Swegon CONDUCTOR W3 Installation Instruction
Swegon CONDUCTOR W3 is a versatile and easy-to-use device that can be used to control various aspects of your home's climate. With its built-in temperature, humidity, and CO2 sensors, the CONDUCTOR W3 can automatically adjust the temperature, fan speed, and ventilation settings to create a comfortable and healthy indoor environment. The device can be controlled via a user-friendly mobile app, allowing you to make changes to the settings from anywhere in your home. Additionally, the CONDUCTOR W3 can be integrated with other smart home devices, such as Amazon Alexa and Google Home, for even more convenience.
광고
광고
CONDUCTOR
W3
Installation instruction
20190923
Art.No. 942428022
Content
Controller ............................................................. 2
To mount the controller ..................................... 2
Mounting on a DIN rail ............................................... 2
To be installed above a false ceiling ............................. 2
Wiring .................................................................. 3
Room unit ............................................................ 4
Overview over the menu system ................................. 5
Room unit overview .................................................... 6
RF pair-up (When RJ12 not used) ................................ 6
Conductor to BMS and SuperWise (WISE gen.1) . 7
Symbols
Warning/Caution!
CONDUCTOR W3
Controller
4
3
To mount the controller
Mounting on a DIN rail
5
2
6
7
1
2
3
4
8
1
Figure 1. Overview of the Controller.
Pos 1. Product marking.
Pos 2. Termination resistance.
1 = The unit is the last node in the network
2 = The unit is the first node in the network
3 = The unit is situated between the first and last nodes
Pos 3. Modular Contact / ModBUS RTU units (pressure sensor and room unit)
Pos 4. Inputs: Wiring terminals for the connection of sensors.
Pos 5. DIP switch for ModBUS RTU.
1 (=on) boosts the controller to Modbus address 1
2 (=on) access to Modbus register via BMS system
(requires a restart of the controller)
Pos 6. LED, indicates the status of the controller.
Pos 7. Input and output for signal to external relay.
Pos 8. Outputs: Wiring terminals for the connection of valve and damper actuators.
Figure 3. To mount the controller.
Pos 1. Plastic hooks
Pos 2. Supporting surface
Pos 3. DIN rail
Pos 4. Snap-on fastener.
To be installed above a false ceiling
If a DIN rail is NOT available pre-mounted or is not available, the controller can be appropriately mounted above the false ceiling ( not on the module).
1
Product Identification Label
1
Conductor RE W3
Modbus Adress 2
Artnr: 942334001
RF id: 00350
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Figure 2. Product identification label on the controller.
Pos 1. Name of the product.
Pos 2. ModBus RTU address default from factory.
Pos 3. Part number.
Pos 4. Controller ID number.
2
3
4
2
Figure 4. To mount the controller.
Pos 1. Supporting surface, NOT for the comfort module or climate beam.
Pos 2. Screws.
a. Secure the controller by means of screws in the upper lefthand and the lower right-hand corners. Use screws suitable for the supporting surface.
2
Swegon reserves the right to alter specifications 20190923
Wiring
Monitoring system via
ModBus
5
6
8
4
1
9
3
2
Signal to external relay
Figure 5. CONDUCTOR W3: Integral Components
1
2
3
4
5
6
7
8
9
Controller
Room unit
Key card/ presence detector
Window contact
Condensation sensor
External temp. sensor
Transformer
Valve actuator
Ventilation damper incl. damper actuator
Conductor RE
Conductor RU
SYST SENSO/
Detect Occupancy
CONDUCTOR T-TG
SYST TS-1
ACTUATOR b 24V NC
CRTc -aaa-2
(aaa = dimension)
7
Room unit
MODBUS RS2
MODBUS RS1
Condensation sensor
Temperature sensor
Transformer
Window contact
Key card
Valve actuator for cooling water.
Valve actuator, for heating water.
Damper, supply air (SA)
Damper, extract air (EA)
CONDUCTOR W3
RJ12 Modular contact
1 Data (B)
2
3
Data (A)
Earth
5
6
Data (B)
Data (A)
7
17
Earth
Resistance
18
19
KTY
20
23 + 24V AC
24 -G0
25 10V
10 10V
26 10V
12 10V
27 -G0
29 +24V
30 -G0
32 +24V
33 -G0
34 0-10V
35 +24V
36 -G0
37 0-10V
38 +24V
Figure 6. Wiring diagram, CONDUCTOR W3
20190923 Swegon reserves the right to alter specifications
3
CONDUCTOR W3
Room unit
2
3
2
1
3b
3a
Figure 7. Wireless: 3xAAA, (pos 3a), Cable: RJ12 (pos 3b).
1
Figure 8. To mount the room unit (thermostat).
Pos 1. Front piece.
Pos 2. Back piece.
Pos 3. Screws suitable for the supporting surface.
• Recommended installation height RU = standard height for light switches
• RU should not be exposed to direct sunlight, or other disturbing heat sources.
• Room air should be able to circulate around the front and sides of the RU.
4
Swegon reserves the right to alter specifications 20190923
CONDUCTOR W3
Overview over the menu system
Main menu
Setup
Enter code
1 9 1 9
Service menu
Regulator adjust Settings System info General Param.
Appl. Param.
Econ SA % 20
Norm SA % 50
Boost SA % 80
Econ EA % 20
Norm EA % 50
Boost EA % 80
Room unit no.
Room temp
Serial Number
Battery Level
RF pair-up
Application
Sw. ver. RE
Sw. ver. RU
Language
Temp C
Temp H
FirstTime func
Change % value to achieve correct damper position/air flow
RF Quality
Temp.calibration
Enter code
3 7 4 9
Enter code
9 4 7 3
Parameter
P_101 value
2
ModBus address
Min 0 Max 79
Parameter
P_1902 values
1
1 or 2 room units
Min 0 Max 2
Alarms
Energy saving
Backlight
Basescreen mode
Set point step
Commissioning
Figure 9. Overview over the menu system of the room unit.
20190923 Swegon reserves the right to alter specifications
5
CONDUCTOR W3
Room unit overview
5 6
4
3
2
1
Figure 10. Overview of the main image of the room unit.
Pos 1. Cursor key for moving DOWN.
Pos 2. Cursor key for moving to the LEFT.
Pos 3. Heating/cooling.
Pos 4. Battery charge status/Window status.
Pos 5. Current airflow.
Pos 6. Operating mode.
Pos 7. Current temperature.
Pos 8. Carbon dioxide content.
Pos 9. Occupancy status
Pos 10. Cursor key for moving UP.
Pos 11. Cursor key for moving to the RIGHT.
Pos 12. OK key.
7
8
9
10
11
12
RF pair-up (When RJ12 not used)
OK 3 sek.
<Exit
Main menu
Setup
▲▼ Select>
<Exit
Press code
1 9 1 9
▲▼
>
<Exit
ModBUS
RF pair-up
RF Quality
▲▼ Select>
<Exit
0
RF pair-up
0 0 0 0
▲▼
Select>
Conductor RE W3
Modbus Adress 2
Artnr: 942334001
RF id: 00350
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Product identification label on the controller.
6
Swegon reserves the right to alter specifications 20190923
Product identification label on the controller.
Conductor to BMS and SuperWise (WISE gen.1)
CONDUCTOR W3
First and middle zone
Last RE in zone
Last zone
Last RE in zone
20190923 Swegon reserves the right to alter specifications
7
CONDUCTOR W3
WARNING:
All electrical installation, including wiring the actuators, valve actuators and various sensors is to be carried out by the electrical contractor or the systems contractor.
Safety precautions / Responsibility
It is the responsibility of the user to do the following:
• Assess all the risks involved in the activities which are related to this instruction.
• Make sure that all necessary safety precautions are made be-fore starting the activities which are related to this instruction.
For US and Canada market
WARNING:
The power feeding shall be a Low Voltage class 2 circuit.
8
Swegon reserves the right to alter specifications 20190923