
9.5 - 11%
9 - 10.5 %
Manifold pressure
FTCW140
FTCW199
MAX FIRE
MIN FIRE
MAX FIRE
MIN FIRE
Table D
‘NG’ type combustibility
2"/3" VENT
-0.216
" WC
0.002
" WC
-0.314
"WC
-0.015
"WC
‘LP’ type combustibility
2"/3" VENT
-0.216
" WC
0.079
" WC
-0.173
"WC
-0.015
"WC
This unit was converted on ____/____/___to _____gas with kit #____________by______________________
(name and company __________________________ accountable)_________________________________
___________________________________________
Cette unité a été converti ____/____/____ten ______gaz en utilisant le kit numéro _____ par______________
(nom et société_________________________________ responsable)___________________________________
_____________________________________________
Figure F (Conversion label)
800.900.9276
•
Fax 800.559.1583
(Customer Service, Service Advisors)
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
Fax 603.335.3355
(Applications Engineering)
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
• pg 4 of 4 www.Laars.com
The FT Series Wall Mounted, Combination Boiler
Page 41
4.15
Plumbing Guidelines
4.15.1
External Plumbing and Water
Connection Guidelines
- Ensure pipe material meets local codes and industry standards.
- The pipe end must be clean and free of debris.
- Do not apply torch heat within 12˝ of the bottom connections of the unit.
- The DHW inlet and outlet connections are 3/4”.
The CH supply and return connections are 1”. The system piping must be a min. of 1-1/4” (see Sections
4.15.4 & 4.15.5 for details).
- Isolation valves (shutoff valve) will be used.
- All piping should be insulated.
4.15.2
Applicable Backflow Preventer
- Apply a backflow preventer valve in the DHW supply inlet (water Inlet) to the unit as required by local codes.
4.15.3
Diaphragm type Expansion tank
- The air in a diaphragm-type expansion tank is separated from the water by a flexible rubber membrane. When the tank is installed in and connected to the piping of the system, water enters the other side of the tank chamber and presses down on the diaphragm.
- You should always install an ‘Automatic Air Vent on the top of the air separator to remove
residual air from the system.
- Automatic air vent has been installed on the inside of the boiler.
- The installation of an additional air vent is optional.
- If the boiler is installed in a closed water supply system, such as one having a backflow preventer in the cold water supply line, it will control thermal expansion.
CAUTION
Use at least the MINIMUM pipe size for the entire boiler loop piping (connecting boiler to and from the primary/secondary connection). Use only primary/secondary piping as shown. Failure to follow these guidelines could result in system problems.
CH pipe minimum size : 1 1/4˝
DWH pipe minimum size : 3/4˝
CAUTION
For guidelines in the use of Glycol Products.
Please refer to Section 8.4 on page 74
CAUTION
Scalding Risk: Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet (boiler location) to reduce potential for scalding.
Contact Manufacturer for recommended models.
Check with local codes.
__________________________________________
Page 42
4.15.4
Zoning with zone valves
- In a valve based system, there is one circulator pump at the boiler and each heating zone has a zone valve which opens when the zone demands.
- Each thermostat is wired directly to the corresponding zone valve. Contacts in the zone valves provide a proper signal to the boiler when the valve is opened.
SECONDARY LOOP
(SPACE HEATING)
(SPACE HEATING)
Auto Fill Valve and Backflow
Preventer Valves are
NOT included (Field
Supplied).
Do not exceed
12"
See
Note
Do not exceed
12"
See
Note
Make-Up Water
Make-Up Water
P
P
Differential
Pressure By-Pass
Pressure By-Pass
Expansion tank
Expansion tank
Automatic air vent
Automatic air vent
Air separator
Air separator
Circulation pump
Circulation pump
Check valve
Check valve
Drain valve
Drain valve valve valve
Backflow preventer
Backflow preventer
Pressure Relief Valve
Pressure Relief Valve
Anti-scald rated
Mixing Valve
Mixing Valve
1 1/4 ”
1 1/4 ”
Min
Piping
Min
Piping
CH
CH
SUPPLY
SUPPLY
DHW INLET
DHW INLET
DHW OUTLET
DHW OUTLET
CH RETURN
CH RETURN
1. This piping diagram is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be 12” (or 4 pipe dia) center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimum pipe size of DHW piping should be 3/4” diameter.
5. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
6. Install a check valve on the return line to the boiler.
7. Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet (boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models. Check with local codes.
P
P
The FT Series Wall Mounted, Combination Boiler
4.15 Plumbing Guidelines (continued)
4.15.5 Zoning with circulation pumps
- In a pump based system, each heating zone of has its own circulator pump which runs when the zone demands.
- Each zone thermostat goes to a controller which controls the pumps.
SECONDARY LOOP
(SPACE HEATING)
(SPACE HEATING)
Auto Fill Valve and Backflow
Preventer Valves are
NOT included (Field
Supplied).
Do not exceed
12"
See
Note
Do not exceed
12"
See
Note
1 1/4 ”
Expansion tank
Min
Piping
Air separator
Air separator
1 1/4 ”
Min
Piping
Make-Up Water
Make-Up Water
DHW INLET
DHW INLET
Check valve
Drain valve
Gate valve
Check valve
Drain valve
Gate valve
Page 43
Anti-scald rated
Mixing Valve
Anti-scald rated
Mixing Valve
CH
SUPPLY
CH
SUPPLY
DHW OUTLET DHW OUTLET
CH RETURN CH RETURN
1. This piping diagram is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes.
2. All closely spaced tees shall be 12” (or 4 pipe dia) center to center spacing.
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees.
4. The minimum pipe size of DHW piping should be 3/4” diameter.
5. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
6. Install a check valve on the return line to the boiler.
7. Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet (boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models. Check with local codes.
Page 44
4.16
Pressure Relief Valve
External pressure relief valves must be installed.
Observe the following. Failure to comply with the guidelines on installing the pressure relief valve and discharge piping can result in personal injury, death or substantial property damage.
WARNING
Do not operate this appliance before the pressure relief valve supplied is installed with sufficient relieving capacity in accordance with the ASME Rating Plate on the boiler.
This hot water boiler is provided with 30 psi safety relief valve that complies with the ANSI/ASME Boiler and
Pressure Vessel Code, Section IV (“Heating Boilers).
(Model : CASE ACME F-82)
This safety relief valve (30 psi) is shipped loose for field installation.
An approved ASME HV Pressure Relief Valve must be installed on the DHW supply line as close to the unit as possible. Valve size 3/4”, maximum 150 psi. Not included with boiler.
For safety, the relief valve(s) must be installed into it’s designed location and not be removed or plugged.
Failure to comply with the guidelines on installing the pressure relief valves and discharge piping can result in personal injury, death or substantial property damage.
Direct the discharge piping of the pressure relief valve so that hot water will not splash on anyone or any nearby equipment. Attach the discharge line to the pressure relief valve and run the end of the line within
6-12″ (150-300mm) of the floor.
WARNING
DO NOT install a CH pipe line relief valve with a pressure higher than 30psi and DHW pipe line relief valve with a pressure higher than 150psi. This is the maximum allowable relief valve setting for the combination boiler.
Test the operation of the valve after filling and pressurizing system by lifting the lever. Make sure the valve discharges freely. If the valve fails to operate correctly, replace it with a new relief valve. Ensure that the discharge capacity of the pressure relief valve is equal to or greater than the maximum pressure rating of the combination boiler.
Ensure that the maximum BTU/H rating on the pressure relief valve is equal to or greater than the maximum input BTU/H rating of the combination boiler.
Pressure Relief Valve must be installed on the CH supply line & DHW outlet line as close to the unit as possible. (CH supply line: maximum 30psi, DHW outlet line : maximum 150psi). No other valves should be placed between the pressure relief valve and the appliance.
This appliance has a high-temperature shut off switch built in as a standard safety feature .Therefore a
“pressure only” relief valve is required.
3/4” 30psi Relief Valve
The FT Series Wall Mounted, Combination Boiler
4.17
Disposal of Condensate
High efficiency gas condensing Boilers create condensation when operating. Condensation has acidic (pH) of approximately 4-5.
Condensate must be drained in accordance with all local regulations. Follow your local code with regards to the disposal of condensation.
One of 4 disposal methods must be followed
1. to floor drain
2. to neutralizer (optional kit)
3. to laundry tub
4. to condensate pump (field supplied)
If a neutralizer is installed, periodic replacement of the lime stone (or neutralizing agent) will be required. The rate of depletion of the lime stone varies upon usage of the boiler. During the first year of operation, please check the neutralizer every few months for depletion.
Apply only corrosion-resistant materials for the condensate drain lines such as 1/2˝ PVC, CPVC,
Polypropylene pipe or included plastic hose.
Condensate
Trap
Condensate drain pipe
NOTICE
Category II & IV water heaters must be installed with a means provided for the drainage of condensate.
Page 45
(View is as if side panel were removed)
AVIS
Catégorie II & ; IV chauffe-eau doit être installé avec une moyens prévus pour l’évacuation des condensats.
2 3
4
1
CAUTION
Condensate is mildly acidic (pH=5), and may harm some floor drains and/or pipes, particularly those that are metal. Ensure that the drain, drainpipe, and anything that will come in contact with the condensate can withstand the acidity, or neutralize the condensate before disposal. Damage caused by failure to install a neutralizer kit or to adequately treat condensate will not be the manufacturer’s responsibility.
Contact Manufacturer to order
Neutralizer Kit# A2123601
_________________________________________
Page 46
4.18 DHW Flow Restrictors
Flow Restrictors are factory installed. Rated at 3.2
GPM for the model 140 and 7.0 GPM for the model
199, both of these factory installed restrictors are white in color. For the 140, an additional flow restrictor, rated at 4.5 GPM, is blue in color and is packaged with the Product Accessories. See Section 1.
If 3.2 GPM is not sufficient for your model 140 installation, replace the factory installed white flow restrictor with the blue flow restrictor by following these instructions.
To replace the Flow Restrictor.
1. Being sure that the unit is completely shut off and drained, locate the DHW inlet adapter on the bottom of the appliance.
2. Pull the two pins to release the DHW inlet filter. See
Illustration. The flow restrictor is attached to the top of the filter assembly.
3. Remove the installed white flow restrictor and replace it with the blue flow restrictor included with the Product Accessories.
4. Reinstall the DHW inlet filter.
5. Re-insert the two pins.
6. Refill and restart your FT as per the Installation
Instructions.
WARNING
If the appliance has been filled and operational, then the gas, water and power must be completely shut off, and the unit must be drained before proceeding with this instruction. See Section 8 of this installation book.
Failure to do so could result in substantial property damage, sever personal injury, or death.
Flow Restrictor
Shown is the 140. The 199 is very similar.
The FT Series Wall Mounted, Combination Boiler
4.19 Electrical Wiring Connections
FTCW140
Page 47
Manual Switch
L N
Terminal Block
0-10V
INPUT
T T
O / S
0 - 10V
External Input
Thermostat Connection
Outdoor
Sensor
WARNING
Install wiring and electrically ground boiler in accordance with authority having jurisdiction or, in the absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1 Electrical Code-Part
1 in Canada.
ELECTRICAL SHOCK HAZARD — For your safety, turn off electrical power supply at service entrance panel before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death.
This appliance must be electrically grounded. Ensure the electrical receptacle that the combination boiler will be plugged into, is properly grounded; if wiring directly.
Do not attach the ground wire to either the gas or the water piping as plastic pipe or dielectric unions may isolate the Combination boiler electrically.
The wiring diagrams contained in this manual are for reference purposes only.
Refer to these diagrams and diagrams from external controls used with this appliance. Read, understand, and follow all wiring instructions.
Do not disconnect the power supply when the unit is in normal operation. Damage caused by freezing is not covered under the warranty.
Manual(Rocker) switch maximum allowable current for each circulator is 1.6 amps at 125VAC.
( Housing : Nylon #66 UL 94V-2 , Rocker : Nylon #66 UL 94V-2, Terminal : Copper Alloy )
Terminal block (External power connector) : DFT-20A-10P (20 amps at 300VAC)
Page 48
4.19 Electrical Wiring Connections (cont)
FTCW199
Terminal Blocks
Manual Switch
0-10V
INPUT
T T
O / S
MAIN POWER CH/BOILER PUMP
Main
Power
External
CH Pump
0 - 10V
External Input
Thermostat Connection
Outdoor
Sensor
The FT Series, Wall Combi, Gas Conversion Kit
4.20 DIP Switches
Document 4288D
ON
MIN Fire
MAX Fire
NG Natural
3” Vent Size
ON OFF
ON
OFF
OFF
ON
OFF
Normal Operation
Normal Operation
LP Propane
2” Vent Size
ON ON
OFF
ON
ON
ON
MBH 120 140 175 199
Table B DIP Switch Settings
Pump1 post circulating time (T1pv)
Pump2 post circulating time (T1pv)
Propane.
Shown is a
Model 140 with 3" Venting and using
Natural Gas System Control Setting
Maximum flame detecting voltage
Pre-purge time (Tp)
11. Now start the unit and adjust combustion as described in Section 4.12
<3s
60s
60s
<6s
<6s
2.4V
Figure D
Maximum 10s, minimum 1s
3s
10s
Gas Valve
Adjustment Port
-
+
12. Upon completion of set up, write in the correct
Conversion Date and the Technicians Name to the included gas conversion sticker. See Figure F.
Then apply that sticker adjacent to the rating plate.
FTCW
140
Figures E
Gas Valve
Adjustment Port
-
800.900.9276
•
Fax 800.559.1583
20 Industrial Way, Rochester, NH 03867
•
603.335.6300
•
FTCW
Fax 603.335.3355
199
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8
•
905.238.0100
•
Fax 905.366.0130
www.Laars.com
The FT Series Wall Mounted, Combination Boiler
4.21 Control Board, Electrical Diagram
Control Board
Page 49
Page 50
4.22 Ladder Diagram
Air
Pressure
Sensor
F/B
level
The FT Series Wall Mounted, Combination Boiler
4.23 Electrical Connections
Connector
#, Location, Type
CN9
65001WS-12
CN6
LW6A4-03
CN1
SMW250-5D
CN4
LWD1140-06D
CN8
SMW250-04D
CN11
LWD1140-16
PIN Label
7
8
5
6
1
2
3
3
4
1
2
1
2
3
9-12
1
3
4
1
8
2
10
3
11
4
12
5
13
6
14
7
15
8
16
4
5
1
2
3
6
RS-485
FAN
MCU ISP
HWL
LWL
HD
TH
APS
EL
BL
HL
-
L
CP1
IT
L(HT)
GV
-
N
N
CP3/3Way
Description
GROUND
Power Supply Line
Not Used
Igniter
Pump : CH
Gas Valve
-
Power Supply Neutral
AC Power COM Line
3 Way Valve
RS485 +
GND
RS485 -
Not Used
GND
VDD
Fan power(start coil)
Fan power(end coil)
Fan speed feedback signal
GND
ISP /Reset port
ISP TOOL0 Data port
VCC
Not Used
Low Water Level Leakage Sensor
Central Heating Demand
Connect to the Display
Control(Thermostat)
Jump
Jump
Burner Limit
Condensate Block
HT SELV
HT (120V~)
HT (120V~)
HT (120V~)
HT (120V~)
HT (120V~)
HT (120V~)
-
HT (120V~)
HT (120V~)
HT (120V~)
HT (120V~)
SELV (5V)
SELV (5V)
SELV (5V)
-
SELV (30V)
SELV (14V)
SELV (30V)
SELV (30V)
SELV (14V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (12V~)
SELV (12V~)
SELV (5V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
Page 51
Page 52
Connector
#, Location, Type PIN Label
CN7
LWD1140-14
CN14
SMW250-09D
2
3
4
13
7
14
1
5
6
7
5
12
6
10
4
11
2
9
3
1
8
F.S
OP.S
DH.S
I.S
BG.S
ST.S
SP.S
DHM
CN3
SMW250-06D
CN5
SMW250-10D
8
1
2
4
5
6
2
3
9
1
APS
SENSOR
FLUX1
RPM
Description
Flame Detect Sensor
Operating water temperature sensor
DHW temperature sensor
Return temperature sensor
Venting (Exhaust) temperature sensor
Not Used
Over-Heat temperature sensor
GND
DHM Stepper motor position
VDD
DHM Stepper motor coil X phase
DHM Stepper motor coil Y phase
VDD
DHM Stepper motor coil /X phase
DHM power IWM Stepper motor coil /Y phase
Unuse
VCC
GND
Voltage Input
VCC
Water Flow Sensor
GND
FAN RPM Check
GND
HT SELV
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
SELV (14V)
-
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
SELV (5V)
The FT Series Wall Mounted, Combination Boiler
SECTION 5
Control Display and Operation
5.1 Control Dial and Buttons
Page 53
The Control Display
The Control Display has a Control Dial (E), 4 buttons (A, B, C, D), and a Liquid
Crystal Display (with 72 back-lit segments). This section of this manual gives instruction on how to navigate into the many functions of the FT and to change temperature set points, set system variables and controller parameters.
Status Light
(constant green when operating normally)
Buttons
A
B
C
D
E
Display
Power
Functionality
PRESS (Tap)
Turns Control Display
ON / OFF
PRESS and HOLD (5 seconds)
Modes Tap to return to menu
(If Display Power was On ) Status Display Mode
(If Display Power was Off )
Installer Mode
Hot Water
Central Heat
DHW Set-Point LOW Range
95 - 120°F (35 - 49°C)
DHW Set-Point HIGH Range
121 - 140°F (49.5 - 60°C)
CH set-point mode
(boiler only)
Toggle (°C / °F)
Scroll /
Select
Turn to scroll, tap to select
(clockwise or counterclockwise)
• Temperature Specifications
Operating ambient Temperature Range : -10 to 60°C.
Operating Relative Humidity up to: 90% at 40°C.
Shipping & Storage Temperature Range of : -20 to 80°C.
Button function Method function method
A turn control on/off press (tap)
B (if the display..... press/hold (5 sec) return to menu tap
C DHW setpoint low ran... press (tap) DHW high range press/hold (5 sec)
D CH setpoint... press (tap) toggle (C/F) press/hold (5 sec)
E turn to scroll..... press (tap)
Page 54
5.2
LCD Overview
CH
Central
Heat
Summer
Mode
(warm weather shutdown)
Outside
Temp Mode or 0-10V
Anti-Freeze
Mode
Domestic Hot Water Mode
Storage
Heating
Numeric Display
Lock Communicating
Pump
Status and
Installer
Modes
Flame
Signal
CH mode
Anti-freeze mode
Storage Heating mode
Lock mode
Communication
Summer mode
Status and Installer mode
Flame signal
Pump icon
Numeric Display
DHW mode
Outside temp or 0-10 V mode
Central Heat mode icon can be adjusted
Anti-freeze mode icon
Stored Water Being Heated, can be adjusted
Buttons-locked mode icon
Communication icon
Only DHW Mode, can be adjusted (warm weather shutdown)
The Status Mode or the Installer Mode is Active (all parameters)
Flame Signal icon
Water pump operation (CH or DHW) icon
Number and character display, to display all parameters
Combination boiler Set Point, can be adjusted
Operating by outside temperature or 0-10V
The LCD will illuminate when a user action is detected (a button is pressed) and will turn back off after 20 seconds.
* NOTE: The display will not allow changes when the lock mode is activated.
To exit the Lock mode, press the button.
WARNING
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that may have been under water.
The FT Series Wall Mounted, Combination Boiler
5.3
Operating Mode
Operating Mode
After the Power is turned on, and/or the Control Display is turned on
, the Control Display will go through a ‘Start Up’ checklist and briefly show a sequence of diagnostic codes before entering into the ‘Operating Mode. It will then display the following information.
Page 55
Indicate
Current Operating Temperature
Temperature sign Celsius or Fahrenheit letter
Display and Controller are communicating
If flame detected
If pump is operating
Outdoor sensor or 0-10V
Example
110°F
°C or °F
Page 56
5.4
Status Display Mode
AUTODESK � � � � � � � � � �
Digital Display
Status Display Parameter
�� � �
O:ot
Outdoor temperature
A: Li or A: GA Flow unit b: It
�� � � AUTODESK ��
Description
Current Outdoor temperature
Current flow value(Li: L/m, GA: GPM)
CH Return Water Temperature Current Return Water Sensor Temperature
C: Fr d: Lc
Fan rpm
Lock mode
Current fan rpm value
Lock mode ON/OFF
E: oP
F: dH
H: Eh
I : St
J: oH
OP temperature
DHW temperature
Exhaust temperature
N/A
Overheat temperature
Current OP temperature
Current DHW temperature
Current Exhaust temperature
Not Used (Default is 0)
Current Overheat temperature
1: PH
Supply power time
Supply power time x 100 hour
L: rt
2: rh
3: rH
Burner
Operation
Time
Burner operation time
Burner operation time
Burner operation time x 1 hour
Burner operation time x 1,000 hour
4: It
5: IH
Ignition cycles
Ignition cycles
Ignition cycles x 10 times
Ignition cycles x 10,000 times
1st Icon 2nd Icon 3rd Icon
P: Ou
Displays output condition for internal primary pump and three way valve.
- Off
Not Used
Pump
- On
To change any of the above listed Status Parameters,
Press and Hold Button B
to get into the Status Display Mode.
Rotate Dial E until you find the Parameter that you wish to change. Tap Dial E to enter that Parameter.
Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.
The FT Series Wall Mounted, Combination Boiler
5.5 DHW Set Point Change Mode
DHW Set Point Change Modes
The display shows the following information when changing water heating temperature set points.
Changing between Celsius and Fahrenheit
When the button D is pressed (for more than 5 seconds), temperature unit will toggle between °C and °F.
Page 57
Indicate
Current DHW set-point temperature
Temperature sign Celsius or Fahrenheit letter
If display is communicating with the main controller normally, the communication icon will be indicated.
When DHW set-point range is high : from 121°F (49.5°C) to 140°F (60.0°C)
When changing DHW setpoint, the DHW icon will flash
Example
120°F
°C or °F
H . 140°F
S24
* Default DHW set-point is 120°F (49°C)
• DHW 95-120°F (35 - 49°C) LOW range (Default)
-To change LOW range, press the C Button. The DHW icon and current DHW LOW will flash (a flashing value means it can be changed).
-Turn dial E clockwise to increase and counterclockwise to decrease until desired temperature is reached.
-Press dial E to save setpoint changes.
• DHW 121 - 140°F (49.5 - 60°C) HIGH range
-To change HIGH range, press and HOLD
the C button for more than 5 seconds. The DHW icon and current DHW HIGH will flash (a flashing value means it can be changed).
-Turn dial E clockwise to increase and counterclockwise to decrease until desired temperature is reached.
-Press dial E to save setpoint changes and to Exit.
DANGER
Scalding may occur within 5 seconds at a setting of 140°F (60°C). Water temperatures over 125°F can cause severe burns, or death from scalding. Children, disabled, and elderly are at highest risk of being scalded. Read all instructions before setting temperature at appliance. Feel water before bathing or showering.
Manufacturer strongly recommends the use of an anti-scald mixing valve at domestic hot water outlet (boiler location) to reduce potential for scalding.Contact Manufacturer for recommended models. Check with local codes.
Page 58
5.6 CH Set Point Change Mode
Changing between Celsius and Fahrenheit
When the button D is pressed (for more than
5 seconds), temperature unit will toggle between
°C and °F.
Indicate
Current Operating Temperature
Temperature sign Celsius or Fahrenheit letter
Display and Controller are communicating
If flame detected
If pump is operating
When changing CH Setpoint, the CH Icon will flash
Example
110°F
°C or °F
Default CH set-point is 120°F (49°C)
CH set-point range is 86 - 180°F (30.0 ~ 82.0°C)
To change CH Setpoint,
press the D desired temperature is reached.
Press E dial to save changes and to Exit.
button. The CH Icon and current
CH Setpoint will flash.
Turn the E dial clockwise to increase, and counterclockwise to decrease CH setpoint, until
5.7 Storage Mode
Indicate
Current Operating Temperature
Temperature sign Celsius or Fahrenheit letter
Display and Controller are communicating
If flame detected
Storage mode indication
Example
110°F
°C or °F
If Pump is operating
To change Storage Mode Temp,
First turn OFF the power to the Control Display.
Then Press and Hold Button B
to get into the Installer Mode.
Rota te Dial E until you find
5:St
Tap Dial E to enter Storage Mode. Storage Mode indicates that the boiler is heating the water held in the internal storage tank. When Storage Mode is active, the display will appear as shown.
Turn the E dial clockwise to increase, and counterclockwise to decrease setting.
Press E dial to save changes and to Exit.
The FT Series Wall Mounted, Combination Boiler
AUTODESK � � � � � � � � � �
5.8 Installer Parameters
�� � � �� � �
To c hange any of the Installer Parameters,
Start by turning
OFF
the Power to the
Display Control.
Then, with the power OFF, Press and HOLD (more than 5 seconds) the Button B
Installer Mode. to get into the
Rotate Dial E until you find the Installer Parameter (full list on facing page) that you wish to change.
Tap Dial E to enter that Parameter.
Adjust to the setting that you require and then press (tap) Dial E to save and to Exit.
Finish by pressing button B
Page 59
Page 60
16:cH
17:cL
18:dH
19:cb
20:db
21:PP
22:Po
23:PF
24:SF
25:So
5.8 Installer Parameters
Index
1: EH
2: cE
3: In
4: Fu
5: St
6: OH
7: OL
8: FH
Parameter
History entry
Clear Error History
System initialize
Flow unit
Heat storage function
Maximum Outdoor
Temperature
Minimum Outdoor
Temperature
Max fan
9: FL
10: dr
11: dI
12: bt
13: Ft
14: bo
Min fan
Delete running time
Delete igniting times
Outside Unit Function
Delay Time (boost time)
Delay time for heating burner operation
Setting temperature of burner ON.
15: OF
26:dt
27:PE
28: HA
29: AP
30: dP
Description
History fault code (E0~E9)
Clearing of error History buffer
System initialize to default gallon / liter
Heat storage function On/Off
Range: (Minimum Outdoor Temperature + 9°F) to 110°F Default 68°F (20°C)
Range: -4°F to (Maximum Outdoor Temperature -9°F)
Adjusts Maximum Fan Speed
Range: -30 - +30
Adjusts Minimum Fan Speed
Range: -30 -+30
Delete running time
Delete igniting times
When heating in the outside unit function for the first time, there will be a delay.
(0~120 min, Default 0)
Burner does not operate during the delay time when the burner is turned off due to the temperature during heating operation. (0~20 min, Default 1 min)
Heating temperature setting during heating operation –
Operate in burner ON temperature setting Range:
-12.7°C(9°F)~-2.7°C(27°F), Default 2.7°C(27°F)
Setting for Heating
Maximum Temperature
Setting for Heating
Minimum Temperature
Setting for Hot Water
Maximum Temperature
Range: 9°F less than Minimum Temperature to 180°F, Default 180F
12.7°C less than Minimum Temperature to 82°C, Default 82°C
Range: 86°F to (9 degrees °F less than Maximum Temperature, Default 86°F
30°C to (12.7degrees °C less than Maximum Temperature, Default 30°C
49°C(120°F)~60°C(140°F), Default 60°C(140°F)
Heating Combustion Rate 50%~100%, Default 100%
Hot Water Combustion Rate 50%~100%, Default 100%
Pump Post-Purge Time
Pump on Time
Pump off Time
Heat storage off
Temperature
(Heating Pump) 1min ~ 60min, Default 40min
(Heating Pump Repeat ON Time) 1 min ~60 min, Default 5 min
(Heating Pump Repeat Off Time) 0min ~60 min, Default 10 min
60°C(140°F)~75°C(167°F),Default(70°C)158°F
Heat storage on
Temperature.
Delay time when switching from DHW mode to CH mode
(off Temperature-Setting Temperature) -12.7°C(9°F)~2.2°C(36°F),
Default (-2.7°C) 27°F
Range: 0 – 2 minutes,Default 2min
Internal CH Pump Post-
Purge Time,
T/T Satisfied
High Altitude setting
Allows the user to set the appliance pump post purge time once the appliance CH setpoint and thermostat are satisfied. Range: 1-5 minutes,Default 1min
(Normal)0<1<2<4 (High)
Internal CH Pump and
3-way valve Pump Test
Mode
Internal CH Pump and
3-way valve Pump Test
Mode
DHW Timeout Feature
This function sets the time to run both the Internal CH and 3-way valve pumps to purge air from the system. Range: 1 – 30 minutes ,
Default 5min
Turn this function on to activate Internal CH and 3-way valve pump testing.
Only works in installation mode. Turns off when in normal mode.
Range: 0~12 time, '0' OFF, Default: 4 time
Default OFF
The FT Series Wall Mounted, Combination Boiler
5.9 Outdoor Reset Adjustment
Outdoor Reset varies the control setpoint based on the outdoor temperature. The reset function works as shown in Figure ‘CH Outdoor Reset’. When the outdoor air temperature reaches 6:OH “high outdoor temperature setpoint”, the control point setting is adjusted to 17:cL “low boiler temperature setpoint”.
When the outdoor air temperature reaches 7:OL “low outdoor temperature setpoint” the control setpoint is adjusted to 16:cH “high boiler temperature”.
Default outdoor reset setpoint is 100°F (38°C)
The Outdoor Temperature Mode Icon on the display will flash if an Outdoor Sensor or 0-10 Volt is not connected to the appliance.
To check the CH Target Temperature while using
Outdoor Temperature Mode, press the button while the appliance is operational and the display panel is powered on.
Operating condition
CH Outdoor Reset
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp setpoint simultaneously.
5.10
External Set Point Temperature Control
A signal from a building management system may be connected to the appliance to enable remote control. This signal should be a 0-10 volt DC signal. When this input is enabled, a building control system can be used to control the set point temperature of the appliance.
The control interprets the 0-10 volt signal as follows; when the signal is between 0 and 1.5 volts, the appliance will be in standby mode, not firing.
When the signal rises above 1.5 volts, the appliance will ignite. As the signal continues to rise towards its maximum of 10 volts, the appliance will increase in set point temperature. Adjust 16:cH and 17:cL to set MIN and MAX boiler water temperatures respectively.
Connect a building management system or other auxiliary control signal to the terminals marked for this purpose on the appliance terminal block (shown in Piping Diagrams, this manual). Caution should be used to ensure that the 0-10 VOLT + connection does not become connected to ground.
Connect to terminal strip as outlined 4.17 Electrical Connections.
NOTE: 0 - 10VDC terminals may not be used for both outdoor reset and 0 - 10VDC temp setpoint simultaneously.
Page 61
Page 62
5.11 Error Mode
Indicate
Error ‘ Er : ’ will flash
Error Code
Display and Controller are communicating
Example
Er:11
Er:11
NOTE: When communication between the Control Display and the main controller is lost, the
will not be displayed.
Flashing
The FT Series Wall Mounted, Combination Boiler
Page 63
SECTION 6 Error Codes
6.1
Error Code Tables
Error
Code
10
11
16
20
28
32
33
Error Code Descrip tion
Flame has Extin
guished 8 (Eight)
Times
Ignition has Failed 10
(Ten) Times
Condensate – Closed is Normal, Open is
Fault (Condensate
Drain Trap)
-
Operating Temperature
Sensor detects Water
Temperature Greater than 203°F (95°C)
Overheat Sensor Open or Short
DHW Sensor Open or
Short
CH Temperature Sen
sor Open or Short
Possible Remedies
Recover methods
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is be
tween 3.5 and 14” WC.
2. Check gas valve wire. Ensure connection is secure.
3. Check flame detection sensor. Ensure connections are secure. Normal operating set
tings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check vent terminations. Ensure there are no blockages.
5. Assure that the flame is stable when lit.
6. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Monitor the gas pressure to the appliance while in operation. Ensure pressure is be
tween 3.5 and 14” WC.
2. Check gas valve wire. Ensure connection is secure.
3. Check flame detection sensor. Ensure connections are secure. Normal operating set
tings are more than 2.5DC before ignition, less than 2.5DC after ignition.
4. Check igniter transformer for proper connection.
5. Clean the spark igniter with steel wool to remove oxides. Ensure proper separation (3-4 mm).
6. Replace the spark igniter if damaged.
7. Assure that the flame is stable when lit.
8. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for normal operation.
2. Check if CH inlet pipe is blocked. Ensure there is enough water flowing to the appli
ance.
3. Check Operating Temperature sensor at CH heat exchanger outlet. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control
Press the Power button to clear the Error Code.
1. Check Condensate and main controller connections. Ensure all are secure.
2. Check Condensate sensor resistance. If resistance is zero, replace the switch.
3. Check Condensate hose. Ensure it is connected and in good condition.
4. Check condensate line and termination for blockages.
5. Check Vent Pipe for blockages.
6. If the problem persists, replace the main control.
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check overheat temperature sensor. Ensure connections are secure.
2. Check overheat sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
This Error Code will go away when outlet DHW temperature decreases.
If Error happens again:
1. Check DHW outlet temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
This Error Code will go away when CH temperature decreases.
If Error happens again:
1. Check CH temperature sensor. Ensure connections are secure.
2. Check CH sensor resistance. If resistance is zero, replace the sensor.
3. If the problem persists, replace the main control.
Hard
Lock
Hard
Lock
Hard
Lock
Hard
Lock
Soft Lock
Soft Lock
Soft Lock
Page 64
Error
Code
35
36
37
38
40
41
42
43
44
45
61
Error Code Description
Venting (Exhaust) Sensor
Open or Short
Abnormal Supply Voltage
Abnormal Supply Frequency
Possible Remedies
Recover methods
This Error Code will go away when exhaust temperature decreases.
If Error happens again:
1. Check Venting (exhaust) temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. Check vent pipes for blockage.
4. If the problem persists, replace the main control
Supply voltage is too low to operate. This Error Code will go away when supply voltage returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the requirements on the rating plate.
2. If problem persists, replace the main control
Supply frequency is too high to operate. This Error Code will go away when supply frequency returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the requirements on the rating plate.
2. If problem persists, replace the main control.
Soft Lock
Soft Lock
Soft Lock
Error Appears When Control
Stores Data, but Data is not
Saved
Press the Power button to clear the Error Code.
Replace the main control.
Hard Lock
Gas Leakage is Detected for
Greater than 5 seconds, or three times within 10 minutes
Fan Speed too High with
Flame On
LWCO Jumper disconnected
Burner Overheat Switch Open
Air Pressure Sensor (APS)
Fault
Air Pressure Sensor (APS)
Open
Fan Speed Feedback Signal
Abnormal
IMPORTANT: If you smell gas, STOP! Follow the instructions on page 2, this manual, and call a qualified service technician or the fuel gas utility.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the appliance cover. Ensure it is secure.
2. Check gas connections for leakage with a soapy solution. Fix any leaks.
3. Check condition of the burner assembly.
4. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the vent connections for blockages.
2. Check the burner assembly.
3. Check fan operation. If fan appears to be operating normally but RPMs are too high, replace the fan.
4. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Ensure the LWCO jumper wire is properly connected.
2. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check burner overheat switch connections. Ensure connections are secure.
2. Check switch resistance. If resistance is zero, replace the switch.
3. If the problem persists, replace the main control.
Press the power button to reset
If error happens again:
1. Check the vent pipe for blockages.
2. Check the vent pipe for blockages.
3. If error do not clear, replace the APS
4. If the problem persists, replace the main control.
Check the aps connection.
1.If APS is closed and connections are secure, check APS connection.
2. If the problem is not happen, replace the APS
3. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the connections to the fan. Ensure all are secure.
2. If the fan does not rotate during the ignition sequence, check for AC8V~26.5V power at the fan connection. If AC8V~26.5V power is present at the control, replace the fan. If the blower does not have AC8V~26.5V power, check power at the control. If
AC8V~26.5V power is not present at the control, replace the control.
3. If the problem persists, replace the main control.
Hard Lock
Hard Lock
Soft Lock
Hard Lock
Hard Lock
Soft Lock
Soft Lock
Error
Code
35
36
37
38
40
41
42
43
44
45
61
Error Code Description
Venting (Exhaust) Sensor
Open or Short
Abnormal Supply Voltage
Abnormal Supply Frequency
Possible Remedies
Recover methods
This Error Code will go away when exhaust temperature decreases.
If Error happens again:
1. Check Venting (exhaust) temperature sensor. Ensure connections are secure.
2. Check sensor resistance. If resistance is zero, replace the sensor.
3. Check vent pipes for blockage.
4. If the problem persists, replace the main control
Supply voltage is too low to operate. This Error Code will go away when supply voltage returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the requirements on the rating plate.
2. If problem persists, replace the main control
Supply frequency is too high to operate. This Error Code will go away when supply frequency returns to normal operating range.
If Error happens again:
1. Ensure appliance is properly wired to a power source meeting the requirements on the rating plate.
2. If problem persists, replace the main control.
Soft Lock
Soft Lock
Soft Lock
Error Appears When Control
Stores Data, but Data is not
Saved
Press the Power button to clear the Error Code.
Replace the main control.
Hard Lock
Gas Leakage is Detected for
Greater than 5 seconds, or three times within 10 minutes
Fan Speed too High with
Flame On
LWCO Jumper disconnected
Burner Overheat Switch Open
Air Pressure Sensor (APS)
Fault
Air Pressure Sensor (APS)
Open
Fan Speed Feedback Signal
Abnormal
IMPORTANT: If you smell gas, STOP! Follow the instructions on page 2, this manual, and call a qualified service technician or the fuel gas utility.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the appliance cover. Ensure it is secure.
2. Check gas connections for leakage with a soapy solution. Fix any leaks.
3. Check condition of the burner assembly.
4. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check the vent connections for blockages.
2. Check the burner assembly.
3. Check fan operation. If fan appears to be operating normally but RPMs are too high, replace the fan.
4. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Ensure the LWCO jumper wire is properly connected.
2. If the problem persists, replace the main control.
Press the Power button to clear the Error Code.
If Error happens again:
1. Check burner overheat switch connections. Ensure connections are secure.
2. Check switch resistance. If resistance is zero, replace the switch.
3. If the problem persists, replace the main control.
Press the power button to reset
If error happens again:
1. Check the vent pipe for blockages.
2. Check the vent pipe for blockages.
3. If error do not clear, replace the APS
4. If the problem persists, replace the main control.
Check the aps connection.
1.If APS is closed and connections are secure, check APS connection.
2. If the problem is not happen, replace the APS
3. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the connections to the fan. Ensure all are secure.
2. If the fan does not rotate during the ignition sequence, check for AC8V~26.5V power at the fan connection. If AC8V~26.5V power is present at the control, replace the fan. If the blower does not have AC8V~26.5V power, check power at the control. If
AC8V~26.5V power is not present at the control, replace the control.
3. If the problem persists, replace the main control.
Hard Lock
Hard Lock
Soft Lock
Hard Lock
Hard Lock
Soft Lock
Soft Lock
The FT Series Wall Mounted, Combination Boiler
SECTION 6. Error Codes
(continued)
Page 65
Error
Code
66
68
70
72
76
80
81
85
94
Error Code Description
Mixing Valve Initial Value
Error
(Mixing Valve Cannot Return to Initial Position)
Mixing Valve Operation Error
(Mixing Valve Stuck in Initial
Position)
Register, Ram, Rom, I/O
Port, AD Abnormal, Important
EPROM Data or Safe Data
Abnormal
Flame Signal Detected before
Ignition
Poor Communication
Low Water Level Sensor
(Low Water Level Detected
Four (4) Consecutive times)
Low Water Level Circuit
Freeze Protection
(Appliance has detected water temperature below
34°F(1°C)
Exhaust Sensor detects Vent
Temperature is Greater than
190oF (88oC)
Possible Remedies
Recover methods
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. Check wiring connections to mixing valve. Ensure all are secure.
3. Replace mixing valve.
4. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. Check wiring connections to mixing valve. Ensure all are secure.
3. Replace mixing valve.
4. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Turn power OFF and ON at the main power switch internal to the appliance.
2. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check the appliance cover. Ensure it is secure. Flame detection sensor can detect an external light source.
2. Check flame detection sensor. Ensure connections are secure. Normal operating settings are more than 2.5DC before ignition, less than 2.5DC after ignition.
3. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check connections from main control to display panel.
2. If the problem persists, replace the display and/or the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Ensure all valves are open to the appliance and there are no leaks.
2. Ensure all air has been purged from the system.
3. Check wiring connections to low water level sensor. Ensure all are secure.
4. Check low water level sensor resistance. If resistance is zero, replace the sensor.
5. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Ensure all valves are open to the appliance and there are no leaks.
2. Check wiring connections to low water level sensor. Ensure all are secure.
3. Check low water level sensor resistance. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control.
This Error Code will go away when the freezing condition is remedied.
If Error happens again:
1. Ensure appliance is located in a mechanical room protected from freezing conditions.
2. Ensure all valves are open to the appliance, there are no leaks.
2. Check wiring connections to low water level sensor. Ensure all are secure.
3. Check low water level sensor resistance. If resistance is zero, replace the sensor.
4. If the problem persists, replace the main control.
This Error Code will go away when the condition is remedied.
If Error happens again:
1. Check if dip switch Max Fire setting is ON. Switches 6 and 7 should be OFF for normal operation.
2. Check exhaust temperature sensor. Ensure connections are secure.
3. Check sensor resistance. If resistance is zero, replace the sensor.
4. Check exhaust vent for blockage.
5. If the problem persists, replace the control.
6. If the problem persists, replace the heat exchanger.
Soft Lock
Soft Lock
Soft Lock
Soft Lock
Soft Lock
Soft Lock
Soft Lock
Soft Lock
Soft Lock
Page 66
6.2 Fault Tree Analysis
1. Flame detection
The FT Series Wall Mounted, Combination Boiler
6.2 Fault Tree Analysis (cont)
2. Gas Detection
Page 67
3. ‘Storage’, ‘DHW’, ‘OP’, ‘CH overheat’, ‘Exhaust heat’ Sensor detects
Error code
E32
E33
E35 contents
DHW NTC open or short
OP NTC open or short
Exhaust NTC open or short
Page 68
SECTION 7
Trouble Shooting
7.1 Diagnostics
Question Answer
Make sure that the ON/OFF button on the Control Panel has been turned ON.
Burner does not ignite when the hot water is opened.
Water is not hot enough.
Water is too hot.
Hot water temperature fluctuates at the opened tap.
If the monitor on the Control Panel is blank, make sure the power cord is plugged and 4A fuses on the main controller in the units are good.
Make sure that there is water supplied to the unit. The unit activates once the inlet water flow is over 0 gpm.
Make sure the cold and hot water lines are not plumbed in reverse side.
Make sure that the cold water and gas supply lines are opened.
Make sure that the water lines are not frozen.
Check that the setting temperature on the unit is not too low
Make sure that the filter in the cold water supply line is not clogged with debris.
Make sure that the gas supply type is correct.
Check the supply and manifold gas pressures are in accordance with specifications.
Make sure that the water flow sensor with three wires has been properly connected on the top of heat exchanger.
Make sure that the setting temperature on the unit is not too hot.
Make sure that the filter in the cold water supply line is not clogged with debris.
Make sure that the gas supply type is correct.
Make sure that the filter in the cold water supply line is clean.
Make sure that the gas supply type is correct.
Check the supply gas pressure is sufficient.
The blower is still oper
ating after the combustion stops.
This is normal because the blower keeps operating for 1 minute to vent
(exhaust) the flue gas from the chamber once the combustion has stopped.
Temperature Rise too Quickly tion.
DHW flow is initiated
Abnormal sounds come from unit during opera-
Heater doesn’t fire when
CH Temp drops lower than expected before unit re-fires
Occurs when supply water temperature in heat exchanger rises faster than
2°F per second during the first two minutes the burner is on. Automatically resets after a few minute delay or using manual reset on control panel. See message displayed TEMPERATURE SENSOR and follow procedure for loose connections.
A leak of combustion gas between sealed chamber and exhaust tube inside the unit. Call a qualified service technician for evaluation.
Improper venting termination, make sure that the venting termination com
plies with specification.
Check the supply gas pressure is sufficient. Insufficient gas pressure will cause unstable burner flame and noise.
Potentially the domestic water flow is too low. Min allowable is 0.75 gpm.
Check in Manual Mode OTO AGA
Change Parameter 14:bo to 10degrees F (5.5 degrees C)
The FT Series Wall Mounted, Combination Boiler
Page 69
7.2
Suggested Corrective Actions
This controller is able to record information about the boiler’s condition at the time of the five previous faults or errors. Refer to the Section ‘5.10 Error Mode’ of this manual.
Display
Nothing shown on display control panel and blower running at full speed.
Condition
Control is not receiving power.
Diagnostic
Check wiring for short circuit or incorrect wiring.
Check transformer connection to the control per wiring diagram. Check for 12V output of transformer.
Check service switch and/or circuit breaker to boiler turned is on.
Corrective Action(s)
Correct wiring per wiring diagram including connection of transformer to the control.
Replace transformer if it is receiving
120V, but not outputting 12Vac.
Turn on service switch to power boiler.
Nothing is shown in display control panel and no other boiler components are operating.
Control is not receiving 120V power.
Nothing is shown on control panel, but boiler is operating.
Occurs when the communication is lost from the control to the display.
Is there 120 Volts at the service switch?
Is the ON/OFF
POWER
SWITCH (inside boiler case) turned on?
Check for 120 volts at the line voltage terminal block located inside the boiler case.
Troubleshoot and correct the power supply to the manual switch.
Turn ON the manual power switch inside the boiler case.
Correct wiring inside the boiler case using the wiring diagram in this manual.
Inspect the fuse.
Replace if necessary.
Check for loose connections and proper pin alignment/ engagement on the
Control's plug.
Cycle power off and on using boiler power switch and check for operation.
Replace the fuse with proper part found in the replacement part section of this manual. If fuse blows again recheck wiring per diagram.
Check for continuity on the wire harness from the display to the control.
See repair parts section for proper replacement part.
Replace with new display module.
See repair parts section for proper replacement part.
Page 70
Fault
TEMPERATURE
SENSOR
FLAME FAULT
BLOWER FAULT
IGNITION
FAULT
GAS VALVE
FAULT
Condition
Occurs when a temperature sensor has electrically shorted
(SHORT) or has become disconnected
(OPEN).
Diagnostic
Reset using manual reset screen on control panel. (Power button)
Corrective Action(s)
Check all the temperature readings of the boiler on the DIAGNOSTICS -
TEMPERATURES menu to determine if any sensors are currently displayed as SHORT or OPEN.
Check wire harness for loose connections and pin engagement at sensor Connection and Control module.
If problem persists after checking items above replace Control. Refer to repair parts section for kit number.
Occurs when flame is detected when there should be no flame.
Blower unable to reach required speed or does not reach 0
RPM when turned off.
Even if boiler went through
8 ignitron attempts, but cannot detect flame
The Control has detected a problem with it gas valve output circuit.
Reset using manual reset screen on control panel.
(Power button)
Reset using manual reset screen on control panel.
(Power button)
Power off and on.
Reset using manual reset screen on control panel.
(Power button)
Burner may be operating too hot due to incorrect combustion. Inspect flame and conduct combustion test.
Check for flame at burner via flame current with burner off. Turn boiler off and watch flame through observation port. If flame continues after shutdown replace gas valve.
Check wire harness for loose connections and pin engagement at blower.
Connections.
Boiler in standby mode and blower not running. If BLOWER SPEED is not 0
RPM then replace blower.
If blower does not rotate during ignition sequence check for 120V power at blower connection. If 120Vac power at blower motor and it doesn't start replace blower. Check power at
Control. If 120Vac is not present at
Control when boiler is powered replace
Control.
Dirty burner and/or heat exchanger will cause high back pressure and poor ignition.
Visual inspection of flue ways often will not be able to diagnose condition.
Check incoming gas pressure with boiler off and at Max fire. Adjust within limits on rating label.
Check for flue pipe and intake pipe restrictions or blockage
Check burner fasteners and gaskets
Check air intake pipe and proper propane orifice
Check wire harness connections between gas valve and Control.
If lockout re-occurs replace Control.
The FT Series Wall Mounted, Combination Boiler
Page 71
SECTION 8 Maintenance
8.1
Annual startup &
general maintenance
Regular Maintenance
- This Manual should be placed in a safe and dry location near the Combination boiler. Maintenance instructions should be carried out by the following guidelines.
Maintenance procedures [ Daily ]
- Check the power source .
Make sure that the power cord is correctly connected. The main power line is connected to the manual switch box inside a combination boiler.
(Power line through the strain relief in the bottom of the combination boiler casing and fix it.)
- Check the status of the control panel
Check status of the power supply. Please check for any debris on the button.
- Check that the boiler casing is closed.
Check if there is any problem with the Combination boiler casing and the two upper and lower screws are tightened well. Combination boiler casing must be closed while it is running.
WARNING
To prevent potential severe personal injury, death or substantial property damage, remove all contaminated materials.
If contaminants are found:
Remove products immediately from the area.
In order to check the status of Combination boiler, call a qualified service technician to inspect the combination boiler for possible damage from acid corrosion.
WARNING
DO NOT store combustible materials, gasoline or any other flammable vapors or liquids near the water heater. Remove them immediately or store them other places.
Maintenance procedures [ Monthly ]
- Check the vent pipe.
Visually inspect the flue gas vent piping for detecting any signs of blockage, leakage or deterioration of the piping. Please contact a qualified service technician immediately if you find any problem.
- Check the air inlet pipe.
Visually inspect the air inlet to be sure it is unobstructed. Inspect entire length of air piping for ensuring that piping is intact and all joints are properly sealed. Call your qualified service technician if you notice any problems.
- Check the relief valve.
Inspect the Combination boiler relief valve and the relief valve discharge pipe for any signs of weeping or leakage. If the relief valve often weeps, immediately contact your qualified service technician for inspecting the Combination boiler and system.
- Check the condensate outlet.
While the Combination boiler is running, check the discharge end of the condensate drain tubing.
Make sure that no flue gas is escaping from the condensate drain tubing.
If flue gas is continuously escaping, it is a serious problem. Call your qualified service technician for inspecting the Combination boiler and condensate line. Also, refill the condensate trap if problem persists regularly.
-
Check the vent terminal screen vent
(rodent screen).
If you encounter a problem of combustion specifications, visually inspect the terminal screen.
And then replace it with spare parts or clean the screens.
Page 72
- Check the air vent
If the air vent valve seems to work freely without leaking, replace cap “A” by twisting all the way on.
Loosen cap “A” one turn to allow vent to operate.
If vent does not operate correctly, replace the vent.
seat. If the valve continues to weep, contact your qualified service technician for inspecting the valve and system. If water does not flow from the valve even though you have lifted the lever completely, the valve or discharge line may be blocked. Shut down the Combination boiler immediately. Call your qualified service technician to inspect the combination boiler and system.
- Check the burner state
You can clean the exterior of burner. However, if you need to clean the inside of the burner stage, you should call a qualified service technician.
Maintenance procedures [Every 6 Months]
- Check the boiler piping (gas and water)
Visually inspect for leaks around internal water piping. Also inspect external water piping, circulators, relief valve and fittings. Immediately call a qualified service technician to repair any leaks. Leaks must be fixed by a qualified service technician immediately.
Failure to comply with this instruction could result in severe personal injury, death or substantial property damage.
- Check the pressure relief valve
WARNING
Leaks must be fixed by a qualified service technician immediately. Failure to comply with this instruction could result in severe personal injury, death or sub
stantial property damage. This discharge line must be installed by a qualified heating installer or a service technician.
Before proceeding, verify that relief valve outlet has been piped to a safe place of discharge, avoiding any possibility of scalding from hot water. If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve
The FT Series Wall Mounted, Combination Boiler
Page 73
8.2
Flushing the Combination Boiler
Flushing the Heat Exchanger is a complicated procedure that should only be done by an authorized technician or licensed professional. Keep in mind that improper maintenance can void your warranty.
V3
V1
V4 V2
1. Disconnect electric power to the combination boiler.
2. Close the shutoff valves on both hot water outlet and cold water inlet lines. (V1 & V2)
3. Connect one hose “D1” to the valve “V3” and place the free end in the bucket. Connect one of the hoses “D3” to the circulation pump outlet and the cold water inlet line at the valve “V4”. Connect other hose “D2” to the circulation pump inlet and place the free end in the bucket.
4. Pour the cleaning solution into the bucket. Place the drain hose
(D1) and the hose (D2) to the pump inlet into the cleaning solution.
5. Open service valves (V3 & V4) on the hot water outlet and cold water inlet lines.
6. Turn on the circulation pump (Operate the pump and allow the cleaning solution to circulate through the combination boiler for at least 1 hour at a rate of 4 gallons per minute.)
7. Rinse the cleaning solution from the combination boiler as follows:
- Remove the free end of the drain hose (D1) from the bucket.
- Close service valve, (V4), and open shut off valve,
(V2).
Do not open shut off valve, (V1).
- Allow water to flow through the combination boiler for
5 minutes.
- Close shut off valve (V2).
D1
D2
8. Disconnect all hoses.
9. Remove the cold water inlet filter from the combination boiler and clean out any residues.
10. Reinsert the filter and ensure the filter cap is securely tightened.
11. Connect electrical power to the combination boiler.
D3
Page 74
8.3 Draining and Cleaning
Flow Restrictor
Cold Water
Inlet Filter
CH Return Filter
FTCW
140
FTCW
199
1. Place a bucket under the appliance to collect the residual water inside the combination boiler.
2. Press the Power button on the front control panel to turn OFF the electrical power to the combination boiler.
3. Turn off the gas valve.
4. Close water supply valve on the inlet to the appliance. If there is no valve, turn off main water valve.
5. Open the hot water faucets completely.
6. Remove the CH (Central Heat) return filter by removing the metal pin and then pulling the filter downward.
7. Remove the Cold Water Inlet filter by removing the two small pins and then pulling the filter downward at an angle. If your system is using a flow restrictor, be sure that the flow restrictor is also cleaned and placed back into the system during re-assembly.
8. Clean them with a toothbrush and clean running water.
9. To refill the combination boiler, reassemble the filters back into the combination boiler and reverse steps 7 back to 1.
8.4 Freeze Protection
FT Series Boilers are certified for indoor use only, and are not design-certified for placement outdoors.
Proper precautions for freeze protection are recommended for boiler installations in areas where the danger of freezing exists.
Power outage, interruption of gas supply, failure of system components, activation of safety devices, etc., may prevent a boiler from firing. Any time a boiler is subjected to freezing conditions, and the boiler is not able to fire, and/or the water is not able to circulate, there is a risk of freezing in the boiler or in the pipes in the system.
When water freezes, it expands which may result in bursting of pipes, or damage to the boiler, which could result in leaking or flooding conditions.
NOTICE
Different glycol products may provide varying degrees of protection. Glycol products must be maintained properly in a heating system, or they may become ineffective. Consult the glycol specifications, or the glycol manufacturer, for information about specific products, maintenance of solutions, and set up according to your particular conditions.
NOTICE
Not all pumps are capable of maintaining the reduced temperature rise required with glycol concentrations greater than 35%.
The FT Series Wall Mounted, Combination Boiler
Page 75
Freeze Protection (continued)
WARNING
SECTION 9 Installation Check
9.1 Quick View
Do NOT use automotive antifreeze or ethylene glycol. Use only inhibited propylene glycol solutions which are specially formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets, seals, and metallic components used in hydronic systems. A correct glycol concentration and inhibitor level is critical.
Before Installing
- Make sure that there is enough space for installing
Water and gas line.
Verify vent/air termination is located as required.
- All models need for propane Conversion which requires a separate gas conversion manual.
Some items to consider are
• Consider the effects of reduced heat transfer and an increase in head pressure against the system circulator. For example: A 30% mixture of glycol will result in a BTU output loss of 15% with a 5% increase in head against the system circulator.
• Glycol mixtures should not exceed 50%. A 50% mixture of glycol will result in a BTU output loss of
30% with a 50% increase in head against the system circulator.
Install Water Piping
- Boiler loop piping must be sized to the minimums listed in the Boiler manual. Using smaller piping will cause performance problems.(page 34)
Install Vent & Air Piping
- Slide the air inlet pipe and vent pipe into the Boiler pipe connector.
- Make sure the terminations are placed as required in the manual and that air intakes are at least 12 inches above normal snow line.
- Refer to the material check list in this guide for a list of items needed.
Install Condensate Piping / Tubing & Components
- Fill out the material check list in this guide to ensure you have the tubing or PVC pipe and all components needed for the condensate piping.
- Connect internal components that are supplied with the Boiler.
• The glycol solution should be tested as recommended by the glycol manufacturer but not less than annually.
Some items of concern are pH additive breakdown, inhibitor reduction, etc.
• Glycol/antifreeze solutions expand more than water; therefore, system design must take this into account.
For example: a 50% by volume solution expands
4.8% in volume for a temperature increase from 32◦F to 180◦F, while water expands 3% over the same temperature rise.
Install Gas Piping
- Install a union and shutoff valve.
CAUTION
It is highly recommended to follow the manufacturers recommended concentrations, expansion requirements, and maintenance recommendations. You must carefully calculate the additional friction loss in the system as well as the reduction in the heat transfer coefficients.
__________________________________________
Wire the Boiler
- Connect power wiring and control wiring per boiler manual wiring diagram.(Section 4.19)
Start up, Adjust & Test
- Follow the Boiler manual instructions to clean the system if needed, then fill and check water chemistry.
Page 76
9.2 Final Check Lists
Final check : Installation Conditions.
• Is the Boiler properly mounted on the wall?
• Is there space for a drain which is close to the
Boiler?
• Are there any combustible materials near the Boiler and vent pipe?
• Is the air supply sufficient for proper operation of the Boiler?
• Are the proper service clearances maintained?
• Is the distance between the Boiler and point of vent termination minimized?
• Is the proper distance from windows, doors, and other intake vents maintained?
Final check : Gas pipe installation
• Is the gas supply line equipped with a manual shut off valve?
• Is the gas supply line a minimum of 3/4˝ inner diameter?
• Is the gas supply line length and diameter adequate to deliver the required BTU’s?
• Has the gas supply line pressure been measured?
• Does the supply gas type match the type indicated on the boiler rating plate?
Final check: Air/Vent pipe installation
• Has the Boiler been vented with 3˝ or 2” PVC,
CPVC, Polypropylene or BH Special
Gas Vent (S636 PVC, CPVC) for Category IV appliances in accordance with this manual and/or your local code?
• Is the vent termination at least 12˝ above the exterior grade?
• Is the total vent length within the maximum vent length restriction?
• Have you checked the air/vent piping for leaks?
• Have you properly supported the vent termination?
• Are all vent runs properly supported?
• Is the vent sloped upward toward the vent termination at a rate of 1/4˝ per foot (2% grade)?
Final check : Condensate drain installation
• Have you installed a condensate drain line from the
Boiler to a drain or laundry tub?
Final check : Setting the DIP switches
• Are all DIP switches correctly set on the main board?
Final check : Connecting the power supply
• Please check that the power is 120V AC.
• Have you checked the polarity of the electrical connection?
Final check : Pressure relief valve
• Have you installed an approved pressure relief valve on the boiler?
• Is the pressure relief valve of CH Plumbing at least
1˝ in diameter?
• Is the pressure relief valve of DHW Plumbing at least
3/4˝ in diameter?
• Have you installed the pressure relief valve on the hot water outlet pipe near the Boiler?
Final check : Burner flames
• The burner flame must be checked periodically for a constant proper blue color.
• If the flame does not appear normal, the burner may need to be cleaned.
If the burner needs to be cleaned, it must be performed by a qualified service technician.
Sight Glass
Blue flame
Casing _
Feature
Casing _
Feature
Mascot FT Combination Boiler
SECTION 10 Parts List and Illustrations
FTCW
140
Page 77
Casing _
Feature
FT1894 Mounting Bracket
Casing _
List
No.
33
34
35
36
37
28
29
30
24
25
26
27
31
32
21
22
23
18
19
20
15-6
15-7
16
16-1
16-2
17
O-7
15
15-1
15-2
15-3
15-4
15-5
Description
Part
Number
O-Ring P7
Exhaust vent duct Assembly
Stainless band (Ø100)
Packing
Exhaust vent duct
Exhaust testing cap
O-Ring P85
Exhaust vent adaptor (Inside)
O-Ring P75
Air inlet duct Assembly
Air inlet duct
Air inlet adaptor (Inside)
Air vent
Air vent rubber packing
Gasket bracket
Safety valve rubber pad
Air pressure sensor (80)
PCB Control (NGTX-900CP)
Ignition transformer
Control sub-bracket
Display Control (P-920C)
FT1954
FT1620
Bracket FT1511
Condensate blockage, Air press switch FT1022
Control bracket
Power switch
Terminal block (10P)
Front cover
Control display cover / window
FT1922
FT1020
FT1021
FT1923
FT1024
FT1612
FT1321
FT1013
FT1797
FT1921
FT1804
FT1899
ST1006
FT1601
FT1002
FT1603
FT1604
FT1611
FT1606
FT1607
FT1608
FT1609
FT1010
FT1605
FT1025 Pressure gauge
Intake/Exhaust sealing pad
Wall Mount bracket (top)
Casing Assembly
Wall Mount bracket (bottom)
FT1771
FT1924
N / A
FT1936
KRB
Code
S322100020
S551100045
H140320030
S551100063
S264100067
S115900025
S223100036
H850150051
S121110029
H120900014
S264100062
H120900013
S264100057
S900140007
H110130132
H850150050
S552200045
H190200003
S453100002
S552100064
S549100119
H850150049
S552200070
S549100121
S552200069
H190200002
S549100120
S529100025
S325100028
S555100029
H140120024
H110330070
H120900017
Price
Mascot FT Combination Boiler
CH Block & DHW Block Ass’y_
Feature
FTCW
140
H190200003
H190200002
15
16
FT1002
FT1010
CASING
Exhaust Duct Assembly
Air Intake Duct Assembly
S115900025
S264100065
S223100028
S122100010
S900140007
S264100062
18
19
20
23
25
FT1014
FT1015
FT1016
FT1019
FT1021
Control
Air pressure switch
26
FT1022
Ignition transformer
0-22A
Display Panel
Terminal Block
Condensate Blockage, Air Pressure switch
Display cover window
H850150050 28
FT1024
S325100028
S489100248
H199990175
S419100042
29
31
A1
33
FT1025
FT1027
0-22A
FT1100
FT1517
Pressure gauge
DHW Hydro block Assembly
DHW Outlet Pipe
0-22A
S514100107
S311200029
S419100041
S317100009
S193000001
S549100150
35
36
38
39
40
43
FT1519
FT1112
FT1521
FT1115
FT1116
FT1119
DHW nipple
Outlet sensor
Flow sensor
Mixing valve
Flow restrictor CH Assembly
S549100145
S549100141
S514100105
44
45
FT1120
FT1121
FT1122
DHW filter mash
DHW filter Cap
47
A2 FT1200
DHW connector
CH hydro Block Assembly
H199990176
S419100040
S311200030
S549100155
S419100039
55
56
57
FT1526
FT1219
FT1220
CH return pipe
58
FT1527
CH return sensor
3-way valve
H160320029 FT1222
S549100166
H140240002
S311200027
59
60
62
63
64
FT1304
FT1306
FT1307
FT1068
Pump
HEAT EXCHANGER ASSEMBLY
Exhaust Pipe
Exhaust sensor BK
Exhaust overheat sensor
Heat Exchanger Assembly
H130120199
S311400021
S311400021
65
FT1309
65-1
FT1310
Over heat Sensor
H130210023
S333100033
S554100041
S322100020
S419100038
65-4
65-6
65-7
65-8
68
FT1313
FT1315
FT1316
FT1665
FT1321
Burner
Igniter
Ignitor gasket
Refractory
Air vent
69
FT1322 CH supply upper pipe
DHW tank
H120420007
S311200026
S312100011
S314200007
S549100134
S421200030
S514100108
70
71
72
74
75
76
FT1323
FT1324
FT1325
FT1327
FT1328
FT1329
Flame detector sensor
Condensate trap
Condensate trap hose
H160510020
S242100058
S549100132
S551200026
S345100008
S551200001
77
83
83-1
83-2
83-3
85
85
86_1
86_2
FT1330
FT1405
FT1406
FT1409
FT1716
FT1412N
FT1412P
FT1728
FT1415
Temperature sensor
Low level sensor
Condensate trap connector
BLOWER & GAS VALVE
Blower Assembly
Blower
Housing, Gas Mixer
O-Ring, Fan Sealing
Orifice (natural)
Orifice (propane)
Gas valve outlet adaptor
Gas valve O-Ring
FT1416 Gas valve
86_3
S412190040
S349100039
86_4
86_5
87
88
FT1538
FT1418
FT1419
FT1420
Gas valve inlet adaptor
Gas valve BK
Gas pipe (down)
Gas inlet adaptor
Initials Date
Status
‘B2’ - CH Block Ass’y_
List
Page 80
No.
P-6
54
55
56
13
14
53
57
B2
O-20
O-22
O-22A
O-25
P-5
58
59
60
61
62
63
CH Assembly
Description
CH Hydro block Assembly
O-Ring P20
O-Ring P22
O-Ring P22A
O-Ring P25
3/4" Packing
1" Packing
Piping clip
Pump clip
Block cap
Return block
R Clip
CH Return, Supply connector
CH Filter
U Clip
CH Return pipe
CH Return sensor
3-way valve
CH Supply pipe
Pump
Part
Number
FT1100
FT1513
FT1644
H199990175
S551200033
S551200034
FT1515 S551200035
FT1516 S551200036
FT1646
FT1691
‘B3’ - DHW Block Ass’y_
List
FT1107 S455100095
FT1108
FT1121
FT1523
FT1524
FT1215
FT1216
FT1217
FT1218
FT1219
FT1220
S455100096
S549100141 DHW Assembly
S549100140
No. Description
S514100106
S549100142
O-15 O-Ring P15
S455100106
O-16 O-Ring P16
S419100040
S311200030
S549100155
Part
Number
FT1200
FT1685
FT1643
FT1687
FT1513
KRB
Code
H199990176
S551200027
S551200028
S551200029
S551200033
FT1515 S551200035
FT1527
FT1222
S419100039
H160320029 FT1645 S551100046
12 Flow sensor clip FT1208 S455100069
45
46
47
48
49
50
51
52
13
40
41
42
43
44
KRB
Code
Price
Piping clip
DHW Outlet pipe
DHW Outer block
DHW Nipple
DHW Temperature sensor
DHW Inlet pipe
Flow sensor
Mixing valve
DHW Inlet block
DHW Filter body
Flow restrictor (12L)
DHW Filter mesh
Block cap
DHW Connector
FT1107
FT1109
FT1518
FT1111
FT1112
FT1114
FT1115
FT1116
FT1522
FT1549
FT1119
FT1120
FT1121
FT1122
S455100095
S419100042
S549100147
S514100107
S311200029
S419100041
S317100009
S193000001
S549100146
S549100143
S549100149
S549100145
S549100141
S514100105
Price
Heat Exchanger & Tank _
Feature
FTCW
140
Heat Exchanger & Tank
Page 81
No.
77
78
79
74
75
76
69-3
69-4
69-5
69-7
69-8
69-9
69-10
70
71
72
73
O-22
66
67
68
69
69-1
69-2
P-5
P-6
64
65
Heat Exchanger & Tank _
List
FTCW
140
Heat Exchanger & Tank
Description
Part
Number
O-Ring P22 FT1644
3/4" Packing
1" Packing
EX-Adaptor
Exhaust pipe
FT1646
FT1691
FT1784
FT1067
Exhaust sensor bracket FT1529
Exhaust overheat sensor FT1307
Exhaust pipe packing (lower) FT1666
Heat Exchanger Assembly
Burner Assembly
FT1313
FT1925
Overheat sensor FT1310
Burner upper case
Burner packing
Burner
Ignition rod
Ignition rod gasket
Burner downside case
Refractory
Stainless band (Ø150)
DHW Tank bracket
DHW Tank
CH Supply upper pipe
FT1926
FT1927
FT1314
FT1315
FT1316
FT1928
FT1665
FT1528
FT1530
FT1323
FT1322
Temperature sensor FT1324
Low level sensor FT1325
Flame detector sensor bracket FT1669
Flame detector sensor FT1327
Flame detector sensor cover FT1069
Condensate trap Assembly FT1783
KRB
Code
S551200034
S551100004
S551100005
S549100223
S549100148
H140240002
S311200027
S552100054
H120240461
H130120301
S311400021
H870060125
S551100083
H130210023
S333100033
S554200007
H870060126
S562200107
S453100015
H120900012
H120420007
S419100038
S311200026
S312100011
H850130001
S314200007
H140240003
H160520005
Price
Fan & Gas Valve _
Feature
FTCW
140
Blower and Gas Valve
Page 83
No.
82
83
84
85
86
86-1
86-2
86-3
86-4
87
88
89
90
91
92
92-1
92-2
92-3
92-4
92-5
93
94
95
Fan & Gas Valve _
List
Page 84
LAARS Heating Systems
FTCW
140
Blower and Gas Valve
Description
Part
Number
KRB
Code
Price
Fan guide FT1532
Fan rubber packing (1.0t) FT1721
Mash FT1720
Fan rubber packing (1.6t) FT1082
Fan Assembly FT1407
Fan FT1406
Fan sealing O-Ring ST1038
Gas mixer housing FT1409
Intake orifice (140K)
Stainless band (Ø60)
Air intake hose (120,140K) FT1533
Nylon Barb Y Fitting
Nozzle (Natural/140K)
FT1535
FT1078
FT1918
FT1412N
Nozzle (Propane/140K) FT1412P
Gas pipe (upper) FT1536
H870060054
S551100047
H140140003
S551100071
H160510059
S242100047
S551200026
S549100132
H160620001
S455100088
S421200052
H850150151
H130010019
H130010020
S412190039
Gas valve Assembly FT1413 H160430012
Gas valve outlet adaptor FT1919
Gas valve O-Ring
Gas valve
Gas valve inlet adaptor
Gas valve bracket
1/2" Spiral packing
Gas pipe(down)
Gas inlet adaptor
H870060055
FT1727
FT1416
FT1538
FT1539
FT1710
FT1419
Optional Item_
S345100010
H120900018
S557100001
S412190040
List
FT1893 No. H870060074 Description
Part
Number
100
101
102
104
105
106
107
108
109
110
111
112
113
114
Pressure Relief Valve FT1500
Outdoor Temp. Sensor
Bird Screen 3"
FT1501
FT1730
Spare Parts Kit FT1930
Condensate Hose
Restrictor (12L)
Wall Hung Bracket
Bird Screen 2"
ST1070
FT1506
FT1894
FT1508
Nozzle LNG 7.1 (3,000~10,000ft) FT1931
Nozzle LNG 5.0 (3,000~6,500ft) FT1932
Nozzle LNG 5.1 (6,500~10,000ft) FT1933
Nozzle LNG 6.2 (3,000~10,000ft) FT1934
Nozzle LNG 4.8 (3,000~10,000ft) FT1935
Wire Harness FT1903
KRB
Code
S323100096
S319300014
S114200020
H990050017
S421200027
S549100150
H140120025
S114200021
H130010024
H130010027
H130010026
H130010025
H130010028
S274400012
Price
Casing _
Feature
The FT Series Wall Mounted, Combination Boiler
FTCW
199
Page 85
27
32
33
34
35
28
29
30
31
36
37
No.
O-7
15
15_1
15_2
15_3
15_4
15_5
15_6
15_7
16
16_1
17
22
23
24
25
26
18
19
20
21
Casing _
List
FTCW
199
Description
O-Ring P7
Exhaust vent duct Assembly
Stainless band (Ø100)
Packing
Exhaust vent duct
Exhaust testing cap
O-Ring P85
Exhaust vent adaptor (Inside)
O-Ring P75
Air inlet duct Assembly
Air inlet duct
Air vent
Air vent rubber packing
Gasket bracket
Safety valve rubber pad
Air pressure sensor (80)
Control bracket
Ignition transformer
Control sub-bracket
Display Control (P-920C)
Bracket
Condensate blockage, Air pressure switch
PCB Control (NGTX-900CP)
Power switch
Terminal block (6P)
Front cover
Control display cover / window
Pressure gauge
Intake/exhaust sealing pad
Wall hung bracket (top)
Wall Mount Bracket
Wall hung bracket (bottom)
FT1022
FT1899
FT1020
FT1827
FT1920
FT1024
FT1025
FT1771
FT1924
FT1894
FT1936
Part
Number
FT1601
FT1002
FT1603
FT1604
FT1611
FT1606
FT1607
FT1608
FT1609
FT1909
FT1605
FT1321
FT1013
FT1797
FT1921
FT1804
FT1751
ST1006
FT1752
FT1620
FT1795
R2080604
CH Block & DHW Block Ass’y_
Page 87
Feature
FTCW
199
CH Assembly B2
‘B2’
CH Block
Ass’y
Packing
Sensor
‘B3’
DHW Block
Ass’y
DHW Assembly B3
Page 88
61
62
63
57
58
59
60
53
54
55
56
P-5
P-6
13
14
‘B2’ - CH Block Ass’y_
List
CH Assembly B2
No. Description
Part
Number
Notes
B2
O-20
CH Hydro block Assembly
O-Ring P20
O-22 O-Ring P22
O-22A O-Ring P22A
O-25 O-Ring P25
FT1937
FT1513
FT1644
FT1515
FT1516
3/4" Packing
1" Packing
Piping clip
Pump clip
Block cap
Return block
R Clip
CH Return, Supply connector
CH Filter
U Clip
CH Return pipe
CH Return sensor
3way valve
CH Supply pipe
Pump
FT1646
FT1691
FT1107
FT1108
FT1121
FT1523
FT1524
FT1215
FT1216
FT1217
FT1807
FT1219
FT1220
FT1808
FT1798
‘B3’ - DHW Block Ass’y_
List
DHW Assembly B3
No.
B3
Description
DHW Hydro block Assembly
Part
Number
FT1938
Notes
O-15
O-16
O-18
O-Ring P15
O-Ring P16
O-Ring P18
FT1685
FT1643
FT1687
46
47
48
42
43
44
45
49
50
51
52
O-20 O-Ring P20
O-22A O-Ring P22A
P-5 3/4" Packing
12
13
40
41
Flow sensor clip
Piping clip
DHW Outlet Pipe
DHW Outer block
DHW Nipple
DHW Temperature sensor
DHW Inlet pipe
Flow sensor
Mixing valve
DHW Inlet block
DHW Filter body
Flow restrictor
DHW Filter mesh
Block cap
DHW Connector
FT1111
FT1112
FT1806
FT1115
FT1116
FT1522
FT1549
FT1513
FT1515
FT1646
FT1208
FT1107
FT1805
FT1518
FT1822
FT1120
FT1121
FT1122
The FT Series Wall Mounted, Combination Boiler
Heat Exchanger & Tank _
Feature
Heat Exchanger & Tank
Feature
Page 89
Page 90
Heat Exchanger & Tank _
List
No.
66
67
68
69
O-22
P-5
P-6
65
70
70-1
70-2
70-3
77
78
79
80
73
74
75
76
70-4
70-5
70-6
70-7
70-8
70-9
71
72
Description
O-Ring P22
3/4" Packing
1" Packing
Exhaust pipe
Exhaust sensor bracket
EX-Adaptor
Exhaust overheat sensor
Exhaust pipe packing (lower)
Heat Exchanger Assembly
Burner Assembly
Burner upper case
Burner packing
Burner
Ignition rod
Ignition rod gasket
Overheat sensor
Burner downside case
Refractory
Stainless band (Ø165)
DHW Tank bracket
DHW Tank
CH Supply upper pipe
Temperature sensor
Low level sensor
Flame detector sensor bracket
Flame detector sensor
Flame detector sensor cover
Condensate trap Assembly
Part
Number
FT1644
FT1646
FT1691
FT1823
FT1529
FT1784
FT1307
FT1836
FT1992
FT1796
FT1760
FT1824
FT1762
FT1763
FT1316
FT1310
FT1764
FT1826
FT1813
FT1793
FT1794
FT1809
FT1324
FT1325
FT1669
FT1327
FT1069
FT1783
Notes
Fan & Gas Valve _
List
No.
89
90
91
92
92-1
92-2
92-3
92-4
93
94
86
87
87-1
87-2
82
83
84
85
87-3
87-4
87-5
88
95
96
97
Description
Fan guide
Damper packing
Damper body
Fan rubber packing (1.6t)
Fan guide packing
Fan Assembly
Fan
Fan sealing O-Ring
AGM Venturi
AGM O-Ring
AGM Body
Stainless band (Ø100)
Air intake hose
Nylon Barb Y Fitting
Stainless band(Ø89)
Gas valve Assembly
Gas valve outlet adaptor
Gas valve O-ring
Gas valve
Gas valve bracket
1/2" Spiral packing
Nozzle (natural)
Nozzle (propane)
Gas pipe (upper)
Gas pipe (down)
Gas inlet adaptor
Part
Number
FT1769
FT1770
FT1915
FT1082
FT1772
FT1916
FT1406
ST1038
FT1917
FT1774
FT1775
FT1603
FT1812
FT1918
FT1777
FT1778
FT1919
FT1727
FT1416
FT1779
FT1710
FT1780
FT1802
FT1810
FT1811
FT1893
Notes
The FT Series Wall Mounted, Combination Boiler
Fan & Gas Valve _
Feature
Feature
Page 91
Page 92
Notes:
For Product and
Service V
IDEOS
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
20 Industrial Way, Rochester, NH, USA 03867
20-01 Document 1318G
advertisement
Related manuals
advertisement