Below you will find brief information for GOLD RX/PX/CX/SD. This manual provides alarm descriptions and information messages for your air handling unit, enabling effective troubleshooting and maintenance. Understand alarm priorities, reset procedures, and the implications of each message to maintain optimal performance.
Advertisement
Advertisement
MANUAL FOR ALARMS AND INFORMATION MESSAGES
GOLD
RX/PX/CX/SD
Generation F
Applicable to Program Version 1.28 and newer versions
Content
Innehåll
1. Alarm Descriptions with Factory Settings ............. 3
2. Information Messages .......................................... 24
GB.GOLDSKFLARM.181221
The document was originally written in Swedish.
2 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
1. Alarm Descriptions with Factory Settings
Alarm No.
Alarm text
Function
Priority Stop Delay
0 = Blocked 0 = In oper. s = second
Resetting
0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
Alarm group 1: Fire alarm
1:1 1 EXTERNAL FIRE ALARM NO. 1 TRIPPED
For the fire protection function connected to terminals
6-7.
1:2 2 EXTERNAL FIRE ALARM NO. 2 TRIPPED
For the fire protection function connected to terminals
8-9.
1:3 3 INTERNAL FIRE ALARM TRIPPED
The air handling unit’s supply air sensor measures more than 70 °C and/or its extract air temperature sensor measures more than 50 °C.
The function must be activated manually.
Alarm group 2: External alarm
2:1
2:2
16
17
EXTERNAL ALARM NO. 1 TRIPPED
External alarm, connected to control unit terminals 10-
11, has tripped..
EXTERNAL ALARM NO. 2 TRIPPED
External alarm, connected to control unit terminals 12-
13, has tripped..
Alarm group 3: Pre-heating
3:1 31 PRE-HEAT, I/O MODULE NO. 9 COMMUNICATION ER-
ROR
The air handling unit’s control unit cannot establish correct communication with I/O module No. 9 for preheating.
3:2
3:3
32
33
PRE-HEATING, OVERHEATING PROTECTION TRIPPED
OR NO SUPPLY VOLTAGE TO THE ELECTRICAL HEATER
The overheating protection has tripped or there is no supply voltage to the electrical heater.
PRE-HEAT, FROST GUARD TRIPPED
Frost guard temperature sensor measures temperature less than preset alarm limit.
Factory setting: 7 °C.
3:4
3:5
3:6
34
35
36
PRE-HEAT, FROST GUARD TEMPERATURE SENSOR
DEFECTIVE
Frost guard temperature sensor is defective or is not connected.
PRE-HEAT, TEMPERATURE SENSOR DEFECTIVE
Sensor is defective or is not connected.
PRE-HEAT, VALVE MONITORING TRIPPED
Valve actuator, air heater for water is defective.
3:7
3:8
37
38
PRE-HEAT, TEMPERATURE BELOW SET POINT ALARM
LIMIT
Temperature is below preset set point longer than 20 minutes.
PRE-HEAT, ALARM INPUT TRIPPED
Alarm input pre-heat has tripped.
Alarm group 4: Extra regulation sequence
4:1 46 EXTRA REGULATION SEQUENCE 1, I/O-MODULE No E
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. E for extra regulation sequence.
A 1)
A 1)
A 1)
A
B
A
A 1)
A 1)
A 1)
A
A
A
A
A
1
1
1
1 3)
0 3)
0 3)
0 3)
1
1
0 3)
0 3)
0 3)
0
0 3)
3 s
3 s
3 s
1 s 2)
1 s 2)
10 s
10 s
5 s
3 s
3 s
10 m
20 m
20 s
10 s
0
0
0
0
0
1
0
0
1
1
0
0
0
1
We reserve the right to alter specifications without notice.
www.swegon.com 3
GB.GOLDSKFLARM.181221
Alarm No.
4:2
4:3
4:4
4:5
4:6
4:7
4:8
4:9
4:10
4:11
4:12
4:13
4:14
47
48
49
50
51
52
53
54
55
56
57
58
59
Alarm text
Function
EXTRA REGULATION SEQUENCE 1, OVERHEATING
PROTECTION TRIPPED OR NO SUPPLY VOLTAGE TO THE
ELECTRICAL HEATER
The overheating protection has tripped or there is no supply voltage to the electrical heater.
EXTRA REGULATION SEQUENCE 1, FROST GUARD
TRIPPED
Frost guard temperature sensor measures temperature less than preset alarm limit.
Factory setting: 7 °C.
EXTRA REGULATION SEQUENCE 1, FROST GUARD
TEMPERATURE SENSOR DEFECTIVE
Frost guard temperature sensor is defective or is not connected.
EXTRA REGULATION SEQUENCE 1, VALVE MONITOR-
ING TRIPPED
Valve actuator, air heater for water, is defective.
EXTRA REGULATION SEQUENCE 1, ALARM INPUT
TRIPPED
Alarm input extra regulation sequence has tripped.
EXTRA REGULATION SEQUENCE 1, TEMPERATURE
PROTECTION VIA COMMUNICATION, COMMUNICA-
TION ERROR
The air handling unit’s control unit is not receiving any temperature reading via the external communication interface within the preset time limit.
EXTRA REGULATION SEQUENCE 1, COMBI COIL
SENSOR DEFECTIVE
Temperature sensor to the combi coil is defective or not connected.
EXTRA REGULATION SEQUENCE 2, I/O-MODULE No F
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. E for extra regulation sequence.
EXTRA REGULATION SEQUENCE 2, OVERHEATING
PROTECTION TRIPPED OR NO SUPPLY VOLTAGE TO THE
ELECTRICAL HEATER
The overheating protection has tripped or there is no supply voltage to the electrical heater.
EXTRA REGULATION SEQUENCE 2, FROST GUARD
TRIPPED
Frost guard temperature sensor measures temperature less than preset alarm limit.
Factory setting: 7 °C.
EXTRA REGULATION SEQUENCE 2, FROST GUARD
TEMPERATURE SENSOR DEFECTIVE
Frost guard temperature sensor is defective or is not connected.
EXTRA REGULATION SEQUENCE 2, VALVE MONITOR-
ING TRIPPED
Valve actuator, air heater for water, is defective.
EXTRA REGULATION SEQUENCE 2, ALARM INPUT
TRIPPED
Alarm input extra regulation sequence has tripped.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 1) 0 3) 10 s 0
A
A
B
A
B
A
A
A
A
A
B
A
1)
1)
1)
1)
1)
0
0
0
0
1
1
0
0
1
1
1
0
3)
3)
3)
3)
5 s
3 s
10 m
20 s
5 m
3 s
10 s
10 s
5 s
3 s
10 m
20 s
0
1
0
0
1
1
1
0
0
1
0
0
4 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
4:15 60 EXTRA REGULATION SEQUENCE 2, COMBI COIL
SENSOR DEFECTIVE
Temperature sensor to the combi coil is defective or not connected.
Alarm group 5: Reheating
5:1 61
5:2
5:3
62
63
RE-HEATING, OVERHEATING PROTECTION TRIPPED OR
NO SUPPLY VOLTAGE TO THE ELECTRICAL HEATER
The overheating protection has tripped or there is no supply voltage to the electrical heater.
REHEAT, FROST GUARD TRIPPED
Frost guard temperature sensor measures temperature less than preset alarm limit.
Factory setting: 7 °C.
REHEAT, FROST GUARD TEMPERATURE SENSOR DE-
FECTIVE
Frost guard temperature sensor is defective or is not connected.
5:4
5:5
64
65
REHEAT, VALVE MONITORING TRIPPED
Valve actuator, air heater for water is defective.
RE-HEATING, ALARM INPUT TRIPPED
Alarm input reheating has tripped.
Alarm group 6: Xzone I/O-module no. A
6:1 76 Xzone, I/O-MODULE NO. A COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. A for
Xzone.
6:2 77
6:3
6:4
6:5
78
79
80
Xzone, OVERHEATING PROTECTION TRIPPED OR NO
SUPPLY VOLTAGE TO THE ELECTRICAL HEATER
The overheating protection has tripped or there is no supply voltage to the electrical heater.
Xzone, FROST GUARD TRIPPED
Frost guard temperature sensor measures temperature less than preset alarm limit.
Factory setting: 7 °C.
Xzone, FROST GUARD TEMPERATURE SENSOR DEFEC-
TIVE
Frost guard temperature sensor is defective or is not connected.
Xzone, SUPPLY AIR TEMPERATURE SENSOR DEFECTIVE
Supply air sensor is defective or is not connected.
6:6
6:7
81
82
Xzone, HEATING VALVE MONITORING TRIPPED
Valve actuator, air heater for water is defective.
Xzone, SUPPLY AIR TEMPERATURE BELOW SET POINT
ALARM LIMIT
The supply air temperature is below the preset set point (ERS and Supply air regulation) or Min SA temp
(Extract air regulation) longer than 20 minutes.
6:8 83 Xzone, SUPPLY AIR TEMPERATURE ABOVE SET POINT
ALARM LIMIT
The supply air temperature is above the preset set point (ERS and Supply air regulation) or Max. SA temp
(Extract air regulation) longer than 20 minutes.
6:9 84 Xzone, HEAT, ALARM INPUT TRIPPED
Alarm input Xzone heat has tripped.
Alarm group 7: Xzone I/O-module no. B
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 1 3 s 1
A
A
A
B
A
A
A
A
A
A
B
A
B
A
1)
1)
1)
1)
1)
1)
0
1
1
0
0
0
0
1
1
1 3)
0 3)
0 3)
0
0
3)
3)
3)
3)
3)
10 s
5 s
3 s
10 m
20 s
10 s
10 s
5 s
3 s
3 s
10 m
20 m
20 m
20 s
0
0
1
0
0
1
0
0
1
1
0
0
0
0
We reserve the right to alter specifications without notice.
www.swegon.com 5
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
7:1
7:2
7:3
7:4
7:5
7:6
91
92
93
94
95
96
Xzone, I/O-MODULE NO. B COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. B for
Xzone.
Xzone, EXTRACT AIR TEMPERATURE SENSOR DEFEC-
TIVE
Extract air sensor is defective or is not connected.
Xzone, COOLING VALVE MONITORING TRIPPED
Valve actuator, air cooler for water is defective.
Xzone, EXTRACT AIR TEMPERATURE SENSOR BELOW
SET POINT ALARM LIMIT
The extract air temperature is below preset alarm limit for more than 20 minutes.
Xzone, COOL, ALARM INPUT 1 TRIPPED
Alarm input 1 Xzone cool has tripped.
Xzone, COOL, ALARM INPUT 2 TRIPPED
Alarm input 2 Xzone cool has tripped.
Alarm group 8: Cooling
8:5
8:6
110 COOLING, VALVE MONITORING TRIPPED
Valve actuator, air cooler, is defective.
111 COOLING ALARM INPUT 1 TRIPPED
Alarm input 1 cooling has tripped.
8:7 112 COOLING ALARM INPUT 2 TRIPPED
Alarm input 2 cooling has tripped.
Alarm group 9: Spare
Alarm group 10: AHU, internal temperature sensor
10:1 136 SUPPLY AIR TEMPERATURE SENSOR DEFECTIVE
Supply air sensor is defective or is not connected.
10:2
10:3
10:4
10:5
10:6
137 SUPPLY AIR TEMPERATURE SENSOR FOR DENSITY
COMPENSATION DEFECTIVE
Supply air sensor in the supply air fan intake cannot establish correct communication or shows an incorrect value.
138 EXTRACT AIR TEMPERATURE SENSOR DEFECTIVE
Extract air sensor is defective or is not connected.
139 EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY
COMPENSATION DEFECTIVE (GOLD RX/PX/CX)
Temperature sensor in extract air fan intake cannot establish correct communication or shows incorrect value.
GOLD RX
Exhaust air regulation has been selected, but the temperature sensor in the exhaust air is defective or is not connected.
140 EXTRACT AIR TEMPERATURE SENSOR FOR HEAT EX-
CHANGER DEFROSTING DEFECTIVE
Temperature sensor, for heat exchanger defrosting is defective.
141 EXTRACT AIR TEMPERATURE SENSOR FOR DENSITY
COMPENSATION IN SD AHU DEFECTIVE
Temperature sensor in extract air fan intake cannot establish correct communication or shows incorrect value.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 0 3) 10 s 1
A
B
A
A
A
B
A
A
A
B
A
B
A
A
1
0
0
0
1
0
1
0
1
1
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3 s
10 m
20 m
20 s
20 s
10 s
20 s
20 s
3 s
3 s
3 s
3 s
10 s
10 s
1
0
0
0
0
0
0
0
1
1
1
1
1
1
6 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
10:7 142 EXTRACT AIR DUCT TEMPERATURE SENSOR DEFEC-
TIVE
The temperature sensor in the extract air duct is defective or is not connected.
10:10 145 OUTDOOR AIR TEMPERATURE SENSOR DEFECTIVE
(GOLD SD)
Outdoor temperature sensor is defective or is not connected.
Alarm group 11: External temperature sensors
11:1
11:2
11:3
11:4
11:5
11:6
151 ROOM TEMPERATURE SENSOR NO. 1 DEFECTIVE
Room temperature sensor 1 is defective or is not connected.
152 ROOM TEMPERATURE SENSOR NO. 2 DEFECTIVE
Room temperature sensor 2 is defective or is not connected.
153 ROOM TEMPERATURE SENSOR NO. 3 DEFECTIVE
Room temperature sensor 3 is defective or is not connected.
154 ROOM TEMPERATURE SENSOR NO. 4 DEFECTIVE
Room temperature sensor 4 is defective or is not connected.
155 Xzone, ROOM TEMPERATURE SENSOR NO. 5 DEFEC-
TIVE
Xzone room temperature sensor 5 is defective or is not connected.
156 Xzone, ROOM TEMPERATURE SENSOR NO. 6 DEFEC-
TIVE
Xzone room temperature sensor 6 is defective or is not connected.
11:7 157 Xzone, ROOM TEMPERATURE SENSOR NO. 7 DEFEC-
TIVE
Xzone room temperature sensor 7 is defective or is not connected.
11:8 158 Xzone, ROOM TEMPERATURE SENSOR NO. 8 DEFEC-
TIVE
Xzone room temperature sensor 8 is defective or is not connected.
11:9 159 OUTDOOR TEMPERATURE SENSOR NO. A DEFECTIVE
Outdoor temperature sensor A is defective or is not connected.
11:10 160 OUTDOOR TEMPERATURE SENSOR NO. B DEFECTIVE
Outdoor temperature sensor B is defective or is not connected.
11:11 161 OUTDOOR TEMPERATURE SENSOR NO. C DEFECTIVE
Outdoor temperature sensor C is defective or is not connected.
11:12 162 OUTDOOR TEMPERATURE SENSOR NO. D DEFECTIVE
Outdoor temperature sensor D is defective or is not connected.
11:13 163 ROOM TEMPERATURE VIA COMMUNICATION, COM-
MUNICATION ERROR
The air handling unit’s control unit is not receiving any temperature reading via the external communication interface within the preset time limit.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 1 3) 10 s 1
B
B
B
B
B
B
B
B
B
B
B
B
B
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
5 m 2)
1
1
1
1
1
1
1
1
1
1
1
1
1
1
We reserve the right to alter specifications without notice.
www.swegon.com 7
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
11.14
164 Xzone, ROOM TEMPERATURE VIA COMMUNICATION,
COMMUNICATION ERROR
The air handling unit’s control unit is not receiving any temperature reading via the external communication interface within the preset time limit.
11:15 165 OUTDOOR TEMPERATURE VIA COMMUNICATION,
COMMUNICATION ERROR
The air handling unit’s control unit is not receiving any temperature reading via the external communication interface within the preset time limit.
Alarm group 12: AHU, temperature diff.
12:1
12:2
166 SUPPLY AIR TEMPERATURE BELOW SET POINT ALARM
LIMIT
The supply air temperature is lower than the preset set point (ERS, ORS, ORE and Supply air regulation) or has deviated from the supply air controller’s current set point (Extract air regulation) longer than 20 minutes.
167 SUPPLY AIR TEMPERATURE ABOVE SET POINT ALARM
LIMIT
The supply air temperature is above the preset set point (ERS, ORS, ORE and Supply air regulation) or has deviated from the supply air controller’s current set point (Extract air regulation) longer than 20 minutes.
12:6 171 EXTRACT AIR TEMPERATURE BELOW ALARM LIMIT
The extract air temperature is below preset alarm limit for more than 20 minutes.
12:11 176 TEMPERATURE PROTECTION BELOW ALARM LIMIT
The temperature protection reading is below preset alarm limit.
12:13 178 HEAT EXCHANGER EFFICIENCY BELOW ALARM LIMIT
The heat exchanger's efficiency is below the preset alarm limit for more than 2 minutes.
Alarm group 13: Humidity/VOC
13:1 181 HUMIDIFICATION, I/O MODULE NO. 4 COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 4 for humidity.
13:2
13:3
182 SUPPLY AIR HUMIDITY SENSOR DEFECTIVE
The humidity sensor in the supply air duct is defective or is not connected.
184 EXTRACT AIR HUMIDITY SENSOR DEFECTIVE
The humidity sensor in the extract air duct is defective or is not connected.
13:4
13:9
184 EXHAUST AIR HUMIDITY SENSOR DEFECTIVE
The humidity sensor in the exhaust air duct is defective or is not connected.
189 HUMIDIFIER, ALARM OUTPUT TRIPPED
The humidifier has tripped alarm output.
13:11 191 VOC SENSOR COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the VOC sensor.
13:12 192 VOC SENSOR, INTERNAL COMMUNICATION ERROR
The air handling unit's control unit cannot achieve correct communication with the VOC sensor.
13:13 193 VOC SENSOR, INTERNAL ERROR
VOC sensor defective.
8 www.swegon.com
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 5 m 2) 1
B
A
B
A
A
B
B
A
A
A
A
B
B
B
0
1
0
1
1
0
0
0
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
5 m 2)
20 m
20 m
20 m
30 s
2 hrs.
10 s
10 s
10 s
10 sec.
10 s
10 s
2)
60 s
60 s
1
0
0
0
0
0
1
1
1
1
0
1
1
1
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
13:14 194 VOC SENSOR, LEVEL BELOW/ABOVE SET POINT
ALARM LIMIT
The VOC sensor has read a level below or above the set point alarm limit for more than 60 seconds.
Alarm group 14: Spare
Alarm group 15: Plate heat exchanger
15:1 211 PLATE HEAT EXCHANGER, I/O-MODULE NO. 2 COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 2 for plate heat exchanger.
15:2
15:3
15:4
15:7
212 PLATE HEAT EXCHANGER, TEMPERATURE SENSOR NO.
1 DEFECTIVE
Temperature sensor 1 for frost guard in heat exchanger cube is defective or is not connected.
213 PLATE HEAT EXCHANGER, TEMPERATURE SENSOR NO.
2 DEFECTIVE
Temperature sensor 2 for frost guard in heat exchanger cube is defective or is not connected.
214 PLATE HEAT EXCHANGER, DAMPER MONITORING
TRIPPED
Damper actuator for plate heat exchanger is defective.
217 PLATE HEAT EXCHANGER, I/O-MODULE NO. 3 COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 3 for the plate heat exchanger.
15:8 218 PLATE HEAT EXCHANGER, BYPASS DAMPER MONI-
TORING TRIPPED
The bypass damper monitoring function of the plate heat exchanger has tripped.
15:9 219 PLATE HEAT EXCHANGER, DAMPER NO. 1 MONITOR-
ING TRIPPED
The section damper 1 monitoring function of the plate heat exchanger has tripped.
15:10 220 PLATE HEAT EXCHANGER, DAMPER NO. 2 MONITOR-
ING TRIPPED
The section damper 2 monitoring function of the plate heat exchanger has tripped.
15:11 221 PLATE HEAT EXCHANGER, I/O-MODULE NO. 3 COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 3 for the plate heat exchanger.
15:12 222 PLATE HEAT EXCHANGER, BYPASS DAMPER MONI-
TORING TRIPPED
The bypass damper monitoring function of the plate heat exchanger has tripped.
15:13 223 PLATE HEAT EXCHANGER, COUNTER-FLOW, DEFROST-
ING PRESSURE OVER ALARM LIMIT
There has been a continuous need for full defrosting for 2 hours.
15:14 224 PLATE HEAT EXCHANGER, DEFROSTING SENSOR NO. C
COMMUNICATION ERROR
The air handling unit’s control unit cannot establish correct communication with defrosting sensor C for the heat exchanger.
We reserve the right to alter specifications without notice.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 60 s 1
A
A
A
A
A
A
A
A
A
A
B
B
1
1
1
0
1
0
0
0
1
0
1
3)4)
3)4)
3)4)
3)4)
3)4)
3)4)
3)4)
3)4)
3)4)
3)4)
3)4)
0
10 s
3 s
3 s
10 m
10 s
10 m
10 m
10 m
10 s
10 m
2 h
10 m
1
1
1
0
1
0
0
0
1
0
0
1 www.swegon.com 9
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
15:15 225 PLATE HEAT EXCHANGER, DEFROSTING PRESSURE
OVER ALARM LIMIT
The need for defrosting has been over 95% continuously for 144 minutes.
Alarm group 16: Coil heat exchangers
16:1
16:2
226 COIL HEAT EXCHANGER, I/O-MODULE NO. 1 COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 1 for coil heat exchanger.
227 COIL HEAT EXCHANGER, TEMPERATURE SENSOR
DEFECTIVE
The temperature sensor on the coil heat exchanger’s pipework package for the frost guard is defective or is not connected.
16:3
16:4
16:5
228 COIL HEAT EXCHANGER, VALVE MONITORING TRIPPED
Valve actuator of the coil heat exchanger is defective.
229 COIL HEAT EXCHANGER, PUMP MONITORING TRIPPED
No in-service indication from the pump is obtained.
230 COIL HEAT EXCHANGER, I/O-MODULE NO. C COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. C for coil heat exchanger.
16:6
16:7
16:8 233 COIL HEAT EXCHANGER, PRESSURE BELOW ALARM
LIMIT
Fluid pressure sensor registers a too low pressure.
Alarm group 17: Rotary heat exchanger
17:1
17:2
241 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER
COMMUNICATION ERROR
The air handling unit’s control unit cannot establish correct communication with the heat exchanger motor controller.
242 ROTARY HEAT EXCHANGER, DEFROSTING PRESSURE
SENSOR NO. 7 COMMUNICATION ERROR
The air handling unit’s control unit cannot establish correct communication with the heat exchanger pressure sensor no. 7. Applicable to the defrosting function only.
17:3
17:4
231 COIL HEAT EXCHANGER, PRESSURE SENSOR DEFEC-
TIVE
Pressure sensor for the coil heat exchanger is defective or is not connected.
232 COIL HEAT EXCHANGER, LOW PRESSURE IN
HYDRONIC CIRCUIT
Pressure gauge registers a too low pressure.
243 ROTARY HEAT EXCHANGER, DEFROSTING PRESSURE
OVER ALARM LIMIT
The need for defrosting has been over 95% continuously for 144 minutes.
244 ROTARY HEAT EXCHANGER, ROTATION DETECTOR
TRIPPED
No impulses from the rotation detector are registered with the heat exchanger controller.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 1 2.4 h 0
A
A
A
A
A
A
A
A
A
B
B
A 1)
1
1
0
1
0
1
1
3)4)
3)4)
3)4)
1 3)4)
1
1
1
1
3)4)
3)
3)4)
3)4)
10 s
3 s
10 m
20 s
10 s
10 m
5 m
10 s
10 s
10 s
2,4 h
3 s
1
1
0
0
1
1
0
1
1
1
0
0
10 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
17:5
17:6
17:7
17:8
245 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER
OVERCURRENT
Heat exchanger motor controller has registered excessively high current supplier to the drive motor.
246 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER
UNDERVOLTAGE
Low feed voltage is supplied to the rotary heat exchanger’s motor controller.
247 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER
OVERVOLTAGE
High feed voltage is supplied to the rotary heat exchanger's motor controller.
248 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER
EXCESS TEMPERATURE
High temperature (90°C) inside the heat exchanger’s motor controller.
17:9
Alarm group 18: AYC
18:1 256 AYC, I/O MODULE No. 7 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 7 for AYC.
18:2
249 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER
START UP ERROR
Drive motor does not rotate during start up.
18:3
257 AYC HEATING, TEMPERATURE SENSOR DEFECTIVE
Heating temperature sensor is defective or is not connected.
258 AYC HEATING, VALVE MONITORING TRIPPED
The heated water valve actuator is defective.
18:4
18:5
18:6
259 AYC HEATING, PUMP MONITORING TRIPPED
The heated water pump is defective.
260 AYC HEATING, TEMPERATURE BELOW SET POINT LIMIT
Heating water temperature is below preset set point longer than 30 minutes.
261 AYC HEATING, TEMPERATURE ABOVE SET POINT
ALARM LIMIT 5)
Heating water temperature exceeds preset set point longer than 30 minutes.
18:9 264 AYC COOLING, TEMPERATURE SENSOR DEFECTIVE
Temperature sensor for the AYC function (All Year
Comfort) cooling is defective or is not connected.
18:10 265 AYC COOLING, VALVE MONITORING TRIPPED
The chilled water valve actuator is defective.
18:11 266 AYC COOLING, PUMP MONITORING TRIPPED
The chilled water pump is defective.
18:12 267 AYC COOLING, TEMPERATURE BELOW SET POINT
ALARM LIMIT
Heating water temperature is below preset set point longer than 30 minutes.
18:13 268 AYC COOLING, TEMPERATURE ABOVE SET POINT
ALARM LIMIT 5)
Cooling water temperature exceeds preset set point longer than 30 minutes.
Alarm group 19-20: Spare
Alarm group 21: COOL DX
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 1) 1 3)4) 3 s 0
A
A
A
A
A
A
B
A
A
B
A
B
A
A
B
1)
1)
1)
1)
1
1
1
1
0
0
0
3)4)
3)4)
3)4)
3)4)
3)
3)
0 3)
0 3)
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3 s
3 s
3 s
3 s
10 s
3 s
10 m
20 s
30 m
30 m
3 s
10 m
20 s
30 m
30 m
0
0
0
0
1
1
0
0
0
0
1
0
0
0
0
We reserve the right to alter specifications without notice.
www.swegon.com 11
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
21:1
21:2
21:3
21:4
21:5
21:6
21:7
21:8
21:9
301 COOL DX, I/O MODULE NO. 2 COMMUNICATION ER-
ROR
The AHU control unit cannot establish correct communication with I/O module No. 2 for the COOL DX.
302 COOL DX, COMPRESSOR NO. 1 LOW PRESSURE SEN-
SOR DEFECTIVE
Low pressure sensor is defective or is not connected.
303 COOL DX, COMPRESSOR NO. 1 LOW PRESSURE BE-
LOW ALARM LIMIT
The low pressure sensor measures lower pressure than preset alarm limit pressure.
304 COOL DX, COMPRESSOR NO. 1 HIGH PRESSURE SEN-
SOR DEFECTIVE
High pressure sensor is defective or is not connected.
305 COOL DX, COMPRESSOR NO. 1 HIGH PRESSURE
ABOVE ALARM LIMIT
The high pressure sensor measures higher pressure than preset alarm limit pressure.
306 COOL DX, COMPRESSOR NO. 1 MONITORING TRIPPED
Monitoring of compressor is defective.
307 COOL DX, COMPRESSOR NO. 1 RESTART ERROR
Compressor will not restart.
308 COOL DX, COMPRESSOR NO. 2 LOW PRESSURE SEN-
SOR DEFECTIVE
Low pressure sensor is defective or is not connected.
309 COOL DX, COMPRESSOR NO. 2 LOW PRESSURE BE-
LOW ALARM LIMIT
The low pressure sensor measures lower pressure than preset alarm limit pressure.
21:10 310 COOL DX, COMPRESSOR NO. 2 HIGH PRESSURE SEN-
SOR DEFECTIVE
High pressure sensor is defective or is not connected.
21:11 311 COOL DX, COMPRESSOR NO. 2 HIGH PRESSURE
ABOVE ALARM LIMIT
The high pressure sensor measures higher pressure than preset alarm limit pressure.
21:12 312 COOL DX, COMPRESSOR NO. 2 MONITORING TRIPPED
Monitoring of compressor is defective.
21:13 313 COOL DX, COMPRESSOR NO. 2 RESTART ERROR
Compressor will not restart.
21:14 314 COOL DX, OUTDOOR AIR TEMPERATURE SENSOR
DEFECTIVE
Outdoor air temperature sensor is defective or is not connected.
21:15 315 COOL DX, PHASE SEQUENCE MONITOR ERROR
Phase sequence protection for feed voltage to COOL
DX has tripped.
Alarm group 22: Spare
Alarm group 23: SMART Link
23:1
23:2
331 SMART Link, COMMUNICATION ERROR
The air handling unit’s control unit cannot establish correct communication with the chiller/heat pump.
332 SMART Link, ALARM LEVEL 1 TRIPPED
Chiller/heat pump has tripped, group alarm level 1.
23:3 333 SMART Link, ALARM LEVEL 2 TRIPPED
Chiller/heat pump has tripped, group alarm level 2.
12 www.swegon.com
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 10 s 1
A
A
A
A
A
A
A 1)
A
A
A
A
A
B
A
A
B
B
1)
1)
1)
1)
1)
1)
1)
0
0
0
0
0
3)
3)
3)
3)
3)
0 3)
0 3)
0
0
0
0
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
5 s
5 s
5 s
3 s
20 s
10 s
5 s
5 s
5 s
3 s
20 s
10 s
3 s
5 s
30 s
30 s
30 s
1
0
1
0
0
0
1
0
1
0
0
0
1
0
1
0
0
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
23:4
23:10 340 AQUA Link, I/O MODULE NO. 5 COMMUNICATION
ERROR
The air handling unit’s control unit cannot establish correct communication with I/O module no. 5, AQUA
Link
23:11 341 AQUA Link, PUMP MONITORING TRIPPED
Pump to AQUA Link is defective.
Alarm group 24: SMART Link DX
24:1
334 SMART Link, ALARM LEVEL 3 TRIPPED
Chiller/heat pump has tripped, group alarm level 3.
24:2
346 SMART Link, no. 1 communication error
The air handling unit's control unit cannot establish correct communication with the chiller/heat pump 1.
347 SMART Link, no. 1 alarm tripped
Chiller 1 defective.
24:4
24:5
24:7
349 SMART Link, no. 2 communication error
The air handling unit's control unit cannot establish correct communication with the chiller/heat pump 2.
350 SMART Link, no. 2 alarm tripped
Chiller 2 defective.
352 SMART Link, no. 3 communication error
The air handling unit's control unit cannot establish correct communication with the chiller/heat pump 3.
24:8 353 SMART Link, no. 3 alarm tripped
Chiller 3 defective.
24:10 355 SMART Link, no. 4 communication error
The air handling unit's control unit cannot establish correct communication with the chiller/heat pump 4.
24:11 356 SMART Link, no. 4 alarm tripped
Chiller 4 defective.
24:13 358 SMART Link, supply air alarm flow below alarm limit
The alarm supply air flow below alarm limit has tripped.
Alarm group 24-25: Spare
Alarm group 26: Pre-filter
26:1 376 PRE-FILTER, SUPPLY AIR PRESSURE SENSOR NO. 8
COMMUNICATION ERROR
The air handling unit’s control unit cannot establish correct communication with the sensor of the supply air pre-filter.
26:2 377 PRE-FILTER, SUPPLY AIR FOULED
The pressure across the supply air pre-filter exceeds the preset alarm limit for more than 10 minutes.
26:7 382 PRE-FILTER, EXTRACT AIR PRESSURE SENSOR NO. 9
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the sensor of the extract air pre-filter.
26:8 383 PRE-FILTER, EXTRACT AIR FOULED
The pressure across the extract air pre-filter exceeds the preset alarm limit for more than 10 minutes.
Alarm group 27: AHU, internal filters
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B
B
0
0
3)
3)
30 s
10 s
0
1
B
A
A
A
A
A
A
A
A
A
B
B
B
B
0
0
0
0
0
0
0
0
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
10 s
30 s
30 s
30 s
30 s
30 s
30 s
30 s
30 s
10 m
10 s
10 m
10 s
10 m
0
1
1
1
1
1
1
1
1
1
1
0
1
0
We reserve the right to alter specifications without notice.
www.swegon.com 13
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
27:1
27:2
391 AHU FILTER, SUPPLY AIR PRESSURE SENSOR NO. 3/4
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the sensor of the AHU supply air filter.
392 AHU FILTER, SUPPLY AIR FOULED
The pressure across the AHU supply air filter has exceeded the preset alarm limit for more than 10 minutes.
27:7 397 AHU FILTER, EXTRACT AIR PRESSURE SENSOR NO. 3/4
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the sensor of the AHU extract air filter.
27:8 398 AHU FILTER, EXTRACT AIR FOULED
The pressure across the AHU extract air filter has exceeded the preset alarm limit for more than 10 minutes.
Alarm group 28: Final filter
28:1 406 END FILTER, SUPPLY AIR PRESSURE SENSOR NO. A
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the sensor of the supply air end filter.
28:2 407 END FILTER, SUPPLY AIR, FOULED
The pressure across the supply air end filter has exceeded the preset alarm limit for more than 10 minutes.
Alarm group 29: Spare
Alarm group 30: Flow measurement
30:1
30:2
436 AIRFLOW MEASUREMENT, SUPPLY AIR PRESSURE SEN-
SOR NO. 1/2 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the flow pressure sensor in the supply air.
437 AIRFLOW MEASUREMENT, SUPPLY AIRFLOW BELOW
SET POINT ALARM LIMIT
The supply airflow has gone below its set point by more that 10%, during a longer period than 20 minutes.
30:3
30:6
30:7
30:8
438 AIRFLOW MEASUREMENT, SUPPLY AIRFLOW ABOVE
SET POINT ALARM LIMIT
The supply airflow has exceeded its set point by more that 10%, during a longer period than 20 minutes.
441 AIRFLOW MEASUREMENT, EXTRACT AIR PRESSURE
SENSOR NO. 1/2 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the flow pressure sensor in the extract air.
442 AIRFLOW MEASUREMENT,EXTRACT AIRFLOW BELOW
SET POINT ALARM LIMIT
The extract airflow has gone below its set point by more that 10%, during a longer period than 20 minutes.
443 AIRFLOW MEASUREMENT, EXTRACT AIRFLOW ABOVE
SET POINT ALARM LIMIT
The extract airflow has exceeded its set point by more that 10%, during a longer period than 20 minutes.
14 www.swegon.com
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 10 s 1
B
B
B
B
B
A
B
B
A
B
B
0
0
0
0
0
1
0
0
1
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
10 m
10 s
10 m
10 s
10 m
10 s
20 m
20 m
10 s
20 m
20 m
0
1
0
1
0
1
0
0
1
0
0
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
30:11 446 AIRFLOW MEASUREMENT, PURGING PRESSURE SEN-
SOR NO. B COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the sensor of the rotary heat exchanger purging sector.
Alarm group 31: Pressure regulation
31:1 451 PRESSURE REGULATION, SUPPLY AIR PRESSURE SEN-
SOR NO. 5 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the duct pressure sensor in the supply air. Applies only to pressure regulation of the supply air.
31:2
31:3
31:6
31:7
452 PRESSURE REGULATION, SUPPLY AIR PRESSURE BELOW
SET POINT ALARM LIMIT
The duct pressure has gone below its set point by more that 10%, during a longer period than 20 minutes ( if pressure sensors are connected).
453 PRESSURE REGULATION, SUPPLY AIR PRESSURE ABOVE
SET POINT ALARM LIMIT
The supply air duct pressure has exceeded its set point by more that 10%, during a longer period than 20 minutes (if pressure sensors are connected).
456 PRESSURE REGULATION, EXTRACT AIR PRESSURE SEN-
SOR NO. 6 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the duct pressure sensor in the extract air. Applies only to pressure regulation of the extract air.
457 PRESSURE REGULATION, EXTRACT AIR PRESSURE
BELOW SET POINT ALARM LIMIT
The extract air duct pressure has gone below its set point by more that 10%, during a longer period than
20 minutes (if pressure sensors are connected).
31:8
Alarm group 32: ReCO
2
32:1
/Intermittent night heating
466 ReCO
2
, I/O MODULE NO. 0 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module no. 0.
32:2
458 PRESSURE REGULATION, EXTRACT AIR PRESSURE
ABOVE SET POINT ALARM LIMIT
The extract air duct pressure has exceeded its set point by more that 10%, during a longer period than 20 minutes (if pressure sensors are connected).
467 ReCO
2
ERROR
, PRESSURE SENSOR NO. 0 COMMUNICATION
The air handling unit's control unit cannot establish correct communication with the pressure sensor.
32:3 468 ReCO
2
/INTERMITTENT NIGHT HEATING, RECIRCULATED
AIR DAMPER MONITORING TRIPPED
The damper actuator does not move to the right position. The position-confirming output signal from the damper is not the same as the input control signal.
32:4 469 ReCO
2
, OUTDOOR AIR DAMPER MONITORING TRIPPED
The damper actuator does not move to the right position. The position-confirming output signal from the damper is not the same as the input control signal.
Alarm group 33: Service
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 10 s 1
A
B
B
A
B
B
A
A
B
B
1
0
0
1
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
10 s
20 m
20 m
10 s
20 m
20 m
10 s
10 s
10 m
10 m
1
0
0
1
0
0
1
1
0
0
We reserve the right to alter specifications without notice.
www.swegon.com 15
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
33:1
33:15 495 LOCK FUNCTION TRIPPED
Contact Swegon or their representative.
Alarm group 34: External controls
34:1
481 PERIOD BETWEEN SERVICING PAST ALARM LIMIT
The preset service period has expired.
If the alarm is RESET via the hand-held terminal, the alarm will be initiated again after 7 days.
A new service period can be set and reset under
ALARM SETTINGS.
34:2
496 EXTERNAL CONTROL, I/O MODULE NO. 3 COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 3 for external control.
497 EXTERNAL CONTROL, I/O MODULE NO. 6 COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 6 for external control.
Alarm group 35: Booster diffusers
35:1 511 BOOSTER AIR TERMINALS, I/O MODULE NO. 8 COM-
MUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. 8 for
Booster diffusers.
Alarm group 36: External communication, I/O-modules
36:1 526 EXTERNAL COMMUNICATION, I/O MODULE NO. A
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. A.
36:2
36:3
36:6
527 EXTERNAL COMMUNICATION, I/O MODULE NO. A
TEMPERATURE SENSOR NO. 1 DEFECTIVE
I/O-module A, temperature sensor 1, is defective or is not connected.
528 EXTERNAL COMMUNICATION, I/O MODULE NO. A
TEMPERATURE SENSOR NO. 2 DEFECTIVE
I/O-module A, temperature sensor 2, is defective or is not connected.
531 EXTERNAL COMMUNICATION, I/O MODULE NO. B
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. B.
36:7
36:8
532 EXTERNAL COMMUNICATION, I/O MODULE NO. B
TEMPERATURE SENSOR NO. 1 DEFECTIVE
I/O-module B, temperature sensor 1, is defective or is not connected.
533 EXTERNAL COMMUNICATION, I/O MODULE NO. B
TEMPERATURE SENSOR NO. 2 DEFECTIVE
I/O-module B, temperature sensor 2, is defective or is not connected.
36:11 536 EXTERNAL COMMUNICATION, I/O MODULE NO. C
COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with I/O module No. C.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 5 s 2) 0
–
B
B
B
B
B
B
B
B
B
B
0
0
0
0
0
0
0
0
0
0
–
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
–
10 s
10 s
10 s
10 s
3 s
3 s
10 s
3 s
3 s
10 s
0
1
1
1
1
1
1
1
1
1
1
6)
16 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
36:12 537 EXTERNAL COMMUNICATION, I/O MODULE NO. C
TEMPERATURE SENSOR NO. 1 DEFECTIVE
I/O-module C, temperature sensor 1, is defective or is not connected.
36:13 538 EXTERNAL COMMUNICATION, I/O MODULE NO. C
TEMPERATURE SENSOR NO. 2 DEFECTIVE
I/O-module C, temperature sensor 2, is defective or is not connected.
Alarm group 37: Spare
Alarm group 38-47: MIRU 1-10 7)
38-
47:1
38-
47:2
556, 571,
586, 601,
616, 631,
646, 661,
676, 691
MIRU NO. 1-10 COMMUNICATION ERROR
The air handling unit’s control unit cannot establish correct communications with MIRU.
557, 572,
587, 602,
617, 632,
647, 662,
677, 692
MIRU NO. 1-10 MOTOR CONTROL ALARM TRIPPED
The MIRU motor control has tripped.
38-
47:3
38-
47:4
38-
47:5
558, 573,
588, 603,
618, 633,
648, 663,
678, 693
MIRU NO. 1-10 MOTOR CONTROL COMMUNICATION
ERROR
MIRU cannot establish correct communications with the power roof ventilator’s motor controller.
559, 574,
589, 604,
619, 634,
649, 664,
679, 694
MIRU NO. 1-10 FLOW MEASUREMENT PRESSURE
SENSOR NO. 0 COMMUNICATION ERROR
MIRU cannot establish correct communications with the power roof ventilator's flow measurement pressure sensor.
560, 575,
590, 605,
620, 635,
650, 665,
680, 695
MIRU NO. 1-10 PRESSURE REGULATION SENSOR NO. 1
COMMUNICATION ERROR
MIRU cannot establish correct communications with the power roof ventilator's duct pressure sensor.
38-
47:6
38-
47:7
38-
40:8
38-
40:9
561, 576,
591, 606,
621, 636,
651, 666,
681, 696
MIRU NO. 1-10 TEMPERATURE SENSOR DEFECTIVE
MIRU temperature sensor is defective or is not connected.
562, 577,
592, 607,
622, 637,
652, 667,
682, 697
MIRU NO. 1-10 FLOW/PRESSURE DEVIATION FROM
THE SET POINT ALARM LIMIT
The air flow/pressure has continuously exceeded or been below its set point by more than 20%.
563, 578,
593
MIRU NO. 1-3 FLOW BELOW SET POINT ALARM LIMIT
The flow has dropped below its set point for a period longer than 30 seconds.
564, 579,
594
MIRU NO. 1-3 FLOW ABOVE SET POINT ALARM LIMIT
The flow has exceeded its set point by more that 10%, during a longer period than 20 minutes.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 3) 3 s 1
B
A
A
A
A
A
B
B
B
B
0
0
0
0
0
0
0
0
0
0
3)
3)
3)
3)
3)
3)
3)
3)
3 s
10 s
5 s
5 s
5 s
5 s
5 s
5 s
1200 s
1200 s
1
1
1
1
1
1
1
1
0
0
We reserve the right to alter specifications without notice.
www.swegon.com 17
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
38-
40:10
565, 580,
595
MIRU NO. 1-3 PRESSURE BELOW SET POINT ALARM
LIMIT
The pressure has dropped below its set point for a period longer than 30 seconds.
38-
40:11
566, 581,
596
MIRU NO. 1-3 PRESSURE ABOVE SET POINT ALARM
LIMIT
The pressure has exceeded its set point by more that
10%, during a longer period than 20 minutes.
Alarm group 49-54: Supply air fan no. 1A-3B 8)
49-
54:1
49-
54:2
49-
54:3
49-
54:4
49-
54:5
49-
54:6
721, 736,
751, 766,
781, 796
SUPPLY AIR FAN 1-3/A-B COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the supply air fan motor controller.
722, 737,
752, 767,
782, 797
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER OVER-
CURRENT
High current supplied to motor
723, 738,
753, 768,
783, 798
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER UN-
DERVOLTAGE
Voltage below the normal level is supplied.
724, 739,
754, 769,
784, 799
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER OVER-
VOLTAGE
Excessively high voltage is supplied.
725, 740,
755, 770,
785, 800
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER EX-
CESS TEMPERATURE
High internal temperature.
726, 741,
756, 771,
786, 801
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROL START UP
ERROR
Supply air fan does not rotate on a start up, rotates in wrong direction or rotates at excessively high speed.
49-
54:7
49-
54:8
49-
54:9
49-
54:10
727, 742,
757, 772,
787, 802
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER UN-
EVEN PHASE VOLTAGE
High voltage difference between the phases (3-phase,
400 V), which causes rippling.
728, 743,
758, 773,
788, 803
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER PHASE
FAILURE
Phase failure in motor controller.
729, 744,
759, 774,
789, 804
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER
MEMORY ERROR
Internal memory error in motor controller.
730, 745,
760, 775,
790, 805
SUPPLY AIR FAN 1-3/A-B MOTOR CONTROLLER CUR-
RENT LIMITATION
Current/Voltage limitation in motor controller.
49-
51:11
731, 746,
761
SUPPLY AIR FAN 1A-3A MOTOR CONTROLLER INTER-
NAL COMMUNICATION ERROR
Internal communication error in motor controller.
Alarm group 55-60: Extract air fan no. 1A-3B 9)
55-
60:1
811, 826,
841, 856,
871, 886
EXTRACT AIR FAN 1-3/A-B COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the extract air fan motor controller.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
B 0 1200 s 0
B
A
A
A
A
A
A
A
A
A
B
A
A
1)
1)
1)
1)
1)
1)
1)
1)
1
1
1
1
1
1
1
1
1
0
1
1
0
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
1200 s
10 s
10 s
60 s
10 s
10 s
10 s
10 s
10 s
10 s
60 s
10 s
10 s
0
1
0
0
0
0
0
1
1
1
1
1
1
18 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
55-
60:2
55-
60:3
55-
60:4
55-
60:5
812, 827,
842, 857,
872, 887
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
OVERCURRENT
High current supplied to motor
813, 828,
843, 858,
873, 888
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
UNDERVOLTAGE
Voltage below the normal level is supplied.
814, 829,
844, 859,
874, 889
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
OVERCURRENT
Excessively high voltage is supplied.
815, 830,
845, 860,
875, 890
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
EXCESS TEMPERATURE
High internal temperature.
55-
60:6
55-
60:7
816, 831,
846, 861,
876, 891
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
START UP ERROR
Extract air fan does not rotate on a start up, rotates in wrong direction or rotates at excessively high speed.
817, 832,
847, 862,
877, 892
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER UN-
EVEN PHASE VOLTAGE
High voltage difference between the phases (3-phase,
400 V), which causes rippling.
55-
60:8
55-
60:9
818, 833,
848, 863,
878, 893
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
PHASE FAILURE
Phase failure in motor controller.
819, 834,
849, 864,
879, 894
ETRACT AIR FAN 1-3/A-B MOTOR CONTROLLER
MEMORY ERROR
Internal memory error in motor controller.
55-
60:10
55-
57:11
820, 835,
850, 865,
880, 895
821, 836,
851
EXTRACT AIR FAN 1-3/A-B MOTOR CONTROLLER CUR-
RENT LIMITATION
Current/Voltage limitation in motor controller.
EXTRACT AIR FAN 1A-3A MOTOR CONTROLLER INTER-
NAL COMMUNICATION ERROR
Internal communication error in motor controller.
Alarm group 61: Supply air fan, I/O module
61:1
61:6
901 SUPPLY AIR FAN NO. 1A I/O MODULE COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with supply air fan no. 1A I/O module.
906 SUPPLY AIR FAN NO. 2A I/O MODULE COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with supply air fan no. 2A I/O module.
61:11 911 SUPPLY AIR FAN NO. 3A I/O MODULE COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with supply air fan no. 3A I/O module.
Alarm group 62: Extract air fan, I/O module
62:1 916 EXTRACT AIR FAN NO. 1A I/O MODULE COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with extract air fan no. 1A I/O module.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 1) 1 3) 3 s 0
A
A
A
A
A
A
A
B
A
A
A
A
A
1)
1)
1)
1)
1)
1)
1)
1
1
1
1
1
1
1
0
1
1
1
1
1
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
3)
60 s
3 s
3 s
3 s
5 s
5 s
5 s
60 s
5 s
10 s
10 s
10 s
10 s
0
0
0
0
1
1
1
1
1
1
1
1
1
We reserve the right to alter specifications without notice.
www.swegon.com 19
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
62:6 921 EXTRACT AIR FAN NO. 2A I/O MODULE COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with extract air fan no. 2A I/O module.
62:11 926 EXTRACT AIR FAN NO. 3A I/O MODULE COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with extract air fan no. 3A I/O module.
Alarm group 63: MIRU, I/O module
63:1 931 MIRU NO. 1 I/O MODULE COMMUNICATIONS ERROR
The air handling unit’s control unit cannot establish correct communications with MIRU no. 1 I/O module.
63:6 936 MIRU NO. 2 I/O MODULE COMMUNICATIONS ERROR
The air handling unit’s control unit cannot establish correct communications with MIRU no. 2 I/O module.
63:11 941 MIRU NO. 3 I/O MODULE COMMUNICATIONS ERROR
The air handling unit’s control unit cannot establish correct communications with MIRU no. 3 I/O module.
Alarm groups 70 – 74: Reversible heat pump/chiller HC
70:1 1036 HC CONTROL UNIT COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct communication with the HC control unit.
70:2 1037 HC CONTROL UNIT GROUP ALARM TRIPPED
The HC control unit has tripped a common fault alarm
70:3 1038 HC CONTROL UNIT DEFECTIVE TIMER CIRCUIT
HC control unit is defective or is not connected.
70:5 1040 HC DEFROSTING, PRESSURE SENSOR NO. D COMMU-
NICATION ERROR
The air handling unit's control unit cannot establish correct communication with the pressure sensor no. D for HC defrosting.
70:6 1041 HC DEFROSTING, I/O MODULE NO. 5 COMMUNIC-
TIONS ERROR
The air handling unit’s control unit cannot establish correct communication with I/O module no. 5 for HC defrosting.
70:7 1042 HC DEFROSTING, RECIRCULATION DAMPER MONITOR-
ING TRIPPED
Recirculation damper alarm HC defrosting has tripped.
70:8 1043 HC DEFROSTING, EL. HEATING COIL TRIPPED
Electric air heating coil alarm HC defrosting has tripped.
70:9 1044 HC DEFROSTING TIME CIRCUIT 1 ABOVE ALARM LIMIT
HC defrosting time for circuit 1 has been exceeded.
70:12 1046 HC PHASE SEQUENCE ERROR
Phase sequence protection for feed voltage to HC has tripped.
71:1 1051 HC COMPRESSOR MOTOR CONTROL COMMUNICA-
TION ERROR
The air handling unit's control unit cannot establish correct communication with the HC compressor motor control.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 1 3) 10 s 1
A
A
A
A
A
A
A
A
A
B
A
B
A
A
1
1
1
1
0
0
0
0
0
0
0
0
0
0
3)
3)
3)
3)
3)
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
180 s
10 s
10 s
5 s
10 s
1
1
1
1
1
1
1
1
1
1
0
1
0
1
20 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
71:2 1052 HC COMPRESSOR MOTOR CONTROL START-UP FAIL-
URE
The compressor motor does not rotate during start up.
71:3 1053 HC COMPRESSOR MOTOR CONTROL OVER OR UNDER
VOLTAGE
Low or high power supply to compressor motor control.
71:4 1054 HC COMPRESSOR OUTSIDE WORKING RANGE
HC compressor works outside its ordinary working range.
71:9 1059 HC EXPANSION VALVE CONTROL CIRCUIT 1 COMMU-
NICATION ERROR
The air handling unit's control unit cannot establish correct communication with the HC expansion valve control circuit 1.
72:1 1066 HC HIGH PRESSURE MONITOR CIRCUIT 1 TRIPPED
The high pressure monitor alarm HC circuit 1, has tripped.
72:2 1067 HC HIGH PRESSURE CIRCUIT 1 ABOVE ALARM LIMIT
The high pressure alarm HC circuit 1, has tripped.
72:3 1068 HC THERMOSTATIC CONTACT CIRCUIT 1 TRIPPED
The thermostatic contacts alarm HC circuit 1, has tripped.
72:4 1069 HC HOT GAS TEMPERATURE CIRCUIT 1 ABOVE
ALARM LIMIT
The hot gas temperature alarm HC circuit 1, has tripped.
72:5 1070 HC HOT GAS TEMPERATURE CIRCUIT 1 DEFECTIVE
Hot gas temperature sensor is defective or is not connected.
72:6 1071 HC HIGH PRESSURE SENSOR CIRCUIT 1 DEFECTIVE
High pressure sensor HC circuit 1, is defective or is not connected.
72:7 1072 HC LOW PRESSURE SENSOR CIRCUIT 1 DEFECTIVE
Low pressure sensor HC circuit 1, is defective or is not connected.
72:8 1073 HC SUCTION GAS TEMPERATURE CIRCUIT 1 DEFEC-
TIVE
Suction gas line temperature sensor HC circuit 1, is defective or is not connected.
72:9 1074 HC PRESSURE DIFFERENCE CIRCUIT 1 BELOW ALARM
LIMIT
The pressure difference HC circuit 1, has tripped.
72:10 1075 HC SERVICE OF CIRCUIT 1 AND COMPRESSOR
Service of circuit 1 and compressor required.
72:11 1076 HC OVERHEATING TEMPERATURE CIRCUIT 1 BELOW
ALARM LIMIT
HC overheating temperature circuit 1 falls below the set alarm limit.
72:12 1077 HC PRESSURE EQUALISATION OF LOW PRESSURE
CIRCUIT 1
HC pressure equalisation low pressure circuit 1, has tripped.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 0 10 s 1
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
We reserve the right to alter specifications without notice.
www.swegon.com 21
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
72:13 1078 HC PRESSURE EQUALISATION OF HIGH PRESSURE
CIRCUIT 1
HC pressure equalisation high pressure circuit 1, has tripped.
72:14 1079 HC LOW PRESSURE CIRCUIT 1 BELOW ALARM LIMIT
HC low pressure circuit 1 falls below the set alarm limit.
Alarm group 77 – 79: MIRU, motor controllers
77-
79:2
77-
79:3
1142,
1157,
1172
1143,
1158,
1173
MIRU NO. 1-3 MOTOR CONTROLLER OVERCURRENT
Motor controller for roof ventilator MIRUVENT has registered excessively high current to the drive motor.
MIRU NO. 1-3 MOTOR CONTROLLER UNDERVOLTAGE
Low supply voltage to the roof ventilator MIRUVENT’s motor controller.
77-
79:4
77-
79:5
1144,
1159,
1174
1145,
1160,
1175
MIRU NO. 1-3 MOTOR CONTROLLER OVER VOLTAGE
High supply voltage to the roof ventilator MIRUVENT’s motor controller.
MIRU NO. 1-3 MOTOR CONTROLLER OVER TEMPERA-
TURE
High internal temperature.
77-
79:6
77-
79:7
1147,
1162,
1177
MIRU NO. 1-3 MOTOR CONTROLLER UNEVEN PHASE
VOLTAGE
High voltage difference between the phases (3-phase,
400 V), which causes rippling.
77-
79:8
77-
79:9
77-
79:10
77-
79:11
1148,
1163,
1178
1149,
1164,
1179
1150,
1165,
1180
1151,
1166,
1181
MIRU NO. 1-3 MOTOR CONTROLLER PHASE ERROR
Phase failure in motor controller.
MIRU NO. 1-3 MOTOR CONTROLLER INTERNAL
MEMORY ERROR
Internal memory error in motor controller.
MIRU NO. 1-3 MOTOR CONTROLLER CURRENT LIMITA-
TION
Current/Voltage limitation in motor controller.
MIRU NO. 1-3 MOTOR CONTROLLER INTERNAL COM-
MUNICATIONS ERROR
Internal communication error in motor controller.
Alarm group 81 – 84: SMART Link, supply air flow
81-
84:2
81-
84:3
1146,
1161,
1176
1202,
1217,
1232,
1247
1203,
1218,
1233,
1248
MIRU NO. 1-3 MOTOR CONTROLLER START-UP FAIL-
URE
Drive motor does not rotate during start up.
SMART LINK NO. 1-4 SUPPLY AIR FLOW BELOW
DEFROSTING ALARM LIMIT
The alarm for supply air flow below defrosting alarm limit has tripped.
SMART LINK NO. 1-4 HIGH PRESSURE MONITOR
TRIPPED
The high pressure monitor alarm has tripped.
81-
84:4
81-
84:5
1204,
1219,
1234,
1249
1205,
1220,
1235,
1250
SMART LINK NO. 1-4 HIGH PRESSURE ABOVE ALARM
LIMIT
The high pressure sensor measures higher pressure than preset alarm limit pressure.
SMART LINK NO. 1-4 LOW PRESSURE BELOW ALARM
LIMIT
The low pressure sensor measures lower pressure than preset alarm limit pressure.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 0 10 s 1
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10 s
10 s
60 sec.
10 s
10 s
10 s
10 s
10 s
10 s
60 sec.
10 s
70 m
30 s
30 s
30 s
1
0
0
0
0
0
1
1
1
1
1
1
1
1
1
22 www.swegon.com
We reserve the right to alter specifications without notice.
GB.GOLDSKFLARM.181221
Alarm No.
Alarm text
Function
81-
84:6
81-
84:7
81-
84:8
81-
84:9
81-
84:10
81-
84:11
1208,
1223,
1238,
1253
1209,
1224,
1239,
1254
1206,
1221,
1236,
1251
1207,
1222,
1237,
1252
1210,
1225,
1240,
1255
1211,
1226,
1241,
1256
SMART LINK NO. 1-4 EVAPORATION TEMPERATURE
BELOW ALARM LIMIT
The evaporation temperature drops below the preset alarm limit for more than 30 seconds.
SMART LINK NO. 1-4 GROUP ALARM FREQUENCY
CONVERTER
The frequency converter has tripped a group alarm
SMART LINK NO. 1-4 OUTSIDE WORKING RANGE
SMART Link works outside its ordinary working range.
SMART LINK NO. 1-4 COMPRESSOR, START-UP FAIL-
URE
The compressor motor does not rotate during start up.
SMART LINK NO. 1-4 HOT GAS TEMPERATURE ABOVE
ALARM LIMIT
Hot gas temperature has exceeded the alarm limit.
SMART LINK NO. 1-4 PRESSURE DIFFERENCE BELOW
ALARM LIMIT
The pressure difference drops below the preset alarm limit for more than 30 seconds.
Priority Stop Delay Resetting
0 = Blocked 0 = In oper. s = second 0 = manual
A = A alarm 1 = Stop m = minute 1 = automatic
B = B alarm h=hour
A 0 30 s 1
A
A
A
A
A
0
0
0
0
0
30 s
30 s
30 s
30 s
30 s
1
1
1
1
1
1) Cannot be blocked.
2) The delay is adjustable.
3) Adjustable.
4) Stops the AHU if the temperature is below the adjustable limit.
5) Inactive as factory setting.
6) Contact Swegon or their representative.
7) Alarm group 38 = MIRU Control 1. Alarm group 39 = MIRU Control 2. Alarm group 40 = MIRU Control 3. Alarm group 41 = MIRU
Control 4. Alarm group 42 = MIRU Control 5. Alarm group 43 = MIRU Control 6. Alarm group 44 = MIRU Control 7. Alarm group 45
= MIRU Control 8. Alarm group 46 = MIRU Control 9. Alarm group 47 = MIRU Control 10.
8) Alarm group 49 = Supply air fan 1A. Alarm group 50 = Supply air fan 2A. Alarm group 51 = Supply air fan 3A. Alarm group 52 =
Supply air fan 1B. Alarm group 53 = Supply air fan 2B. Alarm group 54 = Supply air fan 3B.
9) Alarm group 55 = Extrat air fan 1A. Alarm group 56 = Extrat air fan 2A. Alarm group 57 = Extrat air fan 3A. Alarm group 58 =
Extrat air fan 1B. Alarm group 59 = Extrat air fan 2B. Alarm group 60 = Extrat air fan 3B.
We reserve the right to alter specifications without notice.
www.swegon.com 23
GB.GOLDSKFLARM.181221
98:2
98:3
98:4
98:5
98:6
98:7
98:8
98:9
Message No.
96:1
96:2
96:3
96:4
96:5
97:12
97:13
97:14
97:15
98:1
98:10
98:11
2. Information Messages
Information messages are displayed in the hand-held terminal.
Information messages are displayed only when the terminal is in the Dashboard image.
Information messages provide information e.g. about necessary settings that have not been entered or unfavourable operating conditions.The information message is indicated by a blue circle in the alarm log button on the instrument panel.
Message text
HC DEFROSTING CALIBRATION NOT PERFORMED
HC defrosting calibration cannot be performed.
HC DEFROSTING CALIBRATION NOT APPROVED
HC defrosting calibration is performed, but read values are not approved.
HC LIMIT FOR SUPPLY AIR FLOW IS BELOW THE FACTORY SETTING
The set limit for the supply air flow is below the factory setting that permits HC operation.
HC LIMIT FOR EXTRACT AIR FLOW IS BELOW THE FACTORY SETTING
The set limit for the extract air flow is below the factory setting that permits HC operation.
HC OUTDOOR TEMPERATURE LIMIT FOR HEATING BELOW THE FACTORY SETTING
The set limit for the outdoor air temperature is below the factory setting that permits HC operation.
PLATE HEAT EXCHANGER, BYPASS OPTIMIZATION NOT PERFORMED
Bypass optimization of plate heat exchanger cannot be performed.
PLATE HEAT EXCHANGER, BYPASS OPTIMIZATION FAILURE
Bypass optimization of the plate heat exchanger has been performed, but the readings are not satisfactory.
PLATE HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED
Defrosting calibration of the plate heat exchanger cannot be performed.
PLATE HEAT EXCHANGER DEFROSTING CALIBRATION FAILURE
Defrosting calibration of the plate heat exchanger has been performed, but the readings are not satisfactory.
SUPPLY AIR PRE-FILTER CALIBRATION NOT PERFORMED
Pre-filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals. The message is not received after completed filter calibration.
SUPPLY AIR PRE-FILTER CALIBRATION FAILURE
Pre-filter calibration failure, supply air. Recurrent at 5 second intervals.
EXTRACT AIR PRE-FILTER CALIBRATION NOT PERFORMED
Pre-filter calibration, extract air, not performed after first start. Recurrent at 30 minute intervals. The message is not received after completed filter calibration.
EXTRACT AIR PRE-FILTER CALIBRATION FAILURE
Pre-filter calibration failure, extract air. Recurrent at 5 second intervals.
SUPPLY AIR AHU FILTER CALIBRATION NOT PERFORMED supply air AHU filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals.
The message is not received after completed filter calibration.
SUPPLY AIR AHU FILTER CALIBRATION FAILURE
AHU filter calibration failure, supply air. Recurrent at 5 second intervals.
EXTRACT AIR AHU FILTER CALIBRATION NOT PERFORMED
AHU filter calibration, extract air, not performed after first start. Recurrent at 30 minute intervals. The message is not received after completed filter calibration.
EXTRACT AIR AHU FILTER CALIBRATION FAILURE
AHU filter calibration failure, extract air. Recurrent at 5 second intervals.
SUPPLY AIR END FILTER CALIBRATION NOT PERFORMED
End filter calibration, supply air, not performed after first start. Recurrent at 30 minute intervals. The message is not received after completed filter calibration.
SUPPLY AIR END FILTER CALIBRATION FAILURE
End filter calibration failure, supply air. Recurrent at 5 second intervals.
ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION NOT PERFORMED
Defrost calibration, rotary heat exchanger, not performed after function was activated for first time. Recurrent at 30 minute intervals. The message is not received after completed heat exchanger calibration.
24 www.swegon.com
We reserve the right to alter specifications without notice.
98:12
98:13
98:14
98:15
99:1
99:5
99:7
99:8
99:11
99:14
99:15
GB.GOLDSKFLARM.181221
Alarm text
Function
ROTARY HEAT EXCHANGER DEFROSTING CALIBRATION FAILURE
Defrost calibration failure, rotary heat exchanger. Recurrent at 5 second intervals.
ReCO
2
CALIBRATION NOT PERFORMED
ReCO
2
calibration not performed after function was activated for first time. Recurrent at 30 minute intervals.
Message is not received after completed ReCO
2
calibration.
ReCO
2
ReCO
2
CALIBRATION FAILURE
calibration failure. Recurrent at 5 second intervals.
ReCO
2
WRONG SETTING
Pressure regulation, slave control or wrong type of AHU is selected. Recurrent at 5 second intervals.
E-MAIL ERROR
Error when sending e-mail. The message is received after ten tries.
FTP ERROR
Error when sending to ftp. The message is received after ten tries.
SD SHORT MEMORY SOON FULL
The SD card's memory is soon full. The oldest log data will sonn be deleted. Factory default Off.
SD SHORT MEMORY FULL
The SD card's memory is full. The oldest log data is being deleted. Factory default Off.
NO EXTERNAL OUTDOOR TEMPERATURE SENSOR CONNECTED FOR HEAT-RETAINING FUNCTION
Temperature sensor for heat-retaining function is not fitted or is not connected correctly.
INTERNAL SERIAL MEMORY ERROR CPEx1
Internal serial memory error CPEx1
CLOCK CIRCUIT DEFECTIVE
Circuit for the clock is defective
We reserve the right to alter specifications without notice.
www.swegon.com 25
GB.GOLDSKFLARM.181221
26 www.swegon.com
We reserve the right to alter specifications without notice.
Download
Advertisement
Key features
Detailed alarm descriptions with factory settings.
Comprehensive information messages.
Alarm priority levels for quick assessment.
Stop, delay, and resetting procedures for alarms.
Defined functions for each alarm message.
Frequently asked questions
This indicates that the fire protection function connected to terminals 6-7 has been activated.
Check if the overheating protection has tripped or if there is no supply voltage to the electrical heater.
The supply air temperature is below the preset set point (ERS and Supply air regulation) or Min SA temp (Extract air regulation) longer than 20 minutes.
The pressure across the AHU supply air filter has exceeded the preset alarm limit for more than 10 minutes.
Check if no impulses from the rotation detector are registered with the heat exchanger controller.