Burkert 8696 Quick Start Manual
The Burkert 8696 electropneumatic position controller precisely positions pneumatically actuated control valves in process automation. The device is suitable for controlling single-acting actuators and features automatic adjustment, extensive diagnostics, and safety position functions. Its robust design, compact size, and compatibility with various communication options make it ideal for demanding industrial applications.
विज्ञापन
विज्ञापन
Type 8696
Positioner TopControl Basic
Electropneumatic Position Controller
Elektropneumatischer Stellungsregler
Positionneur électropneumatiques
Quickstart
English Deutsch Français
We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous réserve de modifications techniques.
© Bürkert Werke GmbH & Co. KG, 2007 - 2017
Quickstart 1 805 /07_EU-ML_00805654 / Original DE
Type 8696
Table of Contents
1 QUICKSTART ........................................................................ 4
1.1 Definition of term / abbreviation .................................. 4
1.2 Symbols ....................................................................... 4
2 AUTHORIZED USE ............................................................... 5
3 BASIC SAFETY INSTRUCTIONS .......................................... 5
4 GENERAL INFORMATION .................................................... 7
4.1 Contact address .......................................................... 7
4.2 Warranty ...................................................................... 7
4.3 Information on the internet .......................................... 7
5 SYSTEM DESCRIPTION ....................................................... 7
5.1 Structure and function ................................................. 7
5.2 Model for control of third-party devices ...................... 8
6 TECHNICAL DATA ................................................................. 9
6.1 Conformity ................................................................... 9
6.2 Standards .................................................................... 9
6.3 Licenses ...................................................................... 9
6.4 Operating conditions ................................................... 9
6.5 Mechanical data ........................................................ 10
6.6 Type labels ................................................................. 10
6.7 Pneumatic data ......................................................... 11
6.8 Electrical data ............................................................ 11
6.9 Factory settings of the positioner .............................. 12
7 INSTALLATION .................................................................... 12
7.1 Safety instructions ..................................................... 12
8 PNEUMATIC INSTALLATION .............................................. 14
9 ELECTRICAL INSTALLATION ............................................. 15
9.1 Safety instructions ..................................................... 15
9.2 Electrical installation with circular plug-in connector 15
10 START-UP ............................................................................ 16
10.1 Safety instructions ..................................................... 16
10.2 Automatic adjustment X.TUNE ................................. 16
10.3 Control and display elements .................................... 18
11 SAFETY POSITIONS ........................................................... 21
12 ACCESSORIES ................................................................... 22
12.1 Communications software ......................................... 22
12.2 USB interface ............................................................ 22
12.3 Download .................................................................. 22
13 PACKAGING, TRANSPORT, STORAGE ............................. 22
english 3
Type 8696
Quickstart
1 QUICKSTART
The Quickstart describe the entire life cycle of the device. Keep the
Quickstart in a location which is easily accessible to every user and make the Quickstart available to every new owner of the device.
Important Safety Information.
Read Quickstart carefully and thoroughly. Study in particular
the chapters entitled “Basic safety instructions” and “Autho rized use”
.
▶ Quickstart must be read and understood.
Quickstart explains, for example, how to install and start-up the device.
A detailed description of the device can be found in the operating instructions for positioner Type 8696.
The operating instructions can be found on the Internet at: www.burkert.com
1.1
Definition of term / abbreviation
The term “device” used in these instructions always stands for the positioner Type 8696.
In these instructions, the abbreviation “Ex” always refers to
“potentially explosive”.
1.2
Symbols
The following symbols are used in these instructions.
DANGER!
Warns of an immediate danger.
▶ Failure to observe the warning may result in a fatal or serious injury.
WARNING!
Warns of a potentially dangerous situation.
▶ Failure to observe the warning may result in serious injuries or death.
CAUTION!
Warns of a possible danger.
▶ Failure to observe this warning may result in a medium or minor injury.
NOTE!
Warns of damage to property.
indicates important additional information, tips and recommendations.
refers to information in these operating instructions or in other documentation.
▶ Designates an instruction to prevent risks.
→ designates a procedure that must be carried out.
4 english
Type 8696
Authorized use
2 AUTHORIZED USE
Non-authorized use of the positioner Type 8696 may be a hazard to people, nearby equipment and the environment.
▶ The device is designed to be mounted on pneumatic actuators of process valves for the control of media.
▶ Do not expose the device to direct sunlight.
▶ Use according to the authorized data, operating conditions and conditions of use specified in the contract documents and operating instructions. These are described in the chapter entitled
▶ The device may be used only in conjunction with third-party devices and components recommended and authorized by
Bürkert.
▶ In view of the large number of options for use, before installation, it is essential to study and if necessary to test whether the positioner is suitable for the actual use planned.
▶ Correct transportation, correct storage and installation and careful use and maintenance are essential for reliable and faultless operation.
▶ Use the positioner Type 8696 only as intended.
3 BASIC SAFETY INSTRUCTIONS
These safety instructions do not make allowance for any
• contingencies and events which may arise during the installation, operation and maintenance of the devices.
• local safety regulations – the operator is responsible for observing these regulations, also with reference to the installation personnel.
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
english 5
6
Type 8696
Basic safety instructions
General hazardous situations.
To prevent injury, ensure:
▶ In the potentially explosion-risk area the positioner Type 8696 may be used only according to the specification on the separate approval sticker. For use observe the additional instructions enclosed with the device together with safety instructions for the explosion-risk area.
▶ Devices without a separate approval sticker may not be used in a potentially explosive area.
▶ Installation and repair work may be carried out by authorized technicians only and with the appropriate tools.
▶ After an interruption in the power supply or pneumatic supply, ensure that the process is restarted in a defined or controlled manner.
▶ The device may be operated only when in perfect condition and in consideration of the operating instructions.
▶ The general rules of technology apply to application planning and operation of the device.
To prevent damage to property of the device, ensure:
▶ Do not feed any aggressive or flammable media into the pilot air port.
▶ Do not feed any liquids into the pilot air port.
▶ When unscrewing and screwing in the body casing or the transparent cap, do not hold the actuator of the process valve but the connection housing of Type 8696.
▶ Do not put any loads on the housing (e.g. by placing objects on it or standing on it).
▶ Do not make any external modifications to the device housings.
NOTE!
Electrostatic sensitive components / modules.
The device contains electronic components which react sensitively to electrostatic discharge (ESD). Contact with electrostatically charged persons or objects is hazardous to these components. In the worst case scenario, they will be destroyed immediately or will fail after start-up.
▶ Observe the requirements in accordance with EN 61340-5-1 to minimise or avoid the possibility of damage caused by sudden electrostatic discharge.
▶ Also ensure that you do not touch electronic components when the power supply voltage is present.
english
Type 8696
General information
4 GENERAL INFORMATION
4.1
Contact address
Germany
Bürkert Fluid Control System
Sales Center
Chr.-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: [email protected]
International
Contact addresses can be found on the final pages of the printed operating instructions.
And also on the Internet at: www.burkert.com
4.2
Warranty
The warranty is only valid if the positioner Type 8696 is used as intended in accordance with the specified application conditions.
4.3
Information on the internet
The operating instructions and data sheets for Type 8696 can be found on the Internet at: www.burkert.com
5 SYSTEM DESCRIPTION
5.1
Structure and function
Positioner
Actuator
Valve body
Process valve
Fig. 1: Structure 1
Positioner Type 8696 is an electropneumatic position controller for pneumatically actuated control valves with single-acting actuators.
Together with the pneumatic actuator, the positioner forms a functional unit.
The control valve systems can be used for a wide range of control tasks in fluid technology and, depending on the application conditions, different process valves from the Bürkert range can be combined with the positioner. Angle seat valves, straight seat valves or diaphragm valves of the Type 2300, 2301 or 2103 with an actuator size of 50 mm are suitable.
english 7
Type 8696
System description
Electrical connection
(circular plug-in connector)
Pilot air port (label: 1)
Exhaust air port (label: 3)
Connection housing
Transparent cap removed:
LED 1
LED 2
Communications interface
Pressure limiting valve
(for protection against too high internal pressure in case of error)
Key 1
DIP Switches
Key 2
Fig. 2: Structure 2
The position of the actuator is regulated according to the position set-point value. The nominal position value is specified by an external standard signal.
5.2
Model for control of third-party devices
A special model enables the positioner Type 8696 to be attached to third-party devices.
This model has a different pneumatic connection housing so that the pilot air ports can be connected to the outside of the actuator.
Electrical connection
(circular plug-in connector)
Exhaust air port
(label: 3)
Fastening screws (2 x)
Pilot air port
(label: 1)
Pilot air outlet 2
Pilot air outlet 2
1
2
Connection housing
Fig. 3: Model for third-party devices
NOTE!
Damage or malfunction due to ingress of dirt and moisture.
▶ To comply with protection class IP65 / IP67, connect the pilot air outlet (only for CFA or CFB) which is not required to the free pilot air port of the third-party device or seal with a plug.
8 english
Type 8696
Technical data
“In rest position” means that the pilot valves of the positioner Type 8696 are isolated or not actuated.
If the ambient air is humid, a hose can be connected between pilot air outlet 2 of the positioner and the unconnected pilot air port of the third-party device for control function A or control function B. As a result, the spring chamber of the third-party device is supplied with dry air from the vent duct of the positioner.
Control function
(CF)
A
Process valve closed in rest position
(by spring force)
Pneumatic connection
Type 8696 with third-party device
Pilot air outlet
2
2
1)
2
1
B
Process valve open in rest position
(by spring force)
Pilot air outlet
Tab. 1: Pneumatic connection to third-party device
2
1
2
2
1)
1) Connection optionally, see note.
6 TECHNICAL DATA
6.1
Conformity
In accordance with the EU Declaration of conformity, the positioner Type 8696 is compliant with the EU Directives.
6.2
Standards
The applied standards, which verify conformity with the EU
Directives, can be found on the EU-Type Examination Certificate and / or the EU Declaration of Conformity.
6.3
Licenses
The product is approved for use in zone 2 and 22 in accordance with ATEX directive 2014/34/EU category 3GD.
Observe instructions on operation in an explosion-risk
(Ex) area. Observe the ATEX additional instructions.
The product is cULus approved. Instructions for use in the UL area see chapter
6.4
Operating conditions
WARNING!
Solar radiation and temperature fluctuations may cause mal functions or leaks.
▶ If the device is used outdoors, do not expose it unprotected to the weather conditions.
▶ Ensure that the permitted ambient temperature does not exceed the maximum value or drop below the minimum value.
english 9
Ambient temperature see type label
Degree of protection:
Evaluated by the manufacturer:
IP65 / IP67 according to EN
60529 2)
Evaluated by UL:
UL Type 4x Rating 2)
2) Only if cables, plugs and sockets have been connected correctly and
in compliance with the exhaust air concept, see chapter “8 Pneumatic installation”.
6.5
Mechanical data
Dimensions See data sheet
Body material exterior: PPS, PC, VA interior: PA6; ABS
Sealing material EPDM / FKM
Stroke range of valve spindle Series 2103 and 23xx 3 – 32 mm
Third-party devices
(modified guide element required) 3 – 40 mm
Type 8696
Technical data
6.6
Type labels
6.6.1
Type label (example)
Type; Features of the type code applicable to UL and ATEX
Control function; pilot valve;
Supply voltage pilot valve
8696 -E1-...-0 PU02
Single act Pilot 0.6 24V
Pmax 7 bar
Tamb -10 - +60 °C
S/N 1001
00123456
CE
W15MA
Max. operating pressure
Max. ambient temperature
Serial number; CE mark
Bar code
Identification number; Date of manufacture (encoded)
Fig. 4: Type label (example)
6.6.2
UL additional label (example)
Degree of protection
Circuit with limited power
Supply voltage device
Type 4X enclosure
NEC Class 2 only
Supply voltage: 24 V
Fig. 5: UL additional label (example)
10 english
Type 8696
Technical data
6.7
Pneumatic data
Control medium: neutral gases, air
Quality classes in accordance with ISO 8573-1
Dust content Class 7: max. particle size 40 µm, max. particle density 10 mg/m³
Water content Class 3: max. pressure dew point
- 20 °C or min. 10 °C below the lowest operating temperature
Oil content Class X: max. 25 mg/m³
Temperature range control medium: -10 – +50 °C
Pressure range control medium: 3 – 7 bar
Air output of pilot valve: 7 l
N
/ min (for aeration and deaeration)
(Q
Nn
- value according to definition for pressure drop from 7 to 6 bar absolute)
Connections:
23xx / 2103 (Element): Plug-in hose connector ∅ 6mm / 1/4“
Socket connection G 1/8
Model third-party device: Socket connection G 1/8 with M5 connection for connecting to the third-party device
6.8
Electrical data
WARNING!
Only circuits with limited power may be used for UL approved components according to “NEC Class 2”.
Connections Circular plug-in connector
(M12 x 1, 8-pole)
Pilot valve
Supply voltage 24 V DC ± 10%
- max. residual ripple 10 %
Power input ≤ 3.5 W
Input resistance for set-point value signal 180 Ω at 0/4 – 20 mA /
12 bit resolution
Protection class 3 as per DIN EN 61140 (VDE 0140-1)
Analogue position feedback max. load for current output
0/4 – 20 mA 560 Ω
Binary input 0 – 5 V = log “0”,
12 – 30 V = log “1” inverted input in reverse order
Communications interface Direct connection to PC via USB adapter with integrated interface driver, communication with communications software .
english 11
6.9
Factory settings of the positioner
Functions can be activated via DIP switches:
Function Parameter Value
CUTOFF Sealing function below
Sealing function above
Select characteristic
2 %
98 %
FREE 3) CHARACT
DIR.CMD
Effective direction set-point value
Tab. 2: Factory settings - functions rise
Additional functions are described in the operating instructions Type 8696.
These instructions can be found on the Internet at www.burkert.com
.
3) without change to the settings via the communications software a linear characteristic is stored in FREE.
Type 8696
Installation
7 INSTALLATION
Only for positioner without pre-assembled process valve.
7.1
Safety instructions
DANGER!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
WARNING!
Risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following assembly, ensure a controlled restart.
12 english
Type 8696
Installation
7.2
Installation of the positioner on process valves of series 2103 and 23xx
NOTE!
When mounting on process valves with a welded body, follow the installation instructions in the operating instructions for the process valve.
When the positioner is being installed, the collets of the pilot air ports must not be fitted to the actuator.
NOTE!
Damaged printed circuit board or malfunction.
▶ Ensure that the puck is situated flat on the guide rail.
→ Align the puck and the positioner until
1. the puck can be inserted into the guide rail of the positioner (see
2. the connection pieces of the positioner can be inserted
into the pilot air ports of the actuator (see also “Fig. 7” ).
Connection pieces
Guide rail
→ Push the positioner, without turning it, onto the actuator until no gap is visible on the form seal.
NOTE!
Too high torque when screwing in the fastening screw does not ensure protection class IP65 / IP67.
▶ The fastening screws may be tightened to a maximum torque of 1.5 Nm only.
→ Attach the positioner to the actuator using the two side fastening screws. In doing so, tighten the screws only hand-tight
(max. torque: 1.5 Nm).
Connection pieces
Pilot air ports
(actuator)
Fastening screws max. 1.5 Nm
Fig. 6: Aligning the puck
Puck
Fig. 7: Installation of positioner, 2103 and 23xx series english 13
Type 8696
Pneumatic installation
8 PNEUMATIC INSTALLATION
DANGER!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure and deaerate/drain lines.
Procedure:
→ Connect the control medium to the pilot air port (1)
(3 – 7 bar; instrument air, free of oil, water and dust).
→ Attach the exhaust airline or a silencer to the exhaust air port
(3)
(see “Fig. 8: Pneumatic connection” ).
Keep the adjacent supply pressure always at least 0.5 –
1 bar above the pressure which is required to move the actuator to its end position. This ensures that the control behavior is not extremely negatively affected in the upper stroke range on account of too little pressure difference.
During operation keep the fluctuations of the pressure supply as low as possible (max. ±10 %). If fluctuations are greater, the control parameters measured with the X.TUNE
function are not optimum.
Important information for the problem-free functioning of the device:
▶ The installation must not cause back pressure to build up.
▶ Select a hose for the connection with an adequate cross-section.
▶ The exhaust air line must be designed in such a way that no water or other liquid can get into the device through the exhaust air port.
Pilot air port
(label: 1)
Exhaust air port
(label: 3)
Fig. 8: Pneumatic connection
Caution: (Exhaust air concept) :
In compliance with protection class IP67, an exhaust air line must be installed in the dry area.
14 english
Type 8696
Electrical installation
9 ELECTRICAL INSTALLATION
All electrical inputs and outputs of the device are not galvanically isolated from the supply voltage.
9.1
Safety instructions
DANGER!
Risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
WARNING!
Risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
Risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
9.2
Electrical installation with circular plug-in connector
→ Connect the positioner according to the table.
6
5
4
7
3
8
1
2
Fig. 9: Circular plug M12 x 1, 8-pole
Input signals of the control center (e.g. PLC)
Pin Wire
3)
Configuration External circuit / signal level
1
2 white brown
Set-point value
+
(0/4 – 20 mA)
Set-point value
GND
Binary input +
1
5
2
+ (0/4 – 24 mA)
GND
5 grey + 0 – 5 V (log. 0)
10 – 30 V (log. 1)
6 pink Binary input
GND
6 GND
Tab. 3: Pin assignment - input signals of the control center english 15
Operating voltage
Pin Wire
4)
Configuration External circuit
3
4 green yellow
GND
+ 24 V
3
4
Tab. 4: Pin assignment - operating voltage
24 V DC ± 10 % max. residual ripple 10 %
Output signals to the control center (e.g. PLC) - (required for analogue output option only)
Pin Wire
4)
Configuration External circuit / signal level
8
7 red blue
Analogue position feedback +
Analogue position feedback GND
8
7
+ (0/4 – 24 mA)
GND
Tab. 5: Pin assignment - output signals of the control center - option
When the supply voltage is applied, the positioner is operating.
→ Actuate the automatic adjustment of the positioner, as
described in the chapter entitled “10.2 Automatic adjustment
4) The indicated colors refer to the connecting cable available as an accessory (919061).
16 english
Type 8696
Start-up
10 START-UP
10.1 Safety instructions
WARNING!
Risk of injury from improper operation.
Improper operation may result in injuries as well as damage to the device and the area around it.
▶ Before start-up, ensure that the operating personnel are familiar with and completely understand the contents of the operating instructions.
▶ Observe the safety instructions and intended use.
▶ Only adequately trained personnel may operate the equip ment/the device.
10.2 Automatic adjustment X.TUNE
To adjust the positioner to local conditions, the X.TUNE
function must be run following installation.
WARNING!
Danger due to the valve position changing when the X.TUNE
function is running.
When the X.TUNE
is running under operating pressure, there is an acute risk of injury.
▶ Never run X.TUNE
while a process is running.
▶ Take appropriate measures to prevent the equipment from being accidentally actuated.
Type 8696
Start-up
NOTE!
Avoid maladjustment of the controller due to an incorrect pilot pressure or applied operating medium pressure.
▶ Run X.TUNE
whenever the pilot pressure (= pneumatic auxiliary energy) is available during subsequent operation.
• Run the X.TUNE function preferably without operating medium pressure to exclude interference caused by flow forces.
To run X.TUNE
, the positioner must be in the AUTOMATIC operating status (DIP switch 4 = OFF).
NOTE!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the connection housing.
Transparent cap
Body casing
Connection housing
Actuator
Fig. 10: Open positioner
→ Screw off the transparent cap of the positioner to operate the keys and DIP switches.
LED 2
LED 1
Key 1
DIP Switches
Key 2
Fig. 11: Starting X.TUNE
→ Start the X.TUNE
by pressing key 1 5) for 5 s.
While the X.TUNE
is running, LED 1 flashes quickly (green).
When the automatic adjustment is complete, LED 1 flashes slowly
(green) 6) .
The changes are automatically transferred to the memory (EEPROM) provided the X.TUNE function is successful.
5) The X.TUNE can also be started via communications software.
6) if a fault occurs, LED 1 is lit red.
NOTE!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the connection housing.
Damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way. english 17
→ Close the device (assembly tool: 674078 7) ).
7) The assembly tool (674078) is available from your Bürkert sales office.
10.3 Control and display elements
A detailed description of the operation and functions of the positioner and the communication software can be found in the respective operating instructions.
NOTE!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the connection housing.
Transparent cap
Body casing
Connection housing
Actuator
Type 8696
Start-up
→ Screw off the transparent cap of the positioner to operate the keys and DIP switches.
Key 1
LED 2
LED 1
DIP switches
Key 2
Communica tions interface
Fig. 13: Description of the control elements
NOTE!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the connection housing.
Damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way.
→ Close the device (assembly tool: 674078 8) ).
8) The assembly tool (674078) is available from your Bürkert sales office.
Fig. 12: Open positioner
18 english
Type 8696
Start-up
10.3.1 Operating status
AUTOMATIC (AUTO)
Normal controller mode is implemented and monitored in AUTO-
MATIC operating state.
LED1 flashes green.
MANUAL (MANU)
In MANUAL operating state the valve can be opened and closed manually via the keys.
LED1 flashes red / green alternately.
ON DIP
1 2 3 4
The DIP switch 4 can be used to switch between the two operating states AUTOMATIC and MANUAL.
DIP switches
4 ON
OFF
Tab. 6: DIP switches
Function
Operating status MANUAL (MANU)
Operating status AUTOMATIC (AUTO)
10.3.2 Functions of the keys
The configuration of the 2 keys on the board varies depending on the operating status (AUTOMATIC / MANUAL).
Key 1
Key 2
Fig. 14: Keys
MANUAL operating status (DIP switch 4 set to ON):
Key Function 9)
1 Aerate (manually open / close the actuator) 10)
2 Deaerate (manually open / close the actuator) 10)
Tab. 7: Configuration of the keys for MANUAL operating status
AUTOMATIC operating status (DIP switch 4 set to OFF):
Key Function
1 Press for 5 s to start the X.TUNE
function
2 -
Tab. 8: Configuration of the keys for AUTOMATIC operating status
9) No function if the binary input was activated with the “Manual/Auto change-over” via the communications software.
10) depending on the operating principle of the actuator.
english 19
10.3.3 Function of the DIP switches
ON DIP
DIP switches
Function
1 2 3 4
1 ON Reversal of the effective direction of the set-point value (set-point value 20 – 4 mA corresponds to position 0 – 100 %), descending ( DIR.CMD
)
OFF Normal effective direction of the set-point value
(set-point value 4 – 20 mA corresponds to position 0 – 100 %), ascending
2 ON Sealing function active. The valve completely closes below 2 % 10) and opens above 98 % of the set-point value ( CUTOFF )
OFF No sealing function
3 ON Correction characteristic for adjustment of the operating characteristic (linearization of the process characteristic CHARACT ) 11)
OFF Linear characteristic
4 ON Operating status MANUAL (MANU)
OFF Operating status AUTOMATIC (AUTO)
Tab. 9: DIP switches
11) Can be changed via communications software.
20 english
Type 8696
Start-up
10.3.4 Display of the LEDs
LED 2
LED 1
Fig. 15: Display of the LEDs
LED 1
(green / red)
LED 2
(green / yellow)
Display of
AUTO, MANU, X.TUNE
and FAULT
Display of state of actuator
(open, closed, opens or closes)
Type 8696
Safety positions
LED 1 (green / red)
LED States green on flashes slowly red off off
Display flashing flashing alternating flashes quickly off off flashing slow
MANUAL operating status
X.TUNE function on ERROR (see operating instructions) flashing AUTO operating status for sensor break detection
Tab. 10: Display LED 1
Acceleration phase when Power ON
Operating status AUTO
(AUTOMATIC)
LED 2 (green / yellow)
LED States green on off yellow off on
Display flashes slowly off flashes quickly off flashes slowly off off flashes quickly
Tab. 11: Display LED 2
Actuator closed
Actuator open
Remaining control deviation
(actual value > set-point value)
Remaining control deviation
(actual value < set-point value)
Closing in MANUAL operating status
Opening in MANUAL operating status
11 SAFETY POSITIONS
Actuator system up down
Designation single-acting
Control function A up down
Tab. 12: Safety positions single-acting
Control function B
Safety positions after failure of the auxiliary power electrical pneumatic down up not defined not defined english 21
12 ACCESSORIES
Designation
USB adapter for connection to a PC in conjunction with an extension cable
Order no.
227093
Communicator
Connection cable M12 x 1, 8-pole
Assembly tool
Tab. 13: Accessories
Information at www.burkert.
com
919061
647078
12.1
Communications software
The PC operating program “Communicator” is designed for communication with the devices from the Bürkert positioner family (valid since serial number 20000).
A detailed description and precise schedule of the procedure for the installation and operation of the software can be found in the associated documentation.
12.2
USB interface
The PC requires an USB interface for communication with the positioners as well as an additional adapter with interface driver
).
12.3
Download
Download the software at: www.burkert.com
Type 8696
Accessories
13 PACKAGING, TRANSPORT,
STORAGE
NOTE!
Transport damages.
Inadequately protected equipment may be damaged during transport.
▶ During transportation protect the device against wet and dirt in shock-resistant packaging.
▶ Avoid exceeding or dropping below the permitted storage temperature.
Incorrect storage may damage the device.
▶ Store the device in a dry and dust-free location.
▶ Storage temperature -20 – +65 °C.
Damage to the environment caused by device components contaminated with media.
▶ Dispose of the device and packaging in an environmentally friendly manner.
▶ Observe applicable regulations on disposal and the environment.
22 english