Swegon TAC3 is a device that allows for advanced control and monitoring of ventilation systems. It features a user-friendly interface that makes it easy to set up and operate. The TAC3 can be used to control a variety of ventilation system components, including fans, dampers, and sensors. It can also be used to monitor system performance and generate alarms in the event of a problem.
Some of the key features of the TAC3 include:
- Advanced control algorithms that optimize system performance and efficiency
- Easy-to-use interface that makes it simple to set up and operate
- Comprehensive monitoring capabilities that provide real-time data on system performance
Mainos
Mainos
AS KIT CPT TAC3 AVANCED SETUP
(v.09/2008)
The advanced setup allows to activate certain features or to modify certain parameters:
To start the advanced setup , press simultaneously on ‘SETUP’ and ‘ENTER’ until the text ADVANCED SETUP appears on the screen. Principle: make selections via buttons ↑ ↓, then press ‘ENTER’. The numbers are introduced digit by digit.
Mode
CA
CA
CPf
CA
CPf
LS
CPs
LS
CPs
LS
CPs
Step
1
2
3
4
5
6
-
-
-
-
CA LS
CPs
7
8
If LS mode is configured
-
-
-
-
LS
-
LS
-
9
10
10.1
LS
-
LS
-
11
12
12.1
Text on screen
ENTER ACCES
CODE 0000
INPUT IN1:
MASTER SELECT
FIRE ALARM
STOP: F1/2/3/4
START TORQUE?
2%
STOP FAN IF
V<Vlow? N
Vlow: xx,x V
V>Vhigh? N
Vhigh: xx,x V
Description
If the access code procedure has been activated (see step 24) you will need to enter the access code before going any further.
Input IN1 can be used to :
- select which device (CBr or RC) is master of the fan control to start/stop/select assignment. Select «SELECT MASTER »
- connect a pressure sensor in order to activate an external pressure alarm system. Select « PRESSURE ALARM »
When a fire alarm is activated you can stop :
- ALL the fans: select F1/2/3/4
- Fans F1 and F2: select F1/2
- Fans F3 and F4: select F3/4
Fan starting torque can be modified here. (by default 2%)
Stop the fans automatically if 0-10V signal value is < Vlow
If Y was selected on step 10, fill in value of Vlow
Stop the fans automatically if 0-10V signal value is > Vhigh
If Y was selected on step 12, fill in value of Vhigh
-
-
LS
-
13 0-10V ON K3? N Functionality to control supply fans through a 0-10V signal connected on entry K2 and exhaust fans through another 0-10V signal connected on entry K3. (Same link voltage/airflows for both entries)
If CPs mode is configured
-
-
-
CPs
14 CPs SPEED? 10 Tuning of the reaction speed of the CPs algorithm. The default value is 10 and is the highest possible value. Each increment of
-1 corresponds to a doubling of the reaction time (10=T, 9=2xT,
8=4xT, …).
This feature is very sensible, we recommend it only when operating in constant pressure systems where the system is a room and not a duct.
-
-
-
CPs
15 LOGIC? NEGATIVE Configuration CPs mode logic:
Negative logic:
- the airflow decreases when signal on K2 > assignment value
- the airflow increases when signal on K2 < assignment value
Positive logic:
- the airflow increases when signal on K2 > assignment value
- the airflow decreases when signal on K2 < assignment value
If CA or LS mode is configured
CA
-
-
-
16
17
PRESSURE ALARM:
STOP FAN? N
Functionality to automatically stop the fans in case of alarm pressure (press RESET to restart fans after correction of problem)
1
For all working modes (CA, LS, CPf, CPs)
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
CA
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
LS
CPs
18
19
20
21
22
23
21.1
21.2
FAN RUN TIME? N
TIME RESET? N
DISPLAY TIME? N
21.3 SERVICE ALARM? N If Y was selected at step 21 you have here the possibility to request a runtime alarm service or not.
21.3.1 TIME? 000000 h If Y was selected at step 21.3 you have here the possibility to set the runtime (in hours) after which a maintenance alarm must be activated.
21.4 STOP FAN? N
21.4.1 TIME? 000000 h
If Y was selected at step 21 you have here the possibility to request all fans to stop after a certain runtime.
If Y was selected at step 21.4 fill in the runtime (in hours) after which you want all fans to be automatically stopped.
DISPLAY ALARM
ONLY? N
INIT CP? AUTO
Possibility to activate a runtime counter. How much time the fans have been running. This can help to generate a maintenance procedure, or to stop the fans once a certain runtime is reached.
If Y was selected at step 21 you have here the possibility to set the runtime counter at 0.
If Y was selected at step 21 you have here the possibility to display the actual runtime.
24
25
24.1
ACCESS CODE? N
CODE 0000
BUZZER ON
Possibility to only display the alarms on the screen. "Fan OK" will then be displayed when no alarm is activated.
Define if the constant pressure assignment value (Pa) for the fans:
- is to be automatically determined as a consequence of a selected airflow value: select AUTO.
- is to be typed in by the user: select MANUAL
Possibility to activate an access code to control the access inside the advanced setup.
If Y is selected at step 24, enter here the access code to advanced setup.
Possibility to activate (ON) or deactivate (OFF) the buzzer.
26
27
20.1
OUT3 m³h F1
OUT4 Pa F1
POST VENT? N
TIME PV 0090 sec
FACTORY RESET? N
END SETUP
Selection of the information present on the 0-10V output OUT3:
Select information (airflow or pressure) and fan (F1-F4) to be outputted on OUT3 (default is airflow of fan F1).
Selection of the information present on the 0-10V output OUT4:
Select information (airflow or pressure) and fan (F1-F4) to be outputted on OUT4 (default is pressure of fan F1).
Possibility to activate a post-ventilation (continue to run the fan for some time after softstop has been activated).
Caution: if preheat KWin = yes and/or postheat type KWout is installed then the POSTVENT est automatically activated and can not be set at NO.
If you have selected Y on step 20 enter time of duration of postventilation in seconds.
Attention: if an electrical preheat (KWin) or postheat (KWout) is installed this time is preset to 90sec and may not be reduced.
Possibility to make a complete reset of all the parameters of the
CB. If you chose Y all the factory parameters will be regenerated.
End of advanced setup.